Request for an Extension to Permit No. 6706511 Ma Temporary Use of Reverse Osmosis
ML062080671
Person / Time
Site: Peach Bottom  Constellation icon.png
Issue date: 07/14/2006
From: Grimes J
Exelon Nuclear
To: Jason Draper
NRC Region 1, State of PA, Dept of Environmental Protection
References
PWS 7670905
Download: ML062080671 (1)


Text

Exelkn.

Peach Bottom Atomic Power Station www.exeloncoTp.com 1848 Lay Road Nuclear Delta, PA 17314 July 14, 2006 Ms. Jaala Draper Pennsylvania Department of Environmental Protection 909 Elmerton Avenue Harrisburg PA 17110-8200

Subject:

Peach Bottom Atomic Power Station, PWS 7670905

Reference:

-Permit No. 6704516 MA Temporary Use of Reverse Osmosis- --

Dear Ms. Draper,

Per our telephone conversation on June 16, 2006, Peach Bottom Atomic Power Station, PA 7670905, is requesting an extension to Permit No. 6706511 MA Temporary Use of Reverse Osmosis, which currently expires on July 23, 2006.

Peach Bottom requests the extension to the temporary permit to allow for the following maintenance work:

1) Redirecting flow to the individual polishing effluent turbidimeters so that these meters have constant flow, thus eliminating flow perturbations.
2)

Revise operating procedures to reduce flow to the individual polishing filters to be more in alignment with the design of the polishing filters.

3) Replace some of the carbon steel piping with PVC.
4) Place a new turbidimeter in the polishing filter room as the CFE.
5) Establish a valid sample point on the common discharge.
6) Install a manual bypass on the CFE to raw water.
7) Install an automatic bypass, activated when the CFE approaches the 1.0 NTU limit.
8) Revise operating procedures to require more frequent backwashes.

To allow additional time for this maintenance, Peach Bottom is requesting an extension to December 31, 2006, for Permit No. 6706511 MA in order to accommodate the maintenance described above.

'If you need further information, the points of contact are Daniel Jordan {717} 456-4551 or Wade Scott

-1717}-456-4804.

Sincerely, Jos h P. Grimes, Plant Manager Peach Bottom Atomic Power Station ccn 06-14054 USNRC Region 1 Administrator USNRC Document Control Desk Siglin, Tracy Senior Resident Inspector Angela Anderson, PADEP Jordan, Daniel