ML032940051
| ML032940051 | |
| Person / Time | |
|---|---|
| Site: | Point Beach |
| Issue date: | 10/16/2003 |
| From: | Office of Nuclear Reactor Regulation |
| To: | |
| References | |
| Download: ML032940051 (1) | |
Text
CREFS 3.7.9 3.7 PLANT SYSTEMS 3.7.9 Control Room Emergency Filtration System (CREFS)
LCO 3.7.9 CREFS shall be OPERABLE.
APPLICABILITY:
MODES 1, 2, 3, 4, During movement of irradiated fuel assemblies, During CORE ALTERATIONS.
ACTIONS CONDITION REQUIRED ACTION COMPLETIONTIME A.
A.1 Restore CREFS to 7 days OPERABLE status.
B. Required Action and B.1 Suspend CORE Immediately associated Completion ALTERATIONS.
Time not met.
AND B.2 Suspend movement of Immediately irradiated fuel assemblies.
AND B.3 Be in MODE 3.
6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> AND B.4 Be In MODE 5.
36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br /> I
I Point Beach 3.7.9-1 Unit I - Amendment No. 263, 210 Unit 2 - Amendment No. 208, 215