ML12135A042
| ML12135A042 | |
| Person / Time | |
|---|---|
| Site: | North Anna |
| Issue date: | 04/26/2012 |
| From: | Gerald Bichof Virginia Electric & Power Co (VEPCO) |
| To: | Document Control Desk, Office of Nuclear Material Safety and Safeguards, Office of Nuclear Reactor Regulation |
| References | |
| 12-257 | |
| Download: ML12135A042 (140) | |
Text
VIRGINIA ELECTRIC AND POWER COMPANY RICHMOND Y26
/-April
, ýR y 23261 United States Nuclear Regulatory Commission Serial No.12-257 Attention: Document Control Desk NAPS/JHL Washington, D. C. 20555 Docket Nos.
50-338/339 72-16 72-56 License Nos. NPF-4/7 SNM-2507 VIRGINIA ELECTRIC AND POWER COMPANY (DOMINION)
NORTH ANNA POWER STATION UNIT NOS. 1 AND 2 INDEPENDENT SPENT FUEL STORAGE INSTALLATION (ISFSI)
ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT Enclosed is the 2011 Annual Radioactive Effluent Release Report.
This report is provided pursuant to North Anna Units 1 and 2 Technical Specification 5.6.3 [10 CFR 50.36a] and North Anna Independent Spent Fuel Storage Installation Technical Specification 5.5.2c [10 CFR 72.44(d)(3)].
If you have any questions or require additional information, please contact Donald Taylor at (540) 894-2616.
Very truly yours, G. T. Bischof Site Vice President Enclosure Commitments made in this letter: None cc:
U. S. Nuclear Regulatory Commission Region II Marquis One Tower 245 Peachtree Center Ave., NE Suite 1200 Atlanta, Georgia 30303-1257 Director, Nuclear Material Safety and Safeguards U. S. Nuclear Regulatory Commission Washington, D. C. 20555 NRC Senior Resident Inspector North Anna Power Station
-r q8
ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT NORTH ANNA POWER STATION (JANUARY 01, 2011 TO DECEMBER 31, 2011)
PREPARED REVIEWED APPROVED BY:a o
i, Supervisor -Radiological Analysis and Instrumentation BY:
(C-Supervisbr' Health Physics Technical Services BY:
Manager Radiological Protection and Chemistry
FORWARD This report is submitted in accordance with North Anna Unit 1 and 2 Technical Specification 5.6.3 and North Anna Independent Spent Fuel Storage Installation (ISFSI) Technical Specification 5.5.2.c and 10CFR72.44(d)(3).
ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT FOR THE NORTH ANNA POWER STATION JANUARY 01, 2011 TO DECEMBER 31, 2011 INDEX Section No.
1 2
3 4
Subiect Page EXECUTIVE
SUMMARY
PURPOSE AND SCOPE...................................
DISCUSSION..................................................
SUPPLEMENTAL INFORMATION.......................
Effluent Release Data.................................
Annual and Quarterly Doses........................
Revisions to Offsite Dose Calculation Manual (ODCM)........................................
Major Changes to Radioactive Liquid, Gaseous, and Solid Waste Treatment S yste m s..................................................
Inoperability of Radioactive Liquid and Gaseous Effluent Monitoring Instrumentation........................................
Unplanned Releases.................................
Lower Limits of Detection (LLD) for Effluent Sample Analysis...........................
Results of Ground Water Protection Initiative Sample Analysis.....................................
Carbon-14 Calculations.............................
1-2 2
3-4 4
5 6
7 8
9 10 11-12 13 - 30 31 - 32
1.0 EXECUTIVE
SUMMARY
The Annual Radioactive Effluent Release Report describes the radioactive effluent control program conducted at the North Anna Power Station and Independent Spent Fuel Storage Installation (ISFSI) during the 2011 calendar year. This document summarizes the quantities of radioactive liquid and gaseous effluents and solid waste released from the North Anna Power Station and ISFSI in accordance with R.G.
1.21 during the period January 1 through December 31, 2011, and includes an assessment of radiation doses to the maximum exposed member of the public due to radioactive liquid and gaseous effluents.
There were no releases from the ISFSI during 2011.
There were no unplanned releases, meeting the reporting criteria of section 6.7.2.a.3 of the Offsite Dose Calculation Manual during this reporting period. Neither were there any spills or leaks meeting the voluntary communication criteria of the NEI Ground Water Protection Initiative.
Based on the 2011 effluent release data, 10 CFR 50, Appendix I dose calculations were performed in accordance with the Offsite Dose Calculation Manual. The results of these pathway dose calculations indicate the following:
- a.
The total body dose due to liquid effluents was 4.61E-1 mrem, which is 7.68% of the dose limit and the critical organ dose due to liquid effluents was 4.63E-1 mrem, which is 2.32% of the dose limit.
- b.
The air doses due to noble gases was 5.46E-5 mrad gamma, which is 2.73E-4% of the annual gamma dose limit, and 9.OOE-4 mrad beta, which is 2.25E-3% of the annual beta dose limit.
- c.
The critical organ dose for 1-131, 1-133, H-3, and Particulates with half-lives greater than 8 days including C-14 was 8.15E-01 mrem, which is 2.72% of the annual dose limit. The bases of these calculations are described in Attachment 9.
- d.
The critical organ dose for 1-131,1-133, H-3, and Particulates with half-lives greater than 8 days not including C-14 was 7.34E-3 mrem, which is 2.45E-2% of the annual dose limit.
There were no major changes to either the radioactive liquid waste treatment system, or to the gaseous, and solid waste treatment systems during this reporting period.
There were two revisions to the Offsite Dose Calculation Manual during this reporting period.
I
1.0 EXECUTIVE
SUMMARY
(cont.)
Based on the levels of radioactivity observed during this reporting period and the dose calculations performed, the operations of the North Anna Nuclear Power Station Units 1 and 2 and ISFSI have resulted in negligible dose consequences to the maximum exposed member of the public in unrestricted areas.
During late March of 2011, effluent samples obtain from Ground level release points identified detectable concentrations of 1-131 that could be related to operation of North Anna Power Station. The concentrations detected were above levels historically observed for the plant's operating status during that period. Concentrations returned to those historically observed levels after March. Given the events of March 2011 at the Daiichi plant, Fukushima Japan and the associated airborne releases and subsequent trans-Pacific transportation, the slightly elevated concentrations detected at these release points are reasonably attributed to the Daiichi releases. However, the concentrations detected at North Anna Power Station and projected doses are conservatively included in this report for completeness.
2.0 PURPOSE AND SCOPE The Radioactive Effluent Release Report includes, in Attachment 1, a summary of the quantities of radioactive liquid and gaseous effluents and solid waste as outlined in Regulatory Guide 1.21, "Measuring, Evaluating, and Reporting Radioactivity in Solid Wastes and Releases of Radioactive Materials in Liquid and Gaseous Effluents from Light-Water-Cooled Nuclear Power Plants", Revision 1, June 1974, with data summarized on a quarterly basis for Table 1 and 2 and on an annual basis on Table 3. The report submitted before May 1 st of each year includes an assessment of radiation doses to the maximum exposed member of the public due to radioactive liquid and gaseous effluents released from the site during the previous calendar year. The report also includes a list of unplanned releases during the reporting period, in.
As required by Technical Specification, any changes to the Offsite Dose Calculation Manual (ODCM) for the time period covered by this report are included in Attachment 3.
Major changes to radioactive liquid, gaseous and solid waste treatment systems are reported in Attachment 4, as required by the ODCM, section 6.7.2.a.4. Information to support the reason(s) for the change(s) and a summary of the 10 CFR 50.59 evaluation are included. In lieu of reporting major changes in this report, major changes to the radioactive waste treatment systems may be submitted as part of FSAR updates.
As required by the ODCM, sections 6.2.2.b.2 and 6.3.2.b.3, a list and explanation for the inoperability of radioactive liquid and/or gaseous effluent monitoring instrumentation is provided in Attachment 5 of this report.
2
3.0 DISCUSSION The basis for the calculation of the percent of Technical Specification for the critical organ in Table 1A of is the ODCM, section 6.3.1, which requires that the dose rate for iodine-1 31 & iodine-1 33, for tritium, and for all radionuclides in particulate form with half-lives greater than 8 days shall be less than or equal to 1500 mrem/yr to the critical organ at or beyond the site boundary. The critical organ is the child's bone if C-14 is included and child's thyroid if C-14 is not included both via the inhalation pathway.
The basis for the calculation of percent of Technical Specification for the total body and skin in Table 1 A of is the ODCM, section 6.3.1, which requires that the dose rate for noble gases to areas at or beyond the site boundary shall be less than or equal to 500 mrem/yr to the total body and less than or equal to 3000 mrem/yr to the skin.
The basis for the calculation of the percent of Technical Specification in Table 2A in Attachment 1 is the ODCM, section 6.2.1, which states that the concentrations of radioactive material released in liquid effluents to unrestricted areas shall be limited to 10 times the concentrations specified in 10 CFR 20, Appendix B, Table 2, Column 2 for radionuclides other than dissolved or entrained noble gases. For dissolved or entrained noble gases, the concentration shall be limited to 2.0E-4 RCi/ml.
Percent of Technical Specification calculations are based on the total gaseous or liquid effluents released for that respective quarter.
The annual and quarterly doses, as reported in Attachment 2, were calculated according to the methodology presented in the ODCM. The beta and gamma air doses due to noble gases released from the site were calculated at site boundary. The maximum exposed member of the public from the releases of airborne iodine-1 31 & iodine-1 33, tritium and all radionuclides in particulate form with half-lives greater than 8 days, including carbon-14 is defined as a child, exposed through the vegetation pathway, with the critical organ being the bone. If carbon-14 is excluded from these calculations, the maximum exposed member of the public from the releases of airborne iodine-1 31 & iodine-1 33, tritium and all radionuclides in particulate form with half-lives greater than 8 days, excluding carbon-14, is defined as a child, exposed through the vegetation pathway, with the critical organ being the thyroid gland. The maximum exposed member of the public for calculation of total body dose from radioactive materials in liquid effluents released to unrestricted areas is defined as a child, and also as a child for the calculation of critical organ dose, which was determined to be the liver. The age group is exposed via the drinking water and fish ingestion pathways.
As shown in Attachment 6 there were no unplanned releases meeting the requirements of 6.7.2.a.3 of the ODCM.
3
3.0 DISCUSSION (cont.)
The typical Lower Limit of Detection (LLD) capabilities of the radioactive effluent analysis instrumentation are presented in Attachment 7. These LLD values are based upon conservative conditions (i.e., minimum sample volume and maximum delay time prior to analysis). Actual LLD values may be lower.
If a radioisotope was not detected when effluent samples were analyzed, then the activity of that radioisotope was reported as Not Detectable (N/D) on Attachment 1 of this report. If an analysis for an isotope was not performed, then the activity was reported as Not Applicable (N/A).
4.0 SUPPLEMENTAL INFORMATION As required by the ODCM, section 6.6.2, evaluation of the Land Use Census is made to determine if new location(s) have been identified for the radiological environmental monitoring program pursuant to the ODCM. One (1) new location was added and one (1) change was made to the land use census in 2011.
The vegetation sample location in the ESE sector was removed from the program and a new location in the NNE sector was added to the program.
Section 6.6.1.b.4 of the ODCM requires identification of the cause(s) for the unavailability of milk or leafy vegetation samples, and the identification of new locations for obtaining replacement samples.
All milk samples were collected as required. Vegetation samples were not collected from stations 14A, 15, 16, 21 and 23 from January through April and from 14B, 15, 16, 21 and 23 during December due to seasonal unavailability. All other vegetation samples were obtained. contains the results of samples associated with ground water protection sampling undertaken at North Anna to voluntarily comply with the Nuclear Energy Institute, NEI, Ground Water Protection Initiative. In addition to the well, river, and surface water samples included as part of the Radiological Environmental Monitoring Program, North Anna obtained subsurface water samples from various locations on the site. contains an explanation of the bases for the carbon-14 calculations performed to assess doses due to carbon-14. Doses and %TS for gaseous releases are displayed with C-14 included and without for comparison of the values.
4
ATTACHMENT 1
EFFLUENT RELEASE DATA (01/11 - 12/11)
This attachment includes a summary of the quantities of radioactive liquid and gaseous effluents and solid waste, as outlined in Regulatory Guide 1.21, Appendix B, except that in accordance with Step 6.7.2.a.1 of the ODCM liquid and gaseous data is summarized on a quarterly basis and solid waste is summarized on an annual basis.
5
TABLE JA NORTH ANNA POWER STATION ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT SUMMATION OF ALL GASEOUS EFFLUENT RELEASES FOR (01/11 - 12/11)
Page 1 of 2 1 ST 2 ND ESTIMATED TOTAL UNITS QUARTER QUARTER PERCENT ERROR (%)
A.
Fission and Activiation Gases:
- 1. Total Release Curies O.OOE+00 4.23E-01 1.80E+1
- 2. Average Release Rate For Period piCi/sec O.OOE+00 5.38E-02 B.
- 1. Total Iodine-131 Release Curies 1.30E-05 O.OOE+00 2.80E+1
- 2. Average Release Rate For Period lJCi/sec 1.67E-06 O.OOE+00 C. Particulate (Tll2 > 8 days):
- 1. Total Particulate (T1/2 > 8 days) Release Curies O.OOE+00 O.OOE+00 2.80E+1
- 2. Average Release Rate For Period pCi/sec O.OOE+00 O.OOE+00
- 3. Gross Alpha Radioactivity Release Curies 2.75E-08 O.OOE+00 D. Tritium:
- 1. Total Release Curies 1.78E+00 2.32E+00 3.10E+1
- 2. Average Release Rate For Period piCi/sec 2.29E-01 2.95E-01 E. Carbon-14
- 1. Total Release Curies O.OOE+00 1.31E+00
- 2. Average Release Rate For Period pCi/sec O.OOE+00 1.67E-01 F.
Percentage Of Technical Specification Limits
- 1. Total Body Dose Rate O.OOE+00 1.62E-06
- 2. Skin Dose Rate O.OOE+00 2.28E-05
- 3. Critical Organ Dose Rate (with C-14) 6.41E-15 3.72E-03 Critical Organ Dose Rate (without C-14) 3.75E-05 2.69E-05
TABLE JA NORTH ANNA POWER STATION ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT SUMMATION OF ALL GASEOUS EFFLUENT RELEASES FOR (01/11 - 12111)
Page 2 of 2 3 RD 4 TH ESTIMATED TOTAL UNITS QUARTER QUARTER PERCENT ERROR (%)
A. Fission and Activiation Gases:
- 1. Total Release Curies 4.67E+00 1.06E-01 1.80E+1
- 2. Average Release Rate For Period pCi/sec 5.88E-01 1.34E-02 B. lodines:
- 1. Total Iodine-131 Release Curies 3.69E-06 O.OOE+00 2.80E+1
- 2. Average Release Rate For Period pCi/sec 4.64E-07 O.OOE+00 C.
Particulate (Til2 > 8 days):
- 1. Total Particulate (T1/2 > 8 days) Release Curies 2.83E-05 2.16E-06 2.80E+1
- 2. Average Release Rate For Period pCi/sec 3.56E-06 2.71 E-07
- 3. Gross Alpha Radioactivity Release Curies 1.60E-07 1.83E-07 D. Tritium:
- 1. Total Release Curies 7.37E+00 9.24E+00 3.10E+1
- 2. Average Release Rate For Period pCi/sec 9.27E-01 1.16E+00 F. Carbon-14
- 1. Total Release Curies 1.45E+01 3.29E-01
- 2. Average Release Rate For Period pCi/sec 1.82E+00 4.14E-02 F.
Percentage Of Technical Specification Limits
- 1. Total Body Dose Rate 3.41E-05 1.14E-06 5.82E-05 2.41 E-06
- 2. Skin Dose Rate
- 3. Critical Organ Dose Rate (with C-14) 1.13E-02 3.65E-04 Critical Organ Dose Rate (without C-14) 5.78E-04 7.29E-04
TABLE 1B NORTH ANNA POWER STATION ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT MIXED MODE GASEOUS EFFLUENT RELEASES FOR (01/11 - 12/11)
Page 1 of 4 CONTINUOUS MODE BATCH MODE 1ST 2ND 1ST 2ND NUCLIDES RELEASED UNITS QUARTER QUARTER QUARTER QUARTER Fission & Activation Gases:
Krypton - 85 Ci N/D N/D N/D N/A Krypton - 85m Ci N/D N/D N/D N/A Krypton - 87 Ci N/D N/D N/D N/A Krypton - 88 Ci N/D N/D N/D N/A Xenon - 131m Ci N/D N/D N/D N/A Xenon - 133 Ci N/D N/D N/D N/A Xenon - 133m Ci N/D N/D N/D N/A Xenon - 135 Ci N/D N/D N/D N/A Xenon - 135m Ci N/D N/D N/D N/A Xenon - 137 Ci N/D N/D N/D N/A Xenon - 138 Ci N/D N/D N/D N/A Other (Specify)
N/D N/D N/D N/A Argon - 41 Ci N/D N/D N/D N/A Total For Period Ci N/D N/D N/D N/A lodines:
Iodine - 131 Ci N/D N/D N/D N/A Iodine - 132 Ci N/D N/D N/D N/A Iodine - 133 Ci N/D N/D N/D N/A Iodine - 134 Ci N/D N/D N/D N/A Iodine - 135 Ci N/D N/D N/D N/A Total For Period Ci N/D N/D N/D N/A Particulates:
Manganese - 54 Ci N/D N/D N/D N/A Cobalt - 58 Ci N/D N/D N/D N/A Iron - 59 Ci N/D N/D N/D N/A Cobalt - 60 Ci N/D N/D N/D N/A Zinc - 65 Ci N/D N/D N/D N/A Strontium - 89 Ci N/D N/D N/D N/A Strontium - 90 Ci N/D N/D N/D N/A Cesium - 134 Ci N/D N/D N/D N/A Cesium - 136 Ci N/D N/D N/D N/A Cesium - 137 Ci N/D N/D N/D N/A
TABLE lB NORTH ANNA POWER STATION ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT MIXED MODE GASEOUS EFFLUENT RELEASES FOR (01111
- 12111)
Page 2 of 4 CONTINUOUS MODE BATCH MODE 1ST 2ND 1ST 2ND NUCLIDES RELEASED UNITS QUARTER QUARTER QUARTER QUARTER Particulates:
(cont.)
Barium - Lanthanum - 140 Ci N/D N/D N/D N/A Cerium - 141 Ci N/D N/D N/D N/A Cerium - 144 Ci N/D N/D N/D N/A Other (Specify)
Total for Period (Tl/2 > 8 days)
Ci N/D N/D N/D N/A Total for Period (Tl/2 < 8 days)
Ci N/D N/D N/D N/A Total For Period Ci N/D N/D N/D N/A GROSS ALPHA:
Ci N/D N/D N/D N/A TRITIUM:
Ci 1.78E+00 2.31 E+00 1.89E-04 N/A CARBON-14 Ci N/D N/D N/D N/A
TABLE 1B NORTH ANNA POWER STATION ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT MIXED MODE GASEOUS EFFLUENT RELEASES FOR (01/11 - 12/11)
Page 3 of 4 CONTINUOUS MODE BATCH MODE 3RD 4TH 3RD 4TH NUCLIDES RELEASED UNITS QUARTER QUARTER QUARTER QUARTER Fission & Activation Gases:
Krypton - 85 Ci N/D N/D 2.41E+00 7.OOE-02 Krypton - 85m Ci N/D N/D N/D N/D Krypton - 87 Ci N/D N/D N/D N/D Krypton - 88 Ci N/D N/D N/D Xenon - 131 m Ci N/D N/D 4.46E-02 N/D Xenon - 133 Ci 1.93E-02 N/D 1.40E+00 N/D Xenon - 133m Ci N/D N/D 3.57E-05 N/D Xenon - 135 Ci N/D N/D N/D N/D Xenon - 135m Ci N/D N/D N/D N/D Xenon - 137 Ci N/D N/D N/D N/D Xenon - 138 Ci N/D N/D N/D N/D Other (Specify)
N/D N/D N/D N/D Argon - 41 Ci N/D 3.48E-03 N/D N/D Total For Period Ci 1.93E-02 3.48E-03 3.85E+00 7.OOE-02 lodines:
Iodine - 131 Ci N/D N/D N/D N/D Iodine-132 N/D N/D N/D N/D Iodine-133 Ci N/D N/D N/D N/D Iodine - 134 N/D N/D N/D N/D Iodine - 135 Ci N/D N/D N/D N/D Total For Period Ci N/D N/D N/D N/D Particulates:
Manganese - 54 Ci N/D N/D N/D N/D Cobalt - 58 Ci N/D N/D N/D N/D Iron - 59 Ci N/D N/D N/D N/D Cobalt - 60 Ci N/D N/D N/D N/D Zinc - 65 Ci N/D N/D N/D N/D Strontium - 85 Ci N/D N/D N/D N/D Strontium - 89 Ci N/D N/D N/D N/D Strontium - 90 Ci N/D N/D N/D N/D Cesium - 134 Ci N/D N/D N/D N/D Cesium - 136 Ci N/D N/D N/D N/D Cesium - 137 Ci N/D N/D N/D N/D
TABLE 1B NORTH ANNA POWER STATION ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT MIXED MODE GASEOUS EFFLUENT RELEASES FOR (01111
- 12/11)
Page 4 of 4 CONTINUOUS MODE BATCH MODE 3RD 4TH 3RD 4TH NUCLIDES RELEASED UNITS QUARTER QUARTER QUARTER QUARTER Particulates:
(cont.)
Barium - Lanthanum - 140 Ci N/D N/D N/D N/D Cerium-141 Ci N/D N/D N/D N/D Cerium-144 Ci N/D N/D N/D N/D Other (Specify)
Total for Period (Tl/2 > 8 days)
Ci N/D N/D N/D N/D Total for Period (Tl/2 - 8 days)
Ci N/D N/D N/D N/D Total For Period Ci N/D N/D N/D N/D GROSS ALPHA:
Ci N/D N/D N/D N/D TRITIUM:
Ci 9.73E-01 1.10E+00 3.80E-03 5.12E-04 CARBON-14 Ci 5.98E-02 1.08E-02 1.19E+01 2.17E-01
TABLE 1C NORTH ANNA POWER STATION ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT GROUND LEVEL GASEOUS EFFLUENT RELEASES FOR (01/11 - 12/11)
Page 1 of 4 CONTINUOUS MODE BATCH MODE 1ST 2ND 1ST 2ND NUCLIDES RELEASED UNITS QUARTER QUARTER QUARTER QUARTER Fission & Activation Gases:
Krypton - 85 Ci N/D N/D N/D 4.23E-01 Krypton - 85m Ci N/D N/D N/D N/D Krypton - 87 Ci N/D N/D N/D N/D Krypton - 88 Ci N/D N/D N/D N/D Xenon-131m Ci N/D N/D N/D N/D Xenon - 133 Ci N/D N/D "N/D N/D Xenon - 133m Ci N/D N/D N/D N/D Xenon - 135 Ci N/D N/D N/D N/D Xenon - 135m Ci N/D N/D N/D N/D Xenon - 137 Ci N/D N/D N/D N/D Xenon - 138 Ci N/D N/D N/D N/D Other (Specify)
Argon - 41 Ci N/D N/D N/D N/D Total For Period Ci N/D N/D N/D 4.23E-01 Iodines:
Iodine - 131 Ci 1.30E-05 N/D N/D N/D Iodine - 132 Ci N/D N/D N/D N/D Iodine - 133 Ci N/D N/D N/D N/D Iodine - 134 Ci N/D N/D N/D N/D Iodine - 135 Ci N/D N/D N/D N/D Total For Period Ci 1.30E-05 N/D N/D N/D Particulates:
Manganese - 54 Ci N/D N/D N/D N/D Cobalt - 58 Ci N/D N/D N/D N/D Iron - 59 Ci N/D N/D N/D N/D Cobalt - 60 Ci N/D N/D N/D N/D Zinc - 65 Ci N/D N/D N/D N/D Strontium - 89 Ci N/D N/D N/D N/D Strontium - 90 Ci N/D N/D N/D N/D Cesium - 134 Ci N/D N/D N/D N/D
TABLE 1C NORTH ANNA POWER STATION ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT GROUND LEVEL GASEOUS EFFLUENT RELEASES FOR (01111 - 12/11)
Page 2 of 4 CONTINUOUS MODE BATCH MODE 1ST 2ND 1ST 2ND NUCLIDES RELEASED UNITS QUARTER QUARTER QUARTER QUARTER Particulates:
(cont.)
Cesium - 137 Ci N/D N/D N/D N/D Barium - Lanthanum - 140 Ci N/D N/D N/D N/D Cerium - 141 Ci N/D N/D N/D N/D Cerium - 144 Ci N/D N/D N/D N/D Other (Specify)
Rubidium-88 (Tl/2 < 8 days)
Ci N/D N/D N/D N/D Cerium-143 (Tl/2 < 8 days)
Ci N/D N/D N/D N/D Total for Period (T1/2 > 8 days)
Ci 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Total for Period (Tl/2 < 8 days)
Ci N/D N/D N/D N/D Total For Period Ci 0.OOE+00 O.OOE+00 0.OOE+00 0.OOE+00 GROSS ALPHA:
Ci 2.75E-08 N/D N/D N/D TRITIUM:
Ci N/D N/D 4.39E-05 5.69E-03 CARBON-14 Ci N/D N/D N/D 1.31E+00
TABLE 1C NORTH ANNA POWER STATION ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT GROUND LEVEL GASEOUS EFFLUENT RELEASES FOR (01/11 - 12/11)
Page 3 of 4 CONTINUOUS MODE BATCH MODE 3RD 4TH 3RD 4TH NUCLIDES RELEASED UNITS QUARTER QUARTER QUARTER QUARTER Fission & Activation Gases:
Krypton - 85 Ci N/D N/D 5.52E-01 3.15E-02 Krypton - 85m Ci N/D N/D N/D N/D Krypton - 87 Ci N/D N/D N/D N/D Krypton - 88 Ci N/D N/D N/D N/D Xenon - 131m Ci N/D N/D 1.01E-02 3.50E-04 Xenon - 133 Ci N/D N/D 2.33E-01 8.13E-04 Xenon - 133m Ci N/D N/D 1.64E-03 N/D Xenon - 135 Ci N/D N/D 4.08E-03 N/D Xenon - 135m Ci N/D N/D N/D N/D Xenon-137 Ci N/D N/D N/D N/D Xenon - 138 Ci N/D N/D N/D N/D Other (Specify)
Ci Argon - 41 Ci N/D N/D N/D N/D Total For Period Ci N/D N/D 8.01E-01 3.27E-02 lodines:
Iodine - 131 Ci 3.69E-06 N/D N/D N/D Iodine - 132 Ci N/D N/D N/D N/D Iodine - 133 Ci N/D N/D N/D N/D Iodine - 134 Ci N/D N/D N/D N/D Iodine - 135 Ci N/D N/D N/D N/D Total For Period Ci 3.69E-06 N/D N/D N/D Particulates:
Manganese - 54 Ci N/D N/D N/D N/D Cobalt - 58 Ci 4.07E-06 N/D N/D N/D Iron - 59 Ci N/D N/D N/D N/D Cobalt - 60 Ci 1.31E-05 1.38E-06 8.13E-06 5.66E-07 Zinc - 65 Ci N/D N/D N/D N/D Strontium - 89 Ci N/D N/D N/D N/D Strontium - 90 Ci N/D N/D N/D N/D Cesium - 134 Ci N/D N/D N/D N/D
TABLE 1C NORTH ANNA POWER STATION ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT GROUND LEVEL GASEOUS EFFLUENT RELEASES FOR (01/11 - 12/11)
Page 4 of 4 CONTINUOUS MODE BATCH MODE 3RD 4TH 3RD 4TH NUCLIDES RELEASED UNITS QUARTER QUARTER QUARTER QUARTER Particulates:
(cont.)
Cesium - 137 Ci N/D N/D 2.49E-07 2.09E-07 Barium - Lanthanum - 140 Ci N/D N/D N/D N/D Cerium - 141 Ci N/D N/D N/D N/D Cerium - 144 Ci N/D N/D N/D N/D Other (Specify)
Chromium-51 (T112 > 8 days)
Ci N/D N/D N/D N/D Zirconium-95 (Tl/2 > 8days)
Ci N/D N/D N/D N/D Niobium-95 (Tl/2 > 8days)
Ci 2.71E-06 N/D N/D N/D Silver-11Om (Tl/2 > 8 days)
Ci N/D N/D N/D N/D Total for Period (Tl/2 > 8 days)
Ci 1.99E-05 1.38E-06 8.38E-06 7.75E-07 Total for Period (Tl/2 < 8 days)
Ci N/D N/D N/D N/D Total For Period Ci 1.99E-05 1.38E-06 8.38E-06 7.75E-07 GROSS ALPHA:
Ci 1.60E-07 1.83E-07 N/D N/D TRITIUM:
Ci N/D 5.83E+00 6.39E+00 2.31E+00 CARBON-14 Ci N/D N/D 2.48E+00 1.01E-01
TABLE 2A NORTH ANNA POWER STATION ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT LIQUID EFFLUENT - SUMMATION OF ALL RELEASES FOR (01/11 -
12111)
Page 1 of 2 1 ST 2 ND ESTIMATED TOTAL UNITS QUARTER QUARTER PERCENT ERROR (%)
A.
Fission and Activiation Products:
- 1. Total Release (not including tritium, noble gas, and gross alpha).
Curies 3.44E-03 1.11 E-03 2.OOE+01
- 2. Average diluted concentration during the period.
p.Ci/ml 1.02E-11 1.58E-12
- 3. Percent of applicable limit (T.S.)
1.22E-05 3.18E-06 B.
Tritium:
- 1. Total release activity.
Curies 1.42E+02 1.38E+02 2.OOE+01
- 2. Average diluted concentration during the period.
jICi/ml 4.20E-07 1.97E-07
- 3. Percent of applicable limit (T.S.)
4.20E-03 1.97E-03 C.
Dissolved and Entrained Gases:
- 1. Total release activity.
Curies O.OOE+00 O.OOE+00 2.OOE+01
- 2. Average diluted concentration during the period.
pCi/ml O.OOE+00 O.OOE+00
- 3. Percent of applicable limit (T.S.)
O.OOE+00 O.OOE+00 D. Gross Alpha Radioactivity:
- 1. Total release activity.
Curies O.OOE+00 O.OOE+00 2.00E+01 E.
Volume of waste released: (prior to dilution).
Liters 1.34E+08 1.25E+08 3.OOE+00 F. Total volume of dilution water used during the period.
Liters 3.38E+1 1 7.00E+1 1 3.OOE+00
TABLE 2A NORTH ANNA POWER STATION ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT LIQUID EFFLUENT-SUMMATION OF ALL RELEASES FOR (01/11 - 12/11)
Page 2 of 2 3 RD 4 TH ESTIMATED TOTAL UNITS QUARTER QUARTER PERCENT ERROR (%)
A. Fission and Activiation Products:
- 1. Total Release (not including tritium, noble gas, and gross alpha).
Curies 3.76E-03 2.99E-03 2.OOE+01
- 2. Average diluted concentration during the period.
pCi/ml 6.58E-12 6.23E-12
- 3. Percent of applicable limit (T.S.)
1.21 E-05 1.77E-05 B.
Tritium:
- 1. Total release activity.
Curies 4.80E+02 5.46E+02 2.OOE+01
- 2. Average diluted concentration during the period.
gCi/ml 8.40E-07 1.14E-06
- 3. Percent of applicable limit (T.S.)
8.40E-03 1.14E-02 C.
Dissolved and Entrained Gases:
- 1. Total release activity.
Curies O.OOE+00 O.OOE+00 2.OOE+01
- 2. Average diluted concentration during the period.
jiCi/ml O.OOE+00 O.OOE+00
- 3. Percent of applicable limit (T.S.)
O.OOE+00 O.OOE+00 D. Gross Alpha Radioactivity:
- 1. Total release activity.
Curies O.OOE+00 O.OOE+00 2.OOE+01 E.
Volume of waste released: (prior to dilution).
Liters 1.16E+08 8.74E+07 3.OOE+00 F. Total volume of dilution water used during the period.
Liters 5.72E+11 4.81 E+1 1 3.OOE+00
TABLE 2B NORTH ANNA POWER STATION ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT LIQUID EFFLUENT RELEASES FOR (01/11 - 12/11)
Page 1 of 4 CONTINUOUS MODE BATCH MODE t
1ST 2ND 1ST 2ND NUCLIDES RELEASED UNITS QUARTER QUARTER QUARTER QUARTER Fission & Activation Products:
Manganese - 54 Ci N/D N/D N/A N/A Iron - 55 Ci N/D N/D N/A N/A Cobalt - 58 Ci 2.60E-03 6.26E-04 N/A N/A Cobalt - 60 Ci 8.34E-04 4.37E-04 N/A N/A Strontium - 89 Ci N/D N/D N/A N/A Strontium - 90 Ci N/D N/D N/A N/A Niobium - 95 Ci N/D N/D N/A N/A Ruthenium - 106 Ci N/D N/D N/A N/A Silver - 110m Ci N/D N/D N/A N/A Iodine - 131 Ci N/D N/D N/A N/A Iodine - 133 Ci N/D N/D N/A N/A Cesium - 134 Ci N/D 5.74E-06 N/A N/A Cesium - 137 Ci 4.74E-06 3.91 E-05 N/A N/A Barium-Lathanum - 140 Ci N/D N/D N/A N/A Cerium - 141 Ci N/D N/D N/A N/A Other (Specify)
Ci Niickel - 63 (T1/2 > 8 days)
Ci N/D N/D N/A N/A Total for Period Ci 3.44E-03 1.11E-03 N/A N/A
TABLE 2B NORTH ANNA POWER STATION ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT LIQUID EFFLUENT RELEASES FOR (01/11 - 12/11)
Page 2 of 4 CONTINUOUS MODE BATCH MODE 1ST 2ND 1ST 2ND NUCLIDES RELEASED UNITS QUARTER QUARTER QUARTER QUARTER Dissolved & Entrained Noble Gases:
Xenon - 133 Ci N/D N/D N/A N/A Xenon - 133m Ci N/D N/D N/A N/A Xenon - 135 Ci N/D N/D N/A N/A Xenon - 135m Ci N/D N/D N/A N/A Other (Specify)
Ci N/D N/D N/A N/A Kr-88 ( T1/2 < 8 days)
Ci N/D N/D N/A N/A Kr-85 (T1/2 > 8 days)
Ci N/D N/D N/A N/A Total for Period Ci N/D N/D N/A N/A Tritium Ci 1.42E+02 1.38E+02 N/A N/A Gross Alpha Ci N/D N/D N/A N/A
TABLE 2B NORTH ANNA POWER STATION ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT LIQUID EFFLUENT RELEASES FOR (01/11
- 12/11)
Page 3 of 4 CONTINUOUS MODE BATCH MODE 3RD 4TH 3RD 4TH NUCLIDES RELEASED UNITS QUARTER QUARTER QUARTER QUARTER Fission & Activation Products:
Manganese - 54 Ci N/D 2.32E-05 N/A 3.86E-06 Iron - 55 Ci N/D N/D N/A N/D Cobalt - 58 Ci 1.98E-03 5.66E-04 N/A 1.55E-05 Cobalt - 60 Ci 1.78E-03 2.20E-03 N/A 1.21 E-04 Strontium - 89 Ci N/D N/D N/A N/D Strontium - 90 Ci N/D N/D N/A N/D Niobium - 95 Ci N/D 9.22E-06 N/A N/D Ruthenium - 106 Ci N/D N/D N/A N/D Silver - 11Om Ci N/D N/D N/A 9.64E-07 Iodine - 131 Ci N/D N/D N/A N/D Iodine - 133 Ci N/D N/D N/A N/D Cesium - 134 Ci N/D N/D N/A 1.82E-05 Cesium - 137 Ci N/D N/D N/A 2.64E-05 Barium-Lathanum - 140 Ci N/D N/D N/A N/D Cerium - 141 Ci N/D N/D N/A N/D Other (Specify)
Niickel - 63 (T1/2 > 8 days)
Ci N/D N/D N/A N/D Antimony-1 22 (T1/2 < 8 days)
Ci N/D N/D N/A 2.36E-06 Antimony-125 (T1/2 > 8 days)
Ci N/D N/D N/A 5.96E-06 Tellurium-125m (T1/2 > 8 days)
Ci N/D N/D N/A 1.85E-06 Total for Period Ci 3.76E-03 2.80E-03 N/A 1.96E-04
TABLE 2B NORTH ANNA POWER STATION ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT LIQUID EFFLUENT RELEASES FOR (01/11 - 12/11)
Page 4 of 4 CONTINUOUS MODE BATCH MODE 3RD 4TH 3RD 4TH NUCLIDES RELEASED UNITS QUARTER QUARTER QUARTER QUARTER Dissolved & Entrained Noble Gases:
Xenon - 133 Ci N/D N/D N/A N/D Xenon - 133m Ci NID N/D N/A N/D Xenon - 135 Ci N/D N/D N/A N/D Xenon - 135m Ci N/D N/D N/A N/D Other (Specify)
Argon - 41 (Tl/2 < 8 days)
Ci N/D N/D N/A N/D Krypton - 85 (Tl/2 > 8 days)
Ci N/D N/D N/A N/D Total for Period Ci N/D N/D N/A N/D Tritium Ci 4.80E+02 5.46E+02 N/A 6.09E-04 Gross Alpha Ci N/D N/D N/A N/D
TABLE 3 NORTH ANNA POWER STATION RADIOACTIVE EFFLUENT RELEASE REPORT SUMMATION OF SOLID RADIOACTIVE WASTE AND IRRADIATED FUEL SHIPMENTS FOR 01-01-11 THROUGH 12-31-11 Page 1 of 2 A. SOLID WASTE SHIPPED OFFSITE FOR BURIAL OR DISPOSAL (NOT IRRADIATED FUEL) 12-Month Estimated Total
- 1. Type of Waste Unit Period Percent Error (%)
- a.
Spent resins, sludges, filters sludge, m3 2.56E+01 2.50E+01 evaporator bottoms, etc.,
Ci 5.83E+01 2.50E+01
- b.
Dry compressible waste, contaminated m3 4.02E+02 2.50E+01 equipment, etc.,
Ci 8.62E+00 2.50E+01
- c.
Irradiated components, control rods, m3 1.12E+01 2.50E+01 etc.,
Ci 7.OOE-01 2.50E+01
- d. Other (describe)
Used oil/Blast media/Sewage/Gravel m3 1.71 E+00 2.50E+01 DessicantlSoil/Cons'ruction debris Ci 2.51 E-03 2.50E+01 Animal Carcasses
- 2. Estimate of major nuclide composition Estimated Total (by type of waste)
(M)
(Ci)
Percent Error (%)
- a.
Ni-63 3.47E+01 2.02E+01 2.50E+01 Cs-137 1.81E+01 1.06E+01 2.50E+01 Co-60 1.71E+01 9.98E+00 2.50E+01 Co-58 1.33E+01 7.72E+00 2.50E+01 Cs-134 1.23E+01 7.16E+00 2.50E+01 C-14 1.34E+00 7.79E-01 2.50E+01 Fe-55 1.03E+00 6.02E-01 2.50E+01 Mn-54 7.99E-01 4.65E-01 2.50E+01 Ni-59 6.69E-01 3.90E-01 2.50E+01
- b.
Cr-51 3.76E+01 3.24E+00 2.50E+01 Co-60 2.41E+01 2.08E+00 2.50E+01 Co-58 1.09E+01 9.43E-01 2.50E+01 Nb-95 8.48E+00 7.32E+00 2.50E+01 Fe-55 8.37E+00 7.22E-01 2.50E+01 Zr-95 5.39E+00 4.65E-01 2.50E+01 Mn-54 2.24E+00 1.93E-01 2.50E+01 Ni-63 1.04E+00 8.94E-02 2.50E+01 Fe-59 9.72E-01 8.38E-02 2.50E+01
- c.
Co-60 3.68E+01 2.58E-01 2.50E+01 Fe-55 3.56E+01 2.49E-01 2.50E+01 Ni-63 7.59E+00 5.32E-02 2.50E+01 Cs-137 7.55E+00 5.28E-02 2.50E+01 Cr-51 4.70E+00 3.29E-02 2.50E+01 Co-58 2.52E+00 1.77E-02 2.50E+01 Mn-54 1.78E+00 1.25E-02 2.50E+01 Nb-95 1.71E+00 1.20E-02 2.50E+01 Zr-95 1.15E+00 8.04E-03 2.50E+01
- d.
H-3 5.70E+01 1.43E-03 2.50E+01 Co-60 2.47E+01 6.19E-04 2.50E+01 Co-58 5.46E+00 1.37E-04 2.50E+01 Fe-55 3.21 E+00 8.05E-05 2.50E+01 C-14 2.43E+00 6.08E-05 2.50E+01 Nb-95 2.40E+00 6.00E-05 2.50E+01 Zr-95 1.67E+00 4.18E-05 2.50E+01 Ni-63 1.40E+00 3.52E-05 2.50E+01 SMn-54 7.05E-01 1.76E-05 2.50E+01
TABLE 3 NORTH ANNA POWER STATION RADIOACTIVE EFFLUENT RELEASE REPORT SUMMATION OF SOLID RADIOACTIVE WASTE AND IRRADIATED FUEL SHIPMENTS FOR 01-01-11 THROUGH 12-31-11 Page 2 of 2 3.
Solid Waste Disposition Number of Shipments 1
15 Mode of Transportation Truck Truck Truck Destination Clive, UT Erwin, TN Oak Ridge, TN B.
Irradiated FuAI Shinments (Di~nogition1 IrradiatedFuel Shipments (Dispositioril Number of Shipments Mode of Transportation Destination 0
N/A N/A (1) Shipment of sludge was made to a licensed waste processor.
(2) Shipments of resin/charcoal were made to a licensed wate processor.
(2) Shipments of resin were made to licensed waste processors.
(11) Shipments containing DAW were made to a licensed waste processor. Of these:
(2) also contained activated material (2) also contained bird waste (1) also contained resin (2) also contained mechanical filters (2) of which contained bird waste in addition to the filters.
(1) Shipment of DAW was made to a licensed burial site. This shipment also contained:
(a) Charcoal (b) Metal (c) Soil
ATTACHMENT 2 ANNUAL AND QUARTERLY DOSES (01/11 - 12/11)
An assessment of radiation doses to the maximum exposed member of the public due to radioactive liquid and gaseous effluents released from the site for each calendar quarter for the calendar year of this report, along with an annual total of each effluent pathway will be made as required by ODCM Section 6.7.2.
1st 2nd 3rd 4th Annual Quarter Quarter Quarter Quarter Total Total Body Dose (mrem) 5.01E-2 4.88E-2 1.69E-1 1.93E-1 4.61E-1 Critical Organ Dose (mrem) 5.02E-2 4.96E-2 1.69E-1 1.93E-1 4.63E-1 1st 2nd 3rd 4th Annual Quarter Quarter Quarter Quarter Total Noble Gas Gamma Dose (mrad) 0.OOE+O 2.15E-6 5.10E-5 1.55E-6 5.46E-5 Noble Gas Beta Dose (mrad) 0.OOE+0 2.43E-4 6.33E-4 2.41 E-5 9.OOE-4 Critical Organ (Child bone)
Dose for 1-131, 1-133, H-3, Particulates with T1iA > 8 days (including C-14) (mrem) 4.06E-6 1.44E-1 6.52E-1 1.83E-2 8.15E-1 Critical Organ (Child thyroid)
Dose for 1-131, 1-133, H-3, Particulates with T1% > 8 days (excluding C-14) (torem) 5.76E-4 3.17E-4 2.90E-3 3.55E-3 7.34E-3 6
ATTACHMENT 3
REVISIONS TO OFFSITE DOSE CALCULATION MANUAL (ODCM)
(01/11 - 12/11)
As required by Technical Specification 5.5.1, revisions to the ODCM, effective for the time period covered by this report, are summarized in this attachment.
There were two revisions made to the ODCM in 2011.
Revision 17 was effective 01-27-2011, and Revision 18 was effective 10-04-2011. Revision 17 changed the location of some environmental TLDs due to the Site Separation Project. Revision 18 changed a vegetation sampling location due to land use census dose calculations.
7
Mk Station Dominionw Administrative Procedure
Title:
Offsite Dose Calculation Manual (North Anna)
Process / Program Owner: Manager Radiological Protection and Chemistry (North Anna) hýE Procedure Number Revision Numb E
ctive Date VPAP-2103N 18 On File Revision Summary Revised to change the sampling location for Edible broad a
t based on dose calculations from the Land Use Census PT.
Details:
Atacmnt1, Page 4 of 4. Changed Sap(Moody Lane) to 14B (Stagecoach Road).
<"2,00 Approvals on File
DOMINION VPAP-2103N REVISION 18 PAGE 2 OF 86 TABLE OF CONTENTS Section Page 1.0 PURPOSE 5
2.0 SCOPE 5
3.0 REFERENCES
/COMMITMENT DOCUMENTS 6
4.0 DEFINITIONS 8
5.0 RESPONSIBILITIES 11 6.0 INSTRUCTIONS 12 6.1 Sampling and Monitoring Criteria 12 6.2 Liquid Radioactive Waste Effluents 12 6.2.1 Liquid Effluent Concentr im' i 12 6.2.2 Liquid Monitoring Ins 10 13 6.2.3 Liquid Effluent D 16 6.2.4 Liquid Radw Tr t ent 18 6.2.5 Liquid Sa 19 6.3 Gaseous Rea i
' Effluents 19 6.3.1 G uent Dose Rate Limitation 19 6.3.
Ga(
anitoring Instrumentation 22 as Effluent Air Dose Limit 25 31, 133, H-3 & Radionuclides In Particulate Form Effluent Dose Limit 27 aseous Radwaste Treatment 29 6.4 Radioactive Liquid and Gaseous Release Permits 31 6.4.1 Liquid Waste Batch Release Permits 31 6.4.2 Continuous Release Permit 31 6.4.3 Waste Gas Decay Tank (WGDT) Release Permit 32 6.4.4 Reactor Containment Release Permits 32 6.4.5 Miscellaneous Gaseous Release Permit 32
DOMINION VPAP-2103N REVISION 18 PAGE 3 OF 86 TABLE OF CONTENTS (continued)
Section Page 6.4.6 Radioactive Liquid and Gaseous Release Controls 32 6.5 Total Dose Limit to Public From Uranium Fuel Cycle Sources 34 6.6 Radiological Environmental Monitoring 34 6.6.1 Monitoring Program 34 6.6.2 Land Use Census 36 6.6.3 Interlaboratory Comparison Program 37 6.7 Reporting Requirements 38 6.7.1 Annual Radiological Environmental Operatin 38 6.7.2 Annual Radioactive Effluent Release R 39 6.7.3 Annual Meteorological Data 42 6.7.4 Changes to the ODCM 42 6.7.5 Groundwater Protection In e
e 3.1.35]
43 7.0 RECORDS 44
DOMINION VPAP-2103N REVISION 18 PAGE 4 OF 86 TABLE OF CONTENTS (continued)
Section Page ATTACHMENTS 1
Radioactive Liquid Effluent Monitoring Instrumentation 45 2
Radioactive Liquid Effluent Monitoring Instrumentation Surveillance Requirements 47 3
Radioactive Liquid Waste Sampling and Analysis Program 49 4
Radioactive Gaseous Waste Sampling and Analysis Program 52 5
Gaseous Effluent Dose FactorsK7 56 Radioactive Gaseous Effluent Monitoring Instrumen 59 7
Radioactive Gaseous Effluent Monitoring Instrume 5
Surveillance Requirements 62 8
Critical Organ Dose Factors 65 9
Radiological Environmental Monitoring r
67 10 Environmental Sampling Locations 72 11 Detection Capabilities for Enviro a pie Analysis 76 12 Reporting Levels for Radioa 1 ita tions in Environmental Samples A
78 13 Meteorological, Liqui dse Pathway Analysis 79
DOMINION VPAP-2103N REVISION 18 PAGE 5 OF 86 1.0 PURPOSE The Offsite Dose Calculation Manual (ODCM) establishes requirements for the Radioactive Effluent and Radiological Environmental Monitoring Programs. Methodology and parameters are provided to calculate offsite doses resulting from radioactive gaseous and liquid effluents, to calculate gaseous and liquid effluent monitoring alarm/trip setpoints, and to conduct the Environmental Monitoring Program. Requirements are established for the Annual Radiological Environmental Operating Report and the Annual Radioactive Effluent Release Report required by Station Technical Specifications. Calculation of o oses due to radioactive liquid and gaseous effluents are performed to assure th.
" Concentration of radioactive liquid effluents to the unrestr'/
Ww limited to ten times the effluent concentration values of 10 CFR 20, NX B, le 2, Column 2, for radionuclides other than dissolved or entrained nob ases a-" 2 Ci/ml for dissolved or entrained noble gases.
7>
<2
- Exposure to the maximum exposed member bl"i the unrestricted area from radioactive liquid effluents will not res dosŽx er than the liquid dose limits of 10 CFR 50, AppendixI IS'2§)
" Dose rate at and beyond the site u
ry radioactive gaseous effluents will be limited to:
Noble gases - less th or al t dose rate of 500 mrem/yr to the total body and less than or equal to af mrem/yr to the skin 1131, 1133, and a,11 radonuclides in particulate form with half-lives greater than 8 days - less th r
al to a dose rate of 1500 mrem/yr to any organ
" Exposure radi ctive gaseous effluents to the maximum exposed member of the public in th "stri a will not result in doses greater than the gaseous dose limits of 10 dP)pendix L and
" Exposu real individual will not exceed 40 CFR 190 dose limits 2.0 SCOPE This procedure applies to the Radioactive Effluent and Environmental Monitoring Programs at North Anna Power Station.
DOMINION VPAP-2103N REVISION 18 PAGE 6 OF 86
3.0 REFERENCES
/COMMITMENT DOCUMENTS 3.1 References 3.1.1 10 CFR 20, Standards for Protection Against Radiation 3.1.2 10 CFR 50, Domestic Licensing of Production and Utilization Facilities 3.1.3 40 CFR 190, Environmental Radiation Protection Standards for Nuclear Power Operations 3.1.4 TID-14844, Calculation of Distance Factors for Power and Test Reactor Sites 3.1.5 Regulatory Guide 1.21, Measuring, Evaluating, and Reporti*activity in Solid Wastes and Releases of Radioactive Materials in Liquid a
" aseou Effluents from Light-Water-Cooled Nuclear Power Plants, Rev. 1, U.
R,R* )
74 3.1.6 Regulatory Guide 1.109, Calculation of Annual Dose an Fn Routine Releases of Reactor Effluents for the Purpose of Evaluat With 10 CFR 50, Appendix I, Rev. 1, U.S. NRC, October 197 3.1.7 Regulatory Guide 1.111, Methods for E atin t
pheric Transport and Dispersion of Gaseous Effluents in R n
ea from Light-Water-Cooled Reactors, Rev. 1, U.S. NRC, July 3.1.8 North Anna Technical Specifica i*
3.1.9 North Anna Technical Re en ual (TRM) 3.1.10 NUREG-0324, XOQ or the Meteorological Evaluation of Routine Effluent Releases uc a wer Stations, U.S. NRC, September 1977 3.1.11 NUREG/CR-1 s
ual for the LADTAP II Program, U.S. NRC, May, 1980 3.1.12 TID-45(
-50564, Rev. 1, Concentration Factors of Chemical Elements in Edible Aq *canisms, October, 1972 3.1.13
.258 )ol.
2, July 1973, Numerical Guides for Design Objectives and Limiting 0
Operation to Meet the Criterion "As Low As Practicable" For ive Material in Light Water-Cooled Nuclear Power Reactor Effluents 3.1.14
-0597, User's Guide to GASPAR Code., U.S. NRC, June, 1980 3.1.15 Radiological Assessment Branch Technical Position on Environmental Monitoring, November, 1979, Rev. 1 3.1.16 NUREG-0133, Preparation of Radiological Effluent Technical Specifications for Nuclear Power Stations, October, 1978 3.1.17 NUREG-0543, February 1980, Methods for Demonstrating LWR Compliance With the EPA Uranium Fuel Cycle Standard (40 CFR Part 190) 3.1.18 NUREG-0472, Standard Radiological Effluent Technical Specifications for Pressurized Water Reactors, Proposed Rev. 3, March 1982
DOMINION VPAP-2103N REVISION 18 PAGE 7 OF 86 3.1.19 Environmental Measurements Laboratory, DOE HASL 300 Manual 3.1.20 NRC Generic Letter 89-01, Implementation of Programmatic Controls for Radiological Effluent Technical Specifications (RETS) in the Administrative Controls Section of the Technical Specifications and the Relocation of Procedural Details of RETS to the Offsite Dose Calculation Manual or to the Process Control Program 3.1.21 North Anna UFSAR 3.1.22 Nuclear Reactor Environmental Radiation Monitoring Quality Control Manual, IWL-0032-361 3.1.23 North Anna Circulating Water System Modifications
- a. DC-85-37-1 Unit 1
- b. DC-85-38-2 Unit 2 3.1.24 Plant Issue (Deviation) N-1994-1137, Improp mergency TLDs 3.1.25 ET N-05-0025, Justification for removinS M
8 from service when not in use 3.1.26 VPAP-2802,. Notifications and Re 3.1.27 0-PT-75.21, 1-SW-RM-108Flo i
3.1.28 SAA001092, Non-SA SO ect*"*
gs Review 93-1, Recommendation 3 3.1.29 NEI 07-07, Industry *Cotection Initiative - Final Guidance Document 3.1.30 CA086406, Land suo sults 3.1.31 Quality Assu itort Number 91-03, Observation 08N 3.1.32 Quality A a
u eport Number 92-03, Observation 02N 3.1.33 Quality r
Audit Report Number 92-03, Observation 04NS (Item 2) 3.1.34 Plan ue(
viation) N-1997-0926, Annual Radiological Effluent Release Report 3.1.3:
a
- icensing Commitment) N-2006-4026-R15, Groundwater Monitoring o,Ian 3.1.36 S*
93-1, Diagnosis and Mitigation of RCS Leakage including SGTR 3.2 Commitment Documents None
DOMINION VPAP-2103N REVISION 18 PAGE 8 OF 86 4.0 DEFINITIONS 4.1 Channel Calibration A channel calibration shall be the adjustment, as necessary, of the channel output such that it responds within the necessary range and accuracy to known values of the parameter that the channel monitors. The channel calibration shall encompass all devices in the channel required for channel operability. The channel calibration may be performed by means of any series of sequential, overlapping, or total channel steps.
4.2 Channel Check A qualitative assessment, by observation, of channel behavior ng rat
. This tht" assessment includes, where possible, comparison of the cha4
.li ati nd status with other indications or status derived from independent ins
)nnels measuring the same parameter.
4.3 Channel Operational Test A Channel Operational Test (COT) shall ti f a simulated or actual signal into the channel as close to the sensor as prac 1 e y OPERABILITY of all devices in the channel required for channel OPE IT]*
COT shall include adjustments, as necessary, of the required ala
, e trip setpoints required for channel OPERABILITY such that s in a
ithin the necessary range and accuracy. The COT may be performed by means o r, e sequential, overlapping, or total channel steps.
4.4 Critical Organ _equ tia)
That organ., whic determined to be the maximum exposed organ based on an effluent pathway ana' s, theby ensuring the dose and dose rate limitations to any organ will not be excee "0
e ations to the critical organ will be evaluated in accordance with Techn*
p*n *ications 5.5.4 dose rate limits specified for any organ to verify these limits have not l~~xceeded.
4.5 Dose Equivalent 1-131 That concentration of 1131 (JtCi/cc) that alone would produce the same thyroid dose as the quantity and isotopic mixture of 1131, 1132, 1133, 1134, and 1135 actually present. Thyroid dose conversion factors for this calculation are listed in Table III of TID-14844, Calculation of Distance Factors for Power and Test Reactor Sites. Thyroid dose conversion factors from NRC Regulatory Guide 1.109, Revision 1, may be used.
DOMINION VPAP-2103N REVISION 18 PAGE 9 OF 86 4.6 Frequency Notations NOTE: Frequencies are allowed a maximum extension of 25 percent.
NOTATION FREQUENCY D - Daily At least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> W - Weekly At least once per 7 days M - Monthly At least once per 31 day Q - Quarterly At least once per 92 SA - Semi-annually At least once pe 4
ys R -Refueling At least onc r
0 S/U - Start-up Prior to h rea rt-up P - Prior to release Co ete each release N.A.- Not applicable lca DR-During the release a
e during each release 4.7 Gaseous Radwaste Treatment Sy A system that reduces radioactv uents by collecting primary coolant system offgases from the primary e
a roviding delay or holdup to reduce total radioactivity prior to release to the envi 'Nk't.
e system comprises the waste gas decay tanks, regenerative heat e ng.
gas charcoal filters, process vent blowers, waste gas surge tanks, and waste s
agm compressor.
4.8 General No nca X = C n
n at a point at a given instant (curies per cubic meter)
D =
- quantity of deposited radioactive material per unit area (curies per square meter)
Q = Source strength (instantaneous; grams, curies)
= Emission rate (continuous; grams per second, curies per second)
= Emission rate (continuous line source; grams per second per meter) 4.9 Lower Limit of Detection (LLD)
The smallest concentration of radioactive material in a sample that will yield a net count (above system background) that can be detected with 95 percent probability with only five percent probability of falsely concluding that a blank observation represents a "real" signal.
DOMINION VPAP-2103N REVISION 18 PAGE 10 OF 86 4.10 Members of the Public Individuals who, by virtue of their occupational status, have no formal association with the Station. This category includes non-employees of Dominion who are permitted to use portions of the site for recreational, occupational, or other purposes not associated with Station functions. This category does not include non-employees such as vending machine servicemen or postal workers who, as part of their formal job function, occasionally enter an area that is controlled by Dominion to protect individuals from exposure to radiation and radioactive materials.
4.11 Operable - Operability A system, subsystem, train, component, or device is operabl h
pe ty when it is capable of performing its specified functions and all nec e
instrumentation, controls, normal and emergency electrical power sou coo seal water, lubrication or other auxiliary equipment that are required for t st u
stem, train, component, or device to perform its functions are also capabl or their related support functions.
4.12 Purge - Purging Controlled discharge of air or gas o
ent to maintain temperature, pressure, humidity, concentration, or other er ition, so that replacement air or gas is required to purify the confinement./
A)\\,
4.13 Rated Thermal Pow Total reactor core trfer'ht e to reactor coolant (i.e., North Anna - 2893 MWt).
4.14 Site Boundary The line o..c Dominion does not own, lease, or otherwise control the land.
4.15 SourcJ s
A qualitat, sessment of channel response when a channel sensor is exposed to radiation.
This applies to installed radiation monitoring systems. For MGPI monitors, a source check is the verification of proper computer response to continuous operational checks on the detector and the electronics.
4.16 Special Report A report to NRC to comply with Subsections 6.2, 6.3, or 6.5 of this procedure. Also refer to VPAP-2802, Notifications and Reports.
DOMINION VPAP-2103N REVISION 18 PAGE 11 OF 86 4.17 Thermal Power Total reactor core heat transfer rate to the reactor coolant.
4.18 Unrestricted Area Any area at or beyond the site boundary, access to which is neither limited nor controlled by Dominion for purposes of protection of individuals from exposure to radiation and radioactive materials, or any area within the site boundary used for residential quarters or for industrial, commercial, institutional and/or recreational purposes.
4.19 Ventilation Exhaust Treatment System A system that reduces gaseous radioiodine or radioactive mat t
e form in effluents by passing ventilation or vent exhaust gases throug oa sorbers and High Efficiency Particulate Air (HEPA) filters to remove io s
ulates from a gaseous exhaust stream prior to release to the environment c
yste is not considered to have any effect on noble gas effluents). Engineered Safe e/
e atmospheric cleanup systems are not Ventilation Exhaust Treatment Sys c
on 5.0 RESPONSIBILITIES 5.1 Manager Radiological Protecti a
estry The Manager Radiological eci.
nd Chemistry is responsible for:
5.1.1 Establishing a i
rocedures for surveying, sampling, and monitoring radioactive s
ue environment.
5.1.2 Surveyin g, and analyzing plant effluents and environmental monitoring, and doc nt es activities.
5.1.
g plant effluent trends and recommending actions to correct adverse trends.
5.1.4 P ng Effluent and Environmental Monitoring Program records.
5.2 Manager Nuclear Operations The Manager Nuclear Operations is responsible for requesting samples, analyses, and authorization to release effluents.
DOMINION VPAP-2103N REVISION 18 PAGE 12 OF 86 6.0 INSTRUCTIONS NOTE: Meteorological, liquid, and gaseous pathway analyses are presented in Meteorological, Liquid, and Gaseous Pathway Analysis (Attachment 13).
6.1 Sampling and Monitoring Criteria 6.1.1 Surveys, sampling, and analyses shall use instruments calibrated for the type and range of radiation monitored and the type of discharge monitored.
6.1.2 Installed monitoring systems shall be calibrated for the typ nd ran of radiation or parameter monitored.
6.1.3 A sufficient.number of survey points shall be use e
en to adequately assess the status of the discharge monitored.
6.1.4 Samples shall be representative of the v mf discharge monitored.
6.1.5 Surveys,sampling, analyses, and to r
rds shall be accurately and legibly documented, and sufficiently de meaning and intent of the records are clear.
6.1.6 Surveys, analyses, a 0nlg records shall be reviewed for trends, completeness, and accuracy.
6.2 Liquid Radioactiv a
6.2.1 Liquid oncentration Limitations
- a. I id.
e centrations discharged from the Station shall not exceed the Sr radionuclides (other than dissolved or entrained noble gases), liquid effluent oncentrations released to unrestricted areas shall not exceed ten times the effluent concentration values specified in 10 CFR 20, Appendix B, Table 2, Column 2.
- 2. For dissolved or entrained noble gases, concentrations shall not exceed 2E-4 gCi/ml.
- b. If the concentration of liquid effluent exceeds the limits in Step 6.2.1.a., promptly reduce concentrations to within limits.
DOMINION VPAP-2103N REVISION 18 PAGE 13 OF 86
- c. Daily concentrations of radioactive materials in liquid waste released to unrestricted areas shall meet the following:
Volume of Waste Discharged + Volume of Dilution Water AC i/mli Volume of Waste Discharged x fACW.
i 1A~
where:
6>
gCi/mli = the concentration of nuclide i in the li ef e arge ACWi
= ten times the effluent concentratio u
tricted areas of nuclide i, expressed as pCi/ml
, Appendix B, Table 2, Column 2 for radionuclides an n e gases, and 2E-4 gtCi/ml for dissolved or entrained no egaes 6.2.2 Liquid Monitoring Instrumen
- a. Radioactive Liquid EffluenI nstrumentation Radioactive liquid efflu n"
o nstrumentation channels shown on Radioactive Liquid ue toring Instrumentation (Attachment 1) shall be operable with th d ar setpoints set to ensure that Step 6.2.1.a. limits are not exceeded.
- 1. Ala ti tpo' of these channels shall be determined and adjusted in a
e, with Step 6.2.2.d., Setpoint Calculation.
a ra
- active liquid effluent monitoring instrumentation channel alarm/trip s
is less conservative than required by Step 6.2.2.a., perform one of the Ilowing:
- Promptly suspend release of radioactive liquid effluents monitored by the affected channel
- Declare the channel inoperable
- Change the setpoint to an acceptable, conservative value
DOMINION VPAP-2103N REVISION 18 PAGE 14 OF 86
- b. Radioactive Liquid Effluent Monitoring Instrumentation Operability Each radioactive liquid effluent monitoring instrumentation channel shall be demonstrated operable by performing a Channel Check, Source Check, Channel Calibration, and Channel Operational Test at the frequencies shown in Radioactive Liquid Effluent Monitoring Instrumentation Surveillance Requirements (Attachment 2).
- 1. If the number of operable channels is less than the minimum required by the tables in Radioactive Liquid Effluent Monitoring Inst
'on (Attachment
- 1) perform the action shown in those tables.
- 2. Attempt to return the instruments to operable *uythi days. If unsuccessful and the channel is required t-c en explain in the next Annual Radioactive Effluent Release ort w thinoperability was not corrected in a timely manner.
- c. Applicable Monitors Liquid effluent monitors for i
setpoints shall be determined are:
y Poini
DOMINION VPAP-2103N REVISION 18 PAGE 15 OF 86
- d. Setpoint Calculation NOTE: This methodology does not preclude use of more conservative setpoints.
- 1. Maximum setpoint values shall be calculated by:
CFD S =-
(2)
FE where:
S
=
the setpoint, in ltCi/ml, of the radioac
- suring the radioactivity concentration in the efflu e*
r to dilution C
= the effluent concentration limit sed to implement 10 CFR 20 for the Station, 1 1
FE = maximum design pathway u l.n ate FD -- dilution water flow rate e
D = FE + (218,00 f circ. pumps in service)
- 2. Each of the condense ng ter channels (e.g., SW-130, SW-230) monitors the effl (s
ice er, including component cooling service water, circula
, an quid radwaste) in the circulating water discharge tunnel bey t
st int of possible radioactive material addition. No dilutio s
this pathway. Therefore, Equation (2) becomes:
S =C (3)
Th\\\\.e s i
for Station monitors used to implement 10 CFR 20 for the site the effluent concentration limit.
addition, for added conservatism, setpoints shall be calculated for the liquid rad waste effluent line LW-111 and the Service Water System effluent line SW-108.
DOMINION VPAP-2103N REVISION 18 PAGE 16 OF 86
- 4. For the liquid radwaste effluent line, Equation (2) becomes:
S CFDKLW FE (4) where:
KLW
=l 1
- 5. For the Serv where:
Ksw=
['he fraction of the effluent concentration limit, used to implement
.0 CFR 20 for the site, attributable to the I' w
effluent me pathway ice Water System effluent line,
)
es:
CF s =
i (5)
[he fraction o S_
nt concentration limit, used to implement CFR tpe*othe attributable to the service water effluent 11 not be greater than 1.0.
r 31 days, perform the dose calculations in Step 6.2.3.c. to ensure commitment to the maximum exposed member of the public from erials in liquid releases (from each reactor unit) to unrestricted areas lI
- 6. The sum 6.2.3 Liquid
- a. Rewi to:
. During any calendar quarter:
" Less than or equal to 1.5 mrem to the total body
" Less than or equal to 5 mrem to the critical organ
- 2. During any calendar year:
" Less than or equal to 3 mrem to the total body
" Less than or equal to 10 mrem to the critical organ
DOMINION VPAP-2103N REVISION 18 PAGE 17 OF 86
- b. Action If the calculated dose from release of radioactive materials in liquid effluents exceeds any of the above limits, prepare and submit to the NRC, within 30 days, a special report in accordance with VPAP-2802, Notifications and Reports, that identifies causes for exceeding limits and defines corrective actions taken to reduce releases of radioactive materials in liquid effluents to ensure that subsequent releases will be in compliance with the above limits.
- c. Dose Contribution Calculations Dose contribution shall be calculated for all radio effluents released to unrestricted areas based on:
Where:
Subscripts
i, refers to i uci D
the cumulativeA
-"S*emrt Z
t to the to in liquid (6) le tal body or critical organ from the Bi
- ~od t, in mrem ctors (mrem/Ci) for each age group of interest.
ided in code file for North Anna Power Station organ calculations V.
Qi eased activity for the considered period and the ith nuclide Qi = t x Ci x Waste Flow (7)
=
the period for which Ci and F are averaged for all liquid releases, in hours Ci = the average concentration of radionuclide, i, in undiluted liquid effluent during the period, t, from any liquid releases, in jtCi/mi
DOMINION VPAP-2103N REVISION 18 PAGE 18 OF 86
- d. Quarterly Composite Analyses For radionuclides not determined in each batch or weekly composite, dose contribution to current monthly or calendar quarter cumulative summation may be approximated by assuming an average monthly concentration based on previous monthly or quarterly composite analyses. However, for reporting purposes, calculated dose contribution shall be based on the actual composite analyses.
6.2.4 Liquid Radwaste Treatment Historical data pertaining to the volumes and radioactivity o fluents released in connection with specific station functions, such as m ' t %ce o efueling outages, shall be used in projections as appropriate.
- a. Requirement
- 1. The Liquid Radwaste Treatment all b sed to reduce the radioactive materials in liquid waste prior t sc ge" n projected dose due to liquid effluent, from each reactor t
e ed areas would exceed 0.06 mrem to total body or 0.2 mrem t t organ in a 31-day period.
- 2. Doses due to liqui e
s e projected at least once per 31 days.
- b. Action If radioactive idste discharged without treatment and in excess of the above l ubmit to the NRC, within 30 days, a special report in accora VPc -2802, Notifications and Reports, that includes the follo"t e
nation of why liquid radwaste was being discharged without treatment, entification of any inoperable equipment or sub-system, and the reason for the operability.
- 2. Actions taken to restore inoperable equipment to operable status.
- 3. Summary description of actions taken to prevent recurrence.
- c. Projected Total Body Dose Calculation
- 1. Determine DTB, the total body dose from liquid effluents in the previous 31-day period, per Equation (6).
DOMINION VPAP-2103N REVISION 18 PAGE 19 OF 86
- 2. Estimate R1, the ratio of the estimated volume of liquid effluent releases in the present 31-day period to the volume released in the previous 3 1-day period.
- 3. Estimate F1, the ratio of the estimated liquid effluent radioactivity concentration in the present 31-day period to liquid effluent concentration in the previous 31-day period (ItCi/ml).
- 4. Determine PDTB, the projected total body dose in a 31-day period.
PDTB = DTB(R1Fl)
(8)
- d. Projected Critical Organ Dose Calculation
- 1. Determine DO, the critical organ dose from liq' Iu in the previous 31-day period, per Equation (
- 2. Estimate R1 as in Step 6.2.4.c.2.
- 3. Estimate F, as in Step 6.2.4.c.3.
- 4. Determine PD = prot cdose in a 31-day period.
4.Deerie ~o=project~kX,*,
- D)o(R 1F1 )
DO(RIFI)(9) 6.2.5 Liquid Sam Radioac shall be sampled and analyzed according to the sampling and anal ements in Radioactive Liquid Waste Sampling and Analysis Pro hment 3).
6.3 Gase
~
s c ive Waste Effluents 6.3.1 G*CVs Effluent Dose Rate Limitation
- a. Requirement Dose rate due to radioactive materials released in gaseous effluents from the site to areas at and beyond the site boundary shall be limited to:
- 1. The dose rate limit for noble gases shall be < 500 mrem/year to the total body and < 3000 mrem/year to the skin.
DOMINION VPAP-2103N REVISION 18 PAGE 20 OF 86
- 2. The dose rate limit for 13 1, 1133, for tritium, and for all radioactive materials in particulate form with half-lives greater than 8 days shall be < 1500 mrem/year to the critical organ.
- b. Action
- 1. If dose rates exceed Step 6.3.1.a. limits, promptly decrease the release rate to within the above limits.
- 2. Dose rates due to noble gases in gaseous effluents shall bdetermined, continuously, to be within Step 6.3..a. limits.
- 3. Dose rates due to 1131, 1133, tritium, and all radi cl iculate form with half-lives greater than 8 days, in gaseous ts a be determined to be within the above limits by obtaining mples and performing analyses in accordance with the sa;ýll n
lysis program specified on Radioactive Gaseous Waste Sa n
sis Program (Attachment 4).
K?,,
cz~~
DOMINION VPAP-2103N REVISION 18 PAGE 21 OF 86 YT i
- c. Calculations of Gaseous Effluent Dose Rates
- 1. The dose rate limit for noble gases shall be determined to be within the limit by limiting the release rate to the lesser of:
JK ivvivv + KiPVipv] !500mrem/yr to the total body (10) i OR Livv + 1.1Mivv)Qivv + (Lipv + 1.IMpv )Qipv] *3000mrem/yrto the hi q where:
Subscripts
=
vv, refers to vent rel s
uilding ventilation vent pv, refers to the e
se m the process vent; i, refers to ind u
d lide K
Kipv
=
The total o
ac or ventilation vents or process vent release t
missions for each identified noble gas radie!.,
in em/yr per Curie/sec. Factors are listed in G
uo5e Ef ose Factors (Attachment 5)
Livv, Lipv
=
trrfactor for ventilation vents or process vent re e due to beta emissions for each identified noble gas (x*,,t'(lioj"b ide i, in mrem/yr per Curie/sec. Factors are listed in G
us Effluent Dose Factors (Attachment5) aiv it
=
e air dose factor for ventilation vents or process vent release due to gamma emissions for each identified noble gas radionuclide, i, in mrad/yr per Curie/sec. Factors are listed in Gaseous Effluent Dose Factors (Attachment 5)
The release rate for ventilation vents or process vent of noble gas radionuclide i, in gaseous effluents in Curie/sec (per site)
I
= The unit conversion factor that converts air dose to skin dose, in mrem/mrad
DOMINION VPAP-2103N REVISION 18 PAGE 22 OF 86
- 2. The dose rate limit for 13 1, 113 3, tritium, and for all radionuclides in particulate form with half-lives greater than 8 days, shall be determined to be within the limit by restricting the release rate to:
PivvQivv + PipvQipv]
- 500mrem/yr to the critical organ (12) i where:
PiVV Pipv
=
The critical organ dose factor for ven vents or process vent for 1131,1133, H3, and all radio ides i articulate form with half-lives greater than 8 d
, fo in ation pathway, in mrem/yr per Curie/sec. F rs lis' 4 n Gaseous Effluent Dose Factors (Attac 5)
QivvPv
=
The release rate for ve t
r process vent of 1131, 1133, H3, and all ra lo
- 1de, particulate form with half-lives greate an gaseous effluents in Curie/sec (per site)
- 3. All gaseous releases, not t t
sh*
"Ks vent, are considered ground level and shall be included i t rihation of Qw,.
6.3.2 Gaseous Monitoring I u_
a
- a. Requirement
- 1. The radioat'e*ei_,,
o uent monitoring instrumentation channels shown in Radio 0
s ffluent Monitoring Instrumentation (Attachment 6) shall be o with arm/trip setpoints set to ensure that Step 6.3.1.a. noble gas li' ot exceeded. Alarm/trip setpoints of these channels shall be eter *ed and adjusted in accordance with Step 6.3.2.d.
a radioactive gaseous effluent monitoring instrumentation channel all be demonstrated operable by Channel Checks, Source Checks, Channel Calibrations, and Channel Operational Tests at the frequencies shown in Radioactive Gaseous Effluent Monitoring Instrumentation Surveillance Requirements (Attachment 7).
DOMINION VPAP-2103N REVISION 18 PAGE 23 OF 86
- b. Action
- 1. If a radioactive gaseous effluent monitoring instrumentation channel alarm/trip setpoint is less conservative than required by Step 6.3.2.a. 1, promptly:
" Suspend the release of radioactive gaseous effluents monitored by the affected channel and declare the channel inoperable or
- Change the setpoint so it is acceptably conservative
- 2. If the number of operable channels is less than the m
uired by tables in Radioactive Gaseous Effluent Monitoring Inst PNnition)ttachment 6) take the action shown in those tables.
- 3. Return instruments to operable status wi successful, explain in the next Annual Radioactive Effluen why the inoperability was not corrected in a timely manner
- c. Applicable Monitors Radioactive gaseous effluent o
o>hich alarm/trip setpoints shall be determined are:
Releas o
Instrument Number ro?(e t "1-GW-RM-178-1
- 2) 1(
jector 1-SV-RM-121 2-SV-RM-221 tlilation Vent A I-VG-RM-179-1 lation Vent B
_-VG-RM-180-l
DOMINION VPAP-2103N REVISION 18 PAGE 24 OF 86
- d. Setpoint Calculations
- 1. Setpoint calculations for each monitor listed in Step 6.3.2.c. shall maintain this relationship:
D>D pv + Dcae + Dvv (13) where:
D
=
Step 6.3.1.a. dose limits that implement 10 CFR 20 for the Station, mrem/yr DPV
=
The noble gas site boundary dose rate fr roces ent gaseous effluent releases, mrem/yr 2ea Dcae
=
The noble gas site boundary dose crnser air ejector gaseous effluent releases, mre Dvv
=
The noble gas site bounda o
summation of Ventilation Vent A plusI uent releases, mrem/yr
- 2. Setpoint values shall be deter
,2 N
2 E-03 Fm (14) where:
m he ease pathway, process vent (pv), ventilation vent (vv) enser air ejector (cae)
C 1fe effluent concentration limit implementing Step 6.3.1.a.
for the Station, gCi/ml
\\M
= The release rate limit for pathway m determined from methodology in Step 6.3.l.c., using Xe133 as nuclide to be released, gCi/sec 12E-03
= CFM per ml/sec M
= The maximum flow rate for pathway m, CFM
DOMINION VPAP-2103N REVISION 18 PAGE 25 OF 86 NOTE: According to NUREG-0133, the radioactive effluent radiation monitor alarm/trip setpoints should be based on the radioactive noble gases. It is not practicable to apply instantaneous alarm/trip setpoints to integrating monitors sensitive to radioiodines, radioactive materials in particulate form, and radionuclides other than noble gases.
6.3.3 Noble Gas Effluent Air Dose Limit
- a. Requirement
- 1. The air dose in unrestricted areas due to noble gases rele in gaseous effluents from each unit at or beyond the site bound sal limited to:
- During any calendar quarter: !5 mrads for ga ra*>r\\
n!d *10 mrads for beta radiation
- During any calendar year: *<10 mrads n and <*0 mrads for beta radiation
- 2. Cumulative dose contributions no g
or the current calendar quarter and current calendar year s e
ed in accordance with Step 6.3.3.c.
at least once per 31 days.
- b. Action
/5 If the calculated ai o
active noble gases in gaseous effluents exceeds any of the abo im" pr re and submit to the NRC, within 30 days, a special report iac wi AP-2802, Notifications and Reports, that identifies the causes 4 ec in limits and defines corrective actions that have been taken to re ses and the proposed corrective actions to be taken to assure that s
e ses will be in compliance with the limits in Step 6.3.3.a.
DOMINION VPAP-2103N REVISION 18 PAGE 26 OF 86
- c. Noble Gas Effluent Air Dose Calculation Gaseous releases, not through the process vent, are considered ground level and shall be included in the determination of Qivv.
The air dose to areas at or beyond the site boundary due to noble gases shall be determined by the following:
For gamma radiation:
Dg = 3.17E-087MiQi (15)
A vv (15)
For beta radiation:
Db = 3.17E-08 vv ipvQipv]
(16) 1 Where:
Subscripts
=
vv, t
leases from the building ventilation vents, i
ciar"tors e vent releases from the process vent e
to individual radionuclide D9 e ea ose for gamma radiation, in mrad Db
-r dose for beta radiation, in mrad Mt ie air dose factors for ventilation vents or process vent release due to gamma emissions for each identified noble gas S radionuclide i, in mrad/yr per Curie/sec. Factors are listed in Gaseous Effluent Dose Factors (Attachment 5) ipv the air dose factor for ventilation vents or process vent release due to beta emissions for each identified noble gas radionuclide i, in mrad/yr per Curie/sec. Factors are listed in Gaseous Effluent Dose Factors (Attachment 5)
Qivv Qi
=
the release for ventilation vents or process vent of noble gas radionuclide i, in gaseous effluents for 31 days, quarter, or year as appropriate in Curies (per site) 3.17 E-08
=
the inverse of the number of seconds in a year
DOMINION VPAP-2103N REVISION 18 PAGE 27 OF 86 6.3.4 1-131, 133, H-3 & Radionuclides In Particulate Form Effluent Dose Limit
- a. Requirement
- 1. Methods shall be implemented to ensure that the dose to any organ of a member of the public from 1131, 1133, tritium, and all radionuclides in particulate form with half-lives greater than 8 days, in gaseous effluents released from the site to unrestricted areas from each reactor unit shall be:
" During any calendar quarter: < 7.5 mrem to the critical organ
" During any calendar year: < 15 mrem to the criticalo
- 2. Cumulative dose contributions to a member of th131fro 11,
- 1133, tritium, and radionuclides in particulate form i h iv' eater than 8 days, in gaseous effluents released to unrestricte r t urrent calendar quarter and current calendar year shal detein at least once per 31 days in accordance with Step 6.3.4.c.
- b. Action If the calculated dose from t re.
1133, tritium, and radionuclides in particuilate form, with ha reat than 8 days, in gaseous effluents exceeds any of the above lim e
e a ubmit to the NRC within 30 days, a special report in accorda wi AP-802, Notifications and Reports, that contains the:
- 1. Caues in mits.
- 2. Cor4 IV tion aken to reduce releases.
- 3. Pro
- e rrective actions to be taken to assure that subsequent releases will in c pliance with limits stated in Step 6.3.4.a.
DOMINION VPAP-2103N REVISION 18 PAGE 28 OF 86
- c. Dose Calculations Gaseous releases, not through the process vent, are considered ground level and shall be included in the determination of Qiv,. Historical data pertaining to the volumes and radioactive concentrations of gaseous effluents released in connection to specific Station functions, such as containment purges, shall be used in the estimates as appropriate.
- 1. The dose to the maximum exposed member of the public, attributable to gaseous effluents at and beyond the site boundary, thl/r" 1131, 1133, tritium, and particulate-form radionuclides with h s gre r than 8 days, shall be determined by:
D 3.17E-08YRM Q* v]
(17) r =iv 1vy+
vpv()
Where:
Subscripts
=
vv, refers t
from the building ventilation vents; pv, refer o
leases from the process vent Dr
=
the 0
c-- alorgan of the maximum exposed member e
lcc mrem RMiviVV. RMifhe fac r for ventilation vents or process vent release due 1
133, tritium, and from all particulate-form
'di)uclides with half-lives greater than 8 days, in mrem/yr
/
'~urie/sec. Factors are listed in Critical Organ Dose Factors Sttachment 8)
=
the release for ventilation vents or process vent of 1131, 1133,
=
tritium, and from all particulate-form radionuclides with half-lives greater than 8 days, in Curies
-08
=
the inverse of the number of seconds in a year
DOMINION VPAP-2103N REVISION 18 PAGE 29 OF 86 6.3.5 Gaseous Radwaste Treatment Historical data pertaining to the volumes and radioactive concentrations of gaseous effluents released in connection with specific Station functions, such as containment purges, shall be used to calculate projected doses, as appropriate.
- a. Requirement
- 1. The Gaseous Radwaste Treatment System and the Ventilation Exhaust Treatment System shall be used to reduce radioactive material in gaseous waste before its discharge, when projected gaseous effluent due to gaseous effluent releases, from each unit to areas at and be site undary, would exceed 0.2 mrad for gamma radiation and 0.4 b
iation, averaged over 31 days.
- 2. The Ventilation Exhaust Treatment S rn sham e sed to reduce radioactive materials in gaseous waste before' isc e
en the projected doses due to gaseous effluent releases, from it t eas at and beyond the site boundary, would exceed 0 ritical organ, averaged over 31 days.
- 3. Doses due to gaseou a
fro he site shall be projected at least once per 31 days, base n t C
ions in Step 6.3.5.c.
- b. Action If gaseous *ai*i'ex ds the limits in Step 6.3.5.a. is discharged without treatme l'rea#e a ubmit to the NRC within 30 days, a special report in acco c
VPAP-2802, Notifications and Reports, that includes:
n ex nation why gaseous radwaste was being discharged without treatment, cation of any inoperable equipment or subsystems, and the reason for the operability.
~2-.Actions taken to restore the inoperable equipment to operable status.
- 3. Summary description of actions taken to prevent recurrence.
- c. Projected Gamma Dose
- 1. Determine Dg, the 31-day gamma air dose for the previous 31-day period, per Equation (15).
- 2. Estimate Rg, the ratio of the estimated volume of gaseous effluent in the current 31-day period to the volume released during the previous 31-day period.
DOMINION VPAP-2103N REVISION 18 PAGE 30 OF 86
- 3.
Estimate Fg, the ratio of the estimated noble gas effluent activity in the current 31-day period to the noble gas effluent activity during the previous 31-day period (gCi/ml).
- 4. Determine PDg, the projected 31-day gamma air dose.
PDg = Dg(R x F)
(18)
- d. Projected Beta Dose
- 1. Determine Db, the 31-day beta air dose in thep ous d
per Equation (16).
- 2. Estimate Rg and Fg as in Steps 6.3.5.c..n
- 3. Determine PDb, the projected 31
, b e.
Dg)
(19)
- e. Projected Maximunt ~x og mber of the Public Dose
- 1. Deterrine D
-day maximum exposed member of the public dose in the previou y
I d, per Equation (14), where Dr Dmax.
- 2. Est*
tt of the estimated activity from 1131, 1133, radioactive I
n
/particulate form with half-lives greater than 8 days, and tritium in t,*he ch n* 1-day period to the activity of 1131, 1133, radioactive materials in Ric te form with half-lives greater than 8 days, and tritium in the previous
-- ay period (gCi/ml).
etermine PDmax, the projected 31-day maximum exposed member of the public dose.
PDmax = Dmax(Rg x Fi)
(20)
DOMINION VPAP-2103N REVISION 18 PAGE 31 OF 86 6.4 Radioactive Liquid and Gaseous Release Permits RP shall maintain procedures for Liquid and Gaseous Release Permits to ensure effluent dose limits are not exceeded when making releases.
6.4.1 Liquid Waste Batch Release Permits Operations shall obtain RP authorization before initiating batch releases of radioactive liquids. Examples of batch releases include:
Batch Releases NOTE: If the clarifier is in service, releases from tanks proce:
considered continuous releases.
A Batch Release Permit is required for romm (or potentially contain) radioactive liquia. an
" BRTT
" LLWDT are contain
- HLWDT
- Turbine Bi
- CDT coolant activity exceeds 1.0 E-5 pCi/mi
ýfore initiating continuous releases of 6.4.2 Release Permit is required for:
- Clarifier, unless being bypassed
" Steam generator blowdown when clarifier is bypassed
" Containment mat sumps and service water reservoir when clarifier is bypassed.
Sampling requirements and control and conditions for service water reservoir blowdown, when no radioactivity is detected, shall be specified on the permit.
DOMINION VPAP-2103N REVISION 18 PAGE 32 OF 86 6.4.3 Waste Gas Decay Tank (WGDT) Release Permit Operations shall obtain RP authorization before initiating WGDT releases.
6.4.4 Reactor Containment Release Permits Operations shall obtain authorization from RP before initiating containment purges or containment hogging. Reactor Containment Release Permits shall be valid from start of purge/hog until:
- Routine termination
" Terminated for cause by RP
" Receipt of Radiation Monitoring System (RMS) onitor high alarm 6.4.5 Miscellaneous Gaseous Release Permit KITNV Operations shall obtain RP authorizatiz e g releases of noble gases that may not be accounted for by routine, oy0 y planned release not being routed through the Process Vent or Ve ati
.g., steam driven auxiliary feedwater pump testing if primary to s a
ge exists).
6.4.6 Radioactive Liquid
,lease Controls
- a. Operations sha ti YU pending releases and request RP to initiate the appropriate er Operations shall provide the necessary information to comple *,,,uir lease permit.
- b. A rep
,a e sample shall be obtained of the source to be released.
I
. era ns shall provide RP with liquid samples and sample information (e.g.,
sample) for samples obtained outside the Primary Sample Room, except arifier Proportional Tank and Clarifier Grab Samples.
- 2. Chemistry shall provide RP with liquid samples and sample information for samples obtained from inside the Primary Sample Room.
- 3. RP shall obtain gaseous samples.
- c. RP shall perform required sample analyses.
DOMINION VPAP-2103N REVISION 18 PAGE 33 OF 86
- d. RP shall calculate and record the following information on a release permit:
" Maximum authorized release rate
- Maximum authorized release rate in percentage of limits specified by the ODCM
- Applicable conditions or controls pertaining to the release
- e. RP shall notify the Shift Supervisor if it is determined that a release may not be within the effluent dose limits.
- f. Upon receipt of a release permit from RP, Operations shal
- 1. Verify the correct source is authorized for release
- 2. Note maximum authorized release rate.
- 3. Note percent of Technical Specificatio" se represents.
- 4. Note and ensure compliance with i
aei ntrols or conditions applicable to the release.
- g. When commencing release, 0
'o rovide RP with required information.
As appropriate, required n
11 include:
" Date and time relea rte
" Starting tank/s
" Beginning p
" Releas t
" Dil r flow rate
- h.
ter ating the release, Operations shall return the permit to RP and provide fo necessary for completion of permit. As appropriate, required ainshall include:
ate and time release was stopped
- Tank/sump ending level
- Release flow rate just prior to termination
- Ending pressure
- Volume released
DOMINION VPAP-2103N REVISION 18 PAGE 34 OF 86 6.5 Total Dose Limit to Public From Uranium Fuel Cycle Sources 6.5.1 Requirement The annual (calendar year) dose or dose commitment to a real individual due to releases of radioactivity and radiation from uranium fuel cycle sources shall not exceed 25 mrem to the total body or the critical organ (except the thyroid, which shall not exceed 75 mrem).
6.5.2 Action
- a. If the calculated doses from release of radioactive materijin d or gaseous effluents exceed twice the limits in Steps 6.2.3.a., 6.
a.* 6.3.).., calculate (including direct radiation contribution from the s a fr' tside storage tanks) whether limits in Step 6.5.1 have been
- b. If the limits in Step 6.5.1 have been excee prep I submit to the NRC within 30 days, a special report in ac a c t
PAP-2802, Notifications and Reports, that defines the corrective a b
en to reduce subsequent releases and to prevent recurrence, an c
dule for achieving conformance with the limits. Special reports d
10 CFR 20.2203(a)(4), shall include:
- 1. An analysis that m
radiation exposure (dose) to a real individual from uraniu el c sources, including all effluent pathways and direct radiation, ale year that includes the releases covered by the report.
- 2. A d ip*t' o
evels of radiation and concentrations of radioactive
- SlVOlved, and the cause of the exposure levels or concentrations.
fte ated dose exceeds the limits in Step 6.5.1, and if the release n n that violates 40 CFR 190 has not already been corrected, the special Sport shall include a request for a variance in accordance with the provisions of 0 CFR 190. Submittal of the report is considered a timely request, and a variance is granted until staff action on the request is complete.
6.6 Radiological Environmental Monitoring 6.6.1 Monitoring Program
- a. Requirement
- 1. The Radiological Environmental Monitoring Program shall be conducted as specified in Radiological Environmental Monitoring Program (Attachment 9).
DOMINION VPAP-2103N REVISION 18 PAGE 35 OF 86
- 2. Samples shall be collected from specific locations specified in Environmental Sampling Locations (Attachment 10). [Reference 3.1.31]
- 3. Samples shall be analyzed in accordance with:
- Radiological Environmental Monitoring Program (Attachment 9) requirements
- Detection capabilities required by Detection Capabilities for Environmental Sample Analysis (Attachment 11)
- Guidance of the Radiological Assessment Branch T Position on Environmental Monitoring dated November, 19 visio.
1
- b. Action
- 1. If the Radiological Environmental Moni s not being conducted as required in Step 6.6.1.a., report the tion i cc rdance with VPAP-2802, Notifications and Reports, by pr**e a
a tting to the NRC, in the Annual Radiological Environm per 'ng Report required by Technical Specifications 5.6.2, a des isons for not conducting the program as required, and the n
- ing recurrence.
- 2. If, when averaged r
ar quarter, radioactivity exceeds the reporting levels of Re n
Ifor Radioactivity Concentrations in Environmental Samples c
ent? prepare and submit to the NRC within 30 days, a sp dance with VPAP-2802, Notifications and Reports, that:
e the causes for exceeding the limits, and e
corrective actions to be taken to reduce radioactive effluents so that* potential annual dose to a member of the public is less than the dar year limits of Steps 6.2.3, 6.3.3, and 6.3.4
___hen more than one of the radionuclides listed in Reporting Levels for Radioactivity Concentrations in Environmental Samples (Attachment 12) are detected in the sampling medium, the report shall be submitted if:
concentration (1) + concentration (2) +.
1.0 (21) reporting level (1) reporting level (2)
DOMINION VPAP-2103N REVISION 18 PAGE 36 OF 86
- 3. When radionuclides other than those listed in Reporting Levels for Radioactivity Concentrations in Environmental Samples (Attachment 12) are detected and are the result of plant effluents, the report shall be submitted if the potential annual dose to a member of the public is equal to or greater than the calendar year limits of Steps 6.2.3, 6.3.3, and 6.3.4. The report is not required if the measured level of radioactivity was not the result of plant effluents; however, in such an event, report and describe the condition in the Annual Radiological Environmental Operating Report in accord with VPAP-2802, Notifications and Reports.
- 4. If milk or fresh leafy vegetable samples are una b
e or more of the sample locations required by Environmental
.g jpcations (Attachment 10), identify locations for obtaining re s
es and add them to the radiological environmental monito g
ra ithin 30 days. The specific locations from which samples,
s ai may then be deleted from the monitoring program. Ide e'~
se e unavailability of samples and identify the new location:
rplacement samples in the next Annual Radioactive Effluen a-e in accordance with VPAP-2802,.
Notifications and 0t de in the report a revised figure and table for the ODCM to re t the locations.
6.6.2 Land Use Ce
- a. Requir nt A Ia s sus shall be conducted and shall identify, within a distance of 8 km
( iles), e ation in each of the 16 meteorological sectors of the following:
N ilk animal rest residence arest garden greater than 50 m2 (500 ft2) that produces broad leaf vegetation
- 1. The land use census shall be conducted during the growing season, at least once per 12 months, using methods that will provide the best results (e.g., door-to-door survey, aerial survey, local agriculture authorities). Land use census results shall be included in the Annual Radiological Environmental Operating Report in accordance with VPAP-2802, Notifications and Reports.
DOMINION VPAP-2103N REVISION 18 PAGE 37 OF 86
- 2. In-lieu of the garden census, broad leaf vegetation sampling of at least three different kinds of vegetation may be performed at the site boundary in each of two different direction sectors with the highest predicted ground deposition (D/Qs). Specifications for broad leaf vegetation sampling in Radiological Environmental Monitoring Program (Attachment 9) shall be followed, including analysis of control samples.
- b. Action
- 1. If a land use census identifies locations that yield a c ose or dose commitment greater than the values currently be*i p*late )n 6.3.4.a.2, identify the new locations in the next Annualr.
io iv uent Release Report in accordance with VPAP-2802, N Reports.
- 2. If a land use census identifies locatio at yie Ia lculated dose or dose commitment (via the same expos path
)
percent greater than at a location from which samples ar
- l ng obtained, add the new locations to the Radiologi vir al 61Monitoring Program within 30 days. Sampling locations, dr the control station location, that have the lowest calculated o0 0itments (via the same exposure pathway) may be delete o0 ring program. Identify new locations in the next Annual RaC'act E' lent Release Report and include in the report revised figures
',(<'s re ting the new locations in accordance with VPAP-2802, Not* ati an eports. [Reference 3.1.33]
6.6.3 Interlab ri o Program
- a.
ire t
a e materials (which contain nuclides produced at the Station), supplied as f an Interlaboratory Comparison Program, shall be analyzed.
DOMINION VPAP-2 103N REVISION 18 PAGE 38 OF 86
- b. Action
- 1. Analyses shall be performed at least semiannually as follows:
Program Cross-Check of Milk 1131, Gamma, Sr89 and Sr 90 Water Gross Beta, Gamma, 1131, H3 (Tritium), Sr89 and Sr 90 (blind - any combinations of above radionuclides)
Air Filter Gross Beta, Gamma, Sr 90
- 2. If analyses are not performed as required by
.3.
r port in the Annual Radiological Environmental Operating nce with VPAP-2802.
Notifications and Reports, the corre i aken to prevent recurrence.
- c. Results Results shall be reported in the u
a'gical Environmental Monitoring Report in accordance with VI 5
tifications and Reports.
6.7 Reporting Requirements 6.7.1 Annual Radiologicn* n men aI Operating Report Routine Radiolo*I iron ntal Operating Reports covering the operation of the units during v4 ndar year shall be submitted prior to May 1 of each year.
A single "t*
may e made for the Station. Radiological Environmental Operatin*,
shall include:
l au*
- i nterpretations, and analysis of trends of results of radiological ionmental surveillance activities for the report period, including:
omparison (as appropriate) with preoperational studies, operational controls, and previous environmental surveillance reports
" An assessment of the observed impacts of the plant operation on the environment
" Results of land use census per Step 6.6.2
DOMINION VPAP-2103N REVISION 18 PAGE 39 OF 86
- b. Results of analysis of radiological environmental samples and of environmental radiation measurements taken per Step 6.6.1, Monitoring Program. Results shall be summarized and tabulated in the format of the table in the Radiological Assessment Branch Technical Position on Environmental Monitoring.
- 1. If some individual results are not available for inclusion with the report, the report shall be submitted, noting and explaining reasons for missing results.
- 2. Missing data shall be submitted in a supplementary report as soon as possible.
- c. A summary description of the radiological environmen onit g program.
- d. At least two legible maps covering sampling locaI table giving distances and directions from the centerline of one or.
e map shall cover stations near the site boundary; a second s i
e distant stations.
- e. Results of Station participation in the rl at Comparison Program, per Step 6.6.3.
- f. Discussion of deviations fronetavironmental sampling schedule per Radiological Environme ori Program (Attachment 9).
- g. Discussion of analys n
lower limit of detection (LLD) required by Detection Capabl es ?
nvironmental Sample Analysis (Attachment 11) was not achievable.
- h. Any sa r"eIt any groundwater wells described in the environmental prog N(lver the results were required by the environmental program or not.
6.7.2 A I Ra
- i]ve Effluent Release Report ent
- Station a active Effluent Release Reports covering operation of the units during the oius 12 months of operation shall be submitted before May 1 of each year. A single submittal may be made for the Station and should combine those sections that are common to both units. Radioactive Effluent Release Reports shall include:
- 1. A summary of quantities of radioactive liquid and gaseous effluents and solid waste released. Data shall be summarized on a quarterly basis following the format of Regulatory Guide 1.21, Appendix B, for liquid and gaseous effluents.
Data shall be summarized on an annual basis following the format of Regulatory Guide 1.21, Appendix B, for solid waste. [Reference 3.1.34]
DOMINION VPAP-2103N REVISION 18 PAGE 40 OF 86
- 2. An assessment of radiation doses to the maximum exposed members of the public due to the radioactive liquid and gaseous effluents released from the Station during the previous calendar year. This assessment shall be in accordance with Step 6.7.2.b.
- 3. A list and description of unplanned releases from the site to unrestricted areas, during the reporting period, which meet the following criteria:
- Unplanned releases that exceeded the limits in Steps 6.2.1 and 6.3.1
- Unplanned releases which require a Condition Re and' olve the discharge of contents of the wrong Waste Gas ay k
e wrong liquid radwaste release tank
- Unplanned releases from large leaks toed valve or pipe failures that result in a quantity of release c
t a CFR 50.72, Immediate Notification Requirements fo er 9g ear Power Reactors or 10 CFR
~~?ort 50.73, Licensee Event R S
is required
- Unplanned releases d
in by Radiation Protection Supervision, which may or no qu ondition Report
- 4. Major chan o r tive liquid, gaseous, and solid waste treatment systems during the g iod.
- 5. Cha s t P
03N, Offsite Dose Calculation Manual (North Anna)
.7.4).
liti o new locations for dose calculations or environmental monitoring i7 ed by the land use census (See Step 6.6.2).
- 7.
summary of radioactive leaks or spills meeting the following criteria:
" An unintended spill or leak with the potential to reach groundwater, as defined in NEI 07-07, and
" The spill or leak must be greater than 100 gallons in volume or the volume cannot be quantified but is estimated to be greater than 100 gallons; or
" Any spill or leak, regardless of volume or activity deemed by the licensee to be reportable.
DOMINION VPAP-2103N REVISION 18 PAGE 41 OF 86
- 8. Any groundwater sample results from locations not part of the Radiological Environmental Monitoring Program.
- b. Dose Assessment
- 1. Radiation dose to individuals due to radioactive liquid and gaseous effluents from the Station during the previous calendar year shall either be calculated in accordance with this procedure or in accordance with Regulatory Guide 1.109.
Population doses shall not be included in dose assessments.
- 2. The dose to the maximum exposed member of the liquid and gaseous effluents from the Station shall assessment performed above. If the dose to the public exceeds twice the limits of 6.2.31 the dose assessment shall include the tbu*h NOTE: NUREG-0543 states: "There is reaso e
ran that operating reactors that have relea it dix I d also in conformance with the E'4uel Cycle S
- 3. Meteorological c it*
'g the previous calc radioactive d with the dose ed member of direct radiation.
sites with up to four esign objective values are tandard, 40 CFR Part 190."
endar year or historical dispersion conditions shall be used to determine gaseous
DOMINION VPAP-2103N REVISION 18 PAGE 42 OF 86 NOTE: The Annual Radioactive Effluent Report for the North Anna ISFSI is included as part of the North Anna Station Annual Radioactive Effluent Release Report.
- c. ISFSI Dose Assessment
" Radiation dose to individuals due to radioactive liquid and gaseous effluents during the previous calendar year shall either be calculated in accordance with this procedure or in accordance with Regulatory Guide opulation doses shall not be included in dose assessments.
S The dose to the maximum exposed member of t b1* d dioactive liquid and gaseous effluents from the Station shall b
- or with the dose assessment performed above. If the dose e
exposed member of the public exceeds twice the limits of 6..a.
.2.3 6.3.3.a.1, or 6.3.4.a.1, the dose assessment shall include thentr*tio m direct radiation.
" Meteorological conditions d~
th s calendar year or historical annual average atmospheric disper Ioxr1ios shall be used to determine gaseous pathway doses.
6.7.3 Annual Meteorolo
- lDur,
- a. Meteorologica t
lec during the previous year shall be in the form of joint frequenc wind speed, wind direction, and atmospheric stability.
- b. Mete data shall be retained in a file on site and shall be made available to Cup st.
6.7.4 /,:k DCM to the ODCM shall be:
- a.
viewed and approved by Facility Safety Review Committee (FSRC) and Site Vice President before implementation.
- b. Documented. Records of reviews shall be retained as Station records.
Documentation shall include:
- 1. Sufficient information to support changes, together with appropriate analyses or evaluations justifying changes.
DOMINION VPAP-2103N REVISION 18 PAGE 43 OF 86
- 2. A determination that a change will not adversely impact the accuracy or reliability of effluent doses or setpoint calculations, and will maintain the level of radioactive effluent control required by:
- 10 CFR 20 Subpart D
- 40 CFR 190
- c. Submitted to NRC in the form of a complete, legible cop tire ODCM as a part of, or concurrent with the Annual Radioactive E
-,lea Report for the period of the report in which any change was mad c
a all be identified by markings in the margin of the affected pa i
ating the area of the page that was changed, and shall indicate t a tenth/year) the change was implemented.w7
- d. Submitted to NRC in accordance w'2.,
Notifications and Reports.
6.7.5 Groundwater Protection Initi v
e 3.1.35]
- a. Notifications and Repo
- 1. Informal commu t
e made to state/local/NRC officials by the end of the next b ess for:
" Any si g the requirements of Step 6.7.2.a.7.
" An.
o0 ample result exceeding the reporting levels of Reporting Radioactivity Concentrations in Environmental Samples t 12).
~yr 0-.
report shall be submitted to the NRC and a copy concurrently Srwarded to state and local officials for any groundwater sampling result, hether on site or off site, exceeding the reporting levels of Reporting Levels for Radioactivity Concentrations in Environmental Samples (Attachment 12) and having the potential to reach groundwater that is or could be used as a source of drinking water. A 30-day report is only required on the initial discovery of a contaminated groundwater plume.
- b. Any spill or leak for which an informal notification is made in accordance with Step 6.7.5.a. shall be summarized in the Annual Radioactive Effluent Report.
DOMINION VPAP-2103N REVISION 18 PAGE 44 OF 86
- c. Any groundwater sample result from a groundwater source that is not part of the radiological environmental monitoring program shall be included in the Annual Radioactive Effluent Report.
- d. Any groundwater sample result from any groundwater well described in the radiological environmental monitoring program shall be included in the Annual Radiological Environmental Operating Report.
7.0 RECORDS 7.1 The following record(s) completed as a result of this procedure are uired be transmitted to Nuclear Document Management (DNM). The records have n id and retention requirements established for the Nuclear Records Retention e
S) per RM-AA-100, Record Creation, Transmittal and Retrieval.
Quality Assurance Records
" Records of changes to the ODCM in h
6.7.4
" Records of meteorological data in acc anc
!,Aq p 6.7.3 Records of sampling and analyses
" Records of radioactive materi n
uents released to the environment
- Records of preventive m n c urveillances, and calibrations 7.2 The following item(s) d a esult of this procedure are NOT records and are NOT required to be tran
'tte N
ar Document Management (DNM).
None
DOMINION VPAP-2103N REVISION 18 PAGE 45 OF 86 ATTACHMENT 1 (Page 1 of 2)
Radioactive Liquid Effluent Monitoring Instrumentation Instrument Minimum Operable Action Channels
- 1. Liquid Radwaste Effluent (a) 1-LW-RM-1 11, Liquid Radwaste Effluent Monitor I
(b) 1-LW-FT-104, Liquid Radwaste Effluent Total Flow Measuring 2
Device (c) 1-LW-TK-20, Liquid Waste Effluent Sample Vessel 1
(d) 1-LW-1130, Liquid Waste Effluent Proportional leV (e) 1-SW-RM-I108, Service Water Effluent M ote 2) 1 (f) 1-SW-RM-130, Unit I Circulating e -ste Effluent Line 3
Monitor c:)__..7M (g) 2-SW-RM-230, Unit 2 Circ ti ater -;stem Effluent Line 3
Monitor
- 2. Steam Generator Hi a i owdown (a) Steam Generatty Blowdown Radiation Monitor Unit 1 1-12 1
Unit 1
1 (b) Stea er r High Capacity Blowdown Flash Tank Outlet Flow Rate Unit 1 1-BD-FT-105 1
2 Unit 2 2-BD-FT-205 1
2 (c) Steam Generator High Capacity Blowdown Proportional Sampling System Collection Tank Unit 1 1-BD-TK-4 1
Unit 2 2-BD-TK-4 I
DOMINION VPAP-2103N REVISION 18 PAGE 46 OF 86 ATTACHMENT 1 (Page 2 of 2)
Radioactive Liquid Effluent Monitoring Instrumentation ACTION 1:
If the number of operable channels is less than required, effluent releases via this pathway may continue if, at least once within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />, grab samples are collected and analyzed for gross radioactivity (beta and gamma) at an LLD of at least I x 10-7 JCi/g or an isotopic radioactivity at an LLD of at least 5x10-7 ptCi/g.
ACTION 2:
If the number of operable channels is less than required, e tre es via this pathway may continue if the flow rate is estimated at le on er ours during actual releases. Design capacity performance curves er d^in may be used to estimate flow.
ACTION 3:
If the number of operable channels is less tJ uire ake repairs as soon as possible. Effluent releases via this path m
c it e provided that, at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />, grab samples from the c/
are collected and analyzed for principal gamma emitters as defi i
I five Liquid Waste Sampling and Analysis Program (Attachm NOTE 1:
The capability for obtainint least every 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> must exist. Grab samples shall commence if ther in c of radioactivity in the Service Water System or an indication from other r" i n
initors in the Service Water System of an increase in radioactivity.
NOTE 2:
To utilize 1-i -
08 as the effluent radiation monitor for the associated loop, 0-PT-75 (I-R
-108 Flow Verification) must be performed prior to placing the loop in sp_.Ve monitoring is not required when discharge flowpath is not in service.
DOMINION VPAP-2103N REVISION 18 PAGE 47 OF 86 ATTACHMENT 2 (Page 1 of 2)
Radioactive Liquid Effluent Monitoring Instrumentation Surveillance Requirements Channel Description Channel Source Channel Channel Check Check Calibration Operational Test
- 1. Liquid Radwaste Effluent (a)
I-LW-RM-1 11, Liquid Radwaste Effluent Monitor D
D Q (NOTE 1)
(b) 1-LW-FT-104, Liquid Radwaste Effluent Total Flow D (NOTE 3)(
R Q
Measuring Device (c) I-LW-TK-20, Liquid Waste Effluent Sample Vessel D (
- 4)
N N/A N/A (d) 1-LW-i130, Liquid Waste Effluent Proportional Sam<
OT N/A N/A N/A Valve<
(e) 1-SW-RM-108, SW Effluent Monitor (NO E D
M R
Q (NOTE 2)
(f) 1-SW-RM-130, Unit 1 Circul
- i.
em DN Effluent Line Monitori Circ//l i D
R Q (NOTE 2)
(g) 2-SW-RM-230, Unit 2 C i
g ter System D
M R
Q (NOTE 2)
"Effluent Line Monitor()A "N
- 2.
Steam Generator (S ig pacity Blowdown (a) SG Higv a'Bo wn Radiation Monitor Unit S-I-125 Q (NOTE 6)
Unit 2
-225 D (NOTE 7) D (NOTE 8)
R R (NOTE 5)
(b) SG High Capacity Blowdown Flash Tank Outlet Flow Rate Unit 1 1-BD-FT-105 D (NOTE 8)
N/A R
N/A Unit 2 2-BD-FT-205 (c) SG High Capacity Blowdown Proportional Sampling System Collection Tank Unit 1 1-BD-TK-4 D (NOTE 4)
N/A N/A N/A Unit 2 2-BD-TK-4
DOMINION VPAP-2103N REVISION 18 PAGE 48 OF 86 ATTACHMENT 2 (Page 2 of 2)
Radioactive Liquid Effluent Monitoring Instrumentation Surveillance Requirements NOTE 1:
The Channel Operational Test shall demonstrate:
- a. Automatic isolation of this pathway and Control Room alarm annunciation occur if the instrument indicates measured levels above alarm/trip setpoint.
- b. Alarm annunciation occurs if the instrument controls are not s "operate" mode.
NOTE 2:
The Channel Operational Test shall demonstrate that Control
,alar nnunciation occurs if any of the following conditions exists:
- a. Instrument indicates measured levels above the ale t.
- b. Instrument controls not set in "operate" mod.
NOTE 3:
Channel Check shall consist of verifying i ti;doo uring periods of release.
Channel Check shall be made at least op i
ND Sr-90 N D ND Y-91 ND ND Zr-95 ND ND Nb-95 ND ND Ru-103 )ND ND Ru ND ND A 2 ND ND Te-12 5.37E+6 3.48E+6 Te-129m 4.61E+6 2.98E+6 1-131 8.08E+8 5.23E+8 1-133 1.38E+7 8.93E+6 Cs-134 ND ND Cs-136 ND ND Cs-137 ND ND Ba-140 ND ND Ce-141 ND ND DOMINION VPAP-2103N REVISION 18 PAGE 66 OF 86 ATTACHMENT 8 (Page 2 of 2) Critical Organ Dose Factors DOMINION VPAP-2103N REVISION 18 PAGE 67 OF 86 ATTACHMENT 9 (Page I of 5) Radiological Environmental Monitoring Program Exposure Pathway Number of Sample and Collection Ilype and Frequency of and/or Sample Sample Location (NOTE 2) Frequency Analysis
- 1. DIREC7I RADIATION (NOTE 3) 36 routine monitoring stations, either with two or more dosimeters or with one instrument for measuring and recording dose rate continuously, to be placed as follows:
- 1) An inner ring of stations, one in each emergency GAMMA DOSE meteorological s t within the sit ary
- 2) An outer ri ff 7
stations ei ch emer rgo6c y/ r iXcay ctor Quarterly Quarterly thi? P, ge from ~4e Th.alance of the tio is to be placed in cial interest areas such as population centers, nearby residences, schools, and in 1 or 2 areas to serve as control stations DOMINION VPAP-2103N REVISION 18 PAGE 68 OF 86 ATTACHMENT 9 (Page 2 of 5) Radiological Environmental Monitoring Program Exposure Pathway Number of Sample and Collection Type and V'requency of and/or Sample Sample Location (NOTE 2) Frequency Analysis '2. AIRBlOR{NE Samples from 5 locations: a) 3 samples from close to the 3 site boundary 0 locations (in different sectors) of the highest 1 eanister calculated historical A i ekly annual average ground Conti Radioiodines and level D/Q sa*
- wer Particulates b) 1 sample from the ra)
W* vicinity of a communiatw (co1,1tion Particulate Sampler having the highest Gross beta radioactivity calculated annu cc analysis following filter average grou e change; (NOTE 4) D/Q 5z_'*/.-. c) 1 samp om ntrol Gamma isotopic analy-locati I, sis of composite (by dta~lu in.. east location) quarterly /_ev )nt direction (NOTE 5)
- 3. WAIER13ORNE S
I om 3 locations: x) ample upstream Gamma isotopic analysis monthly; (NOTE 5) a) Surfa b I sample downstream Grab Monthly mo ste fOr ti Composite for tritium c) 1 sample from cooling analysis quarterly lagoon Sample from I or 2 sources Gy Gamma isotopic and tritium b) Ground only if likely to be affected Grab Quarterly analysis quarterly (NOTE onlyif ikey tobe ffeted5) 1 sample from downstream Gamma isotopic analysis c) Sediment area with existing or Semi-Annually semi-annually (NOTE 5) potential recreational value DOMINION VPAP-2103N REVISION 18 PAGE 69 OF 86 ATTACHMENT 9 (Page 3 of 5) Radiological Environmental Monitoring Program and/or Sample Sample Location (NOTE 2) .4.
- 4. INUL
- tI_,
IUIN a) Milk (NOTE 7) a) Samples from milking animals in 3 locations within 5 km that have the highest potential. If there are none, then 1 sample from milking animals in each of 3 areas between 5 to 8 km where doses are calculated to be greater than 1 mrem per yr (NOTE 6) b) 1 sample from milkin* animals at a control I (15-30 km in the prevalent win re=r ). "0dnmma isotopic (NOTE 5) and 1131 analysis monthly a) I sawe recre; b) Fish and Invertebrates >h'f catfish) discharge a~nmma isotonic on edible Semiannually I po-rions of same species in influenced by plant e c) Food Products 'Zý,ples of an edible broad leaf vegetation grown nearest each of two different offsite locations of highest predicted historical annual average ground level D/Q if milk sampling is not performed b) 1 sample of broad leaf vegetation grown 15-30 km in the least prevalent wind direction if milk sampling is not performed Monthly if available, or at harvest Gamma isotopic (NOTE 5) and 1131 analysis DOMINION VPAP-2103N REVISION 18 PAGE 70 OF 86 ATTACHMENT 9 (Page 4 of 5) Radiological Environmental Monitoring Program NOTE 1: The number, media, frequency, and location of samples may vary from site to site. This table presents an acceptable minimum program for a site at which each entry is applicable. Local site characteristics must be examined to determine if pathways not covered by this table may significantly contribute to an individual's dose and be included in the sampling program. NOTE 2: For each and every sample location in Environmental Sampli ttachment 10), specific parameters of distance and direction sector fro c rli the reactor, and additional description where pertinent, shall be provi n ac nt 10. Refer to Radiological Assessment Branch Technical Positi and G-0 133, Preparation of Radiological Effluent Technical Specificatiol or ea ower Plant. Deviations are permitted from the required sampling sche e pec\\ ns are unattainable due to hazardous conditions, seasonal unavaJ yty tion of automatic sampling equipment and other legitimate reaso
- p mens are unattainable due to sampling equipment malfunction, every o
al ade to complete corrective action before the end of the nexi sampling ions from the sampling schedule shall be 'documented in ihe An R io cal Environmental Operating Report pursuant to Step 6.7.1. It is recy ./ at times, it may not be possible or practicable to continue to obtain sampi of t me of choice at the most desired location or time. In these instances, su lemative media and locations may be chosen for the particular pathway in quest and r° iate substitutions made within 30 days in the radiological en e toring program. In lieu of a Licensee Event Report and pursuant to St entify the cause of the unavailability of samples for that pathway and identify the ne tions for obtaining replacement samples in the next Annual Radioactive Effluent Release Report, and include revised figures and tables from the ODCM reflecting the new locations in the report. DOMINION VPAP-2103N REVISION 18 PAGE 71 OF 86 ATTACHMENT 9 (Page 5 of 5) Radiological Environmental Monitoring Program NOTE 3: One or more instruments, such as a pressurized ion chamber, for measuring and recording dose rate continuously may be used in place of, or in addition to, integrating dosimeters. For the purposes of this table, a thermoluminescent dosimeter (TLD) is considered to be one phosphor; two or more phosphors in a packet are considered as two or more dosimeters. Film badges shall not be used as dosimeters for measuring direct The 36 stations are not an absolute number. The number of direct radiatio n ng st.iions may be reduced according to geographical limitations, e.g., at anCante, sectors will be over water so that the number of dosimeters may be red c or i ly. The frequency of analysis or readout for TLD systems will depend n et ristics of the specific system used and should be selected to obtaind91m os formation with minimal fading. NOTE 4: Airborne particulate sample filters sh an or gross beta radioactivity 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> or more after sampling to allow for r oron daughter decay. If gross beta activity in air particulate samples is gj ran es the yearly mean of control samples, gamma isotopic analysis s INd on the individual samples. NOTE 5: Gamma isotopic anal is id'ification and quantification of gamma-emitting radionuclides tha b r ble to effluents from the facility. NOTE 6: The dose shal ated r the maximum organ and age group, using the methodology and parameter t DCM" NOTE 7: If mia mng not be performed, use item 4.c (Page 3 of 5, Radiological E
- ro btonitoring Program (Attachment 9)).
DOMINION VPAP-2103N REVISION 18 PAGE 72 OF 86 ATTACHMENT 10 (Page 1 of 4) Environmental Sampling Locations Distance and Direction From Unit No. 1 Nample Location Station Distance Direction Collection Remarks Media I I No. I (Miles) DIr n R aFrequencys Environmental TLDs ( NAPS Sewage Treatment Plant 01 0.20 NE Quarterly & Annually On-Site Frederick's Hall 02 5.30 SSW T Mineral,VA 03 7.10 WS Q rl Wares Crossroads 04 5.10 Route 752 05 4.20 NNE Fuarterly & ,....**Annually Sturgeon's Creek 05A 4V Quarterly & Marina Annually
Annually End of Route 685 /** 1.00 WNW Quarterly & Site Boundary ,___Annually Route 700 1.00 WSW Quarterly & Site Boundary Rout070,_ \\Annually "Aspen Hi 2 0.93 SSE Quarterly & Site Boundary _____Annually
- Orange, 24 22.00 NW Quarterly & Control Annually Bea Coo))g Towet N-1/33 0.06 N
Quarterly On-Site N-2/34 2.04 N Quarterly P** Lot "C" NNE-3/35 0.24 NNE Quarterly On-Site Good Hope Church NNE-4/36 3.77 NNE Quarterly Parking Lot "B" NE-5/37 0.20 NE Quarterly On-Site Bogg's Drive NE-6/38 1.46 NE Quarterly Weather Tower Fence ENE-7/39 0.36 ENE Quarterly On-Site Route 689 ENE-8/40 2.43 ENE Quarterly Near Training Facility E-9/41 0.30 E Quarterly On-Site "Morning Glory Hill" E-10/42 285 Eh Quarterly Island Dike ESE-11/4i .12 ESE I Quarterly 0n-Site Route 622 h= - 1 /-/44 4-l. /U
- L15, Q~uarterly
DOMINION VPAP-2103N REVISION 18 PAGE 73 OF 86 ATTACHMENT 10 (Page 2 of 4) Environmental Sampling Locations Distance and Direction From Unit No. 1 Sample Location Station Distance Collection Remarks Media No. (Miles) Direction Frequency tlnvironmental TLDs Biology Lab SE-13/45 0.64 SE Quarterly On-Site Route 701 SE-14/46 5.88 SE fua% (Dam Entrance) Ei5S ._S* Site "Aspen Hills" SSE-15/47 0.93 S Boundary Elk Creek SSE-16/48 2.33 rterly NAPS Access Road S-17/49 0.2/4 -\\N036-r uarterly On-Site Elk Creek Church S-18/50 Quarterly NAPS Access Road SSW-19/51 Quarterly On-Site Route 618 S S W-20 \\2. S SS W Quarterly 500KV Tower SW-2 53 SW Quarterly On-Site Route 700 4 .96 SW Quarterly NAPS Radio Tower 5 0.38 WSW Quarterly On-Site RSite -2t4/56 1.00 WSW Quarterly Boundary South Gate of -25/57 0.32 W Quarterly On-Site Switchy ardl/"-N P Route 6K N1/ W-26/58 1.55 W Quarterly EnddfRo** 6 WNW-27/59 1.00 WNW Quarterly Boundary zl te WNW-28/60 1.40 WNW Quarterly n e Noth NW-29/61 0.52 NW Quarterly On-Site LQ l nna Campground NW-30/62 2.54 NW Quarterly
- 1/#2 Intake NNW-31/63 0.07 NNW Quarterly On-Site Route 208 NNW-32/64 2.21 NNW Quarterly Bumpass Post Office C-1/2 7.30 SSE Quarterly Orange. VA C-3/4 22.00 NW Quarterly Control Mineral, VA C-5/6 7.10 WSW Quarterly_
Rev, 17 Louisa, VA C-7/8 11.54 WSW Quarterly Control DOMINION VPAP-2103N REVISION 18 PAGE 74 OF 86 ATTACHMENT 10 (Page 3 of 4) Environmental Sampling Locations Distance and Direction From Unit No. 1 Sample Location Station Distance D Collection Remarks Media No. (Miles) Frequency Airborne NAPS Sewage 01 0.20 NE Weekly On-Site Treatment Plant Particulate Biology Lab 01-A 0.64 SE Wee On-Site and Frederick's Hall 02 5.30 SSW ly Radioiodine Mineral, VA 03 7.10 WSW /,eWhN Wares Crossroads 04 5.10 WNW ) f Route 752 05 4.20 NNE - ee Sturgeon's Creek 05A 2.04 Marina 05A 20k Levy, VA 06 4.701*--* Weekly Bumpass, VA 07
- 7.
SS-Weekly End of Route 685 21 ON 0 Weekly Site Boundary Route 700 22 100 SW Weekly Site Boundary "Aspen Hills" .93----9.), SSE Weekly Site Boundary Orange, VA 1 4 NW Weekly Control Surtace Water Waste Heat Treatme [Reference Facility (Second 3.37 SSE Monthly 3.1.31] Cooling Lagoon) __,/__ North Anna* 09 (upstream 66 09A 12.9 WNW Monthly Control Bridge)( 0 \\J Noenna y 11 5.80 SE Monthly ,(ov eari4 Ciroundwater La.r (well water) La1A 0.64 SE Quarterly Aquatic W"W.Aeat Treatment Semi-Sediment Fac-i ity (Second 08 3.37 SSE Annually Sedient Cooling Lagoon) Anal North Anna River (upstream) Rt 669 09A 12.9 WNW Semi-Control Bridge (Brook's Annually Bridge) North Anna River 11 5.80 SE Semu-(downstream) Annually Shoreline Soil Lake Anna 08 3.37 SSE Semi-Annually Soil NAPS Sewage 01 0.20 NE Once per 3 yrs On-Site Treatment Plant DOMINION VPAP-2103N REVISION 18 PAGE 75 OF 86 ATTACHMENT 10 (Page 4 of 4) Environmental Sampling Locations Distance and Direction From Unit No. 1 Sample Location Station Distance Direction Collection Remarks Media No. (Miles) Frequency Soil Fredericks Hall 92 -53. -- S*W-Once per 3 yrs (continued) Mineral, VA 03 7.10 WSW Once per3,rs Wares Crossroads 04 5.10 WNW Once Route 752 05 4.20 NNE Oe 3 yrs) Sturgeon's Creek /a Marina Levy, VA 06 4.70 E Xek/yl yr, Bumpass, VA 07 7.30 cer 3 yr, End of Route 685 21 1.00 ce per 3 yrs Site Boundary Route 700 22 1.0 5 ( Once per 3 yrs Site Boundary "Aspen Hills" 23 Q3"3 88 Once per 3 yrs Site Boundary Orange, VA 24 2"2.. Once per 3 yrs Control Milk Lakeside Dairy 1.50 NW Monthly (Charles Harris) Waste Heat Treatment _1 zZ_ Fish Facility (Second 3.37 SSE Semi-Annually Cooling Lagoon)w " IN, Lake Orange/-,- < 16.50 NW Semi-Annually Control Food Products Stagecoac oad)) 4 varies NNE Monthly (Edible l if available, broadleaf Route 6 15 varies SE or at harvest vegetation') \\ e16 varies NW Control C 26 varies S "'sp./Hills" Area 23 1varies SSE
- a. If edible broa eaf vegetation is unavailable, non-edible vegetation of similar leaf characteristics may be substituted.
DOMINION VPAP-2103N REVISION 18 PAGE 76 OF 86 ATTACHMENT 11 (Page 1 of 2) Detection Capabilities for Environmental Sample Analysis LOWER LIMIT OF DETECTION (LLD) Airborne Fish Food Sediment Analysis Water Particulate Milk Products (pCig) (NOTE 2) (pCi/l) or Gases (pCiweg) (pCi/l) (pCi/kg) (dry) (pCi/m 3 ) (wet) Gross beta 4 0.01 H-3 2,000 Mn-54 15 130 Fe-59 30 260 Co-5860 15 Zn-65 30 20 z Zr-95 30 Nb-95 15 1-131 (NOTE 3) 1 0.07 6 Cs-134 15 0.05 15 60 150 Cs-137 18 \\16 150 18 80 180 Ba-140 60 60 La-140 15.,'/-))Y 15 NOTE 1: Required de ti. abilities for thermoluminescent dosimeters used for environmental measure ents in Regulatory Guide 4.13. NOTE 2: Thi b lot an that only these nuclides are to be detected and reported. Other peaks th (1 ta ura le and identifiable, together with the above nuclides, shall also be identi fd reported. NOTE 3: LLD for the ground (drinking) water samples. The LLD for the surface (non-drinking) water samples is 10 pCi/l. DOMINION VPAP-2103N REVISION 18 PAGE 77 OF 86 ATTACHMENT 11 (Page 2 of 2) Detection Capabilities for Environmental Sample Analysis LOWER LIMIT OF DETECTION (LLD) (NOTE 3) NOTE 1: For a particular measurement system (which may include radiochemical separation): 4.66 sb LLD = 4.6. b (25-1) E e V e 2.22E+06
- Y e
Where: LLD the "a priori" (before the fact) Lowe tion as defined above (as microcuries per unit mass or ume) ee"ubsection 4.9) Sb= the standard deviation of the b gr ing rate or of the counting rate of a blank samplei as.a (a nts per minute, cpm) E =the counting effici c nts per disintegration) V =the sample (i mass or volume) 2.22E+06 = the n er di egrations per minute (dpm) per microcurie Y = xochemical yield (when applicable) x t, adioactive decay constant for the particular radionuclide At t elapsed time between sample collection (or end of the sample ( ollection period) and time of counting (for environmental samples, not plant effluent samples) Typical values of E, V, Y and At should be used in the calculation. The LLD is an "a priori" (before the fact) limit representing the capability of a measurement system and not a "posteriori" (after the fact) limit for a particular measurement. DOMINION VPAP-2103N REVISION 18 PAGE 78 OF 86 ATTACHMENT 12 (Page 1 of 1) Reporting Levels for Radioactivity Concentrations in Environmental Samples Water Airborne Fish Milk Food Products Analysis (pCi/1) Particulate or Gases (pCi/m3) (pCi/kg, wet) (pCi/l) (pCi/kg, wet) (NOTE 1) H-3 20,000 Mn-54 1,000 30,000 Fe-59 400 10,000 Co-58 1,000 30,000 Co-60 300 1o o,\\ Zn-65 300 0.* Zr-Nb-95 400 1-131 2 1.9 100 Cs-134 30 60 1,000 Cs-137 50 70 2,000 Ba-La-140 200 300 NOTE 1: For drinking water NK2 DOMINION VPAP-2103N REVISION 18 PAGE 79 OF 86 ATTACHMENT 13 (Page 1 of 8) Meteorological, Liquid, and Gaseous Pathway Analysis 1.0 METEOROLOGICAL ANALYSIS 1.1 Purpose The purpose of the meteorological analysis was to determine the annual average X/Q and D/Q values at critical locations around the Station for ventilation vent (ground level) and process vent (mixed mode) releases. The annual average X/Q and D/Q valu ee d to perform a dose pathway analysis to determine both the maximum exposed i)pvl I at boundary and member of the public. The X/Q and D/Q values resulting in mn uN osures were incorporated into the dose factors in Gaseous Effluent D a s achment 5) and Critical Organ Dose Factors (Attachment 8). 1.2 Meteorological Data, Parameters, and Meth lo Onsite meteorological data for the period J 19, through December 31, 1981, were used in calculations. These data include i hind direction, and differential temperature for the purpose of dete ng-J.n quency distributions for those releases characterized as ground level (e..,- vent), and those characterized as mixed mode (i.e., process vent). The po/@ se characterized as ground level were based on AT158.9ft-28.2ft and 28.2 fo d , and the portions characterized as mixed mode were based on AT 15 8,9ft-) t wind data. X/Q's and D/Q' e culated using the NRC computer code "XOQDOQ - Program for the Meteor ical. u"ion of Routine Effluent Releases at Nuclear Power Stations," Septen) 19 code is based upon a straight line airflow model implementing the assum t 'htiied in Section C (excluding Cl a and C 1 b) of Regulatory Guide 1.111, "Method stimating Atmospheric Transport and Dispersion of Gaseous Effluents in Routine Releases from Light-Water-Cooled Reactors." The open terrain adjustment factors were applied to the X/Q values as recommended in Regulatory Guide 1.111. The site region is characterized by gently rolling terrain so open terrain correction factors were considered appropriate. The ground level ventilation vent release calculations included a building wake correction based on a 1516 m 2 containment minimum cross-sectional area. DOMINION VPAP-2103N REVISION 18 PAGE 80 OF 86 ATTACHMENT 13 (Page 2 of 8) Meteorological, Liquid, and Gaseous Pathway Analysis The effective release height used in mixed mode release calculations was based on a process vent release height of 157.5 ft, and plume rise due to momentum for a vent diameter of 3 in. with plume exit velocity of 100 ft/sec. Ventilation vent, and vent releases other than from the process vent, are considered ground level as specified in Regulatory Guide 1.111 for release points less than the height of adjacent solid structures. Terrain elevae obtained from North Anna Power Station Units 1 and 2, Virginia Electric andP o y Final Safety Analysis Report Table 1 C.2-8. V/Q and D/Q values were calculated for the nearest site ent, milk cow, and vegetable garden by sector for process vent and yen i lses at distances specified from North Anna Power Station Annual Environ ta ata for 1981. X/Q values were also calculated for the nearest lake shoreline b for process vent and ventilation vent releases. According to the definition for sho in G-0133, "Preparation of Radiological Effluent Technical Specification r Power Stations," October, 1978, some gaseous releases may fit this catego/rip waste gas decay tank releases and containment purges. However, these releases a51 e't-ong term for dose calculations as past releases were both random in tim a an tion as evidenced by reviewing past release reports. Therefore, the u a l average concentrations is appropriate according to NUREG-0133. The XJ/Q an val ca culated from 1981 meteorological data are comparable to the values presenenAthe nna Power Station UFSAR. 1.3 Results-- The X/Q value that resulted in the maximum total body, skin and inhalation exposure for ventilation vent releases was 9.3E-06 sec/m 3 at a site boundary location 1416 meters SE sector. For process vent releases, the site boundary X/Q value was 1.2E-06 sec/m 3 at a location 1513 meters S sector. The shoreline X/Q value that resulted in the maximum inhalation exposure for ventilation vent releases was 1.OE-04 sec/m 3 at a location 274 meters NNE sector. The shoreline XIQ value for process vent was 2.7E-06 sec/m 3 at a location 274 meters NNE sector. DOMINION VPAP-2103N REVISION 18 PAGE 81 OF 86 ATTACHMENT 13 (Page 3 of 8) Meteorological, Liquid, and Gaseous Pathway Analysis The original pathway analysis indicated that the maximum exposure from 1131, 1133, and from all radionuclides in particulate form with half-lives greater than 8 days was through the grass-cow-milk pathway. The D/Q value from ventilation vent releases resulting in the maximum exposure was 2.4E-09 per m2 at a location 3250 meters N sector. For process vent releases, the D/Q value was 1. 1E-09 per m2 at a location 3250 meters For tritium, the X/Q value from ventilation vent releases resulting in the maximu sure r the milk pathway was 7.2E-07 sec/m 3, and 3.9E-07 sec/m 3 for proces , nte a location 3250 meters N sector. Analysis using 2007 release data indicates that the miti organ is the child's thyroid. The location is 1593 meters SSE sector r leases, the D/Q is 1.1E-8. For tritium releases, the X/Q values at this loca e 9 -7 for the process vent and 3.3E-6 for the ventilation vents. 2.0 LIQUID PATHWAY ANALYS 2.1 Purpose The purpose of the liquid w an is was to determine the maximum exposed member of the public in unres i a) esult of radioactive liquid effluent releases. The analysis includes a determi on mos estrictive liquid pathway, most restrictive age group, and critical organ. Th' i 's is required for Subsection 6.2. 2.2 Data, P *n<* s, a Methodology Initial r tive liquid effluent release data for the years 1979, 1980, and 1981 were compile o e North Anna Power Station semi-annual effluent release reports. The data for each year, a ong with appropriate site specific parameters and default selected parameters, were entered into the NRC computer code LADTAP as described in NUREG-0133. DOMINION VPAP-2103N REVISION 18 PAGE 82 OF 86 ATTACHMENT 13 (Page 4 of 8) Meteorological, Liquid, and Gaseous Pathway Analysis Re-concentration of effluents using the small lake connected to larger water body model was selected with the appropriate parameters determined from Table 3.5.3.5, Design Data for Reservoir and Waste Heat Treatment Facility from Virginia Electric and Power Company, Applicant's Environmental Report Supplement, North Anna Power Station, Units 1 and 2, March 15, 1972. Dilution factors for aquatic foods, shoreline, and dter were set to one. Transit time calculations were based on average flow rates. I,'r p meters were defaults selected by the LADTAP computer code. Beginning in 1997, the activity by nuclide released in is entered into the North Anna Power Station liquid pathway critical o, c.alcu o s spreadsheet, which calculates the most limiting age group total bod, d iih an. This Process is repeated annually. 2.3 Results Initially, the fish pathway resulted' g
- e. The critical organ each year was the liver, and the adult and teenage age '
the same organ dose. However, since the adult total body dose was greate an e>t* total body dose for each year, the adult was selected as the most restrictive a . Be ning in 1997, the most limiting age group for both total body and critical or is cu from the spreadsheet for North Anna Power Station liquid pathway critical a culations. DOMINION VPAP-2103N REVISION 18 PAGE 83 OF 86 ATTACHMENT 13 (Page 5 of 8) Meteorological, Liquid, and Gaseous Pathway Analysis 3.0 GASEOUS PATHWAY ANALYSIS 3.1 Purpose A gaseous effluent pathway analysis was performed to determine the location that would result in the maximum doses due to noble gases for use in demonstrating com liance with Steps 6.3.l.a. and 6.3.3.a. The analysis also included a determinatio th tical pathway, location of maximum exposed member of the public, and the crf the maximum dose due to 1131, 1133, tritium, and for all radionuclides in pa l t0o*,th half-lives greater than 8 days for use in demonstrating compliance e s in Step 6.3.4.a. 1. In addition, the analysis included a determination of the ctai y, maximum age group, and sector location of an exposed individual thr the a on pathway from I 13, I1, tritium, and particulates with half-lives greate4,*'ay' demonstrate compliance with Step 6.3.1.a. 3.2 Data, Parameters, and Methodo Annual average XIQ values wer -cK described in Section 1 of this attachment, for the nearest site boundary in h ?i' t*onal sector and at other critical locations beyond the site boundary. The largest Yu determined to be 9.3E-06 sec/m 3 at site boundary for ventilation vent rele, 1416 meters SE direction, and 1.2E-06 sec/m 3 at site boundary for pr sreleases at a location 1513 meters S direction. The maximum doses to total bodyad sa*n
- ir doses for gamma and beta radiation due to noble gases, would be at the i
locations. The doses from both release points are summed in calcul on a ate total maximum dose. Step 6.3... d ose limits apply specifically to the inhalation pathway. Therefore, the locations and X/Q values determined for maximum noble gas doses can be used to determine the maximum dose from 113, 1133, tritium, and for all radionuclides in particulate form with half-lives greater than 8 days for the inhalation pathway. DOMINION VPAP-2103N REVISION 18 PAGE 84 OF 86 ATTACHMENT 13 (Page 6 of 8) Meteorological, Liquid, and Gaseous Pathway Analysis The NRC computer code GASPAR, "Evaluation of Atmospheric Releases," Revised 8/19/77, was run using 1979. 1980 and 1981 North Anna Power Station Gaseous Effluent Release Report data. Doses from i131, 1133, tritium, and particulates for the inhalation pathway were calculated using the 9.3E-06 sec/m 3 site boundary X/Q. Except for the source term data and the X/Q value, computer code default parameters were used. Results for indicated that the critical age group was the child and the critical organ was the for e inhalation pathway. The gamma and beta dose factors Kivv, Livv, Mivv, a I ,hrus Effluent Dose Factors (Attachment 5) were obtained by performin ts co rsion of the appropriate dose factors from Table B-I, Regulatory Guide 1.109
- v. >X* iyr per Ci/m3 or mrad/yr per Ci/m 3, and multiplying by the ventilation vents nd value of 9.3E-06 sec/m 3.The same approach was used in calculating t a
eta dose factors Kipv, Lipv, Mipv, and Nipv in Gaseous Effluent Dose Facto .A't t 5) using the process vent site boundary X/Q value of 1.2E-06 sec/m 3. The inhalation pathway do ct rs, and Pipv in Gaseous Effluent Dose Factors (Attachment 5) were calcu "ihe following equation: DFA (x/Q) (mrem/yr per Curie/sec) (29-1) where: K' of unit conversion, 1E+12 pCi/Ci BR h eathing rate of the child age group, 3700 m3/yr, from Table E-5, Regulatory il fde 1. 109, Rev.lI DFAi = the thyroid organ inhalation dose factor for child age group for the ith radionuclide, in mremlpCi, from Table E-9, Regulatory Guide 1.109, Rev. 1 X/Q = the ventilation vent site boundary X/Q, 9.3E-06 sec/m 3, or the process vent site boundary X/Q, 1.2E-06 sec/m 3, as appropriate DOMINION VPAP-2103N REVISION 18 PAGE 85 OF 86 ATTACHMENT 13 (Page 7 of 8) Meteorological, Liquid, and Gaseous Pathway Analysis Step 6.3.4.a., requires that the dose to the maximum exposed member of the public from 1131, 1133, tritium, and from all radionuclides in particulate form with half-lives greater than 8 days be less than or equal to the specified limits. Dose calculations were performed for an exposed member of the public within site boundary unrestricted areas, and to an exposed member of the public beyond site boundary at locations identified in the North Ann tation Annual Environmental Survey Data for 1981. It was determined that the member of the public within site n/) nn be using Lake Anna for recreational purposes a maximum of 2232 ho assumed that this member of the public would be located the entire 2 ours a he ake shoreline with the largest annual X/Q of 1.01E-04 at a location 274 er tor. The NRC computer code GASPAR was run to calculate the inhalation do is i *vidual. The GASPAR results were corrected for the frqctional year the me r oc would be using the lake. Using the NRC computer code G an al average X/Q and D/Q values obtained as described in Section 1 of this atteember of the public receiving the largest dose beyond site boundary was 4m)e' be located 1432 meters N sector. The critical pathway was vegetation, the maxim po ge group was the child, and the critical organ was the thyroid. Pathway analysis dicate that existing pathways, including ground and inhalation, within five s of th-nna Power Station, yield Ri dose factors less than those determined for the ati erence 3.1.32] The R v a Mipv dose factors, except for tritium, in Critical Organ Dose Factors (Attachment ) were calculated by multiplying the appropriate D/Q value with the following equation: Ri(K' +(r ) (DFLi)UclFLe X + Ufgeit (29-2) where: K' = a constant of unit conversion, 1E+12 pCi/Ci YV = vegetable areal density in Kg/mi2 DOMINION VPAP-2103N REVISION 18 PAGE 86 OF 86 ATTACHMENT 13 (Page 8 of 8) Meteorological, Liquid, and Gaseous Pathway Analysis Uc, = child leafy vegetable consumption rate, 26 Kg/yr Ucs= child stored vegetable consumption rate, 520 Kg/yr r = fraction of deposited activity retained on vegetation, 1.0 for radioiodine, and 0.2 for particulates DFLi = thyroid ingestion dose factor for the ith radionuclide for the enipCi, from Table E-13, Regulatory Guide 1.109, Rev. 1 ki = decay constant for the ith radionuclide, in sec-1, fro' Ew eddecay constant for removal of activity of leaf and fa by weathering, 5.73E-07 sec-1I (corresponding to a 14 dayh tf = time between harvest of leafy vegetation o8.60E+4, in seconds th =time between harvest of stored vegetin on., 5.18E+6, in seconds fL = fraction of annual intake of leafy, t\\ s n locally, 1.0 (dimensionless) fg = fraction of annual intake of sto I grown locally, 0.76 (dimensionless) Parameters used in the above equ re ,'ed from NUREG-0133 and Regulatory Guide 1.109, Revision 1 Since the concentration o t ti in '* etation is based on the airborne concentration rather than the deposition, c Dose Factors (Attachment 8)for tritium were calculated by multiplying t g equation by the appropriate X/Q: KwK u fL + U fg](DFLi)a[0.75(0.5/H)] (29-3) K"' = a constant of unit conversion I E+03 gm/kg H = absolute, humidity of the atmosphere, 8.0, gm/M 3 0.75 = the fraction of total feed that is water 0.5 = the ratio -of the specific activity of the feed grass to the atmospheric water Other parameters have been previously defined. ATTACHMENT 4 MAJOR CHANGES TO RADIOACTIVE LIQUID. GASEOUS. AND SOLID WASTE TREATMENT SYSTEMS (01/11 - 12/11) As required by the ODCM, Section 6.7.2.a.4, major changes to radioactive liquid, gaseous and solid waste treatment systems for the time period covered by this report are synopsized in this attachment. Supporting information as to the reason(s) for the change(s) and a summary of the 10 CFR 50.59 evaluations are included, as applicable. There were no major changes to the radioactive liquid, gaseous, and solid waste treatment systems for 2011. 8 ATTACHMENT 5 INOPERABILITY OF RADIOACTIVE LIQUID AND GASEOUS EFFLUENT MONITORING INSTRUMENTATION (01/11 - 12/11) As required by the ODCM, Sections 6.2.2.b.2 and 6.3.2.b.3, a list and explanation for extended inoperability of radioactive liquid and/or gaseous effluent monitoring instrumentation is provided in this attachment. There was no radioactive liquid and/or gaseous effluent monitoring instrumentation out-of-service for more than 30 days during 2011. 9 ATTACHMENT 6 UNPLANNED RELEASES (01/11 - 12/11) As required by the ODCM, Section 6.7.2.a.3, a list of unplanned releases, from the site to unrestricted areas, of radioactive material in gaseous and liquid effluents occurring during the reporting period, is made in this attachment. There were no unplanned releases during 2011 meeting the criteria of Section 6.7.2.a.3 of the ODCM from the site to unrestricted area and there were no spills or leaks that required voluntary communication under the criteria of the NEI Ground Water Protection Initiative, NEI 07-07. However, it was identified in CR462600 that a voluntary 30 day report should have been made to the NRC based on sample results from September 07, 2011. Following this discovery a 30 Day Report was made to the NRC on February 21, 2012. 10 ATTACHMENT 7 LOWER LIMITS OF DETECTION FOR EFFLUENT SAMPLE ANALYSIS (01/11 - 12/11) Gaseous Effluents: Required L.L.D. Typical L.L.D. Radioisotope aICi/mL LCi/mL Krypton - 87 1.00E-4 2.50E-8 7.50E-8 Krypton - 88 1.00E-4 1.50E-7 4.60E-7 Xenon - 133 1.OOE-4 4.90E-8 9.90E-8 Xenon - 133m 1.00E-4 1.IOE-7 3.80E-7 Xenon - 135 1.OOE-4 4.30E-8 7.60E-8 Xenon - 135m 1.OOE-4 2.20E-7 3.90E-7 Xenon - 138 1.00E-4 2.80E-7 7.10E-7 Iodine - 131 1.00E-12 5.40E-14 1.30E-13 Iodine - 133 1.OOE-10 3.80E-13 2.50E-11 Manganese - 54 1.00E-11 6.80E-14 8.10E-14 Cobalt - 58 1.OOE-11 5.30E-14 8.80E-14 Iron - 59 1.OOE-11 8.20E-14 4.40E-13 Cobalt - 60 1.00E-11 5.20E-14 2.40E-13 Zinc - 65 1.OOE-11 7.10E-14 5.20E-13 Strontium - 89 1.OOE-11 1.62E-14 8.64E-12 Strontium - 90 1.OOE-11 3.71 E-15 9.33E-12 Molybdenum - 99 1.00E-11 3.50E-13 1.30E-12 Cesium - 134 1.OOE-11 9.60E-15 3.30E-14 Cesium - 137 1.OOE-11 5.20E-14 8.10E-14 Cerium - 141 1.OOE-11 7.50E-14 2.80E-13 Cerium - 144 1.OOE-11 3.OOE-13 8.90E-13 Gross Alpha 1.00E-11 7.20E-15 1.IOE-14 Tritium 1.OOE-6 4.10E-09 8.80E-09 11 ATTACHMENT 7 LOWER LIMITS OF DETECTION FOR EFFLUENT SAMPLE ANALYSIS (01/11 - 12/11) Liquid Effluents: Required L.L.D. Typical L.L.D. Radioisotope aCilmL uCi/mL Krypton - 87 1.OOE-5 3.60E-8 1.70E-7 Krypton - 88 1.OOE-5 6.80E-8 3.1OE-7 Xenon - 133 1.00E-5 6.00E-8 1.40E-7 Xenon. 133m 1.00E-5 9.10E-8 3.20E-7 Xenon - 135 1.00E-5 7.20E-9 5.20E-8 Xenon. 135m 1.00E-5 4.40E-8 4.60E-7 Xenon - 138 1.OOE-5 8.40E-8 1.OOE-6 Iodine - 131 1.OOE-6 2.50E-8 7.70E-8 Manganese - 54 5.00E-7 3.30E-8 6.IOE-8 Iron - 55 1.OOE-6 2.90E-7 8.60E-7 Cobalt - 58 5.OOE-7 2.20E-8 2.IOE-7 Iron - 59 5.00E-7 3.90E-8 7.20E-8 Cobalt - 60 5.00E-7 4.10E-8 8.50E-8 Zinc - 65 5.OOE-7 3.10E-8 6.70E-8 Strontium - 89 5.00E-8 2.20E-8 4.20E-8 Strontium - 90 5.00E-8 1.40E-8 4.60E-8 Molybdenum - 99 5.OOE-7 5.60E-8 1.80E-7 Cesium - 134 5.OOE-7 9.40E-8 4.50E-7 Cesium - 137 5.00E-7 3.70E-8 8.80E-8 Cerium - 141 5.OOE-7 7.10E-8 2.50E-7 Cerium - 144 5.OOE-7 1.30E-7 5.OOE-7 Gross Alpha 1.OOE-7 2.90E-8 7.60E-8 Tritium 1.OOE-5 2.70E-6 4.30E-6 12 ATTACHMENT 8 RESULTS OF GROUND WATER PROTECTION INITIATIVE SAMPLE ANALYSIS (01/11 - 12/11) The Ground Water Protection Program was established to improve North Anna's management of and response to instances where the inadvertent release of radioactive substances may result in low but detectible levels of plant-related materials in subsurface soils and water. It complies with the requirements of NEI 07-07, INDUSTRY GROUND WATER PROTECTION INITIATIVE - FINAL GUIDANCE DOCUMENT. The industry initiative is intended to improve public trust and confidence in the nuclear industry through sampling and analysis of ground water and timely and effective communication with stakeholders, including the public and local, state, and federal officials. Samples are obtained from monitoring wells installed outside the restricted area on a quarterly basis and analyzed by Teledyne Brown Engineering Laboratories. Additional samples are obtained from wells located inside the restricted area and analyzed by Teledyne Brown. Samples are obtained from sumps and yard drains on a quarterly basis and analyzed onsite. Finally, samples may be obtained more frequently than normal, if required. These samples may be analyzed on-site or by a vendor such as Teledyne Brown. The required Lower Limits of Detection, LLDs, and reporting limits for the ground water detection program are those associated with the radiological environmental program as listed in Attachmentsl 1 & 12 to VPAP-2103N, which is attached to this document. On the following pages is a summary of the samples and results of the ground water protection program taken for calendar year 2011. All liquid results are report in pCi/L, while soil results for tritium are reported in pCi/g of soil, wet. An "N/A" indicates a sample analysis was not performed for that sample. An "ND" indicates an analysis was performed but the result was less than the Minimum Detectable Activity, MDA, and the required LLD. If a result is greater than the MDA, but less than the LLD the result is listed. Some of these results may be false positives, due to the analysis software or interferences from naturally occurring radioactivity. In these cases, instead of the value, an explanatory footnote is provided. 13 ATTACHMENT 8 RESULTS OF GROUND WATER PROTECTION INITIATIVE SAMPLE ANALYSIS (01/11 - 12/11) 1st Quarter 2011 Licensed Licensed Sample Date Sample H-3 Gamma - 1-131 Sr-89/90 Fe-55 Ni-63 Alpha Pu-241 Media Emitting TRU Particulates PZ-1 01/05/2011 WATER INSUFFICIENT VOLUME TO SAMPLE PZ-2 01/05/2011 WATER INSUFFICIENT VOLUME TO SAMPLE PZ-3 01/05/2011 WATER 2.02E+3 N/A IN/A I N/A I N/A I N/A N/A N/A PZ-1 01/15/2011 WATER INSUFFICIENT VOLUME TO SAMPLE PZ-2 01/15/2011 WATER INSUFFICIENT VOLUME TO SAMPLE PZ-3 01/15/2011 WATER 2.59E+3 N/A IN/A I N/A I N/A I N/A N/A N/A PZ-1 01/21/2011 WATER INSUFFICIENT VOLUME TO SAMPLE PZ-2 01/21/2011 WATER INSUFFICIENT VOLUME TO SAMPLE PZ-3 01/21/2011 WATER 2.68E+3 N/A IN/A I N/A I N/A I N/A N/A N/A PZ-1 01/29/2011 WATER INSUFFICIENT VOLUME TO SAMPLE PZ-2 01/29/2011 WATER INSUFFICIENT VOLUME TO SAMPLE PZ-3 01/31/2011 WATER 2.07E+3 N/A N/A N/A N/A N/A N/A N/A U-i INTAKE STORM 02/01/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A DRAINS U-2 INTAKE STORM 02/01/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A DRAINS DISCHARGE CANAL 02/01/2011 WATER 4.33E+3 N/A N/A N/A N/A N/A N/A N/A STORM DRAINS SUBSURFACE DRAINS 02/01/2011 WATER 1.48E+3 N/A N/A N/A N/A N/A N/A N/A PZ-1 02/03/2011 WATER INSUFFICIENT VOLUME TO SAMPLE PZ-2 02/03/2011 WATER INSUFFICIENT VOLUME TO SAMPLE PZ-3 02/03/2011 WATER 2.15E+3 N/A IN/A I N/A N/A I N/A N/A N/A PZ-1 02/09/2011 WATER INSUFFICIENT VOLUME TO SAMPLE PZ-2 02/09/2011 WATER INSUFFICIENT VOLUME TO SAMPLE PZ-3 02/09/2011 WATER 2.65E+3 N/A IN/A I N/A N/A I N/A N/A N/A PZ-1 02/13/2011 WATER INSUFFICIENT VOLUME TO SAMPLE PZ-2 02/13/2011 WATER INSUFFICIENT VOLUME TO SAMPLE PZ-3 02/13/2011 WATER 2.93E+3 N/A IN/A I N/A N/A I N/A N/A N/A PZ-1 02/13/2011 WATER INSUFFICIENT VOLUME TO SAMPLE PZ-2 02/13/2011 WATER INSUFFICIENT VOLUME TO SAMPLE PZ-3 02/13/2011 WATER 2.37E+3 N/A N/A N/A N/A N/A N/A N/A GWP-3 (VENDOR) 02/24/2011 WATER 2.97E+3 ND ND N/A N/A N/A N/A N/A GWP-3 02/24/2011 WATER 1.44E+3 N/A N/A N/A N/A N/A N/A N/A GWP-7 (VENDOR) 02/24/2011 WATER ND ND ND N/A N/A N/A N/A N/A GWP-7 02/24/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-4 (VENDOR) 02/28/2011 WATER 2.44E+3 ND ND N/A N/A N/A N/A N/A GWP-4 02/28/2011 WATER 2.48E+3 N/A N/A N/A N/A N/A N/A N/A GWP-8 02/28/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-9 (VENDOR) 03/01/2011 WATER ND ND ND N/A N/A N/A N/A N/A PZ-3 03/01/2011 WATER 2.34E+3 N/A N/A N/A N/A N/A N/A N/A GWP-3 03/01/2011 WATER 2.64E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 03/01/2011 WATER 2.29E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 (VENDOR) 03/01/2011 WATER 2.43E+3 ND ND N/A N/A N/A N/A N/A GWP-3 (VENDOR) 03/02/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-3 03/02/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A 14 ATTACHMENT 8 RESULTS OF GROUND WATER PROTECTION INITIATIVE SAMPLE ANALYSIS (01/11 - 12/11) Ist Quarter 2011 Sample Gamma - Sample Date Sam H-3 Emitting 1-131 Sr-89/90 Fe-55 Ni-63 Alh Pu-241 MediaTRU Particulates GWP-4 (VENDOR) 03/02/2011 WATER 1.03E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 03/02/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-7 (VENDOR) 03/02/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-9 03/02/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-4 03/02/2011 WATER 1.86E+3 N/A N/A N/A N/A N/A N/A N/A GWP-8 (VENDOR) 03/03/2011 WATER ND ND ND N/A N/A N/A N/A N/A GWP-8 03/03/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-8 (VENDOR) 03/03/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-9 (VENDOR) 03/03/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-7 03/02/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-8 03/03/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-9 03/03/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 03/03/2011 WATER 1.81 E+4 N/A N/A N/A N/A N/A N/A N/A GWP-6(1) 03/03/2011 WATER 1.85E+4 N/A N/A N/A N/A N/A N/A N/A GWP-6(1) 03/03/2011 WATER 1.82E+4 N/A N/A N/A N/A N/A N/A N/A GWP-5A (VENDOR) 03/07/2011 WATER ND ND ND N/A N/A N/A N/A N/A GWP-5A 03/07/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 (VENDOR) 03/07/2011 WATER N/A ND ND ND ND ND ND ND GWP-4 03/08/2011 WATER 1.79E+3 N/A N/A N/A N/A N/A N/A N/A GWP-7 03/08/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-8 03/08/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-9 03/08/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 (VENDOR) 03/09/2011 WATER 4.08E+3 ND ND N/A N/A N/A N/A N/A PZ-1 03/09/2011 WATER INSUFFICIENT VOLUME TO SAMPLE PZ-2 03/09/2011 WATER INSUFFICIENT VOLUME TO SAMPLE PZ-3 03/09/2011 WATER 4.26E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3(C) 03/09/2011 WATER 4.48E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 (VENDOR) 03/10/2011 WATER 1.80E+4 ND ND N/A N/A N/A N/A N/A GWP-6 03/10/2011 WATER 1.70E+4 N/A N/A N/A N/A N/A N/A N/A RAINWATER 03/10/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A TTW-2 (VENDOR) 03/11/2011 WATER ND ND ND N/A N/A N/A N/A N/A TTW-4 (VENDOR) 03/11/2011 WATER ND ND ND N/A N/A N/A N/A N/A BTW-4 (VENDOR) 03/11/2011 WATER ND ND ND N/A N/A N/A N/A N/A U-1 MAT SUMP EAST 03/17/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-1 MAT SUMP SOUTH 03/17/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-2 MAT SUMP INSIDE 03/21/2011 WATER 2.18E+3 N/A N/A N/A N/A N/A N/A N/A U-2 MAT SUMP 03/21/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A OUTSIDE BTW-1 (VENDOR) 03/26/2011 WATER ND ND ND N/A N/A N/A N/A N/A BTW-2(2 ) (VENDOR) 03/26/2011 WATER ND ND ND N/A N/A N/A N/A N/A TTW-1(VENDOR) 03/26/2011 WATER INSUFFICIENT VOLUME TO SAMPLE TTW3 (2 ) (VENDOR) 03/26/2011 WATER ND j ND ND N/A IN/AIN/AIN/AI N/A TTW-5(2) (VENDOR) 03/26/2011 WATER ND ND ND N/A N/A N/A N/A N/A (1) Re-analysis of original sample. (2) These results were falsely positive forlI-i 31. Samples were held for eight days and recounted. A second count was performed two days later. The recounts showed increasing activity. This is not consistent with 1-131 decay. Gamma analysis of the samples show Ra-226 and daughter interference. The activity that was initially seen was from Ra-226 and not 1-131. 15 ATTACHMENT 8 RESULTS OF GROUND WATER PROTECTION INITIATIVE SAMPLE ANALYSIS (01/11 - 12/11) 2nd Quarter 2011 Sample ~ Gamma -Alh Sample Date Sampledia H-3 Emitting 1-131 Sr-89/90 Fe-55 Ni-63 TRU Pu-241 Particulates PZ-2 (VENDOR) 04/11/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-3 (VENDOR) 04/12/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 (VENDOR) 04/12/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-4 (VENDOR) 04/12/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-5A (VENDOR) 04/12/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 (VENDOR) 04/14/2011 WATER 1.05E+4 N/A N/A N/A N/A N/A N/A N/A GWP-7 (VENDOR) 04/13/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-8 (VENDOR) 04/12/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-9 (VENDOR) 04/13/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-2 04/11/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-3 04/12/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 04/12/2011 WATER 1.87E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 04/12/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-5A 04/12/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 04/14/2011 WATER 9.43E+3 N/A N/A N/A N/A N/A N/A N/A GWP-7 04/13/2011 WATER 1.33E+3 N/A N/A N/A N/A N/A N/A N/A GWP-8 04/12/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-9 04/13/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-2 (VENDOR) 04/18/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-3 (VENDOR) 04/19/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 (VENDOR) 04/19/2011 WATER 3.44E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 (VENDOR) 04/19/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-5A (VENDOR) 04/20/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 (VENDOR) 04/19/2011 WATER 9.07E+3 N/A N/A N/A N/A N/A N/A N/A GWP-7 (VENDOR) 04/20/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-8 (VENDOR) 04/19/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-9 (VENDOR) 04/20/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-2 04/18/2011 WATER 1.45E+3 N/A N/A N/A N/A N/A N/A N/A GWP-3 04/19/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 04/19/2011 WATER 2.54E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 04/19/2011 WATER 1.41 E+3 N/A N/A N/A N/A N/A N/A N/A GWP-5A 04/20/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 04/19/2011 WATER 9.84E+3 N/A N/A N/A N/A N/A N/A N/A GWP-7 04/20/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-8 04/19/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-9 04/20/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-2 05/02/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-3 05/02/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 05/02/2011 WATER 2.59+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 05/02/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-5A 05/02/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 05/02/2011 WATER 7.74E+3 N/A N/A N/A N/A N/A N/A N/A GWP-7 05/02/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A 16 ATTACHMENT 8 RESULTS OF GROUND WATER PROTECTION INITIATIVE SAMPLE ANALYSIS (01/11 - 12/11) 2nd Quarter 2011 Sample Gamma - Sample Date Media H-3 Emitting 1-131 Sr-89/90 Fe-55 Ni-63 TRU Pu-241 Particulates GWP-8 05/02/2011 WATER 1.27E+6 N/A N/A N/A N/A N/A N/A N/A GWP-9 05/02/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-2 05/02/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-3 05/02/2011 WATER 2.07E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/02/2011 WATER 4.09E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 05/02/2011 WATER 1.86E+3 N/A N/A N/A N/A N/A N/A N/A GWP-5A 05/02/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 05/02/2011 WATER 7.51E+3 N/A N/A N/A N/A N/A N/A N/A GWP-7 05/02/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-8 05/02/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-9 05/02/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 05/09/2011 WATER 5.44E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/09/2011 WATER 6.18E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/09/2011 WATER 5.90E+3 N/A N/A N/A N/A N/A N/A N/A GWP-3 05/09/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-4 05/09/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-5A 05/09/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 05/09/2011 WATER 6.31 E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/10/2011 WATER 6.74E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 05/10/2011 WATER 6.09E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/10/2011 WATER 6.32E+3 N/A N/A N/A N/A N/A N/A N/A GWP-3 05/10/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-4 05/10/2011. WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-5A 05/10/2011 WATER 1.53E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/10/2011 WATER 6.45E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/11/2011 WATER 6.47E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/11/2011 WATER 6.70E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/11/2011 WATER 7.05E+3 N/A N/A N/A N/A N/A N/A N/A GWP-3 05/11/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-4 05/11/2011 WATER 1.79E+3 N/A N/A N/A N/A N/A N/A N/A GWP-5A 05/11/2011 WATER 1.51 E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 05/11/2011 WATER 7.10E+3 N/A N/A N/A N/A N/A N/A N/A U-1 INTAKE STORM 05/11/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A DRAINS U-2 INTAKE STORM 05/11/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A DRAINS DISCHARGE CANAL 05/11/2011 WATER 2.82E+3 N/A N/A N/A N/A N/A N/A N/A STORM DRAINS SUBSURFACE DRAINS 05/11/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 05/11/2011 WATER 7.26E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/12/2011 WATER 6.99E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/12/2011 WATER 8.31 E+3 N/A N/A N/A N/A N/A N/A N/A GWP-3 05/12/2011 WATER 2.10E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 05/12/2011 WATER 2.40E+3 N/A N/A N/A N/A N/A N/A N/A GWP-5A 05/12/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 05/12/2011 WATER 8.38E+3 N/A N/A N/A N/A N/A N/A N/A 17 ATTACHMENT 8 RESULTS OF GROUND WATER PROTECTION INITIATIVE SAMPLE ANALYSIS (01/11 - 12111) 2 nd Quarter 2011 Gamma - Sample Date Sample H-3 Emitting 1-131 Sr-89/90 Fe-55 Ni-63 Alh Pu-241 Particulates PZ-3 05/12/2011 WATER 7.63E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/13/2011 WATER 7.28E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/13/2011 WATER 7.99E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/13/2011 WATER 7.39E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/14/2011 WATER 6.51E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/14/2011 WATER 6.04E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/14/2011 WATER 7.89E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/15/2011 WATER 7.96E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/15/2011 WATER 7.86E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/15/2011 WATER 7.78E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/16/2011 WATER 7.09E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/16/2011 WATER 7.76E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/16/2011 WATER 7.77E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/16/2011 WATER 7.74E+3 N/A N/A N/A N/A N/A N/A N/A GWP-3 05/16/2011 WATER 2.15E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 05/16/2011 WATER 1.71 E+3 N/A N/A N/A N/A N/A N/A N/A GWP-5A 05/16/2011 WATER 1.55E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 05/16/2011 WATER 8.06E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/17/2011 WATER 8.43E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/17/2011 WATER 8.29E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/17/2011 WATER 8.19E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/17/2011 WATER 8.09E+3 N/A N/A N/A N/A N/A N/A N/A GWP-3 05/17/2011 WATER 1.45E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 05/17/2011 WATER 1.54E+3 N/A N/A N/A N/A N/A N/A N/A GWP-5A 05/17/2011 WATER 2.31 E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 05/17/2011 WATER 8.76E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/17/2011 WATER 8.19E+3 N/A N/A N/A N/A N/A N/A N/A GWP-3 05/18/2011 WATER 2.01E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 05/18/2011 WATER 2.27E+3 N/A N/A N/A N/A N/A N/A N/A GWP-5A 05/18/2011 WATER 2.11E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 05/18/2011 WATER 7.80E+3 N/A N/A N/A N/A N/A N/A N/A GWP-7 05/18/2011 WATER 1.42E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/18/2011 WATER 7.54E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/18/2011 WATER 8.03E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/18/2011 WATER 8.26E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/19/2011 WATER 8.38E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/19/2011 WATER 7.30E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/19/2011 WATER 7.15E+3 N/A N/A N/A N/A N/A N/A N/A GWP-3 05/19/2011 WATER 2.19E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 05/19/2011 WATER 1.59E+3 N/A N/A N/A N/A N/A N/A N/A GWP-5A 05/19/2011 WATER 2.65E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 05/19/2011 WATER 8.1OE+3 N/A N/A N/A N/A N/A N/A N/A GWP-7 05/19/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A 18 ATTACHMENT 8 RESULTS OF GROUND WATER PROTECTION INITIATIVE SAMPLE ANALYSIS (01/11 - 12/11) 2nd Quarter 2011 Date Sample Gamma - Sample Date Media H-3 Emitting 1-131 Sr-89/90 Fe-55 Ni-63 TRU Pu-241 Particulates TURBINE BLDG GROUND WATER 05/19/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A INTRUSION PZ-3 05/20/2011 WATER 7.05E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/20/2011 WATER 7.04E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/20/2011 WATER 7.37E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/21/2011 WATER 6.19E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/21/2011 WATER 7.06E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/21/2011 WATER 6.45E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/21/2011 WATER 7.93E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/22/2011 WATER 8.33E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/22/2011 WATER 7.58E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/22/2011 WATER 6.74E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/22/2011 WATER 7.03E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/23/2011 WATER 7.50E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/23/2011 WATER 8.20E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/23/2011 WATER 7.44E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/23/2011 WATER 7.59E+3 N/A N/A N/A N/A N/A N/A N/A GWP-3 05/23/2011 WATER 1.68E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 05/23/2011 WATER 1.77E+3 N/A N/A N/A N/A N/A N/A N/A GWP-5A 05/23/2011 WATER 2.48E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 05/23/2011 WATER 6.68E+3 N/A N/A N/A N/A N/A N/A N/A GWP-7 05/23/2011 WATER 2.06E+3 N/A N/A N/A N/A N/A N/A N/A GWP-3 05/24/2011 WATER 2.32E+3 N/A N/A N/A N/A N/A N/A N/A GWP-8 05/24/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 05/24/2011 WATER 8.55E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/24/2011 WATER 8.OOE+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/24/2011 WATER 7.83E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/24/2011 WATER 7.43E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 05/24/2011 WATER 2.30E+3 N/A N/A N/A N/A N/A N/A N/A GWP-5A 05/24/2011 WATER 3.06E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 05/24/2011 ] WATER 7.83E+3 N/A N/A N/A N/A N/A N/A N/A GWP-7 05/24/2011 WATER 1.30E+3 N/A N/A N/A N/A N/A N/A N/A GWP-3 05/25/2011 WATER 1.30E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 05/25/2011 WATER 1.89E+3 N/A N/A N/A N/A N/A N/A N/A GWP-5A 05/25/2011 WATER 1.34E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 05/25/2011 WATER 6.21E+3 N/A N/A N/A N/A N/A N/A N/A GWP-7 05/25/2011 WATER 1.61 E+3 N/A N/A N/A N/A N/A N/A N/A GWP-8 05/25/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 05/25/2011 WATER 6.20E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/25/2011 WATER 8.04E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/25/2011 WATER 6.20E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/25/2011 WATER 6.47E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/26/2011 WATER 7.54E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/26/2011 WATER 6.70E+3 N/A N/A N/A N/A N/A N/A N/A 19 ATTACHMENT 8 RESULTS OF GROUND WATER PROTECTION INITIATIVE SAMPLE ANALYSIS (01/11 - 12/11) 2nd Quarter 2011 Gamma - Sample Date Sample H-3 Emitting 1-131 Sr-89/90 Fe-55 Ni-63 Alh Pu-241 Media TRU Particulates PZ-3 05/26/2011 WATER 5.67E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 05/26/2011 WATER 1.59E+3 N/A N/A N/A N/A N/A N/A N/A GWP-5A 05/26/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-7 05/26/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-8 05/26/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-3 05/26/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 05/26/2011 WATER 5.62E+3 N/A N/A N/A N/A N/A N/A N/A U-1 MAT SUMP EAST 05/26/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-1 MAT SUMP SOUTH 05/26/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-2 MAT SUMP INSIDE 05/26/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-2 MAT SUMP UTSIDE 05/26/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A OUTSIDE PZ-3 05/27/2011 WATER 7.41 E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/27/2011 WATER 7.72E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 05/27/2011 WATER 8.OOE+3 N/A N/A N/A N/A N/A N/A N/A BTW-1 (VENDOR) 06/26/2011 WATER ND ND ND N/A N/A N/A N/A N/A BTW-2 (VENDOR) 06/26/2011 WATER ND ND ND N/A N/A N/A N/A N/A BTW-4 (VENDOR) 06/26/2011 WATER ND ND ND N/A N/A N/A N/A N/A r-W-1 (VENDOR) 06/26/2011 WATER INSUFFICIENT VOLUME TO SAMPLE TTW-2 (VENDOR) 06/26/2011 WATER ND ND ND N/A N/A N/A N/A N/A I--W-3(1) (VENDOR) 06/26/2011 WATER ND ND ND N/A N/A N/A N/A N/A TTW-4 (VENDOR) 06/26/2011 .WATER ND ND ND N/A N/A N/A N/A N/A TTW-5 (VENDOR) 06/26/2011 WATER ND ND ND N/A N/A N/A N/A N/A PZ-1 (VENDOR) 06/27/2011 WATER ND INSUFFICIENT VOLUME TO PERFORM ANALYSES PZ-2 (VENDOR) 06/27/2011 WATER ND INSUFFICIENT VOLUME TO PERFORM ANALYSES PZ-3 (VENDOR) 06/27/2011 WATER 3.43E+3 ND ND N/A N/A N/A N/A N/A PZ-1 06/27/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-2 06/27/2011 WATER 2.80E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 06/27/2011 WATER 3.56E+3 N/A N/A N/A N/A N/A N/A N/A GWP-3 06/30/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-4 06/30/2011 WATER 4.05E+3 N/A N/A N/A N/A N/A N/A N/A GWP-5A 06/30/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 06/30/2011 WATER 6.61 E+3 N/A N/A N/A N/A N/A N/A N/A GWP-7 06/30/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-8 06/30/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-9 06/30/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A (1) Sample was positive for 1-131. The 1-131 counts were suspected to be from an interfering nuclide. The sample was held for seven (7) days and recounted. A second count was performed two (2) days later. The recounts showed increasing activity. This is not congruent with normal 1-131 activity. 20 ATTACHMENT 8 RESULTS OF GROUND WATER PROTECTION INITIATIVE SAMPLE ANALYSIS (01/11 - 12/11) 3rd Quarter 2011 Sample ~ Gamma -Alh Sample Date Sampledia H-3 Emitting 1-131 Sr-89190 Fe-55 Ni-63 AlphaTRU Pu-241 Particulates I HOLE #1 (VENDOR) 07/13/2011 SOIL <3.05(1) N/A N/A N/A N/A N/A N/A N/A HOLE #2 (VENDOR) 07/13/2011 SOIL <2.87(') N/A N/A N/A N/A N/A N/A N/A HOLE #3 (VENDOR) 07/13/2011 SOIL <2.89(1) N/A N/A N/A N/A N/A N/A N/A HOLE #4 (VENDOR) 07/13/2011 SOIL <3.35(') N/A N/A N/A N/A N/A N/A N/A HOLE #5 (VENDOR) 07/13/2011 SOIL <3.17(1) N/A N/A N/A N/A N/A N/A N/A HOLE #6 (VENDOR) 07/13/2011 SOIL <3.13(1) N/A N/A N/A N/A N/A N/A N/A HOLE #8 @ 7' 07/13/2011 SOIL <2.91(1) N/A N/A N/A N/A N/A N/A N/A (VENDOR) HOLE #8 @7 75' (VENDOR) 07/13/2011 SOIL <3.33(l) N/A N/A N/A N/A N/A N/A N/A ISFSI Well #1 07/14/2011 WATER ND ND N/A ND N/A N/A N/A N/A ISFSI Well #4 07/14/2011 WATER ND ND N/A ND N/A N/A N/A N/A GWP-3 07/31/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-5A 07/31/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-7 07/31/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-8 07/31/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-9 07/31/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-1 07/31/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-2 07/31/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 07/31/2011 WATER 5.03E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 07/31/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 07/31/2011 WATER 8.23E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 08/07/2011 WATER 4.51 E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 08/07/2011 WATER 1.71 E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 08/07/2011 WATER 9.74E+3 N/A N/A N/A N/A N/A N/A N/A GWP-3 08/21/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-4 08/21/2011 WATER 4.37E+3 N/A N/A N/A N/A N/A N/A N/A GWP-5A 08/21/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 08/21/2011 WATER 1.10E+4 N/A N/A N/A N/A N/A N/A N/A GWP-7 08/21/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 08/21/2011 WATER 3.47E+3 N/A N/A N/A N/A N/A N/A N/A U-1 ABGWMS 08/25/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-1 MAT SUMP EAST 08/25/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-1 MAT SUMP SOUTH 08/25/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-2 ABGWMS 08/25/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-2 MAT SUMP INSIDE 08/25/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-2 MAT SUMP OUTSIDE 08/25/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 08/27/2011 WATER 2.54E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 08/27/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 08/27/2011 WATER 9.55E+3 N/A N/A N/A N/A N/A N/A N/A GWP-3 09/01/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-5A 09/01/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-7 09/01/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-8 09/01/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-9 09/01/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A (1) Units are pCi/g soil wet. 21 ATTACHMENT 8 RESULTS OF GROUND WATER PROTECTION INITIATIVE SAMPLE ANALYSIS (01/11 - 12/11) 3rd Quarter 2011 Gamma - Sample Date Sampledia H-3 Emitting 1-131 Sr-89/90 Fe-55 Ni-63 TRU Pu-241 Particulates PZ-3 09/07/2011 WATER 5.63E+3 N/A N/A N/A N/A N/A N/A N/A GWP-3 09/07/2011 WATER 1.68E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 09/07/2011 WATER 3.74E+3 N/A N/A N/A N/A N/A N/A N/A GWP-5A 09/07/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 09/07/2011 WATER 2.02E+4 N/A N/A N/A N/A N/A N/A N/A GWP-7 09/07/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-8 09/07/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-9 09/07/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-3(1) 09/07/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6(1) 09/07/2011 WATER 2.07E+4 N/A N/A N/A N/A N/A N/A N/A PZ-3 09/08/2011 WATER 3.50E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 09/08/2011 WATER 3.25E+3 N/A N/A N/A N/A N/A N/A N/A GWP-5A 09/08/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 09/08/2011 WATER 2.24E+4 N/A N/A N/A N/A N/A N/A N/A U-1 ABGWMS 09/08/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-1 MAT SUMP EAST 09/08/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-1 MAT SUMP SOUTH 09/08/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-2 ABGWMS 09/08/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-2 MAT SUMP INSIDE 09/08/2011 WATER 1.34E+3 N/A N/A N/A N/A N/A N/A N/A U-2 MAT SUMP 09/08/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A OUTSIDE PZ-3 09/09/2011 WATER 2.21E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 09/09/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-5A 09/09/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 09/09/2011 WATER 1.53E+4 N/A N/A N/A N/A N/A N/A N/A HVAC DRAIN LINE OUTSIDE ELECTRIC 09/09/2011 WATER 3.OOE+4 N/A N/A N/A N/A N/A N/A N/A SHOP PZ-3 09/10/2011 WATER 1.62E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 09/10/2011 WATER 2.56E+3 N/A N/A N/A N/A N/A N/A N/A GWP-5A 09/10/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 09/10/2011 WATER 1.80E+4 N/A N/A N/A N/A N/A N/A N/A HVAC DRAIN LINE OUTSIDE ELECTRIC 09/11/2011 WATER 2.19E+4 N/A N/A N/A N/A N/A N/A N/A SHOP PZ-3 09/12/2011 WATER 2.82E+3 N/A N/A N/A N/A N/A N/A N/A GWP-3 09/12/2011 WATER 1.62E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 09/12/2011 WATER 2.29E+3 N/A N/A N/A N/A N/A N/A N/A GWP-5A 09/12/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 09/12/2011 WATER 2.49E+4 N/A N/A N/A N/A N/A N/A N/A U-1 ABGWMS 09/13/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-1 MAT SUMP EAST 09/13/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-1 MAT SUMP SOUTH 09/13/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-2 ABGWMS 09/13/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-2 MAT SUMP INSIDE 09/13/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-2 MAT SUMP 09/13/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A OUTSIDE (1) RE-ANALYSIS 22 ATTACHMENT 8 RESULTS OF GROUND WATER PROTECTION INITIATIVE SAMPLE ANALYSIS (01/11 - 12/11) 3rd Quarter 2011 Sample ~ Gamma -Alh Sample Date Sampledia H-3 Emitting 1-131 Sr-89190 Fe-55 Ni-63 TRU Pu-241 Particulates PZ-3 09/13/2011 WATER 2.31E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 09/13/2011 WATER 1.67E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 09/13/2011 WATER 2.17E+4 N/A N/A N/A N/A N/A N/A N/A GWP-7 09/13/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A HVAC DRAIN LINE OUTSIDE ELECTRIC 09/14/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A SHOP PZ-3 09/14/2011 WATER 1.52E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 09/14/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 09/14/2011 WATER 2.41 E+4 N/A. N/A N/A N/A N/A N/A N/A GWP-8 09/14/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A BIG BLOCK ON CURVE-09/14/2011 SOIL <1.12(') N/A N/A N/A N/A N/A N/A N/A SOIL (VENDOR) SOILK 13ENDORI 09/14/2011-SOIL < 1. 12(l) N/A N/A N/A N/A N/A N/A N/A BLOCK 13 - SOIL (VENDOR) 09/14/2011-SOIL <1.12(l) N/A N/A N/A N/A N/A N/A N/A BLOCK 12D - SOIL (VENDOR) 09/14/2011 SOIL <1.08(1) N/A N/A N/A N/A N/A N/A N/A BLOCK 12 VEHICLE MAINTENANCE SHOP - 09/14/2011 SOIL <1.08(1) N/A N/A N/A N/A N/A N/A N/A SOIL (VENDOR) PZ-3 09/15/2011 WATER 2.47E3 N/A N/A N/A N/A N/A N/A N/A GWP-4 09/15/2011 WATER 2.40E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 09/15/2011 WATER 2.01E+4 ND ND N/A N/A N/A N/A N/A GWP-9 09/15/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 (VENDOR) 09/13/2011-WATER 2.18E+4 ND ND ND ND ND ND ND 09/15/2011 DISCHARGE CANAL STORM DRAIN 09/16/2011 WATER 1.57E+3 ND ND ND ND ND ND ND PZ-3 09/16/2011 WATER 1.65E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 09/16/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 09/16/2011 WATER 1.22E+4 ND ND N/A N/A N/A N/A N/A PZ-3 09/17/2011 WATER 1.83E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 09/17/2011 WATER 1.62E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 09/17/2011 WATER 1.38E+4 ND ND N/A N/A N/A N/A N/A GWP-3 09/19/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-4 09/19/2011 WATER 1.82E+3 N/A N/A N/A N/A N/A N/A N/A GWP-5A 09/19/2011 WATER ND ND ND N/A N/A N/A N/A N/A GWP-6 09/19/2011 WATER 1.16E+4 N/A N/A N/A N/A N/A N/A N/A PZ-3 09/19/2011 WATER 1.97E+3 N/A N/A N/A N/A N/A N/A N/A U-1 MAT SUMP EAST 09/19/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-1 MAT SUMP SOUTH 09/19/2011 WATER 1.40E+3 N/A N/A N/A N/A N/A N/A N/A U-1 ABGWMS 09/19/2011 WATER 1.37E+3 N/A N/A N/A N/A N/A N/A N/A U-2 MAT SUMP INSIDE 09/19/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-2 MAT SUMP OUTSIDE 09/19/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-2 ABGWMS 09/19/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 09/19/2011 WATER 1.80E+3 N/A N/A N/A N/A N/A N/A N/A (1) Units are pCi/g soil wet. 23 ATTACHMENT 8 RESULTS OF GROUND WATER PROTECTION INITIATIVE SAMPLE ANALYSIS (01/11 - 12/11) 3 rd Quarter 2011 Gamma - Sample Date Sample H-3 Emitting 1-131 Sr-89/90 Fe-55 Ni-63 Alh Pu-241 Media TRU Particulates GWP-4 09/20/2011 WATER 1.48E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 09/20/2011 WATER 2.84E+4 N/A N/A N/A N/A N/A N/A N/A GWP-7 09/20/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-3 09/21/2011 WATER 1.69E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 09/21/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6(1 ) 09/21/2011 WATER 1.26E+4 N/A N/A N/A N/A N/A N/A N/A GWP-6(2) 09/21/2011 WATER 1.96E+4 N/A N/A N/A N/A N/A N/A N/A GWP-8 09/21/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 09/22/2011 W,'-TER 2.69E+4 N/A N/A N/A N/A N/A N/A N/A GWP-6 09/22/2011 WATER 1.33E+4 N/A N/A N/A N/A N/A N/A N/A GWP-6 09/22/2011 WATER 2.OOE+4 N/A N/A N/A N/A N/A N/A N/A PZ-3 09/22/2011 WATER 2.07E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 09/22/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-9 09/22/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A DISCHARGE CANAL STORM DAN 09/22/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A STORM DRAIN PUDDLE 09/22/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-1 INTAKE STORM 09/23/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A DRAIN RUN OFF 09/23/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A DRAIN RUN OFF 09/23/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 09/24/2011 WATER 2.08E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 09/24/2011 WATER 2.18E+3 N/A N/A N/A N/A N/A N/A N/A GWP-5 09/24/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 09/24/2011 WATER 3.37E+4 N/A N/A N/A N/A N/A N/A N/A HVAC DRAIN LINE OUTSIDE ELECTRIC 09/24/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A SHOP GWP-6 09/25/2011 WATER 3.06E+4 N/A N/A N/A N/A N/A N/A N/A GWP-6 09/25/2011 WATER 3.1OE+4 N/A N/A N/A N/A N/A N/A N/A GWP-6 09/25/2011 WATER 3.67E+4 N/A N/A N/A N/A N/A N/A N/A GWP-6 09/26/2011 WATER 2.52E+4 N/A N/A N/A N/A N/A N/A N/A BTW-1 (VENDOR) 09/27/2011 WATER ND ND ND N/A N/A N/A N/A N/A BTW-2 (VENDOR) 09/27/2011 WATER ND ND ND N/A N/A N/A N/A N/A BTW-4 (VENDOR) 09/27/2011 WATER ND ND ND N/A N/A N/A N/A N/A TT/W-1 (VENDOR) 09/27/2011 WATER INSUFFICIENT VOLUME TO SAMPLE TTW-2 (VENDOR) 09/27/2011 WATER ND ND ND N/A N/A N/A N/A N/A TTW-3 (VENDOR) 09/27/2011 WATER ND ND ND N/A N/A N/A N/A N/A TTW-4 (VENDOR) 09/27/2011 WATER ND ND ND N/A N/A N/A N/A N/A TTW-5 (VENDOR) 09/27/2011 WATER ND ND ND N/A N/A N/A N/A N/A BTW-1 09/27/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A BTW-2 09/27/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A BTW-4 09/27/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A TTW-2 09/27/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A TTW-3 09/27/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A (1) pH MEASURED @ 6.84 (2) pH MEASURED @ 6.90 24 ATTACHMENT 8 RESULTS OF GROUND WATER PROTECTION INITIATIVE SAMPLE ANALYSIS (01/11 - 12/11) 3rd Quarter 2011 Gamma - Sample Date Sample H-3 Emitting 1-131 Sr-89190 Fe-55 NI-63 Alpha Pu-241 SampeMedia Particulates TRU TTW-4 09/27/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A TTW-5 09/27/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 09/28/2011 WATER 3.14E+4 N/A N/A N/A N/A N/A N/A N/A GWP-6 09/29/2011 WATER 3.04E+4 N/A N/A N/A N/A N/A N/A N/A GWP-5A 09/29/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-4 09/29/2011 WATER 1.90E+3 N/A N/A N/A N/A N/A N/A N/A GWP-3 09/29/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 09/29/2011 WATER 1.96E+3 N/A N/A N/A N/A N/A N/A N/A PZ-2 (VENDOR) 09/29/2011 WATER INSUFFICIENT VOLUME TO SAMPLE PZ-1 (VENDOR) 09/29/2011 WATER INSUFFICIENT VOLUME TO SAMPLE GWP-3 (VENDOR) 09/29/2011 WATER ND ND ND N/A N/A N/A N/A N/A PZ-3 (VENDOR) 09/29/2011 WATER 1.39E+3 ND ND N/A N/A N/A N/A N/A GWP-4 (VENDOR) 09/29/2011 WATER 1.86E+3 ND ND N/A N/A N/A N/A N/A GWP-5A (VENDOR) 09/29/2011 WATER ND ND ND N/A N/A N/A N/A N/A GWP-7 (VENDOR) 09/30/2011 WATER ND ND ND N/A N/A N/A N/A N/A GWP-8 (VENDOR) 09/30/2011 WATER ND ND ND N/A N/A N/A N/A N/A GWP-9 (VENDOR) 09/30/2011 WATER ND ND ND N/A N/A N/A N/A N/A GWP-6 09/30/2011 WATER 3.37E+4 N/A N/A N/A N/A N/A N/A N/A GWP-7 09/30/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-8 09/30/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-9 09/30/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-1 MAT SUMP EAST 09/30/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-1 MAT SUMP SOUTH 09/30/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-1 ABGWMS 09/30/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-2 MAT SUMP INSIDE 09/30/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A U-2 MAT SUMP 09/30/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A OUTSIDE U-2 ABGWMS 09/30/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A 25 ATTACHMENT 8 RESULTS OF GROUND WATER PROTECTION INITIATIVE SAMPLE ANALYSIS (01/11 - 12/11) 4th Quarter 2011 Sa mpleGamma -Alh Sample Date Sampledia H-3 Emitting 1-131 Sr-89/90 Fe-55 Ni-63 TRU Pu-241 Particulates I GWP-4 10/01/2011 WATER 2.07E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 10/01/2011 WATER 1.74E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 10/01/2011 WATER 3.50E+4 N/A N/A N/A N/A N/A N/A N/A GWP-4 10/03/2011 WATER 2.14E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 10/03/2011 WATER 2.OOE+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 10/03/2011 WATER 3.28E+4 N/A N/A N/A N/A N/A N/A N/A GWP-4 10/04/2011 WATER 1.47E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 10/04/2011 WATER 1.47E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 10/04/2011 WATER 3.30E+4 N/A N/A N/A N/A N/A N/A N/A GWP-4 10/05/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 10/05/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 10/05/2011 WATER 2.84E+4 N/A N/A N/A N/A N/A N/A N/A GWP-4 10/06/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 10/06/2011 WATER 1.96E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 10/06/2011 WATER 3.49E+4 N/A N/A N/A N/A N/A N/A N/A GWP-4 10/07/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 10/07/2011 WATER 3.48E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 10/07/2011 WATER 3.54E+4 N/A N/A N/A N/A N/A N/A N/A PZ-2 10/08/2011 WATER INSUFFICIENT VOLUME TO SAMPLE PZ-1 10/08/2011 WATER INSUFFICIENT VOLUME TO SAMPLE PZ-3 10/08/2011 WATER 1.51 E+3 N/A N/A N/A N/A N/A N/A N/A GWP-3 10/08/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-4 10/08/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-5A 10/08/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 10/08/2011 WATER 3.45E+4 N/A N/A N/A N/A N/A N/A N/A GWP-7 10/08/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-8 10/08/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-9 10/08/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 10/09/2011 WATER 3.29E+4 N/A N/A N/A N/A N/A N/A N/A GWP-4 10/09/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 10/09/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 10/10/2011 WATER 1.40E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 10/10/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 10/10/2011 WATER 3.51E+4 N/A N/A N/A N/A N/A N/A N/A PZ-3 10/11/2011 WATER 1.59E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 10/11/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 10/11/2011 WATER 3.65E+4 N/A N/A N/A N/A N/A N/A N/A GWP-6 10/13/2011 WATER 3.54E+4 N/A N/A N/A N/A N/A N/A N/A GWP-4 10/13/2011 WATER 1.37E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 10/13/2011 WATER 1.91 E+3 N/A N/A N/A N/A N/A N/A N/A TURBINE BLDG TUNNEL 10/13/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A SWITCH GEAR 10/13/2011 WATER 1.67E+3 N/A N/A N/A N/A N/A N/A N/A 26 ATTACHMENT 8 RESULTS OF GROUND WATER PROTECTION INITIATIVE SAMPLE ANALYSIS (01/11 - 12/11) 4th Quarter 2011 Sample Gamma -Alh Sample Date Sampledia H-3 Emitting 1-131 Sr-89/90 Fe-55 Ni-63 AlphaTRU Pu-241 Particulates GWP-6 10/14/2011 WATER 3.94E+4 N/A N/A N/A N/A N/A N/A N/A GWP-4 10/14/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 10/14/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A MUD PUDDLE 10/14/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 10/16/2011 WATER 1.82E+4 N/A N/A N/A N/A N/A N/A N/A PZ-3 10/16/2011 WATER 1.48E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 10/16/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 10/17/2011 WATER 1.62E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 10/17/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 10/17/2011 WATER 3.97E+4 N/A N/A N/A N/A N/A N/A N/A GWP-4 10/18/2011 WATER 1.60E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 10/18/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 10/18/2011 WATER 3.82E+4 N/A N/A N/A N/A N/A N/A N/A GWP-6 10/19/2011 WATER 3.55E+4 N/A N/A N/A N/A N/A N/A N/A GWP-6(') 10/19/2011 WATER 3.56E+4 N/A N/A N/A N/A N/A N/A N/A GWP-4 10/19/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 10/19/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-2 10/20/2011 WATER INSUFFICIENT VOLUME TO SAMPLE PZ-1 10/20/2011 WATER INSUFFICIENT VOLUME TO SAMPLE PZ-3 10/20/2011 WATER 1.39E+3 ND(2) ND(2) N/A N/A N/A N/A N/A GWP-3 10/20/2011 WATER ND ND(2) ND(2) N/A N/A N/A N/A N/A GWP-4 10/20/2011 WATER 1.31 E+3 ND(2) ND(2) N/A N/A N/A N/A N/A GWP-5A 10/20/2011 WATER ND ND(2) ND(2) N/A N/A N/A N/A N/A GWP-6 10/20/2011 WATER 3.55E+4 ND(2) ND(2) N/A N/A N/A N/A N/A GWP-7 10/20/2011 WATER 1.30E+3 ND(2) ND(2) N/A N/A N/A N/A N/A GWP-7(') 10/20/2011 WATER ND ND(2) ND(2) N/A N/A N/A N/A N/A GWP-8 10/20/2011 WATER ND ND(2) ND(2) N/A N/A N/A N/A N/A GWP-9 10/20/2011 WATER ND ND(2) ND(2) N/A N/A N/A N/A N/A U-1 MAT SUMP EAST 10/20/2011 WATER ND ND(2) ND(2) N/A N/A N/A N/A N/A U-1 MAT SUMP SOUTH 10/20/2011 WATER ND ND(2) ND(2) N/A N/A N/A N/A N/A U-1 ABGWMS 10/20/2011 WATER ND ND(2) ND(2) N/A N/A N/A N/A N/A U-2 MAT SUMP INSIDE 10/20/2011 WATER ND ND(2) ND(2) N/A N/A N/A N/A N/A U-2 MAT SUMPND2 ND* OUTSIDE 10/20/2011 WATER ND ND( 2 ) ND( 2 ) N/A N/A N/A N/A N/A U-2 ABGWMS 10/20/2011 WATER ND ND(2) ND(2) N/A N/A N/A N/A N/A DISCHARGE CANAL STORM DAN 10/20/2011 WATER 1.60E+3 N/A N/A N/A N/A N/A N/A N/A STORM DRAIN U-i INTAKE STORM 10/20/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A DRAIN__ U-2 INTAKE STORM DRAIN 10/20/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A DR2INAIN STORM__ SUBSURFACE DRAINS 10/20/2011 WATER 1.60E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 10/21/2011 WATER 2.OOE+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 10/21/2011 WATER 2.35E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 10/21/2011 WATER 3.66E+4 N/A N/A N/A N/A N/A N/A N/A (1) Re-analysis. (2) Volume counted was 100 mL. This was for DOT classification for shipment to vendor for boron analysis only. No effort was made to achieve environmental LLD. 27 ATTACHMENT 8 RESULTS OF GROUND WATER PROTECTION INITIATIVE SAMPLE ANALYSIS (01/11 - 12/11) 4th Quarter 2011 Sample Gamma - Sample Date Media H-3 Emitting 1-131 Sr-89/90 Fe-55 Ni-63 AlphaTRU Pu-241 Particulates PZ-3 10/23/2011 WATER 1.45E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 10/23/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 10/23/2011 WATER 3.46E+4 N/A N/A N/A N/A N/A N/A N/A PZ-3 10/24/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-4 10/24/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 10/24/2011 WATER 3.57E+4 N/A N/A N/A N/A N/A N/A N/A PZ-3 10/25/2011 WATER 1.70E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 10/25/2011 WATER 1.91 E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 10/25/2011 WATER 3.76E+4 N/A N/A N/A N/A N/A N/A N/A PZ-3 10/26/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-4 10/26/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 10/26/2011 WATER 2.94E+4 N/A N/A N/A N/A N/A N/A N/A PZ-3 10/27/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-4 10/27/2011 WATER 1.87E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 10/27/2011 WATER 3.51E+4 N/A N/A N/A N/A N/A N/A N/A PZ-3 10/28/2011 WATER 1.41 E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 10/28/2011 WATER 1.85E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 10/28/2011 WATER 3.07E+4 N/A N/A N/A N/A N/A N/A N/A GWP-6 10/30/2011 WATER 3.16E+4 N/A N/A N/A N/A N/A N/A N/A GWP-4 10/30/2011 WATER 1.50E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 10/30/2011 WATER 1.76E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 10/31/2011 WATER 3.73E+4 N/A N/A N/A N/A N/A N/A N/A GWP-4 10/31/2011 WATER 1.67E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 10/31/2011 WATER 1.34E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 11/01/2011 WATER 3.37E+4 N/A N/A N/A N/A N/A N/A N/A GWP-4 11/01/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 11/01/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 11/02/2011 WATER 3.16E+4 N/A N/A N/A N/A N/A N/A N/A GWP-4 11/02/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 11/02/2011 WATER 1.37E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 11/03/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-4 11/03/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 11/03/2011 WATER 3.05E+4 N/A N/A N/A N/A N/A N/A N/A PZ-3 11/04/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-4 11/04/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 11/04/2011 WATER 3.32E+4 N/A N/A N/A N/A N/A N/A N/A GWP-6 11/07/2011 WATER 3.37E+4 N/A N/A N/A N/A N/A N/A N/A GWP-4 11/07/2011 WATER 2.12E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 11/07/2011 WATER 1.65E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 11/08/2011 WATER 3.89E+4 N/A N/A N/A N/A N/A N/A N/A GWP-4 11/08/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 11/08/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A 28 ATTACHMENT 8 RESULTS OF GROUND WATER PROTECTION INITIATIVE SAMPLE ANALYSIS (01/11 - 12/11) 4th Quarter 2011 Sample H-I Gamma - Alpha Sample Date Mpedi H-3 Emitting 1-131 Sr-89/90 Fe-55 Ni-63 Alh Pu-241 Particulates I I I I I PZ-2 11/09/2011 WATER INSUFFICIENT VOLUME TO SAMPLE PZ-1 11/09/2011 WATER INSUFFICIENT VOLUME TO SAMPLE GWP-3 11/09/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-4 11/09/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 11/09/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-SA 11/09/2011 WATER 1.54E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 11/09/2011 WATER 4.06E+4 N/A N/A N/A N/A N/A N/A N/A GWP-4 11/10/2011 WATER 1.39E+3 N/A N/A N/A N/A N/A N/A N/A PZ-3 11/10/2011 WATER 1.39E+3 N/A N/A N/A N/A N/A N/A N/A GWP-5A 11/10/2011 WATER 1.67E+3 N/A N/A N/A N/A N/A N/A N/A GWP-6 11/10/2011 WATER 3.58E+4 N/A N/A N/A N/A N/A N/A N/A GWP-7 11/10/2011 WATER 1.47E+3 N/A N/A N/A N/A N/A N/A N/A GWP-8 11/10/2011 WATER 2.4E+3 N/A N/A N/A N/A N/A N/A N/A GWP-9 11/10/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 11/14/2011 WATER 1.37E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 11/14/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 11/14/2011 WATER 4.19E+4 N/A N/A N/A N/A N/A N/A N/A GWP-8 11/14/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 11/15/2011 WATER 1.68E+3 N/A N/A N/A N/A N/A N/A N/A GWP-4 11/15/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-5A 11/15/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 11/15/2011 WATER 3.49E+4 N/A N/A N/A N/A N/A N/A N/A PZ-3 11/17/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-4 11/17/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 11/17/2011 WATER 3.46E+4 N/A N/A N/A N/A N/A N/A N/A PZ-3 11/18/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-4 11/18/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 11/18/2011 WATER 3.68E+4 N/A N/A N/A N/A N/A N/A N/A PZ-3 11/21/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-4 11/21/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 11/21/2011 WATER 3.52E+4 N/A N/A N/A N/A N/A N/A N/A PZ-3 11/23/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-4 11/23/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 11/23/2011 WATER 4.01E+4 N/A N/A N/A N/A N/A N/A N/A PZ-2 12/01/2011 WATER INSUFFICIENT VOLUME TO SAMPLE PZ-1 12/01/2011 WATER INSUFFICIENT VOLUME TO SAMPLE GWP-3 12/01/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 12/01/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-4 12/01/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-5A 12/01/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 12/01/2011 WATER 4.18E+4 N/A N/A N/A N/A N/A N/A N/A GWP-7 12/02/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-8 12/02/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-9 12/02/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A 29 ATTACHMENT 8 RESULTS OF GROUND WATER PROTECTION INITIATIVE SAMPLE ANALYSIS (01/11 - 12/11) 4 th Quarter 2011 Sample Gamma - I Alpha Sample Date aMpled H-3 Emitting 1-131 Sr-89/90 Fe-55 Ni-63 TRU Pu-241 Particulates I I I I PZ-2 12/08/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-1 12/08/2011 WATER INSUFFICIENT VOLUME TO SAMPLE GWP-3 12/08/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 12/08/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-4 12/08/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-SA 12/08/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 12/08/2011 WATER 4.32E+4 N/A N/A N/A N/A N/A N/A N/A GWP-7 12/08/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-8 12/08/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-9 12/08/2011-WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-2 12/15/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-1 12/15/2011 WATER INSUFFICIENT VOLUME TO SAMPLE GWP-3 12/15/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 12/15/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-4 12/15/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-5A 12/15/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 12/15/2011 WATER 4.60E+4 ND ND N/A N/A N/A N/A N/A GWP-7 12/15/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-8 12/15/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-9 12/15/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A GWP-6 12/22/2011 WATER 4.33E+4 N/A N/A N/A N/A N/A N/A N/A SUBSURFACE DRAINS 12/22/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-2 12/23/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-3 12/23/2011 WATER ND N/A N/A N/A N/A N/A N/A N/A PZ-2 (VENDOR) 12/23/2011 WATER ND ND ND N/A N/A N/A N/A N/A PZ-3 (VENDOR) 12/23/2011 WATER ND ND ND N/A N/A N/A N/A N/A GWP-6 12/22/2011 WATER 4.33E+4 N/A N/A N/A N/A N/A N/A N/A GWP-6 (VENDOR) 12/22/2011-WATER 4.85E+4 ND ND ND ND ND ND ND 12/23/2011 - GWP-6 (VENDOR) 12/22/2011-WATER 5.33E+4 N/A N/A N/A N/A N/A N/A N/A 12/23/20 11 1_____ BTW-1 (VENDOR) 12/26/2011 WATER ND ND ND N/A N/A N/A N/A N/A BTW-2 (VENDOR) 12/26/2011 WATER ND ND ND N/A N/A N/A N/A N/A BTW-4 (VENDOR) 12/26/2011 WATER ND ND ND N/A N/A N/A N/A N/A TTW-1 (VENDOR) 12/26/2011 WATER INSUFFICIENT VOLUME TO SAMPLE TTW-2 (VENDOR) 12/26/2011 WATER ND ND ND N/A N/A N/A N/A N/A TTW-3 (VENDOR) 12/26/2011 WATER ND ND ND N/A N/A N/A N/A N/A TTW-4 (VENDOR) 12/26/2011 WATER ND ND ND N/A N/A N/A N/A N/A TTW-5 (VENDOR) 12/26/2011 WATER ND ND ND N/A N/A N/A N/A N/A GWP-6 12/29/2011 WATER 4.90E+4 N/A N/A N/A N/A N/A N/A N/A 30 ATTACHMENT 9 CARBON-14 CALCULATIONS (01/11 - 12/11) Carbon-1 4,C-1 4, is a naturally occurring isotope of carbon produced by cosmic ray interactions in the atmosphere. Nuclear weapons testing in the 1950s and 1960s significantly increased the amount of C-1 4 in the atmosphere. Due to its long half-life, 5730 years, a significant portion of the C-14 from this testing is still present in the environment. C-1 4 is also produced in commercial nuclear reactors, but the amounts produced are much less than those produced naturally or from weapons testing. In Regulatory Guide 1.21, Revision 2, "Measuring, Evaluating, and Reporting Radioactive Material in Liquid and Gaseous Effluents and Solid Waste", the NRC has recommended that U.S. nuclear power plants evaluate whether C-1 4 is a "principal radionuclide", and if so, report the amount of C-1 4 released. At North Anna, improvements over the years in fuel performance have resulted in a decrease in the amount and distribution radionuclides released to the environment in gaseous effluents. As a result, C-14 has become a "principal radionuclide" for the gaseous effluent pathway at North Anna, as defined in Regulatory Guide 1.21, Rev. 2. Because the dose contribution of C-14 to liquid radioactive waste is a small fraction of the dose compared to other nuclides, evaluation of C-1 4 in liquid effluents is not required by Ref. Reg. Guide 1.21, Rev. 2. The quantity of gaseous C-1 4 released to the environment can be estimated by use of a C-1 4 source term scaling factor based on power generation. North Anna utilized methodology in EPRI Report, Estimation of C-1 4 in Nuclear Power Gaseous Effluents. Based on this document, at full capacity, North Anna would generate and release about 23 Ci of C-1 4 per year. Since the units did not operate at full power for 100% of the year, this value was corrected for the capacity factor of each unit yielding an estimated 16.1 Ci of C-14 produced and released. North Anna assumed that the fractional release of gaseous C-14 in any quarter and pathway could be approximated by the fraction of noble gasses released via that pathway in that quarter. Most C-14 species initially produced in a PWR are organic, e.g., methane. C-14 releases in PWRs occur primarily as a mix of organic carbon and carbon dioxide released from the waste gas system. C-14 in the primary coolant is essentially all organic with a large fraction as a gaseous species. Any time the RCS liquid or gas is exposed to an oxidizing environment, a slow transformation from an organic to an inorganic chemical form can occur. Various studies documenting measured C-1 4 releases from PWRs suggest a range of 70% to 95% organic. North Anna used a value of 70% organic and 30% CO2 in its calculations. 31 Public dose estimates from airborne C-14 were performed using dose models in NUREG-0133 and Regulatory Guide 1.109. The estimated C-14 dose impact on the maximum organ dose from airborne effluents released at North Anna is estimated to be 5.78E-2 mrem from the inhalation pathway, or 3.85E-03%TS of the 1500 mrem/yr dose rate limit and 8.15E-01 mrem from the ingestion pathway or 2.72% of the 10CFR50, Appendix I, ALARA design objective of 15 mrem/yr per unit. In both cases the critical organ was determined to be the child's bone. 32