ML11346A528
| ML11346A528 | |
| Person / Time | |
|---|---|
| Site: | Indian Point |
| Issue date: | 12/12/2011 |
| From: | Edson J, Jackson J, Roberts E, Udy A Idaho National Engineering Lab (INEL), Office of Nuclear Regulatory Research |
| To: | |
| SECY RAS | |
| References | |
| RAS 21523, 50-247-LR, 50-286-LR, ASLBP 07-858-03-LR-BD01, NYS000012, Job Code A6389 INEL-95/0573, NUREG/CR-5753 | |
| Download: ML11346A528 (66) | |
Text
i Aging of Safety Class iiE Transformers in i
iSafety Systems of
,Nuclear Power Plants
- Prepared by
. E. W. Roberts, J. L. Edson, A. C. Udy
- Idaho National Engineering Laboratory Lockheed Idaho Technologies Company Prepared for U.S. Nuclear Regulatory Commission DISTRIBUTiON OF THIS DOCUMENT IS UNU~TEO <f'/Z
~--~--------- ~---- --.--
NUREG/CR-5753 INEL-95/0573 FEB 2 7 12~S 0ST' MASTER OAGI0001164_00001 NYS000012 Submitted: December 12, 2011
AVAILABILITY NOTICE Availability of Reference Materials Cited in NRC Publications Most documents cited In NRC publications will be available from one of the following sources;
- 1.
The NRC Public Document Room. 2120 L Street. NW.* Lower Level. Washington. DC 20555-0001
- 2.
The Superintendent of Documents. U.S. Government Printing Office. P. O. Box 37082, Washington. DC 20402-9328
- 3.
The NatIonal Technical Information Service. Springfield. VA 22161-0002 Although the Ifsting that follows represents the majority of documents cited in NRC publications. it is not in-tended to be exhaustive.
Referenced documents available for inspection and copying for a fee from the NRC Public Document Room include NRC correspondence and internal NRC memoranda; NRC bulletins. circulars. information notices. in-spection and investigation notices; licensee event reports: vendor reports and correspondence: Commission papers; and applicant and licensee documents and correspondence.
The following documents In the NUREG series are available for purchase from the Government Printing Office:
formal NRC staff and contractor reports. NRC-sponsored conference proceedings. international agreement reports, grantee reports. and NRC booklets and brochures. Also available are regulatory guides. NRC regula-tions In the Code of Federal Regulations, and Nuclear Regulatory Commission Issuances.
Documents available from the National Technical Information Service include NUREG-series reports and tech-nical reports prepared by other Federal agencies and reports prepared by the Atomic Energy Commission, forerunner agency to the Nuclear Regulatory Commission.
Documents available from public and special technical libraries include all open literature items. such as books.
journal articles, and transactions. Federal Register notices. Federal and State legislation. and congressional reports can usually be obtained from these libraries.
Documents such as theses. dissertations. foreign reports and translations, and non-NRC conference pro-ceedings are available for purchase from the organization sponsoring the publication cited.
Single copies of NRC draft reports are available free, to the extent of supply. upon written request to the Office of Administration. Distribution and Mail Services Section. U.S. Nuclear Regulatory Commission. Washington.
DC 20555-0001.
Copies of Industry codes and standards used in a substantive manner in the NRC regulatory process are main-tained at the NRC Ubrary. Two White Flint North. 11545 Rockville Pike, Rockville. MD 20852-2738. for use by the public. Codes and standards are usually copyrighted and may be purchased from the originating organiza-tion or, if they are American National Standards. from the American National Standards Institute. 1430 Broad-way, New York. NY 10018-3308.
DISCLAIMER NOTICE This report was prepared as an account of work sponsored by an agency of the United States Govemment.
Neitherthe United States Govemment nor any agency thereof, nor any oftheiremployees, makes any warranty, expressed or implied, or assumes any legal liability or responsibility for any third party's use, orthe results of such use, of any information, apparatus. product, or process disclosed in this report, or represents that its use by such third party would not infringe privately owned rights.
OAGI0001164_00002
Aging of Safety Class IE Transformers in Safety Systems of Nuclear Power Plants Manuscript Completed: November 1995 Date Published: February 1996 Prepared by E. W. Roberts, J. L. Edson, A C. Udy Idaho National Engineering Laboratory Lockheed Idaho Technologies Company Idaho Falls, ill 83415 J. Jackson, NRC Project Manager Prepared for Division of Engineering Technology Office of Nuclear Regulatory Research U.S. Nuclear Regulatory Commission Washington, DC 20555-0001 NRC Job Code A6389 NUREG/CR-5753 INEL-95/0573 OAGI0001164_00003
OAGI0001164_00004
ABSTRACT This report discusses aging effects on safety-related power transformers in nuclear power plants. It also evaluates maintenance, testing, and monitoring prac-tices with respect to their effectiveness in detecting and mitigating the effects of aging. The study follows the U.S. Nuclear Regulatory Commission's (NRC's)
Nuclear Plant-Aging Research approach. It investigates the materials used in trans-former construction, identifies stressors and aging mechanisms, presents operating and testing experience with aging effects, analyzes transformer failure events reported in various databases, and evaluates maintenance practices. Databases maintained by the nuclear industry were analyzed to evaluate the effects of aging on the operation of nuclear power plants.
iii NUREG/CR-5753
<----~-- ~--=----~---::---------::-----------
OAGI0001164_00005
OAGI0001164_00006
CONTENTS ABSTRACT............. *........ *..............................................
iii LIST OF FIGURES................... *............................ *..............
vii LIST OF TABLES.*.................................................. *........ *..
vii EXECUTIVE
SUMMARY
ix
- 1.
INTRODUCTION........................................ *........ *. *........
1
- 2.
POWER TRANSFORMERS....*....................*.........................
3 2.1 Transformer Construction.............**.................................
3 2.1.1 2.1.2 2.1.3 2.1.4 2.1.5 Core and Windings.....................................*..*.....
Solid Insulation.................................................
Insulating/Cooling Medium..*.......................*............
Transformer Bushings....................*....*.......*..........
Transformer Tank (enclosure)......**.....................*........
3 3
5 7
7 2.2 Transformer Cooling Systems.............................................
7 2.3 Load Tap Changers.....................................................
- 8
- 3.
SIGNIFICANCE OF AGING. *.................................................
15 3.1 Major Transformer Components...........................................
15 3.2 Construction Materials................................................ *..
18 3.3 Transformer Loading....................................................
18 3.4 Transformer Capacity Considerations.......................................
18
- 4.
TRANSFORMER AGING MECHANISMS.................................**...*
21
- 5.
REVIEW OF OPERATING EXPERIENCE.................**.......*....*...*...
24 5.1 Types, Applications, and Descriptions of Safety Class IE Power Transformers.......
25 5.2 Transformer Age....*..................................................
25 5.3 Transformer Problems, Failures, and Replacements................*...........
25 5.4 Trends.............................. *................... *.............
27 5.5 NRC IE Information Notices..................*...........................
27 5.6 Summary.................................................... *........
28
- 6.
TRANSFORMER RISK ANALYSIS........ *.......... *.........................
30 v
NUREG/CR-5753 OAGI0001164_00007
- 7.
TRANSFORMER INSPECTION, SURVEILLANCE, MONITORING, AND MAIN1ENANCE....**...*...**.............**....*...*....*................
31 7.1 Guidance for Maintenance, Surveillance, Monitoring, and Inspection.............,
31 7.1.1 Oil-Filled Transformers.....*.................*..*.............*.
31 7.1.2 Dry-Type Transformers. *.... *.... * *................. * *. * *. *......
38 7.1.3 Gas-Cooled Transformers.......................... * *..... *... *...
40 7.2 Current Maintenance Practices for Safety Class IE Transformers *.*.*............
41 7.3 Comparison of Typical and Current Maintenance Practices.....*.............*.*
41 7.4 Functional Indicators of Transformer Degradation...............*....***..*.*.
42
- 8.
REVIEW OF STANDARDS, GUIDES, AND DESIGN CRITERIA RELATED TO TRANSFORMER AGING......**....*.....*...............*.....*...*.*...**.
43
- 9.
CONCLUSIONS... *...................................... *.. *. * *.. * *. *.....
50
- 10. BffiLIOGRAPHY............................................................
52 NUREG/CR-S7S3 vi OAGI0001164_00008
LIST OF FIGURES 2-1. Typical nuclear power station electrical diagram....................................
4 2-2. Basic components of a power transformer.........................................
5 2-3. Electrical diagram of power transformer load tap changer................... *.........
8 3-1. Comparison of windings used for core-and shell-form transformers....................
17 5-1. Class IE and nonclass 1E power transformer problems and failures listed by year...... *...
28 LIST OF TABLES 2-1. Components for air-cooled power transformer.. * * *....... * *....... * *. *....... *.....
9 2-2. Components for nitrogen-or fluorogas-cooled power transformer...............*.....*
10 2-3. Components for low voltage <<15 kV) fluid cooled power transformer..................
11 2-4. Components for high voltage (> 15 kV) mineral oil-cooled power transformer........*...
12 2-5. Components of power transformer cooling systems...... *...........................
14 3-1. Components of power transformers and materials of construction.....*................
16 3-2. Component stressors and failure mechanisms..........*.........................*.
19 5-1. Type cooling for NPRDS-listed Class IE power transformers..........................
25 5-2. Voltage ratings of NPRDS-listed power transformers....*...........................
25 5-3. Age of NPRDS-listed safety Class IE power transformers *...........................
25 5-4. Reported safety-related transformer problems.****..**..*.*.......**...............
26 5-5. Transformer problems by cooling type (1983 through May 1991)..........*........**.
27 7-1. Maintenance intervals for oil-filled transformers.....................*..............
32 7-2. Maintenance intervals for dry-type transformers....*.............*.................
39 7-3. Maintenance intervals for gas-cooled transformers.*........*........*..............
41 7-4. Maintenance practices for oil-filled transformers at a typical nuclear power station.........
42 7-5. Functional indicators of transformer degradation............. *......................
42 8-1. Acceptance criteria and guidelines for electric power transformers........ *... *.........
43 8-2. Industry standards applicable to Class IE power transformers.....***...........**....
44 vii NUREG/CR-5753 OAGI0001164_00009
OAGI0001164_00010
EXECUTIVE
SUMMARY
Power transformers of various sizes and types operate in the Class IE power systems at nuclear facilities throughout the United States. Continued safe and reliable operation of these transformers is critical to the overall safe operation of the nuclear facility. Therefore, it is important to iden-tify the aging mechanisms and their effects that can lead to transformer failure and to implement maintenance and testing practices that can identi-fy and alleviate the effects of these aging mechanisms.
This report describes a study that was spon-sored by the U.S. Nuclear Regulatory Commis-sion and performed at the Idaho National Engineering Laboratory to evaluate aging effects on Class IE power distribution transformers in nuclear power plants. The study identifies materi-als used in transformer construction, stressors, and aging mechanisms; presents data on Class IE transformer failure events as reported in various databases; and compares current transformer maintenance and testing procedures.
Transformer data from the NRC Licensee Event Reports (LERs), the Nuclear Plant Reli-ability Data System (NPRDS), and the Nuclear Power Experience data system were reviewed to determine if evidence of transformer aging effects could be found in the nuclear plant operat-ing experience. A cooperating utility provided manufacturing data, operating experience data, and maintenance information for the study. Main-tenance practices and scheduling information were obtained from an operating nuclear station.
Using the information from the above sources, transformer records were examined for 88 plants for the years of 1983 through 1990. During this period, 33 disabling problems and failures were reported on the 723 Class IE power transformers listed in the NPRDS. Five of the reported incidents resulted in reportable events (LERs).
The data for the 88 plants also show that 95% of the Class I E transformers were under 20 years old, and nearly 75% are less than 15 years old.
The low number of problems occurring on the Class IE power transformers give little indication ix that the aging of transformers is causing signifi-cant problems or that there is an increasing num-ber of problems and failures. However, because of the relative young age of the Class IE trans-formers it is difficult to determine if this is an accurate picture of the effects of transformer aging at the nuclear plants.
A standard probabilistic risk assessment (PRA) was reviewed to determine the risk significance of Class IE transformers and the potential for aging to increase the risk significance. The fault trees for the PRA included transformers along with other Class IE components. Truncation of the cut sets still left the transformers as poten-tially risk-significant components. Reevaluation with a unity failure probability for the most risk-significant type of transformer shows that aging of the transformer has the potential to signifi-cantly increase core damage frequency. Aging is an important factor for the most risk-significant transformers.
An example maintenance program was devel-oped for oil, gas, and air-cooled power trans-formers using industry and manufacturer's recommendations. The maintenance program for an operating nuclear station was examined and compared with the developed program. The pro-gram compared favorably with the example program, with only minor deviations.
It is our conclusion that there is no presently identified transformer aging mechanism that would cause a safety concern. If nuclear plants use currently recognized monitoring and testing methods and follow a rigorous surveillance, test-ing, maintenance, and replacement program (based on current and future manufacturers and industry guidelines) the effects of transformer aging will not increase the risk to nuclear plant safety. These conclusions are based on our review of (a) the transformer aging mechanisms, (b) the accepted transformer monitoring and testing methods, (c) the manufacturer's and industry transformer maintenance and surveillance guide-lines, (d) the current transformer surveillance and maintenance practices at an operating nuclear NUREG/CR-5753 OAGI0001164_00011
station, and (e) the transformer plant operating experience for 88 nuclear plants.
However, it is our opinion that owing to the age of the Class 1 E power transformers in use at nuclear plants (which are relatively young in comparison to the expected transformer life), the past operating experience may not truly reflect NUREG/CR-5753 x
the effects of transformer aging or the current surveillance and maintenance practices in the industry. Review of plant operating data (approxi-mately every 5 years) would be useful in deter-mining if present information remains accurate and in determining if any significant unidentified trends are developing.
OAGI0001164_00012
Aging of Safety Class 1 E Transformers in Safety Systems of Nuclear Power Plants
- 1. INTRODUCTION The U.S. Nuclear Regulatory Commission (NRC) initiated the Nuclear Plant-Aging Research Program (NPAR) to obtain a better understanding of how degradation caused by ag-ing of key components could affect nuclear plant safety, if not corrected before loss of functional capability, and how the aging process may change the likelihood of component failures in systems that mitigate transients and accidents. The possi-bility of aging degradation causing accidents is also a concern.
This report presents an engineering study of power transformers used in safety-related appli-cations. While the IE power system includes other transformers, such as current, potential, control, and instrumentation transformers, these transformers are not included in this study. Con-trol transformers, which are commonly found in motor control centers, are included in an aging assessment of motor control centers reported in NUREG/CR-5053. Control transformers are sim-ilar to current and potential transformers. There-fore, this study focuses on power transformers.
The work supports the NPAR goals stated in NUREG-Il44, summarized as follows:
Identify and characterize aging and service-wear effects associated with electrical and mechanical components, interfaces, and systems likely to impair plant safety.
Identify and recommend methods of inspec-tion, surveillance, and condition monitoring of electrical and mechanical components and systems that will be effective in detecting significant aging effects before loss of safety function, so that timely main-tenance and repair or replacement can be implemented.
Identify and recommend acceptable mainte-nance practices that can be undertaken to 1
mitigate the effects of aging and to diminish the rate and extent of degradation caused by aging and service wear.
The NPAR Program is being conducted at several national laboratories, including the Idaho National Engineering Laboratory (INEL).
A nuclear plant typically has between 4 and 12 Class IE power transformers supplying the many safety-related systems and equipment.
Reliability of these transformers is essential to ensure continued safe operation of the plant. Even though sufficient redundancy is provided so that failure of only one transformer will not place the plant in an unsafe condition, the failure of one transformer does result in challenges to plant operation (such as reactor scram) and reduces the reliability and redundancy aspects of the IE power system. This study attempts to resolve two issues: (a) whether aging of transformers is expected to significantly reduce reliability during their installed lifetime, and (b) whether careful monitoring and maintenance would improve or ensure reliability over their service life.
Section 2 describes the power transformers themselves and the components they use; Sec-tion 3 describes the materials used; Section 4 reviews transformer failure modes; Section 5 reviews operating experience using various data-bases and plant specific information; Section 6 addresses transformer aging risk analysis; Section 7 discusses transformer inspection, surveillance, monitoring. and maintenance; Section 8 reviews standards, guides, and design criteria applicable to the Class IE power transformers; and Section 9 presents conclusions.
This study used two databases to evaluate the effects of aging on transformers in nuclear power plants: the Nuclear Power Experience database (NPE) and the Nuclear Plant Reliability Data System (NPRDS). In addition, Licensee Event NUREG/CR-5753 OAGI0001164_00013
Introduction Reports (LERs) were used to identify transfonn-ers failures that resulted in events that were reportable to the NRC. During this study, it was determined that the NPRDS was the only infonnation source with nameplate data on Class IE power transformers. For this reason, the NPRDS was used to identify specific types and ages of transformer that experienced failures. All of the infonnation sources were used to identify NUREG/CR-5753 2
failure causes and effects on plant operation.
Because this study was on the effects of power transfonner aging, the decision was made not to use the transformer data on plants placed in ser-vice after January 1, 1989. Subsequent review of NPRDS data shows that only 88 other plants had Class IE transformer nameplate data included in the database. The information from these plants was used in the study.
OAGI0001164 00014
- 2. POWER TRANSFORMERS Figure 2-1 shows a typical nuclear plant elec-trical distribution system with the associated power transformers. The maximum voltage for transformers, electrical buses, and electrical equipment within the dashed line is 15 kV. The voltages on the high-voltage winding (primary) of transformers, located outside the dashed line, varies between 15 and 500 kV, depending on the individual plants and the connected commercial power system.
During this study, NPRDS transformer records were reviewed for 88 nuclear plants. NPRDS event records and engineering data show that 19 of the plants list a total for 50 Class IE high-voltage (> 15 kV) transformers. The high-voltage rating for these transformers varied between 19 and 500 kYo The transformers use a liquid insula-tor/coolant, usually mineral oil. These high-voltage transformers have forced-air and forced-oil supplementary cooling. The 88 plants have 673 Class IE low-voltage <<15 kV) trans-formers, with 70 of these using liquid insulation/
coolant (mineral oil or noninflammable fluid), 50 using a flourogas insulation/coolant, and 553 using air as the insulation/coolant. A review of the electrical diagrams for several of the 19 plants listed as having 1E high-voltage transformers and conversations with persons with inplant experi-ence indicate that none of these high-voltage transformers are likely to be actually classified as IE. However. with the exception of some of the auxiliary equipment on the high-voltage trans-formers. such as load tap changers and forced-oil cooling. descriptions and failure mechanisms are generally applicable to both high-and low-voltage liquid-filled transformers. In addition, failure of these nonsafety-related transformers usually has a significant impact on the operation of the plant, such as reactor scram, actuation of emergency power sources, or loss of redundancy.
Therefore. the high-voltage transformers classi-fied as IE by NPRDS, though probably not actu-ally IE, will be included in this report.
Although individual plants have different power supply circuitry and corresponding 3
different numbers and location of power trans-formers, the information on the construction, aging, and maintenance of transformers applies to all transformers used in nuclear plants.
The sections that follow describe the basic ele-ments of the Class IE power transformers for the 88 nuclear plants used in this study. Transformers have many special design and construction meth-ods for cores, windings, tanks, bushings, load tap changers, and other elements. No attempt has been made to describe these design and construc-tion methods.
2.1 Transformer Construction Figure 2-2 shows the basic components of power transformers. As the figure shows, the basic transformer components include a silicon-steel core, primary and secondary windings (with con-nections to the bushings), solid insulation, the win-ding/core insulator/coolant medium, a transformer tank enclosure, and the primary and secondary bushings. Tables 2-1 through 2-5, located at the end of Section 2 (beginning on page 9), show all of the components normally used for air, nitrogen, and fluorogas, and low-and high:voltage fluid-cooled transformers, respectively.
2.1.1 Core and Windings. Power transform-ers are constructed using separate copper or alu-minum primary and secondary windings on a silicon-steel core. Upon applying an ac voltage to the primary winding, a corresponding varying magnetic flux is created in the core. The magnetic flux in the core, in turn, induces a voltage on the secondary winding. Some transformers have mul-tiple windings allowing power to be transformed to different voltages. The input to output voltages are a direct ratio to the number of turns on each winding. The use of power transformers allows power to be transmitted at high voltages (reducing line losses) and then lowered to usable voltages.
2.1.2 Solid Insulation. To prevent electrical shorting between adjacent turns and between NUREG/CR-5753 OAGI0001164_00015
~
Q
~
w
.j::..
Transmission lines 6!
.............. Main transformer Maln::C Transmission IInesJ....
generator
""T" "'I!~I-----Unlt aux transformers
~ ~
System aux transfQ.([ller
. ) NC Note - Voltages vary with plant-specific designs. Voltage ranges are listed below.
A Bus voltage: 4160-13800 Vac B Bus voltage: 208-600 Vac C Bus voltage: 208-600 Vac D Bus voltage: 125 or 250 Vdo E Bus voltage: 120 or 240 Vac F Battery voltage: 125 or 250 Vdc MCC motor control center...
NO normally open NC normally closed
- - - - Class 1 E power system boundary F
o Manual ~e breaker I.-_J..<-__ -,
DC contror bus II Q
I Reactor protection channel Reactor protection channel CJ'!f!.~ 11! p_o_"!.e!_sy!!e..".!_b_o_u_n~aD!. _____ ______ ;- __
- _____________________ _
Tram 2 Train 1
- Traln 21s Identical to Train 1 C 148*WHT.l195-0I Figure 2*1. Typical nuclear power station electrical diagram.
~
~
- ?
~
~
low voltage bushings (2)
(secondary)
Power Transfonners High voltage bushings (2)
(primary)
Low voltage winding (secondary) r------..
Tank (enclosure)
Insulator/coolant medium I
I I
High voltage winding (primary)
L ______ J Winding and wire insulation T920696 Figure 2-2. Basic components of a power transformer.
separate windings, various methods and materials are used to provide the necessary dielectric strength (insulation) between the winding turns, the high-and low-voltage windings, the magnetic core, and other electrical conductive materials.
The insulating methods include applying layer insulation or coil insulation between parts of windings and applying tum insulation between individual or groups of strands forming a single turn. The materials used are described in Section 3 of this report.
2.1.3Insulating/Cooling Medium. The trans-former winding and wire insulation materials have the necessary dielectric strength to prevent electrical shorting between individual winding turns, the windings, the core, and other electrical conductive material. However, entry of contami-nating materials to the winding insulation is a threat to the transformer operation. Water is the most frequent contaminant experienced during transformer operation. All contaminants have the potential to reduce the dielectric strength of the winding insulation and can compromise the elec-trical insulation.
To prevent the entry of contaminating materi-als, the transformer solid insulation is surrounded by an insulation medium with a dielectric strength 5
as good as, or in some cases better than, the wind-ing insulation. Although different materials and designs are used in transformers, all power trans-formers use either a gas or liquid insulating medium to surround the solid insulation. These insulating mediums prevent the entry of contami-nants. In addition, the insulating medium serves another critical function; it transfers the heat gen-erated by core and winding losses to the atmo-sphere. Without this heat removal, the life of the solid insulating materials would be significantly reduced. Note also that because the liquids and gases are critical to cooling the transformer core, the terms type insulated and type cooled are interchangeable.
2.1.3.1 Liquid-Cooled Transformers.
The liquid coolants in power transformers are mineral oil or various low-flammability fluids.
Mineral oil has a characteristic of high dielectric strength, an ability to recover after high dielectric stress, and an excellent heat transfer capability.
Because of its high dielectric strength, mineral oil is used in all transformers with high voltages over 34 kV. In addition, because of its heat transfer capability, mineral oil is the most efficient medium to remove internal heat from power transformers and prevent excessive temperatures that shorten the life of the transformer. However, NUREG/CR-5753 OAGI0001164_00017
Power Transformers mineral oil is very flammable. Mineral oil-cooled transformers cannot be located where a transformer fire would be a hazard to other equipment or buildings. Mineral oil-cooled transformers are used for all high-voltage
(> 15 kV) transformers.
Although transformer oil is a highly refined product, it is not chemically pure. It is a mixture of hydrocarbons with other natural compounds, some of which are detrimental to the oil and oth-ers beneficial in retarding the oxidation of the oil.
Oil impurities are destructive to dielectric proper-ties. The most troublesome impurities are water, oxygen, and the many combinations of com-pounds formed by water and hydrogen (acids) at elevated temperatures. Under ideal conditions, only very small amounts of water will dissolve in a true solution with the oil. Small amounts of dis-solved water have little affect on the dielectric strength of the oil. However, the presence of acids increases the amount of water that will be dis-solved, reducing the dielectric strength of the oil accordingly. The oil-water solution will be subse-quently absorbed by the* paper and paperboard used in the winding insulation. The result will be a decrease in the dielectric strength of the insulat-ing materials and an accelerated aging of the paper. The problem of air and water in transformer oil can be minimized by eliminating them from, and keeping them out of, the trans-former oil. For this reason, all oil-cooled trans-formers are completely sealed. There are three basic methods used in nuclear plant transformers to perform these functions and permit normal expansion and contraction of the transformer oil without disturbing the integrity of the seal.
Leaving an air space above the oil in the sealed tank. The small amounts of water and oxygen present in the air will be absorbed, leaving a space filled with the nitrogen gas from the air. This method is used for transformers with voltages below 15 kV.
Although unconfirmed, it is believed that there are no Class 1 E transformers in the 88 plants reviewed that use this method to maintain the integrity of mineral oil-filled transformers.
Maintaining a pressurized nitrogen atmo-sphere above the oil in the sealed tank. A low nitrogen gas pressure is maintained using nitrogen cylinders, pressure gauges, and pressure regulators.
Using a sealedflexible diaphragm on top of the oil inside the sealed tank with an air space above the diaphragm. A flexible dia-phragm completes the seal between the oil in the tank and the air space. The diaphragm is able to accommodate expansion or con-traction of the oil and oil leaks.
The other types of fluids used for liquid insu-lated transformers are Askarel, silicones, high-flash-point hydrocarbons, chlorinated benzenes, or chlorofluorocarbons. Because of environmen-tal concerns, transformers using Askarel are no longer manufactured and are being phased out of service. The low flammability types of insulating fluids have a much lower dielectric constant and can only be used in transformers with a voltage less than 34 kV. These transformers do not trans-fer heat as well as mineral oil; however, they transfer heat much better than gas-insulated trans-formers. Transformers using these types of insu-lating fluids can be used inside of buildings.
These transformers use a sealed case with a gas space above the fluid.
2.1.3.2 Gas-Cooled Transformers (Dry).
Gas-cooled transformers, commonly known as dry type transformers, use air, fluorogas, or nitro-gen as the insulating coolant. Air has a low dielectric strength and low heat transfer capabil-ity. To make full use of the limited heat transfer capabilities of air, most transformers of this type are usually not sealed and are ventilated to the surrounding atmosphere. To prevent the intrusion of contaminants, including water, the transform-ers are located in a clean and dry atmosphere.
This type of transformer is used in nuclear plant Class IE power supply systems with a maximum voltage less than 15 kV.
Nitrogen-cooled transformers have dielectric and heat transfer characteristics similar to dry air.
Nitrogen insulated transformers require a sealed case; pressure monitoring instruments, and a OAGI0001164_00018
means to add nitrogen. They may be used in con-taminated atmospheres.
Fluorogas-cooled transformers have better dielectric strength and heat-transfer capacity than air or nitrogen. The dielectric strength and the heat-transfer capability increase with density of the fluorogas. For this reason, fluorogas-insulated transformers are used with the internal gas pres-sure above atmospheric pressure, in some cases with a 3-atm gauge pressure. As with the nitrogen insulated transformers, the fluorogas transformer requires a sealed transformer case, gas pressure monitoring instruments, and a means to add fluorogas. This type of transformer is used in place of air-cooled transformers in contaminated atmospheres where the space is limited and increased load handling capability is required.
2.1.4 Transformer Bushings. A transformer bushing is a structure that provides an insulated passageway through the transformer tank wall for an electrical conductor. The bushing allows exter-nal connections to be made to transformer inter-nal electrical parts without violating the tank internal integrity (sealing). The power trans-former bushings are designed with insulation capable of handling the dielectric stresses in the transition through the transformer tank to the con-nection to electric wire or cables. Porcelain is used for the exposed bushing surfaces. Bushings used outside andlor in contaminated atmospheres, are designed with one or more (depending on voltage and atmosphere) skirts to prevent normal moisture or other contamination from making an electrical path across the porcelain. As the volt-ages are increased, the transformer bushings require an increased dielectric strength. The bush-ings use insulation materials similar to those used in a transformer, including mineral oil in their internal construction.
2.1.5 Transformer Tank (enclosure). All power transformers have a steel enclosure for the winding and core. This enclosure provides both a physical barrier to the electric parts and a sealed container for the liquids and gases (excluding air) used as an insulator and coolant medium. The enclosures are made using both welded and 7
Power Transformers bolted steel plates. A transformer tank may enclose multiple windings and cores. Normally, a three-phase transformer will have the windings and cores for all three phases in one tank.
2.2 Transformer COOling Systems An important part in the operation of the trans-former is preventing high core/winding tempera-tures that would shorten the life of the electrical insulation. Almost all modem transformers have insulation systems designed for operation at 65°C average and 80°C hot spot winding temperature rise over an ambient temperature of 30°C. Older transformers were designed with a 55°C average and 65°C hot spot rise over a 30°C ambient tem-perature. All power transformers are designed to maintain the transformer temperatures within these limits when the transformer load is within the nameplate rating. There are three methods used to remove the winding/core heat from power transformers: (a) natural convection (self-cooled), (b) forced-air, and (c) forced-oil cooling.
A self-cooled transformer mayor may not have an external radiator(s); forced-air and forced-oil cooling requires them. Self-cooled is inherent, and forced-air cooling can be applied to all trans-formers. A forced-oil system uses a pump to move the hot oil above the windings and core to the forced-air cooling radiator. The cooled oil is returned to the bottom of the transformer. All of the 50 high-voltage transformers examined have forced-air and forced-oil cooling. Forced-oil cooling was not used on any lower voltage Class IE transformers. Each transformer has a self-cooled electrical load rating (kVa). Increas-ing kVa ratings are allowed for each additional cooling capability included on the transformer.
Secondary water cooling is also used on high-power transformers; however, this type of supple-mentary cooling is not used on any of the transformers for the plants reviewed. Forced-air and forced-oil cooling systems have temperature transducers, control systems, and fan/pump motors to maintain transformer temperatures below set limits. Note that the failure-of any forced cooling system requires the corresponding reduction in transformer loading.
~~~--_._~_.-
OAGI0001164_00019
Power Transfonners 2.3 load Tap Changers Anumberofthehigh.voltage (>15 kVA) trans*
fonners used in the nuclear plants have load tap changing (LTC) equipment. This equipment enables the transfonner to automatically maintain a constant voltage (+/-2.5%) for plant equipment under variable offsite power conditions. As shown in Figure 2*3, the regulation is perfonned by increasing or decreasing the active turns in the high-voltage winding. To prevent load interrup-tion, the change is made by shunting one winding load tap to another without opening the winding.
Although special methods are used to limit circu-Low voltage (secondary) i i
i !
i !
i !
1 i i i i !
1 1
! i i
i 1
i lating currents through the shunt and connecting contacts, a small amount of arcing is always pres-ent during the changing of taps. Because of the contact arcing, the load tap changer contacts and winding connections are always located in a sealed oil-filled compartment that is isolated from the transfonner core and windings. An external motor mechanism drives the internal shunting contacts. This mechanism includes the necessary gearing, mechanical coupling, cam-operated stepping switches, and other equipment to step the internal tap contacts. Voltage measuring and tap changer motor controls allow both a variable time delay and voltage operational band to pre-vent unnecessary wear of the system parts.
Stepping shunt
... 1 High voltage (Primary)
Figure 2-3. Electrical diagram of power transfonner load tap changer.
OAGI0001164_00020
Table 2-1.
Components for air-cooled power transfonner.
Component Windings Silicon-steel core Solid insulation Tank (enclosure)
Bushings Temperature indicator Radiator Fan(s) and motor(s)
Temperature transducer (contacts)
Fan motor controller(s)
Use High-and low-voltage windings.
Tertiary windings.
Contains magnetic flux for voltage induction between core windings.
Electrical insulation between winding turns, windings, and all electrical conductive materials.
Physical protection for electrical parts. May enclose multiple windings and cores.
Structure to provide for termina-tions and insulated pathway through transformer tank wall for electrical conductor.
Indication of interior and ambient temperatures.
Forced-air cooling.
Forced-air cooling.
Control of forced-air cooling.
Controls fan motors for forced-air cooling.
9 Power Transfonners Comments There may be multiple low-voltage windings.
Unsealed and normally ventilated to atmosphere.
Separate bushings are required for each connection to transformer winding.
May include alarm and contacts. Sensor location depends on design specifications.
Required for forced-air cooling.
Required for forced-air cooling.
May be included with temperature indicator.
NUREG/CR-5753 OAGI0001164 00021
Power Transformers Table 2-2.
Components for nitrogen-or fluorogas-cooled power transfonner.
Component Windings Silicon-steel core Solid insulation Tank (sealed enclosure)
Bushings Fluorogas insulator coolant cylinder(s)/
regulator/control Nitrogen insulator/
coolant cylinder(s)/
regulator/control Temperature indicator Radiator (fins)
Fan(s) and motor(s)
Temperature transducer (contacts)
Fan motor controller(s)
NUREGfCR-5753 Use High-and low-voltage windings.
Tertiary windings.
Contains magnetic flux for voltage induction between core windings.
Electrical insulation between winding turns, windings, and all electrical conductive materials Physical protection for electrical parts. May enclose multiple windings and cores.
Structure to provide for tennina-tions and insulated pathway through transfonner tank wall for electrical conductor.
Provides fluorogas, controls tank pressure, and provides indication of tank interior pressure.
Provides nitrogen gas, controls tank pressure, and provides indication of tank interior pressure.
Indication of interior and ambient temperatures.
Forced-air cooling.
Forced-air cooling.
Start-stop forced-air cooling.
Controls fan motors for forced-air cooling.
10 Comments There may be multiple low-voltage windings.
Sealed from outside atmosphere under nitrogen or fluorogas pressure.
Separate bushings are required for each circuit connection to transfonner winding.
Fluorogas insulated transfonners.
Nitrogen insulated transfonners.
May include alarm and contacts.
Sensor location depends on design specifications.
Required for forced-air cooling.
Required for forced-air cooling.
Required for forced-air cooling.
May be included with temperature indicator.
Required for forced-air cooling.
OAGI0001164_00022
Power Transfonners Table 2*3.
Components for low voltage <<15 kV) fluid cooled power transformer.
Component Wmdings Silicon-steel core Solid insulation Tank (sealed enclosure)
Bushings Insulator/coolant (mineral oil)
Insulator/coolant (nonflammable fluids)
Nitrogen blanket Use High-and low-voltage windings.
Tertiary windings.
Voltage induction between core windings.
Electrical insulation between winding turns, windings, and all electrical conductive materials.
Physical protection for electrical parts. May enclose multiple windings and cores. Contains cool-ant fins.
Structure to provide for termina-tions and insulated pathway through transformer tank wall for electrical conductor.
Provides dielectric insulation support, protection from contaminants, and a medium to remove winding/core heat. Used where fire does not present hazard to other equipment or buildings.
Provides dielectric insulation support, protection from contaminants, and a medium to remove winding/core heat.
Optional-Provides nitrogen gas blanket over the transformer fluid.
The blanket acts to prevent the entry of contaminants and allow for the expansion/contraction offluids.
11 Comments There may be multiple low volt-age windings.
Tank seals internal components from outside atmosphere. Uses a gas blanket to prevent the entry of air, water, and other contaminants.
Separate bushings are required for each circuit connection to transformer winding.
Mineral oil has a high dielectric strength, the ability to recover after dielectric stress, and is an excellent heat transfer medium.
Oil is flammable and is not used where a fire would present a hazard to equipment or facilities.
The nonflammable fluids used are siIicons, high-flash-point hydrocarbons, chlorinated benzenes, or chlorofluorocarbons.
Askarel is being phased out.
Silicons are used on modem transformers. These fluids have lower dielectric strength than mineral oil.
The equipment used for the system include gas cylinders, gas regulator, a pressure control, and a gas pressure indicator.
NUREG/CR-5753 OAGI0001164_00023
Power Transfonners Table 2-3.
(continued).
Component Temperature indicators Radiator (fins)
Air fanes) and motor(s)
Temperature transducer (contacts)
Fan motor controller(s)
Liquid level gauge Pressure relief valve Top liquid temperature gauge Use Comments Indicate bulk or hot spot May include alarm contacts.
temperature of windings.
Forced-air cooling.
Required for forced-air cooling.
Forced-air cooling.
Required for forced-air cooling.
Start-stop forced-air cooling.
Required for forced-air cooling.
May be included with temperature indicator.
Controls fan motors for forced-air Required for forced-air cooling.
cooling.
Indicates liquid level.
May include alarm/control contacts.
Automatic relief and reseal after high pressure in tank.
Indicates oil temperature at high point of oil.
May include alarm/control contacts.
May include alarm/control contacts.
Table 2-4.
Components for high voltage (> 15 kV) mineral oil-cooled power transformer.
Component Windings Silicon-steel core Solid insulation Tank (sealed enclosure)
NUREG/CR-5753 Use High-and low-voltage windings.
Tertiary windings.
Contains magnetic flux for voltage induction between core windings.
Electrical insulation between wind-ing turns, windings, and all electri-cal conductive materials. Contains mineral oil. Provides core support.
Physical protection for electrical parts. The tank may enclose multi-ple windings and cores. Contains mineral oil. Provides core support.
12 Comments There may be multiple low-voltage windings and windings for taps.
Tank seals internal components from outside atmosphere. Uses a gas blanket to prevent th~ entry of air, water, and other contaminants.
OAGI0001164_00024
Table 2*4. (continued).
Component Bushings Insulator/coolant (mineral oil)
Filter press, drain, and sampling valves Flexible diaphragm Radiator (fins)
Air fanes), motor(s),
temperature transducers, and controls Air fanes), motor(s),
temperature transducers, and controls Liquid level gauge Pressure/vacuum relief valves Top liquid temperature indicator Winding temperature indicator Rapid pressure rise relay Load tap changer Use Structure provides for terminations and insulated pathway through transformer tank wall for electrical conductor.
Provides dielectric insulation sup-port to winding insulation and acts as a medium to remove winding!
core heat.
Theses valves are required to allow the sampling and testing of the oil, the addition of oil, and filtering of contaminated oil.
Flexible synthetic-rubber dia-phragm is sometimes used over the mineral oil to prevent the entry of air/water/contaminants and allows the expansion and contraction of the oil without damaging the tank; maintains positive pressure.
Required for forced-air and forced-oil cooling.
Required for forced-air and forced-liquid cooling.
Required for forced-oil cooling.
Indication of liquid level.
Automatic relief and reseal after tank high/vacuum pressure.
Indication of oil temperature at high point of oil.
Indication of average winding or hot spot winding temperature.
Provides alarmltrip in the event of transformer failure.
Regulates output voltage to plant with varying off-site voltages.
13 Power Transfonners Comments The bushings are mineral oil-filled with a level gauge. Separate bushings are required for each cir-cuit connection to a transformer winding.
Mineral oil has a high dielectric strength, the ability to recover after dielectric stress, and is an excellent heat transfer medium.
Required for forced-air and forced-liquid cooling.
Required for forced-air and forced-liquid cooling Required for forced-air cooling.
Transducer input may be from oil temperature gauge contacts.
May include alarmlcontrol contacts.
May include alarmlcontrol contacts.
May include alarmlcontrol contacts.
May include alarmlcontrol contacts.
High maintenance item.
_~~_~_ ~ ___
~ _______. _____
~._,_, -------c------
---.~-----.
OAGI0001164_00025
Power Transfonners Table 2*5.
Components of power transformer cooling systems.
Required by coolant system Forced-air-Forced-oil Self-cooled cooled cooled Component (AA)
(FA)
(Fo)a Gas heat exchanger(s)-air, nitrogen, or No Yes No fluorogas-cooled transformers Liquid heat exchanger(s)-oil or No Yes Yes nonflammable liquid cooled transformers Temperature transducers Optional Yes Yes Control system(s)
No Yes Yes Fan(s) and motor(s)
No Yes Design dependentb Pump(s) and motor(s)
No No Yes Temperature indicator(s)
Yes Yes Yes
- a.
Forced-oil cooling is only used on high-voltage transfonners (>15 kY).
- b. Nonnally yes for transfonners rated ~ 15 kV.
NUREG/CR-5753 14 OAGI0001164_00026
- 3. SIGNIFICANCE OF AGING Aging of Class 1 E transfonners has the poten-tial to degrade their ability to meet design require-ments. General Design Criteria 17 of 10 CFR 50, speaks in general tenns of requirements placed on transformers. The IE power system, including transfonners, must have sufficient capacity and capability to ensure adequate protection of the reactor core, reactor coolant pressure boundary, and the containment integrity. In addition, suffi-cient independence, redundancy, and testability must be provided to perform their safety func-tions assuming a single failure. Aging has the potential to affect the capability to provide rated capacity and to reduce the effectiveness of redun-dancy through aging degradation that is common to redundant transfonners. General Design Crite-ria 17 also requires the consideration of environ-mental conditions that are a result of accidents.
However, Class IE transformers are located in buildings and rooms that have controlled environ-ments that are independent of postulated acci-dents and, therefore, are not affected by this requirement.
Aging is a natural phenomenon and is highly related to the environmental conditions the trans-fonner encounters. Transfonner aging would be minimal if the transformer were not operating.
However, environmental conditions inherent with transformer operation cause components to degrade with time in service. Aging of trans-former insulation causes deterioration that can reduce the period a transfonner is capable of pro-ducing the needed capacity. In addition, as trans-fonners approach their end of life, deteriorated insulation becomes more susceptible to failures caused by electrical transients such as those caused by lightning and switching. Some aging mechanisms are reversible, and quality can be regained, such as moisture or impurities in the insulation oil that can be removed, while others are irreversible, such as deterioration of the cellu-losic paper used as insulating material. With an appropriate transfonner surveillance and mainte-nance program, the rate of aging can be mini-mized. Thus, the full design life of the transfonner can be achieved.
~---
15 3.1 Major Transformer Components A transfonner is composed of a magnetic core, electrical windings and tenninations, an enclo-sure, and insulation and coolant. Table 3-1 gives a brief description of these major components.
The magnetic circuit of a transformer com-prises mainly a core of laminations. There are two basic core lamination design types: the core-fonn type is typically used in power transfonners up to 50 MVA. and the shell-fonn type is typically used for transformers with ratings greater than 50 MVA. Figure 3-1 shows the two design types.
The cores used in modern transformers are improved versions of the fundamental designs developed early in the twentieth century. Most transfonner cores are constructed of thin sheets (approximately O.3-mm thick) of grain-oriented, 3% silicon steel. Steel is used because it carries and confines the magnetic field better than air or other low cost materials. The industry is exper-imentaIIy using an amorphous steel developed by Allied-Signal, Inc. The amorphous steel, called Metglass, has greatly reduced core losses over conventional silicon steels.
Early transfonners used thick laminations of soft iron. Excessive hysteresis and eddy current losses produced heat in the cores. This excessive core heat caused transfonner failures. Modern transformer cores are constructed of thin steel sheets with their grain oriented to give less resistance to magnetic flux and to reduce eddy cur-rents. In addition, flux densities are design-limited to minimize hysteresis losses. Modern design methods for transfonner cores and windings have improved projected transfonner life. Transfonner cores are very reliable if the transfonners are oper-ated within the temperature limits specified by the manufacturers and the cores are properly sup-ported to reduce vibration and mechanical damage.
NUREG/CR-5753 OAGI0001164_00027
o >>
G) o o o (J)
I.j::>.
o o o N
CD
-I
~
Q
~
~
W 0\\
Table 3-1.
Components of power transformers and materials of construction.
Component Core Windings Solid insulation Liquid-insulating!
cooling medium Gas-insulating!
cooling medium Bushings Tank Connections Materials Silicon steel Cooper or aluminum Cellulose, kraft paper, phenolics, fiberglass',
and varnishes-shellac, enamel, or various resins Fibrous-resin-paper laminates, pressboard and various kinds of paper (nylon or wood based)
High-flammability Mineral oil Low-flammability Askarel, silicones, high-flash-point hydrocar-bons, chlorinated benzenes, or chlorofluoro-carbons Air Nitrogen/fluorogas Porcelain. kraft paper. metal foil, mineral oil and copper or aluminum conductor Carbon steel Copper. aluminum, solder, brazing Comments Laminated sheets.
Each turn may be made up of groups of strands.
Used to provide wire, turn, and layer insulation for the windings. Paper wrapping is also used on the leads coming from the windings.
Used to bond and protect (mechanical and moisture) fibrous insulating material.
High dielectric strength and excellent heat transfer capability. No high voltage (> 15 kV) restrictions.
Good dielectric strength and heat transfer capabili-ties. High voltage limit is s 15 kV. Askarel is being phased out. Silicones are used on all modem low-flammability fluid transformers.
Relatively low dielectric strength and heat transfer capabilities.
Relatively low dielectric strength and heat transfer capabilities. Requires pressure regulation system to maintain pressure in sealed tank.
High-voltage bushings use kraft paper. metal foil.
and oil inside a porcelain outer surface. Lower volt-age bushings use kraft paper with a conductor inside a porcelain outer surface.
Heavy gauge steel, painted to prevent corrosion.
en
<§.
5i
~
G g,
J:
~.
-(1n arrangement of winding used with core-form transformers..,
Significance of Aging An arrangemen.t of winding used with shell-form transformers.
Figure 3-1. Comparison of windings used for core-and shell-form transformers.
Transformer windings have two major compo-nents: conductors and insulation. The conductors commonly used in power transformers are copper or aluminum. Each material has specific advan-tages. For instance, copper has greater mechanical strength and greater electrical conductivity than aluminum. Aluminum, however, costs less and is lighter than copper. The many turns in a winding must be insulated from each other and from neigh-boring windings. Winding conductors use Kraft paper,a Nomex, cellulose, or another similar insu-lating medium. Windings include spaces, or chan-nels, to allow flow of the insulating coolant (such as air, oil, or gas). This cooling establishes the life of the insulation. Degraded cooling accelerates the aging of the insulating materials.
Heavy gauge structural steel is typically used to make transformer enclosures. The enclosures can be vented or sealed, indoor or outdoor, pad-mounted or pole-mounted, or dry-type or liquid-filled. The enclosure contains the insulating
- a.
Mention of specific products or manufacturers in this document implies neither endorsement, prefer-ence, nor disapproval by the U.S. Government, any of its agencies, or Lockheed Martin Idaho, of the use of a specific product for any purpose.
17 medium and coolant, and it protects the trans-former from external environments.
The majority of transformers used in Class IE applications are open-wound, dry-type trans-formers. Dry-type transformers use air as the sole source of coolant. The insulation is provided by a combination of air or nitrogen and solid insulat-ing materials. Most dry-type transformers use a Class H, 220°C insulation system. Thus, the max-imum allowable hot spot winding temperature is 220°C.
Liquid-filled transformers are also used in Class IE applications. A specific liquid is used as a heat transfer medium. The liquid removes heat from the transformer core and windings. The enclosure surface and radiators dissipate the heat to the ambient environment. Oil pumps, forced air fans, and external radiators increase the cooling capacity of the liquid-filled transformer. The cooling fluid is in contact with the transformer windings. Therefore, the fluid must be an accept-able insulator. Historically, liquid-filled trans-formers have a high reliability because of the high dielectric strength of the coolant, the *insulating structure, the sealed enclosure construction, and a proven design. Many different insulating liquids are currently used in liquid-filled transformers, NUREG/CR-5753 OAGI0001164_00029
Significance of Aging including mineral oils, silicone fluids, synthetic hydrocarbons, high molecular weight hydrocar-bons, trichlorotrifluoroethane, and chlorinated benzene.
Gas-cooled (vapor-cooled) transformers have characteristics that are similar to liquid-filled transformers. A gas-cooled transformer has its core and windings immersed in a refrigerant such as Freon (R-113). The refrigerant vaporizes at the core or winding interface with the refrigerant.
The vaporization removes the heat from the core or winding. The vaporized coolant rises to a con-densing unit above the transformer. It cools and condenses to a liquid state before returning to the transformer tank by gravity.
3.2 Construction Materials Materials used in dry-type, liquid-filled, and gas-cooled transformers are, in general, the same, except that the cooling medium differs. Every material has its own aging mechanisms. The aging mechanisms are accelerated by contami-nants or excessive heat. As the dielectric strength of the insulation decreases, a point is reached where flashover (winding to winding, winding to ground, or primary winding to secondary wind-ing) occurs. The flashover results in contamina-tion (discharge tracking) of the insulation. This permanently reduces the insulation's dielectric strength. These effects accelerate aging and increase the likelihood of further flashovers.
Typical transformers are constructed of high permeability silicon steel cores. Structural steel forms the tank (enclosure) and structural sup-ports. Windings are formed by copper or alumi-num conductors. Liquid coolants can include mineral oils, silicone fluids, synthetic hydrocar-bons, high molecular weight hydrocarbons, trich-lorotrifluoroethane, and chlorinated benzene.
Insulation can be cellulosic (paper or pressboard),
Kraft paper or Nomex, phenolics, plastics, porce-lain, wood, epoxy, fiberglass, rubber, cork, ther-moplastics, and varnishes. Other miscellaneous materials include paints and solder. The above materials do not include auxiliary equipment such as cooling fans, radiators, and oil pumps.
NUREG/CR-5753 18 Each material listed above has its own aging mechanism, as identified in Table 3-2.
3.3 Transformer Loading An issue separate from reduced transformer capacity induced by aging is increased trans-former loads resulting from plant modifications.
Modifications to the plant design over years of operation add electrical loads to the electrical dis-tribution system and transformers. These addi-tionalloads cut into the design reserve capacity of the transformers. Thus, late in the design life of a transformer, a transformer may be loaded beyond the original station design requirements. The transformer may be loaded beyond its continuous rated capacity under accident conditions as a result. The additional loads will accelerate the naturally occurring aging of the transformer. This is because transformer-generated heat is directly proportional to the transformer load. The heat generated can be further increased by the physical condition of the transformer. The amount of heat retained in the transformer is related to the physi-cal condition of its cooling system.
3.4 Transformer Capacity Considerations As stated, transformers are specified and designed with minimum design capacity and capa-bility. The transformers are relied on to operate under postulated accident and environmental conditions while minimizing the likelihopd of simultaneous failures. Thus, with the additional loads imposed by responding to an accident, a transformer is designed to have sufficient design reserve capacity to continue operation. This design reserve capacity exists beyond additional growth loads caused by plant modifications and loss of transformer capacity caused by transformer aging.
Additionally, the loads imposed may be peaked by such items as swing loads and loads such as bat-tery chargers operating at their maximum output.
Catastrophic failure or end of transformer life, it is hoped, will not occur during an accident or accident recovery. System redundancy alleviates the concern. However, the same aging mecha-nisms are at work on both redundant transformers.
OAGI0001164_00030
0 >>
G) 0 0
0 (J)
.j::>.
I 0
0 0
- 0)
I
\\0
~
Q
(")
~
til
~
loU Table 3-2.
Component stressors and failure mechanisms.
Component Windings Core Solid insulation Bushings Connections Stressor Overvoltages.
High continuous current (overloads).
Lightning and switching surges.
Vibration.
Vibration.
Heat above design limits.
Moisture.
Contaminants.
Core movement.
Heat and moisture on inside of bush-ing.
Contamination on outside of bushing.
Oxidation and vibra-tion.
Failure mechanism Partial discharge.
Solid insulation hot spot tem-peratures.
Core movement.
Delamination.
Core telescoping and lateral shifts.
(I) Loss of mechanical strength-increases brittle-ness.
(2) Eventual reduction in dielectric strength.
Reduced dielectric strength of solid insulation.
Same as "Moisture."
Insulation compaction.
Mechanical damage.
See "Solid Insulation" for failure mechanisms, results and comments.
Reduced electrical distance though air to ground.
High electrical resistance, arcing, and high heat.
Result Breakdown of tum-to-tum insula-tion.
Aging of solid insulation increases with increased heat.
Insulation deformation.
Tum-lo-tum short.
Increase in core heat/hot spots.
Core movement deforms solid insulation. Decomposition of insulation by core vibration.
Heat speeds up the chemical action that eventually destroys the insulation.
Electrical shorts between turns, winding, and/or ground. Disable transformer.
Same as "Moisture."
Decomposition of insulation.
Electrical failure.
Cracking, embrittlement.
Short to tank (ground).
Open circuits and protective relay tripping.
Comments Long term damage to the insulation is the most likely occurrence.
See "Solid Insulation."
See "Solid Insulation."
Hot spot or average winding temperatures above the rated temperature increases the aging rate of the solid insulation. The effects of the overheating solid insulation are accumulative, that is, nonreversible.
Moisture held in combined form releases under increasing temperatures producing same conse-quences as free moisture.
Contaminants usually have inferior dielectric strength.
Reduces ability to withstand lightning and switching-induced surge voltages and 60 Hz over voltages and transient.
Can be easily cleaned and prevented.
Visual and infrared inspection used to detect.
Cf.l
<§.
- n
~
ell
~
~
JJ'
o >>
G) o o o (J)
I.j::>..
o o o
- 0)
N I
'," j
-I I
- 1 !
I I
~
Q
~
U!
w
~
Table 3*2. (continued).
Component Mineral oil (Insulating!
cooling mediums)
Stressor Entrained air or water.
Failure mechanism Sludge formed.
Acids formed.
Solid insulation absorbs water.
Result Reduced heat transfer capability.
Absorbed by fibrous insulations attacks metallic and other compo-nents.
Absorbs increasing amounts of moisture in solution.
Reduces electrical breakdown strength.
Comments Requires derating transformer or sludge removal.
Buildup causes shrinkage of cellulose insulation.
Most acids formed are weakly acidic, however, over time, material aging is accelerated if acids not removed.
See "solid insulation-moisture."
Decomposition products include H2, CH4, C2H2, C3H3. H3, and other types of hydrocarbons.
en C§.....
- n o
~
('l) g,
~
Jg'
- 4. TRANSFORMER AGING MECHANISMS Historically, transformers have been reliable components in electrical power systems. How-ever, various stressors and aging mechanisms can cause transformer failures, and many of these can lead to sudden failure under electrical stress. For this reason, transformers tend to appear as a two-state device; it operates or it fails. Through an understanding of transformer aging mechanisms, material conditions can be tested and trended so timely replacement or repair can be performed prior to catastrophic failure. In addition, mainte-nance actions can be taken to minimize the rate of aging and ensure maximum transformer lifetime.
Transformer failures are classified as one of four types: magnetic circuit, winding, insulation, or structural failures. These do not include fail-ures of auxiliary equipment such as cooling fans.
Some overlap of these classifications may occur, such as the structural failure of an insulating bushing. Another example of overlapping classi-fication is a flashover between adjacent winding turns that causes degradation of the dielectric strength of the insulating structure.
The metals in the structure, magnetic circuit, and windings are, in general, not subject to aging as are nonmetallic components. Thus, the life of the transformer depends mostly on the life of the insulation. Transformer failures follow a typical bathtub curve. Manufacturing defects (such as poor design, faulty materials, burred conductors, and workmanship) show up early in the life of a transformer. Then a period of relatively trouble free operation occurs. Late in the life of a trans-former, aging mechanisms could potentially translate into transformer failures. The objective of General Design Criteria 17 is to have trans-formers operate in the second, bottom portion of the bathtub curve. That is, transformer life will either extend beyond the station life or the trans-former will be replaced before failure would occur if responding to an accident condition.
Temperature is an aging mechanism that decreases the mechanical strength and increases the brittleness of the fibrous insulation. This aging mechanism accelerates with increased operating 21 or hot spot temperatures. Heat accelerates the chemical reactions that liberate oxygen from the fibrous atomic structure. This mechanism makes a transformer more likely to fail as it increases in age. This occurs even though the dielectric strength of the insulation material may not be seri-ously decreased. The deterioration of the fibrous insulation is not reversible. Monitoring trans-former temperatures to verify continued operation within design temperature limits helps to ensure the design transformer life. Imbedded temperature sensors and infrared heat scans can be used.
Moisture in an insulating medium (oil, air, or gas) is another aging mechanism. Heat accelerates this mechanism. The primary concern with mois-ture is that the paper and pressboard insulation readily absorbs the moisture. This decreases the dielectric strength, accelerating the aging of the insulator structure. Appreciable quantities of water in insulating oil decreases the dielectric strength of the oil. This may lead to failure at oper-ating voltages. Moisture permanently damages the insulation. Subsequent drying of the insulation only reduces the rate of deterioration. The lower the water content in the insulation, the greater the possibility of meeting the design life of the trans-former. Complete removal of moisture from a cel-lulose insulation is not possible without damaging the cellulose.
The dielectric strength of the oil and cellulose insulation systems are drastically weakened when there are free gas intrusions (bubbles). In an oil-filled transformer, gas bubbles in the oil can result in partial discharges and reduced cooling effec-tiveness. Wet fibers can distort the electrical field and cause local stress that can also result in partial discharges. Partial discharges can also be caused by small conducting particles or contaminants in the insulating coolant. These discharges result in burning and charring of the insulating materials.
Gaseous combustion products are released by these discharges also.
All these aging accelerators can be monitored by periodic sampling and analysis or by on-line analysis of the cooling (liquid or gas) fluid and NUREG/CR-5753 OAGI0001164_00033
Transfonner Aging Mechanisms insulation testing. The design life of the trans-former can be preserved by maintaining the purity of the cooling fluid and the insulating properties of the insulation. The historical trend and the current condition of the insulation and any cooling fluid can be used for identification of maintenance mea-sures needed to preserve or extend the life of a transformer. Physical inspections of all trans-former types can provide similar and supportive end information. The interpretation of the condi-tion of the insulation depends primarily on com-parison of current insulation testing with previous test results.
Oil-filled transformers have the separate aging mechanism of sludge formation. Sludge is one of many oil decay products. Sludges formed into solid insulation cause insulation shrinkage.
Insulation shrinkage results in winding motion under shock or impulse loading. Sludge deposits result in higher transformer operating tempera-ture. Derating the transformer to account for sludge deposits helps ensure the design life of the transformer.
Another aging concern is solar magnetic dis-turbances. Solar flares have a characteristic effect on earth. Solar magnetic disturbances cause geomagnetic-induced currents in the miles-long transmission circuits. These currents are harmon-ics of the base (60-Hz) power frequency. The harmonics cause a half-cycle saturation of the transformer. There is a direct relation between geomagnetic-induced currents and half-cycle transformer saturation. The saturation causes increased heating and greatly increased gen-eration of combustible gases within the transformer. There are known instances of trans-former failures attributed to active solar storm activity.
Systems to monitor the effects of geomagnetic-induced current flows are being developed by industry. These will supplement any other trans-former monitoring program. Having ample reserve transformer capacity will help the trans-former weather the storm.
Lightning-and switching-induced impulse voltages have similar effects on a transformer.
NUREG/CR-5753 22 However, the stress loads caused by lightning and switching transients are somewhat limited by their short duration and by installed surge protective device characteristics.
The ambient temperature directly affects the equilibrium temperature of an operating trans-former. Electrical and mechanical properties of insulating materials are related to their tempera-ture. Softening of polymeric insulators increases as the temperature rises. Other temperature-related changes such as, melting, crystallization, embrittlement, deformation, and creep occur in insulating materials. Some of these changes are not reversible. Dielectric loss also exhibits a temperature-dependent change. Increased dielec-tric loss could lead to local thermal runaway. On the other hand, maintaining transformer tempera-tures under design limits ensures that the useful life of the transformer is not compromised. If the temperature is maintained low enough, the useful life of the transformer may extend beyond the design life.
The magnetic forces within a transformer exert mechanical forces on the windings and the mag-netic materials. These repulsive and attractive forces combine with thermal expansion and con-traction forces. These forces may distort insulating structures, especially if the structure is already weakened by temperature-induced deformations.
Stationary windings can move as much as three inches under short-circuit conditions. A short cir-cuit generates considerable magnetic force.
Steady 60-Hz alternating current also causes mag-netic forces to operate on the windings. The con-tinual alternating force causes a vibration that, over time, will compact the mechanical insulation structure that holds the windings in place. Thus, both vibration-and surge-induced core move-ments damage the insulating structure of the trans-former. A loose transformer structure means unrestrained windings for impulse-and fault-induced stress. These conditions when further stressed, cause further transformer aging.
Systematic programs that monitor physical conditions, insulation properties, sound levels, coolant properties and purity, geomagnetic-induced transients, and transformer temperatures
~-
OAGI0001164_00034
help to ensure the design life of the transformer. A program of testing and monitoring, along with preventive and corrective maintenance, is the key to achieving the desired transformer life.
23 Transformer Aging Mechanisms Confidence that a transformer has always operated within its design envelope gives assurance that a transformer will operate to or beyond its design life.
~(}/~-5753 OAGI0001164_00035
- 5. REVIEW OF OPERATING EXPERIENCE This review was completed using information obtained from the Nuclear Regulatory Commis-sion's Licensee Event Reports (LERs), the Insti-tute for Nuclear Power Operations' Nuclear Plant Reliability Data System (NPRDS), the Nuclear Power Experience database (NPE), and informa-tion obtained from a cooperating utility. The data and information were analyzed to determine the types of Safety Class IE transformers used, their ages, and their problems and failures associated with aging. The information was also analyzed to determine if any transformer problem/failure trends have developed as the transformers became older.
The use of information from the NPRDS data-base, the NPE database, or the LER records has limitations. Licensee reporting requirements are such that a complete record cannot be obtained from anyone of the sources. Because each data-base requires different information, in varying degrees of detail, a partial piece of information might be misleading, and might be recorded in one database and not in another. The NPE and LER databases only report problems and failures resulting in recordable events (LERs). They do not include any transformer specifications or non-event transformer failures for either Safety Class IE or non-IE transformers. The NPRDS, how-ever, includes information on transformer specifi-cations and failures (event and nonevent) for each reporting plant.
The use of the NPRDS transformer specifica-tion and inservice data also had some limitations.
Only 91 operating plants have Class IE power transformer nameplate data and failure informa-tion in the NPRDS. In addition, a comparison of failures (LERs) reported in the LER, NPE, and NPRDS show that the NPRDS records were sometimes incomplete. To obtain a better view of the problems and trends caused by transformer aging, the NPRDS transformer information on plants licensed since January 1, 1989, was not used in this study, resulting in the use of NPRDS data from 88 plants for this study.
NUREG/CR-5753 24 Some plants included'information in the NPRDS for large numbers of special transform-ers. One nuclear power station included informa-tion for 120 transformers in the NPRDS. Included in the data was information on special low-power transformers, such as current and potential, con-trol, voltage regulating (electronic controlled),
and adjustable voltage transformers. Because this study is on power transformers, all NPRDS infor-mation was reviewed, and data on nonpower transformers were not included in the study.
The majority of reported transformer problems and failures in the NPRDS, NPE, and the LER are not directly related to power transformer aging.
These include problems and failures caused by human error, design and operation deficiencies, and acts of nature. The database also lists as transformer-related, problems for other power equipment. For example, problems on electrical buses, breakers, lightning arresters, relays, and other equipment were frequently included in the transformer category. To ensure that all problems and failures included in this study were actually on power transformers, an examination was made on each problem and failure that was reported in the databases.
To separate problems that were directly asso-ciated with the transformer proper and the aging of the transformer, guidelines were established for the engineering evaluation of the database infor-mation. The guidelines used are listed as follows:
The transformer envelope included connec-tions, insulators (bushings), current trans-formers, and potential transformers on the transformer proper.
The transformer envelope also included all cooling equipment (controls, control trans-formers, and fans).
Database reported transformer problems and failures not associated with the transformer envelope andlor not related to the aging of power transformers were not to be used in this study.
OAGI0001164_00036
During the study, a detailed engineering review was completed on 269 NPRDS problem reports, 1167 NPRDS transformer information records, 400 NPE entries, and 70 LER reports. All reports, records, and entries that were not related to the effects of power transformer aging were dis-carded. For comparison, the NPRDS-reported operating experience for non-l E power trans-formers is also included in this report.
Note that as discussed in Section 2, transform-ers listed in NPDRS as IE and having voltage rat-ings above 15 kV are likely not actually IE transformers. However, NPRDS data are being used, and the NPRDS classifications will be used in this section of the report.
5.1 Types, Applications, and Descriptions of Safety Class 1 E Power Transformers Transformers currently in Safety Class IE installations in Nuclear Power Plants consist largely of three types: liquid-filled, dry-type, and gas-cooled. Each type has specific applications for which they are commonly used. A typical nuclear power station electrical diagram is shown in Figure 2-1. The Safety Class IE transformers covered by this component aging study are shown within the dashed line area.
As shown in Table 5-1, the NPRDS records of the 88 plants show a total of 723 Safety Class IE power transformers, 76.5% of these are air-cooled (dry-type), 16.6% are oil-filled, and 6.9%
are gas cooled.
Table 5-2 shows the high-voltage rating for NPRDS-listed Safety Class IE power transform-ers. As shown in the table, the majority of Safety Class IE transformers have a high-voltage rating between 601 and 15,000 volts. The highest Safety Class IE transformer voltage rating included in the NPRDS data is 500 kV for two transformers at one nuclear station.
25 Review of Operating Experience 5.2 Transformer Age The ranges of age for the Safety Class 1 E power transformers are shown in Table 5-3. The NPRDS data for the 88 plants indicate that over 95% of the transformers are less than 20-years old, and about 75% are under 15-years old.
5.3 Transformer Problems, Failures, and Replacements The NPRDS data show that 56 power trans-formers have been put in service since the plants Table 5-1.
Type cooling for NPRDS-listed Class IE power transformers.
Type Percentage of cooling Number transformer Oil 120 (16.6%)
Air 553 (76.5%)
Gas 50 (6.9%)
Total 723 (100%)
Table 5-2.
Voltage ratings of NPRDS-Iisted power transformers.
High-voltage rating of transformers o to 601 volts 601 to 15,000 volts Over 15,000 volts Percentage of transformers 36.1 57 6.9 Table 5-3.
Age of NPRDS-listed safety Class IE power transformers.
Age Number Percentage o to 5 years 119 16.5 5 to 10 years 218 30.1 10 to 15 years 199 27.5 15 to 20 years 154 21.3 Over 20 years 33 4.6 Total 723 100.0 NUREG/CR-5753 OAGI0001164_00037
Review of Operating Experience have been licensed, with 33 of these occurring since 1983. 1Wenty-six of these were oil-filled, and the remainder were dry type. The data do not show the reasons for the installation or whether they were replacements for existing transformers.
The installations of these transformers happened between 4 to 18 years after plant licensing. The installations do not correspond to identified prob-lems, failures, or LERs.
Table 5-4 shows both the NPRDS-recorded Safety Class IE and all classes of plant trans-former aging-related problems and failures dur-ing the period from January 1983 through April 1991. During this period, a total of 143 problems/
failures occurred on all classes of transformers at the 88 plants. Of these problems, 33 were attrib-uted to Safety Class IE transformers. Only 38 of the 143 recorded problems/failures resulted in reportable events (LERs). Of the 33 recorded Safety Class IE problems/failures, five caused reportable events (LERs).
The NPRDS data show that detection of failures during routine observation, preventive mainte-nance, and surveillance tests appear to have pre-vented reportable events. For example, either an "Internal Failure" or a "Bushing (Insulator)" fail-ure result in-the total failure of a transformer.
However, only 50% of these types of failures resulted in LERs. Only three events (LERs) resulted from the ten problems with "Load Tap Changers" and "Connections." Other events were prevented by problem detection during routine observations, incidental observations, inservice inspections, and surveillance tests. The problems with "Oil, Nitrogen, and Gas Leakage" did not result in any events during the period reviewed.
However, undetected leakage can result in trans-former failure, as reported in NRC 1 E Information Notice Number 82-53, Main Transformer Failures at the North Anna Nuclear Power Station, December 24, 1982. (See Section 5.5 of this report.)
Table 5-5 shows the causes of transformer problems and failures for both NPRDS-listed Class IE and all safety classes (Class IE and nonclass IE) versus the type cooling for the period between January 1, 1983, and April 30, 1991. As can be observed, 64% of the problems and failures occurred on oil-cooled transformers for both IE and non-IE transformers. Sixty-four percent of Class IE transformer problems and failures occurred on a population of 16.6% of the total transformers in service (see Table 5-1).
This was attributed to use of oil-cooled transformers at high voltages and greater loads, with the resulting increased stresses on insulation. In addition, problems with load tap changers were the cause of 5 of the 21 reported problems and failures for NPRDS-listed Table 5*4.
Reported safety-related transformer problems.
Problems and failures Internal failure Bushing (insulator)
Cooling system Transformer connections Load tap changers Oil, nitrogen, gas leakage Total NUREG/CR-5753 All safety classes transformers Total LERs 49 23 11 7
44 3
9 1
11 4
19 0
143 38 26 Safety Class IE transformers Total LERs 6
1 3
1 7
0 5
1 5
2 7
0 33 5
OAGI0001164_00038
Review of Operating Experience Table 5-5.
Transfonner problems by cooling type (1983 through May 1991).
All safety classes Safety Class IE Problems and failures Oil Air Gas Oil Air Internal failure 25 25 2
4 Bushing (insulator) 10 I
2 1
Cooling system 31 13 4
3 Transformer connections 1
8 1
4 Load tap changers 11 5
Oil, nitrogen, gas leak 14 5
7 Total 92 (64%)
46 (32%)
5 (4%)
21 (64%)
12 (36%)
Class 1 E transformers. Load tap changers are only used to regulate output voltages for oil-cooled, high-power, and high-voltage trans-fanners.
5.4 Trends The transformer problems/failures for all NPRDS-listed transformers and Safety Class IE transformers, from 1983 through 1990, are shown in Figure 5-1. The experience of all classes of transformers shows a peak period of problems and failures starting in 1985 with 19 occurrences, rising to 27 during 1987, receding to 19 during 1988, and followed by 16 each during 1989 and 1990. The Safety Class IE transformer experi-ence is very similar, with a peak of 8 problems and failures occurring in 1987. During 1987, cooling equipment problems were the major fac-tor for the failures in all classes of transformers, while connections proved to be the major prob-lem experienced by Safety Class IE transfonners.
5.5 NRC IE Information Notices Since 1982, there have been two Inspection and Enforcement Notices providing information on significant transformer problems. A summary of each notice follows:
IE Information Notice 82-53, Main Trans-former Failures at the North Anna Nuclear Power Station.
27 This notice described a series of seven main transformer failures on the 330-MVA, 500-kV primary winding main power trans-formers. The problems experienced are also common to all oil type transformers, includ-ing cooling system and bushing failures.
Although all of the factors leading to the failures are contributors to, and indicators of, the aging of the transformer, none of the described failures were directly attributed to transformer aging.
IE Informat~on Notice 83-37, Transformer Failure Resulting from Degraded Internal Connection Cables.
This notice described an event caused by a degraded internal transformer connection on a Safety Class IE 4160/480 volt dry-type transformer at Brunswick 2 on April 26, 1983. The failure was attributed to long-term, heat-induced degradation initially caused by a poor connection. Later inspec-tion of similar safety-related transformers at Brunswick 2 identified eight of 48 con-nections with cable-to-Iug degradation.
Detailed transformer inspections, necessary to detect these failure mechanisms prior to complete failure, were not included in the licensee preventive maintenance program.
Similar connection problems and failures have been detailed in the NPRDS, LER, and NPE data bases, with 8 occurrences in 1987 NUREG/CR-5753 OAGI0001164_00039
Review of Operating Experience 30r---------------------------------------------------~
Non Class 1E Transformers en 1
~
20
- J
'(ij LL 16
"'0 16 c
tU en E
Q) :a 10 0....
- a.
OL---------------------------------------------------~
1983 1984 1985 1986 Years 1987 1988 1989 1990 Figure 5-1. Class 1E and nonc1ass IE power transfonner problems and failures listed by year.
(3 for Class IE transfonners). However, none of these have occurred since 1987.
5.6 Summary A review of the infonnation provided by the NPRDS database, the NPE database, and LERs yields the following information:
The NPRDS records of the 88 plants show a total of 723 Safety Class IE power trans-formers; with 76.5% of these using air (dry-type), 16.6% oil, and 6.9% using an inert gas as the insulation and cooling medium. Over 57% of the transformers have a high-voltage rating of 600 volts to 15 kV, and only 6.9% have a rating over 15kV.
This review shows that about 95% of the transformers are under 20 years of age, and NUREG/CR-5753 28 about 75% are less than 15 years old. The young age of the transfonners makes it diffi-cult, if not impossible, to determine the effects of transformer aging using plant operating experience.
FromJanuary 1983 through April 1991, only 5 LERs were caused by problems or failures of Safety Class IE transformers (Table 5-4).
Only 33 failures were reported on 723 Class IE power transfonners. Based on the number of plants operating in a given year, this is an average failure rate of 0.822 X 10-6 failures per hour per transfonner. Categories oftransfonnerprob-lems and failures include internal failure, bushing (insulator), cooling system, trans-fanner connections, load tap changers, and oil, nitrogen, or gas leakage. About 64% of the problems occurred on oil-insulated transformers. (During this same period, 38 LERs were caused by problems or OAGI0001164 00040
failures on non-IE power transformers at the plants. There were 143 total problems or failures on these transformers. About 64% of the problems occurred on oil-insulated transformers.)
It was not possible to determine the reasons for the installation of 56 transformers after the plants start up (34 of these occurring since 1983). If this information were avail-able, a better understanding of the transfor-mer experience, the detection of failures, and the licensee's surveillance/maintenance programs might have been obtained. In any 29 Review of Operating Experience case, if they were replacements for existing failed units, the problems were detected in time to prevent licensing events (LERs).
There is no present evidence, based on the NPRDS, NPE, and LER data that there are significant problems with the aging of transformers. This is based on the NPRDS, NPE, and LER data, which show that only 56 replacements, 33 problems/failures and 5 LERs occurred from 1983 through 1990 on the 723 Safety Class IE transformers for the 88 plants studied.
NUREG/CR-5753 OAGI0001164_00041
- 6. TRANSFORMER RISK ANALYSIS A standard PRA was used to determine which components were risk significant. The PRA for the Surry Nuclear Power Station (Bertucio 1990) was used. The Surry PRA was chosen because it is well documented in NRC-supported literature and is familiar to many in the PRA community.
Additionally, the authors had previously loaded the PRA and verified it to quantify correctly on the Integrated Reliability and Risk Assessment System (IRRAS) software. The quantified risk was expressed in terms of core damage frequency.
The fault trees for the Surry PRA included break-ers, transformers, bus work, inverters, rectifiers and batteries. Only the relays and isolation devices were not included explicitly in the PRA.
Quantification of a PRA generally involves truncation of those cut sets that do not contribute significantly to the final core damage frequency.
This was the case for the Surry PRA. All cut sets with a probability of less than 1.0E-09 before recovery were truncated. The truncation resulted in the complete removal of the battery, inverter, and rectifier components from the final set of cut sets. This left only the breakers, transformers, NUREG/CR-5753 30 and bus work as potentially risk-significant components.
It is possible to further screen components based on the increase in risk caused by assuming that the failure probability of a particular compo-nent is unity. If such an assumption does not result in a significant increase in risk, then the aging of the component is not risk significant. Unity fail-ure probability for a key IE transformer yields a risk increase of 1.0E-04. Comparing this increase to the total core damage frequency of 3.0E-OS indicates that the increase in failure probability of transformers could contribute significantly to plant risk.
The Surry PRA used a transformer failure rate of 1.7E-06. The average failure rate observed in this study was 0.822E-06. At the time of this study, there does not appear to be an increase in the transformer failure rate with the age of the transformers. If the transformer failure rate is kept at the presently observed level, by using a maintenance and surveillance program, an increase in the risk of core damage because of the aging of transformers is not expected.
OAGI0001164_00042
- 7. TRANSFORMER INSPECTION, SURVEILLANCE, MONITORING, AND MAINTENANCE 7.1 Guidance for Maintenance, Surveillance, Monitoring, and Inspection Inspection and testing of certain items on the Safety Class IE transformers at regular intervals extends the life of the transformer. Recommended maintenance and inspection practices for Safety Class IE transformers vary according to trans-former type (dry, oil-filled, or gas-filled), size (kVA), and voltage ratings. The objective of the inspections is to verify that there are no abnorma-lities with regard to noise, leakage, level, and temperature of the dielectric, and operation of the cooling system. The following maintenance, inspection, and testing procedures follow the rec-ommended procedures of transformer manufac-turers and those sources closely involved with the power distribution transformer industry, including S. D. Myers, Inc., and the J &P Transformer Book by Franklin and Franklin (see Bibliography).
Some of the recommended procedures cannot be performed during reactor operation; therefore, schedules coinciding with refueling outages are appropriate.
7.1.1 Oil-Filled Transformers. Maintenance intervals for Safety Class IE oil-fiIled trans-formers are summarized in Table 7-1. Where a interval is listed as annual, this can be understood as during a refueling outage.
Periodic Cleaning and Inspections.
Inspection of porcelain bushings at regular inter-vals helps ensure they are kept free from dust, dirt, acid fumes, salt deposits. and other contami-nants. The accumulations of contaminants on the external surface may result in flashover.
Although surge arresters do not require testing, inspection for dirt or dust contamination reduces the likelihood of external flashover.
Keeping the heat radiating surfaces of the transformers and the screened openings in the breathers and/or pressure-vacuum bleeder clean 31 helps reduce internal pressures and operating temperatures. Painting transformers prevents cor-rosion of the metal parts.
Verifying that connections to the terminals are tight avoids abnormal junction heating.
Liquid Level. Low transformer oil levels invite transformer failure. A liquid level gage with remote alarm contacts on oil-filled trans-formers can help prevent low fluid levels. A monthly inspection and calibration of the liquid level gage, along with testing of the low-level alarm circuit, is important for the proper operation of that instrumentation.
Cooling Fans. The regular inspection of forced-air cooling equipment verifies it is in satis-factory operating condition. Motor bearings, if permanently lubricated and sealed at the factory, need no attention. Otherwise, monitoring motor bearings for wear and periodic oiling, if called for, helps ensure reliable fan operation. Oiling is needed if the bearings are not sealed. Painting fan blades can cause an imbalance that may lead to the destruction of the blade. Checking excessive noise from the pumps and fans can detect possible anomalies.
Control Circuits and Equipment. Regular inspection of the following items for control circuits helps ensure transformer operability:
Control-circuit voltage Collections of dirt and gum Evidence of excess heating of parts (discol-oration, odor, etc.)
Freedom of moving parts Corrosion of metal parts Excess wear on contacts Loose connections NUREG/CR-5753 OAGI0001164_00043
Transfonner Inspection Table 7-1.
Maintenance intervals for oil-filled transfonners.
Maintenance item Tap changers Bushings Radiators Cooling intakes Oil filters Inspect for leaks Cooling fans Pumps Connections Control circuits Transfonner housing Vacuum interrupter Auto gas control Surge arresters Temperature gages Pressure gages Level gages Alarm circuits On-line gas analyzer Load tap changers Relays Oil-dielectric Oil-acidity Oil-moisture Oil-color Oil-sludge Combustible gas analysis Gas chromatography Acoustic emissions Infrared scan NUREG/CR-5753 Frequency Visual Inspections AnnuaUya Monthly Monthly On demand Weeldy Weekly Daily Daily Monthly Quarterly Quarterly AnnuaUya Quarterly Quarterly Instrumentation and Control Monthly Annuallya Monthly Annuallya Monthly Annuallya Annuallya Monthly Monthly Monthly Annuallya Annuallya Annuallya Annuallya Annuallya On-line monitor Testing Every 3 months or when warranted When conditions warrant Annuallya and when damage is suspected 32 Comments Clean and inspect functionality Clean and inspect Clean and inspect Clean and inspect Clean Visual inspection Inspect for damage and noise Inspect for damage and noise Inspect and tighten Inspect and test Paint if needed Inspect for wear Inspect and maintain Clean and inspect Functional test Calibrate Functional test Calibrate Functional test Calibrate Check functionality Check functionality Check functionality Clean and test OAGI0001164_00044
Transfonner Inspection Table 7-1.
(continued).
Maintenance item Frequency Comments Doble Power Factor Tests Windings Bushings Liquid Annuallya Annuallya Annuallya Electrical Insulation Tests Excitation current Annuallya and when damage is suspected Turns ratio test Annuallya and when damage is suspected Winding resistance Annuallya and when damage is suspected Ground resistance Annuallya
- a. Annually means 18 months or during each scheduled reactor refueling outage.
Proper contact pressure Excessive arcing in opening circuits Evidence of water in controls Excess slam on pickup Worn or broken mechanical parts.
Combustible Gas Analysis. Sampling Safety Class IE liquid-filled transformers greater than 500 kVA for combustible gases at regular intervals is an effective way to detect insulation degradation. Either a portable gas analyzer or an online combustible gas analyzer can be used. Of the two methods, the online gas analyzer is the most desirable. It provides alarm capabilities of an internal fault in the transformer when a preset level of combustible gases is exceeded. The online gas analyzer has an excellent record for reliability in predicting incipient failures in both old and new transformers. Gas chromatography (laboratory gas analysis), following any indica-tion of an incipient fault by the online gas ana-lyzer, confJfD1s a preliminary diagnosis.
33 The types of gases (H2, CH4, C2H2. C2H4,C2H6, CO, and C02) present in a sample and their rela-tive amounts enable the nature of the fault to be determined (thermal or electrical). The type of material producing the gas can also be determined.
A log of combustible gas readings, if kept, will show an increasing trend. With an increasing trend, the time between tests can be shortened. If the combustible gas content exceeds a preset limit
(>1 % by volume), a laboratory dissolved-gas-in-oil analysis helps to develop a plan of action.
Acoustic Emission Measurement. When used in conjunction with a gas-in-oil analysis, acoustic emission CAE) measurements of corona (partial discharges) provide an accurate pre-diction of incipient failures. Acoustic emission measurements can detect imminent faults. An online gas detector has delays of hours and even days while the gases propagate through the oil to the analyzer. Present AE technology offers the advantage of being able to determine the location of partial discharges and/or arcing within a trans-former to a high degree of accuracy.
AE measurements are made externally, on the transformer housing, or with a waveguide, which is placed in the oil next to each high-voltage NUREG/CR-5753 OAGI0001164_00045
Transfonner Inspection winding. With new installations, wave guides can be installed during transformer fabrication. The drawback with acoustic emissions detection is that it takes a trained operator to both take and in-terpret the data. AE does not replace a gas analy-sis, but it is a method of conflrming the results of a gas analysis and is a means to help pinpoint fault locations within the transformer.
Sampling and Testing Insulating Oil.
Transformer oil not only serves as the cooling medium, it plays a major role as part of the electri-cal insulation system. It can reflect the cleanliness, dryness, and to some extent, the degree of aging of the transformer. The following information covers the sampling and testing of transformer oil and the significance of the test results.
Sampling-The accuracy of the test results can be seriously affected by an improper sampling procedure. Procedures outlined in American Soci-ety for Testing and Materials (ASTM) Method D923, if followed, help obtain consistent results.
ASTM Method D923 addresses recording the top oil temperature at the time of sampling. Particular attention is given to the cleaning and drying oftest-ing containers: Taking samples when the insulat-ing oil is at least as warm as the ambient air avoids moisture condensation. Samples taken on a clear dry day, avoids the possibility of water or dust con-tamination. The sample must be protected from contact with light, air, and moisture. It is very important that the sample not be exposed to the ultraviolet rays of the sunlight. which will acceler-ate aging: Ideally, the sample will be drawn quickly, kept in a dark sealed container, and tested as quickly as possible.
The following tests determine the condition of the transformer oil:
Dielectric strength test Acidity (neutralization)
Water or moisture content Color NUREG/CR-5753 34 Sludge (interfacial tension).
Dielectric Strength Test-Maintaining a high dielectric strength of the insulating oil ensures transformer operability. Oil samples taken from transformers in the field, tested according to ASTM Method D 1816 helps achieve this goal. A low breakdown voltage is an indica-tion that impurities such as moisture, conductive dust, lint, or carbonized particles have entered the oil. Compact and efficient dielectric test equip-ment is available for use in the field. The test set applies an ac voltage at a controlled rate to two electrodes immersed in the dielectric fluid.
Ideally. the oil tests 26 kV or higher with a O.040-in. (I-mm) spacing between electrodes. Oil testing lower than 25 kV is either filtered to bring it back to 26 kV or replaced.
Although the dielectric test can indicate the presence of some impurities in the oil, it cannot detect the presence of dissolved water below 80%
saturation, acids, or sludges.
Acidity Test-The acidity test is the best single test for indicating oil oxidation. ASTM Method D974 is a laboratory means measuring acidity from oil oxidation in transfonners. Acids are detrimental to the insulation system and can induce rusting of metal parts when moisture is present. An increase in the neutralization number is an index to the rate of deterioration of the oil.
Under normal conditions, the oil acidity is below 0.2 mg KOH. There are fleld tests available to measure acidity (ASTM Method DI534); how-ever, they are not as sensitive as the laboratory method and therefore are not recommended.
Water and Moisture Content-Water content is critical in that an increase can indicate a leaking condition and ultimate reduction in dielectric strength. Free water may be detected in the sample by visual examination, in the form of droplets or as a cloud dispersed throughout the oil. Because water in solution cannot be detected visually, the Karl Fischer Reagent method (ASTM Method D1533) is recommended as a means of determining water content in the oil, in parts per million.
OAGI0001164_00046
Instrumentation suitable for water-in-oil analy-sis is available for use in the field. Recording results from this analysis periodically aids in detecting anomalities. Although a gradual increase in water content over the life of the trans-former is to be expected, any abrupt increase needs investigation to ascertain if serious condi-tions, such as leaks, may exist.
Color Test-The next in a series of oil sample tests is the color test. A gradual darkening of the oil in service can be expected. The test, meaningless by itself, is significant when there is a distinct change. The color test can be useful for diagnostic purposes, along with acidity and other tests to indicate the degree of contamination or deterioration of the oil.
There are two ASTM methods available for performing the color test: (a) a laboratory method (see ASTM Method DI500), and (b) a field test kit (see ASTM Method D1524).
Sludge Test-The test used to determine the degree of sludging in the insulation system is called the interfacial tension test (1FT).
The test procedure is described in ASTM Method D971. IFf test results are related to the degree of the oils oxidation and are an indicator of the degree of oil deterioration and contamination of the oil by the solid materials immersed in it.
Electrical Insulation Tests. The following tests are used to evaluate the condition of the transformer insulation. When the results from the insulation tests are coordinated with data from the oil tests, the general working condition of the transformer can be determined.
Insulation Power Factor TestS-The insulation power factor (IPF) tests are divided into the following three categories:
- 1.
Winding IPF
- 2.
- 3.
Liquid IPF.
35 Transformer Inspection The purpose of the insulation power factor tests is to provide an indication of the integrity of the insulation system. Power factor is a measure of the power loss through the insulation system to ground, caused by leakage current. The IPF can be measured by applying a voltage across a capacitive network, in this case the transformer insulation, and measuring the amperes and watts loss and using these data to calculate a power factor. For field application, a de-energized series of tests that measure insulation power factor (Doble tests) are used.
All insulating systems will have some minor leakage paths that permit a small current to flow.
A transformer is deemed suspect if the insulation power factor exceeds 2%. The causes of high power factor can be determined through additional testing. The bushings and liquid insulation can be tested to determine if they contribute to the high reading.
The recommended procedure for testing bush-ings is the ungrounded specimen test (UST) method. The equipment manufacturer recom-mends a maximum permissible test voltage not to be exceeded during testing.
The liquid IPF is determined by taking an oil sample from the transformer and testing for a power factor using the UST Method. New oil should have a power factor of ~ 0.05% at 20°C.
When the power factor exceeds 0.5%, further tests (insulation resistance or moisture content tests) can determine the cause, or whether mois-ture is present.
Excitation Current-Excitation current measurements are made to detect shorted turns and heavy core damage. The excitation current tests are performed using the UST method and the same test equipment used for the power factor tests. The test results can be compared to factory and pre-vious field test data to determine abnormal read-ings. High precision in excitation current measurements is not a requirement, because fault conditions found as a result of the test have excita-tion current values greater than 10% over normal.
Transformer Turns Ratio (TTR)
Test-The transformer turns ratio test can be NUREG/CR-5753 OAGI0001164_00047
Transformer Inspection performed in the field to detect short-circuited turns, incorrect tap settings, mislabeled terminals, and tap changer failures. A TIR test can indicate that a fault exists, but does not determine its exact location. The test is normally performed annually, any time a transformer has been repaired or modi-fied in the field, or if a fault has occurred drop-ping the transformer offline.
The TIR test uses the transformer turns ratio test set. The test equipment has an internal alter-nator to supply test voltage and is reliable and simple to use in the field.
Winding Resistance Measurements-Winding resistance measurements will reveal a change in de winding resistance when there are short-circuited turns, poor joints, or bad connec-tions. Prior factory andlor field test readings are required so that a comparison of data can be made.
Measurements made with a Wheatstone or Kelvin double bridge yield the most accurate results. It is essential that the temperature of the windings be accurately measured top to bottom, as all test readings must be converted to a com-mon temperature to give meaningful results. The dc circulating current applied to the system needs to settle down before measurements are taken.
Ground Resistance Measurements-Ground resistance measurements are conducted to determine the integrity of the grounding con-nections and the copper ground conductors. High resistance readings can indicate a poor condition of the ground grid or ground electrode or that the soil may have to be conditioned with water or chemicals. A good ground system will protect both personnel and equipment. The resistance measured to ground should not exceed 5 ohms.
Load Records. Records of load and voltage on the transformer, when checked regularly, veri-fies that the transformer is operating within its prescribed limits and is being used efficiently.
Temperature Measurements-The operating temperature of the transformer has limits defined in American National Standards Institute (ANSI) Standard CS7.12.00. Tempera-NUREG/CR-5753 36 tures above those recommended limits will result in accelerated deterioration of the oil and aging of the cellulose insulation. Local overheating is a pri-mary indicator of incipient faults within a transformer.
Top-liquid and bottom-liquid temperature are not suitable for indicating operating conditions within the transformer. Hot-spot temperature readings give a more accurate indication of load conditions within the transformer windings. 1\\vo winding temperature indicating instruments are suitable for existing transformers. One local tem-perature gage with a high limit set point mounted at the transformer at eye level aids local operators.
A second temperature indicator with an audible high-temperature alarm and room operators located at a manned remote location aids control.
Operating temperatures, along with coincident records of ambient temperature, load, and voltage, when carefully recorded as often as practical, aid in evaluating the operating history of the transformer.
Changes in operating temperatures are often the only means by which the operator can detect an abnormal condition within the transformer.
Infrared Detectors-Portable infrared detectors can be used periodicaIIy to aid in the de-tection of incipient faults on both old and new transformers. Periodic thermal imaging is per-formed with an operating guide that defines tem-perature as a function of image color. Although the infrared detector will not pinpoint a fault loca-tion, it can aid in determining whether or not a piece of equipment has overheated.
Polarization Recovery Voltage Test. A method of detecting moisture and aging degrada-tion products in the paper insulation, as well as the oil, has been developed and marketed for use in Europe and in the United States. The technique applies a voltage between a transformer winding and the transformer tank for a period of time, applies a short to the winding. removes the short, and then records therecovery voltage as a'function of time. This process is repeated by varying the period of time that the voltage and short are applied. An analysis of the results provides an indication of the moisture content and the presence OAGI0001164_00048
of aging degradation products. The presence of either of these products indicates a degradation of the total insulation system. The technique appears to be very sensitive to the presence of moisture and aging degradation products. Oil analysis provides a good measurement of moisture content in the oil, but since moisture is more readily absorbed in the paper than in the oil this technique may be particu-larly useful for indicating the presence of moisture in the paper insulation.
Fluoroptic Sensors-online hot spot measurements using fluoroptic sensors wound into the transformer windings can accurately mea-sure winding temperature. The fluoroptic device uses a phosphor sensor at the end of an optical fiber to measure temperature. The temperature of the sensor is determined by measuring the rate of decay of the fluorescence of the phosphor after it has been excited by a pulse of blue-violet light sent down the fiber from a Xenon flash lamp within the instrument. Once the rate of decay of the fluores-cence has been measured, sensor temperature can be determined by comparison with an empirical calibration curve. The probes and fibers are made of durable material that can withstand shock and vibration within the transformer and many years of continuous exposure to hot transformer oil.
Because the fluoroptic sensors are installed within the transformer windings, they should only be considered for new installations where the sensors can be installed at the factory. The relative high cost of the fluoroptic system must be weighed against the cost and critical nature of the trans-former to determine whether or not the system is cost effective.
Pressure Relief Devices and Sensors.
An excessive increase in tank pressure is an indi-cation that an internal fault condition exists.
Mechanical pressure relief devices, fault-pressure relays with alarm contacts, and digital or analog pressure gages (with a means of recording tank pressures) ensure that pressures have remained within normal limits.
Pressure Relief Devices. Pressure relief diaphragms are usually mounted on the end of a pipe connected to the transformer case above the 37 Transfonner Inspection liquid. They are designed to rupture at IOta 15 psi. Mechanical-relief devices are usually mounted on the top of the tank. The pressure relief device typically include alarm contacts to indicate operation of the device.
Fault-Pressure Relay-The fault-pressure relay is designed to de-energize the trans-former and/or initiate an alarm in the event of sudden pressure rise. The relay is not susceptible to trip because of vibration, mechanical shock, or pressure variations due to transformer temperature changes. The relay is mounted on a valve on the tank wall, near the base of the transformer.
If a periodic test program is followed, it will help ensure that fault pressure relays are available for their role of protecting the transformer and initiating an alarm. Electrically tripping the relays during any scheduled outage of equipment and at yearly intervals will ensure that they are in good condition, and that all the circuits are complete so that breakers and alarms can be tripped.
Relay contacts can be cleaned during testing with a flexible brushing tool to ensure reliable operation. Knives, files, or abrasive paper or cloth should not be used to clean relay contacts.
Load Tap Changers (LTCsj. Load tap changers are typically inspected and tested for proper operation annually; the following six pro-cedures are normal:
- 1.
Check the condition and dielectric strength of the oil in the tap selector compartment and replace if necessary. Proper minimum oil level should be maintained.
- 2.
Check the self-adjusting oil seal for wear or leaks.
- 3.
Check operation of the protective system.
- 4.
Verify that the gear-teeth paint marks are properly aligned.
- 5.
Keep the mechanism gears and control cams lightly greased.
- 6.
Clean relay contact surfaces.
-~----~----~~-~~------------------~----~------
OAGI0001164_00049
Transfonner Inspection Vacuum Interrupter. The arcing contacts within the interrupter will gradually wear over a period of time as a result of interrupting current during each tap change. Inspection of the wear in-dicators and the entire switch mechanism, annu-ally or after 25,000 operations, whichever occurs fIrst, helps ensure reliable operation. Worn inter-rupters should be replaced based on manu-facturer's recommendations.
Automatic Gas Controls. Some medium power Safety Class IE transformers may be equipped with automatic gas-control equipment.
The purpose of gas-control equipment is to main-tain an atmosphere of dry nitrogen under pressure between the top oil surface and the transformer cover. This isolates the oil from the outside air and prevents oxygen, moisture, and other contaminants from being absorbed in the oil. The nitrogen is supplied from a gas cylinder and enters the transformer through a gas regulator.
High-and low-pressure alarms, along with the transformer gas space pressure gage, are normally part of these controls.
Excessive loss of gas can be the result of a high oil level, abnormal loading, a defective regulator, or leaks. A log of transformer pressure, oil tem-perature, and gas cylinder pressure, if kept, can aid in determining the cause of gas consumption.
Regulator operation is tested, and a leak test per-formed on the nitrogen system on a regular basis to ensure reliable operation.
Transient Recorders. One primary cause of transformer failure is power line disturbance. The purpose of the transient recorder is to keep a record of the power line anomalies that tend to accelerate transformer aging. By knowing the fre-quency of occurrence and the magnitude of the transients, testing can be initiated to detect pos-sible damage to the transformers before failure of the unit occurs.
7.1.2 Dry-Type Transformers. Maintenance, testing, and instrumentation procedures for the dry-type transformers are similar to the oil-fIlled units with the exception of the oil testing common NUREG/CR-5753 38 to the oil-insulated transformers. Procedures and requirements for electrical insulation testing and dielectric testing of the windings (Doble Tests) are similar to the oil-fIlled units (discussed pre-viously). The following sections discuss mainte-nance, inspection, and surveillance practices common to dry-type transformers. Maintenance intervals for dry-type transformers are summa-rized in Table 7-2.
Periodic Cleaning and Inspections. With the transformer de-energized, the front and rear access panels are removed. Inspections are made for dirt, especially on insulating surfaces or for those that will restrict air flow, for loose connec-tions, for the condition of tap changers or terminal boards, and for the general overall condition of the transformer. Tracking or carbonization are signs of overheating and voltage creeping over insulating surfaces. Any anomalies are identifIed and corrected where possible.
Painted surfaces are checked for signs of rust, corrosion, or deterioration. Any deteriorated sur-faces need to be cleaned, prepared, and repainted with the type of paint recommended by the trans-former manufacturer.
Fans and motors are inspected for wear or dam-age and receive periodic service. The fan control system is checked to ensure that air delivery is made to the transformer coils.
Excessive dirt on the windings or insulators is removed to permit free air circulation and to pro-tect against insulation breakdown. Cleanliness of the top and bottom ends of winding assemblies, as well as ventilating ducts, ensures ventilation. Tap changers, terminal boards, bushings, and other insulating surfaces can be brushed or wiped with a dry cloth. Pressurized air should not be used for cleaning because it may blow abrasive debris into the winding~ and damage the winding insulation.
Insulation Resistance and Dielectric Tests. Prior to initial energization of the trans-former, and following any shutdown exceeding 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, an insulation resistance test will deter-mine if moisture is present in the insulation.
~--~.
OAGI0001164_00050
Transfonner Inspection Table 7-2.
Maintenance intervals for dry-type transfonners.
Maintenance item Frequency Comments Visual Inspections Internal surfaces Quarterly Clean and inspect Tap changers Quarterly Clean and inspect Tenninal boards Quarterly Clean and inspect Transformer housing Quarterly Paint if needed Connections Monthly Inspect and tighten Cooling fans Daily Inspect for damage and noise Windings AnnuaUy.
I 0
0 0
(J1 (J)
Table 8*2.
(continued),
Addresses these items relative to aging Inspection System Standard Aging Operational surveillance component function number Title degradation Maintenance records monitoring Comments Documentation IEEE 494-1974 Standard Method for Identification of No No No No Documents Related to Class IE Equipment and Systems for Nuclear Power Generating Stations Safety system criteria IEEE 603-1977 Standard Criteria for Safety Systems for No No No No Aging not included Nuclear Power Generating Stations in Sections 4 and 5
,I Safety system qualification IEEE 627-1980 Design Qualification of Safety Systems Generically No EQonly EQonly Equipment Used in Nuclear Power Generating Stations
~
Quality assurance ANSIIASME Standard Recommended Practices for No No Yes Yes NQA-I-1983 Quality Assurance Program Requirements NQA-2-1986 Applicable to All Phases of Nuclear Power Plant Design, Construction, and Operation Replacement parts 934-1987 Standard Requirements for Replacements No No No Yes Parts for Class IE equipment in Nuclear Power Generating Stations Statistical analysis 930-1987 Guide for Statistical Analysis of Voltage Yes No No No Endurance Data for Electrical Insulation
- 0
~
Standards for IE Power
~
Systems
('D
=E Design criteria 308-1980 Criteria for Class 1 E power Systems for No No No Yes 0
Q
>-+>
Nuclear Power Generation Stations CI.l
~
0 Testing programs 415-1986 Preoperational Testing Programs for No No Preoperation Preoperation
- 8.
G)
-...J Class IE power Systems for Nuclear test testing only B-Ut 0
w Power Generating Stations procedures en 0
0 -"
(J)
.j::>.
I 0
0 0
(J1
-....J
~
Table 8-2.
(continued).
l:tI
~
~
Q Addresses these items relative to aging
~
0
~
""!)
Inspection CI.l VI System Standard Aging Operational surveillance g
~
0-VI component function number Title degradation Maintenance records monitoring Comments a
w rn Protection of IE power 741-1986 Protection of Class IE Power Systems Degraded No Test and Degradcd and Equipment in Nuclear Power voltage records only voltage Generating Stations IE Power Component Standards All electrical equipment 943-1986 IEEE Guide for Aging Mechanisms and Yes No No Only as Diagnostic Procedures in Evaluating applied to Electrical Insulation Systems diagnostic
~
techniques Askarel ANSIIASTM Test for Color of Chlorinated Aromatic Yes No No Yes D2129-79 Hydrocarbons (Askarel)
ANSIIASTM Test for Thermal Stability of Chlorinated Yes No No Yes D1936*64R1980 Aromatic Hydrocarbons (Askarels)
IEEE 76*1974 Transformer Askarel in Equipment No Yes No No Bushings ANSIIIEEE Loading Power Apparatus Bushings No Yes No No 757-1983 ANSIIIEEE Outdoor Apparatus Bushings, Require-No Tests No No 24-1976 ments, and Tests ANSIIIEEE Outdoor Apparatus Bushings, No No No Yes 24-1984 Performance 0 >>
Insulating materials, ANSIIIEEE Acceptance and Maintenance of Insul-No Yes No No G) 0 systems, and electric CS7.106-1977 ating Oil in Equipment 0
insulations 0 -"
(J)
.j::>.
I 0
0 0
(J1 CD
-j
~
~
Q 0
~
G)
I VI 0
~
0 VI w
0 (J)
I.j::>.
0 0
0 (J1 CD Table 8*2.
(continued),
Addresses these items relative to aging System component function Insulators Power apparatus Testing equipment and testing Aging Standard number Title degradation Maintenance IEEE 266-1969 RI981 Evaluation of Insulation Systems for Electronic Power Transformers No IEEE 62-1978 Field Testing Power Apparatus Insulation No HVI-1978 ANSI/EIA RS364-2IA-1983 ULI446 ANSI C29.1-1982 High-voltage Insulators No Insulation Resistance Test Test Systems of Insulating Materials-General No Electrical Power Insulators No IEEE 62-1978 Field Testing Power Apparatus Insulation No IEEE 498-1980 Calibration and Control of Measuring and No Test Equipment Used in the Construction and Maintenance of Nuclear Power Gen-erating Stations IEEE C57.12.14 Dielectric Test Requirements for Power No Transformers for Operation at System Voltages from 115kV to 230kV ANSI/IEEE C57.98-1968 Transformer Impulse Tests No Yes Yes Yes Yes No Yes Yes Yes Yes Yes Operational records No No No No No No No No No No Inspection surveillance monitoring No' No No No Yes Yes No No No No Comments
~
~.
~
til
.... [ a en
~
Table 8-2.
(continued),
~
~
Q Addresses these items relative to aging
~
~
Inspection C'/)
VI System Standard Aging Operational surveillance g
--.l VI component function number Title degradation Maintenance records monitoring Comments
- a.
w a
CIl Transfonners ANSIIIEEE Acceptance and Maintenance of Insul-No Yes No No C57.106-1977 ating Oil in Equipment ANSI/IEEE Detection and Detennination of Gen-Yes Yes No No C57.104-1978 erated Gases in Oil-immersed Trans-fonners and Their Relation to Service-ability of the Equipment IEEE C57.12.14 Dielectric Test Requirements for Power No Yes No No Transfonners for Operation at System Voltages from 115 kV to 230 kV
~
NEMA TR98-Guide for Loading Oil-immersed Power No Yes No No 1978 Transfonners With 65C Average Winding Rise ANSI/IEEE Installation, Application, Operation, and No Yes No No C57.94-1982 Maintenance of Dry-type General Purpose Distribution Transfonners ANSI C57.12.
Liquid-filled Transformers Used in Unit No Yes No No 27-1982 Installations Including Unit Substations ANSI/IEEE Liquid-immersed Distribution, Power, No Yes No No CS7.12.90-1980 and Regulating Transformers and Guide for Short-circuit Testing of Distribution and Power Transformers ANSI CS7.12.
Load-tap Changing Transformers No Yes No No 30-1977 ANSIIIEEE Loading Mineral Oil-immersed Power No Yes No No C57.92-1981 Transformers
~
~
~
0
~
G)
U\\
0 v:
0 w
0 (J)
I.j::>.
0 0
0 (J)
Table 8-2.
(continued).
Addresses these items relative to aging Aging System component function Standard number TItle degradation Maintenance Operational records Inspection surveillance monitoring IEEE 756 Loading Mineral Oil-immersed Power No Transformers ANSIJIEEE Oil-immersed Transformers No C57.l2.11-1980 ANSI C57.12.
High-voltage Bushings No 22-1980 ANSI C57.12.
52-1981Property "ANSI code" (as page type) with input value "ANSI C57.12.</br></br>52-1981" contains invalid characters or is incomplete and therefore can cause unexpected results during a query or annotation process. Pad-mounted Compartmental-type Self-No cooled Three-phase Distribution Trans-Formers With Separable Insulated High-Voltage Connectors ANSI CS7.12.
Sealed Dry-type Power Transformers No 26-1975 ANSI/IEEE Test Procedure for Thermal Evaluation of No CS7.100-1974 Oil-immersed Distribution Transformers ANSI/iEEE Terminology for Power and Distribution No C57.12.80-1978 Transformers Yes Yes Yes Yes Yes Yes Yes No No No No No No No No No No No No No No Comments
- d
~
0
~
Q.,
en g Q.. a (I)
- 9. CONCLUSIONS The results presented in this section are the product of the Phase I study for understanding and managing aging of transformers. Transform-ers perform their primary function without the use of moving parts but do depend on auxiliary equip-ment such as fans, motors, pumps, and load tap changers. Transformers have the critically impor-tant function of providing power to equipment that is necessary for accident prevention, accident management, and accident mitigation. The fol-lowing conclusions have been developed and supported by failure data from several databases and from plant-specific records. They provide the basis for future research and work to mitigate ag-ing degradation and improve the reliability of transformers.
Degradation or deterioration of electrical insu-lation is the most significant failure mode for transformers. Failures of the windings (tum to tum, winding to winding, or winding to ground faults) and failures in the bushings that provide the interface between the transformer and the transmission lines are primarily caused by a fail-ure of the insulation system. Insulation failures are caused by excessive temperature, excessive voltages, moisture, and contamination. Contami-nation is most often in the form of moisture, acids, and foreign material from the outside envi-ronment or from the aging of internal compo-nents. Vibration also causes insulation failures by contributing to the breaking down of solid insula-tion material.
Transformers currently installed in Class IE applications consist of three types: liquid-filled, dry-type, and gas-cooled. Dry-type (air cooled) account for about 76.5% of the transformers, while 16.6% are liquid-filled, and 6.9% are gas-cooled. Liquid-filled are primarily used in high-voltage, high-power applications such as those that supply power to the 4160-Vac bus. Dry-type are typically used in lower-voltage, lower-power applications such as those found in the distribu-tion system within the various buildings.
Gas-cooled transformers are found in applica-tions where more power is needed than would NUREG/CR-5753 50 normally be supplied by a dry-type but where the use of oil is not appropriate, such as inside appli-cations where the concern for transformer flres prevents the use of oil.
Failure data from the NPRDS, LERs, and NPE databases were reviewed. The failure rate of transformers does not indicate an increased failure rate with age of transformer. However, over 95% of the transformers are less than 20-years old and 75% are under 15-years old.
Because transformers are normally considered to be a long life item (40 years or greater), a signifi-cant trend with age would not be expected at this time. Reported categories of transformer prob-lems include internal failure, bushing (insulator),
cooling system. transformer connections, load tap changers. and oil. nitrogen or gas leakage. The total number of transformer failures is not large.
From January 1983 through May 1991, NPRDS data for 88 plants with 723 safety-grade Class IE transformers reported only 33 problems and failures. The incidence of transformer fail-ures does not appear to be increasing with the age of the transformer. Therefore, we conclude that presently identified aging mechanisms are not expected to cause safety problems.
A review of the Surry PRA revealed that trans-formers, along with circuit breakers and buses, are the risk-significant components in the Class IE power system. If the transformer failure rate is kept at the presently observed level, an increase in the risk of core damage frequency is not expected.
A continual program of inspection, surveil-lance, monitoring, and maintenance will help ensure transformer reliability. Such a program will detect and reduce stressors that shorten trans-former life, prevent stressors before they cause degradation, and detect degradation in the early stages so that preventive and corrective action can be taken prior to transformer failure to reduce the rate of aging. An effective program of inspection, surveillance, monitoring, and maintenance con-sists of periodic cleaning and inspections; testing of dielectric strength; and testing of oil in Uquid-OAGI0001164_00062
filled transformers; testing to verify that electrical characteristics such as winding resistance, insulation resistance, turns ratio, excitation cur-rent, and resistance to ground are maintained.
Regular measurement of temperature is an impor-tant element of a transformer monitoring pro-gram. There are numerous codes and standards that are applicable to transformers. These codes and standards provide guidance for design, the performance of several tests, and maintenance of all types of transformers.
51 Conclusions Because transformers installed in nuclear faci-lities are relatively young, a periodic review of operating experience of transformers would be useful to monitor their continued performance.
A period of five years would be appropriate for the review. The review would determine if the present information remains accurate, and deter-mine whether significant trends, not previously identified, are developing.
-- ------ - ---~ ---- -- -----
OAGI0001164_00063
- 10. BIBLIOGRAPHY Atwood, C. L., Estimating Hazard Functions for Repairable Components, EGG-SSRE-8972, May 1990.
Atwood, C. L., User's Guide to PHAZE, a Computer Program for Parametric Hazard Function Estimation, EGG-SSRE-90I7, July 1990.
Bertucio, R. C., J. A. Julius, and W. R. Cramond, Analysis of Core Damage Frequency: Surry Power Sta-tion, Unit 1 Internal Events, NUREG/CR-4550, Volume 3, parts 1-3, April 1990.
Franklin, A. C. and D. P. Franklin, The J & P Transformer Book, 11th edition, London: Butterworth & Co.
Ltd, 1983.
General Electric Co., Instruction Manual, GEK-95915, 1987.
Hochart, Bernard, 1982, Power Transformer Handbook, English edition, London: Butterworth & Co. Ltd.
Levy, I. S., et al., Prioritization ofTIRGALEX-Recommended Components for Further Aging Research, NUREG/CR-5248, PNL-6701, January 1988.
Meyer, L. C. and J. L. Edson, Nuclear Plant Aging Research: The IE Power System, NUREG/CR-5181, EGG-2545, 1990.
Myers, S. D., J. J. Kelly, and R. H. Parrish, Fifty Plus Years: A Guide to Transformer Maintenance (in situ, in vivo), Ohio: S. D. Myers, Inc., 1981.
Shier, W. and M. Subdhi, Operating Experience and Aging Assessment of Motor Control Centers, NUREGI CR-5053, BNL-NUREG-52118, July 1988.
Square D Company, Instructions for Receiving, Installing, Operating and Maintaining Dry Type Transformers, Manual 7421-1, 1985.
NUREG/CR-S7S3 52 OAGI0001164_00064
NRC FORM 335 12*89)
NRCM 1102.
3201.3202
- 2. TITLE AND SUBTITLE U.S. NUCLEAR REGULATORY COMMISSION BIBLIOGRAPHIC DATA SHEET (See insrructions on rhe reversel Aging of Safety Class 1E Transformers in Safety Systems of Nuclear Power Plants
- 5. AUTHOR IS)
E. W. Roberts J. L. Edson A.C. Udy
- 1. RE?ORT NUMBER J.
(AulgnOd by NRC. Add Vol ** SuPP ** Rlv..
end AddindumNumbort.lllny.1 NVREG/CR-5753 INEL-95/0573 DATE REPORT PUBLISHED MONTH I
YEAR February 1996
- 6. TYPE OF REPORT
- 7. PERIOD COVERED (InC(USIl"~ Datesl B. PERFORMI NG ORGANIZATION - NAM E AND ADDRESS (If NRC. provid~ Division. Oflice Dr Region. U.S. Nud ** r Regul.tory Commiuion. and rrui!ing.ddr,m:iI conrracror.providd nMTIe.nd m.JIIng addT'lu.}
Idaho National Engineering Laboratory Lockheed Idaho Technologies Company P.O. Box 1625 Idaho Falls, Idaho 83415
- 9. SPONSORING ORGANIZATION _ NAME AND ADDRESS (II NRC. Iype "SA"", asabo..... if conrraclor.pro.ide NRC D;';sion. OWe" or Region. U.s. Nuc/eor Re9u/dlOry Comminion *
- nd milling.dd,t.,.1 Division of Engineering Technology Office of Nuclear Regulatory Research U.S. Nuclear Regulatory Commission Washington, D.C. 20555 - 0001
- 10. SUPPLEMENTARY NOTES J. Jackson, NRC Project Manager
- 11. ABSTRACT (200 word. o,l.ul This report discusses aging effects on safety-related power transformers in nuclear power plants. It also evaluates maintenance, testing, and monitoring practices, with respect to their effectiveness in detecting and mitigating the effects of aging. The study follows the U.S. Nuclear Regulatory Commission's (NRC) Nuclear Plant-Aging Research approach. It investigates the materials used in transformer construction, identifies stressors and aging mechanisms, presents operating and testing experience with aging effects, analyzes transformer failure events reported in various databases, and evaluates maintenance practices. Databases that were analyzed included the NRC's Licensee Event Report (LER) system and the Institute for Nuclear Power Operations' Nuclear Plant Reliability Data System (NPRDS).
- 12. KEY WO R OS/DESCR: PTO R S (List words or phrlse. mil wi" aui$! "" ** rr:non in locating rho "'pOrt. I Transformers Aging Stressors Class IE
'lAC FOAM ll5 12-891
- 13. AVAILABILITY STATEMENT Unlimited
- 14. SECURITY CLASSIFICATION IThl'PAge' Unclassified
/ThisR.pom Unclassified
- 15. NUMBER OF PAGES
- 16. PRICE OAGI0001164 00065
- Printed on recycled paper Federal Recycling Program OAGI0001164_00066