Control Rod Scram Times 3.1.4 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.1.42 Verify, for a representative sample, each tested control 200 days rod scram time Is within the limits of Table 3.1.4-1 with cumulative reactor steam dome pressure 2 800 psig.

operation In MODE 1 SR 3.1.4.3 Verify each affected control rod scram time Is within Prior to declaring the limits of Table 3.1.4-1 with any reactor steam dome control rod pressure.

OPERABLE after work on control rod or CRD System that could affect scram time SR 3.1.4.4 Verify each affected control rod scram time is within Prior to exceeding the limits of Table 3.1.4-1 with reactor steam dome 40% RTP after fuel pressure 2 800 psig.

movement within the affected core cell AND Prior to exceeding 40% RTP after work on control rod or CRD System that could affect scram time I.

Brunswick Unit 2 3.1-13 Amendment No. 264 l