ML061950667

From kanterella
Jump to navigation Jump to search

Tom Gurdziel Letter NUREG-1433
ML061950667
Person / Time
Site: FitzPatrick Constellation icon.png
Issue date: 06/27/2006
From: Tom Gurdziel
- No Known Affiliation
To:
Office of Public Affairs
References
NUREG-1433
Download: ML061950667 (4)


Text

I John Boska - FitzPatrick Batteries Page 11 From:

"Tom Gurdziel" <tgurdziel@twcny.rr.com>

To:

<opa@nrc.gov>

Date:

6/27/2006 11:12:44 PM

Subject:

FitzPatrick Batteries Good morning, Please send this to Mr. John P. Boska.

Thank you, Tom Gurdziel CC:

"Ed Stronski" <ESTRONSKI@aol.com>, "David Lochbaum" <dlochbaum@ucsusa.org>

I c-\\temp\\GW)00001.TMP Page 1*

I c:tep...

001.TMP

=

Pag 1 Mail Envelope Properties (44A1F3A8.9DF: 11: 63967)

Subject:

Creation Date From:

Created By:

FitzPatrick Batteries 6/27/2006 11:11:57 PM "Tom Gurdziel" <tgurdziel @twcny.rr.com>

tgurdziel@twcny.rr.com Recipients nrc.gov TWGWPO02.HQGWDO01 OPA 0 ucsusa.org dlochbaum CC (David Lochbaum) aol.com ESTRONSKI CC (Ed Stronski)

Post Office TWGWPO02.HQGWDOO1 Route nrc.gov ucsusa.org aol.com Files MESSAGE Battery 3.doc Mime.822 Options Expiration Date:

Priority:

ReplyRequested:

Return Notification:

Concealed

Subject:

Security:

Size 104 21504 31269 Date & Time 6/27/2006 11:11:57 PM None Standard No None No Standard

9 Twin Orchard Drive Oswego, NY 13126 June 27, 2006 Mr. John P. Boska Project Manager, NRR US NRC Washington, DC 20555-0001

Dear Mr. John P. Boska:

I have been reading NUREG 1433 tonight. (Both Vol. 1 and Vol. 2 are Rev. 3.) (I believe it to be the appropriate Standard Technical Specification for the Entergy/FitzPatrick type of BWR.) It appears to me that it implicitly accepts the 1995 version of IEEE Standard 450since it specifies it as a reference. (See page 572 of 671 of Vol. 2, for one example.) Therefore, I ask if your Request for Additional Information (ML060810234), question "4 a." should not be withdrawn?

However, the main reason I am writing is to point out what I believe to be a major obstacle in logic. Assume one cell of a station battery has an open circuit voltage of less than 2.07 volts. (I know it says float voltage in STS LCO 3.8.6, but I think that is also incorrect.) There are three required actions, A.1, A.2, and A.3. The first simply requires that you verify the battery (not cell) terminal voltage is greater than, or equal to the minimum float voltage. (You should have been there anyway.) Next, you have to verify that the battery float current is less than a certain amount, perhaps 2 amps. (You were probably there, too.) So, how are you going to restore the affected cell voltage?

Can I suggest an equalization charge is needed?

For instance, from page 33 of "Electrotechnology Volume 3, Stationary Lead-Acid Batteries, Applications and Performance" by Edward J. Friedman (and others), Ann Arbor Science Publishers, 1980:

"Equalization is a method of obtaining uniform conditions among the various cells in a battery through controlled overcharging. During long-term float charging, some cells may exhibit loss of capacity. This may be detected as a specific gravity or cell voltage deviation.'

And, from page 35:

"The duration of the equalization may be several days, depending on the initial condition of the battery."

So, the logic problem that seems to appear is this, can you get the cell voltage restored in 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> if you keep the charging current low and you don't have to lift the charging voltage above minimum?

Very truly yours, Tom Gurdziel Copy:

M.J. Colomb, Entergy Nuclear Operations, Inc