ML082690653
| ML082690653 | |
| Person / Time | |
|---|---|
| Site: | Indian Point |
| Issue date: | 09/25/2008 |
| From: | Doerflein L Engineering Region 1 Branch 2 |
| To: | Joseph E Pollock Entergy Nuclear Operations |
| References | |
| IR-08-010, IR-08-012 | |
| Download: ML082690653 (26) | |
See also: IR 05000247/2008012
Text
September 25, 2008
Mr. Joseph E. Pollock
Site Vice President
Entergy Nuclear Operations, Inc.
Indian Point Energy Center
450 Broadway, GSB
P.O. Box 249
Buchanan, NY 10511-0249
SUBJECT:
INDIAN POINT ENERGY CENTER - NRC EVALUATION OF CHANGES,
TESTS, OR EXPERIMENTS AND PERMANENT PLANT MODIFICATIONS
TEAM INSPECTION REPORT - UNIT 2; AND OPEN ITEM CLOSEOUT - UNIT 3
COMBINED INSPECTION REPORT 05000247/2008012 AND
Dear Mr. Pollock:
On August 14, 2008, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection
at Indian Point Energy Center (IPEC). The enclosed inspection report documents the inspection
results, which were discussed on August 14, 2008, with Mr. T. Orlando, Director of Engineering,
and other members of your staff.
The inspection examined activities conducted under your license as they relate to safety and
compliance with the Commissions rules and regulations and with the conditions of your license.
The inspection involved field walkdowns; examination of selected procedures, calculations and
records; observation of activities; and interviews with station personnel.
This report documents one NRC identified finding which was of very low safety significance
(Green). The finding was determined to involve a violation of NRC requirements. However,
because of the very low safety significance of the violation, and because it was entered into
your corrective action program, the NRC is treating it as a non-cited violation (NCV) consistent
with Section VI.A of the NRC Enforcement Policy. If you contest the NCV in this report, you
should provide a response within 30 days of the date of this inspection report, with the basis for
your denial, to the U. S. Nuclear Regulatory Commission, ATTN: Document Control Desk,
Washington, D.C. 20555-0001, with copies to the Regional Administrator, Region 1; the
Director, Office of Enforcement, U.S. Nuclear Regulatory Commission, Washington, D.C.
20555-0001; and the NRC Resident Inspectors at the IPEC.
J. Pollock
2
In accordance with 10 CFR 2.390 of the NRC's "Rules of Practice," a copy of this letter, its
enclosure, and your response (if any) will be available electronically for public inspection in the
NRC Public Document Room or from the Publicly Available Records (PARS) component of the
NRC's document system (ADAMS). ADAMS is accessible from the NRC Web site at
http://www.nrc.gov/reading-rm/adams.html (the Public Electronic Reading Room).
Sincerely,
/RA/
Lawrence T. Doerflein, Chief
Engineering Branch 2
Division of Reactor Safety
Docket No:
50-247/286
License No:
Enclosure:
Combined Inspection Report 05000247/2008012 and 05000286/2008010
w/Attachment: Supplemental Information
cc w/encl:
Senior Vice President, Entergy Nuclear Operations
Vice President, Operations, Entergy Nuclear Operations
Vice President, Oversight, Entergy Nuclear Operations
Senior Manager, Nuclear Safety and Licensing, Entergy Nuclear Operations
Senior Vice President and COO, Entergy Nuclear Operations
Assistant General Counsel, Entergy Nuclear Operations
Manager, Licensing, Entergy Nuclear Operations
P. Tonko, President and CEO, New York State Energy Research and Development Authority
C. Donaldson, Esquire, Assistant Attorney General, New York Department of Law
A. Donahue, Mayor, Village of Buchanan
J. G. Testa, Mayor, City of Peekskill
R. Albanese, Four County Coordinator
S. Lousteau, Treasury Department, Entergy Services, Inc.
Chairman, Standing Committee on Energy, NYS Assembly
Chairman, Standing Committee on Environmental Conservation, NYS Assembly
Chairman, Committee on Corporations, Authorities, and Commissions
M. Slobodien, Director, Emergency Planning
P. Eddy, NYS Department of Public Service
Assemblywoman Sandra Galef, NYS Assembly
T. Seckerson, County Clerk, Westchester County Board of Legislators
A. Spano, Westchester County Executive
R. Bondi, Putnam County Executive
C. Vanderhoef, Rockland County Executive
E. A. Diana, Orange County Executive
T. Judson, Central NY Citizens Awareness Network
M. Elie, Citizens Awareness Network
D. Lochbaum, Nuclear Safety Engineer, Union of Concerned Scientists
Public Citizen's Critical Mass Energy Project
J. Pollock
3
M. Mariotte, Nuclear Information & Resources Service
F. Zalcman, Pace Law School, Energy Project
L. Puglisi, Supervisor, Town of Cortlandt
Congressman John Hall
Congresswoman Nita Lowey
Senator Hillary Rodham Clinton
Senator Charles Schumer
G. Shapiro, Senator Clinton's Staff
J. Riccio, Greenpeace
P. Musegaas, Riverkeeper, Inc.
M. Kaplowitz, Chairman of County Environment & Health Committee
A. Reynolds, Environmental Advocates
D. Katz, Executive Director, Citizens Awareness Network
K. Coplan, Pace Environmental Litigation Clinic
M. Jacobs, IPSEC
W. Little, Associate Attorney, NYSDEC
M. J. Greene, Clearwater, Inc.
R. Christman, Manager Training and Development
J. Spath, New York State Energy Research, SLO Designee
A. J. Kremer, New York Affordable Reliable Electricity Alliance (NY AREA)
J. Pollock
2
In accordance with 10 CFR 2.390 of the NRC's "Rules of Practice," a copy of this letter, its
enclosure, and your response (if any) will be available electronically for public inspection in the
NRC Public Document Room or from the Publicly Available Records (PARS) component of the
NRC's document system (ADAMS). ADAMS is accessible from the NRC Web site at
http://www.nrc.gov/reading-rm/adams.html (the Public Electronic Reading Room).
Sincerely,
/RA/
Lawrence T. Doerflein, Chief
Engineering Branch 2
Division of Reactor Safety
Docket No:
50-247/286
License No:
Enclosure:
Combined Inspection Report 05000247/2008012 and 05000286/2008010
w/Attachment: Supplemental Information
Distribution w/encl:
(via E-mail)
S. Collins, RA
M. Dapas, DRA
M. Gamberoni, DRS
D. Roberts, DRS
S. Williams, RI OEDO
R. Nelson, NRR
L. Doerflein, DRS
A. Ziedonis, DRS
M. Gray, DRP
B. Bickett, DRP
S. McCarver, DRP
C. Hott, DRP, IP2 RI
T. Koonce, DRP, IP3 RI
Region I Docket Room (with concurrences)
ROPreports Resource
DRS File
SUNSI Review Complete: LTD (Reviewers Initials)
DOCUMENT NAME: G:\\DRS\\Engineering Branch 2\\Ziedonis\\Inspection Reports\\IP2&3_combined_report--2008-
012_Mods_and_2008-010_URI_closeout.doc
After declaring this document An Official Agency Record it will be released to the Public.
To receive a copy of this document, indicate in the box: "C" = Copy without attachment/enclosure "E" = Copy with attachment/enclosure
"N" = No copy
ADAMS ACC#ML082690653
OFFICE
RI/DRS
RI/DRS
RI/DRP
RI/DRS
NAME
AZiedonis/DS/LTD for
WSchmidt/WCook for
MGray/MG
LDoerflein/LTD
DATE
09/24/08
09/24/08
09/25/08
09/25/08
OFFICIAL RECORD COPY
Enclosure
U. S. NUCLEAR REGULATORY COMMISSION
REGION I
Docket No:
50-247, 50-286
License No:
Report No:
05000247/2008012 and 05000286/2008010
Licensee:
Entergy Nuclear Northeast
Facility:
Indian Point Nuclear Generating Units 2 and 3
Location:
450 Broadway, GSB
Buchanan, NY 10511-0308
Dates:
July 28, 2008 through August 14, 2008
Inspectors:
A. Ziedonis, Reactor Inspector (Team Leader)
K. Mangan, Senior Reactor Inspector
S. Smith, Reactor Inspector
Approved by:
Lawrence T. Doerflein, Chief
Engineering Branch 2
Division of Reactor Safety
ii
Enclosure
SUMMARY OF FINDINGS
IR 05000286/2008-010, 05000247/2008-012; 07/28/2008 - 08/14/2008; Indian Point Nuclear
Generating Units 2 and 3; Followup of Events and Notices of Enforcement Discretion and Other
Activities.
The report documents a two week (on-site) team inspection covering the Evaluations of
Changes, Tests, or Experiments and Permanent Plant Modifications on Unit 2; open item
closure on Unit 3; and, Followup of Events and Notices of Enforcement Discretion inspections
on both units. The inspection was conducted by three region-based engineering inspectors.
One finding of very low risk significance (Green) was identified, and was considered to be a
non-cited violation. The significance of most findings is indicated by their color (Green, White,
Yellow, Red) using Inspection Manual Chapter (IMC) 0609, Significance Determination
Process (SDP). Findings for which the SDP does not apply may be Green or be assigned a
severity level after NRC management review. The NRCs program for overseeing the safe
operation of commercial nuclear power reactors is described in NUREG-1649, Reactor
Oversight Process, Revision 4, dated December 2006.
A.
NRC-Identified and Self-Revealing Findings
Cornerstone: Mitigating Systems
Green. The team identified a non-cited violation (NCV) of 10 CFR 50, Appendix B,
Criterion III, Design Control, because Entergy did not verify the adequacy of the
internal recirculation pump minimum flow rates. Specifically, Entergy did not verify
the adequacy of the pump minimum flow rates for sustained operation under low flow
rate conditions or for strong-pump to weak-pump interactions which could result in
dead-heading the weaker pump during parallel pump operation. Following
identification of the issue, Entergy revised the Emergency Operating Procedures
(EOP) to not start a second internal recirculation pump during conditions of high
head recirculation, submitted a licensee event report (LER) for each generating unit,
and entered the issue into the corrective action program.
The finding was determined to be more than minor because it is associated with the
design control attribute of the Mitigating Systems (MS) Cornerstone and affected the
cornerstone objective of ensuring the availability, reliability, and capability of systems
that respond to initiating events to prevent undesirable consequences. On Unit 2,
the team determined the finding was of very low safety significance because it was a
design or qualification deficiency confirmed not to result in loss of operability or
functionality. On Unit 3, the finding was determined to be of very low safety
significance based on a Significance Determination Process (SDP) Phase 3 risk
assessment. Also, the Unit 3 finding had a crosscutting aspect in the area of
Problem Identification and Resolution because Entergy did not implement operating
experience information through changes to station processes, procedures, and
equipment. (IMC 0305 aspect P.2 (b)) (Section 4OA5)
B.
Licensee-Identified Violations
None.
Enclosure
REPORT DETAILS
1.
REACTOR SAFETY
Cornerstones: Initiating Events, Mitigating Systems, Barrier Integrity
1R17 Evaluations of Changes, Tests, or Experiments and Permanent Plant Modifications (IP
.1
Evaluations of Changes, Tests, or Experiments (24 samples)
a.
Inspection Scope
The team reviewed one safety evaluation to determine whether the changes to the
facility or procedures, as described in the Updated Final Safety Analysis Report
(UFSAR), had been reviewed and documented in accordance with 10 CFR 50.59. In
addition, the team evaluated whether Entergy had been required to obtain NRC approval
prior to implementing the change. The team interviewed plant staff and reviewed
supporting information including calculations, analyses, design change documentation,
procedures, the UFSAR, technical specifications (TS), and plant drawings, to assess the
adequacy of the safety evaluation. The team compared the safety evaluation and
supporting documents to the guidance and methods provided in Nuclear Energy Institute
(NEI) 96-07, Guidelines for 10 CFR 50.59 Evaluations, as endorsed by NRC
Regulatory Guide 1.187, "Guidance for Implementation of 10 CFR 50.59, Changes,
Tests, and Experiments," to determine the adequacy of the safety evaluation.
The team also reviewed a sample of twenty-three 10 CFR 50.59 screenings and
applicability determinations for which Entergy had concluded that no safety evaluation
was required. These reviews were performed to assess whether Entergy's threshold for
performing safety evaluations was consistent with 10 CFR 50.59. The sample of issues
inspected that had been screened out by Entergy included procedure changes, design
changes, calculations, and set point changes.
The single safety evaluation reviewed was the only safety evaluation performed by
Entergy during the time period covered under this inspection (i.e., since the last team
inspection that evaluated changes, tests, or experiments). The screenings and
applicability determinations were selected based on the risk significance of the
associated structures, systems, and components (SSCs).
In addition, the team compared Entergy's administrative procedures, used to control the
screening, preparation, review, and approval of safety evaluations, to the guidance in
NEI 96-07 to determine whether those procedures adequately implemented the
requirements of 10 CFR 50.59. The safety evaluations, screenings, and applicability
determinations reviewed by the team are listed in the attachment.
b.
Findings
No findings of significance were identified.
2
Enclosure
.2
Permanent Plant Modifications (8 samples)
.2.1
125 Volt Direct Current Circuit Breaker Replacements
a.
Inspection Scope
The team reviewed a modification to replace the direct current (DC) HFB-model circuit
breakers in panel 23 due to breaker age concerns. The review was performed to
determine whether the design bases, licensing bases, and performance capability of the
DC electrical distribution system had been degraded by the modification. Additionally,
the 10 CFR 50.59 screen associated with this modification was reviewed as described in
section 1.1 of this report.
The team assessed selected design attributes to determine whether they were
consistent with the design and licensing bases. The attributes included component
safety classification, breaker trip coordination requirements, and seismic qualification of
the breaker and electrical panel. The team evaluated design assumptions in the
supporting evaluations and analyses to determine whether they were technically
appropriate and consistent with the Updated Final Safety Analysis Report (UFSAR).
The team reviewed selected evaluations, drawings, analysis, procedures, and the
UFSAR to determine whether they were properly updated with any revised design
information. The team evaluated the post-modification tests to determine whether the
breaker would function in accordance with design requirements. In addition, the team
interviewed the responsible design and system engineers to discuss the circuit breaker
replacements and design requirements. The documents reviewed are listed in the
attachment.
b.
Findings
No findings of significance were identified.
.2.2
Removal of Turbine Trip Protection for Uneven Expansion
a.
Inspection Scope
The team reviewed a modification to remove the turbine trip feature protecting against
uneven expansion of turbine rotational components with respect to the stationary
components of the system. The review was performed to determine whether the design
bases, licensing bases, and performance capability of the steam system or reactor
protection system had been degraded by the modification. Additionally, the 10 CFR
50.59 screen associated with this modification was reviewed as described in section 1.1
of this report.
The team assessed selected design attributes to determine whether they were
consistent with the design and licensing bases. These attributes included component
safety classification, adequacy of operator indication for protection of the turbine, and the
establishment of appropriate procedure guidance to manually trip the turbine in the event
of uneven turbine expansion. The team evaluated design assumptions in the supporting
evaluations and analyses to determine whether they were technically appropriate and
consistent with the UFSAR. The team reviewed selected evaluations, drawings,
3
Enclosure
analyses, procedures, and the UFSAR to determine whether they were properly updated
with any revised design information. The team evaluated the post-modification test to
verify that the trip function had been properly isolated. In addition, the team interviewed
the responsible design and system engineers to discuss the modification and the design
requirements. The documents reviewed are listed in the attachment.
b.
Findings
No findings of significance were identified.
.2.3
Removal of Turbine Trip Protective Features
a.
Inspection Scope
The team reviewed a modification to the main generator stator water cooling system.
The modification removed single point vulnerabilities that could lead to an inadvertent
main turbine trip, including main generator rectifier cooling flow and stator water cooling
inlet flow. The review was performed to determine whether the design bases, licensing
bases, and performance capability of the steam system or reactor protection system had
been degraded by the modification. Additionally, the 10 CFR 50.59 screen associated
with this modification was reviewed as described in section 1.1 of this report.
The team assessed selected attributes of the modification process to determine whether
they were consistent with the design and licensing bases. These attributes included
component safety classification, adequacy of operator indication for protection of the
turbine, and the establishment of appropriate procedure guidance to manually trip the
turbine based on alarms and other indications. Design assumptions were reviewed to
evaluate whether they were technically appropriate and consistent with the UFSAR. The
team reviewed selected calculations, drawings, analysis, procedures, and the UFSAR to
determine whether they were properly updated with revised design information and
operating guidance. The team evaluated the post-modification tests to verify that the
safety related trip functions associated with the turbine were not degraded by the
modification. In addition, the team interviewed the responsible design and system
engineers to discuss the modification and the design requirements. The documents
reviewed are listed in the attachment.
b.
Findings
No findings of significance were identified.
.2.4
Internal Recirculation Pump Level Transmitter Modification
a. Inspection Scope
The team reviewed a modification to level transmitter LT-938, which is used for
indication of internal recirculation pump suction level during inservice testing. The
modification was performed to support changes in testing requirements of the internal
recirculation pumps, due to changes in American Society of Mechanical Engineers
(ASME) code acceptance criteria, which will require a higher suction water level to
ensure adequate submergence during testing at higher flow rates. The review was
4
Enclosure
performed to determine whether the design bases, licensing bases, and performance
capability of the internal recirculation system had been degraded by the modification.
Additionally, the 10 CFR 50.59 screen associated with this modification was reviewed as
described in section 1.1 of this report.
The team assessed selected design attributes to determine whether they were
consistent with the design and licensing bases. These attributes included component
safety classification, instrument uncertainty, adequacy of level transmitter position, and
adequacy of the water level for pump testing. The team evaluated design assumptions
in the supporting evaluations and analyses to determine whether they were technically
appropriate and consistent with the UFSAR. The team reviewed selected evaluations,
drawings, analysis, procedures, and the UFSAR to determine whether they were
properly updated with any revised design information. The team evaluated the post-
modification test to determine whether the final installed set points were within the
acceptance band to verify that the level transmitter would function in accordance with
design assumptions. In addition, the team interviewed the responsible design and
system engineers to discuss the modification and the design requirements. The
documents reviewed are listed in the attachment.
b.
Findings
No findings of significance were identified.
.2.5
Installation of 3/4-inch Vent Line in Safety Injection System Piping
a.
Inspection Scope
The team reviewed a modification to install a vent line on a relative high point in the
safety injection discharge line to allow for venting gasses to ensure the safety injection
piping remains full of water. The review was performed to determine whether the design
bases, licensing bases, and performance capability of the safety injection system had
been degraded by the modification. Additionally, the 10 CFR 50.59 screen associated
with this modification was reviewed as described in section 1.1 of this report.
The team assessed selected design attributes to determine whether they were
consistent with the design and licensing bases. These attributes included component
safety classification, ASME piping requirements, and procedural guidance for venting
operations. The team evaluated design assumptions in the supporting evaluations and
analyses to determine whether they were technically appropriate and consistent with the
UFSAR. The team reviewed selected evaluations, drawings, analysis, procedures, and
the UFSAR to determine whether they were properly updated with any revised design
information. The team evaluated the post-modification test to determine whether the
new piping and valve would function in accordance with design requirements. In
addition, the team interviewed the responsible design and system engineers to discuss
the installation of the vent line as well as design requirements. Finally, the team walked
down the safety injection system vent line to detect any potentially abnormal installation
conditions. The documents reviewed are listed in the attachment.
5
Enclosure
b.
Findings
No findings of significance were identified.
.2.6
Modification to Replace Hydraulic Snubbers
a.
Inspection Scope
The team reviewed documents regarding the replacement of Bergen-Patterson snubbers
with Lisega snubbers of equivalent load rating and pin-to-pin dimension. The Bergen-
Patterson snubbers were replaced due to age degradation and obsolescence. The new
snubbers were selected based on equivalency of design. Additionally, the new snubbers
enhanced design qualities related to inspection and preventive maintenance
requirements. The review was performed to determine whether the design bases,
licensing bases, and performance capability of systems and components supported by
the snubbers had been degraded by the modification. Additionally, the 10 CFR 50.59
screen associated with this modification was reviewed as described in section 1.1 of this
report.
The team assessed selected design attributes to determine whether they were
consistent with the design and licensing bases. These attributes included component
safety classification, load rating and load requirements, hydraulic fluid viscosity,
allowable displacement, and snubber inspection requirements. The team evaluated
design assumptions in the supporting evaluations and analyses to determine whether
they were technically appropriate and consistent with the UFSAR. The team reviewed
selected evaluations, drawings, analyses, procedures, and the UFSAR to determine
whether they were properly updated with any revised design information. In addition, the
team interviewed the responsible design and system engineers to discuss vendor
acceptance testing of the snubbers, as well as snubber installation and post-installation
inspection. Finally, the team walked down a sample of Lisega snubbers to detect any
potentially abnormal installation conditions. The documents reviewed are listed in the
attachment.
b.
Findings
No findings of significance were identified.
.2.7
Main Boiler Feed Pump Temperature Control Valve Modifications
a.
Inspection Scope
The team reviewed a modification to replace the temperature control valves (TCVs) on
the seal water injection system for the main boiler feed pump. The modification was
performed to increase the reliability of the automated temperature control feature, as
well as provide more appropriately sized valves for temperature control of the seal water
injection system. The review was performed to determine whether the design bases,
licensing bases, and performance capability of the safety injection system had been
degraded by the modification. Additionally, the 10 CFR 50.59 screen associated with
this modification was reviewed as described in section 1.1 of this report.
6
Enclosure
The team assessed selected design attributes to determine whether they were
consistent with the design and licensing bases. These attributes included component
safety classification, automated set points, manual valve control features, and the ability
to provide adequate seal water injection to ensure functionality of the main boiler feed
pumps. The team evaluated design assumptions in the supporting evaluations and
analyses to determine whether they were technically appropriate and consistent with the
UFSAR. The team reviewed selected evaluations, drawings, work orders, procedures,
and the UFSAR to determine whether they were properly updated with any revised
design information. The team evaluated the post-modification tests to determine
whether the new valves would function in accordance with design assumptions. In
addition, the team interviewed the responsible design and system engineers to discuss
the modification and the design requirements. Finally, the team walked down the new
TCVs to detect any potentially abnormal installation conditions. The documents
reviewed are listed in the attachment.
b.
Findings
No findings of significance were identified.
.2.8
Modification to Install a Spacer Ring in Main Feedwater Valve
a.
Inspection Scope
The team reviewed a modification to install a cage spacer in main feedwater flow control
valve (FCV) 427, to prevent the valve cage from shifting in position while in service. The
review was performed to determine whether the design bases, licensing bases, and
performance capability of the safety injection system had been degraded by the
modification. Additionally, the 10 CFR 50.59 screen associated with this modification
was reviewed as described in section 1.1 of this report.
The team assessed selected design inputs and attributes to determine whether they
were consistent with the design and licensing bases. These attributes included
component safety classification, effect on valve flow coefficient and stroke time, material
compatibility with feedwater chemistry, and evaluations for changes in piping stress.
The team evaluated design assumptions in the supporting evaluations and analyses to
determine whether they were technically appropriate and consistent with the UFSAR.
The team reviewed selected evaluations, drawings, analysis, procedures, and the
UFSAR to determine whether they were properly updated. The team evaluated the
post-modification tests to verify that the valves ability to stroke was not degraded by the
modification. In addition, the team interviewed the responsible design and system
engineers to discuss the modification and the design requirements. The team also
walked down the main feedwater flow control valves to detect possible abnormal
installation conditions. The documents reviewed are listed in the attachment.
b.
Findings
No findings of significance were identified.
7
Enclosure
4.
OTHER ACTIVITIES
4OA2 Identification and Resolution of Problems (IP 71152)
a.
Inspection Scope
The team reviewed a sample of condition reports associated with 10 CFR 50.59 issues
and plant modification issues to determine whether Entergy was appropriately
identifying, characterizing, and correcting problems associated with these areas, and
whether the planned or completed corrective actions were appropriate. The condition
reports reviewed are listed in the attachment.
b.
Findings
No findings of significance were identified.
4OA3 Follow-up of Events and Notices of Enforcement Discretion (IP 71153 - 2 samples)
.a
Inspection Scope
.1
(Closed) LER 05000247/2007005, Technical Specification Prohibited Condition Due to
Exceeding the Allowed Completion Time for an Inoperable Recirculation Pump Caused
by a Potential Strong Pump-Weak Pump Interaction During a Small Break Loss of
Coolant Accident (SBLOCA)
On November 8, 2007, Unit 2 entered Technical Specification 3.5.2, Emergency Core
Cooling System, Condition A, for one or more Emergency Core Cooling (ECCS) trains
inoperable. A condition was identified, during an NRC Component Design Bases
Inspection, where a stronger internal recirculation pump could shut the discharge check
valve of the weaker internal recirculation pump, causing the weaker pump to deadhead.
This condition applied to certain accident scenarios with conditions of high pump head
and low flow, such as during a SBLOCA. Immediate actions were taken to declare one
train of the internal recirculation system inoperable, and revise Emergency Operating
Procedures (EOPs) to eliminate the requirement to start a second internal recirculation
pump. The team reviewed the LER, as well as the corrective actions to the EOPs to
verify that the changes were adequate. The team also reviewed additional procedures,
calculations, condition reports, corrective actions, and conducted interviews with
engineering staff to verify that the condition was adequately corrected. The team
determined that Entergys failure to evaluate the internal recirculation pumps for
adequate minimum flowrates was a finding of very low safety significance (Green)
involving a non-cited violation (NCV) of 10 CFR 50, Appendix B, Design Control (see
section 4OA5.1b below). This LER is closed.
.2
(Closed) LER 05000286/2007003, Technical Specification Prohibited Condition Due to
Exceeding the Allowed Completion Time for an Inoperable Recirculation Pump Caused
by a Potential Strong Pump-Weak Pump Interaction During a Small Break Loss of
Coolant Accident (SBLOCA)
On November 8, 2007, the Unit 3 internal recirculation pump no. 31 was declared
inoperable and Technical Specification 3.5.2, Emergency Core Cooling System,
8
Enclosure
Condition A, was entered for one or more Emergency Core Cooling (ECCS) trains
inoperable. A condition was identified, during an NRC Component Design Bases
Inspection, where a stronger internal recirculation pump could shut the discharge check
valve of the weaker internal recirculation pump, causing the weaker pump to deadhead.
This condition applied to certain accident scenarios with conditions of high pump head
and low flow, such as during a SBLOCA. Immediate actions were taken to declare one
train of the internal recirculation system inoperable, and revise Emergency Operating
Procedures (EOPs) to eliminate the requirement to start a second internal recirculation
pump. The team reviewed the LER, as well as the corrective actions to the EOPs to
verify that the changes were adequate. The team also reviewed additional procedures,
calculations, condition reports, corrective actions, and conducted interviews with
engineering staff to verify that the condition was adequately corrected. Also see section
4OA5.1a below for additional inspection activity related to this Unit 3 LER. The team
determined that Entergys failure to evaluate the internal recirculation pumps for
adequate minimum flowrates was a finding of very low safety significance (Green)
involving an NCV of 10 CFR 50, Appendix B, Design Control. (see section 40A5.1b
below) This LER is closed.
b.
Findings
See section 4OA5.1b for the finding related to LERs 05000247/2007005 and
4OA5 Other Activities
.1
(Closed) URI 05000286/2007006-02: Inadequate Design Control of Recirculation
Pumps
a.
Inspection Scope
During the Unit 3 Component Design Bases Inspection (CDBI) performed in 2007, the
team identified an unresolved item (URI) concerning the adequacy of design control
associated with a modification that replaced both internal recirculation pumps (low
pressure recirculation (LPR) pumps 31 and 32, or 31 LPR pump and 32 LPR pump) in
March 2007. Specifically, Entergy did not assess two critical design parameters
associated with design basis requirements for the pumps: minimum flow requirements
for sustained pump operation under low flow conditions, which involved design flow rates
for small break loss-of-coolant accidents (SBLOCA) that were potentially below the
vendor recommended flow rates for sustained operation of the pumps; and strong-pump
to weak-pump interactions that could result in parallel pump dead-heading of the weaker
pump. With respect to conditions of parallel pump operation that result in a strong-pump
to weak-pump interaction, the weaker pump will become dead-headed without an
adequately sized minimum flow line. As a result of the NRC-identified issue, Entergy
determined that the weaker pump was only susceptible to dead-heading during SBLOCA
scenarios involving high head recirculation. Immediate corrective actions were taken by
Entergy to address this performance deficiency. URI 2007006-02 was opened to allow
an integrated NRC review of the LPR pumps prior operability with respect to pump
dead-heading, and also with respect to Entergys evaluation of the LPR pumps
sustained minimum flow requirements, which was still ongoing at the completion of the
CDBI inspection in December 2007.
9
Enclosure
During this inspection, the team completed the integrated review of both the sustained
minimum flow and the dead-heading issues. The team reviewed procedures, design
basis documents, calculations, condition reports, corrective actions, and conducted
interviews with engineering staff to verify measures were established to maintain design
basis requirements with respect to:
the sustained minimum flow issue. The team reviewed recirculation system
hydraulic models performed by Entergy for SBLOCA scenarios to determine the
expected minimum core flows and individual pump flows. The team also
reviewed evaluations performed by the pump vendor, Flowserve, to evaluate the
sustained minimum flow requirements of the new internal recirculation pumps
during SBLOCA scenarios. Based on review of Entergys analyses and
Flowserves evaluations, the team was able to verify that individual pump flows
during SBLOCA scenarios would be sufficient to meet the sustained minimum
flow requirements for the pumps to operate successfully. The team noted the
analysis for LPR pump sustained minimum flow was performed on both units.
the LPR pump dead-heading issue. The team reviewed completed surveillance
test data and vendor pump curve data. See the discussion under Description in
section 4OA5.1.b.
Based on the teams review of the Entergy analysis of the sustained minimum flow issue
and the corrective actions taken to address the dead-heading issue, this unresolved item
is closed.
b.
Findings
Introduction: The team identified a finding of very low safety significance (Green)
involving a non-cited violation (NCV) of 10 CFR 50, Appendix B, Criterion III, Design
Control, at both Unit 2 and Unit 3, because Entergy did not verify the adequacy of the
internal recirculation pump minimum flow rates. Specifically, Entergy did not verify the
adequacy of the pump minimum flow rates for sustained operation under low flow rate
conditions or for strong-pump to weak-pump interactions.
Description: For both units, the internal recirculation portion of the low-head safety
injection system consists of two low pressure recirculation (LPR) pumps, located in
primary containment, that take suction from a containment sump and discharge into a
common header. Each LPR pump has a 3/4-inch minimum flow line upstream of the
pump discharge check valve, and the two pumps share a 2-inch minimum flow line on
the common discharge header. All three minimum flow lines return to the containment
sump. With respect to system operation, prior to December 2007, the EOPs directed
operators to sequentially start both recirculation pumps during the recirculation phase of
any loss-of-coolant accident (LOCA).
NRC Bulletin 88-04, "Safety-Related Pump Loss," documented industry operating
experience regarding design deficiencies involving a weaker pump (i.e., low discharge
head at a given flow rate) that could be dead-headed when operated in parallel with a
stronger pump (i.e., higher discharge head at the equivalent flow rate), under low flow
conditions, for system configurations where both pumps share a common minimum flow
line. Letter IP3-89-036, dated May 12, 1989, provided the licenseesBulletin 88-04
10
Enclosure
response to the NRC. The licensee stated that although the recirculation pumps shared
a common minimum flow line, the potential for a stronger pump to dead-head a weaker
pump did not exist. The basis, in part, was that having the individual pump minimum
flow lines upstream of the pump discharge check valve would ensure flow through the
pump even if the stronger pump would cause the discharge check valve on the weaker
pump to close. The licensee also credited the EOPs with preventing the weak pump
from becoming dead-headed, based on an assumption that by the time the EOPs
directed starting of the second pump, flow to the reactor core would be sufficient to allow
both pumps to operate at a point on their performance curves where there was adequate
flow for both pumps.
In December 2007, following NRC identification of potential parallel pump dead-heading
of the LPR pumps at Unit 3, Entergy took actions to prevent the parallel operation of the
internal LPR pumps. Subsequent action was taken by Entergy at Unit 2 upon
confirmation of a similar configuration. Entergy entered this issue into their corrective
action program as CR-IP2-2007-04558 and CR-IP3-2007-04212. As an immediate
corrective action, Entergy revised EOPs 2-ES-1.2 and 2-ES-1.3, Transfer to Cold Leg
Recirculation, and also 2-ES-1.4 and 3-ES-1.4, Transfer to Hot Leg Recirculation, so
that the second internal recirculation pump would not be started during conditions of high
head recirculation on either unit.
The team concluded that Entergy, as part of the Unit 3 modification in 2007 and the Unit
2 modification in 2000 which installed two new LPR pumps on each unit, had not
evaluated the design for strong-pump to weak-pump interaction. Regarding Unit 3, the
team determined, based on a review of vendor supplied pump performance curves and
pump surveillance data, that the 31 LPR pump was susceptible to dead-heading if both
the 31 and 32 LPR pumps were operated in parallel during certain SBLOCA scenarios
involving high head recirculation, as required by EOPs. The team's review of the new
recirculation pump performance curves identified that the 32 LPR pump had
approximately 10 pounds-per-square-inch (psi) greater discharge pressure, under low
flow conditions, than the 31 LPR pump. The team noted that the installed 3/4 inch
minimum flow valve was throttled to 1.5 turns open, resulting in an as-found 0.1 gallons-
per-minute (gpm) flow. This low flow rate would not have been sufficient to prevent
pump damage if the 31 LPR pump discharge check valve closed due to the higher
discharge pressure for the 32 LPR pump.
In addition, the previous engineering evaluation for potential strong-pump to weak-pump
interaction of the recirculation pumps appeared to be inconsistent with Entergys most
current SBLOCA accident analysis performed as a result of the NRC-identified issue,
and also inconsistent with the current throttled configuration of the 3/4 inch minimum
flow line.
Regarding Unit 2, the team determined that it was unlikely that the 21 and 22 LPR
pumps were susceptible to parallel pump dead-heading, based on vendor pump curves
and surveillance test data, which showed that the current pump discharge pressures
were nearly equivalent for low flow conditions.
As noted in section 40A5.1a, Entergy performed an analysis for both units which
determined the individual LPR pump flows during SBLOCA scenarios would be sufficient
to meet the sustained minimum flow requirements for the pumps.
11
Enclosure
Analysis: The team determined that Entergys failure to evaluate the LPR pumps for
suitability of application to the internal recirculation system configuration at Unit 2 and
Unit 3 constituted a performance deficiency and a finding. Absent the 2007 NRC CDBI
identification of the issue at Unit 3, the similar issue at Unit 2 would likely have remained
undiscovered. The finding is greater than minor because it is associated with the design
control attribute of the Mitigating Systems (MS) Cornerstone and affected the
cornerstone objective of ensuring the availability, reliability, and capability of systems
that respond to initiating events to prevent undesirable consequences (i.e., core
damage).
Unit 3: Using Phases 1 and 3 of the NRCs Significance Determination Process, the
team determined the significance of the 31 LPR pump susceptibility to parallel pump
dead-heading, between March 2007 and December 2007. The team evaluated this
finding using NRC Inspection Manual Chapter (IMC) 0609.04, Phase 1 - Initial
Screening and Characterization of Findings. Using the Table 4a characterization
worksheet for the MS Cornerstone, the finding was determined to represent an actual
loss of a safety function for a single LPR train for greater than the Technical
Specification allowed outage time because of the differences in pump performance,
during certain SBLOCA scenarios that required high pressure recirculation (HPR).
Accordingly, this issue required evaluation under Appendix A to IMC 0609.
A Region I Senior Reactor Analyst (SRA) completed a Phase 3 risk assessment
determining that this issue was of very low safety significance (Green). The Phase 3
assessment was conducted because the issue was not suitable to a Phase 2 analysis.
The 31 LPR pump was assumed to fail internally, due to insufficient minimum pump flow
(pump damage), if the 32 LPR pump also was started in SBLOCA initiating events when
entering high pressure recirculation. The operation of the 31 LPR pump would not have
been affected if the 32 LPR pump failed to start independently or because it did not have
electrical power. The SRA used the IP3 Standardized Plant Analysis Review (SPAR)
model version 3.45 to complete an internal events review. As a bounding case, the SRA
assumed that the 31 internal LPR pump would fail to run in all SBLOCA initiating events.
The SRA then reviewed the increase in core damage probability for sequences where
HPR was assumed to fail. The dominate core damage sequence was a SBLOCA with:
success of AFW and high pressure injection, failure to cooldown, and subsequent failure
of HPR. The estimated increase in core damage probability, given the nine month
exposure period (March to December 2007), was very small: four-orders of magnitude
below the 1E-6 per year Green-White risk significance threshold (E-10 per year).
The cause of this finding had a cross-cutting aspect in the area of Problem Identification
and Resolution because Entergy did not implement operating experience information
through changes to station processes, procedures, and equipment (P.2.(b)).
Specifically, during the recent modification to the internal recirculation pumps, Entergy
did not sufficiently review their original response to NRC Bulletin 88-04 regarding the
potential dead-heading of safety related pumps. Additionally, previous Licensee Event
Reports (LERs) from other stations document that the same strong-pump to weak-pump
interaction has occurred at other power reactor plants within the industry.
Unit 2: The team determined that both LPR pumps (21 and 22) were not likely
susceptible to parallel pump dead-heading during certain SBLOCA scenarios, based on
vendor pump curves and current surveillance test data, and therefore would have
12
Enclosure
delivered adequate coolant flow to the reactor core as required by Emergency Operating
Procedures. The team evaluated this finding using NRC Inspection Manual Chapter
(IMC) 0609.04, Phase 1 - Initial Screening and Characterization of Findings. Using the
Table 4a characterization worksheet for the MS Cornerstone, the finding was determined
to be of very low safety significance (Green) because it was a design or qualification
deficiency confirmed not to result in loss of operability or functionality.
This deficiency was not indicative of current performance because the modification on
Unit 2 was performed in May of 2000. Therefore, there was no cross-cutting aspect
associated with this finding.
Enforcement: 10 CFR Part 50, Appendix B, Criterion III, Design Control, requires, in
part, that measures be established for verifying or checking the adequacy of design such
as by the performance of design reviews, by the use of alternate or simplified
calculational methods, or by the performance of a suitable testing program. Contrary to
the above, Entergy replaced the internal recirculation pumps during modifications on
Unit 3 in March of 2007 and on Unit 2 in May 2000, and did not verify the design
adequacy of the pump minimum flow rates for sustained operation under low flow rate
conditions or for strong-pump to weak pump interactions which could result in dead-
heading the weaker pump during parallel pump operation. This condition existed until
identified by the NRC in December of 2007, resulting in subsequent corrective actions by
Entergy to revise the EOPs, as described above. Because this finding was of very low
safety significance and was entered into the corrective action program as CR-IP2-2007-
4558, and as CR-IP3-2007-4212, this violation is being treated as an NCV, consistent
with section VI.A.1 of the NRC Enforcement Policy. (NCV 05000247/2008012-01, and
NCV 05000286/2008010-01, Inadequate Design Control of Internal Recirculation
Pumps)
.2
(Closed) URI 05000247/2007007-03: Use of Motor Control Center (MCC) Methodology
for Periodic Verification of the Design Basis Capability of Safety-Related Motor Operated
Valves (MOVs)
a.
Inspection Scope
During a Component Design Bases Inspection (CDBI) performed in 2007, the team
identified an unresolved item (URI) concerning the adequacy of MCC testing
methodology for MOVs. Specifically, Entergy did not use the testing methodology
approved by the NRC as part of the Generic Letter (GL) 96-05 reviews, which required
direct measurements of stem thrust and torque to be recorded at-the-valve. The URI
was opened to determine if the results from the MCC testing methodology could
adequately show that the design basis of the MOVs was maintained. The team
interviewed the system engineer and found that following NRC-identification of the issue,
Entergy suspended the MCC testing program, and subsequently re-tested all valves that
had been previously tested using the MCC testing methodology. The re-test used the
GL 96-05 testing methodology, and the team verified that the MOVs had maintained
their design basis capability.
Additionally, the team reviewed the licensees commitments as described in their
response to GL 96-05 and determined that Entergy had committed to the at-the-valve
testing methodology. The team concluded that prior to implementing the MCC testing
13
Enclosure
methodology, Entergy was required to submit a change to the GL commitment. The
team found that because the testing methodology did not conform to all the requirements
outlined in the methodology basis documents, and the testing had not been previously
approved by NRC, a violation of NRC requirements had occurred. However, because
the retest determined that the valves had maintained their design basis capability, the
team concluded that the associated finding was of minor significance that was not
subject to enforcement action per section IV.B of the Enforcement Policy. This URI is
closed.
b.
Findings
No findings of significance were identified.
4OA6 Meetings, including Exit
The team presented the inspection results to Mr. T. Orlando, Director of Engineering,
and other members of Entergy's staff at an exit meeting on August 14, 2008. The team
verified that this report does not contain proprietary information.
A-1
Attachment
ATTACHMENT
SUPPLEMENTAL INFORMATION
KEY POINTS OF CONTACT
Licensee Personnel
H. Anderson
Licensing Specialist
F. Bloise
Senior Design Engineer
G. Dahl
Licensing Specialist
J. Hill
Design Engineering Supervisor, I&C
T. McCaffrey
Design Engineering Manager
V. Myers
Design Engineering Supervisor, Mechanical
T. Orlando
Director of Engineering
A. Vitale
General Manager of Plant Operations
R. Walpole
Licensing Manager
A. Williams
Managers of Operations
J. Bencivenga
Senior Design Engineer
LIST OF ITEMS OPENED, CLOSED AND DISCUSSED
Open and Closed 05000247/2008012-01
Inadequate Design Control of Internal
Recirculation Pumps (Section 4OA5.1)05000286/2008010-01
Inadequate Design Control of Internal
Recirculation Pumps (Section 4OA5.1)
Closed
Technical Specification Prohibited Condition
Due to Exceeding the Allowed Completion
Time for an Inoperable Recirculation Pump
Caused by a Potential Strong Pump-Weak
Pump Interaction During a Small Break
Loss of Coolant Accident (Sections 4OA3.1)
Technical Specification Prohibited Condition
Due to Exceeding the Allowed Completion
Time for an Inoperable Recirculation Pump
Caused by a Potential Strong Pump-Weak
Pump Interaction During a Small Break
Loss of Coolant Accident (Section 4OA3.2)
A-2
Attachment 05000247/2007007-03
Use of Motor Control Center Methodology
for Periodic Verification of the Design Basis
Capability of Safety-Related MOVs (Section
4OA5.2)05000286/2007006-02
Inadequate Design Control of Internal
Recirculation Pumps (Section 4OA5.1)
LIST OF DOCUMENTS REVIEWED
Section 1R017: Evaluations of Changes, Tests, or Experiments and Permanent
Plant Modifications
10 CFR 50.59 Evaluations
07-2002-01-Eval, 10 CFR 72.212 Report Appendix F: New Licensing Basis Document
10 CFR 50.59 Screened-out Evaluations
0-AOP-SEC-2, Aircraft Threat, Rev. 4
2-PT-M021A, Emergency Diesel Generator 21 Load Test, Rev. 17
2-PT-M108R04, RHR/SI System Venting, dated 4/19/08
2-PT-Q024B, 22 EDG Fuel Oil Transfer Pump, Rev. 10
2-PT-Q033A, 21 Charging Pump, Rev. 13
2-PT-R007AR20, Motor Driven AF Pump Full Flow, dated 1/22/08
2-SOP-27.3.1.1 21 Emergency Diesel Generator Manual Operation, Rev. 21
EC 5456, Revision to the 22 AFP Turbine Overspeed Set Point Lower Tolerance, Rev. 0
EOPs E-0 through ES-3.2, Westinghouse Owners Group Changes to Revision Number 2 of the
EOPs (All procedures are Rev. 0)
ER-04-2-072, Main Boiler Feed Pump Seal Injection System Upgrade, Rev. 0
ER-05-2-137, Increase Reliability of the Stator Water Cooling Generator, Rev. 0
ER-06-2-027, Increase Recirculation Pump flows to meet IST Code Requirements by 2008,
dated 4/22/08
ER-06-2-031, 118V AC/ 118V AC Electrical (Replacement of 2 Pole HFB Bkrs in IP2 125V DC
Power Panel 23), Rev. 0
ER-06-2-048, Installation of 3/4 Vent Valve Downstream of SI-MOV-888A/B, Rev. 0
ER-06-2-058, Hydraulic Snubber Replacements, Rev. 0
ER-06-2-115, Install Surge Suppressors on Relays to Defeat 21 and 22 MBFP, Rev. 0
ER-06-2-141, DC/ 125 DC System (Removing Delta Expansion Turbine Trip), Rev. 0
ER-07-2-047, FCV-427 Anti-Rotation Device, Rev. 0
IP2-03-24983, Power Uprate: Setpoint Changes, dated 1/3/07
IP-CALC-06-00218, AST Analysis for a Design-Basis Stem Generator Tube Rupture Analysis,
Rev. 0
IP-SMM-AD-102, IPEC Implementing Procedure Preparation, Review, and Approval -
Attachment 10.2: Core Operation Limits Report (COLR), Rev. 5
SCR-07-2-058, Set Point Change Number 07-2-058, Internal Recirculation Pump Level
Transmitter Modification, Rev. 0
SPDDF-PC-439AR01, ESFAS Actuation on High Differential Steam line Pressure, dated
11/27/06
A-3
Attachment
Modification Packages
ER-04-2-072, Main Boiler Feed Pump Seal Injection System Upgrade, Rev. 0
ER-05-2-137, Increase Reliability of the Stator Water Cooling Generator, Rev. 0
ER-06-2-048, 3/4-inch Vent Line Install, Rev. 0
ER-06-2-058, Hydraulic Snubber Replacements, Rev. 0
ER-06-2-031, Replacement of 2 Pole HFB Bkrs in IP2 125V DC Power Panel 23, Rev. 0
ER-06-2-141, Removing Delta Expansion Turbine Trip, Rev. 0
ER-07-2-047, FCV-427 Anti-Rotation Device, Rev. 0
SCR-07-2-058, Set Point Change Number 07-2-058, Internal Recirculation Pump Level
Transmitter Modification, Rev. 0
Calculations & Analysis
IP-CALC-07-00184, SIS Valve Operation Inside the Vapor Containment, Rev. 0
IP-CALC-06-00218, AST Analysis for a Design-Basis Steam Generator Tube Rupture
Accident, Rev. 0
FIX-00046, Calibration of Turbine Inlet Pressure and High Steam Flow (SF)/ Safety
Injection Components for Stretch Power Uprate, Rev. 03P
FIX-00129, Turbine Inlet Pressure Transmitter Static Head Sealing and Calibrations,
Rev. 5
GMS-00035, Stress Analysis of Line 60 Due to Addition of Vent Valve Downstream of
888A and 888B, Rev. 0
Drawings
A225105, Logic Diagram - Safeguards Actuation Signals, Rev. 10
A225106, Logic Diagram - Feedwater Isolation, Rev. 7
ISI-2735, In-Service Inspection Program - Safety Injection System, Rev. 1
220619, Instrument and Control Loop Diagram Safety Injection System Loop 938 and
939, Rev. 2
9321-F-2019-114, Flow Diagram - Boiler Feedwater, 12/16/87
Drawing Change Notice (DCN)
EC-7052, Model D-1008-160-2 Valve Assembly (FCV-427), 04/04/08
Surveillance and Modifications Acceptance Tests
2-PT-Q62, High Steam Flow and Turbine First Stage Pressure Bistables, Rev. 14
2-PC-R19, Turbine First Stage Pressure, Rev. 21
PC-R19, Turbine First Stage Pressure, Rev. 19
PT-Q62, High Steam Flow and Turbine First Stage Pressure Bistables, Rev. 13
Audits and Self-Assessments
QA-04-2008-IP-1, Engineering Design Control, Rev. 0
Procedures
0-CY-1640, Chemistry Shutdown Plan, Rev. 17
0-CY-1645, Chemistry Response to Plant Causalities, Rev. 5
0-CY-2350, Primary System Zinc Injection, Rev. 2
0-RES-401-GEN, Lisega Snubber Installation and Removal, Rev. 1
2-ARP-SEF, Turbine and GE Generator Start-up, Rev. 55
2-PI-V001A, Inaccessible Snubber Inspections, Rev. 15
2-PI-V001B, Accessible Snubber Inspections, Rev. 14
A-4
Attachment
2-PT-M108, RHR/SI System Venting, Rev. 4
2-PT-R002B, Recirculation Sump Level, Rev. 18.
2-PT-R016, Recirculation Pumps, Rev. 20
2-PT-Q033A, 21 Charging Pump, Rev. 13
2-PT-Q62, High Steam Flow and Turbine First State Pressure Bistables, Rev. 14
2-SOP-3.1, Charging Seal Water and Letdown Control, Rev. 61
2-SOP-3.5, Placing CVCS Demineralizers in or out of Service, Rev. 22
EN-DC-117, Post Modification Testing and Special Instructions, Rev. 1
EN-LI-100, Process Applicability Determination, Rev. 7
EN-LI-101, 10 CFR 50.59 Review Program, Rev. 4
PT-V11A-4, Recalibration of NIS and OT/OP Delta T Parameters Channel IV, Rev. 14
Work Orders
51229162
51326377
00144204
Work Requests
128436
128439
Vendor Manuals
IB 56-352-400, TURBO-GRAF - Turbine Supervisory Instruments Differential Expansion
IP 56-352-340A, TURBO-GRAF -Turbine Supervisory Instruments Casing Expansion /
Differential Expansion
Miscellaneous
05-0299-MD-00-RE, 50.59 Evaluation for IP3 Cycle 14 Core Reload Design, Rev. 1
ER 03-2-217, Setpoints, Rev. 0
Final Report, Control Room Envelope In-leakage Testing at Indian Point 2 Nuclear Generating
Station, dated 02/00
Indian Point Nuclear Generating Unit No. 2 - Issuance of Amendment RE: 3.36 percent Power
Uprate (TAC No. MC 1865), dated 10/27/04
Indian Point 2 Improved Technical Specifications
Indian Point 2 Improved Technical Specifications
IPEC Top 10 Technical Issue: IPEC Power Supply PMs, Rev. 2
IP2-FW/SGL DBD, Feedwater System / Steam Generator Control System Design Basis
Document, Rev. 1
Letter from Consolidated Edison Company to NRC, NEI Pilot Program for use of NURGEG-
1465, dated 04/13/00
Letter from NRR to Entergy, Indian Point Nuclear Generating Unit No. 2 - Relief
Request P-2 on Testing of Recirculation Pumps, dated 04/01/08
Lisega: Shock Absorbers Rigid Struts 93, April 1996 Edition
Letter, Lake Engineering Co. to Entergy, Seal Life Evaluation of Bergen-Paterson
Snubbers Entergy Nuclear Contract No. 4500543558 - Change 1 Lake Engineering
Company Project No. 948, dated 12/28/05
Letter, USNRC to Consolidated Edison Company: Issuance of Amendment Number 173
for Indian Point Nuclear Generating Unit 2, dated 07/26/94
NF-IP-07-25, Indian Point Unit 2 Cycle Core 19 Loading Plan, 03/24/08
PFP-212, General Floor Plan - Primary Auxiliary Building, Rev. 7
A-5
Attachment
QA-04-2008-IP-1, Quality Assurance Audit Report: Engineering Design Control
Updated Final Safety Analysis Report: Indian Point Unit 2, Rev. 20
WCAP-16157-P, Indian Point Nuclear Generating Unit No. 2 Stretch Power Uprate NSSS and
BOP Licensing Report, Rev. 0
Westinghouse Certification of Conformance for Breaker RHFA3100Y, dated 03/28/08
Section 4OA2: Identification and Resolution of Problems
Condition Reports (* denotes NRC identified during this inspection)
IP2-2008-01822*
IP2-2008-03778*
IP2-2008-03801*
Section 4OA3: Event Followup
IP 2 LER 2007-005-00: Technical Specification Prohibited Condition due to Exceeding
the Allowed Completion Time for an Inoperable Recirculation Pump caused by a
Potential Strong Pump-Weak Pump Interaction During a Small Break LOCA,
01/07/08
IP 3 LER 2007-003-00: Technical Specification Prohibited Condition due to Exceeding
the Allowed Completion Time for an Inoperable Recirculation Pump caused by a
Potential Strong Pump-Weak Pump Interaction During a Small Break LOCA,
01/07/08
Section 4A05: Other Activities
10 CFR 50.59 Screened-out Evaluations
EC 5682, Revision of Procedures EOP ES-1.3 and ES-1.4, 02/12/08
Condition Reports
Procedures
2-ES-1.3, Transfer to Cold Leg Recirculation, Rev. 1
2-ES-1.4, Transfer to Hot Leg Recirculation, Rev. 1
2-PT-R016, Recirculation Pumps, Rev. 20
3-ES-1.3, Transfer to Cold Leg Recirculation, Rev. 1
3-ES-1.3, Transfer to Hot Leg Recirculation, Rev. 2
3PT-R013, Recirculation Pumps In-Service Test, Rev. 19
EN-DC-313, Procurement Engineering Process, Rev. 2
EN-DC-141, Design Inputs, 07/24/06
EN-DC-141, Design Inputs, 01/28/08
EN-MP-101, Materials, Purchasing, and Contracts Process, Rev. 2
EN-MP-121, Materials, Purchasing and Contracts Training, Qualification and
Certification, Rev. 1
QA-04-2008-IP-1, Quality Assurance Audit Report, Rev. 0
Miscellaneous
280-RLCA02848-02A, Unit 3 Internal Recirculation Pump Curves, 01/16/07
IP-CALC-04-00809, Attachment 10, Unit 2 Internal Recirculation Pump Curves, 01/11/00
A-6
Attachment
IP-RPT-04-00890, Technical Basis for Using MC2 Technology for Periodic Verification
Testing at Indian Point 2 and Indian Point 3, Rev. 02
IP-RPT-08-00009, Engineering Study for Pump Minimum Flow Evaluation - Safety
Injection Recirculation Pumps, 01/29/08
IPEC Licensed Operator Requalification Training Program: E-1 and FR-P Series EOPs,
06/25/08
Letter from Consolidated Edison Company to NRC, Completion of Licensing Action for
Generic Letter 96-05 Regarding Capability of Motor-Operated Valves, Indian
Point Nuclear Generating Unit No. 2 (TAC No. M97057), dated 03/05/01
NRC Bulletin 88-04: Potential Safety-Related Pump Loss, 05/05/88
NRC Inspection Report 05000286/2007006, Indian Point Unit 3 Component Design Bases
Inspection (CDBI), 02/01/08
NRC Regulatory Issue summary 2000-17, Managing Regulatory Commitments Made by Power
Reactor Licensees to the NRC Staff
PS98-002, Procurement Specification for Replacement of Two Containment
Recirculation Pumps, 04/08/99
SAO 270, Indian Point Station Procurement Program, 06/19/99
STR-27, Indian Point Energy Center MC2 Program Questions, Rev. 0
A-7
Attachment
LIST OF ACRONYMS
American Society of Mechanical Engineers
CFR
Code of Federal Regulations
Design Basis Accident
Direct Current
Emergency Operating Procedure
Flow Control Valve
gpm
Gallons per Minute
HPR
High Pressure Recirculation
IMC
Inspection Manual Chapter
Indian Point Energy Center
IR
Inspection Report
LER
Licensee Event Report
Loss-of-Coolant Accident
LPR
Low Pressure Recirculation
Motor Control Center
Motor Operated Valve
MS
Mitigating System
Non-Cited Violation
NEI
Nuclear Energy Institute
NRC
Nuclear Regulatory Commission
Pressurized Water Reactor
Small Break Loss-of-Coolant Accident
Significance Determination Process
Standardized Plant Analysis Review
Senior Reactor Analyst
Structures, Systems and Components
TS
Technical Specification
Updated Final Safety Analysis Report
Unresolved Item