- 05000374/LER-1993-002-06, :on 930223,RCIC Sys Declared Inoperable When Required Sys Flow of 600 Gpm Could Not Be Obtained.Caused by Inoperable Turbine Control Box.Work Request L21599 Written to Investigate & Repair Problem (← links)
- 05000373/LER-1993-003-04, :on 930129,discovered Failure in RCIC Turbine Barometric Condenser Condensate Pump.Caused by Loose Wire Connections on RCIC Ramp Generator Signal Converter Terminal.Connections Fastened Securely (← links)
- IR 05000277/1990001 (← links)
- 05000278/LER-1990-001-03, :on 900108,HPCI Sys Declared Inoperable During Surveillance Testing When Start Time Exceeded 25 S.Caused by Inadequate Calibr Procedure Which Allowed Setting of 18 S. Ramp Generator & Signal Converter Replaced (← links)
- 05000324/LER-1980-068-03, /03L-0:on 800909,during Reactor Startup,Hpci Sys Turbine Control Valve 2E41-V9 Would Not Open W/Auxiliary Oil Pump Running.Caused by Cracked Electronic Governor Reverse Actuator Assembly Plug.Plug & Affected Components Repla (← links)
- 05000293/LER-1989-028, :on 890907,HPCI Sys Declared Inoperable Because Mechanical Overspeed Trip Occurred During Surveillance Test. Caused by Failure of Ramp Generator Signal Converter Module. Module Removed & Sent to Mfg for Exam (← links)
- ML18011A703 (← links)
- 05000325/LER-2015-001, (Bsep), Unit 1, Regarding High Pressure Coolant Injection (HPCI) System Inoperable Due to Auxiliary Oil Pump Failure (← links)
- 05000263/LER-2012-004, Regarding High Pressure Coolant Injection Inoperable When Inverter Is Out of Service (← links)
- 05000325/LER-2012-004, Regarding High Pressure Coolant Injection (HPCI) Inoperable Due to Erratic Governor Operation (← links)
- 05000388/LER-2011-002-01, Regarding Condition Prohibited by Technical Specification Due to Unknown RCIC Inoperablitliy (← links)
- 05000293/LER-2011-006, HPCI Turbine Governor Control Valve Failure (← links)
- 05000388/LER-2011-004, Regarding Unit 2 HPCI Inoperability (← links)
- 05000388/LER-2011-002, Regarding Condition Prohibited by Technical Specification Due to Unknown RCIC Inoperability (← links)
- 05000259/LER-2011-005, Regarding Reactor Water Level Scram Due to Distracted Operations Crew (← links)
- 05000353/LER-2006-001, Regarding HPCI Ramp Generator Signal Converter Failure (← links)
- IR 05000373/2025001 (← links)
- 05000298/LER-1996-003, :on 960320,single Train RCIC Sys Inoperable Due to Equipment Malfunction.Specific Cause of Failure Could Not Be Determined.Malfunctioning EGM Control Box Was Replaced (← links)
- 05000296/LER-2025-002, Reactor Core Isolation Cooling Inoperable Due to Failed Ramp Generating Signal Converter (← links)