MONTHYEARML1027307792010-09-30030 September 2010 CLI-10-27 Memorandum and Order Denying Interlocutory Appeals, Reverse the Board Order, and Terminate Adjudicatory Proceeding Project stage: Request ML1107408522011-03-14014 March 2011 Declaration of Karen Hadden on Behalf of Seed Coalition Project stage: Other ML1107408502011-03-14014 March 2011 Declaration of Susan Dancer on Behalf of Seed Coalition Project stage: Other ML1107408482011-03-14014 March 2011 Petition for Leave to Intervene and Request for Hearing of Seed Coalition and Susan Dancer Project stage: Request ML1109705442011-04-0707 April 2011 STP Nuclear Operating Companys Answer Opposing Request for Hearing and Petition for Leave to Intervene Project stage: Request ML1109706592011-04-0707 April 2011 NRC Staffs Answer to Petition for Leave to Intervene and Request for Hearing of Seed Coalition and Susan Dancer Project stage: Request ML1112800022011-05-0808 May 2011 Petitioners Proposed Amended Petition for Leave to Intervene & Request for Hearing of Seed Coalition & Susan Dancer Project stage: Request ML1112800032011-05-0808 May 2011 Intervenors Request for Oral Argument on Contentions Raised on Relicensing Project stage: Request ML1114307992011-05-23023 May 2011 Order (Scheduling Oral Argument) Project stage: Request ML11161A1432011-06-0202 June 2011 License Amendment Request for Approval of a Revision to the South Texas Project Fire Protection Program Related to the Alternative Shutdown Capability Project stage: Request ML1115303932011-06-0202 June 2011 NRC Staff Answer to Proposed Amended Petition for Leave to Intervene and Request for Hearing of Seed Coalition and Susan Dancer Project stage: Request ML1120101502011-07-22022 July 2011 License Amendment Request to Approve Revision to Fire Protection Program Related to Alternate Shutdown Capability - Unacceptable for Review with Opportunity to Supplement Project stage: Other NOC-AE-11002703, Supplement to the License Amendment Request for Approval of a Revision to the South Texas Fire Protection Program Related to the Alternative Shutdown Capability2011-08-0101 August 2011 Supplement to the License Amendment Request for Approval of a Revision to the South Texas Fire Protection Program Related to the Alternative Shutdown Capability Project stage: Supplement ML11221A2302011-08-0101 August 2011 Supplement to the License Amendment Request for Approval of a Revision to the South Texas Fire Protection Program Related to the Alternative Shutdown Capability Project stage: Supplement ML1121404492011-08-0909 August 2011 License Amendment Request to Approve Revision to Fire Protection Program Related to Alternate Shutdown Capability - Acceptable for Review Following Supplement Project stage: Other ML1204001382012-02-0808 February 2012 Email, Request for Additional Information, License Amendment Request to Approve Revision to Fire Protection Program in Fire Hazards Analysis Report Related to Alternate Shutdown Capability Project stage: RAI ML1204001462012-02-0808 February 2012 Request for Additional Information, License Amendment Request to Approve Revision to Fire Protection Program in Fire Hazards Analysis Report Related to Alternate Shutdown Capability Project stage: RAI ML1204701642012-02-16016 February 2012 Request for Additional Information Email, Round 2, License Amendment Request to Approve Revision to Fire Protection Program in Fire Hazards Analysis Report Related to Alternate Shutdown Capability Project stage: RAI ML1204701612012-02-16016 February 2012 Email, Request for Additional Information, Round 2, License Amendment Request to Approve Revision to Fire Protection Program in Fire Hazards Analysis Report Related to Alternate Shutdown Capability Project stage: RAI ML12079A0382012-03-0808 March 2012 Response to Request for Additional Information Regarding License Amendment Request for Revision to the Fire Protection Program Related to the Alternative Shutdown Capability Project stage: Response to RAI NOC-AE-12002801, Response to Request for Additional Information Regarding License Amendment Request for Revision to the Fire Protection Program Related to the Alternative Shutdown Capability2012-03-0808 March 2012 Response to Request for Additional Information Regarding License Amendment Request for Revision to the Fire Protection Program Related to the Alternative Shutdown Capability Project stage: Response to RAI ML12101A2232012-04-0303 April 2012 Response to Request for Additional Information, 01.1, Regarding to the License Amendment Request to Revise the South Texas Project Fire Protection Program Related to the Alternative Shutdown Capability Project stage: Response to RAI NOC-AE-12002827, Response to Request for Additional Information, 01.1, Regarding to the License Amendment Request to Revise the South Texas Project Fire Protection Program Related to the Alternative Shutdown Capability2012-04-0303 April 2012 Response to Request for Additional Information, 01.1, Regarding to the License Amendment Request to Revise the South Texas Project Fire Protection Program Related to the Alternative Shutdown Capability Project stage: Response to RAI NOC-AE-12002838, Response to Request for Additional Information, RAI-01.1, Regarding the License Amendment Request to Revise the South Texas Project Fire Protection Program Related to the Alternative Shutdown Capability2012-05-0303 May 2012 Response to Request for Additional Information, RAI-01.1, Regarding the License Amendment Request to Revise the South Texas Project Fire Protection Program Related to the Alternative Shutdown Capability Project stage: Response to RAI ML12135A1822012-05-0303 May 2012 Response to Request for Additional Information, RAI-01.1, Regarding the License Amendment Request to Revise the South Texas Project Fire Protection Program Related to the Alternative Shutdown Capability Project stage: Response to RAI ML12213A0592012-07-31031 July 2012 Notice of Appearance of Lloyd B. Subin on Behalf of the U.S. Nuclear Regulatory Commission in the Matter of South Texas, Units 1 and 2 Project stage: Request NOC-AE-12002892, Withdrawal of Proposed License Amendment Request to Revise the South Texas Project Fire Protection Program Related to the Alternative Shutdown Capability2012-07-31031 July 2012 Withdrawal of Proposed License Amendment Request to Revise the South Texas Project Fire Protection Program Related to the Alternative Shutdown Capability Project stage: Withdrawal ML12220A5092012-07-31031 July 2012 Withdrawal of Proposed License Amendment Request to Revise the South Texas Project Fire Protection Program Related to the Alternative Shutdown Capability Project stage: Withdrawal ML12222A0262012-08-14014 August 2012 FRN - Withdrawal of License Amendment Request to Approve Revision to Fire Protection Program in Fire Hazards Analysis Report Related to Alternate Shutdown Capability Project stage: Withdrawal ML12222A0232012-08-14014 August 2012 Letter, Withdrawal of License Amendment Request to Approve Revision to Fire Protection Program in Fire Hazards Analysis Report Related to Alternate Shutdown Capability Project stage: Withdrawal NRC-2012-0196, South Texas Project, Units 1 and 2 - FRN - Withdrawal of License Amendment Request to Approve Revision to Fire Protection Program in Fire Hazards Analysis Report Related to Alternate Shutdown Capability (TAC Nos. ME6346 and ME6347)2012-08-14014 August 2012 South Texas Project, Units 1 and 2 - FRN - Withdrawal of License Amendment Request to Approve Revision to Fire Protection Program in Fire Hazards Analysis Report Related to Alternate Shutdown Capability (TAC Nos. ME6346 and ME6347) Project stage: Withdrawal 2011-08-01
[Table View] |
Text
REQUEST FOR ADDITIONAL INFORMATION LICENSE AMENDMENT REQUEST REVISION TO THE SOUTH TEXAS PROJECT (STP), UNITS 1 AND 2 FIRE PROTECTION PROGRAM RELATED TO THE ALTERNATE SHUTDOWN VCAPABILITY
- 1. In its submittal dated June 2, 2011 (Agencywide Documents Access and Management System (ADAMS) Accession No. ML11161A143), STP Nuclear Operating Company (STPNOC, the licensee) stated that a fire induced spurious opening of the pressurizer PORVs would result in an engineered safety features safety injection (SI) signal in approximately 71 seconds. In submittal dated August 1, 2011 (ADAMS Accession No. ML11221A230), however, the time is identified as 61 seconds following reactor trip.
Please clarify which value is correct.
- 2. The its request dated June 2, 2011, the licensee states that operators can close the power operated relief valve (PORV) block valves within sixty seconds. Analytic results indicate that a SI signal would be received in either 61 or 71 seconds following spurious PORV opening on reactor trip, assuming the reactor is in a nominal condition prior to reactor trip. Please quantify the uncertainty in SI signal receipt time attributable to the pre-trip power level, reactor coolant system (RCS) average temperature, pressurizer pressure and level, and RCS flow uncertainties and demonstrate that this uncertainty, when accounted for, leaves enough time for operator intervention to close the PORV block valves post-trip.
- 3. Letter dated June 2, 2011 states that operators can place centrifugal charging pumps in pull to lock within 120 seconds, and a SI actuation would occur at 146 seconds, if the pressurizer auxiliary spray valve opens on reactor trip. Please demonstrate that the 26 second margin between stated operator capability and the analyzed SI injection signal receipt time is sufficient to account for reactor pre-trip statepoint uncertainties.
- 4. Letter dated August 1, 2011, states that steam generator water level will go off-scale high in 130 seconds following a reactor trip with a spurious main feedwater isolation valve opening. The letter dated June 2, 2011 states that operators have demonstrated the capability to secure startup feed pumps within 120 seconds. Please demonstrate that the 10-second difference between stated operator capability and analytic results is sufficient to account for pre-trip reactor statepoint uncertainty.
- 5. Letter dated June 2, 2011 appears to consider each of the credited post-trip operator actions independently. Please clarify whether operators are assessed in their capability to follow all actions in aggregate following a reactor trip due to fire, or whether the actions are assessed separately. If the actions are assessed separately, explain how the independent assessments lead to a conclusion that all operator actions can be performed within their stated time frames, when performed together.