ML092330471
| ML092330471 | |
| Person / Time | |
|---|---|
| Site: | Oconee |
| Issue date: | 08/13/2009 |
| From: | Baxter D Duke Energy Carolinas |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| Download: ML092330471 (17) | |
Text
Ph Duke
- OrEnergy, DAVE BAXTER Vice President Oconee Nuclear Station Duke Energy ON01 VP / 7800 Rochester Highway Seneca, SC 29672 August 13, 2009 U.
S.
Nuclear Regulatory Commission Washington, D.
C. 20555 864-873-4460 864-873-4208 fax dabaxter@dukeenergy. com Attention: Document Control Desk
Subject:
Duke Energy Carolinas, LLC Oconee Nuclear Station Docket Numbers 50-269, 270, and 287 Technical Specification Bases (TSB)
Change On July 27, 2009 Station Management approved revisions to TSB 3.3.11, Automatic Feedwater Isolation System Instrumentation and TSB 3.3.13, Automatic Feedwater Isolation System Digital Channels to revise the reference to modules to be 'trip and trip confirm' modules.
Attachment 1 contains the new TSB pages, Attachment 2 contains the marked up version of the TSB pages.
If any additional information is needed, please contact Reene Gambrell at 864-873-3364.
Sincerley, Dave Baxter, Vice President Oconee Nuclear Site AooI www. duke-energy. com
U.
S.
Nuclear Regulatory Commission August 13, 2007 Page 2 CC:
Mr.
John Stang Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Mail Stop 0-8 G9A Washington, DC 20555 Mr.
Louis Reyes Regional Administrator, Region II Atlanta Federal Center 61 Forsyth St.,
SW, Suite 23T85 Atlanta, Georgia 30303 Eric Riggs Senior Resident Inspector Oconee Nuclear Station S.
E.
Jenkins, Section Manager Division of Waste Management Environmental Control 2600 Bull Street
- Columbia, SC 29201 bcc: w/o attachments L.
F.
Vaughn Ken Ashe MNS R.
D.
Hart CNS R.
L.
Gill NRI&IA w/attachments Document Management ELL NSRB MR Coordinator (Ron Harris)
Licensing Working Group
AFIS Instrumentation B 3.3.11 B 3.3 INSTRUMENTATION B 3.3.11 Automatic Feedwater Isolation System (AFIS) Instrumentation BASES BACKGROUND A Main Steam Line Break (MSLB) can lead to containment overpressure, unacceptable thermal stresses to the steam generator tubes, and significant core overcooling. Main and Emergency Feedwater must be promptly isolated to limit the effects of a MSLB. The AFIS instrumentation is designed to provide automatic termination of feedwater flow to the affected steam generator. The AFIS instrumentation automatically terminates Main Feedwater (MFW) by tripping both MFW pumps and closing the affected steam generator's main and startup feedwater control valves and block valves. Although the main and startup feedwater block valves are automatically closed, their closure is not credited for mitigation of a MSLB. The AFIS instrumentation automatically terminates emergency feedwater (EFW) by stopping the turbine-driven emergency feedwater pump (TDEFWP) and tripping the motor-driven emergency feedwater pump (MDEFWP) aligned to the affected steam generator. Manual overrides for the TDEFWP and MDEFWP's are provided to allow the operator to subsequently start the EFW pumps if necessary for decay heat removal.
In addition, AFIS instrumentation provides runout protection for the EFW pumps in the event of a MSLB and certain large break MFW line breaks with the pump in the automatic mode of operation.
Main Steam header pressure is used as input signals to the AFIS circuitry.
There are four pressure transmitters per steam generator with each feeding a steam pressure signal to an analog isolation module. The output of the analog isolation module provides an analog signal to the trip and trip confirm modules that actuates isolation functions at desired setpoints. One pressure transmitter per steam generator, applicable associated Integrated Control System (ICS) signal isolator(s) and analog isolation module inputs constitute an AFIS analog channel.
The four AFIS analog channels per steam generator feed two redundant digital channels. Each digital channel provides independent circuit functions to isolate each steam generator. If the logic is satisfied, a trip output is energized. The use of an 'energized to trip output' from the trip and trip confirm modules ensures that a loss of power to the digital channel will not result in an inadvertent feedwater isolation. If either digital channel is actuated, feedwater is isolated to the affected steam generator.
Energizing the trip outputs results in closure of contacts in various control circuits for systems and components used for the MSLB and feedwater OCONEE UNITS 1, 2,3 B 3.3.11 -1 BASES REVISION DATED 08/06/09 1
AFIS Instrumentation B 3.3.11 BASES BACKGROUND (continued) line break mitigation. Therefore, when the trip outputs are actuated, the systems and components perform their isolation functions. Other features of the digital channels include a test/manual initiation pushbutton and an "enable" or "arming" switch. An AFIS digital channel is defined as two analog isolation modules (AVIM), a trip module and a trip confirm module, the Enable/Disable pushbutton, the associated output relays, the trip relay outputs to the feedwater pumps, the redundant switchgear trips for the MDEFWP, the solenoid valves for the MFCV & SFCV, the trip solenoid valves for the feedwater pumps, and the TDEFWP trip function. The trip module and trip confirm module utilize 2 out of 4 logic. There are two digital channels per steam generator. The trip module and trip confirm module of each digital channel are configured in a two out of two logic arrangement. In this configuration, a random failure of one of the modules will not result in a spurious actuation. In addition, a random failure of one of the modules will not preclude a valid AFIS actuation due to the redundant digital channel. While AFIS provides isolation of the feedwater block valves, this is not a credited function and is not a requirement for digital channel operability.
The AFIS digital channels are enabled and disabled administratively rather than automatically. Appropriate operating procedures contain provisions to enable/disable the digital channels.
APPLICABLE SAFETY ANALYSES Based on the containment pressure response reanalysis, the containment design pressure would be exceeded for a MSLB inside containment without immediate operator or automatic action to isolate main feedwater to the affected steam generator.
In addition, prompt operator or automatic action would be required to isolate EFW to the affected steam generator to limit the resultant thermal stresses on the steam generator tubes following a MSLB.
Main Steam header pressure is used as input signals to the AFIS circuitry.
When a MSLB is sensed, or upon manual actuation, main feedwater is terminated by tripping both MFW pumps and closing the affected steam generators main and startup feedwater control valves and block valves.
Although the main and startup feedwater block valves are automatically closed, they are not credited for mitigation of a MSLB. In addition, EFW is terminated by stopping the TDEFWP and tripping the MDEFWP aligned to the affected steam generator. Manual overrides for the TDEFWP and MDEFWP are provided to allow the operator to subsequently start the EFW pumps if necessary for decay heat removal.
The AFIS Instrumentation satisfies Criterion 3 of 10 CFR 50.36 (Ref. 3).
OCONEE UNITS 1, 2,3 B 3.3.11-2 BASES REVISION DATED 08/06/09 1
AFIS Instrumentation B 3.3.11 BASES (continued)
LCO This LCO requires that instrumentation necessary to initiate a MFW and EFW isolation shall be OPERABLE. Failure of any instrument renders the affected analog channel(s) inoperable and reduces the reliability of the Function.
Four analog channels per SG are required to be OPERABLE to ensure that no single failure prevents Feedwater isolation. Each AFIS analog channel includes the sensor, ICS signal isolator and an analog isolation module.
APPLICABILITY The AFIS Function shall be OPERABLE in MODES 1 and 2, and MODE 3 with main steam header pressure _> 700 psig because the SG inventory can be at a high energy level and contribute significantly to the peak pressure with a secondary side break. Feedwater must be able to be isolated on each SG to limit mass and energy releases to the reactor building. Once the SG pressures have decreased below 700 psig, the AFIS Function can be bypassed to avoid actuation during normal unit cooldowns. In MODES 4, 5, and 6, the energy level is low and the secondary side feedwater flow rate is low or nonexistent. In MODES 4, 5, and 6, the primary system temperatures are too low to allow the SGs to effectively remove energy and AFIS instrumentation is not required to be OPERABLE.
ACTIONS If a channel's trip setpoint is found nonconservative with respect to the Allowable Value, or any of the transmitter or signal processing electronics, are found inoperable, then the Function provided by that channel must be declared inoperable and the unit must enter the appropriate Conditions.
A Note has been added to the ACTIONS indicating that a separate Condition entry is allowed for analog channels associated with each SG.
A.1 Condition A applies to failures of a single AFIS analog channel. With one channel inoperable or tripped, the channel(s) must be placed in bypass within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />. Bypassing the affected channel places the Function in a two-out-of-three configuration. Operation in this configuration may continue indefinitely since the AFIS Function is capable of performing its isolation function in the presence of any single random failure. The Completion Time of 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> is adequate to. perform Required Action A. 1.
OCONEE UNITS 1, 2,3 B 3.3.11-3 BASES REVISION DATED 08/06/09 1
AFIS Instrumentation B 3.3.11 BASES ACTIONS B.1 (continued)
With two channels inoperable or if the Required Action and associated Completion Time of Condition A can not be met, the channel(s). must be returned to service within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />. An inoperable channel includes any channel bypassed by Condition A.
C.1 and C.2 With the Required Action and associated Completion Time of Condition B not met, the unit must be placed in MODE 3 within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and main steam header pressure must be reduced to less than 700 psig within 18 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br />. The allowed Completion Time is reasonable, based on operating experience, to reach the required unit conditions from full power conditions in an orderly manner and without challenging unit systems.
SURVEILLANCE SR 3.3.11.1 REQUIREMENTS Performance of the CHANNEL CHECK once every 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> ensures that a gross failure of instrumentation has not occurred. A CHANNEL CHECK is normally a comparison of the parameter indicated on one channel to a similar parameter on other channels. It is based on the assumption that instrument channels monitoring the same parameter should read approximately the same value. Significant deviations between the two instrument channels could be an indication of excessive instrument drift in one of the channels or of something even more serious. CHANNEL CHECK will detect gross channel failure; therefore, it is key in verifying that the instrumentation continues to operate properly between each CHANNEL FUNCTIONAL TEST and CHANNEL CALIBRATION.
Agreement criteria are based on a combination of the channel instrument uncertainties, including isolation, indication, and readability. If a channel is outside the criteria, it may be an indication that the transmitter or the signal processing equipment has drifted outside its limit. If the channels are within the criteria, it is an indication that the channels are OPERABLE. If the channels are normally off scale during times when surveillance is required, the CHANNEL CHECK will only verify that they are off scale in the same direction. Off scale low current loop channels are verified, where practical, to be reading at the bottom of the range and not failed downscale.
A continuous, automatic CHANNEL CHECK function is provided by Software. If a channel is outside the criteria, then an alarm is provided to the control room. Manual performance of the CHANNEL CHECK is acceptable.
OCONEE UNITS 1, 2,3 B 3.3.11-4 BASES REVISION DATED 08/06/09 1
AFIS Instrumentation B 3.3.11 BASES SURVEILLANCE SR 3.3.11.1 (continued)
REQUIREMENTS The frequency, about once every shift, is based on operating experience that demonstrates channel failure is rare. Since the probability of two random failures in redundant channels in any 12 hour1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> period is extremely low, the CHANNEL CHECK minimizes the chance of loss of protective function due to failure of redundant channels. The CHANNEL CHECK supplements less formal, but potentially more frequent, checks of channel OPERABILITY during normal operational use of the displays associated with the LCO required channels.
SR 3.3.11.2 A CHANNEL FUNCTIONAL TEST is performed by comparing the test input signal to the value transmitted to the Calibration and Test Computer.
This enables verification of the voltage references and the signal commons. This will ensure the channel will perform its intended function.
The Frequency of 31 days is based on operating experience, with regard to channel OPERABILITY and drift, which demonstrates that failure of more than one channel in any 31 day interval is a rare event.
SR 3.3.11.3 CHANNEL CALIBRATION is a complete check of the instrument channel including the sensor. The test verifies the channel responds to a measured parameter within the necessary range and accuracy. CHANNEL CALIBRATION leaves the channels adjusted to account for instrument drift to ensure that the instrument channel remains operational between successive tests. CHANNEL CALIBRATION shall find that measurement errors and setpoint errors are within the assumptions of the setpoint analysis. CHANNEL CALIBRATIONS must be performed consistent with the assumptions of the setpoint analysis.
The Frequency is based on the assumption of an 18 month calibration interval in the determination of the magnitude of equipment drift in the setpoint analysis.
REFERENCES
- 1.
OCONEE UNITS 1, 2,3 B 3.3.11-5 BASES REVISION DATED 08/06/09 I
AFIS Digital Channels B 3.3.13 B 3.3 INSTRUMENTATION B 3.3.13 Automatic Feedwater Isolation System (AFIS) Digital Channels BASES BACKGROUND The four AFIS analog channels per steam generator feed two redundant feedwater digital channels. Each digital channel provides independent circuit functions to isolate each steam generator. If the logic is satisfied, a trip output is energized. The use of an energized to trip output from the trip and trip confirm modules ensures that a loss of power to the digital channels will not result in an inadvertent feedwater isolation. If either digital channel is actuated, feedwater to the affected steam generator is isolated.
Energizing the trip outputs results in actuation of contacts in various control circuits for systems and components used for the MSLB and feedwater line break mitigation. Therefore, when the trip outputs are actuated, the systems and components perform their isolation functions. An AFIS digital channel is defined as two analog isolation modules (AVIM), a trip module and a trip confirm module, the Enable/Disable pushbutton, the associated output relays, the trip relay outputs to the feedwater pumps, the redundant switchgear trips for the MDEFWP, the solenoid valves for the MFCV &
SFCV, the trip solenoid valves for the feedwater pumps, and the TDEFWP trip function. The trip module and trip confirm module utilize 2 out of 4 logic. There are two digital channels per steam generator. The trip and trip confirm modules of each digital channel are configured in a two out of two logic arrangement. In this configuration a random failure of one of the logic modules will not result in a spurious actuation. In addition, a random failure of one of the logic modules will not preclude a valid AFIS actuation due to the redundant digital channel. While AFIS provides isolation of the feedwater block valves, this is not a credited function and is not a requirement for digital channel operability.
Trip Setpoints and Allowable Values Trip setpoints are the nominal values that are user defined in AFIS software. AFIS software is considered to be properly adjusted when the "as left" value is within the band for analog CHANNEL CALIBRATION accuracy.
The trip setpoints used in the AFIS software are selected such that adequate protection is provided when all sensor and processing time delays are taken into account. To allow for calibration tolerances, instrumentation uncertainties, instrument drift, and severe environment induced errors for AFIS channels that must function in harsh OCONEE UNITS 1, 2, & 3 B 3.3.13-1 BASES REVISION DATED 08/06/09 1
AFIS Digital Channels B 3.3.13 BASES BACKGROUND Trip Setpoints and Allowable Values (continued) environments as defined by 10 CFR 50.49, the Allowable Values specified are conservatively adjusted with respect to the analytical limits.
The actual nominal trip setpoint entered into the software for low MS pressure is 550 psig and the rate of depressurization setpoint will be 3 psi/sec. A channel is inoperable if its actual trip setpoint is not within its required Allowable Value.
Setpoints, in accordance with the Allowable Values, ensure that the consequencesof accidents will be acceptable, providing the unit is operated from within the LCOs at the onset of the accident and the equipment functions as designed.
Each analog channel can be tested online to verify that the setpoint accuracy is within the specified allowance requirements. The analog CHANNEL FUNCTIONAL TEST is performed by comparing the test input signal to the value transmitted to the Calibration and Test Computer.
This enables verification of the voltage references and the signal commons to ensure the analog channel will perform its intended function.
A continuous, automatic analog CHANNEL CHECK is provided by AFIS software. If the channel is outside acceptance criteria, an alarm is provided to the control room.
APPLICABLE AFIS circuitry is installed equipment necessary to automatically isolate SAFETY ANALYSES main and emergency feedwater to the affected steam generator following a MSLB. The AFIS circuitry provides protection against exceeding containment design pressure for MSLB's inside containment and provides protection against exceeding allowable thermal stresses on the steam generator tubes following a MSLB.
Main Steam header pressure is used as input signals to the AFIS circuitry.
When a MSLB is sensed, or upon manual actuation, MFW is terminated by tripping both MFW pumps and closing the affected steam generator's main and startup feedwater control valves and block valves. Although the main and startup feedwater block valves are automatically closed, they are not credited for mitigation of a MSLB. In addition, EFW is terminated by stopping the TDEFWP and tripping the MDEFWP aligned to the affected steam generator. Manual overrides for the TDEFWP and MDEFWP's are provided to allow the operator to subsequently start the emergency feedwater pumps if necessary for decay heat removal.
The AFIS logic channels satisfy Criterion 3 of 10 CFR 50.36 (Ref. 1).
OCONEE UNITS 1, 2, & 3 B 3.3.13-2 BASES REVISION DATED 08/06/09 I
AFIS Digital Channels B 3.3.13 BASES (continued)
LCO Two AFIS digital channels per steam generator shall be OPERABLE. Both the trip and trip confirm modules of a digital channel shall be in the untripped condition for the digital channel to be considered OPERABLE.
APPLICABILITY The AFIS digital channels shall be OPERABLE in MODES 1 and 2, and MODE 3 with main steam header pressure > 700 psig because SG inventory can be at a high energy level and can contribute significantly to the peak containment pressure during a secondary side line break. In MODES 4, 5, and 6, the energy level is low and the secondary side feedwater flow rate is low or nonexistent.
ACTIONS A Note has been added to the ACTIONS indicating that a separate Condition entry is allowed for logic channels associated with each SG.
A.1 With one digital channel inoperable, the inoperable digital channel must be restored to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />. The Completion Time of 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> is based on unit operating experience and administrative controls, which provide alternative means of AFIS initiation via individual component controls. The 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> Completion Time is consistent with the allowed outage time for the components actuated by AFIS.
B.1 and B.2 With both digital channels inoperable or the Required Action and associated Completion Time not met, the Unit must be placed in MODE 3 within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and the main steam header pressure must be reduced to less than 700 psig within 18 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br />. The allowed Completion Times are reasonable, based on operating experience, to reach the required MODES from full power conditions in an orderly manner and without challenging Unit systems.
OCONEE UNITS 1, 2, & 3 B 3.3.13-3 BASES REVISION DATED 08/06/09 I
AFIS Digital Channels B 3.3.13 BASES (continued)
SURVEILLANCE SR 3.3.13.1 REQUIREMENTS This SR requires the performance of a CHANNEL FUNCTIONAL TEST to ensure that the digital channels can perform their intended functions. The Frequency of 18 months is based on engineering judgment and operating experience that determined testing on an 18 month interval provides reasonable assurance that the circuitry is available to perform its safety function, while the risks of testing during Unit operation is avoided.
REFERENCES
- 1.
OCONEE UNITS 1, 2, & 3 B 3.3.13-4 BASES REVISION DATED 08/06/09 I
Attachment #2 Markup of current TSB
AFIS Instrumentation B 3.3.11 B 3.3 INSTRUMENTATION B 3.3.11 Automatic Feedwater Isolation System (AFIS) Instrumentation BASES BACKGROUND A Main Steam Line Break (MSLB) can lead to containment overpressure, unacceptable thermal stresses to the steam generator tubes, and significant core overcooling. Main and Emergency Feedwater must be promptly isolated to limit the effects of a MSLB. The AFIS instrumentation is designed to provide automatic termination of feedwater flow to the affected steam generator. The AFIS instrumentation automatically terminates Main Feedwater (MFW) by tripping both MFW pumps and closing the affected steam generator's main and startup feedwater control valves and block valves. Although the main and startup feedwater block valves are automatically closed, their closure is not credited for mitigation of a MSLB. The AFIS instrumentation automatically terminates emergency feedwater (EFW) by stopping the turbine-driven emergency feedwater pump (TDEFWP) and tripping the motor-driven emergency feedwater pump (MDEFWP) aligned to the affected steam generator. Manual overrides for the TDEFWP and MDEFWP's are provided to allow the operator to subsequently start the EFW pumps if necessary for decay heat removal.
In addition, AFIS instrumentation provides runout protection for the EFW pumps in the event of a MSLB and certain large break MFW line breaks with the pump in the automatic mode of operation.
Main Steam header pressure is use~dasJoput s4ignals to the AFIS circuitry.
There-are-our pressure transmitters per steam generator with-ech--,
feeding a steam pressure signal to an analog isolation module. The output\\
of the analog isolation module, es an analog signal to the trip and trip confirm module a pr-cessor moedu at actuates isolation functions atu,)
esired-setpointst eransmitter per steam-generator.
applicable a sociated Integrated Control System (ICýgglator s
and an log i olation module inputs constitute an AFIS deteGti.eanalog hetG annel.
The four AFIS analog channels per steam generator feed two redundant digital channels._E~ach-digital-hg n-el'-p-0ides-independe functions-tdoisolate each steam generator. If the logic is satisfied, a trip output is energized.
use of an energized to trip output from the trip and trip confirm module esser m
-nsures that a loss of power to the digital channel will not resu in an inadvertent feedwater isolation. If eithe digitalbcannel-is-a*Ct-eid, 'fee-dwater is isolated to the--ectestearn generator. Energizing the trip outputs res-altin closure of contacts in OCONEE UNITS 1, 2, 3 B 3.3.11-1 eAnedff ent-Ntos-ý5, 336, & e337-
£&4SC3 A7LVCSyjslo
[ATCD X/x Y/0*
AFIS Instrumentation B 3.3.11 BASES BACKGROUND (continued) and components used for the MSLB and feedwater line break mitigation.
Therefore, when the trip outputs are actuated, thesystems and components perform.theJrisolatio n-cti digital channels include a testImanual initiation pushbutton and an "rnable'or "arming" swvitch. An AFIS digital channel is defined as an two analog isolation/modules (AVIM)
" m Trip Module (and a Trip Confirm MOe, the Ena isa button, t associated..ooutput relays the trip relay outputs to the feedwat eps*
redundant switchgear--trips for the MDDEF*WP-be solenoidvalves for the s
",e MEGV.&SFCV-,tte trip solenoid-valves for the, feedwater pumps, and the TDFVPtrip function. The ýprip Vfoduie and Xtrip Oonfirm 0odule utilize 2 out of 4 logic. There are two digital channels per steam generator. The trip and trip confirm modules of each digital channel are configured in a two out of two logic arrangement. In this configuration a random failure of one of theJkimodules will not result in/spuoious actuation -FIS
- cg--ri,.
In add ition random failure of-on of thlmodules will not precIud 2 validLAAFiS actuation due to the redundant digital channel. While AFlJ$provides isolation of the feed~vater block valves his is not a credited function and is not a requirenfodigital channel operability.
The AFIS digital channels are enabled and disabled administratively rather than automatically. Appropriate operating procedures contain provisions to enable/disable the digital channels.
APPLICABLE SAFETY ANALYSES Based on the containment pressure response reanalysis, the containment design pressure would be exceeded for a MSLB inside containment without immediate operator or automatic action to isolate main feedwater to the affected steam generator.
In addition, prompt operator or automatic action would be required to isolate EFW to the affected steam generator to limit the resultant thermal stresses on the steam generator tubes following a MSLB.
Main Steam header pressure is used as input signals to the AFIS circuitry.
When a MSLB is sensed, or upon manual actuation, main feedwater is terminated by tripping both MFW pumps and closing the affected steam generators main and startup feedwater control valves and block valves.
Although the main and startup feedwater block valves are automatically closed, they are not credited for mitigation of a MSLB. In addition, EFW is terminated by stopping the TDEFWP and tripping the MDEFWP aligned to the affected steam generator. Manual overrides for the TDEFWP and MDEFWP are provided to allow the operator to subsequently start the EFW pumps if necessary for decay heat removal.
OCONEE UNITS 1, 2,3 B 3.3.1 1-3 Amedmen*t*.
&156-5 PIcWvsIDon D/Wrt,
AFIS Digital Channels B 3.3.13 B 3.3 INSTRUMENTATION B 3.3.13 Automatic Feedwater Isolation System (AFIS) Digital Channels BASES BACKGROUND The four-AFIS-analog-channels-per-steam-generator feed two-redundan fCedwater digital c-annels. Each digita-channel provides indepenent circuit functions to isolate each steam generator. If the logic is satisfied, a i
/"
trip output is energized. The use of an energized to trip output from the trip rand trip confirm modules m
ensures that a loss of power to the digital channels will ndt-result in an inadvertent feedwater isolation. If
,either digitaGhannel is actuated, feedwe to the affected steamn generator is isolated.-Eergizing the trip outputs results in actuation of contacts in various control circuits for systems and components used for the MSLB.and-fe'mdt-iter-ne-bre'k-m t gation Ther-e~fre.e7when-the trip outpu-ts' e actuated, the systemýs-and components perform their isolation functions. An AFIS di channel is defined as two an analog isolation modules (AVIM),
c d
rip dule and a Orip ýonfirm Vodul the EnaZble piiisa ibiiiiton, the associated output relays, the trip relay outputs to the feedwater pumps, the redundantn witchgear trips for the MDEFWP, the solenoid valves for the MFCV &
SFCV, the trip solInoid valves for the feedwater pumps, and the TDEFWP I
trip function. The trip V'odule and &drip onfirm odule utilize 2 out of 4 logic. There are two digital channels per *team g nerator. The trip and trip confirm modules of each digital channel are configured) in a two out of two logic arrangement. In this configuration a random failuret of one of the logic modules will not result in a spurious actuation(A In addition, a random failure of one of
" 1 ilmodules will not preclude a valid AFIS actuation due to the r dundant digital channel. While AFIS provides isolation of the feedwater,,ck valves, this is not a credited function and is not rQjuirement-for digital channel operability.
Triri Setr~oints and Allowable Values Trip setpoints are the nominal values that are user defined in AFIS software. AFIS software is considered to be properly adjusted when the "as left" value is within the band for analog CHANNEL CALIBRATION accuracy.
The trip setpoints used in the AFIS software are selected such that adequate protection is provided when all sensor and processing time delays are taken into account. To allow for calibration tolerances, instrumentation uncertainties, instrument~dr-ift,-and severe environment OCONEE UNITS 1, 2, & 3 B 3.3.13-1
--Ame-t-drrrntr Nos. 33-6, 336, &-337-764,5es6
/&Vislon DY7T1p x/x ?(/d3
AFIS Digital Channels B 3.3.13 BASES (continued)
LCO Two AFIS digital channels pest'am generator shall be OPERABLE. Both the trip and trip confirm egji-module of a digital channel shall be in the untripped condition for the digital ch nnel to be considered OPERABLE.
APPLICABILITY The AFIS digital channels shall be OPERABLE in MODES 1 and 2, and MODE 3 with main steam header pressure _> 700 psig because SG inventory can be at a high energy level and can contribute significantly to the peak containment pressure during a secondary side line break. In MODES 4, 5, and 6, the energy level is low and the secondary side feedwater flow rate is low or nonexistent.
ACTIONS A Note has been added to the ACTIONS indicating that a separate Condition entry is allowed for logic channels associated with each SG.
A.1 With one digital channel inoperable, the inoperable digital channel must be restored to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />. The Completion Time of 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> is based on unit operating experience and administrative controls, which provide alternative means of AFIS initiation via individual component controls. The 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> Completion Time is consistent with the allowed outage time for the components actuated by AFIS.
B.1 and B.2 With both digital channels inoperable or the Required Action and associated Completion Time not met, the Unit must be placed in MODE 3 within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and the main steam header pressure must be reduced to less than 700 psig within 18 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br />. The allowed Completion Times are reasonable, based on operating experience, to reach the required MODES from full power conditions in an orderly manner and without challenging Unit systems.
OCONEE UNITS 1, 2, & 3 B 3.3.13-4 F-Am.entdmn~c~t Nv.336-, 336-, &337-