ENS 52769
ENS Event | |
|---|---|
03:30 May 24, 2017 | |
| Title | All Four Edgs Autostarted During Transfer of Shutdown Board to Normal Power Source for Unit 2 Testing |
| Event Description | On May 23, 2017 at 2330, while transferring 2A-A 6.9 kV Shutdown Board from its alternate power source to its normal power source in support of outage testing, a failure occurred which resulted in the loss of the Shutdown Board, emergency start of all 4 Emergency Diesel Generators (EDGs), and required the manual emergency stop of 2A-A EDG.
During transfer of the 2A-A 6.9kV Shutdown Board, the hand switch for the normal feeder breaker on the shutdown board was being maintained in the 'CLOSE' position while the alternate feeder breaker hand switch was placed in 'TRIP.' As expected, the alternate feeder breaker opened and the normal feeder breaker closed. However, the upstream supply breaker to the normal feeder breaker immediately tripped due to an overcurrent relay actuation on a single phase. As a result, the 2A-A 6.9 kV Shutdown Board deenergized, initiating a blackout signal which started all 4 of the station's EDGs. During board stripping (opening of all feeder and load breakers, to prepare the board for automatic reenergization from the EDG), the normal feeder breaker to the Shutdown Board failed to trip. This failure to trip prevented the emergency feeder breaker in the output of 2A-A EDG from closing, in accordance with interlock logic. As a result, 2A-A 6.9 kV Shutdown Board remained deenergized which prevented the cooling water supply valve for the EDG from opening due to loss of motive power. This lack of cooling caused operators to emergency stop the 2A-A EDG. Power was restored to the Shutdown Board on May 24, 2017 at 0037. Unit 1 is currently stable in Mode 1, at 100% power and Unit 2 is stable in Mode 5 with RCS at 164 F and 340 psig. The cause of the breaker trip on overcurrent and the failure of the normal feeder to trip on load shedding are under investigation. This event had no impact on the health and/or safety of the public. The NRC Resident Inspector has been notified. |
| Where | |
|---|---|
| Sequoyah Tennessee (NRC Region 2) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(iv)(A), System Actuation | |
| LER: | 05000327/LER-1917-002 Regarding Automatic Actuation of Emergency Diesel Generators Due to Loss of Power to 6.9kV Shutdown Board |
| Time - Person (Reporting Time:+0.67 h0.0279 days <br />0.00399 weeks <br />9.17766e-4 months <br />) | |
| Opened: | Robert Camenisch 04:10 May 24, 2017 |
| NRC Officer: | Steve Sandin |
| Last Updated: | May 24, 2017 |
| 52769 - NRC Website
Loading map... {"minzoom":false,"maxzoom":false,"mappingservice":"leaflet","width":"350px","height":"250px","centre":false,"title":"","label":"","icon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"zoom":6,"defzoom":14,"layers":["OpenStreetMap"],"image layers":[],"overlays":[],"resizable":false,"fullscreen":false,"scrollwheelzoom":true,"cluster":false,"clustermaxzoom":20,"clusterzoomonclick":true,"clustermaxradius":80,"clusterspiderfy":true,"geojson":"","clicktarget":"","imageLayers":[],"locations":[{"text":"\u003Cb\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003E\u003Ca class=\"mw-selflink selflink\"\u003EENS 52769\u003C/a\u003E - \u003Ca href=\"/Sequoyah\" title=\"Sequoyah\"\u003ESequoyah\u003C/a\u003E\n\u003C/p\u003E\u003C/div\u003E\u003C/b\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003EAll Four Edgs Autostarted During Transfer of Shutdown Board to Normal Power Source for Unit 2 Testing\n\u003C/p\u003E\u003C/div\u003E","title":"ENS 52769 - Sequoyah\n","link":"","lat":35.22651944444444,"lon":-85.09192777777778,"icon":"/w/images/c/ce/Tennessee_Valley_Authority_icon.png"}],"imageoverlays":null} | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
Unit 2 | |
|---|---|
| Reactor critical | Not Critical |
| Scram | No |
| Before | Cold Shutdown (0 %) |
| After | Cold Shutdown (0 %) |
WEEKMONTHYEARENS 577792025-06-24T07:51:00024 June 2025 07:51:00
[Table view]10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unit 2 Manual Reactor Trip ENS 577782025-06-24T04:14:00024 June 2025 04:14:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unit 1 Manual Reactor Trip ENS 574952025-01-16T14:50:00016 January 2025 14:50:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Trip While Shutdown ENS 573512024-09-29T09:56:00029 September 2024 09:56:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to Turbine Trip ENS 572852024-08-23T16:19:00023 August 2024 16:19:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip ENS 572532024-07-30T20:41:00030 July 2024 20:41:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to Turbine Trip ENS 544462019-12-16T08:58:00016 December 2019 08:58:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Emergency Diesel Generator Autostart Due to Loss of Power to 1B Shutdown Board ENS 542422019-08-27T05:09:00027 August 2019 05:09:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip ENS 539992019-04-14T07:20:00014 April 2019 07:20:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation En Revision Imported Date 8/7/2019 ENS 527692017-05-24T03:30:00024 May 2017 03:30:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation All Four Edgs Autostarted During Transfer of Shutdown Board to Normal Power Source for Unit 2 Testing ENS 524692016-12-30T18:05:00030 December 2016 18:05:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Due to Control Rod Not Withdrawing as Expected ENS 517202016-02-09T19:15:0009 February 2016 19:15:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation, 10 CFR 50.72(b)(2)(iv)(A), System Actuation - ECCS Discharge Eccs Discharge to Rcs Via Charging System ENS 515592015-11-23T13:44:00023 November 2015 13:44:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip After Partial Msiv Closure ENS 513922015-09-14T08:26:00014 September 2015 08:26:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Due to Loss of Power to Vital Instrument Board ENS 512652015-07-27T14:43:00027 July 2015 14:43:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor/Turbine Trip ENS 512592015-07-24T17:51:00024 July 2015 17:51:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to Turbine Trip on Main Generator Lockout ENS 508782015-03-11T10:21:00011 March 2015 10:21:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to a Nuclear Instrumentation Signal ENS 508562015-03-02T11:45:0002 March 2015 11:45:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip ENS 487782013-02-24T17:05:00024 February 2013 17:05:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Due to Loss of Condenser Vacuum Indication ENS 481982012-08-16T23:26:00016 August 2012 23:26:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Reactor Trip from a Reactor Coolant Pump Trip ENS 471692011-08-19T02:50:00019 August 2011 02:50:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to Reactor Coolant Pump Bus Undervoltage ENS 470812011-07-21T01:29:00021 July 2011 01:29:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to Negative Rate Trip Following Rapid Turbine Load Reduction ENS 469912011-06-26T20:14:00026 June 2011 20:14:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to Turbine Trip ENS 464922010-12-20T05:50:00020 December 2010 05:50:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Due to a Fire in the Main Generator Bus Duct ENS 464242010-11-17T03:10:00017 November 2010 03:10:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Based on Decreasing Steam Generator Level ENS 455202009-11-26T07:42:00026 November 2009 07:42:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Trip Due to Loss of Vacuum on Turbine Driven Feedwater Pump ENS 450972009-05-27T23:04:00027 May 2009 23:04:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Reactor Trip from Power Range High Neutron Flux Rate ENS 450452009-05-07T02:56:0007 May 2009 02:56:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Due to Feed Regulating Valve Failure ENS 450292009-04-29T01:59:00029 April 2009 01:59:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Initiated as a Result of a Loss of Condensate Flow ENS 449342009-03-26T08:52:00026 March 2009 08:52:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip and Aux Feed Water Start Due to Loss of an Off Site Power Source ENS 449352009-03-26T08:52:00026 March 2009 08:52:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip and Aux Feed Water Start Due to Loss of an Off Site Power Source ENS 446492008-11-09T23:21:0009 November 2008 23:21:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Reactor Trip Breakers Opened Manually Due to Indicated Dropped Control Rod ENS 439092008-01-17T00:25:00017 January 2008 00:25:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Due to Lowering Steam Generator Level ENS 432332007-03-13T19:27:00013 March 2007 19:27:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Due to "a" Main Feedwater Pump ENS 431152007-01-23T17:44:00023 January 2007 17:44:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Reactor Trip Due to Feedwater Regulating Valve Failure ENS 424442006-03-22T21:24:00022 March 2006 21:24:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Turbine Trip / Reactor Trip Caused by Main Generator Trip ENS 415832005-04-09T15:11:0009 April 2005 15:11:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip on Turbine Trip Due to Low Auto Stop Oil Pressure on Pressure Switches ENS 414372005-02-24T02:06:00024 February 2005 02:06:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip on Low-Low Steam Generator Level ENS 405892004-03-15T20:18:00015 March 2004 20:18:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to Main Generator Electrical Fault Signal ENS 404752004-01-25T08:16:00025 January 2004 08:16:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unplanned Auto Start of Turbine Driven Auxiliary Feedwater Pump ENS 403052003-11-10T04:15:00010 November 2003 04:15:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Sequoyah Unit 2 Auxiliary Feedwater Actuation During Outage ENS 401132003-08-28T20:04:00028 August 2003 20:04:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Alert Declared Due to Reactor Protection System Failure 2025-06-24T07:51:00 | |