| Title | Part 21 - Fisher Type 377 Trip Valves Not Processed as Required |
| Event Description | Fisher Information Notice: FIN 2013-05
Purpose: The purpose of this Fisher Information Notice (FIN) is to alert Dominion Virginia Power, Omaha Public Power District and Florida Power and Light that as of 17 December 2013, Fisher Controls International LLC ('Fisher') became aware of the possibility of a situation which may affect the performance of the applicable equipment. Fisher is informing you of this circumstance in accordance with Section 21.21 (b) of 10CFR Part 21. Applicability: This notice applies only to the subject equipment supplied by Fisher, identified in the above referenced orders. Discussion: The Type 377 Trip Valve assembly was subjected to the processing requirements of Fisher Controls FMP2K27 (Control of Commercial Grade Items to be Dedicated for Use in Nuclear Safety-Related Applications) and was supplied as a safety related component. However, for the above referenced orders, Fisher supplied various other parts, in addition to the Type 377 Trip Valve, that were not processed as required by the requirements of 2K27; thus, such parts were supplied as commercial items. Action Required: Each recipient needs to: (i) evaluate the situation for each application of the Type 377 Trip Valve; (ii) determine what portions of the Trip Valve system are 'essential to function'; and (iii) determine what commercial parts may be installed in the Type 377 Trip systems in their respective plants. 10CFR21 Implications: Fisher requests that the recipient of this notice review it and take appropriate action in accordance with 10CFR Part 21. If there are any technical questions or concerns, please contact: George Baitinger Manager, Quality Fisher Controls International LLC 205 South Center Street Marshalltown, La 50158 Fax: (641) 754-2854 Phone: (641) 754-2026 George.Baitinger@Emerson.com North Anna, Surry, Fort Calhoun, and St. Lucie plants are affected by this Fisher Information Notice. |
| Where | |
|---|---|
| Fisher Controls International, Llc Marshalltown, Iowa (NRC Region 3) | |
| Organization: | Fisher Controls International, Llc |
| Reporting | |
| 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect | |
| Time - Person (Reporting Time:+58.7 h2.446 days <br />0.349 weeks <br />0.0804 months <br />) | |
| Opened: | Dennis Swanson 16:42 Dec 19, 2013 |
| NRC Officer: | Dong Park |
| Last Updated: | Dec 19, 2013 |
| 49664 - NRC Website | |
Fisher Controls International, Llc with 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect | |
WEEKMONTHYEARENS 529352017-08-28T05:00:00028 August 2017 05:00:00
[Table view]10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 Report - Flow Scanner 6.6 Code Error ENS 518102016-01-22T05:00:00022 January 2016 05:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 - Plug/Stem Assembly ENS 517002016-01-05T06:00:0005 January 2016 06:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 - Improper Accessory Mounting Bracket Processing ENS 506352014-10-06T05:00:0006 October 2014 05:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 - Type 67 Afr Regulators with Improperly Dedicated Diaphragm Valve Seats ENS 496642013-12-17T06:00:00017 December 2013 06:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 - Fisher Type 377 Trip Valves Not Processed as Required ENS 493372013-08-02T05:00:0002 August 2013 05:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 Report - Improper Dedication of Actuator Parts ENS 484922012-11-07T06:00:0007 November 2012 06:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 Report- Commercial Grade Dedication Not Properly Applied to Butterfly Valves ENS 478462012-04-18T05:00:00018 April 2012 05:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Fisher Type 9500 Butterfly Valves Contain Non Dedicated Parts 2017-08-28T05:00:00 | |