LR-N12-0160, Special Report - Safety/Relief Valve Position Indicators

From kanterella
Jump to navigation Jump to search
Special Report - Safety/Relief Valve Position Indicators
ML12171A570
Person / Time
Site: Hope Creek PSEG icon.png
Issue date: 05/31/2012
From: Doris Lewis
Public Service Enterprise Group
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
LR-N12-0160
Download: ML12171A570 (2)


Text

PSEG Nuclear LLC P.O. Box 236, Hancocks Bridge, New Jersey 08038-0236 C PSEG Nuclear LLC MAY 3 1 2012 LR-N12-0160 TS 3.3.7.5 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555-0001 HOPE CREEK GENERATING STATION FACILITY OPERATING LICENSE NO. NPF-57 DOCKET NO. 50-354

Subject:

Special Report - Safety/Relief Valve Position Indicators This special report is being submitted, pursuant to the requirements of Hope Creek Technical Specification (TS) Table 3.3.7.5-1, "Accident Monitoring Instrumentation" Action 80, due to having less than the required number of position indication channels for the "J" Safety/Relief Valve (SRV) Position Indicator for greater than 30 days.

On May 11, 2012, the "J" SRV tailpipe temperature indication failed upscale.

Troubleshooting activities determined that the temperature element failed open. The TS requires two SRV position indication channels per valve to be operable, consisting of one tailpipe temperature element and one acoustic monitoring probe., With one of the two required channels inoperable for more than 30 days, a special report is required to be submitted.

The failure has been determined to be inside the drywell and is not accessible during power operations. Repair activities are being planned for the first outage of sufficient duration.

There are no regulatory commitments contained in this letter.

Should you have any questions concerning this letter, please contact Paul Bonnett at (856) 339-1923.

Sincerely, David P. Lewis Plant Manager - Hope Creek

Document Control Desk LR-N 12-0160 Page 2 cc:

Mr. W. Dean, Administrator - Region I U. S. Nuclear Regulatory Commission 2100 Renaissance Blvd, Suite 100 King of Prussia, PA 19406-2713 U. S. Nuclear Regulatory Commission Mr. J. Hughey, Project Manager - Hope Creek Mail Stop 08B3 Washington, DC 20555-0001 USNRC Senior Resident Inspector - Hope Creek (X24)

Mr. P. Mulligan, Manager IV Bureau of Nuclear Engineering New Jersey Department of Environmental Protection PO Box 420 Trenton, New Jersey 08625 Hope Creek Commitment Coordinator (H02)

Corporate Commitment Coordinator (N21)