P .
ATTACHMENT 3 Unit 1 Revision Page 3/4 3-30 Replace l
l l
l
)
t 91052200B7 910517 PDR ADOCK 05000348 PDR p
TABLE 3.3-5 (Continued)
ENGINEERED SAFETY FEATURES RESPONSE TIMES INITIATING SIGNAL AND FUNCTION RESPONSE TIME IN SECONDS
- 3. Pressurizer Pressure-Lov
- a. Safety Injection (FCCS) f 27.0'*'/12.0
- b. Reactor Trip (from SI) 3 2.0
- c. Feedvater Isolation 3 32.0
- d. Containment Isolation-Phase "A" 3 17.0
- e. Containment Purge Isolation f 5.0
- f. Auxiliary Feedvater Pumps Not Applicable
- g. Service Vater System f 77.0/87.0'1'
- 4. Differential Pressure Between Steam Lines-liig
- a. Safety Injection (ECCb) 3 12.0/22.0
- b. Reactor Trip (from SI) 3 2.0
- c. Feedvater Isolation 3 32.0
- d. Containment Isolation-Phase "A" f 17.0/27.0
- e. Containment Purge Isolation Not Applicable
- f. Auxiliary Feedvater Pumps Not Applicable
- g. Service Water System 3 77.0/87.0
- 5. Steam Flow in Two Steam Lines-fligh coincident with T --Low-Lov
- a. Steam Line Isolation f 11.0 l P
- 6. Steam Line Pressure-Lov
- a. Safety Injection (ECCS) 3 12.0(4'/22.0
- b. Reactor Trip (from SI) f 2.0
- c. Feedvater Isolation f 32.0
- d. Containment Isolation-Phase "A" f 17.0/27.0
- e. Containment Purge Isolation Not Applicable
- f. Auxiliary Feedvater Pumps Not Applicable
- g. Service Water System f 77.0/87.0
i Steam Line Isolation 3 7.0 FARLEY - UNIT 1 3/4 3-30 AMENDMENT NO.