ENS 53647
ENS Event | |
|---|---|
05:00 Oct 5, 2018 | |
| Title | En Revision Imported Date 10/19/2018 |
| Event Description | EN Revision Text: UNPLANNED LOSS OF THE ASSESSMENT CAPABILITY DUE TO TECHNICAL SUPPORT DIESEL
At 05:52 CDT on 10/5/2018, the [Wolf Creek Nuclear Operating Corporation] (WCNOC) Technical Support Center (TSC) Diesel fuel oil transfer pump would not run. There was ongoing modification to the facility Halon system at the time. The modification process had included a jumper to the fuel oil transfer pump to allow it to continue to be available. This issue was discovered during testing as the modification was progressing. The pump was verified to function on 10/4/2018 by normal operations rounds. If an emergency is declared requiring the TSC activation during the time the TSC diesel is non-functional, the TSC will be staffed and activated using existing emergency planning procedure. If offsite power is lost, the TSC will relocate to the Alternate TSC using existing emergency planning procedures. There was no impact to the health and safety of the public or plant personnel. The NRC Resident Inspector has been notified.
Event Notification53647, made on October 8, 2018, is being retracted because during the time that the TSC Diesel fuel oil transfer pump was not available, normal power was continuously available. The Alternative TSC was also available. Consequently, the condition did not meet the criteria for a 8-hour notification per 10 CFR 50.72(b)(3)(xiii) for any event that results in a major loss of emergency assessment capability, offsite response capability, or offsite communications capability (e.g., significant portion of control room indication, Emergency Notification System, or offsite notification system). The NRC Resident Inspector has been notified of the Event Notification retraction. Notified R4DO (Pick). |
| Where | |
|---|---|
| Wolf Creek Kansas (NRC Region 4) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness | |
| Time - Person (Reporting Time:+4.98 h0.208 days <br />0.0296 weeks <br />0.00682 months <br />) | |
| Opened: | Marcy Blow 09:59 Oct 5, 2018 |
| NRC Officer: | Andrew Waugh |
| Last Updated: | Oct 18, 2018 |
| 53647 - NRC Website
Loading map... {"minzoom":false,"maxzoom":false,"mappingservice":"leaflet","width":"350px","height":"250px","centre":false,"title":"","label":"","icon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"zoom":6,"defzoom":14,"layers":["OpenStreetMap"],"image layers":[],"overlays":[],"resizable":false,"fullscreen":false,"scrollwheelzoom":true,"cluster":false,"clustermaxzoom":20,"clusterzoomonclick":true,"clustermaxradius":80,"clusterspiderfy":true,"geojson":"","clicktarget":"","imageLayers":[],"locations":[{"text":"\u003Cb\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003E\u003Ca class=\"mw-selflink selflink\"\u003EENS 53647\u003C/a\u003E - \u003Ca href=\"/Wolf_Creek\" title=\"Wolf Creek\"\u003EWolf Creek\u003C/a\u003E\n\u003C/p\u003E\u003C/div\u003E\u003C/b\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003EEn Revision Imported Date 10/19/2018\n\u003C/p\u003E\u003C/div\u003E","title":"ENS 53647 - Wolf Creek\n","link":"","lat":38.239158333333336,"lon":-95.68945833333333,"icon":"/w/images/4/42/Wolf_Creek_Nuclear_Operating_Corporation_icon.png"}],"imageoverlays":null} | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
WEEKMONTHYEARENS 549682020-10-27T21:08:00027 October 2020 21:08:00
[Table view]10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Emergency Plan Dose Assessment Capability ENS 536472018-10-05T05:00:0005 October 2018 05:00:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness En Revision Imported Date 10/19/2018 ENS 521842016-08-16T16:00:00016 August 2016 16:00:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Failure of All Emergency Sirens ENS 512972015-08-06T22:39:0006 August 2015 22:39:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Technical Support Center Non-Functional ENS 504072014-08-27T13:05:00027 August 2014 13:05:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Communications Due to Power Supply Failure ENS 496922014-01-06T09:30:0006 January 2014 09:30:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Three Emergency Plan Sirens ENS 486492013-01-03T12:04:0003 January 2013 12:04:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Saftey Parameter Display System (Spds) ENS 467202011-04-04T05:30:0004 April 2011 05:30:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Emergency Sirens Out of Service Due to Severe Weather ENS 465752011-01-28T16:09:00028 January 2011 16:09:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Planned Primary Communications Maintenance ENS 439742008-02-09T19:20:0009 February 2008 19:20:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Safety Parameter Display System (Spds) Removed from Service for Scheduled Maintenance ENS 434402007-06-22T01:00:00022 June 2007 01:00:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness "Spds (Safety Parameter Display System) Inoperable Due to Plant Computer Inoperability ENS 433962007-05-31T07:10:00031 May 2007 07:10:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Emergency Plan Sirens Due to 69Kv Distribution System Fault ENS 433942007-05-29T13:08:00029 May 2007 13:08:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Safety Parameter Display System (Spds) Removed from Service for Computer Upgrade ENS 431192007-01-25T11:42:00025 January 2007 11:42:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Safety Parameters Display System (Spds) ENS 426352006-06-12T20:56:00012 June 2006 20:56:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Spds During Planned Computer Maintenance ENS 418312005-07-10T03:54:00010 July 2005 03:54:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Emergency Assessment Capability Due to Inoperable Ep Sirens ENS 417842005-06-17T21:54:00017 June 2005 21:54:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Safety Parameter Display System ENS 415092005-03-21T21:53:00021 March 2005 21:53:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Safety Parameter Display System (Spds) Function for Greater than 8 Hours. ENS 403452003-11-20T23:00:00020 November 2003 23:00:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Spds for Greater than 8 Hours ENS 402592003-10-18T22:20:00018 October 2003 22:20:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Emergency Assessment Capability 2020-10-27T21:08:00 | |