Other: LIC-08-0069, Letter of Intent to Adopt NFPA 805, Performance-Based Standard for Fire Protection for Light Water Reactor Electric Generating Plants, 2001 Edition, ML082710002, ML083030225, ML083030246, ML083330066, ML083640401, ML090220584, ML090650061, ML090720066, ML090720068, ML090830248, ML090860762, ML090930256, ML091070269, ML091170031, ML091380365, ML091400110, ML091830055, ML091880258, ML101040676, ML101050376, ML101270268, ML102010302, ML102020397, ML102290232, NLS2009099, SAMA Meteorological Anomaly Related to the Cooper Nuclear Station License Renewal Application
|
MONTHYEARLIC-08-0069, Letter of Intent to Adopt NFPA 805, Performance-Based Standard for Fire Protection for Light Water Reactor Electric Generating Plants, 2001 Edition2008-06-0909 June 2008 Letter of Intent to Adopt NFPA 805, Performance-Based Standard for Fire Protection for Light Water Reactor Electric Generating Plants, 2001 Edition Project stage: Other ML0830302462008-09-24024 September 2008 Copper Nuclear Station, License Renewal Application, Appendix E, Environmental Report Project stage: Other ML0830302252008-09-24024 September 2008 Transmittal Letter of Cooper Nuclear Station, Regarding License Renewal Application Project stage: Other ML0827100022008-11-20020 November 2008 Response to Letter of Intent to Adopt National Fire Protection Association Standard 805, Performance-Based Standard for Fire Protection for Light-Water Reactor Electric Generation Plants, 2001 Edition Project stage: Other ML0833300662008-12-19019 December 2008 Determination of Acceptability and Sufficiency for Docketing and Opportunity for a Hearing Regarding the Application from Nebraska Public Power District, for Renewal of the Operating License for the Cooper Nuclear Station Project stage: Other ML0901203602009-01-0909 January 2009 Safety Evaluation Report Project stage: Request ML0836404012009-01-21021 January 2009 Notice of Intent to Prepare an Environmental Impact Statement and Conduct Scoping Process for License Renewal for the Cooper Nuclear Station Unit 1 (TAC No. MD9763 and MD 9737) LTR Project stage: Other ML0906500612009-02-0202 February 2009 Letter from Nebraska State Historical Society Regarding Cooper Nuclear Station License Renewal Project stage: Other ML0908400622009-02-25025 February 2009 Transcript of Cooper Nuclear Station License Renewal Pubic Meeting - Evening Session, February 25, 2009, Pages 1-41 Project stage: Meeting ML0908400632009-02-25025 February 2009 Transcript of Cooper Nuclear Station License Renewal Public Meeting - Afternoon Session, Wednesday, February 25, 2009, Pages 1-33 Project stage: Meeting ML0907200662009-02-25025 February 2009 Comment (1) of James Gerweck, on Behalf of the Richardson County, Nebraska, Emergency Management Agency, Supporting CNS License Renewal Project stage: Other ML0907506862009-02-25025 February 2009 Scoping and Process Public Meeting Sides of February 25, 2009 Project stage: Request ML0907200682009-02-27027 February 2009 Comment (3) of Ashtin Paris, on Behalf of the City of Rock Port, Supporting Nebraska Public Power Districts Cooper Nuclear Station License Renewal Project stage: Other ML0908607622009-03-0909 March 2009 Letter from the Nebraska Department of Natural Resources the Cooper Nuclear Station License Renewal Project stage: Other ML0907200672009-03-10010 March 2009 Comment (2) of Alan Richard, on Behalf of Pawnee City Development Corporation, Supporting Renewal of License for Cooper Nuclear Station Project stage: Request ML0902205842009-04-0303 April 2009 Proposed Review Schedule Regarding the Application from Nebraska Public Power District for Renewal of the Operating License for the Cooper Nuclear Station Project stage: Other ML0908302482009-04-0303 April 2009 Environmental Site Audit Regarding Cooper Nuclear Station Unit 1 License Renewal Application Project stage: Other ML0909302562009-04-0909 April 2009 Audit Plan for Aging Management Program Site Audit Regarding Cooper Nuclear Station Unit 1, License Renewal Application (Tac No. MD9737) Project stage: Other ML0909103082009-04-14014 April 2009 Summary of Public Environmental Scoping Meeting Related to the Review of the Cooper Nuclear Station, Licensed Renewal Application Project stage: Meeting ML0910702692009-04-16016 April 2009 EPA Comment on the Cooper Nuclear Station License Renewal Application Project stage: Other ML0911700312009-04-28028 April 2009 Environmental Site Audit Regarding Cooper Nuclear Station Unit 1 License Renewal Application Project stage: Other ML0909704142009-04-30030 April 2009 Summary of Site Audit Related to the Review of the License Review Application for Cooper Nuclear Station, Unit 1 Project stage: Approval ML0911905972009-05-0101 May 2009 Request for Additional Information for the Review of the Cooper Nuclear Station License Renewal Application Project stage: RAI ML0914001102009-05-0808 May 2009 License Renewal Consultation Email with Nebraska Game and Park Commission Project stage: Other NLS2009039, Response to Request for Additional Information for License Renewal Application - Balance-of-Plant Scoping and Screening2009-05-28028 May 2009 Response to Request for Additional Information for License Renewal Application - Balance-of-Plant Scoping and Screening Project stage: Response to RAI ML0912000172009-05-29029 May 2009 Issuance of Environmental Scoping Summary Report Associated with the Staffs Review of the Application by the Nebraska Public Power District, for Renewal of the Operating License for Cooper Nuclear Station Unit 1 Project stage: Approval ML0917500882009-06-0101 June 2009 CNS Lr - NDEQ 2009 Ambient Network Plan Project stage: Request ML0915303162009-06-0808 June 2009 Request for Additional Information for the Review of the Cooper Nuclear Station License Renewal Application Project stage: RAI ML0918300552009-06-0808 June 2009 Reply from Fish and Wildlife Service on Transmission Line for Cooper Nuclear Station License Renewal Project stage: Other ML0917501182009-06-11011 June 2009 CNS Lr - Tornado Occurrences in Nemaha County, Ne 1950-2009 Project stage: Request NLS2009040, Response to Request for Additional Information for License Renewal Application - Aging Management Programs2009-06-15015 June 2009 Response to Request for Additional Information for License Renewal Application - Aging Management Programs Project stage: Response to RAI ML0913803652009-06-15015 June 2009 Audit Report Regarding the Cooper Nuclear Station, Unit 1, License Renewal Application Project stage: Other NLS2009049, Response to Request for Additional Information for License Renewal Application - Section B and C2009-06-22022 June 2009 Response to Request for Additional Information for License Renewal Application - Section B and C Project stage: Response to RAI ML0916002782009-06-29029 June 2009 Request for Additional Information for the Review of the Cooper Nuclear Station License Renewal Application Project stage: RAI ML0916002892009-06-29029 June 2009 Request for Additional Information for Cooper Nuclear Station License Renewal Project stage: RAI ML0917503682009-07-0101 July 2009 Summary of Regulatory Audit Related to the Review of the License Renewal Application for Cooper Nuclear Station Project stage: Approval NLS2009048, Response to Request for Additional Information for License Renewal Application Severe Accident Mitigation Alternatives2009-07-0101 July 2009 Response to Request for Additional Information for License Renewal Application Severe Accident Mitigation Alternatives Project stage: Response to RAI ML0918802582009-07-0808 July 2009 Environment Project Manager Change for the License Renewal of Cooper Nuclear Station Project stage: Other ML0919005022009-07-14014 July 2009 Request for Additional Information for the Review of the Cooper Nuclear Station License Renewal Application Project stage: RAI ML0918804822009-07-14014 July 2009 Request for Additional Information for the Review of Cooper Nuclear Station License Renewal Application Project stage: RAI ML0918804782009-07-14014 July 2009 Request for Additional Information Project stage: RAI ML0918702982009-07-16016 July 2009 Request for Additional Information for the Review of the Cooper Nuclear Station License Renewal Application Project stage: RAI ML0918703042009-07-16016 July 2009 License Renewal Request for Additional Information Project stage: RAI ML0921600842009-07-20020 July 2009 Notice of Diane Currans Withdrawal of Appearance Project stage: Request ML0920902762009-07-29029 July 2009 Request for Additional Information for the Review of the Cooper Nuclear Station License Renewal Application (TACs MD9763 and MD9737) Project stage: RAI NLS2009055, Response to Request for Additional Information for License Renewal Application2009-07-29029 July 2009 Response to Request for Additional Information for License Renewal Application Project stage: Response to RAI NLS2009063, Response to Request for Additional Information for License Renewal Application2009-08-17017 August 2009 Response to Request for Additional Information for License Renewal Application Project stage: Response to RAI ML0919600402009-08-19019 August 2009 Summary of Regulatory Audit Related to the Review of the License Renewal Application for Cooper Nuclear Station Project stage: Approval ML0923106542009-08-28028 August 2009 Request for Additional Information for the Review of the Cooper Nuclear Station License Renewal Application Project stage: RAI ML0926500572009-09-28028 September 2009 Request for Additional Information for the Review of the Cooper Nuclear Station License Renewal Application Project stage: RAI 2009-05-28
[Table View] |
Text
July 14, 2009 Mr. Stewart B. Minahan Chief Nuclear Officer, Vice President - Nuclear Cooper Nuclear Station Nebraska Public Power District 72676 648A Avenue Brownville, NE 68321
SUBJECT:
REQUEST FOR ADDITIONAL INFORMATION FOR THE REVIEW OF THE COOPER NUCLEAR STATION LICENSE RENEWAL APPLICATION (TAC NO.
MD9763 AND MD9737)
Dear Mr. Minahan:
By letter dated September 24, 2008, Nebraska Public Power District submitted an application pursuant to 10 CFR Part 54, to renew the operating license, DPR-46, for Cooper Nuclear Station for review by the U.S. Nuclear Regulatory Commission (NRC or the staff). The staff is reviewing the information contained in the license renewal application and the associated Environmental Report submitted. The staff has identified, in the enclosure, areas where additional information is needed to complete the review. Further requests for additional information may be issued in the future.
Items in the enclosure were discussed with Mr. David Bremer. A mutually agreeable date for the response is within 30 days from the date of this letter, in order to maintain the license renewal review schedule. If you have any questions, please contact Emmanuel Sayoc at 301-415-1924 or by e-mail at emmanuel.sayoc@nrc.gov, or Tam Tran at 301-415-3617 or by e-mail at tam.tran@nrc.gov.
Sincerely,
/RA/
Tam Tran, Project Manager Projects Branch 1 Division of License Renewal Office of Nuclear Reactor Regulation Docket No. 50-298
Enclosure:
As stated cc w/encl: See next page
ML091880476 (Pkg), ML0918804XX (Ltr), ML091880478 (Encl)
OFFICE PM:DLR:RPB2 LA:DLR PM:DLR:RPB2 BC:DLR:RPB2 PM:DLR:RPB1 NAME ESayoc SFigueroa TTran DPelton TTran (Signature)
DATE 07/10/09 07/10/09 07/10/09 07/13/09 07/14/09
Letter to Stewart. B. Minahan from Tam Tran, dated July 14, 2009
SUBJECT:
REQUEST FOR ADDITIONAL INFORMATION FOR THE REVIEW OF THE COOPER NUCLEAR STATION LICENSE RENEWAL APPLICATION (TAC NO.
MD9763 AND MD9737)
DISTRIBUTION:
E-MAIL:
PUBLIC RidsNrrDlrResource RidsNrrDlrRpb1 Resource RidsNrrDlrRpb2 Resource RidsNrrDlrRer1 Resource RidsNrrDlrRer2 Resource RidsNrrDlrRerb Resource RidsNrrDlrRpob Resource RidsNrrDciCvib Resource RidsNrrDciCpnb Resource RidsNrrDciCsgb Resource RidsNrrDraAfpb Resource RidsNrrDraApla Resource RidsNrrDeEmcb Resource RidsNrrDeEeeb Resource RidsNrrDssSrxb Resource RidsNrrDssSbpb Resource RidsNrrDssScvb Resource RidsOgcMailCenter Resource T. Tran E. Sayoc F. Lyon D. Roth (OGC)
A. Jones (OGC)
N. Taylor (RIV)
E. Collins (RIV)
C. Casto (RIV)
B. Maier (RIV)
V. Dricks (RIV)
D. Chamberlain (RIV)
A. Vegel (RIV)
W. Walker (RIV)
G. Miller (RIV)
G. Pick (RIV)
S. Burnell (RIV)
Cooper Nuclear Station cc:
Mr. Ronald D. Asche President and Chief Executive Officer Nebraska Public Power District 1414 15th Street Columbus, NE 68601 Mr. Gene Mace Nuclear Asset Manager Nebraska Public Power District P.O. Box 98 Brownville, NE 68321 Mr. John C. McClure Vice President and General Counsel Nebraska Public Power District P.O. Box 499 Columbus, NE 68602-0499 Mr. David Van Der Kamp Licensing Manager Nebraska Public Power District P.O. Box 98 Brownville, NE 68321 Mr. Michael J. Linder, Director Nebraska Department of Environmental Quality P.O. Box 98922 Lincoln, NE 68509-8922 Chairman Nemaha County Board of Commissioners Nemaha County Courthouse 1824 N Street Auburn, NE 68305 Ms. Julie Schmitt, Manager Radiation Control Program Nebraska Health & Human Services R&L Public Health Assurance 301 Centennial Mall, South P.O. Box 95007 Lincoln, NE 68509-5007 Mr. H. Floyd Gilzow Deputy Director for Policy Missouri Department of Natural Resources P.O. Box 176 Jefferson City, MO 65102-0176 Senior Resident Inspector U.S. Nuclear Regulatory Commission P.O. Box 218 Brownville, NE 68321 Regional Administrator, Region IV U.S. Nuclear Regulatory Commission 612 E. Lamar Blvd., Suite 400 Arlington, TX 76011-4125 Director, Missouri State Emergency Management Agency P.O. Box 116 Jefferson City, MO 65102-0116 Chief, Radiation and Asbestos Control Section Kansas Department of Health and Environment Bureau of Air and Radiation 1000 SW Jackson Suite 310 Topeka, KS 66612-1366 Ms. Melanie Rasmussen Radiation Control Program Director Bureau of Radiological Health Iowa Department of Public Health Lucas State Office Building, 5th Floor 321 East 12th Street Des Moines, IA 50319 Mr. Keith G. Henke, Planner Division of Community and Public Health Office of Emergency Coordination 930 Wildwood P.O. Box 570 Jefferson City, MO 65102 Mr. Art Zaremba, Director of Nuclear Safety Assurance Nebraska Public Power District P.O. Box 98 Brownville, NE 68321 Mr. John F. McCann, Director Licensing, Entergy Nuclear Northeast Entergy Nuclear Operations, Inc.
440 Hamilton Avenue White Plains, NY 10601-1813
Cooper Nuclear Station cc:
Mr. Mike Boyce Cooper Strategic Initiatives Manager Cooper Nuclear Station 72676 - 648A Avenue Brownville, NE 68321 Mr. Dave Bremer License Renewal Project Manager Cooper Nuclear Station 72676 - 648A Avenue Brownville, NE 68321 Mr. Bill Victor License Renewal Project Licensing Lead Cooper Nuclear Station 72676 - 648A Avenue Brownville, NE 68321 Mr. Jim Loynes License Renewal Project Engineer Cooper Nuclear Station 72676 - 648A Avenue Brownville, NE 68321 Mr. Garry Young License Renewal Manager Entergy Nuclear 1448 S.R. 333, N-GSB-45 Russellville, AK 72802 Alan Cox License Renewal Technical Manager Entergy Nuclear 1448 S.R. 333, N-GSB-45 Russellville, AK 72802 Mr. Dave Lach LRP Entergy Project Manager Entergy Nuclear 1448 S.R. 333, N-GSB-45 Russellville, AK 72802