Text
Page i CALCULATION COVER SHEET Calcul ation No: PTN-BFJH-96-005
Title:
Fire Barrier Am acit Correction Factors - Extra olation of Test Results for 3 Hour Barrier Original Issue !
l(~
No. Descri tion By Date Chkd Date Appr Date REV IS IONS Form 82A, Rev 6/94 9hi2260324 9hi2i9 PDR ADQCK 05000335 P PDR
Page ii LIST OF EFFECTIVE PAGES Calculation No. PTN-BFJM-96-005 Rev.
Title Fire Barrier Am acit Correction Factors - Extra olation of Test Results for 3 Hour Barrier Pa e Section Rev. Pa e Section Rev.
1 0 ll 0 111 0 1 1,2 0 2 3 0 3 4 0 4 5 0 5 5 0 6 5 0 7 5 0' 8 5 9 6 0 A1 15 Pages)
A2 1 Page )
A3 3 Pages)
A4 2 Pages)
Form 82B, Rev 6/94
Page iii TABLE OF CONTENTS CALCULATION NUMBER PTN-BFJM-96-005 REV.
SECTION TITLE PAGES Cover Sheet List of Effective Pages Table of Contents 1.0 Purpose/Scope 2.0 References 3.0 Methodology 4.0 Assumptions/Bases 5.0 Calculation 6.0 Results ATTACH NO. TITLE PAGES Omega Point Lab Test Report kl2340- 15
.94583,95165,95168,95246, "Electrical Test to'etermine the Ampacity Derating of a Protective Envelope for Class 1E Electrical Conduits" ANSI C80. 1-1990 Table 2 - "Dimensions and Weights of Rigid Steel Conduits" Ebasco Calculation EC-096, "Cable Ampacity And Voltage Drop Calculation" Addendum B Pages 2,3,4.
TSI Inc., Thermolag 330-1 Thermal Properties 2 Form 82C, Rev 6/94
CALCULATION SHEET REV' SHEET NO.
1.0 Purpose/Scope GL 92-08 (Ref. 2. 1) has required FPL to review the ampacity correction factors (ACF) used for raceway with fire barriers. The ampacity correction will be based on testing performed at Omega Point Laboratories for Texas Utilities Comanche Peak Plant. The testing included conduit and cable tray with a 1 Hour fire barrier installed. This calculation will use heat transfer calculations to extrapolate the results from the 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> barrier tests to three hour rated barriers used at the Turkey Point and St. Lucie Plants.
2.0 References
- 2. 1 GL-92-08, "Thermo-Lag 330-1 Fire Barriers" Dated December 17, 1992.
2.2 Omega Point Lab Test Report ¹ 12340-94583,95165,95168,95246, "Electrical Test to Determine the Ampacity Derating of a Protective Envelope for Class lE Electrical Conduits" (Included as Attachment 1) 2.3 ASHRAE Handbook, 1991 Fundamentals 2.4 NRC Safety Evaluation of Ampacity Issues Related to Thermo-Lag Fire Barriers at Comanche Peak Steam Electric Station, Unit 2 (TAC No. H8599) Dated June 14, 1995.
ANSI C80. 1-1990, Table 2 "Dimensions and Weights of Rigid Steel Conduits" ( Included as Attachment 2) 2.6 Ebasco Calculation EC-096, "Cable Ampacity And Voltage Drop Calculation" ( Included as Attachment 3) 2.7. TSI Inc., Thermolag 330-1 Thermal Properties (Included as Attachment 4)
Form 83, Rev 6/94
CALCULATION SHEET I;
CALCULATION NO. PTN- BF JM-96-005 REV 0 SHEET NO.
3.0 Methodology THERI'AO-LAG CONDUIT CABLE Ri Rt Rs Rg Heat transfer will be calculated per foot of raceway length in accordance with the following relationship:
q (Tc-Ta) / (Ri + Rg + Rt + Rs) q Rate of heat transfer from raceway Tc Temperature of conductor (90'C/194'F)
Ta Ambient temperature (40'C/104'F)
Ri Thermal resistance of all items within the raceway including the raceway itself Rg Thermal resistance of the air gap between the raceway and the fire barrier material Rt Thermal resistance of the fire barrier material Rs Thermal resistance at the surface of the protected or unprotected raceway The heat transferred from the raceway under steady state conditions is essentially equal to the I'R losses within the conductors. These heat values can be determined from the test data based on the measured current and size of conductor used.
Tc and Ta are fixed test parameters with values which are listed above.
Form 83, Rev 6/94
CALCULATION SHEET 0 CALCULATION NO.
The thermal PTN- BF JH-96-005 resistance values will be REV 0 SHEET NO.
determined based on test data and physical properties as follows:
Ri will be calculated from the test data for raceway without fire barrier Rg will be calculated from the test data for raceway with a I hour barrier Rt will be calculated based on the known thermal conductivity (k) for The~mn-Lag Rs will be based un known physical properties considering convection arid radiation heat transfer.
After all of the thermal resistance values have been established, the heat transferred can be calculated for the raceway with the three hour barrier.
Since the heat is a function of the current squared, the ampacity correction factor (ACF) will be determined by the following relationship.
ACF I/I V(q,~q where the subscript p refers to the protected raceway Assumptions/Bases The effect of inductive losses in the raceway and cable sheath will be negligible with respect to applying the test data to the Turkey Point and St. Lucie configurations, 4.2 Surface emittance for cable, raceway, and Thermo-Lag will be assumed to be equal to 0.9.
Note that a high emittance value will reduce the thermal resistance at the surface having an overall effect of maximizing the ampacity de-rating.
4.3 Heat transfer through the sides of cable tray will be assumed to be zero. This will reduce the heat transfer equation for tray to a one dimensional heat transfer equation. As the tested cable tray is relatively wide ,24", this is expected to be a good approximation for all cable tray.
4.4 One hour Thermo-Lag fire barrier will be assumed to be at the minimum thickness of 1/2" (I/4" for overlay where used). This thickness will provide a conservative value when calculating the R value for the gap between the raceway and the barrier.
4.5 Three hour Thermo-Lag fire barrier will be assumed to be at the nominal thickness in accordance with the manufacture's tolerance, l-l/4 inches. This thickness'will provide a conservative result when calculating the heat transferred with the three hour barrier, as the value of the initial I hour wrap was minimized. It was judged to be unrealistically conservative to go to the maximum thickness tolerance of 1.5 inches.
4.6 Raceway is made of rigid steel, magnetic material, which is typical for power plant installations.
Banked conduit which is banked in a single plane can be assumed to be equivalent to cable tray. Both configurations involve a cable mass arranged in a shallow rectangular section.
Both configurations involve an air gap between the cables and the fire barrier material.
Form 83, Rev 6.'94
CALCULATION SHEET CALCULATION NO. PTN- BF JN-96-005 REV 0 SHEET NO. 4 4.8 The thermal resistance values for all items within the raceway and for the gap between the conduit and the Thermolag material will be assumed to remain constant as additional thickness of Thermolag is installed. Considering that the geometry of these areas is not changed, this approximation is reasonable for the purpose of extrapolating the thermal resistance from raceway with 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> wrap to raceway with 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> wrap.
5.0 Calculation
- 5. 1 Determination of test heat loads Test heat loss in watts is calculated by the following equation:
q IRN q Heat Per Foot I Test Current R Cable Resistance Per Foot N Number of Conductors Raceway (Conductor) Test Resistance Number of Heat/Ft Heat/Ft Size Current, Per Foot, Conductors Watts ~BTU Hr 3/4 (I-3C/0'10) 39.6'5.9
.001404 6.61 22.6 3/4 Wrapped 5.43 18.5 2 (I-3C/86) 64.5 .000555 3 6.93 23.7 .
2 Wrapped 60.2 6.03 20.6 5 (4-750 kCMil) 571 .0000224 4 29.21 99.7 5 Wrapped 510 23.30 79.5 Tray (126 -3C/86) 23.1 .000555 378 111.9 382.1 Tray Wrapped 15.8 52.4 178.7
- 1. Current is from Reference 2.2
- 2. Resistance per foot is from Ref. 2.6
- 3. Hultiply Watts by 3.413 to obtain BTU/Hr Form 83, Rev 6'94
CALCULATION SHEET CALCULATION NO. PTN- BF JH-96-005 REV 0 SHEET NO.
5.2 Determination of Thermo-Lag R values (R,)
For heat transfer through Thermo-Lag cylinder R Ln(RJR;)/2vkL (Ref. 2.3,Page 2.3)
R. Outside Radius R; Inside Radius k- Thermal Conductivity 0. 1 BTU/Hr-FT-'F (Ref. 2.7)
L Length 1 Ft. (Per Foot)
For heat transfer through Thermo-Lag sheet R L/kA (Ref. 2'.3,Page 2.3)
L Thickness k Thermal Conductivity 0. 1 BTU/Hr-FT-'F (Ref. 2.7)
A Surface Area N
A full tabulation of the Thermo-Lag R values for the various sizes is included in the spreadsheet below.
5.3 Determination of surface R values (R,)
The surface resistance will consider free convection and radiation heat transfer.
For free convection q, hAKT q, heat transferred by convection h - convection heat transfer coefficient For horizontal cylinders in air h .27(hT/L)'" (Ref. 2.3,Page 2. 12)
A - Surface Area L - Characteristic length in feet (diameter or width) q, .27(4T/L)"MT For radiation q, ohe(T, -T, ) (Ref. 2.3,Page 2. 11) q, Heat transferred by radiation 0 1.714X10 BTU/Hr-Ft -R', Boltzmann Constant A Surface area Surface Emittance .9 (Assumption 4. 1)
T Absolute Temperature, Rankine q, -1.714X10'(.9) A(T,'-T,')
Form 83, Rev 6/94
CALCULATION SHEET CALCULATION NO. PTN- BF JM-96-005 REV 0 SHEET NO. 6 For total heat transferred from the surface q, - q, + q, q, ~ .27(QT/L)'T + 1.714X10 (.9)A(T, -T2 )
q, = [.27(bT/L)' 1.714X10 (.9)(T, -T, )/QT]AbT GT/q, R, 1/ t,.27(GT/L) "+ 1.714X10'(.9.) (T,'-T,')/LT]A 5.4 Calculation of ACF The ACF is calculated using a spreadsheet in accordance with the methodology described above. A description of the spreadsheet follows:
OD/W This is an input value of the conduit outside diameter or cable tray width. Conduit diameters are obtained from Reference 2.5.
TH This value is the thermolag thickness. For each raceway size a thickness representing no wrap, 1 Hr wrap, and 3 Hr wrap is entered.
ODT This is the outside diameter of the raceway with any wrap calculated from the 00 and TH. For cable tray OD is not calculated because it will always be equal to W, A The outer surface heat transfer area. Note that for raceway both the top and bottom areas are included. Area is calculated on the basis of a one foot length of raceway.
Ri Inside thermal resistance as defined above. The value is calculated from the test data with no wrap in accordance with the following formula. The Ri value calculated is then used for the cases with 1 Hr and 3 Hr wrap. Note that there is no Rg and Rt for this case.
Ri hT/q - Rs, Where hT = 90'F (Temp drop from conductor surface to ambient)
Rg Gap thermal resistance as defined above. The value is calculated from the test data with 1 Hr wrap in accordance with the following formula. The Rg value calculated is then used for the case with 3 Hr wrap.
Rg bT/q - (Ri + Rt + Rs), Where hT - 90'F Rt Thermo-Lag thermal resistance. The value is calculated in accordance with the following equations which were developed above.
Conduit Rt Ln(ODT/OD)/2vk, k .1 (Ref. 2.7)
Tray Rt TH/kA, K .1 Form 83, Rev 6/94 r
CALCULATION SHEET CALCULATION NO. PTN- BF JH-96-005 REV 0 ,SHEET NO. 7 Rs Surface thermal resistance is calculated in accordance with the following equations which were developed above. Note that the hT in this equation is between the surface and ambient and the T4 values must be in 'R. The ambient temperature used is 104'F/564'R.
Rs 1/[.27((Ts-104)/ODT)" + 1.714X10'.9)((Ts +460)'-564')/(Ts-104)]A Ts Surface temperature of Thermo-Lag nr bare conduit. The value is determined by iteration until q q'.
q Heat transferred - For no wrap or 1 Hr wrap the value from the test data is used.
for 3 Hr wrap calculate as follows:
q hT/(Ri + Rg + Rt +-Rs), Where hT 90'F q'eat transferred follows:
from the surface - Calculate heat transferred from the surface as q - hT/Rs, Where hT Ts - 104'F From continuity', the heat transferred from the surface is the same as the total heat transferred. In order to solve the various cases, Ts is adjusted by iteration until ACF Ampacity correction factor calculated by the following equation which was developed above.
ACF v (q,~q Form 83, Rev 6/94
PTN-BF JM-96-005 Revision 0 Page8of 9 RACEWAY HEAT TRANSFER AND AMPACITYDE-RATING CONDUIT OD TH ODT A Ri Rg Rt Rs - Ts ACF IN IN IN SQFT BTU/HR-F BTU/HR-F BTU/HR-F BTU/HR-F F BTU/H BTU/H 1.05 0 1.05 0.2749 2.474 1.5088 138.10 22.60- 22.60 NIA 1.05 0.75 2.55 0.6676 2.474 0.201 . 1.4122 0.7782 118.40 18.50 18.50 0.905 1.05 1.25 3.55- 0.9294 2.474 0.201 1.9388 0.5996 114.35 17.27 17.27 0.874 2.375 0 2.375 0.6218 2.997 0.8006 122.97 23.70 23.70 N/A 2.375 0.75 3.875 1.0145 2.997 0.044 0.7791 0.5484 115.30 20.60 20.60 0.932 2.375 1.25 4.875 1.2763 2.997 0.044 1.1445 0.4564 1'12.85 19.39 19.39 0.904 5.563 1E-19 5.563 1.4564 0.560 0.3428 138.18 99.70,99.70 NIA 5.563 0.5 6.563 1.7182 0.560 0.000 0.2631 0.3094 128.60 79.50 79.50 0.893 5.563 1.25 8.063 2.1109 0.560 0.000 0.5907 0.2686 121.04 63.43 63.43 0.798 CABLE TRAY I BANKED CONDUIT W TH A Ri Rg Rt Rs Ts ACF IN IN SQFT BTU/HR-F BTU/HR-F BTU/HR-F BTU/HR-F F BTU/H BTU!H 24 0 4 0.102 0.1335 155.00 382.10 382.10 N/A 24 0.500 c 4 0.102 0.150 0.1042 0.147 130.27 178.70 I 78.70 0.684 24 1.25 4 0.102 0.150 0.2604 0.1513 124.50 135.50 135.50 0.595
0 CALCULATION SHEET CALCULATION NO. PTN- BF JH-96-005 REV 0 SHEET NO.
6.0 Results The ampacity correction factors for I Hr Thermo-Lag from testing and 3 hour3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> Thermo-Lag extrapolated by calculation are as follows.
Item ACF 1 Hr 3 Hr Conduit .89 .80 Tray (Banked Conduit) .69 .60 Form 83, Rev 6:94
PTN- BF JH-96-005 ATTACHMENT I REVISION, 0 PAGE I of 15 AMPACITY DEBATING OF FlRE PROTECTED CABLES Project No. 12343-94583,95165-95168,95246 ELECTRICAL TEST TO DETERMINE THE AMPACITYDERATING OF A PROTECTIVE ENVELOPE FOR CLASS 1E ELECTRICAL CIRCUITS March 19, 1993 Prepared For:
TU Electric COMQICHE PEAK STEAM ELECTRIC STATION P.O. Box 1002 Glen Rose, Texas 76043-1002 p ppcp)ypD OCT 2 0 f993
~~A Pp C~
0 r
o'hara
,PTN-BFJH-96-005 Report No. 12340-94583,95165-95168/5246 ATTACHHENT 1 Texas Utilities Electric REVISION 0 PAGE 2 of 15 Three conduit assemblies, two air drop assemblies, and one cable tray assembly, clad with Thermo-Lag materials as described herein,'ere evaluated in accordance with the Texas Utilities Electric TEST PLAN, Rev. 4, yielding the following ampacity derating values:
PERCENT TEST ITEM DERATING 3C/¹10 in 3/4" Conduit 9.34 3C/¹6 in 2" Conduit 6.67 3C/¹6 in Air Drop 24" Cable Tra 31.6 750 kCMil in Air Dro 31.8 4/C 750 kCMilin 5" Conduit) 10.7 The details, procedures and observations reported herein are correct and true within the limits of sound engineering practice. All specimens and test sample assemblies were produced, installed and tested under the surveillance of either Texas Utilities'r the testing laboratory's Quality Assurance Program. This report describes the analysis of distinct assemblies and includes descriptions of the test procedure followed, the assemblies tested, and all results obtained. All test data are on Gle and remain available for review'by authorized persons.
Herbert W Stansberry H Date Project Manager Constance A. Humphrey Date Manager, QA Dept.
Deggary N. Priest Date President
PTN-BFJH-96-005 Report, Ne. 12340-94583,95165-95168@5246 ATTACHMENT 1 Texas Utilities Electric REV I S10N 0 PAGE 3 of 15 TABLE OF CONTENTS INTRODUCTION TEST PROCEDURE 1 Test Enclosure 1 Thermo couples 2 Data Acquisition system 2 Current Control System 2 Final Current Measurements 3 TEST ASSEMBLY Test Items (General) 4 Test Items 5 Electrical Cables 7 Thermocouple Placement 8 Thermo-Lag Installation Highlights 8 TEST RESULTS 10 APPENDICES Appendix A: CONSTRUCTION DRAWINGS ]3 Appendix B: TEST PLAN 16 Appendix C: THERMOCOUPLE LOCATIONS 25 Appendix D: TABULA,TEST DATA 32 Appendix E: QUALITYASSURANCE 382 Appendix F: PHOTOGRAPHS 781 Appendix G: THERMO-LAG INSTALLATIONDETAILS 802 Last Page of Document 8%
OQAyo+
PTN-BFJH-96-005 Report No. 12340-94583,95165-95168/5246 ATTACHMENT I Texas Utilities Electric RE'Y I S ION 0 PAGE 4 of 15 A Fire Protective Envelope protects electrical components from the eQ'ects of fire.
In doing sc, it vriQ reduce the inQow of energy into the system and maintain the internal temperature below maximum limits. These limits will ensure that the cable systems remain functional during a fire, and allow operators to maintain control of systems required for fire safe shutdown.
The addition of a Are . rotective Envelope on a cable system will not only protect the contained cable from elevated temperatures associated with a fire, but will impede the heat dissipation associated with cable operation. The evaluation described herein will yield aa accurate and realistic value for the ampacity deratiag of cables when a Fire Protective Envelope is iastaQed on the cable system.
This entire test prolpmn was performed in accordance with Texas Utilities Electric TEST PLAN, Rev. 4, which has been included in Appendix B. The specific details of this project wiQ be found in that document.
TEA ENCLOSURE The ampacity test enclosure was constructed of steel stud waQs and ceiling with a minunum of I in. of polystyrene insulatioa liaing the interior of the room. The overaQ dimensions of the test enclosure were 20 ft. x 18 &. x 8 ft. An entry door was provided in oae wall and an observation window was placed in an adjacent waQ. The waQ with the observation window was made to be removable to facilitate easier location of test articles. Four 1.5 kW heaters were disposed about the room to regu1ate ambient conditions. Two of the heaters were vaxiable from outside of the test enclosure via connection to standard laboratory variable transformers.
Located directly behind each heater was a 24 in. box fan to gently stir the air and more evenly distribute the heat. A total of nine thermocouples were suspended from the ceiling and positioned ia the horizontal plane of the test items, 12 in.
away Epsom various test items to monitor the ambient room temperatures. Two stanchions were erected to support the test articles. Each staachion consisted of a length of 2 in. square steel tubing supported at several points by an A-frame leg.
A length of 2 in. x 4 in. wood stud was aQixed to the top surface of each stanchion.
In the case of all but the 5 ia. conduit, the test article with the fire protective system installed was tested first. Once the system had attained. equilibrium and aQ final measurements h'ad been tatea, the fire protective barrier was removed from the system (in the case of the air drop assemblies and the cable tray
PTN-BFJH-96-005 Report No. 12340-94583,95165-95168/5246 ATTACHHENT I Texas Utilities Electric REV IS IQN 0 PAGE 5 of l5 assembly) or the instrumented cable was removed from the clad conduit and inserted into a similarly constructed, bare conduit.
THERMOCOUPUK Temperatures on the cable conductors within the conduit and air drop assemblies were measured with Type T, 24 gauge, Copper-Constantan electrically welded thermocouples formed from Copper and Constantan wires of special limits of error (&.5'C)," and covered with TeQon FEY insulation. Temperatures on the cable conductors within the cable tray assembly were measured with Type K, 24 gauge, Chromel-Alumel electrically welded thermocouples formed from Chromel and Alumel wires of "special limits of error (21.1'C)," and covered with braided fiberglass insulation. All thermocouple wire was calibrated to &.5'C.
DATAACQUXSZZXON SYSTEM The outputs-of the test article thermocouples and room control thermocouples were monitored by a data acquisition system consisting of a John Fluke Mfg. Co.
Model HELIOS I 2289A Computer Front End, and an Apple Computer Co.
Macintosh Classic microcomputer. The Computer Front End was connected to the RS422 Serial Interface Port of the Macintosh. The computer was prograxnmed in Microsoft BASIC to command the HELIOS unit to sample the data input lines, receive and convert data into a digital format, and to manipulate the data for display on screen, the hard copy printout, and saving to hard disk. The computer program determined, and displayed, the average temperatures at each of the three positions on each test article. The rate of change of temperature for the average of the thermocouples located in the center portion of the test article was.
then calculated. All individual data points and calculated values were saved on hard disk at one minute intervals. A record of individual location temperatures, maximum temperatures and rates of change of temperatures was printed at five minute intervals. All test data is presented in Appendix F: TEST DATA.
CONTROL SYSTEM The current Qow through the test articles was regulated using process control type devices. The available voltage for any test control circuit was 208 Vac single phase. A Silicon Controlled RectIfier (SCR) device (Halmar Robicon Group Model No. 140P-FK2-CL) was used to vaxy the voltage available to the primary side of a step-down transformer between 0 Vac and 208 Vac in proportion to a 4-20 mA control input. The test article was connected to the secondary side of the step-down transformer. A proportional-integral-derivative process controller (Honeywell Universal Digital Controller Model No. UDC 3002-0-000-1-00-XXXK) was responsible for generating the '4-20 mA signal fed to the SCR device, based on a voltage feedback loop. A current transforxner (Flex-Core Model No.58-151, 150:5 a "oJ~
0 Cy oRAxo
0 PTN-BFJH-96-005 Report Na. 12340-94583,95165-95168@5246 ATTACHHENT I Texas Utilities Electric REVISION 0 PAGE 6 of 15 or 76-102, 1000:5 ratio; input amps:output amps) was fitted to one lead of the test article to monitor the current flow through the conductor. The output of the current transformer was connected to a current transducer (Flex-Core Model No.
CT5-005A) with a mA to mV converter (Flex-Core Model No. LRB-10000) to produce a 0-10 Vdc signal proportional to 'a 0-150 A or 0-1000 A current span in the sample conductor. This 0-10 Vdc signal is used as the 'process variable" in the feedback loop to the controller. In essence, the above circuitry made up a constant-current device, insensitive to line voltage changes.
The current in aay given system was driven to a level high enough to bring the conductor to 90'C as quickly as possible by increasiag the'output signal of the process controller via keypad commands. As the conductor temperature approached 90'C, the current level was reduced aad the test article was given time to respond to current changes before another adjustment was made to the current. During this time period, the controller was turned to "automatic" control and the "process variable set point" (the voltage output from the current transformer that represents the current level at which the controller will maintain the system) was adjusted to the same value as the displayed process variable (the controller varies its output ia order the maintain the process variable at the level indicated by the set point).
This process of adjusting the controller output (and the control variab1e set point) and waiting for the system to stabilize (about 1/2 hour to about 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />, depending upon the nature of the system) was coatinued until the temperature parameters of the test article were within the specified limits. The coatroller was allowed to operate the system for a muumum of three hours. If, at the end of three hours, the system was still within the bounds of all specifications, a final current and voltage measurement were taken and the system was deemed .to be in equilibrium.
s All final current measurements were performed using ammeters suppHed and calibrated by Texas UtiTities Electric. These ammeter used were manufactured by James Biddle Co. and identified as Biddle Iastruments Digital Clamp-On RMS Volt-Ammeter, Cat. No. 278001 (TU Electric ID No. IC-1029 and IC-1030).
Measurements recorded for test items containing 3C/¹10 AWG of 3C/¹6 AWG cable were taken with the ammeter ID No. IC-1030. Current measurements recorded for test items containing 750 kCMil cable were taken with the ammeter ID No. IC-1029. Calibration documentation for these devices can be found i' Appeadix G: Quality Assurance.
t'y
~~A Po r+
0
- OpAgO
'eport No. 12340-94583,95165-95168@5246 PTW-BAH-96-005 Texas Utilities Electric AITACHHchT I REV IS ION 0 PAGE 7 of 15 1%B1PEAS (GENERAL)
The conduit materials used in the test were provided by Texas Utilities, and are representative of those installed at CPSES.
Cable tray materials used in this test were purchased by Omega Point Laboratories from B-Line Systems, Inc. (Cat. No. 248P0924144). The following table provides pertinent data on the cable tray material used:
ATXRIBUTE DMENSION Side rail thickness 0.048 in.
Run thickness 18 GA Run s acin 9 in. o.c.
Rung dimensions 1-5/8 in. w x 13/16 in. h x 3/8 in. le Cable tray straight sections consisted of ASTM A446, GR A, pre-galvanized steel, ASTM A525.
All test items (with the exception of the cable tray assembly) were constructed from materials extracted from TU Electric's Comanche Peak Steam electric Station stock material storage areas in accordance with existing site procedures.
Electrical cables used in this test (with the exception of the cable tray assembly) consisted of cables supplied by TU Electric and taken from CPSES inventory.
Cables used in these tests were as follows:
CBOSS-CABLE 8ECTIONAL FUNCXXON DESCKPIXON AREA (in )
W420 Power 3C/¹6 AWG 60Qv. 0980 0.754 Power 3C/¹10 A%G 60Qv. 0.617 0299 Power l/C 750 kCMil. 600v. 1.307 Power 3C/¹6 A%'G 600v. 0.750 '.442 The diameters and cross-sectional areas listed herein represent the Laboratory's average of ten measurements of each cable type.
~~A 0o 0
osa~o+
PTN-BFJM-96-005 Report No. 12340-94583,95165-95168/5246 Texas Utilities Electric ATTACHHENT I REVISION 0 PAGE 8 of 15 Thermo-Lag 330-1 Ma~tais Thermo-Lag materials were procured from Thermal Science, Inc. (TSI), St.
Louis, MO. The Thermo-Lag'aterials were extracted from CPSES stock and were representative of materials installed in the plant. Each one hour rated Thermo-Lag 330-1 V-Ribbed Panel is 1/2 in. thick (normal) x 48 in. wide x 78 in.
long, with stress skin monolith caQy adhered to the panel on one face. Each panel was received with 350 Topcoat factory applied. Each 330-1 Pre-Shaped Conduit Section is 36 in. long. Two thicknesses of conduit section materials were used, V2 in. thick (nominal) and 1/4 in. thick (nominal) "overlay" sections, both with stress skin monolithically adhered to the surface installed facing the protected conduit.
The 330-1 conduit materials were also received with 350 Topcoat factory applied.
Other materials supplied by TSI were 330-1 Trowel (bulk) Grade Subliming Compound (used to pre-caulk all joints 'and seams on the cable tray and conduit assemblies), 330-660 Flexi-Blanket Material used to wrap the cable air drop assemblies, 330-660 Trowel (bulk) Grade Material (used to pre-caulk all seams on the cable air drop assemblies), 330-69 Stress Skin Material (used to reinforce joints on the cable tray assembly) and 350 Topcoat (two part water-based mixture). All Thermo-Lag materials were measured, saw cut and installed onto the respective test assembly by Peak Seals crude personnel using approved CPSES drawings, procedures and specifications. Installations were inspected by GPSES-ceitified quality control inspectors.
Other MateriaLs Other commercial grade products used were: 1/2 in. wide x 0.020 in. thick, type 304 stainless steel rolled-edge banding straps with wing seals; 16 to 18 GA stirless steel tie wire; and, 0.010 in. s'tainless steel sheet metal.
Scheme SAC-1 The assembly consisted of a 3/4 in. conduit through which was pulled a single three conductor cable (W-026, 3C/410 AWG, 600V). The total cab1e length used for this test item was 60 ft. The three separate conductors within the cable were connected into a single series circuit. The current source was then connected to the two free cable ends. Two conduits were prepared for testing, one clad and one bare - for baseline testing.
Report No. ~94583,95165-9516845246 PTN-BFJH-96-005 Texas Utilities Electric ATTACHMENT 1 REVISION 0 PAGE 9 of 15 Scheme ¹AC4 The assembly consisted of a 2 in. conduit through wnich vras pulled a single three conductor cable (W-020, 3C/¹6 AWG, 600V). The total cable length used for this test item was 60 ft. The three separate conductors within the cable vrere connected into a single series circuit. The current source was then connected to the tvro free cable ends. Two conduits were prepared ror testing, one ciad and one bare - for base1iae testing.
Scheme ¹AC-5 The assembly consisted of a 5 in. conduit through vrhich was pulled four separate single conductor cables (W-008, 1/C 750 kCMil, 600V). The total cable leagth used for this test item was 88 ft. The four separate conductors were connected into a single series circuit. The current source vras then connected to the two free cable ends. Tvro coaduits were prepared for testing, one clad and one bare - for baseline testing.
Scheme ¹AA 1-1 The assembly consisted of a single three conductor cable (W-020, 3C/¹6 AWG, 600V) representing an air drop assembly. The total cable length used for this test item vras 60 ft. The three separate conductors within the cable were connected iato a single series circuit. The current source vras then connected to the two free cable ends. The cable was clad and allovred to cure. The material was then removed to perform the baseline testing.
The assembly consisted of three separate siagle conductor cables (W-008, 1/C 750 kCMil, 600V) representing an air drop assembly. The total cable length used for this test item was 88 ft. The three separate coaductors vrere connected into a single series circuit. The current source was then connected to the tvro free cable eads. The cable vras clad aad allowed to cure. The material vras then removed to perform the baseline testing.
Scheme OAT-1 r
The assembly consisted of a 24 in. wide 4 in. deep cable tray assembly into which was laid 126 passes of single three coaductor cable (3C/¹6 AWG, TC XHHW CDRS, 600 Volt). The total cable length used for this test item vras 1720 K The three separate conductors'withia the cable were connected into a single series circuit and the cuzrent source was then connected to the tvro free cable eads. The
~~A Do 0
r ORA<O+
PTN-BFJH-96-005 Report No. 12340-94583,95165-951685246 ATTACHHENT 1 Texas Utilities Electric REVISION 0 PAGE 10 of 15 cable tray assembly vras clad and allowed to cure. The material was then removed to perform the baseline testing.
The internal cross-sectional areas for the conduits are as follows:
CONDUITSIZE ACTUALCONDUIT CROSSBE TIONAL (INCEST) I33. (INCHES) AIUM(in2) 0.824 0.533 2.067 3.356 5.047 20.006 The usable cross-sectional area of the cable tray was (3 in. deep r 24 in. wide) 72 square inches.
The table below shows the cable types used in each test article, the number of each cable installed, the total cross-sectional area of each cable type and the percent of the total available area taken up by cable in each test article.
3/4 in. CONDUIT CEK)S&
CABLE SECXXONAL % OF TOTAL TYPE ALUM (in2) AEU<M W26 0299 I 56.10 2 in. CONDUIT CBOSS.
SECTIONAL % OF TOTAL ABER (in2) AIRE W%20 0.754 22.47 5 in. CONDUIT CBXkS-CA'BL'E NUMBER SECTXONAL % OF TOTAL PBESENI,'BEA (in>) ARE&
W-008 5.228 26.13
~GA DO r+
0 osA~o~
PTN-BFJM-96-005 Report: No. 12340-94583,95165-95168/5246 ATTACHMENT 1 Texas Utilities Electric REVISION 0 PAGE 11 of 15 24 IN. CABLE TRAY CROSS-SECTIONAL 9o OF TOTAL AREA (in2) AEU~M 3C/¹6 77.31 TEEZUYCOCOUPLE PLACEZHKKT 24 gauge, Type T, Copper-Constantan electrically welded thermocouples (Special Limits of Error: 0.5'C, purchased with lot traceability and calibration certifications) were attached in nine places within each conduit or air drop assembly, by slicing through the outer jacket of the cable (down to bare conductor) and placing the thermojunction in direct contact with the top surface of the cable conductor and covering the slit with a double wrap of glass Qber reinforced electrical tap'e (Glass Cloth Electrical Tape, Class "B" Insulation, 1/2 in. wide, 3M Corporation, Item No. 27) for a minimum distance of 3-1/2 inches. Thirty-nine 24 gauge, Type K, Chromel-Alumel electrically welded thermocouples (Special Limits of Error: 21.1'C, purchased with lot traceability) were siaMuly secured to the cables within the cable tray assembly. A representative sample of the thermocouple wire used in the cable tray test article was calibrated aRer the test procedure.
One thermocouple was located on each of the three conductors in each systexn (except the cable tray and 5 in. conduit having four conductors) at the mid-point of the assembly, and at both ends of the assembly (36 in. lefh and right of mid-point).
The 5 in. conduit having four conductors was similarly instrumented,. however, the fourth conductor had no thermocouples installed. The cable tray assembly was instrumented with a total of thirty-nine thermocouples (thirteen located at the mid-point of the cable tray, thirteen located 36 in. to the left and 36 in. to, the right of mid-point) located within the second and third layer of cables.
THERMhLAG INSTALLATIONHIGHLIGHTS Thermo-Lag materials were installed in accordance with the instructions contained in the CPSES Site Procedures referenced in Test Plan, Rev. 4. Short abstracts of the installation are included herein to clarify specific details.
Thermo-Lag 330-X Pre-Shaped ConduM Sections (Xf2 in. nom. thicknear)
This material was used to construct the 3/4 in., 2 in. and 5 in. diameter raceway design protective envelopes.
oA +0 0
0 Report No. 12340-94583,95165-95168+5246 PTN-BFJM-96-005 Texas Utilities Electric ATTACHHEN7 1 REY I S ION 0 PAGE 12 of 15 Thermo-Lag+ 330-1 Pre-Shaped Conduit Sections (I/4 in. nom. thickness)
This material was used as an overlay on the 3/4 in. and 2 in. diameter raceway design protective envelopes.
Thermo-Lag+ 330-1 U-ribbed Panels (I)2 in, nom. thickness)
This material was used to construct the cable tray protective envelope.
Thermo-Leg/'30-1 Subliming Trowel Grade Material This material was used to pre-caulk all joints, seams and upgraded areas between pre-shaped sections.
Thermo-L,ag 33&660E7exi-BLm~
This material was used to construct the cable air drop protective envelopes.
Thermo-Lag 33~ Sublimb~'.Pnuael Grade Material This material was used to pre-caulk all joints and seams between 330-660 Flexi-Blanket material and all joints of 330 Flexi-Blanket.
Application Methods Each rigid conduit assembly was clad with Thermo-Lag 330-1 V2 in. (nominal) thick Pre-Shaped Conduit Section Material. All joints and seams were pre-caulked with 330-1 Trowel Grade Material. The sections installed on the 5 in.
diameter conduit were secured using stainless steel banding material. The sections installed on the 3/4 in. and the 2 in. diameter conduits were secured using stainless steel tie wire. ARer being clad with 1/2 in. thick 330-1 Pre-Shaped Conduit Sections, V4 in. thick (nominal) Pre-Shaped Conduit Section ("overlay" )
Material was installed on the 3/4 in. and the 2 in. diameter conduits. All joints and seams were pre-cauiked with 330-1 Trowel Grade Material and then secured using stainless steel banding. Finally, Thermo-Lag 350 Topcoat was applied over areas where the 330-1 Trowel Grade Material had been applied following a 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> (mixumum cure time).
The entire cable tray system was clad with Thermo-Lag 330-1 V2 in. (nominal)
V-Ribbed Panel Material. To prevent sagging of the top panels, the cable tray was pre-banded using stainless steel banding. Al joints and seams of the protective envelope were pre-caulked with 330-1 Trowel Grade Material and secured with stainless steel bands spaced at 12 in, intervals.
~GA Do 0
C
~e o~a~o+
PTN-BFJM-96-005 Report No. 12340-94583,95165-95168,95246 ATTACHMENT 1 Texas Utilities Electric REVISION 0 PAGE 13 of 15 During construction of the cable tray protective envelope, several areas of the envelope were reinforced vrith combinations of stainless steel wire, Thermo-LaP 330-1 Trowel Grade Material and Thermo-Lago 330-69 Stress Skin vrhich was secured with staples. The areas reinforced included butt joints betvreen panels on the bottom surface of the envelope and the longitudinal seams where the top and bottom panels overlap panel pieces installed at the tray side rails.
The butt joints betvreen panels on the bottom surface were "stitched" with stainless steel tie wires on 5 in. centers. A thin layer of 330-1 Trowel Grade Material (approximately 3/16 in. thick) was aext applied extending 5 in. on each side of the butt joiats. Stress skin was cut and wrapped circumferentially around the envelope to overlap the butt joints by 5 ia. oa each side. The stress shin was worked into the trowel grade layer and secured ia place with staples and stainless steel tie wire. A skim coat of 330-1 Trowel Grade Material, approximately V16 in.
thick, was then applied over the stress skia and the tie vrires.
To reinforce the longitudinal seams at the side rails, a 3/16 in. thick layer of 330-1 Trovrel Grade Material vras applied over the panels installed at the side rails and extending 5 ia. tovrards the middle of the tray and both the top and bottom surfaces. Stress skin vras cut and formed into a squared, U-shaped configuration which vras placed over the sides and onto the top and bottom surfaces for a 5 in.
distance. The stress skin vras worked into the trovrel grade layer and secured in place with staples and stainless steel tie wire. A skim coat of 330-1 Trowel Grade Material, approximately V16 in. thick, was then applied over the stress skin and tie wires.
Finally, Thermo-Lag 350 Topcoat was applied over all areas where 330-1 Trowel Grade Material had been applied follovring a 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> (minimum) cure time.
Each cable air drop assembly was clad with three complete-wraps of Thermo-Lag 330-660 Flexi-Blanket Material. An overlap of 2 ia. - 4 in. was maintained for each wrap. The overlap area of each wrap was pre-caulked with Thermo-Lag 330-660 Trowel Grade Material and secured with stainless steel bands spaced on 6 in. centers. The overlap areas vrere positioned 180'rom one another.
The completed test specimens were placed in the Laboratory's test enclosure and the thermocouples connected to the data acquisition system and their outputs verified; The tests vrere conducted from March 2, 1993, to March 14, 1998, by Herbert W Stansberry II, project manager, with the follovring persons preseat at various times:
~oA Oo 0
r Cy
~
oeA~o~
0 Report No. ~~'4M3,961%-96168$ 6246 PTN- BF JH-96-005 ATTACHHENT 1 Texas Utilities Electric REVISION 0 PAGE 14 of 15 Renaldo Jeans USNRC Dick Wilson USNRC Bill Rodgers USNRC John White TU Electric Chester Pruett TU Electric (Fluor-Daniel Corporation)
Melvin Quick TU Electric (Stone &, Webster Engineering)
Kent Brown TVA Deggarg N. Priest Omega Point Laboratories, Inc.
Kerry Hitchcock Omega Point I aboratories, Inc.
Connie Humphry Omega Point Laboratories, Inc.
Laudencio Castanon Omega Point Laboratories, Inc.
EQU. EQU. EQU. ROOM CORRECTED VOLTAGE CURRENT TEMP TEMP CURRENT PERCENT TEST ITEM (VOLTS) (AMPS) ('C) ('C) (AMPS) D ERATING 3C/¹10 in 11.9 39.4 89.8 40,3 39.6 3/4" Conduit (base) 9.34 3C/¹10 in 11.0 36.0 89.4 39,3 35,9 3/4 Conduit (clad) 3C/¹6 in 2" Conduit 64.6 40.3 64.5 (base) 6.67 3C/¹6 in 2 Conduit 9.15 89.1 39.3 (clad) 3C/¹6 in Air Drop 10.9 94.0 89.9 39.5 93.6 (base) 212 3C/¹6 in Air Drop ,
8.12 74.0 90.9 40.5 73.8 (clad) 3C/¹6 in 24" Cable Tray 46.5 89.8 39.5 23.1 (base) 31.6 3C/¹6 in 24 Cable Tray 15.9 90.3 39.9 15.8 (clad)
~oa Do 0
r Cy oea~<~
PTN-BFJH-96-005 Report No. 12340-94583,95165-95168g5246 ATTACHHENT Texas Utilities Electric REVISION 0 PAGE 15 og 15 PS)
EQU. EQU. EQU. ROOM CORRECTED VOLTAGE CURRENT TEMP TEMP CURRENT PERCENT TEST ITEM (VOLTS) (AM ('C) ('C) (AMPS) DE RATING 750 kCMil in Air Drop 521 89.5 402 (ba" e) 31.8 750 kCMil in Air Drop 3.62 90.0 39.9 (clad) 4C 750 kCMil in 5 Conduit 2.19 89.4 402 (base) , 10.7 4/C 750 kCMil in 5 Conduit 2.08 90.0 402 510 (clad)
The equilibrium current values are single-point measurements performed after the system was at equilibrium and the change in current was very low. The Equ.
Temp (equilibrium conductor temperature at the hottest location), and the Room Temp are reported as 60 minute average values. The Corrected Current values are those calculated in accordance with P 848/D12 IEEE Standard Procedure for the Determination of the Ampacity Derating of Fire Protected Cables~, which corrects these current values to a room temperature of 40'C and a conductor.
temperature of 90'C.
Ta') x(a+ Tc)
-
(Tc Ta) x (u + Tc')
where I test current at equilibrium, amperes Tc'a'Tc'-
Tc hottest conductor temperature at center at equilibrium, 'C Ta measured enclosure ambient temperature, 'C I ~
normalized current, amperes normalized conductor temperature = 90'C normalized ambient temperature = 40'C 234.5 for copper .
~~A Po 0
Table 2 - Dlmenslons and weights of rigid steel conduit Customary inch-pound units Metric units Minimum Minimum weight of weight of ten unit ten unit Nominal lengths or trade Nominal Nominal lengths Length with Nominal Nominal Length with size of inside Outside wall without coupllngs Inside Outside wall conduit diameter diameter without coupllngs thickness coupling attached diameter diameter thickness coupling 'ttached In ln ln in ft and in Ib mm mm meters kg 3/8 0.493 0.675 0.091 9'11 -1/2" 51.5 12.5 17.1 2.31 3.04 23.36 1/2 0.632- 0.840 0.104 9'11 -1/4" 79.0 16.1 21.3 2.64 3.03 35.83 3/4 0.836 1.050 0.107 9'11 -1/4 105.0 21.2 26.7 2.72 3.03 47.63 1 1.063 1.315 0.126 9'11 153.0 27.0 33.4 3.20 3.02 69.40 1 -1/4 1.394 1.660 0.133 9'11 201.0 35.4 42.2 3.38 3.02 . 91.17 1 -1/2 1.624 1.900 0.138 9'11 249.0 41.2 48.3 3.51 3.02 112.95 2 2.083 2.375 0.146 9'11 332.0 52.9 60.3 3.71 3.02 150.60 2 -1/2 2.489 2.875 0.193 9'10 -1/2 527.0 63.2 73.0 4.90 3.01 239.05 3 3.090 3.500 0.205 9'10 -1/2 682.6 78.5 88.9 5.21 3.01 309.63 3 -1/2 3.570 4.000 0.215 9'10 -1/4 831.0 90.7 101.6 5.46 3.00 376.94 4 4.050 4.500 0.225 9'10 -1/4 972.3 102.9 114.3 5.72 3.00 441.04 5 5.073 5.563 0.245 9'10 1313.6 128.9 141.3 6.22 3.00 595.85 6 6.093 6.625 0.266 9'10" 1745.3 154.8 168.3 6.76 3.00 791.67 NOTE -Applicable toie~ ..ces:
Length: k 1/0 in (k 8.35 mm) (without coupling)
Outside I',ameter for tra.e sizes 3/8 in through 2 In: k 0.015 In (a 0.38 mm) for tr ide sizes 2-1/2 In through 4 ln: k 0.025 In (k 0.64 mm) for 'rade sizes 5 and 6 In:21%
N'.ll thickness: See 7.3. C) <
m I m~ C/l Am ll I
W lCl OI I
C)
NO Cll
PTN-BFJH-96-005 ATTACHHENT 3 EBASCO SERVICES INCORPORATED REVISION 0 PAGE I of 3
~P i
UAIu V M I Vii By 45 DATE 4 2V-VO REVISION 1 SHEET~ OF~
CHKD. BY DATE OFS NO.~ DEPT NO.~
CLIENT PROJECT SUBJECT 4
Conductor Single 3/c or Triplex Sing'le 3/c or Casubu;hu; Xrh>JJs 812 AWG 1.72 1.789 1.72 x 1.25 = 2.15 1. 789 x 1. 25 = 2.236 810 AWG 1.08 1.123 1.08 x 1.25 = 1.35 1. 123 x l. 25 1.404 88 AWG 0.679 0.706 0.679 x 1.25 = 0.849 0. 706 x 1. 25 = 0.883 N6 AWG 0.427 0.444 0.427 x 1.25 = 0.534 0.444 x 1.25 = 0.555 P4 AWG 0.269 0.280 0.269 x 1.25 ~ 0.336 0. 280 x 1. 25 = 0.350.
N2 AWG 0.169 0.176 0.169 x 1.25 = 0.211 0.176 x 1.25 = 0.220 N1/0 AWG 0.106 0.110 0.106 x 1.25 = 0.133 0.110 x 1.25 = 0.138 02/0 AWG 0.0843 0.0877 0.0843 x 1.25 = 0.105 0.877 x 1.25 = 0.110 04/0 AWG 0.0525 0.0546 0.0525 x 1.25. = 0.0656 0.0546 x 1.25 = 0.0683 8250 kcmil 0.0449 0.0467 0.0449 x 1.25 = 0.0561 0.0467 x 1.25 = 0.0584 8350 kcmil 0.0320 0.0333 0.0320 x 1.25 = 0.040 0.0333 x 1.25 = 0.0416 8500 kcmil 0.0222 0.0231 0.0222 x 1.25 = 0.0278 0.0231 x 1.25 = 0.0289 8750 kcmil 0.0148 0.0154 0.0148 x 1.25 = 0.0185 81000 kcmll 0.0111 0.0115 0.0111 x 1.25 = 0.0139 81250 kcmil 0.00888 0.00924 0.00888 x 1.25 = 0.0111 1099E/2
EBASCO SERVICES INCORPORATED PTN-BFJH-96-005 g
)
~d/
ATTACHHENT 3
/"" REVISION 0 CHKD. BX CLIENT DATE > 2f DATE~6Kq I>
Fo- REVISION 1 OFS NO. Q~~
PAGE 2 DE P of T NO. ~
3 PROJECT SUBJECT AC/DC AC Resistance at 90 C Conductor Resistance Ratio Single Conductor Hakim~
N12 AWG 1.0 1.0 2.15 x 1.0 = 2.15 2.15 x 1.0 = 2.15 Nlo AWG 1.0 1.0 1.35 x 1.0 = 1.35 1.35 x 1.0 = 1.35 N8 AWG 1.0 1.0 0.849x 1.0 ~ 0.849 0.849x 1.0 = 0.849 N6 AWG 1. 0'.0 1.0 0.534x 1.0 = 0.534 0.534x 1.0 = 0.534 N4 AWG 1.0 0.336x 1.0 = 0.336 0.336x 1.0 = 0.336 N2 AWG 1.0 1.01 0.2llx 1.0 ~ 0.211 0.211x 1.01= 0.213 Nl/0 AWG 1.001 1.02 0.133x1.001~ 0.133 0.133x 1.02= 0.136 N2lo AWG 1.001 1.03 0.105x1.001= 0.105 0.105x 1.03= 0.108 NOIO AWG 1.004 1.05 0.0656x1.004= 0.0659 0.0656x1.05= 0.0689 N250 kcmil 1.005 1.06 0.056lx1.005= 0.0564 0.0561xl.06= 0.0595 N350 kcmil 1.009 1.08 0.0400xl.009= 0.0404 0.0400xl.08= 0.0432
'N500 kcmil 1.018 1 ~ 13 0.0278xl.018=0.0283 0.0278x1.13= 0.0314 N750 kcmil 1.039 1.21 0.0185x1.039=0.0192 0.0185x1.21= 0.0224 N1000kcmi1 1.067 1.30 0.0139x1.067~0.0148 0.0139x1.3 ~ 0.0181 N1250kcmi1 1.102 1.41 0.0111x1.102=0.0122 0.011lx1.41= 0.0157 1099E/3
PTN-,BFJM-96-005 ATTACHMENT 3 EBAS<<SERVICES INCORPORATED Rf VISION 0 PAGE 3 of EC-096
. CHKD. BY DATE~M-Wu DATE~62/ qO REVISION 1 OFS NO.Q~~
S8FET 4 DEPT OF~
No.~
CLIENT PROJECT SUBJECT 0
(See Table 7.2.2.2a for ac/dc resistance ratios)
AC Resistance at 90 C Conductor 3/C or Triplex Uazm~
812 AWG 2.236 x 1.0 = 2.236 2.236 x 1.0 = 2.236 010 AWG 1.404 x 1.0 = 1.404 1.404 x 1.0 = 1.404 88'WG 0.883 x 1.0 = 0.883 0.883 x 1.0 = 0.883 86 AWG 0.555 x 1.0 = 0.555 0.555 x 1.0 = 0.555 t4 AWG 0.350 x 1.0 = 0.350 0.350 x 1.0 = 0.350-82 AWG 0.220 x 1.0 = 0.220 0.220 x 1.01= 0.222 81/0 AWG 0.138 x 1.OOl=O.138 0.138 x 1.02= 0.141 82/0 AWG 0.110 x 1.001=0.110 0.11'0 x 1.03= 0.113 84/0 AWG 0.0683x 1.004=0.0686 0.0683x 1.05= 0.0720 8250 kcmil 0.0584x 1.005~0.0587 0.0584x 1.06= 0.0619 8350 kcmil 0.0416x 1.009=0.0420 0.0416x 1.08= 0.0449 8500 kcmil 0.0289x 1.018=0.0294 0.0289x 1.13= 0.0327 1099E/4
1N C. PTN-BFJH-96-005 ATTACHHENT 4 APPROVED FIRE BARRIERS FOR REVISION PAGE I of 0
2 THE biUCLEAR INDUSTRY therma-hg'30-1 F IRE BARRIER MATERIAl. PROPERTIES This brochure presents the major properties of AMPACITY DERATING THFRMO-LAG in interest for nuclear generating Ampacity derating tests performed in accordance plant application. For additional data not with IPCEA Publication Number P-54-440 consult TSI. 'resented.
(Second Edition) (to determine cable base ampacity) and NEMA Publication No.
WC51-1975. The following results were obtained RADIATION RESISTANCE (for 40 percent loading):
2.12 x 1P rads total 40 year integrated dose One-Hour THERMO-LAG Barriers After irradiation no degradation in fire resistive Tray 12.5 percent derating properties Conduit 6.8 percent derating Three-Hour THERMO-LAG Barriers FIRE PROTECTIVE FEATURES ASTM E-84 Testing for THERMO-LAG 330-1 Flame Spread Rating ~ Tray Conduit 17 percent derating 10.9 percent derating Fuel Contributed Rating
- Smoke Developed Rating
5 0 ..
15 ASTM E-84 Testing for THERMO-LAG Primer MECHANICAL(PHYSICAL) PROPORTIES Flame Spread Rating 0 Density wet 10.5 Ibs/gallon Fuel Contributed Rating 0 Density dry 75~3 Ibs/tP Smoke Developed Rating 5 Dry Weight 1/2 inch thickness ASTM E-84 Testing for. THERMO-LAG 350-2P (one-hour rated) ~ 3.25 Ib/ftz Topcoat Dry Weight inch thickness 1
(three-hour rated) = 6.5 Ib/fthm Flame Spread Rating Water based Fuel Contributed Rating Smoke Developed Rating
5 0 Tensile strength p5'F) 1100 800 PSI 0 Shear strength p5'F) PSI One-hour Flexural stitfness (75'F) 85 KSI and .htee-hour fire endurance test in accordance with ASTM E-119, and Flexural strength p5')
2200 PSI ANI/MAERPtest "ANI/MAERP Standard Fire Bond strength p5') 57570 KSIPSI
.
Endurance Test Method to Qualify a Protective initial Modulus ~>~'F)
Envelope for Class 1E Electrical Circuits".
Thermal Conductivity (Unfired, full cured) 0.1 Btu/hr tt.~ F/
1/2 Inch THERMO-LAG rated one hour 1 Inch THERMO-LAG rated three hours
~
. , ASTM E-119 hose stream test on electrical SEISMIC PROPORTY trays and conduit for one and three hour rated THERMO-LAG has been qualified by static THERMO-LAG (2-1/2 minute hose stream analysis for a very conservative loading. A value application) of 7.5g horizontal, and 6.0g vertical acceleration.
ASTM E-119 fire tests for structural steel, ~
combined biaxially was used for the analysis.
hangers to determine required THERMO-LAG These values bound most nuclear generating thickness for one and three nour rating plant seismic criteria.
t'bove
~
'torage Conaitions Non-toxic free 32'F and below 100'F'sbestoes High humidi;y Industrial atrnospnere (COr SO>
Salt spray mix)
Interior Environmental Conditions C HEMICAL RESISTANCE OF THERMO-LAG 330-1 High humidity COz SO> atmosphere mix Water Sulfuric acid 10 percent solution Chlorine Hydrochloric acid 10 percent solution Results: Service life of at least 40 years Sodium hydroxide 10 percent solution Sodium chloride 5 percent solution PTN-BFJM-96-005 Acetic acid Kerosene ATTACHMENT REVISION 4
Anhydrous Ammonia of 0
LNG PAGE 2 2 LPG Methanol CHEMICAL RESISTANCE OF THERMO-LAG 350-2P TOPCOAT Frequent Contact Alkali solutions Salt solutions Alcohols Aliphatic hydrocarbons Aromatic hydrocarbons Occasional Contact Fresh water Waste water Mineral oils Vegetable oils Organic acids Mineral acid s
Oxidizing Ketones agents
.
260 Si...,,
Br snnon Ave Sc. Louis, Mo. 631 39
~ t31 4) 352 8422 s Telex: 44 2384
~ Telex: 20-9901
PTN-BFJH-96-005 ATTACHHENT 1 REVISION 0 PAGE 1 of 15 AMPACITY DEBATING OF FIRE PROTECT'ED CABLES Pmject No. 12340-94583,95165-95168/5246 ELECTRICAL TEST TO DETERMINE THE AMPACITYDERATING OF A PROTECTIVE ENVELOPE FOR CLASS 1E ELECTRICAL CIRCUITS March 19, 1993 Prepared For.
TU Electric COAGQlCHE PEAK STEAM ELECTRIC STATION P.O. Box 1002 Glen Rose, Texas 76043-1002 E..'REGE)YED DGT 2 0 )s93
~gA ~o 0
- oeATOO
PTN-BFJH-96-005 Repo*Nc 12340-94583,95165-95168/5246 ATTACHNEMT I Texas Utilities "Electric REV IS IOH 0 PAGE 2 of 15 Three conduit assemblies, two air drop assemblies, and one cable tray asseinbly, clad with Thermo-Lag materials as described herein, were evaluated in accordance with the Texas Utilities Electric TEST PLAN, Rev. 4, yielding the following ampacity derating values:
PERCENT TEST ITEM DERATING 3C/¹10 in 3/4" Conduit 9,34 3C/¹6 in 2" Conduit 6.6?
3C/¹6 in Air Dro 24" Cable Tra 3L6 750 kCMil in Air Dro 31.8 4/C 750 kCMilin 5" Conduit) 10.7 The details, procedures and observations reported herein are correct and true within the hmits of sound engineering practice. All specimens and test sample assemblies were produced, installed and tested under the surveillance of either Texas Utilities'r the testing laboratory's Quality Assurance Program. This report describes the ana1ysis of distinct assemb1ies and includes descriptions of the test procedure followed, the assemblies tested, and all results obtained. All test data are on BIe and remain available for review by authorized persons.
Herbert W. Stansberxy II Date Project Manager Constance A. Humphrey Manager, QA Dept.
Deggary President
¹ Priest Date
~>4 "o 0
oea~o+
0 0
0
PTN-BFJN-96-005 Report No. ~94583,95165-95168@&?A6 Texas Utilities Electric ATTACHMENT REVISION PAGE 3 o~ I~
TABLE OF CONTENTS INTRODUCTION 1
'HMT PROCEDURE 1 Test Enclosure 1 Thermo couples 2 Data Acquisition system 2 Current Control System 2
- Final Current Measurements 3 TEST ASSEMBLY 4 Test Items (General) 4 Test Items 5 Electrical Cables 7 Thermocouple Placement 8 Thermo-Lag Installation Highlights 8
'H<DT RESULTS 1D APPENDICES Appendix A: CONSTRUCTION DRAWINGS i3 Appendix B: TEST PLAN 38 Appendix C: THERMOCOUPLE LOCATIONS 25 Appendix D: TABULARTEST DATA 32 Appendix E: QUALITYASSUEVLÃCE 382 Appendix F: PHOTOGRAPHS 781 Appendix G: THERMO-LAG INSTALLATIONDETAILS 802 Last Page of Document 8%
~A OO 0
4y
~e eAt<
PT¹-8FJH-96-005 Report No. 12340-94583,95165-95168/5246 ATTACHHENT 1 Texas Utilities Electric REV IS IO¹ 0 PAGE 4 of 15 A Fire Protective Envelope protects electrical components from the eG'ects of fire.
In doing so, it will reduce the inQow of energy into the system and maintain the internal temperature below maximum limits. These limits will ensure that the cable systems remain functional during a fire, and allow operators to maintain control of systems required for fire safe shutdown..
The addition of a Fire Protective Envelope on a cable system will not only protect the contained cable from elevated temperatures associated with a fire, but will impede the heat dissipation associated with cable operation. The evaluation described herein will yield an accurate and realistic value for the ampacity derating of cables when a Fire Protective Envelope is'instaQed on the cable system.
This entire test program was performed in accordance with Texas Utilities Electric TEST PLAN, Rev. 4, which has been included in Appendix B. The specific details of this project will be found in that document.
The ampacity test enclosure was constructed of steel stud walls and ceiling with a muiimum of 1 in. of polystyrene insulation lining the interior of the room. The overaQ dimensions of the test enclosure were 20 ft. x 18 R. x 8 R. An entry door was provided in one wall and an observation window was placed in an adjacent waQ. The waQ with the observation window was made to be removable to facilitate easier location of test articles. Four 1.5 RW heaters were disposed about the room to regulate ambient conditions. Two of the heaters were variable from outside of the test enclosure via connection to standard laboratory variable transformers.
Located directly behind each heater was a 24 in. box fan to gently stir the air and more evenly distribute the heat. A total of nine thermocouples were suspended from the ceiling and positioned in the horizontal plane of the test items, 12 in.
away from various test items to monitor the ambient room temperatures. Two stanchions were erected to support the test articles. Each stanchion consisted of a length of 2 in. square steel tubing supported at several points by an A-frame leg.
A length of 2 in. x 4 in. wood stud was afBxed to,the top surface of each stanchion.
In the case of all but the 5 in. conduit, the test article with the fire protective system installed was tested first. Once the system had attained equilibrium and all final measurements had been taken, the fire protective barrier was removed from the system (in the case of the air drop assemblies and the cable tray
~oA Ao r+
0 ~4 Cg o~a~o+
PTN-BFJH-96-005 Report No. 12340-94583,95165-95168@5246 ATTACHMENT I Texas Utilities Electric REVISION 0 PAGE 5 of 15 assembly) or the instrumented cable was removed from the clad conduit and inserted into a similarly constructed, bare conduit.
TEGWKOCOUPUH Temperatures on the cable conductors within the conduit and air drop assemblies were measured with Type T, 24 gauge, Copper-Constantan electrically welded thermocouples formed from Copper and Constantan wires of "special limits of error (M.5'C)," and covered with TeQon FEY insulation. Temperatures on the cable conductors within the cable tray assembly were measured with Type K, 24 ga'uge, Chromel-Alumel electrically welded thermocouples formed from Chromel and Alumel wires of "special limits of error (%1.1'C)," and covered with braided fiberglass insulation. All thermocouple wire was calibrated to &.5 C.
DATAACQUISXHON SYSTEM The outputs-of the test article thermocouples and room control thermocouples were monitored by a data acquisition system consisting of a John Fluke Mfg. Co.
Model HELIOS I 2289A Computer Front End, and an Apple Computer Co.
Macintosh Classic microcomputer. The Computer Front End was connected to the RS422 Serial Interface Port of the Macintosh. The computer was programmed in MicrosoR BASIC to command the HELIOS unit to sample the data input lines, receive and convert data into a digital format, and to manipulate the data for display on screen, the hard copy printout, and saving to hard disk. The computer program determined, and displayed, the average temperatures at each of the three positions on each test article. The rate of change of temperature for the average of the thexmocouples located in the center portion of the test article was then calculated. All individual data points and calculated values were saved on hard disk at one minute intervals. A record of individual location temperatures, zmuamum temperatures and rates of change of temperatures was printed at Gve minute intervals. Alltest data is presented in Appendix F: TEST DATA.
CORZROL SYBZESX The current Qow through the test articles was regulated using process control type devices. The available voltage for any test control circuit was 208 Vac single phase. A Silicon Controlled=Rectifier (SCR) device (Ha1mar Robicon Group Model No. 140P-FK2-CL) was used to vary the voltage available to the primary side of a step-down transformer between 0 Vac and 208 Vac in proportion to a 4-20 mA control input. The test article was connected to the secondary side of the step-down transformer. A proportional-integral-derivative process controller (Honeywell Universal Digital ControQer Model No. UDC 3002-0-000-1-00-ZQZ) was responsible for generating the 4-20 mA signal fed to the SCR device, based on a voltage feedback loop. A current transformer (Flex-Core Model No.58-151, 150:5
~~A Ag r+
0
- 07 OATO
PTN-BFJH-96-005 Report No. 12340-94583,95165-95168/5246 ATTACHHENT I Texas Utilities Electric RE VIS ION 0 PAGE 6 of 15 or 76-102, 1000:5 ratio; input amps:output amps) was fitted to one lead of the test article to monitor the current flow'hrough the conductor. The output of the current transformer was connected to a current transducer (Flex-Core Model No.
CT5-005A) with a mA to mV converter (Flex-Core Model No. LRB-10000) to produce a 0-10 Vdc signal proportional to a 0-150 A or 0-1000 A current span in the sample conductor. This 0-10 Vdc signal is used as the "process variable" in the feedback loop to the controller. 'In essence, the above circuitry made up a constant-curx'ent device, insensitive to line voltage changes.
The current in any given system was driven to a level high enough to bring the conductor to 90'G as quickly as possible by increasing the'output signal of the process controller via keypad commands. As the conductor temperature approached 90'C, the current level was reduced and the test article was given time to respond to current changes before another adjustment was made to the During this time period, the controller was turned to "automatic" control 'urrent.
and the "process variable set point" (the voltage output from the current transformer that represents the current level at which the controller will maintain the system) was adjusted to the same value as the displayed process variable (the controller varies its output in order the maintain the process variable at the level indicated by the set point).
This process of adjusting the controller output (and the control variable set point) and waiting for the system to stabilize (about 1/2 hour to about 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />, depending upon the nature of the system) was continued until the temperature parameters of the test article were within the specified limits. The controller was allowed to operate the system for a minimum of three hours. If, at the end of three hours, the system was still within the bounds of all specifications, a final current and voltage measurement were taken and the system was deemed .to be in equilibrium.
All final current measurements were performed using ammeters supplied and calibrated by Texas Utilities Electric. These ammeter used were manufactured by James Biddle Co. and identified as Biddle Instruments Digital Clamp-On RMS Volt-Aauneter, Cat. No. 278001 (TU Electric ID No. IC-1029 and IC-1030).
Measurements recorded for test items containing 3C/¹10 AWG of 3C/¹6 AWG cable were taken with the ammeter ID No. IC-1030. Current measurements recorded for test items containing 750 kCMil cable were taken with the ammeter ID No. IC-1029. Calibration documentation for these devices can be found in Appendix G: Quality Assurance.
Ops 0+
Repo*Na 12340-94583,95165-95168/5246 PTN-BF JH-96-006 Texas Utilities Electric ATTACHHENT I REVISION 0 PAGE 7 of 15 xeEZ IXZ2tB (GENEtIALl The conduit materials used in the test were provided by Texas Utilities, and are representative of those installed, at CPSES.
Cable tray materials used in this test were purchased by Omega 'Point Laboratories from B-Line Systems, Inc. (Cat. No. 248P0924144). The following table provides pertinent data on the cable tray material used:
DIMENSION Side rail thickness 0.048 in.
Run thickness 18 GA Run s acin 9 in. o.c.
Rung dimensions 1-5/8 in. w x 13/16 in. hx 3/8 in. le Cable tray straight sections consisted of ASTM A446, GR A, pre-galvanized steel, ASTM A525.
AH test items (with the exception of the cable tray assembly) were constructed from materials extracted from TU Electric's Comanche Peak Steam Electric Station stock material storage areas in accordance with existing site procedures.
Electrical cables used in this test (with the exception of the cable tray assembly) consisted of cables supplied by TU Electric and taken from CPSES inventory.
Cables used, in these tests were as follows:
CK538S.
CAIKZ CABLE SECTIONAL TYPE FUNCTION DESCMPZIDN AREA (in?)
%420 Power 3C/¹6 AWG 600v.
W426 Power 3C/¹10 AWG 600v. 0.617 0299 W408 Power l/C 750 kCMil. 600v. 1307 Power 3C/¹6 AWG 600v. 0.750 '.442 The diameters and cross-sectional areas listed herein represent the Laboratory's average of ten measurements of each cable type.
PTN-BFJH-96-005 Report NL 12340-94583,95165-95168/5246 Texas Utilities Electric ATTACHHENT I REVISION 0 PAGE 8 of 15 Thermo-Lag 330-1 Matexials Thermo-Lag materials were procured from Thermal Science, Inc. (TSI), St.
Louis, MO. The Thermo-Lag materials were extracted from CPSES stock and were representative of materials installed in the plant. Each one hour rated Thermo-Lag 330-1 7-Ribbed Panel is 1/2 in. thick (nominal) x 48 in. wide x 78 in.
long, with stress skin moaolithim~Jy adhered to the pand on one face. Hach panel was received with 350 Topcoat factory applied. Each 330-1 Pre-Shaped Conduit Section is 36 in. long. Two thicknesses of conduit section materials were used, V2 in. thick (nomixml) and 1/4 in. thick (nominal) overlay" sections, both with stress skin monolithically adhered to the surface installed facing the protected conduit.
The 330-1 conduit materials were also received with 350 Topcoat factory applied.
Other materials supplied by TSI were 330-1 Trowel (bulk) Grade Subliming Compound (used to pre-caulk all joints and seams on the cable tray and conduit assemblies), 330-660 Flexi-Blanket Material used to wrap the cable air drop assemblies, 330-660 Trowel (bulk) Grade Material (used to pre~ulk all seams on the cable air drop assemblies), 330-69 Stress Skin Material (used to reinforce joints on the cable tray assembly) and 350 Topcoat (two part water-based mixture). All Thermo-Lag materials were measured, saw cut.and installed onto the respective test assembly by Peak Seals craS personnel using approved CPSES drawings, procedures and speci6cations. InstaQations were inspected by CPSES-certiGed quality control inspectors, Other Materials Other commercial grade products used were: V2 in. vride x 0.020 in. thick, type 304 stainless steel rolled-edge banding straps with wing seals; 16 to 18 GA stainless steel tie wire; and, 0.010 in. stainless steel sheet metal.
Scheme ¹AC-I The assembly consisted of a 3/4 in. conduit through which was pulled a single three conductor cable (W-026, 3C/¹10 AWG, 600V). The total cable length used for this test item was 60 ft. The three separate conductors within the cable were connected into a single series circuit. The current source was then connected to the two free cable ends. Two conduits were prepared for testing, one clad and one bare - for baseline testing.
~pa 04
~L 4lrar4+
PTN-BFJM-96-PP5 Report No. 12340-94583,95165-9516845246 Texas Utilities Electric ATTACHHENT REVISION 0 PAGE 9 of I5 Scheme ¹AC4 The assembly consisted of a 2 in. conduit through which was pulled a single three conductor cable (W-020, 3C/¹6 AWG, 600V}. The total cable length used for this test item was 60 ft. The three separate conductors within the cable were connected into a single series circuit. The current source was then connected to the two free cable ends. Two conduits were prepared for testing, one clad and one bare - for baseline testing.
Scheme ¹AC-5 The assembly consisted of a 5 in. conduit through which was pulled four separate single conductor cables (W-008, VC 750 RCMil, 600V}. The total cable length used for this test item was 88 ft. The four separate conductors were connected into a single series circuit. The current source was then connected to the two i'ree cable ends. Two conduits were prepared for testing, one clad and one hare - for baseline testing.
Scheme ¹AA 1-1 The assembly consisted of a single three conductor cable (W-020, 3C/¹6 AWG, 600V} representing an air drop assembly. The total cable length used for this test item was 60 ft. The three separate conductors within the cable were connected into a single series circuit. The current source was then connected to the two kee cable ends. The cable was clad and allowed to cure. The material was then removed to perform the baseline testing.
Scheme ¹AA4-2 The assembly consisted of three separate single conductor cables (W-008, VC 750 kCMil, 600V) representing an air drop assembly. The total cable length used for this test item was 88'A. The three separate conductors were connected into a single series circuit. The numnt source was then connected to the two free cable ends. The cable was clad and allowed to cure. The material was then removed to perform the baseline testing.
Scheme ¹AT-1 r
The assembly consisted of a 24 in. wide 4 in. deep cable tray assembly into which was laid 126 passes of single three conductor cable (3C/¹6 AWG, TC XHHW CDRS, 600 Volt}. The total cable length used for this test item was 1720 ft. The three separate conductors within the cable were connected into a single series circuit and the current source was then connected to the two free cable ends. The
PTN-BFJH-96-005 Report No. 12340-94583,95165-9516S$ 5246 'ATTACHMENT 1 Texas Utilities Electric REVISION 0 PAGE 10 of 15 cable tray assembly, was clad and allowed to cure. The material was then removed to perform the baseline testing.
The internal cross-sectional areas for the conduits are as follows:
CONDUITSIZZ ACTUALCONDUIT CROSSSEGTIONAL (INCH') LD. (INCHES) AIKA(hP) 0824 0.533 3.356 5.047 20.006 The usable cross-sectional area of the cable tray was (3 in. deep x 24 in. wide) 72 square inches.
The table below shows the cable types used in each test article, the number of each cable installed, the total cross-sectional area of each cable type and the percent of the total available area taken up by cable in each test article.
3/4 in. CONDUIT CROSS.
NUMBHL SECXXONAL % OF Tm'AL PRESEKZ AREA (in2) A%%A W%26 56.10 2 in. CONDUIT CRC)SS-CAXKZ NUMBI<2k SECTIONAL % OF TOTAL TYPE PBESENX'REA (in2) Mu&
W20 0.754 22.47 5 in. CONDUIT CROSS NUMBI<22 SECTIONAL % QF TOTAL PIKS EKE ARFA (hP) AXu<M W408 26.13 a~o
PTN-BFJM-96-005 Report No. 12340-94583,95165-95168/5246 ATTACHMENT 1 Texas Utilities Electric REVISION 0 PAGE 11 of 15 24 IN. CABLE TRAY GROS&
CABLE NUMBER SECTIONAL 9o OF TOTAL TYPE PK~~ÃZ AREA (ixl2) AMUk 3C/ee 77.31 TEG<2LMOCOUPLE PLACEIHKÃZ 24 gauge, Type T, Copper-Constantan electrically welded thermocouples (Special Limits of Error: 0.5 C, purchased with lot traceability and calibration certifications) were attached in nine places within each conduit or air drop assembly, by slicing through the outer jacket of the cable (down to bare conductor) and placing the thermojunction in direct contact with the top surface of the cable conductor and covering the slit with a double wrap of glass fiber reinforced electrical tape (Glass Cloth Electrical Tape, Class "B" Insulation, V2 in. wide, 3M Corporation, Item No. 27) for a mixdmum distance of 3-1/2 inches. Thirty-nine 24 gauge, Type K, Chromel-Alumel electrically welded thermocouples (Special Limits of Error: kl.l C, purchased with lot traceability) were similarly secured to the cables within the cable tray assembly. A representative sample of the thermocouple wire used in the cable tray test article was calibrated after the test procedure.
One thermocouple was located on each of the three conductors in each system (except the cable tray and 5 in. conduit having four conductors) at the mid-point of the assembly, and at both ends of the assembly (36 in. leR and right of mid-point).
The 5 in. conduit having four conductors was similarly instrumented, however, the fourth conductor had no thermocouples installed. The cable tray assembly was instrumented with a total of thirty-nine thermocouples (thirteen located at the mid-point of the cable tray, thirteen located 36 in. to the ldt and 36 in. to the right of mid-point) located within the second and third layer of cables.
TEEZMO-LAG INSTALLATIONHIGHLIGHTS Thermo-Lag materials were installed in accordance with the instructions contained in the CPSES Site Procedures referenced in Test Plan, Rev. 4. Short abstracts of the instaOation are included herein to clarify speci6c details.
Conduit Sections (LfP in. nonL thickness)
~ ~
This material was used to construct the 3/4 in., 2 in. and 5 in. diameter raceway
~
design protective envelopes.
yA >0 0
- L
~,'
f
Report No. 12340-94583,95165-95168,95246 PTN-BFJN-96 pp5 Texas Utilities Electric ATTACHHENT REVISION p PAGE 12 of l5 Thermo-Lag/'30-1 Pre&haped Conduit Sections fl/4 in. nom. thickness)
This material was used as an overlay on the 3/4 in. and 2 in. diameter raceway design protective envelopes.
Thermo-Lag 330-1 V-ribbed Panels (I/2 in, nom. thickness)
This material was used to construct the cable tray protective envelope.
Thermo-Lag 88M Sublinung Zmuel Grade Material This material was used to pre-caulk all joints, seams and upgraded areas between pre-shaped sections.
Thermo-L ag 83&869Ehmi-Blanket This material was used to construct the cable air drop protective envelopes.
Thermo-Lag 8804N SubHnur~ Tmceel Grade Material This material was used to pr~ulk all joints and seams between 330-660 Flexi-Blanket material and all joints of 330 Flexi-Blanket.
Application Methods Each rigid conduit assembly was clad with Thermo-Lag 330-1 V2 in. (nominal) thick Pre-Shaped Conduit Section Material. All joints and seams were pre-caulked with 330-1 Trowel Grade Material. The sections installed on the 5 in.
diameter conduit were secured using stainless steel banding material. The sections installed on the 3/4 in. and the 2 in. diameter conduits were secured using stainless steel tie wire. AGE being clad with V2 in. thick 330-1 P~haped Conduit Sections, 1/4 in. thick (nominal) Pre-Shaped Conduit Section ("overlay" )
Material was instaQed on the 3/4 in. and the 2 in. diameter conduits. Alljoints and seams were pre-caulked with 330-1 Trowel Grade Material and then secured using stainless steel banding. Finally, Thermo-Lag 350 Topcoat was applied over areas where the 330-1 Trowel Grade Material had been applied following a 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> (annimum cure time).
The entire cable tray system was clad with Thermo-Lag 330-1 1/2 in. (nominal)
V-Ribbed Panel Material. To prevent sagging of the top panels, the cable tray was pre-banded using stainless steel banding. Al joints and seams of the protective envelope were pre-caulked with 330-1 Trowel Grade Material and secured with stainless steel bands spaced at 12 in, intervals.
a~o 45 oea~o~
PTN-BFJM-96-005 Report No. 12340-94583,95165-95168,95246 ATTACHMENT 1 Texas Utilities Electric REVISION 0 PAGE 13 of 15 During construction of the cable tray protective envelope, several areas of the envelope vrere reinforced with combinations of stainless steel wire, Thermo-Lag 330-1 Trowel Grade Material and Thermo-Lag 330-69 Stress Skin which vras secured vrith staples. The areas reinforced included butt joints between panels on the bottom surface of the envelope and the longitudinal seams where the top and bottom panels overlap panel pieces installed at the tray side rails.
The butt joints between panels on the bottom surface vrere "stitched" with stainless steel tie wires on 5 in. centers. A thin layer of 330-1 Trowel Grade Material (approximately 3/16 in. thick) was next applied extending 5 in. on each side of the butt joints. Stress shin vras cut and vrrapped circumferentially around the envelope to overlap the butt joints by 5 in. on each side. The stress skin was worked into the trowel grade layer and secured in place with staples and stainless steel tie wire. A shim coat of 330-1 Trowel Grade Material, approximately V16 in.
thick, vras then applied over the stress skin and the tie vrires.
To reinforce the longitudinal seams at the side rails, a 3/16 in. thick layer of 330-1 Trowel Grade Material vras applied over the panels instaQed at the side rails and extending 5 in. tovrards the middle of the tray and both the top and bottom surfaces. Stress skin was cut and formed into a squared, U-shaped con6guration which was placed over the sides and onto the top and bottom surfaces for a 5 in.
distance. The stress shin was worked into the trowel grade layer and secured in place with staples and stainless steel tie vrire. A shim coat of 330-1 Trowel Grade Material, approximately V16 in. thick, vras then applied over the stress skin and tie vrires.
Finally, Thermo-Lag 350 Topcoat was applied over all areas vrhere 330-1 Trovrel Grade Material had been applied foQovring a 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> (minimum) cure time.
Each cable air drop assembly vras clad vrith three complete'-wraps of Thermo-Lag 330-660 Flexi-Blanket Material. An overlap of 2 in. - 4 in. was maintained for each wrap. The overlap area of each wrap vras pre-caulked with Thermo-Lag 330460 Trowel Grade Material and secured with stainless steel bands spaced on 6 in. centers. The overlap areas vrere positioned 180'om one another.
The completed test specimens vrere placed in the Laboratory's test enclosure and the thermocouples connected to the data acquisition system and their outputs veriGed. The tests vrere conducted from March 2, 1993, to March 14, 1993, by Herbert W. Stansberry II, project manager, vrith the foQovring persons present at various times:
~o A Ao.
0
- 4eato
PTN- BF JM-96-005 Report No. 12340-94583,95165-95168/5246 ATTACHMENT 1 Texas Utilities Electric REV IS ION 0 PAGE 14 of 15 Renaldo Jeakins USNRC Dick Wilson USNRC Bill Rodgers USNRC John White TU Electric Chester Pruett TU Electric (Fluor-Daniel Corporation)
Melvin Quick TU Electric (Stone & Webster Engineering)
Kent Broma Deggary ¹ Kerry Hitchcock Priest TVA Omega Omega Point Point Laboratories, Laboratories, Iac.
Inc.
Connie Humphry Omega Point Laboratories, Iac.
Laudeacio Castanon Omega Poiat Laboratories, Iac.
EQU. EQU. EQU. ROOM CORRECTED VOLTAGE CURRENT TEMP TEMP 'URRENT PERCENT TEST ITEM (VOLTS) (AMPS) ('C) ('C) (AMPS) DERATING 3C/¹10 in 11.9 39.4 89.8 40.3 39.6 3/4" Conduit (base) 9.34 3C/¹10 Ul 11.0 36.0 89.4 39.3 35.9 3/4 Conduit (clad) 3C/¹6 in 2 Conduit 9.96 90.5 40.3 64.5 (base) 3C/¹6 in 2 Conduit 9.15 89.1 39.3 (clad) 3C/¹6 in Air Drop 10.9 94.0 89.9 39.5 93.6 (base) 212 3C/¹6 in Air Drop 8.12 74.0 90.9 40.5 73.8 (clad) 3C/¹6 in 24" Cable Tray 46,5 39.5 23.1 89.8 (base) 31.6 3C/¹6 in 24" Cable Tray 15.9 90.3 39.9 15.8 (clad)
PTN-BFJH-96-005 Report No. 12340-94583,95165-9516845246 ATTACHMENT 1 Texas Utilities Electric REVISION 0 PAGE 15 of 15 EQU. EQU. EQU. ROOM CORRECTED VOLTAGE CURRENT TEMP TEMP CURRENT PERCENT TEST ITEM , (VOLTS) (AMPS) ('C) ('C) (AM PS) DERATING 750 kCMil in Air Drop 521 89.5 402 (hase) 31.8 750 kCMil in Air Drop 3.62 90.0 39.9 (clad) 4C 750 kCMil in 5 Conduit 2.19 89.4 402 (base) 10.7 4/C 750 kCMil in 5 Conduit 2.08 90.0 402 (clad)
The equilibrium current values are single-point measurements performed aRer the system was at equilibrium and the change in current was very low. The Equ.
Temp (equilibrium conductor temperature at the hottest location), and the Room Temp are reported as 60 minute aver'age values. The Corrected Current values are those calculated in accordance with P 848/D12 IEEE Standard Procedure for the Determination of the Ampacity Derating of Fire Protected Cables~, which corrects, these current values to a room temperature of 40;C and a conductor.
temperature of 90'C.
(Tc'- Ta') x(a+ Tc)
(Tc- Ta) x(a+ Tc')
where I test current at equilibrium, amperes Tc hottest conductor temperature at center at equilibrium, 'C Ta measured enclosure ambient temperature, 'C normalized current, amperes Tc normalized. conductor temperature = 90'C Ta normalized ambient temperature = 40'C a 234.5 for copper-a~o 0
L, Table 2- Dimensions and weights of rlgld steel conduit Customary Inch-pound units Metric units Minimum Mlnlmum weight of weight of ten unit ten unit Nominal lengths lengths or trade Nominal Nominal Length with Nominal Nominal Leng th with size of inside Outside wall without coup lings inside Outside wall without couplings conduit diameter diameter thickness coupling attached diameter diameter thickness coupling attached ln in in ln ft and in Ib mm mm meters kg 3/8 0.493 0.675 0,091 9'11 -1/2" 518 12.5 17.1 2.31 3.04 23.36 1/2 0.632 0.840 0.104 9'11 -1/4" 79.0 16.1 21.3 2.64 3.03 35.83 3/4 0.836 1.050 0.107 9'11 -1/4 105.0 21.2 26.7 2.72 3.03 47.63 1 1.063 1.315 0.126 9'11 153.Q 27.Q 33A 3.20 3.02 69.40 1 -1/4 1.394 1.660 0.133 9'11 201.0 35.4 42.2 3.38 3.02 . 91.17 1 -1/2 1.624 1.900 0.138 9'11" 249.0 41.2 48.3 3.51 3.02 112.95 2 2.083 2.375 0.146 9'11 332.0 52.9 60.3 3.71 3.02 150.60 2-1/2 . 2489 2.875 0.193 9'10 -1/2 527.0 63.2 73.0 4.90 3.01 239.05 3 3.090 3.500 0.205 9'10 -1/2" 682.6 78.5 88.9, 5.21 3.01 309.63 3 -1/2 3.570 4.000 0.215 9'10 -1/4 831.0 90.7 101.6 5.46 3.00 376.94 4.050 4.500 0.225 9'10 -1/4" 972.3 102.9 114.3 5.72 3.00 441.04 5 5.073 5.563 0.245 9e1 Qe 1313.6 128.9 141.3 6.22 3.00 595.85 6 6.093 6.625 0.266 9'10" 1745.3 154.8 168.3 6.76 3.00 791.67 NOTE -Applicable toie~ ..ces:
Length: ~ 1/0 <n (t B.35 mm) (without coupling)
Outside r',ameter for tra..e sizes 3/8 in through 2 In: k 0.015 in (a 0.3B mm) for triode sizes 2-1/2 ln through 4 ln: a 0.025 ln (k 0.64 mm) for sade sizes 5 and B ln:H% 0 X) W %
W m m -I W.ll thickness: See 7.3. m~~
Ch A Cl
~Cl%C RmX I 0 +lb Ch I
~ONO
PTN-BFJM-96-005 ATTACHMENT 3 EBASCO SERVICES INCORPORATED REVlSION 0 PAGE 1 of 3 UALuULALlvl'I ou vwv Y DATE 4-2'/-VO REVISION 1 SHEET~ OF~
CHKD. BY W DATE~b9t a OFS NO.
CLIENT PROJECT SUBJECT Conductor Single 3/c or Triplex Single 3/c or C Camhu;hu. Txiylm 812 AWG 1.72 1 ~ 789 1.72 x 1.25 ~ 2.15 1. 789 x 1. 25 = 2. 236 810 AWG 1.08 1.123 1.08 x 1.25 = 1.35 1.123 x 1.25 = 1.404 88 AWG 0.679 0.706 0.679 x 1.25 = 0.849 0.706 x 1.25 = 0.883 86 AWG 0.427 0.444 0.427 x 1.25 = 0.534 0.444 x 1.25 = 0.555 84 AWG 0.269 0.280 0.269 x 1.25 ~ 0.336 0.280 x 1.25 = 0.350 N2 AWG 0.169 0.176 0.169 x 1.25 = 0.211 0.176 x 1.25 = 0.220 81/0 AWG 0.106 0.110 0.106 x 1.25 ~ 0.133 0.110 x 1.25 = 0.138 82/0 AWG 0.0843 0.0877 0.0843 x 1.25 = 0.105 0.877 x 1.25 = 0.110 N4/0 AWG 0.0525 0.0546 0.0525 x 1.25 = 0.0656 0.0546 x 1.25 = 0.0683 8250 kcmil 0.0449 0.0467 0.0449 x 1.25 = 0.0561 0.0467 x 1.25 = 0.0584 8'350 kcmil 0.0320 0.0333 0.0320 x 1.25 = 0.040 0.0333 x 1.25 = 0.0416 8500 kcmil 0.0222 .-
0.0231 0.0222 x 1.25 = 0.0278 0.0231 x 1.25 ='.0289 8750 kc il 0.0148 f11000 kcmil 0.0111 0.0154 0.0148 x 1.25 = 0.0185 0.0115 0.0111 x 1.25 ~ 0.0139 81250 kcmil 0.00888 0.00924 0.00888 x 1.25 = 0.0111 1099E/2
EBASCO SERVICES INCORPORATED PTN-BFJH-96-005 yl ATTACHHENT 3 e,~e~
CHKD. BY DATE 4-2f-fO DATE~62g !0 REVISION 1 OFS NO.~
REVISION PAGE 2 DEPT of 0
3 NO.~
'96 CLIENT PROJECT SUBJECT X6MX 7~~i AC/DC AC Resistance at 90oC Conductor Resistance Ratio Single Conductor'@uuJM N 12 AWG 1.0 1.0 2.15 x 1.0 = 2.15 2.15 x 1.0 = 2.15 810 AWG 1.0 1.0 1.35 x 1.0 ~ 1.35 1.35 x 1.0 = 1.35 88 AWG 1.0 1.0 0.849x 1.0 ~ 0.849 0.849x 1.0 = 0.849 86 AWG 1.0 1.0 0.534x 1.0 = 0.534 0.534x 1.0 = 0.534 I4 AWG 1.0 1.0 0.336x 1.0 = 0.336 0.336x 1.0 = 0.336 2 AWG 1.0 1.01 0.211x 1.0 ~ 0.211 0.21lx 1.01= 0.213 01/0 AWG 1.001 1.02 0.133xl.ppl~ 0.133 0.133x 1.02= 0.136 82/0 AWG 1.001 1.03 0.105K1.001= 0.105 0.105x 1.03= 0.108 84/0 AWG 1.004 1.05 0.0656xl.004= 0.0659 0.0656x1.05= 0.0689 8250 kcmil 1.005 1.06 0.0561x1.005~ 0.0564 0.0561x1.06= 0.0595 8350 kcmil 1.009 1.08 0.0400x1.009= 0.0404 0.0400x1.08= 0.0432 fbop kcmil 1.018 1.13 0.0278x1.018&.0283 0.0278xl.13= 0.0314 kc il 81000kcmil
'750 1.039 1.067 1.21 0.0185x1.039~0.0192 0.0185x1.21= 0.0224 1.30 0.0139xl.067~0.0148 0.0139xl.3 ~ 0.0181 N1250kcmil 1.102 1.41 O.plllxl.102~0.0122 0.0lllx1.41= 0.0157 1099E/3
k',"
i~~iti
PTN-BFJM-96-005 ATTACHMENT 3 EBASCO SERVICES INCORPORATED REVISION 0 PAGE 3 of 3 EC-096
- ~a~
CHKD. BY DATE~M DATE~62q ED REVISION OFS NO.~~
SHEET 4 DEPT OF~2 NO.~
CLIENT PROJECT SUBJECT G D (See Table 7.2.2.2a for ac/dc resistance ratios)
AC Resistance at 90oC Conductor 3/C or Triplex Harm~
812 AWG 2.236 x 1.0 = 2.236 2.236 x 1.0 = 2.236 810 AWG 1.404 x 1.0 = 1.404 1.404 x 1.0 = 1.404 88 AWG 0.883 x 1.0 = 0.883 0.883 x 1.0 = 0.883 86 AWG 0.555 x 1.0 = 0.555 0.555 x 1.0 = 0.555 I4 AWG 0.350 x 1.0 = 0.350 0.350 x 1.0 = 0.350 82 AWG 0.220 x 1.0 = 0.220 0.220 x 1.01= 0.222 81/0 AWG 0.138 x 1.001=0.138 0.138 x 1.02= 0.141 82/0 AWG 0.110 x 1.001=0.110 0.110 x 1.03= 0.113 N4/0 AWG 0.0683x 1.004=0.0686 0.0683x 1.05= 0.0720 f/250 kcmil 0.0584x 1.005~0.0587 0.0584x 1.06~ 0.0619 8350 kcmil 0.0416x 1.009=0.0420 0.0416x 1.08= 0.0449
'8500 kcmil 0.0289x 1.018=0.0294 0.0289x 1.13= 0.0327 1099E/4
INC. PTN-BFJM-96-005 ATTACHHENT 4 APPROVED FIRE BARRlERS FOR REVISION 0 PAGE I of THE RUClEAR INDUSTRY 2 thermO-hg'30-1 FIRE BARRIE R MATER IAL PR 0 PER TI S f This brochure presents the major properties of AMPACITY DERATING THERMO-LAG in interest for nuclear generating Ampacity derating tests performed in accordance plant application. For additional data not with IPCEA Publication Number P-54-440 consult TSI. 'resented.
(Second Edition) (to determine cable base ampacity) and NEMA Publication No.
WC51-1975, The following results were obtained RADIATION RESISTANCE (for 40 percent loading):
2.12 x 1P rads total 40 year integrated dose One-Hour THERMO-LAG Barriers After irradiation no degradation in fire resistive Tray 12.5 pere'ent derating properties Conduit 6.8 percent derating FIRE PROTECTIVE FEATURES Three-Hour THERMO-LAG Barriers ASTM E-84 Testing for THERMO-LAG 330-1
.= Tray 17 percent derating Flame Spread Rating Fuel Contributed Rating
- Smoke Developed Rating
,
15 5
0 .
Conduit 10.9 percent derating ASTM E-84 Testing for THERMO-LAG Primer Flame Spread Rating MECHANICAL(PHYSICAI-) PROPORTIES Fuel Contributed Rating Smoke Developed Rating
0 0
Density wet 10.5 lbs/gallon Density dry 75~3 Ibs/ft3 5 Dry Weight 1/2 inch thickness ASTM E-84 Testing for THERMO-LAG 350-2P (one*our rated) ~ 3.25 Ib/Its Topcoat Dry Weight inch thickness 1
Flame Spread Rating (three-hour rated) ~ 6.5 Ib/ltz Fuel Contributed Rating Smoke Developed Rating 5
0 Venter based Tensile strength (75'F) 800 PSI 0 Shear strength (75'F) 1100 PSI One-hour and;hTee-hour fire endurance Flexural stiffness (75'F) 85 KSI test Flexural strength (75'F)
.
in accordance with ASTM E-119, and ANI/MAERP test "ANI/MAERPStandard Fire E'ndurance Test Method to Qualify a Protective
-
Bond strength initial Modulus (75'F)
~~'F) 2200 PSI 57570 KSIPSI Envelope for Class 1E Electrical Circuits". Thermal Conductivity 1/2 Inch THERMO-LAG rated one hour (Unfired. full cured) 0.1 Btu/hr ft.z'F/
inch THERMO-LAG rated three hours 1
. ASTM E-119 hose stream test on electrical SEISMIC PROPORTY trays and conduit for one and thrcc hour rated THERMO-LAG has been qualified by static THERMO-LAG (2-1/2 minute hose stream analysis for a very conservative loading. A value application) of 7.5g horizontal and 6.0g vertical acceleration, ASTM E-119 fire tests for structural steel,
~
~ combined biaxially was used for the analysis.
hangers to determine required THERMO-LAG These values bound most nuclear generating thickness for onc and three hour rating plant seismic criteria.
0 (Ilute>ar se C'P ~ ~l w t~ l I ~ ~ ~ lwl (Bulk)
C
-
><rage Conditions High humidity above 32'F and below 100 F Industrial atmosphere (CO> SO> mix)
(a Asbestoes free Salt spray Non-toxic Interior Environmental Conditions HEMICAL RESISTANCE OF High humidity ERMO-LAG 330-1 CO> S+ atmosphere mix Water Chlorine Sulfuric acid 10 percent solution 10 percent solution Results: Service life of at least 40 years Hydrochloric acid 10 percent solution Sodium hydroxide 5 percent solution PTN-BFJH-96-005 Sodium chloride ATTACHMENT 4 Acetic acid REVISION 0 Kerosene of Anhydrous Ammonia PAGE 2 2 LNG LPG Methanol CHEMICAL RESISTANCE OF
~ THERMO-LAG 3$ 0-2P TOPCOAT Frequent Contact Alkali solutions Salt solutions Alcohols Aliphatic hydrocarbons Aromatic hydrocarbons Occasional Contact Fresh water Waste water Mineral oils Vegetable oils Organic acids Mineral acids Oxidizing agents Ketoncs ~