. . _. . . . . - _ _ _-_ .

t '

v: y -

o . New Hompshire? m .,

Senior Vice President and '

Chief Operating Officer l NYN-90010 )

January 11, 1990 United States Nuclear Regulatory Commission Washingtoni DC- 20555 a

Attention: Document Control Desk ,

i

References:

(a). Facility Operating License NPF-67,. Docket No. 50-443' l L

(b) NRC Bulletin 88-09 . dated' July 26, 1988, " Thimble Tube. I l

Thinning-in Westinghouse Reactors' i

Subject Information Regarding Incore Instrumentation Thimble Thinning' ,

L Gentlemen: i

! This letter provides currently-available information regarding.the .

( subject of incore instrumentation ' thimble thinning as it' applies to Seabrook l

Station. New Hampshire Yankee.(NHY) is planning to-provide the requested i i

response to NRC Bulletin 88-09 following completion of the first). refueling outage of Seabrook Station Unit 1 in accordance with.the schedule specified i by the Bulletin.

The Seabrook Station fixed / movable incore instrumentation system features a ,

unique mechanical design which provides in-depth protection,against. reactor

! coolant leakage consequent to thimble wear. The'in-core instrumentation l thimble contains fis:ed detectors. Consequently, the design Includes two concentric thimbles. The inner thimble permits the moveable = detector'to l traverse the core and serves as the reactor: coolant pressure-boundary.- The l outer thimble serves as the housing for the fixed incore'detectoru and --

incore thermocouples, which are located between the inner and outer ~

thimbles. Failure of the outer thimble would not breach the reactor coolant-pressure boundary. Failure of both outer and inner thimbles would'be s

. required to breach-the reactor coolant pressure' boundary. -In the.h_ighly unlikely event of a wear-induced failure of both inner and outer thimbles,  ;

isolation valves at the seal table can be used to terminate reactor = coolant '

leakage.

New Hampshire Yankee expects to develop .n inspection program to monitor thimble performance. The program will 'e based, in part, upon industry experience and' vendor recommendations. The program will'be-implemented at'

..I

.. the first refueling outage of Seabrook Station Unit 1. The report 6 .

confirming that the program has been established and that the initial .

thimble inspections have been performed in accordance with the requirements '

of the program will be submitted within thirty (30) days of completion of

. the inspections.

9001230028 900111 F [

PDR ADOCK 05000443 /

Q PDC ,

New Hampshire Yonkee Division of Public Service Company of New Hampshire (p i P.O. Box 300

  • Seabrook, NH 03874
  • Telephone (603) 474 9521 -
  • .- I, United States. Nuclear Regulatory Commission January 11, 1990-Attention: Document Control Desk Page 2.

L If you have any questions on this matter please contact Mr. Geoffrey

[ Kingston at (603) 474-9521..

Very truly yours, h&f 4 &

L Ted C. Feigenbaum j cc: Mr. William T. Russell

l. Regional Administrator l United States Nuclear Regulatory Commission ,

Region I '

l 475 Allendale Road l King of Prussia, PA 19406 .;

Mr. Victor Herses, Project Manager  !

l Project Directorate I-3 j l United States Nuclear Regulatory Commission l l

Division of Reactor Projects  ;

i Washington, DC 20555  !

l NRC Senior Resident Inspector l P.O. Box 1149 l Seabrook, NH 03874 l >

l 1 1

I i

i i

l l

, _ . .