IR 05000255/2020003: Difference between revisions

From kanterella
Jump to navigation Jump to search
(StriderTol Bot change)
(StriderTol Bot change)
 
Line 31: Line 31:


Sincerely,
Sincerely,
/RA/
/RA/  
Billy C. Dickson, Jr., Chief Branch 2 Division of Reactor Projects Docket No. 05000255 License No. DPR-20
 
Billy C. Dickson, Jr., Chief Branch 2 Division of Reactor Projects  
 
Docket No. 05000255 License No. DPR-20  


===Enclosure:===
===Enclosure:===
As stated
As stated  


==Inspection Report==
==Inspection Report==
Docket Number: 05000255 License Number: DPR-20 Report Number: 05000255/2020003 Enterprise Identifier: I-2020-003-0031 Licensee: Entergy Nuclear Operations, Inc.
Docket Number:
05000255  
 
License Number:
DPR-20  
 
Report Number:
05000255/2020003  
 
Enterprise Identifier: I-2020-003-0031  
 
Licensee:
Entergy Nuclear Operations, Inc.  
 
Facility:
Palisades Nuclear Plant
 
Location:
Covert, MI
 
Inspection Dates:
July 01, 2020 to September 30, 2020
 
Inspectors:
J. Benjamin, Senior Reactor Inspector
 
J. Bozga, Senior Reactor Inspector
 
E. Fernandez, Reactor Inspector
 
M. Holmberg, Senior Reactor Inspector
 
P. Laflamme, Senior Resident Inspector
 
J. Mancuso, Resident Inspector
 
V. Myers, Senior Health Physicist
 
C. St. Peters, Resident Inspector


Facility: Palisades Nuclear Plant Location: Covert, MI Inspection Dates: July 01, 2020 to September 30, 2020 Inspectors: J. Benjamin, Senior Reactor Inspector J. Bozga, Senior Reactor Inspector E. Fernandez, Reactor Inspector M. Holmberg, Senior Reactor Inspector P. Laflamme, Senior Resident Inspector J. Mancuso, Resident Inspector V. Myers, Senior Health Physicist C. St. Peters, Resident Inspector Approved By: Billy C. Dickson, Jr., Chief Branch 2 Division of Reactor Projects Enclosure
Approved By:
Billy C. Dickson, Jr., Chief
Branch 2
Division of Reactor Projects  


=SUMMARY=
=SUMMARY=
Line 46: Line 90:


===List of Findings and Violations===
===List of Findings and Violations===
No findings or violations of more than minor significance were identified.
No findings or violations of more than minor significance were identified.


Line 62: Line 105:


==REACTOR SAFETY==
==REACTOR SAFETY==
==71111.04 - Equipment Alignment==
==71111.04 - Equipment Alignment==
===Partial Walkdown Sample (IP Section 03.01) (3 Samples)===
The inspectors evaluated system configurations during partial walkdowns of the following systems/trains:


===Partial Walkdown Sample (IP Section 03.01) (3 Samples)===
(1)1-2 emergency diesel generator (EDG) lube oil and jacket water cooling water system on July 6, 2020
The inspectors evaluated system configurations during partial walkdowns of the following systems/trains:
: (1) 1-2 emergency diesel generator (EDG) lube oil and jacket water cooling water system on July 6, 2020
: (2) Station battery number 1 on August 6, 2020
: (2) Station battery number 1 on August 6, 2020
: (3) Spent fuel pool (SFP) cooling system on September 15, 2020
: (3) Spent fuel pool (SFP) cooling system on September 15, 2020


==71111.05 - Fire Protection==
==71111.05 - Fire Protection==
===Fire Area Walkdown and Inspection Sample (IP Section 03.01) (4 Samples)===
===Fire Area Walkdown and Inspection Sample (IP Section 03.01) (4 Samples)===
The inspectors evaluated the implementation of the fire protection program by conducting a walkdown and performing a review to verify program compliance, equipment functionality, material condition, and operational readiness of the following fire areas:
The inspectors evaluated the implementation of the fire protection program by conducting a walkdown and performing a review to verify program compliance, equipment functionality, material condition, and operational readiness of the following fire areas:
: (1) South west penetration room on July 13, 2020
: (1) South west penetration room on July 13, 2020
: (2) Cable spreading room on August 18, 2020
: (2) Cable spreading room on August 18, 2020 (3)1C 2.4kV switchgear room on August 24, 2020
: (3) 1C 2.4kV switchgear room on August 24, 2020
: (4) Charging pump room on August 25, 2020
: (4) Charging pump room on August 25, 2020


==71111.06 - Flood Protection Measures==
==71111.06 - Flood Protection Measures==
===Inspection Activities - Internal Flooding (IP Section 03.01) (1 Sample)===
===Inspection Activities - Internal Flooding (IP Section 03.01) (1 Sample)===
The inspectors evaluated internal flooding mitigation protections in the:
The inspectors evaluated internal flooding mitigation protections in the:
: (1) West engineering safeguards room on September 21, 2020
: (1) West engineering safeguards room on September 21, 2020  
 
===71111.08P - Inservice Inspection Activities (PWR)
 
PWR Inservice Inspection Activities Sample (IP Section 03.01) (1 Partial)
 
(1)
(Partial)
The inspectors verified that the reactor coolant system boundary, steam generator tubes, reactor vessel internals, risk-significant piping system boundaries, and containment boundary are appropriately monitored for degradation and that repairs and replacements were appropriately fabricated, examined and accepted by reviewing the following activities from 08/31/2020 to 09/30/2020:


===71111.08P - Inservice Inspection Activities (PWR) PWR Inservice Inspection Activities Sample (IP Section 03.01) (1 Partial)
    (1)  (Partial)
The inspectors verified that the reactor coolant system boundary, steam generator tubes, reactor vessel internals, risk-significant piping system boundaries, and containment boundary are appropriately monitored for degradation and that repairs and replacements were appropriately fabricated, examined and accepted by reviewing the following activities from 08/31/2020 to 09/30/2020:
03.01.a - Nondestructive Examination and Welding Activities.
03.01.a - Nondestructive Examination and Welding Activities.
* Encoded Phased Array Ultrasonic Examination (PAUT) of SDC Safe End to Elbow Dissimilar Metal Weld. Component ID PCS-12-SDC-2H1-1
* Encoded Phased Array Ultrasonic Examination (PAUT) of SDC Safe End to Elbow Dissimilar Metal Weld. Component ID PCS-12-SDC-2H1-1
Line 94: Line 138:
* Bare Metal Visual Exam (BMVT) of 1" Instrument Tap. Component ID PCS-042 Weld 6 "B Hot Leg"
* Bare Metal Visual Exam (BMVT) of 1" Instrument Tap. Component ID PCS-042 Weld 6 "B Hot Leg"
* Bare Metal Visual Exam (BMVT) of 1" Instrument Tap. Component ID PCS-042 Weld 8 "B Hot Leg"
* Bare Metal Visual Exam (BMVT) of 1" Instrument Tap. Component ID PCS-042 Weld 8 "B Hot Leg"
* Bare Metal Visual Exam (BMVT) of 1" Instrument Tap. Component ID PCS-042 Weld 10 "B Hot Leg" 03.01.b - Pressurized-Water Reactor Vessel Upper Head Penetration Examination Activities.
* Bare Metal Visual Exam (BMVT) of 1" Instrument Tap. Component ID PCS-042 Weld 10 "B Hot Leg"  
 
03.01.b - Pressurized-Water Reactor Vessel Upper Head Penetration Examination Activities.
* Bare Metal Visuals (BMV) of 54 Penetrations on the Reactor Vessel Closure Head (RVCH)
* Bare Metal Visuals (BMV) of 54 Penetrations on the Reactor Vessel Closure Head (RVCH)
* Ultrasonic Examination (UT) of 54 Penetrations on the Reactor Vessel Closure Head (RVCH)
* Ultrasonic Examination (UT) of 54 Penetrations on the Reactor Vessel Closure Head (RVCH)
* Half Nozzle Weld Repair of Penetrations 17 and 34, Work Order 00550825 03.01.c - Pressurized-Water Reactor Boric Acid Corrosion Control Activities.
* Half Nozzle Weld Repair of Penetrations 17 and 34, Work Order 00550825  
 
03.01.c - Pressurized-Water Reactor Boric Acid Corrosion Control Activities.
* CR-PLP-2019-02918 Pressurizer Spray Valve from Loop 1A CV-1057
* CR-PLP-2019-02918 Pressurizer Spray Valve from Loop 1A CV-1057
* CR-PLP-2019-04528 Flange downstream of MV-ES3418
* CR-PLP-2019-04528 Flange downstream of MV-ES3418
* CR-PLP-2019-02059 Flange near HC4-H103 and Temporary Connection for SFP Cooling 03.01.d - Pressurized-Water Reactor Steam Generator Tube Examination Activities.
* CR-PLP-2019-02059 Flange near HC4-H103 and Temporary Connection for SFP Cooling  
 
03.01.d - Pressurized-Water Reactor Steam Generator Tube Examination Activities.
* Eddy current testing of 7,589 Tubes in steam generator (SG 1A) and 7753 Tubes in (SG 1B)
* Eddy current testing of 7,589 Tubes in steam generator (SG 1A) and 7753 Tubes in (SG 1B)


==71111.11Q - Licensed Operator Requalification Program and Licensed Operator Performance==
==71111.11Q - Licensed Operator Requalification Program and Licensed Operator Performance==
Licensed Operator Performance in the Actual Plant/Main Control Room (IP Section 03.01)


Licensed Operator Performance in the Actual Plant/Main Control Room (IP Section 03.01)
===
===
{{IP sample|IP=IP 71111.08|count=2}}
{{IP sample|IP=IP 71111.08|count=2}}
: (1) The inspectors observed and evaluated licensed operator performance in the Control Room during reactor shutdown on August 30, 2020
: (1) The inspectors observed and evaluated licensed operator performance in the Control Room during reactor shutdown on August 30, 2020
: (2) The inspectors observed and evaluated licensed operator performance in the Control Room during reduced inventory on September 4, 2020
: (2) The inspectors observed and evaluated licensed operator performance in the Control Room during reduced inventory on September 4, 2020  


===Licensed Operator Requalification Training/Examinations (IP Section 03.02) (1 Sample)===
===Licensed Operator Requalification Training/Examinations (IP Section 03.02) (1 Sample)===
Line 115: Line 165:


==71111.12 - Maintenance Effectiveness==
==71111.12 - Maintenance Effectiveness==
===Maintenance Effectiveness (IP Section 03.01) (2 Samples)===
===Maintenance Effectiveness (IP Section 03.01) (2 Samples)===
The inspectors evaluated the effectiveness of maintenance to ensure the following structures, systems, and components (SSCs) remain capable of performing their intended function:
The inspectors evaluated the effectiveness of maintenance to ensure the following structures, systems, and components (SSCs) remain capable of performing their intended function:
Line 122: Line 171:


==71111.13 - Maintenance Risk Assessments and Emergent Work Control==
==71111.13 - Maintenance Risk Assessments and Emergent Work Control==
===Risk Assessment and Management Sample (IP Section 03.01) (4 Samples)===
===Risk Assessment and Management Sample (IP Section 03.01) (4 Samples)===
The inspectors evaluated the accuracy and completeness of risk assessments for the following planned and emergent work activities to ensure configuration changes and appropriate work controls were addressed:
The inspectors evaluated the accuracy and completeness of risk assessments for the following planned and emergent work activities to ensure configuration changes and appropriate work controls were addressed:
Line 131: Line 179:


==71111.15 - Operability Determinations and Functionality Assessments==
==71111.15 - Operability Determinations and Functionality Assessments==
===Operability Determination or Functionality Assessment (IP Section 03.01) (4 Samples)===
===Operability Determination or Functionality Assessment (IP Section 03.01) (4 Samples)===
The inspectors evaluated the licensee's justifications and actions associated with the following operability determinations and functionality assessments:
The inspectors evaluated the licensee's justifications and actions associated with the following operability determinations and functionality assessments:
Line 140: Line 187:


==71111.19 - Post-Maintenance Testing==
==71111.19 - Post-Maintenance Testing==
===Post-Maintenance Test Sample (IP Section 03.01) (5 Samples)===
===Post-Maintenance Test Sample (IP Section 03.01) (5 Samples)===
The inspectors evaluated the following post maintenance test activities to verify system operability and functionality:
The inspectors evaluated the following post maintenance test activities to verify system operability and functionality:
Line 150: Line 196:


==71111.20 - Refueling and Other Outage Activities==
==71111.20 - Refueling and Other Outage Activities==
Refueling/Other Outage Sample (IP Section 03.01) (1 Partial)
(1)
(Partial) The inspectors evaluated refueling outage 1R27 beginning August 30, 2020


Refueling/Other Outage Sample (IP Section 03.01) (1 Partial)
  (1)    (Partial)          The inspectors evaluated refueling outage 1R27 beginning August 30, 2020
==71111.22 - Surveillance Testing==
==71111.22 - Surveillance Testing==
 
The inspectors evaluated the following surveillance tests:  
The inspectors evaluated the following surveillance tests:


===Surveillance Tests (other) (IP Section 03.01)===
===Surveillance Tests (other) (IP Section 03.01)===
Line 162: Line 209:
: (2) RO-128-1, 1-1 EDG 24-hour load run test on August 8, 2020
: (2) RO-128-1, 1-1 EDG 24-hour load run test on August 8, 2020
: (3) Left train safety injection system test on August 18, 2020
: (3) Left train safety injection system test on August 18, 2020
: (4) RT-8C, engineering safeguards test on September 24, 2020
: (4) RT-8C, engineering safeguards test on September 24, 2020  


===Inservice Testing (IP Section 03.01) (1 Sample)===
===Inservice Testing (IP Section 03.01) (1 Sample)===
: (1) QO-19B - high pressure safety injection (HPSI) pump and emergency safety system           check valve operability test, on July 15,
: (1) QO-19B - high pressure safety injection (HPSI) pump and emergency safety system check valve operability test, on July 15,


==RADIATION SAFETY==
==RADIATION SAFETY==
==71124.01 - Radiological Hazard Assessment and Exposure Controls==
==71124.01 - Radiological Hazard Assessment and Exposure Controls==
===Radiological Hazard Assessment (IP Section 03.01) (1 Sample)===
===Radiological Hazard Assessment (IP Section 03.01) (1 Sample)===
: (1) The inspectors evaluated how the licensee identifies the magnitude and extent of radiation levels and the concentrations and quantities of radioactive materials and how the licensee assesses radiological hazards
: (1) The inspectors evaluated how the licensee identifies the magnitude and extent of radiation levels and the concentrations and quantities of radioactive materials and how the licensee assesses radiological hazards  


===Instructions to Workers (IP Section 03.02) (1 Sample)===
===Instructions to Workers (IP Section 03.02) (1 Sample)===
: (1) The inspectors evaluated radiological protection-related instructions to plant workers
: (1) The inspectors evaluated radiological protection-related instructions to plant workers  


===Contamination and Radioactive Material Control (IP Section 03.03) (2 Samples)===
===Contamination and Radioactive Material Control (IP Section 03.03) (2 Samples)===
The inspectors evaluated licensee processes for monitoring and controlling contamination and radioactive material:
The inspectors evaluated licensee processes for monitoring and controlling contamination and radioactive material:
: (1) The inspectors observed surveys of potentially contaminated material leaving the radiologically controlled are.
: (1) The inspectors observed surveys of potentially contaminated material leaving the radiologically controlled are.
: (2) The inspectors observed workers exiting the radiologically controlled area
: (2) The inspectors observed workers exiting the radiologically controlled area  


===Radiological Hazards Control and Work Coverage (IP Section 03.04) (3 Samples)===
===Radiological Hazards Control and Work Coverage (IP Section 03.04) (3 Samples)===
Line 186: Line 231:
: (1) Reactor vessel disassembly under RWP 20200433
: (1) Reactor vessel disassembly under RWP 20200433
: (2) Scaffolding activities in containment under RWP 20200424
: (2) Scaffolding activities in containment under RWP 20200424
: (3) Steam generator primary side activities under RWP 20200454 High Radiation Area and Very High Radiation Area Controls (IP Section 03.05) (2 Samples)
: (3) Steam generator primary side activities under RWP 20200454  
 
High Radiation Area and Very High Radiation Area Controls (IP Section 03.05) (2 Samples)  
 
The inspectors evaluated licensee controls of the following High Radiation Areas and Very High Radiation Areas:
The inspectors evaluated licensee controls of the following High Radiation Areas and Very High Radiation Areas:
: (1) Access to the reactor cavity, located inside containment
: (1) Access to the reactor cavity, located inside containment
: (2) Area surrounding the regenerative heat exchanger, located inside containment Radiation Worker Performance and Radiation Protection Technician Proficiency (IP Section 03.06) (1 Sample)
: (2) Area surrounding the regenerative heat exchanger, located inside containment  
 
Radiation Worker Performance and Radiation Protection Technician Proficiency (IP Section 03.06) (1 Sample)
: (1) The inspectors evaluated radiation worker and radiation protection technician performance as it pertains to radiation protection requirements
: (1) The inspectors evaluated radiation worker and radiation protection technician performance as it pertains to radiation protection requirements


==71124.02 - Occupational ALARA Planning and Controls==
==71124.02 - Occupational ALARA Planning and Controls==
===Implementation of ALARA and Radiological Work Controls (IP Section 03.03) (2 Samples)===
===Implementation of ALARA and Radiological Work Controls (IP Section 03.03) (2 Samples)===
The inspectors evaluated the licensees communication of as low as is reasonably achievable ALARA and radiological work controls for the following work activities:
The inspectors evaluated the licensees communication of as low as is reasonably achievable ALARA and radiological work controls for the following work activities:
: (1) Reactor vessel disassembly under RWP 20200433
: (1) Reactor vessel disassembly under RWP 20200433
: (2) Steam generator primary side activities under RWP 20200454
: (2) Steam generator primary side activities under RWP 20200454  


===Radiation Worker Performance (IP Section 03.04) (1 Sample)===
===Radiation Worker Performance (IP Section 03.04) (1 Sample)===
The inspectors evaluated radiation worker and radiation protection technician performance   during:
The inspectors evaluated radiation worker and radiation protection technician performance during:
: (1) Reactor vessel disassembly under RWP
: (1) Reactor vessel disassembly under RWP


==OTHER ACTIVITIES - BASELINE==
==OTHER ACTIVITIES - BASELINE==
===71151 - Performance Indicator Verification
The inspectors verified licensee performance indicators submittals listed below:


===71151 - Performance Indicator Verification The inspectors verified licensee performance indicators submittals listed below:
MS07: High Pressure Injection Systems (IP Section 02.06)===
MS07: High Pressure Injection Systems (IP Section 02.06) ===
{{IP sample|IP=IP 71151|count=1}}
{{IP sample|IP=IP 71151|count=1}}
: (1) Unit 1 (July 1, 2018-June 30, 2020)
: (1) Unit 1 (July 1, 2018-June 30, 2020)  


===MS09: Residual Heat Removal Systems (IP Section 02.08) (1 Sample)===
===MS09: Residual Heat Removal Systems (IP Section 02.08) (1 Sample)===
: (1) Unit 1 (July 1, 2018-June 30, 2020)
: (1) Unit 1 (July 1, 2018-June 30, 2020)  


===BI02: RCS Leak Rate Sample (IP Section 02.11) (1 Sample)===
===BI02: RCS Leak Rate Sample (IP Section 02.11) (1 Sample)===
Line 226: Line 277:
=DOCUMENTS REVIEWED=
=DOCUMENTS REVIEWED=


Inspection Type             Designation       Description or Title                                       Revision or
Inspection
Procedure                                                                                                  Date
Procedure
71111.04   Corrective Action CR-PLP-2020-     Protected Equipment for 1-2 Emergency Diesel Generator     07/06/2020
Type
Documents        02120
Designation
CR-PLP-2020-     Notification per MISO that Maintenance Activities Must be   07/06/2020
Description or Title
2126            Curtailed Due to Generation Availability Constraints
Revision or
CR-PLP-2020-     During Performance of MO-7A-1, FI-0890, Diesel Generator   07/08/2020
Date
2149            1-1 Service Water Flow was Reading 710gpm
71111.04
CR-PLP-2020-     VC-10 Suction Pressure Cycling From 52 psig to 58 psig on   07/21/2020
Corrective Action
298            PI-1676
Documents
CR-PLP-2020-     P-7B Service Water Pump Basket Strainer                    07/25/2020
CR-PLP-2020-
2120
Protected Equipment for 1-2 Emergency Diesel Generator
07/06/2020
CR-PLP-2020-
2126
Notification per MISO that Maintenance Activities Must be
Curtailed Due to Generation Availability Constraints
07/06/2020
CR-PLP-2020-
2149
During Performance of MO-7A-1, FI-0890, Diesel Generator
1-1 Service Water Flow was Reading 710gpm
07/08/2020
CR-PLP-2020-
298
VC-10 Suction Pressure Cycling From 52 psig to 58 psig on
PI-1676
07/21/2020
CR-PLP-2020-
2345
2345
CR-PLP-2020-     Corrosion Found During Rounds in Station Battery Number 2  07/26/2020
P-7B Service Water Pump Basket Strainer
07/25/2020
CR-PLP-2020-
2354
2354
CR-PLP-2020-     Induction Disc of the GE 12IAC53A101A Relay 151-106 X-     08/10/2020
Corrosion Found During Rounds in Station Battery Number 2 07/26/2020
2542            Phase was Stuck to the Backstop of the Time Dial/Lever
CR-PLP-2020-
Corrective Action CR-PLP-2020-     NRC Identified the Floor Drain Cover on the South End of   07/06/2020
2542
Documents        02129            the 1-2 Emergency Diesel Generator Ajar
Induction Disc of the GE 12IAC53A101A Relay 151-106 X-
Resulting from    CR-PLP-2020-     The NRC Identified that the 1-2 Emergency Diesel           07/06/2020
Phase was Stuck to the Backstop of the Time Dial/Lever
Inspection        02130            Generator Vents are Dirty and may Require Cleaning
08/10/2020
CR-PLP-2020-     NRC Identified a Potential Oil Leak on the North End of the 07/06/2020
Corrective Action
2131            1-1 Emergency Diesel Generator
Documents
CR-PLP-2020-     NRC Identified There is Vegetation Growing on the North     07/23/2020
Resulting from
2329            and North East Sides of EX-17, Station Transformer 17
Inspection
CR-PLP-2020-     NRC Identified Debris on the Floor of the 1-1 and 1-2 EDG   07/23/2020
CR-PLP-2020-
2330            Rooms
2129
Drawings          M-221             Piping & Instrumentation Diagram, Spent Fuel Pool Cooling   61
NRC Identified the Floor Drain Cover on the South End of
the 1-2 Emergency Diesel Generator Ajar
07/06/2020
CR-PLP-2020-
2130
The NRC Identified that the 1-2 Emergency Diesel
Generator Vents are Dirty and may Require Cleaning
07/06/2020
CR-PLP-2020-
2131
NRC Identified a Potential Oil Leak on the North End of the
1-1 Emergency Diesel Generator
07/06/2020
CR-PLP-2020-
2329
NRC Identified There is Vegetation Growing on the North
and North East Sides of EX-17, Station Transformer 17
07/23/2020
CR-PLP-2020-
2330
NRC Identified Debris on the Floor of the 1-1 and 1-2 EDG
Rooms
07/23/2020
Drawings
M-221
Piping & Instrumentation Diagram, Spent Fuel Pool Cooling
System, Sheet 2
System, Sheet 2
Miscellaneous     DBD 2.07         Design Basis Document for Spent Fuel Pool Cooling System   5
Miscellaneous
Procedures       AOP-26           Loss of Spent Fuel Pool Cooling                             3
DBD 2.07
SOP-27           Fuel Pool System                                           72
Design Basis Document for Spent Fuel Pool Cooling System
71111.05   Corrective Action CR-PLP-2020-     PI-5350A, Fire Protection System Header Pressure was       07/30/2020
Procedures
Documents        02416            Trending Down
AOP-26
Fire Plans       Pre-Fire Plan 13B Charging Pump Rooms / Elevation 590'                       5
Loss of Spent Fuel Pool Cooling
Inspection Type             Designation     Description or Title                                         Revision or
SOP-27
Procedure                                                                                                  Date
Fuel Pool System
Pre-Fire Plan 2 Cable Spreading Room; Elevation 607'                         5
71111.05
Pre-Fire Plan 26 Southwest Cable Penetration Room; Elevation 590' & 607'       5
Corrective Action
Pre-Fire Plan 4 1-C Switchgear Room and Manhole 1, 2, & 3/Elevation 590'     5
Documents
71111.06   Corrective Action CR-PLP-2020-     Expansion Joint XJ-0421 Flood Barrier on HB-23-3" was         08/04/2020
CR-PLP-2020-
Documents        02461            Identified as Having a Slit in the Joint Approximately Midway
2416
PI-5350A, Fire Protection System Header Pressure was
Trending Down
07/30/2020
Fire Plans
Pre-Fire Plan 13B Charging Pump Rooms / Elevation 590'  
 
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
Pre-Fire Plan 2
Cable Spreading Room; Elevation 607'
Pre-Fire Plan 26
Southwest Cable Penetration Room; Elevation 590' & 607'
Pre-Fire Plan 4
1-C Switchgear Room and Manhole 1, 2, & 3/Elevation 590'
71111.06
Corrective Action
Documents
CR-PLP-2020-
2461
Expansion Joint XJ-0421 Flood Barrier on HB-23-3" was
Identified as Having a Slit in the Joint Approximately Midway
Down the Southern Side of the Joint
Down the Southern Side of the Joint
Miscellaneous     DBD 7.08         Design Basis Document Plant Protection Against Flooding       6
08/04/2020
Procedures       AOP-39           Internal Plant Flooding                                       1
Miscellaneous
71111.08P Corrective Action CR-PLP-2020-     Ultrasonic Data Analysis of a Relevant Indication on         09/11/2020
DBD 7.08
Documents        03380            Penetration 34 on the Reactor Vessel Head
Design Basis Document Plant Protection Against Flooding
Resulting from    CR-PLP-2020-     Ultrasonic Data Analysis of a Relevant Indication on         09/13/2020
Procedures
Inspection        03427            Penetration 17 on the Reactor Vessel Head
AOP-39
Procedures       54-ISI-400-023   NONDESTRUCTIVE EXAMINATION PROCEDURE                         12/12/2018
Internal Plant Flooding
71111.08P
Corrective Action
Documents
Resulting from
Inspection
CR-PLP-2020-
03380
Ultrasonic Data Analysis of a Relevant Indication on
Penetration 34 on the Reactor Vessel Head
09/11/2020
CR-PLP-2020-
03427
Ultrasonic Data Analysis of a Relevant Indication on
Penetration 17 on the Reactor Vessel Head
09/13/2020
Procedures
54-ISI-400-023
NONDESTRUCTIVE EXAMINATION PROCEDURE
Multi-Frequency Eddy Current Examination of SG Tubing
Multi-Frequency Eddy Current Examination of SG Tubing
54-ISI-619-000   Automated Ultrasonic Examination of Open Tube RPV             07/30/2020
2/12/2018
54-ISI-619-000
Automated Ultrasonic Examination of Open Tube RPV
Closure Head Penetrations-Palisades Specific
Closure Head Penetrations-Palisades Specific
CEP-NDE-0955     Visual Examination (VE) of Bare-Metal Surfaces               307
07/30/2020
LMT-10-PAUT-     Fully Encoded Phased Array Ultrasonic Examination of         3
CEP-NDE-0955
007              Dissimilar Metal Piping Welds
Visual Examination (VE) of Bare-Metal Surfaces
SEP-BAC-PLP-     Boric Acid Corrosion Control Program Engineering Nuclear     4
307
001              Programs Applicable Sites
LMT-10-PAUT-
71111.11Q Miscellaneous     SES-405         LOR Simulator Exam Scenario                                   1
007
Procedures       GOP-14           Reduced Inventory Checklist                                   53
Fully Encoded Phased Array Ultrasonic Examination of
GOP-8           Power Reduction and Plant Shutdown to Mode 2 or Mode 3       40
Dissimilar Metal Piping Welds
                                              = 525°F
SEP-BAC-PLP-
71111.12   Corrective Action CR-PLP-2018-     CV-0869, CAC VHX-4 SW Inlet, Valve Actuator Moved in the     11/09/2018
001
Documents        05815            Closed or Open Direction, but Valve Itself did not Move
Boric Acid Corrosion Control Program Engineering Nuclear
CR-PLP-2019-     Baker Offline Motor Test Could not be Completed              12/16/2019
Programs Applicable Sites
71111.11Q Miscellaneous
SES-405
LOR Simulator Exam Scenario
Procedures
GOP-14
Reduced Inventory Checklist
GOP-8
Power Reduction and Plant Shutdown to Mode 2 or Mode 3  
= 525°F
71111.12
Corrective Action
Documents
CR-PLP-2018-
05815
CV-0869, CAC VHX-4 SW Inlet, Valve Actuator Moved in the
Closed or Open Direction, but Valve Itself did not Move
11/09/2018
CR-PLP-2019-
04925
04925
CR-PLP-2020-     Discharge Accumulator for P-55C Charging Pump the "As         08/05/2020
Baker Offline Motor Test Could not be Completed
2475            Found" Pressure of the Tank Bladder was 1287 psig
2/16/2019
CR-PLP-2020-     Charging Pump "As Found" Pressure of the Tank Bladder         08/05/2020
CR-PLP-2020-
2476            was 0.0 psig
2475
CR-PLP-2020-     Critical Service Water System (CSW) has Exceeded the         08/10/2020
Discharge Accumulator for P-55C Charging Pump the "As
Inspection Type             Designation   Description or Title                                       Revision or
Found" Pressure of the Tank Bladder was 1287 psig
Procedure                                                                                              Date
08/05/2020
2543         Near (a)(1) Threshold
CR-PLP-2020-
CR-PLP-2020- Exceeded Maintenance Rule (MR) Performance Criteria         09/07/2020
2476
03184        (PC) for Number of Functional Failures (#) in 24 Months for
Charging Pump "As Found" Pressure of the Tank Bladder
was 0.0 psig
08/05/2020
CR-PLP-2020-
Critical Service Water System (CSW) has Exceeded the
08/10/2020  
 
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
2543
Near (a)(1) Threshold
CR-PLP-2020-
03184
Exceeded Maintenance Rule (MR) Performance Criteria  
(PC) for Number of Functional Failures (#) in 24 Months for
the Main Steam System
the Main Steam System
Miscellaneous     System Health Chemical & Volume Control System                            2018
09/07/2020
Miscellaneous
System Health
Report
Report
System Health Chemical & Volume Control System                           2019
Chemical & Volume Control System
2018
System Health
Report
Report
System Health CSW - Critical Service Water                                Q2-2019
Chemical & Volume Control System
2019
System Health
Report
Report
System Health CSW - Critical Service Water                               Q2-2020
CSW - Critical Service Water
Q2-2019
System Health
Report
Report
System Health CSW - Critical Service Water                               Q4-2018
CSW - Critical Service Water
Q2-2020
System Health
Report
Report
System Health CSW - Critical Service Water                               Q4-2019
CSW - Critical Service Water
Q4-2018
System Health
Report
Report
71111.13   Corrective Action CR-PLP-2020- Removed from Service to Clean BS-1318, P-7A Service         07/31/2020
CSW - Critical Service Water
Documents        02421        Water Pump Basket Strainer
Q4-2019
CR-PLP-2020- Control Room Envelope                                      08/10/2020
71111.13
Corrective Action
Documents
CR-PLP-2020-
2421
Removed from Service to Clean BS-1318, P-7A Service
Water Pump Basket Strainer
07/31/2020
CR-PLP-2020-
2551
2551
CR-PLP-2020- Entered AOP-38 "Acts of Nature" due to High Wind Warning   08/11/2020
Control Room Envelope
2552        on August 10, 2020
08/10/2020
CR-PLP-2020- Start Up Transformer 1-2 Electrical Maintenance Failed to   08/11/2020
CR-PLP-2020-
2555        Finish the Work as Scheduled due to Acts of Nature
2552
Procedures       4.11         Safety Function Determination Program                       7
Entered AOP-38 "Acts of Nature" due to High Wind Warning
71111.15   Corrective Action CR-PLP-2020- Spalling of the Concrete Near Containment Vertical Tendon   06/24/2020
on August 10, 2020
Documents        02009        V-140 Anchorage
08/11/2020
CR-PLP-2020- The Official Monthly Lake Michigan Elevation for June, as   07/21/2020
CR-PLP-2020-
2303        Measured by the Calumet Harbor, Illinois Buoy, has
2555
Start Up Transformer 1-2 Electrical Maintenance Failed to
Finish the Work as Scheduled due to Acts of Nature
08/11/2020
Procedures
4.11
Safety Function Determination Program
71111.15
Corrective Action
Documents
CR-PLP-2020-
2009
Spalling of the Concrete Near Containment Vertical Tendon
V-140 Anchorage
06/24/2020
CR-PLP-2020-
2303
The Official Monthly Lake Michigan Elevation for June, as
Measured by the Calumet Harbor, Illinois Buoy, has
Exceeded the Assumed Starting Elevation for the Design
Exceeded the Assumed Starting Elevation for the Design
Basis Seiche Event
Basis Seiche Event
CR-PLP-2020- Per CR-PLP-2020-02303 the Elevation of Lake Michigan in     07/22/2020
07/21/2020
2316        the Area of the Plant has Exceeded the Assumed Design-
CR-PLP-2020-
2316
Per CR-PLP-2020-02303 the Elevation of Lake Michigan in
the Area of the Plant has Exceeded the Assumed Design-
Basis Value for External Flooding Protection
Basis Value for External Flooding Protection
Inspection Type             Designation Description or Title                                     Revision or
07/22/2020
Procedure                                                                                          Date
 
CR-PLP-2020- Adjustment on HIC-0826, Instrument Air Regulator for CV- 07/27/2020
Inspection
2365        0826
Procedure
CR-PLP-2020- EK-EK-1171, Component CLG E-54B Hi-Lo Temp                07/28/2020
Type
Designation
Description or Title
Revision or
Date
CR-PLP-2020-
2365
Adjustment on HIC-0826, Instrument Air Regulator for CV-
26
07/27/2020
CR-PLP-2020-
2366
2366
CR-PLP-2020- Operator Noted EVI-27/D2, BTRY D02 DC Volt               07/29/2020
EK-EK-1171, Component CLG E-54B Hi-Lo Temp
2389        Indicator/Undervolt RLY Reading 129 8V
07/28/2020
CR-PLP-2020- Cooling Fan M201 in ED-09 was Discovered to be Operating 07/30/2020
CR-PLP-2020-
2394        Approximately 18°F Warmer than the Other 2 Fans
2389
CR-PLP-2020- Discovered in ED-09, Wire 821 on TC No. 3, Terminal J4-11 07/30/2020
Operator Noted EVI-27/D2, BTRY D02 DC Volt
2395        was Approximately 33°F Warmer than the Similar Wires
Indicator/Undervolt RLY Reading 129 8V
CR-PLP-2020- EK-1132, Service Water Pump Basket Strainer D/P Alarms   07/30/2020
07/29/2020
2399        not Actuating at Proper D/P
CR-PLP-2020-
CR-PLP-2020- RT-202B Precals for Channels 1 and 2 were Calibrated     07/30/2020
2394
2405        Above Stated Ranges
Cooling Fan M201 in ED-09 was Discovered to be Operating
CR-PLP-2020- Service Water Piping Inside Containment                  09/02/2020
Approximately 18°F Warmer than the Other 2 Fans
07/30/2020
CR-PLP-2020-
2395
Discovered in ED-09, Wire 821 on TC No. 3, Terminal J4-11
was Approximately 33°F Warmer than the Similar Wires
07/30/2020
CR-PLP-2020-
2399
EK-1132, Service Water Pump Basket Strainer D/P Alarms
not Actuating at Proper D/P
07/30/2020
CR-PLP-2020-
2405
RT-202B Precals for Channels 1 and 2 were Calibrated
Above Stated Ranges
07/30/2020
CR-PLP-2020-
2941
2941
CR-PLP-2020- Service Water Piping Inside Containment                   09/02/2020
Service Water Piping Inside Containment
09/02/2020
CR-PLP-2020-
2943
2943
Corrective Action CR-PLP-2020- Service Water P-7C was Removed from Service to Clean     08/01/2020
Service Water Piping Inside Containment
Documents        02432        BS-1320, P-7C Service Water Pump Basket Strainer
09/02/2020
Resulting from    CR-PLP-2020- Editorial Error at the Bottom of the Tabulation on FSAR   08/18/2020
Corrective Action
Inspection        02617        Page 5.8-33
Documents
Engineering       86917       Continued Operation when Lake Michigan Design Basis       0
Resulting from
Changes                        Levels are Exceeded
Inspection
289       Concrete Spalling Near V-140 Tendon Anchorage on         0
CR-PLP-2020-
2432
Service Water P-7C was Removed from Service to Clean
BS-1320, P-7C Service Water Pump Basket Strainer
08/01/2020
CR-PLP-2020-
2617
Editorial Error at the Bottom of the Tabulation on FSAR
Page 5.8-33
08/18/2020
Engineering
Changes
86917
Continued Operation when Lake Michigan Design Basis
Levels are Exceeded
289
Concrete Spalling Near V-140 Tendon Anchorage on
Containment Dome
Containment Dome
87503       Supplement to EC 87289 on ACI Bearing Strength           0
87503
87696       Supplement to EC 87289 and EC 87503 on Steel Plate       0
Supplement to EC 87289 on ACI Bearing Strength
87696
Supplement to EC 87289 and EC 87503 on Steel Plate
Applied Stresses
Applied Stresses
Engineering       87503        Supplement to EC 87289 on ACI Bearing Strength            0
Engineering
Evaluations
Evaluations
Miscellaneous     PLP-RPT-15- Palisades Nuclear Plant Flooding Hazard Re-Evaluation     1
87503
00010        Report
Supplement to EC 87289 on ACI Bearing Strength
Procedures       QO-5,       Valve Stroke Testing Data Sheet CV-0821, CV-0822,         08/29/2019
Miscellaneous
Inspection Type             Designation   Description or Title                                       Revision or
PLP-RPT-15-
Procedure                                                                                              Date
00010
17 CV-0823, CV-0826
Palisades Nuclear Plant Flooding Hazard Re-Evaluation
SOP-15       Palisades Nuclear Plant System Operating Procedure:         69
Report
Procedures
QO-5,
Valve Stroke Testing Data Sheet CV-0821, CV-0822,
08/29/2019  
 
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
17
CV-0823, CV-0826
SOP-15
Palisades Nuclear Plant System Operating Procedure:
Service Water System
Service Water System
Work Orders       52922071      QO-5 -Vlv Test Proc (Inc Cont Isolation Vlvs)               05/26/2020
Work Orders
71111.19   Corrective Action CR-PLP-2020- Fan M-201 for ED-09 Inverter #4 was Replaced               07/31/2020
2922071
Documents        02423
QO-5 -Vlv Test Proc (Inc Cont Isolation Vlvs)
CR-PLP-2020- Buildup of Dirt & Dust on the Bottom of M1, M2 &M201 Heat   07/31/2020
05/26/2020
2424        Sinks
71111.19
CR-PLP-2020- Service Water P-7B was Removed from Service to Clean       07/31/2020
Corrective Action
2426        BS-1319, P-7B Service Water Pump Basket Strainer
Documents
CR-PLP-2020- SSC: CV-3057, Safety Injection Refueling Water Tank         09/02/2020
CR-PLP-2020-
2911        (SIRWT) Isolation
2423
Miscellaneous                  Control Room Logs                                           07/28/2020
Fan M-201 for ED-09 Inverter #4 was Replaced
Failure Modes NI-3, Wide Range Nuclear Instrument                        09/13/2020
07/31/2020
CR-PLP-2020-
2424
Buildup of Dirt & Dust on the Bottom of M1, M2 &M201 Heat
Sinks
07/31/2020
CR-PLP-2020-
2426
Service Water P-7B was Removed from Service to Clean
BS-1319, P-7B Service Water Pump Basket Strainer
07/31/2020
CR-PLP-2020-
2911
SSC: CV-3057, Safety Injection Refueling Water Tank  
(SIRWT) Isolation
09/02/2020
Miscellaneous
Control Room Logs
07/28/2020
Failure Modes
and Effects
and Effects
Worksheet
Worksheet
Procedures       EN-MA-125     Troubleshooting Control of Maintenance Activities           09/23/2020
NI-3, Wide Range Nuclear Instrument
EN-MA-134     Offline Motor Electrical Testing                           07/27/2020
09/13/2020
EN-RE-326     PWR Core Loading Verification                               09/16/2020
Procedures
EN-WM-105     Off-Line Baker Testing of Motor EMA-1208 for P-52B         07/27/2020
EN-MA-125
RFL-V-9       Core Verification                                           9
Troubleshooting Control of Maintenance Activities
RI-99         Left Channel Nuclear Instrumentation Calibrations           18
09/23/2020
SOP-22       Emergency Diesel Generator                                 80
EN-MA-134
Work Orders       00550833     NI-1/3A, Indication Failed - Replace Suspect 8D's "A8 & A9" 09/21/2020
Offline Motor Electrical Testing
2864755     EEQ Maint-Comp. Cooling. EMA-1208, P-52B Motor             07/27/2020
07/27/2020
2872985     Core Mapping System Setup and Operation                     09/16/2020
EN-RE-326
71111.20   Corrective Action CR-PLP-2020- CV-0701, SG E-50A FW Regulating Valve                       08/30/2020
PWR Core Loading Verification
Documents        02793
09/16/2020
CR-PLP-2020- Rod Deviation Alarms were Received                          08/30/2020
EN-WM-105
Off-Line Baker Testing of Motor EMA-1208 for P-52B
07/27/2020
RFL-V-9
Core Verification
RI-99
Left Channel Nuclear Instrumentation Calibrations
SOP-22
Emergency Diesel Generator
Work Orders
00550833
NI-1/3A, Indication Failed - Replace Suspect 8D's "A8 & A9"
09/21/2020
2864755
EEQ Maint-Comp. Cooling. EMA-1208, P-52B Motor
07/27/2020
2872985
Core Mapping System Setup and Operation
09/16/2020
71111.20
Corrective Action
Documents
CR-PLP-2020-
2793
CV-0701, SG E-50A FW Regulating Valve
08/30/2020
CR-PLP-2020-
2795
2795
CR-PLP-2020- RV-2006, Letdown Heat Exch E-58 Inlet Safety Relief and     08/30/2020
Rod Deviation Alarms were Received
2796        Primary Coolant System (PCS)
08/30/2020
CR-PLP-2020- CV-2002 is not Opening with SV-2002B in AUTO                08/30/2020
CR-PLP-2020-
2796
RV-2006, Letdown Heat Exch E-58 Inlet Safety Relief and
Primary Coolant System (PCS)
08/30/2020
CR-PLP-2020-
2802
2802
Inspection Type             Designation Description or Title                                       Revision or
CV-2002 is not Opening with SV-2002B in AUTO
Procedure                                                                                            Date
08/30/2020
CR-PLP-2020- Boric Acid Leak was Identified on CRD-12                  08/30/2020
 
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
CR-PLP-2020-
2820
2820
CR-PLP-2020- Boric Acid Leak was Identified on CRD-18                  08/30/2020
Boric Acid Leak was Identified on CRD-12
08/30/2020
CR-PLP-2020-
2821
2821
CR-PLP-2020- Air Hoses Were Ran Thru the Equipment Hatch Without Ops   09/01/2020
Boric Acid Leak was Identified on CRD-18
2894        Alignment and Hose Labeling per GOP-14
08/30/2020
CR-PLP-2020- T-2, Condensate Storage Tank                              09/05/2020
CR-PLP-2020-
2894
Air Hoses Were Ran Thru the Equipment Hatch Without Ops
Alignment and Hose Labeling per GOP-14
09/01/2020
CR-PLP-2020-
03094
03094
CR-PLP-2020- Control Room Operators Entered AOP-36, Loss of             09/10/2020
T-2, Condensate Storage Tank
262        Component Cooling
09/05/2020
CR-PLP-2020- Breaker 25H9 (Generator Output Breaker) Failed to Close   09/18/2020
CR-PLP-2020-
03620        from the Control Room
262
Corrective Action CR-PLP-2020- NRC Identified - During the Containment Walkdown a        08/31/2020
Control Room Operators Entered AOP-36, Loss of
Documents         02838        Puddle of Oil was Found on the 590' Clean Waste Receiver
Component Cooling
Resulting from                 Tank Room About Half Under the 607' Catwalk
09/10/2020
CR-PLP-2020-
03620
Breaker 25H9 (Generator Output Breaker) Failed to Close
from the Control Room
09/18/2020
Corrective Action
Documents
Resulting from
Inspection
Inspection
Procedures       EM-04-08     Mode 3, Tave = 525°F Shutdown Margin Calculation           08/24/2020
CR-PLP-2020-
EN-RE-302   PWR Reactivity Maneuver - Reactivity Plan Form             08/25/2020
2838
GOP-14       Shutdown Cooling Operations                               53
NRC Identified - During the Containment Walkdown a
71111.22   Corrective Action CR-PLP-2020- PI-1475, Diesel Generator K-6A Fuel Oil Pressure was at 25 08/05/2020
Puddle of Oil was Found on the 590' Clean Waste Receiver
Documents        02471        psig
Tank Room About Half Under the 607' Catwalk
CR-PLP-2020- RO-128-1, Diesel Generator 1-1 24 Hour Load Run, Table     08/05/2020
08/31/2020
2472        for Acceptance Criteria
Procedures
CR-PLP-2020- LLRT for Penetration MZ-42, Could not Establish <10sccm   08/31/2020
EM-04-08
2834        on Step 5.2.13(h)2 and 3, Actual Reading was 30 sccm
Mode 3, Tave = 525&deg;F Shutdown Margin Calculation
CR-PLP-2020- Leakage from Containment Penetration #15 was 8400 sccm     09/04/2020
08/24/2020
2996        and Exceeded the 5000 sccm Troubleshooting Guideline
EN-RE-302
CR-PLP-2020- CV-0847, SW Supply to Cont (MZ-12)                        09/25/2020
PWR Reactivity Maneuver - Reactivity Plan Form
08/25/2020
GOP-14
Shutdown Cooling Operations
71111.22
Corrective Action
Documents
CR-PLP-2020-
2471
PI-1475, Diesel Generator K-6A Fuel Oil Pressure was at 25
psig
08/05/2020
CR-PLP-2020-
2472
RO-128-1, Diesel Generator 1-1 24 Hour Load Run, Table
for Acceptance Criteria
08/05/2020
CR-PLP-2020-
2834
LLRT for Penetration MZ-42, Could not Establish <10sccm
on Step 5.2.13(h)2 and 3, Actual Reading was 30 sccm
08/31/2020
CR-PLP-2020-
2996
Leakage from Containment Penetration #15 was 8400 sccm
and Exceeded the 5000 sccm Troubleshooting Guideline
09/04/2020
CR-PLP-2020-
03806
03806
Procedures       QO-1         Safety Injection System                                   70
CV-0847, SW Supply to Cont (MZ-12)
QO-15       Inservice Test Procedure - Component Cooling Water         40
09/25/2020
Procedures
QO-1
Safety Injection System
QO-15
Inservice Test Procedure - Component Cooling Water
Pumps
Pumps
QO-19B       Inservice Test Procedure - HPSI Pumps and Emergency       44
QO-19B
Safety System Check Valve Operability Test
Inservice Test Procedure - HPSI Pumps and Emergency
Inspection Type             Designation Description or Title                                 Revision or
Safety System Check Valve Operability Test  
Procedure                                                                                      Date
 
RT-8C       Engineered Safeguards System - Left Channel         09/14/2020
Inspection
Work Orders       52871419    RT-8C - Engineered Safeguards System - Left Channel 09/14/2020
Procedure
2928850     QO-15B, Inservice Test Procedure - Component Cooling 07/27/2020
Type
Designation
Description or Title
Revision or
Date
RT-8C
Engineered Safeguards System - Left Channel
09/14/2020
Work Orders
2871419
RT-8C - Engineered Safeguards System - Left Channel
09/14/2020
2928850
QO-15B, Inservice Test Procedure - Component Cooling
Pump P-52B
Pump P-52B
71124.01   Procedures       EN-RP-101   Access Control for Radiologically Controlled Areas   15
07/27/2020
EN-RP-106-01 Radiological Survey Guidlines                       6
71124.01
EN-RP-122   Alpha Monitoring                                     10
Procedures
EN-RP-131   Air Sampling                                         17
EN-RP-101
Radiation Work   20200424    Scaffolding Activities in Containment               00
Access Control for Radiologically Controlled Areas
Permits (RWPs)    20200433    Refuel Project: Disassembly of the Reactor Head and 00
EN-RP-106-01
Radiological Survey Guidlines
EN-RP-122
Alpha Monitoring
EN-RP-131
Air Sampling
Radiation Work
Permits (RWPs)
200424
Scaffolding Activities in Containment
200433
Refuel Project: Disassembly of the Reactor Head and
Associated Work Activities
Associated Work Activities
200454     Steam Generator Primary Side Activities             00
200454
71124.02   ALARA Plans       20200424    Scaffolding Activities in Containment               00
Steam Generator Primary Side Activities
200433     Refuel Project: Disassembly of the Reactor Head and 00
71124.02
ALARA Plans
200424
Scaffolding Activities in Containment
200433
Refuel Project: Disassembly of the Reactor Head and
Associated Work Activities
Associated Work Activities
200454     Steam Generator Primary Side Activities             00
200454
Procedures       EN-RP-110   ALARA Program                                       14
Steam Generator Primary Side Activities
71151     Miscellaneous                 NRC Performance Indicators 2Q2020                   04/01/2020 -
Procedures
EN-RP-110
ALARA Program
71151
Miscellaneous
NRC Performance Indicators 2Q2020
04/01/2020 -
06/30/2020
06/30/2020
NRC Performance Indicators 1Q2020                   01/01/2020 -
NRC Performance Indicators 1Q2020
01/01/2020 -
03/31/2020
03/31/2020
NRC Performance Indicators 4Q2019                   10/01/2019 -
NRC Performance Indicators 4Q2019
10/01/2019 -
2/31/2019
2/31/2019
NRC Performance Indicators 3Q2019                   07/01/2019 -
NRC Performance Indicators 3Q2019
07/01/2019 -
09/330/2019
09/330/2019
NRC Performance Indicators 2Q2019                   04/01/2019 -
NRC Performance Indicators 2Q2019
04/01/2019 -
06/30/2019
06/30/2019
NRC Performance Indicators 4Q2018                   10/01/2018 -
NRC Performance Indicators 4Q2018
10/01/2018 -
2/31/2018
2/31/2018
NRC Performance Indicators 3Q2018                   07/01/2018 -
NRC Performance Indicators 3Q2018
07/01/2018 -
09/30/2018
09/30/2018
Procedures                     NRC Performance Indicators 1Q2019                   01/01/2019 -
Procedures
NRC Performance Indicators 1Q2019
01/01/2019 -
03/31/2019
03/31/2019
71152     Corrective Action CR-PLP-2020- CV-0826 CCW HX E-54B SW Outlet Pinned Incorrectly   07/27/2020
71152
Inspection Type       Designation Description or Title                                 Revision or
Corrective Action
Procedure                                                                              Date
CR-PLP-2020-
Documents 02365
CV-0826 CCW HX E-54B SW Outlet Pinned Incorrectly
Procedures QO-5       Valve Test Procedure (Includes Containment Isolation 109
07/27/2020  
 
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
Documents
2365
Procedures
QO-5
Valve Test Procedure (Includes Containment Isolation
Valves)
Valves)
SOP-15     Service Water System                                 70
109
16
SOP-15
Service Water System
70
}}
}}

Latest revision as of 13:44, 29 November 2024

Integrated Inspection Report 05000255/2020003
ML20318A040
Person / Time
Site: Palisades Entergy icon.png
Issue date: 11/13/2020
From: Billy Dickson
NRC/RGN-III/DRP/B2
To: Corbin D
Entergy Nuclear Operations
References
IR 2020003
Download: ML20318A040 (18)


Text

November 13, 2020

SUBJECT:

PALISADES NUCLEAR PLANT - INTEGRATED INSPECTION REPORT 05000255/2020003

Dear Mr. Corbin:

On September 30, 2020, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at Palisades Nuclear Plant. On October 28, 2020, the NRC inspectors discussed the results of this inspection with you and other members of your staff. The results of this inspection are documented in the enclosed report.

No findings or violations of more than minor significance were identified during this inspection.

This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with Title 10 of the Code of Federal Regulations 2.390, Public Inspections, Exemptions, Requests for Withholding.

Sincerely,

/RA/

Billy C. Dickson, Jr., Chief Branch 2 Division of Reactor Projects

Docket No. 05000255 License No. DPR-20

Enclosure:

As stated

Inspection Report

Docket Number:

05000255

License Number:

DPR-20

Report Number:

05000255/2020003

Enterprise Identifier: I-2020-003-0031

Licensee:

Entergy Nuclear Operations, Inc.

Facility:

Palisades Nuclear Plant

Location:

Covert, MI

Inspection Dates:

July 01, 2020 to September 30, 2020

Inspectors:

J. Benjamin, Senior Reactor Inspector

J. Bozga, Senior Reactor Inspector

E. Fernandez, Reactor Inspector

M. Holmberg, Senior Reactor Inspector

P. Laflamme, Senior Resident Inspector

J. Mancuso, Resident Inspector

V. Myers, Senior Health Physicist

C. St. Peters, Resident Inspector

Approved By:

Billy C. Dickson, Jr., Chief

Branch 2

Division of Reactor Projects

SUMMARY

The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees performance by conducting an integrated inspection at Palisades Nuclear Plant, in accordance with the Reactor Oversight Process. The Reactor Oversight Process is the NRCs program for overseeing the safe operation of commercial nuclear power reactors. Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information.

List of Findings and Violations

No findings or violations of more than minor significance were identified.

Additional Tracking Items

None.

PLANT STATUS

The plant began the inspection period at rated thermal power and remained at or near rated thermal power until August 5, 2020. On August 5, 2020, the plant began coast down until reaching approximately 88 percent power on August 30, 2020. On August 30, 2020, the plant was down powered and taken offline for a refueling outage. The plant remained offline for the remainder of the inspection period.

INSPECTION SCOPES

Inspections were conducted using the appropriate portions of the inspection procedures (IPs) in effect at the beginning of the inspection unless otherwise noted. Currently approved IPs with their attached revision histories are located on the public website at http://www.nrc.gov/reading-rm/doc-collections/insp-manual/inspection-procedure/index.html. Samples were declared complete when the IP requirements most appropriate to the inspection activity were met consistent with Inspection Manual Chapter (IMC) 2515, Light-Water Reactor Inspection Program - Operations Phase. The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel to assess licensee performance and compliance with Commission rules and regulations, license conditions, site procedures, and standards.

Starting on March 20, 2020, in response to the National Emergency declared by the President of the United States on the public health risks of the coronavirus (COVID-19), resident inspectors were directed to begin telework and to remotely access licensee information using available technology. During this time the resident inspectors performed periodic site visits each week and during that time conducted plant status activities as described in IMC 2515, Appendix D; observed risk significant activities, and completed on-site portions of IPs. In addition, resident and regional baseline inspections were evaluated to determine if all or a portion of the objectives and requirements stated in the IP could be performed remotely. If the inspections could be performed remotely, they were conducted per the applicable IP. In some cases, portions of an IP were completed remotely and on-site. The inspections documented below met the objectives and requirements for completion of the IP.

REACTOR SAFETY

71111.04 - Equipment Alignment

Partial Walkdown Sample (IP Section 03.01) (3 Samples)

The inspectors evaluated system configurations during partial walkdowns of the following systems/trains:

(1)1-2 emergency diesel generator (EDG) lube oil and jacket water cooling water system on July 6, 2020

(2) Station battery number 1 on August 6, 2020
(3) Spent fuel pool (SFP) cooling system on September 15, 2020

71111.05 - Fire Protection

Fire Area Walkdown and Inspection Sample (IP Section 03.01) (4 Samples)

The inspectors evaluated the implementation of the fire protection program by conducting a walkdown and performing a review to verify program compliance, equipment functionality, material condition, and operational readiness of the following fire areas:

(1) South west penetration room on July 13, 2020
(2) Cable spreading room on August 18, 2020 (3)1C 2.4kV switchgear room on August 24, 2020
(4) Charging pump room on August 25, 2020

71111.06 - Flood Protection Measures

Inspection Activities - Internal Flooding (IP Section 03.01) (1 Sample)

The inspectors evaluated internal flooding mitigation protections in the:

(1) West engineering safeguards room on September 21, 2020

===71111.08P - Inservice Inspection Activities (PWR)

PWR Inservice Inspection Activities Sample (IP Section 03.01) (1 Partial)

(1)

(Partial)

The inspectors verified that the reactor coolant system boundary, steam generator tubes, reactor vessel internals, risk-significant piping system boundaries, and containment boundary are appropriately monitored for degradation and that repairs and replacements were appropriately fabricated, examined and accepted by reviewing the following activities from 08/31/2020 to 09/30/2020:

03.01.a - Nondestructive Examination and Welding Activities.

  • Bare Metal Visual Exam (BMVT) of 1" Instrument Tap. Component ID PCS-042 Weld 6 "B Hot Leg"
  • Bare Metal Visual Exam (BMVT) of 1" Instrument Tap. Component ID PCS-042 Weld 8 "B Hot Leg"
  • Bare Metal Visual Exam (BMVT) of 1" Instrument Tap. Component ID PCS-042 Weld 10 "B Hot Leg"

03.01.b - Pressurized-Water Reactor Vessel Upper Head Penetration Examination Activities.

  • Bare Metal Visuals (BMV) of 54 Penetrations on the Reactor Vessel Closure Head (RVCH)

03.01.c - Pressurized-Water Reactor Boric Acid Corrosion Control Activities.

03.01.d - Pressurized-Water Reactor Steam Generator Tube Examination Activities.

71111.11Q - Licensed Operator Requalification Program and Licensed Operator Performance

Licensed Operator Performance in the Actual Plant/Main Control Room (IP Section 03.01)

=

(1) The inspectors observed and evaluated licensed operator performance in the Control Room during reactor shutdown on August 30, 2020
(2) The inspectors observed and evaluated licensed operator performance in the Control Room during reduced inventory on September 4, 2020

Licensed Operator Requalification Training/Examinations (IP Section 03.02) (1 Sample)

(1) The inspectors observed and evaluated PSLEG-LOR-20C-01 on August 11, 2020

71111.12 - Maintenance Effectiveness

Maintenance Effectiveness (IP Section 03.01) (2 Samples)

The inspectors evaluated the effectiveness of maintenance to ensure the following structures, systems, and components (SSCs) remain capable of performing their intended function:

(1) Chemical and volume control system on July 10, 2020
(2) Service water system on September 22, 2020

71111.13 - Maintenance Risk Assessments and Emergent Work Control

Risk Assessment and Management Sample (IP Section 03.01) (4 Samples)

The inspectors evaluated the accuracy and completeness of risk assessments for the following planned and emergent work activities to ensure configuration changes and appropriate work controls were addressed:

(1) Elevated risk for planned maintenance on component cooling water system and battery charger #4 on July 27, 2020
(2) Elevated risk for planned maintenance on high pressure safety injection and containment spray systems on July 28, 2020
(3) Elevated risk for a severe weather warning impacting the 2400V 1C startup transformer breaker maintenance activities on August 10, 2020
(4) Shutdown risk assessment during reduced inventory on September 8, 2020

71111.15 - Operability Determinations and Functionality Assessments

Operability Determination or Functionality Assessment (IP Section 03.01) (4 Samples)

The inspectors evaluated the licensee's justifications and actions associated with the following operability determinations and functionality assessments:

(1) Elevated Lake Michigan water level evaluation on July 21, 2020
(2) CV-0826 cotter pin misalignment evaluation on July 28, 2020
(3) Spalling of the concrete near containment vertical tendon V-140 anchorage on August 21, 2020
(4) Elevated inverter #4 temperatures evaluation on August 24, 2020

71111.19 - Post-Maintenance Testing

Post-Maintenance Test Sample (IP Section 03.01) (5 Samples)

The inspectors evaluated the following post maintenance test activities to verify system operability and functionality:

(1) EDG 1-2 start test following PCV-1489 replacement on July 21, 2020
(2) P-52 B component cooling water (CCW) baker testing on August 5, 2020
(3) CV-0826 control valve testing on August 6, 2020
(4) Core verification examination on September 25, 2020
(5) Nuclear instrument source range testing on September 28, 2020

71111.20 - Refueling and Other Outage Activities

Refueling/Other Outage Sample (IP Section 03.01) (1 Partial)

(1)

(Partial) The inspectors evaluated refueling outage 1R27 beginning August 30, 2020

71111.22 - Surveillance Testing

The inspectors evaluated the following surveillance tests:

Surveillance Tests (other) (IP Section 03.01)

(1) QO-15B, P-52B component cooling water (CCW) pump test on July 30, 2020
(2) RO-128-1, 1-1 EDG 24-hour load run test on August 8, 2020
(3) Left train safety injection system test on August 18, 2020
(4) RT-8C, engineering safeguards test on September 24, 2020

Inservice Testing (IP Section 03.01) (1 Sample)

(1) QO-19B - high pressure safety injection (HPSI) pump and emergency safety system check valve operability test, on July 15,

RADIATION SAFETY

71124.01 - Radiological Hazard Assessment and Exposure Controls

Radiological Hazard Assessment (IP Section 03.01) (1 Sample)

(1) The inspectors evaluated how the licensee identifies the magnitude and extent of radiation levels and the concentrations and quantities of radioactive materials and how the licensee assesses radiological hazards

Instructions to Workers (IP Section 03.02) (1 Sample)

(1) The inspectors evaluated radiological protection-related instructions to plant workers

Contamination and Radioactive Material Control (IP Section 03.03) (2 Samples)

The inspectors evaluated licensee processes for monitoring and controlling contamination and radioactive material:

(1) The inspectors observed surveys of potentially contaminated material leaving the radiologically controlled are.
(2) The inspectors observed workers exiting the radiologically controlled area

Radiological Hazards Control and Work Coverage (IP Section 03.04) (3 Samples)

The inspectors evaluated in-plant radiological conditions during facility walkdowns and observation of radiological work activities:

(1) Reactor vessel disassembly under RWP 20200433
(2) Scaffolding activities in containment under RWP 20200424
(3) Steam generator primary side activities under RWP 20200454

High Radiation Area and Very High Radiation Area Controls (IP Section 03.05) (2 Samples)

The inspectors evaluated licensee controls of the following High Radiation Areas and Very High Radiation Areas:

(1) Access to the reactor cavity, located inside containment
(2) Area surrounding the regenerative heat exchanger, located inside containment

Radiation Worker Performance and Radiation Protection Technician Proficiency (IP Section 03.06) (1 Sample)

(1) The inspectors evaluated radiation worker and radiation protection technician performance as it pertains to radiation protection requirements

71124.02 - Occupational ALARA Planning and Controls

Implementation of ALARA and Radiological Work Controls (IP Section 03.03) (2 Samples)

The inspectors evaluated the licensees communication of as low as is reasonably achievable ALARA and radiological work controls for the following work activities:

(1) Reactor vessel disassembly under RWP 20200433
(2) Steam generator primary side activities under RWP 20200454

Radiation Worker Performance (IP Section 03.04) (1 Sample)

The inspectors evaluated radiation worker and radiation protection technician performance during:

(1) Reactor vessel disassembly under RWP

OTHER ACTIVITIES - BASELINE

===71151 - Performance Indicator Verification

The inspectors verified licensee performance indicators submittals listed below:

MS07: High Pressure Injection Systems (IP Section 02.06)===

(1) Unit 1 (July 1, 2018-June 30, 2020)

MS09: Residual Heat Removal Systems (IP Section 02.08) (1 Sample)

(1) Unit 1 (July 1, 2018-June 30, 2020)

BI02: RCS Leak Rate Sample (IP Section 02.11) (1 Sample)

(1) Unit 1 (July 1, 2018-June 30, 2020)

INSPECTION RESULTS

No findings were identified.

EXIT MEETINGS AND DEBRIEFS

The inspectors verified no proprietary information was retained or documented in this report.

  • On October 28, 2020, the inspectors presented the integrated inspection results to Mr. D. Corbin, Site Vice President, and other members of the licensee staff.
  • On October 1, 2020, the inspectors presented the radiation protection inspection results to Mr. D. Corbin, Site Vice President, and other members of the licensee staff.

DOCUMENTS REVIEWED

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

71111.04

Corrective Action

Documents

CR-PLP-2020-

2120

Protected Equipment for 1-2 Emergency Diesel Generator

07/06/2020

CR-PLP-2020-

2126

Notification per MISO that Maintenance Activities Must be

Curtailed Due to Generation Availability Constraints

07/06/2020

CR-PLP-2020-

2149

During Performance of MO-7A-1, FI-0890, Diesel Generator

1-1 Service Water Flow was Reading 710gpm

07/08/2020

CR-PLP-2020-

298

VC-10 Suction Pressure Cycling From 52 psig to 58 psig on

PI-1676

07/21/2020

CR-PLP-2020-

2345

P-7B Service Water Pump Basket Strainer

07/25/2020

CR-PLP-2020-

2354

Corrosion Found During Rounds in Station Battery Number 2 07/26/2020

CR-PLP-2020-

2542

Induction Disc of the GE 12IAC53A101A Relay 151-106 X-

Phase was Stuck to the Backstop of the Time Dial/Lever

08/10/2020

Corrective Action

Documents

Resulting from

Inspection

CR-PLP-2020-

2129

NRC Identified the Floor Drain Cover on the South End of

the 1-2 Emergency Diesel Generator Ajar

07/06/2020

CR-PLP-2020-

2130

The NRC Identified that the 1-2 Emergency Diesel

Generator Vents are Dirty and may Require Cleaning

07/06/2020

CR-PLP-2020-

2131

NRC Identified a Potential Oil Leak on the North End of the

1-1 Emergency Diesel Generator

07/06/2020

CR-PLP-2020-

2329

NRC Identified There is Vegetation Growing on the North

and North East Sides of EX-17, Station Transformer 17

07/23/2020

CR-PLP-2020-

2330

NRC Identified Debris on the Floor of the 1-1 and 1-2 EDG

Rooms

07/23/2020

Drawings

M-221

Piping & Instrumentation Diagram, Spent Fuel Pool Cooling

System, Sheet 2

Miscellaneous

DBD 2.07

Design Basis Document for Spent Fuel Pool Cooling System

Procedures

AOP-26

Loss of Spent Fuel Pool Cooling

SOP-27

Fuel Pool System

71111.05

Corrective Action

Documents

CR-PLP-2020-

2416

PI-5350A, Fire Protection System Header Pressure was

Trending Down

07/30/2020

Fire Plans

Pre-Fire Plan 13B Charging Pump Rooms / Elevation 590'

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

Pre-Fire Plan 2

Cable Spreading Room; Elevation 607'

Pre-Fire Plan 26

Southwest Cable Penetration Room; Elevation 590' & 607'

Pre-Fire Plan 4

1-C Switchgear Room and Manhole 1, 2, & 3/Elevation 590'

71111.06

Corrective Action

Documents

CR-PLP-2020-

2461

Expansion Joint XJ-0421 Flood Barrier on HB-23-3" was

Identified as Having a Slit in the Joint Approximately Midway

Down the Southern Side of the Joint

08/04/2020

Miscellaneous

DBD 7.08

Design Basis Document Plant Protection Against Flooding

Procedures

AOP-39

Internal Plant Flooding

71111.08P

Corrective Action

Documents

Resulting from

Inspection

CR-PLP-2020-

03380

Ultrasonic Data Analysis of a Relevant Indication on

Penetration 34 on the Reactor Vessel Head

09/11/2020

CR-PLP-2020-

03427

Ultrasonic Data Analysis of a Relevant Indication on

Penetration 17 on the Reactor Vessel Head

09/13/2020

Procedures

54-ISI-400-023

NONDESTRUCTIVE EXAMINATION PROCEDURE

Multi-Frequency Eddy Current Examination of SG Tubing

2/12/2018

54-ISI-619-000

Automated Ultrasonic Examination of Open Tube RPV

Closure Head Penetrations-Palisades Specific

07/30/2020

CEP-NDE-0955

Visual Examination (VE) of Bare-Metal Surfaces

307

LMT-10-PAUT-

007

Fully Encoded Phased Array Ultrasonic Examination of

Dissimilar Metal Piping Welds

SEP-BAC-PLP-

001

Boric Acid Corrosion Control Program Engineering Nuclear

Programs Applicable Sites

71111.11Q Miscellaneous

SES-405

LOR Simulator Exam Scenario

Procedures

GOP-14

Reduced Inventory Checklist

GOP-8

Power Reduction and Plant Shutdown to Mode 2 or Mode 3

= 525°F

71111.12

Corrective Action

Documents

CR-PLP-2018-

05815

CV-0869, CAC VHX-4 SW Inlet, Valve Actuator Moved in the

Closed or Open Direction, but Valve Itself did not Move

11/09/2018

CR-PLP-2019-

04925

Baker Offline Motor Test Could not be Completed

2/16/2019

CR-PLP-2020-

2475

Discharge Accumulator for P-55C Charging Pump the "As

Found" Pressure of the Tank Bladder was 1287 psig

08/05/2020

CR-PLP-2020-

2476

Charging Pump "As Found" Pressure of the Tank Bladder

was 0.0 psig

08/05/2020

CR-PLP-2020-

Critical Service Water System (CSW) has Exceeded the

08/10/2020

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

2543

Near (a)(1) Threshold

CR-PLP-2020-

03184

Exceeded Maintenance Rule (MR) Performance Criteria

(PC) for Number of Functional Failures (#) in 24 Months for

the Main Steam System

09/07/2020

Miscellaneous

System Health

Report

Chemical & Volume Control System

2018

System Health

Report

Chemical & Volume Control System

2019

System Health

Report

CSW - Critical Service Water

Q2-2019

System Health

Report

CSW - Critical Service Water

Q2-2020

System Health

Report

CSW - Critical Service Water

Q4-2018

System Health

Report

CSW - Critical Service Water

Q4-2019

71111.13

Corrective Action

Documents

CR-PLP-2020-

2421

Removed from Service to Clean BS-1318, P-7A Service

Water Pump Basket Strainer

07/31/2020

CR-PLP-2020-

2551

Control Room Envelope

08/10/2020

CR-PLP-2020-

2552

Entered AOP-38 "Acts of Nature" due to High Wind Warning

on August 10, 2020

08/11/2020

CR-PLP-2020-

2555

Start Up Transformer 1-2 Electrical Maintenance Failed to

Finish the Work as Scheduled due to Acts of Nature

08/11/2020

Procedures

4.11

Safety Function Determination Program

71111.15

Corrective Action

Documents

CR-PLP-2020-

2009

Spalling of the Concrete Near Containment Vertical Tendon

V-140 Anchorage

06/24/2020

CR-PLP-2020-

2303

The Official Monthly Lake Michigan Elevation for June, as

Measured by the Calumet Harbor, Illinois Buoy, has

Exceeded the Assumed Starting Elevation for the Design

Basis Seiche Event

07/21/2020

CR-PLP-2020-

2316

Per CR-PLP-2020-02303 the Elevation of Lake Michigan in

the Area of the Plant has Exceeded the Assumed Design-

Basis Value for External Flooding Protection

07/22/2020

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

CR-PLP-2020-

2365

Adjustment on HIC-0826, Instrument Air Regulator for CV-

26

07/27/2020

CR-PLP-2020-

2366

EK-EK-1171, Component CLG E-54B Hi-Lo Temp

07/28/2020

CR-PLP-2020-

2389

Operator Noted EVI-27/D2, BTRY D02 DC Volt

Indicator/Undervolt RLY Reading 129 8V

07/29/2020

CR-PLP-2020-

2394

Cooling Fan M201 in ED-09 was Discovered to be Operating

Approximately 18°F Warmer than the Other 2 Fans

07/30/2020

CR-PLP-2020-

2395

Discovered in ED-09, Wire 821 on TC No. 3, Terminal J4-11

was Approximately 33°F Warmer than the Similar Wires

07/30/2020

CR-PLP-2020-

2399

EK-1132, Service Water Pump Basket Strainer D/P Alarms

not Actuating at Proper D/P

07/30/2020

CR-PLP-2020-

2405

RT-202B Precals for Channels 1 and 2 were Calibrated

Above Stated Ranges

07/30/2020

CR-PLP-2020-

2941

Service Water Piping Inside Containment

09/02/2020

CR-PLP-2020-

2943

Service Water Piping Inside Containment

09/02/2020

Corrective Action

Documents

Resulting from

Inspection

CR-PLP-2020-

2432

Service Water P-7C was Removed from Service to Clean

BS-1320, P-7C Service Water Pump Basket Strainer

08/01/2020

CR-PLP-2020-

2617

Editorial Error at the Bottom of the Tabulation on FSAR

Page 5.8-33

08/18/2020

Engineering

Changes

86917

Continued Operation when Lake Michigan Design Basis

Levels are Exceeded

289

Concrete Spalling Near V-140 Tendon Anchorage on

Containment Dome

87503

Supplement to EC 87289 on ACI Bearing Strength

87696

Supplement to EC 87289 and EC 87503 on Steel Plate

Applied Stresses

Engineering

Evaluations

87503

Supplement to EC 87289 on ACI Bearing Strength

Miscellaneous

PLP-RPT-15-

00010

Palisades Nuclear Plant Flooding Hazard Re-Evaluation

Report

Procedures

QO-5,

Valve Stroke Testing Data Sheet CV-0821, CV-0822,

08/29/2019

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

17

CV-0823, CV-0826

SOP-15

Palisades Nuclear Plant System Operating Procedure:

Service Water System

Work Orders

2922071

QO-5 -Vlv Test Proc (Inc Cont Isolation Vlvs)

05/26/2020

71111.19

Corrective Action

Documents

CR-PLP-2020-

2423

Fan M-201 for ED-09 Inverter #4 was Replaced

07/31/2020

CR-PLP-2020-

2424

Buildup of Dirt & Dust on the Bottom of M1, M2 &M201 Heat

Sinks

07/31/2020

CR-PLP-2020-

2426

Service Water P-7B was Removed from Service to Clean

BS-1319, P-7B Service Water Pump Basket Strainer

07/31/2020

CR-PLP-2020-

2911

SSC: CV-3057, Safety Injection Refueling Water Tank

(SIRWT) Isolation

09/02/2020

Miscellaneous

Control Room Logs

07/28/2020

Failure Modes

and Effects

Worksheet

NI-3, Wide Range Nuclear Instrument

09/13/2020

Procedures

EN-MA-125

Troubleshooting Control of Maintenance Activities

09/23/2020

EN-MA-134

Offline Motor Electrical Testing

07/27/2020

EN-RE-326

PWR Core Loading Verification

09/16/2020

EN-WM-105

Off-Line Baker Testing of Motor EMA-1208 for P-52B

07/27/2020

RFL-V-9

Core Verification

RI-99

Left Channel Nuclear Instrumentation Calibrations

SOP-22

Emergency Diesel Generator

Work Orders

00550833

NI-1/3A, Indication Failed - Replace Suspect 8D's "A8 & A9"

09/21/2020

2864755

EEQ Maint-Comp. Cooling. EMA-1208, P-52B Motor

07/27/2020

2872985

Core Mapping System Setup and Operation

09/16/2020

71111.20

Corrective Action

Documents

CR-PLP-2020-

2793

CV-0701, SG E-50A FW Regulating Valve

08/30/2020

CR-PLP-2020-

2795

Rod Deviation Alarms were Received

08/30/2020

CR-PLP-2020-

2796

RV-2006, Letdown Heat Exch E-58 Inlet Safety Relief and

Primary Coolant System (PCS)

08/30/2020

CR-PLP-2020-

2802

CV-2002 is not Opening with SV-2002B in AUTO

08/30/2020

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

CR-PLP-2020-

2820

Boric Acid Leak was Identified on CRD-12

08/30/2020

CR-PLP-2020-

2821

Boric Acid Leak was Identified on CRD-18

08/30/2020

CR-PLP-2020-

2894

Air Hoses Were Ran Thru the Equipment Hatch Without Ops

Alignment and Hose Labeling per GOP-14

09/01/2020

CR-PLP-2020-

03094

T-2, Condensate Storage Tank

09/05/2020

CR-PLP-2020-

262

Control Room Operators Entered AOP-36, Loss of

Component Cooling

09/10/2020

CR-PLP-2020-

03620

Breaker 25H9 (Generator Output Breaker) Failed to Close

from the Control Room

09/18/2020

Corrective Action

Documents

Resulting from

Inspection

CR-PLP-2020-

2838

NRC Identified - During the Containment Walkdown a

Puddle of Oil was Found on the 590' Clean Waste Receiver

Tank Room About Half Under the 607' Catwalk

08/31/2020

Procedures

EM-04-08

Mode 3, Tave = 525°F Shutdown Margin Calculation

08/24/2020

EN-RE-302

PWR Reactivity Maneuver - Reactivity Plan Form

08/25/2020

GOP-14

Shutdown Cooling Operations

71111.22

Corrective Action

Documents

CR-PLP-2020-

2471

PI-1475, Diesel Generator K-6A Fuel Oil Pressure was at 25

psig

08/05/2020

CR-PLP-2020-

2472

RO-128-1, Diesel Generator 1-1 24 Hour Load Run, Table

for Acceptance Criteria

08/05/2020

CR-PLP-2020-

2834

LLRT for Penetration MZ-42, Could not Establish <10sccm

on Step 5.2.13(h)2 and 3, Actual Reading was 30 sccm

08/31/2020

CR-PLP-2020-

2996

Leakage from Containment Penetration #15 was 8400 sccm

and Exceeded the 5000 sccm Troubleshooting Guideline

09/04/2020

CR-PLP-2020-

03806

CV-0847, SW Supply to Cont (MZ-12)

09/25/2020

Procedures

QO-1

Safety Injection System

QO-15

Inservice Test Procedure - Component Cooling Water

Pumps

QO-19B

Inservice Test Procedure - HPSI Pumps and Emergency

Safety System Check Valve Operability Test

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

RT-8C

Engineered Safeguards System - Left Channel

09/14/2020

Work Orders

2871419

RT-8C - Engineered Safeguards System - Left Channel

09/14/2020

2928850

QO-15B, Inservice Test Procedure - Component Cooling

Pump P-52B

07/27/2020

71124.01

Procedures

EN-RP-101

Access Control for Radiologically Controlled Areas

EN-RP-106-01

Radiological Survey Guidlines

EN-RP-122

Alpha Monitoring

EN-RP-131

Air Sampling

Radiation Work

Permits (RWPs)

200424

Scaffolding Activities in Containment

200433

Refuel Project: Disassembly of the Reactor Head and

Associated Work Activities

200454

Steam Generator Primary Side Activities

71124.02

ALARA Plans

200424

Scaffolding Activities in Containment

200433

Refuel Project: Disassembly of the Reactor Head and

Associated Work Activities

200454

Steam Generator Primary Side Activities

Procedures

EN-RP-110

ALARA Program

71151

Miscellaneous

NRC Performance Indicators 2Q2020

04/01/2020 -

06/30/2020

NRC Performance Indicators 1Q2020

01/01/2020 -

03/31/2020

NRC Performance Indicators 4Q2019

10/01/2019 -

2/31/2019

NRC Performance Indicators 3Q2019

07/01/2019 -

09/330/2019

NRC Performance Indicators 2Q2019

04/01/2019 -

06/30/2019

NRC Performance Indicators 4Q2018

10/01/2018 -

2/31/2018

NRC Performance Indicators 3Q2018

07/01/2018 -

09/30/2018

Procedures

NRC Performance Indicators 1Q2019

01/01/2019 -

03/31/2019

71152

Corrective Action

CR-PLP-2020-

CV-0826 CCW HX E-54B SW Outlet Pinned Incorrectly

07/27/2020

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

Documents

2365

Procedures

QO-5

Valve Test Procedure (Includes Containment Isolation

Valves)

109

SOP-15

Service Water System

70