05000458/LER-2021-001, Manual Reactor Scram Due to Loss of Main Condenser Vacuum

From kanterella
Jump to navigation Jump to search
Manual Reactor Scram Due to Loss of Main Condenser Vacuum
ML21141A193
Person / Time
Site: River Bend Entergy icon.png
Issue date: 05/20/2021
From: Vercelli S
Entergy Operations
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
RBG-48094 LER 2021-01-00
Download: ML21141A193 (4)


LER-2021-001, Manual Reactor Scram Due to Loss of Main Condenser Vacuum
Event date:
Report date:
4582021001R00 - NRC Website

text

Abstract

On March 25, 2021 at 09:01 CDT, River Bend Station was operating at 93% reactor power when Main Condenser vacuum began to lower. Reactor power was lowered in an attempt to maintain Main Condenser vacuum. At 09:18 a manual reactor scram was initiated from approximately 80% reactor power due to Main Condenser vacuum continuing to lower. All control rods fully inserted and there were no complications. All systems responded as designed.

The loss of vacuum was caused by the in-service Steam Air Ejector Suction Valve closing due to faults within the valves control components. The Steam Air Ejector Suction Valve function was restored by replacing the faulted components.

River Bend Station will establish a program to test the fail-as-is function of the Steam Air Ejector Suction Valves every outage.