ENS 51929
ENS Event | |
|---|---|
10:38 May 15, 2016 | |
| Title | Unusual Event Due to Main Generator Hydrogen Leak in Turbine Building |
| Event Description | At 0638 EDT on 5/15/2016, an Unusual Event (EAL GU.2) was declared on Millstone Unit 3 due to a Main Generator hydrogen gas leak into the Turbine Building. At 0645 EDT, operators manually tripped the reactor. All rods inserted. All systems functioned as expected following the reactor trip. Operators are currently venting the remaining hydrogen from the generator through the normal vent path. There is no safety related equipment out-of-service. The plant is in a normal post-trip electrical line-up. All Emergency Diesel Generators are available.
The licensee notified the State of Connecticut and the NRC Resident Inspector. Notified DHS SWO, FEMA Ops Center, and DHS NICC Watch Officer. Notified via E-mail FEMA National Watch Center and NuclearSSA.
At 0949 EDT, the licensee terminated the Unusual Event. At 0645 EDT on 5/15/16, a manual reactor trip was initiated at Millstone Unit 3 due to a hydrogen leak from the main generator. As expected, Auxiliary Feedwater System (AFW) initiated on the reactor trip. The trip was uncomplicated and the plant is currently in Mode 3 with a normal electric lineup and decay heat is being removed via steam dumps to the condenser. The cause of the hydrogen leakage is under investigation. This is reportable under 10 CFR 50.72(b)(2)(iv)(B) - RPS actuation while critical, and 10 CFR 50.72 (b)(3)(iv)(A) - valid specified system actuation. The licensee has notified Waterford Township, the State of Connecticut and the NRC Resident Inspector. Notified R1DO (Burritt), NRR ET (McDermott), NRR EO (Morris), IRD (Grant), DHS SWO, FEMA Ops Center, DHS NICC, FEMA National Watch Center (email) and NuclearSSA (email). |
| Where | |
|---|---|
| Millstone Connecticut (NRC Region 1) | |
| Reporting | |
| Emergency class: | Unusual Event |
| 10 CFR 50.72(a) (1) (i), Emergency Class Declaration 10 CFR 50.72(b)(3)(iv)(A), System Actuation 10 CFR 50.72(b)(2)(iv)(B), RPS Actuation | |
| Time - Person (Reporting Time:+-3.5 h-0.146 days <br />-0.0208 weeks <br />-0.00479 months <br />) | |
| Opened: | Michael Ciccone 07:08 May 15, 2016 |
| NRC Officer: | Donald Norwood |
| Last Updated: | May 15, 2016 |
| 51929 - NRC Website
Loading map... {"minzoom":false,"maxzoom":false,"mappingservice":"leaflet","width":"350px","height":"250px","centre":false,"title":"","label":"","icon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"zoom":6,"defzoom":14,"layers":["OpenStreetMap"],"image layers":[],"overlays":[],"resizable":false,"fullscreen":false,"scrollwheelzoom":true,"cluster":false,"clustermaxzoom":20,"clusterzoomonclick":true,"clustermaxradius":80,"clusterspiderfy":true,"geojson":"","clicktarget":"","imageLayers":[],"locations":[{"text":"\u003Cb\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003E\u003Ca class=\"mw-selflink selflink\"\u003EENS 51929\u003C/a\u003E - \u003Ca href=\"/Millstone\" title=\"Millstone\"\u003EMillstone\u003C/a\u003E\n\u003C/p\u003E\u003C/div\u003E\u003C/b\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003EUnusual Event Due to Main Generator Hydrogen Leak in Turbine Building\n\u003C/p\u003E\u003C/div\u003E","title":"ENS 51929 - Millstone\n","link":"","lat":41.310722222222225,"lon":-72.16767777777778,"icon":"/w/images/b/b0/Dominion_icon.png"}],"imageoverlays":null} | |
Unit 3 | |
|---|---|
| Reactor critical | Critical |
| Scram | Yes, Manual Scram |
| Before | Power Operation (100 %) |
| After | Hot Standby (0 %) |
Millstone | |
WEEKMONTHYEARENS 576942025-05-07T01:08:0007 May 2025 01:08:00
[Table view]10 CFR 50.72(b)(3)(iv)(A), System Actuation Specified System Actuation - Automatic Start of Emergency Diesel Generator ENS 565442023-05-30T08:46:00030 May 2023 08:46:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Reactor Trip ENS 549882020-11-08T13:29:0008 November 2020 13:29:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Due to Earthquake Felt Onsite ENS 546632020-04-13T19:50:00013 April 2020 19:50:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Automatic Trip Due to Low Condenser Vacuum ENS 546312020-04-01T20:25:0001 April 2020 20:25:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Automatic Reactor Trip Due to Circuit Fault ENS 544572019-12-27T12:04:00027 December 2019 12:04:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Trip Due to Feedwater Pump Trip ENS 530052017-10-09T18:05:0009 October 2017 18:05:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Unusual Event - Flammable Gas in the Turbine Building ENS 529042017-08-15T11:48:00015 August 2017 11:48:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Due to Fire Alarm in Containment ENS 521692016-08-11T13:59:00011 August 2016 13:59:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Reactor Trip Due to Loss of Two Circulating Water Pumps ENS 519292016-05-15T10:38:00015 May 2016 10:38:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Due to Main Generator Hydrogen Leak in Turbine Building ENS 516822016-01-25T06:47:00025 January 2016 06:47:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to Reactor Coolant Pump Trip ENS 515212015-11-08T07:30:0008 November 2015 07:30:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Reactor Trip Due to Reactor Coolant Pump Oil Leak ENS 515132015-11-04T16:33:0004 November 2015 16:33:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Fire on the 'A' Emergency Diesel Generator ENS 514482015-10-04T13:32:0004 October 2015 13:32:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Identified Rcs Leakage > 25 Gpm ENS 501412014-05-25T11:02:00025 May 2014 11:02:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Due to Loss of Offsite Power ENS 501422014-05-25T11:02:00025 May 2014 11:02:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation, 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Unusual Event Due to Loss of Offsite Power ENS 495252013-11-09T20:13:0009 November 2013 20:13:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to Loss of Condenser Vacuum ENS 492602013-08-10T01:19:00010 August 2013 01:19:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip on Low Steam Generator Water Level ENS 520002013-06-13T00:13:00013 June 2013 00:13:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation, 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Technical Specification Required Shutdown and Reactor Trip ENS 490392013-05-16T06:56:00016 May 2013 06:56:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip During Control Rod Testing ENS 474612011-11-20T22:58:00020 November 2011 22:58:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Due to Loss of Condenser Vacuum During Startup ENS 469712011-06-20T15:52:00020 June 2011 15:52:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unit 2 Reactor Trip Following the Loss of the "B" Main Feedwater (Mfw) Pump ENS 464412010-11-28T20:15:00028 November 2010 20:15:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip After Turbine Trip Due to Loss of Condenser Vacuum ENS 459452010-05-22T20:45:00022 May 2010 20:45:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Due to Loss of Steam Generator Water Level Control ENS 459312010-05-17T14:17:00017 May 2010 14:17:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to Low Steam Generator Water Level ENS 457292010-02-26T16:25:00026 February 2010 16:25:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Due to Loss of Two Circulating Water Pumps ENS 455832009-12-20T03:53:00020 December 2009 03:53:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Caused by a Turbine/Generator Electrical Fault ENS 454982009-11-15T13:26:00015 November 2009 13:26:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unit 2 Declared an Unusual Event Due to a Loss of Annunciators ENS 451832009-07-03T17:05:0003 July 2009 17:05:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Reactor Trip Resulting from Turbine Trip ENS 445642008-10-12T02:36:00012 October 2008 02:36:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Turbine Trip/ Automatic Reactor Trip on Low Steam Generator Level ENS 443262008-06-28T15:46:00028 June 2008 15:46:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Reactor Trip Due to Loss of Both Feedwater Pumps ENS 442382008-05-24T13:54:00024 May 2008 13:54:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Loss of Offsite Power ENS 442342008-05-22T18:20:00022 May 2008 18:20:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Reactor Trip Due to Lightning Strike ENS 441212008-04-06T17:17:0006 April 2008 17:17:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event from Reactor Coolant System Leakage ENS 433182007-04-25T15:01:00025 April 2007 15:01:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Loss of Offsite Power While Defueled ENS 427252006-07-25T13:45:00025 July 2006 13:45:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Reactor Trip Breakers Opened During Maintenance on Steam Generator Wide Level Channels ENS 423672006-02-23T15:22:00023 February 2006 15:22:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Due to Loss of Main Feedwater ENS 421802005-12-01T19:45:0001 December 2005 19:45:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to Low Steam Generator Level ENS 420242005-09-29T17:10:00029 September 2005 17:10:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Due to Loss of Circulating Water Pumps ENS 416072005-04-17T12:42:00017 April 2005 12:42:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation, 10 CFR 50.72(b)(2)(iv)(A), System Actuation - ECCS Discharge Alert Declared Due to Unit 3 Main Steam Relief Valves Not Reseating After Actuation ENS 413332005-01-14T14:55:00014 January 2005 14:55:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Licensee Reported a Fire in the Turbine Building ENS 405912004-03-16T01:20:00016 March 2004 01:20:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip at Millstone 2 Due to Spurious Loss of One Main Feed Pump ENS 405702004-03-06T05:50:0006 March 2004 05:50:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip at Millstone 2 Due to Spurious Trip of the "B" Feed Pump ENS 403612003-11-29T03:05:00029 November 2003 03:05:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Reactor Trip from 11% Power Due to Turbine Vibration ENS 403582003-11-27T11:29:00027 November 2003 11:29:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Plant Had a Manual Reactor Trip from 23% Power Due to Turbine Vibration ENS 402452003-10-14T08:04:00014 October 2003 08:04:00 10 CFR 50.72(b)(3)(v)(B), Loss of Safety Function - Remove Residual Heat, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared - Loss of Shutdown Cooling 2025-05-07T01:08:00 | |