05000528/LER-2005-008, Re Inverter Failure - Technical Specification Violation

From kanterella
Jump to navigation Jump to search
Re Inverter Failure - Technical Specification Violation
ML060530506
Person / Time
Site: Palo Verde Arizona Public Service icon.png
Issue date: 02/10/2006
From: Eubanks C
Arizona Public Service Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
102-05409-CE/SAB/DFH LER 05-008-00
Download: ML060530506 (5)


LER-2005-008, Re Inverter Failure - Technical Specification Violation
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(i)

10 CFR 50.73(a)(2)(vii), Common Cause Inoperability

10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded

10 CFR 50.73(a)(2)(viii)(A)

10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition

10 CFR 50.73(a)(2)(viii)(B)

10 CFR 50.73(a)(2)(iii)

10 CFR 50.73(a)(2)(ix)(A)

10 CFR 50.73(a)(2)(iv)(A), System Actuation

10 CFR 50.73(a)(2)(x)

10 CFR 50.73(a)(2)(v)(A), Loss of Safety Function - Shutdown the Reactor

10 CFR 50.73(a)(2)(v)(B), Loss of Safety Function - Remove Residual Heat

10 CFR 50.73(a)(2)(v), Loss of Safety Function
5282005008R00 - NRC Website

text

10 CFR 50.73 BA subsidiary of Pinnacle West Capital Corporation Cliff Eubanks Mail Station 7602 Palo Verde Nuclear Vice President Tel (623) 393-6116 PO Box 52034 Generating Station Nuclear Operations Fax (623) 393-6077 Phoenix, Arizona 85072-2034 102-05409-CE/SAB/DFH February 10, 2006 ATTN: Document Control Desk U. S. Nuclear Regulatory Commission Washington, DC 20555-0001

Dear Sirs:

Subject:

Palo Verde Nuclear Generating Station (PVNGS)

Unit I Docket No. STN 50-528 License No. NPF-41 Licensee Event Report 20,05-008-00 Attached, please find Licensee Event Report (LER) 50-528/2005-008, which reports a failure to meet a Technical Specification (TS) that requires two Operable trains of inverters.

In accordance with 10 CFR 50.4, a copy of this LER is being forwarded to the NRC Regional Office, NRC Region IV and the Resident Inspector. If you have questions regarding this submittal, please contact James A. Proctor, Section Leader, Regulatory Affairs, at (623) 393-5730.

Arizona Public Service Company makes no commitments in this letter. The corrective actions described in this LER are not necessary to maintain compliance with regulations.

Sincerely, CE/SAB/DFH/ca Attachment cc:

B. S. Mallett NRC Region IV Regional Administrator Gi. G. Warnick NRC Senior Resident Inspector for PVNGS M/l. B. Fields NRC NRR Project Manager

NRC FORM 366 U.S. NUCLEAR REGULATORY COMMISSION APPROVED BY OMB: NO. 3150-0104 EXPIRES: 06/30/2007 (6-2004)

, the NRC may sfor each block) not conduct or sponsor, and a person is not required to respond to, the digits/characters

- o ah lc)information collection.__________________
3. PAGE PALO VERDE NUCLEAR GENERATING STATION UNIT 1 05000528 1 OF 4
4. TITLE Inverter Failure - Technical Specification Violation - Unit 1
5. EVENT DATE
6. LER NUMBER
7. REPORT DATE
8. OTHER FACILITIES INVOLVED SEUNILRVFACILITY NAME DOCKET NUMBER MONTH DAY YEAR YEAR NUMBEN REV MONTH DAY YEAR FACILITY NAME DOCKET NUMBER 10 30 2005 2005 008 00 2

10 2006

9. OPERATING MODE I1'. THIS REPORT IS SUBMITED FPURSUANT TO THE REQUIREMENTS OF 10 CFR§: (Check all that apply) o 20.2201(b) al 20.2203(a)(3)(i)

El 50.73(a)(2)(i)(C)

E 50.73(a)(2)(vii)

Defueled El 20.2201(d)

El 20.2203(a)(3)(ii)

El 50.73(a)(2)(ii)(A)

El 50.73(a)(2)(viii)(A)

O 20.2203(a)(1)

El 20.2203(a)(4)

El 50.73(a)(2)(ii)(B)

El 50.73(a)(2)(viii)(B)

_ o 20.2203(a)(2)(i)

El 50.36 c)(1)(i)(A)

El 50.73(a)(2)(iii)

El 50.73(a)(2)(ix)(A)

10. POWER LEVEL E

20.2203(a)(2)(ii) l 50.36(c)(1)(ii)(A)

E 50.73(a)(2)(iv)(A)

El 50.73(a)(2)(x) rl 20.2203(a)(2)(iii) 0 50.36(c)(2)

E 50.73(a)(2)(v)(A)

El 73.71(a)(4)

El 20.2203(a)(2)(iv)

El 50.46(a)(3)(ii)

El 50.73(a)(2)(v)(B)

El 73.71(a)(5) 0 F1 20.2203(a)(2)(v)

El 50.731a)(2)(i)(A)

El 50.73(a)(2)(v)(C)

El OTHER Cl 20.2203(a)(2)(vi) 0 50.731a)(2)(i)(B) a 50.73(a)(2)(v)(D)

Specify in Abstract below or in (if mnre space is required, use additional copies of (If n7ore space is required, use additional copies of (If more space is required, use additional copies of NRC Form 366A)

An equipment root cause of failure was preformed on the failed inverter and inspections to identify the extent of the condition were completed in all three Units. No other inverters were found with a similar condition as the failed inverter. Additionally, the warehouse stock of similar capacitors were inspected and verified not to be affected.

Since this issue was not identified in the commercial grade dedication program, CRDR 284581,8 was generated to evaluate the adequacy of the dedication process that was used to dedicate the affected capacitors.

8. PREVIOUS SIMILAR EVENTS

No similar condition has been reported in the past three years.

9.

ADDITIONAL INFORMATION

None.