ENS 47713
From kanterella
Jump to navigation
Jump to search
ENS Event | |
|---|---|
23:05 Mar 1, 2012 | |
| Title | Battery Room Ventilation System Degraded |
| Event Description | While Units 1 and 2 were in Mode 1, operating at 100% power, an issue was identified with the doors for the safety related battery rooms and their normal position. Several doors to the battery rooms were found to be held open via electromagnetic door devices. These doors are an integral part of their battery room exhaust system. As designed, there is no uninterruptible power to the door mechanisms, all the doors are expected to close in the event of a Loss of Offsite Power.
The closure of the doors to the battery rooms, being an integral part of the exhaust system, would disrupt ventilation in the battery rooms and could allow hydrogen to increase to unacceptable levels during Loss of Offsite Power events. Compensatory measures have been taken to secure the doors open to maintain the hydrogen purging function before required limits are reached. The battery room ventilation system remains functional supporting operability of the batteries. Luminant Power determined this issue to be reportable as an unanalyzed condition per 10 CFR 50.72(b)(3)(ii)(B). The licensee will notify the NRC Resident Inspector. |
| Where | |
|---|---|
| Comanche Peak Texas (NRC Region 4) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition | |
| Time - Person (Reporting Time:+-4.4 h-0.183 days <br />-0.0262 weeks <br />-0.00603 months <br />) | |
| Opened: | Raul Martinez 18:41 Mar 1, 2012 |
| NRC Officer: | John Knoke |
| Last Updated: | Mar 1, 2012 |
| 47713 - NRC Website
Loading map... {"minzoom":false,"maxzoom":false,"mappingservice":"leaflet","width":"350px","height":"250px","centre":false,"title":"","label":"","icon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"zoom":6,"defzoom":14,"layers":["OpenStreetMap"],"image layers":[],"overlays":[],"resizable":false,"fullscreen":false,"scrollwheelzoom":true,"cluster":false,"clustermaxzoom":20,"clusterzoomonclick":true,"clustermaxradius":80,"clusterspiderfy":true,"geojson":"","clicktarget":"","imageLayers":[],"locations":[{"text":"\u003Cb\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003E\u003Ca class=\"mw-selflink selflink\"\u003EENS 47713\u003C/a\u003E - \u003Ca href=\"/Comanche_Peak\" title=\"Comanche Peak\"\u003EComanche Peak\u003C/a\u003E\n\u003C/p\u003E\u003C/div\u003E\u003C/b\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003EBattery Room Ventilation System Degraded\n\u003C/p\u003E\u003C/div\u003E","title":"ENS 47713 - Comanche Peak\n","link":"","lat":32.29839166666667,"lon":-97.78532222222222,"icon":"/w/images/d/d7/Luminant_icon.png"}],"imageoverlays":null} | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
Unit 2 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
WEEKMONTHYEARENS 528172017-06-21T15:00:00021 June 2017 15:00:00
[Table view]10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Postulated Fire Event Could Adversely Impact Safe Shutdown Equipment ENS 526462017-03-29T00:57:00029 March 2017 00:57:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition for a Postulated Moderate Energy Line Break ENS 524842017-01-11T21:00:00011 January 2017 21:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Teflon Found in Containment Spray Pump Components ENS 522442016-09-15T20:40:00015 September 2016 20:40:00 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition, 10 CFR 50.72(b)(3)(v)(C), Loss of Safety Function - Release of Radioactive Material Potential Degradation of Eccs Pump Pressure Indicators ENS 522392016-09-13T22:30:00013 September 2016 22:30:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Involving Station Service Water Trains ENS 522172016-09-01T15:25:0001 September 2016 15:25:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition on Turbine Driven Auxiliary Feedwater Pump ENS 517512016-02-23T23:00:00023 February 2016 23:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Involving Normally Open Battery Room Doors ENS 508352015-02-19T22:00:00019 February 2015 22:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Involving Normally Closed Watertight Doors ENS 500432014-04-18T17:52:00018 April 2014 17:52:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Cable Routing Unanalyzed for Fire Safe Shutdown Barrier ENS 494192013-10-08T17:40:0008 October 2013 17:40:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Postulated Hot Short Fire Event That Could Adversely Impact Safe Shutdown Equipment ENS 477132012-03-01T23:05:0001 March 2012 23:05:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Battery Room Ventilation System Degraded ENS 473572011-10-20T01:02:00020 October 2011 01:02:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Due to Pressure Instruments Containing Aluminum Material ENS 473522011-10-18T20:45:00018 October 2011 20:45:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Aluminum Valve Discovered Installed in Containment ENS 470862011-07-21T16:53:00021 July 2011 16:53:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Vulnerability from a Potential Control Room Fire on "a" Safeguards Bus ENS 435622007-08-13T14:00:00013 August 2007 14:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Inadequate Fire Protection on Safety Chilled Water System Electrical Cables 2017-06-21T15:00:00 | |