Entergy GNRO-2012/00022 March 30, 2012 U.S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, DC 20555-0001

SUBJECT:

Emergency Response Data System (EROS) Changes Grand Gulf Nuclear Station, Unit 1 Docket No. 50-416 License No. NPF-29 opeiratll::ms, Inc.

Christina L. Perino

Dear Sir or Madam:

In accordance with the requirements of 10 CFR 50, Appendix E, Section VI.3.a, Entergy is submitting this letter to provide notification of changes to the Grand Gulf Nuclear Station Emergency Response Data System (EROS) link software implemented on March 1,2012. Any hardware and software changes that affect the transmitted data points identified in the EROS Data Point Library (DPL) must be submitted to the NRC within 30 days after the changes are completed.

These changes will involve a deletion of four EROS data points and a modification of four data points, requiring a Data Point Library (DPL) change.

This letter contains no commitments. If you have questions, please contact Mr. Chris Lewis, Manager, Emergency Preparedness, at (601) 437-2166.

Sincerely, : EROS Data Point Change Package cc: (See Next Page)

cc:

Gulf Nuclear Station Port Gibson, MS 50 U.

Nuclear Regulatory Commission Region Administrator, Region IV ATTN: Mr. Elmo Collins, Jr.

1600 East Lamar Boulevard Arlington, TX 76011-4125 U.S. Nuclear Regulatory Commission AnN: Mr. Alan Wang, NRR/DORL (w/2)

Mail Stop OWFN/8 B1 Washington, D,C. 20555-0001 to GNRO-2012/00022 EROS Data Point Change Package

OFFICIAL DATA POINT LIBRARY CHANGE Please DELETE listed below.

DATE:

March 1,2012 REACTOR UNIT:

1 DATA FEEDER:

C51NA055 NRC ERDS PARAMETER:

NI_POWER_RNG 4x POINT ID:

C51NA055 PLANT SPEC POINT DESC:

APRM E FLUX LEVEL GENERIC/COHD DESC:

AVERAGE POWER RANGE MONITOR ANALOG/DIGITAL:

ANALOG ENGR UNITS/DIG STATES:

ENGR UNITS CONVERSION:

LINEAR (0-160MV)

MINIMUM INSTR RANGE:

0 MAXIMUM INSTR RANGE:

125 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A PROC OR SENS:

S NUMBER OF SENSORS:

1 HOW PROCESSED:

N/A SENSOR LOCATIONs:

REACTOR CORE ALARM/TRIP SET POINTS:

N/A NI DETECTOR POWER SUPPLY CUT-vOFF POWER LEVEL:

NEVER CUT OFF NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

ALWAYS TURND.ON INSTRUMENT FAILURE MODE:

LOW WITH ALARM TEMPERATURE COMPENSATION FOR DP TRANSMITIERS:

N LEVEL REFERENCE DESC:

N/A UNIQUE SYSTEM DESC:

REQUIRES INPUT FROM AT LEAST 14 (NORMAL IS 22) LPRMS FOR PROPER OPERATION APRM READING AND OUTPUT TO RPS CAN BE AFFECTED BY FAILED LPRMS (IE.

UPSCALE/DOWNSCALE LPRMS).

IJIQ'::;l<;:!Q DELETE the listed below:

DATE:

March 1, 2012 REACTOR UNIT:

1 DATA FEEDER:

C51NA056 NRC ERDS PARAMETER:

NI_POWER_RNG 5x POINT ID:

C51NA056 PLANT SPEC POINT DESC:

APRM F FLUX LEVEL GENERIC/COHD DESC:

AVERAGE POWER RANGE MONITOR ANALOG/DIGITAL:

ANALOG ENGR UNITS/DIG STATES:

ENGR UNITS CONVERSION:

LINEAR (0-160MV)

MINIMUM INSTR RANGE:

0 MAXIMUM INSTR RANGE:

125 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A PROC OR SENS:

S NUMBER OF SENSORS:

1 HOW PROCESSED:

N/A SENSOR LOCATIONs:

REACTOR CORE ALARM/TRIP SET POINTS:

N/A NI DETECTOR POWER SUPPLY CUT"OFF POWER LEVEL:

NEVER CUT OFF NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

ALWAYS TURND.ON INSTRUMENT FAILURE MODE:

LOW WITH ALARM TEMPERATURE COMPENSATION FOR DP TRANSMITIERS:

N LEVEL REFERENCE DESC:

N/A UNIQUE SYSTEM DESC:

REQUIRES INPUT FROM AT LEAST 14 (NORMAL IS 22) LPRMS FOR PROPER OPERATION APRM READING AND OUTPUT TO RPS CAN BE AFFECTED BY FAILED LPRMS (IE.

UPSCALE/DOWNSCALE LPRMS).

Please DELETE the DATE:

REACTOR UNIT:

DATA FEEDER:

NRC EROS PARAMETER:

POINT 10:

PLANT SPEC POINT DESC:

GENERIC/COHO DESC:

ANALOG/DIGITAL:

ENGR UNITS/DIG STATES:

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS:

NUMBER OF SENSORS:

HOW PROCESSED:

SENSOR LOCATIONs:

ALARM/TRIP SET POINTS:

March 1, 1

C51NA057 NI_POWER_RNG 6x C51NA057 APRM G FLUX LEVEL AVERAGE POWER RANGE MONITOR ANALOG LINEAR (O-160MV) o 125 N/A N/A S

1 N/A REACTOR CORE N/A NI DETECTOR POWER SUPPLY CUT'OFF POWER LEVEL:

NEVER CUT OFF NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

ALWAYS TURND.ON INSTRUMENT FAILURE MODE:

LOW WITH ALARM TEMPERATURE COMPENSATION FOR DP TRANSMITIERS:

N LEVEL REFERENCE DESC:

N/A UNIQUE SYSTEM DESC:

REQUIRES INPUT FROM AT LEAST 14 (NORMAL IS 22) LPRMS FOR PROPER OPERATION APRM READING AND OUTPUT TO RPS CAN BE AFFECTED BY FAILED LPRMS (IE.

UPSCALE/DOWNSCALE LPRMS).

IJIQ':::U::!Q DELETE the listed below:

DATE:

March 1, 2012 REACTOR UNIT:

1 DATA FEEDER:

C51NA058 NRC ERDS PARAMETER:

NLPOWER_RNG 7x POINTID:

C51NAOS8 PLANT SPEC POINT DESC:

APRM H FLUX LEVEL GENERIC/COHD DESC:

AVERAGE POWER RANGE MONITOR ANALOG/DIGITAL:

ANALOG ENGR UNITS/DIG STATES:

ENGR UNITS CONVERSION:

LINEAR (0-160MV)

MINIMUM INSTR RANGE:

0 MAXIMUM INSTR RANGE:

125 ZERO POINT

REFERENCE:

N/A REFERENCE POINT NOTES:

N/A PROC OR SENS:

S NUMBER OF SENSORS:

1 HOW PROCESSED:

N/A SENSOR LOCATIONs:

REACTOR CORE ALARM/TRIP SET POINTS:

N/A NI DETECTOR POWER SUPPLY CUT'vOFF POWER LEVEL:

NEVER CUT OFF NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

ALWAYS TURND.ON INSTRUMENT FAILURE MODE:

LOW WITH ALARM TEMPERATURE COMPENSATION FOR DP TRANSMITIERS:

N LEVEL REFERENCE DESC:

N/A UNIQUE SYSTEM DESC:

REQUIRES INPUT FROM AT LEAST 14 (NORMAL IS 22) LPRMS FOR PROPER OPERATION APRM READING AND OUTPUT TO RPS CAN BE AFFECTED BY FAILED LPRMS (IE.

UPSCALE/DOWNSCALE LPRMS).

Please MODIFY the data DATE:

REACTOR UNIT:

DATA FEEDER:

NRC ERDS PARAMETER:

POINT ID:

PLANT SPEC POINT DESC:

GENERIC/COHD DESC:

ANALOG/DIGITAL:

ENGR UNITS/DIG STATES:

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS:

NUMBER OF SENSORS:

HOW PROCESSED:

SENSOR LOCATIONs:

ALARM/TRIP SET POINTS:

listed below:

April 3, 2012 1

C51NA051 NI_POWER_RNG C51NA051 APRM A FLUX LEVEL AVERAGE POWER RANGE MONITOR A ANALOG LINEAR (0-160MV) o 125 N/A N/A S

1 N/A REACTOR CORE N/A APRM 1 FLUX LEVEL AVERAGE POWER RANGE MONITOR 1 AFTER AN INITIAL OPRM MONITORING PERIOD ENTERGY WILL ENABLE THE OPRM WHICH EMPLOYS THREE DIFFERENT SOFTWARE ALGORITHMS RUNNING ON A NUMARC PRNM MICROPROCESSOR COMPUTER PLATFORM TO AUTOMATICALLY DETECT AND SUPPRESS REACTOR THERMAL-HYDRALIC INSTABILITIES.

NI DETECTOR POWER SUPPLY CUT'OFF POWER LEVEL:

NEVER CUT OFF NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

ALWAYS TURND.ON INSTRUMENT FAILURE MODE:

LOW WITH ALARM TEMPERATURE COMPENSATION FOR DP TRANSMITIERS:

N LEVEL REFERENCE DESC:

N/A UNIQUE SYSTEM DESC:

REQUIRES INPUT FROM AT LEAST 14 (NORMAL IS

22) LPRMS FOR PROPER OPERATION APRM READING AND OUTPUT TO RPS CAN BE AFFECTED BY FAILED LPRMS (IE. UPSCALE/DOWNSCALE LPRMS).

Please MODIFY the data point listed below:

DATE:

REACTOR UNIT:

DATA FEEDER:

NRC EROS PARAMETER:

POINT 10:

PLANT SPEC POINT DESC:

GENERIC/COHO DESC:

ANALOG/DIGITAL:

ENGR UNITS/DIG STATES:

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS:

NUMBER OF SENSORS:

HOW PROCESSED:

SENSOR LOCATIONs:

ALARM/TRIP SET POINTS:

April 3, 2012 1

C51NA052 NI_POWER_RNG 1x C51NA052 APRM B FLUX LEVEL AVERAGE POWER RANGE MONITOR B ANALOG LINEAR (0-160MV) o 125 N/A N/A S

1 N/A REACTOR CORE N/A APRM 2 FLUX LEVEL AVERAGE POWER RANGE MONITOR 2 AFTER AN INITIAL OPRM MONITORING PERIOD ENTERGY WILL ENABLE THE OPRM WHICH EMPLOYS THREE DIFFERENT SOFTWARE ALGORITHMS RUNNING ON A NUMARC PRNM MICROPROCESSOR COMPUTER PLATFORM TO AUTOMATICALLY DETECT AND SUPPRESS REACTOR THERMAL-HYDRALIC INSTABILITIES.

NI DETECTOR POWER SUPPLY CUT'OFF POWER LEVEL:

NEVER CUT OFF NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

ALWAYS TURND.ON INSTRUMENT FAILURE MODE:

LOW WITH ALARM TEMPERATURE COMPENSATION FOR DP TRANSMITTERS:

0 LEVEL REFERENCE DESC:

A UNIQUE SYSTEM DESC:

REQUIRES INPUT FROM AT LEAST 14 (NORMAL IS

22) LPRMS FOR PROPER OPERATION APRM READING AND OUTPUT TO RPS CAN BE AFFECTED BY FAILED LPRMS (IE. UPSCALE/DOWNSCALE LPRMS).

..... I~:::::l~~ MODIFY the data DATE:

REACTOR UNIT:

DATA FEEDER:

NRC EROS PARAMETER:

POINT 10:

PLANT SPEC POINT DESC:

GENERIC/COHO DESC:

ANALOG/DIGITAL:

ENGR UNITS/DIG STATES:

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS:

NUMBER OF SENSORS:

HOW PROCESSED:

SENSOR LOCATIONs:

ALARM/TRIP SET POINTS:

listed below:

April 3, 2012 1

C51NA053 NI_POWER_RNG 2x C51NA053 APRM C FLUX LEVEL AVERAGE POWER RANGE MONITOR C ANALOG LINEAR (0-160MV) o 125 N/A N/A S

1 N/A REACTOR CORE N/A APRM 3 FLUX LEVEL AVERAGE POWER RANGE MONITOR 3 AFTER AN INITIAL OPRM MONITORING PERIOD ENTERGY WILL ENABLE THE OPRM WHICH EMPLOYS THREE DIFFERENT SOFTWARE ALGORITHMS RUNNING ON A NUMARC PRNM MICROPROCESSOR COMPUTER PLATFORM TO AUTOMATICALLY DETECT AND SUPPRESS REACTOR THERMAL-HYDRALIC INSTABILITIES.

NI DETECTOR POWER SUPPLY CUrvOFF POWER LEVEL:

NEVER CUT OFF NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

ALWAYS TURND.ON INSTRUMENT FAILURE MODE:

LOW WITH ALARM TEMPERATURE COMPENSATION FOR DP TRANSMITIERS:

N LEVEL REFERENCE DESC:

N/A UNIQUE SYSTEM DESC:

REQUIRES INPUT FROM AT LEAST 14 (NORMAL IS

22) LPRMS FOR PROPER OPERATION APRM READING AND OUTPUT TO RPS CAN BE AFFECTED BY FAILED LPRMS (IE. UPSCALE/DOWNSCALE LPRMS).

1-I1~,::U::t~ MODIFY listed below:

DATE:

REACTOR UNIT:

DATA FEEDER:

NRC ERDS PARAMETER:

POINT ID:

PLANT SPEC POINT DESC:

GENERIC/COHD DESC:

ANALOG/DIGITAL:

ENGR UNITS/DIG STATES:

ENGR UNITS CONVERSION:

MINIMUM INSTR RANGE:

MAXIMUM INSTR RANGE:

ZERO POINT

REFERENCE:

REFERENCE POINT NOTES:

PROC OR SENS:

NUMBER OF SENSORS:

HOW PROCESSED:

SENSOR LOCATIONs:

ALARM/TRIP SET POINTS:

April 3, 2012 1

C51NA054 NI_POWER_RNG 3x C51NA054 APRM D FLUX LEVEL AVERAGE POWER RANGE MONITOR D ANALOG LINEAR (0-160MV) o 125 N/A N/A S

1 N/A REACTOR CORE N/A APRM 4 FLUX LEVEL AVERAGE POWER RANGE MONITOR 4 AFTER AN INITIAL OPRM MONITORING PERIOD ENTERGY WILL ENABLE THE OPRM WHICH EMPLOYS THREE DIFFERENT SOFTWARE ALGORITHMS RUNNING ON A NUMARC PRNM MICROPROCESSOR COMPUTER PLATFORM TO AUTOMATICALLY DETECT AND SUPPRESS REACTOR THERMAL-HYDRALIC INSTABILITIES.

NI DETECTOR POWER SUPPLY CUTrvOFF POWER LEVEL:

NEVER CUT OFF NI DETECTOR POWER SUPPLY TURN-ON POWER LEVEL:

ALWAYS TURND.ON INSTRUMENT FAILURE MODE:

LOW WITH ALARM TEMPERATURE COMPENSATION FOR DP TRANSMITIERS:

N LEVEL REFERENCE DESC:

N/A UNIQUE SYSTEM DESC:

REQUIRES INPUT FROM AT LEAST 14 (NORMAL IS

22) LPRMS FOR PROPER OPERATION APRM READING AND OUTPUT TO RPS CAN BE AFFECTED BY FAILED LPRMS (IE. UPSCALE/DOWNSCALE LPRMS).