ENS 54826
ENS Event | |
|---|---|
17:58 Aug 10, 2020 | |
| Title | Notice of Unusual Event Due to Loss of Offsite Power Due to High Winds |
| Event Description | At 1258 CDT on August 10, 2020, Duane Arnold Energy Center declared an Unusual Event due to a loss of offsite power due to high winds. The event at the single unit plant resulted in an automatic scram from 82 percent power (Mode-1) to zero percent power (Mode-3). They are headed to Mode-4. There is damage on site, but the Reactor Building is intact. All rods inserted and cooling is being addressed via Reactor Core Isolation Cooling (RCIC) for level control and Safety Relief Valves are removing decay heat to the torus. Both Standby Diesel Generator are running.
The licensee notified the NRC Resident Inspector, the Iowa Department of Emergency Management, and the Linn County and Benton County Emergency Management agencies. Notified DHS SWO, FEMA Operations Center, CISA Central, FEMA NWC (email), DHS Nuclear SSA (email), and FEMA NRCC SASC (email).
This report is being made under CFR 50.72 (b)(2)(iv)(B) for an automatic reactor scram due to loss of offsite power due to high winds. In addition, this report is being made under CFR 50.72 (b)(3)(iv)(A) and (B) due to PCIS [(Primary Containment Isolation System)] Groups 1, 2, 3, 4 and 5 [activating] due to loss of offsite power. All isolations went to completion. RCIC injecting for level control. All rods fully inserted during the scram. The plant electrical line up is both SBDGs (Standby Diesel Generators) are running. Decay heat is being removed via SRVs (Safety Relief Valves) to the torus. Progress towards shutdown cooling. NRC Senior Resident [Inspector] notified at 1448. Notified R3DO (Pelke). |
| Where | |
|---|---|
| Duane Arnold Iowa (NRC Region 3) | |
| Reporting | |
| Emergency class: | Unusual Event |
| 10 CFR 50.72(a) (1) (i), Emergency Class Declaration | |
| LER: | 05000331/LER-2020-001-01 Notice of Unusual Event and Unit Trip Due to Loss of Offsite Power Due to High Winds |
| Time - Person (Reporting Time:+-3.33 h-0.139 days <br />-0.0198 weeks <br />-0.00456 months <br />) | |
| Opened: | Scott Welch 14:38 Aug 10, 2020 |
| NRC Officer: | Ossy Font |
| Last Updated: | Aug 10, 2020 |
| 54826 - NRC Website
Loading map... {"minzoom":false,"maxzoom":false,"mappingservice":"leaflet","width":"350px","height":"250px","centre":false,"title":"","label":"","icon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"zoom":6,"defzoom":14,"layers":["OpenStreetMap"],"image layers":[],"overlays":[],"resizable":false,"fullscreen":false,"scrollwheelzoom":true,"cluster":false,"clustermaxzoom":20,"clusterzoomonclick":true,"clustermaxradius":80,"clusterspiderfy":true,"geojson":"","clicktarget":"","imageLayers":[],"locations":[{"text":"\u003Cb\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003E\u003Ca class=\"mw-selflink selflink\"\u003EENS 54826\u003C/a\u003E - \u003Ca href=\"/Duane_Arnold\" title=\"Duane Arnold\"\u003EDuane Arnold\u003C/a\u003E\n\u003C/p\u003E\u003C/div\u003E\u003C/b\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003ENotice of Unusual Event Due to Loss of Offsite Power Due to High Winds\n\u003C/p\u003E\u003C/div\u003E","title":"ENS 54826 - Duane Arnold\n","link":"","lat":42.10089166666667,"lon":-91.77759444444445,"icon":"/w/images/9/9b/NextEra_Energy_icon.png"}],"imageoverlays":null} | |
WEEKMONTHYEARENS 548262020-08-10T17:58:00010 August 2020 17:58:00
[Table view]10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notice of Unusual Event Due to Loss of Offsite Power Due to High Winds ENS 468132011-05-03T18:44:0003 May 2011 18:44:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(1), 50.54(x) TS Deviation Alert Declared Due to Fire Affecting Access to Safety Related Equipment ENS 442912008-06-12T16:30:00012 June 2008 16:30:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Unusual Event Declared Due to a Major Loss of Response and Communications Capability ENS 422992006-02-02T00:55:0002 February 2006 00:55:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Site External Communications 2020-08-10T17:58:00 | |