Page 1 rC:\\WINDOWS\\TEMP\\GW}O0001.TMP Mail Envelope Properties (3CCE8A61.533 :15 : 21310)
Subject:
Creation Date:
From:
Created By:
Draft RAI Re: GL 96-06 4/30/02 8:13AM Mohan Thadani MCT@nrc.gov Recipients nppd.com dvkunse (Intemet:dvkunse @ nppd.com) nppd.com pvflemi (INTernet:pvflemi @ nppd.com) nrc.gov owf2_po.OWFNDO JET 1 CC (James Tatum)
WLJ CC (Walton Jensen)
Post Office nppd.com owf2_po.OWFNDO Files MESSAGE Options Auto Delete:
Expiration Date:
Notify Recipients:
Priority:
Reply Requested:
Return Notification:
Concealed
Subject:
Security:
To Be Delivered:
Status Tracking:
Size 1895 Action Transferred Transferred Delivered Opened Opened Delivered 04/30/02 08:13AM Date & Time 04/30/02 08:13AM Date & Time 04/30/02 08:13AM 04/30/02 08:13AM 04/30/02 08:13AM 04/30/02 08:16AM 04/30/02 08:22AM Route Internet nppd.com nrc.gov No None Yes Standard No None No Standard Immediate Delivered & Opened
TMQhan Thadani - Draft RAI Re: GL 96-06 Page From:
Mohan Thadani To:
Internet:dvkunse @ nppd.com; INTernet:pvflemi @ nppd.com Date:
4/30/02 8:13AM
Subject:
>>> Walton Jensen 04/29/02 02:21 PM >>>
DRAFT RAI The NRC Staff is reviewing the status of Cooper relative to GL 96-06 and has identified the following draft RAI for your rsponse. We wish to set up a conference call at your convenience to discuss the following questions. Please let me know your options. Thanks.
- 1. Do the cooling water lines into the drywell for supply and discharge to the drywell coolers auto isolate following a loss of coolant accident?
- 2. Do the drywell coolers trip flowing a LOCA?
- 3. Will relief valves in the drywell cooling water lines inside the drywell open following a LOCA?
- 4. Are there provisions manually restarting the drywell cooling system following a LOCA that take into account possible void formation in the system?
James Tatum; Walton Jensen CCO: