ML17031A347: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
(Created page by program invented by StriderTol)
Line 17: Line 17:


=Text=
=Text=
{{#Wiki_filter:STATION: SYSTEM: TASK: TASK NUMBER: JPM NUMBER: OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SALEM Reactor Coolant System Measure Leakage to the Containment Sump N0020080101 15-01 NRC RO A1-1 KIA NUMBER: 2.1.25 ALTERNATE PATH: D IMPORTANCE FACTOR: 3.9 APPLICABILITY:
{{#Wiki_filter:OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION:                SALEM SYSTEM:                Reactor Coolant System TASK:                  Measure Leakage to the Containment Sump TASK NUMBER:            N0020080101 JPM NUMBER:            15-01 NRC RO A1-1 ALTERNATE PATH:      D                                      KIA NUMBER:     ~~~~~~~~~~
RO EOD RO[]] STAD SRoD EVALUATION SETTING/METHOD:
2.1.25 IMPORTANCE FACTOR:               3.9 APPLICABILITY:                                                                   RO             SRO EOD           RO[]]             STAD           SRoD EVALUATION SETTING/METHOD:               Classroom
Classroom  


==REFERENCES:==
==REFERENCES:==
S2.0P-AR.ZZ-0003, Overhead Annunciators Window C, Rev. 19 S2.0P-SO.RC-0004, Identifying and Measuring Leakage, Rev. 16 (Both Rev checked 8-9-16)
TOOLS AND EQUIPMENT:            Calculator VALIDATED JPM COMPLETION TIME:                      10 min TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS:                            N/A Developed By:                    G Gauding                              Date: 8-9-16 Instructor Validated By:                    R Evans I N Mulford                    Date: 9-22-16 I 9-29-16 SME or Instructor ~
Approved By:
Oper~ng ~a~r Approved By:
Ope~rtment ACTUAL JPM COMPLETION TIME:
ACTUAL TIME CRITICAL COMPLETION TIME:
PERFORMED BY:
GRADE:    D    SAT      D    UNSAT REASON, IF UNSATISFACTORY:
EVALUATOR'S SIGNATURE:                                                          DATE:
Page 1 of 7 PSEG Restricted- Possession Requires Specific Permission From Nuclear Training


S2.0P-AR.ZZ-0003, Overhead Annunciators Window C, Rev. 19 S2.0P-SO.RC-0004, Identifying and Measuring Leakage, Rev. 16 (Both Rev checked 8-9-16) TOOLS AND EQUIPMENT:
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME:   ~~~~~~~~~~~~~~
Calculator VALIDATED JPM COMPLETION TIME: 10 min TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: Developed By: Validated By: Approved By: Approved By: G Gauding Instructor R Evans I N Mulford SME or Instructor ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY:
DATE:   ~~~~~~~~~~~~~~
EVALUATOR'S SIGNATURE:
SYSTEM:                         Reactor Coolant System TASK:                           Measure Leakage to the Containment Sump TASK NUMBER:                   N0020080101 SIMULATOR SETUP                 N/A INITIAL CONDITIONS:
Page 1 of 7 N/A Date: 8-9-16 Date: 9-22-16 I 9-29-16 DATE: PSEG Restricted-Possession Requires Specific Permission From Nuclear Training SRO OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME:
Unit 2 is operating at 100% power, steady state, SOL.
DATE:
At 0015, OHA C-2 CNTMT SUMP PMP START unexpectedly annunciates, along with OHA A-41.
SYSTEM: Reactor Coolant System TASK: Measure Leakage to the Containment Sump TASK NUMBER: N0020080101 SIMULATOR SETUP N/A INITIAL CONDITIONS:
The Aux typewriter shows 21 containment sump pump has started. 2 minutes later, OHA C-2 clears, OHA A-41 annunciates, and the Aux typewriter shows 21 containment sump pump has stopped. The plant remains stable, no indications of a RCS leak are apparent, and no operations have been performed which would cause containment sump level to rise.
Unit 2 is operating at 100% power, steady state, SOL. At 0015, OHA C-2 CNTMT SUMP PMP START unexpectedly annunciates, along with OHA A-41. The Aux typewriter shows 21 containment sump pump has started. 2 minutes later, OHA C-2 clears, OHA A-41 annunciates, and the Aux typewriter shows 21 containment sump pump has stopped. The plant remains stable, no indications of a RCS leak are apparent, and no operations have been performed which would cause containment sump level to rise. INITIATING CUE: You are the RO. Calculate the leak rate into the Containment Sump by performing Section 5.3 of S2.0P-SO.RC-0004, Identifying and Measuring Leakage. Successful Completion Criteria:
INITIATING CUE:
You are the RO. Calculate the leak rate into the Containment Sump by performing Section 5.3 of S2.0P-SO.RC-0004, Identifying and Measuring Leakage.
Successful Completion Criteria:
: 1. All critical steps completed.
: 1. All critical steps completed.
: 2. All sequential steps completed in order. 3. All time-critical steps completed within allotted time. 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made (and NRC concurrence is obtained}.
: 2. All sequential steps completed in order.
: 3. All time-critical steps completed within allotted time.
: 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made (and NRC concurrence is obtained}.
Task Standard for Successful Completion:
Task Standard for Successful Completion:
: 1. Calculate leakage into Containment Sump of 0.85-1.0 gpm. Page 2 of 7 PSEG Restricted-Possession Requires Specific Permission From Nuclear Training SYSTEM: Reactor Coolant System TASK: Measure Leakage to the Containment Sump STEP STEP (*Denotes a Critical Step)
: 1. Calculate leakage into Containment Sump of 0.85-1.0 gpm.
* NO. Provide blank copy of 82.0P-SO.RC-0004, and marked up copy of Attachment
Page 2 of 7 PSEG Restricted- Possession Requires Specific Permission From Nuclear Training
: 1. SO.RC-4 !E either Containment Sump Pump 5.3.1 AUTO starts, THEN RECORD the following on Attachment 1, Section 2.0:
 
* Operating Containment Sump ... Pump Number
OPERATOR TRAINING PROGRAM NAME: ~~~~~~~~~~-
* Time of pump start
JOB PERFORMANCE MEASURE DATE: ~~~~~~~~~~
* SO.RC-4 CALCULATE elapsed time in minutes 5.3.2 between start time and previous Containment Sump Pump stop time AND RECORD on Attachment 1, Section 2.0.
SYSTEM: Reactor Coolant System TASK:   Measure Leakage to the Containment Sump STEP                                                                                   COMMENTS STEP             (*Denotes a Critical Step)                                                           EVAL    (Required for UNSAT
* SO.RC-4 ENSURE no draining, sampling, or 5.3.3 liquid additions to Containment Sump have occurred during selected time frame. OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STANDARD Records 21 Cont Sump Records time of pump start as 0015 Calculates elapsed time in minutes between start time and previous Containment Sump Pump stop time and records on Attachment 1, Section 2.0 by using previous stop time of 1855 yesterday, and with cue of 0015 today determines elapsed time is 320 minutes. Determines from initial conditions that no draining, sampling, or liquid additions to Containment Sump have occurred during selected time frame. Page 3 of 7 NAME:
* NO.                                                                 STANDARD                          S/U        Evaluation)
DATE:
Provide blank copy of 82.0P-SO.RC-0004, and marked up copy of Attachment 1.
COMMENTS EVAL (Required for UNSAT S/U Evaluation)
SO.RC-4   !E either Containment Sump Pump 5.3.1     AUTO starts, THEN RECORD the following on Attachment 1, Section 2.0:
PSEG Restricted-Possession Requires Specific Permission From Nuclear Training SYSTEM: Reactor Coolant System TASK: Measure Leakage to the Containment Sump STEP STEP (*Denotes a Critical Step)
Records 21 Cont Sump
* NO. SO.RC-4 CALCULATE Containment Sump 5.3.4 Leak Rate using Attachment
                    ...
: 3.
* Operating Containment Sump Pump Number
* SO.RC-4 RECORD Containment Sump Pump 5.3.5 stop time and date on Attachment 1, Section 2.0. SO.RC-4 !E leakage to Containment Sump 5.3.6 exceeds 1.0 gpm AND Unit in Modes 1-4, THEN: A. INITIATE S2.0P-ST.RC-0008(Q), Reactor Coolant Water Inventory Balance. B. REFER to Technical Specification 3.4.7.2. OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STANDARD Calculates Containment Sump Leak Rate using Attachment 3 (page 1 of 2), and determines the 320 minute line crosses the 0.9 gpm leak rate line. Note: Due to no increment between 300 and 350 minutes, extrapolation of data may result in leak rate slightly above or below 0.9 gpm. However, the leakrate MUST be determined to be within the bounding numbers for actions required >0.85 gpm (to initiate Section 5.6) and >1.0 gpm (to initiate S2.0P-ST.RC-0008) Records Containment Sump Pump stop time as 0017 and todays date on Attachment 1, Section 2.0. Determines leakage to Containment Sump does not exceed 1.0 gpm Page 4 of 7 NAME:
    *
DATE:
* Time of pump start                 Records time of pump start as 0015 SO.RC-4   CALCULATE elapsed time in minutes          Calculates elapsed time in minutes 5.3.2     between start time and previous            between start time and previous Containment Sump Pump stop time             Containment Sump Pump stop time and AND RECORD on Attachment 1,                 records on Attachment 1, Section 2.0 by Section 2.0.                                using previous stop time of 1855
COMMENTS EVAL (Required for UNSAT S/U Evaluation)
* yesterday, and with cue of 0015 today determines elapsed time is 320 minutes.
PSEG Restricted-Possession Requires Specific Permission From Nuclear Training SYSTEM: Reactor Coolant System TASK: Measure Leakage to the Containment Sump STEP STEP (*Denotes a Critical Step)
SO.RC-4    ENSURE no draining, sampling, or 5.3.3    liquid additions to Containment Sump        Determines from initial conditions that have occurred during selected time          no draining, sampling, or liquid additions frame.                                      to Containment Sump have occurred during selected time frame.
* NO. SO.RC-4 !E leakage to Containment Sump 5.3.7 exceeds 0.85 gpm, THEN INITIATE Section 5.6 of this procedure.
Page 3 of 7 PSEG Restricted- Possession Requires Specific Permission From Nuclear Training
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STANDARD Determines leakage to Containment Sump does exceed 0.85 gpm, and initiates Section 5.6 of procedure.
 
OPERATOR TRAINING PROGRAM NAME: ~~~~~~~~~~
JOB PERFORMANCE MEASURE DATE: ~~~~~~~~~~-
SYSTEM: Reactor Coolant System TASK:   Measure Leakage to the Containment Sump STEP                                                                                   COMMENTS STEP             (*Denotes a Critical Step)                                                           EVAL    (Required for UNSAT
* NO.                                                                 STANDARD                          S/U        Evaluation)
SO.RC-4     CALCULATE Containment Sump                 Calculates Containment Sump Leak 5.3.4     Leak Rate using Attachment 3.             Rate using Attachment 3 (page 1 of 2),
* and determines the 320 minute line crosses the 0.9 gpm leak rate line.
Note: Due to no increment between 300 and 350 minutes, extrapolation of data may result in leak rate slightly above or below 0.9 gpm. However, the leakrate MUST be determined to be within the bounding numbers for actions required
                                                              >0.85 gpm (to initiate Section 5.6) and
                                                              >1.0 gpm (to initiate S2.0P-ST.RC-0008)
SO.RC-4    RECORD Containment Sump Pump              Records Containment Sump Pump stop 5.3.5      stop time and date on Attachment 1,        time as 0017 and todays date on Section 2.0.                              Attachment 1, Section 2.0.
SO.RC-4    !E leakage to Containment Sump              Determines leakage to Containment 5.3.6      exceeds 1.0 gpm AND Unit in Modes          Sump does not exceed 1.0 gpm 1-4, THEN:
A. INITIATE S2.0P-ST.RC-0008(Q),
Reactor Coolant Water Inventory Balance.
B. REFER to Technical Specification 3.4.7.2.
Page 4 of 7 PSEG Restricted- Possession Requires Specific Permission From Nuclear Training
 
OPERATOR TRAINING PROGRAM NAME: ~~~~~~~~~~-
JOB PERFORMANCE MEASURE DATE: ~~~~~~~~~~-
SYSTEM: Reactor Coolant System TASK:   Measure Leakage to the Containment Sump STEP                                                                                   COMMENTS STEP           (*Denotes a Critical Step)                                                           EVAL    (Required for UNSAT
* NO.                                                                 STANDARD                        S/U        Evaluation)
SO.RC-4   !E leakage to Containment Sump             Determines leakage to Containment 5.3.7     exceeds 0.85 gpm, THEN INITIATE           Sump does exceed 0.85 gpm, and Section 5.6 of this procedure.            initiates Section 5.6 of procedure.
Terminate JPM when procedure is returned to evaluator.
Terminate JPM when procedure is returned to evaluator.
Page 5 of 7 NAME:
Page 5 of 7 PSEG Restricted- Possession Requires Specific Permission From Nuclear Training
DATE:
 
COMMENTS EVAL (Required for UNSAT S/U Evaluation)
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below.
PSEG Restricted-Possession Requires Specific Permission From Nuclear Training OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation.
  ~  W\   ~      1. Task description and number, JPM description and number are identified.
Prior to JPM usage, revalidate JPM using steps 8 and 11 below. W\ vv M ,,/ \µ N'\ \y m d Vv N'l A/ \JV Md \f\ M / N"\ d
vv M ,,/        2. Knowledge and Abilities (KIA) references are included.
: 1. Task description and number, JPM description and number are identified.
  \µ N'\  ~      3. Performance location specified. (in-plant, control room, or simulator)
: 2. Knowledge and Abilities (KIA) references are included.
  \y md            4. Initial setup conditions are identified.
: 3. Performance location specified. (in-plant, control room, or simulator)
Vv  N'l  A/    5. Initiating and terminating Cues are properly identified.
: 4. Initial setup conditions are identified.
\JV Md            6. Task standards identified and verified by SME review.
: 5. Initiating and terminating Cues are properly identified.
\f\ M /            7. Critical steps meet the criteria for critical steps and are identified with an asterisk(*).
: 6. Task standards identified and verified by SME review. 7. Critical steps meet the criteria for critical steps and are identified with an asterisk(*).
  ~ N"\ d          8. Verify the procedure referenced by this JPM matches the most current revision of that procedure: Procedure Rev. Jj_ Date t./* z. i. ' t IP
: 8. Verify the procedure referenced by this JPM matches the most current revision of that procedure:
                                                            /C, N'\~        9. Pilot test the JPM:
Procedure Rev. Jj_ Date t./* z. i. 't IP /C, 9. Pilot test the JPM: a. verify Cues both verbal and visual are free of conflict, and b. ensure performance time is accurate.
: a. verify Cues both verbal and visual are free of conflict, and
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructor: SME/lnstructoro
: b. ensure performance time is accurate.
{)fLtj cl Date: ,,z.
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM.
Date: _'\ .___{ J._q _hb_ SME/lnstructor:
____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.
____________
SME/lnstructor: ~                                                Date:  ,,z.  ~''I.I SME/lnstructoro   {)fLtj ~;l{Vcl                                                J._q_hb_
_ Date: _____ _ Page 6 of 7 PSEG Restricted-Possession Requires Specific Permission From Nuclear Training INITIAL CONDITIONS:
Date: _ ' \.___{
Unit 2 is operating at 100% power, steady state, SOL. At 0015, OHA C-2 CNTMT SUMP PMP START unexpectedly annunciates, along with OHA A-41. The Aux typewriter shows 21 containment sump pump has started. 2 minutes later, OHA C-2 clears, OHA A-41 annunciates, and the Aux typewriter shows 21 containment sump pump has stopped. The plant remains stable, no indications of a RCS leak are apparent, and no operations have been performed which would cause containment sump level to rise. INITIATING CUE: You are the RO. Calculate the leak rate into the Containment Sump by performing Section 5.3 of S2.0P-SO.RC-0004, Identifying and Measuring Leakage. Page 7 of 7 PSEG Restricted-Possession Requires Specific Permission From Nuclear Training STATION: SYSTEM: TASK: TASK NUMBER: JPM NUMBER: OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SALEM Conduct of Operations Calculate Shutdown Margin N1200030301 15-01 NRC RO A1-2 KIA NUMBER: 2.1.43 ALTERNATE PATH: D IMPORTANCE FACTOR: 4.1 APPLICABILITY:
SME/lnstructor: _ _ _ _ _ _ _ _ _ _ _ __                          Date: _ _ _ _ __
RO EOCJ R0[8J STAL] SROCJ EVALUATION SETTING/METHOD:
Page 6 of 7 PSEG Restricted- Possession Requires Specific Permission From Nuclear Training
Classroom  
 
INITIAL CONDITIONS:
Unit 2 is operating at 100% power, steady state, SOL.
At 0015, OHA C-2 CNTMT SUMP PMP START unexpectedly annunciates, along with OHA A-41.
The Aux typewriter shows 21 containment sump pump has started. 2 minutes later, OHA C-2 clears, OHA A-41 annunciates, and the Aux typewriter shows 21 containment sump pump has stopped. The plant remains stable, no indications of a RCS leak are apparent, and no operations have been performed which would cause containment sump level to rise.
INITIATING CUE:
You are the RO. Calculate the leak rate into the Containment Sump by performing Section 5.3 of S2.0P-SO.RC-0004, Identifying and Measuring Leakage.
Page 7 of 7 PSEG Restricted- Possession Requires Specific Permission From Nuclear Training
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION:                SALEM SYSTEM:                Conduct of Operations TASK:                  Calculate Shutdown Margin TASK NUMBER:            N1200030301 JPM NUMBER:            15-01 NRC RO A1-2 ALTERNATE PATH:      D                                  KIA NUMBER:   ~~~~~~~~~~
2.1.43 IMPORTANCE FACTOR:           4.1 APPLICABILITY:                                                               RO           SRO EOCJ         R0[8J           STAL]         SROCJ EVALUATION SETTING/METHOD:               Classroom


==REFERENCES:==
==REFERENCES:==
SC.RE-ST.ZZ-0002(0), Rev. 23 SHUTDOWN MARGIN CALCULATION S2.RE-RA.ZZ-0016(Q), Rev. 8 CURVE BOOK (both checked 8-9-16)
TOOLS AND EQUIPMENT:          None VALIDATED JPM COMPLETION TIME:                    30 min TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS:                    50 minutes Developed By:                    G Gauding                        Date: 8-9-16 Instructor Validated By:                R Evans I N Mulford                  Date: 9-22-16 I 9-29-16 SME  or lnstructo~l Approved By:
Tra~1ent Approved By:
Operbrtment ACTUAL JPM COMPLETION TIME:
ACTUAL TIME CRITICAL COMPLETION TIME:
PERFORMED BY:
GRADE:    D  SAT      D    UNSAT REASON, IF UNSATISFACTORY:
EVALUATOR'S SIGNATURE:                                                    DATE:
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 1 of 7


SC.RE-ST.ZZ-0002(0), Rev. 23 SHUTDOWN MARGIN CALCULATION S2.RE-RA.ZZ-0016(Q), Rev. 8 CURVE BOOK (both checked 8-9-16) TOOLS AND EQUIPMENT:
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME:     ~~~~~~~~~~~~~~-
None VALIDATED JPM COMPLETION TIME: 30 min TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: Developed By: Validated By: Approved By: Approved By: G Gauding Instructor R Evans I N Mulford SME or Operbrtment ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY:
DATE:
EVALUATOR'S SIGNATURE:
SYSTEM:               Conduct of Operations TASK:                 Calculate Shutdown Margin TASK NUMBER:           N1200030301 INITIAL CONDITIONS:           - Unit 2 Reactor Power is 100%.
50 minutes Date: 8-9-16 Date: 9-22-16 I 9-29-16 DATE: PSEG Restricted
                      - All Control Rod Group Demand Counters are at 227 steps.
-Possession Requires Specific Permission from Nuclear Training Page 1 of 7 SRO OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME:
                      - Current boron concentration is 300 ppm.
DATE: SYSTEM: Conduct of Operations TASK: Calculate Shutdown Margin TASK NUMBER: N1200030301 INITIAL CONDITIONS:  
                      - Current core burn up is 10,000 EFPH.
-Unit 2 Reactor Power is 100%. INITIATING CUE: -All Control Rod Group Demand Counters are at 227 steps. -Current boron concentration is 300 ppm. -Current core burn up is 10,000 EFPH. -Control Rod 105 was been declared INOPERABLE at 1000 today due to not moving out during a rod exercise test. You have been directed to perform a Shutdown Margin Calculation IAW SC.RE-ST.ZZ-0002 to satisfy the action requirement of TSAS 3.1.3.1 Action c.3. -Control Rod 105 has been identified as trippable and is currently at 214 steps. The current time is 1010. This is a time critical JPM. Time will commence when you are provided with the applicable procedures.
                      - Control Rod 105 was been declared INOPERABLE at 1000 today due to not moving out during a rod exercise test. You have been directed to perform a Shutdown Margin Calculation IAW SC.RE-ST.ZZ-0002 to satisfy the action requirement of TSAS 3.1.3.1 Action c.3.
When performing calculation, the CRS directs you to use only the tables as directed by SC.RE-ST.ZZ-0002, do not use Figures. Successful Completion Criteria:
                      - Control Rod 105 has been identified as trippable and is currently at 214 steps.
INITIATING CUE:
The current time is 1010.
This is a time critical JPM. Time will commence when you are provided with the applicable procedures.
When performing calculation, the CRS directs you to use only the tables as directed by SC.RE-ST.ZZ-0002, do not use Figures.
Successful Completion Criteria:
: 1. All critical steps completed
: 1. All critical steps completed
: 2. All sequential steps completed in order 3. All time-critical steps completed within allotted time 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made. Task Standard for Successful Completion:
: 2. All sequential steps completed in order
: 1. Perform SOM calculation and determine SOM is -2441 (+/-5 pcm) and SAT. PSEG Restricted  
: 3. All time-critical steps completed within allotted time
-Possession Requires Specific Permission from Nuclear Training Page 2 of 7 OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: DATE:
: 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made.
System: Conduct of Operations Task: Calculate Shutdown Margin
Task Standard for Successful Completion:
* STEP NO. 3.0 5.1 5.1.1.C Att. 3 2.1 Att. 3 3.0 STEP STANDARD EVAL COMMENTS (*Denotes a Critical Step) SIU (Required for UNSAT evaluation)
: 1. Perform SOM calculation and determine SOM is -2441 (+/- 5 pcm) and SAT.
Obtains copy of procedure SC.RE-Provide Rev. 23 of surveillance.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 2 of 7
 
OPERATOR TRAINING PROGRAM                   NAME: ~~~~~~~~~~-
JOB PERFORMANCE MEASURE                   DATE: ~~~~~~~~~~-
System:   Conduct of Operations Task:     Calculate Shutdown Margin
* STEP NO.                       STEP                                 STANDARD                   EVAL               COMMENTS
(*Denotes a Critical Step)                                                     SIU     (Required for UNSAT evaluation)
Obtains copy of procedure SC.RE-           Provide Rev. 23 of surveillance.
ST.ZZ-0002(0).
ST.ZZ-0002(0).
Obtains copy of 82.RE-RA.ZZ-0016 Curve Book. Provide Rev. 8 of Curve Book. Evaluator:
Obtains copy of 82.RE-RA.ZZ-0016                                                                                             I Curve Book.                                 Provide Rev. 8 of Curve Book.
MARK start time of JPM: Reviews and signs off Precautions and Reviews Precautions  
I Evaluator: MARK start time of JPM:
& Limitations and Limitations Section 3.0 signs off Steps 3.1 -3.7. SELECT the applicable step below (e.g. Determines 5.1.1.C is the correct step 5.1.1.A):
3.0    Reviews and signs off Precautions and     Reviews Precautions & Limitations and Limitations Section 3.0                   signs off Steps 3.1 - 3.7.
for the current conditions, which is to complete Attachment
5.1  SELECT the applicable step below (e.g.     Determines 5.1.1.C is the correct step 5.1.1.A):                                 for the current conditions, which is to complete Attachment 3.
: 3. !E SOM is to be verified (per T/S Refers to Attachment
5.1.1.!E SOM     is to be verified (per T/S       Refers to Attachment 3.
: 3. 4.1.1.1.1.a) with reactor critical (Mode 1 or 2) and one or more control rods are inoperable, THEN COMPLETE Attachment
4.1.1.1.1.a) with reactor critical (Mode 1 or 2) and one or more control rods are inoperable, THEN COMPLETE Attachment 3.
: 3. The reactor is in Mode 1 or Mode 2 Determines Unit is in Mode 1. with kett .:::. 1.0 Precautions and Limitations:
Att. 3   The reactor is in Mode 1 or Mode 2         Determines Unit is in Mode 1.
Section Reviews and signs steps 3.1-3.5. 3.0 PSEG Restricted  
with kett .:::. 1.0 2.1 Att. 3  Precautions and Limitations: Section       Reviews and signs steps 3.1-3.5.
-Possession Requires Specific Permission from Nuclear Training Page 3 of 7 I I I System: Conduct of Operations Task: Calculate Shutdown Margin
3.0  3.0 I
* STEP NO. STEP (*Denotes a Critical Step)
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 3 of 7
* Att.3 Section 4 contains the data points Section required and the calculations to 4.1 determine shutdown margin.
 
* Att. 3 Section 4.2
OPERATOR TRAINING PROGRAM                NAME: _ _ _ _ _ _ _ _ _ __
* Att. 3 Section 4.3 OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STANDARD Determines the following data and calculations:
JOB PERFORMANCE MEASURE                  DATE: _ _ _ _ _ _ _ _ _ __
4.1.1 100% 4.1.2 300 ppm 4.1.3 D@ 227 steps 4.1.4 10,000 EFPH 4.1.5 0 4.1.6 1 4.2.1 -3841 4.2.2 -3335 4.2.3 728 4.2.4 0 4.2.5 500 4.2.6 0 4.2.7 -5948 4.3.1 -5948 4.3.2 645 4.3.3 120 4.3.4 2742 4.3.5 -2441 NAME: __________
System:     Conduct of Operations Task:       Calculate Shutdown Margin
_ DATE: __________
* STEP NO.                   STEP                                 STANDARD                  EVAL                COMMENTS
_ EVAL COMMENTS S/U (Required for UNSAT evaluation)
(*Denotes a Critical Step)                                                S/U      (Required for UNSAT evaluation)
PSEG Restricted  
Att.3   Section 4 contains the data points     Determines the following data and
-Possession Requires Specific Permission from Nuclear Training Page 4 of 7 I System: Conduct of Operations Task: Calculate Shutdown Margin
* Section required and the calculations to       calculations:
* STEP NO. STEP OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STANDARD .. NAME: __________
4.1   determine shutdown margin.             4.1.1 100%
_ DATE: __________
4.1.2 300 ppm 4.1.3 D@ 227 steps 4.1.4 10,000 EFPH 4.1.5 0                                                                           I 4.1.6 1 Att. 3                                          4.2.1 -3841
_ EVAL COMMENTS (*Denotes a Critical Step) SIU (Required for UNSAT evaluation) 4.4 *
* Section                                          4.2.2 -3335 4.2                                            4.2.3 728 4.2.4 0 4.2.5 500 4.2.6 0 4.2.7 -5948 Att. 3                                          4.3.1 -5948
* Att 4 Acceptance Criteria Reviews required SOM in MODE 1 or 2 of -1300 pcm and initials 4.4.1. 4.4.1 IS THE SOM (Item 4.3.5) EQUAL TO OR MORE NEGATIVE THAN Determines calculated SOM is SAT and (-)1300 PCM? initials SAT. Evaluator:
* Section                                          4.3.2 645 4.3                                            4.3.3 120 4.3.4 2742 4.3.5 -2441 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 4 of 7
MARK stop time of JPM: when procedures are returned to proctor. Total time from START to STOP is 50 minutes or less. Terminating Cue: Once operator has returned procedures to proctor, terminate JPM. PSEG Restricted  
 
-Possession Requires Specific Permission from Nuclear Training Page 5 of 7 I I OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation.
                                                                                                                                .
Prior to JPM usage, revalidate JPM using steps 8 and 11 below. f\M. 1. Task description and number, JPM description and number are identified.
OPERATOR TRAINING PROGRAM                  NAME: _ _ _ _ _ _ _ _ _ __
f'M. -( 2. Knowledge and Abilities (KIA) references are included.
JOB PERFORMANCE MEASURE                    DATE: _ _ _ _ _ _ _ _ _ __
N"' / 3. Performance location specified. (in-plant, control room, or simulator)
System:   Conduct of Operations Task:     Calculate Shutdown Margin
N"\ / 4. Initial setup conditions are identified.
* STEP NO.                 STEP                                 STANDARD                 EVAL               COMMENTS
(*Denotes a Critical Step)                                                 SIU     (Required for UNSAT evaluation) 4.4 Att 4 Acceptance Criteria             Reviews required SOM in MODE 1 or 2 of -1300 pcm and initials 4.4.1.
* 4.4.1 IS THE SOM (Item 4.3.5) EQUAL I
TO OR MORE NEGATIVE THAN               Determines calculated SOM is SAT and                                             I
(-)1300 PCM?                           initials SAT.
Evaluator:     MARK stop time of JPM:               when procedures are returned to proctor.
* Total time from START to STOP is 50 minutes or less.
Terminating Cue: Once operator has returned procedures to proctor, terminate JPM.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 5 of 7
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below.
f\M. ~        1. Task description and number, JPM description and number are identified.
f'M. -(     2. Knowledge and Abilities (KIA) references are included.
N"' /       3. Performance location specified. (in-plant, control room, or simulator)
N"\ /       4. Initial setup conditions are identified.
: 5. Initiating and terminating Cues are properly identified.
: 5. Initiating and terminating Cues are properly identified.
: 6. Task standards identified and verified by SME review. 7. Critical steps meet the criteria for critical steps and are identified with an asterisk (*). 8. Verify the procedure referenced by this JPM matches the most current revision of that procedure:
: 6. Task standards identified and verified by SME review.
Procedure Date 7-z-z-1 11> 13 9. Pilot test the JPM: a. verify Cues both verbal and visual are free of conflict, and b. ensure performance time is accurate.
: 7. Critical steps meet the criteria for critical steps and are identified with an asterisk (*).
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructor: SME/lnstructor:C/
: 8. Verify the procedure referenced by this JPM matches the most current revision of that procedure: Procedure Rev.~ Date 7- z-z- 1 11>
1£,(A SME/lnstructor:  
13
-------------
: 9. Pilot test the JPM:
Date: )-2 <: -t /, Date:
: a. verify Cues both verbal and visual are free of conflict, and
__ Date: ------PSEG Restricted  
: b. ensure performance time is accurate.
-Possession Requires Specific Permission from Nuclear Training Page 6 of 7 INITIAL CONDITIONS:  
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM.
-Unit 2 Reactor Power is 100%. -All Control Rod Group Demand Counters are at 227 steps. -Current boron concentration is 300 ppm. -Current core burnup is 10,000 EFPH. -Control Rod 105 was been declared INOPERABLE at 1000 today due to --not moving out during a rod exercise test. You have been directed to perform a Shutdown Margin Calculation IAW SC.RE-ST.ZZ-0002 to satisfy the action requirement of TSAS 3.1.3.1 Action c.3. -Control Rod 105 has been identified as trippable and is currently at 214 steps. INITIATING CUE: The current time is 1010. This is a time critical JPM. Time will commence when you are provided with the applicable procedures.
____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.
When performing calculation, the CRS directs you to use only the Tables as directed by SC.RE-ST.ZZ-0002, do not use Figures. PSEG Restricted  
                      ~                                              Date:  )- 2 <: -t/,
-Possession Requires Specific Permission from Nuclear Training Page 7 of 7 STATION: SYSTEM: TASK: TASK NUMBER: JPM NUMBER: OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SALEM 1 & 2 Chemical and Volume Control Demonstrate the Operability of the RWST and/or the BASTs N0040420201 15-01 NRC RO Admin A2 KIA NUMBER: 2.2.37 ALTERNATE PATH: ..... I _ _.I IMPORTANCE FACTOR: 3.6 APPLICABILITY:
                        ~:_,.,(,
EOLJ ROITJ STAD SROO] EVALUATION SETTING/METHOD:
SME/lnstructor:
Perform n/11:ihb  
SME/lnstructor:C/                           1&#xa3;,(A               Date: _q~/~_q_/1b__
SME/lnstructor:                                                   Date: - - - - - -
                    -------------
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 6 of 7
 
INITIAL CONDITIONS:
- Unit 2 Reactor Power is 100%.
- All Control Rod Group Demand Counters are at 227 steps.
- Current boron concentration is 300 ppm.
- Current core burnup is 10,000 EFPH.
- Control Rod 105 was been declared INOPERABLE at 1000 today due to
- -not moving out during a rod exercise test. You have been directed to perform a Shutdown Margin Calculation IAW SC.RE-ST.ZZ-0002 to satisfy the action requirement of TSAS 3.1.3.1 Action c.3.
- Control Rod 105 has been identified as trippable and is currently at 214 steps.
INITIATING CUE:
The current time is 1010.
This is a time critical JPM. Time will commence when you are provided with the applicable procedures.
When performing calculation, the CRS directs you to use only the Tables as directed by SC.RE-ST.ZZ-0002, do not use Figures.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 7 of 7
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION:                  SALEM 1 & 2 SYSTEM:                  Chemical and Volume Control TASK:                    Demonstrate the Operability of the RWST and/or the BASTs TASK NUMBER:              N0040420201 JPM NUMBER:              15-01 NRC RO Admin A2 ALTERNATE PATH:     I....._ _.I                             KIA NUMBER:          2.2.37
                                                                          ~~~~-~--~~
IMPORTANCE FACTOR:       3.6          4.6 APPLICABILITY:
                                                                          - -RO- -        SRO EOLJ         ROITJ             STAD             SROO]
EVALUATION SETTING/METHOD:                 ,~,~~*-
n/11:ihb Perform S2.0P-ST.CVC-0010, Rev. 10 (checked 9-28-16)


==REFERENCES:==
==REFERENCES:==
Salem Tech Specs TOOLS AND EQUIPMENT:              None VALIDATED JPM COMPLETION TIME:                        11 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS:                          N/A Developed By:                      G Gauding                          Date: 8-9-16 Instructor Validated By:                  S Harris I J Pierce                  Date: 9-28-16 SME or lnstruc          J\l, Approved By:
Training      partme~
Date:  1*) ,/,
Approved By:
Operatic~!                                Date: /6jfl/1c, ACTUAL JPM COMPLETION TIME:
ACTUAL TIME CRITICAL COMPLETION TIME:
PERFORMED BY:
GRADE:    D  SAT        D    UNSAT REASON, IF UNSATISFACTORY:
EVALUATOR'S SIGNATURE:                                                      DATE:
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 1 of 8


S2.0P-ST.CVC-0010, Rev. 10 (checked 9-28-16) Salem Tech Specs TOOLS AND EQUIPMENT:
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: ~~~~~~~~~~~~~~
None VALIDATED JPM COMPLETION TIME: 11 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: Developed By: Validated By: Approved By: Approved By: G Gauding Instructor S Harris I J Pierce SME or lnstruc J\l, Training ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY:
DATE: ~~~~~~~~~~~~~~
EVALUATOR'S SIGNATURE:
SYSTEM:                 Chemical and Volume Control TASK:                 Demonstrate the Operability of the RWST and/or the BASTs TASK NUMBER:           N0040420201 SIMULATOR SETUP:             N/A INITIAL CONDITIONS:
----RO N/A Date: 8-9-16 Date: 9-28-16 Date: 1*) ,/, Date: /6jfl/1c, DATE: PSEG Restricted
-Possession Requires Specific Permission from Nuclear Training Page 1 of 8 4.6 SRO OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME:
DATE:
SYSTEM: Chemical and Volume Control TASK: Demonstrate the Operability of the RWST and/or the BASTs TASK NUMBER: N0040420201 SIMULATOR SETUP: N/A INITIAL CONDITIONS:
* Salem Unit 2 is at 100% power.
* Salem Unit 2 is at 100% power.
* 21 BAT pump developed a leak that went unnoticed until the cross-connected BAST's reached their low level alarm setpoint.
* 21 BAT pump developed a leak that went unnoticed until the cross-connected BAST's reached their low level alarm setpoint.
* 21 BAT pump, and the leak, are isolated.
* 21 BAT pump, and the leak, are isolated.
* 21 BAST level -49.5%
* 21 BAST level - 49.5%
* 22 BAST level -49.5%
* 22 BAST level - 49.5%
* 21 BAST temp -98.2&deg;F
* 21 BAST temp - 98.2&deg;F
* 22 BAST temp -97.1&deg;F
* 22 BAST temp - 97.1&deg;F
* RWST temperature  
* RWST temperature - 70&deg;F
-70&deg;F
* RWST levels are:
* RWST levels are:
* CHl-41.4'
* CHl-41.4'
* CH II -41.4'
* CH II - 41.4'
* CH 111-41.4'
* CH 111-41.4'
* CH IV-41.5'
* CH IV-41.5'
* Chemistry reports current RWST and BAST boron concentrations are:
* Chemistry reports current RWST and BAST boron concentrations are:
* 21 BAST -6610 ppm
* 21 BAST - 6610 ppm
* 22 BAST -6610 ppm
* 22 BAST - 6610 ppm
* RWST -2350 ppm
* RWST - 2350 ppm
* Off Normal and Off-Normal Tagged list review has been performed SAT. INITIATING CUE: You are the Reactor Operator.
* Off Normal and Off-Normal Tagged list review has been performed SAT.
Perform S2.0P-ST.CVC-0010, Borated Water Sources. Successful Completion Criteria:
INITIATING CUE:
You are the Reactor Operator. Perform S2.0P-ST.CVC-0010, Borated Water Sources.
Successful Completion Criteria:
: 1. All critical steps completed.
: 1. All critical steps completed.
: 2. All sequential steps completed in order. 3. All time-critical steps completed within allotted time. 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made. Task Standard for Successful Completion:
: 2. All sequential steps completed in order.
: 1. Complete Attachment 2 of S2.0P-ST.CVC-0010 per key and determine the Surveillance is SAT PSEG Restricted  
: 3. All time-critical steps completed within allotted time.
-Possession Requires Specific Permission from Nuclear Training Page 2 of 8 SYSTEM: TASK: STEP
: 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made.
* NO. 3.0 5.1.1
Task Standard for Successful Completion:
* Att. 2
: 1. Complete Attachment 2 of S2.0P-ST.CVC-0010 per key and determine the Surveillance is SAT PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 2 of 8
* Att. 2 Chemical and Volume Control OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE Demonstrate the Operability of the RWST and/or the BASTs STEP (* Denotes a Critical Step) STANDARD Provide marked up copy of S2.0P-ST.CVC-0010, Borated Water Sources and Tech Spec 3.1.2.6 (2 Precautions and Limitations Reads and initials steps. COMPLETE Attachment 2 per the Completes Attachment 2 with the below data. following:
 
OPERATOR TRAINING PROGRAM                         NAME:  ~~~~~~~~-
JOB PERFORMANCE MEASURE                           DATE: ~~~~~~~~-
SYSTEM:      Chemical and Volume Control TASK:        Demonstrate the Operability of the RWST and/or the BASTs STEP                                                                                 COMMENTS STEP
(* Denotes a Critical Step)                                                         EVAL    (Required for UNSAT
* NO.                                                                      STANDARD S/U      evaluation)
Provide marked up copy of S2.0P-ST.CVC-0010, Borated Water Sources and Tech Spec 3.1.2.6 (2 pa~es) 3.0      Precautions and Limitations                   Reads and initials steps.
5.1.1    COMPLETE Attachment 2 per the                 Completes Attachment 2 with the below data.
following:
* RECORD Data .
* RECORD Data .
* RECORD Test Results by initialing SAT or UNSAT column using the stated Acceptance Criteria.
* RECORD Test Results by initialing SAT or UNSAT column using the stated Acceptance Criteria.
RWST Level Records RWST level with channel for which calibration data was obtained RWST levels are: CH I: 41.4 CH II: 41.4 CH Ill: 41.4 CH IV: 41.5 Initials SAT for RWST Level and inserts date. RWSTTemp Refers to initial conditions for RWST temperature 70&deg;F. Initials SAT for RWST Temp and inserts date. NAME: DATE: EVAL S/U PSEG Restricted  
* Att. 2    RWST Level                                   Records RWST level with channel for which calibration data was obtained RWST levels are:
-Possession Requires Specific Permission from Nuclear Training Page 3 of 8 COMMENTS (Required for UNSAT evaluation)
CH I:     41.4 CH II:     41.4 CH Ill:   41.4 CH IV:     41.5 Initials SAT for RWST Level and inserts date.
SYSTEM: TASK-STEP
* Att. 2    RWSTTemp                                     Refers to initial conditions for RWST temperature 70&deg;F. Initials SAT for RWST Temp and inserts date.
* NO.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 3 of 8
* Att. 2
 
* Att. 2
OPERATOR TRAINING PROGRAM                        NAME: ~~~~~~~~-
* Att. 2 Chemical and Volume Control OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE Demonstrate the Operability of the RWST and/or the BASTs STEP (* Denotes a Critical Step) STANDARD RWST Cone Refers to initial conditions for RWST boron concentration and enters 2350 ppm. Initials SAT for RWST boron concentration and inserts date. 21 BAST Vol AND/OR 22 BAST Vol Refers to initial conditions for 21 and 22 BAST level and enters: 21 BAST vol-49.5% 22 BAST vol -49.5% Uses Tech Spec 3.1.2.6.a, 3.1.2.6.b, and Figure 3.1-2 and determines 21 BAST Vol AND/OR 22 BAST Vol is SAT. Initials SAT for BAST volume and inserts date. 21 BAST Temp AND/OR 22 BAST Temp Refers to initial conditions for 21 and 22 BAST temp and records: 21 BAST temp -98.2&deg;F 22 BAST temp -97.1&deg;F Initials SAT for 21 BAST Temp AND/OR 22 BAST Temp and inserts date. NAME: DATE: EVAL S/U PSEG Restricted  
JOB PERFORMANCE MEASURE                          DATE: ~~~~~~~~-
-Possession Requires Specific Permission from Nuclear Training Page 4 of 8 COMMENTS (Required for UNSAT evaluation)
SYSTEM:      Chemical and Volume Control TASK-        Demonstrate the Operability of the RWST and/or the BASTs STEP                                                                                 COMMENTS STEP
SYSTEM: TASK: STEP
(* Denotes a Critical Step)                                                         EVAL    (Required for UNSAT
* NO.
* NO.                                                                      STANDARD S/U      evaluation)
* Att. 2 5.3.1 5.3.2 5.4.1 Chemical and Volume Control OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE Demonstrate the Operability of the RWST and/or the BASTs STEP (*Denotes a Critical Step) STANDARD Refers to initial conditions for BAST boron 21 BAST Cone AND/OR 22 BAST Cone concentrations and enters 6610 ppm for 21 BAST and 6610 ppm for 22 BAST. Uses Tech Spec 3.1.2.6.a, 3.1.2.6.b, and Figure 3.1-2 and determines 21 and 22 BAST boron concentration is SAT. Initials and inserts date. This surveillance is considered satisfactory when Attachments 2 and 3 Initials step 5.3.1 (as applicable) are complete with components listed meeting Acceptance Criteria stated in each Attachment.
* Att. 2    RWST Cone                                     Refers to initial conditions for RWST boron concentration and enters 2350 ppm. Initials SAT for RWST boron concentration and inserts date.
OR This surveillance is unsatisfactory.
* Att. 2    21 BAST Vol AND/OR 22 BAST Vol               Refers to initial conditions for 21 and 22 BAST level and enters:
N/A's 5.3.2. A. INITIATE Notification(s) to correct the unsatisfactory condition.
21 BAST vol- 49.5%
B. RECORD Notification number(s) and reason for unsatisfactory completion on Attachment 4 in the Comments Section. COMPLETE Attachment 4, Sections 1.0 Completes Attachment 4, Sections 1.0 and and 2.0, AND FORWARD this procedure 2.0, and returns procedure to JPM Evaluator.
22 BAST vol - 49.5%
to the SM/CRS for review. NAME: DATE: EVAL S/U PSEG Restricted  
Uses Tech Spec 3.1.2.6.a, 3.1.2.6.b, and Figure 3.1-2 and determines 21 BAST Vol AND/OR 22 BAST Vol is SAT. Initials SAT for BAST volume and inserts date.
-Possession Requires Specific Permission from Nuclear Training Page 5 of 8  
* Att. 2    21 BAST Temp AND/OR 22 BAST Temp             Refers to initial conditions for 21 and 22 BAST temp and records:
---------COMMENTS (Required for UNSAT evaluation)
21 BAST temp - 98.2&deg;F 22 BAST temp - 97.1&deg;F Initials SAT for 21 BAST Temp AND/OR 22 BAST Temp and inserts date.
SYSTEM: TASK: STEP
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 4 of 8
* NO. Chemical and Volume Control OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE Demonstrate the Operability of the RWST and/or the BASTs STEP (* Denotes a Critical Step) STANDARD JPM is complete when procedure is returned to evaluator.
 
NAME: DATE: EVAL S/U PSEG Restricted  
OPERATOR TRAINING PROGRAM                          NAME:
-Possession Requires Specific Permission from Nuclear Training Page 6 of 8 ------------------COMMENTS (Required for UNSAT evaluation) 
                                                                                                                    --------~
' . \;v \j-J \Y \;J \j'1 \jJ \) JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation.
JOB PERFORMANCE MEASURE                            DATE:
Prior to JPM usage, revalidate JPM using steps 8 and 11 below. ' Jl 7 J 'A /l 1. Task description and number, JPM description and number are identified.
                                                                                                                    ---------
: 2. Knowledge and Abilities (KIA) references are included.
SYSTEM:      Chemical and Volume Control TASK:        Demonstrate the Operability of the RWST and/or the BASTs STEP                                                                                 COMMENTS STEP
: 3. Performance location specified. (in-plant, control room, or simulator)
(*Denotes a Critical Step)                                                           EVAL    (Required for UNSAT
: 4. Initial setup conditions are identified.
* NO.                                                                        STANDARD S/U      evaluation)
: 5. Initiating and terminating Cues are properly identified.
Refers to initial conditions for BAST boron
: 6. Task standards identified and verified by SME review. 7. Critical steps meet the criteria for critical steps and are identified with an asterisk(*).
* Att. 2    21 BAST Cone AND/OR 22 BAST Cone               concentrations and enters 6610 ppm for 21 BAST and 6610 ppm for 22 BAST.
: 8. Verify the procedure referenced by this JPM matchys the most current revision of that procedure:
Uses Tech Spec 3.1.2.6.a, 3.1.2.6.b, and Figure 3.1-2 and determines 21 and 22 BAST boron concentration is SAT. Initials and inserts date.
Procedure Rev. _1_0_ Date 4-f IJ., l 13 9. Pilot test the JPM: a. verify Cues both verbal and visual are free of conflict, and b. ensure performance time is accurate.
5.3.1    This surveillance is considered satisfactory when Attachments 2 and 3         Initials step 5.3.1 (as applicable) are complete with components listed meeting Acceptance Criteria stated in each Attachment.
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.
OR 5.3.2    This surveillance is unsatisfactory.           N/A's 5.3.2.
t.,, :J
A. INITIATE Notification(s) to correct the unsatisfactory condition.
* SME/lnstructor;,A JJlJA,I.<%  
B. RECORD Notification number(s) and reason for unsatisfactory completion on Attachment 4 in the Comments Section.
&#xa3;1 S -il..6(n* SM Ell nstructor:
5.4.1    COMPLETE Attachment 4, Sections 1.0           Completes Attachment 4, Sections 1.0 and and 2.0, AND FORWARD this procedure           2.0, and returns procedure to JPM Evaluator.
Date: [ 1 i <o ------Date: c, /-i,g ( l(.o ------Date: ------PSEG Restricted  
to the SM/CRS for review.
-Possession Requires Specific Permission from Nuclear Training Page 7 of 8 INITIAL CONDITIONS:
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 5 of 8
 
OPERATOR TRAINING PROGRAM                          NAME:
                                                                                                                ---------
JOB PERFORMANCE MEASURE                            DATE:
                                                                                                                ---------
SYSTEM:   Chemical and Volume Control TASK:      Demonstrate the Operability of the RWST and/or the BASTs STEP                                                                                 COMMENTS STEP
(* Denotes a Critical Step)                                                         EVAL    (Required for UNSAT
* NO.                                                                  STANDARD S/U      evaluation)
JPM is complete when procedure is returned to evaluator.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 6 of 8
 
' .
JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below.
    \;v ' ~            1. Task description and number, JPM description and number are identified.
      \j-J    Jl        2. Knowledge and Abilities (KIA) references are included.
      \Y      7 h~      3. Performance location specified. (in-plant, control room, or simulator)
      \;J      J        4. Initial setup conditions are identified.
      \j'1    'A        5. Initiating and terminating Cues are properly identified.
                ~
        \jJ            6. Task standards identified and verified by SME review.
      ~                  7. Critical steps meet the criteria for critical steps and are identified with an asterisk(*).
        ~      /l      8. Verify the procedure referenced by this JPM matchys the most current revision of that procedure: Procedure Rev. _1_0_ Date 4-f IJ., l 13
        \)      ~        9. Pilot test the JPM:
: a. verify Cues both verbal and visual are free of conflict, and
: b. ensure performance time is accurate.
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM.
____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.
SME/lnstructo~JOL~ t.,,               :J * "?,<'/<"'-              Date:    ~ [ 2-~ 1i <o
                                                                                      ------
SME/lnstructor;,A     JJlJA,I.<% &#xa3;1   S- il..6(n* ~              Date: - -c, /-i,g (l(.o
                                                                                                ----
SM Ell nstructor:                                                  Date: - - - - - -
                              ------------~
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 7 of 8
 
INITIAL CONDITIONS:
* Salem Unit 2 is at 100% power.
* Salem Unit 2 is at 100% power.
* 21 BAT pump developed a leak that went unnoticed until the cross-connected BAST's reached their low level alarm setpoint.
* 21 BAT pump developed a leak that went unnoticed until the cross-connected BAST's reached their low level alarm setpoint.
* 21 BAT pump, and the leak, are isolated.
* 21 BAT pump, and the leak, are isolated.
* 21 BAST level -49.5%
* 21 BAST level - 49.5%
* 22 BAST level -49.5%
* 22 BAST level - 49.5%
* 21 BAST temp -98.2&deg;F
* 21 BAST temp - 98.2&deg;F
* 22 BAST temp -97.1&deg;F
* 22 BAST temp - 97.1&deg;F
* RWST temperature  
* RWST temperature - 70&deg;F
-70&deg;F
* RWST levels are:
* RWST levels are:
* CH 1-41.4'
* CH 1- 41.4'
* CH 11 -41 .4'
* CH 11 - 41 .4'
* CH 111 -41.4'
* CH 111 - 41.4'
* CH IV-41.5'
* CH IV-41.5'
* Chemistry reports current RWST and BAST boron concentrations are:
* Chemistry reports current RWST and BAST boron concentrations are:
* 21 BAST -6610 ppm
* 21 BAST - 6610 ppm
* 22 BAST -6610 ppm
* 22 BAST - 6610 ppm
* RWST -2350 ppm
* RWST - 2350 ppm
* Off Normal and Off-Normal Tagged list review has been performed SAT. INITIATING CUE: You are the Reactor Operator.
* Off Normal and Off-Normal Tagged list review has been performed SAT.
Perform S2.0P-ST.CVC-0010, Borated Water Sources Data. PSEG Restricted  
INITIATING CUE:
-Possession Requires Specific Permission from Nuclear Training Page 8 of 8 STATION: SYSTEM: OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SALEM ADMINISTRATIVE (ALARA) TASK: Perform Stay Time Calculation for Emergency Condition.
You are the Reactor Operator. Perform S2.0P-ST.CVC-0010, Borated Water Sources Data.
TASK NUMBER: N1200100104 JPM NUMBER: 15-01 NRC RO A3 ALTERNATE PATH: D KIA NUMBER: 2.3.4 ----------i IMPORTANCE FACTOR: 3.2 ----APPLICABILITY:
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 8 of 8
RO SRO EoD Ro[K] STAD SROD EVALUATION SETTING/METHOD:
 
Classroom  
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION:          SALEM SYSTEM:            ADMINISTRATIVE (ALARA)
TASK:             Perform Stay Time Calculation for Emergency Condition.
TASK NUMBER:       N1200100104 JPM NUMBER:         15-01 NRC RO A3 ALTERNATE PATH:   D                             KIA NUMBER:
                                                              ----------i 2.3.4 IMPORTANCE FACTOR: - -      3.2
                                                                    --
APPLICABILITY:                                                     RO           SRO EoD         Ro[K]         STAD         SROD EVALUATION SETTING/METHOD:         Classroom


==REFERENCES:==
==REFERENCES:==
Radiological Survey Maps, RP-AA-203 Rev. 6, NC.EP-EP.ZZ-0304 Rev. 16 TOOLS AND EQUIPMENT:      Calculator VALIDATED JPM COMPLETION TIME:            10 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS:              N/A Developed By:                  G Gauding                  Date:    8-9-16 Instructor Validated By:            R Evans IN Mulford Date:  9-22-16 I 9-29-16 SME  or lnst:t~~l Approved By:
T~ent                          Date:  /0 )1/1  \_p Approved By:
O~rtment                        Date:  !b/11//(~
ACTUAL JPM COMPLETION TIME:
ACTUAL TIME CRITICAL COMPLETION TIME:
PERFORMED BY:
GRADE:  D  SAT  D UNSAT REASON, IF UNSATISFACTORY:
EVALUATOR'S SIGNATURE:                                          DATE:


Radiological Survey Maps, RP-AA-203 Rev. 6, NC.EP-EP.ZZ-0304 Rev. 16 TOOLS AND EQUIPMENT:
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME:   ~~~~~~~~~~~~~~
Calculator VALIDATED JPM COMPLETION TIME: 10 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: Developed By: Validated By: Approved By: Approved By: G Gauding Instructor R Evans IN Mulford SME or ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY:
EVALUATOR'S SIGNATURE:
N/A Date: 8-9-16 Date: 9-22-16 I 9-29-16 Date: /0 )1/1 \_p Date:
DATE:
DATE:
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME:
SYSTEM:               ADMINISTRATIVE (ALARA)
DATE: SYSTEM: ADMINISTRATIVE (ALARA) TASK: Perform Stay Time Calculation for Emergency Condition.
TASK:                 Perform Stay Time Calculation for Emergency Condition.
TASK NUMBER: N1200100104 INITIAL CONDITIONS:
TASK NUMBER:         N1200100104 INITIAL CONDITIONS:
: 1. Unit 1 experienced Rx trip with a small RCS leak from 100% power. 2. The Rx failed to automatically trip on a valid trip demand, and was tripped successfully with the Rx trip handle. 3. Salem is currently in an Alert. 4. Your TEDE dose for the year is 1925 mrem. INITIATING CUE: You have been directed to perform a detailed inspection of 22 RHR pump room prior to starting the pump. You will NOT be going into the 22 RHR HX area. Your job is estimated to take 2 hours to complete.
: 1. Unit 1 experienced Rx trip with a small RCS leak from 100% power.
: 2. The Rx failed to automatically trip on a valid trip demand, and was tripped successfully with the Rx trip handle.
: 3. Salem is currently in an Alert.
: 4. Your TEDE dose for the year is 1925 mrem.
INITIATING CUE:
You have been directed to perform a detailed inspection of 22 RHR pump room prior to starting the pump. You will NOT be going into the 22 RHR HX area. Your job is estimated to take 2 hours to complete.
Using the correct survey map, and conservatively using the HIGHEST dose rate anywhere in the pump room for your ENTIRE exposure, determine:
Using the correct survey map, and conservatively using the HIGHEST dose rate anywhere in the pump room for your ENTIRE exposure, determine:
: 1. Can you complete the job without exceeding your current dose authorization
: 1. Can you complete the job without exceeding your current dose authorization
: 2. What would be your new TEDE dose for the year after performing the job (or as much as possible)
: 2. What would be your new TEDE dose for the year after performing the job (or as much as possible) WITHOUT exceeding your current dose authorization?
WITHOUT exceeding your current dose authorization?
Successful Completion Criteria:
Successful Completion Criteria:
: 1. All critical steps completed.
: 1. All critical steps completed.
: 2. All sequential steps completed in order. 3. All time-critical steps completed within allotted time. 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made. Task Standard for Successful Completion:
: 2. All sequential steps completed in order.
: 3. All time-critical steps completed within allotted time.
: 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made.
Task Standard for Successful Completion:
Determines:
Determines:
YES job can be performed
YES job can be performed
: 2. Calculates new TEDE dose of 2005 mrem.
: 2. Calculates new TEDE dose of 2005 mrem.
SYSTEM: ADMINISTRATIVE (ALARA) OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE TASK: Determine Radiological Conditions For Personnel Exposure STEP STEP
 
* NO. (*Denotes a Critical Step) STANDARD Provide the attached survey maps of 21 and 22 RHR rooms, and S1 and S2 55 Selects the Survey Map General area. Also have blank copies of "S2 AUX 045' 22 RHR ROOMS" 1 RP-AA-203, Exposure Control and Map# 21045Z2 Authorization and NC.EP-EP.ZZ-0304, Operational Support Center (OSC) Radiation Protection Response if asked for. START TIME: If asked, provide NC.EP-EP.ZZ-0304, Note: Contains guidance for automatic OSC Radiation Protection Response.
OPERATOR TRAINING PROGRAM                    NAME:
increase in allowed dose to 4500 mrem. (Section 5.0 Note.) Determines dose limit is automatically raised to 4500 mrem upon the declaration of an ALERT or higher Emergency.
                                                                                                          ----------
Page 3 of 6 NAME: ----------
JOB PERFORMANCE MEASURE                    DATE:
DATE: ----------
                                                                                                          ----------
COMMENTS EVAL (Required for UNSAT S/U evaluation)
SYSTEM:   ADMINISTRATIVE (ALARA)
SYSTEM: ADMINISTRATIVE (ALARA) OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE TASK: Determine Radiological Conditions For Personnel Exposure -STEP STEP
TASK:     Determine Radiological Conditions For Personnel Exposure STEP                                                                         COMMENTS STEP
* NO. (*Denotes a Critical Step) STANDARD
(*Denotes a Critical Step)                                                   EVAL  (Required for UNSAT
* 2 Determine highest dose rate in room. Per the survey map, squares are dose rates in mrem/hr, and circles are smear locations.
* NO.                                                                  STANDARD S/U      evaluation)
The highest square is located under the words "22RH37" on the map and indicates 40 mrem/hr. Note: The square with "250" inside it is in the RHR HX room, and is not in the area which the operator will go.
Provide the attached survey maps of 21 and 22 RHR rooms, and S1 and S2 55         Selects the Survey Map General area. Also have blank copies of     "S2 AUX 045' 22 RHR ROOMS" RP-AA-203, Exposure Control and 1                                                    Map# 21045Z2 Authorization and NC.EP-EP.ZZ-0304, Operational Support Center (OSC)
* 3 Calculate TEDE dose for year Subtracts year to date TEDE dose from Emergency Dose limit of 4,500 mrem, and gets 2575 mrem. Determines 2 hours of work will result in 80 mrem dose, and new TEDE dose is 2005 mrem, which does NOT exceed 4,500 mrem authorized in an Emergency.
Radiation Protection Response if asked for.
START TIME:
If asked, provide NC.EP-EP.ZZ-0304,         Note: Contains guidance for automatic OSC Radiation Protection Response.         increase in allowed dose to 4500 mrem.
(Section 5.0 Note.)
Determines dose limit is automatically raised to 4500 mrem upon the declaration of an ALERT or higher Emergency.
Page 3 of 6
 
OPERATOR TRAINING PROGRAM                      NAME:
                                                                                                              ~---------
JOB PERFORMANCE MEASURE                        DATE: - - - - - - - - - -
SYSTEM:   ADMINISTRATIVE (ALARA)
TASK:     Determine Radiological
                            -
Conditions For Personnel Exposure STEP                                                                             COMMENTS STEP
(*Denotes a Critical Step)                                                       EVAL    (Required for UNSAT
* NO.                                                                  STANDARD S/U        evaluation) 2       Determine highest dose rate in room.       Per the survey map, squares are dose
* rates in mrem/hr, and circles are smear locations. The highest square is located under the words "22RH37" on the map and indicates 40 mrem/hr.
Note: The square with "250" inside it is in the RHR HX room, and is not in the area which the operator will go.
3       Calculate TEDE dose for year               Subtracts year to date TEDE dose from
* Emergency Dose limit of 4,500 mrem, and gets 2575 mrem. Determines 2 hours of work will result in 80 mrem dose, and new TEDE dose is 2005 mrem, which does NOT exceed 4,500 mrem authorized in an Emergency.
Terminate JPM when candidate has returned paperwork.
Terminate JPM when candidate has returned paperwork.
4 STOP TIME: Page 4 of 6 NAME:
4       STOP TIME:
DATE: ----------
Page 4 of 6
COMMENTS EVAL (Required for UNSAT S/U evaluation)
 
JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation.
JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below.
Prior to JPM usage, revalidate JPM using steps 8 and 11 below. Vv N'\ d \}-' N'\ vN'\-t V M v rt\ vMf v-N1 / \J N1 -( N1 &#xa3; 1. Task description and number, JPM description and number are identified.
Vv N'\ d         1. Task description and number, JPM description and number are identified.
: 2. Knowledge and Abilities (KIA) references are included.
\}-' N'\ ~        2. Knowledge and Abilities (KIA) references are included.
: 3. Performance location specified. (in-plant, control room, or simulator)
vN'\-t            3. Performance location specified. (in-plant, control room, or simulator)
: 4. Initial setup conditions are identified.
V M ~            4. Initial setup conditions are identified.
: 5. Initiating and terminating Cues are properly identified.
v    rt\ ~      5. Initiating and terminating Cues are properly identified.
: 6. Task standards identified and verified by SME review. 7. Critical steps meet the criteria for critical steps and are identified with an asterisk (*). 8. Verify the procedure referenced by this JPM matches the most current revision of that procedure:
vMf              6. Task standards identified and verified by SME review.
Procedure Date  
v-    N1 /        7. Critical steps meet the criteria for critical steps and are identified with an asterisk (*).
'"' '"' 9. Pilot test the JPM: a. verify Cues both verbal and visual are free of conflict, and b. ensure performance time is accurate.
\J  N1 -(        8. Verify the procedure referenced by this JPM matches the most current revision of that procedure: Procedure Rev.-~-- Date S'~"Z"'-* '"'
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructor: SME/lnstructor:
N1 &#xa3;        9. Pilot test the JPM:
SME/lnstructor:  
                                                                      '"'
-------------
: a. verify Cues both verbal and visual are free of conflict, and
Page 5 of 6 Date: 9-2. -'"" Date: q /q.ci/1b Date: ------
: b. ensure performance time is accurate.
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM.
____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.
SME/lnstructor: ~                                                Date:  9- 2. ~ - '""
SME/lnstructor: ~lfw-J                                            Date:  q /q.ci/1b SME/lnstructor:                                                    Date:
                        -------------                                           ------
Page 5 of 6
 
INITIAL CONDITIONS:
INITIAL CONDITIONS:
: 1. Unit 1 experienced Rx trip with a small RCS leak from 100% power. 2. The Rx failed to automatically trip on a valid trip demand, and was tripped successfully with the Rx trip handle. 3. Salem is currently in an Alert. 4. Your TEDE dose for the year is 1925 mrem. INITIATING CUE: You have been directed to perform a detailed inspection of 22 RHR pump room prior to starting the pump. You will NOT be going into the 22 RHR HX area. Your job is estimated to take 2 hours to complete.
: 1. Unit 1 experienced Rx trip with a small RCS leak from 100% power.
: 2. The Rx failed to automatically trip on a valid trip demand, and was tripped successfully with the Rx trip handle.
: 3. Salem is currently in an Alert.
: 4. Your TEDE dose for the year is 1925 mrem.
INITIATING CUE:
You have been directed to perform a detailed inspection of 22 RHR pump room prior to starting the pump. You will NOT be going into the 22 RHR HX area. Your job is estimated to take 2 hours to complete.
Using the correct survey map, and conservatively using the HIGHEST dose rate anywhere in the pump room for your ENTIRE exposure, determine:
Using the correct survey map, and conservatively using the HIGHEST dose rate anywhere in the pump room for your ENTIRE exposure, determine:
: 1. 2. 1. Can you complete the job without exceeding your current dose authorization
: 1. Can you complete the job without exceeding your current dose authorization
: 2. What would be your new TEDE dose for the year after performing the job (or as much as possible)
: 2. What would be your new TEDE dose for the year after performing the job (or as much as possible) WITHOUT exceeding your current dose authorization?
WITHOUT exceeding your current dose authorization?
1.
Page 6 of 6 STATION: SYSTEM: SALEM OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE ADMINISTRATIVE TASK: Review a completed surveillance to demonstrate Operability of 21 CFCU TASK NUMBER: N1230300302 JPM NUMBER: 15-01 NRC SRO Admin A1-1 KIA NUMBER: 2.1.25 ALTERNATE PATH: ._I _ _.I IMPORTANCE FACTOR: APPLICABILITY:
2.
EOCJ ROCJ STAL] SROCK] EVALUATION SETTING/METHOD:
Page 6 of 6
Classroom  
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION:              SALEM SYSTEM:                ADMINISTRATIVE TASK:                 Review a completed surveillance to demonstrate Operability of 21 CFCU TASK NUMBER:           N1230300302 JPM NUMBER:             15-01 NRC SRO Admin A1-1 ALTERNATE PATH:      ._I_  _.I                              KIA NUMBER: ~~~~~~~~~~
2.1.25 IMPORTANCE FACTOR:                           4.2 APPLICABILITY:                                                               RO            SRO EOCJ         ROCJ               STAL]           SROCK]
EVALUATION SETTING/METHOD:               Classroom


==REFERENCES:==
==REFERENCES:==
S2.0P-ST.CBV-0003, Rev. 19 (checked 8-10-16)
TOOLS AND EQUIPMENT:
VALIDATED JPM COMPLETION TIME:                        12 min TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS:                        N/A Developed By:                          G Gauding                    Date:  8-10-16 Instructor Validated By:                        R Boyer I P Williams          Date:  9-28-16 / 10-4-16 SME or Instructor~
Approved By:
                                      . .
                                . Trammg rt;t.f<Vlt pa men Date:    1~//r0 Approved By:*
Op~artment                        Date:
10)/;1, ACTUAL JPM COMPLETION TIME:
ACTUAL TIME CRITICAL COMPLETION TIME:
PERFORMED BY:
GRADE:    D  SAT      D      UNSAT REASON, IF UNSATISFACTORY:
EVALUATOR'S SIGNATURE:                                                      DATE:
Page 1 of 5 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training


S2.0P-ST.CBV-0003, Rev. 19 (checked 8-10-16) TOOLS AND EQUIPMENT:
OPERATORTRAININGPROGRAM JOB PERFORMANCE MEASURE NAME:   ~~~~~~~~~~~~-
VALIDATED JPM COMPLETION TIME: 12 min TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: Developed By: G Gauding Instructor N/A Date: 4.2 RO SRO 8-10-16 Validated By: R Boyer I P Williams SME or Date: 9-28-16 / 10-4-16 Date:
DATE:
T . . rt;t.f <Vlt . rammg pa men Approved By: Approved By:*
SYSTEM:                           Administrative TASK:                             Review a completed surveillance to demonstrate Operability of 21 CFCU TASK NUMBER:                      N1230300302 INITIAL CONDITIONS:               21 CFCU was returned from corrective maintenance. S2.0P-ST.CBV-0003, Containment Systems - Containment Cooling was performed for the Operability Retest.
Date: 10)/;1, ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY:
INITIATING CUE:
EVALUATOR'S SIGNATURE:
You have been directed to review the surveillance for completeness and accuracy IAW Step 5.3.4.
DATE: Page 1 of 5 PSEG Restricted
If any discrepancies are identified, note them and any actions that you would take on Attachment 8, Section 1.0, Comments.
-Possession Requires Specific Permission from Nuclear Training OPERATORTRAININGPROGRAM JOB PERFORMANCE MEASURE NAME: DATE:
SYSTEM: Administrative TASK: TASK NUMBER: Review a completed surveillance to demonstrate Operability of 21 CFCU N1230300302 INITIAL CONDITIONS:
INITIATING CUE: 21 CFCU was returned from corrective maintenance.
S2.0P-ST.CBV-0003, Containment Systems -Containment Cooling was performed for the Operability Retest. You have been directed to review the surveillance for completeness and accuracy IAW Step 5.3.4. If any discrepancies are identified, note them and any actions that you would take on Attachment 8, Section 1.0, Comments.
Successful Completion Criteria:
Successful Completion Criteria:
: 1. All critical steps completed
: 1. All critical steps completed
: 2. All sequential steps completed in order 3. All time-critical steps completed within allotted time 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made (and NRC concurrence is obtained).
: 2. All sequential steps completed in order
: 3. All time-critical steps completed within allotted time
: 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made (and NRC concurrence is obtained).
Task Standard for Successful Completion:
Task Standard for Successful Completion:
: 1. Identify that the Minimum Flow Rate recorded on Attachment 1, Section 3.0, for 87 psid is incorrectly recorded as 1592. Identify the correct Minimum Flow Rate should be 1638. 2. Identify that the actual Cooling Water Flow Rate (1625) is below the Minimum Flow Rate required as shown on Attachment 1 and Exhibit 1, and the surveillance is UNSAT vs SAT. Page 2 of 5 PSEG Restricted  
: 1. Identify that the Minimum Flow Rate recorded on Attachment 1, Section 3.0, for 87 psid is incorrectly recorded as 1592. Identify the correct Minimum Flow Rate should be 1638.
-Possession Requires Specific Permission from Nuclear Training System: ADMINISTRATIVE OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE Task: Review a completed surveillance to demonstrate Operability of 21 CFCU
: 2. Identify that the actual Cooling Water Flow Rate (1625) is below the Minimum Flow Rate required as shown on Attachment 1 and Exhibit 1, and the surveillance is UNSAT vs SAT.
* STEP STEP STANDARD NO. (* Denotes a Critical Step) Provide completed S2.0P-ST.CBV-0003 surveillance.
Page 2 of 5 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
OPERATOR TRAINING PROGRAM                       NAME: _ _ _ _ _ _ _ _ _ __
JOB PERFORMANCE MEASURE                         DATE: _ _ _ _ _ _ _ _ _ __
System:  ADMINISTRATIVE Task:   Review a completed surveillance to demonstrate Operability of 21 CFCU
* STEP                 STEP                                       STANDARD                           EVAL        COMMENTS NO.       (* Denotes a Critical Step)                                                               S/U    (Required for UNSAT evaluation)
Provide completed S2.0P-ST.CBV-0003 surveillance.
Reviews procedure.
Reviews procedure.
Identifies that the Minimum Flow Rate recorded
Identifies that the Minimum Flow Rate recorded on Attachment 1, 21 CFCU Data Sheet,
* on Attachment 1, 21 CFCU Data Sheet, Section 3.0, for 87 psid is incorrectly recorded as 1592. (This was due to operator performing ST rounding down as opposed to rounding up IAW P&L 3.4.) Identifies correct value for Minimum Flow
* Section 3.0, for 87 psid is incorrectly recorded as 1592. (This was due to operator performing ST rounding down as opposed to rounding up IAW P&L 3.4.)
* Required as 1638. Cue: IF candidate only determines flow is wrong, THEN ask candidate to determine correct flow.
Identifies correct value for Minimum Flow Required as 1638.
* Identifies that the actual Cooling Water Flow Rate of 1625 gpm is below the Minimum Flow Rate of 1638 as shown on Exhibit 1 and the ST is UNSAT. When candidate turns in JPM, ensure they have provided correct flow as per Cue above, then state JPM is complete.
* Cue: IF candidate only determines flow is wrong, THEN ask candidate to determine correct flow.
Page 3 of5 NAME: __________
* Identifies that the actual Cooling Water Flow Rate of 1625 gpm is below the Minimum Flow Rate of 1638 as shown on Exhibit 1 and the ST is UNSAT.
_ DATE: __________
When candidate turns in JPM, ensure they have provided correct flow as per Cue above, then state JPM is complete.
_ EVAL COMMENTS S/U (Required for UNSAT evaluation)
Page 3 of5 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
PSEG Restricted  
 
-Possession Requires Specific Permission from Nuclear Training OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST TQ-AA-106-0303 Revision 4 NOTE: All steps of this checklist should be performed upon initial validation.
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE TQ-AA-106-0303 Revision 4 JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below.
Prior to JPM usage, revalidate JPM using steps 8 and 11 below. V /
V/   ~Task description and number, JPM description and number are identified.
description and number, JPM description and number are identified.
IJ ./ &#xa3;?2. Knowledge and Abilities (KIA) references are included.
IJ ./ &#xa3;?2. Knowledge and Abilities (KIA) references are included.  
\J / /J ~Performance            location specified. (in-plant, control room, or simulator)
\J / /J location specified. (in-plant, control room, or simulator)
V. I   tf/-V4.   *Initial setup conditions are identified.
V. I tf/-V4. *Initial setup conditions are identified. </!-A and terminating Cues are properly identified.
~ </!-A~nitiating and terminating Cues are properly identified.
U. 9 6. Task standards identified and verified by SME review. \J I fj:) 7. Critical steps meet the criteria for critical steps and are identified with an asterisk (*).
U.         9 6. Task standards identified and verified by SME review.
the procedure referenced by this JPM matches the most current revision of that procedure:
\J I   fj:)   7. Critical steps meet the criteria for critical steps and are identified with an asterisk (*).
Procedure Rev. _j_!J_ Date s/u/1 L test the JPM: ' a. verify Cues both verbal and visual are free of conflict, and b. ensure performance time is accurate.
    ~Verify the procedure referenced by this JPM matches the most current revision of that procedure: Procedure Rev. _j_!J_ Date             s/u/1 L L~t test the JPM:                                                         '
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. Date: -+--o/
: a. verify Cues both verbal and visual are free of conflict, and
a'--'----1/f, _
: b. ensure performance time is accurate.
SME/lnstructor:  
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM.
--------------
____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.
Date: _____ _ Page 4 of5 PSEG Restricted  
                                                                                      ; ._. =:. . !~
-Possession Requires Specific Permission from Nuclear Training INITIAL CONDITIONS:
Date: -+--o/           a'--'----1/f,_
21 CFCU was returned from corrective maintenance.
Date:_/~~.____*"4-~~{b=---
S2.0P-ST.CBV-0003, Containment Systems -Containment Cooling was performed for the Operability Retest. INITIATING CUE: You have been directed to review the surveillance for completeness and accuracy IAW Step 5.3.4. If any discrepancies are identified, note them and any actions that you would take on Attachment 8, Section 1.0, Comments.
SME/lnstructor:                                                       Date: _ _ _ _ __
Page5of5 PSEG Restricted  
                      --------------
-Possession Requires Specific Permission from Nuclear Training STATION: SYSTEM: SALEM OPERA TOR TRAINING PROGRAM JOB PERFORMANCE MEASURE ADMINISTRATIVE TASK: Direct Actions for Spent Fuel Movement (Determine equipment allowed to be removed from service while SFP manipulations are in progress)
Page 4 of5 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
TASK NUMBER: N1120760102 JPM NUMBER: 15-01 NRC SRO A 1-2 KIA NUMBER: 2.1.42 ALTERNATE PATH: D IMPORTANCE FACTOR: 3.4 ----APPLICABILITY:
 
RO SRO EOCJ ROCJ STAL] SRO[TI EVALUATION SETTING/METHOD:
INITIAL CONDITIONS:
Classroom or Simulator  
21 CFCU was returned from corrective maintenance. S2.0P-ST.CBV-0003, Containment Systems - Containment Cooling was performed for the Operability Retest.
INITIATING CUE:
You have been directed to review the surveillance for completeness and accuracy IAW Step 5.3.4.
If any discrepancies are identified, note them and any actions that you would take on , Section 1.0, Comments.
Page5of5 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION:              SALEM SYSTEM:                ADMINISTRATIVE TASK:                 Direct Actions for Spent Fuel Movement (Determine equipment allowed to be removed from service while SFP manipulations are in progress)
TASK NUMBER:           N1120760102 JPM NUMBER:           15-01 NRC SRO A 1-2 ALTERNATE PATH:      D                                  KIA NUMBER:
                                                                        ~--------~
2.1.42 IMPORTANCE FACTOR:                           3.4
                                                                        ----
APPLICABILITY:                                                               RO           SRO EOCJ         ROCJ             STAL]           SRO[TI EVALUATION SETTING/METHOD:             Classroom or Simulator


==REFERENCES:==
==REFERENCES:==
S2.0P-IO.ZZ-0010, Rev. 33, S2.0P-SO.CH-0001 Rev 32, S2.0P-SO.SW-0005 Rev 42 S2.0P-SO.DG-0005, Rev. 6 (all rev checked 8-10-16) Salem Tech Specs TOOLS AND EQUIPMENT:
VALIDATED JPM COMPLETION TIME:                    30 min TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS:                        N/A Developed By:                        G Gauding                    Date:    8-10-16 Instructor Validated By:                  R Boyer IP Williams                Date:  9-28-16110-4-16 SME or Instructor Approved By:                                      AA  /J          Date:    100~
Traini;~rtm~-,{(ft-t, Approved By:                      ~                                Date:  10/1j1t, Op-;rations Depa"nt ACTUAL JPM COMPLETION TIME:
ACTUAL TIME CRITICAL COMPLETION TIME:
PERFORMED BY:
GRADE:    D SAT D UNSAT REASON, IF UNSATISFACTORY:
EVALUATOR'S SIGNATURE:                                                    DATE:
Page 1 of 7 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training


S2.0P-IO.ZZ-0010, Rev. 33, S2.0P-SO.CH-0001 Rev 32, S2.0P-SO.SW-0005 Rev 42 S2.0P-SO.DG-0005, Rev. 6 (all rev checked 8-10-16) Salem Tech Specs TOOLS AND EQUIPMENT:
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME:
VALIDATED JPM COMPLETION TIME: 30 min TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: Developed By: Validated By: G Gauding Instructor R Boyer IP Williams SME or Instructor Approved By: AA /J Approved By: Op-;rations Depa"nt ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY:
                                                                      ~~~~~~~~~~~~~~~
EVALUATOR'S SIGNATURE:
DATE:
Page 1 of 7 N/A Date: 8-10-16 Date: 9-28-16110-4-16 Date: Date: 10/1j1t, DATE: PSEG Restricted
SYSTEM:               Administrative TASK:                   Direct Actions for Spent Fuel Movement (Determine equipment allowed to be removed from service while SFP manipulations are in progress)
-Possession Requires Specific Permission from Nuclear Training OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME:
TASK NUMBER:           N1120760102 INITIAL                 Salem Unit 2 is operating at199% power, coasting down into a refueling outage CONDITIONS:            which will start in 2 weeks.
DATE: SYSTEM: Administrative TASK: Direct Actions for Spent Fuel Movement (Determine equipment allowed to be removed from service while SFP manipulations are in progress)
Irradiated fuel movement is in progress in the Spent Fuel Pool IAW S2.0P-IO.ZZ-0010, Spent Fuel Pool Manipulations, and will continue without interruption for the next 8 hours, at which time it will terminate.
TASK NUMBER: N1120760102 INITIAL CONDITIONS:
The unit has no active Tech Spec LCOs.
INITIATING CUE: Salem Unit 2 is operating at199% power, coasting down into a refueling outage which will start in 2 weeks. Irradiated fuel movement is in progress in the Spent Fuel Pool IAW S2.0P-IO.ZZ-0010, Spent Fuel Pool Manipulations, and will continue without interruption for the next 8 hours, at which time it will terminate.
21 SW pump is CIT for emergent strainer work.
The unit has no active Tech Spec LCOs. 21 SW pump is CIT for emergent strainer work. The current time is 0800. You have been directed to review the upcoming work for the shift and determine which activities may proceed as scheduled while continuing the fuel movement in the Spent Fuel Pool uninterrupted.
The current time is 0800.
Work scheduled for today Circle whether each activity may or may not be performed lE any of the activities cannot proceed, explain your reason(s) 0900-22 SW pump packing replacement 1000-2A EOG tagout for maintenance 1300-21 Chiller compressor oil change 1400-Delivery of New Fuel into the Fuel Handling Building for upcoming refueling outage. MAY MAY MAY MAY MAY NOT MAY NOT MAY NOT MAY NOT Successful Completion Criteria:
INITIATING CUE:
You have been directed to review the upcoming work for the shift and determine which activities may proceed as scheduled while continuing the fuel movement in the Spent Fuel Pool uninterrupted.
Work scheduled for today                       Circle whether each activity may or may not be performed lE any of the activities cannot proceed, explain your reason(s) 0900- 22 SW pump packing replacement             MAY          MAY NOT 1000- 2A EOG tagout for maintenance               MAY          MAY NOT 1300- 21 Chiller compressor oil change           MAY            MAY NOT 1400- Delivery of New Fuel into the Fuel         MAY            MAY NOT Handling Building for upcoming refueling outage.
Successful Completion Criteria:
: 1. All critical steps completed
: 1. All critical steps completed
: 2. All sequential steps completed in order 3. All time-critical steps completed within allotted time 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made (and NRC concurrence is obtained).
: 2. All sequential steps completed in order
: 3. All time-critical steps completed within allotted time
: 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made (and NRC concurrence is obtained).
Task Standard for Successful Completion:
Task Standard for Successful Completion:
: 1. Determines that 22 SW pp work, 2A EOG surveillance, and 21 Chiller work MAY be performed.
: 1. Determines that 22 SW pp work, 2A EOG surveillance, and 21 Chiller work MAY be performed.
: 2. Determines that New Fuel delivery may NOT be performed.
: 2. Determines that New Fuel delivery may NOT be performed.
Page 2 of 7 PSEG Restricted  
Page 2 of 7 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
-Possession Requires Specific Permission from Nuclear Training System: ADMINISTRATIVE OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: __________
 
_ DATE: __________
                                                                                                                                      '.'ii OPERATOR TRAINING PROGRAM                       NAME: _ _ _ _ _ _ _ _ _ __
_ Task: Direct Actions for Spent Fuel Movement (Determine equipment allowed to be removed from service while SFP manipulations are in progress)
JOB PERFORMANCE MEASURE                         DATE: _ _ _ _ _ _ _ _ _ __
* STEP STEP STANDARD EVAL COMMENTS NO. (* Denotes a Critical Step) SIU (Required for UNSAT evaluation)
System:   ADMINISTRATIVE Task:   Direct Actions for Spent Fuel Movement (Determine equipment allowed to be removed from service while SFP manipulations are in progress)
Provide blank copies of: S2.0P-IO.ZZ-0010, Spent Fuel Pool Manipulations.
* STEP                     STEP                                     STANDARD                         EVAL         COMMENTS NO.           (* Denotes a Critical Step)                                                           SIU     (Required for UNSAT evaluation)
S2.0P-SO.DG-0005, Preparation for Removing a Diesel Generator from Service. S2.0P-SO.SW-0005, Service Water System Operation.
Provide blank copies of:
S2.0P-IO.ZZ-0010, Spent Fuel Pool Manipulations.
S2.0P-SO.DG-0005, Preparation for Removing a Diesel Generator from Service.
S2.0P-SO.SW-0005, Service Water System Operation.
S2.0P-SO.CH-0001, Chilled Water System Operation.
S2.0P-SO.CH-0001, Chilled Water System Operation.
Provide copies of Tech Specs. Page 3 of7 PSEG Restricted  
Provide copies of Tech Specs.
-Possession Requires Specific Permission from Nuclear Training '.'ii System: ADMINISTRATIVE OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME:
Page 3 of7 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
DATE:
 
Task: Direct Actions for Spent Fuel Movement (Determine equipment allowed to be removed from service while SFP manipulations are in progress)
OPERATOR TRAINING PROGRAM                       NAME:  ~~~~~~~~~~~
* STEP STEP STANDARD EVAL COMMENTS NO. (*Denotes a Critical Step) S/U (Required for UNSAT evaluation)
JOB PERFORMANCE MEASURE                         DATE: ~~~~~~~~~~~
Notes: TSAS 3.8.1.2 applies during Modes 5 and 6 and during movement of irradiated fuel, and only requires two EDGs. Only one FHB exhaust fan is required to be backed by an operable EOG (IOP-10 P&L 3. 7 and page 17) Operable SFP pumps only need one of them backed by operable EOG. (IOP-10 P&L 3.4 and page 17) TSAS 3. 7 .10 allows a chiller to be taken out of service if movement of irradiated fuel is already on-going, and gives 14 days to restore it. Two SW pumps are required to be operable, one of which is EOG backed. (IOP-10 page 18.) The four remaining SW pumps are powered from Band C vital and their EDGs remain operable.
System:   ADMINISTRATIVE Task:   Direct Actions for Spent Fuel Movement (Determine equipment allowed to be removed from service while SFP manipulations are in progress)
TSAS 3.7.4 will be entered for less than two operable SW loops, but is a 72 hour action. Page 4 of7 PSEG Restricted  
* STEP                     STEP                                       STANDARD                       EVAL         COMMENTS NO.           (*Denotes a Critical Step)                                                             S/U     (Required for UNSAT evaluation)
-Possession Requires Specific Pennission from Nuclear Training System: ADMINISTRATIVE OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: -----------
Notes:
0 ATE: __________
TSAS 3.8.1.2 applies during Modes 5 and 6 and during movement of irradiated fuel, and only requires two EDGs.
_ Task: Direct Actions for Spent Fuel Movement (Determine equipment allowed to be removed from service while SFP manipulations are in progress)
Only one FHB exhaust fan is required to be backed by an operable EOG (IOP-10 P&L 3. 7 and page 17)
* STEP STEP STANDARD EVAL COMMENTS NO. (* Denotes a Critical Step) S/U (Required for UNSAT evaluation)
Operable SFP pumps only need one of them backed by operable EOG. (IOP-10 P&L 3.4 and page 17)
Notes: (cont) FHB Truck Bay Door is required to be closed. (IOP-10 paqe 19) Determines that:
TSAS 3. 7 .10 allows a chiller to be taken out of service if movement of irradiated fuel is already on-going, and gives 14 days to restore it.
Two SW pumps are required to be operable, one of which is EOG backed.
(IOP-10 page 18.) The four remaining SW pumps are powered from Band C vital and their EDGs remain operable.
TSAS 3.7.4 will be entered for less than two operable SW loops, but is a 72 hour action.
Page 4 of7 PSEG Restricted - Possession Requires Specific Pennission from Nuclear Training
 
                                                                                                                                      ~
OPERATOR TRAINING PROGRAM                       NAME:
                                                                                                            -----------
JOB PERFORMANCE MEASURE                        0 ATE: _ _ _ _ _ _ _ _ _ __
System:  ADMINISTRATIVE Task:   Direct Actions for Spent Fuel Movement (Determine equipment allowed to be removed from service while SFP manipulations are in progress)
* STEP                     STEP                                       STANDARD                       EVAL         COMMENTS NO.           (* Denotes a Critical Step)                                                           S/U     (Required for UNSAT evaluation)
Notes: (cont)
FHB Truck Bay Door is required to be closed. (IOP-10 paqe 19)
Determines that:
* 22 SW pump work MAY be performed.
* 22 SW pump work MAY be performed.
* 2A EOG surveillance MAY be performed.
* 2A EOG surveillance MAY be performed.
* 21 Chiller oil replacement MAY be
* 21 Chiller oil replacement MAY be performed.
* performed.
* New Fuel delivery may NOT be performed because FHB Truck Bay door is required to be closed per IOP-10, page 19.
New Fuel delivery may NOT be performed because FHB Truck Bay door is required to be closed per IOP-10, page 19. Evaluator ensure tear off sheet has candidates name and status for each of the four work activities, then terminate JPM. Page 5 of7 PSEG Restricted  
Evaluator ensure tear off sheet has candidates name and status for each of the four work activities, then terminate JPM.
-Possession Requires Specific Permission from Nuclear Training Name: OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation.
Page 5 of7 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
Prior to JPM usage, revalidate JPM using steps 8 and 11 below . .Id' 01. Task description and number, JPM description and number are identified.
 
and Abilities (KIA) references are included.  
Name:
,/._ d location specified. (in-plant, control room, or simulator) 1.d<f:Z--4.
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE TQ-AA-106-0303 Revision 4 JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below .
Initial setup conditions are identified.  
.Id' 01.       Task description and number, JPM description and number are identified.
/ A Initiating and terminating Cues are properly identified.
~Knowledge and Abilities (KIA) references are included.
j ff standards identified and verified by SME review. TQ-AA-106-0303 Revision 4 I a Critical steps meet the criteria for critical steps and are identified with an asterisk (*).
,/._ d ~Performance location specified. (in-plant, control room, or simulator) 1.d<f:Z--4. Initial setup conditions are identified.
the procedure referenced by this JPM matches the most current revision of that procedure:
/ A~.          Initiating and terminating Cues are properly identified.
Procedure Rev. ilei,y1J'.,S Date 1 h.!J I<, test the JPM: a. verify Cues both verbal and visual are free of conflict, and b. ensure performance time is accurate.
j ff ~-Task          standards identified and verified by SME review.
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructor:
I     a~        Critical steps meet the criteria for critical steps and are identified with an asterisk (*).
Date:  
  ~erify the procedure referenced by this JPM matches the most current revision of that procedure: Procedure Rev. ilei,y1J'.,S Date       1h.!J I<,
------Page 6 of7 PSEG Restricted  
  ~at test the JPM:
-Possession Requires Specific Permission from Nuclear Training INITIAL CONDITIONS:
: a. verify Cues both verbal and visual are free of conflict, and
Salem Unit 2 is operating at 99% power, coasting down into a refueling outage which will start in 2 weeks. Irradiated fuel movement is in progress in the Spent Fuel Pool IAW S2.0P-IO.ZZ-0010, Spent Fuel Pool Manipulations, and will continue without interruption for the next 8 hours, at which time it will terminate.
: b. ensure performance time is accurate.
The unit has no active Tech Spec LCOs. 21 SW pump is C/T for emergent strainer work. The current time is 0800. INITIATING CUE: You have been directed to review the upcoming work for the shift and determine which activities may proceed as scheduled while continuing the fuel movement in the Spent Fuel Pool uninterrupted.
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM.
Work scheduled for today Circle whether each activity may or may not be performed lE any of the activities cannot proceed, explain your reason(s) 0900-22 SW pump packing replacement 1000-2A EOG tag out for maintenance 1300-21 Chiller compressor oil change 1400-Delivery of New Fuel into the Fuel Handling Building for upcoming refueling outage. MAY MAY MAY MAY Page 7 of7 MAY NOT MAY NOT MAY NOT MAY NOT PSEG Restricted  
____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.
-Possession Requires Specific Permission from Nuclear Training STATION: SYSTEM: TASK: TASK NUMBER: JPM NUMBER: SALEM OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE ADMINISTRATIVE Review a completed surveillance to calculate Shutdown Margin 1200030301 15-01 NRC SRO A2 KIA NUMBER: 2.2.12 ALTERNATE PATH: D IMPORTANCE FACTOR: APPLICABILITY:
SME/lnstructor:                                                       Date: - - - - - -
EoD ROD STAD sRo[KJ EVALUATION SETTING/METHOD:
                    ~-------------
Classroom  
Page 6 of7 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
INITIAL CONDITIONS:
Salem Unit 2 is operating at 99% power, coasting down into a refueling outage which will start in 2 weeks.
Irradiated fuel movement is in progress in the Spent Fuel Pool IAW S2.0P-IO.ZZ-0010, Spent Fuel Pool Manipulations, and will continue without interruption for the next 8 hours, at which time it will terminate.
The unit has no active Tech Spec LCOs.
21 SW pump is C/T for emergent strainer work.
The current time is 0800.
INITIATING CUE:
You have been directed to review the upcoming work for the shift and determine which activities may proceed as scheduled while continuing the fuel movement in the Spent Fuel Pool uninterrupted.
Work scheduled for today                           Circle whether each activity may or may not be performed lE any of the activities cannot proceed, explain your reason(s) 0900- 22 SW pump packing replacement                   MAY              MAY NOT 1000- 2A EOG tag out for maintenance                   MAY              MAY NOT 1300- 21 Chiller compressor oil change                 MAY              MAY NOT 1400- Delivery of New Fuel into the Fuel             MAY              MAY NOT Handling Building for upcoming refueling outage.
Page 7 of7 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION:                SALEM SYSTEM:                ADMINISTRATIVE TASK:                  Review a completed surveillance to calculate Shutdown Margin TASK NUMBER:            1200030301 JPM NUMBER:            15-01 NRC SRO A2 ALTERNATE PATH:      D                                  KIA NUMBER:     ~~~~~~~~~~
2.2.12 IMPORTANCE FACTOR:                             4.1 APPLICABILITY:                                                               RO            SRO EoD           ROD             STAD           sRo[KJ EVALUATION SETTING/METHOD:             Classroom


==REFERENCES:==
==REFERENCES:==
SC.RE-ST.ZZ-0002, Rev. 23 Shutdown Margin Calculation S2.RE-RA.ZZ-0016, Rev. 8 Figures Salem Unit 2 Technical Specifications TSAS 3.1.3.1 Movable Control Assemblies TOOLS AND EQUIPMENT:          Calculator VALIDATED JPM COMPLETION TIME:                  20 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS:                      30 minutes Developed By:                  G Gauding                            Date:  8-10-16 Instructor Validated:                R Boyer I P Williams                      Date:  9-28-16 / 10-4-16 Approved By:                  s~:~f;(                                Date:  10//rl.
Tra/1:~nment Approved By:                                                        Date:  1oj1~r.,
Operations Repr    entative ACTUAL JPM COMPLETION TIME:
ACTUAL TIME CRITICAL COMPLETION TIME:
PERFORMED BY:
GRADE:    D  SAT      D    UNSAT REASON, IF UNSATISFACTORY:
EVALUATOR'S SIGNATURE:                                                      DATE:
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 1 of 6


SC.RE-ST.ZZ-0002, Rev. 23 Shutdown Margin Calculation S2.RE-RA.ZZ-0016, Rev. 8 Figures 4.1 RO SRO Salem Unit 2 Technical Specifications TSAS 3.1.3.1 Movable Control Assemblies TOOLS AND EQUIPMENT:
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME:   ~~~~~~~~~~~~~~~
Calculator VALIDATED JPM COMPLETION TIME: 20 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: Developed By: Validated:
DATE:
Approved By: Approved By: G Gauding Instructor R Boyer I P Williams Operations Repr entative ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY:
SYSTEM:               Administrative TASK:                 Review a completed surveillance to calculate Shutdown Margin TASK                   1200030301 NUMBER:
EVALUATOR'S SIGNATURE:
INITIAL CONDITIONS:
30 minutes Date: 8-10-16 Date: 9-28-16 / 10-4-16 Date: 10//rl. Date:
          -   Unit 2 Reactor Power is 100%.
DATE: PSEG Restricted
          -   All Control Rod Group Demand Counters are at 227 steps.
-Possession Requires Specific Permission from Nuclear Training Page 1 of 6 OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME:
          -   Current boron concentration is 300 ppm.
DATE: SYSTEM: Administrative TASK: Review a completed surveillance to calculate Shutdown Margin TASK 1200030301 NUMBER: INITIAL CONDITIONS:  
          -   Current core burnup is 10,000 EFPH.
-Unit 2 Reactor Power is 100%. -All Control Rod Group Demand Counters are at 227 steps. -Current boron concentration is 300 ppm. -Current core burnup is 10,000 EFPH. -Control Rod 105 was declared INOPERABLE at 1000 today due to not moving out during a rod exercise test. A Shutdown Margin Calculation has been performed IAW SC.RE-ST.ZZ-0002, Shutdown Margin Calculation, to satisfy the action requirement of TSAS 3.1.3.1 Action c.3. -Control Rod 105 has been identified as trippable and is currently at 214 steps. -The current time is 1030. INITIATING CUE: 1. Review the attached SOM calculation procedure SC.RE-ST.ZZ-0002 for completeness and accuracy.
          -   Control Rod 105 was declared INOPERABLE at 1000 today due to not moving out during a rod exercise test. A Shutdown Margin Calculation has been performed IAW SC.RE-ST.ZZ-0002, Shutdown Margin Calculation, to satisfy the action requirement of TSAS 3.1.3.1 Action c.3.
: 2. Note any discrepancies found by the review on Attachment
          - Control Rod 105 has been identified as trippable and is currently at 214 steps.
: 7. 3. Determine if SOM is SAT. This is a time critical JPM. Time will start when procedures are given to you. Time will stop when procedures are returned to proctor. Successful Completion Criteria:
          - The current time is 1030.
INITIATING CUE:
: 1. Review the attached SOM calculation procedure SC.RE-ST.ZZ-0002 for completeness and accuracy.
: 2. Note any discrepancies found by the review on Attachment 7.
: 3. Determine if SOM is SAT.
This is a time critical JPM. Time will start when procedures are given to you. Time will stop when procedures are returned to proctor.
Successful Completion Criteria:
: 1. All critical steps completed.
: 1. All critical steps completed.
: 2. All sequential steps completed in order. 3. All time-critical steps completed within allotted time. 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made Task Standard for Successful Completion:
: 2. All sequential steps completed in order.
: 1. Determines the incorrect value for Control Bank Worth and Shutdown Bank Worth have been used. 2. Determines SOM with correct values used is SAT. 3. Completes review within 30 minutes. PSEG Restricted  
: 3. All time-critical steps completed within allotted time.
-Possession Requires Specific Permission from Nuclear Training Page 2 of 6 OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: _________
: 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made Task Standard for Successful Completion:
_ DATE: _________
: 1. Determines the incorrect value for Control Bank Worth and Shutdown Bank Worth have been used.
_ System: ADMINISTRATIVE Task: Review a completed surveillance to calculate Shutdown Margin STEP
: 2. Determines SOM with correct values used is SAT.
* NO. 1 2 3 *
: 3. Completes review within 30 minutes.
* STEP (*Denotes a Critical Step) STANDARD EVAL SIU Note to Evaluator:
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 2 of 6
The time critical aspect refers to the time required when the Shutdown Margin requirement of TSAS 3.1.3.1.c must be met. Provide the marked up copy of SC.RE-Ensures Sections 3 and 4 are completed.
 
ST.ZZ-0002 and copy of S2.RE-RA.ZZ-0016, Curve Book. Time Start: Review Section 5 to ensure the correct Reviews Section 5 and determines the correct Attachment was performed.
OPERATOR TRAINING PROGRAM                     NAME: _ _ _ _ _ _ _ _ __
Attachment (3) was performed.
JOB PERFORMANCE MEASURE                       DATE: _ _ _ _ _ _ _ _ __
Review the completed Shutdown Reviews SOM and determines:
System: ADMINISTRATIVE Task:   Review a completed surveillance to calculate Shutdown Margin STEP                                                                               COMMENTS STEP         (*Denotes a Critical Step)                             STANDARD                     EVAL   (Required for UNSAT
Margin Calculation:
* NO.                                                                                              SIU       Evaluation)
: 1. An incorrect value for Total Control Bank Worth (Step 4.2.1) has been used (0 EFPH value vs current 10,000 EFPH value) 2. An incorrect value for Total Shutdown Bank Worth (Step 4.2.2)has been used (0 EFPH value vs current 10,000 EFPH value) PSEG Restricted  
Note to Evaluator: The time critical aspect refers to the time required when the Shutdown Margin requirement of TSAS 3.1.3.1.c must be met.
-Possession Requires Specific Permission from Nuclear Training Page 3 of 6 COMMENTS (Required for UNSAT Evaluation)
1      Provide the marked up copy of SC.RE- Ensures Sections 3 and 4 are completed.
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: __________
ST.ZZ-0002 and copy of S2.RE-RA.ZZ-0016, Curve Book.
_ DATE: -----------
Time Start:
System: ADMINISTRATIVE Task: Review a completed surveillance to calculate Shutdown Margin STEP
2      Review Section 5 to ensure the correct   Reviews Section 5 and determines the correct Attachment was performed.               Attachment (3) was performed.
* NO.
3      Review the completed Shutdown             Reviews SOM and determines:
* 3 can't * *
* Margin Calculation:                           1. An incorrect value for Total Control Bank Worth (Step 4.2.1) has been used (0 EFPH value vs current
* 4
* 10,000 EFPH value)
* STEP (*Denotes a Critical Step) STANDARD EVAL S/U 3. Determines Trippable Rod Worth is incorrect based on incorrect steps 4.2.1 and 4.2.2) 4. Determines Ten Percent Rod Worth Penalty (step 4.3.2) is incorrect based on incorrect steps 4.2.1 and 4.2.2) 5. Determines SOM is incorrect based on incorrect steps 4.2.1 and 4.2.2 and 4.3.2) Correct Values are: 4.2.1 -3841 4.3.1 -5948 4.2.2 -3335 4.3.2 645 4.2.3 728 4.3.4 2742 4.2.4 0 4.3.5 -2441 4.2.5 500 4.2.6 0 4.2.7 -5948 Acceptance Criteria Determines Acceptance Criteria are still met with correct values used. Turns in procedures within 30 minutes of start time. Time Stop: ****Total time to complete JPM MUST be 30 minutes or less.****
: 2. An incorrect value for Total Shutdown Bank Worth (Step 4.2.2)has been used (0 EFPH value vs current 10,000 EFPH value)
PSEG Restricted  
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 3 of 6
-Possession Requires Specific Permission from Nuclear Training Page 4 of 6 COMMENTS (Required for UNSAT Evaluation) 
 
. I OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation.
OPERATOR TRAINING PROGRAM                       NAME: _ _ _ _ _ _ _ _ _ __
Prior to JPM usage, revalidate JPM using steps 8 and 11 below. v 1. Task description and number, JPM description and number are identified.
JOB PERFORMANCE MEASURE                         DATE:- - - - - - - - - - -
v / }t; 2. Knowledge and Abilities (KIA) references are included.  
System:   ADMINISTRATIVE Task:   Review a completed surveillance to calculate Shutdown Margin STEP                                                                                   COMMENTS STEP         (*Denotes a Critical Step)                             STANDARD                       EVAL   (Required for UNSAT
"'-/ ; Performance location specified. (in-plant, control room, or simulator) v Initial setup conditions are identified.  
* NO.                                                                                                S/U       Evaluation)
\r I J 5. Initiating and terminating Cues are properly identified.
* 3                                                    3. Determines Trippable Rod Worth is can't                                                      incorrect based on incorrect steps 4.2.1 and 4.2.2)
v-/ P/ 9--6. Task standards identified and verified by SME review. \]'-
* 4. Determines Ten Percent Rod Worth Penalty (step 4.3.2) is incorrect based on incorrect steps 4.2.1 and 4.2.2)
steps meet the criteria for critical steps and are identified with an asterisk (').
* 5. Determines SOM is incorrect based on incorrect steps 4.2.1 and 4.2.2 and 4.3.2)
the procedure referenced by this JPM matches the most current revision of that procedure:
Correct Values are:
Procedure Date
4.2.1 -3841                 4.3.1 -5948 4.2.2 -3335                 4.3.2 645 4.2.3 728                   4.3.4 2742 4.2.4 0                     4.3.5 -2441 4.2.5 500 4.2.6 0 4.2.7 -5948
__ _ J D9. Pilot test the JPM: a. verify Cues both verbal and visual are free of conflict, and b. ensure performance time is accurate.
* 4  Acceptance Criteria                       Determines Acceptance Criteria are still met with correct values used.
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructor:  
* Turns in procedures within 30 minutes of start time.
-------------
Time Stop:
Date: r6yj,&#xa3;_ Date:
                                                          ****Total time to complete JPM MUST be 30 minutes or less.****
Date: ------PSEG Restricted  
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 4 of 6
-Possession Requires Specific Permission from Nuclear Training Page 5 of 6 INITIAL CONDITIONS:
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE -Unit 2 Reactor Power is 100%. -All Control Rod Group Demand Counters are at 227 steps. -Current boron concentration is 300 ppm. -Current core burnup is 10,000 EFPH. -Control Rod 105 was declared INOPERABLE at 1000 today due to not moving out during a rod exercise test. A Shutdown Margin Calculation has been performed IAW SC.RE-ST.ZZ-0002, Shutdown Margin Calculation, to satisfy the action requirement of TSAS 3.1.3.1 Action c.3. -Control Rod 105 has been identified as trippable and is currently at 214 steps. -The current time is 1030. INITIATING CUE: 1. Review the attached SOM calculation procedure SC.RE-ST.ZZ-0002 for completeness and accuracy.
I
: 2. Note any discrepancies found by the review on Attachment
  .
: 7. 3. Determine if SOM is SAT. This is a time critical JPM. Time will start when procedures are given to you. Time will stop when procedures are returned to proctor. PSEG Restricted  
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below.
-Possession Requires Specific Permission from Nuclear Training Page 6 of 6 STATION: SYSTEM: TASK: TASK NUMBER: JPM NUMBER: OPERA TOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SALEM ADMINISTRATIVE Determine required actions upon Radioactive Effluent Monitor failure N1200010301 15-01 NRC SRO Admin A3 KIA NUMBER: 2.3.11 ALTERNATE PATH: CJ _________
v   ~ 1. Task description and number, JPM description and number are identified.
_, IMPORTANCE FACTOR: 4.3 ----APPLICABILITY:
v / }t; 2. Knowledge and Abilities (KIA) references are included.
RO SRO EOCJ ROCJ STAL] SRO[ZJ EVALUATION SETTING/METHOD:
      "'- /   ; ~3. Performance location specified. (in-plant, control room, or simulator) v   ~4. Initial setup conditions are identified.
Classroom Salem ODCM, Salem Tech Specs, S1 .OP-SO.WL-0001, Rev. 27, S1 .OP-SO.WG-
      \r I J~      5. Initiating and terminating Cues are properly identified.
v- /     P/ 9--6. Task standards identified and verified by SME review.
    \]'-
          ~Critical steps meet the criteria for critical steps and are identified with an asterisk (').
          ~Verify the procedure referenced by this JPM matches the most current revision of that procedure: Procedure Rev.~ Date _1:;~/"'~l'_'*-_ __
J D9.     Pilot test the JPM:
: a. verify Cues both verbal and visual are free of conflict, and
: b. ensure performance time is accurate.
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM.
____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.
Date:    r6yj,&#xa3;_
Date: --./9f---<Tm~~--
SME/lnstructor:                                                 Date: - - - - - -
                            -------------
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 5 of 6
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE INITIAL CONDITIONS:
          - Unit 2 Reactor Power is 100%.
          - All Control Rod Group Demand Counters are at 227 steps.
          - Current boron concentration is 300 ppm.
          - Current core burnup is 10,000 EFPH.
          - Control Rod 105 was declared INOPERABLE at 1000 today due to not moving out during a rod exercise test. A Shutdown Margin Calculation has been performed IAW SC.RE-ST.ZZ-0002, Shutdown Margin Calculation, to satisfy the action requirement of TSAS 3.1.3.1 Action c.3.
          - Control Rod 105 has been identified as trippable and is currently at 214 steps.
        - The current time is 1030.
INITIATING CUE:
: 1. Review the attached SOM calculation procedure SC.RE-ST.ZZ-0002 for completeness and accuracy.
: 2. Note any discrepancies found by the review on Attachment 7.
: 3. Determine if SOM is SAT.
This is a time critical JPM. Time will start when procedures are given to you. Time will stop when procedures are returned to proctor.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 6 of 6
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION:                SALEM SYSTEM:                ADMINISTRATIVE TASK:                  Determine required actions upon Radioactive Effluent Monitor failure TASK NUMBER:            N1200010301 JPM NUMBER:            15-01 NRC SRO Admin A3 ALTERNATE PATH:      CJ                                    KIA NUMBER:     _________    2.3.11     _,
IMPORTANCE FACTOR:                               4.3
                                                                              - -RO- -           SRO APPLICABILITY:
EOCJ         ROCJ             STAL]           SRO[ZJ EVALUATION SETTING/METHOD:               Classroom Salem ODCM, Salem Tech Specs, S1 .OP-SO.WL-0001, Rev. 27, S1 .OP-SO.WG-


==REFERENCES:==
==REFERENCES:==
0011, Rev. 31, S1 .OP-SO.CBV-0002, Rev. 21 (All checked 8-10-16)
TOOLS AND EQUIPMENT:
VALIDATED JPM COMPLETION TIME:                      25 min TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS:                              N/A Developed By:                        G Gauding                          Date: 8-10-16 Instructor Validated By:                                                            Date:  9-28-16 / 10-4-16 Approved By:
Approved By:
ACTUAL TIME CRITICAL COMPLETION TIME:
PERFORMED BY:
GRADE:    D    SAT      D    UNSAT REASON, IF UNSATISFACTORY:
EVALUATOR'S SIGNATURE:                                                          DATE:
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 1 of 8


0011, Rev. 31, S1 .OP-SO.CBV-0002, Rev. 21 (All checked 8-10-16) TOOLS AND EQUIPMENT:
,.
VALIDATED JPM COMPLETION TIME: 25 min TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: Developed By: Validated By: Approved By: Approved By: G Gauding Instructor ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY:
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME:
EVALUATOR'S SIGNATURE:
DATE:
N/A Date: 8-10-16 Date: 9-28-16 / 10-4-16 DATE: PSEG Restricted
SYSTEM:              Administrative TASK:                Determine required actions upon Radioactive Effluent Monitor failure TASK NUMBER:          N1200010301 INITIAL              Unit 1 is operating at 100% power.
-Possession Requires Specific Permission from Nuclear Training Page 1 of 8 
CONDITIONS:
,. SYSTEM: TASK: TASK NUMBER: INITIAL CONDITIONS:
Radiation Monitor 1R12A, Containment Noble Gas, failed its Source Check when preparing to perform a normal Containment Pressure Relief IAW S1 .OP-SO.CBV-0002, Containment Pressure-Vacuum Relief System Operation.
INITIATING CUE: OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: DATE: Administrative Determine required actions upon Radioactive Effluent Monitor failure N1200010301 Unit 1 is operating at 100% power. Radiation Monitor 1R12A, Containment Noble Gas, failed its Source Check when preparing to perform a normal Containment Pressure Relief IAW S1 .OP-SO.CBV-0002, Containment Pressure-Vacuum Relief System Operation.
11 CVCS Monitor Tank is ready for release.
11 CVCS Monitor Tank is ready for release. 14 Gas Decay Tank (GOT) is ready for release. Prior to initiating the Containment Pressure Relief, Rad Monitor 1 R41 D, Plant Vent Release Rate, indication fails high, and is confirmed as an instrument failure. For the following radiological releases, determine:
14 Gas Decay Tank (GOT) is ready for release.
: 1) Can the release be performed with the failed monitors described above, and, 2) If the release can be performed, what compensatory actions are required, if any. Assume each release will be performed individually.
INITIATING            Prior to initiating the Containment Pressure Relief, Rad Monitor 1R41 D, Plant Vent CUE:                  Release Rate, indication fails high, and is confirmed as an instrument failure.
RELEASES REQ
For the following radiological releases, determine:
* 14 GOT release
: 1)     Can the release be performed with the failed monitors described above, and,
* Containment Pressure Relief
: 2)     If the release can be performed, what compensatory actions are required, if any.
* 11 CVCS Monitor Tank release CAN BE RELEASED?
Assume each release will be performed individually.
COMP ACTION YES I NO YES I NO YES I NO Successful Completion Criteria:
RELEASES                           CAN BE RELEASED?        COMP ACTION REQ
: 1. All critical steps completed
* 14 GOT release                           YES I NO
: 2. All sequential steps completed in order 3. All time-critical steps completed within allotted time 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made (and NRC concurrence is obtained).
* Containment Pressure Relief             YES I NO
* 11 CVCS Monitor Tank release             YES I NO Successful Completion Criteria:
: 1.     All critical steps completed
: 2.     All sequential steps completed in order
: 3.     All time-critical steps completed within allotted time
: 4.     JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made (and NRC concurrence is obtained).
Task Standard for Successful Completion:
Task Standard for Successful Completion:
: 1. Determines ALL the releases may be performed.
: 1. Determines ALL the releases may be performed.
: 2. Determines additional compensatory measures apply for the Waste Gas Release and the Containment Pressure Relief per key, and no additional compensatory actions are required for Liquid Release.
: 2. Determines additional compensatory measures apply for the Waste Gas Release and the Containment Pressure Relief per key, and no additional compensatory actions are required for Liquid Release.
System: ADMINISTRATIVE OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: ----------
 
DATE: _________
OPERATOR TRAINING PROGRAM                       NAME:
_ Task: Determine required actions upon Radioactive Effluent Monitor failure
                                                                                                        ----------
* STEP STEP NO.
JOB PERFORMANCE MEASURE                        DATE: _ _ _ _ _ _ _ _ __
* Denotes a Critical Step Provide blank copies of: S1 .OP-SO.WG-0011 S1 .OP-SO.CBV-0002 S1 .OP-SO.WL-0001 Salem ODCM Waste Gas Release S1 .OP-SO.WG-0011 STANDARD EVAL COMMENTS S/U (Required for UNSAT evaluation)
System:  ADMINISTRATIVE Task:   Determine required actions upon Radioactive Effluent Monitor failure
Determines ODCM 3.3.3.9 applies to Gaseous Effluent which directs actions per Table 3.3-13. Determines Table 3.3-13, Instrument  
* STEP               STEP                               STANDARD                        EVAL                COMMENTS NO.
#1, Waste Gas Holdup System is applicable, which requires (1)
* Denotes a Critical Step                                                     S/U            (Required for UNSAT evaluation)
D. Action 31 applies. PSEG Restricted  
Provide blank copies of:
-Possession Requires Specific Permission from Nuclear Training Page 3 of 8 System: ADMINISTRATIVE OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: ----------
S1 .OP-SO.WG-0011 S1 .OP-SO.CBV-0002 S1 .OP-SO.WL-0001 Salem ODCM Waste Gas Release             Determines ODCM 3.3.3.9 applies to S1 .OP-SO.WG-0011              Gaseous Effluent which directs actions per Table 3.3-13.
DATE: _________
Determines Table 3.3-13, Instrument #1, Waste Gas Holdup System is applicable, which requires (1) 1R41A~ D. Action 31 applies.
_ Task: Determine required actions upon Radioactive Effluent Monitor failure
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 3 of 8
* STEP STEP NO.
 
* Denotes a Critical Step * *
OPERATOR TRAINING PROGRAM                       NAME:
* STANDARD EVAL COMMENTS S/U (Required for UNSAT evaluation)
                                                                                                        ----------
Action 31 states that with less than the minimum required Operable channels, the contents of the tank may be released provided that prior to the initiating the release: a. At least two independent samples of the tanks contents are analyzed, and b. At least two technically qualified members of the facility Staff independently verify the release rate calculations and discharge valving lineup; otherwise suspend release of radioactive effluents via this pathway. Additionally, S1.0P-SO.WG-0011, Discharge of 14 Gas Decay Tank to Plant Vent, Attachment 2, Section 3.0, Dose Estimates and Approval, Step 3.4.C (on page 18) states ... " Grab samples are being obtained at least once per 8 hours AND analyzed for gaseous principal emitters within 24 hours PSEG Restricted  
DATE: _ _ _ _ _ _ _ _ __
-Possession Requires Specific Permission from Nuclear Training Page 4 of 8 System: ADMINISTRATIVE OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: __________
JOB PERFORMANCE MEASURE System:  ADMINISTRATIVE Task:   Determine required actions upon Radioactive Effluent Monitor failure
_ DATE: __________
* STEP               STEP                               STANDARD                        EVAL                COMMENTS NO.
_ Task: Determine required actions upon Radioactive Effluent Monitor failure
* Denotes a Critical Step                                                     S/U           (Required for UNSAT evaluation)
* STEP STEP NO.
Action 31 states that with less than the minimum required Operable channels, the contents of the tank may be released provided that prior to the initiating the release:
* Denotes a Critical Step Containment Pressure Relief S1 .OP-SO.CBV-0002 STANDARD EVAL COMMENTS S/U (Required for UNSAT evaluation)
* a. At least two independent samples of the tanks contents are analyzed,
Determines that Precaution and Limitation 2.3 of S1 .OP-SO.CBV-0001 directs operator to notify Chemistry to comply with the contingency actions associated with the ODCM prior to performing a Containment Pressure Relief. Determines Table 3.3-13, Instrument  
* and
#3, applies to the Containment Pressure Relief. With both channels (1 R41A 1 R12A) inoperable, Action 37 applies. PSEG Restricted  
: b. At least two technically qualified members of the facility Staff independently verify the release rate calculations and discharge valving lineup; otherwise suspend release of radioactive effluents via this pathway.
-Possession Requires Specific Permission from Nuclear Training Page 5 of 8 System: ADMINISTRATIVE OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: __________
* Additionally, S1.0P-SO.WG-0011, Discharge of 14 Gas Decay Tank to Plant Vent, Attachment 2, Section 3.0, Dose Estimates and Approval, Step 3.4.C (on page 18) states ... " Grab samples are being obtained at least once per 8 hours AND analyzed for gaseous principal
_ DATE: __________
                                          ~amma emitters within 24 hours PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 4 of 8
_ Task: Determine required actions upon Radioactive Effluent Monitor failure
 
* STEP STEP STANDARD EVAL COMMENTS NO.
OPERATOR TRAINING PROGRAM                       NAME: _ _ _ _ _ _ _ _ _ __
* Denotes a Critical Step S/U (Required for UNSAT evaluation)
JOB PERFORMANCE MEASURE                       DATE: _ _ _ _ _ _ _ _ _ __
System: ADMINISTRATIVE Task:   Determine required actions upon Radioactive Effluent Monitor failure STEP                STEP                              STANDARD                        EVAL                COMMENTS
* NO.
* Denotes a Critical Step                                                     S/U           (Required for UNSAT evaluation)
Containment Pressure Relief    Determines that Precaution and Limitation S1 .OP-SO.CBV-0002            2.3 of S1 .OP-SO.CBV-0001 directs operator to notify Chemistry to comply with the contingency actions associated with the ODCM prior to performing a Containment Pressure Relief.
Determines Table 3.3-13, Instrument #3, applies to the Containment Pressure Relief.
With both channels (1 R41A ~DOR 1R12A) inoperable, Action 37 applies.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 5 of 8
 
OPERATOR TRAINING PROGRAM                       NAME: _ _ _ _ _ _ _ _ _ __
JOB PERFORMANCE MEASURE                       DATE: _ _ _ _ _ _ _ _ _ __
System:   ADMINISTRATIVE Task:   Determine required actions upon Radioactive Effluent Monitor failure STEP               STEP                               STANDARD                       EVAL                 COMMENTS
* NO.
* Denotes a Critical Step                                                     S/U           (Required for UNSAT evaluation)
Action 37 states that with less than the minimum required Operable channels, Containment Pressure Reliefs may be performed provided that prior to initiating the release:
Action 37 states that with less than the minimum required Operable channels, Containment Pressure Reliefs may be performed provided that prior to initiating the release:
* a. At least two independent samples of the tanks contents are analyzed, and
* a. At least two independent samples of the tanks contents are analyzed, and
* b. At least two technically qualified members of the facility Staff independently verify the release rate calculations, otherwise suspend release of radioactive effluents via this pathway. Note: Applicant may identify compensatory actions per P&L 3.11
* b. At least two technically qualified members of the facility Staff independently verify the release rate calculations, otherwise suspend release of radioactive effluents via this pathway.
* Waste Liquid Release Determines no compensatory actions are S1 .OP-SO.WL-0001 required to initiate the Liquid Release. Terminate JPM when all paperwork is handed in. Note to Evaluator:
Note: Applicant may identify compensatory actions per P&L 3.11
JPM modeled after Pilgrim Jan 2011 NRC Exam SRO Admin JPM RC. PSEG Restricted  
* Waste Liquid Release         Determines no compensatory actions are S1 .OP-SO.WL-0001             required to initiate the Liquid Release.
-Possession Requires Specific Permission from Nuclear Training Page 6 of 8 OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation.
Terminate JPM when all paperwork is handed in.
Prior to JPM usage, revalidate JPM using steps 8 and 11 below. \}v / 1f1*. Task description and number, JPM description and number are identified.  
Note to Evaluator: JPM modeled after Pilgrim Jan 2011 NRC Exam SRO Admin JPM RC.
\j-/ Knowledge and Abilities (KIA) references are included.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 6 of 8
Vv /
 
Performance location specified. (in-plant, control room, or simulator) I Initial setup conditions are identified.  
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below.
'-J ./-r-Initiating and terminating Cues are properly identified.  
\}v / ~ 1f1*. Task description and number, JPM description and number are identified.
/ r P6. Task standards identified and verified by SME review. l""'-[;?7.
\j- /     ~~- Knowledge and Abilities (KIA) references are included.
Critical steps meet the criteria for critical steps and are identified with an asterisk (*). ,eA--
Vv /       ~<{Ji;j. Performance location specified. (in-plant, control room, or simulator)
the procedure referenced by this JPM matches the most current revision of that procedure:
~ I ~ ~- Initial setup conditions are identified.
Procedure Rev. __ Date----..,----
'-J ./- r- ~-        Initiating and terminating Cues are properly identified.
/)_.,,-A\\ 9. Pilot test the JPM: a. verify Cues both verbal and visual are free of conflict, and b. ensure performance time is accurate.
      /r P6.         Task standards identified and verified by SME review.
r-Jft/8;;-(i_Dthe JPM cannot be performed as written with proper responses, then revise the JPM . .... w'fT11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.
l""'-[;?7. Critical steps meet the criteria for critical steps and are identified with an asterisk (*).
SME/lnstructor: fv; Date: ci /2$} lb Date: SME/lnstructor:
          ,eA-- ~*Verify the procedure referenced       by this JPM matches the most current revision of that procedure: Procedure Rev. _ _ Date----..,----
Date: -------------
              /)_.,,-                                         A\\   N-v:t.:JJ'~ ~w ~fz.<1;ltio
------PSEG Restricted  
          ~ 9. Pilot test the JPM:
-Possession Requires Specific Permission from Nuclear Training Page 7 of 8 INITIAL CONDITIONS:
: a. verify Cues both verbal and visual are free of conflict, and
Unit 1 is operating at 100% power. Radiation Monitor 1R12A, Containment Noble Gas, failed its Source Check when preparing to perform a normal Containment Pressure Relief IAW S1 .OP-SO.CBV-0002, Containment Pressure-Vacuum Relief System Operation.
: b. ensure performance time is accurate.
11 CVCS Monitor Tank is ready for release. 14 Gas Decay Tank (GOT) is ready for release. INITIATING CUE: Prior to initiating the Containment Pressure Relief, Rad Monitor 1 R41 D, Plant Vent Release Rate, indication fails high, and is confirmed as an instrument failure. For the following radiological releases, determine:
r-Jft/8;;-(i_Dthe JPM cannot be performed as written with proper responses, then revise the JPM .
: 1) Can the release be performed with the failed monitors described above, and, 2) If the release can be performed, what compensatory actions are required, if any. Assume each release will be performed individually.
          . . w'fT11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.
RELEASES CAN BE RELEASED?
SM81nstructo~-~(t;_                                                Date:     ci /2$} lb SME/lnstructor:            ~/          fv; ~J--L                  Date:   l~C SME/lnstructor:                                                     Date: - - - - - -
COMP ACTION REQ
                          -------------
* 14 GOT release YES I NO
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 7 of 8
* Containment Pressure Relief YES/ NO
 
* 11 CVCS Monitor Tank release YES I NO PSEG Restricted  
INITIAL CONDITIONS:
-Possession Requires Specific Permission from Nuclear Training Page 8 of 8 STATION: SYSTEM: OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SALEM Emergency Plan TASK: Classify an event and complete an ICMF within the regulatory committed time limit (ESG-1) TASK NUMBER: 1240020502 JPM NUMBER: 15-01 NRC SRO Admin A4-1 (ESG-1) KIA NUMBER: 2.4.41 ALTERNATE PATH: _I __ I IMPORTANCE FACTOR: 4.6 APPLICABILITY:
Unit 1 is operating at 100% power.
RO SRO EoD ROD STAD SRO[K] EVALUATION SETTING/METHOD:
Radiation Monitor 1R12A, Containment Noble Gas, failed its Source Check when preparing to perform a normal Containment Pressure Relief IAW S1 .OP-SO.CBV-0002, Containment Pressure-Vacuum Relief System Operation.
Simulate (Simulator or Classroom)  
11 CVCS Monitor Tank is ready for release.
14 Gas Decay Tank (GOT) is ready for release.
INITIATING CUE:
Prior to initiating the Containment Pressure Relief, Rad Monitor 1R41 D, Plant Vent Release Rate, indication fails high, and is confirmed as an instrument failure.
For the following radiological releases, determine:
: 1)     Can the release be performed with the failed monitors described above, and,
: 2)     If the release can be performed, what compensatory actions are required, if any.
Assume each release will be performed individually.
RELEASES                           CAN BE RELEASED?         COMP ACTION REQ
* 14 GOT release                           YES I NO
* Containment Pressure Relief             YES/ NO
* 11 CVCS Monitor Tank release             YES I NO PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 8 of 8
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION:              SALEM SYSTEM:                Emergency Plan TASK:                 Classify an event and complete an ICMF within the regulatory committed time limit (ESG-1)
TASK NUMBER:           1240020502 JPM NUMBER:           15-01 NRC SRO Admin A4-1 (ESG-1)
ALTERNATE PATH:      _ I_ _I                              KIA NUMBER:   ~~~~~~~~~~
2.4.41 IMPORTANCE FACTOR:                           4.6 APPLICABILITY:                                                                 RO           SRO EoD           ROD               STAD           SRO[K]
EVALUATION SETTING/METHOD:               Simulate (Simulator or Classroom)


==REFERENCES:==
==REFERENCES:==
EP-SA-111-F2 Rev. 2 (ALERT)
TOOLS AND EQUIPMENT:            Inform Simulator Operators - DO NOT ERASE ANY PROCEDURES UNTIL THE SRO EVALUATOR APPROVES VALIDATED JPM COMPLETION TIME:                    12 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS:                      15 minutes Developed By:                        G Gauding                      Date:    9-19-15 Instructor Validated By:                C Davis IP Williams                    Date:    9-21-16110-4-16 SME or Ins ruct~
Approved By:
Traini    epaUent Date:  1ff  u Approved By:                                                        Date: 1oj;j1r, obepartment ACTUAL JPM COMPLETION TIME:
ACTUAL TIME CRITICAL COMPLETION TIME:
PERFORMED BY:
GRADE:    D  SAT      D UNSAT REASON, IF UNSATISFACTORY:
EVALUATOR'S SIGNATURE:                                                      DATE:
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 1 of 8


EP-SA-111-F2 Rev. 2 (ALERT) TOOLS AND EQUIPMENT:
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME:   ~~~~~~~~~~~~~~-
Inform Simulator Operators
DATE:
-DO NOT ERASE ANY PROCEDURES UNTIL THE SRO EVALUATOR APPROVES VALIDATED JPM COMPLETION TIME: 12 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: Developed By: Validated By: Approved By: Approved By: G Gauding Instructor C Davis IP Williams SME or Ins Traini epaUent obepartment ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY:
SYSTEM:                 Emergency Plan TASK:                   Classify an event and complete an ICMF within the regulatory committed time limit (ESG-1)
EVALUATOR'S SIGNATURE:
TASK NUMBER:           1240020502 INITIAL CONDITIONS:
15 minutes Date: 9-19-15 Date: 9-21-16110-4-16 Date: 1ff u Date: 1oj;j1r, DATE: PSEG Restricted
: 1. You have a maximum of 5 minutes to review the Emergency Operating Procedures used during this scenario to refresh your memory of all events/paths. At the end of your review you will become the Shift Manager (SM). Inform the Evaluator when you are ready to assume SM duties. You may continue to reference the procedures or to look at the control board but "the clock will be running." If there are multiple ECG calls, classify the most severe.
-Possession Requires Specific Permission from Nuclear Training Page 1 of 8 OPERA TOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME:
INITIATING CUE:
DATE: SYSTEM: Emergency Plan TASK: Classify an event and complete an ICMF within the regulatory committed time limit (ESG-1) TASK NUMBER: 1240020502 INITIAL CONDITIONS:
You are the Duty SM. Classify the event, complete the correct ECG Attachment and provide an ICMF to the Primary Communicator.
: 1. You have a maximum of 5 minutes to review the Emergency Operating Procedures used during this scenario to refresh your memory of all events/paths.
This is a Time Critical JPM.
At the end of your review you will become the Shift Manager (SM). Inform the Evaluator when you are ready to assume SM duties. You may continue to reference the procedures or to look at the control board but "the clock will be running." If there are multiple ECG calls, classify the most severe. INITIATING CUE: You are the Duty SM. Classify the event, complete the correct ECG Attachment and provide an ICMF to the Primary Communicator.
Successful Completion Criteria:
This is a Time Critical JPM. Successful Completion Criteria:
: 1. All critical steps completed.
: 1. All critical steps completed.
: 2. All sequential steps completed in order. 3. All time-critical steps completed within allotted time. 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made. Task Standard for Successful Completion:
: 2. All sequential steps completed in order.
: 1. Declare an ALERT under EAL RB3.P within 15 minutes of start time, and provide ICMF to the Primary Communicator within the next 15 minutes. PSEG Restricted  
: 3. All time-critical steps completed within allotted time.
-Possession Requires Specific Permission from Nuclear Training Page 2 of 8 OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM: Emergency Plan TASK: Classify an event and complete an ICMF within the regulatory committed time limit (ESG-1) STEP
: 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made.
* NO. Att 2 A.1 STEP (*Denotes a Critical Step) STANDARD Provide candidate with 'Tear-off sheet" Reviews initial conditions and EOP's (as and Blank Copies of EP-SA-111-F1 necessary  
Task Standard for Successful Completion:
-5 minute limit prior to starting) through F4 (UE, ALERT, SAE, GE) *START TIME: *Start time begins when candidate Cue: The regulatory commitment time reports he/she is ready to assume SM clock has started. duties Reviews ECG to classify event Note: It is acceptable to use the laminated tables in the simulator, rather than the ECG Classifies the event Determines the classification of the event and refers to ECG Attachment 2 (Alert) CALL communicators to the Control Pages communicators and initials as SM Room Cue: I am the Primary Communicator PSEG Restricted  
: 1. Declare an ALERT under EAL RB3.P within 15 minutes of start time, and provide ICMF to the Primary Communicator within the next 15 minutes.
-Possession Requires Specific Permission from Nuclear Training Page 3 of 8 NAME: ------DATE: ------COMMENTS EVAL (Required for UNSAT S/U evaluation)
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 2 of 8
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM: Emergency Plan TASK: Classify an event and complete an ICMF within the regulatory committed time limit (ESG-1) STEP
 
* NO. Att 2 A.2 Att 2 A.3 STEP (*Denotes a Critical Step) STANDARD IF a Security Event is in progress, THEN Determines Security Event is not in IMPLEMENT the prompt actions of progress.
OPERATOR TRAINING PROGRAM                       NAME:
                                                                                                                ------
JOB PERFORMANCE MEASURE                         DATE: - - - - - -
SYSTEM:     Emergency Plan TASK:       Classify an event and complete an ICMF within the regulatory committed time limit (ESG-1)
COMMENTS STEP STEP                                                                                                         (Required
(*Denotes a Critical Step)                                                     EVAL
* NO.                                                                  STANDARD                             for UNSAT S/U evaluation)
Provide candidate with 'Tear-off sheet"   Reviews initial conditions and EOP's (as and Blank Copies of EP-SA-111-F1           necessary - 5 minute limit prior to starting) through F4 (UE, ALERT, SAE, GE)
                *START TIME:
                *Start time begins when candidate         Cue: The regulatory commitment time reports he/she is ready to assume SM       clock has started.
duties Reviews ECG to classify event             Note: It is acceptable to use the laminated tables in the simulator, rather than the ECG Classifies the event                       Determines the classification of the event and refers to ECG Attachment 2 (Alert)
Att 2      CALL communicators to the Control         Pages communicators and initials as SM A.1      Room Cue: I am the Primary Communicator PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 3 of 8
 
OPERATOR TRAINING PROGRAM                  NAME:
                                                                                                              ------
JOB PERFORMANCE MEASURE                    DATE: - - - - - -
SYSTEM:     Emergency Plan TASK:       Classify an event and complete an ICMF within the regulatory committed time limit (ESG-1)
COMMENTS STEP STEP                                                                                                         (Required
(*Denotes a Critical Step)                                                     EVAL
* NO.                                                                    STANDARD                           for UNSAT S/U evaluation)
Att 2      IF a Security Event is in progress, THEN       Determines Security Event is not in A.2      IMPLEMENT the prompt actions of               progress.
NC.EP-EP.ZZ-0102, EC Response, Attachment 10, prior to the classification.
NC.EP-EP.ZZ-0102, EC Response, Attachment 10, prior to the classification.
If time allows, DIRECT Classification Cue: No independent verification will be Independent Verification to be performed.
If time allows, DIRECT Classification Att 2                                                    Cue: No independent verification will be A.3      Independent Verification to be                 performed.
performed.
performed.
PSEG Restricted  
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 4 of 8
-Possession Requires Specific Permission from Nuclear Training Page 4 of 8 NAME: ------DATE: ------COMMENTS EVAL (Required for UNSAT S/U evaluation)
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM: Emergency Plan TASK: Classify an event and complete an ICMF within the regulatory committed time limit (ESG-1) STEP
OPERATOR TRAINING PROGRAM                        NAME:
* NO. Att 2 A.4 *
                                                                                                              ------
* Att 2 ' A.5 STEP (*Denotes a Critical Step) STANDARD After Classification Independent Declares an ALERT under RB3.P within Verification is obtained:
JOB PERFORMANCE MEASURE                          DATE: - - - - - -
15 minutes of Start Time:
SYSTEM:     Emergency Plan TASK:       Classify an event and complete an ICMF within the regulatory committed time limit (ESG-1)
* DECLARE the ALERT (enter time and date on ICMF) *COMPLETE I APPROVE the ICMF Completes and Approves the ICMF as follows: EAL#(s): RB3.P Description of Event: Potential Loss of the Reactor Coolant System Boundary Note: Description of Event is found in EAL Description Table Fills out Section Ill: Checks IS NOT for a Radiological Release in progress.
COMMENTS STEP STEP                                                                                                        (Required
Fills out Section IV: Retrieves wind speed (10)and direction (160) data from SPDS Initials for a1212roval to transmit I If time allows OBTAIN accuracy peer check of the completed ICMF Cue: No peer check will be performed.
(*Denotes a Critical Step)                                                     EVAL
PSEG Restricted  
* NO.                                                                  STANDARD                             for UNSAT S/U evaluation)
-Possession Requires Specific Permission from Nuclear Training Page 5 of 8 NAME: ------DATE: ------COMMENTS EVAL (Required S/U for UNSAT evaluation) i OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM: Emergency Plan TASK: Classify an event and complete an ICMF within the regulatory committed time limit (ESG-1) STEP
Att 2 After Classification Independent         Declares an ALERT under RB3.P within A.4 Verification is obtained:                 15 minutes of Start Time:
* NO. Att 2 A.6
*
* STEP (*Denotes a Critical Step) STANDARD Continue with NOTIFICATION AND ACTIVATION as follows:
* DECLARE the ALERT (enter time and date on ICMF)
* If not previously performed, ACTIVATE Cue: Activation of ERO Emergency I DIRECT ACTIVATION of ERO Emergency Callout (EP 96-003) Callout is not required for this JPM.
Completes and Approves the ICMF as
* DIRECT the Primary Communicator to Provides ICMF to Primary Communicator implement ECG Attachment 6 within 15 minutes of event declaration Terminate JPM when ICMF is given to the Evaluator.
*              *COMPLETE I APPROVE the ICMF follows:
PSEG Restricted  
EAL#(s): RB3.P Description of Event: Potential Loss of the Reactor Coolant System Boundary Note: Description of Event is found in EAL Description Table Fills out Section Ill:
-Possession Requires Specific Permission from Nuclear Training Page 6 of 8 NAME: ------DATE: ------COMMENTS EVAL (Required forUNSAT S/U evaluation)
Checks IS NOT for a Radiological Release in progress.
TQ-AA-106-0303 JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation.
Fills out Section IV:
Prior to JPM usage, revalidate JPM using steps 8 and 11 below. \,tJ description and number, JPM description and number are identified.  
Retrieves wind speed (10)and direction (160) data from SPDS Initials for a1212roval to transmit Att 2  '                                      I                                                 i A.5      If time allows OBTAIN accuracy peer check of the completed ICMF               Cue: No peer check will be performed.
/ 1),-.._ Knowledge and Abilities (KJA) references are included.  
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 5 of 8
/ Performance location specified. (in-plant, control room, or simulator)  
 
/ Initial setup conditions are identified.  
OPERATOR TRAINING PROGRAM                    NAME: - - - - - -
/ 4--s. Initiating and terminating Cues are properly identified.
JOB PERFORMANCE MEASURE                      DATE: - - - - - -
standards identified and verified by SME review. l-.... <fh. Critical steps meet the criteria for critical steps and are identified with an asterisk(*).
SYSTEM:     Emergency Plan TASK:       Classify an event and complete an ICMF within the regulatory committed time limit (ESG-1)
t,_tfi> 8. Verify the procedure referenced by this JPM matches the most current revision of procedure:
COMMENTS STEP STEP                                                                                                      (Required
Procedure Rev. __1_ Date '\ -'lf. { 6 f/\..,, 9. Pilot test the JPM: a. verify Cues both verbal and visual are free of conflict, and b. ensure performance time is accurate.
(*Denotes a Critical Step)                                                  EVAL
If the JPM cannot be performed as written with proper responses, then revise the JPM. (,,,.._
* NO.                                                                   STANDARD                          forUNSAT S/U evaluation)
JPM is revalidated, SME or Instructor sign and date JPM cover page.
Att 2 A.6       Continue with NOTIFICATION AND ACTIVATION as follows:
SME/lnstructor:
* If not previously performed, ACTIVATE I DIRECT ACTIVATION of ERO              Cue: Activation of ERO Emergency Callout is not required for this JPM.
SME/lnstructor:
Emergency Callout (EP 96-003)
____________
* DIRECT the Primary Communicator to       Provides ICMF to Primary Communicator
_
* implement ECG Attachment 6             within 15 minutes of event declaration Terminate JPM when ICMF is given to the Evaluator.
Date: _____ _ PSEG Restricted  
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 6 of 8
-Possession Requires Specific Permission from Nuclear Training Page 7 of 8 INITIAL CONDITIONS:
 
: 1. You have a maximum of 5 minutes to review the Emergency Operating Procedures used during this scenario to refresh your memory of all events/paths.
TQ-AA-106-0303 JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below.
At the end of your review you will become the Shift Manager (SM). Inform the Evaluator when you are ready to assume SM duties. You may continue to reference the procedures or to look at the control board but "the clock will be running."-lf there are multiple ECG calls, classify the most severe. INITIATING CUE: You are the Duty SM. Classify the event, complete the correct ECG Attachment and provide an ICMF to the Primary Communicator.
\,tJ /~~Task description and number, JPM description and number are identified.
This is a Time Critical JPM. PSEG Restricted  
      / 1),-.._~- Knowledge and Abilities (KJA) references are included.
-Possession Requires Specific Permission from Nuclear Training Page 8 of 8 STATION: SYSTEM: OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SALEM Emergency Plan TASK: Classify an event and complete an ICMF within the regulatory committed time limit (ESG-2) TASK NUMBER: 1240020502 JPM NUMBER: 15-01 NRC SRO Admin A4-1 (ESG-2) ALTERNATE PATH: KIA NUMBER: 2.4.41 IMPORTANCE FACTOR: 4.6 APPLICABILITY:
      / ~ Performance location specified. (in-plant, control room, or simulator)
RO SRO EOCJ ROCJ STAC] SRO[IJ EVALUATION SETTING/METHOD:
    /     ~-            Initial setup conditions are identified.
Simulate (Simulator or Classroom)  
    /     ~4--s.         Initiating and terminating Cues are properly identified.
          ~-Task standards identified and verified                 by SME review.
l-.... <fh. Critical steps meet the criteria for critical steps and are identified with an asterisk(*).
t,_tfi> 8. Verify the procedure referenced by this JPM matches the most current revision of
                    ~hat procedure: Procedure Rev. __1_ Date '\ -'lf. { 6 f/\..,,   9. Pilot test the JPM:
: a. verify Cues both verbal and visual are free of conflict, and
: b. ensure performance time is accurate.
            ~-~. If the JPM cannot be performed as written with proper responses, then revise the JPM.
(,,,.._   ~When JPM is revalidated, SME or Instructor sign and date JPM cover page.
SME/lnstructor~Af''&deg;                                                  Date:~
SME/lnstructor:                                 /~~J                  Date:~
SME/lnstructor: _ _ _ _ _ _ _ _ _ _ _ __                              Date: _ _ _ _ __
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 7 of 8
 
INITIAL CONDITIONS:
: 1. You have a maximum of 5 minutes to review the Emergency Operating Procedures used during this scenario to refresh your memory of all events/paths. At the end of your review you will become the Shift Manager (SM). Inform the Evaluator when you are ready to assume SM duties.
You may continue to reference the procedures or to look at the control board but "the clock will be running."-lf there are multiple ECG calls, classify the most severe.
INITIATING CUE:
You are the Duty SM. Classify the event, complete the correct ECG Attachment and provide an ICMF to the Primary Communicator.
This is a Time Critical JPM.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 8 of 8
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION:              SALEM SYSTEM:                Emergency Plan TASK:                 Classify an event and complete an ICMF within the regulatory committed time limit (ESG-2)
TASK NUMBER:           1240020502 JPM NUMBER:           15-01 NRC SRO Admin A4-1 (ESG-2)
ALTERNATE PATH:                                         KIA NUMBER:   ~~~~~~~~~~
2.4.41 IMPORTANCE FACTOR:                           4.6 APPLICABILITY:                                                               RO           SRO EOCJ         ROCJ           STAC]           SRO[IJ EVALUATION SETTING/METHOD:             Simulate (Simulator or Classroom)


==REFERENCES:==
==REFERENCES:==
EP-SA-111-F2 Rev. 2 (ALERT)
TOOLS AND EQUIPMENT:          Inform Simulator Operators - DO NOT ERASE ANY PROCEDURES UNTIL THE SRO EVALUATOR APPROVES VALIDATED JPM COMPLETION TIME:                  12 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS:                    15 minutes Developed By:                      G Gauding                      Date:    9-19-15 Instructor Validated By:                                                      Date:    9-21-16110-4-16 Approved By:
Approved By:
ACTUAL JPM COMPLETION TIME:
ACTUAL TIME CRITICAL COMPLETION TIME:
PERFORMED BY:
GRADE:    D  SAT      D UNSAT REASON, IF UNSATISFACTORY:
EVALUATOR'S SIGNATURE:                                                    DATE:
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 1of8


EP-SA-111-F2 Rev. 2 (ALERT) TOOLS AND EQUIPMENT:
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME:   ~~~~~~~~~~~~~~-
Inform Simulator Operators
DATE:
-DO NOT ERASE ANY PROCEDURES UNTIL THE SRO EVALUATOR APPROVES VALIDATED JPM COMPLETION TIME: 12 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: Developed By: Validated By: Approved By: Approved By: ACTUAL JPM COMPLETION TIME: G Gauding Instructor ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY:
SYSTEM:                 Emergency Plan TASK:                   Classify an event and complete an ICMF within the regulatory committed time limit (ESG-2)
EVALUATOR'S SIGNATURE:
TASK NUMBER:           1240020502 INITIAL CONDITIONS:
15 minutes Date: 9-19-15 Date: 9-21-16110-4-16 DATE: PSEG Restricted
: 1. You have a maximum of 5 minutes to review the Emergency Operating Procedures used during this scenario to refresh your memory of all events/paths. At the end of your review you will become the Shift Manager (SM). Inform the Evaluator when you are ready to assume SM duties. You may continue to reference the procedures or to look at the control board but "the clock will be running." If there are multiple ECG calls, classify the most severe.
-Possession Requires Specific Permission from Nuclear Training Page 1of8 OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME:
INITIATING CUE:
DATE: SYSTEM: Emergency Plan TASK: Classify an event and complete an ICMF within the regulatory committed time limit (ESG-2) TASK NUMBER: 1240020502 INITIAL CONDITIONS:
You are the Duty SM. Classify the event, complete the correct ECG Attachment and provide an ICMF to the Primary Communicator.
: 1. You have a maximum of 5 minutes to review the Emergency Operating Procedures used during this scenario to refresh your memory of all events/paths.
This is a Time Critical JPM.
At the end of your review you will become the Shift Manager (SM). Inform the Evaluator when you are ready to assume SM duties. You may continue to reference the procedures or to look at the control board but "the clock will be running." If there are multiple ECG calls, classify the most severe. INITIATING CUE: You are the Duty SM. Classify the event, complete the correct ECG Attachment and provide an ICMF to the Primary Communicator.
Successful Completion Criteria:
This is a Time Critical JPM. Successful Completion Criteria:
: 1. All critical steps completed.
: 1. All critical steps completed.
: 2. All sequential steps completed in order. 3. All time-critical steps completed within allotted time. 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made. Task Standard for Successful Completion:
: 2. All sequential steps completed in order.
: 1. Declare an ALERT under EAL RB3.L within 15 minutes of start time, and provide ICMF to the Primary Communicator within the next 15 minutes. PSEG Restricted  
: 3. All time-critical steps completed within allotted time.
-Possession Requires Specific Permission from Nuclear Training Page 2 of 8 OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM: Emergency Plan TASK: Classify an event and complete an ICMF within the regulatory committed time limit (ESG-2) STEP
: 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made.
* NO. Att 2 A.1 STEP (*Denotes a Critical Step) STANDARD Provide candidate with "Tear-off sheet" Reviews initial conditions and EOP's (as and Blank Copies of EP-SA-111-F1 necessary  
Task Standard for Successful Completion:
-5 minute limit prior to starting) through F4 (UE, ALERT, SAE, GE) *START TIME: *Start time begins when candidate Cue: The regulatory commitment time reports he/she is ready to assume SM clock has started. duties Reviews ECG to classify event Note: It is acceptable to use the laminated tables in the simulator, rather than the ECG Classifies the event Determines the classification of the event and refers to ECG Attachment 2 (Alert) CALL communicators to the Control Pages communicators and initials as SM Room Cue: I am the Primary Communicator PSEG Restricted  
: 1. Declare an ALERT under EAL RB3.L within 15 minutes of start time, and provide ICMF to the Primary Communicator within the next 15 minutes.
-Possession Requires Specific Permission from Nuclear Training Page 3 of 8 NAME: ------DATE: ------COMMENTS EVAL (Required for UNSAT S/U evaluation)
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 2 of 8
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM: Emergency Plan TASK: Classify an event and complete an ICMF within the regulatory committed time limit (ESG-2) STEP
 
* NO. Att 2 A.2 Att 2 A.3 STEP (*Denotes a Critical Step) STANDARD IF a Security Event is in progress, THEN Determines Security Event is not in IMPLEMENT the prompt actions of progress.
OPERATOR TRAINING PROGRAM                       NAME:
                                                                                                                ------
JOB PERFORMANCE MEASURE                         DATE: - - - - - -
SYSTEM:     Emergency Plan TASK:       Classify an event and complete an ICMF within the regulatory committed time limit (ESG-2)
COMMENTS STEP STEP                                                                                                         (Required
(*Denotes a Critical Step)                                                     EVAL
* NO.                                                                  STANDARD                             for UNSAT S/U evaluation)
Provide candidate with "Tear-off sheet"   Reviews initial conditions and EOP's (as and Blank Copies of EP-SA-111-F1           necessary - 5 minute limit prior to starting) through F4 (UE, ALERT, SAE, GE)
                *START TIME:
                *Start time begins when candidate         Cue: The regulatory commitment time reports he/she is ready to assume SM       clock has started.
duties Reviews ECG to classify event             Note: It is acceptable to use the laminated tables in the simulator, rather than the ECG Classifies the event                       Determines the classification of the event and refers to ECG Attachment 2 (Alert)
Att 2      CALL communicators to the Control         Pages communicators and initials as SM A.1      Room Cue: I am the Primary Communicator PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 3 of 8
 
OPERATOR TRAINING PROGRAM                  NAME:
                                                                                                              ------
JOB PERFORMANCE MEASURE                    DATE: - - - - - -
SYSTEM:     Emergency Plan TASK:       Classify an event and complete an ICMF within the regulatory committed time limit (ESG-2)
COMMENTS STEP STEP                                                                                                         (Required
(*Denotes a Critical Step)                                                     EVAL
* NO.                                                                    STANDARD                           for UNSAT S/U evaluation)
Att 2      IF a Security Event is in progress, THEN       Determines Security Event is not in A.2      IMPLEMENT the prompt actions of               progress.
NC.EP-EP.ZZ-0102, EC Response, Attachment 10, prior to the classification.
NC.EP-EP.ZZ-0102, EC Response, Attachment 10, prior to the classification.
If time allows, DIRECT Classification Cue: No independent verification will be Independent Verification to be performed.
If time allows, DIRECT Classification Att 2                                                    Cue: No independent verification will be A.3      Independent Verification to be                 performed.
performed.
performed.
PSEG Restricted  
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 4 of 8
-Possession Requires Specific Permission from Nuclear Training Page 4 of 8 NAME: ------DATE: ------COMMENTS EVAL (Required for UNSAT S/U evaluation)
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM: Emergency Plan TASK: Classify an event and complete an ICMF within the regulatory committed time limit (ESG-2) STEP
OPERATOR TRAINING PROGRAM                      NAME: - - - - - -
* NO. Att 2 A.4 *
JOB PERFORMANCE MEASURE                        DATE: - - - - - -
* Att 2 A.5 STEP (*Denotes a Critical Step) STANDARD After Classification Independent Declares an ALERT under RB3.L within Verification is obtained:
SYSTEM:     Emergency Plan TASK:       Classify an event and complete an ICMF within the regulatory committed time limit (ESG-2)
15 minutes of Start Time:
COMMENTS STEP STEP                                                                                                     (Required
* DECLARE the ALERT (enter time and date on ICMF) *COMPLETE I APPROVE the ICMF Completes and Approves the ICMF as follows: EAL#(s): RB3.L Description of Event: Loss of the Reactor Coolant System Boundary Note: Description of Event is found in EAL Description Table Fills out Section Ill: Checks IS for a Radiological Release in progress.
(*Denotes a Critical Step)                                                   EVAL
Fills out Section IV: Retrieves wind speed (10)and direction (160) data from SPDS Initials for aggroval to transmit lftime allows OBTAIN accuracy peer check of the completed ICMF Cue: No peer check will be performed.
* NO.                                                                  STANDARD                           for UNSAT S/U evaluation)
PSEG Restricted  
Att 2 After Classification Independent         Declares an ALERT under RB3.L within A.4 Verification is obtained:               15 minutes of Start Time:
-Possession Requires Specific Permission from Nuclear Training Page 5 of 8 NAME: ------DATE: ------COMMENTS EVAL (Required for UNSAT S/U evaluation)
*
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM: Emergency Plan TASK: Classify an event and complete an ICMF within the regulatory committed time limit (ESG-2) STEP
* DECLARE the ALERT (enter time and date on ICMF)
* NO. Att 2 A.6
Completes and Approves the ICMF as
* STEP (*Denotes a Critical Step) STANDARD Continue with NOTIFICATION AND ACTIVATION as follows:
*              *COMPLETE I APPROVE the ICMF follows:
* If not previously performed, ACTIVATE Cue: Activation of ERO Emergency I DIRECT ACTIVATION of ERO Emergency Callout (EP 96-003) Callout is not required for this JPM.
EAL#(s): RB3.L Description of Event: Loss of the Reactor Coolant System Boundary Note: Description of Event is found in EAL Description Table Fills out Section Ill:
* DIRECT the Primary Communicator to Provides ICMF to Primary Communicator implement ECG Attachment 6 within 15 minutes of event declaration Terminate JPM when ICMF is given to the Evaluator.
Checks IS for a Radiological Release in progress.
PSEG Restricted  
Fills out Section IV:
-Possession Requires Specific Permission from Nuclear Training Page 6 of 8 NAME: ------DATE: ------COMMENTS EVAL (Required for UNSAT S/U evaluation)
Retrieves wind speed (10)and direction (160) data from SPDS Initials for aggroval to transmit Att 2 A.5      lftime allows OBTAIN accuracy peer check of the completed ICMF             Cue: No peer check will be performed.
TQ-AA-106-0303 JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 5 of 8
Prior to JPM usage, revalidate JPM using steps 8 and 11 below. l-...
 
description and number, JPM description and number are identified.
OPERATOR TRAINING PROGRAM                    NAME: - - - - - -
and Abilities (KIA) references are included.
JOB PERFORMANCE MEASURE                      DATE: - - - - - -
0 U&deg;3:'Performance location specified. (in-plant, control room, or simulator)  
SYSTEM:     Emergency Plan TASK:       Classify an event and complete an ICMF within the regulatory committed time limit (ESG-2)
&-t& Initial setup conditions are identified.
COMMENTS STEP STEP                                                                                                      (Required
(*Denotes a Critical Step)                                                  EVAL
* NO.                                                                   STANDARD                          for UNSAT S/U evaluation)
Att 2 A.6       Continue with NOTIFICATION AND ACTIVATION as follows:
* If not previously performed, ACTIVATE I DIRECT ACTIVATION of ERO              Cue: Activation of ERO Emergency Callout is not required for this JPM.
Emergency Callout (EP 96-003)
*
* DIRECT the Primary Communicator to       Provides ICMF to Primary Communicator implement ECG Attachment 6             within 15 minutes of event declaration Terminate JPM when ICMF is given to the Evaluator.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 6 of 8
 
TQ-AA-106-0303 JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below.
l-... ~Task description and number, JPM description and number are identified.
  ~Q.*Knowledge and Abilities (KIA) references are included.
0     U&deg;3:'Performance location specified. (in-plant, control room, or simulator)
  &-t& Initial setup conditions are identified.
V\ Qs.-lnitiating and terminating Cues are properly identified.
V\ Qs.-lnitiating and terminating Cues are properly identified.
0, standards identified and verified by SME review.
0,     ~Task standards identified and verified by SME review.
Critical steps meet the criteria for critical steps and are identified with an asterisk (*). {/)s. Verify the procedure referenced by this JPM matches the m2st current revision of
  ~CM_ Critical steps meet the criteria for critical steps and are identified with an asterisk (*).
* that procedure:
  ~ {/)s. Verify the procedure referenced by this JPM matches the m2st current revision of
Procedure Date fl, it.[(.,,_
* that procedure: Procedure Rev.~ Date             fl, it.[(.,,_
test the JPM: a. verify Cues both verbal and visual are free of conflict, and b. ensure performance time is accurate.
  ~BPilot test the JPM:
{/\_ If the JPM cannot be performed as written with proper responses, then revise the JPM. Q 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructor:
: a. verify Cues both verbal and visual are free of conflict, and
SME/lnstructor:
: b. ensure performance time is accurate.
____________
{/\_   ~- If the JPM cannot be performed as written with proper responses, then revise the JPM.
_ Date: _____ _ PSEG Restricted  
  ~Q       11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.
-Possession Requires Specific Permission from Nuclear Training Page 7 of 8 INITIAL CONDITIONS:
SME/lnstructor:       ~
: 1. You have a maximum of 5 minutes to review the Emergency Operating Procedures used during this scenario to refresh your memory of all events/paths.
SME/lnstructor~/lt~
At the end of your review you will become the Shift Manager (SM). Inform the Evaluator when you are ready to assume SM duties. You may continue to reference the procedures or to look at the control board but "the clock will be running." If there are multiple ECG calls, classify the most severe. INITIATING CUE: You are the Duty SM. Classify the event, complete the correct ECG Attachment and provide an ICMF to the Primary Communicator.
SME/lnstructor: _ _ _ _ _ _ _ _ _ _ _ __                        Date: _ _ _ _ __
This is a Time Critical JPM. PSEG Restricted  
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 7 of 8
-Possession Requires Specific Permission from Nuclear Training Page 8 of 8 STATION: SYSTEM: TASK: TASK NUMBER: JPM NUMBER: ALTERNATE PATH: OPERATOR TRArnING PROGRAM JOB MEASURE SALEM Rod Control Perform a Control Rod Operability Verification N0010070101 15-01 NRC Sim a K/A NUMBER: 001 A4.03 I x I IMPORTANCE FACTOR: 4.0 APPLICABILITY:
 
RO EoO ROCK] STAD SROCK] EVALUATION SETTING/METHOD:
INITIAL CONDITIONS:
Simulator  
: 1. You have a maximum of 5 minutes to review the Emergency Operating Procedures used during this scenario to refresh your memory of all events/paths. At the end of your review you will become the Shift Manager (SM). Inform the Evaluator when you are ready to assume SM duties.
You may continue to reference the procedures or to look at the control board but "the clock will be running." If there are multiple ECG calls, classify the most severe.
INITIATING CUE:
You are the Duty SM. Classify the event, complete the correct ECG Attachment and provide an ICMF to the Primary Communicator.
This is a Time Critical JPM.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 8 of 8
 
OPERATOR TRArnING PROGRAM JOB PERFORlVIAl~CE MEASURE STATION:              SALEM SYSTEM:                Rod Control TASK:                  Perform a Control Rod Operability Verification TASK NUMBER:          N0010070101 JPM NUMBER:            15-01 NRC Sim a ALTERNATE PATH:      I x I                                    K/A NUMBER:           001 A4.03
                                                                            ~~~~~~~~~~~
IMPORTANCE FACTOR:           4.0           3.7 APPLICABILITY:                                                                   RO           SRO EoO         ROCK]           STAD               SROCK]
EVALUATION SETTING/METHOD:               Simulator


==REFERENCES:==
==REFERENCES:==
S2.0P-ST.RCS-0001, Rev. 22 (checked 8-3-16)
TOOLS AND EQUIPMENT:          None VALIDATED JPM COMPLETION TIME:                        10 min TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS:                            N/A Developed By:                    G Gauding                            Date: 8-3-16 Instructor Validated By:                M Lutek I W Russell                      Date: 8-22-16 SME or Instructor Approved By:                                  tv'\ ~ Ffl'-\
Train in    partment Approved By:
Ope~ment ACTUAL JPM COMPLETION TIME:
ACTUAL TIME CRITICAL COMPLETION TIME:
PERFORMED BY:
GRADE:    D  SAT      D    UNSAT REASON, IF UNSATISFACTORY:
EVALUATOR'S SIGNATURE:                                                        DATE:


S2.0P-ST.RCS-0001, Rev. 22 (checked 8-3-16) TOOLS AND EQUIPMENT:
OPERATOR TRAINING PROGRAlVI JOB PERFORMAl~CE MEASURE JOB PERFORMANCE MEASURE SIMULATOR SETUP INSTRUCTIONS SYSTEM:            Rod Control TASK:              Perform a Control Rod Operability Verification TASK NUMBER:      N0010070101 SIMULATOR IC:      IC-251 in 15-01 NRC JPMs MALFUNCTIONS REQUIRED:          RT-1 will trip 21 SGFP MALF: BF0105A, 21 STM GEN FEED PUMP TRIP, Final Value: 3 OVERRIDES REQUIRED:          None SPECIAL INSTRUCTIONS:      None Note to Evaluator:  OP-AP-300-1001 required a peer check for all non-emergency manual rod motion.
None VALIDATED JPM COMPLETION TIME: 10 min TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: N/A Developed By: Validated By: Approved By: Approved By: G Gauding Instructor M Lutek I W Russell SME or Instructor tv'\ Ffl'-\ Train in partment ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY:
Do NOT correct operator if a mistake is made when performing a peer check. For all required peer checks simply state "Peer check SAT".
EVALUATOR'S SIGNATURE:
 
Date: 8-3-16 Date: 8-22-16 DATE: 3.7 SRO SYSTEM: TASK: TASK NUMBER: SIMULATOR IC: MALFUNCTIONS REQUIRED:
OPERATOR TRAINING PROGRANI JOB PERFORMANCE MEASURE NAME:   ~~~~~~~~~~~~~~~~
OVERRIDES REQUIRED:
DATE: ~~~~~~~~~~~~~~~
SPECIAL INSTRUCTIONS:
SYSTEM:               Rod Control TASK:                 Perform a Control Rod Operability Verification TASK NUMBER:         N0010070101 INITIAL CONDITIONS:
Note to Evaluator:
Unit 2 is operating at steady state, 100% power. Power has been at 100% for 30 days.
OPERATOR TRAINING PROGRAlVI JOB MEASURE JOB PERFORMANCE MEASURE SIMULATOR SETUP INSTRUCTIONS Rod Control Perform a Control Rod Operability Verification N0010070101 IC-251 in 15-01 NRC JPMs RT-1 will trip 21 SGFP MALF: BF0105A, 21 STM GEN FEED PUMP TRIP, Final Value: 3 None None OP-AP-300-1001 required a peer check for all non-emergency manual rod motion. Do NOT correct operator if a mistake is made when performing a peer check. For all required peer checks simply state "Peer check SAT".
INITIATING CUE:
OPERATOR TRAINING PROGRANI JOB PERFORMANCE MEASURE NAME:
* You are directed to perform S2.0P-ST.RCS-0001, Reactivity Control System Rod Control Assemblies.
DATE:
* A Maintenance Technician is stationed at the Rod Control System Power Cabinets .
SYSTEM: Rod Control TASK: Perform a Control Rod Operability Verification TASK NUMBER: N0010070101 INITIAL CONDITIONS:
* Communications   are established via plant page between the Control Room and Jeff Stevens, NEO, at the Rod Control System Power Cabinets.
Unit 2 is operating at steady state, 100% power. Power has been at 100% for 30 days. INITIATING CUE:
* You are directed to perform S2.0P-ST.RCS-0001, Reactivity Control System Rod Control Assemblies.  
*
* A Maintenance Technician is stationed at the Rod Control System Power Cabinets . Communications are established via plant page between the Control Room and Jeff Stevens, NEO, at the Rod Control System Power Cabinets.
* The CRS has directed that steps 5.1.2 through 5.1.9 are to be performed in order .
* The CRS has directed that steps 5.1.2 through 5.1.9 are to be performed in order .
* The CRS directs that 15 steps of rod insertion are to be performed for each bank to ensure that each rod moves at least 10 steps.
* The CRS directs that 15 steps of rod insertion are to be performed for each bank to ensure that each rod moves at least 10 steps.
* Initial Control Rod Positions are: SDA F-04 229 D-10 228 K-12 227 M-06 227 B-04 230 D-14 224 P-12 229 M-02 230 SOB SOC G-03 229 E-03 229 C-09 227 C-11 223 J-13 227 L-13 224 N-07 229 N-05 224 J-02 223 C-06 223 G-13 227 N-09 230 Successful Completion Criteria:
* Initial Control Rod Positions are:
SDA                 SOB                SOC              SOD F-04 229             G-03 229           E-03 229           C-05 229 D-10 228            C-09 227           C-11 223           E-13 223 K-12 227            J-13 227           L-13 224           N-11 224 M-06 227            N-07 229           N-05 224           L-03 227 B-04 230            J-02 223 D-14 224            C-06 223 P-12 229            G-13 227 M-02 230            N-09 230 Successful Completion Criteria:
: 1. All critical steps completed.
: 1. All critical steps completed.
: 2. All sequential steps completed in order. SOD C-05 229 E-13 223 N-11 224 L-03 227 3. All time-critical steps completed within allotted time. 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made (and NRG concurrence is obtained).
: 2. All sequential steps completed in order.
: 3. All time-critical steps completed within allotted time.
: 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made (and NRG concurrence is obtained).
Task Standard for Successful Completion:
Task Standard for Successful Completion:
Operator trips the Rx when Shutdown Bank B is inserted in the core and a SGFP trips.
Operator trips the Rx when Shutdown Bank B is inserted in the core and a SGFP trips.
SYSTEM: Rod Control TASK: Perform a Control Rod Operability Verification STEP STEP (*Denotes a Critical Step)
 
* NO. Provide marked up copy of S2.0P-ST.RCS-0001, Rev. 22, with Prerequisite Sections 2.1-2.8 filled out. Provide copy of OP-AP-300-1001, PWR Control Rod Movement Requirements.
OPERATOR TRAINING PROGRAM NAME:
5.1.1 IF this surveillance is to be performed
JOB PERFORMANCE MEASURE DATE:
.... 5.1.2 PERFORM Attachment 2, Rod Control System Voltage Checks as follows: A. PLACE Rod Bank Selector Switch to -"MANUAL".
SYSTEM:     Rod Control TASK:       Perform a Control Rod Operability Verification STEP                                                                               COMMENTS STEP                     (*Denotes a Critical Step)                                                     EVAL      (Required for UNSAT
B. Direct Maintenance to COMPLETE -Attachment 2, Rod Control System Voltage Checks. OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STANDARD Reviews Prerequisites.
* NO.                                                                             STANDARD                S/U          Evaluation)
Reviews OP-AP-300-1001, PWR Control Rod Movement Requirements.
Provide marked up copy of S2.0P-ST.RCS-             Reviews Prerequisites.
0001, Rev. 22, with Prerequisite Sections 2.1-2.8 filled out.
Provide copy of OP-AP-300-1001, PWR Control         Reviews OP-AP-300-1001, PWR Control Rod Movement Requirements.                          Rod Movement Requirements.
Reviews and signs Precautions and Limitations.
Reviews and signs Precautions and Limitations.
Cue: lE ASKED, state that no special contingency actions have been briefed other than what is in the P&L's. Determines step is N/A based on steady state 100% operation.
Cue: lE ASKED, state that no special contingency actions have been briefed other than what is in the P&L's.
Performs Attachment 2 Rod Control System Voltage Checks by: A. Places Rod Bank Selector Switch to manual. B. Directs Direct Maintenance to complete Attachment 2, Rod Control System Voltage Checks. Cue: Maintenance reports Attachment 2 Rod Control System Voltage Checks are complete SAT. NAME: DATE: COMMENTS EVAL (Required for UNSAT S/U Evaluation)
5.1.1        IF this surveillance is to be performed ....        Determines step is N/A based on steady state 100% operation.
SYSTEM: Rod Control TASK: Perform a Control Rod Operability Verification STEP STEP (*Denotes a Critical Step)
5.1.2        PERFORM Attachment 2, Rod Control System            Performs Attachment 2 Rod Control Voltage Checks as follows:                          System Voltage Checks by:
* NO. Note _The Shutdown Rod Insertion Limit (TS 3.1.3.4) is not applicable during the performance of this test for rods actually undergoing testing. _Steps 5.1.3 through 5.1.10 may be performed in anv order. OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STANDARD Initials both notes. NAME: DATE:
A. PLACE Rod Bank Selector Switch to              A. Places Rod Bank Selector Switch
COMMENTS EVAL (Required for UNSAT SIU Evaluation)
                  -
SYSTEM: Rod Control TASK: Perform a Control Rod Operability Verification STEP STEP (*Denotes a Critical Step)
                            "MANUAL".                                            to manual.
* NO. 5.1.3 PERFORM Shutdown Bank A testing as follows: A. lE the Rx is critical, THEN ENSURE T avg is within +/-1&deg;F of Tret* B. PLACE Bank Selector Switch in the * "SBA" position.
                  -    B. Direct Maintenance to COMPLETE                  B. Directs Direct Maintenance to Attachment 2, Rod Control System                    complete Attachment 2, Rod Voltage Checks.                                      Control System Voltage Checks.
C. ENSURE GRP. SELECT "C" lights are illuminated on Rod Control System Power Cabinets 21AC and 22AC. D. Maneuver Shutdown Bank A at least 10
Cue: Maintenance reports Attachment 2 Rod Control System Voltage Checks are complete SAT.
* steps in any one direction.
 
E. ENSURE each rod in Shutdown Bank A indicated rod movement of at least 10 steps. F. RECORD Shutdown Bank A "Test Results" by initialing in Attachment
OPERATOR TRAINING PROGRAM NAME:
: 1. G. RESTORE Shutdown Bank A to pre-test
JOB PERFORMANCE MEASURE DATE: ~~~~~~~~~~-
* condition.
SYSTEM:   Rod Control TASK:     Perform a Control Rod Operability Verification STEP                                                                 COMMENTS STEP                 (*Denotes a Critical Step)                                       EVAL        (Required for UNSAT
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STANDARD Checks Tave/Tref recorder on 2RP4 and notes Tavg is within 1&deg;F of Tref .. Rotates Bank Selector Switch fully counter clockwise to the SBA position.
* NO.                                                                         STANDARD  SIU            Evaluation)
Contacts NEO and directs him to verify GRP. SELECT "C" lights are illuminated on Rod Control System Power Cabinets 21 AC and 22AC. Cue: GRP SELECT "C" lights are illuminated at Rod Control System Power Cabinets 21 AC and 22AC. IAW OP-AA-300-1001, prior to rod movement, operator states initial Shutdown Bank A position, target control rod position, and direction of rod movement, then inserts SBA at least 10 steps to stated target position.
Note       _The Shutdown Rod Insertion Limit (TS             Initials both notes.
Verifies rod movement by viewing rod position on P-250 computer.
3.1.3.4) is not applicable during the performance of this test for rods actually undergoing testing.
Initials SAT for Groups 1 and 2 for SBA on Att 1. Operator states initial Shutdown Bank A position, target control rod position, and direction of rod movement, then withdraws SBA to stated target ARO position.
_Steps 5.1.3 through 5.1.10 may be performed in anv order.
 
OPERATOR TRAINING PROGRAM NAME:  ~~~~~~~~~~
JOB PERFORMANCE MEASURE DATE: ~~~~~~~~~~-
SYSTEM:     Rod Control TASK:       Perform a Control Rod Operability Verification STEP                                                                                   COMMENTS STEP                   (*Denotes a Critical Step)                                                       EVAL        (Required for UNSAT
* NO.                                                                           STANDARD                  S/U            Evaluation) 5.1.3       PERFORM Shutdown Bank A testing as follows:
A. lE the Rx is critical, THEN ENSURE T avg   Checks Tave/Tref recorder on 2RP4 and is within +/-1&deg;F of Tret*                 notes Tavg is within 1&deg;F of Tref ..
B. PLACE Bank Selector Switch in the           Rotates Bank Selector Switch fully counter
*                       "SBA" position.                            clockwise to the SBA position.
C. ENSURE GRP. SELECT "C" lights are           Contacts NEO and directs him to verify illuminated on Rod Control System          GRP. SELECT "C" lights are illuminated Power Cabinets 21AC and 22AC.              on Rod Control System Power Cabinets 21 AC and 22AC.
Cue: GRP SELECT "C" lights are illuminated at Rod Control System Power Cabinets 21 AC and 22AC.
D. Maneuver Shutdown Bank A at least 10        IAW OP-AA-300-1001, prior to rod
* steps in any one direction.                movement, operator states initial Shutdown Bank A position, target control rod position, and direction of rod movement, then inserts SBA at least 10 steps to stated target position.
E. ENSURE each rod in Shutdown Bank A        Verifies rod movement by viewing rod indicated rod movement of at least 10      position on P-250 computer.
steps.
F. RECORD Shutdown Bank A "Test              Initials SAT for Groups 1 and 2 for SBA on Results" by initialing in Attachment 1. Att 1.
G. RESTORE Shutdown Bank A to pre-test        Operator states initial Shutdown Bank A
* condition.                                position, target control rod position, and direction of rod movement, then withdraws SBA to stated target ARO position.
Continuous rod withdrawal is acceptable.
Continuous rod withdrawal is acceptable.
NAME:
 
DATE:
OPERATOR TRAINING PROGRAM NAME: ~~~~~~~~~~-
COMMENTS EVAL (Required for UNSAT S/U Evaluation)
JOB PERFORMANCE MEASURE DATE: ~~~~~~~~~~
SYSTEM: Rod Control TASK: Perform a Control Rod Operability Verification STEP STEP (*Denotes a Critical Step)
SYSTEM:     Rod Control TASK:       Perform a Control Rod Operability Verification STEP                                                                                 COMMENTS STEP                   (*Denotes a Critical Step)                                                       EVAL        (Required for UNSAT
* NO. 5.1.4 PERFORM Shutdown Bank B testing as follows: A. lE the Rx is critical, THEN ENSURE Tavg is within +/-1&deg;F of Tref* B. PLACE Bank Selector Switch in the * "SBB" position.
* NO.                                                                           STANDARD                  S/U            Evaluation) 5.1.4       PERFORM Shutdown Bank B testing as follows:
C. ENSURE GRP. SELECT "C" lights are illuminated on Rod Control System Power Cabinets 21 BD and 22BD. D. MANUEVER Shutdown Bank B at least
A. lE the Rx is critical, THEN ENSURE Tavg   Checks Tave/Tref recorder on 2RP4 and is within +/-1&deg;F of Tref*                 notes Tavg is within 1&deg;F of Tref.
* 10 steps in any one direction.
B. PLACE Bank Selector Switch in the         Rotates Bank Selector Switch clockwise to
E. ENSURE each rod in Shutdown Bank B indicated rod movement of at least 1 O steps.
*                         "SBB" position.                          the SBB position.
* OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STANDARD Checks Tave/Tref recorder on 2RP4 and notes Tavg is within 1&deg;F of Tref. Rotates Bank Selector Switch clockwise to the SBB position.
C. ENSURE GRP. SELECT "C" lights are         Contacts NEO and directs him to verify illuminated on Rod Control System        GRP. SELECT "C" lights are illuminated Power Cabinets 21 BD and 22BD.            on Rod Control System Power Cabinets 21 BD and 22BD.
Contacts NEO and directs him to verify GRP. SELECT "C" lights are illuminated on Rod Control System Power Cabinets 21 BD and 22BD. Cue: GRP SELECT "C" lights are illuminated at Rod Control System Power Cabinets 21 BD and 22BD. Operator states initial Shutdown Bank B position, target control rod position, and direction of rod movement, then inserts SBB at least 10 steps to stated target position.
Cue: GRP SELECT "C" lights are illuminated at Rod Control System Power Cabinets 21 BD and 22BD.
SIMULATOR OPERATOR:
D. MANUEVER Shutdown Bank B at least        Operator states initial Shutdown Bank B
INSERT RT-1 when the operator is checking rod position after insertion.
* 10 steps in any one direction.            position, target control rod position, and direction of rod movement, then inserts SBB at least 10 steps to stated target position.
This will trip 21 SGFP. Responds to 21 SGFP trip by tripping the Rx IAW P&L 3.13. (This is Alternate Path) Movement of the Rod Bank Selector Switch to MAN or AUTO under these conditions is incorrect.
E. ENSURE each rod in Shutdown Bank B        SIMULATOR OPERATOR: INSERT RT-1 indicated rod movement of at least 1O    when the operator is checking rod position steps.                                    after insertion. This will trip 21 SGFP.
Responds to 21 SGFP trip by tripping the
* Rx IAW P&L 3.13. (This is Alternate Path)
Movement of the Rod Bank Selector Switch to MAN or AUTO under these conditions is incorrect.
When the operator has either tripped the Rx or initiated rod insertion in MAN or AUTO, state JPM is complete.
When the operator has either tripped the Rx or initiated rod insertion in MAN or AUTO, state JPM is complete.
NAME:
 
DATE:
OPERATOR TRAINING PROGRAM JOB PERFORlVIAl~CE MEASURE TQ-AA-106-0303 Revision 4 JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below.
COMMENTS EVAL (Required for UNSAT S/U Evaluation)
V /   'd-lJ'll1. Task description and number, JPM description and number are identified.
OPERA TOR TRAINING PROGRAM JOB MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation.
(,A I   rlfll 2. Knowledge and Abilities (KIA) references are included.
Prior to JPM usage, revalidate JPM using steps 8 and 11 below. V / 'd-lJ'll1.
V ./   ~ ltQl3. Performance location specified. (in-plant, control room, or simulator)
Task description and number, JPM description and number are identified.
V I     '?r-lft. Initial setup conditions are identified.
(,A I rlfll 2. Knowledge and Abilities (KIA) references are included.
V I       (;- L&#xa3;1. Initiating and terminating Cues are properly identified.
V ./ ltQl3. Performance location specified. (in-plant, control room, or simulator)
(/"' I   (r- ~.Task standards identified and verified by SME review.
V I '?r-lft. Initial setup conditions are identified.
v       I &sect;-~. Critical steps meet the criteria for critical steps and are identified with an asterisk (*).
V I (;-L&#xa3;1. Initiating and terminating Cues are properly identified.
(,   I   ~ ~. Verify the procedure referenced by th is J PM matches thepost current revision of iJ1   that procedure: Procedure Rev.           _21_ Date ~/ 1 :e, ti   ~
(/"' I (r-standards identified and verified by SME review. v I Critical steps meet the criteria for critical steps and are identified with an asterisk (*). (, I Verify the procedure referenced by th is J PM matches the post current revision of iJ1 that procedure:
          ~      9. Pilot test the JPM:
Procedure Rev. _21_ Date / 1 :e, ti 9. Pilot test the JPM: 1 /{/\ a. verify Cues both verbal and visual are free of conflict, and TQ-AA-106-0303 Revision 4 wu \ b. ensure performance time is accurate.
                /{/\     a. verify Cues both verbal and visual are free of conflict, and 1
0 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructor:
wu \       b. ensure performance time is accurate.
__ f_V\_L_v_t_-t..-_L
0       10. If the JPM cannot be performed as written with proper responses, then revise the JPM.
____ _ SM E/I  
____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.
....
SME/lnstructor: _ _    f_V\_L_v_t_-t..-_L_____                    Date:        ~f ,_,_)If::,
__ SME/lnstructor:
SM E/I nstructor:~f/i~* -'~IL4(~-"--+--~&#xa3;~.=f.=~*=e1/"'-'-
____________
                                                  . __                   Date: _ _ f" /~-z:i--+L_,__d~o*_
_ Date: ,_,_)If::, Date: __ f"
r       '
_ r ' Date: ------
SME/lnstructor: _ _ _ _ _ _ _ _ _ _ _ __                          Date: - - - - - -
INITIAL CONDITIONS:
 
OPERATOR TRAINING PROGRA1"VI JOB PERFORMANCE MEASURE Unit 2 is operating at steady state, 100% power. Power has been at 100% for 30 days. INITIATING CUE:
OPERATOR TRAINING PROGRA1"VI JOB PERFORMANCE MEASURE INITIAL CONDITIONS:
* You are directed to perform S2.0P-ST.RCS-0001, Reactivity Control System Rod Control Assemblies.  
Unit 2 is operating at steady state, 100% power. Power has been at 100% for 30 days.
*
INITIATING CUE:
* A Maintenance Technician is stationed at the Rod Control System Power Cabinets . Communications are established via plant page between the Control Room and Jeff Stevens, NEO, at the Rod Control System Power Cabinets.
* You are directed to perform S2.0P-ST.RCS-0001, Reactivity Control System Rod Control Assemblies.
* A Maintenance Technician is stationed at the Rod Control System Power Cabinets .
* Communications are established via plant page between the Control Room and Jeff Stevens, NEO, at the Rod Control System Power Cabinets.
* The CRS has directed that steps 5.1.2 through 5.1.9 are to be performed in order .
* The CRS has directed that steps 5.1.2 through 5.1.9 are to be performed in order .
* The CRS directs that 15 steps of rod insertion are to be performed for each bank to ensure that each rod moves at least 10 steps.
* The CRS directs that 15 steps of rod insertion are to be performed for each bank to ensure that each rod moves at least 10 steps.
* Initial Control Rod Positions are: SDA F-04 229 D-10 228 K-12 227 M-06 227 8-04 230 D-14 224 P-12 229 M-02 230 SOB SOC G-03 229 E-03 229 C-09 227 C-11 223 J-13 227 L-13 224 N-07 229 N-05 224 J-02 223 C-06 223 G-13 227 N-09 230 SOD C-05 229 E-13 223 N-11 224 L-03 227 STATION: SYSTEM: TASK: TASK NUMBER: SALEM OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE: Emergency Operating Procedures Perform Actions for Containment Sump blockage N 1150900501 JPM NUMBER: 15-01 NRC Sim b KIA NUMBER: 2.4.4 ALTERNATE PATH: I x I ------------!
* Initial Control Rod Positions are:
IMPORTANCE FACTOR: 4.5 4.7 APPLICABILITY:
SDA                   SOB                SOC            SOD F-04   229           G-03 229           E-03 229         C-05 229 D-10    228            C-09 227           C-11 223         E-13 223 K-12    227            J-13 227           L-13 224         N-11 224 M-06    227            N-07 229           N-05 224         L-03 227 8-04  230            J-02 223 D-14    224            C-06 223 P-12    229            G-13 227 M-02    230            N-09 230
RO SRO EOr=J RO[KJ STAD SRO[KJ EVALUATION SETTING/METHOD:
 
Simulator I Perform  
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE:
STATION:                SALEM SYSTEM:                Emergency Operating Procedures TASK:                  Perform Actions for Containment Sump blockage TASK NUMBER:            N 1150900501 JPM NUMBER:             15-01 NRC Sim b ALTERNATE PATH:       I x   I                           KIA NUMBER:
                                                                        ------------!2.4.4 IMPORTANCE FACTOR:           4.5           4.7 APPLICABILITY:                                                               RO           SRO EOr=J         RO[KJ           STAD           SRO[KJ EVALUATION SETTING/METHOD:             Simulator I Perform 2-EOP-LOCA-1, REV. 30, 2-EOP-LOCA-3, Rev. 30, 2-EOP-APPX-7, Rev. 0, OP-


==REFERENCES:==
==REFERENCES:==
AA-101-111-1003, Rev. 6 (All rev checked 5/9/16)
TOOLS AND EQUIPMENT:          None VALIDATED JPM COMPLETION TIME:                  5 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS:                      NIA Developed By:                  G Gauding                          Date:  5-9-16 Instructor Validated By:                  D Cox I M Lutek                    Date:  8-22-16 SME or Instructor Approved By:
Tra~~~j{'t                            Date:  lo lo/"
Approved By:
Oper~ent                                Date: /o /1Dj;r.,
ACTUAL JPM COMPLETION TIME:
ACTUAL TIME CRITICAL COMPLETION TIME:
PERFORMED BY:
GRADE:    D  SAT      D    UNSAT REASON, IF UNSATISFACTORY:
EVALUATOR'S SIGNATURE:                                                  DATE:
PSEG Restricted-Possession Requires Specific Permission from Nuclear Training


2-EOP-LOCA-1, REV. 30, 2-EOP-LOCA-3, Rev. 30, 2-EOP-APPX-7, Rev. 0, AA-101-111-1003, Rev. 6 (All rev checked 5/9/16) TOOLS AND EQUIPMENT:
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE:
None VALIDATED JPM COMPLETION TIME: 5 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: Developed By: Validated By: Approved By: Approved By: G Gauding Instructor D Cox I M Lutek SME or Instructor ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY:
NAME: ~~~~~~~~~~~~~-
EVALUATOR'S SIGNATURE:
DATE:
NIA Date: 5-9-16 Date: 8-22-16 Date: lo lo/" Date: /o /1Dj;r., DATE: PSEG Restricted-Possession Requires Specific Permission from Nuclear Training SYSTEM: TASK: OPERA TOR TRAINING PROGRAM JOB PERFORMANCE MEASURE: NAME:
SYSTEM:                Emergency Operating Procedures TASK:                  Perform Actions for Containment Sump blockage TASK NUMBER:           N1150900501 SIMULATOR SETUP:               RT-1   MALFS: VL0120 21SJ44 fails to position (0-100%) Severity 1.0 VL0121 22SJ44 fails to position (0-100%) Severity 2.0 I/O's:         AA04 B LO 21SJ44 SIS SUMP VALVE OPEN: ON AAOS B LO 21SJ44 SIS SUMP VALVE OPEN: ON AAOS CLO 22SJ44 SIS SUMP VALVE CLOSED: OFF AA04 CLO 21SJ44 SIS SUMP VALVE CLOSED: OFF ET-1         KAA01TPN 21 RHR pump STOP PB, tied to delete VL0120 ET-3         KAA01TPN 21 RHR pump STOP PB, tied to delete VL0121
DATE: Emergency Operating Procedures Perform Actions for Containment Sump blockage TASK NUMBER: N1150900501 SIMULATOR SETUP: RT-1 MALFS: VL0120 21SJ44 fails to position (0-100%) Severity 1.0 VL0121 22SJ44 fails to position (0-100%) Severity 2.0 I/O's: AA04 B LO 21SJ44 SIS SUMP VALVE OPEN: ON AAOS B LO 21SJ44 SIS SUMP VALVE OPEN: ON AAOS CLO 22SJ44 SIS SUMP VALVE CLOSED: OFF AA04 CLO 21SJ44 SIS SUMP VALVE CLOSED: OFF ET-1 KAA01TPN 21 RHR pump STOP PB, tied to delete VL0120 ET-3 KAA01TPN 21 RHR pump STOP PB, tied to delete VL0121 ***Check SJ44 OPEN lights are lit.*** Mark up LOCA-3 up to step 21. INITIAL CONDITIONS:
                              ***Check SJ44 OPEN lights are lit.***
Mark up LOCA-3 up to step 21.
INITIAL CONDITIONS:
* A LBLOCA has occurred.
* A LBLOCA has occurred.
* The crew has responded by performing TRIP-1 and LOCA-1.
* The crew has responded by performing TRIP-1 and LOCA-1.
* The crew is performing LOCA-3 with all AC buses energized from off-site power, and is waiting at step 21 for RWST lo-lo level alarm.
* The crew is performing LOCA-3 with all AC buses energized from off-site power, and is waiting at step 21 for RWST lo-lo level alarm.
* All ECCS pumps are operating except 22 CS pump which was stopped at step 8. INITIATING CUE: You are the Reactor Operator.
* All ECCS pumps are operating except 22 CS pump which was stopped at step 8.
Continue performing LOCA-3. Successful Completion Criteria:
INITIATING CUE:
You are the Reactor Operator. Continue performing LOCA-3.
Successful Completion Criteria:
: 1. All critical steps completed.
: 1. All critical steps completed.
: 2. All sequential steps completed in order. 3. All time-critical steps completed within allotted time. 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made. Task Standard for Successful Completion:
: 2. All sequential steps completed in order.
: 1. Secure all ECCS pumps. 2. Reestablish recirculation flow with ONE RHR pump and ONE charging OR SI pump. PSEG Restricted-Possession Requires Specific Permission from Nuclear Training SYSTEM: Emergency Operating Procedures TASK: Perform Actions for Containment Sumo block STEP STEP
: 3. All time-critical steps completed within allotted time.
* NO. (*Denotes a Critical Step) OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STANDARD Simulator Operator:
: 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made.
Insert RT-1 to cause cavitation of both RHR pumps. Determines ECCS pumps are exhibiting signs of cavitation and recognizes entry into APPX-7 is warranted from Continuous Action Summary. Evaluator:
Task Standard for Successful Completion:
IF the intention to stop the cavitating RHR pumps is voiced, THEN FOR RO APPLICANT ONL Y 1 IMMEDIATELY CUE: The CRS directs you to implement Appendix-7. (This is to prevent activation of Event Trigger when 21 RHR pump is stopped. CUE IF REQUIRED:
: 1. Secure all ECCS pumps.
The CRS directs you to implement Appendix-?.
: 2. Reestablish recirculation flow with ONE RHR pump and ONE charging OR SI pump.
Note: Operator may go to EOP-LOCA-5, but first step of LOCA-5 will direct performance of APPX-7. Use above cue if required in LOCA-5. Evaluator:
PSEG Restricted-Possession Requires Specific Permission from Nuclear Training
Provide paper copy of 2-EOP-APPX-7. NAME: ----------
 
DATE: ----------
OPERATOR TRAINING PROGRAM                          NAME:
COMMENTS EVAL (Required for S/U UNSAT evaluation)
                                                                                                                  ----------
PSEG Restricted-Possession Requires Specific Permission from Nuclear Training SYSTEM: Emergency Operating Procedures OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE TASK: Perform Actions for Containment Sumo block -*--STEP STEP
JOB PERFORMANCE MEASURE                           DATE:
* NO. (*Denotes a Critical Step) STANDARD APPX-7 CAUTION
                                                                                                                  ----------
* Any pump receiving suction from Evaluator:
SYSTEM:    Emergency Operating Procedures TASK:     Perform Actions for Containment Sumo block STEP                                                                                COMMENTS STEP
Stopping RHR pumps here an RHR pump should be stopped WITHOUT first stopping any SI or Charging before stopping the RHR pump. pumps receiving suction from RHR pump
(*Denotes a Critical Step)                                                            EVAL    (Required for
* If any Charging Pump, SI Pump, discharge is failure criteria.
* NO.                                                                    STANDARD S/U  UNSAT evaluation)
or Containment Spray Pump loses suction or shows indication of cavitation, the pump should be stopped. 1 (CAS) MONITOR RHR Pump suction conditions:
Simulator Operator: Insert RT-1 to cause cavitation of both RHR pumps.
: a. CHECK NO indications of Determines BOTH RHR pumps exhibit signs cavitation.
Determines ECCS pumps are exhibiting signs of cavitation and recognizes entry into APPX-7 is warranted from Continuous Action Summary.
of cavitation, as well as ALL ECCS pumps
Evaluator: IF the intention to stop the cavitating RHR pumps is voiced, THEN FOR RO APPLICANT ONL Y1 IMMEDIATELY CUE:
* Pump Amps -stable and normal being supplied from RHR pumps. for discharge pressure and flow.
The CRS directs you to implement Appendix-7. (This is to prevent activation of Event Trigger when 21 RHR pump is stopped.
* Flow -stable and normal for discharge pressure.
CUE IF REQUIRED: The CRS directs you to implement Appendix-?.
* Discharge Pressure -stable and normal for flow
Note: Operator may go to EOP-LOCA-5, but first step of LOCA-5 will direct performance of APPX-7. Use above cue if required in LOCA-5.
* Oscillations  
Evaluator: Provide paper copy of 2-EOP-APPX-7.
-none indicated NAME: ----------
PSEG Restricted-Possession Requires Specific Permission from Nuclear Training
DATE: ----------
 
COMMENTS EVAL (Required for S/U UNSAT evaluation}
OPERATOR TRAINING PROGRAM                        NAME:
PSEG Restricted-Possession Requires Specific Permission from Nuclear Training SYSTEM: Emergency Operating Procedures Perform Actions for Containment S TASK ----------------block ----STEP STEP
                                                                                                                    ----------
* NO. (*Denotes a Critical Step) 1.a a. PERFORM the following:
JOB PERFORMANCE MEASURE                        DATE:
RNO 1. ENSURE 21 RH29 AND 22RH29 in AUTO.
                                                                                                                    ----------
* 2. STOP ANY Charging Pump or SI Pump taking suction from affected RHR Pump(s)
SYSTEM:    Emergency Operating Procedures TASK:       Perform Actions for Containment Sumo block -*- -
: 3. IF indications of cavitation continue, THEN CLOSE 21 CS36 AND 22CS36, RHR TO CS VALVE. 4. lE indications of cavitation continue AND radiological conditions permit, THEN PERFORM the following:
STEP                                                                               COMMENTS STEP
: a. SEND an operator to release tags and restore CA to RH18(s). b. CLOSE affected RH18(s).
(*Denotes a Critical Step)                                                             EVAL    (Required for
* 5. lE indications of cavitation continue, THEN REMOVE LOCKOUT(s)
* NO.                                                                      STANDARD S/U  UNSAT evaluation}
AND CLOSE affected SJ49(s), RHR TO COLD LEG.
APPX-7                       CAUTION
* 6. lE indications of cavitation continue, THEN STOP affected RHR Pump(s). OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STANDARD Places 21 RH29 and 22RH29 in AUTO. Stops 21 and 22 Charging pumps and 21 and 22 SI pumps. Determines pump cavitation is continuing, verifies 21 CS36 and 22CS36 are shut. CUE: Radiation Protection has determined both RHR pump rooms to be unavailable for access due to high radiation levels. Determines RHR pump cavitation is continuing, and removes lockout from 21 SJ49 and 22SJ49 RHR TO COLD LEG and shuts 21 SJ49 and 22SJ49. Determines indications of cavitation continue, and stops 21 and 22 RHR pump. Simulator Operator:
* Any pump receiving suction from         Evaluator: Stopping RHR pumps here an RHR pump should be stopped       WITHOUT first stopping any SI or Charging before stopping the RHR pump.       pumps receiving suction from RHR pump
Ensure ET-1 and ET-3 are TRUE when 21 and 22 RHR pump STOP PBs are depressed.
* If any Charging Pump, SI Pump,         discharge is failure criteria.
This removes the SJ44 failures.
or Containment Spray Pump loses suction or shows indication of cavitation, the pump should be stopped.
NAME:
1       (CAS) MONITOR RHR Pump suction conditions:
DATE:
: a. CHECK NO indications of               Determines BOTH RHR pumps exhibit signs cavitation.                         of cavitation, as well as ALL ECCS pumps
COMMENTS EVAL (Required for S/U UNSAT evaluation)
* Pump Amps - stable and normal           being supplied from RHR pumps.
PSEG Restricted-Possession Requires Specific Permission from Nuclear Training SYSTEM: Emergency Operating Procedures TASK: Perform Actions for Containment Sumo block STEP STEP
for discharge pressure and flow.
* NO. (*Denotes a Critical Step) 2 CHECK ALL AVAILABLE CFCUs running in Low Speed. 3. SECURE Containment Spray flow path:
* Flow - stable and normal for discharge pressure.
* a. STOP ALL Containment Spray Pumps. b. CHECK 21CS36 AND 22CS36 CLOSED. 4. (CAS) CHECK RWST level >1.2 feet. 5. ATTEMPT to establish RHR Pump suction: a. CHECK 21 SJ44 AND 22SJ44 OPEN. b. CHECK AT LEAST ONE RHR Pump running, with suction aligned to Containment Sump. 5.b b. PERFORM the following:
* Discharge Pressure - stable and normal for flow
RNO 5.b 1. REMOVE LOCKOUT(s)
* Oscillations - none indicated PSEG Restricted-Possession Requires Specific Permission from Nuclear Training
AND RNO CLOSE affected SJ49(s) RHR DISCH TO COLD LEG. 5.b 2. ENSURE 21 RH29 AND 22RH29 RNO in AUTO
 
* 5.b 3. START ONE RHR Pump. RNO OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STANDARD Determines all CFCUs are running in Low Speed. Stops 21 CS pump. Determines 21 CS36 and 22CS36 are shut. Determines RWST level is >1.2 feet. Determines 21 SJ44 AND 22SJ44 are open. Determines NEITHER RHR Pumps is running with suction aligned to Containment Sump. Determines 21 SJ49 and 22SJ49 previously shut. Determines 21 RH29 and 22RH29 are in AUTO. Starts 21 OR 22 RHR pump. NAME: ---------DATE: COMMENTS EVAL (Required for S/U UNSAT evaluation)
OPERATOR TRAINING PROGRAM                        NAME:  ~~~~~~~~~-
PSEG Restricted-Possession Requires Specific Permission from Nuclear Training SYSTEM: Emergency Operating Procedures Perform Actions for Containment S TASK block --STEP STEP
JOB PERFORMANCE MEASURE                          DATE: ~~~~~~~~~-
* NO. (*Denotes a Critical Step) 5.b 4. !E indications of cavitation occur, RNO THEN STOP the running RHR pump, AND START the other RHR pump. 5.b 5. !E NO RHR Pumps can be run RNO without cavitation, THEN STOP any running RHR Pumps AND GO TO Step 8. 5. c) CHECK 21 RH29 AND 22RH29 in AUTO. d) REMOVE LOCKOUT(s)
SYSTEM:    Emergency Operating Procedures TASK      Perform Actions
AND CLOSE affected SJ49(s) RHR DISCH TO COLD LEG. e) CHECK ONLY ONE RHR Pump running with suction from Containment Sump. 6. ATTEMPT to establish Charging Pump or SI Pump flow in recirculation mode: a. CHECK Charging Pump and SI Pump suction aligned to running RHR pump. b. CHECK ONLY ONE Charging Pump OR SI Pump running. OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STANDARD Determines cavitation is NOT occurring.
                      --    for Containment
Determines RHR pump can be run without cavitation.
                                  --- --- --- S -- - - - block
Determines 21 RH29 and 22RH29 are in AUTO. Determines BOTH SJ49's are shut. Determines only one RHR pumps is running. Checks Charging Pump and SI Pump suction aligned to running RHR pump by: a.1. Checks 2SJ67 and 2SJ68 SHUT a.2 Checks 22SJ45 OPEN a.3 Checks 21 SJ45 OPEN a.4 Checks 21 SJ113 and 22SJ113 OPEN a.5 Checks 2SJ1 and 2SJ2 OPEN a.6 Checks 2SJ30 SHUT Determine NO Charging or SI pumps are running. NAME:
                                                              -- --
DATE:
STEP                                                                                        COMMENTS STEP
COMMENTS EVAL (Required for SIU UNSAT evaluation)
(*Denotes a Critical Step)                                                                      EVAL   (Required for
PSEG Restricted-Possession Requires Specific Permission from Nuclear Training SYSTEM: Emergency Operating Procedures TASK: Perform Actions for Containment Sumo block STEP STEP
* NO.                                                                                STANDARD S/U UNSAT evaluation) 1.a      a. PERFORM the following:
* NO. (*Denotes a Critical Step)
RNO            1. ENSURE 21 RH29 AND 22RH29                      Places 21 RH29 and 22RH29 in AUTO.
* 6.b START OR STOP, Charging and SI RNO Pumps, as required, to obtain ONLY ONE pump running in recirculation alignment.
in AUTO.
6 c. CHECK Charging Pump or SI Pump running in recirculation alignment.
* 2. STOP ANY Charging Pump or SI                  Stops 21 and 22 Charging pumps and 21 and Pump taking suction from                    22 SI pumps.
: d. GO TO Step 9 OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE --STANDARD Starts ONLY ONE Charging or SI pump. Note: Per the NOTE at top of page 3, the intent of Step 6 is to start only a single pump (Charging or SI), and it is preferable to start a Charging pump. SAT performance of Step 6 does not require starting a Charging pump, just one of the 4 available charqinq or SI pumps. Determines Charging or SI pump is running in recirculation alignment.
affected RHR Pump(s)
Terminate JPM when operator goes to Step 9. NAME:
: 3. IF indications of cavitation                   Determines pump cavitation is continuing, continue, THEN CLOSE 21 CS36                 verifies 21 CS36 and 22CS36 are shut.
DATE:
AND 22CS36, RHR TO CS VALVE.
COMMENTS EVAL (Required for S/U UNSAT evaluation)
: 4. lE indications of cavitation continue AND radiological conditions permit, THEN PERFORM the following:                       CUE: Radiation Protection has determined
PSEG Restricted-Possession Requires Specific Permission from Nuclear Training JOB PERFORMANCE MEASURE TQ-AA-106-0303 JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation.
: a. SEND an operator to release               both RHR pump rooms to be unavailable for tags and restore CA to                   access due to high radiation levels.
Prior to JPM usage, revalidate JPM using steps 8 and 11 below. 1 J I / 1. Task description and number, JPM description and number are identified. V ! 1 r /2. Knowledge and Abilities (KIA) references are included.
RH18(s).
CA 0 J 3. Performance location specified. (in-plant, control room, or simulator) lll 4. Initial setup conditions are identified.
: b. CLOSE affected RH18(s).
1.rv Initiating and terminating Cues are properly identified.  
* 5. lE indications of cavitation                   Determines RHR pump cavitation is continue, THEN REMOVE                       continuing, and removes lockout from 21 SJ49 LOCKOUT(s) AND CLOSE                         and 22SJ49 RHR TO COLD LEG and shuts affected SJ49(s), RHR TO COLD                 21 SJ49 and 22SJ49.
\. 7}, '\.. Task standards identified and verified by SME review. \J &#xb5; 7. Critical steps meet the criteria for critical steps and are identified with an asterisk (*). Verify the procedure referenced by this JPM mat&#xa3;hes the n;iost current revision of that procedure:
LEG.
Procedure Rev. _i2__ Date 8
* 6. lE indications of cavitation                   Determines indications of cavitation continue, continue, THEN STOP affected                 and stops 21 and 22 RHR pump.
* 2'2--I t.,. 9. Pilot test the JPM: ----a. verify Cues both verbal and visual are free of conflict, and b. ensure performance time is accurate.
RHR Pump(s).                                 Simulator Operator: Ensure ET-1 and ET-3 are TRUE when 21 and 22 RHR pump STOP PBs are depressed. This removes the SJ44 failures.
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructore}:>
PSEG Restricted-Possession Requires Specific Permission from Nuclear Training
C, .* tff' ( / SME/lnstructor:
 
N\1 v:n[.U--..,.. SME/lnstructor:
OPERATOR TRAINING PROGRAM                          NAME:
-------------
                                                                                                                  ---------
Date: Date: Date: 8-22-lb 6-/ 7, ,_,I 110 ------PSEG Restricted-Possession Requires Specific Permission from Nuclear Training JOB PERFORMANCE MEASURE INITIAL CONDITIONS:
JOB PERFORMANCE MEASURE                          DATE:
SYSTEM:   Emergency Operating Procedures TASK:     Perform Actions for Containment Sumo block STEP                                                                               COMMENTS STEP
(*Denotes a Critical Step)                                                           EVAL    (Required for
* NO.                                                                  STANDARD S/U  UNSAT evaluation) 2        CHECK ALL AVAILABLE CFCUs                 Determines all CFCUs are running in Low running in Low Speed.                     Speed.
: 3.       SECURE Containment Spray flow path:
* a. STOP ALL Containment Spray           Stops 21 CS pump.
Pumps.
: b. CHECK 21CS36 AND 22CS36             Determines 21 CS36 and 22CS36 are shut.
CLOSED.
: 4.       (CAS) CHECK RWST level >1.2 feet.         Determines RWST level is >1.2 feet.
: 5.       ATTEMPT to establish RHR Pump suction:
: a. CHECK 21 SJ44 AND 22SJ44             Determines 21 SJ44 AND 22SJ44 are open.
OPEN.
: b. CHECK AT LEAST ONE RHR               Determines NEITHER RHR Pumps is running Pump running, with suction       with suction aligned to Containment Sump.
aligned to Containment Sump.
5.b         b. PERFORM the following:
RNO 5.b           1. REMOVE LOCKOUT(s) AND               Determines 21 SJ49 and 22SJ49 previously RNO                CLOSE affected SJ49(s) RHR         shut.
DISCH TO COLD LEG.
5.b         2. ENSURE 21 RH29 AND 22RH29         Determines 21 RH29 and 22RH29 are in RNO               in AUTO                           AUTO.
* 5.b         3. START ONE RHR Pump.                 Starts 21 OR 22 RHR pump.
RNO PSEG Restricted-Possession Requires Specific Permission from Nuclear Training
 
OPERATOR TRAINING PROGRAM                     NAME:  ~~~~~~~~~-
JOB PERFORMANCE MEASURE                       DATE:  ~~~~~~~~~-
SYSTEM:    Emergency Operating Procedures TASK      Perform Actions for Containment
                                    - -      S      block STEP                                                                                COMMENTS STEP
(*Denotes a Critical Step)                                                            EVAL    (Required for
* NO.                                                                       STANDARD SIU  UNSAT evaluation) 5.b          4. !E indications of cavitation occur,    Determines cavitation is NOT occurring.
RNO                THEN STOP the running RHR pump, AND START the other RHR pump.
5.b          5. !E NO RHR Pumps can        be run      Determines RHR pump can be run without RNO                without cavitation, THEN STOP          cavitation.
any running RHR Pumps AND GO TO Step 8.
: 5.          c) CHECK 21 RH29 AND 22RH29              Determines 21 RH29 and 22RH29 are in in AUTO.                             AUTO.
d) REMOVE LOCKOUT(s) AND                  Determines BOTH SJ49's are shut.
CLOSE affected SJ49(s) RHR DISCH TO COLD LEG.
e) CHECK ONLY ONE RHR Pump                Determines only one RHR pumps is running.
running with suction from Containment Sump.
: 6.       ATTEMPT to establish Charging Pump or SI Pump flow in recirculation mode:        Checks Charging Pump and SI Pump suction
: a. CHECK Charging Pump and SI            aligned to running RHR pump by:
Pump suction aligned to running      a.1. Checks 2SJ67 and 2SJ68 SHUT RHR pump.                             a.2 Checks 22SJ45 OPEN a.3 Checks 21 SJ45 OPEN a.4 Checks 21 SJ113 and 22SJ113 OPEN a.5 Checks 2SJ1 and 2SJ2 OPEN a.6 Checks 2SJ30 SHUT
: b. CHECK ONLY ONE Charging               Determine NO Charging or SI pumps are Pump OR SI Pump running.               running.
PSEG Restricted-Possession Requires Specific Permission from Nuclear Training
 
OPERATOR TRAINING PROGRAM                           NAME:  ~~~~~~~~~-
JOB PERFORMANCE MEASURE                             DATE:  ~~~~~~~~~-
SYSTEM:    Emergency Operating Procedures TASK:      Perform Actions for Containment Sumo block  --
STEP                                                                                  COMMENTS STEP
(*Denotes a Critical Step)                                                              EVAL    (Required for
* NO.                                                                     STANDARD S/U  UNSAT evaluation)
* 6.b      START OR STOP, Charging and SI           Starts ONLY ONE Charging or SI pump.
RNO        Pumps, as required, to obtain ONLY ONE pump running in recirculation        Note: Per the NOTE at top of page 3, the alignment.                               intent of Step 6 is to start only a single pump (Charging or SI), and it is preferable to start a Charging pump. SAT performance of Step 6 does not require starting a Charging pump, just one of the 4 available charqinq or SI pumps.
6            c. CHECK Charging Pump or SI        Determines Charging or SI pump is running in Pump running in recirculation      recirculation alignment.
alignment.
: d. GO TO Step 9 Terminate JPM when operator goes to Step 9.
PSEG Restricted-Possession Requires Specific Permission from Nuclear Training
 
JOB PERFORMANCE MEASURE TQ-AA-106-0303 JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below.
1 J    I ~/    1. Task description and number, JPM description and number are identified.
V      !~I r /2.
1        Knowledge and Abilities (KIA) references are included.
CA      /~  0 J 3. Performance location specified. (in-plant, control room, or simulator) lll  ~4. Initial setup conditions are identified.
1.rv    ~5. Initiating and terminating Cues are properly identified.
\. 7},
  '\.. ~6. Task standards identified and verified by SME review.
  \J    &#xb5;        7. Critical steps meet the criteria for critical steps and are identified with an asterisk (*).
        ~8. Verify the procedure referenced by this JPM mat&#xa3;hes the n;iost current revision of
          ~/       that procedure: Procedure Rev.      _i2__ Date        8
* 2'2-- I t.,.
        - - - - 9. Pilot test the JPM:
: a. verify Cues both verbal and visual are free of conflict, and
: b. ensure performance time is accurate.
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM.
____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.
SME/lnstructore}:>
SME/lnstructor:
C, .*
(   /
tff' N\1..,.. v:n[.U--
Date:
Date:
8-22-lb 6-/ 7, ,_,I 110 SME/lnstructor:                                                  Date:
                        -------------                                           ------
PSEG Restricted-Possession Requires Specific Permission from Nuclear Training
 
JOB PERFORMANCE MEASURE INITIAL CONDITIONS:
* A LBLOCA has occurred.
* A LBLOCA has occurred.
* The crew has responded by performing TRIP-1 and LOCA-1.
* The crew has responded by performing TRIP-1 and LOCA-1.
* The crew is performing LOCA-3 with all AC buses energized from off-site power, and is waiting at step 21 for RWST lo-lo level alarm.
* The crew is performing LOCA-3 with all AC buses energized from off-site power, and is waiting at step 21 for RWST lo-lo level alarm.
* All ECCS pumps are operating except 22 CS pump which was stopped at step 8. INITIATING CUE: You are the Reactor Operator.
* All ECCS pumps are operating except 22 CS pump which was stopped at step 8.
Continue performing LOCA-3. PSEG Restricted-Possession Requires Specific Permission from Nuclear Training STATION: SYSTEM: TASK: TASK NUMBER: JPM NUMBER: SALEM ECCS OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE Isolate the ECCS Accumulators IAW TRIP-6 1150070501 15-01 NRC Sim c ALTERNATE PATH: I x I KIA NUMBER: E09 EA1 .1 IMPORTANCE FACTOR: 3.5 3.5 APPLICABILITY:
INITIATING CUE:
EoD RO[]:] STAL] SROITJ EVALUATION SETTING/METHOD:
You are the Reactor Operator. Continue performing LOCA-3.
Simulator I Perform  
PSEG Restricted-Possession Requires Specific Permission from Nuclear Training
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION:               SALEM SYSTEM:                 ECCS TASK:                   Isolate the ECCS Accumulators IAW TRIP-6 TASK NUMBER:            1150070501 JPM NUMBER:            15-01 NRC Sim c ALTERNATE PATH:       I   x   I                               KIA NUMBER:   ~~~~~~~~~~~
E09 EA1 .1 IMPORTANCE FACTOR:             3.5             3.5 APPLICABILITY:                                                                   RO              SRO EoD           RO[]:]           STAL]           SROITJ EVALUATION SETTING/METHOD:                 Simulator I Perform


==REFERENCES:==
==REFERENCES:==
2-EOP-TRIP-6 Rev. 30 (Rev checked 8-3-16)
TOOLS AND EQUIPMENT:            None VALIDATED JPM COMPLETION TIME:                      8 Minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS:                            N/A Developed By:                  G Gauding                              Date:    8-3-16 Instructor Validated By:              W Russell / D Cox SME or Instructor    i                  Date:    8-22-16 Approved By:
Train~~('-;;                                Date:    10/;/v Approved By:
Op rations De    rtment Date:  /D;/1f r, ACTUAL JPM COMPLETION TIME:
ACTUAL TIME CRITICAL COMPLETION TIME:
PERFORMED BY:
GRADE:    D  SAT      D    UNSAT REASON, IF UNSATISFACTORY:
EVALUATOR'S SIGNATURE:                                                        DATE:
PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 1 of 6


2-EOP-TRIP-6 Rev. 30 (Rev checked 8-3-16) TOOLS AND EQUIPMENT:
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME:
None VALIDATED JPM COMPLETION TIME: 8 Minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: Developed By: Validated By: Approved By: Approved By: G Gauding Instructor W Russell / D Cox SME or Instructor i
DATE:
Op rations De rtment ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY:
SYSTEM:                 ECCS TASK:                   Isolate the ECCS Accumulators IAW TRIP-6 TASK NUMBER:           1150070501 SIMULATOR SETUP:
EVALUATOR'S SIGNATURE:
: 1. Trip RCP's
RO SRO N/A Date: 8-3-16 Date: 8-22-16 Date: 10/;/v Date: /D;/1f r, DATE: PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 1 of 6 OPERA TOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: DATE: SYSTEM: ECCS TASK: Isolate the ECCS Accumulators IAW TRIP-6 TASK NUMBER: 1150070501 SIMULATOR SETUP: 1. Trip RCP's 2. Perform EOP's to TRIP-6, Step 12 -SI ACCUM ISOLATION
: 2. Perform EOP's to TRIP-6, Step 12 - SI ACCUM ISOLATION
: 3. Override 24SJ54, Acc. Isolation Valve, close PB in the OFF position.
: 3. Override 24SJ54, Acc. Isolation Valve, close PB in the OFF position.
: 4. Place SPDS on Press/Temp Display 5. Put RCS Tcolds on trend on console. 6. Provide marked up copy of TRIP-6 INITIAL CONDITIONS:
: 4. Place SPDS on Press/Temp Display
: 5. Put RCS Tcolds on trend on console.
: 6. Provide marked up copy of TRIP-6 INITIAL CONDITIONS:
A reactor trip occurred when a 500KV grid perturbation occurred, which also caused all RCPs to trip. The operating crew has progressed through the EOP's and is now in 2-EOP-TRIP-6, NATURAL CIRCULATION RAPID COOLDOWN WITH RVLIS. The RCPs will NOT be restarted.
A reactor trip occurred when a 500KV grid perturbation occurred, which also caused all RCPs to trip. The operating crew has progressed through the EOP's and is now in 2-EOP-TRIP-6, NATURAL CIRCULATION RAPID COOLDOWN WITH RVLIS. The RCPs will NOT be restarted.
INITIATING CUE: Begin performing 2-EOP-TRIP-6, NATURAL CIRCULATION RAPID COOLDOWN WITH RVLIS at step 12. Successful Completion Criteria:
INITIATING CUE:
Begin performing 2-EOP-TRIP-6, NATURAL CIRCULATION RAPID COOLDOWN WITH RVLIS at step 12.
Successful Completion Criteria:
: 1. All critical steps completed.
: 1. All critical steps completed.
: 2. All sequential steps completed in order. 3. All time-critical steps completed within allotted time. 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made. Task Standard for Successful Completion:
: 2. All sequential steps completed in order.
: 1. Shut 21, 22, and 23 SJ54's. 2. Vent 24 Accumulator to atmospheric pressure.
: 3. All time-critical steps completed within allotted time.
PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 2 of 6 SYSTEM: TASK: STEP
: 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made.
* NO. 12 12.1
Task Standard for Successful Completion:
* 12.1 12.1 12.2 *
: 1. Shut 21, 22, and 23 SJ54's.
* ECCS OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE Isolate the ECCS Accumulators IAW TRIP-6 STEP (*Denotes a Critical Step) STANDARD Reviews conditions and the marked up EOP-TRIP-6 Natural Circ Cooldown With RVLIS IS RCS PRESSURE <1000 PSIG Verifies RCS pressure <1000 psig. REMOVE LOCKOUT FROM 21-24SJ54 At 2RP4 Panel, selects VALVE OPERABLE on (ACCUMULATOR OUTLET VALVES) 21-24SJ54 ACCUMULATOR OUTLET VALVES LOCKOUT switches.
: 2. Vent 24 Accumulator to atmospheric pressure.
CLOSE 21-24SJ54 Depresses CLOSE PB on 21-24SJ54, noting that 21, 22, and 23SJ54 begin to stroke closed. ARE 21-24SJ54 CLOSED Determines 24SJ54 is OPEN. Alternate path actions start here. VENT ANY AFFECTED ACCUMULATORS:
PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 2 of 6
* MAINTAIN RCS PRESSURE Verifies RCS Pressure >24 Accumulator GREATER THAN ACCUMULATOR Pressure NITROGEN PRESSURE
 
* OPEN 2NT35 (N2 HOR VALVE) Opens 2NT35 (N2 HOR VALVE)
OPERATOR TRAINING PROGRAM                         NAME:  ~~~~~~~~~-
* OPEN AFFECTED SJ93 (N2 Opens 24SJ93 (N2 SUPPLY VAL VE) and SUPPLY VALVE) observes 24 Accumulator pressure lowering PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 3 of 6 NAME:
JOB PERFORMANCE MEASURE                           DATE:
DATE: COMMENTS EVAL (Required for UNSAT S/U evaluation)
SYSTEM:    ECCS TASK:      Isolate the ECCS Accumulators IAW TRIP-6 STEP                                                                                   COMMENTS STEP
SYSTEM: TASK: STEP
(*Denotes a Critical Step)                                                         EVAL    (Required for UNSAT
* NO. 12.3 *
* NO.                                                                      STANDARD S/U        evaluation)
* ECCS OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE Isolate the ECCS Accumulators IAW TRIP-6 STEP (*Denotes a Critical Step) STANDARD WHEN ACCUMULATOR VENTING IS Cue: 24 Accumulator has been completely COMPLETE THEN CLOSE: vented and 24 Accumulator pressure is now
Reviews conditions and the marked up EOP-TRIP-6 Natural Circ Cooldown With RVLIS 12        IS RCS PRESSURE <1000 PSIG                 Verifies RCS pressure <1000 psig.
* 2NT35 reading ZERO. 21 THRU 24 SJ93 Closes 2NT35 N2 HOR VALVE
12.1      REMOVE LOCKOUT FROM 21-24SJ54               At 2RP4 Panel, selects VALVE OPERABLE on (ACCUMULATOR OUTLET VALVES)                 21-24SJ54 ACCUMULATOR OUTLET VALVES LOCKOUT switches.
* Closes 24SJ93 N2 SUPPLY VALVE Cue: JPM is complete PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 4 of 6 NAME:
* 12.1      CLOSE 21-24SJ54                             Depresses CLOSE PB on 21-24SJ54, noting that 21, 22, and 23SJ54 begin to stroke closed.
DATE: COMMENTS EVAL (Required for UNSAT S/U evaluation)
12.1      ARE 21-24SJ54 CLOSED                       Determines 24SJ54 is OPEN.
JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation.
Alternate path actions start here.
Prior to JPM usage, JPM using steps 8 and 11 below . . Task description and number, JPM description and number are identified.
VENT ANY AFFECTED ACCUMULATORS:
(; / 5. Initiating and terminating cues are properly identified. V / 6. Task standards identified and verified by SME review. (/ 7. Critical steps meet the criteria for critical steps and are identified with an asterisk n . Verify the procedure referenced by this JPM mate es the most current revision of that procedure:
12.2
Procedure Rev.
* MAINTAIN RCS PRESSURE               Verifies RCS Pressure >24 Accumulator GREATER THAN ACCUMULATOR           Pressure NITROGEN PRESSURE
8" t2 lo . Pilot test the JPM: a. verify cues both verbal and visual are free of conflict, and b. ensure performance time is accurate.
*
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructor:. (J/ SME/lnstructor: , { i>/' I SME/lnstructor:
* OPEN 2NT35 (N2 HOR VALVE)           Opens 2NT35 (N2 HOR VALVE)
____________
*
_ Date: _____ _ PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 5 of 6 INITIAL CONDITIONS:
* OPEN AFFECTED SJ93 (N2             Opens 24SJ93 (N2 SUPPLY VAL VE) and SUPPLY VALVE)                       observes 24 Accumulator pressure lowering PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 3 of 6
 
OPERATOR TRAINING PROGRAM                          NAME: ~~~~~~~~~-
JOB PERFORMANCE MEASURE                            DATE:
SYSTEM:     ECCS TASK:       Isolate the ECCS Accumulators IAW TRIP-6 STEP                                                                                   COMMENTS STEP
(*Denotes a Critical Step)                                                         EVAL    (Required for UNSAT
* NO.                                                                    STANDARD S/U        evaluation) 12.3      WHEN ACCUMULATOR VENTING IS                 Cue: 24 Accumulator has been completely COMPLETE THEN CLOSE:                       vented and 24 Accumulator pressure is now reading ZERO.
*
* 2NT35 Closes 2NT35 N2 HOR VALVE
*
* 21 THRU 24 SJ93 Closes 24SJ93 N2 SUPPLY VALVE Cue: JPM is complete PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 4 of 6
 
JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, rev~lidate JPM using steps 8 and 11 below .
                    . Task description and number, JPM description and number are identified.
(;   /           5. Initiating and terminating cues are properly identified.
V     / ~ 6. Task standards identified and verified by SME review.
(/   ~ 7. Critical steps meet the criteria for critical steps and are identified with an asterisk n
                    . Verify the procedure referenced by this JPM mate es the most current revision of that procedure: Procedure Rev. ~Date 8" t2 lo
                    . Pilot test the JPM:
: a. verify cues both verbal and visual are free of conflict, and
: b. ensure performance time is accurate.
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM.
____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.
SME/lnstructor:.   (J/ ~
SME/lnstructor:   ~,     { i>/'
I SME/lnstructor: _ _ _ _ _ _ _ _ _ _ _ __                        Date: _ _ _ _ __
PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 5 of 6
 
INITIAL CONDITIONS:
A reactor trip occurred when a 500KV grid perturbation occurred, which also caused all RCPs to trip. The operating crew has progressed through the EOP's and is now in 2-EOP-TRIP-6, NATURAL CIRCULATION RAPID COOLDOWN WITH RVLIS. The RCPs will NOT be restarted.
A reactor trip occurred when a 500KV grid perturbation occurred, which also caused all RCPs to trip. The operating crew has progressed through the EOP's and is now in 2-EOP-TRIP-6, NATURAL CIRCULATION RAPID COOLDOWN WITH RVLIS. The RCPs will NOT be restarted.
INITIATING CUE: Begin performing 2-EOP-TRIP-6, NATURAL CIRCULATION RAPID COOLDOWN WITH RVLIS at step 12. PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 6 of 6 STATION: SYSTEM: OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SALEM 1 & 2 Emergency Operating Procedures TASK: Respond to a Loss of Heat Sink (Initiate Bleed and Feed with SI pumps and Rx Head Vents) TASK NUMBER: N 1150290501 JPM NUMBER: 15-01 NRC Sim d ALTERNATE PATH: I x I KIA NUMBER: EPE E05 EA 1.1 IMPORTANCE FACTOR: 4.1 ----APPLICABILITY:
INITIATING CUE:
RO EOCJ RO[KJ STACJ SRO[KJ EVALUATION SETTING/METHOD:
Begin performing 2-EOP-TRIP-6, NATURAL CIRCULATION RAPID COOLDOWN WITH RVLIS at step 12.
Simulator  
PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 6 of 6
-Perform  
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION:              SALEM 1 & 2 SYSTEM:                Emergency Operating Procedures TASK:                 Respond to a Loss of Heat Sink (Initiate Bleed and Feed with SI pumps and Rx Head Vents)
TASK NUMBER:           N 1150290501 JPM NUMBER:           15-01 NRC Sim d ALTERNATE PATH:       I x I                               KIA NUMBER:           EPE E05 EA 1.1
                                                                        ---~---~-~
IMPORTANCE FACTOR:
                                                                        - -4.1- -             4.0 APPLICABILITY:                                                               RO             SRO EOCJ         RO[KJ         STACJ           SRO[KJ EVALUATION SETTING/METHOD:             Simulator - Perform


==REFERENCES:==
==REFERENCES:==
2-EOP-FRHS-1, Loss of Secondary Heat Sink,      Rev.~ 61    At- 1-:Jf',~,<c TOOLS AND EQUIPMENT:          None VALIDATED JPM COMPLETION TIME:                  6 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS:                        N/A Developed By:                  G Gauding                          Date:    8-2-16 Instructor Validated By:                S Harris I J Pierce                    Date:    9-28-16 Approved By:
                            ~ru~~{l Traini~Department 1o)j1t,,
Approved By:
Ope~ment                                  Date:
ACTUAL JPM COMPLETION TIME:
ACTUAL TIME CRITICAL COMPLETION TIME:
PERFORMED BY:
GRADE:    D  SAT      D    UNSAT REASON, IF UNSATISFACTORY:
EVALUATOR'S SIGNATURE:                                                      DATE:
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 1 of 8


2-EOP-FRHS-1, Loss of Secondary Heat Sink, 61 At-TOOLS AND EQUIPMENT:
..                                       OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME:   ~~~~~~~~~~~~~~
None VALIDATED JPM COMPLETION TIME: 6 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: Developed By: Validated By: Approved By: Approved By: G Gauding Instructor S Harris I J Pierce ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY:
DATE:   ~~~~~~~~~~~~~~
EVALUATOR'S SIGNATURE:
SYSTEM:                 Emerqencv Operatinq Procedures TASK:                   TCAF a Loss of Heat Sink (Initiate Bleed and Feed with SI pumps and Rx Head Vents)
N/A Date: 8-2-16 Date: 9-28-16 Date: 1o)j1t,, DATE: PSEG Restricted
TASK NUMBER:           N1150290501 SIMULATOR SETUP:               RX HEAD VENT KEYS ARE LOCATED IN SIM BOOTH IC-254 developed by: MSL rupture (1 Oo/o)downstream of MS IVs. Fail all MSIVs open. All AFW pumps failed. Fail 2PR2 shut. Performed TRIP-1 through Step 20. SG WR levels <32%.
-Possession Requires Specific Permission from Nuclear Training Page 1 of 8 4.0 SRO 
INITIAL CONDITIONS:
.. OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME:
DATE:
SYSTEM: Emerqencv Operatinq Procedures TASK: TCAF a Loss of Heat Sink (Initiate Bleed and Feed with SI pumps and Rx Head Vents) TASK NUMBER: N1150290501 SIMULATOR SETUP: RX HEAD VENT KEYS ARE LOCATED IN SIM BOOTH IC-254 developed by: MSL rupture (1 Oo/o)downstream of MS IVs. Fail all MSIVs open. All AFW pumps failed. Fail 2PR2 shut. Performed TRIP-1 through Step 20. SG WR levels <32%. INITIAL CONDITIONS:
* Unit 2 initiated a Rx trip from 100% power in response to a Main Steam line break at the mixing bottle.
* Unit 2 initiated a Rx trip from 100% power in response to a Main Steam line break at the mixing bottle.
* An automatic Safety Injection initiated.
* An automatic Safety Injection initiated.
* The Main Turbine failed to trip automatically, and was manually tripped from the control console.
* The Main Turbine failed to trip automatically, and was manually tripped from the control console.
* MSLI failed, and all MSIV's remain open.
* MSLI failed, and all MSIV's remain open.
* All AFW flow has been lost. --------------*** ------* EOP-TRIP-1 was performed and a transition to FRHS-1, Loss of Secondary Heat Sink was made at Step 20.1 INITIATING CUE: You are the Reactor Operator.
* All AFW flow has been lost.                           --- - - - - ----- --*** - ---- -
Perform FRHS-1 starting at Step 1. Successful Completion Criteria:
* EOP-TRIP-1 was performed and a transition to FRHS-1, Loss of Secondary Heat Sink was made at Step 20.1 INITIATING CUE:
You are the Reactor Operator. Perform FRHS-1 starting at Step 1.
Successful Completion Criteria:
: 1. All critical steps completed.
: 1. All critical steps completed.
: 2. All sequential steps completed in order. 3. All time-critical steps completed within allotted time. 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made. Task Standard for Successful Completion:
: 2. All sequential steps completed in order.
: 1. Stop ALL RCPs. 2. Open 2PR1. 3. Open Rx Head Vent Valves 2RC40-2RC43.
: 3. All time-critical steps completed within allotted time.
PSEG Restricted  
: 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made.
-Possession Requires Specific Permission from Nuclear Training Page 2 of 8 SYSTEM: TASK: STEP
Task Standard for Successful Completion:
* NO. 1 2 3 3.1 4 Emergency Operating Procedures OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE Respond to a Loss of Heat Sink (Initiate Bleed and Feed with SI pumps and Rx Head Vents) STEP (* Denotes a Critical Step) STANDARD IS TOTAL AFW FLOW LESS THAN Determines it was not operator action which 22E04 LB/HR DUE TO OPERATOR caused total AFW flow to be less than 22E04 ACTIONS lb/hr. !E AT LEAST ONE INTACT OR Recognizes ALL SGs are faulted. RUPTURED SG IS AVAILABLE, THEN DO NOT FEED A FAUL TED SG IS RCS PRESSURE GREATER THAN Checks RCS pressure on control console ANY INTACT OR RUPTURED SG and determines it is greater than all SG PRESSURE pressures checked on control console. ARE RCS T-HOTS GREATER THAN Checks RCS Thot indication on control 350&deg;F console and determines that RCS Thots are greater than 350&deg;F. !E WR LEVELS IN AT LEAST TWO SG's Determines at least 2 SG WR levels < 32% ARE LESS THAN 32% (37% ADVERSE), and goes to Step 21. THEN IMMEDIATELY GO TO STEP 21 TO INITIATE RCS BLEED AND FEED NAME:
: 1. Stop ALL RCPs.
DATE:
: 2. Open 2PR1.
COMMENTS EVAL (Required for UNSAT S/U evaluation)
: 3. Open Rx Head Vent Valves 2RC40-2RC43.
PSEG Restricted  
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 2 of 8
-Possession Requires Specific Permission from Nuclear Training Page 3 of 8 SYSTEM: TASK: STEP
 
* NO. 21
OPERATOR TRAINING PROGRAM                        NAME: ~~~~~~~~
* 23 22 23 Emergency Operating Procedures OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE Respond to a Loss of Heat Sink (Initiate Bleed and Feed with SI pumps and Rx Head Vents) STEP (* Denotes a Critical Step) STANDARD CAUTION TO ESTABLISH RCS HEAT REMOVAL Reads Step. BY RCS BLEED AND FEED, STEPS 24 THRU 29 MUST BE PERFORMED QUICKLY AND WITHOUT INTERRUPTION STOP ALL RCPS Depresses STOP PB for 21-24 RCPs and verifies green stop light illuminates and red start light extinguishes.
JOB PERFORMANCE MEASURE                          DATE: ~~~~~~~~~
INITIATE SI Uses Safeguards key and initiates SI on at least one train of Safeguards initiation.
SYSTEM:    Emergency Operating Procedures TASK:      Respond to a Loss of Heat Sink (Initiate Bleed and Feed with SI pumps and Rx Head Vents)
ARE SI VALVES IN SAFEGUARDS Checks 2RP4 and/or console indication to POSITION determine that all valves listed in Table B are in Safeguards position.
STEP                                                                                 COMMENTS STEP
Table B valves are: 2SJ4 OPEN BIT INLET 2SJ5 OPEN BIT INLET 2SJ12 OPEN BIT OUTLET 2SJ13 OPEN BIT OUTLET 2CV68 CLOSED CHARGING DISCHARGE 2CV69 CLOSED CHARGING DISCHARGE (continued next paqe) NAME: DATE: EVAL S/U PSEG Restricted
(* Denotes a Critical Step)                                                         EVAL    (Required for UNSAT
-Possession Requires Specific Permission from Nuclear Training Page 4 of 8 .. ------------------COMMENTS (Required for UNSAT evaluation)
* NO.                                                                  STANDARD S/U        evaluation) 1      IS TOTAL AFW FLOW LESS THAN                 Determines it was not operator action which 22E04 LB/HR DUE TO OPERATOR                 caused total AFW flow to be less than 22E04 ACTIONS                                     lb/hr.
SYSTEM: TASK: STEP
2    !E   AT LEAST ONE INTACT OR                 Recognizes ALL SGs are faulted.
* NO. 23.1 23.2 Emergency Operating Procedures OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE Respond to a Loss of Heat Sink (Initiate Bleed and Feed with SI pumps and Rx Head Vents) STEP (* Denotes a Critical Step) STANDARD Table B Valves (can't): 21-24SJ54 OPEN ACCUMULATOR OUTLET 2SJ1 OPEN RWST TO CHARGING 2SJ2 OPEN RWST TO CHARGING 2CV40 CLOSED DISCHARGE STOP 2CV41 CLOSED DISCHARGE STOP IS 21 OR 22 CHARGING PUMP Checks control console and determines 21 RUNNING and 22 charging pump are running. IS BIT FLOW ESTABLISHED Checks console and determines BIT flow is established.
RUPTURED SG IS AVAILABLE, THEN DO NOT FEED A FAULTED SG 3      IS RCS PRESSURE GREATER THAN               Checks RCS pressure on control console ANY INTACT OR RUPTURED SG                   and determines it is greater than all SG PRESSURE                                   pressures checked on control console.
IS ANY SI PUMP RUNNING Checks control console and determines 21 and 22 SI pumps are running. ARE VALVES IN TABLE COPEN FOR Checks control console indication for valves AT LEAST ONE RUNNING SI PUMP listed in Table C and determines the valves are open for at least one running SI pump. Table C valves are: 21 /22 SI PUMPS 2SJ30 (FROM RWST) 21/22SJ33 (SI PUMP SUCTION) 2SJ135 (COLD LEG DISCHARGE) 21/22SJ134 (COLD LEG DISCHARGE)
3.1    ARE RCS T-HOTS GREATER THAN                 Checks RCS Thot indication on control 350&deg;F                                       console and determines that RCS Thots are greater than 350&deg;F.
NAME: DATE: EVAL S/U PSEG Restricted  
4    !E WR LEVELS IN AT LEAST TWO SG's           Determines at least 2 SG WR levels < 32%
-Possession Requires Specific Permission from Nuclear Training Page 5 of 8 ------------------COMMENTS (Required for UNSAT evaluation)
ARE LESS THAN 32% (37% ADVERSE),             and goes to Step 21.
SYSTEM: TASK: STEP
THEN IMMEDIATELY GO TO STEP 21 TO INITIATE RCS BLEED AND FEED PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 3 of 8
* NO. 24
 
* 24.1
                                                                                                                                      .
* 24.2 Emergency Operating Procedures OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE Respond to a Loss of Heat Sink (Initiate Bleed and Feed with SI pumps and Rx Head Vents) STEP (* Denotes a Critical Step) STANDARD ARE ALL CHARGING AND SI PUMPS Determines all charging and SI pumps are RUNNING AND ALIGNED TO DELIVER running and aligned to deliver flow. FLOW OPEN BOTH PZR PORV STOP VALVES Checks control console and determines BOTH 2PR6 and 2PR7 PORV STOP VALVES are open. OPEN BOTH PZR PORVS Places 2PR1 in manual and depresses 2PR1 PZR PORV open PB and verifies green closed light extinguishes and red open light illuminates.
OPERATOR TRAINING PROGRAM                           NAME: - - - - - - - - -
Places 2PR2 in manual and depresses 2PR2 PZR PORV open PB and reports that 2PR2 will not open. ARE BOTH PZR PORV STOP VALVES Checks control console and determines BOTH OPEN 2PR6 and 2PR7 PORV STOP VALVES are open. AREBOTHPZRPORVSOPEN Determines 2PR2 PZR PORV is not open. Alternate path actions start here. OPEN 2RC40 THRU 2RC43 (REACTOR Inserts key into each 2RC40 THRU 2RC43 HEAD VENTS) (REACTOR HEAD VENTS) switch on 2RP3, turns to open, and verifies each valve opens. Terminate JPM when operator has opened 2RC40 thru 2RC43 Reactor Head Vents. NAME: DATE: EVAL S/U PSEG Restricted  
JOB PERFORMANCE MEASURE                           DATE: - - - - - - - - -
-Possession Requires Specific Permission from Nuclear Training Page 6 of 8 ------------------COMMENTS (Required for UNSAT evaluation)
SYSTEM:    Emergency Operating Procedures TASK:      Respond to a Loss of Heat Sink (Initiate Bleed and Feed with SI pumps and Rx Head Vents)
JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation.
STEP                                                                                   COMMENTS STEP
Prior to JPM usage, revalidate JPM using steps 8 and 11 below. V / Y 1. Task description and number, JPM description and number are identified. , If: 2. Knowledge and Abilities (KIA) references are included.
(* Denotes a Critical Step)                                                           EVAL    (Required for UNSAT
Lt 3. Performance location specified. (in-plant, control room, or simulator)
* NO.                                                                    STANDARD S/U        evaluation) 21                    CAUTION TO ESTABLISH RCS HEAT REMOVAL               Reads Step.
Ir' I !Jr 4. Initial setup conditions are identified. , I 1-= "1 s. Initiating and terminating Cues are properly identified.  
BY RCS BLEED AND FEED, STEPS 24 THRU 29 MUST BE PERFORMED QUICKLY AND WITHOUT INTERRUPTION
/ / 7 \ 6. Task standards identified and verified by SME review. v I -t' 7. Critical steps meet the criteria for critical steps and are identified with an asterisk(*).
* 23    STOP ALL RCPS                               Depresses STOP PB for 21-24 RCPs and verifies green stop light illuminates and red start light extinguishes.
I !1.,, \ 8. Verify the procedure referenced by this JPM matches the most current revision of I
22    INITIATE SI                                 Uses Safeguards key and initiates SI on at least one train of Safeguards initiation.
* v' that procedure:
23    ARE SI VALVES IN SAFEGUARDS                 Checks 2RP4 and/or console indication to POSITION                                     determine that all valves listed in Table B are in Safeguards position.
Procedure Rev. 20 Date .,12t/1-'
Table B valves are:
V \ 9. Pilot test the JPM: ---,----a. verify Cues both verbal and visual are free of conflict, and b. ensure performance time is accurate.
2SJ4 OPEN           BIT INLET 2SJ5 OPEN             BIT INLET 2SJ12 OPEN           BIT OUTLET 2SJ13 OPEN           BIT OUTLET 2CV68 CLOSED CHARGING DISCHARGE 2CV69 CLOSED CHARGING DISCHARGE (continued next paqe)
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructor: Date: 7)9)&#xa3; SME/lnstructor:
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 4 of 8
5 .  
 
'Jvjk Date: ;,
OPERATOR TRAINING PROGRAM                          NAME: - - - - - - - - -
* SME/lnstructor:
JOB PERFORMANCE MEASURE                            DATE: - - - - - - - - -
Date: PSEG Restricted  
SYSTEM:   Emergency Operating Procedures TASK:      Respond to a Loss of Heat Sink (Initiate Bleed and Feed with SI pumps and Rx Head Vents)
-Possession Requires Specific Permission from Nuclear Training Page 7 of 8 INITIAL CONDITIONS:
STEP                                                                                   COMMENTS STEP
(* Denotes a Critical Step)                                                         EVAL    (Required for UNSAT
* NO.                                                                  STANDARD S/U        evaluation)
Table B Valves (can't):
21-24SJ54 OPEN ACCUMULATOR OUTLET 2SJ1         OPEN RWST TO CHARGING 2SJ2       OPEN RWST TO CHARGING 2CV40       CLOSED DISCHARGE STOP 2CV41       CLOSED DISCHARGE STOP 23.1    IS 21 OR 22 CHARGING PUMP                   Checks control console and determines 21 RUNNING                                     and 22 charging pump are running.
IS BIT FLOW ESTABLISHED                     Checks console and determines BIT flow is established.
23.2    IS ANY SI PUMP RUNNING                     Checks control console and determines 21 and 22 SI pumps are running.
ARE VALVES IN TABLE COPEN FOR               Checks control console indication for valves AT LEAST ONE RUNNING SI PUMP                 listed in Table C and determines the valves are open for at least one running SI pump.
Table C valves are:
21 /22 SI PUMPS 2SJ30 (FROM RWST) 21/22SJ33 (SI PUMP SUCTION) 2SJ135 (COLD LEG DISCHARGE) 21/22SJ134 (COLD LEG DISCHARGE)
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 5 of 8
 
OPERATOR TRAINING PROGRAM                        NAME: - - - - - - - - -
JOB PERFORMANCE MEASURE                          DATE: - - - - - - - - -
SYSTEM:   Emergency Operating Procedures TASK:     Respond to a Loss of Heat Sink (Initiate Bleed and Feed with SI pumps and Rx Head Vents)
STEP                                                                                   COMMENTS STEP
(* Denotes a Critical Step)                                                         EVAL    (Required for UNSAT
* NO.                                                                  STANDARD S/U        evaluation)
ARE ALL CHARGING AND SI PUMPS               Determines all charging and SI pumps are RUNNING AND ALIGNED TO DELIVER             running and aligned to deliver flow.
FLOW 24    OPEN BOTH PZR PORV STOP VALVES               Checks control console and determines BOTH 2PR6 and 2PR7 PORV STOP VALVES are open.
* OPEN BOTH PZR PORVS                         Places 2PR1 in manual and depresses 2PR1 PZR PORV open PB and verifies green closed light extinguishes and red open light illuminates.
Places 2PR2 in manual and depresses 2PR2 PZR PORV open PB and reports that 2PR2 will not open.
24.1    ARE BOTH PZR PORV STOP VALVES               Checks control console and determines BOTH OPEN                                       2PR6 and 2PR7 PORV STOP VALVES are open.
AREBOTHPZRPORVSOPEN                         Determines 2PR2 PZR PORV is not open.
Alternate path actions start here.
* 24.2    OPEN 2RC40 THRU 2RC43 (REACTOR             Inserts key into each 2RC40 THRU 2RC43 HEAD VENTS)                                 (REACTOR HEAD VENTS) switch on 2RP3, turns to open, and verifies each valve opens.
Terminate JPM when operator has opened 2RC40 thru 2RC43 Reactor Head Vents.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 6 of 8
 
JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below.
V /     ,Y ~          1. Task description and number, JPM description and number are identified.
If:         ~    2. Knowledge and Abilities (KIA) references are included.
Lt ~ 3.                 Performance location specified. (in-plant, control room, or simulator)
Ir' I   ,!Jr   ~  4. Initial setup conditions are identified.
I     1-= "1 s. Initiating and terminating Cues are properly identified.
            /
      / 7\           6. Task standards identified and verified by SME review.
v I     -t'   ~    7. Critical steps meet the criteria for critical steps and are identified with an asterisk(*).
I
          !1.,, \     8. Verify the procedure referenced by this JPM matches the most current revision of I     *v'   that procedure: Procedure Rev. 20           Date   .,12t/1-'
V \ 9. Pilot test the JPM:
      ---,----             a. verify Cues both verbal and visual are free of conflict, and
: b. ensure performance time is accurate.
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM.
____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.
SME/lnstructor:
                                ~.~\~a-r~                        Date:   7)9)&#xa3; SME/lnstructor:         5 . Linn'~          'Jvjk                       Date:   ;, /~s */1~
SME/lnstructor:                                                         Date:
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 7 of 8
 
INITIAL CONDITIONS:
* Unit 2 initiated a Rx trip from 100% power in response to a Main Steamline break at the mixing bottle.
* Unit 2 initiated a Rx trip from 100% power in response to a Main Steamline break at the mixing bottle.
* An automatic Safety Injection initiated.
* An automatic Safety Injection initiated.
Line 969: Line 1,681:
* MSLI failed, and all MSIV's remain open.
* MSLI failed, and all MSIV's remain open.
* All AFW flow has been lost.
* All AFW flow has been lost.
* EOP-TRIP-1 was performed and a transition to FRHS-1, Loss of Secondary Heat Sink was made at Step 20.1 INITIATING CUE: You are the Reactor Operator.
* EOP-TRIP-1 was performed and a transition to FRHS-1, Loss of Secondary Heat Sink was made at Step 20.1 INITIATING CUE:
Perform FRHS-1 starting at Step 1. PSEG Restricted  
You are the Reactor Operator. Perform FRHS-1 starting at Step 1.
-Possession Requires Specific Permission from Nuclear Training Page 8 of 8 STATION: SYSTEM: TASK: TASK NUMBER: OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE Salem Generating Station Emergency Operating Procedures TCAF Total Loss of All Service Water N1140380401 JPM NUMBER: 15-01 NRC Sim e KIA NUMBER: 076 A2.01 ALTERNATE PATH: CJ ----------l IMPORTANCE FACTOR: 3.5 3.7 ----APPLICABILITY:
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 8 of 8
RO EOCJ RO[[] STAC] SRO[[] EVALUATION SETTING/METHOD:
 
Simulator I Perform  
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION:              Salem Generating Station SYSTEM:                Emergency Operating Procedures TASK:                  TCAF Total Loss of All Service Water TASK NUMBER:          N1140380401 JPM NUMBER:           15-01 NRC Sim e ALTERNATE PATH:     CJ                                 KIA NUMBER:
                                                                    - - - -076 A2.01
                                                                              -- ----l IMPORTANCE FACTOR:         3.5           3.7
                                                                    --   --
APPLICABILITY:                                                           RO           SRO EOCJ         RO[[]         STAC]           SRO[[]
EVALUATION SETTING/METHOD:           Simulator I Perform S2.0P-AB.SW-0001, Loss of SW Header Pressure, Rev. 16 S2.0P-AB.SW-0005, Loss of All Service Water Rev. 4 S2.0P-AR.ZZ-0002, Overhead Annunciator Window B Rev. 36


==REFERENCES:==
==REFERENCES:==
(All rev checked 8-3-16)
TOOLS AND EQUIPMENT:          None VALIDATED JPM COMPLETION TIME:                  5 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS:                    N/A Developed By:                  G Gauding                        Date:  3-23-16 Instructor Validated By:                W Russell I D Cox                  Date:  8-22-16 SME or Instructor Approved By:                                                    Date:
Approved By:                                                    Date:
ACTUAL JPM COMPLETION TIME:
ACTUAL TIME CRITICAL COMPLETION TIME:
PERFORMED BY:
GRADE:    D SAT D UNSAT REASON, IF UNSATISFACTORY:
EVALUATOR'S SIGNATURE:                                                DATE:
PSEG Confidential- Possession Requires Specific Approval from Nuclear Training
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: ~~~~~~~~~~~~~~
DATE:
SYSTEM:              Abnormal Operating Procedures TASK:                TCAF a Total Loss of All Service Water TASK:                N1140380401 Simulator Setup:                    IC-255    100% power. 21 charging pump in service 2 SW bay removed from service IAW S2.0P-AB.SW-003, Service Water Bay Leak. All 4 bay pumps in service.
S2.0P-AB.SW-003 out and marked up.
MALFS: Tied to RT-1 24 SW pump trip 25 SW pump trip 26 SW pump trip INITIAL CONDITIONS:
Unit 2 is operating at 100% power.
21 charging pump is in service.
23 charging pump is aligned for Normal operation IAW Section 4.1 of S2.0P-SO.CVC-0002, Charging Pump Operation.
#2 SW Bay has been removed from service to isolate a leak in the bay IAW S2.0P-AB.SW-0003, Service Water Bay Leak.
All #4 Service Water Bay pumps are in service.
INITIATING CUE:
You are the Reactor Operator. Respond to all indications and alarms.
Successful Completion Criteria
: 1. All critical steps completed.
: 2. All sequential steps completed in order.
: 3. All time-critical steps completed within allotted time.
: 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made Task Standard for Successful Completion:
: 1. Trip the Rx
: 2. Stop all RCPs prior to or within 3 minutes of any RCP bearing temperature reaching 175&deg;F or any other RCP trip criteria being met in S2.0P-AB.RCP-001.
: 3. Place 23 Charging pump in service.
: 4. Reduce operating CCW pumps to one.
PSEG Confidential- Possession Requires Specific Approval from Nuclear Training
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME:
DATE:
SYSTEM:    Abnormal Operating Procedures TASK:      TCAF a Loss of all Service Water STEP                          STEP                                  STANDARD                  EVAL COMMENTS
* No.                                                                                            S/U Simulator Operator: Insert RT-1 after operator assumes watch. This trips all 4 Bay SW pumps.
Recognizes that all SW pumps have tripped.
Enters S2.0P-AB.SW-0005, Loss of All Service Water directly, or responds IAW ARP for [ow service water header pressures. ARP steps are after AB.SW-5 steps here in JPM.
AB.SW-1 steps are after ARP steps here in JPM.
* AB.SW-5    TRIP the reactor, AND CONFIRM the        Trips the Rx using either trip handle, and 3.1      Reactor Trip.                            confirms the Rx trip.
* AB.SW-5    STOP all RCPs.                          Depresses stop PBs for all RCPs.
3.2 GO TO 2-EOP-TRIP-1, Reactor Trip or      Cue: You are to continue with S2.0P-AB.SW-Safety Injection, AND CONTINUE with this 0005 while other operators perform TRIP-1.
procedure.                              Evaluator: Silence OHA's as not associated with loss of SW.
AB.SW-5    CLOSE the following valves to isolate


S2.0P-AB.SW-0001, Loss of SW Header Pressure, Rev. 16 S2.0P-AB.SW-0005, Loss of All Service Water Rev. 4 S2.0P-AR.ZZ-0002, Overhead Annunciator Window B Rev. 36 (All rev checked 8-3-16) TOOLS AND EQUIPMENT:
===3.4 letdown===
None VALIDATED JPM COMPLETION TIME: 5 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: Developed By: Validated By: Approved By: Approved By: G Gauding Instructor W Russell I D Cox SME or Instructor ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY:
*
EVALUATOR'S SIGNATURE:
* 2CV3, 45 GPM ORIFACE               Shuts the open orifice isolation valve and PSEG Confidential- Possession Requires Specific Approval from Nuclear Training
N/A Date: 3-23-16 Date: 8-22-16 Date: Date: DATE: SRO PSEG Confidential-Possession Requires Specific Approval from Nuclear Training OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME:
 
DATE: SYSTEM: Abnormal Operating Procedures TASK: TCAF a Total Loss of All Service Water TASK: N1140380401 Simulator Setup: IC-255 100% power. 21 charging pump in service INITIAL CONDITIONS:
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STEP                       STEP                                    STANDARD                   EVAL COMMENTS
2 SW bay removed from service IAW S2.0P-AB.SW-003, Service Water Bay Leak. All 4 bay pumps in service. S2.0P-AB.SW-003 out and marked up. MALFS: Tied to RT-1 24 SW pump trip 25 SW pump trip 26 SW pump trip Unit 2 is operating at 100% power. 21 charging pump is in service. 23 charging pump is aligned for Normal operation IAW Section 4.1 of S2.0P-SO.CVC-0002, Charging Pump Operation.
* No.                                                                                              S/U
#2 SW Bay has been removed from service to isolate a leak in the bay IAW S2.0P-AB.SW-0003, Service Water Bay Leak. All #4 Service Water Bay pumps are in service. INITIATING CUE: You are the Reactor Operator.
* 2CV4, 75 GPM ORIFICE               ensures the remaining orifice isolation valves
Respond to all indications and alarms. Successful Completion Criteria 1. All critical steps completed.
* 2CV5, 75 GPM ORIFICE               are shut.
: 2. All sequential steps completed in order. 3. All time-critical steps completed within allotted time. 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made Task Standard for Successful Completion:
AB.SW-5 INITIATE Attachment 1, Continuous Action   Initiates Attachment 1, Continuous Action 3.5  Summary.                                   Summary.
: 1. Trip the Rx 2. Stop all RCPs prior to or within 3 minutes of any RCP bearing temperature reaching 175&deg;F or any other RCP trip criteria being met in S2.0P-AB.RCP-001.
AB.SW-5 3.6  IF a Centrifugal Charging Pump is in       Determines a centrifugal charging pump is in service AND the 23 Charging Pump is       service and 23 charging pump is immediately IMMEDIATELY available to be placed in     available to be placed in service.
: 3. Place 23 Charging pump in service. 4. Reduce operating CCW pumps to one. PSEG Confidential-Possession Requires Specific Approval from Nuclear Training OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: DATE: SYSTEM: Abnormal Operating Procedures TASK: TCAF a Loss of all Service Water STEP STEP STANDARD
service, THEN PERFORM the following:
* No. Simulator Operator:
A VERIFY ALL 21-24 RCP Seal Inlet Temperatures <225&deg;F as indicated on 2CC1 or the Plant Computer B. ENSURE 23 Charging Pump is aligned for Normal Operation IAW S2.0P-SO.CVC-0002(Q) Charging Pump Operation.
Insert RT-1 after operator assumes watch. This trips all 4 Bay SW pumps. Recognizes that all SW pumps have tripped. Enters S2.0P-AB.SW-0005, Loss of All Service Water directly, or responds IAW ARP for [ow service water header pressures.
C. PLACE 23 Charging Pump in MANUAL.
ARP steps are after AB.SW-5 steps here in JPM. AB.SW-1 steps are after ARP steps here in JPM.
* D. PLACE Charging Master Flow Controller in MANUAL.
* AB.SW-5 TRIP the reactor, AND CONFIRM the Trips the Rx using either trip handle, and 3.1 Reactor Trip. confirms the Rx trip.
* E. SET 23 Charging Pump Speed Demand to 10-12%.
* AB.SW-5 STOP all RCPs. Depresses stop PBs for all RCPs. 3.2 GO TO 2-EOP-TRIP-1, Reactor Trip or Cue: You are to continue with S2.0P-AB.SW-Safety Injection, AND CONTINUE with this 0005 while other operators perform TRIP-1. procedure.
* F. START 23 Charging Pump AND immediately INCREASE Speed Demand to approximately 20% to couple pump.
Evaluator:
G. ADJUST 23 Charging Pump Speed Demand to obtain desired flow.
Silence OHA's as not associated with loss of SW. AB.SW-5 CLOSE the following valves to isolate 3.4 letdown:
H. ENSURE Seal Injection Flow 6-12 gpm to each Reactor Coolant Pump not to exceed 40 gpm total Seal PSEG Confidential- Possession Requires Specific Approval from Nuclear Training
* 2CV3, 45 GPM ORIFACE Shuts the open orifice isolation valve and
 
* PSEG Confidential-Possession Requires Specific Approval from Nuclear Training EVAL COMMENTS S/U STEP
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STEP                         STEP                                      STANDARD                     EVAL COMMENTS
* No. AB.SW-5 3.5 AB.SW-5 3.6 * *
* No.                                                                                                  S/U Injection Flow.
* OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STEP STANDARD
* I. STOP 21 and 22 Centrifugal Charging Pumps.
* 2CV4, 75 GPM ORIFICE ensures the remaining orifice isolation valves
J. DISPATCH an Operator to monitor operation of 23 Charging Pump due to the potential for rising Component Cooling Water System temperature.
* 2CV5, 75 GPM ORIFICE are shut. INITIATE Attachment 1, Continuous Action Initiates Attachment 1, Continuous Action Summary. Summary. IF a Centrifugal Charging Pump is in Determines a centrifugal charging pump is in service AND the 23 Charging Pump is service and 23 charging pump is immediately IMMEDIATELY available to be placed in available to be placed in service. service, THEN PERFORM the following:
AB.SW-5  !E a Centrifugal Charging Pump is in         Determines a Centrifugal Charging Pump is not 3.7  service AND the 23 Charging Pump is NOT       in service IMMEDIATELY available to be placed in service, THEN STOP 21 and 22 Centrifugal Charging Pumps.
A VERIFY ALL 21-24 RCP Seal Inlet Temperatures  
AB.SW-5  PLACE 2CC131, RCP THERMAL                     Places 2CC131, RCP THERMAL BARRIER, in 3.8  BARRIER, in MANUAL.                           MANUAL.
<225&deg;F as indicated on 2CC1 or the Plant Computer B. ENSURE 23 Charging Pump is aligned for Normal Operation IAW S2.0P-SO.CVC-0002(Q)
AB.SW-5  PLACE Component Cooling Pumps in             Places all Component Cooling Pumps in
Charging Pump Operation.
* 3.9  MANUAL AND REDUCE the number of               MANUAL AND stops all but one Component operating Component Cooling Water             Cooling Water Pumps.
C. PLACE 23 Charging Pump in MANUAL. D. PLACE Charging Master Flow Controller in MANUAL. E. SET 23 Charging Pump Speed Demand to 10-12%. F. START 23 Charging Pump AND immediately INCREASE Speed Demand to approximately 20% to couple pump. G. ADJUST 23 Charging Pump Speed Demand to obtain desired flow. H. ENSURE Seal Injection Flow 6-12 gpm to each Reactor Coolant Pump not to exceed 40 gpm total Seal PSEG Confidential-Possession Requires Specific Approval from Nuclear Training EVAL COMMENTS S/U STEP
Pumps to one.
* No.
Terminate JPM.
* AB.SW-5 3.7 AB.SW-5 3.8 AB.SW-5
ARP    3.1 VERIFY header low pressure using         Determines header pressure is low.
* 3.9 ARP OHA's B-13,14 OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STEP STANDARD Injection Flow. I. STOP 21 and 22 Centrifugal Charging Pumps. J. DISPATCH an Operator to monitor operation of 23 Charging Pump due to the potential for rising Component Cooling Water System temperature.  
OHA's  2PA5373 on 2CC1.
!E a Centrifugal Charging Pump is in Determines a Centrifugal Charging Pump is not service AND the 23 Charging Pump is NOT in service IMMEDIATELY available to be placed in service, THEN STOP 21 and 22 Centrifugal Charging Pumps. PLACE 2CC131, RCP THERMAL Places 2CC131, RCP THERMAL BARRIER, in BARRIER, in MANUAL. MANUAL. PLACE Component Cooling Pumps in Places all Component Cooling Pumps in MANUAL AND REDUCE the number of MANUAL AND stops all but one Component operating Component Cooling Water Cooling Water Pumps. Pumps to one. Terminate JPM. 3.1 VERIFY header low pressure using Determines header pressure is low. 2PA5373 on 2CC1. 3.2 !E low pressure conditions exists due to Determines loss of SW system pressure does known system configuration, THEN GO TO not conditions exists due to known system S2.0P-SO.SW-0001 (Q) Service water configuration.
B-13,14 3.2 !E low pressure conditions exists due to Determines loss of SW system pressure does known system configuration, THEN GO TO       not conditions exists due to known system S2.0P-SO.SW-0001 (Q) Service water           configuration.
Pump operation, to adjust system pressure.
Pump operation, to adjust system pressure.
3.3 IF a valid low pressure condition exists, Determines valid low pressure condition exists, THEN GO TO 82.0P-AB.SW-0001 (Q), and goes to $2.0P-AB.SW-0001, Loss of PSEG Confidential-Possession Requires Specific Approval from Nuclear Training EVAL COMMENTS S/U STEP
3.3 IF a valid low pressure condition exists, Determines valid low pressure condition exists, THEN GO TO 82.0P-AB.SW-0001 (Q),             and goes to $2.0P-AB.SW-0001, Loss of PSEG Confidential- Possession Requires Specific Approval from Nuclear Training
* No. AB.SW-1 3.1 AB.SW-1 3.2 AB.SW-1 3.4 AB.SW-1 3.5 AB.SW-1 3.6 AB.SW-1 3.7 AB.SW-1 3.8 OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STEP STANDARD Loss of Service Water Header Pressure.
 
Service Water Header Pressure.
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STEP                         STEP                                      STANDARD                   EVAL COMMENTS
INITIATE Attachment 1, Continuous Action Initiates Attachment 1, Continuous Action Summary. Summary. Is there indication of a leak in a Service Determines there is no unisolated leak (SW Water Bay per the following?
* No.                                                                                                S/U Loss of Service Water Header Pressure.     Service Water Header Pressure.
Bay 2 has been isolated)
AB.SW-1  INITIATE Attachment 1, Continuous Action   Initiates Attachment 1, Continuous Action 3.1    Summary.                                     Summary.
AB.SW-1  Is there indication of a leak in a Service   Determines there is no unisolated leak (SW 3.2    Water Bay per the following?                 Bay 2 has been isolated)
* Visual indication
* Visual indication
* OHA B-29, 21-23 SW PMP SMP AREA LVL HI
* OHA B-29, 21-23 SW PMP SMP AREA LVL HI
* OHA B-30, 24-26 SW PMP SMP AREA LVL HI START Service Water pumps to maintain Determines no SW pumps are available to be header pressure between 95 and 105 psig. started. Is there a leak or valve malfunction on the Determines the cause of low SW header turbine header as indicated by any of the pressure is from loss of all SW pumps. following?
* OHA B-30, 24-26 SW PMP SMP AREA LVL HI AB.SW-1  START Service Water pumps to maintain       Determines no SW pumps are available to be 3.4    header pressure between 95 and 105 psig. started.
Are both nuclear Service Water headers in Determines neither nuclear SW header is in service? service. IF the Unit is in a Service Water Header Determines the Unit is not in a Service Water Outage ... Header Outage. lE the Unit is NOT in a Service Water Determines the Unit is not in a Service Water Header Outage, THEN GO TO S2.0P-Header Outage, and goes to S2.0P-AB,SW-AB.SW-0005 (Q), Loss of All Service Water 0005. TERMINATING CUE: After reduction of CCW pumps to one, terminate JPM. PSEG Confidential-Possession Requires Specific Approval from Nuclear Training EVAL COMMENTS S/U OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation.
AB.SW-1  Is there a leak or valve malfunction on the Determines the cause of low SW header 3.5    turbine header as indicated by any of the   pressure is from loss of all SW pumps.
Prior to JPM usage, revalidate JPM using steps 8 and 11 below. \,l 1.11111 1 . Task description and number, J PM description and number a re identified.
following?
It /WI\ / 2. Knowledge and Abilities (KIA) references are included.  
AB.SW-1  Are both nuclear Service Water headers in   Determines neither nuclear SW header is in 3.6    service?                                     service.
\}.
AB.SW-1  IF the Unit is in a Service Water Header     Determines the Unit is not in a Service Water 3.7    Outage ...                                   Header Outage.
: 3. Performance location specified. (in-plant, control room, or simulator) V / 4. Initial setup conditions are identified.
AB.SW-1  lE the Unit is NOT in a Service Water       Determines the Unit is not in a Service Water 3.8    Header Outage, THEN GO TO S2.0P-             Header Outage, and goes to S2.0P-AB,SW-AB.SW-0005 (Q), Loss of All Service Water   0005.
l \f ( 5. Initiating and terminating Cues are. properly identified.
TERMINATING CUE: After reduction of CCW pumps to one, terminate JPM.
TQ-AA-106-0303 Revision 5 \.r / Task standards 1dent1f1ed and venfled by SME review. /JA {Critical steps meet the criteria for critical steps and are identified with an asterisk('). 8. Verify the procedure referenced by this JPM matches the most current revision of that procedure:
PSEG Confidential- Possession Requires Specific Approval from Nuclear Training
Procedure Rev. _'i_* _Date 8'} i.Z-bro I I W't\ J9. Pilot test the JPM: a. verify Cues both verbal and visual are free of conflict, and b. ensure performance time is accurate.
 
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructor:
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE TQ-AA-106-0303 Revision 5 JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below.
SME/lnstructor:
\,l   1.11111 ~ 1. Task description and number, J PM description and number a re identified.
SME/lnstructor:  
It /WI\ / 2. Knowledge and Abilities (KIA) references are included.
-------------
\}. ,/~* 3. Performance location specified. (in-plant, control room, or simulator)
Date:
V/               4. Initial setup conditions are identified.
I -z_z Date: Date: ------PSEG Confidential-Possession Requires Specific Approval from Nuclear Training INITIAL CONDITIONS:
l
Unit 2 is operating at 100% power. 21 charging pump is in service. OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE 23 charging pump is aligned for Normal operation IAW Section 4.1 of S2.0P-SO.CVC-0002, Charging Pump Operation.  
  \f (             5. Initiating and terminating Cues are. properly identified.
#2 SW Bay has been removed from service to isolate a leak in the bay IAW S2.0P-AB.SW-0003, Service Water Bay Leak. All #4 Service Water Bay pumps are in service. INITIATING CUE: You are the Reactor Operator.
  \.r / ~6. Task standards 1dent1f1ed and venfled             by SME review.
Respond to all indications and alarms. PSEG Confidential-Possession Requires Specific Approval from Nuclear Training STATION: SYSTEM: TASK: TASK NUMBER: JPM NUMBER: ALTERNATE PATH: OPERATOR TRAINING PROGRAlVI JOB PERFORMANCE MEASURE SALEM Pressurizer and PRT Adjust PRT level and pressure N0100110101 15-01 NRC Sim f K/ANUMBER:
          /JA     {Critical steps meet the criteria for critical steps and are identified with an asterisk(').
007 A4.04 IMPORTANCE FACTOR: 2.6 -----APPLICABILITY:
        ~~*8. Verify the procedure referenced by this JPM matches the most current revision of that procedure: Procedure Rev.     _'i_*_Date   8'}I i.Z-bro I
RO EoO RO[ZJ STAD SRO[Z] EVALUATION SETTING/METHOD:
W't\ J9. Pilot test the JPM:
Simulator I Perform  
: a. verify Cues both verbal and visual are free of conflict, and
: b. ensure performance time is accurate.
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM.
____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.
SME/lnstructor:                                                   Date:  --=-g+-=/i;,'-=zji'l--'-1-=~
I SME/lnstructor:                                                   Date:      ~      -z_z    ~;L SME/lnstructor:                                                   Date:  ------
                        -------------
PSEG Confidential- Possession Requires Specific Approval from Nuclear Training
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE INITIAL CONDITIONS:
Unit 2 is operating at 100% power.
21 charging pump is in service.
23 charging pump is aligned for Normal operation IAW Section 4.1 of S2.0P-SO.CVC-0002, Charging Pump Operation.
#2 SW Bay has been removed from service to isolate a leak in the bay IAW S2.0P-AB.SW-0003, Service Water Bay Leak.
All #4 Service Water Bay pumps are in service.
INITIATING CUE:
You are the Reactor Operator. Respond to all indications and alarms.
PSEG Confidential- Possession Requires Specific Approval from Nuclear Training
 
OPERATOR TRAINING PROGRAlVI JOB PERFORMANCE MEASURE STATION:              SALEM SYSTEM:                Pressurizer and PRT TASK:                  Adjust PRT level and pressure TASK NUMBER:          N0100110101 JPM NUMBER:            15-01 NRC Sim f ALTERNATE PATH:                                                  K/ANUMBER:                   007 A4.04
                                                                                  ----------~
IMPORTANCE FACTOR:                                 2.6
                                                                                  - - 2.6---
APPLICABILITY:                                                                         RO             SRO EoO         RO[ZJ             STAD               SRO[Z]
EVALUATION SETTING/METHOD:               Simulator I Perform


==REFERENCES:==
==REFERENCES:==
S2.0P-SO.PZR-0003, Rev. 15 (checked 8-5-16)
TOOLS AND EQUIPMENT:            None VALIDATED JPM COMPLETION TIME:                          8 min TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS:                                N/A Developed By:                G Gauding                                      Date:    8-5-16 Instructor Validated By:            M Lutek I W Russell SME or Instructor      i,                        Date:    8-22-16 Approved By:
Tra~CrJ* 4                                          Date:
Approved By:
obartment ACTUAL JPM COMPLETION TIME:
ACTUAL TIME CRITICAL COMPLETION TIME:
PERFORMED BY:
GRADE:    D  SAT      D    UNSAT REASON, IF UNSATISFACTORY:
EVALUATOR'S SIGNATURE:                                                              DATE:
PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 1 of7


S2.0P-SO.PZR-0003, Rev. 15 (checked 8-5-16) TOOLS AND EQUIPMENT:
OPERATOR TRAINING PROGRAM JOB PERFORMAL~CE MEASURE NAME:   ~~~~~~~~~~~~~~~~
None VALIDATED JPM COMPLETION TIME: 8 min TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: N/A Developed By: Validated By: Approved By: Approved By: G Gauding Instructor M Lutek I W Russell SME or Instructor i, obartment ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY:
DATE:   ~~~~~~~~~~~~~~~~
EVALUATOR'S SIGNATURE:
SYSTEM:                 Pressurizer and PRT TASK:                   Adjust PRT level and pressure TASK NUMBER:             N0450040101 SIMULATOR SETUP:             15-01 NRC IC-256 PRT level 56.2% (or low enough for the PRT Hi-Lo Lvl alarm to be locked in) with PRT pressure 9.8 psig. Paper copies of procedure needed.
Date: 8-5-16 Date: 8-22-16 Date: DATE: PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 1 of7 2.6 SRO OPERATOR TRAINING PROGRAM JOB MEASURE NAME:
INITIAL CONDITIONS:
DATE:
Unit 2 is at 100% power.
SYSTEM: Pressurizer and PRT TASK: Adjust PRT level and pressure TASK NUMBER: N0450040101 SIMULATOR SETUP: 15-01 NRC IC-256 PRT level 56.2% (or low enough for the PRT Hi-Lo Lvl alarm to be locked in) with PRT pressure 9.8 psig. Paper copies of procedure needed. INITIAL CONDITIONS:
2PR1 is leaking and 2PR6 is shut with power applied. Operators have been attempting to determine the leak rate through 2PR1.
Unit 2 is at 100% power. 2PR1 is leaking and 2PR6 is shut with power applied. Operators have been attempting to determine the leak rate through 2PR1. Console alarm PRT Level Hi-Lo is in alarm (lo) with PRT level at 56.2%. INITIATING CUE: You are directed to raise PRT level to 60% IAW S2.0P-SO.PZR-0003, Pressurizer Relief Tank Operation, Section 5.1. Successful Completion Criteria:
Console alarm PRT Level Hi-Lo is in alarm (lo) with PRT level at 56.2%.
INITIATING CUE:
You are directed to raise PRT level to 60% IAW S2.0P-SO.PZR-0003, Pressurizer Relief Tank Operation, Section 5.1.
Successful Completion Criteria:
: 1. All critical steps completed.
: 1. All critical steps completed.
: 2. All sequential steps completed in order. 3. All time-critical steps completed within allotted time. 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made (and NRC concurrence is obtained).
: 2. All sequential steps completed in order.
: 3. All time-critical steps completed within allotted time.
: 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made (and NRC concurrence is obtained).
Task Standard for Successful Completion:
Task Standard for Successful Completion:
: 1. Raise PRT level to > 60% while maintaining PRT pressure psig. PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 2 of7 SYSTEM: PZR and PRT TASK: Adjust PRT level and pressure STEP STEP
: 1. Raise PRT level to > 60% while maintaining PRT pressure ~10 psig.
* NO. (*Denotes a Critical Step) Provide marked up paper copy of S2.0P-SO.PZR-0003.
PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 2 of7
5.1.1 IF PRT level is low, THEN PERFORM the following:
 
* 5.1.1.A !E required, THEN ST ART 21 or 22 Primary Water Pump. OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STANDARD Reviews Precautions and Limitations.
OPERATOR TRAINING PROGRAM NAME:
Note: The step for reducing PRT pressure may be performed prior to raising level, since pressure is close to the maximum allowed. (See Step 5.1.1.D) IF PRT pressure reduction is performed first, THEN Cue if PRT pressure is lowered past 7 psig ... " CRS states that the pressure reduction is sufficient to allow filling of the PRT now." Depresses start pushbutton for 22 Primary Water Pump. (aligned for manual start) OR Places 21 Primary Water Pump in manual and depresses start pushbutton for 21 Primary Water Pump. IF operator does not start a Primary Water Pump and will gravity feed to makeup to the PRT, THEN Cue: The CRS directs you to use a Primary Water pump to makeup to the PRT. PSEG Restricted-Possession Requires Specific Pem1ission from Nuclear Training Page 3 of7 NAME: DATE: EVAL COMMENTS S/U (Required for UNSAT Evaluation)
JOB PERFORMANCE MEASURE DATE:
SYSTEM: PZR and PRT TASK: Adjust PRT level and pressure STEP STEP
SYSTEM:     PZR and PRT TASK:       Adjust PRT level and pressure STEP                             STEP                                                                               EVAL          COMMENTS
* NO. (*Denotes a Critical Step)
* NO.                   (*Denotes a Critical Step)                                 STANDARD                          S/U      (Required for UNSAT Evaluation)
* 5.1.1.B OPEN 2WR80, CONT PRI WATER STOP.
Provide marked up paper copy of S2.0P-               Reviews Precautions and Limitations.
* 5.1.1.C OPEN 2WR82, PRT WATER SUPPLY.
SO.PZR-0003.
* 5.1.1.D !E PRT pressure approaches 10 psig, THEN OPEN 2PR15, VENT, as necessary, to maintain PRT pressure at >3 psig and _:::10 psig. OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STANDARD Depresses open pushbutton for 2WR80 CONT PRI WATER STOP and verifies open light lit. Depresses open pushbutton for 2WR82, PRT WATER SUPPLY and verifies open light lit. Depresses open pushbutton for 2PR15, VENT prior to PRT pressure rising above 10.0 psig, and depresses close pushbutton prior to PRT pressure lowering below 3.1 psig. Note: IF PRT Hi Pressure alarm is received, it prevents the 2PR15 from opening, and pressure cannot be reduced. When operator has demonstrated that they can raise level without exceeding 10 psig, then Cue: PRT level is now 60% PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 4 of7 NAME:
5.1.1       IF PRT level is low, THEN PERFORM the                 Note: The step for reducing PRT pressure following:                                            may be performed prior to raising level, since pressure is close to the maximum allowed. (See Step 5.1.1.D)
DATE:
IF PRT pressure reduction is performed first, THEN Cue if PRT pressure is lowered past 7 psig ... " CRS states that the pressure reduction is sufficient to allow filling of the PRT now."
EVAL COMMENTS S/U (Required for UNSAT Evaluation)
* 5.1.1.A      !E required, THEN ST ART 21 or 22 Primary            Depresses start pushbutton for 22 Primary Water Pump.                                          Water Pump. (aligned for manual start)
SYSTEM: PZR and PRT TASK: Adjust PRT level and pressure STEP STEP
OR Places 21 Primary Water Pump in manual and depresses start pushbutton for 21 Primary Water Pump.
* NO. (*Denotes a Critical Step) 5.1.1.E When PRT level increases to between 59% and
IF operator does not start a Primary Water Pump and will gravity feed to makeup to the PRT, THEN Cue: The CRS directs you to use a Primary Water pump to makeup to the PRT.
PSEG Restricted-Possession Requires Specific Pem1ission from Nuclear Training Page 3 of7
 
OPERATOR TRAINING PROGRAM NAME: ~~~~~~~~~~
JOB PERFORMANCE MEASURE DATE: ~~~~~~~~~~
SYSTEM:     PZR and PRT TASK:       Adjust PRT level and pressure STEP                             STEP                                                                             EVAL          COMMENTS
* NO.                   (*Denotes a Critical Step)                                STANDARD                          S/U      (Required for UNSAT Evaluation)
* 5.1.1.B     OPEN 2WR80, CONT PRI WATER STOP.                    Depresses open pushbutton for 2WR80 CONT PRI WATER STOP and verifies open light lit.
* 5.1.1.C     OPEN 2WR82, PRT WATER SUPPLY.                      Depresses open pushbutton for 2WR82, PRT WATER SUPPLY and verifies open light lit.
* 5.1.1.D     !E PRT pressure approaches   10 psig, THEN         Depresses open pushbutton for 2PR15, OPEN 2PR15, VENT, as necessary, to maintain         VENT prior to PRT pressure rising PRT pressure at >3 psig and _:::10 psig.           above 10.0 psig, and depresses close pushbutton prior to PRT pressure lowering below 3.1 psig.
Note: IF PRT Hi Pressure alarm is received, it prevents the 2PR15 from opening, and pressure cannot be reduced.
When operator has demonstrated that they can raise level without exceeding 10 psig, then Cue: PRT level is now 60%
PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 4 of7
 
OPERATOR TRAINING PROGRAM NAME:
JOB PERFORMANCE MEASURE DATE:
SYSTEM:     PZR and PRT TASK:       Adjust PRT level and pressure STEP                               STEP                                                                               EVAL          COMMENTS
* NO.                   (*Denotes a Critical Step)                                  STANDARD                          S/U      (Required for UNSAT Evaluation) 5.1.1.E     When PRT level increases to between 59% and           When PRT level rises to 60%:
* 86%:
* 86%:
* 1. CLOSE 2WR80, CONT PRI WATER STOP. 2. CLOSE 2WR82, PRT WATER SUPPLY
Closes 2WR80, CONT PRI WATER
* 3. ENSURE 2PR15, VENT is closed. 4. lE Primary Water Pump is in service IAW Step 5.1.1.A, AND is NOT required to be in service for any other reason, THEN STOP running Primary Water Pump. 5.1.1.F DIRECT a second Operator to perform an Independent Verification of component position in Attachment 1, Section 1.0 OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STANDARD When PRT level rises to 60%: Closes 2WR80, CONT PRI WATER STOP. Closes 2WR82, PRT WATER SUPPLY. Ensures 2PR15, VENT is closed. Depresses stop pushbutton for running Primary Water Pump. lE 21 Primary Water pump was used to fill PRT, THEN places 21 or 22 Primary Water pump in auto. TERMINATING CUE: After operator reads Step 5.1.1.F, state JPM is complete.
* 1. CLOSE 2WR80, CONT PRI WATER                     STOP.
PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 5 of7 NAME: DATE: EVAL COMMENTS S/U (Required for UNSAT Evaluation)
STOP.
OPERATOR TRAINING PROGRA1"\1 JOB MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation.
: 2. CLOSE 2WR82, PRT WATER SUPPLY                   Closes 2WR82, PRT WATER SUPPLY.
Prior to JPM usage, revalidate JPM using steps 8 and 11 below. \A I (r ldh1. Task description and number, JPM description and number are identified.  
* 3. ENSURE 2PR15, VENT is closed.                   Ensures 2PR15, VENT is closed.
"' / wt 2. Knowledge and Abilities (KIA) references are included.
: 4. lE Primary Water Pump is in service             Depresses stop pushbutton for running Primary Water Pump. lE 21 Primary IAW Step 5.1.1.A, AND is NOT required Water pump was used to fill PRT, THEN to be in service for any other reason, places 21 or 22 Primary Water pump in THEN STOP running Primary Water auto.
II-/ d"-l#fl 3. Performance location specified. (in-plant, control room, or simulator)  
Pump.
\,. / d--l6'?1 4. Initial setup conditions are identified. / (f"" VJ/15. Initiating and terminating Cues are properly identified. (J.i / l}JI\, 6. Task standards identified and verified by SME review. v )'-7. Critical steps meet the criteria for critical steps and are identified with an asterisk(*).  
5.1.1.F     DIRECT a second Operator to perform an Independent Verification of component position in Attachment 1, Section 1.0 TERMINATING CUE: After operator reads Step 5.1.1.F, state JPM is complete.
}" 8. Verify the procedure referenced by this JPM matches the most current revision of that procedure:
PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 5 of7
Procedure Rev. IS Date 3/2;i./11,;
 
f \Ml 9. Pilot test the JPM: a. verify Cues both verbal and visual are free of conflict, and b. ensure performance time is accurate.
OPERATOR TRAINING PROGRA1"\1 JOB PERFORMAl~CE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below.
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructor:
\A I     (r ldh1. Task description and number, JPM description and number are identified.
Date: SMEii nstructor:__.h/......._,_'  
  "' / wt~          2. Knowledge and Abilities (KIA) references are included.
'---Date: SME/lnstructor:  
II- / d"- l#fl   3. Performance location specified. (in-plant, control room, or simulator)
-------------
  \,. / d-- l6'?1 4. Initial setup conditions are identified.
Date: _____ _ PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 6 of 7 INITIAL CONDITIONS:
  ~ / (f"" VJ/15. Initiating and terminating Cues are properly identified.
Unit 2 is at 100% power. OPERATOR TRAINll'IG PROGRAM JOB PERFOR.L\IIANCE MEASURE 2PR1 is leaking and 2PR6 is shut with power applied. Operators have been attempting to determine the leak rate through 2PR1. Console alarm PRT Level Hi-Lo is in alarm (lo) with PRT level at 56.2%. INITIATING CUE: You are directed to raise PRT level to 60% IAW S2.0P-SO.PZR-0003, Pressurizer Relief Tank Operation, Section 5.1. PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 7 of 7 STATION: SYSTEM: OPERA TOR TRAINING PROGRAM JOB PERFORMANCE MEASURE Salem Generating Station Emergency Operating Procedures TASK: Perform Actions for a Loss of All AC Power (Energize a 4KV Vital Bus from a Station Power Transformer)
(J.i /   ~ l}JI\, 6. Task standards identified and verified by SME review.
TASK NUMBER: 1150140501 JPM NUMBER: 15-01 NRC Sim g ALTERNATE PATH: D KIA NUMBER: EPE 055 EA 1.07 IMPORTANCE FACTOR: 4.3 APPLICABILITY:
v   )'- ~ 7. Critical steps meet the criteria for critical steps and are identified with an asterisk(*).
RO EoD RO[ZJ STAD SRO[Z] EVALUATION SETTING/METHOD:
        }"   ~      8. Verify the procedure referenced by this JPM matches the most current revision of that procedure: Procedure Rev. IS                   Date 3/2;i./11,;
Simulator I Perform  
f   \Ml     9. Pilot test the JPM:
: a. verify Cues both verbal and visual are free of conflict, and
: b. ensure performance time is accurate.
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM.
____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.
SME/lnstructor:           4Lv~1t---/ ~                                        Date:
                                      '-'lUJr-=--"'--=---'-----'-R-'-u-'-~-s SMEii nstructor:__.h/......._,_'                           ~=---~*
                                                                        '---         Date:
SME/lnstructor:                                                               Date: _ _ _ _ __
                            -------------
PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 6 of 7
 
OPERATOR TRAINll'IG PROGRAM JOB PERFOR.L\IIANCE MEASURE INITIAL CONDITIONS:
Unit 2 is at 100% power.
2PR1 is leaking and 2PR6 is shut with power applied. Operators have been attempting to determine the leak rate through 2PR1.
Console alarm PRT Level Hi-Lo is in alarm (lo) with PRT level at 56.2%.
INITIATING CUE:
You are directed to raise PRT level to 60% IAW S2.0P-SO.PZR-0003, Pressurizer Relief Tank Operation, Section 5.1.
PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 7 of 7
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION:              Salem Generating Station SYSTEM:              Emergency Operating Procedures TASK:                 Perform Actions for a Loss of All AC Power (Energize a 4KV Vital Bus from a Station Power Transformer)
TASK NUMBER:         1150140501 JPM NUMBER:           15-01 NRC Sim g ALTERNATE PATH:     D                                   KIA NUMBER:         EPE 055 EA 1.07
                                                                      ~~~~~~~~--1 IMPORTANCE FACTOR:             4.3             4.5 APPLICABILITY:                                                             RO             SRO EoD         RO[ZJ         STAD           SRO[Z]
EVALUATION SETTING/METHOD:           Simulator I Perform


==REFERENCES:==
==REFERENCES:==
S2.0P-SO.DG-0001, Rev. 39, S2.0P-S0.4KV-0001, Rev. 32 TOOLS AND EQUIPMENT:          None VALIDATED JPM COMPLETION TIME:                10 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS:                      NIA Developed By:                  G Gauding                          Date:  4-18-16 Instructor Validated By:                  Hancock I Russell                  Date:    8-16-16 SME or Instructor Approved By:
Tra~ment Approved By:
Operbsentative ACTUAL JPM COMPLETION TIME:
ACTUAL TIME CRITICAL COMPLETION TIME:
PERFORMED BY:
GRADE:    D  SAT    D UNSAT REASON, IF UNSATISFACTORY:
EVALUATOR'S SIGNATURE:                                                    DATE:
PSEG Confidential- Possession Requires Specific Approval from Nuclear Training Page 1 of 7


S2.0P-SO.DG-0001, Rev. 39, S2.0P-S0.4KV-0001, Rev. 32 TOOLS AND EQUIPMENT:
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME:  ~~~~~~~~~~~~~~
None VALIDATED JPM COMPLETION TIME: 10 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: Developed By: Validated By: Approved By: Approved By: G Gauding Instructor Hancock I Russell SME or Instructor Operbsentative ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY:
DATE:  ~~~~~~~~~~~~~~
EVALUATOR'S SIGNATURE:
SYSTEM:            Emergency Operating Procedures TASK:              Perform Actions for a Loss of All AC Power (Energize a 4KV Vital Bus from a Station Power Transformer)
NIA Date: 4-18-16 Date: 8-16-16 DATE: 4.5 SRO PSEG Confidential-Possession Requires Specific Approval from Nuclear Training Page 1 of 7 OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME:
TASK                1150140501 NUMBER:
Simulator Setup:          IC-256 (with 24ASO racked down and control power off)
INITIAL CONDITIONS:
: 1. Unit 2 is recovering from a loss of all AC Power.
: 2. The crew is performing step 16 of 2-EOP-LOPA-1.
: 3. 23 AFW pump is supplying all required AFW flow.
: 4. 2A EOG was started first and is providing power to 2A Vital Bus
: 5. 2B EOG was just started and is powering 2B 4KV vital bus.
: 6. 2C 4KV Vital Bus remains deenergized and unavailable.
: 7. 24 Station Power Transformer (SPT) has just been energized.
: 8. With 24 SPT now available, the CRS has directed that S2.0P-SO.DG-0001 Section 5.8 and S2.0P-S0.4KV-0001 Section 5.3.6 be utilized to swap 2A Vital Bus from 2A EOG to 24 SPT.
INITIATING CUE:
You are the Control Board Operator. Complete Section 5.8 of S2.0P-SO.OG-0001, and then utilize Section 5.3.6 of S2.0P-S0.4KV-0001 to restore power to 2A Vital Bus from 24 SPT. Prerequisites and Precautions and Limitations have been reviewed and signed.
Successful Completion Criteria
: 1. All critical steps completed.
: 2. All sequential steps completed in order.
: 3. All time-critical steps completed within allotted time.
: 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made Task Standard for Successful Completion:
- Energize 2A 4KV vital bus using 24 SPT PSEG Confidential- Possession Requires Specific Approval from Nuclear Training Page 2 of 7
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME:
DATE:
DATE:
SYSTEM: Emergency Operating Procedures TASK: Perform Actions for a Loss of All AC Power (Energize a 4KV Vital Bus from a Station Power Transformer)
SYSTEM:     Emergency Operating Procedures TASK:       Perform Actions for a Loss of All AC Power (Energize a 4KV Vital Bus from a Station Power Transformer)
TASK NUMBER: 1150140501 Simulator Setup: IC-256 (with 24ASO racked down and control power off) INITIAL CONDITIONS:
STEP                             STEP                                     STANDARD                     EVAL COMMENTS No.                  (* denotes critical task)                                                           S/U Provide marked up copies of S2.0P-SO.DG-0001 and S2.0P-S0.4KV-0001.
: 1. Unit 2 is recovering from a loss of all AC Power. 2. The crew is performing step 16 of 2-EOP-LOPA-1.
SO.DG-1     !E 2A EOG     is paralleled on 2A 4KV Vital   Determines 2A Diesel Generator is not 5.8.1     Bus ....                                       paralleled on 2A 4KV Vital Bus.
: 3. 23 AFW pump is supplying all required AFW flow. 4. 2A EOG was started first and is providing power to 2A Vital Bus 5. 2B EOG was just started and is powering 2B 4KV vital bus. 6. 2C 4KV Vital Bus remains deenergized and unavailable.
5.8.2    !E 2A Vital Bus is isolated and energized from 2A EOG, THEN:                             Places redundant equipment in service as
: 7. 24 Station Power Transformer (SPT) has just been energized.
*
: 8. With 24 SPT now available, the CRS has directed that S2.0P-SO.DG-0001 Section 5.8 and S2.0P-S0.4KV-0001 Section 5.3.6 be utilized to swap 2A Vital Bus from 2A EOG to 24 SPT. INITIATING CUE: You are the Control Board Operator.
* PLACE redundant equipment in             needed:
Complete Section 5.8 of S2.0P-SO.OG-0001, and then utilize Section 5.3.6 of S2.0P-S0.4KV-0001 to restore power to 2A Vital Bus from 24 SPT. Prerequisites and Precautions and Limitations have been reviewed and signed. Successful Completion Criteria 1. All critical steps completed.
service as necessary to support deenergizing 2A Vital Bus
: 2. All sequential steps completed in order. 3. All time-critical steps completed within allotted time. 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made Task Standard for Successful Completion:
-Energize 2A 4KV vital bus using 24 SPT PSEG Confidential-Possession Requires Specific Approval from Nuclear Training Page 2 of 7 SYSTEM: TASK: STEP No. Emergency Operating Procedures OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: DATE: Perform Actions for a Loss of All AC Power (Energize a 4KV Vital Bus from a Station Power Transformer)
STEP STANDARD EVAL (* denotes critical task) S/U Provide marked up copies of S2.0P-SO.DG-0001 and S2.0P-S0.4KV-0001.
SO.DG-1 !E 2A EOG is paralleled on 2A 4KV Vital Determines 2A Diesel Generator is not 5.8.1 5.8.2 *
* Bus .... paralleled on 2A 4KV Vital Bus. !E 2A Vital Bus is isolated and energized from 2A EOG, THEN: Places redundant equipment in service as
* PLACE redundant equipment in needed: service as necessary to support deenergizing 2A Vital Bus
* 22 CCW pump Note: 1 SW pump with the TGA isolated is
* 22 CCW pump Note: 1 SW pump with the TGA isolated is
* STOP all 2A Vital Bus loads using sufficient for maintaining SW header pressure Attachment 1 Stops the following equipment (if running):
*
* STOP all 2A Vital Bus loads using     sufficient for maintaining SW header pressure Attachment 1 Stops the following equipment (if running):
* 21 CCW pump
* 21 CCW pump
* 21 SW pump
* 21 SW pump
Line 1,118: Line 1,983:
* 21 FHB Exhaust Fan
* 21 FHB Exhaust Fan
* 21 AFW pump
* 21 AFW pump
* 21 SI I 21 CS pumps PSEG Confidential-Possession Requires Specific Approval from Nuclear Training Page 3 of 7 COMMENTS STEP No. 5.8.3
* 21 SI I 21 CS pumps PSEG Confidential- Possession Requires Specific Approval from Nuclear Training Page 3 of 7
* 5.8.4 5.8.5 S0.4KV-1 5.3.6 5.3.6.A
 
* 5.3.6.B OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STEP STANDARD (* denotes critical task) OPEN 2A DIESEL GENERATOR BREAKER Opens 2A DIESEL GENERATOR BREAKER by performing one of the following:
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STEP                         STEP                                                              EVAL STANDARD                         COMMENTS No.              (* denotes critical task)                                                     S/U 5.8.3  OPEN 2A DIESEL GENERATOR BREAKER             Opens 2A DIESEL GENERATOR BREAKER by performing one of the following:         by performing one of the following:
by performing one of the following:
* OPEN 2AD1AX6D, 2A DIESEL
* OPEN 2AD1AX6D, 2A DIESEL
* Directs opening of 2AD1AX6D, 2A GENERATOR BREAKER (64' Swgr DIESEL GENERATOR BREAKER (64' Rm), or Swgr Rm), or
* Directs opening of 2AD1AX6D, 2A GENERATOR BREAKER (64' Swgr                 DIESEL GENERATOR BREAKER (64' Rm), or                                     Swgr Rm), or
*
* PRESS 2A BREAKER OPEN
* PRESS 2A BREAKER OPEN
* Presses 2A BREAKER OPEN pushbutton (2CC3), or pushbutton (2CC3), or
* Presses 2A BREAKER OPEN pushbutton (2CC3), or                       pushbutton (2CC3), or
* PLACE 2A-DF-GCP-3, GENERATOR
* PLACE 2A-DF-GCP-3, GENERATOR
* Directs placing 2A-DF-GCP-3, CIRCUIT (BCS), to TRIP (2A DIG GENERATOR CIRCUIT (BCS), to Control Panel). TRIP (2A DIG Control Panel). ALLOW Diesel to run unloaded 3 Cue: 2A EOG will be shutdown by local minutes prior to stopping the EOG. operator.
* Directs placing 2A-DF-GCP-3, CIRCUIT (BCS), to TRIP (2A DIG             GENERATOR CIRCUIT (BCS), to Control Panel).                             TRIP (2A DIG Control Panel).
If diesel unloading  
5.8.4  ALLOW Diesel to run unloaded for~ 3         Cue: 2A EOG will be shutdown by local minutes prior to stopping the EOG.           operator.
... Determines step is NIA IF 2A 4KV Vital Bus is to be energized from 24 SPT,THEN:
5.8.5  If diesel unloading ...                     Determines step is NIA S0.4KV-1 IF 2A 4KV Vital Bus is to be energized from 5.3.6  24 SPT,THEN:
Direct NEO to RACK UP 2AD1AX24ASD, Contacts NEO and directs them to rack up 24 STATION POWER TRANSFORMER 2AD1AX24ASD, 24 STATION POWER INFEED BREAKER (64' Swgr Rm). TRANSFORMER INFEED BREAKER. Simulator Operator:
5.3.6.A Direct NEO to RACK UP 2AD1AX24ASD,           Contacts NEO and directs them to rack up 24 STATION POWER TRANSFORMER                 2AD1AX24ASD, 24 STATION POWER INFEED BREAKER (64' Swgr Rm).               TRANSFORMER INFEED BREAKER.
MODIFY REMOTE ED21D to ON, then report 2AD1AX24ASD, 24 STATION POWER TRANSFORMER INFEED BREAKER is racked up. PRESS Mimic Bus 2A VITAL INFEED 24ASD Depresses Mimic Bus 2A VITAL INFEED pushbutton AND ENSURE Console Bezel 24ASD pushbutton AND determines the 24ASD MIMIC BUS INTLK CLOSE Console Bezel 24ASD MIMIC BUS INTLK SELECTION illuminates.
Simulator Operator: MODIFY REMOTE ED21D to ON, then report 2AD1AX24ASD, 24 STATION POWER TRANSFORMER INFEED BREAKER is racked up.
CLOSE SELECTION illuminates.
* 5.3.6.B PRESS Mimic Bus 2A VITAL INFEED 24ASD       Depresses Mimic Bus 2A VITAL INFEED pushbutton AND ENSURE Console Bezel         24ASD pushbutton AND determines the 24ASD MIMIC BUS INTLK CLOSE                 Console Bezel 24ASD MIMIC BUS INTLK SELECTION illuminates.                       CLOSE SELECTION illuminates.
PSEG Confidential-Possession Requires Specific Approval from Nuclear Training Page 4 of 7 EVAL COMMENTS S/U 5.3.6.C
PSEG Confidential- Possession Requires Specific Approval from Nuclear Training Page 4 of 7
* OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE PERFORM the following:
 
: 1. PRESS AND HOLD control console Presses and Holds control console 24ASD 24ASD CLOSE pushbutton.
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE 5.3.6.C PERFORM the following:
CLOSE pushbutton, then releases pushbutton
* 1. PRESS AND HOLD control console             Presses and Holds control console 24ASD 24ASD CLOSE pushbutton.                       CLOSE pushbutton, then releases pushbutton
: 2. RELEASE pushbutton when 24ASD when 24ASD indicates closed. indicates CLOSED. 3. ENSURE the following:
: 2. RELEASE pushbutton when 24ASD               when 24ASD indicates closed.
Checks Console bezel 24ASD MIMIC BUS a. Console bezel 24ASD MIMIC BUS INTLK INTLK CLOSE SELECTION is extinguished.
indicates CLOSED.
: 3. ENSURE the following:                       Checks Console bezel 24ASD MIMIC BUS
: a. Console bezel 24ASD MIMIC BUS INTLK     INTLK CLOSE SELECTION is extinguished.
CLOSE SELECTION is extinguished.
CLOSE SELECTION is extinguished.
: b. 2A 4KV Vital Bus voltage is 4.275 -4.336KV (normal) OR 4.330 -4.417KV (single source of off-site Determines 2A Vital Bus voltage is 4.275 -power). 4.385KV (single source of off-site power. c. OHA J-17, 2A 4KV VTL BUS Determines OHA J-17 2A 4KV VTL BUS UNDRVOL T, is clear. UNDRVOL T is clear. Terminate JPM. PSEG Confidential-Possession Requires Specific Approval from Nuclear Training Page 5 of 7 OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation.
: b. 2A 4KV Vital Bus voltage is 4.275 -
Prior to JPM usage, revalidate JPM using steps 8 and 11 below. I! / ;:J-1. Task description and number, JPM description and number are identified. " ./ (), 2. Knowledge and Abilities (KJA) references are included.
4.336KV (normal)
v 3. Performance location specified. (in-plant, control room, or simulator) v 4. Initial setup conditions are identified.
OR 4.330 - 4.417KV (single source of off-site Determines 2A Vital Bus voltage is 4.275 -
v 5. Initiating and terminating Cues are properly identified.
power).                                   4.385KV (single source of off-site power.
v 6. Task standards identified and verified by SME review . . v --9--7. Critical steps meet the criteria for critical steps and are identified with an asterisk (*). V ___Q_ 8. Verify the procedure referenced bl_ this JPM matchei the most current revision of that procedure:
: c. OHA J-17, 2A 4KV VTL BUS                 Determines OHA J-17 2A 4KV VTL BUS UNDRVOLT, is clear.                       UNDRVOLT is clear.
Procedure Rev. 2j_ Date <3/Jvlllo fJ 9. Pilot test the JPM: .] z_ -C-a. verify Cues both verbal and visual are free of conflict, and b. ensure performance time is accurate. 10. If the JPM cannot be performed as written with proper responses, then revise the JPM / 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructor:
Terminate JPM.
Date: $> J (L Date: S / i G /J 6 I I Date: ------PSEG Confidential-Possession Requires Specific Approval from Nuclear Training Page 6 of 7 INITIAL CONDITIONS:
PSEG Confidential- Possession Requires Specific Approval from Nuclear Training Page 5 of 7
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE 1. Unit 2 is recovering from a loss of all AC Power. 2. The crew is performing step 16 of 2-EOP-LOPA-1.
 
: 3. 23 AFW pump is supplying all required AFW flow. 4. 2A EOG was started first and is providing power to 2A Vital Bus 5. 2B EOG was just started and is powering 2B 4KV vital bus. 6. 2C 4KV Vital Bus remains deenergized and unavailable.
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below.
I! /   ;:J-   1. Task description and number, JPM description and number are identified.
  " ./   (),   2. Knowledge and Abilities (KJA) references are included.
v     I~
    ~ 3. Performance location specified. (in-plant, control room, or simulator) v   ~ 4. Initial setup conditions are identified.
v   ~ 5.         Initiating and terminating Cues are properly identified.
v   ~ 6. Task standards identified and verified by SME review .
  .v --9--     7. Critical steps meet the criteria for critical steps and are identified with an asterisk (*).
V   ___Q_ 8. Verify the procedure referenced         bl_ this JPM matchei the most current revision of
        ~        that procedure: Procedure Rev.     2j_ Date <3/Jvlllo fJ 9. Pilot test the JPM:                     . ] z_
    -C- a. verify Cues both verbal and visual are free of conflict, and
: b. ensure performance time is accurate.
    ~ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM
    /         11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.
    ~nstructo?!IL~"""'k_.-                                            Date:   $> J(L /1~
    's-M(;lnstructor,.~              ~l(                                Date:   S I/ i G /J I
6 SME/lnstructor:                                                    Date: - - - - - -
                      ~-----------~
PSEG Confidential- Possession Requires Specific Approval from Nuclear Training Page 6 of 7
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE INITIAL CONDITIONS:
: 1. Unit 2 is recovering from a loss of all AC Power.
: 2. The crew is performing step 16 of 2-EOP-LOPA-1.
: 3. 23 AFW pump is supplying all required AFW flow.
: 4. 2A EOG was started first and is providing power to 2A Vital Bus
: 5. 2B EOG was just started and is powering 2B 4KV vital bus.
: 6. 2C 4KV Vital Bus remains deenergized and unavailable.
: 7. 24 Station Power Transformer (SPT) has just been energized.
: 7. 24 Station Power Transformer (SPT) has just been energized.
: 8. With 24 SPT now available, the CRS has directed that S2.0P-SO.DG-0001 Section 5.8 and S2.0P-S0.4KV-0001 Section 5.3.6 be utilized to swap 2A Vital Bus from 2A EOG to 24 SPT. INITIATING CUE: You are the Control Board Operator.
: 8. With 24 SPT now available, the CRS has directed that S2.0P-SO.DG-0001 Section 5.8 and S2.0P-S0.4KV-0001 Section 5.3.6 be utilized to swap 2A Vital Bus from 2A EOG to 24 SPT.
Complete Section 5.8 of S2.0P-SO.OG-0001, and then utilize Section 5.3.6 of S2.0P-S0.4KV-0001 to restore power to 2A Vital Bus from 24 SPT. Prerequisites and Precautions and Limitations have been reviewed and signed. PSEG Confidential-Possession Requires Specific Approval from Nuclear Training Page 7 of 7 STATION: SYSTEM: TASK: TASK NUMBER: JPM NUMBER: OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SALEM 1 & 2 Loss of Control Air TCAF a Loss of Control Air N1140070401 15-01 NRC Sim h ALTERNATE PATH: I x I KIA NUMBER: APE 065 AA2.06 IMPORTANCE FACTOR: 3.6 4.2 APPLICABILITY:
INITIATING CUE:
RO SRO EOCJ RO[KJ STACJ SRO[KJ EVALUATION SETTING/METHOD:
You are the Control Board Operator. Complete Section 5.8 of S2.0P-SO.OG-0001, and then utilize Section 5.3.6 of S2.0P-S0.4KV-0001 to restore power to 2A Vital Bus from 24 SPT. Prerequisites and Precautions and Limitations have been reviewed and signed.
Simulator  
PSEG Confidential- Possession Requires Specific Approval from Nuclear Training Page 7 of 7
-Perform  
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION:              SALEM 1 & 2 SYSTEM:                Loss of Control Air TASK:                  TCAF a Loss of Control Air TASK NUMBER:          N1140070401 JPM NUMBER:            15-01 NRC Sim h ALTERNATE PATH:       I x I                             KIA NUMBER:         APE 065 AA2.06
                                                                        ~~~~~~~~~~
IMPORTANCE FACTOR:             3.6           4.2 APPLICABILITY:                                                               RO           SRO EOCJ         RO[KJ         STACJ           SRO[KJ EVALUATION SETTING/METHOD:             Simulator - Perform S2.0P-AB.CA-0001, Rev. 21 Loss of Control Air (both rev checked 8-5-16)


==REFERENCES:==
==REFERENCES:==
S2.0P-AR.ZZ-0011, Rev. 60, pages 118-128 TOOLS AND EQUIPMENT:          None VALIDATED JPM COMPLETION TIME:                  8 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS:                        N/A Developed By:                  G Gauding                          Date: 8-5-16 Instructor Validated By:              M Lutek I W Russell                    Date: 8-22-16 SME or Instructor      fJL_
Approved By:
Trai~:n;v                              Date:
Approved By:                                                      Date:
Operbrtment ACTUAL JPM COMPLETION TIME:
ACTUAL TIME CRITICAL COMPLETION TIME:
PERFORMED BY:
GRADE:    D  SAT      D    UNSAT REASON, IF UNSATISFACTORY:
EVALUATOR'S SIGNATURE:                                                    DATE:
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 1 of 13


S2.0P-AB.CA-0001, Rev. 21 Loss of Control Air (both rev checked 8-5-16) S2.0P-AR.ZZ-0011, Rev. 60, pages 118-128 TOOLS AND EQUIPMENT:
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: ~~~~~~~~~~~~~-
None VALIDATED JPM COMPLETION TIME: 8 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: Developed By: Validated By: Approved By: Approved By: G Gauding Instructor M Lutek I W Russell SME or Instructor fJL_
DATE: ~~~~~~~~~~~~~-
Operbrtment ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY:
SYSTEM:                 Loss of Control air TASK:                   TCAF Loss of Control Air TASK NUMBER:           N1140070401 SIMULATOR SETUP:             Check 2WG41 is open 15-01 NRC IC-258 RT-1 MALF: CA0221 #2 STATION AIR CMPRSSR TRIP REM: CA13D LOCKOUT #1 STATION AIR CMPRSR, Delay 1:30 1/0 : AQ01 OVLO COMP 1 TROUBLE ALARM, Fin Val: ON, Delay 1:30 Other setup:
EVALUATOR'S SIGNATURE:
REM: CA15D LOCKOUT #3 STATION AIR CMPRSR CA11D #1 EMERGENCY AIR COMPRSR IN AUTO Fin Val: MANUAL CA 12M #1 EMRGENCY AIR CMPRSR SWITCH Fin Val: Stop 1/0 : AQ01       OVLO COMP 3 TROUBLE ALARM, Fin Val: ON INITIAL CONDITIONS:
N/A Date: 8-5-16 Date: 8-22-16 Date: Date: DATE: PSEG Restricted
-Possession Requires Specific Permission from Nuclear Training Page 1 of 13 OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM: Loss of Control air TASK: TCAF Loss of Control Air TASK NUMBER: N1140070401 SIMULATOR SETUP: 15-01 NRC IC-258 RT-1 Check 2WG41 is open MALF: CA0221 #2 STATION AIR CMPRSSR TRIP NAME:
DATE:
REM: CA13D LOCKOUT #1 STATION AIR CMPRSR, Delay 1:30 1/0 : AQ01 OVLO COMP 1 TROUBLE ALARM, Fin Val: ON, Delay 1 :30 Other setup: REM: CA15D LOCKOUT #3 STATION AIR CMPRSR CA11D #1 EMERGENCY AIR COMPRSR IN AUTO Fin Val: MANUAL CA 12M #1 EMRGENCY AIR CMPRSR SWITCH Fin Val: Stop 1/0 : AQ01 OVLO COMP 3 TROUBLE ALARM, Fin Val: ON INITIAL CONDITIONS:
* Unit 2 is operating at 100% power.
* Unit 2 is operating at 100% power.
* A WG release is in progress from 21 GOT. * #3 SAC is CIT for scheduled maintenance.
* A WG release is in progress from 21 GOT.
* Unit 1 is operating at 100% power. INITIATING CUE: You are the Unit 2 Reactor Operator.
    *   #3 SAC is CIT for scheduled maintenance.
Respond to all indications and alarms. Successful Completion Criteria:
* Unit 1 is operating at 100% power.
INITIATING CUE:
You are the Unit 2 Reactor Operator. Respond to all indications and alarms.
Successful Completion Criteria:
: 1. All critical steps completed.
: 1. All critical steps completed.
: 2. All sequential steps completed in order. 3. All time-critical steps completed within allotted time. 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made. Task Standard for Successful Completion:
: 2. All sequential steps completed in order.
: 1. Isolate Letdown 2. Terminate Gaseous Release 3. Trip the Rx prior to auto trip on lo lo SG NR level. PSEG Restricted  
: 3. All time-critical steps completed within allotted time.
-Possession Requires Specific Permission from Nuclear Training Page 2of13 SYSTEM: TASK: STEP
: 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made.
* NO. Loss of Control Air TCAF a Loss of Control Air STEP (* Denotes a Critical Step) Simulator Operator:
Task Standard for Successful Completion:
Insert RT-1 after operator assumes watch. OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STANDARD Note: The #1 and #3 Compressor Trouble alarms on 2CC1 do NOT have audible or flash capabilities (S2.0P-AR.ZZ-0011 page 120). Determines  
: 1. Isolate Letdown
#2 Station Air Compressor (SAC) has tripped, and the Unit 2 Emergency Control Air Compressor (ECAC) has automatically started. Note: All 3 SAC supply breakers open is an auto start signal for both ECAC's. The Unit 2 ECAC will auto start, (Unit 1 will not). By design, the ECAC will not load until its control air header pressure lowers to 85 psig. 2A control air header is supplied from #2 ECAC, 2B control air header is supplied from #1 ECAC. Note: The next-to-load SAC (follow) will not immediately start. It requires Station Air header pressure to drop to 5 psig below the follow setpoint ( 105 psig) for -5 seconds. Refers to the S2.0P-AR.ZZ-0011, Control Console 2CC1, ARP for COMPR 2 TROUBLE. NAME: DATE: EVAL SIU PSEG Restricted  
: 2. Terminate Gaseous Release
-Possession Requires Specific Permission from Nuclear Training Page 3 of 13 ------------------COMMENTS (Required for UNSAT evaluation)
: 3. Trip the Rx prior to auto trip on lo lo SG NR level.
SYSTEM: Loss of Control Air TASK: TCAF a Loss of Control Air STEP STEP
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 2of13
* NO. (*Denotes a Critical Step) ARP 3.1 lE SAC 2 trips, THEN: A. COORDINATE (as necessary) with Unit 1 B. ENSURE operating OR START at least one SAC IAW SC.OP-SO.SA-0001(Z), Station Air System Operation.
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STANDARD Coordinates with Unit 1 to start at least one SAC IAW SC.OP-SO.SA-0001{Z), Station Air System Operation.
OPERATOR TRAINING PROGRAM                            NAME: - - - - - - - - -
Cue when contacted as Unit 1: Unit 1 will ensure #1 SAC is placed in service. NAME: 0 ATE: EVAL S/U ARP 3.2 IF AT ANY TIME Station Air pressure GOES TO S2.0P-AB.CA-0001(Q), Loss of cannot be maintained  
JOB PERFORMANCE MEASURE                            DATE: - - - - - - - - -
.:::,100 psig, THEN Control Air, when Station Air pressure lowers GO TO S2.0P-AB.CA-0001(Q), Loss of to 100 psig if AB not entered previously.
SYSTEM:    Loss of Control Air TASK:      TCAF a Loss of Control Air STEP                                                                                   COMMENTS STEP
Control Air. Simulator Operator:
(* Denotes a Critical Step)                                                         EVAL    (Required for UNSAT
Ensure #1 SAC locks out 1 :30 after insertion of RT-1, then announce twice on plant page: "#1 Station Air Compressor Trip." Recognizes that no SAC's are running, and enters S2.0P-AB.CA-0001 if not entered previously.
* NO.                                                                 STANDARD SIU        evaluation)
PSEG Restricted  
Note: The #1 and #3 Compressor Trouble alarms on 2CC1 do NOT have audible or flash capabilities (S2.0P-AR.ZZ-0011 page 120).
-Possession Requires Specific Permission from Nuclear Training Page 4of13 ------------------COMMENTS (Required for UNSAT evaluation)
Simulator Operator: Insert RT-1 after operator assumes watch.
SYSTEM: TASK: STEP
Determines #2 Station Air Compressor (SAC) has tripped, and the Unit 2 Emergency Control Air Compressor (ECAC) has automatically started.
* NO. AB.CA 3.1 3.2 Loss of Control Air TCAF a Loss of Control Air STEP (* Denotes a Critical Step) INITIATE Attachment 1, Continuous Action Summary. EITHER of the following conditions exist?
Note: All 3 SAC supply breakers open is an auto start signal for both ECAC's. The Unit 2 ECAC will auto start, (Unit 1 will not). By design, the ECAC will not load until its control air header pressure lowers to 85 psig. 2A control air header is supplied from #2 ECAC, 2B control air header is supplied from #1 ECAC.
* ALL Station Air Compressors stopped
Note: The next-to-load SAC (follow) will not immediately start. It requires Station Air header pressure to drop to 5 psig below the follow setpoint ( 105 psig) for - 5 seconds.
* EITHER Station Air Header <100 psig OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STANDARD Note: Approximate event times are listed below from insertion of RT-1. 1 min -1 SAC auto starts. 1 min 30 sec -1 SAC trips. 3 min 50 sec -2 ECAC begins loading. 4 min 10 sec -28 Control Air header pressure reaches 80 PSIG, and SA low pressure alarm. 4 min 25 sec -CA low pressure alarm. 6.5 min 24BF19 Feed Reg Valves begin closing. 7 min 10 sec -G-15 OHA ADFCS TRBL. Initiates Attachment 1, Continuous Action Summary. Cue IF Required:
Refers to the S2.0P-AR.ZZ-0011, Control Console 2CC1, ARP for COMPR 2 TROUBLE.
If CAS Step 8.0 action is being taken to refer to Attachment 2 for valve fail positions and for further action to be taken, then: Cue: The CRS will refer to Attachment 2 Determines all SAC's are stopped or determines Station Air Header pressure is <100 psig. NAME: DATE: EVAL S/U ' PSEG Restricted  
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 3 of 13
-Possession Requires Specific Permission from Nuclear Training Page 5of13 ------------------COMMENTS (Required for UNSAT evaluation)
 
SYSTEM: TASK: STEP
OPERATOR TRAINING PROGRAM                          NAME:
* NO. 3.3 3.4 3.5 Loss of Control Air TCAF a Loss of Control Air STEP (* Denotes a Critical Step) lE a loss of 1 F Group Bus has occurred, AND 1 H Group Bus is available, THEN SEND an Operator to restore power to #1 SAC Auxiliary Oil pump by transferring 11 Turbine West 230V Control Center IAW Attachment 14, Section 1.0. IF a loss of 2F Group Bus has occurred, AND 2H Group Bus is available, THEN SEND an Operator to restore power to #2 SAC Auxiliary Oil pump by transferring 21 Turbine West 230V Control Center IAW Attachment 14, Section 2.0. lE a loss of 1 H Group Bus has occurred, AND 1 F Group Bus is available, THEN SEND an Operator to restore power to #3 SAC Auxiliary Oil pump by transferring 11 Turbine East 230V Control Center IAW Attachment 14, Section 3.0. OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STANDARD Determines a loss of 1 F Group Bus has not occurred.
                                                                                                                    ---------
Determines a loss of 2F Group Bus has not occurred.
JOB PERFORMANCE MEASURE                            0 ATE:
Determines a loss of 1 H Group Bus has not occurred.
                                                                                                                    ---------
NAME: DATE: EVAL S/U i PSEG Restricted
SYSTEM:     Loss of Control Air TASK:       TCAF a Loss of Control Air STEP                                                                                   COMMENTS STEP
-Possession Requires Specific Permission from Nuclear Training Page 6of13 ------------------COMMENTS (Required for UNSAT evaluation)
(*Denotes a Critical Step)                                                           EVAL    (Required for UNSAT
SYSTEM: TASK" STEP
* NO.                                                                    STANDARD S/U        evaluation)
* NO. 3.6 3.7 3.8 3.9 3.10/3.11 Loss of Control Air TCAF a Loss of Control Air STEP (*Denotes a Critical Step) START or have Unit One Control Room START Next to Load Station Air Compressor.
ARP 3.1     lE SAC 2 trips, THEN:
Either Station Air Header indicating less than100 psig? Attempt to START, or have Unit One Control Room START, remaining Station Air Compressor.
A. COORDINATE (as necessary)           Coordinates with Unit 1 to start at least one with Unit 1                          SAC IAW SC.OP-SO.SA-0001{Z), Station Air B. ENSURE operating OR START at        System Operation.
NOTIFY the CRS/SM to evaluate use of temporary air compressors.
least one SAC IAW SC.OP-SO.SA-0001(Z), Station Air           Cue when contacted as Unit 1: Unit 1 will System Operation.                    ensure #1 SAC is placed in service.
2A Control Air Header less than or equal to 88 psig? OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STANDARD Determines no SAC's are available.
ARP 3.2     IF AT ANY TIME Station Air pressure         GOES TO S2.0P-AB.CA-0001(Q), Loss of cannot be maintained .:::,100 psig, THEN   Control Air, when Station Air pressure lowers GO TO S2.0P-AB.CA-0001(Q), Loss of         to 100 psig if AB not entered previously.
Cue if required:
Control Air.
If Unit 1 is contacted, report that #3 Station Air Compressor is tagged out and #1 Station Air Compressor has tripped, and that an operator has been dispatched to the Station Air Compressors.
Simulator Operator: Ensure #1 SAC locks out 1:30 after insertion of RT-1, then announce twice on plant page: "#1 Station Air Compressor Trip."
Determines both Station Air Headers are indicating less than 100 psig. Determines no SAC's can be started. Cue: CRS will evaluate use of temporary air compressors.
Recognizes that no SAC's are running, and enters S2.0P-AB.CA-0001 if not entered previously.
Determines 2A control air header pressure is: less than or equal to 88 psig and determines
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 4of13
#2 ECAC is in service OR >88 psig. NAME: DATE: EVAL S/U PSEG Restricted
 
-Possession Requires Specific Permission from Nuclear Training Page 7 of 13 ------------------COMMENTS (Required for UNSAT evaluation)
OPERATOR TRAINING PROGRAM                        NAME:
SYSTEM: Loss of Control Air OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: DATE: TASK TCAF a Loss of Control Air -STEP
                                                                                                                  ---------
* NO. 3.12/3.13 3.14 3.15 STEP (*Denotes a Critical Step) STANDARD EVAL S/U 2B Control Air Header less than or equal Determines 2B control air header pressure is: to 88 psig? less than or equal to 88 psig and contacts Unit 1 to place #1 ECAC in service OR >88 psig. Cue: When Unit 1 is contacted to start #1 ECAC, state: " # 1 ECAC has tripped. " SEND operators to: Dispatches operators to:
JOB PERFORMANCE MEASURE                          DATE: - - - - - - - - -
SYSTEM:     Loss of Control Air TASK:       TCAF a Loss of Control Air STEP                                                                                   COMMENTS STEP
(* Denotes a Critical Step)                                                         EVAL    (Required for UNSAT
* NO.                                                                    STANDARD S/U        evaluation)
Note: Approximate event times are listed below from insertion of RT-1.
1 min - 1 SAC auto starts.
1 min 30 sec - 1 SAC trips.
3 min 50 sec - 2 ECAC begins loading.
4 min 10 sec - 28 Control Air header pressure reaches 80 PSIG, and SA low pressure alarm.
4 min 25 sec - CA low pressure alarm.
6.5 min 24BF19 Feed Reg Valves begin           '
closing.
7 min 10 sec - G-15 OHA ADFCS TRBL.
AB.CA    INITIATE Attachment 1, Continuous            Initiates Attachment 1, Continuous Action 3.1      Action Summary.                              Summary.
Cue IF Required: If CAS Step 8.0 action is being taken to refer to Attachment 2 for valve fail positions and for further action to be taken, then:
Cue: The CRS will refer to Attachment 2 3.2      EITHER of the following conditions exist?    Determines all SAC's are stopped or
* ALL Station Air Compressors            determines Station Air Header pressure is stopped                              <100 psig.
* EITHER Station Air Header <100 psig PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 5of13
 
OPERATOR TRAINING PROGRAM                          NAME:
                                                                                                                    ---------
JOB PERFORMANCE MEASURE                            DATE: - - - - - - - - -
SYSTEM:   Loss of Control Air TASK:     TCAF a Loss of Control Air STEP                                                                                   COMMENTS STEP
(* Denotes a Critical Step)                                                           EVAL    (Required for UNSAT
* NO.                                                                  STANDARD S/U        evaluation) 3.3    lE a loss of 1 F Group Bus has occurred,     Determines a loss of 1F Group Bus has not AND 1H Group Bus is available, THEN         occurred.
SEND an Operator to restore power to #1 SAC Auxiliary Oil pump by transferring 11 Turbine West 230V Control Center IAW Attachment 14, Section 1.0.
3.4    IF a loss of 2F Group Bus has occurred,     Determines a loss of 2F Group Bus has not AND 2H Group Bus is available,               occurred.
THEN SEND an Operator to restore power to #2 SAC Auxiliary Oil pump by                                                             i transferring 21 Turbine West 230V Control Center IAW Attachment 14, Section 2.0.
3.5    lE a loss of 1H Group Bus has occurred,     Determines a loss of 1H Group Bus has not AND 1F Group Bus is available,               occurred.
THEN SEND an Operator to restore power to #3 SAC Auxiliary Oil pump by transferring 11 Turbine East 230V Control Center IAW Attachment 14, Section 3.0.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 6of13
 
OPERATOR TRAINING PROGRAM                         NAME:
                                                                                                                    ---------
JOB PERFORMANCE MEASURE                           DATE: - - - - - - - - -
SYSTEM:      Loss of Control Air TASK"        TCAF a Loss of Control Air STEP                                                                                  COMMENTS STEP
(*Denotes a Critical Step)                                                            EVAL    (Required for UNSAT
* NO.                                                                      STANDARD evaluation)
S/U 3.6      START or have Unit One Control Room          Determines no SAC's are available.
START Next to Load Station Air Compressor.                                  Cue if required: If Unit 1 is contacted, report that #3 Station Air Compressor is tagged out and #1 Station Air Compressor has tripped, and that an operator has been dispatched to the Station Air Compressors.
3.7      Either Station Air Header indicating less    Determines both Station Air Headers are than100 psig?                                indicating less than 100 psig.
3.8      Attempt to START, or have Unit One           Determines no SAC's can be started.
Control Room START, remaining Station Air Compressor.
3.9      NOTIFY the CRS/SM to evaluate use of        Cue: CRS will evaluate use of temporary air temporary air compressors.                  compressors.
3.10/3.11    2A Control Air Header less than or equal     Determines 2A control air header pressure is:
to 88 psig?                                 less than or equal to 88 psig and determines
                                                              #2 ECAC is in service OR
                                                              >88 psig.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 7 of 13
 
OPERATOR TRAINING PROGRAM                          NAME: - - - - - - - - -
JOB PERFORMANCE MEASURE                            DATE: - - - - - - - - -
SYSTEM:       Loss of Control Air TASK
  -         TCAF a Loss of Control Air STEP                                                                                    COMMENTS STEP                                                                                                              (Required for UNSAT
(*Denotes a Critical Step)                                                             EVAL
* NO.                                                                       STANDARD S/U        evaluation) 3.12/3.13   2B Control Air Header less than or equal     Determines 2B control air header pressure is:
to 88 psig?
less than or equal to 88 psig and contacts Unit 1 to place #1 ECAC in service OR
                                                                >88 psig.
Cue: When Unit 1 is contacted to start #1 ECAC, state: " # 1 ECAC has tripped. "
3.14      SEND operators to:                           Dispatches operators to:
* LOCATE AND ISOLATE ANY air
* LOCATE AND ISOLATE ANY air
* LOCATE AND ISOLATE any air system leaks. system leaks.
* LOCATE AND ISOLATE any air system leaks.                                 system leaks.
* INVESTIGATE cause of ANY air
* INVESTIGATE cause of ANY air
* INVESTIGATE cause of air compressor trip/trouble.
* INVESTIGATE cause of air compressor trip/trouble.                       compressor trip/trouble.
compressor trip/trouble.
3.15      IF Station Air is lost, AND EITHER of the     Determines Station Air is lost, and neither of following are in service:                     the following are in service:
IF Station Air is lost, AND EITHER of the Determines Station Air is lost, and neither of following are in service: the following are in service:
* Spent Fuel Pool Transfer Pool
* Spent Fuel Pool Transfer Pool
* Spent Fuel Pool Transfer Pool Weir Weir Gate Seals Gate Seals
* Spent Fuel Pool Transfer Pool Weir Weir Gate Seals                               Gate Seals
* SG Nozzle Dams
* SG Nozzle Dams
* SG Nozzle Dams THEN: A. EVACUATE personnel from areas subject to leakage/flooding.
* SG Nozzle Dams THEN:
B. INITIATE monitoring of Fuel Pool or Reactor Vessel levels for the need to makeup due to leakage. PSEG Restricted  
A. EVACUATE personnel from areas subject to leakage/flooding.
-Possession Requires Specific Permission from Nuclear Training Page 8 of 13 ------------------COMMENTS (Required for UNSAT evaluation)
B. INITIATE monitoring of Fuel Pool or Reactor Vessel levels for the need to makeup due to leakage.
SYSTEM: TASK: STEP
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 8 of 13
* NO. 3.16 3.17 3.18 3.19 3.57
 
* 3.58 Loss of Control Air TCAF a Loss of Control Air STEP (*Denotes a Critical Step) !E cooling water to the Station or Emergency Air Compressors is lost, THEN INITIATE the applicable portion of Attachment
OPERATOR TRAINING PROGRAM                        NAME: - - - - - - - - -
: 6. BOTH 2A and 2B Control Air Headers less than 80 psig? ANY Excess Flow Check Valve closed as indicated by at least one of the following? (Attachment 5, Excess Flow Check Valve Table) [INPO IER L2 15-16]
JOB PERFORMANCE MEASURE                          DATE: - - - - - - - - -
SYSTEM:   Loss of Control Air TASK:      TCAF a Loss of Control Air STEP                                                                                   COMMENTS STEP
(*Denotes a Critical Step)                                                           EVAL    (Required for UNSAT
* NO.                                                                      STANDARD S/U        evaluation) 3.16      !E cooling water to the Station or            Determines cooling water to the Station or Emergency Air Compressors is lost,             Emergency Air Compressors is not lost.
THEN INITIATE the applicable portion of Attachment 6.
3.17      BOTH 2A and 2B Control Air Headers             Determines both 2A and 2B Control Air less than 80 psig?                             Headers are not <80 psig.
3.18      ANY Excess Flow Check Valve closed as indicated by at least one of the following?
(Attachment 5, Excess Flow Check Valve        Determines NO Excess Flow Check Valve Table) [INPO IER L2 15-16]                     closed.
* Groups of valves repositioning with normal air pressure indicated in Control Room
* Groups of valves repositioning with normal air pressure indicated in Control Room
* Local observation of low pressure downstream of an Excess Flow Check Valve 2B Control Air Header less than 80 psig? CONTINUE CLOSE the following valves: A. 2CV3, LTDWN ORIFICE !SOL VALVE B. 2CV4, LTDWN ORIFICE !SOL VALVE C. 2CV5, LTDWN ORIFICE ISOL VALVE D. 2CV2 LETDOWN LINE !SOL VALVE E. 2CV277 LTDWN LINE !SOL VALVE F. 2CV7 LTDWN HX INLET VALVE OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STANDARD Determines cooling water to the Station or Emergency Air Compressors is not lost. Determines both 2A and 2B Control Air Headers are not <80 psig. Determines NO Excess Flow Check Valve closed. Determines 28 Control Air Header is <80 psig. Alternate Path actions start here. Closes the following valves: A. 2CV3, L TOWN ORIFICE !SOL VALVE B. 2CV4, LTDWN ORIFICE !SOL VALVE C. 2CV5, LTDWN ORIFICE !SOL VALVE D. 2CV2 LETDOWN LINE !SOL VALVE E. 2CV277 LTDWN LINE ISOL VALVE F. 2CV7 LTDWN HX INLET VALVE NAME: DATE: EVAL S/U PSEG Restricted  
* Local observation of low pressure downstream of an Excess Flow Check Valve 3.19      2B Control Air Header less than 80 psig?       Determines 28 Control Air Header is <80 psig.
-Possession Requires Specific Permission from Nuclear Training Page 9of13 ------------------COMMENTS (Required for UNSAT evaluation)
Alternate Path actions start here.
SYSTEM: TASK: STEP
3.57      CONTINUE
* NO. 3.57
* 3.58      CLOSE the following valves:                   Closes the following valves:
* CAS 6.0
A. 2CV3, LTDWN ORIFICE !SOL VALVE             A. 2CV3, LTOWN ORIFICE !SOL VALVE B. 2CV4, LTDWN ORIFICE !SOL VALVE               B. 2CV4, LTDWN ORIFICE !SOL VALVE C. 2CV5, LTDWN ORIFICE ISOL VALVE               C. 2CV5, LTDWN ORIFICE !SOL VALVE D. 2CV2 LETDOWN LINE !SOL VALVE                 D. 2CV2 LETDOWN LINE !SOL VALVE E. 2CV277 LTDWN LINE !SOL VALVE                  E. 2CV277 LTDWN LINE ISOL VALVE F. 2CV7 LTDWN HX INLET VALVE                     F. 2CV7 LTDWN HX INLET VALVE PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 9of13
* Loss of Control Air TCAF a Loss of Control Air STEP (*Denotes a Critical Step) VERIFY ANY Liquid or Gaseous release is stopped by ensuring the following valves CLOSED:
 
* 2WL51, TO CIRC WTR DISCHARGE
OPERATOR TRAINING PROGRAM                          NAME:
* 2WG41, GAS DECAY TK TO PLANT VENT IF AT ANY TIME Station Air is lost, THEN:
                                                                                                                    ---------
* INITIATE monitoring of 21-24BF19 SG FW CONT VALVE, operation.  
JOB PERFORMANCE MEASURE                            DATE:
* !E ANY BF19 SG FW CONT VALVE closes AND Applicable SG water level CANNOT be maintained, THEN: A. TRIP the Reactor B. CONTINUE with this procedure C. GO TO 2-EOP-TRIP-1, Reactor Trip Or Safety Injection.
                                                                                                                    ---------
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STANDARD Determines 2WG41, GAS DECAY TK TO PLANT VENT is open, and shuts 2WG41, GAS DECAY TK TO PLANT VENT. Verifies 2WL51 is shut. Identifies all BF19 valves closing. Trips the Reactor. NAME: DATE: EVAL S/U PSEG Restricted  
SYSTEM:     Loss of Control Air TASK:      TCAF a Loss of Control Air STEP                                                                                 COMMENTS STEP
-Possession Requires Specific Permission from Nuclear Training Page 10of13 ------------------COMMENTS (Required for UNSAT evaluation)
(*Denotes a Critical Step)                                                             EVAL    (Required for UNSAT
SYSTEM: TASK STEP
* NO.                                                                      STANDARD S/U        evaluation) 3.57    VERIFY ANY Liquid or Gaseous release         Determines 2WG41, GAS DECAY TK TO
* NO. TRIP-1 Loss of Control Air TCAF a Loss of Control Air STEP (* Denotes a Critical Step) OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STANDARD Performs Immediate Actions of EOP-TRIP-1:
* is stopped by ensuring the following         PLANT VENT is open, and shuts 2WG41, valves CLOSED:                               GAS DECAY TK TO PLANT VENT.
* 2WL51, TO CIRC WTR DISCHARGE                           Verifies 2WL51 is shut.
* 2WG41,   GAS DECAY TK TO PLANT VENT CAS      IF AT ANY TIME Station Air is lost, 6.0      THEN:
* INITIATE monitoring of 21-           Identifies all BF19 valves closing.
24BF19 SG FW CONT VALVE,
* operation.                          Trips the Reactor.
                    * !E ANY BF19 SG FW CONT VALVE closes AND Applicable SG water level CANNOT be maintained, THEN:
A. TRIP the Reactor B. CONTINUE with this procedure C. GO TO 2-EOP-TRIP-1, Reactor Trip Or Safety Injection.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 10of13
 
OPERATOR TRAINING PROGRAM                          NAME:
                                                                                                                ---------
JOB PERFORMANCE MEASURE                            DATE: - - - - - - - - -
SYSTEM:     Loss of Control Air TASK        TCAF a Loss of Control Air STEP                                                                                   COMMENTS STEP                                                                                                        (Required for UNSAT
(* Denotes a Critical Step)                                                         EVAL
* NO.                                                                STANDARD S/U        evaluation)
TRIP-1                                              Performs Immediate Actions of EOP-TRIP-1:
Confirms the Rx trip Trips the Main turbine Checks at least 1 4KV vital bus energized Determines SI is not initiated or required.
Confirms the Rx trip Trips the Main turbine Checks at least 1 4KV vital bus energized Determines SI is not initiated or required.
Cue after Immediate Actions have been performed:
Cue after Immediate Actions have been performed: The CRS and another operator will continue performing the EOPs. You are to continue in current procedure.
The CRS and another operator will continue performing the EOPs. You are to continue in current procedure.
Terminate JPM once Rx has been tripped, letdown isolated, and the WG release terminated.
Terminate JPM once Rx has been tripped, letdown isolated, and the WG release terminated.
NAME: DATE: EVAL S/U PSEG Restricted  
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 11 of 13
-Possession Requires Specific Permission from Nuclear Training Page 11 of 13 ------------------COMMENTS (Required for UNSAT evaluation)
 
JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation.
JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below.
Prior to JPM usage, revalidate JPM using steps 8 and 11 below. /
/ ~tut]        Task description and number, JPM description and number are identified.
Task description and number, JPM description and number are identified.  
/   )--   ~-Knowledge and Abilities (KIA) references are included.
/ )--
I   ~- Performance location specified. (in-plant, control room, or simulator)
and Abilities (KIA) references are included.
/ G~. Initial setup conditions are identified.
I Performance location specified. (in-plant, control room, or simulator)  
I             . Initiating and terminating Cues are properly identified.
/ Initial setup conditions are identified.
/ M.           Task standards identified and verified by SME review.
I . Initiating and terminating Cues are properly identified.  
0 ~- Critical steps meet the criteria for critical steps and are identified with an asterisk(*).
/ M. Task standards identified and verified by SME review. 0 Critical steps meet the criteria for critical steps and are identified with an asterisk(*).  
  }-Lil. 8. Verify the procedure referenced 2rs JPM mate es th                 most current revision of that procedure: Procedure Rev.                 Date   "'l--, _
}-Lil. 8. Verify the procedure referenced 2 rs JPM mate es th most current revision of that procedure:
  '(s:\J./!'g_ Pilot test the JPM:
Procedure Rev. Date "'l--,_ '(s:\J./!'g_
: a. verify Cues both verbal and visual are free of conflict, and
Pilot test the JPM: a. verify Cues both verbal and visual are free of conflict, and b. ensure performance time is accurate.
: b. ensure performance time is accurate.
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. --SME/lnstructor:
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM.
____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.
                                                        --
SME/lnstructor: __~_~L....,.......,_v_~~.r~~~----'P.+--=-,.cAr----
__
__
__
SME/lnstructor:~A~~-"'-~~~-~-~_u_ss-_*_t_l_ _
_t_l __ SME/lnstructor:
SME/lnstructor:                                                     Date: - - - - - -
Date: --------------
                    --------------
------PSEG Restricted  
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 12 of 13
-Possession Requires Specific Permission from Nuclear Training Page 12 of 13 INITIAL CONDITIONS:
 
INITIAL CONDITIONS:
* Unit 2 is operating at 100% power.
* Unit 2 is operating at 100% power.
* A WG release is in progress from 21 GOT. * #3 SAC is CIT for scheduled maintenance.
* A WG release is in progress from 21 GOT.
* Unit 1 is operating at 100% power. INITIATING CUE: You are the Unit 2 Reactor Operator.
    * #3 SAC is CIT for scheduled maintenance.
Respond to all indications and alarms. PSEG Restricted  
* Unit 1 is operating at 100% power.
-Possession Requires Specific Permission from Nuclear Training Page 13 of 13 STATION: SYSTEM: TASK: TASK NUMBER: JPM NUMBER: SALEM OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE Pressurizer/Pressure Relief Transfer Pressurizer 22 Backup Heaters to Emergency Power Supply 115 043 05 01 15-01 NRC Annual IP-i KIA NUMBER: 010 A4.02 ALTERNATE PATH: D IMPORTANCE FACTOR: 3.6 APPLICABILITY:
INITIATING CUE:
RO EOCJ RO[D STAC] SRO[D EVALUATION SETTING/METHOD:
You are the Unit 2 Reactor Operator. Respond to all indications and alarms.
In Plant, Simulate  
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 13 of 13
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION:              SALEM SYSTEM:              Pressurizer/Pressure Relief TASK:                Transfer Pressurizer 22 Backup Heaters to Emergency Power Supply TASK NUMBER:          115 043 05 01 JPM NUMBER:          15-01 NRC Annual IP-i ALTERNATE PATH:      D                                  KIA NUMBER:         010 A4.02
                                                                      ~~~~~~~~---!
IMPORTANCE FACTOR:           3.6           3.4 APPLICABILITY:                                                           RO           SRO EOCJ         RO[D           STAC]           SRO[D EVALUATION SETTING/METHOD:           In Plant, Simulate


==REFERENCES:==
==REFERENCES:==
S2.0P-SO.PZR-0010 Rev. 10 (Rev. checked 8-5-16)
TOOLS AND EQUIPMENT:        None VALIDATED JPM COMPLETION TIME:                  20 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS:                    N/A Developed By:                  G Gauding                        Date:  8-5-16 Instructor Validated By:              S Bickhart I J Hancock              Date:  9-30-16 SME or  lnstruc~:{~
10~0~<..,
Tr~rtment Approved By:                                                    Date:
Jo/10/1t.~
Approved By:
Ope~ons Dep~1ent                        Date:
ACTUAL JPM COMPLETION TIME:
ACTUAL TIME CRITICAL COMPLETION TIME:
PERFORMED BY:
GRADE:    D  SAT    D  UNSAT REASON, IF UNSATISFACTORY:
EVALUATOR'S SIGNATURE:                                                  DATE:
Page 1of6


S2.0P-SO.PZR-0010 Rev. 10 (Rev. checked 8-5-16) TOOLS AND EQUIPMENT:
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM:             Pressurizer/Pressure Relief TASK:               Transfer Pressurizer 22 Backup Heaters to Emergency Power Supply TASK                 1150430501 NUMBER:
None VALIDATED JPM COMPLETION TIME: 20 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: Developed By: Validated By: Approved By: Approved By: G Gauding Instructor S Bickhart I J Hancock SME or ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY:
INITIAL CONDITIONS:
EVALUATOR'S SIGNATURE:
Due to a loss of power to the group buses it is necessary to energize the PZR Backup Heaters from their emergency power supply.
Page 1of6 N/A Date: 8-5-16 Date: 9-30-16 Date:
INITIATING CUE:
Date:
The CRS directs you to perform S2.0P-SO.PZR-0010(Q), Section 5.3, Transferring Pzr Htr 22 BU Group To The Emergency Power Supply.
DATE: 3.4 SRO OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM: Pressurizer/Pressure Relief TASK: Transfer Pressurizer 22 Backup Heaters to Emergency Power Supply TASK 1150430501 NUMBER: INITIAL CONDITIONS:
All prerequisites and Precautions and Limitations have been reviewed and completed.
Due to a loss of power to the group buses it is necessary to energize the PZR Backup Heaters from their emergency power supply. INITIATING CUE: The CRS directs you to perform S2.0P-SO.PZR-0010(Q), Section 5.3, Transferring Pzr Htr 22 BU Group To The Emergency Power Supply. All prerequisites and Precautions and Limitations have been reviewed and completed.
2A EOG is carrying 2A Vital Bus and is loaded to 2400 KW.
2A EOG is carrying 2A Vital Bus and is loaded to 2400 KW. You have a JAM key. Successful Completion Criteria:
You have a JAM key.
Successful Completion Criteria:
: 1. All critical steps completed.
: 1. All critical steps completed.
: 2. All sequential steps completed in order. 3. All time-critical steps completed within allotted time. 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made (and NRC concurrence is obtained).
: 2. All sequential steps completed in order.
: 3. All time-critical steps completed within allotted time.
: 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made (and NRC concurrence is obtained).
Task Standard for Successful Completion:
Task Standard for Successful Completion:
: 1. Simulate opening all but three PZR heater disconnects.
: 1. Simulate opening all but three PZR heater disconnects.
: 2. Simulate aligning emergency power to PZR heater bus from 2A vital bus. Page 2of6 PSEG Restricted  
: 2. Simulate aligning emergency power to PZR heater bus from 2A vital bus.
-Possession Requires Specific Permission from Nuclear Training OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM: Pressurizer/Pressure Relief TASK: Transfer 22 Backup Heaters to Emergency Power Supply STEP
Page 2of6 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
* STEP (*Denotes a Critical Step) NO. STANDARD Operator obtains procedure S2.0P-Provide marked up copy of S2.0P-SO.PZR-0010, Pressurizer Backup Heaters SO.PZR-0010, Pressurizer Backup Power Supply Transfer.
 
Heaters Power Supply Transfer 5.3.1 ENSURE 2AX1AX14X, 2EP Locates breaker 2AX1AX14X 2EP PRESSURIZER HEATER BUS FEED PRESSURIZER HEATER BUS FEED (EMERGENCY) is OPEN (84' Swgr Rm). (EMERGENCY) on 2A 460V Vital Bus, Elev. 84' Swgr Rm and determines current breaker position.
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE                                 NAME:~~~~~~~~~~
Cue: 2AX1AX14X Breaker indicates OPEN. 5.3.2 Request NCO to PERFORM the following:
SYSTEM: Pressurizer/Pressure Relief                                                                           DATE:~~~~~~~~~~
Locates nearest means of A. PLACE 22 Backup Group in communications and requests NCO to MANUAL. place 22 B/U Htrs in MANUAL and B. PRESS the 22 BACKUP OFF press the 22 BACKUP OFF pushbutton pushbutton.
TASK: Transfer 22 Backup Heaters to Emergency Power Supply STEP                                                                                 COMMENTS
* STEP             (*Denotes a Critical Step)                                                           EVAL  (Required for UNSAT NO.                                                                     STANDARD                         S/U    Evaluation)
Operator obtains procedure S2.0P-               Provide marked up copy of S2.0P-SO.PZR-0010, Pressurizer Backup Heaters         SO.PZR-0010, Pressurizer Backup Power Supply Transfer.                         Heaters Power Supply Transfer 5.3.1     ENSURE 2AX1AX14X, 2EP                           Locates breaker 2AX1AX14X 2EP PRESSURIZER HEATER BUS FEED                     PRESSURIZER HEATER BUS FEED (EMERGENCY) is OPEN (84' Swgr Rm).             (EMERGENCY) on 2A 460V Vital Bus, Elev. 84' Swgr Rm and determines current breaker position.
Cue: 2AX1AX14X Breaker indicates OPEN.
5.3.2     Request NCO to PERFORM the following:
Locates nearest means of A. PLACE 22 Backup Group in                 communications and requests NCO to MANUAL.                                 place 22 B/U Htrs in MANUAL and B. PRESS the 22 BACKUP OFF                 press the 22 BACKUP OFF pushbutton                               pushbutton.
Cue: NCO reports 22 B/U Htrs are in MANUAL and 22 BACKUP OFF pushbutton has been depressed.
Cue: NCO reports 22 B/U Htrs are in MANUAL and 22 BACKUP OFF pushbutton has been depressed.
* 5.3.3 ENSURE 2EX1 EP2EPX, 2EP 480V Locates 2EX1 EP2EPX, 2EP 480V PRESSURIZER HEATER BUS MAIN PRESSURIZER HEATER BUS MAIN BREAKER is OPEN (78' Electrical BREAKER on El. 78 Electrical Pen. Penetration).
* 5.3.3     ENSURE 2EX1 EP2EPX, 2EP 480V                   Locates 2EX1 EP2EPX, 2EP 480V PRESSURIZER HEATER BUS MAIN                     PRESSURIZER HEATER BUS MAIN BREAKER is OPEN (78' Electrical                 BREAKER on El. 78 Electrical Pen.
Cue: 2EX1EP2EPX, 2EP 480V PRESSURIZER HEATER BUS MAIN BREAKER is OPEN. Page 3of6 COMMENTS EVAL (Required for UNSAT S/U Evaluation)
Penetration).                                   Cue: 2EX1EP2EPX, 2EP 480V PRESSURIZER HEATER BUS MAIN BREAKER is OPEN.
PSEG Restricted  
Page 3of6 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
-Possession Requires Specific Permission from Nuclear Training OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM: Pressurizer/Pressure Relief TASK: Transfer 22 Backup Heaters to Emergency Power Supply STEP
 
* STEP (*Denotes a Critical Step) NO. STANDARD
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE                                 NAME: _ _ _ _ _ _ _ _ _~
* 5.3.4 REMOVE interlock key from breaker Describes turning key and removing 2EX1 EP2EPX. interlock key from breaker 2EX1 EP2EPX. Note: Tab must be pushed in to rotate key to allow its removal.
SYSTEM: Pressurizer/Pressure Relief                                                                             DATE:
* 5.3.5 PLACE any eleven of the following Operator locates individual heater disconnects in OFF (only three disconnects disconnects, places all but three are to remain ON) AND MARK the disconnects in OFF and notes remaining disconnects as N/A: disconnects left ON as N/A in procedure.
TASK: Transfer 22 Backup Heaters to Emergency Power Supply
* 5.3.6 PLACE, 2AX1AX14X-1, 2EP PZR HTR Operator locates 2AX1AX14X-1, 2EP BUS EMERGENCY FEED DISCONNECT PZR HTR BUS EMERGENCY FEED SWITCH, in the ON position (Elev 78' DISCONNECT SWITCH, and places it Electrical Penetration).
                                                                                                                      ----------
in the ON position (Elev 78' Electrical Penetration).
STEP                                                                                     COMMENTS
* 5.3.7 INSERT interlock key, AND UNLOCK Locates Corry Key Interlock on breaker 2AX1AX14X.
* STEP               (*Denotes a Critical Step)                                                             EVAL      (Required for UNSAT NO.                                                                       STANDARD                         S/U        Evaluation)
2AX1AX14X breaker, inserts and turns key. 5.3.8 NOTIFY NCO that PZR Htr 22 B/U Group Candidate makes report to the Control has been transferred to the emergency Room. power supply (2A 460V Vital Bus). Repeat back notification and state: JPM is comolete.
* 5.3.4     REMOVE interlock key from breaker                 Describes turning key and removing 2EX1 EP2EPX.                                     interlock key from breaker 2EX1 EP2EPX.
Page 4 of6 NAME: _________ DATE: ----------
Note: Tab must be pushed in to rotate key to allow its removal.
COMMENTS EVAL (Required for UNSAT S/U Evaluation)
* 5.3.5     PLACE any eleven of the following                 Operator locates individual heater disconnects in OFF (only three disconnects       disconnects, places all but three are to remain ON) AND MARK the                   disconnects in OFF and notes remaining disconnects as N/A:                     disconnects left ON as N/A in procedure.
PSEG Restricted  
* 5.3.6     PLACE, 2AX1AX14X-1, 2EP PZR HTR                   Operator locates 2AX1AX14X-1, 2EP BUS EMERGENCY FEED DISCONNECT                     PZR HTR BUS EMERGENCY FEED SWITCH, in the ON position (Elev 78'             DISCONNECT SWITCH, and places it Electrical Penetration).                         in the ON position (Elev 78' Electrical Penetration).
-Possession Requires Specific Permission from Nuclear Training
* 5.3.7     INSERT interlock key, AND UNLOCK                 Locates Corry Key Interlock on breaker 2AX1AX14X.                               2AX1AX14X breaker, inserts and turns key.
., OPERATIONS TRAINING PROGRAM JOB PERFORMANCE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation.
5.3.8     NOTIFY NCO that PZR Htr 22 B/U Group             Candidate makes report to the Control has been transferred to the emergency             Room.
Prior to JPM usage, revalidate JPM using steps 8 and 11 below. Task description and number, JPM description and number are identified.
power supply (2A 460V Vital Bus).                 Repeat back notification and state:
W 2. Knowledge and Abilities (KIA) references are included. Performance location specified. (in-plant, control room, or simulator) Initial setup conditions are identified. Initiating and terminating Cues are properly identified.
JPM is comolete.
J 16. Task standards identified and verified by SME review. Critical steps meet the criteria for critical steps and are identified with an asterisk(').
Page 4 of6 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
J..--4 8. Verify the procedure referenced by this JPM mat9hEis the most current revision of < that procedure:
 
Procedure Rev. __J.._ Date H L'11 S _); } 9. Pilot test the JPM: a. verify Cues both verbal and visual are free of conflict, and b. ensure performance time is accurate.
.,
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructor:  
OPERATIONS TRAINING PROGRAM JOB PERFORMANCE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below.
...
  ~1. Task description and number, JPM description and number are identified.
SME/lnstructor:  
W         2. Knowledge and Abilities (KIA) references are included.
-------------
  ~3. Performance location specified. (in-plant, control room, or simulator)
Date: '/Jo/1" Date: 'lf3v,h6 Date: ------
  ~4. Initial setup conditions are identified.
INITIAL CONDITIONS:
  ~5. Initiating and terminating Cues are properly identified.
OPERATIONS TRAINING PROGRAM JOB PERFORMANCE MEASURE Due to a loss of power to the group buses it is necessary to energize the PZR Backup Heaters from their emergency power supply. INITIATING CUE: The CRS directs you to perform S2.0P-SO.PZR-0010(Q), Section 5.3, Transferring Pzr Htr 22 BU Group To The Emergency Power Supply. All prerequisites and Precautions and Limitations have been reviewed and completed.
J 16. Task standards identified and verified by SME review.
2A EOG is carrying 2A Vital Bus and is loaded to 2400 KW. You have a JAM key. Page 6of6 PSEG Restricted  
  ~7. Critical steps meet the criteria for critical steps and are identified with an asterisk(').
-Possession Requires Specific Permission from Nuclear Training STATION: SYSTEM: TASK: TASK NUMBER: OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE: SALEM Auxiliary Feedwater Perform Auxiliary Feedwater Back Leakage Test N0610160204 JPM NUMBER: 15-01 NRC IP-j KIA NUMBER: 061 K1 .02 ALTERNATE PATH: I I IMPORTANCE FACTOR: 3.4 3.7 ----APPLICABILITY:
J..--4
RO SRO EOLJ RO[KJ STALJ SRO[KJ EVALUATION SETTING/METHOD:
        <    8. Verify the procedure referenced by this JPM mat9hEis the most current revision of that procedure: Procedure Rev. __J.._ Date H L'11     S
lnplant-Simulate  
_);   }   9. Pilot test the JPM:
: a. verify Cues both verbal and visual are free of conflict, and
: b. ensure performance time is accurate.
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM.
____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.
SME/lnstructor:   ~&..II ... ~                                Date:    '/Jo/1" SME/lnstruct~                  __..-1$fdt~~                    Date:    'lf3v,h6 SME/lnstructor:                                               Date: - - - - - -
                    -------------
 
OPERATIONS TRAINING PROGRAM JOB PERFORMANCE MEASURE INITIAL CONDITIONS:
Due to a loss of power to the group buses it is necessary to energize the PZR Backup Heaters from their emergency power supply.
INITIATING CUE:
The CRS directs you to perform S2.0P-SO.PZR-0010(Q), Section 5.3, Transferring Pzr Htr 22 BU Group To The Emergency Power Supply.
All prerequisites and Precautions and Limitations have been reviewed and completed.
2A EOG is carrying 2A Vital Bus and is loaded to 2400 KW.
You have a JAM key.
Page 6of6 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE:
STATION:                SALEM SYSTEM:                Auxiliary Feedwater TASK:
Perform Auxiliary Feedwater Back Leakage Test TASK NUMBER:            N0610160204 JPM NUMBER:             15-01 NRC IP-j ALTERNATE PATH:      I      I                            KIA NUMBER:           061 K1 .02
                                                                        ~----------.,
IMPORTANCE FACTOR:
                                                                        - -3.4--            3.7 APPLICABILITY:                                                               RO             SRO EOLJ           RO[KJ           STALJ           SRO[KJ EVALUATION SETTING/METHOD:               lnplant- Simulate


==REFERENCES:==
==REFERENCES:==
S1 .OP-PT.AF-0002, Rev. 7, Auxiliary Feedwater Backleakage (checked 8-5-16)
TOOLS AND EQUIPMENT:                Calculator VALIDATED JPM COMPLETION TIME:                    5 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS:                        NIA Developed By:                    G Gauding                          Date:  8-5-16 Instructor Validated By:                  S Bickhart I J Hancock              Date:  9-30-16 SME or Instructor Approved By:                  ~ Mvff(W\                            Date:  tojof  0 Training~partment Approved By:                                                        Date: /ofcf~
Opebrtment ACTUAL JPM COMPLETION TIME:
ACTUAL TIME CRITICAL COMPLETION TIME:
PERFORMED BY:
GRADE:    D  SAT      D UNSAT REASON, IF UNSATISFACTORY:
EVALUATOR'S SIGNATURE:                                                    DATE:
Page 1 of 8 PSEG Restricted-Possession Requires Specific Permission from Nuclear Training


S1 .OP-PT.AF-0002, Rev. 7, Auxiliary Feedwater Backleakage (checked 8-5-16) TOOLS AND EQUIPMENT:
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE:
Calculator VALIDATED JPM COMPLETION TIME: 5 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: Developed By: Validated By: Approved By: Approved By: G Gauding Instructor S Bickhart I J Hancock SME or Instructor Mvff(W\
NAME: ~~~~~~~~~~~~~~
Opebrtment ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY:
DATE: ~~~~~~~~~~~~~~
EVALUATOR'S SIGNATURE:
SYSTEM:               Auxiliary Feedwater System TASK:                 Perform Auxiliary Feedwater Back Leakage Test TASK NUMBER:           N0610160204 INITIAL CONDITIONS:
Page 1 of 8 NIA Date: 8-5-16 Date: 9-30-16 Date: tojof 0 Date:
Unit 1 is operating at 100% power. 11 AFW pump was secured 30 minutes ago after its normally scheduled quarterly surveillance run.
DATE: PSEG Restricted-Possession Requires Specific Permission from Nuclear Training OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE: NAME:
INITIATING CUE:
DATE:
You are directed to perform S1 .OP-PT.AF-0002, Auxiliary Feedwater Backleakage.
SYSTEM: Auxiliary Feedwater System TASK: Perform Auxiliary Feedwater Back Leakage Test TASK NUMBER: N0610160204 INITIAL CONDITIONS:
Unit 1 is operating at 100% power. 11 AFW pump was secured 30 minutes ago after its normally scheduled quarterly surveillance run. INITIATING CUE: You are directed to perform S1 .OP-PT.AF-0002, Auxiliary Feedwater Backleakage.
Successful Completion Criteria:
Successful Completion Criteria:
: 1. All critical steps completed.
: 1. All critical steps completed.
: 2. All sequential steps completed in order. 3. All time-critical steps completed within allotted time. 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made. Task Standard for Successful Completion:
: 2. All sequential steps completed in order.
: 1. Determine 11 AFW pump and piping requires venting. 2. Vents 11 AFW pump and piping. Page 2 of 8 PSEG Restricted-Possession Requires Specific Permission from Nuclear Training SYSTEM: AFW OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: DATE: TASK Perform Auxiliary Feedwater Back Leakaae Test * * * *
: 3. All time-critical steps completed within allotted time.
* STEP NO. 5.1.1 5.1.2 STEP (*Denotes a Critical Step) Provide operator with blank copy of S1 PT.AF-0002, Rev. 7, and a calculator.
: 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made.
RECORD following on Attachment 1, Section 1.0:
Task Standard for Successful Completion:
* AFW Line Temperatures (1TA165551)
: 1. Determine 11 AFW pump and piping requires venting.
* Highest line temperature
: 2. Vents 11 AFW pump and piping.
* Average line temperature
Page 2 of 8 PSEG Restricted-Possession Requires Specific Permission from Nuclear Training
* Temperature difference IF temperature in each line is <120&deg;F, AND temperature difference between highest and average line temp is .:::_10&deg;F, THEN RECORD Test Results in Attachment 1, Section 5.0. STANDARD Reviews and initial all Prerequisites and Precautions and Limitations.
 
After locating 1TA165551, provide the following AFW line temperatures:
                                                                                                                                      "'
11-104 12-106 13-161 14-108 On Attachment 1, records AFW temperatures, calculates total of 479, divides that by 4 and determines highest line temp is 161 and average line temp is 119. 75. Determines Temp Diff 161-119.75 = 41.25. Determines highest temp is >120&deg;F Page 3 of 8 EVAL S/U PSEG Restricted-Possession Requires Specific Permission from Nuclear Training "'
OPERATOR TRAINING PROGRAM                       NAME: ~~~~~~~~~-
COMMENTS (Required for UNSAT evaluation)
JOB PERFORMANCE MEASURE                         DATE: ~~~~~~~~~-
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM: AFW TASK *
SYSTEM:   AFW TASK       Perform Auxiliary Feedwater Back Leakaae Test STEP                                                                           COMMENTS STEP
* Perform Auxiliarv Feedwater Back Leakaae Test STEP NO. 5.1.3 5.1.4 STEP (*Denotes a Critical Step) IF temperature in any line is .'.:'._120&deg;F AND <160&deg;F, THEN: A. RECORD Auxiliary Feedwater System piping temperatures every hour in Control Room Narrative Log. B. RECORD Test Results in Attachment 1, Section 5.0. IF temperature difference between highest and average line temp is >10&deg;F, THEN RECORD Test Results in Attachment 1, Section 5.0. 5.1.6 I IF temperature in any line is .'.::160&deg;F THEN: A. RECORD findings in Control Room Narrative Log. B. VENT Auxiliary Feedwater pumps/piping IAW Section 5.2. STANDARD Determines highest temp is >160&deg;F Determines temperature difference between highest and average line temp is >10&deg;F, and records Test Results in Attachment 1, Section 5.0., as UNSAT for all three categories.
(*Denotes a Critical Step)                                                     EVAL  (Required for UNSAT
Page 4 of 8 NAME: DATE: EVAL S/U PSEG Restricted-Possession Requires Specific Permission from Nuclear Training COMMENTS (Required for UNSAT evaluation)
* NO.                                                                      STANDARD S/U      evaluation)
SYSTEM: AFW OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: DATE: TASK: Perform Auxiliarv Feedwater B -------T STEP STEP
Provide operator with blank copy of S1 .OP-    Reviews and initial all Prerequisites PT.AF-0002, Rev. 7, and a calculator.          and Precautions and Limitations.
* NO. (*Denotes a Critical Step) STANDARD EVAL S/U
5.1.1      RECORD following on Attachment 1, Section 1.0:                                           After locating 1TA165551, provide
* 5.2.1 IF 11 Auxiliary Feedwater Pump and piping is affected, THEN: A. SLOWLY THROTTLE OPEN 11AF83, AF Locates and opens 11 AF83, AF PUMP VENT, until a solid stream of water is PUMP VENT, until a solid stream of observed.
* AFW Line Temperatures (1TA165551)       the following AFW line
water is observed.
* Highest line temperature                 temperatures:
11-104
* Average line temperature 12- 106
* Temperature difference                   13- 161 14- 108
* On Attachment 1, records AFW temperatures, calculates total of 479,
* divides that by 4 and determines
* highest line temp is 161 and average line temp is 119. 75.
* Determines Temp Diff 161- 119.75     =
41.25.
5.1.2      IF temperature in each line is <120&deg;F, AND temperature difference between highest      Determines highest temp is >120&deg;F and average line temp is .:::_10&deg;F, THEN RECORD Test Results in Attachment 1, Section 5.0.
Page 3 of 8 PSEG Restricted-Possession Requires Specific Permission from Nuclear Training
 
OPERATOR TRAINING PROGRAM                     NAME: ~~~~~~~~~-
JOB PERFORMANCE MEASURE                       DATE: ~~~~~~~~~-
SYSTEM:   AFW TASK       Perform Auxiliarv Feedwater Back Leakaae Test STEP                                                                             COMMENTS STEP
(*Denotes a Critical Step)                                                     EVAL  (Required for UNSAT
* NO.                                                                        STANDARD S/U      evaluation) 5.1.3      IF temperature in any line is .'.:'._120&deg;F AND <160&deg;F, THEN:                                 Determines highest temp is >160&deg;F A. RECORD Auxiliary Feedwater System piping temperatures every hour in Control Room Narrative Log.
B. RECORD Test Results in Attachment 1, Section 5.0.
5.1.4      IF temperature difference between highest and average line temp is >10&deg;F, THEN               Determines temperature difference RECORD Test Results in Attachment 1,               between highest and average line
* Section 5.0.                                       temp is >10&deg;F, and records Test Results in Attachment 1, Section 5.0.,
as UNSAT for all three categories.
5.1.6   I IF temperature in any line is .'.::160&deg;F THEN:
A. RECORD findings in Control Room Narrative Log.
B. VENT Auxiliary Feedwater pumps/piping IAW Section 5.2.
Page 4 of 8 PSEG Restricted-Possession Requires Specific Permission from Nuclear Training
 
:'
OPERATOR TRAINING PROGRAM                         NAME: ~~~~~~~~~-
JOB PERFORMANCE MEASURE                           DATE: ~~~~~~~~~-
SYSTEM:   AFW TASK:     Perform Auxiliarv Feedwater B --
                                        -       --- - T STEP                                                                           COMMENTS STEP
(*Denotes a Critical Step)                                                     EVAL  (Required for UNSAT
* NO.                                                                    STANDARD S/U       evaluation)
* 5.2.1     IF 11 Auxiliary Feedwater Pump and piping is affected, THEN:
A. SLOWLY THROTTLE OPEN 11AF83, AF             Locates and opens 11 AF83, AF PUMP VENT, until a solid stream of water is   PUMP VENT, until a solid stream of observed.                                     water is observed.
Cue: A solid stream of water is observed.
Cue: A solid stream of water is observed.
B. CLOSE 11 AF83. Closes 11 AF83 C. SLOWLY THROTTLE OPEN 11AF114, Locates and opens 11 AF114, AF AF PUMP DISCH VENT, until a solid stream PUMP DISCH VENT, until a solid of water is observed.
B. CLOSE 11 AF83.                             Closes 11 AF83 Locates and opens 11 AF114, AF C. SLOWLY THROTTLE OPEN 11AF114, PUMP DISCH VENT, until a solid AF PUMP DISCH VENT, until a solid stream stream of water is observed.
stream of water is observed.
of water is observed.                         Cue: A solid stream of water is observed.
Cue: A solid stream of water is observed.
D. CLOSE 11AF114.                             Closes 11AF114.
D. CLOSE 11AF114. Closes 11AF114. Terminate JPM I Page 5 of 8 PSEG Restricted-Possession Requires Specific Permission from Nuclear Training :'
Terminate JPM I
COMMENTS (Required for UNSAT evaluation)
Page 5 of 8 PSEG Restricted-Possession Requires Specific Permission from Nuclear Training
This page intentionally blank. Page 6 of 8 JOB PERFORMANCE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation.
 
Prior to JPM usage, revalidate JPM using steps 8 and 11 below. Task description and number, JPM description and number are identified.
This page intentionally blank.
U 2. Knowledge and Abilities (KIA) references are included.
Page 6 of 8
V ;I-')I 3. Performance location specified. (in-plant, control room, or simulator)
 
V / 'S / 4_ Initial setup conditions are identified.  
JOB PERFORMANCE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below.
\/ er L2L5. Initiating and terminating Cues are properly identified.
    ~ ~1. Task description and number, JPM description and number are identified.
Task standards identified and verified by SME review. I> /7. Critical steps meet the criteria for critical steps and are identified with an asterisk n \!'-d 18. Verify the procedure referenced by this JPM maJchfs the most current rev1s1on of that procedure:
U~ 2. Knowledge and Abilities (KIA) references are included.
Procedure Rev. :f-Date /,ffJ{-fJ. 9. Pilot test the JPM: a. verify Cues both verbal and visual are free of conflict, and b. ensure performance time is accurate.
V ;I- ')I 3. Performance location specified. (in-plant, control room, or simulator)
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructor:
V/         'S / 4_ Initial setup conditions are identified.
t-SME/lnstructor:  
  \/ erL2L5.         Initiating and terminating Cues are properly identified.
-------------
  \J'~/6. Task standards identified and verified by SME review.
Page 7 of 8 Date: 9/.Jo//h Date: co. Date: ------PSEG Restricted-Possession Requires Specific Permission from Nuclear Training JOB PERFORMANCE MEASURE INITIAL CONDITIONS:
I>               /7. Critical steps meet the criteria for critical steps and are identified with an asterisk n
Unit 1 is operating at 100% power. 11 AFW pump was secured 30 minutes ago after its normally scheduled quarterly surveillance run. INITIATING CUE: You are directed to perform S1 .OP-PT.AF-0002, Auxiliary Feedwater Backleakage.
\!'-   d         18. Verify the procedure referenced by this JPM maJchfs the most current rev1s1on of that procedure: Procedure Rev.     :f- Date /,ffJ{-fJ.
Page 8 of 8 PSEG Restricted-Possession Requires Specific Permission from Nuclear Training STATION: SYSTEM: ASK NUMBER: PM NUMBER: L TERNATE PATH: OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SALEM Emergency Diesel Generator Start and synchronize an Emergency Diesel Generator 113 0010501 15-01 NRC IP-k KIA NUMBER: 064 A2.09 D IMPORTANCE FACTOR: 3.1 3.3 ----PPLICABILITY:
        ~          9. Pilot test the JPM:
RO SRO EoD ROW STAD sRoW EVALUATION SETTING/METHOD:
: a. verify Cues both verbal and visual are free of conflict, and
In Plant I Simulate  
: b. ensure performance time is accurate.
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM.
____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.
SME/lnstructor:     ~~                                          Date:  9/.Jo//h SME/lnstructo~cft!Mll                          t-                 Date:    9/~ ~JI co.
SME/lnstructor:                                                  Date:
                          -------------                                         ------
Page 7 of 8 PSEG Restricted-Possession Requires Specific Permission from Nuclear Training
 
JOB PERFORMANCE MEASURE INITIAL CONDITIONS:
Unit 1 is operating at 100% power. 11 AFW pump was secured 30 minutes ago after its normally scheduled quarterly surveillance run.
INITIATING CUE:
You are directed to perform S1 .OP-PT.AF-0002, Auxiliary Feedwater Backleakage.
Page 8 of 8 PSEG Restricted-Possession Requires Specific Permission from Nuclear Training
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION:              SALEM SYSTEM:              Emergency Diesel Generator Start and synchronize an Emergency Diesel Generator ASK NUMBER:        113 0010501 PM NUMBER:          15-01 NRC IP-k L TERNATE PATH:    D                                      KIA NUMBER:
IMPORTANCE FACTOR:
064 A2.09
                                                                            ~----------!
3.1               3.3
                                                                            --     --
PPLICABILITY:                                                                   RO               SRO EoD         ROW             STAD             sRoW EVALUATION SETTING/METHOD:             In Plant I Simulate


==REFERENCES:==
==REFERENCES:==
2A Diesel Generator Operation, S2.0P-SO.DG-0001 (Q)Rev. 39 (checked 8-5-16)
OOLS AND EQUIPMENT:        None ALIDATED JPM COMPLETION TIME:                      20 min IME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS:                          N/A Developed By:                    G Gauding                          Date:    8-5-16 Instructor alidated By:                S Bickhart I J Hancock                Date:    9-30-16 pproved By:                                                        Date:    10/o/c...
pproved By:
CTUAL JPM COMPLETION TIME:
CTUAL TIME CRITICAL COMPLETION TIME:
PERFORMED BY:
GRADE:    DsAT      OuNSAT REASON, IF UNSATISFACTORY:
EVALUATOR'S SIGNATURE:                                                          DATE:
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 1 of 12


2A Diesel Generator Operation, S2.0P-SO.DG-0001 (Q)Rev. 39 (checked 8-5-16) OOLS AND EQUIPMENT:
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM:            EOG TASK:              Start and synchronize an Emergency Diesel Generator TASK                113 0010501 NUMBER:
None ALIDATED JPM COMPLETION TIME: 20 min IME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: Developed By: alidated By: pproved By: pproved By: G Gauding Instructor S Bickhart I J Hancock CTUAL JPM COMPLETION TIME: CTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: DsAT OuNSAT REASON, IF UNSATISFACTORY:
INITIAL                    Unit 2 is operating at 100% power, with no equipment OOS. Engineering has CONDITIONS:                requested a loaded run of 2A EOG.
EVALUATOR'S SIGNATURE:
INITIATING CUE:
N/A Date: 8-5-16 Date: 9-30-16 Date: 10/ o/c... DATE: PSEG Restricted -
The Unit 2 CRS has directed you to locally start and parallel load 2A DIG IAW S2.0P-SO.DG-0001 (Q), Section 5.2. & 5.4 Prerequisites, Precautions and Limitations, and Section 5.1, Diesel Generator Startup Checks have been performed.
Possession Requires Specific Permission from Nuclear Training Page 1 of 12 SYSTEM: TASK: TASK NUMBER: INITIAL CONDITIONS:
INITIATING CUE: EOG OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE Start and synchronize an Emergency Diesel Generator 113 0010501 Unit 2 is operating at 100% power, with no equipment OOS. Engineering has requested a loaded run of 2A EOG. The Unit 2 CRS has directed you to locally start and parallel load 2A DIG IAW S2.0P-SO.DG-0001 (Q), Section 5.2. & 5.4 Prerequisites, Precautions and Limitations, and Section 5.1, Diesel Generator Startup Checks have been performed.
Successful Completion Criteria:
Successful Completion Criteria:
: 1. All critical steps completed.
: 1. All critical steps completed.
: 2. All sequential steps completed in order. 3. All time-critical steps completed within allotted time. 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made (and NRC concurrence is obtained).
: 2. All sequential steps completed in order.
: 3. All time-critical steps completed within allotted time.
: 4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made (and NRC concurrence is obtained).
Task Standard for Successful Completion:
Task Standard for Successful Completion:
Perform S2.0P-SO.DG-0001 Sections 5.2 and 5.4 in correct order and to completion.
Perform S2.0P-SO.DG-0001 Sections 5.2 and 5.4 in correct order and to completion.
PSEG Restricted  
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 2 of 12
-Possession Requires Specific Permission from Nuclear Training Page 2 of 12 SYSTEM: TASK: *
 
* OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE Emergency Diesel Generator Locally start and load an Emergency Diesel Generator STEP NO. 5.2.1 5.2.2 5.2.3 5.2.4 STEP (*Denotes a Critical Step) STANDARD Provide marked up copy of S2.0P-SO.DG-0001 2A Diesel Generator Operation NOTIFY NCO that 2A Diesel Generator is Locates nearest page. to be locally started. Cue: NCO acknowledqes.
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM:  Emergency Diesel Generator                                                                     NAME:~~~~~~~~~~~~~
CHECK voltage permissive indicator light Points out voltage permissive indicator 2DAE4-L T2, EDG VOLT AGE, on light 2DAE4-L T2, EOG VOLTAGE, on Generator Control Panel is OFF Generator Control Panel. Cue: Liqht is off CHECK speed permissive indicator light Points out speed permissive indicator 2DAE4-L T3, EOG SPEED, on Generator light 2DAE4-L T3, EOG SPEED, on Control Panel is OFF. Generator Control Panel. Cue: Liqht is off !E 2A 4KV Vital Bus is currently energized, (Diesel Generator is to be parallel loaded), THEN: Points out 2A-DF-GCP-1, 2A DIESEL A. PLACE 2A-DF-GCP-1, 2A DIESEL GEN LOADING SW., and simulates GEN LOADING SW in MANUAL rotating to DROOP position. (DROOP). B. ENSURE B-9, GENERATOR LOADING Cue: Annunciator B-9, Generator IN DROOP MODE, is in alarm. loading in Droop Mode annunciates.
TASK:    Locally start and load an Emergency Diesel Generator                                           DATE:~~~~~~~~~~~~~
PSEG Restricted  
COMMENTS STEP                                                                       EVAL STEP                                                                          STANDARD                            (Required for UNSAT
-Possession Requires Specific Permission from Nuclear Training Page 3of12 EVAL COMMENTS S/U (Required for UNSAT Evaluation)
(*Denotes a Critical Step)                                                             S/U
SYSTEM: TASK: * *
* NO.                                                                                                                  Evaluation)
* I OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE Emergency Diesel Generator Locally start and load an Emergency Diesel Generator STEP NO. 5.2.5 5.2.6 5.2.7 STEP (*Denotes a Critical Step) STANDARD PLACE 2A-DF-SS, 2A DG STOP/START Points out 2A-DF-SS, 2A DG SWITCH in START. STOP/START SWITCH, and simulates placing in START. Cue: 2A Diesel is acceleratinq.  
Provide marked up copy of S2.0P-SO.DG-0001 2A Diesel Generator Operation 5.2.1        NOTIFY NCO that 2A Diesel Generator is           Locates nearest page.
!E Diesel Generator Speed is NOT 900 rpm, THEN SET speed to 900 rpm using Cue when Speed indicator is the SPEED CONTROL SWITCH (GS). checked: Speed is 880 rpm. Points out SPEED CONTROL SWITCH (GS) and simulates turning in RAISE direction.
to be locally started.
Cue: 2A Diesel Speed is 900 rpm. !E 2AD1AX6D*, 2A Diesel Generator 125VDC breaker is closed, THEN:
Cue: NCO acknowledqes.
* CHECK voltage permissive Points out voltage permissive indicator indicator light 2DAE4-L T2, EOG light 2DAE4-L T2, EOG VOLTAGE. VOLTAGE, on Generator Control Cue: Voltage permissive indicator light Panel is ON. 2DAE4-L T2, EOG VOLTAGE Light is on
5.2.2        CHECK voltage permissive indicator light         Points out voltage permissive indicator 2DAE4-LT2, EDG VOLT AGE, on                     light 2DAE4-LT2, EOG VOLTAGE, on Generator Control Panel is OFF                   Generator Control Panel.
* CHECK speed permissive indicator Points out speed permissive indicator light 2DAE4-L T3, EOG SPEED, on light 2DAE4-L T3, EOG SPEED Generator Control Panel is ON. Cue: Speed permissive indicator light 2DAE4-L T3, EOG SPEED light is on PSEG Restricted  
Cue: Liqht is off 5.2.3        CHECK speed permissive indicator light           Points out speed permissive indicator 2DAE4-LT3, EOG SPEED, on Generator               light 2DAE4-LT3, EOG SPEED, on Control Panel is OFF.                           Generator Control Panel.
-Possession Requires Specific Permission from Nuclear Training Page 4of12 EVAL COMMENTS S/U (Required for UNSAT Evaluation)
Cue: Liqht is off
SYSTEM: TASK:
* 5.2.4        !E 2A 4KV Vital   Bus is currently energized, (Diesel Generator is to be parallel loaded),
* OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: Emergency Diesel Generator Locally start and load an Emergency Diesel Generator STEP NO. 5.2.8 5.2.9 5.2.10 STEP (*Denotes a Critical Step) STANDARD IF Field Ground Relay 64/G white indicating light is OFF, AND C-6, GENERATOR FIELD GROUND, is clear, Points out Field Ground Relay 64/G THEN: white indicating light. A. RESET 64/G relay B. ENSURE 64/G white indicating Cue: Field Ground Relay 64/G white light is illuminated.
THEN:                                           Points out 2A-DF-GCP-1, 2A DIESEL A. PLACE 2A-DF-GCP-1, 2A DIESEL                 GEN LOADING SW., and simulates GEN LOADING SW in MANUAL                         rotating to DROOP position.
indicating light is illuminated.
(DROOP).
ENSURE 2A Diesel Generator K1 C Field Points out 2A Diesel Generator K1 C Flashing Relay Supervisory Light is OFF. Field Flashing Relay Supervisory Light Cue: 2A Diesel Generator K1 C Field Flashing Relay Supervisory Light is off. RECORD the following Diesel Generator Points out gages and switches to Start Readings:
B. ENSURE B-9, GENERATOR LOADING                 Cue: Annunciator B-9, Generator IN DROOP MODE, is in alarm.                     loading in Droop Mode annunciates.
determine readings.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 3of12
Cue when proper gauge is pointed out: 2VM189 Gen. Volts -4160 Volts on all 3 phases 2FM186 Gen. Frequency  
 
-60 Hz 2PL6429 LO Hdr. Press -80 psig 2PL6449 JW Hdr. Press -45 psig 2PL7209 Air Manifold Press -0 psig 2TA16524 Gen. Stator Temp -187&deg; PSEG Restricted  
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM:  Emergency Diesel Generator                                                                     NAME:~~~~~~~~~~~~
-Possession Requires Specific Permission from Nuclear Training Page 5of12 EVAL COMMENTS S/U (Required for UNSAT Evaluation)
TASK:    Locally start and load an Emergency Diesel Generator                                           DATE:~~~~~~~~~~~~
SYSTEM: TASK:
COMMENTS STEP                                                                     EVAL STEP                                                                         STANDARD                            (Required for UNSAT
* OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE Emergency Diesel Generator DATE: Locally start and load an Emergency Diesel Generator STEP NO. 5.2.11 5.2.12 5.4.1 5.4.2 5.4.3 STEP (*Denotes a Critical Step) STANDARD lE 2A Diesel Generator is to be operated Determines from initiating cue that 2A unloaded for an extended period of EOG is to be parallel loaded. time(>30 minutes), THEN INITIATE Section 5.7, Diesel Generator Running Checks. lE Diesel Generator is to be parallel Initiates Section 5.4, Diesel Generator loaded, THEN INITIATE Section 5.4, Parallel Loading. Diesel Generator Parallel Loading. lE Section 5.1 Diesel Generator Startup Verifies Section 5.1 is complete.
(*Denotes a Critical Step)                                                             S/U
Checks, was NOT performed, THEN at 2A DG 4KV cabinet cubicle breaker 2AD1AX60, PLACE selector switch 2A DG SYNC ENABLE in ENABLE. NOTIFY NCO that 2A EOG is to be Cue: NCO acknowledges 2A DG is to synchronized and loaded locally. be synchronized and loaded locally. ENSURE 2A-DF-GCP-1, 2A DIESEL GEN Verifies 2A-DF-GCP-1, 2A DIESEL LOADING SW, in MANUAL (DROOP) GEN LOADING SW, is in MANUAL (DROOP) PSEG Restricted  
* NO.                                                                                                                Evaluation)
-Possession Requires Specific Permission from Nuclear Training Page 6of12 EVAL COMMENTS S/U (Required for UNSAT Evaluation)
* 5.2.5      PLACE 2A-DF-SS, 2A DG STOP/START                 Points out 2A-DF-SS, 2A DG SWITCH in START.                                 STOP/START SWITCH, and simulates placing in START.
SYSTEM: TASK: *
Cue: 2A Diesel is acceleratinq.
* OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE Emergency Diesel Generator Locally start and load an Emergency Diesel Generator STEP NO. 5.4.4 5.4.5 5.4.6 STEP (*Denotes a Critical Step) STANDARD ADJUST 2A EOG output voltage, as indicated on VOLTMETER-GEN (2VM189) When operator points out 2VM189 to 50 -100 Volts higher than that of 2A and 2VM190, then Cue: 2VM189 reads 4KV Vital Bus voltage, as indicated by 4150, and 2VM190 reads 4150. VOLTMETER-BUS (2VM190), using the VOLTAGE CONTROL SWITCH (VCS). Points out VOLTAGE CONTROL SWITCH (VCS) and simulates going to RAISE. Cue: 2VM189 reads 4210, and 2VM190 reads 4150. ENSURE generator terminal voltage is Points out VOLTMETER SWITCH -present on all 3 phases by rotating GEN (VS-G), simulates rotating through VOLTMETER SWITCH -GEN (VS-G) each position, while observing 2VM189 through each position AND OBSERVING voltmeter 2VM189. Cue: Voltage is present on all three phases. ENSURE 2A 4KV Vital Bus voltage is Points out VOLTMETER SWITCH -present on all 3 phases by rotating BUS (VS-B), simulates rotating through VOLTMETER SWITCH -BUS (VS-B) each position, while observing 2VM190 through each position AND OBSERVING voltmeter 2VM190. Cue: Voltage is present on all three phases. PSEG Restricted  
* 5.2.6      !E Diesel Generator Speed is NOT 900 rpm, THEN SET speed to 900 rpm using             Cue when Speed indicator is the SPEED CONTROL SWITCH (GS).                   checked: Speed is 880 rpm.
-Possession Requires Specific Permission from Nuclear Training Page 7of12 EVAL COMMENTS S/U (Required for UNSAT Evaluation)
Points out SPEED CONTROL SWITCH (GS) and simulates turning in RAISE direction.
SYSTEM: TASK: *
Cue: 2A Diesel Speed is 900 rpm.
* OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: Emergency Diesel Generator Locally start and load an Emergency Diesel Generator DATE:
5.2.7      !E 2AD1AX6D*, 2A Diesel Generator 125VDC breaker is closed, THEN:
STEP NO. 5.4.7 5.4.8 5.4.9 5.4.10 5.4.10 A. STEP (*Denotes a Critical Step) STANDARD PLACE the following switches in "1-2": Points out VOLTMETER SWITCH -GEN (VS-G) and VOLTMETER
* CHECK voltage permissive                   Points out voltage permissive indicator indicator light 2DAE4-LT2, EOG         light 2DAE4-LT2, EOG VOLTAGE.
* VOLTMETER SWITCH -GEN SWITCH -BUS (VS-B) (VS-G)
VOLTAGE, on Generator Control           Cue: Voltage permissive indicator light Panel is ON.                           2DAE4-LT2, EOG VOLTAGE Light is on
* VOLTMETER SWITCH -BUS (VS-B) Cue: Switches are in 1-2. ENSURE 2DAE4-L T2, EOG Voltage Points out 2DAE4-L T2, EOG Voltage indication light is ON. indication light. Cue: 2DAE4-L T2, EOG Voltage indication liqht is on. ENSURE 2DAE4-L T3, EOG Speed Points out 2DAE4-L T3, EOG Speed indication light is ON. indication light. Cue: 2DAE4-L T2, EOG Voltage indication liaht is on. SYNCHRONIZE 2A Diesel Generator to 2A 4KV Vital Bus as follows: PLACE 2A-DF-SYNCH, 2A DG SYNC SWITCH (SS) to ON. Points out 2A-DF-SYNCH, 2A DG SYNC SWITCH (SS), and simulates placing in ON position.
* CHECK speed permissive indicator       Points out speed permissive indicator light 2DAE4-LT3, EOG SPEED, on         light 2DAE4-LT3, EOG SPEED Generator Control Panel is ON.         Cue: Speed permissive indicator light 2DAE4-LT3, EOG SPEED light is on I
PSEG Restricted  
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 4of12
-Possession Requires Specific Permission from Nuclear Training Page 8of12 EVAL COMMENTS S/U (Required for UNSAT Evaluation)
 
SYSTEM: TASK: *
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM: Emergency Diesel Generator                                                                     NAME:
* OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE Emergency Diesel Generator Locally start and load an Emergency Diesel Generator STEP NO. 5.4.10 B. 5.4.10 C. 5.4.10 D. 5.4.10 E. STEP (*Denotes a Critical Step) STANDARD ADJUST Diesel speed using the SPEED When operator points out CONTROL SWITCH (GS) such that synchroscope, then Cue: Scope is Synchroscope pointer rotates slowly in the going in the slow direction.
DATE:~~~~~~~~~~~~~
TASK:    Locally start and load an Emergency Diesel Generator COMMENTS STEP                                                                      EVAL STEP                                                                           STANDARD                            (Required for UNSAT
(*Denotes a Critical Step)                                                             S/U
* NO.                                                                                                                  Evaluation) 5.2.8      IF Field Ground Relay 64/G white indicating light is OFF, AND C-6, GENERATOR FIELD GROUND, is clear,                 Points out Field Ground Relay 64/G THEN:                                             white indicating light.
A. RESET 64/G relay B. ENSURE 64/G white indicating             Cue: Field Ground Relay 64/G white light is illuminated.                   indicating light is illuminated.
5.2.9        ENSURE 2A Diesel Generator K1 C Field             Points out 2A Diesel Generator K1 C Flashing Relay Supervisory Light is OFF.         Field Flashing Relay Supervisory Light Cue: 2A Diesel Generator K1 C Field Flashing Relay Supervisory Light is off.
5.2.10      RECORD the following Diesel Generator             Points out gages and switches to Start Readings:                                   determine readings.
Cue when proper gauge is pointed out:
2VM189 Gen. Volts - 4160 Volts on all 3 phases 2FM186 Gen. Frequency - 60 Hz 2PL6429 LO Hdr. Press - 80 psig 2PL6449 JW Hdr. Press - 45 psig 2PL7209 Air Manifold Press - 0 psig 2TA16524 Gen. Stator Temp - 187&deg; PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 5of12
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM:  Emergency Diesel Generator                                                                   NAME:~~~~~~~~~~~~~
TASK:   Locally start and load an Emergency Diesel Generator                                         DATE:  ~~~~~~~~~~~~~
COMMENTS STEP                                                                        EVAL STEP                                                                         STANDARD                            (Required for UNSAT
(*Denotes a Critical Step)                                                             S/U
* NO.                                                                                                                Evaluation) 5.2.11      lE 2A Diesel Generator is to be operated       Determines from initiating cue that 2A unloaded for an extended period of             EOG is to be parallel loaded.
time(>30 minutes), THEN INITIATE Section 5.7, Diesel Generator Running Checks.
5.2.12      lE Diesel Generator is to be parallel           Initiates Section 5.4, Diesel Generator loaded, THEN INITIATE Section 5.4,             Parallel Loading.
Diesel Generator Parallel Loading.
5.4.1      lE Section 5.1 Diesel Generator Startup         Verifies Section 5.1 is complete.
Checks, was NOT performed, THEN at 2A DG 4KV cabinet cubicle breaker 2AD1AX60, PLACE selector switch 2A DG SYNC ENABLE in ENABLE.
5.4.2      NOTIFY NCO that 2A EOG is to be                 Cue: NCO acknowledges 2A DG is to synchronized and loaded locally.               be synchronized and loaded locally.
5.4.3      ENSURE 2A-DF-GCP-1, 2A DIESEL GEN               Verifies 2A-DF-GCP-1, 2A DIESEL LOADING SW, in MANUAL (DROOP)                   GEN LOADING SW, is in MANUAL (DROOP)
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 6of12
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM: Emergency Diesel Generator                                                                   NAME:~~~~~~~~~~~~
TASK:  Locally start and load an Emergency Diesel Generator                                         DATE:~~~~~~~~~~~~-
COMMENTS STEP                                                                       EVAL STEP                                                                        STANDARD                            (Required for UNSAT
(*Denotes a Critical Step)                                                             S/U
* NO.                                                                                                                Evaluation)
* 5.4.4      ADJUST 2A EOG output voltage, as indicated on VOLTMETER-GEN (2VM189)             When operator points out 2VM189 to 50 - 100 Volts higher than that of 2A       and 2VM190, then Cue: 2VM189 reads 4KV Vital Bus voltage, as indicated by         4150, and 2VM190 reads 4150.
VOLTMETER-BUS (2VM190), using the VOLTAGE CONTROL SWITCH (VCS).                   Points out VOLTAGE CONTROL SWITCH (VCS) and simulates going to RAISE.
Cue: 2VM189 reads 4210, and 2VM190 reads 4150.
5.4.5      ENSURE generator terminal voltage is           Points out VOLTMETER SWITCH -
present on all 3 phases by rotating             GEN (VS-G), simulates rotating through VOLTMETER SWITCH - GEN (VS-G)                   each position, while observing 2VM189 through each position AND OBSERVING voltmeter 2VM189.                               Cue: Voltage is present on all three phases.
5.4.6      ENSURE 2A 4KV Vital Bus voltage is             Points out VOLTMETER SWITCH -
present on all 3 phases by rotating             BUS (VS-B), simulates rotating through VOLTMETER SWITCH - BUS (VS-B)                   each position, while observing 2VM190 through each position AND OBSERVING voltmeter 2VM190.                               Cue: Voltage is present on all three phases.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 7of12
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM: Emergency Diesel Generator                                                                     NAME:  ~~~~~~~~~~~~-
TASK:    Locally start and load an Emergency Diesel Generator                                           DATE:   ~~~~~~~~~~~~-
COMMENTS STEP                                                                       EVAL STEP                                                                          STANDARD                            (Required for UNSAT
(*Denotes a Critical Step)                                                            S/U
* NO.                                                                                                                 Evaluation) 5.4.7       PLACE the following switches in "1-2":                Points out VOLTMETER SWITCH -
GEN (VS-G) and VOLTMETER
* VOLTMETER SWITCH - GEN                       SWITCH - BUS (VS-B)
(VS-G)
* VOLTMETER SWITCH - BUS (VS-B)                                     Cue: Switches are in 1-2.
5.4.8      ENSURE 2DAE4-LT2, EOG Voltage                   Points out 2DAE4-LT2, EOG Voltage indication light is ON.                         indication light.
Cue: 2DAE4-LT2, EOG Voltage indication liqht is on.
5.4.9      ENSURE 2DAE4-LT3, EOG Speed                     Points out 2DAE4-LT3, EOG Speed indication light is ON.                         indication light.
Cue: 2DAE4-LT2, EOG Voltage indication liaht is on.
5.4.10      SYNCHRONIZE 2A Diesel Generator to 2A 4KV Vital Bus as follows:
* 5.4.10      PLACE 2A-DF-SYNCH, 2A DG SYNC A.        SWITCH (SS) to ON.                               Points out 2A-DF-SYNCH, 2A DG SYNC SWITCH (SS), and simulates placing in ON position.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 8of12
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM:  Emergency Diesel Generator                                                                     NAME:~~~~~~~~~~~~
TASK:    Locally start and load an Emergency Diesel Generator                                           DATE:~~~~~~~~~~~~-
COMMENTS STEP                                                                       EVAL STEP                                                                         STANDARD                            (Required for UNSAT
(*Denotes a Critical Step)                                                             S/U
* NO.                                                                                                                  Evaluation)
* 5.4.10      ADJUST Diesel speed using the SPEED             When operator points out B.        CONTROL SWITCH (GS) such that                   synchroscope, then Cue: Scope is Synchroscope pointer rotates slowly in the       going in the slow direction.
FAST (clockwise) direction.
FAST (clockwise) direction.
Points out SPEED CONTROL SWITCH (GS)and simulates going to RAISE. Cue Synchroscope pointer rotating slowly in the FAST direction.
Points out SPEED CONTROL SWITCH (GS)and simulates going to RAISE.
ENSURE the following four SYNC CHECK Points out four SYNC CHECK RELAY RELAY 25 UPPER AND LOWER 25 UPPER AND LOWER VOLTAGE VOLTAGE LIMIT LEDS are ON. LIMIT LEDS. "Upper Voltage Limit" "L OK" "B OK" "Lower Voltage Limit" "LOK" "B OK" Cue as each LED is located: Light is on. IF the SYNC CHK RELAY 25 i'.1F OK LED Points out SYNC CHK RELAY 25 i'.1F is OFF, THEN ADJUST 2A Diesel OK LED. Generator speed using the SPEED CONTROL SWITCH (GS) until the i'.1F OK Cue Light is on. LED is ON. ENSURE DG SYNC PERMISSIVE green indicating light is ON each time the Cue DG SYNC PERMISSIVE green synchroscope indicator is near 12 o'clock indicating light is ON each time the position ( +/-approximately 3 minutes), synchroscope indicator is near 12 AND is OFF in any other position of the o'clock position ( +/-approximately 3 synchroscope.
Cue Synchroscope pointer rotating slowly in the FAST direction.
minutes), AND is OFF in any other position of the svnchroscope.
5.4.10      ENSURE the following four SYNC CHECK             Points out four SYNC CHECK RELAY C.        RELAY 25 UPPER AND LOWER                         25 UPPER AND LOWER VOLTAGE VOLTAGE LIMIT LEDS are ON.                       LIMIT LEDS.
PSEG Restricted  
                    "Upper Voltage Limit" "L OK" "B OK" "Lower Voltage Limit" "LOK" "B OK"               Cue as each LED is located: Light is on.
-Possession Requires Specific Permission from Nuclear Training Page 9of12 EVAL COMMENTS S/U (Required for UNSAT Evaluation)
5.4.10      IF the SYNC CHK RELAY 25 i'.1F OK LED           Points out SYNC CHK RELAY 25 i'.1F D.        is OFF, THEN ADJUST 2A Diesel                   OK LED.
SYSTEM: TASK: *
Generator speed using the SPEED CONTROL SWITCH (GS) until the i'.1F OK           Cue Light is on.
* OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE Emergency Diesel Generator Locally start and load an Emergency Diesel Generator STEP NO. 5.4.10 F 5.4.10 G STEP (*Denotes a Critical Step) STANDARD COORDINATE the following when the synchroscope is at "12 o'clock" (+zero, -2 minutes):
LED is ON.
: 1. CLOSE 2A-DF-GCP-3 Points out 2A-DF-GCP-3 GENERATOR GENERATOR CIRCUIT CIRCUIT BREAKER SWITCH (BCS) BREAKER SWITCH (BCS) and simulates taking to the CLOSE position when the synch scope is at 12 2. RAISE 2A Diesel Generator load to o'clock. .:::_ 500KW using SPEED CONTROL SWITCH (GS) to Cue 2A Diesel Generator Breaker has prevent tripping the Diesel closed. Generator Breaker on reverse power. Points out SPEED CONTROL SWITCH (GS) simulates going to RAISE while observing KW meter. Cue Load is 500 KW. PLACE 2A-DF-SYNCH, 2A DG SYNCH Points out 2A-DF-SYNCH, 2A DG SWITCH (SS) to OFF. SYNCH SWITCH (SS), and simulates placing it in OFF position.
5.4.10      ENSURE DG SYNC PERMISSIVE green E.        indicating light is ON each time the             Cue DG SYNC PERMISSIVE green synchroscope indicator is near 12 o'clock       indicating light is ON each time the position ( +/- approximately 3 minutes),         synchroscope indicator is near 12 AND is OFF in any other position of the         o'clock position ( +/- approximately 3 synchroscope.                                   minutes), AND is OFF in any other position of the svnchroscope.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 9of12
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM:  Emergency Diesel Generator                                                                       NAME:~~~~~~~~~~~~~
TASK:    Locally start and load an Emergency Diesel Generator                                             DATE:~~~~~~~~~~~~-
COMMENTS STEP                                                                         EVAL STEP                                                                             STANDARD                            (Required for UNSAT
(*Denotes a Critical Step)                                                             S/U
* NO.                                                                                                                    Evaluation)
* 5.4.10      COORDINATE the following when the F        synchroscope is at "12 o'clock" (+zero, -2 minutes):
: 1. CLOSE 2A-DF-GCP-3                           Points out 2A-DF-GCP-3 GENERATOR GENERATOR CIRCUIT                         CIRCUIT BREAKER SWITCH (BCS)
BREAKER SWITCH (BCS)                     and simulates taking to the CLOSE position when the synch scope is at 12
: 2. RAISE 2A Diesel Generator load to           o'clock.
                              .:::_ 500KW using SPEED CONTROL SWITCH (GS) to                   Cue 2A Diesel Generator Breaker has prevent tripping the Diesel               closed.
Generator Breaker on reverse power.                                   Points out SPEED CONTROL SWITCH (GS) simulates going to RAISE while observing KW meter.
Cue Load is 500 KW.
5.4.10      PLACE 2A-DF-SYNCH, 2A DG SYNCH                     Points out 2A-DF-SYNCH, 2A DG G          SWITCH (SS) to OFF.                                 SYNCH SWITCH (SS), and simulates placing it in OFF position.
Cue: JPM is complete.
Cue: JPM is complete.
PSEG Restricted  
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 10of12
-Possession Requires Specific Permission from Nuclear Training Page 10of12 EVAL COMMENTS S/U (Required for UNSAT Evaluation)
 
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation.
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below.
Prior to JPM usage, revalidate JPM using steps 8 and 11 below. t,, Task description and number, JPM description and number are identified.
t,, ~1. Task description and number, JPM description and number are identified.
e.. Knowledge and Abilities (KIA) references are included. Performance location specified. (in-plant, control room, or simulator)
e.. ~2. Knowledge and Abilities (KIA) references are included.
: Initial setup conditions are identified. Initiating and terminating Cues are properly identified . .J ) /6. Task standards identified and verified by SME review. / J JI 7. Critical steps meet the criteria for critical steps and are identified with an asterisk(*). " r") ) 8. Verify the procedure referenced by this JPM matches the most current revision of c-r-that procedure:
~ ~3. Performance location specified. (in-plant, control room, or simulator)
Procedure Rev. _n_ Date !i/3ohlo _ci____f9.
:     ~4. Initial setup conditions are identified.
Pilot test the JPM: / a. verify Cues both verbal and visual are free of conflict, and b. ensure performance time is accurate.
      ~5.            Initiating and terminating Cues are properly identified .
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.
      ~
c,l..., SME/lnstruc . Pt :t-SME/lnstructor:  
      .J ) /6. Task standards identified and verified by SME review.
--------------
            /
Date: 1 /Jo U'2 Date:
      "
Date: ------PSEG Restricted  
J JI 7. Critical steps meet the criteria for critical steps and are identified with an asterisk(*).
-Possession Requires Specific Permission from Nuclear Training Page 11 of 12 INITIAL CONDITIONS:
c-r-r")   )   8. Verify the procedure referenced by this JPM matches the most current revision of that procedure: Procedure Rev. _n_ Date !i/3ohlo
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE Unit 2 is operating at 100% power, with no equipment OOS. Engineering has requested a loaded run of 2A EOG. INITIATING CUE: The Unit 2 CRS has directed you to locally start and parallel load 2A DIG IAW S2.0P-SO.DG-0001 (Q), Section 5.2. & 5.4 Prerequisites, Precautions and Limitations, and Section 5.1, Diesel Generator Startup Checks have been performed.
_ci____f9. Pilot test the JPM:
PSEG Restricted  
      /               a. verify Cues both verbal and visual are free of conflict, and
-Possession Requires Specific Permission from Nuclear Training Page 12of12 SCENARIO TITLE: SCENARIO NUMBER: EFFECTIVE DATE: SIMULATOR EXAMINATION SCENARIO GUIDE 15-01 NRC ESG-1 15-01 NRC ESG-1 See Approval Dates TQ-AA-106-0204 Page 1of27 EXPECTED DURATION:
: b. ensure performance time is accurate.
60 minutes REVISION NUMBER: PROGRAM: Revision Summary 00 .__ _ _.I LO. REQUAL X j INITIAL LICENSE .__ _ _.I STA New issue for 15-01 !LOT NRC exam PREPARED BY: G Gauding Lead Regulatory Exam Author APPROVED BY: APPROVED BY: 7-18-16 Date ----------;ri .... Oat PSEG Restricted  
____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM.
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 2 of 27 A. Given the order or indications of a charging system malfunction, perform actions as the nuclear control operator to RESPOND to the loss or malfunction of the charging system in accordance with S2.0P-AB.CVC-0001.
____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.
B. Given indication of a loss or malfunction of the Charging system DIRECT corrective action for a Charging System malfunction in accordance with S2. OP-AB. CVC-0001.
SME/lnstruc~~ c,l...,                                           Date:    1 /Jo U'2 SME/lnstruc     .                   Pt     :t-                 Date:    q~//6 SME/lnstructor:                                                 Date: - - - - - -
C. Given the indications of a reactor coolant system (RCS) malfunction or leak, perform actions as the nuclear control operator to RESPOND to the malfunctioning accordance with AB.RC-0001.
                        --------------
D. Given the indications of a reactor coolant system (RCS) malfunction or leak, DIRECT the response to the malfunction in accordance with S2.0P-AB.RC-0001.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 11 of 12
E. Given the order or indications of a reactor trip, perform actions as the nuclear control operator to RESPOND to the reactor trip in accordance with 2-EOP-TRIP-1.
 
F. Given indication of a reactor trip, DIRECT the response to the reactor trip in accordance with 2-EOP-TRIP-1.
OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE INITIAL CONDITIONS:
G. Given the order or indications of a safety injection, perform actions as the nuclear control operator to RESPOND to the safety injection in accordance with the approved station procedures.
Unit 2 is operating at 100% power, with no equipment OOS. Engineering has requested a loaded run of 2A EOG.
H. Given indication of a safety injection, DIRECT the response to the safety injection in accordance with the approved station procedures.
INITIATING CUE:
I. Given a safety injection has occurred and inadequate ECCS flow exists, ALIGN equipment to obtain required ECCS flow in accordance with station procedures.
The Unit 2 CRS has directed you to locally start and parallel load 2A DIG IAW S2.0P-SO.DG-0001 (Q),
J. Given the order or indications of a loss of coolant accident (LOCA), complete actions as the nuclear control operator to PERFORM the immediate response to the LOCA in accordance with the approved station procedures.
Section 5.2. & 5.4 Prerequisites, Precautions and Limitations, and Section 5.1, Diesel Generator Startup Checks have been performed.
K. Given indication of a loss of coolant accident (LOCA), DIRECT the immediate response to the LOCA in accordance with the approved station procedures.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 12of12
L. Given conditions that allow SI termination, perform actions as the nuclear control operator to TERMINATE safety injection in accordance with the approved station procedures.
 
M. Given conditions that allow SI termination, DIRECT the response to the safety injection termination in accordance with the approved station procedures.  
TQ-AA-106-0204 Page 1of27 SIMULATOR EXAMINATION SCENARIO GUIDE SCENARIO TITLE:                  15-01 NRC ESG-1 SCENARIO NUMBER:                  15-01 NRC ESG-1 EFFECTIVE DATE:                  See Approval Dates EXPECTED DURATION:                60 minutes REVISION NUMBER:                 00 PROGRAM:                       .___ _.I   LO. REQUAL X   j INITIAL LICENSE
*MAJb . ::i,E:N ..... " .... *v"* '.\ .. '.. A. Controlling PZR Level Channel fails low B. 20 gpm RCS leak C. 150 gpm SBLOCA D. SBLOCA escalation during SI termination PSEG Restricted  
                                .___ _.I   STA
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 3 of 27 A. The crew will take the watch with the unit at 100% power, MOL. PZR Pressure Channel Ill is selected for Control. B. After the crew assumes the watch, the controlling PZR level channel will fail low. eves Letdown will isolate, and the Master Flow Controller will raise charging flow. The crew will enter S2.0P-AB.CVC-0001, Loss of Charging.
                                ~-~'OTHER Revision Summary New issue for 15-01 !LOT NRC exam PREPARED BY:                     G Gauding                                 7-18-16 Lead Regulatory Exam Author                         Date
The crew will take manual control of charging flow and return PZR level to program. The crew will remove the failed channel from service. The crew will restore normal letdown. The CRS will identify Tech Specs. C. After the PZR level channel failure has been addressed, a 20 gpm RCS leak will occur. The crew will diagnose the leak. The crew will swap to a centrifugal charging pump and a 45 gpm orifice, and estimate the leak rate. The CRS will identify Tech Specs. D. The CRS will determine a unit shutdown is required based on the RCS leak. The crew ill initiate a controlled shutdown.
                                                                  --------- -;ri . .
E. After the downpower has commenced, the RCS leak rate will rise to 150 gpm. The crew will diagnose deteriorating primary conditions.
APPROVED BY:
When it is determined that PZR level will be unable to be maintained  
(~
>11 %, the crew will take the CAS action to trip the reactor and initiate Safety Injection.
Oat APPROVED BY:
F. The crew will perform plant stabilization and diagnostics in EOP-TRIP-1, Reactor Trip or Safety Injection.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
The crew will identify no AFW flow. 2A SEC will not reset, and will require deenergization to start 21 AFW pump. The crew will establish at least 22E4 lbm/hr AFW flow. (CT#1) G. The crew will determine there is no High Head ECCS flow, and open the BIT Isolation Valves to establish High Head ECCS Injection (CT#2). H. The crew will transition to EOP-LOCA-1, Loss of Reactor Coolant when directed in TRIP-1. I. The crew will reset Safeguards in LOCA-1, and determine SI termination criteria are met to transition to EOP-TRIP-3, SI Termination.
 
J. The crew will stop all but one Charging pump and align CVCS for normal charging.
TQ-AA-106-0204 Page 2 of 27 A.         Given the order or indications of a charging system malfunction, perform actions as the nuclear control operator to RESPOND to the loss or malfunction of the charging system in accordance with S2.0P-AB.CVC-0001.
When evaluating the leak, the SBLOCA will get significantly larger. The crew will diagnose degrading conditions and take the CAS action to start ECCS pumps as necessary, and go to EOP-LOCA-2. K. The scenario will terminate when the transition to LOCA-2 has been made. PSEG Restricted  
B.         Given indication of a loss or malfunction of the Charging system DIRECT corrective action for a Charging System malfunction in accordance with S2. OP-AB. CVC-0001.
-Possession Requires Specific Permission from Nuclear Training IC-231 TQ-AA-106-0204 Page 4 of 27 PREP FOR TRAINING equipment)  
C.         Given the indications of a reactor coolant system (RCS) malfunction or leak, perform actions as the nuclear control operator to RESPOND to the malfunctioning accordance with S2.0P-AB.RC-0001.
'. ' '*-, ;< ' ','' .. .. , ', Initial I Description 1 VC1 and VC4 CIT 2 RCPs (SELF CHECK) _ 3 RTBs (SELF CHECK) _4 MS167s (SELF CHECK) _ 5 500 KV SWYD (SELF CHECK) _ 6 SGFP Trip (SELF CHECK) _ 7 23 CV PP (SELF CHECK) 8 PZR Pressure Channel Ill selected for Control. g Complete Attachment 2 "Simulator Ready-for-Training/Examination Checklist." Note: Tables with blue headings may be populated by external program, do not change column name without consulting Simulator Support group PSEG Restricted  
D.         Given the indications of a reactor coolant system (RCS) malfunction or leak, DIRECT the response to the malfunction in accordance with S2.0P-AB.RC-0001.
-Possession Requires Specific Permission from Nuclear Training ET# Description 11 EVENT-ACTION:
E.         Given the order or indications of a reactor trip, perform actions as the nuclear control operator to RESPOND to the reactor trip in accordance with 2-EOP-TRIP-1.
I COMMAND: PURPOSE: CHECK SELF-01 02 03 04 05 06 07 08 CHECK 01 02 03 04 05 SELF-CHECK 01 Description PR0017A PZR LEVEL CH I LT459 FAILS H/L RC0002 RCS LEAK INTO CONTAINMENT (equiv to 0-4 inches RP0342 2SJ12 FAILS TO AUTO OPEN ON SEC RP0343 2SJ13 FAILS TO AUTO OPEN ON SEC RP318E1 Aux Feed Pum 21 Fails to Start on SEC RP318E2 Aux Feed Pump 22 Fails to Start on SEC AF0353A 21 AFP FAILURE TO AUTO START ON ANY (ALL SIGNALS AF0353B 22 AFP FAILURE TO AUTO START ON ANY ALL SIGNALS Description DG01 D DE ENERGIZE "A" SEC CABINET SP01A1 Prevailin Wind S eed SP01A2 Prevailin Wind Direction MS05A 21 MS45 21 STM GEN STM SUP-23 AFP MS06A 23MS45 23 STM GEN STM SUP-23 AFP Description CB09 A DI KCB09ASE 2A SFGD EMER OPR-EMERG LOADING RESET Delay Time NIA N/A N/A NIA NIA NIA NIA N/A Delay Time N/A N/A NIA NIA NIA Delay Time NIA Initial Value N/A N/A NIA NIA NIA NIA NIA Initial Value N/A N/A N/A NIA N/;\ Initial Value N/A Ramp Time N/A N/A N/A NIA NIA NIA NIA Ramp Time NIA NIA N/A N/A N/A Ramp Time i'JIA TQ-AA-106-0204 Page 5 of 27 Trigger Severity RT-1 0 RT-3 20 N/A N/A N/A N/A N/A NIA Trigger Condition RT-9 YES N/A 10 NIA 160 NIA 0 NIA 0 Trigger Condition/
F.         Given indication of a reactor trip, DIRECT the response to the reactor trip in accordance with 2-EOP-TRIP-1.
Sem;ty j i'J/A OFF PSEG Restricted
G.         Given the order or indications of a safety injection, perform actions as the nuclear control operator to RESPOND to the safety injection in accordance with the approved station procedures.
-Possession Requires Specific Permission from Nuclear Training
H.         Given indication of a safety injection, DIRECT the response to the safety injection in accordance with the approved station procedures.
: 1. Description TQ-AA-106-0204 Page 6 of 27 PSEG Restricted
I.         Given a safety injection has occurred and inadequate ECCS flow exists, ALIGN equipment to obtain required ECCS flow in accordance with station procedures.
-Possession Requires Specific Permission from Nuclear Training A. State shift job assignments.
J.         Given the order or indications of a loss of coolant accident (LOCA), complete actions as the nuclear control operator to PERFORM the immediate response to the LOCA in accordance with the approved station procedures.
TQ-AA-106-0204 Page 7 of 27 B. Hold a shift briefing, detailing instruction to the shift: (provide crew members a copy of the shift turnover sheet). C. Inform the crew "The simulator is running. You may commence panel walkdowns at this time. CRS please inform me when your crew is ready to assume the shift". D. Allow sufficient time for panel walk-downs.
K.         Given indication of a loss of coolant accident (LOCA), DIRECT the immediate response to the LOCA in accordance with the approved station procedures.
When informed by the CRS that the crew is ready to assume the shift, ensure the simulator is cleared of unauthorized personnel.
L.         Given conditions that allow SI termination, perform actions as the nuclear control operator to TERMINATE safety injection in accordance with the approved station procedures.
PSEG Restricted  
M.         Given conditions that allow SI termination, DIRECT the response to the safety injection termination in accordance with the approved station procedures.
-Possession Requires Specific Permission from Nuclear Training
*MAJb           .::i,E:N
.....".... *v"* ~:. '.\ ..'..
A.         Controlling PZR Level Channel fails low B.         20 gpm RCS leak C.         150 gpm SBLOCA D.         SBLOCA escalation during SI termination PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 3 of 27 A. The crew will take the watch with the unit at 100% power, MOL. PZR Pressure Channel Ill is selected for Control.
B. After the crew assumes the watch, the controlling PZR level channel will fail low. eves Letdown will isolate, and the Master Flow Controller will raise charging flow. The crew will enter S2.0P-AB.CVC-0001, Loss of Charging. The crew will take manual control of charging flow and return PZR level to program. The crew will remove the failed channel from service.
The crew will restore normal letdown. The CRS will identify Tech Specs.
C. After the PZR level channel failure has been addressed, a 20 gpm RCS leak will occur. The crew will diagnose the leak. The crew will swap to a centrifugal charging pump and a 45 gpm orifice, and estimate the leak rate. The CRS will identify Tech Specs.
D. The CRS will determine a unit shutdown is required based on the RCS leak. The crew ill initiate a controlled shutdown.
E. After the downpower has commenced, the RCS leak rate will rise to 150 gpm. The crew will diagnose deteriorating primary conditions. When it is determined that PZR level will be unable to be maintained >11 %, the crew will take the CAS action to trip the reactor and initiate Safety Injection.
F. The crew will perform plant stabilization and diagnostics in EOP-TRIP-1, Reactor Trip or Safety Injection. The crew will identify no AFW flow. 2A SEC will not reset, and will require deenergization to start 21 AFW pump. The crew will establish at least 22E4 lbm/hr AFW flow.
(CT#1)
G. The crew will determine there is no High Head ECCS flow, and open the BIT Isolation Valves to establish High Head ECCS Injection (CT#2).
H. The crew will transition to EOP-LOCA-1, Loss of Reactor Coolant when directed in TRIP-1.
I. The crew will reset Safeguards in LOCA-1, and determine SI termination criteria are met to transition to EOP-TRIP-3, SI Termination.
J. The crew will stop all but one Charging pump and align CVCS for normal charging. When evaluating the leak, the SBLOCA will get significantly larger. The crew will diagnose degrading conditions and take the CAS action to start ECCS pumps as necessary, and go to EOP-LOCA-2.
K. The scenario will terminate when the transition to LOCA-2 has been made.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 4 of 27 IC-231 PREP FOR TRAINING             (i.e.,computerset~oints, 1 procedures',be~el ~gver~';te1gged equipment)
                                          '.   '   '*-           ,           ;<       '   ',''       ..   ..   ,   ',
Initial I Description 1 VC1 and VC4 CIT 2 RCPs (SELF CHECK)
_       3 RTBs (SELF CHECK)
_ 4 MS167s (SELF CHECK)
_       5 500 KV SWYD (SELF CHECK)
_       6 SGFP Trip (SELF CHECK)
_       7 23 CV PP (SELF CHECK) 8 PZR Pressure Channel Ill selected for Control.
g Complete Attachment 2 "Simulator Ready-for-Training/Examination Checklist."
Note: Tables with blue headings may be populated by external program, do not change column name without consulting Simulator Support group PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 5 of 27 ET# Description 1 1 EVENT-ACTION: I COMMAND:
PURPOSE:
SELF-       Description                                    Delay Initial  Ramp      Trigger    Severity CHECK                                                      Time  Value    Time 01   PR0017A PZR LEVEL CH I LT459 FAILS H/L         NIA              N/A      RT-1          0 RC0002 RCS LEAK INTO CONTAINMENT (equiv to 0-02                                                    N/A    N/A      ~J/A    RT-3        20 4 inches 03    RP0342 2SJ12 FAILS TO AUTO OPEN ON SEC         N/A    N/A      N/A      N/A 04    RP0343 2SJ13 FAILS TO AUTO OPEN ON SEC         NIA    NIA      N/A      N/A 05    RP318E1 Aux Feed Pum 21 Fails to Start on SEC   NIA    NIA      NIA      N/A 06    RP318E2 Aux Feed Pump 22 Fails to Start on SEC NIA    NIA      NIA      N/A AF0353A 21 AFP FAILURE TO AUTO START ON ANY 07                                                    NIA    NIA      NIA      N/A (ALL SIGNALS AF0353B 22 AFP FAILURE TO AUTO START ON ANY 08                                                    N/A    NIA      NIA      NIA ALL SIGNALS SELF-      Description                                   Delay Initial  Ramp      Trigger    Condition CHECK                                                      Time  Value    Time 01    DG01 D DE ENERGIZE "A" SEC CABINET             N/A  N/A      NIA      RT-9        YES 02    SP01A1 Prevailin Wind S eed                    N/A  N/A      NIA      N/A          10 03    SP01A2 Prevailin Wind Direction                 NIA    N/A      N/A      NIA          160 04    MS05A 21 MS45 21 STM GEN STM SUP-23 AFP         NIA  NIA      N/A      NIA          0 05    MS06A 23MS45 23 STM GEN STM SUP-23 AFP         NIA  N/;\      N/A      NIA          0 SELF-CHECK 01 Description CB09 A DI KCB09ASE 2A SFGD EMER OPR-EMERG Delay Time NIA Initial Value N/A Ramp Time i'JIA Trigger i'J/A Condition/
Sem;ty  j OFF LOADING RESET PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 6 of 27 Description 1.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 7 of 27 A. State shift job assignments.
B. Hold a shift briefing, detailing instruction to the shift: (provide crew members a copy of the shift turnover sheet).
C. Inform the crew "The simulator is running. You may commence panel walkdowns at this time.
CRS please inform me when your crew is ready to assume the shift".
D. Allow sufficient time for panel walk-downs. When informed by the CRS that the crew is ready to assume the shift, ensure the simulator is cleared of unauthorized personnel.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training


Activily ,@: ... '
TQ-AA-106-0204 Page 8 of 27 Jfv~fUatpW1nstr:dctqr Activily ,@: ... ' ;if:'ex{.tlctecJ'~,ia{lt/Sfodel)t:Rlsponse; J::SBT'''
J::SBT''' . 1. Controlling PZR Level Channel Fails LOW ,simulafor Insert RT *1 *** on direction from L.ead Evaluator . .
                                                  .
I ,(LT459)FAH.:5H/L  
: 1. Controlling PZR Level Channel Fails LOW
**' . Severity:
  ,simulafor Oper:at~r: Insert RT*1
0 .
*** on direction from L.ead Evaluator.
* RO reports unexpected OHA E-36, PZR HTR OFF LVL LO. RO diagnoses controlling PZR level channel failure. RO may request permission to place the Master Flow Controller in manual prior to direction in AB.eve to do so. CRS enters 82.0P-AB.CVC-0001, Loss of Charging.
  .MALF~PR0017APZRtVLCH I
CRS directs initiation of Attachment 1 CAS. RO reports charging pumps are running, and no indication of cavitation.
    ,(LT459)FAH.:5H/L **' .
RO reports PZR level channel I has failed low. If not previously performed, RO takes manual control of charging and maintains PZR level within band assigned by CRS. PSEG Restricted  
Severity: 0 .
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 8 of 27
* RO reports unexpected OHA E-36, PZR HTR OFF LVL LO.
.* ri<e;ta1uator/lnstfucli  
RO diagnoses controlling PZR level channel failure.
',*,' '1i-;'.  
RO may request permission to place the Master Flow Controller in manual prior to direction in AB.eve to do so.
;+/-}*.':. I  
CRS enters 82.0P-AB.CVC-0001, Loss of Charging.
-. ' Proceed to next event after Tech Spec call at direction from Lead evaluator.
CRS directs initiation of Attachment 1 CAS.
exriected, . .SBTi RO selects operable channel for Control, Alarm, and Recorders.
RO reports charging pumps are running, and no indication of cavitation.
RO reports PZR level channel I has failed low.
If not previously performed, RO takes manual control of charging and maintains PZR level within band assigned by CRS.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 9 of 27
.* ',ri<e;ta1uator/lnstfucli
    *,' '1i-;'. )~J' ;+/-}*.':. I .?:.:'.,~* -. '
exriected, i>1ant/s~lltl~nt:R~spO,ose,&:,  . .SBTi
                                                                                                      ~.
RO selects operable channel for Control, Alarm, and Recorders.
RO restores PZR heaters to pre-event condition.
RO restores PZR heaters to pre-event condition.
RO announces OHA E-20 PZR HTR ON L VL HI as expected when it annunciates due to no letdown with charging flow established.
RO announces OHA E-20 PZR HTR ON LVL HI as expected when it annunciates due to no letdown with charging flow established.
PO restores letdown by: -Ensuring open 2CV7 -Placing 2CV18 in manual and closing, then opening until close PB extinguishes.  
PO restores letdown by:
-Opening 2CV2 and 2CV277, then placing both in auto. -Ensuring charging flow is 90 gpm. -Opening a 75 gpm orifice isolation valve while adjusting 2CV18 to control letdown pressure -300 psig. -Placing 2CV18 in auto. RO returns Master Flow Controller to auto when PZR level returns to proqram. CRS contacts IC for assistance in removing channel from service. CRS enter LCO 3.3.1.1 action 6. PSEG Restricted
                                                          - Ensuring open 2CV7
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 9 of 27 eva1u*at0rlfrndruclor Activity
                                                          - Placing 2CV18 in manual and closing, then opening until close PB extinguishes.
,,.,!
                                                          - Opening 2CV2 and 2CV277, then placing both in auto.
;{('f,(<<:e
                                                          - Ensuring charging flow is 90 gpm.
: 3. 20 gpm RCS leak Simulator Operator:
                                                          - Opening a 75 gpm orifice isolation valve while adjusting 2CV18 to control letdown pressure -300 psig.
Insert RT-3 orfdirection from Lead Evaluator
                                                          - Placing 2CV18 in auto.
*MALF: RC0002 ,.;..
RO returns Master Flow Controller to auto when PZR level returns to proqram.
into containment..
CRS contacts IC for assistance in removing channel from service.
* Final Value: 20 gpm* Note: PZR level is above program, and charging flow will be lower than normal to reduce PZR level. If charging flow is raised here to stabilize level, then step to place a centrifugal charging pump in
CRS enter LCO 3.3.1.1 action 6.
.. ,,,,,, *
Proceed to next event after Tech Spec call at direction from Lead evaluator.
* ____ ,. *"*----*--, ;,*.*.*' * '"t ,_, '""""'"" RO reports that charging flow is rising (if MFC has been returned to auto) and PZR level is lowering slowly. Crew reports reading on 2R11A containment radiation monitor is rising. RO reports unexpected OHA C-2 CNTMT SUMP PMP START when it occurs. CRS enters S2. OP-AB. RC-0001, Reactor Coolant System Leak. CRS directs initiation of Attachment 1 CAS. RO reports RCS temperature
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
> 350&deg;F in Mode 1. RO reports PZR level is lowering.
LOG't PSEG Restricted  
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 10 of 27
... 11t" 


,.'A,*, '-''C), i'.' ,}
TQ-AA-106-0204 Page 10 of 27 eva1u*at0rlfrndruclor Activity ~.,*'
*'',,0/?f',,
  ~?Jf"': ,,.,! ~:,~.?'-- '.*~,f,;;'''\ !~;,~'**+_ ~~-:;::( ,~?;~fe:'~,. ;{('f,(<<:e i:r""'~*
t ,* '-)7 service may not be performed.
                                                                                                    'F!xpeq~ed:(P~~nt/Student.Re'ipdnse
Role Play: If contacted state Rad Pro recommends placing 2 CFCU's in Low Speed and 2 CFCU's in High Speed. *** ..
                                                                                                      , ;~:c~~
J'lafntJStuderlt
1
,;;# , 4 ',,
                                                                                                              . ,,,,,, **____,. *"*---- *--, ;,*.*.*' *'"t ,_, '""""'""
"'"'-" ' '.<<*'* ,,,-,c .li'SBT CRS enters S2.0P-AB.RAD-0001, Abnormal Radiation after OHA A-6 unexpected annunciation.
                                                                                                                                                                        ~ssf,'.
RO swaps to a centrifugal charging pump IAW Step 3.14, and raises charging flow to stabilize PZR level. PO reduces letdown flow to minimum by opening 2CV3, maintaining letdown pressure -300 psig with 2CV18 in manual, then closing the open 75 gpm orifice and returning 2CV18 to auto. RO stabilizes PZR level and estimates leak rate. CRS initiates S2.0P-ST.RC-0008, Reactor Coolant System Water Inventory Balance. CRS contacts Rad Pro for recommendation on CFCU operation.
LOG't
PO places 2 CFCU's in Low Speed and 2 CFCU's in High Speed. CRS initiates actions to locate and isolate the leak IAW Attachment
                                                                                                                                                                                &c~,M~"t:>~;r' . 11t"
: 2. PSEG Restricted  
: 3. 20 gpm RCS leak Simulator Operator: Insert RT-3 orfdirection from Lead Evaluator
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 11of27 <fomment: 1 ,
*MALF: RC0002 ,.;.. ~cs                                        Le~k into containment..
,,"J,, 
* Final Value: 20 gpm*
RO reports that charging flow is rising (if MFC has been returned to auto) and PZR level is lowering slowly.
Crew reports reading on 2R11A containment radiation monitor is rising.
RO reports unexpected OHA C-2 CNTMT SUMP PMP START when it occurs.
CRS enters S2. OP-AB. RC-0001, Reactor Coolant System Leak.
CRS directs initiation of Attachment 1 CAS.
RO reports RCS temperature > 350&deg;F in Mode 1.
RO reports PZR level is lowering.
Note: PZR level is above program, and charging flow will be lower than normal to reduce PZR level. If charging flow is raised here to stabilize level, then step to place a centrifugal charging pump in PSEG Restricted - Possession Requires Specific Permission from Nuclear Training


*. ;'lt, .. ''i J''' , ,'&sect;' .  
TQ-AA-106-0204 Page 11of27
' ,, ' Exi>&cted*Ptant1stuaenl ResPtlnse*
    .EvaluatofJl~itrii(;tf>riActivitY                                        * * . '.l:xJ)~ctiJ.~f J'lafntJStuderlt Rispori~~ ,,,-,c
.; wj. iJt , __ A[.!*, :  
                                                                                                                                      .li'SBT        <fomment:.;~&#xa5;<1,
.,,,"s***a**Tc  
                                                                                                                                                    ~kr "'~~( /~~/
******** .*. *a_,51( ... CRS enters TSAS 3.4.7.2.b action b for RCS leakage, and 3.6.1.4 for containment pressure if it has reached 0.3 psiq. Role Play: After RCS leakage Tech Spec has been identified, if CRS does not initiate a power reduction to bring the unit offline, call Control Room as Operations Director and instruct the CRS to initiate a 30% per hour load reduction to 20% in preparation for taking Unit 2 offline to investigate and repair the RCS leak. CRS briefs power reduction.
  ,.'A,*, )~ '- ''C), i'.' ,} /"!~, *'',,0/?f',, ~)/'. >~>j/ t ,* '- )7          ,;;#  ,    4 ',, .**~' "'"'- "    '  '.<<*'*
                                                                                                                                                        ,,"J,,
service may not be performed.
CRS enters S2.0P-AB.RAD-0001, Abnormal Radiation after OHA A-6 unexpected annunciation.
RO swaps to a centrifugal charging pump IAW Step 3.14, and raises charging flow to stabilize PZR level.
PO reduces letdown flow to minimum by opening 2CV3, maintaining letdown pressure
                                                                          -300 psig with 2CV18 in manual, then closing the open 75 gpm orifice and returning 2CV18 to auto.
RO stabilizes PZR level and estimates leak rate.
CRS initiates S2.0P-ST.RC-0008, Reactor Coolant System Water Inventory Balance.
CRS contacts Rad Pro for recommendation on CFCU operation.
Role Play: If contacted state Rad Pro recommends placing 2 CFCU's in Low Speed and 2 CFCU's in High Speed.
PO places 2 CFCU's in Low Speed and 2 CFCU's in High Speed.
CRS initiates actions to locate and isolate the leak IAW Attachment 2.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 12 of 27
    .*.;~~E'laluc:ilor/lh$ltuetoJ;~&#xa3;Act1VitY
    ,v~. A~" ~ .. ''i :._,.-~, ~ ~, ~,1tr:* J''' , ,'&sect;' . "~,AL
                                                                          *.;'lt,
                                                                ' ~ ,, ' ;.~;*
                                                                                      ~ Exi>&cted*Ptant1stuaenl
                                                                                          ~;J, .; wj. iJt           ResPtlnse*
                                                                                                                , __A[.!*, : >~t<*'
                                                                                                                                    .,,,"s***a**Tc * * * *
                                                                                                                                    .*. *a_,51(           !rco'l)r~J"lr:;:* ***
...
CRS enters TSAS 3.4.7.2.b action b for RCS leakage, and 3.6.1.4 for containment pressure if it has reached 0.3 psiq.
Role Play: After RCS leakage Tech Spec has been identified, if CRS does not initiate a power reduction to bring the unit offline, call Control Room as Operations Director and instruct the CRS to initiate a 30% per hour load reduction to 20% in preparation for taking Unit 2 offline to investigate and repair the RCS leak.
CRS briefs power reduction.
RO initiates boration.
RO initiates boration.
PO initiates turbine load reduction at 30% per hour. CRS may enter S2.0P-AB.LOAD-0001 Rapid Load Reduction to perform the power reduction.
PO initiates turbine load reduction at 30% per hour.
CRS may enter S2.0P-AB.LOAD-0001 Rapid Load Reduction to perform the power reduction.
Proceed to next event on direction from Lead Evaluator.
Proceed to next event on direction from Lead Evaluator.
: 3. SBLOCA Simulator Operator: .MODIFY MALF RC0002 from 20 to 150 on direction from Lead Evaluator.
: 3. SBLOCA Simulator Operator: .MODIFY MALF RC0002 from 20 to 150 on direction from Lead Evaluator.
PSEG Restricted  
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 12 of 27  
 
*********
TQ-AA-106-0204 Page 13 of 27 eval,uatb.rtlnstructor ActivitY;'*       . Expict~CI      PlantlsfodeijfRespoJ\sef""       '/\'$'81''       Commeilf''      *
eval,uatb.rtlnstructor ActivitY;'* .
                                                              ..                                                      . *7*.  .."t*
PlantlsfodeijfRespoJ\sef"" '/\'$'81''
.    .*      i'. ... ****,                     F     ',.\.,~    J      >              37' * ;1*   LOG* *i RO reports PZR level trending down and adjusts charging flow to maintain PZR level.
i'. ... ****, F  
RO reports PZR level will not be able to be maintained >17%.
.. 37' * ;1* LOG* *i . .* J > RO reports PZR level trending down and adjusts charging flow to maintain PZR level. RO reports PZR level will not be able to be maintained  
CRS directs Rx trip and Safety Injection RO trips the reactor and confirms the reactor trip.
>17%. CRS directs Rx trip and Safety Injection RO trips the reactor and confirms the reactor trip. RO initiates Safety Injection.
RO initiates Safety Injection.
RO continues Immediate Actions of TRIP-1 -Trips the Main Turbine -Reports at least one 4KV vital bus energized.  
RO continues Immediate Actions of TRIP-1
-Reports SI initiated.
                                                - Trips the Main Turbine
CRS and RO verify performance of immediate actions. 4. AFW fails to initiate PO reports SEC loading is not complete for 2A and 28 vital buses, 21 and 22 AFW pumps have failed to start. Reports 23 AFW pump started but is not providinq any AFW flow. RO blocks 2A and 28 SECs. PO resets 2A and 28 SECs. PO reports 2A SEC will not reset. PSEG Restricted  
                                                - Reports at least one 4KV vital bus energized.
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 13 of 27 Commeilf''
                                                - Reports SI initiated.
* . *7*. .."t*
CRS and RO verify performance of immediate actions.
TQ-AA-106-0204 Page 14 of 27 *<r ..
: 4. AFW fails to initiate PO reports SEC loading is not complete for 2A and 28 vital buses, 21 and 22 AFW pumps have failed to start. Reports 23 AFW pump started but is not providinq any AFW flow.
Resp<>n$e,, '"Y" . ,,., '*"'' ,, . ' . > .,;,sBT1;:S  
RO blocks 2A and 28 SECs.
**
PO resets 2A and 28 SECs.
:,;',-:' .*. .. . *. ... . .. ---CRS dispatches operator to deenergize 2A SEC. Simulator Operator:
PO reports 2A SEC will not reset.
2 minutes being dispatched, jnsert RT-9 to deenergize 2A SEC: RO starts 22 AFW pump. CT#1 (cr.:s) Establish atleast ** 22E4 lbl11/hr AFWflowto the *** SG's prior to a transition to FRHS*1 being required.  
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
* ..... '>\' UNSAT SAT ' PO reports AFW pump status, and starts 21 AFW pump when 2A SEC is deenergized.
 
TQ-AA-106-0204 Page 14 of 27
*<r .. evafo~lotll~stru~o~.A,ctijitf'              5~:';expected.:P1a11tf5tudent Resp<>n$e,,
                                                      '"Y" .     ,,.,     '*"'' ,, . ' .
                                                                                                    .,;,sBT1;:S
* corl)ment,~:,
                                                .                                                      ---
                                                                                              >
:,;',- :' .*. ..                       *.           ...               ...   :~
CRS dispatches operator to deenergize 2A SEC.
Simulator Operator: 2 minutes
~fter being dispatched, jnsert RT-9 to deenergize 2A SEC:
RO starts 22 AFW pump.
CT#1 (cr.:s) Establish atleast
* 22E4 lbl11/hr AFWflowto the *
* SG's prior to a transition to FRHS*1 being required. *
                                          .....
  '>\'
SAT                      UNSAT
                                    '
PO reports AFW pump status, and starts 21 AFW pump when 2A SEC is deenergized.
PO reports not all valve groups in Table B are in safequards position.
PO reports not all valve groups in Table B are in safequards position.
PO reports 2SJ 12 and 2SJ 13 BIT isolation valves have not opened. RO opens 2SJ12 and 2SJ13 and reports BIT flow is established.
PO reports 2SJ 12 and 2SJ 13 BIT isolation valves have not opened.
CT#2 {CT*6) Establish flow from 'atleastone charging pump prior to transition out ofTRIP-1.
RO opens 2SJ12 and 2SJ13 and reports BIT flow is established.
SAT UNSAT PSEG Restricted  
CT#2 {CT*6) Establish flow from
-Possession Requires Specific Permission from Nuclear Training
'atleastone charging pump prior to transition out ofTRIP-1.
", ..,, I JS;.. iJ!
SAT                     UNSAT PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
y;:: .* ,cklJ:ii, ft :fd;.
 
r* ... **** <* ;) t:cf<' t** Y,'.;Jw .:0:. LOGt RO reports 21 and 22CA330s are shut. RO reports containment pressure has remained <15 psig. PO reports no high steam flow condition.
TQ-AA-106-0204 Page 15 of 27
CRS directs implementation of the ECG. PO reports all 4KV vital buses enerqized.
            ~-        ~                                                                                                              7 Commenf"   *
RO reports CAV in AP mode. RO reports 2 switchgear supply and one exhaust fan are running. RO reports 2 or more CCW pumps running. RO reports RCS not aligned for Cold Leg Recirc. RO reports charging flow is at least 100 gpm on SI systems charc::iinq flow meter. RO reports RCS pressure is not <1540 psiq. PO reports total AFW flow is 22E4 lbm/hr or 9% level in at least one SG NR level, then maintains 19-33% level. RO reports all RCPs running, and RCS temperature is stable at or trending to 547&deg;F. PSEG Restricted  
  ..,, ", ~
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 15 of 27 7 Commenf"
JS;.. iJ! ~t~fii y;:: .* ,cklJ:ii, ft :fd;. ;~~jt    r* ... **** <*
* Acdvlfy  
                                                                                  ;) t:cf<'     t**   Y,'.;Jw .:0:. LOGt I
,,.,, Note: CFST monitoring will commence after the transition out of TRI P-1. ST A will report to the control room 10 minutes after being paged. Expebted, Plaht/Student RespoHse **** RO reports both RTBs are open. RO reports both PZR PORVs are shut with their Block Valves open. RO reports all RCPs in service and PZR spray operating as expected for current plant conditions.
RO reports 21 and 22CA330s are shut.
RO reports RCS pressure >1350 psig and maintains seal injection flow to all RCPs. PO reports no indication of faulted SGs. PO/RO report no indications of a steam generator tube rupture. RO reports radiation monitor channel status in Table F. PO reports 2 or more channels rising or in warninq or alarm. CRS transitions to EOP-LOCA-1, Loss of Reactor Coolant. PO reports no faulted SGs. SBT TQ-AA-106-0204 Page 16 of 27 . r Comment .\.Bn* .... PSEG Restricted  
RO reports containment pressure has remained <15 psig.
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204
PO reports no high steam flow condition.
:'h Respo*nse  
CRS directs implementation of the ECG.
".ii'*IV' Page 17 of 27 ,,vi "Cofumerii''.'
PO reports all 4KV vital buses enerqized.
7 r,, *  
RO reports CAV in AP mode.
;.,sat PO reports total AFW flow is 22E4 lbm/hr or 9% level in at least one SG NR level, then maintains 19-33% level. PO reports no ruptured SGs. RO resets SI, Phase A, and Phase B isolations.
RO reports 2 switchgear supply and one exhaust fan are running.
RO reports 2 or more CCW pumps running.
RO reports RCS not aligned for Cold Leg Recirc.
RO reports charging flow is at least 100 gpm on SI systems charc::iinq flow meter.
RO reports RCS pressure is not <1540 psiq.
PO reports total AFW flow is 22E4 lbm/hr or 9% level in at least one SG NR level, then maintains 19-33% level.
RO reports all RCPs running, and RCS temperature is stable at or trending to 547&deg;F.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 16 of 27
'f,Evaluator!lnst~ctor Acdvlfy                   " 7~:~ Expebted, Plaht/Student RespoHse **     SBT                  . r Comment .\.Bn* ....
i~;,:cr~ :>}".\~*~(,,.c ,,.,,
RO reports both RTBs are open.
RO reports both PZR PORVs are shut with their Block Valves open.
RO reports all RCPs in service and PZR spray operating as expected for current plant conditions.
RO reports RCS pressure >1350 psig and maintains seal injection flow to all RCPs.
PO reports no indication of faulted SGs.
PO/RO report no indications of a steam generator tube rupture.
RO reports radiation monitor channel status in Table F.
PO reports 2 or more channels rising or in warninq or alarm.
CRS transitions to EOP-LOCA-1, Loss of Reactor Coolant.
Note: CFST monitoring will commence after the transition out of TRI P-1. STA will report to the control room 10 minutes after being paged.
PO reports no faulted SGs.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 17 of 27
.,.~e:valuatCff!(~~tructorAcUvify 1
                                                    'Sxpd~ted 'f>1aflt/StuBent Respo*nse ".ii'*IV' ;.,sat              ,,vi "Cofumerii''.'7 r,, *
                                                                                                                      '{7~>
:'h                AT~:!'~ ,~,**'!~J:JF;~;~;,,,
PO reports total AFW flow is 22E4 lbm/hr or 9% level in at least one SG NR level, then maintains 19-33% level.
PO reports no ruptured SGs.
RO resets SI, Phase A, and Phase B isolations.
RO opens 21 and 22CA330s.
RO opens 21 and 22CA330s.
PO resets 2C SEC, and reports 230V control centers reset. RO resets SGBD Sample Isolation Bypass and opens 21-24SS94s.
PO resets 2C SEC, and reports 230V control centers reset.
CRS directs chemistry to sample SGs for activity and boron. RO reports PORVs are shut with Block valves open. RO reports subcoolinq  
RO resets SGBD Sample Isolation Bypass and opens 21-24SS94s.
> 0&deg;F. PO reports AFW flow >22E4 lbm/hr or SG NR level >9%. RO reports RCS pressure is stable or risinq. RO reports PZR level >11 %. CRS transitions to EOP-TRIP-3, SI Termination.
CRS directs chemistry to sample SGs for activity and boron.
PSEG Restricted  
RO reports PORVs are shut with Block valves open.
-Possession Requires Specific Permission from Nuclear Training Evaiuator/lnstfocfor A'ctivitY  
RO reports subcoolinq > 0&deg;F.
... '1 .il'0'lft , ,, i2t*'*5 Simulator Operator:
PO reports AFW flow >22E4 lbm/hr or SG NR level >9%.
MODIFY MALF RC0002 from .. 150 to 2000 when 2CV68 and 2CV69 are ooen.
RO reports RCS pressure is stable or risinq.
' v''";>'..*;  
RO reports PZR level >11 %.
'' '  
CRS transitions to EOP-TRIP-3, SI Termination.
"' RO resets SI, Phase A, and Phase B isolations if not previously reset. RO opens 21 and 22CA330s if not previously performed.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
RO reports spray valves are not failed open. PO resets 2C SEC and reports 230V control centers reset if not previously performed.
 
RO stops all but one charqinq pump. RO reports RCS pressure is stable or risinq. RO reports charging pump suction is aligned to the RWST. RO opens 2CV139 and 2CV140 if shut. RO shuts BIT isolation valves 2SJ4, 2SJ5, 2SJ12, 2SJ13. RO shuts 2CV55 Charqinq Flow Control valve. RO opens 2CV68 and 2CV69 Charging Discharqe valves. RO adjusts 2CV55 to maintain PZR level SBT LOG PSEG Restricted  
TQ-AA-106-0204 Page 18 of 27 Evaiuator/lnstfocfor A'ctivitY . .         E;xp~Cfe(ltPlant/StuCle*nt Resp(mse~"":            SBT          comment    *,*M*\
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 18 of 27 comment *,*M*\5&#xa3; *, * 
5
'' Evaluatortl'nstruct.6r Activity::
                                                                                                                                  &#xa3; *, *
',; /,, :. ..  
    '1 .il'0'lft , ,, ';~ ~;*  i2t*'*5             ' v''";>'..*; ''   '  .~J'.'.)RQ{)t/"'- "'
,}:>*:**  
LOG RO resets SI, Phase A, and Phase B isolations if not previously reset.
' Terminate scenario on direction from Lead Evaluator after the transition to LOCA-2 is made. "''!1ft1c.pected*
RO opens 21 and 22CA330s if not previously performed.
Plant/Student' Response .. A". .,,,:;; .. s >d'.>: '*
RO reports spray valves are not failed open.
fr,: . :t' : .. >25%. RO reports PZR level is not stable or risinq. PO reports no faulted SGs. RO opens BIT isolation valves 2SJ4,5, 12, 13, and shuts normal charging line isolation valves 2CV68 and 69. CRS goes to EOP-LOCA-2, Post LOCA Cooldown and Depressurization.
PO resets 2C SEC and reports 230V control centers reset if not previously performed.
SB T:3*;.
RO stops all but one charqinq pump.
> .*. L;\;l\.;J
RO reports RCS pressure is stable or risinq.
... j PSEG Restricted  
RO reports charging pump suction is aligned to the RWST.
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 19 of 27 Commen'f *
RO opens 2CV139 and 2CV140 if shut.
*.
RO shuts BIT isolation valves 2SJ4, 2SJ5, 2SJ12, 2SJ13.
A. Alarm Response Procedures (Various)
RO shuts 2CV55 Charqinq Flow Control valve.
B. Technical Specifications C. Emergency Plan (ECG) D. OP-AA-101-111-1003, Use of Procedures E. S2.0P-10.ZZ-0004, Power Operation F. S2.0P-AB.CVC-0001, Loss of Charging G. S2.0P-AB.RC-0001, Reactor Coolant System Leak H. 2-EOP-TRIP-1, Reactor Trip or Safety Injection I. 2-EOP-TRIP-3, Safety Injection Termination J. 2-EOP-LOCA-1, Loss of Reactor Coolant K. 2-EOP-LOCA-2, Post LOCA Cooldown and Depressurization TQ-AA-106-0204 Page 20 of 27 PSEG Restricted  
RO opens 2CV68 and 2CV69 Charging Discharqe valves.
-Possession Requires Specific Permission from Nuclear Training ATTACHMENT 1 UNIT TWO PLANT STATUS TODAY MODE: 1 POWER: 100% RCS BORON: SHUTDOWN SAFETY SYSTEM STATUS (5, 6 & DEFUELED):
Simulator Operator: MODIFY MALF RC0002 from . 150 to 2000 when 2CV68 and 2CV69 are ooen.
RO adjusts 2CV55 to maintain PZR level PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 19 of 27
  '' Evaluatortl'nstruct.6r
      ',; /,, :. .
              ~:    )~{' ,}:>*:**
Activity::'
                                      ~:*.;',
                                                            "''!1ft1c.pected* Plant/Student' Response ..
A".                                   ~
T:3*;.
SB ,.~&sect;~~'.''.  > Commen'f *)J&:J1!:~r *.
                                                                                                          ..
                                                    .,,,:;; 1n~*7 '*    .s >d'.>: '*
                                                                                        '.~* fr,: . :t' :   .*. L;\;l\.;J ..   .j
                                                      >25%.
RO reports PZR level is not stable or risinq.
PO reports no faulted SGs.
RO opens BIT isolation valves 2SJ4,5, 12, 13, and shuts normal charging line isolation valves 2CV68 and 69.
CRS goes to EOP-LOCA-2, Post LOCA Cooldown and Depressurization.
Terminate scenario on direction from Lead Evaluator after the transition to LOCA-2 is made.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 20 of 27 A. Alarm Response Procedures (Various)
B. Technical Specifications C. Emergency Plan (ECG)
D. OP-AA-101-111-1003, Use of Procedures E. S2.0P-10.ZZ-0004, Power Operation F. S2.0P-AB.CVC-0001, Loss of Charging G. S2.0P-AB.RC-0001, Reactor Coolant System Leak H. 2-EOP-TRIP-1, Reactor Trip or Safety Injection I. 2-EOP-TRIP-3, Safety Injection Termination J. 2-EOP-LOCA-1, Loss of Reactor Coolant K. 2-EOP-LOCA-2, Post LOCA Cooldown and Depressurization PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 21of27 ATTACHMENT 1 UNIT TWO PLANT STATUS TODAY MODE:     1       POWER:     100%       RCS BORON:       857          MWe        1220 SHUTDOWN SAFETY SYSTEM STATUS (5, 6 & DEFUELED):
NA REACTIVITY PARAMETERS MOST LIMITING LCO AND DATEfflME OF EXPIRATION:
NA REACTIVITY PARAMETERS MOST LIMITING LCO AND DATEfflME OF EXPIRATION:
857 EVOLUTIONS/PROCEDURES/SURVEILLANCES IN PROGRESS:
EVOLUTIONS/PROCEDURES/SURVEILLANCES IN PROGRESS:
ABNORMAL PLANT CONFIGURATIONS:
ABNORMAL PLANT CONFIGURATIONS:
PZR Pressure Channel Ill is selected for Control CONTROL ROOM: Unit 1 and Hope Creek at 100% power. No penalty minutes in the last 24 hrs. PRIMARY: SECONDARY:
PZR Pressure Channel Ill is selected for Control CONTROL ROOM:
Unit 1 and Hope Creek at 100% power.
No penalty minutes in the last 24 hrs.
PRIMARY:
SECONDARY:
RADWASTE:
RADWASTE:
No discharges in progress CIRCULATING WATER/SERVICE WATER: TQ-AA-106-0204 Page 21of27 MWe 1220 PSEG Restricted  
No discharges in progress CIRCULATING WATER/SERVICE WATER:
-Possession Requires Specific Permission from Nuclear Training ATTACHMENT 2 SIMULATOR READY FOR TRAINING CHECKLIST
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
: 1. Verify simulator is in "TRAIN" Load 2. Simulator is in RUN 3. Overhead Annunciator Horns ON 4. All required computer terminals in operation
 
TQ-AA-106-0204 Page 22 of 27 ATTACHMENT 2 SIMULATOR READY FOR TRAINING CHECKLIST
: 1. Verify simulator is in "TRAIN" Load
: 2. Simulator is in RUN
: 3. Overhead Annunciator Horns ON
: 4. All required computer terminals in operation
: 5. Simulator clocks synchronized
: 5. Simulator clocks synchronized
: 6. All tagged equipment properly secured and documented
: 6. All tagged equipment properly secured and documented
: 7. TSAS Status Board up-to-date
: 7. TSAS Status Board up-to-date
: 8. Shift manning sheet available
: 8. Shift manning sheet available
: 9. Procedures in progress open and signed-off to proper step TQ-AA-106-0204 Page 22 of 27 10. All OHA lamps operating (OHA Test) and burned out lamps replaced 11. Required chart recorders advanced and ON (proper paper installed)
: 9. Procedures in progress open and signed-off to proper step
: 12. All printers have adequate paper AND functional ribbon 13. Required procedures clean 14. Multiple color procedure pens available
: 10. All OHA lamps operating (OHA Test) and burned out lamps replaced
: 11. Required chart recorders advanced and ON (proper paper installed)
: 12. All printers have adequate paper AND functional ribbon
: 13. Required procedures clean
: 14. Multiple color procedure pens available
: 15. Required keys available
: 15. Required keys available
: 16. Simulator cleared of unauthorized material/personnel
: 16. Simulator cleared of unauthorized material/personnel
: 17. All charts advanced to clean traces and chart recorders are on. 18. Rod step counters correct (channel check) and reset as necessary
: 17. All charts advanced to clean traces and chart recorders are on.
: 18. Rod step counters correct (channel check) and reset as necessary
: 19. Exam security set for simulator
: 19. Exam security set for simulator
: 20. Ensure a current RCS Leak Rate Worksheet is placed by Aux Alarm Typewriter with Baseline Data filled out 21. Shift logs available if required 22. Recording Media available (if applicable)
: 20. Ensure a current RCS Leak Rate Worksheet is placed by Aux Alarm Typewriter with Baseline Data filled out
: 23. Ensure ECG classification is correct 24. Reference verification performed with required documents available
: 21. Shift logs available if required
: 25. Verify phones disconnected from plant after drill. 26. Verify EGC paperwork is marked "Training Use Only" and is current revision.
: 22. Recording Media available (if applicable)
: 23. Ensure ECG classification is correct
: 24. Reference verification performed with required documents available
: 25. Verify phones disconnected from plant after drill.
: 26. Verify EGC paperwork is marked "Training Use Only" and is current revision.
: 27. Ensure sufficient copies of ECG paperwork are available.
: 27. Ensure sufficient copies of ECG paperwork are available.
PSEG Restricted  
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
-Possession Requires Specific Permission from Nuclear Training ATTACHMENT 3 CRITICAL TASK METHODOLOGY TQ-AA-106-0204 Page 23 of 27 In reviewing each proposed CT, the examination team assesses the task to ensure, that it is essential to safety. A task is essential to safety if, in the judgment of the examination team, the improper performance or omission of this task by a licensee will result in direct adverse consequences or in significant degradation in the mitigative capability of the plant. The examination team determines if an automatically actuated plant system would have been required to mitigate the consequences of an individual's incorrect performance.
 
If incorrect performance of a task by an individual necessitates the crew taking compensatory action that would complicate the event mitigation strategy, the task is safety significant.
TQ-AA-106-0204 Page 23 of 27 ATTACHMENT 3 CRITICAL TASK METHODOLOGY In reviewing each proposed CT, the examination team assesses the task to ensure, that it is essential to safety. A task is essential to safety if, in the judgment of the examination team, the improper performance or omission of this task by a licensee will result in direct adverse consequences or in significant degradation in the mitigative capability of the plant.
The examination team determines if an automatically actuated plant system would have been required to mitigate the consequences of an individual's incorrect performance. If incorrect performance of a task by an individual necessitates the crew taking compensatory action that would complicate the event mitigation strategy, the task is safety significant.
I. Examples of CTs involving essential safety actions include those for which operation or correct performance prevents ...
I. Examples of CTs involving essential safety actions include those for which operation or correct performance prevents ...
* degradation of any barrier to fission product release
* degradation of any barrier to fission product release
Line 1,655: Line 3,021:
* take one or more actions that would prevent a challenge to plant safety.
* take one or more actions that would prevent a challenge to plant safety.
* prevent inappropriate actions that create a challenge to plant safety (such as an unintentional Reactor Protection System (RPS) or ESF actuation.
* prevent inappropriate actions that create a challenge to plant safety (such as an unintentional Reactor Protection System (RPS) or ESF actuation.
PSEG Restricted  
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 24 of 27 SCENARIO IDENTIFIER:
 
15-01 ILOT NRC ESG-1 REVIEWER:
TQ-AA-106-0204 Page 24 of 27 SCENARIO IDENTIFIER:               15-01 ILOT NRC ESG-1         REVIEWER: C Recchione Initials     Qualitative Attributes CR       1. The scenario has clearly stated objectives in the scenario.
C Recchione Initials CR CR CR CR CR CR CR CR CR CR CR CR 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. Qualitative Attributes The scenario has clearly stated objectives in the scenario.
CR      2. The initial conditions are realistic, in that some equipment and/or instrumentation may be out of service, but it does not cue crew into expected events.
The initial conditions are realistic, in that some equipment and/or instrumentation may be out of service, but it does not cue crew into expected events. The scenario consists mostly of related events. Each event description consists of:
CR      3. The scenario consists mostly of related events.
CR      4. Each event description consists of:
* the point in the scenario when it is to be initiated
* the point in the scenario when it is to be initiated
* the malfunction(s) that are entered to initiate the event
* the malfunction(s) that are entered to initiate the event
* the symptoms/cues that will be visible to the crew
* the symptoms/cues that will be visible to the crew
* the expected operator actions (by shift position)
* the expected operator actions (by shift position)
* the event termination point No more than one non-mechanistic failure (e.g., pipe break) is incorporated into the scenario without a credible preceding incident such as a seismic event. The events are valid with regard to physics and thermodynamics.
* the event termination point CR      5. No more than one non-mechanistic failure (e.g., pipe break) is incorporated into the scenario without a credible preceding incident such as a seismic event.
Sequencing/timing of events is reasonable, and allows for the examination team to obtain complete evaluation results commensurate with the scenario objectives.
CR      6. The events are valid with regard to physics and thermodynamics.
The simulator modeling is not altered. All crew competencies can be evaluated.
CR      7. Sequencing/timing of events is reasonable, and allows for the examination team to obtain complete evaluation results commensurate with the scenario objectives.
The scenario has been validated.
CR      8. The simulator modeling is not altered.
If the sampling plan indicates that the scenario was used for training during the requalification cycle, evaluate the need to modify or replace the scenario.
CR      9. All crew competencies can be evaluated.
ESG-PSA Evaluation Form is completed for the scenario at the applicable facility.
CR      10. The scenario has been validated.
PSEG Restricted  
CR      11. If the sampling plan indicates that the scenario was used for training during the requalification cycle, evaluate the need to modify or replace the scenario.
-Possession Requires Specific Permission from Nuclear Training Initial GG GG GG GG GG GG 3 2 1 2 0 2 TQ-AA-106-0204 Page 25 of 27 Quantitative Attributes (as per ES-301-4, and ES-301 Section 0.5.d) Malfunctions after EOP entry: 1-2 Abnormal Events: 2-4 Major Transients:
CR      12. ESG-PSA Evaluation Form is completed for the scenario at the applicable facility.
1-2 EOPs entered/requiring substantive actions: 1-2 EOP contingencies requiring substantive actions: 0-2 EOP based Critical tasks: 2-3 COMMENTS:
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
PSEG Restricted  
 
-Possession Requires Specific Permission from Nuclear Training 15-01 NRC ESG-1 TQ-AA-106-0204 Page 26 of 27 CT#1 (CT-4) Establish the minimum required feed flow prior to a transition to FRHS-1 being required.
TQ-AA-106-0204 Page 25 of 27 Initial              Quantitative Attributes (as per ES-301-4, and ES-301 Section 0.5.d)
Basis: Failure to establish the required minimum feed flow rate under the postulated plant conditions, results in "adverse consequence(s) or significant degradation in the mitigative capability of the plant." Failure to perform the critical task represents a "demonstrated inability of the crew to: Take an action or combination of actions that would prevent a challenge to plant safety Recognize a failure I incorrect auto actuation of an ESF system or component." CT#2 (CT-6) Establish flow from at least one high-head ECCS pump before transition out of TRIP-1. Basis: Failure to manually start at least one Charging pump under the postulated conditions constitutes misoperation or incorrect crew performance in which the crew does not prevent "degraded emergency core cooling system (ECCS) ... capacity." In this case, at least one Charging/SI pump (high-head SI pump for LP plants) can be manually started from the control room. Therefore, failure to manually start a Charging/SI pump (high-head SI pump for LP plants) also represents a failure by the crew to "demonstrate the following abilities:
GG    3    Malfunctions after EOP entry: 1-2 GG    2    Abnormal Events: 2-4 GG      1  Major Transients: 1-2 GG    2    EOPs entered/requiring substantive actions: 1-2 GG      0  EOP contingencies requiring substantive actions: 0-2 GG    2    EOP based Critical tasks: 2-3 COMMENTS:
Effectively direct or manipulate engineered safety feature (ESF) controls that would prevent a significant reduction of safety margin beyond that irreparably introduced by the scenario Recognize a failure or an incorrect automatic actuation of an ESF system or component" Additionally, under the postulated plant conditions, failure to manually start a Charging/SI pump (high-head SI pump for LP plants) (when it is possible to do so) is a "violation of the facility license condition." Note to Evaluators:
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
CT numbers in parentheses are the corresponding Westinghouse ERG Rev. 2-based Critical Task procedure WCAP-17711-NP PSEG Restricted  
 
-Possession Requires Specific Permission from Nuclear Training ATTACHMENT6:
TQ-AA-106-0204 Page 26 of 27 15-01 NRC ESG-1 CT#1 (CT-4) Establish the minimum required feed flow prior to a transition to FRHS-1 being required.
TQ-AA-106-0204 Page 27 of 27 '* ... ' . ' ESG-PRA EVENTS LEADING TO CORE DAMAGE Y/N Event Y/N Event N TRANSIENTS with PCS Unavailable N Loss of Service Water N Steam Generator Tube Rupture N Loss ofCCW N Loss of Offsite Power N Loss of Control Air N Loss of Switchgear and Pen Area Ventilation N Station Black Out y LOCA COMPONENT/TRAIN/SYSTEM UNAVAILABILITY THAT INCREASES CORE DAMAGE FREQUENCY Y/N COMPONENT, SYSTEM, OR TRAIN Y/N COMPONENT, SYSTEM, OR N Containment Sump Strainers N Gas Turbine N SSWS Valves to Turbine Generator Area N Any Diesel Generator N RHR Suction Line valves from Hot Leg y Auxiliary Feed Pump N CVCS Letdown line Control and Isolation Valves N SBO Air Compressor OPERATOR ACTIONS IMPORTANT IN PREVENTING CORE DAMAGE Y/N OPERATOR ACTION N Restore AC power during SBO N Connect to gas turbine N Trip Reactor and RCPs after loss of component cooling system N Re-align RHR system for re-circulation N Un-isolate the available CCW Heat Exchanger N Isolate the CVCS letdown path and transfer charging suction to RWST N Cooldown the RCS and depressurize the system N Isolate the affected Steam Generator that has the tube rupture(s)
Basis: Failure to establish the required minimum feed flow rate under the postulated plant conditions, results in "adverse consequence(s) or significant degradation in the mitigative capability of the plant."
N Early depressurize the RCS N Initiate feed and bleed Complete this evaluation form for each ESG.
Failure to perform the critical task represents a "demonstrated inability of the crew to:
SCENARIO TITLE: SCENARIO NUMBER: EFFECTIVE DATE: SIMULATOR EXAMINATION SCENARIO GUIDE 15-01 NRC ESG-2 15-01 NRC ESG-2 See Approval Dates EXPECTED DURATION:
Take an action or combination of actions that would prevent a challenge to plant safety Recognize a failure I incorrect auto actuation of an ESF system or component."
60 minutes REVISION NUMBER: PROGRAM: Revision Summary 00 ,___ _ ___,\ LO. REQUAL X \ INITIAL LICENSE ..________,\
CT#2 (CT-6) Establish flow from at least one high-head ECCS pump before transition out of TRIP-1.
ST A New issue for 15-01 !LOT NRC exam PREPARED BY: G Gauding Lead Regulatory Exam Author APPROVED BY: JVivFl raining Manager APPROVED BY: .i.f/LA.ifij aClHty Repre atlve TQ-AA-106-0204 Page 1 of 32 8-3-16 Date (
Basis: Failure to manually start at least one Charging pump under the postulated conditions constitutes misoperation or incorrect crew performance in which the crew does not prevent "degraded emergency core cooling system (ECCS) ... capacity." In this case, at least one Charging/SI pump (high-head SI pump for LP plants) can be manually started from the control room. Therefore, failure to manually start a Charging/SI pump (high-head SI pump for LP plants) also represents a failure by the crew to "demonstrate the following abilities:
4 ate {J)/,, 'Tdate PSEG Restricted  
Effectively direct or manipulate engineered safety feature (ESF) controls that would prevent a significant reduction of safety margin beyond that irreparably introduced by the scenario Recognize a failure or an incorrect automatic actuation of an ESF system or component" Additionally, under the postulated plant conditions, failure to manually start a Charging/SI pump (high-head SI pump for LP plants) (when it is possible to do so) is a "violation of the facility license condition."
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 2 of 32 TQ-AA-106-0204 Page 3 of 32 A. Given a loss of a heater drain pump or condensate pump, take corrective action IAW AB.CN-0001.
Note to Evaluators: CT numbers in parentheses are the corresponding Westinghouse ERG Rev. 2- based Critical Task procedure WCAP-17711-NP PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 27 of 27
                                      '*
ATTACHMENT6:
                                              ...         '       .       '
ESG-PRA     ~ELATIONSHIP: E~A~UATION EVENTS LEADING TO CORE DAMAGE Y/N   Event                                                   Y/N   Event N   TRANSIENTS with PCS Unavailable                           N     Loss of Service Water N   Steam Generator Tube Rupture                             N     Loss ofCCW N   Loss of Offsite Power                                     N     Loss of Control Air N   Loss of Switchgear and Pen Area Ventilation               N     Station Black Out y   LOCA COMPONENT/TRAIN/SYSTEM UNAVAILABILITY THAT INCREASES CORE DAMAGE FREQUENCY Y/N   COMPONENT, SYSTEM, OR TRAIN                             Y/N COMPONENT, SYSTEM, OR TO~lll.I N   Containment Sump Strainers                               N     Gas Turbine N   SSWS Valves to Turbine Generator Area                   N     Any Diesel Generator N   RHR Suction Line valves from Hot Leg                     y     Auxiliary Feed Pump N   CVCS Letdown line Control and Isolation Valves           N     SBO Air Compressor OPERATOR ACTIONS IMPORTANT IN PREVENTING CORE DAMAGE Y/N   OPERATOR ACTION N   Restore AC power during SBO N   Connect to gas turbine N   Trip Reactor and RCPs after loss of component cooling system N   Re-align RHR system for re-circulation N   Un-isolate the available CCW Heat Exchanger N   Isolate the CVCS letdown path and transfer charging suction to RWST N   Cooldown the RCS and depressurize the system N   Isolate the affected Steam Generator that has the tube rupture(s)
N   Early depressurize the RCS N   Initiate feed and bleed Complete this evaluation form for each ESG.
 
TQ-AA-106-0204 Page 1 of 32 SIMULATOR EXAMINATION SCENARIO GUIDE SCENARIO TITLE:                  15-01 NRC ESG-2 SCENARIO NUMBER:                  15-01 NRC ESG-2 EFFECTIVE DATE:                  See Approval Dates EXPECTED DURATION:               60 minutes REVISION NUMBER:                 00 PROGRAM:                       ,____    ___,\ LO. REQUAL X       \ INITIAL LICENSE
                                ..________,\ STA
                                ~-~'OTHER Revision Summary New issue for 15-01 !LOT NRC exam PREPARED BY:                     G Gauding                               8-3-16 Lead Regulatory Exam Author                       Date APPROVED BY:                                     JVivFl raining Manager
("~?late 4
APPROVED BY:
                        ~  aClHty  Repre    ~ .i.f/LA.ifij atlve
{J)/,, IL~
                                                                      'Tdate PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 2 of 32
 
TQ-AA-106-0204 Page 3 of 32 A. Given a loss of a heater drain pump or condensate pump, take corrective action IAW S2.0P-AB.CN-0001.
B. Given the order or indications of a feedwater or condensate system malfunction, perform actions as the nuclear control operator to RESPOND to the malfunction in accordance with S2.0P-AB.CN-0001.
B. Given the order or indications of a feedwater or condensate system malfunction, perform actions as the nuclear control operator to RESPOND to the malfunction in accordance with S2.0P-AB.CN-0001.
C. Given indication of a feedwater or condensate system malfunction, DIRECT the response to the malfunction in accordance with S2.0P-AB.CN-0001.
C. Given indication of a feedwater or condensate system malfunction, DIRECT the response to the malfunction in accordance with S2.0P-AB.CN-0001.
D. Given a steam generator tube leak, take corrective action, IAW S2.0P-AB.SG-0001.
D. Given a steam generator tube leak, take corrective action, IAW S2.0P-AB.SG-0001.
E. Given the order or indications of a steam generator tube leak (SGTL), perform actions as the nuclear control operator to RESPOND to the tube leak in accordance with S1/S2.0P-AB.SG-0001. F. Given the order or indications of a steam generator tube leak (SGTL), DIRECT the response to the tube leak, in accordance with S2.0P-AB.SG-0001.
E. Given the order or indications of a steam generator tube leak (SGTL), perform actions as the nuclear control operator to RESPOND to the tube leak in accordance with S1/S2.0P-AB.SG-0001.
F. Given the order or indications of a steam generator tube leak (SGTL), DIRECT the response to the tube leak, in accordance with S2.0P-AB.SG-0001.
G. Given the order or indications of a reactor trip, perform actions as the nuclear control operator to RESPOND to the reactor trip in accordance with 2-EOP-TRIP-1.
G. Given the order or indications of a reactor trip, perform actions as the nuclear control operator to RESPOND to the reactor trip in accordance with 2-EOP-TRIP-1.
H. Given indication of a reactor trip, DIRECT the response to the reactor trip in accordance with 2-EOP-TRIP-1.
H. Given indication of a reactor trip, DIRECT the response to the reactor trip in accordance with 2-EOP-TRIP-1.
Line 1,696: Line 3,084:
K. Given the order or indications of a steam generator tube rupture (SGTR), perform actions as the nuclear control operator to RESPOND to the tube rupture in accordance with the approved station procedures.
K. Given the order or indications of a steam generator tube rupture (SGTR), perform actions as the nuclear control operator to RESPOND to the tube rupture in accordance with the approved station procedures.
L. Given indication of a steam generator tube rupture (SGTR), DIRECT the response to the SGTR in accordance with the approved station procedures.
L. Given indication of a steam generator tube rupture (SGTR), DIRECT the response to the SGTR in accordance with the approved station procedures.
A. 2C EDG Pre-lube pump failure (TS) B. 23 Condensate pump trip /Power Reduction C. 21 SGTL I 21 SGTR D. Loss of Spray during RCS depressurization E. Stuck open PZR PORV during RCS depressurization PSEG Restricted  
A. 2C EDG Pre-lube pump failure (TS)
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 4 of 32 A. The crew will take the watch with the unit at 89.4% power, BOL. Power was reduced last shift in preparation for performing Main Turbine Valve testing later this shift. 2C EOG Jacket Water heater failed last shift. Condensate Polisher is in service. B. After the crew assumes the watch, the 2C EOG Pre-lube pump will fail. The CRS will identify 2C EOG is now inoperable, and enter the appropriate LCO. The CRS will initiate actions to ensure S2.0P-ST.500-0001, Electrical Power Systems AC Sources Alignment is performed within one hour. C. After the EOG failure has been addressed, 23 Condensate pump will trip. The crew will enter S2.0P-AB.CN-0001, Main Feedwater I Condensate System Abnormality, and perform actions to bypass the polisher and feedwater heaters strings as required to maintain SGFP suction pressure.
B. 23 Condensate pump trip /Power Reduction C. 21 SGTL I 21 SGTR D. Loss of Spray during RCS depressurization E. Stuck open PZR PORV during RCS depressurization PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
D. The crew will perform a power reduction 85% power and ensure SGFP suction pressure remains above 320 psig. E. During the power reduction, a SGTL will occur on 21 SG. The crew will enter S2.0P-AB.SG-0001, Steam Generator Tube Leak. The crew will perform actions to minimize the spread of secondary contamination and minimize the potential for steam release from the affected SG. The crew will isolate the steam supply to 23 AFW pump from 21 SG, and the CRS will identify 23 AFW is inoperable and enter the appropriate LCO. F. After the AFW pump LCO is identified, the SG tube will rupture. The crew will identify the SGTR, and initiate a Rx trip and Safety Injection based on the uncontrolled rise in 21 SG NR or WR level. G. The crew will perform plant stabilization and diagnostics in EOP-TRIP-1, Reactor Trip or Safety Injection.
21 AFW pump will trip shortly after starting.
The crew will isolate AFW flow to and steam flow from 21 SG. (CT-1 ). H. The crew will transition to EOP-SGTR-1, Steam Generator Tube Rupture to address the tube rupture. The crew will perform a cooldown to target temperature and demonstrate the ability to maintain RCS temperature<
Target temperature (CT-2). The crew will initiate a RCS depressurization.
During the depressurization the RCP providing driving head for Spray flow will trip. The crew will open a PZR PORV to continue the depressurization.
If 2PR1 is the selected PORV, it will not open, and 2PR2 will be used. I. The PZR PORV opened to depressurize the RCS will fail to shut when demanded after the depressurization is complete.
The crew will attempt to terminate the depressurization by closing the PORV Block valve, which will not shut. J. The scenario will be terminated after the CRS transitions to EOP-SGTR-3, SGTR with LOCA -Subcooled Recovery, to address the loss of RCS pressure with the stuck open PORV. PSEG Restricted
-Possession Requires Specific Permission from Nuclear Training IC-232 TQ-AA-106-0204 Page 5 of 32 ,, PREP computer ,tagged equipment)
Initial I Description 1 VC1 and VC4 CIT 2 RCPs (SELF CHECK) _ 3 RTBs (SELF CHECK) _ 4 MS167s (SELF CHECK) _ 5 500 KV SWYD (SELF CHECK) _ 6 SGFP Trip (SELF CHECK) _ 7 23 CV PP (SELF CHECK) 8 Complete Attachment 2 "Simulator Ready-for-Training/Examination Checklist." Note: Tables with blue headings may be populated by external program, do not change column name without consulting Simulator Support group PSEG Restricted
-Possession Requires Specific Permission from Nuclear Training SELF-CHECK 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 CHECK 01 Description
------TQ-AA-106-0204 Page.6 of 32 EVENT ACTION: MONP254 <10. //CONTROL BANK C GROUP POSITION 1 COMMAND: PURPOSE: <update as needed> ---EVENT ACTION: KB202LCI //2PR7 RELIEF VALVE-22 STOP VALVE 3 COMMAND: PURPOSE: <update as needed> Description AN0266 SER 266 FAILS -:J20 2C DIESEL GENERATOR URGENT TROUBLE CN0117C 23 CONDENSATE PUMP TRIP SG0078A 21 STEAM GENERATOR TUBE RUPTURE AN3735 AAS 735 FAILS -:21 TGA SUMP LEVEL HIGH AN3736 AAS 736 FAILS -:22 TGA SUMP LEVEL HIGH AN3737 AAS 737 FAILS -:23 TGA SUMP LEVEL HIGH AN3738 AAS 738 FAILS -:24 TGA SUMP LEVEL HIGH AN3739 AAS 739 FAILS -:25 TGA SUMP LEVEL HIGH AF0181A 21 AUX FEEDWATER PUMP TRIP VL0297 2PR1 Fails to Position 0-100%) VL0298 2PR2 Fails to Position 0-100% RC0003C 23 RC PUMP ELECTRICAL TRIP RC0003A 21 RC PUMP ELECTRICAL TRIP VL0123 2PR7 Fails to Position ( 0-100%) CV0035 CHRG MASTER FLO CNTRLR FAILS H/L Description SP01A1 Prevailing Wind Speed Delay Time N/A N/A N/A 00:03:00 00:03:10 00:03:20 00:03:30 00:03:50 00:04:00 NIA NIA N/A NIA NIA N/A Delay Time NIA Initial Value N/A NIA NIA N/A N/A N/A N/A N/A NIA N/A N/A NIA NIA NIA NIA Initial Value NIA Ramp Time N/A NIA N/A N/A NIA N/A N/A NIA N/A N/A N/A NIA N/A NIA t'11A Ramp Time NIA Trigger RT-1 RT-3 RT-5 RT-11 RT-11 RT-11 RT-11 RT-11 ET-1 N/A RT-13 RT-7 RT-9 ET-3 RT-15 Trigger NIA PSEG Restricted
-Possession Requires Specific Permission from Nuclear Training Severity SER POINT FAILS/OVRD TOON 5 AAS POINT FAILS/OVRD TOON AAS POINT FAILS/OVRD TOON AAS POINT FAILS/OVRD TOON AAS POINT FAILS/OVRD TOON AAS POINT FAILS/OVRD TOON 0 100 90 26 Condition 10 02 CHECK 01 GP01A2 Prevailing Wind Direction Description C201 A LO QC201AY3 2C DIESEL GEN-TROUBLE ALARM Description
: 1. None NIA Delay Time N/A Initial Value NIA NIA Ramp Time NIA TQ-AA-106-0204 Page 7 of 32 Trigger Condition/
Severity NIA ON PSEG Restricted
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 8 of 32 \j\1,i ' "'---*<gq A. State shift job assignments.
B. Hold a shift briefing, detailing instruction to the shift: (provide crew members a copy of the shift turnover sheet). C. Inform the crew "The simulator is running. You may commence panel walkdowns at this time. CRS please inform me when your crew is ready to assume the shift". D. Allow sufficient time for panel walk-downs.
When informed by the CRS that the crew is ready to assume the shift, ensure the simulator is cleared of unauthorized personnel.
PSEG Restricted
-Possession Requires Specific Permission from Nuclear Training


Activ'lty  
TQ-AA-106-0204 Page 4 of 32 A. The crew will take the watch with the unit at 89.4% power, BOL. Power was reduced last shift in preparation for performing Main Turbine Valve testing later this shift. 2C EOG Jacket Water heater failed last shift. Condensate Polisher is in service.
... .,Y':, *, j  
B. After the crew assumes the watch, the 2C EOG Pre-lube pump will fail. The CRS will identify 2C EOG is now inoperable, and enter the appropriate LCO. The CRS will initiate actions to ensure S2.0P-ST.500-0001, Electrical Power Systems AC Sources Alignment is performed within one hour.
> . , ", d,
C. After the EOG failure has been addressed, 23 Condensate pump will trip. The crew will enter S2.0P-AB.CN-0001, Main Feedwater I Condensate System Abnormality, and perform actions to bypass the polisher and feedwater heaters strings as required to maintain SGFP suction pressure.
: 1. 2C EOG Pre-Lube pump failure Simulator Operator:
D. The crew will perform a power reduction to~ 85% power and ensure SGFP suction pressure remains above 320 psig.
Insert RT-1 oh direction from Lead.Evaluator. .MALF: lAN0266 SER,266 Fails;...
E. During the power reduction, a SGTL will occur on 21 SG. The crew will enter S2.0P-AB.SG-0001, Steam Generator Tube Leak. The crew will perform actions to minimize the spread of secondary contamination and minimize the potential for steam release from the affected SG.
J20 GENERATOR::
The crew will isolate the steam supply to 23 AFW pump from 21 SG, and the CRS will identify 23 AFW is inoperable and enter the appropriate LCO.
URGENT TROUBLE Role play: 2 minutes after being dispatched call control room and report 2C EOG Alarm Window A-7 PRE-LUBE PUMP FAILURE is in alarm. You have checked the lube pump and it is NOT running. The Pre-lube pump breaker remains shut.
F. After the AFW pump LCO is identified, the SG tube will rupture. The crew will identify the SGTR, and initiate a Rx trip and Safety Injection based on the uncontrolled rise in 21 SG NR or WR level.
* ! ;. ;,HJ 7,r,. i1#'' 1 . . ;tt .. > . ; ;;,1lN: * .. . *. PO announces unexpected OHA J-20, 2C DG URGENT TRBL. The crew refers to the ARP and dispatches an operator to investiaate.
G. The crew will perform plant stabilization and diagnostics in EOP-TRIP-1, Reactor Trip or Safety Injection. 21 AFW pump will trip shortly after starting. The crew will isolate AFW flow to and steam flow from 21 SG. (CT-1 ).
CRS refers to S2.0P-SO.DG-0003, 2C Diesel Generator Operation and recognizes 2C EOG is now inoperable with the Jacket Water Heater and Pre-lube pump inoperable, and enters LCO 3.8.1.1.b, action b. CRS determines that S2.0P-ST.500-0001, Electrical Power Systems AC Sources Alianment must be oerformed within one hour PSEG Restricted  
H. The crew will transition to EOP-SGTR-1, Steam Generator Tube Rupture to address the tube rupture. The crew will perform a cooldown to target temperature and demonstrate the ability to maintain RCS temperature< Target temperature (CT-2). The crew will initiate a RCS depressurization. During the depressurization the RCP providing driving head for Spray flow will trip. The crew will open a PZR PORV to continue the depressurization. If 2PR1 is the selected PORV, it will not open, and 2PR2 will be used.
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 9 of 32 comment****
I. The PZR PORV opened to depressurize the RCS will fail to shut when demanded after the depressurization is complete. The crew will attempt to terminate the depressurization by closing the PORV Block valve, which will not shut.
E\(alii'atofl:ln:stiuctor ActivltY,;  
J. The scenario will be terminated after the CRS transitions to EOP-SGTR-3, SGTR with LOCA -
.. . ExReCted PlanflStudent,Response c" .* ;J 1?s'er ,,, '.  
Subcooled Recovery, to address the loss of RCS pressure with the stuck open PORV.
! iJ.:;,:.li> ,  
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
.. t
 
_ *. ,  
TQ-AA-106-0204 Page 5 of 32 IC-232
.';**?:-
                                                                    ,,
1 <:?; -
PREP    FOR<TRAINl~G (i.e,~ computer setpoint~~,proc~dure!), l:>~zel C()V~~s ,tagged equipment)
zf LoG. Proceed to next event on direction from Lead Evaluator.
Initial I Description 1 VC1 and VC4 CIT 2 RCPs (SELF CHECK)
: 2. 23 Condensate pump trip I down power Simulator Operator:
_      3 RTBs (SELF CHECK)
Insert RT-3 on dfrection from Lead Evaluator.
_      4 MS167s (SELF CHECK)
1 MALF:CN0117C 23 Condensate pump trip* Role Play: If dispatched, after 3 minutes report as NEO that you can't see anything wrong with 21 condensate pump. If dispatched to 4KV breaker, report after 2 minutes that there is an overcurrent relay flag dropped. to demonstrate the operability of the independent AC Sources (action b.1) PO announces 23 Condensate pump trip. CRS enters S2.0P-AB.CN-0001, Main Feedwater I Condensate System Abnormality.
_      5 500 KV SWYD (SELF CHECK)
PO reports no SGFP tripped. PO reports 23 Condensate pump tripped. PO bypasses condensate polisher by opening 21 thru 23 CN108 if SGFP suction pressure is <320 psiQ. PSEG Restricted  
_      6 SGFP Trip (SELF CHECK)
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 10 of 32 Commeot 1 t 1 ,. * 
_      7 23 CV PP (SELF CHECK) 8 Complete Attachment 2 "Simulator Ready-for-Training/Examination Checklist."
. J;yaluat0rl1fistr4c(orActivity . .
Note: Tables with blue headings may be populated by external program, do not change column name without consulting Simulator Support group PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
* Response . ,;  
 
,, , ''.  
TQ-AA-106-0204 Page.6 of 32 Description
*: ,', , ,  
              - -~*        - -                                              -        --
,,c Note: Crew should discuss power increase expected when the CN47 is opened. (Note in AB.CN-1 ). 3. Master Flow Controller failure I Simulator Operator:
EVENT ACTION:            MONP254 <10. //CONTROL BANK C GROUP POSITION 1          COMMAND:
Once the PO reports SGFP suction pressure.
PURPOSE:        <update as needed>
CRS directs 2CN47 opened if suction pressure remains< 320 psig. PO isolates letdown by closing 21-24BG4 and 21-24GB185 if 2CN47 is open. CRS directs power reduction to 85% at with 2 Condensate pumps and 3 Heater Drain pumps in service IAW Attachment
                                                    -              -      -
: 4. CRS enters S2.0P-AB.LOAD-0001, Rapid Load Reduction, to perform the load reduction.
EVENT ACTION:            KB202LCI //2PR7 RELIEF VALVE-22 STOP VALVE 3          COMMAND:
CRS directs initiation of AB.LOAD CAS. RO calculates boron addition and rate for power reduction.
PURPOSE:        <update as needed>
SELF-      Description                                      Delay    Initial  Ramp      Trigger    Severity CHECK                                                      Time    Value      Time SER POINT AN0266 SER 266 FAILS - :J20 2C DIESEL 01                                                    N/A      N/A      N/A      RT-1    FAILS/OVRD GENERATOR URGENT TROUBLE TOON 02  CN0117C 23 CONDENSATE PUMP TRIP                  N/A      NIA      NIA      RT-3 03  SG0078A 21 STEAM GENERATOR TUBE RUPTURE          N/A      NIA      N/A      RT-5          5 AAS POINT 04  AN3735 AAS 735 FAILS - :21 TGA SUMP LEVEL HIGH  00:03:00  N/A      N/A      RT-11    FAILS/OVRD TOON AAS POINT 05  AN3736 AAS 736 FAILS - :22 TGA SUMP LEVEL HIGH  00:03:10  N/A      NIA      RT-11    FAILS/OVRD TOON AAS POINT 06  AN3737 AAS 737 FAILS - :23 TGA SUMP LEVEL HIGH  00:03:20  N/A      N/A      RT-11    FAILS/OVRD TOON AAS POINT 07  AN3738 AAS 738 FAILS - :24 TGA SUMP LEVEL HIGH  00:03:30  N/A      N/A      RT-11    FAILS/OVRD TOON AAS POINT 08  AN3739 AAS 739 FAILS - :25 TGA SUMP LEVEL HIGH  00:03:50  N/A      NIA      RT-11    FAILS/OVRD TOON 09  AF0181A 21 AUX FEEDWATER PUMP TRIP              00:04:00  NIA      N/A        ET-1 10  VL0297 2PR1 Fails to Position  0-100%)          NIA      N/A      N/A        N/A          0 11  VL0298 2PR2 Fails to Position 0-100%              NIA      N/A      N/A      RT-13        100 12  RC0003C 23 RC PUMP ELECTRICAL TRIP                N/A      NIA      NIA      RT-7 13  RC0003A 21 RC PUMP ELECTRICAL TRIP                NIA      NIA      N/A      RT-9 14  VL0123 2PR7 Fails to Position ( 0-100%)          NIA      NIA      NIA        ET-3        90 15  CV0035 CHRG MASTER FLO CNTRLR FAILS H/L          N/A      NIA      t'11A    RT-15        26 SELF-      Description                                      Delay  Initial    Ramp      Trigger  Condition CHECK                                                      Time    Value      Time 01  SP01A1 Prevailing Wind Speed                      NIA      NIA      NIA        NIA          10 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 7 of 32 02  GP01A2 Prevailing Wind Direction            NIA        N/A      NIA SELF-      Description                              Delay    Initial  Ramp      Trigger  Condition/
CHECK                                                Time      Value      Time              Severity C201 A LO QC201AY3 2C DIESEL GEN-TROUBLE 01                                                        NIA      NIA      NIA      ON ALARM Description
: 1. None PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 8 of 32
\j\1,i '"'--
    -*<gq A. State shift job assignments.
B. Hold a shift briefing, detailing instruction to the shift: (provide crew members a copy of the shift turnover sheet).
C. Inform the crew "The simulator is running. You may commence panel walkdowns at this time.
CRS please inform me when your crew is ready to assume the shift".
D. Allow sufficient time for panel walk-downs. When informed by the CRS that the crew is ready to assume the shift, ensure the simulator is cleared of unauthorized personnel.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 9 of 32
  ,.lEva'u~tptr11il'structor Activ'lty ...                                             {~:~'Exp,~te~"'plawnt/Stu~1enf R~!e#fise
* comment****
.,Y':, *,     )~i j c:~,f,~4 > ~', ~?:/,'>;*~, ;',:;,~L,~, ~= ~, . , ", d, ,_.~,
                                                                                        ! ;. ;,HJ 7,r,. i1#'' 1. . ;tt .> . ; ;;,1lN: *.. . *.
: 1. 2C EOG Pre-Lube pump failure Simulator Operator: Insert RT-1 oh direction from Lead.Evaluator.
.MALF: lAN0266 SER,266 Fails;...
J20 2C~DlESEL GENERATOR::
URGENT TROUBLE PO announces unexpected OHA J-20, 2C DG URGENT TRBL.
The crew refers to the ARP and dispatches an operator to investiaate.
Role play: 2 minutes after being dispatched call control room and report 2C EOG Alarm Window A-7 PRE-LUBE PUMP FAILURE is in alarm. You have checked the Pre-lube pump and it is NOT running.
The Pre-lube pump breaker remains shut.
CRS refers to S2.0P-SO.DG-0003, 2C Diesel Generator Operation and recognizes 2C EOG is now inoperable with the Jacket Water Heater and Pre-lube pump inoperable, and enters LCO 3.8.1.1.b, action b.
CRS determines that S2.0P-ST.500-0001, Electrical Power Systems AC Sources Alianment must be oerformed within one hour PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 10 of 32
      ~.* E\(alii'atofl:ln:stiuctor ActivltY,; .                 .ExReCted PlanflStudent,Response c" .* ;J 1?s'er                       Commeot1t          1
                                                                                                                                                                ,. *
  , , '. *:~~i~ ~r;;* *~.*rt ! iJ.:;,:.li> ;<ii~; ,   -~,-k  . t ~>>~gJ~~i\1f _*. , .:i1~:'** .';**?:- *,P~*~;;;: 1<:?; - :J~~~ zf LoG. ,,;~t~k ~,:~~TI:-; -~
to demonstrate the operability of the independent AC Sources (action b.1)
Proceed to next event on direction from Lead Evaluator.
: 2. 23 Condensate pump trip I down power Simulator Operator: Insert RT-3 on dfrection from Lead Evaluator.
1 MALF:CN0117C 23 Condensate pump trip*
PO announces 23 Condensate pump trip.
CRS enters S2.0P-AB.CN-0001, Main Feedwater I Condensate System Abnormality.
PO reports no SGFP tripped.
PO reports 23 Condensate pump tripped.
PO bypasses condensate polisher by opening 21 thru 23 CN108 if SGFP suction pressure is
                                                            <320 psiQ.
Role Play: If dispatched, after 3 minutes report as NEO that you can't see anything wrong with 21 condensate pump. If dispatched to 4KV breaker, report after 2 minutes that there is an overcurrent relay flag dropped.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 11 of 32
  . J;yaluat0rl1fistr4c(orActivity ~
* Expec!id;~1ant1~tudent Response .
* Comment1f!t:
  ,; J\t~t, , , '. ':::Y~~>ilZ,r *:  ,'~ ,',
                                              ..
                                              *;:7~~  , , ,'*ltc;;,;hf1t~ ,;'~*:, i~l~'., ,c '~~~,' +1~,*:~g~;
PO reports SGFP suction pressure.
Note: Crew should discuss power increase expected when the CN47 is opened. (Note in AB.CN-1 ).
CRS directs 2CN47 opened if suction pressure remains< 320 psig.
PO isolates letdown by closing 21-24BG4 and 21-24GB185 if 2CN47 is open.
CRS directs power reduction to 85% at
                                                  ~5%/min        with 2 Condensate pumps and 3 Heater Drain pumps in service IAW Attachment 4.
CRS enters S2.0P-AB.LOAD-0001, Rapid Load Reduction, to perform the load reduction.
CRS directs initiation of AB.LOAD CAS.
RO calculates boron addition and rate for power reduction.
RO initiates boration.
RO initiates boration.
PO initiates turbine load reduction to 85% at rate directed by CRS.
PO initiates turbine load reduction to 85% at rate directed by CRS.
PSEG Restricted  
: 3. Master Flow Controller failure I Simulator Operator: Once the PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 11 of 32
 
* Comment1f!t:  
TQ-AA-106-0204 Page 12 of 32
.
                  .~.~~?~tivi,,f        *
* Expe'eted~planOStudent Res~onse'.*
* mment . f;w
                                              ,': tr r~' ' :t' ,, ~,{]~~;'.' , !;:( ' ;;,!~' / ,                    ;,, )',
power reduction is underway, insert RT-15 to fail the. Master F.low Controller.
power reduction is underway, insert RT-15 to fail the. Master F.low Controller.
MALF: CV0035' CHRG Master Flow Controller fails H/L .... Severitv:
MALF: CV0035' CHRG Master Flow Controller fails H/L . .
26 * * * **  
Severitv: 26 **
** ,': tr ' :t' ,, , !;:( '
RO reports unexpected low seal injection flow alarms on all RCP's.
/ , RO reports unexpected low seal injection flow alarms on all RCP's. RO reports Master Flow Controller is failed based on lower than expected Charging flow 75 apm vs 87 aom CRS enters S2.0P-AB.CVC-0001, Loss of Charaina.
RO reports Master Flow Controller is failed based on lower than expected Charging flow 75 apm vs 87 aom CRS enters S2.0P-AB.CVC-0001, Loss of Charaina.
RO may use Alarm Response Procedure initially in response to Low Seal Injection Flow to adjust 2CV71 to restore seal injection flow to above the alarm setpoint, but this will not restore normal charaina flow. RO reports: -A charging pump is running with no indication of cavitation RO reports neither a PZR level nor a VCT level channel has failed. No indication of charaina svstem leak RO reports the Charging Master Flow Controller has failed. RO takes manual control of 23 charain PSEG Restricted  
RO may use Alarm Response Procedure initially in response to Low Seal Injection Flow to adjust 2CV71 to restore seal injection flow to above the alarm setpoint, but this will not restore normal charaina flow.
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 12 of 32 mment . f;w ;,, )',
RO reports:
TQ-AA-106-0204 Page 13 of 32 ccfmme'nf  
                                      - A charging pump is running with no indication of cavitation RO reports neither a PZR level nor a VCT level channel has failed.
* **
No indication of charaina svstem leak RO reports the Charging Master Flow Controller has failed.
* s \j .* !* *.di?/ ::/ r:r, ff .:.I'' *; ;xtfi.ffil,&.&sect;'LUl:i J/}., ,,f; pump, and adjusts speed to maintain PZR level on proqram IAW Att. 2. RO reports PZR level can be maintained stable or rising. RO announces auto rod motion when it occurs. Proceed to next event on direction from Lead Evaluator.
RO takes manual control of 23 charain PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
: 4. 21 SG Tube Leak Simulator Operator; Insert RT-5 on direction from Lead evaluator.  
 
.* MALF: SG00078A 21 STEAM .GENERATOR TUBE RUPTURE Severity:
TQ-AA-106-0204 Page 13 of 32 ccfmme'nf *   *
5 ; RO reports unexpected OHA A-6 and identifies 2R53A 21 Main Steamline N2 monitor from CRT indication in alarm. RO reports 2R53A level >1000 qpd. CRS enters S2.0P-AB.SG-0001, Steam Generator Tube Leak, and S2.0P-AB.RAD-0001, Abnormal Radiation.
* s   \j .* !* *.di?/ ::/ r:r, .~0* ff .:.I'' *; ;xtfi.ffil,&.&sect;'LUl:i ';r~l\1".*
RO reports OHA A-6 reflash is 2R15 Condenser Air Ejector monitor in alarm. CRS directs initiation of AB.SG CAS. PSEG Restricted  
J/}., ,,f; pump, and adjusts speed to maintain PZR level on proqram IAW Att. 2.
-Possession Requires Specific Permission from Nuclear Training
RO reports PZR level can be maintained stable or rising.
**1i;Evalqator/1nstructor J(ct1v1fy:i!f!!!J;.  
RO announces auto rod motion when it occurs.
<' ';f.:d.i', n
Proceed to next event on direction from Lead Evaluator.
.. , ,, .... * ,; ,
: 4. 21 SG Tube Leak Simulator Operator; Insert RT-5 on direction from Lead evaluator.
* ExnecteCl
.* MALF: SG00078A 21 STEAM
.. 0 fant/student "l , c  
  .GENERATOR TUBE RUPTURE Severity: 5         ;
* , , , sar: ,,,, ;::t'' *.. ...*  
RO reports unexpected OHA A-6 and identifies 2R53A 21 Main Steamline N2 monitor from CRT indication in alarm.
,;'c ,.* . ** ..*... -*-._.,,c, *:W ' RO reports when 2R 19A is in warning and alarm. PO reports when SGBD isolation occurs on hiqh radiation.
RO reports 2R53A level >1000 qpd.
CRS dispatches operator to isolate TGA and Condensate Polisher area sump pumps. Simulator Operator:.
CRS enters S2.0P-AB.SG-0001, Steam Generator Tube Leak, and S2.0P-AB.RAD-0001, Abnormal Radiation.
When dispatched to.* isolatetf GA and polisher building sum'ps, insert RT-,11. This deenergizes 21 :25 TGA sump pumps after a 3 minute time delay. RO reports PZR level being maintained stable by risinq charqinq flow. Note: Initial charging flow with stable PZR level is -89 gpm. 23 charging pump will deliver -99 gpm at full flow and seal injection of -26 gpm. IF RO reports PZR level is lowering (due to lag in Master Flow control response,)
RO reports OHA A-6 reflash is 2R15 Condenser Air Ejector monitor in alarm.
then RO will swap to a centrifugal charging pump at Step 3.6. RO reports PZR level can be maintained stable or risinq. Note: SGBD will isolate -2.5 minutes after 2R53D alarms. This PSEG Restricted  
CRS directs initiation of AB.SG CAS.
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 14 of 32 '
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
* E\/alUator11nstn.ictor ActNitY ;,I ,j,J;;,
 
will cause RCS temp and PZR level to rise. Note: Do NOT report the 21 MS45 is shut until AFTER 23 AFW pump has been tripped at step 4. 7 of SGTR-1. Proceed to next event on direction from Lead Evaluator after Tech Specs have been addressed.
TQ-AA-106-0204 Page 14 of 32
  **1i;Evalqator/1nstructor
              <'            n J(ct1v1fy:i!f!!!J;.               *ExnecteCl,fr>..~*.
                                                                                                              . 0 fant/student Rijsp''o1lae'.l11:*.~~*.***
                                                                                                          , N.r:~::            *      ,        :,~~~>>' ,,
sar:
                                                                                                                                                            ,,,,                  ' if~-~
                                                                                                                                          ..*...
b,f';;~*:J    ';f.:d.i',   ~.,.Zd .. , .~~.c0 ''      ,,   .... *     ,; ,       "l                 c
                              ;::t''                         *.. ,.~ ...*       ~***  ,;'c ,.*                     **. **                              -*- ._.,,c, *:W '
RO reports when 2R 19A is in warning and alarm.
PO reports when SGBD isolation occurs on hiqh radiation.
CRS dispatches operator to isolate TGA and Condensate Polisher area sump pumps.
Simulator Operator:. When dispatched to.* isolatetfGA and polisher building sum'ps, insert RT-
,11. This deenergizes 21 :25 TGA sump pumps after a 3 minute time delay.
RO reports PZR level being maintained stable by risinq charqinq flow.
Note: Initial charging flow with stable PZR level is -89 gpm. 23 charging pump will deliver -99 gpm at full flow and seal injection of -26 gpm. IF RO reports PZR level is lowering (due to lag in Master Flow control response,) then RO will swap to a centrifugal charging pump at Step 3.6.
RO reports PZR level can be maintained stable or risinq.
Note: SGBD will isolate -2.5 minutes after 2R53D alarms. This PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 15 of 32
  *E\/alUator11nstn.ictor ActNitY                                                                                         comment:"'*            *
    ;,I <~~rj~'f *;;~:-, ,j,J;;, ,~.J~~t~,-                                                                                      ,"~
                                                                                                                              ~wr  -,
will cause RCS temp and PZR level to rise.
PO reports when load reduction is complete.
PO reports when load reduction is complete.
RO reports unit 2 is in MODE 1. RO reports 21 SG is affected SG. PO sets 21MS10 to 1045 psig, and ensures 21GB4, 21MS18, and 21MS7 are shut. CRS dispatches an operator to shut 21 MS45 steam supply to 23 AFW pump. CRS enters LCO 3. 7 .1.2 for less than 3 operable AFW pumps, and LCO 3.4.7.2.c for >150 gpd primary to secondary leakage though 21 SG. CRS determines (Action Level 3) the unit must be less than 50% in less than one hour, the unit placed in Hot Standby within 6 hours. CRS dispatches an operator to realign SGBD and Samplinq.
RO reports unit 2 is in MODE 1.
PSEG Restricted  
RO reports 21 SG is affected SG.
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 15 of 32 comment:"'*
PO sets 21MS10 to 1045 psig, and ensures 21GB4, 21MS18, and 21MS7 are shut.
** -, 
CRS dispatches an operator to shut 21 MS45 steam supply to 23 AFW pump.
'eva1 '';Jr Ai ... 5. SGTR Simulator Operator:
Note: Do NOT report the 21 MS45 is shut until AFTER 23 AFW pump has been tripped at step 4. 7 of SGTR-1.
MODIFY . MALF SG00078A from 5 to 650 on direction from Lead Evaluator.
CRS enters LCO 3. 7 .1.2 for less than 3 operable AFW pumps, and LCO 3.4.7.2.c for
Simulator Operator:
                                                  >150 gpd primary to secondary leakage though 21 SG.
Ensure ET*1 is true when the* rx is tripped., This trips 21 AFW pump after a 4 minute delay. CT#1 (CT-18) Isolate feed flow into (oart 1) and steam flow from e** d 1]>1ant1Student R, RO reports indications of worsening tube leak/rupture, with lowering PZR level and pressure.
CRS determines (Action Level 3) the unit must be less than 50% in less than one hour, the unit placed in Hot Standby within 6 hours.
CRS directs RO to trip the Rx, confirm the Rx trip, and initiate a Safety Injection, then enter TRIP-1. RO trips the Rx, confirms the Rx trip, and initiates Safety Injection.
CRS dispatches an operator to realign SGBD and Samplinq.
Proceed to next event on direction from Lead Evaluator after Tech Specs have been addressed.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 16 of 32
    'eva1   '';Jr         Ai ...               e**      d1]>1ant1Student R,              SBT                  *;;~rc~:0,1m~~~,;~r**
: 5. SGTR Simulator Operator: MODIFY
. MALF SG00078A from 5 to 650 on direction from Lead Evaluator.
RO reports indications of worsening tube leak/rupture, with lowering PZR level and pressure.
CRS directs RO to trip the Rx, confirm the Rx trip, and initiate a Safety Injection, then enter TRIP-1.
RO trips the Rx, confirms the Rx trip, and initiates Safety Injection.
Simulator Operator: Ensure ET*1 is true when the* rx is tripped., This trips 21 AFW pump after a 4 minute delay.
RO backs up the Main Turbine trip, reports 4KV vital buses energized, and reports SI manually initiated.
RO backs up the Main Turbine trip, reports 4KV vital buses energized, and reports SI manually initiated.
CRS and RO verify TRIP-1 immediate actions. PO receives CRS concurrence and isolates AFW to 21 SG by closing 21AF11 and 21AF21. SBT TQ-AA-106-0204 Page 16 of 32
CRS and RO verify TRIP-1 immediate actions.
* PSEG Restricted
PO receives CRS concurrence and isolates AFW to 21 SG by closing 21AF11 and 21AF21.
-Possession Requires Specific Permission from Nuclear Training (part 2) 21SG prior to a transition to SGTR-3 being required .. (steamflow isolation will be on page 19) Part*1 SAT --UNSAT __ 6. 21 AFW pump trip Note: 21 AFW pp supplies 23/24 SGs 22 AFW pp supplies 21/22 SGs 23 AFW pump supplies all SGs Simulator Operator:
CT#1 (CT-18) Isolate feed flow into (oart 1) and steam flow from PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
Use
 
* REMOTE AF20 to OFF 2 minutes after being dispatched to remove ** control power from 21 AFW pump breaker. * ..
TQ-AA-106-0204 Page 17 of 32
* ** <' :7,&#xa3;}: , ;, _'*'' .
                                        *. E~pected Pliint/s~&#xb5;aenf Res~onse **
'
                                          <' :7,&#xa3;}: '~' , ;, _'*' . ~t00,,', ' ;~f~:~;- '
' PO receives CRS concurrence and reduces total AFW flow to no less than 22E04 lbm/hr until at least one SG NR level is> 9%, then maintains NR levels 19-33%. PO reports when 21 AFW pump trips, and adjusts flow from 22 and 23 AFW pumps as reauired based on current SG NR levels. PO reports all available equipment started on SEC loadina. PO reoorts which AFW oumps are runnin PSEG Restricted  
                                                                                                              .Co~;;",~:!~~if!I ~:: iiw,*1"'**
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 17 of 32 . ! iiw,*1"'**
                                                                                                                                  !          ,
' *Evaluator/f nsln1ctor
(part 2) 21SG prior to a transition to SGTR-3 being required ..(steamflow isolation will be perform~~ on page 19)
-_,,,,>AL ,  
Part*1 UNSAT_ _
,,,,, ,
SAT
* Pla'nt/Studenf Response $BT .. ' .. . PO reports correct safeguards valve alignment.
    --
RO reports 21 and 22CA330s are shut. RO reports containment pressure remains less than 15 psig. PO reports no indication of hi steam flow. PO reports all 4KV vital buses enerqized.
PO receives CRS concurrence and reduces total AFW flow to no less than 22E04 lbm/hr until at least one SG NR level is> 9%, then maintains NR levels 19-33%.
: 6. 21 AFW pump trip PO reports when 21 AFW pump trips, and adjusts flow from 22 and 23 AFW pumps as reauired based on current SG NR levels.
Note:
21 AFW pp supplies 23/24 SGs 22 AFW pp supplies 21/22 SGs 23 AFW pump supplies all SGs Simulator Operator: Use
* REMOTE AF20 to OFF 2 minutes after being dispatched to remove **
control power from 21 AFW pump breaker.
PO reports all available equipment started on SEC loadina.
PO reoorts which AFW oumps are runnin PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 18 of 32
' *Evaluator/fnsln1ctor Acti~ityw*
    - '.-:~?f~~- ~rr ~ _,,,,>AL , ;;v~:, ,,,,, , 'l~','
                                                              *;i~1Expe~te& Pla'nt/Studenf Response           $BT . '                . Comment , . ~' *~tt
                                                                                              ..     .
PO reports correct safeguards valve alignment.
RO reports 21 and 22CA330s are shut.
RO reports containment pressure remains less than 15 psig.
PO reports no indication of hi steam flow.
PO reports all 4KV vital buses enerqized.
RO reports ventilation systems lineups correct for current plant conditions.
RO reports ventilation systems lineups correct for current plant conditions.
RO reports at least 2 CCW pumps are running. RO reports proper ECCS flow indicated for current plant conditions.
RO reports at least 2 CCW pumps are running.
PO reports AFW status, and maintains at least 22E4 lbm/hr flow until at least one SG NR level is >9%, then maintains SG NR levels 19-33%. RO reports RCP status, and RCS temperature stable at or trendinq to 547&deg;. RO reports both RTBs are open. RO reports PZR PORVs are shut with Block valves open. PSEG Restricted  
RO reports proper ECCS flow indicated for current plant conditions.
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 18 of 32 . Comment , . * 
PO reports AFW status, and maintains at least 22E4 lbm/hr flow until at least one SG NR level is >9%, then maintains SG NR levels 19-33%.
RO reports RCP status, and RCS temperature stable at or trendinq to 547&deg;.
RO reports both RTBs are open.
RO reports PZR PORVs are shut with Block valves open.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training


.. r,,;. __ ,,,,,,;'Jt*  
TQ-AA-106-0204 Page 19 of 32
,,'.l"''<  
  *e,,~ruator/rr;1str~Pf6r,e.ctivi~x~..                          Expecte'tl .Plant/StuClenr Respons~,f" *                              **~.e'f*    :    ir*gomJQPnF
''"'* Note: ST A will report to Control Room 10 minutes after being paged to report, and initiate monitoring of CFSTs. Note: These steps complete CT#1 CT#1 (CT-18) Isolate feed flow into and steam flow from 21 SG prior to a transition to SGTR-3 Expecte'tl .Plant/StuClenr
                                                                                                                                                        .118
* 1 ';;.
    ~l r,,;. _ ,,,,,,;'Jt* *;:(f~f( ,,'.l"''< ~c,j~),, ' "'*       !;;/:;~* ~\f~~* ~ff;* f~~f-~t 1 ';;. ,~'.~~P' *,;,:~i?f' 1 J.'./,, ., J.r:OG; ..,.
1 J.'./,, ., RO reports PZR spray status for current plant conditions.
RO reports PZR spray status for current plant conditions.
RO reports RCS pressure is >1350 psig. RO maintains seal injection flow to RCPs. PO reports no SGs are faulted. PO reports NR or WR level is risinq in 21 SG. CRS transitions to EOP-SGTR-1, Steam Generator Tube Rupture. RO maintains seal injection flow to all RCPs. PO reports 21 SG is ruptured, and ensures 21MS10 is set at 1045 psiq. PO reports 21 MS10 operating as expected for current pressure.
RO reports RCS pressure is >1350 psig.
RO maintains seal injection flow to RCPs.
PO reports no SGs are faulted.
PO reports NR or WR level is risinq in 21 SG.
CRS transitions to EOP-SGTR-1, Steam Generator Tube Rupture.
Note: STA will report to Control Room 10 minutes after being paged to report, and initiate monitoring of CFSTs.
RO maintains seal injection flow to all RCPs.
PO reports 21 SG is ruptured, and ensures 21MS10 is set at 1045 psiq.
PO reports 21 MS10 operating as expected for current pressure.
PO shuts 21MS167, and verifies 21MS7, 21MS18, and 21GB4 are shut.
PO shuts 21MS167, and verifies 21MS7, 21MS18, and 21GB4 are shut.
J.r:OG; .. , .. TQ-AA-106-0204 Page 19 of 32 : .11 8 ir*gomJQPnF PSEG Restricted  
Note: These steps complete CT#1 CT#1 (CT-18) Isolate feed flow into and steam flow from 21 SG prior to a transition to SGTR-3 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
-Possession Requires Specific Permission from Nuclear Training being required.
 
SAT UNSAT 1:). Eipedted' Plant/Student Re$poose'  
TQ-AA-106-0204 Page 20 of 32 1:). Eipedted' Plant/Student               Re$poose' *        *set
* , ,
                            , ~f ,,'~j;f,'._ , *:1; 1
__ , * :1; 1 ,*:J <("",_ , : *, >f:/:\., : ,.,/\:iL PO reoorts 21 SG is ruotured.
                                                      ,*:J <("",_ , : *, >f:/:\., : ,.,/\:iL '' t '
PO reports 23 AFW pump is not the only source of AFW. PO ensures 23 AFW pump speed at minimum and trios 23 AFW oumo. CRS dispatches operator to shut 21 MS45 if not oreviouslv oerformed.
bOG being required.
CRS dispatches operator to shut 2SS321 sample valve. PO reports 21 SG is isolated from all intact SGs. PO controls AFW flow if required to maintain 21 SG NR level >9%. PO reports when 21MS10 opens for pressure control av 1045 osia. PO reoorts 21 SG oressure is >375 osi CRS determines target temperature from Table D. (503&deg;F for ruptured SG pressure osia. PO reports intact SGs are available for cooldown.  
SAT          UNSAT PO reoorts 21 SG is ruotured.
*set '' t ' bOG PSEG Restricted  
PO reports 23 AFW pump is not the only source of AFW.
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 20 of 32 "r :At';E'181uator1tnstrucJq( Activity;{...  
PO ensures 23 AFW pump speed at minimum and trios 23 AFW oumo.
* -:-1
CRS dispatches operator to shut 21 MS45 if not oreviouslv oerformed.
:':", >, ;; ,* -),:; -,  
CRS dispatches operator to shut 2SS321 sample valve.
*' ,  
PO reports 21 SG is isolated from all intact SGs.
-t of/Student Response *** ,
PO controls AFW flow if required to maintain 21 SG NR level >9%.
{-???-; c'.''Y'' Note: When hottest CET is <503&deg;F, crew will stop cooldown with steps on next page. PO reports steam dumps are available, and places in MS Pressure Control-Manual at 25% to perform cooldown.
PO reports when 21MS10 opens for pressure control av 1045 osia.
PO bypasses Tavg when Tavg Low-Low is reached. Crew monitors hottest CET temperature while continuina in procedure.
PO reoorts 21 SG oressure is >375 osi CRS determines target temperature from Table D. (503&deg;F for ruptured SG pressure
RO reports power is available to both PZR PORV Stop valves, both PZR PORVs are shut, and both PZR PORV Stop valves are ooen. RO resets SI and Phase A isolation, and reoorts Phase B isolation reset. RO ooens 21 and 22CA330. PO resets each SEC and reports 230V control centers are reset. RO reports RHR suction is aligned to the RWST and no RHR oumo discharae flow. RO stoos both RHR s. PO reports 21 SG is ruptured and 21MS167 is shut. PSEG Restricted  
                          ~1000 osia.
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 21of32
PO reports intact SGs are available for cooldown.
** *
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
*lloG*z ', '. cf+rJ?+ RO shuts charging pump mini flows when RCS ressure is < 1500 si . RO reports when hottest CET is less than RCS cooldown tar et tern . CT#2 (CT-19) Establish and maintain an RCS temperature so that transition from SGTR-1 does** not qccur because temperature is too high to maintain minimum suocooling,.
 
or: so lowJt causes transition to FRTS or FRSM. **** SAT UNSAT PO re orts 21 SG ressure is stable or risin RO re RO re orts normal PZR s ra is available.
TQ-AA-106-0204 Page 21of32 "r :At';E'181uator1tnstrucJq( Activity;{...
RO full o ens both PZR S ra Valves. RO reports PZR Spray is reducing RCS ressure. Crew continues de ressurization.
* of/Student
: 7. 23 RCP trip PSEG Restricted  
                                                                                                                ,
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 22 of 32 c<>mmr'nt"'  
Response ***
... ?qlf ,,,,
{- ???-;
Simulator Operator:
c~nnment *  ~'. **
Insert RT-7 on.directionJrom Lead Evaluator once.RO reports spray effectiveness.
-:-1 F~rn: :':", >, ;; *c~ ,* -),:; ~; -, ;l9fi:,'":~,'.' *' , J 1:~'., t -,~dat~_.:._...:.=..--'-"-"--=-~
MALF: 23 RCP tri Note: The crew is in a "do loop" when reducing RCS pressure using spray, and will return to Step 19.2 Simulator Operator:
                                                                      -
IF crew continues to use spray flow to lower RCS pressure, .THEN insert RT*9 on direction from Lead Evaluator to trio 21 RCP. Simulator Ooerator:
                                                                                                                  'ij~~:r c'.''Y''
Insert RT-13 *'*i TEipectea'Pla'nt/S$dent Resji'onsef ,
PO reports steam dumps are available, and places in MS Pressure Control-Manual at 25%
cT
to perform cooldown.
*;;>'/, ,.;,
PO bypasses Tavg when Tavg Low-Low is reached.
' ' 1
Crew monitors hottest CET temperature while continuina in procedure.
'. ,/ RO reoorts 23 RCP RO reports with loss of 23 RCP, spray is no lonaer effectivelv reducina RCS pressure.
Note: When hottest CET is <503&deg;F, crew will stop cooldown with steps on next page.
RO shuts both PZR Sorav valves. RO reoorts both PZR PORVs are available.
RO reports power is available to both PZR PORV Stop valves, both PZR PORVs are shut, and both PZR PORV Stop valves are ooen.
RO resets SI and Phase A isolation, and reoorts Phase B isolation reset.
RO ooens 21 and 22CA330.
PO resets each SEC and reports 230V control centers are reset.
RO reports RHR suction is aligned to the RWST and no RHR oumo discharae flow.
RO stoos both RHR                 s.
PO reports 21 SG is ruptured and 21MS167 is shut.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 22 of 32 c<>mmr'nt"' . . ?qlf ~*
                                                                                      ', *lloG*z
                                                                                          '. cf+rJ?+                 ,,,,
RO shuts charging pump mini flows when RCS ressure is < 1500 si .
RO reports when hottest CET is less than RCS cooldown tar et tern .
CT#2 (CT-19)       Establish and maintain an RCS temperature so that transition from SGTR-1 does**
not qccur because temperature is too high to maintain minimum suocooling,. or: so lowJt causes transition to FRTS or FRSM. *
* SAT           UNSAT PO re orts 21 SG ressure is stable or risin RO re RO re orts normal PZR s ra is available.
RO full o ens both PZR S ra Valves.
RO reports PZR Spray is reducing RCS ressure.
Crew continues de ressurization.
: 7. 23 RCP trip PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 23 of 32
                                    *'*i      TEipectea'Pla'nt/S$dent Resji'onsef ,                              '!; SBt''W' ,1J~Pl>>1if;Qenl" '?]*,~''  .
(\~<,_,L,    cT ;~:;~_,// *;;>'/,      ,.;, ,v';f/i[~"; ' ' 1 ''~~:i~< '. ,/    LOG, Simulator Operator: Insert RT-7 on.directionJrom Lead Evaluator once.RO reports spray effectiveness.
MALF: 23 RCP tri RO reoorts 23 RCP              tri~.
Note: The crew is in a "do loop" when reducing RCS pressure using spray, and will return to Step 19.2 RO reports with loss of 23 RCP, spray is no lonaer effectivelv reducina RCS pressure.
Simulator Operator: IF crew continues to use spray flow to lower RCS pressure, .THEN insert RT*9 on direction from Lead Evaluator to trio 21 RCP.
RO shuts both PZR Sorav valves.
RO reoorts both PZR PORVs are available.
Crew reviews depressurization criteria.
Crew reviews depressurization criteria.
IF 2PR1 is selected as the PORV to deoressurize, RO reports 2PR1 will not open. RO opens 2PR2. '!; SBt''W' LOG, PSEG Restricted  
IF 2PR1 is selected as the PORV to deoressurize, RO reports 2PR1 will not open.
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 23 of 32
RO opens 2PR2.
* 'E.valuaterir  
Simulator Ooerator: Insert RT-13 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
** * :*
 
as soon as 2PR2 is open. MALF:. 2PR2.fails to 100%. 8. PZR PORV fails to shut Simulator Operator:
TQ-AA-106-0204 Page 24 of 32
Ensure is TRUE when 2PR7 shut PB is depressed.
                                                                                                                                    ''
This fails 2PR7 90% ooen. Terminate the scenario when the transition to SGTR-3 is announced.
    *'E.valuaterir * *                   '   * &#xa5;\' 1" { ' ' * ,,' ' ' \"     <l"''
' * &#xa5;\' 1" {'' * ,,' ' ' \" <l"'' ;>  
                                          +~4 E:xpe~ted ,Plant/Student,Re$ponse" j / , 111~
'  
                                                                                          ;> Yj",Y""-''~''''~      ' ,1&sect;''""~''     'v/ '.""''"~"t'<t' 11 ;!SBT:, *
'' 'v/  
                                                                                                                                                            ,-;C*'""''
,-;C*'""'' ,Plant/Student,Re$ponse" j/ ,
tYci1;iJ:2f11C~m~'~t;i)-1''' , ,. ,
11;!SBT:, * :* '.% t.f14''' I'''"'! ;;.J ;Pf'.*11 ,;,. " ** .. * . *1c,(1P'1 . LOG;' RO reoorts when condition in Table E is met. RO reoorts 2PR2 will not shut. CRS directs closure of 2PR7 PZR PORV Block Valve. RO reports that after initiating closed on 2PR7, the open limit extinguished but the closed limit has not illuminated.
:* -~,,~J:,f~}~\(ic'*,*,);i$~).~            :*   '.% t.f14'' I'''"'!       ;;.J   ;Pf'.*11         ,;,. " * . * .     *1c,(1P'1   .       LOG;'
CRS transitions to EOP-SGTR-3, SGTR with LOCA-Subcooled Recoverv.
as soon as 2PR2 is open.
TQ-AA-106-0204 Page 24 of 32 , ,. , PSEG Restricted  
MALF:. 2PR2.fails to 100%.
-Possession Requires Specific Permission from Nuclear Training A. Alarm Response Procedures (Various)
RO reoorts when condition in Table E is met.
B. Technical Specifications C. Emergency Plan (ECG) D. OP-AA-101-111-1003, Use of Procedures E. S2.0P-10.ZZ-0004, Power Operation F. S2.0P-SO.DG-0003, 2C Diesel Generator Operation G. S2.0P-ST.500-0001, Electrical Power Systems AC Sources Alignment H. S2.0P-AB.SG-0001, Steam Generator Tube Leak I. S2.0P-AB.LOAD-0001, Rapid Load Reduction J. 2-EOP-TRIP-1, Reactor Trip or Safety Injection K. 2-EOP-SGTR-1, Steam Generator Tube Rupture TQ-AA-106-0204 Page 25 of 32 PSEG Restricted
: 8. PZR PORV fails to shut RO reoorts 2PR2 will not shut.
-Possession Requires Specific Permission from Nuclear Training ATTACHMENT 1 UNIT TWO PLANT STATUS TODAY MODE: 1 POWER: 89.4% RCS BORON: 1114 SHUTDOWN SAFETY SYSTEM STATUS (5, 6 & DEFUELED):
CRS directs closure of 2PR7 PZR PORV Block Valve.
NA REACTIVITY PARAMETERS Control Bank D is at 193 steps. Xenon is building in at 25 pcm I hr following downpower last shift MOST LIMITING LCO AND DATE/TIME OF EXPIRATION:
Simulator Operator: Ensure ~
is TRUE when 2PR7 shut PB is depressed. This fails 2PR7 90%
ooen.
RO reports that after initiating closed on 2PR7, the open limit extinguished but the closed limit has not illuminated.
CRS transitions to EOP-SGTR-3, SGTR with LOCA- Subcooled Recoverv.
Terminate the scenario when the transition to SGTR-3 is announced.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 25 of 32 A. Alarm Response Procedures (Various)
B. Technical Specifications C. Emergency Plan (ECG)
D. OP-AA-101-111-1003, Use of Procedures E. S2.0P-10.ZZ-0004, Power Operation F. S2.0P-SO.DG-0003, 2C Diesel Generator Operation G. S2.0P-ST.500-0001, Electrical Power Systems AC Sources Alignment H. S2.0P-AB.SG-0001, Steam Generator Tube Leak I. S2.0P-AB.LOAD-0001, Rapid Load Reduction J. 2-EOP-TRIP-1, Reactor Trip or Safety Injection K. 2-EOP-SGTR-1, Steam Generator Tube Rupture PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 26 of 32 ATTACHMENT 1 UNIT TWO PLANT STATUS TODAY MODE:     1       POWER:       89.4%       RCS BORON:       1114         MWe        1080 SHUTDOWN SAFETY SYSTEM STATUS (5, 6 & DEFUELED):
NA REACTIVITY PARAMETERS Control Bank D is at 193 steps.
Xenon is building in at 25 pcm I hr following downpower last shift MOST LIMITING LCO AND DATE/TIME OF EXPIRATION:
EVOLUTIONS/PROCEDURES/SURVEILLANCES IN PROGRESS:
EVOLUTIONS/PROCEDURES/SURVEILLANCES IN PROGRESS:
TQ-AA-106-0204 Page 26 of 32 MWe 1080 S2.0P-PT.TRB-0003, Main Turbine Valve testing is being briefed by a dedicated test team to be performed in one hour. ABNORMAL PLANT CONFIGURATIONS:
S2.0P-PT.TRB-0003, Main Turbine Valve testing is being briefed by a dedicated test team to be performed in one hour.
2C EOG Jacket Water heater is failed and CIT. CONTROL ROOM: Unit 1 and Hope Creek at 100% power. No penalty minutes in the last 24 hrs. PRIMARY: SECONDARY:
ABNORMAL PLANT CONFIGURATIONS:
2C EOG Jacket Water heater is failed and CIT.
CONTROL ROOM:
Unit 1 and Hope Creek at 100% power.
No penalty minutes in the last 24 hrs.
PRIMARY:
SECONDARY:
Condensate Polisher is in service RADWASTE:
Condensate Polisher is in service RADWASTE:
No discharges in progress CIRCULATING WATER/SERVICE WATER: PSEG Restricted  
No discharges in progress CIRCULATING WATER/SERVICE WATER:
-Possession Requires Specific Permission from Nuclear Training ATTACHMENT 2 SIMULATOR READY FOR TRAINING CHECKLIST
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
: 1. Verify simulator is in "TRAIN" Load 2. Simulator is in RUN 3. Overhead Annunciator Horns ON 4. All required computer terminals in operation
 
TQ-AA-106-0204 Page 27 of 32 ATTACHMENT 2 SIMULATOR READY FOR TRAINING CHECKLIST
: 1. Verify simulator is in "TRAIN" Load
: 2. Simulator is in RUN
: 3. Overhead Annunciator Horns ON
: 4. All required computer terminals in operation
: 5. Simulator clocks synchronized
: 5. Simulator clocks synchronized
: 6. All tagged equipment properly secured and documented
: 6. All tagged equipment properly secured and documented
: 7. TSAS Status Board up-to-date
: 7. TSAS Status Board up-to-date
: 8. Shift manning sheet available
: 8. Shift manning sheet available
: 9. Procedures in progress open and signed-off to proper step TQ-AA-106-0204 Page 27 of 32 10. All OHA lamps operating (OHA Test) and burned out lamps replaced 11. Required chart recorders advanced and ON (proper paper installed)
: 9. Procedures in progress open and signed-off to proper step
: 12. All printers have adequate paper AND functional ribbon 13. Required procedures clean 14. Multiple color procedure pens available
: 10. All OHA lamps operating (OHA Test) and burned out lamps replaced
: 11. Required chart recorders advanced and ON (proper paper installed)
: 12. All printers have adequate paper AND functional ribbon
: 13. Required procedures clean
: 14. Multiple color procedure pens available
: 15. Required keys available
: 15. Required keys available
: 16. Simulator cleared of unauthorized material/personnel
: 16. Simulator cleared of unauthorized material/personnel
: 17. All charts advanced to clean traces and chart recorders are on. 18. Rod step counters correct (channel check) and reset as necessary
: 17. All charts advanced to clean traces and chart recorders are on.
: 18. Rod step counters correct (channel check) and reset as necessary
: 19. Exam security set for simulator
: 19. Exam security set for simulator
: 20. Ensure a current RCS Leak Rate Worksheet is placed by Aux Alarm Typewriter with Baseline Data filled out 21. Shift logs available if required 22. Recording Media available (if applicable)
: 20. Ensure a current RCS Leak Rate Worksheet is placed by Aux Alarm Typewriter with Baseline Data filled out
: 23. Ensure ECG classification is correct 24. Reference verification performed with required documents available
: 21. Shift logs available if required
: 25. Verify phones disconnected from plant after drill. 26. Verify EGC paperwork is marked "Training Use Only" and is current revision.
: 22. Recording Media available (if applicable)
: 23. Ensure ECG classification is correct
: 24. Reference verification performed with required documents available
: 25. Verify phones disconnected from plant after drill.
: 26. Verify EGC paperwork is marked "Training Use Only" and is current revision.
: 27. Ensure sufficient copies of ECG paperwork are available.
: 27. Ensure sufficient copies of ECG paperwork are available.
PSEG Restricted  
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
-Possession Requires Specific Permission from Nuclear Training ATTACHMENT 3 CRITICAL TASK METHODOLOGY TQ-AA-106-0204 Page 28 of 32 In reviewing each proposed CT, the examination team assesses the task to ensure, that it is essential to safety. A task is essential to safety if, in the judgment of the examination team, the improper performance or omission of this task by a licensee will result in direct adverse consequences or in significant degradation in the mitigative capability of the plant. The examination team determines if an automatically actuated plant system would have been required to mitigate the consequences of an individual's incorrect performance.
 
If incorrect performance of a task by an individual necessitates the crew taking compensatory action that would complicate the event mitigation strategy, the task is safety significant.
TQ-AA-106-0204 Page 28 of 32 ATTACHMENT 3 CRITICAL TASK METHODOLOGY In reviewing each proposed CT, the examination team assesses the task to ensure, that it is essential to safety. A task is essential to safety if, in the judgment of the examination team, the improper performance or omission of this task by a licensee will result in direct adverse consequences or in significant degradation in the mitigative capability of the plant.
The examination team determines if an automatically actuated plant system would have been required to mitigate the consequences of an individual's incorrect performance. If incorrect performance of a task by an individual necessitates the crew taking compensatory action that would complicate the event mitigation strategy, the task is safety significant.
I. Examples of CTs involving essential safety actions include those for which operation or correct performance prevents ...
I. Examples of CTs involving essential safety actions include those for which operation or correct performance prevents ...
* degradation of any barrier to fission product release
* degradation of any barrier to fission product release
Line 1,909: Line 3,473:
* take one or more actions that would prevent a challenge to plant safety.
* take one or more actions that would prevent a challenge to plant safety.
* prevent inappropriate actions that create a challenge to plant safety (such as an unintentional Reactor Protection System (RPS) or ESF actuation.
* prevent inappropriate actions that create a challenge to plant safety (such as an unintentional Reactor Protection System (RPS) or ESF actuation.
PSEG Restricted  
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 29 of 32 SCENARIO IDENTIFIER:
 
15-01 ILOT NRC ESG-2 REVIEWER:
TQ-AA-106-0204 Page 29 of 32 SCENARIO IDENTIFIER:                 15-01 ILOT NRC ESG-2         REVIEWER: C Recchione Initials       Qualitative Attributes CR       1. The scenario has clearly stated objectives in the scenario.
C Recchione Initials CR CR CR CR CR CR CR CR CR CR CR CR 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. Qualitative Attributes The scenario has clearly stated objectives in the scenario.
CR      2. The initial conditions are realistic, in that some equipment and/or instrumentation may be out of service, but it does not cue crew into expected events.
The initial conditions are realistic, in that some equipment and/or instrumentation may be out of service, but it does not cue crew into expected events. The scenario consists mostly of related events. Each event description consists of:
CR      3. The scenario consists mostly of related events.
CR      4. Each event description consists of:
* the point in the scenario when it is to be initiated
* the point in the scenario when it is to be initiated
* the malfunction(s) that are entered to initiate the event
* the malfunction(s) that are entered to initiate the event
* the symptoms/cues that will be visible to the crew
* the symptoms/cues that will be visible to the crew
* the expected operator actions (by shift position)
* the expected operator actions (by shift position)
* the event termination point No more than one non-mechanistic failure (e.g., pipe break) is incorporated into the scenario without a credible preceding incident such as a seismic event. The events are valid with regard to physics and thermodynamics.
* the event termination point CR      5. No more than one non-mechanistic failure (e.g., pipe break) is incorporated into the scenario without a credible preceding incident such as a seismic event.
Sequencing/timing of events is reasonable, and allows for the examination team to obtain complete evaluation results commensurate with the scenario objectives.
CR      6. The events are valid with regard to physics and thermodynamics.
The simulator modeling is not altered. All crew competencies can be evaluated.
CR      7. Sequencing/timing of events is reasonable, and allows for the examination team to obtain complete evaluation results commensurate with the scenario objectives.
The scenario has been validated.
CR      8. The simulator modeling is not altered.
If the sampling plan indicates that the scenario was used for training during the requalification cycle, evaluate the need to modify or replace the scenario.
CR      9. All crew competencies can be evaluated.
ESG-PSA Evaluation Form is completed for the scenario at the applicable facility.
CR      10. The scenario has been validated.
PSEG Restricted  
CR      11. If the sampling plan indicates that the scenario was used for training during the requalification cycle, evaluate the need to modify or replace the scenario.
-Possession Requires Specific Permission from Nuclear Training Initial GG GG GG GG GG GG 2 3 1 1 0 2 TQ-AA-106-0204 Page 30 of 32 Quantitative Attributes (as per ES-301-4, and ES-301 Section D.5.d) Malfunctions after EOP entry: 1-2 Abnormal Events: 2-4 Major Transients:
CR      12. ESG-PSA Evaluation Form is completed for the scenario at the applicable facility.
1-2 EOPs entered/requiring substantive actions: 1-2 EOP contingencies requiring substantive actions: 0-2 EOP based Critical tasks: 2-3 COMMENTS:
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
PSEG Restricted  
 
-Possession Requires Specific Permission from Nuclear Training 15-01 ILOT NRC ESG-2 TQ-AA-106-0204 Page 31of32 CT#1 (CT-18) Isolate feed flow into and steam flow from 21 SG prior to a transition to SGTR-3 being required.
TQ-AA-106-0204 Page 30 of 32 Initial Quantitative Attributes (as per ES-301-4, and ES-301 Section D.5.d)
Basis: Failure to isolate the ruptured SG causes a loss of differential pressure between the ruptured SG and the intact SGs. The fact that the crew allows the differential pressure to dissipate and, as a result, are then forced to transition to a contingency ERG constitutes an incorrect performance that "necessitates the crew taking compensating action that would complicate the event mitigation strategy .... " CT #2: {CT-19) Establish and maintain an RCS temperature so that transition from SGTR does not occur because temperature is too high to maintain minimum subcooling, or so low it causes transition to FRTS or FRSM. Basis: Failure to establish and maintain the correct RCS temperature during a SGTR leads to a transition from E-3 to a contingency ERG. This failure constitutes an incorrect performance that "necessitates the crew taking compensating action that would complicate the event mitigation strategy .... " Note to Evaluator:
GG      2  Malfunctions after EOP entry: 1-2 GG      3  Abnormal Events: 2-4 GG      1  Major Transients: 1-2 GG      1  EOPs entered/requiring substantive actions: 1-2 GG      0  EOP contingencies requiring substantive actions: 0-2 GG      2  EOP based Critical tasks: 2-3 COMMENTS:
CT numbers in parentheses are the corresponding Westinghouse ERG Rev. 2-based Critical Tasks procedure WCAP-17711-NP PSEG Restricted  
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
-Possession Requires Specific Permission from Nuclear Training ATTACHMENT6
 
--TQ-AA-106-0204 Page 32 of 32 REl..ATIONSHIP EVENTS LEADING TO CORE DAMAGE Y/N Event Y/N Event N TRANSIENTS with PCS Unavailable N Loss of Service Water y Steam Generator Tube Rupture N Loss ofCCW N Loss of Offsite Power N Loss of Control Air N Loss of Switchgear and Pen Area Ventilation N Station Black Out N LOCA COMPONENT/TRAIN/SYSTEM UNAVAILABILITY THAT INCREASES CORE DAMAGE FREQUENCY COMPONENT, SYSTEM, OR TRAIN Y/N COMPONENT, SYSTEM, OR N Containment Sump Strainers N Gas Turbine N SSWS Valves to Turbine Generator Area Y Any Diesel Generator N RHR Suction Line valves from Hot Leg Y Auxiliary Feed Pump N CVCS Letdown line Control and Isolation Valves N SBO Air Compressor OPERATOR ACTIONS IMPORTANT IN PREVENTING CORE DAMAGE Y/N OPERATOR ACTION N Restore AC power during SBO N Connect to gas turbine N Trip Reactor and RCPs after loss of component cooling system N Re-align RHR system for re-circulation N Un-isolate the available CCW Heat Exchanger N Isolate the CVCS letdown path and transfer charging suction to RWST Y Cooldown the RCS and depressurize the system Y Isolate the affected Steam Generator that has the tube rupture(s)
TQ-AA-106-0204 Page 31of32 15-01 ILOT NRC ESG-2 CT#1 (CT-18) Isolate feed flow into and steam flow from 21 SG prior to a transition to SGTR-3 being required.
N Early depressurize the RCS N Initiate feed and bleed Complete this evaluation form for each ESG.
Basis: Failure to isolate the ruptured SG causes a loss of differential pressure between the ruptured SG and the intact SGs. The fact that the crew allows the differential pressure to dissipate and, as a result, are then forced to transition to a contingency ERG constitutes an incorrect performance that "necessitates the crew taking compensating action that would complicate the event mitigation strategy .... "
SCENARIO TITLE: SCENARIO NUMBER: EFFECTIVE DATE: SIMULATOR EXAMINATION SCENARIO GUIDE 15-01 NRC ESG-3 15-01 NRC ESG-3 See Approval Dates EXPECTED DURATION:
CT #2: {CT-19) Establish and maintain an RCS temperature so that transition from SGTR does not occur because temperature is too high to maintain minimum subcooling, or so low it causes transition to FRTS or FRSM.
60 minutes REVISION NUMBER: PROGRAM: Revision Summary 00 LO. REQUAL X ! INITIAL LICENSE New issue for 15-01 ILOT NRC exam PREPARED BY: G Gauding Lead Regulatory Exam Author APPROVED BY: APPROVED BY: JdllkUlj aciiifyResentative TQ-AA-106-0204 Page 1of29 8-11-16 Date (o/,/c, 'oate 1ofit!afc, ate PSEG Restricted  
Basis: Failure to establish and maintain the correct RCS temperature during a SGTR leads to a transition from E-3 to a contingency ERG. This failure constitutes an incorrect performance that "necessitates the crew taking compensating action that would complicate the event mitigation strategy .... "
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 2 of 29 TQ-AA-106-0204 Page 3 of 29 A. Given the order or indications of a pressurizer control system malfunction, perform actions as the nuclear control operator to RESPOND to the malfunction in accordance with S2.0P-AB.PZR-0001.
Note to Evaluator: CT numbers in parentheses are the corresponding Westinghouse ERG Rev. 2- based Critical Tasks procedure WCAP-17711-NP PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 32 of 32 ATTACHMENT6              -        -
ESG~PRA REl..ATIONSHIP E~AlUATION EVENTS LEADING TO CORE DAMAGE Y/N   Event                                                   Y/N   Event N   TRANSIENTS with PCS Unavailable                           N     Loss of Service Water y   Steam Generator Tube Rupture                             N     Loss ofCCW N   Loss of Offsite Power                                     N     Loss of Control Air N   Loss of Switchgear and Pen Area Ventilation               N     Station Black Out N   LOCA COMPONENT/TRAIN/SYSTEM UNAVAILABILITY THAT INCREASES CORE DAMAGE FREQUENCY COMPONENT, SYSTEM, OR TRAIN                             Y/N   COMPONENT, SYSTEM, OR Tc:>~lll.I N   Containment Sump Strainers                               N     Gas Turbine N   SSWS Valves to Turbine Generator Area                     Y     Any Diesel Generator N   RHR Suction Line valves from Hot Leg                     Y     Auxiliary Feed Pump N   CVCS Letdown line Control and Isolation Valves           N     SBO Air Compressor OPERATOR ACTIONS IMPORTANT IN PREVENTING CORE DAMAGE Y/N   OPERATOR ACTION N   Restore AC power during SBO N   Connect to gas turbine N   Trip Reactor and RCPs after loss of component cooling system N   Re-align RHR system for re-circulation N   Un-isolate the available CCW Heat Exchanger N   Isolate the CVCS letdown path and transfer charging suction to RWST Y   Cooldown the RCS and depressurize the system Y   Isolate the affected Steam Generator that has the tube rupture(s)
N   Early depressurize the RCS N   Initiate feed and bleed Complete this evaluation form for each ESG.
 
TQ-AA-106-0204 Page 1of29 SIMULATOR EXAMINATION SCENARIO GUIDE SCENARIO TITLE:                  15-01 NRC ESG-3 SCENARIO NUMBER:                  15-01 NRC ESG-3 EFFECTIVE DATE:                  See Approval Dates EXPECTED DURATION:               60 minutes REVISION NUMBER:                 00 PROGRAM:                       ~-~' LO. REQUAL X   ! INITIAL LICENSE
                                ~~!STA
                                ~-~'OTHER Revision Summary New issue for 15-01 ILOT NRC exam PREPARED BY:                     G Gauding                             8-11-16 Lead Regulatory Exam Author                       Date APPROVED BY:                               ~V\                        (o/,/c,
                                                                        'oate APPROVED BY:
                        ~ JdllkUlj aciiifyResentative 1ofit!afc, ate PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 2 of 29
 
TQ-AA-106-0204 Page 3 of 29 A. Given the order or indications of a pressurizer control system malfunction, perform actions as the nuclear control operator to RESPOND to the malfunction in accordance with S1/S2.0P-S2.0P-AB.PZR-0001.
B. Given indication of a pressurizer control system malfunction, DIRECT the response to the malfunction in accordance with S2.0P-AB.PZR-0001.
B. Given indication of a pressurizer control system malfunction, DIRECT the response to the malfunction in accordance with S2.0P-AB.PZR-0001.
C. Given indication of a dropped control rod perform actions as the nuclear control operator to RESPOND to the malfunction in accordance with S2.0P-AB.ROD-0002.
C. Given indication of a dropped control rod perform actions as the nuclear control operator to RESPOND to the malfunction in accordance with S2.0P-AB.ROD-0002.
Line 1,948: Line 3,527:
K. Given the order or indications of a multiple steam generator depressurization, perform actions as the nuclear control operator to RESPOND to the generator depressurization in accordance with EOP-LOSC-2.
K. Given the order or indications of a multiple steam generator depressurization, perform actions as the nuclear control operator to RESPOND to the generator depressurization in accordance with EOP-LOSC-2.
L. Given indication of a multiple steam generator depressurization, DIRECT the response to the generator depressurization in accordance with EOP-LOSC-2.
L. Given indication of a multiple steam generator depressurization, DIRECT the response to the generator depressurization in accordance with EOP-LOSC-2.
A. Power Ascension B. Controlling PZR Pressure Instrument fails high C. Dropped control rod D. Steam Leak/Rupture in containment PSEG Restricted  
A. Power Ascension B. Controlling PZR Pressure Instrument fails high C. Dropped control rod D. Steam Leak/Rupture in containment PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 4 of 29 A. The crew will take the watch with the unit stable at 1 x1 o-s Amps during a plant startup, BOL. 21 SGFP is in service and 22 SGFP is O/S. Steam dumps are in MS Pressure Control -Auto @ 1 ,000 psig. 25 CFCU is CIT for maintenance.
23 charging pump is CIT for emergent maintenance.
The crew will be instructed to raise power to 2%. B. The crew will initiate a power ascension to 2% using Main Steam Dumps and control rods. C. After the power ascension is started the controlling PZR Pressure instrument will fail high, deenergizing PZR heaters and causing both PZR Spray valves to open fully. The crew will respond IAW S2.0P-AB.PZR-0001, Pressurizer Pressure Malfunction to establish manual control of PZR pressure control and restore pressure to normal, swap to an operable channel, and remove the failed channel from service. The CRS will identify applicable LCO's. D. After the Pressurizer Pressure control system failure has been addressed, a control rod will drop fully into the core. The crew will respond IAW S2.0P-AB.ROD-0002, Dropped Rod. The crew will identify the Rx is subcritical, and initiate control rod insertion to fully insert all Control and Shutdown rods. The CRS will identify applicable LCO's. E. During the rod insertion, a steam leak in containment will occur on 21 SG. The crew will diagnose changing containment conditions, and determine a Rx trip is required and MSLI will be required in an attempt to isolate the steam leak. F. The crew will trip the Rx. The steamline will rupture. MSLI (auto and manual) will fail to shut any MSIV. The crew will initiate Safety Injection when it is identified that the source of the steam leak is not isolated.
G. The crew will perform plant stabilization actions in EOP-TRIP-1, Reactor Trip or Safety Injection.
With all SGs faulted, the crew will maintain AFW flow to each SG. 21 AFW pump will trip during TRIP-1 performance.
Containment Spray pumps will not automatically start when demanded on hi-hi containment pressure, and the crew will manually start at least one CS pump (CT-1 ). The crew will transition to EOP-LOSC-1, Loss of Secondary Coolant. H. The crew will transition to EOP-LOSC-2, Multiple Steam Generator Depressurization with all SG's faulted. I. The crew will identify the RCS cooldown rate of >100&deg;F I hr, and control AFW flow to minimize RCS cooldown (CT-2). The crew will reset Safeguards.
When evaluating SI Flow Reduction Criteria, local operators will successfully shut a MSIV. The crew will recognize rising pressure in that SG, and transition to LOSC-1. J. The scenario will be terminated upon transition to LOSC-1. PSEG Restricted
-Possession Requires Specific Permission from Nuclear Training IC-233 TQ-AA-106-0204 Page 5 of 29 PREP FOR (i.e. computer setpoints, procedures, bezel ,tagged eqt1ipment)
' ,, ' ,, ,, ' -' ,, ' . ->' ',, Initial I Description 1 VC1 and VC4 CIT 2 RCPs (SELF CHECK) _ 3 RTBs (SELF CHECK) _ 4 MS167s (SELF CHECK) _ 5 500 KV SWYD (SELF CHECK) _ 6 SGFP Trip (SELF CHECK) _ 7 23 CV PP (SELF CHECK) __ 8 21 Charging pump in service 9 25 CFCU CIT _ 10 23 Charging pump CIT 11 IOP-3 open and complete up to Section 4.3, Power Operation.
12 Complete Attachment 2 "Simulator Ready-for-Training/Examination Checklist." PSEG Restricted
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 6 of 29 Note: Tables with blue headings may be populated by external program, do not change column name without consulting Simulator Support group Description
------------------* EVENT ACTION: MONP254 <10 II CONT ROD BANK C < 10 ( RX TRIP ) 1 COMMAND: PURPOSE: <update as needed> SELF-Description Delay Initial Ramp Trigger Severity CHECK Time Value Time 01 PR0016A PZR PRESS CH I PT455 FAILS H/L N/A N/A N/A RT-1 2500 02 RD0267 ANY ROD S INADVERTENTLY DROPS NIA N/A N/A RT-3 3 03 MS0090Ar 21 Main Steam Line Leak Inside Cont N/A N/A N/A RT-5 2 AFTER orifice 04 RP0279A AUTO MSLIS FAILS TO ACT, TRNA NIA NIA NIA NIA 05 RP0279B AUTO MSLIS FAILS TO ACT, TRN B N/A N/A NIA NIA 06 MS0092E 21MS167 FAILS OPEN N/A NIA NIA NIA 07 MS0092F 22MS167 FAILS OPEN Ni A NIA N/A N/A 08 MS0092G 23MS167 FAILS OPEN Ni A NIA NIA N/A 09 MS0092H 24MS167 FAILS OPEN N/A NIA N/A NIA 10 RP0274A AUTO SI FAILS TO ACT, TRNA NIA N/A N/A N/A 11 RP0274B AUTO SI FAILS TO ACT, TRN B NIA NIA N/A Ni A 12 AF0181A 21 AUX FEEDWATER PUMP TRIP 00:05:00 N/A NIA ET-1 13 RP318L 1 21 CS Pum Fails to Start on SEC NIA N/A NIA NIA 14 RP318L2 22 CS Pum Fails to Start on SEC NIA NIA NIA NIA SELF-Description Delay Initial Ramp Trigger Condition CHECK Time Value Time 01 CV52D 23 CHG PUMP BKR CONTROL POWER N/A N/A N/A NIA OFF 02 PR34D PORV STOP VALVE 2PR6 TAGGED N/A NIA N/A RT-7 TAGGED 03 SP01A1 Prevailing Wind Speed NIA N/A N/A N/A 10 04 SP01A2 Prevailin Wind Direction N/A N/A NIA NIA 160 05 CT195-1D 25 CFCU BKR #1 Hi h S eed 125VDC N/A N/A NIA NIA OFF 06 CT195-2D 25 CFCU BKR #2 Hi h Speed 125VDC N/A NIA NIA NIA OFF -----* PSEG Restricted
-Possession Requires Specific Permission from Nuclear Training 07 I CT195-3D 25 CFCU BKR #3 Low Speed 125VDC NIA SELF-Description Delay CHECK Time 01 Cl11 CLO QCl11HR2 TURNING GEAR-ENGAGED N/A 02 Cl11 E LO QCl11PR2 TURNING GEAR-STARTED N/A 03 Cl11 FLO QCl11TG2 TURNING GEAR-STOPPED N/A 04 Cl11 D LO QCl11LG2 TURNING GEAR-DISENGAGED NIA 1. None N/A N/A Initial Ramp Value Time N/A N/A NIA N/A NIA N/A NIA TQ-AA-106-0204 Page 7 of 29 N/A I ___ OFF_] Trigger Condition/
Severity NIA ON NIA ON NIA OFF WA OFF PSEG Restricted
-Possession Requires Specific Permission from Nuclear Training A. State shift job assignments.
TQ-AA-106-0204 Page 8 of 29 B. Hold a shift briefing, detailing instruction to the shift: (provide crew members a copy of the shift turnover sheet). C. Inform the crew "The simulator is running. You may commence panel walkdowns at this time. CRS please inform me when your crew is ready to assume the shift". D. Allow sufficient time for panel walk-downs.
When informed by the CRS that the crew is ready to assume the shift, ensure the simulator is cleared of unauthorized personnel.
PSEG Restricted
-Possession Requires Specific Permission from Nuclear Training 
, 1. Power ascension Continue to next event on direction from Lead evaluator.
: 2. Controlling PZR pressure instrument fails HIGH SimulatQr Operato,r:
Insert RT-1 on directiOn from Lead EvalUatOr:&deg; MALF: MALF: PR0016A PZR Press CHI (PT-455) fails H/L Final Value: 2500 * 'Ex'Pected 1?lan,t1stildi;tnt Response ,. 'w */'.; ;(f' ; ;"' *./ : 'we -*'''Y0J'o' CRS directs power ascension using Main Steam Dumps and control rods. PO raises steam dump demand. RO adjusts control rods to maintain Tave on program. RO announces when POAH is observed.
RO announces unexpected OHA alarms D-8 RC Press HI, and E-42 2PR1 Yz Trip. RO determines actual pressure is not high and reports spray valves open, and recommends placinq Master Pressure Controller in manual. CRS directs RO to place Master Pressure Controller in manual. SBT' l!OG, , ** TQ-AA-106-0204 Page 9 of 29
< '"t''*" ::,wv'0 vommen .
PSEG Restricted
-Possession Requires Specific Permission from Nuclear Training 


.. Response **seT l  
TQ-AA-106-0204 Page 4 of 29 A. The crew will take the watch with the unit stable at 1x1 o-s Amps during a plant startup, BOL.
/il q :i;  
21 SGFP is in service and 22 SGFP is O/S. Steam dumps are in MS Pressure Control - Auto
,. ,)ii, ..: ;*r/*' LOG/ .. RO takes manual control of Master Pressure controller, and lowers demand (increase pressure) to close sprays. CRS enters S2.0P-AB.PZR-001, Pressurizer Pressure Malfunction.
  @ 1,000 psig. 25 CFCU is CIT for maintenance. 23 charging pump is CIT for emergent maintenance. The crew will be instructed to raise power to 2%.
CRS directs initiation of AB.PZR CAS. CRS gives band for control of PZR pressure.
B. The crew will initiate a power ascension to 2% using Main Steam Dumps and control rods.
RO identifies PZR Press Channel I failed high. RO selects Channel Ill for control. RO matches master pressure controller demand to current pressure and returns Master Pressure Controller to AUTO. RO shuts 2PR6. Note: The requirement to shut 2PR6 and deenergize it is within one hour of the PZR Pressure Channel I instrument failure IAW Tech Specs. CRS directs WCC to remove power from 2PR6. Simulator Operator:
C. After the power ascension is started the controlling PZR Pressure instrument will fail high, deenergizing PZR heaters and causing both PZR Spray valves to open fully. The crew will respond IAW S2.0P-AB.PZR-0001, Pressurizer Pressure Malfunction to establish manual control of PZR pressure control and restore pressure to normal, swap to an operable channel, and remove the failed channel from service. The CRS will identify applicable LCO's.
Insert RT-7 2 minutes after being directed to remove power from 2PR6. REMOTE: PR340 PORV Stop PSEG Restricted  
D. After the Pressurizer Pressure control system failure has been addressed, a control rod will drop fully into the core. The crew will respond IAW S2.0P-AB.ROD-0002, Dropped Rod. The crew will identify the Rx is subcritical, and initiate control rod insertion to fully insert all Control and Shutdown rods. The CRS will identify applicable LCO's.
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Pag.e 10 of 29
E. During the rod insertion, a steam leak in containment will occur on 21 SG. The crew will diagnose changing containment conditions, and determine a Rx trip is required and MSLI will be required in an attempt to isolate the steam leak.
:
F. The crew will trip the Rx. The steamline will rupture. MSLI (auto and manual) will fail to shut any MSIV. The crew will initiate Safety Injection when it is identified that the source of the steam leak is not isolated.
Aottiify ""'"*-.. '" . w-, ., Valve 2PR6 taaaed Note: Crew may wait for l&C response before performing any actions in S2. OP-SO. RPS-0003.
G. The crew will perform plant stabilization actions in EOP-TRIP-1, Reactor Trip or Safety Injection. With all SGs faulted, the crew will maintain AFW flow to each SG. 21 AFW pump will trip during TRIP-1 performance. Containment Spray pumps will not automatically start when demanded on hi-hi containment pressure, and the crew will manually start at least one CS pump (CT-1 ). The crew will transition to EOP-LOSC-1, Loss of Secondary Coolant.
H. The crew will transition to EOP-LOSC-2, Multiple Steam Generator Depressurization with all SG's faulted.
I. The crew will identify the RCS cooldown rate of >100&deg;F I hr, and control AFW flow to minimize RCS cooldown (CT-2). The crew will reset Safeguards. When evaluating SI Flow Reduction Criteria, local operators will successfully shut a MSIV. The crew will recognize rising pressure in that SG, and transition to LOSC-1.
J. The scenario will be terminated upon transition to LOSC-1.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 5 of 29 IC-233 PREP FOR' TRAINH~G
                      ,,  '
(i.e. ,,computer
                                            ,, '
setpoints,
                                                    -      '
procedures,
                                                              ,,
bezel
                                                                        '
e~vers
                                                                              . - >'
                                                                                        ,tagged eqt1ipment)
                                                                                      ',,
Initial I Description 1 VC1 and VC4 CIT 2 RCPs (SELF CHECK)
_      3 RTBs (SELF CHECK)
_      4 MS167s (SELF CHECK)
_      5 500 KV SWYD (SELF CHECK)
_      6 SGFP Trip (SELF CHECK)
_      7 23 CV PP (SELF CHECK)
__ 8 21 Charging pump in service 9 25 CFCU CIT
_    10 23 Charging pump CIT 11 IOP-3 open and complete up to Section 4.3, Power Operation.
12 Complete Attachment 2 "Simulator Ready-for-Training/Examination Checklist."
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 6 of 29 Note: Tables with blue headings may be populated by external program, do not change column name without consulting Simulator Support group Description
                    --- ---        -                          -              --  - ---                -    ---*
EVENT ACTION: MONP254 <10 II CONT ROD BANK C < 10 ( RX TRIP )
1            COMMAND:
PURPOSE: <update as needed>
SELF-          Description                                                  Delay      Initial    Ramp          Trigger      Severity CHECK                                                                        Time        Value      Time 01      PR0016A PZR PRESS CH I PT455 FAILS H/L                        N/A          N/A        N/A          RT-1          2500 02      RD0267 ANY ROD S INADVERTENTLY DROPS                          NIA          N/A        N/A          RT-3            3 MS0090Ar 21 Main Steam Line Leak Inside Cont 03                                                                    N/A          N/A        N/A          RT-5            2 AFTER orifice 04      RP0279A AUTO MSLIS FAILS TO ACT, TRNA                        NIA          NIA        NIA            NIA 05      RP0279B AUTO MSLIS FAILS TO ACT, TRN B                        N/A          N/A        NIA            NIA 06      MS0092E 21MS167 FAILS OPEN                                    N/A          NIA        NIA            NIA 07      MS0092F 22MS167 FAILS OPEN                                    Ni A        NIA        N/A            N/A 08      MS0092G 23MS167 FAILS OPEN                                    NiA          NIA        NIA          N/A 09      MS0092H 24MS167 FAILS OPEN                                    N/A          NIA        N/A          NIA 10      RP0274A AUTO SI FAILS TO ACT, TRNA                            NIA          N/A        N/A          N/A 11      RP0274B AUTO SI FAILS TO ACT, TRN B                          NIA          NIA        N/A          NiA 12      AF0181A 21 AUX FEEDWATER PUMP TRIP                        00:05:00      N/A          NIA          ET-1 13      RP318L 1 21 CS Pum Fails to Start on SEC                      NIA          N/A        NIA            NIA 14      RP318L2 22 CS Pum Fails to Start on SEC                      NIA          NIA        NIA            NIA SELF-          Description                                                Delay        Initial    Ramp          Trigger      Condition CHECK                                                                        Time        Value      Time 01      CV52D 23 CHG PUMP BKR CONTROL POWER                          N/A        N/A        N/A            NIA          OFF 02      PR34D PORV STOP VALVE 2PR6 TAGGED                            N/A        NIA        N/A            RT-7        TAGGED 03      SP01A1 Prevailing Wind Speed                                  NIA        N/A        N/A            N/A            10 04      SP01A2 Prevailin Wind Direction                              N/A        N/A        NIA            NIA            160 05      CT195-1D 25 CFCU BKR #1 Hi h S eed 125VDC                    N/A        N/A        NIA            NIA          OFF 06      CT195-2D 25 CFCU BKR #2 Hi h Speed 125VDC                    N/A        NIA        NIA            NIA          OFF
                                                                                                                                -----*
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 7 of 29 07  I CT195-3D 25 CFCU BKR #3 Low Speed 125VDC    NIA      N/A        N/A      N/A  I ___OFF_]
SELF-        Description                                Delay    Initial  Ramp      Trigger  Condition/
CHECK                                                  Time    Value      Time                Severity 01    Cl11 CLO QCl11HR2 TURNING GEAR-ENGAGED      N/A      N/A        N/A      NIA        ON 02    Cl11 E LO QCl11PR2 TURNING GEAR-STARTED    N/A      NIA      N/A      NIA        ON 03    Cl11 FLO QCl11TG2 TURNING GEAR-STOPPED      N/A      NIA      N/A      NIA        OFF 04    Cl11 D LO QCl11LG2 TURNING GEAR-DISENGAGED  NIA      ~~!A      NIA      WA        OFF
: 1. None PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 8 of 29 A. State shift job assignments.
B. Hold a shift briefing, detailing instruction to the shift: (provide crew members a copy of the shift turnover sheet).
C. Inform the crew "The simulator is running. You may commence panel walkdowns at this time.
CRS please inform me when your crew is ready to assume the shift".
D. Allow sufficient time for panel walk-downs. When informed by the CRS that the crew is ready to assume the shift, ensure the simulator is cleared of unauthorized personnel.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 9 of 29 Eva'1aitodln$fructQr~ActivitY' ,      'Ex'Pected 1?lan,t1stildi;tnt Response                        SBT'          *.*'#'~
::,wv' 0 vommen<    '"t''*".
                                                                                                                  *~t        //**1i~'~
                                          ,. 'w  */'.; ;(f' ; ;"'  *./ : 'we -*'''Y0J'o' .~il!i ~'Ir' l!OG, ,*
: 1. Power ascension CRS directs power ascension using Main Steam Dumps and control rods.
PO raises steam dump demand.
RO adjusts control rods to maintain Tave on program.
RO announces when POAH is observed.
Continue to next event on direction from Lead evaluator.
: 2. Controlling PZR pressure instrument fails HIGH SimulatQr Operato,r: Insert RT-1 on directiOn from Lead EvalUatOr:&deg; MALF: MALF: PR0016A PZR Press CHI (PT-455) fails H/L Final Value: 2500
* RO announces unexpected OHA alarms D-8 RC Press HI, and E-42 2PR1 Yz Trip.
RO determines actual pressure is not high and reports spray valves open, and recommends placinq Master Pressure Controller in manual.
CRS directs RO to place Master Pressure Controller in manual.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Pag.e 10 of 29 Evafuatoilinsfructor,~ctlvi~                Eii>ec\iae1antl~tua~.111*. Response                 **seT l
i'g~j    /il   q :i;       .*~**  .1t~**  ,. ,)ii, . : ;*r/*' J*~  LOG/ .
RO takes manual control of Master Pressure controller, and lowers demand (increase pressure) to close sprays.
CRS enters S2.0P-AB.PZR-001, Pressurizer Pressure Malfunction.
CRS directs initiation of AB.PZR CAS.
CRS gives band for control of PZR pressure.
RO identifies PZR Press Channel I failed high.
RO selects Channel Ill for control.
RO matches master pressure controller demand to current pressure and returns Master Pressure Controller to AUTO.
RO shuts 2PR6.
Note: The requirement to shut 2PR6 and deenergize it is within one hour of the PZR Pressure Channel I instrument failure IAW Tech Specs.
CRS directs WCC to remove power from 2PR6.
Simulator Operator: Insert RT-7 2 minutes after being directed to remove power from 2PR6.
REMOTE: PR340 PORV Stop PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 11of29
:1~pwev:a1uatc>rnat1tructor Aottiify        'Tuexpected)>fiint/~tudenf  Response        ;;iffS'BT iiii'!iv}}r***                  *~!:'aorri'ment ,}}}}Tu.~ **
  ""'"*-. . '"   . w-, .,     ~,,
                                                '~" '                                                              ,"*c;-ilii0)i'.f> * ,J::
Valve 2PR6 taaaed CRS directs PO to initiate removing failed channel from service and contact l&C for support IAW S2.0P-SO.RPS-003.
PO checks that tripping associated bistables will not result in an ESF or RPS actuation.
Note: Crew may wait for l&C response before performing any actions in S2. OP-SO. RPS-0003.
PO verifies that Channel Ill is selected for Master Pressure Control.
PO selects PZR Pressure recorder to channel other than I.
CRS enters TSAS 3.3.1.1 Action 6, 3.3.2.1.b Action 19*, 3.4.5.b, and 3.2.5.
Proceed to next event on direction from Lead Evaluator.
Proceed to next event on direction from Lead Evaluator.
: 3. Dropped control rod Simulator Operator:
: 3. Dropped control rod Simulator Operator: Insert RT-3 1: oh direction from Lead Evaluator.
Insert RT-3 1: oh direction from Lead Evaluator.  
                -         . ~
-. MALF: .RD0064.ANY.ROD INADVERTENTLY DROPS Severitv:
MALF: .RD0064.ANY.ROD INADVERTENTLY DROPS Severitv: 3 RO reports unexpected OHA E-48 ROD PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
3 Response ' CRS directs PO to initiate removing failed channel from service and contact l&C for support IAW S2.0P-SO.RPS-003.
 
PO checks that tripping associated bistables will not result in an ESF or RPS actuation.
TQ-AA-106-0204 Page 12 of 29
PO verifies that Channel Ill is selected for Master Pressure Control. PO selects PZR Pressure recorder to channel other than I. CRS enters TSAS 3.3.1.1 Action 6, 3.3.2.1.b Action 19*, 3.4.5.b, and 3.2.5. RO reports unexpected OHA E-48 ROD ;;iffS'BT iiii'!iv}}r***
                  . . !h:t8~,~~ivi.tJ#~,                                                  .
TQ-AA-106-0204 Page 11of29
                                                        ~,;*a~iJsi'ud ftl~rnSRT              *v* 1iL "'
** ,"*c;-ilii0)i'.f>
                                                                                            'C. Ltr6i.
* ,J:: PSEG Restricted  
BOTTOM, and reports Shutdown Bank rod 1SA3 rod bottom liaht is illuminated.
-Possession Requires Specific Permission from Nuclear Training
CRS enters S2.0P-AB.ROD-0002, Dropped Rod.
....
RO reoorts control rods are in manual.
Simulator Operator:
PO reoorts Main Turbine is S/D.
Once rod insertion has commenced, insert RT-5 on direction from Lead Evaluator' MALF: MS0090Ar .. Severitv:
RO reports the reactor is subcritical as a result of the droooed rod.
2 4. 21 SG steam leak I rupture in containment BOTTOM, and reports Shutdown Bank rod 1 SA3 rod bottom liaht is illuminated.
CRS directs RO to insert all control and shutdown bank rods.
CRS enters S2.0P-AB.ROD-0002, Dropped Rod. RO reoorts control rods are in manual. PO reoorts Main Turbine is S/D. RO reports the reactor is subcritical as a result of the droooed rod. CRS directs RO to insert all control and shutdown bank rods. RO initiates insertion of control rods in manual. PO announces OHA C-38, CFCU LK DET HI as unexpected, and shortly after, OHA C-30, CFCU LK DET HI-HI as well. PO refers to ARP for OHA C-38 and C-30. PO reoorts indications of a steam leak inside .
RO initiates insertion of control rods in manual.
'C. Ltr6i. PSEG Restricted  
Simulator Operator: Once rod insertion has commenced, insert RT-5 on direction from Lead Evaluator' MALF: MS0090Ar .
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 12 of 29 *v* 1iL "'
Severitv: 2
Evaluator/Instructor Activity Note: A MSLI will be required to attempt to isolate the steam leak in containment.
: 4. 21 SG steam leak I rupture in containment PO announces OHA C-38, CFCU LK DET HI as unexpected, and shortly after, OHA C-30, CFCU LK DET HI-HI as well.
The CRS can use the CAS of AB.STM for direction, or will use Step 11 in TRIP-1 when containment pressure exceeds 15 psig. Auto and Manual MSLI are Expected Plant/Student Response containment including:  
PO refers to ARP for OHA C-38 and C-30.
-Containment pressure rising -Tavg slowly lowering -Rising steam flows on all loops -Steam dump demand lowerinq CRS enters S2.0P-AB.STM-0001, Excessive Steam Flow. CRS directs monitorinq of AB.STM CAS. CRS notifies Emergency Services of the steam leak. PO reports that the Main Turbine is not latched. PO reports no indication of MS10 or steam dump valves malfunction.
PO reoorts indications of a steam leak inside PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
RO reports no indication of a SG Safety Valve partially open or leakinq. RO reports Rx power and RCS temperature are NOT stable. CRS directs the RO to trip the Rx. SBT LOG PSEG Restricted  
 
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 13 of 29 Comment 
TQ-AA-106-0204 Page 13 of 29 Evaluator/Instructor Activity         Expected Plant/Student Response             SBT                    Comment LOG containment including:
,
                                              - Containment pressure rising
failed and will not actuate. Simulator Operator:
                                              - Tavg slowly lowering
After the Rx is tripped, then MODIFY MALF MS0090Ar to 100 with a 5 minute ramo. . Simulator .op.erafo6'Ellsure is true upon the Rxtrip.' Thistrips 21 AFW.pump after a 5 minute delav. 5. All MSIVs fail to shut *nf/Stuaent Rel onsef/ . ;Jltf \&#xa5;*': I .*I
                                              - Rising steam flows on all loops
* I RO trios the Rx and confirms the Rx . IF using AB.STM CAS, then RO will attempt a MSLI, and reoorts it did not actuate. IF using AB.STM CAS, RO reports the steam leak is NOT isolated.
                                              - Steam dump demand lowerinq CRS enters S2.0P-AB.STM-0001, Excessive Steam Flow.
RO continues Immediate Actions of TRIP-1: Reports the Main Turbine is tripped. Reports all 4KV vital buses are energized.
CRS directs monitorinq of AB.STM CAS.
Reports a demand for Safety Injection is present and Safety Injection has NOT actuated (or reports Safety injection was manuallv initiated as described in PSEG Restricted  
CRS notifies Emergency Services of the steam leak.
-Possession Requires Specific Permission from Nuclear Training I TQ-AA-106-0204 Page 14 of 29 L'' *v>.1 ;> * 
PO reports that the Main Turbine is not latched.
.
PO reports no indication of MS10 or steam dump valves malfunction.
J,;>< , =
RO reports no indication of a SG Safety Valve partially open or leakinq.
: , r bf' i y Note: With all SGs faulted, AFW flow should not be isolated to any SG. 6. 21 AFW pump trip 7. Containment Spray pumps fail to start <'i jt&sect;JI[ .*J ,,;,. *Ai./ 1 if"'' j** * .. * .;/ {ii'' * /1'"' * : ... , ** ,,,. * <>lP' LU\.:J .j previous step). RO initiates Safety Injection (if not previously performed.)
RO reports Rx power and RCS temperature are NOT stable.
CRS directs the RO to trip the Rx.
Note: A MSLI will be required to attempt to isolate the steam leak in containment. The CRS can use the CAS of AB.STM for direction, or will use Step 11 in TRIP-1 when containment pressure exceeds 15 psig. Auto and Manual MSLI are PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 14 of 29
    ,e~~~~at~Zlir**                                        *nf/Stuaent Rel onsef/ .                                      L'' ~4'
                                                                                            *&#xa5;&#xa5;>~~~:rz:I
                                                                                                                      *v>.1 ;>
                                                          ;Jltf \&#xa5;*': l~l ~I,, r.0~~i!f *
                                                                                                                                ~*
I    .*I            I
      , ~,:;\*                                                                                                  I failed and will not actuate.
Simulator Operator: After the Rx is tripped, then MODIFY MALF MS0090Ar to 100 with a 5 minute ramo.
RO trios the Rx and confirms the Rx      tri~ .
.Simulator .op.erafo6'Ellsure ET~f is true upon the Rxtrip.' Thistrips 21 AFW.pump after a 5 minute delav.
: 5. All MSIVs fail to shut IF using AB.STM CAS, then RO will attempt a MSLI, and reoorts it did not actuate.
IF using AB.STM CAS, RO reports the steam leak is NOT isolated.
RO continues Immediate Actions of TRIP-1:
Reports the Main Turbine is tripped.
Reports all 4KV vital buses are energized.
Reports a demand for Safety Injection is present and Safety Injection has NOT actuated (or reports Safety injection was manuallv initiated as described in PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 15 of 29
.J,;><.~:eva1uator1fr:l$t
        , ~* ~~gsi : 'j.}~,r~ , ~
r Atilvity~***                                                                                                          ~t'1'? ;!'''\''
        =
bf' i~df i ~,~:!I:
y
                                                        <'i jt&sect;JI[ .*J ,,;,. *Ai./ 1 if"'' j** * ..* .;/ {ii'' * /1'"' * : ... ,**,,,. * <>lP' LU\.:J .j previous step).
RO initiates Safety Injection (if not previously performed.)
Note: With all SGs faulted, AFW flow should not be isolated to any SG.
PO reports SEC loading is not complete.
PO reports SEC loading is not complete.
PO reports all available equipment started. PO reports 21 and 22 AFW pumps are running, and if not previously performed, receives permission to throttle total AFW flow to no less than 22E4 lbm/hr. PO reports valve groups in Table B are in Safequards position.
PO reports all available equipment started.
RO reports 21 and 22CA330 are shut. PO reports when 21 AFW pump trips, and adjusts AFW flow if required.
PO reports 21 and 22 AFW pumps are running, and if not previously performed, receives permission to throttle total AFW flow to no less than 22E4 lbm/hr.
RO reports containment pressure has not remained less than 15 psig. RO initiates Phase B and Spray actuation.
PO reports valve groups in Table B are in Safequards position.
PSEG Restricted  
RO reports 21 and 22CA330 are shut.
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 15 of 29  
: 6. 21 AFW pump trip PO reports when 21 AFW pump trips, and adjusts AFW flow if required.
;!'''\'' 
: 7. Containment Spray pumps fail to start RO reports containment pressure has not remained less than 15 psig.
*
RO initiates Phase B and Spray actuation.
% .;, -l'.i : /,'%&sect;' , , , ,,, \(",
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
* p '/W ;1 '':'. .1: .i;'.tt >.;;bf' . p .. :.lJil* ' l"'"set::
 
LOG . '" ,, .. .. . .. RO reports neither Containment Spray pump has started. RO blocks 2A and 2C SECs. PO resets 2A and 2C SEC's. RO starts 21 and 22 CS pumps. CT#.1 (CT-3) Manually start at least one Containment Spray . pump before a red path
TQ-AA-106-0204 Page 16 of 29
* challenge develops c>n'thEt containment CSF. ' . SAT UNSAT RO reports MSLI has failed to close any MSIV. RO stops all RCPs. RO reports MSLI has failed to close any MSIV. CRS dispatches operators to place valves from Table D {locally close MSIVs) in safeguards position if not previously performed.
    *evat$la~or11o*struciofActi'!JtY"
        % .;, -l'.i : /,'%&sect;'  ;-,_'t#lf~' ,, , ,,, \(",
Ex'ecteci1'Plant1studenlResz~on$e
* p '/W ;1 '':'.
                                                                                  .
                                                                                    .1: .i;'.tt >.;;bf' .p ..:.lJil* '
                                                                                                '" ,,.. ..
l"'"set::
LOG ...
                                                                                                                                    .~*co~.ie~:;w. A*:
* RO reports neither Containment Spray pump has started.
RO blocks 2A and 2C SECs.
PO resets 2A and 2C SEC's.
RO starts 21 and 22 CS pumps.
CT#.1 (CT-3) Manually start at least one Containment Spray
. pump before a red path
* challenge develops c>n'thEt containment CSF. '
      .
SAT                       UNSAT RO reports MSLI has failed to close any MSIV.
RO stops all RCPs.
RO reports MSLI has failed to close any MSIV.
CRS dispatches operators to place valves from Table D {locally close MSIVs) in safeguards position if not previously performed.
PO reports all 4KV vital buses are energized.
PO reports all 4KV vital buses are energized.
RO reports control room ventilation is in Accident Pressurized mode. PSEG Restricted
RO reports control room ventilation is in Accident Pressurized mode.
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 16 of 29 .
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
.. A *: ** 
* <\.Eva11
* i, 1. Y$[
* i:;SBT +1trw* i .. RO reports 2 switchgear supply and 1 exhaust fan are runninq. RO reports 2 CCW pumps runninq. RO reports ECCS flow as expected for current RCS pressure.
PO maintains total AFW flow greater than 22E4 lbm/hr until at least one SG NR level is >15% (adverse), then maintains SG NR level 19-33%. RO reports no RCPs are runninq. RO reports RCS Tcolds are droppinq.
PO reports no dumpinq steam. RO reports MSLI failed to isolate anv MSIV. RO reports both RTBs are open. RO reports both PZR PORVs are closed. RO reports 2PR6 is shut, and 2PR7 is open. CRS dispatches operator to restore power to 2PR6 if deenerqized.
RO reports no RCPs are running. RO maintains seal injection flow to all RCPs. PSEG Restricted
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 17 of 29
.. 
;.,;i:Ev Iv; . ;y**<*
* 14f:1t *X;; ',
:{' ' ,; :<Jr A,cih1ity
:
Note: CFSTs are in effect when transition out of TRIP-1 occurs. STA will report to control room 10 minutes after being summoned via page to monitor CFSTs. Note: 23 AFW pump may be left in "' '' '''" '. .. ,...., .
d ..... PO reports all SG pressures are dropping in an uncontrolled manner or completely depressurized with MSLI failure. CRS transitions to EOP-LOSC-1, Loss of Secondary Coolant. RO reports MSLI failed to shut any MSIV, all MS? and MS18 valves are shut, and action has been directed to locally shut MSIVs. PO reports all SG pressures are dropping in an uncontrolled manner. CRS transitions to EOP-LOSC-2, Multiple Steam Generator Depressurization.
PO reports all valves in table A are shut except for all MSIVs. CRS dispatches operators, if not previously performed, to locally shut valves in Table A one loop at a time. CRS determines 23 AFW pump in service, and either stops 23 AFW pump or leaves it in service. PSEG Restricted  
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 18 of 29 


* ,, E"pe,c:;ted PlanfiStuCleQtResp'onse'' , ,p;;'?:SBT 1;.iiir' service if it is determined it is necessary to maintain minimum AFW flow to keep SG tubes wet. IF required, PO lowers 23 AFW pump speed to minimum, trips then stops 23 AFW pump. IF required, CRS dispatches operator to shut 21 and 23MS45 steam supplies to 23 AFW pump. RO reports RCS cooldown rate is >100&deg;F I hr. PO reduces AFW flow to each SG to no less than 1.0E4 lbm I hr. CT#2 (CT.;33) Control the AFW rate to notless'than 1E4 lbm/hr to minimize the cooldownrate.
TQ-AA-106-0204 Page 17 of 29
SAT UNSAT When ST A reports RED path on Heat Sink, CRS transitions to FRHS-1, verifies operator action was cause of RED path, and returns to procedure in effect. RO reports RCS Thots are dropping.
* <\.Eva11 i,  1. Y$[
RO reports RCS pressure, and reports a cooldown is in progress or RCPs are secured. RO reports both PZR PORVs are closed. RO reports 2PR6 is shut, and 2PR7 is open. PSEG Restricted  
            *        * ''t'ExpectedPl~nt/Student"Re~ponse            i:;SBT +1trw*          cbr~;pnegt ..
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 19 of 29 co.mment 4.i;;
                                                                                                ~J&> )#~,,~
, EvaluatorUnstructor
i    ..
,,  
RO reports 2 switchgear supply and 1 exhaust fan are runninq.
)1 ,'  
RO reports 2 CCW pumps runninq.
/  
RO reports ECCS flow as expected for current RCS pressure.
;;{  
PO maintains total AFW flow greater than 22E4 lbm/hr until at least one SG NR level is
'
                    >15% (adverse), then maintains SG NR level 19-33%.
E;xpecteCl.:.PJanllSfUdenf Re,sponse SBT RO resets SI, Phase A, and Phase B. RO opens 21 and 22CA330. PO reports all SECs are reset. PO reports all 230V Control Centers reset. RO resets SGBD Sample Isolation Bypass, and opens 21-24SS94s.
RO reports no RCPs are runninq.
CRS directs Chemistry to sample SGs for activity and boron. PO reports no indication of any SGTR. RO reports RHR pumps running with suction from RWST, and no discharqe flow. RO reports RCS pressure is stable or rising, and stops both RHR pumps .. RO reports both CS pumps are runninq. RO reports containment pressure.
RO reports RCS Tcolds are droppinq.
PO reports no dumpinq steam.
RO reports MSLI failed to isolate anv MSIV.
RO reports both RTBs are open.
RO reports both PZR PORVs are closed.
RO reports 2PR6 is shut, and 2PR7 is open.
CRS dispatches operator to restore power to 2PR6 if deenerqized.
RO reports no RCPs are running.
RO maintains seal injection flow to all RCPs.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 18 of 29
    ;.,;i:Ev Iv; .;y**<*
* 5~m ,nt 1
14f:1t *X;; tlf~3J()r[!                        :<Jr A,cih1ity
~' ', '~ .~ .J'.~t"''', :{' ' ,; '.";;,t;t~ ~>'  v,,,ir<~f' : ','.\~~J;,,,              '. .. ,....,  .                      .....
                                                                            "'    '' '''"                    ~-,.
d  ~*
PO reports all SG pressures are dropping in an uncontrolled manner or completely depressurized with MSLI failure.
CRS transitions to EOP-LOSC-1, Loss of Secondary Coolant.
Note: CFSTs are in effect when transition out of TRIP-1 occurs.
STA will report to control room 10 minutes after being summoned via page to monitor CFSTs.
RO reports MSLI failed to shut any MSIV, all MS? and MS18 valves are shut, and action has been directed to locally shut MSIVs.
PO reports all SG pressures are dropping in an uncontrolled manner.
CRS transitions to EOP-LOSC-2, Multiple Steam Generator Depressurization.
PO reports all valves in table A are shut except for all MSIVs.
CRS dispatches operators, if not previously performed, to locally shut valves in Table A one loop at a time.
CRS determines 23 AFW pump in service, and either stops 23 AFW pump or leaves it in service.
Note: 23 AFW pump may be left in PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 19 of 29 EvalMe1f8r~1,nitructo~Ac** *            ,, E"pe,c:;ted PlanfiStuCleQtResp'onse''   , ,p;;'?:SBT1;.iiir'     co.mment 4.i;;
:.f',~,:/~\* ,,~{/'": '~;' c;;,~1;'
service if it is determined it is necessary to maintain minimum AFW flow to keep SG tubes wet.
IF required, PO lowers 23 AFW pump speed to minimum, trips then stops 23 AFW pump.
IF required, CRS dispatches operator to shut 21 and 23MS45 steam supplies to 23 AFW pump.
RO reports RCS cooldown rate is >100&deg;F I hr.
PO reduces AFW flow to each SG to no less than 1.0E4 lbm I hr.
CT#2 (CT.;33) Control the AFW rate to notless'than 1E4 lbm/hr to minimize the cooldownrate.
SAT               UNSAT When STA reports RED path on Heat Sink, CRS transitions to FRHS-1, verifies operator action was cause of RED path, and returns to procedure in effect.
RO reports RCS Thots are dropping.
RO reports RCS pressure, and reports a cooldown is in progress or RCPs are secured.
RO reports both PZR PORVs are closed.
RO reports 2PR6 is shut, and 2PR7 is open.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 20 of 29
        , EvaluatorUnstructor Aalvi~}t                                                    E;xpecteCl.:.PJanllSfUdenf Re,sponse    SBT                    '?rii%;:,~3;f:~+t/:, . .
, ;'.;,l~Jti ) 1,' /,;t(~J:},~ (~;~; / 'i!~{'~'""" ;;{ :~<thl~'~ ' "";';'""'',~}>~t"'
RO resets SI, Phase A, and Phase B.
RO opens 21 and 22CA330.
PO reports all SECs are reset.
PO reports all 230V Control Centers reset.
RO resets SGBD Sample Isolation Bypass, and opens 21-24SS94s.
CRS directs Chemistry to sample SGs for activity and boron.
PO reports no indication of any SGTR.
RO reports RHR pumps running with suction from RWST, and no discharqe flow.
RO reports RCS pressure is stable or rising, and stops both RHR pumps ..
RO reports both CS pumps are runninq.
RO reports containment pressure.
If/when containment pressure is <13 psig, then RO:
If/when containment pressure is <13 psig, then RO:
* Resets Spray actuation
* Resets Spray actuation
* Stops both CS pumps
* Stops both CS pumps
* Shuts 21 and 22CS2 CS pump discharge valves PSEG Restricted  
* Shuts 21 and 22CS2 CS pump discharge valves PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 20 of 29
... 


*
TQ-AA-106-0204 Page 21of29
* ianffstuUenf"'ResP'Qose SSTi7i!l''
,1;1ir"evii'uatorlinstrllctoFActi~itY'::;* **     ffEx.lfe'l:t  ianffstuUenf"'ResP'Qose         SSTi7i!l''         corii'riient'1i1ft**
ffEx.lf e'l:t [; ; J' 3' , ,,01": *.
v~~r::
1:tz LO(J" :: RO reports RWST lo level alarm has not actuated.
[; ;             J' 3' , ,,01": *.~:rz    1:tz LO(J" ::                 *~ ',;-''\'
RO reports RWST lo level alarm has not actuated.
RO reports RCS Thats status. IF <375, PO removes lockouts for 21-24SJ54's, and RO shuts 21-24SJ54's.
RO reports RCS Thats status. IF <375, PO removes lockouts for 21-24SJ54's, and RO shuts 21-24SJ54's.
RO reports subcoolinQ is >0&deg;F. RO reports RCS pressure and trend. RO reports RCS pressure is stable or rising and:
RO reports subcoolinQ is >0&deg;F.
RO reports RCS pressure and trend.
RO reports RCS pressure is stable or rising and:
* Realigns charging pump through normal charging line and adjusts 2CV55 to maintain PZR level >33%.
* Realigns charging pump through normal charging line and adjusts 2CV55 to maintain PZR level >33%.
* Reports PZR level trend . Simulator Operator:
* Reports PZR level trend .
When Step 20 is complete then shut 23MS167 by deleting MAL.F MS0092G and . ensurino 23MS167 shuts. PO reports indication of 23MS 167 being shut. CRS determines pressure rise in 23 SG requires transition to LOSC-1. CRS transitions to LOSC-1. Terminate the scenario when the transition to LOSC-1 is announced.
Simulator Operator: When Step 20 is complete then shut 23MS167 by deleting MAL.F MS0092G and .
PSEG Restricted  
ensurino 23MS167 shuts.
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 21of29 corii'riient'1i 1 ft** ',;-''\'
PO reports indication of 23MS 167 being shut.
A. Alarm Response Procedures (Various)
CRS determines pressure rise in 23 SG requires transition to LOSC-1.
B. Technical Specifications C. Emergency Plan (ECG) D. OP-AA-101-111-1003, Use of Procedures E. S2.0P-IO.ZZ-0003, Hot Standby to Minimum Load F. S2.0P-AB.PZR-0001, Pressurizer Pressure Malfunction G. S2.0P-AB.ROD-0002, Dropped Rod H. S2.0P-AB.STM-0001, Excessive Steam Flow I. 2-EOP-TRIP-1, Reactor Trip or Safety Injection J. 2-EOP-LOSC-1 Loss of Secondary Coolant K. 2-EOP-LOSC-2 Multiple Steam Generator Depressurization TQ-AA-106-0204 Page 22 of 29 PSEG Restricted
CRS transitions to LOSC-1.
-Possession Requires Specific Permission from Nuclear Training ATTACHMENT 1 UNIT TWO PLANT STATUS TODAY MODE: 1 POWER: 1x10-8 A RCS BORON: SHUTDOWN SAFETY SYSTEM STATUS (5, 6 & DEFUELED):
Terminate the scenario when the transition to LOSC-1 is announced.
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 22 of 29 A. Alarm Response Procedures (Various)
B. Technical Specifications C. Emergency Plan (ECG)
D. OP-AA-101-111-1003, Use of Procedures E. S2.0P-IO.ZZ-0003, Hot Standby to Minimum Load F. S2.0P-AB.PZR-0001, Pressurizer Pressure Malfunction G. S2.0P-AB.ROD-0002, Dropped Rod H. S2.0P-AB.STM-0001, Excessive Steam Flow I. 2-EOP-TRIP-1, Reactor Trip or Safety Injection J. 2-EOP-LOSC-1 Loss of Secondary Coolant K. 2-EOP-LOSC-2 Multiple Steam Generator Depressurization PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 23 of 29 ATTACHMENT 1 UNIT TWO PLANT STATUS TODAY MODE:     1       POWER:     1x10-8 A   RCS BORON:       1711          MWe      0 SHUTDOWN SAFETY SYSTEM STATUS (5, 6 & DEFUELED):
NA REACTIVITY PARAMETERS Control Bank D at 130 steps withdrawn.
NA REACTIVITY PARAMETERS Control Bank D at 130 steps withdrawn.
Core burnup 500 EFPH. MOST LIMITING LCO AND DATE/TIME OF EXPIRATION:
Core burnup 500 EFPH.
3.6.2.3 for 25 CFCU action a expires in 165 hours. 1711 EVOLUTIONS/PROCEDURES/SURVEILLANCES IN PROGRESS:
MOST LIMITING LCO AND DATE/TIME OF EXPIRATION:
TQ-AA-106-0204 Page 23 of 29 MWe 0 S2.0P-IO.ZZ-0003, Hot Standby to Minimum Load complete up to Section 4.3, Power Operation.
3.6.2.3 for 25 CFCU action a expires in 165 hours.
EVOLUTIONS/PROCEDURES/SURVEILLANCES IN PROGRESS:
S2.0P-IO.ZZ-0003, Hot Standby to Minimum Load complete up to Section 4.3, Power Operation.
ABNORMAL PLANT CONFIGURATIONS:
ABNORMAL PLANT CONFIGURATIONS:
CONTROL ROOM: Unit 1 and Hope Creek at 100% power. PRIMARY: 21 Charging pump in service 23 Charging pump CIT for emergent repair, expected return in 2 hours 25 CFCU CIT for breaker replacement SECONDARY:
CONTROL ROOM:
Unit 1 and Hope Creek at 100% power.
PRIMARY:
21 Charging pump in service 23 Charging pump CIT for emergent repair, expected return in 2 hours 25 CFCU CIT for breaker replacement SECONDARY:
21 SGFP in service 22 SGFP O/S with steam supply valves shut RADWASTE:
21 SGFP in service 22 SGFP O/S with steam supply valves shut RADWASTE:
No discharges in progress CIRCULATING WATER/SERVICE WATER: PSEG Restricted  
No discharges in progress CIRCULATING WATER/SERVICE WATER:
-Possession Requires Specific Permission from Nuclear Training ATTACHMENT 2 SIMULATOR READY FOR TRAINING CHECKLIST
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
: 1. Verify simulator is in "TRAIN" Load 2. Simulator is in RUN 3. Overhead Annunciator Horns ON 4. All required computer terminals in operation
 
TQ-AA-106-0204 Page 24 of 29 ATTACHMENT 2 SIMULATOR READY FOR TRAINING CHECKLIST
: 1. Verify simulator is in "TRAIN" Load
: 2. Simulator is in RUN
: 3. Overhead Annunciator Horns ON
: 4. All required computer terminals in operation
: 5. Simulator clocks synchronized
: 5. Simulator clocks synchronized
: 6. All tagged equipment properly secured and documented
: 6. All tagged equipment properly secured and documented
: 7. TSAS Status Board up-to-date
: 7. TSAS Status Board up-to-date
: 8. Shift manning sheet available
: 8. Shift manning sheet available
: 9. Procedures in progress open and signed-off to proper step TQ-AA-106-0204 Page 24 of 29 10. All OHA lamps operating (OHA Test) and burned out lamps replaced 11. Required chart recorders advanced and ON (proper paper installed)
: 9. Procedures in progress open and signed-off to proper step
: 12. All printers have adequate paper AND functional ribbon 13. Required procedures clean 14. Multiple color procedure pens available
: 10. All OHA lamps operating (OHA Test) and burned out lamps replaced
: 11. Required chart recorders advanced and ON (proper paper installed)
: 12. All printers have adequate paper AND functional ribbon
: 13. Required procedures clean
: 14. Multiple color procedure pens available
: 15. Required keys available
: 15. Required keys available
: 16. Simulator cleared of unauthorized material/personnel
: 16. Simulator cleared of unauthorized material/personnel
: 17. All charts advanced to clean traces and chart recorders are on. 18. Rod step counters correct (channel check) and reset as necessary
: 17. All charts advanced to clean traces and chart recorders are on.
: 18. Rod step counters correct (channel check) and reset as necessary
: 19. Exam security set for simulator
: 19. Exam security set for simulator
: 20. Ensure a current RCS Leak Rate Worksheet is placed by Aux Alarm Typewriter with Baseline Data filled out 21. Shift logs available if required 22. Recording Media available (if applicable)
: 20. Ensure a current RCS Leak Rate Worksheet is placed by Aux Alarm Typewriter with Baseline Data filled out
: 23. Ensure ECG classification is correct 24. Reference verification performed with required documents available
: 21. Shift logs available if required
: 25. Verify phones disconnected from plant after drill. 26. Verify EGC paperwork is marked "Training Use Only" and is current revision.
: 22. Recording Media available (if applicable)
: 23. Ensure ECG classification is correct
: 24. Reference verification performed with required documents available
: 25. Verify phones disconnected from plant after drill.
: 26. Verify EGC paperwork is marked "Training Use Only" and is current revision.
: 27. Ensure sufficient copies of ECG paperwork are available.
: 27. Ensure sufficient copies of ECG paperwork are available.
PSEG Restricted  
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
-Possession Requires Specific Permission from Nuclear Training ATTACHMENT3 CRITICAL TASK METHODOLOGY TQ-AA-106-0204 Page 25 of 29 In reviewing each proposed CT, the examination team assesses the task to ensure, that it is essential to safety. A task is essential to safety if, in the judgment of the examination team, the improper performance or omission of this task by a licensee will result in direct adverse consequences or in significant degradation in the mitigative capability of the plant. The examination team determines if an automatically actuated plant system would have been required to mitigate the consequences of an individual's incorrect performance.
 
If incorrect performance of a task by an individual necessitates the crew taking compensatory action that would complicate the event mitigation strategy, the task is safety significant.
TQ-AA-106-0204 Page 25 of 29 ATTACHMENT3 CRITICAL TASK METHODOLOGY In reviewing each proposed CT, the examination team assesses the task to ensure, that it is essential to safety. A task is essential to safety if, in the judgment of the examination team, the improper performance or omission of this task by a licensee will result in direct adverse consequences or in significant degradation in the mitigative capability of the plant.
The examination team determines if an automatically actuated plant system would have been required to mitigate the consequences of an individual's incorrect performance. If incorrect performance of a task by an individual necessitates the crew taking compensatory action that would complicate the event mitigation strategy, the task is safety significant.
I. Examples of CTs involving essential safety actions include those for which operation or correct performance prevents ...
I. Examples of CTs involving essential safety actions include those for which operation or correct performance prevents ...
* degradation of any barrier to fission product release
* degradation of any barrier to fission product release
Line 2,122: Line 3,887:
* take one or more actions that would prevent a challenge to plant safety.
* take one or more actions that would prevent a challenge to plant safety.
* prevent inappropriate actions that create a challenge to plant safety (such as an unintentional Reactor Protection System (RPS) or ESF actuation.
* prevent inappropriate actions that create a challenge to plant safety (such as an unintentional Reactor Protection System (RPS) or ESF actuation.
PSEG Restricted  
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
-Possession Requires Specific Permission from Nuclear Training TQ-AA-106-0204 Page 26 of 29 SCENARIO IDENTIFIER:
 
15-01 NRC ESG-3 REVIEWER:
TQ-AA-106-0204 Page 26 of 29 SCENARIO IDENTIFIER:                 15-01 NRC ESG-3               REVIEWER: C Recchione Initials       Qualitative Attributes CR       1. The scenario has clearly stated objectives in the scenario.
C Recchione Initials CR CR CR CR CR CR CR CR CR CR CR CR 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. Qualitative Attributes The scenario has clearly stated objectives in the scenario.
CR      2. The initial conditions are realistic, in that some equipment and/or instrumentation may be out of service, but it does not cue crew into expected events.
The initial conditions are realistic, in that some equipment and/or instrumentation may be out of service, but it does not cue crew into expected events. The scenario consists mostly of related events. Each event description consists of:
CR      3. The scenario consists mostly of related events.
CR      4. Each event description consists of:
* the point in the scenario when it is to be initiated
* the point in the scenario when it is to be initiated
* the malfunction(s) that are entered to initiate the event
* the malfunction(s) that are entered to initiate the event
* the symptoms/cues that will be visible to the crew
* the symptoms/cues that will be visible to the crew
* the expected operator actions (by shift position)
* the expected operator actions (by shift position)
* the event termination point No more than one non-mechanistic failure (e.g., pipe break) is incorporated into the scenario without a credible preceding incident such as a seismic event. The events are valid with regard to physics and thermodynamics.
* the event termination point CR      5. No more than one non-mechanistic failure (e.g., pipe break) is incorporated into the scenario without a credible preceding incident such as a seismic event.
Sequencing/timing of events is reasonable, and allows for the examination team to obtain complete evaluation results commensurate with the scenario objectives.
CR      6. The events are valid with regard to physics and thermodynamics.
The simulator modeling is not altered. All crew competencies can be evaluated.
CR      7. Sequencing/timing of events is reasonable, and allows for the examination team to obtain complete evaluation results commensurate with the scenario objectives.
The scenario has been validated.
CR      8. The simulator modeling is not altered.
If the sampling plan indicates that the scenario was used for training during the requalification cycle, evaluate the need to modify or replace the scenario.
CR      9. All crew competencies can be evaluated.
ESG-PSA Evaluation Form is completed for the scenario at the applicable facility.
CR      10. The scenario has been validated.
PSEG Restricted  
CR      11. If the sampling plan indicates that the scenario was used for training during the requalification cycle, evaluate the need to modify or replace the scenario.
-Possession Requires Specific Permission from Nuclear Training Initial GG GG GG GG GG GG 2 3 1 2 0 2 TQ-AA-106-0204 Page 27 of 29 Quantitative Attributes (as per ES-301-4, and ES-301 Section 0.5.d) Malfunctions after EOP entry: 1-2 Abnormal Events: 2-4 Major Transients:
CR      12. ESG-PSA Evaluation Form is completed for the scenario at the applicable facility.
1-2 EOPs entered/requiring substantive actions: 1-2 EOP contingencies requiring substantive actions: 0-2 EOP based Critical tasks: 2-3 COMMENTS:
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
PSEG Restricted  
 
-Possession Requires Specific Permission from Nuclear Training 15-01 NRC ESG-3 TQ-AA-106-0204 Page 28 of 29 CT#1 (CT-3) Manually actuate at least one Containment Spray pump before an extreme challenge develops to the containment CSF. Basis: Failure to manually actuate the minimum required complement of containment cooling equipment under the postulated conditions demonstrates the inability of the crew to "recognize a failure or an incorrect automatic actuation of an ESF system or component." CT#2 (CT-33) Control the AFW rate to not less than 1 E4 lbm/hr to minimize the cooldown rate. Basis: Failure to control the AFW flow rate to the SGs leads to an unnecessary and avoidable severe challenge to the integrity CSF. Also, failure to perform the critical task increases the challenges to the subcriticality and the containment CSFs beyond those irreparably introduced by the postulated plant conditions.
TQ-AA-106-0204 Page 27 of 29 Initial Quantitative Attributes (as per ES-301-4, and ES-301 Section 0.5.d)
Thus, failure to perform the critical task constitutes a demonstrated inability by the crew to "take one or more actions that would prevent a challenge to plant safety." It also fails to prevent "a significant reduction of safety margin beyond that irreparably introduced by the scenario." Note to Evaluator:
GG      2  Malfunctions after EOP entry: 1-2 GG      3  Abnormal Events: 2-4 GG      1  Major Transients: 1-2 GG      2  EOPs entered/requiring substantive actions: 1-2 GG      0  EOP contingencies requiring substantive actions: 0-2 GG      2  EOP based Critical tasks: 2-3 COMMENTS:
CT numbers in parentheses are the corresponding Westinghouse ERG Rev. 2-based Critical Tasks procedure WCAP-17711-NP PSEG Restricted  
PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
-Possession Requires Specific Permission from Nuclear Training ATTACHMENT 6 --TQ-AA-106-0204 Page 29 of 29 ESG.;PRA RELATIONSHIP EVALUATION EVENTS LEADING TO CORE DAMAGE Y/N Event Y/N Event N TRANSIENTS with PCS Unavailable N Loss of Service Water N Steam Generator Tube Rupture N Loss ofCCW N Loss of Offsite Power N Loss of Control Air N Loss of Switchgear and Pen Area Ventilation N Station Black Out N LOCA COMPONENT/TRAIN/SYSTEM UNAVAILABILITY THAT INCREASES CORE DAMAGE FREQUENCY Y/N COMPONENT, SYSTEM, OR TRAIN Y/N COMPONENT, SYSTEM, OR N Containment Sump Strainers N Gas Turbine N SSWS Valves to Turbine Generator Area N Any Diesel Generator N RHR Suction Line valves from Hot Leg y Auxiliary Feed Pump N CVCS Letdown line Control and Isolation Valves N SBO Air Compressor OPERATOR ACTIONS IMPORTANT IN PREVENTING CORE DAMAGE Y/N OPERATOR ACTION N Restore AC power during SBO N Connect to gas turbine N Trip Reactor and RCPs after loss of component cooling system N Re-align RHR system for re-circulation N Un-isolate the available CCW Heat Exchanger N Isolate the CVCS letdown path and transfer charging suction to RWST N Cooldown the RCS and depressurize the system N Isolate the affected Steam Generator that has the tube rupture(s)
 
N Early depressurize the RCS N Initiate feed and bleed Complete this evaluation form for each ESG.}}
TQ-AA-106-0204 Page 28 of 29 15-01 NRC ESG-3 CT#1 (CT-3) Manually actuate at least one Containment Spray pump before an extreme challenge develops to the containment CSF.
Basis: Failure to manually actuate the minimum required complement of containment cooling equipment under the postulated conditions demonstrates the inability of the crew to "recognize a failure or an incorrect automatic actuation of an ESF system or component."
CT#2 (CT-33) Control the AFW rate to not less than 1E4 lbm/hr to minimize the cooldown rate.
Basis: Failure to control the AFW flow rate to the SGs leads to an unnecessary and avoidable severe challenge to the integrity CSF. Also, failure to perform the critical task increases the challenges to the subcriticality and the containment CSFs beyond those irreparably introduced by the postulated plant conditions. Thus, failure to perform the critical task constitutes a demonstrated inability by the crew to "take one or more actions that would prevent a challenge to plant safety." It also fails to prevent "a significant reduction of safety margin beyond that irreparably introduced by the scenario."
Note to Evaluator: CT numbers in parentheses are the corresponding Westinghouse ERG Rev. 2- based Critical Tasks procedure WCAP-17711-NP PSEG Restricted - Possession Requires Specific Permission from Nuclear Training
 
TQ-AA-106-0204 Page 29 of 29 ATTACHMENT 6
                                                        -      -
ESG.;PRA RELATIONSHIP EVALUATION EVENTS LEADING TO CORE DAMAGE Y/N   Event                                                   Y/N   Event N   TRANSIENTS with PCS Unavailable                         N     Loss of Service Water N   Steam Generator Tube Rupture                             N     Loss ofCCW N   Loss of Offsite Power                                   N     Loss of Control Air N   Loss of Switchgear and Pen Area Ventilation             N     Station Black Out N   LOCA COMPONENT/TRAIN/SYSTEM UNAVAILABILITY THAT INCREASES CORE DAMAGE FREQUENCY Y/N   COMPONENT, SYSTEM, OR TRAIN                           Y/N COMPONENT, SYSTEM, OR TD~ll\I N   Containment Sump Strainers                             N     Gas Turbine N   SSWS Valves to Turbine Generator Area                   N     Any Diesel Generator N   RHR Suction Line valves from Hot Leg                   y     Auxiliary Feed Pump N   CVCS Letdown line Control and Isolation Valves           N     SBO Air Compressor OPERATOR ACTIONS IMPORTANT IN PREVENTING CORE DAMAGE Y/N OPERATOR ACTION N   Restore AC power during SBO N   Connect to gas turbine N   Trip Reactor and RCPs after loss of component cooling system N   Re-align RHR system for re-circulation N   Un-isolate the available CCW Heat Exchanger N   Isolate the CVCS letdown path and transfer charging suction to RWST N   Cooldown the RCS and depressurize the system N   Isolate the affected Steam Generator that has the tube rupture(s)
N   Early depressurize the RCS N   Initiate feed and bleed Complete this evaluation form for each ESG.}}

Revision as of 09:02, 30 October 2019

Final Operating Test (Sections a, B, and C) (Folder 3)
ML17031A347
Person / Time
Site: Salem  PSEG icon.png
Issue date: 12/12/2016
From:
NRC Region 1
To:
Public Service Enterprise Group
Shared Package
ML16076A441 List:
References
U01930
Download: ML17031A347 (252)


Text

{{#Wiki_filter:OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION: SALEM SYSTEM: Reactor Coolant System TASK: Measure Leakage to the Containment Sump TASK NUMBER: N0020080101 JPM NUMBER: 15-01 NRC RO A1-1 ALTERNATE PATH: D KIA NUMBER: ~~~~~~~~~~ 2.1.25 IMPORTANCE FACTOR: 3.9 APPLICABILITY: RO SRO EOD RO[]] STAD SRoD EVALUATION SETTING/METHOD: Classroom

REFERENCES:

S2.0P-AR.ZZ-0003, Overhead Annunciators Window C, Rev. 19 S2.0P-SO.RC-0004, Identifying and Measuring Leakage, Rev. 16 (Both Rev checked 8-9-16) TOOLS AND EQUIPMENT: Calculator VALIDATED JPM COMPLETION TIME: 10 min TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: N/A Developed By: G Gauding Date: 8-9-16 Instructor Validated By: R Evans I N Mulford Date: 9-22-16 I 9-29-16 SME or Instructor ~ Approved By: Oper~ng ~a~r Approved By: Ope~rtment ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY: EVALUATOR'S SIGNATURE: DATE: Page 1 of 7 PSEG Restricted- Possession Requires Specific Permission From Nuclear Training

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: ~~~~~~~~~~~~~~ DATE: ~~~~~~~~~~~~~~ SYSTEM: Reactor Coolant System TASK: Measure Leakage to the Containment Sump TASK NUMBER: N0020080101 SIMULATOR SETUP N/A INITIAL CONDITIONS: Unit 2 is operating at 100% power, steady state, SOL. At 0015, OHA C-2 CNTMT SUMP PMP START unexpectedly annunciates, along with OHA A-41. The Aux typewriter shows 21 containment sump pump has started. 2 minutes later, OHA C-2 clears, OHA A-41 annunciates, and the Aux typewriter shows 21 containment sump pump has stopped. The plant remains stable, no indications of a RCS leak are apparent, and no operations have been performed which would cause containment sump level to rise. INITIATING CUE: You are the RO. Calculate the leak rate into the Containment Sump by performing Section 5.3 of S2.0P-SO.RC-0004, Identifying and Measuring Leakage. Successful Completion Criteria:

1. All critical steps completed.
2. All sequential steps completed in order.
3. All time-critical steps completed within allotted time.
4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made (and NRC concurrence is obtained}.

Task Standard for Successful Completion:

1. Calculate leakage into Containment Sump of 0.85-1.0 gpm.

Page 2 of 7 PSEG Restricted- Possession Requires Specific Permission From Nuclear Training

OPERATOR TRAINING PROGRAM NAME: ~~~~~~~~~~- JOB PERFORMANCE MEASURE DATE: ~~~~~~~~~~ SYSTEM: Reactor Coolant System TASK: Measure Leakage to the Containment Sump STEP COMMENTS STEP (*Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD S/U Evaluation)

Provide blank copy of 82.0P-SO.RC-0004, and marked up copy of Attachment 1. SO.RC-4 !E either Containment Sump Pump 5.3.1 AUTO starts, THEN RECORD the following on Attachment 1, Section 2.0: Records 21 Cont Sump

                    ...
  • Operating Containment Sump Pump Number
    *
  • Time of pump start Records time of pump start as 0015 SO.RC-4 CALCULATE elapsed time in minutes Calculates elapsed time in minutes 5.3.2 between start time and previous between start time and previous Containment Sump Pump stop time Containment Sump Pump stop time and AND RECORD on Attachment 1, records on Attachment 1, Section 2.0 by Section 2.0. using previous stop time of 1855
  • yesterday, and with cue of 0015 today determines elapsed time is 320 minutes.

SO.RC-4 ENSURE no draining, sampling, or 5.3.3 liquid additions to Containment Sump Determines from initial conditions that have occurred during selected time no draining, sampling, or liquid additions frame. to Containment Sump have occurred during selected time frame. Page 3 of 7 PSEG Restricted- Possession Requires Specific Permission From Nuclear Training

OPERATOR TRAINING PROGRAM NAME: ~~~~~~~~~~ JOB PERFORMANCE MEASURE DATE: ~~~~~~~~~~- SYSTEM: Reactor Coolant System TASK: Measure Leakage to the Containment Sump STEP COMMENTS STEP (*Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD S/U Evaluation)

SO.RC-4 CALCULATE Containment Sump Calculates Containment Sump Leak 5.3.4 Leak Rate using Attachment 3. Rate using Attachment 3 (page 1 of 2),

  • and determines the 320 minute line crosses the 0.9 gpm leak rate line.

Note: Due to no increment between 300 and 350 minutes, extrapolation of data may result in leak rate slightly above or below 0.9 gpm. However, the leakrate MUST be determined to be within the bounding numbers for actions required

                                                              >0.85 gpm (to initiate Section 5.6) and
                                                              >1.0 gpm (to initiate S2.0P-ST.RC-0008)

SO.RC-4 RECORD Containment Sump Pump Records Containment Sump Pump stop 5.3.5 stop time and date on Attachment 1, time as 0017 and todays date on Section 2.0. Attachment 1, Section 2.0. SO.RC-4 !E leakage to Containment Sump Determines leakage to Containment 5.3.6 exceeds 1.0 gpm AND Unit in Modes Sump does not exceed 1.0 gpm 1-4, THEN: A. INITIATE S2.0P-ST.RC-0008(Q), Reactor Coolant Water Inventory Balance. B. REFER to Technical Specification 3.4.7.2. Page 4 of 7 PSEG Restricted- Possession Requires Specific Permission From Nuclear Training

OPERATOR TRAINING PROGRAM NAME: ~~~~~~~~~~- JOB PERFORMANCE MEASURE DATE: ~~~~~~~~~~- SYSTEM: Reactor Coolant System TASK: Measure Leakage to the Containment Sump STEP COMMENTS STEP (*Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD S/U Evaluation)

SO.RC-4 !E leakage to Containment Sump Determines leakage to Containment 5.3.7 exceeds 0.85 gpm, THEN INITIATE Sump does exceed 0.85 gpm, and Section 5.6 of this procedure. initiates Section 5.6 of procedure. Terminate JPM when procedure is returned to evaluator. Page 5 of 7 PSEG Restricted- Possession Requires Specific Permission From Nuclear Training

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below.

 ~   W\    ~      1. Task description and number, JPM description and number are identified.

vv M ,,/ 2. Knowledge and Abilities (KIA) references are included.

  \µ N'\   ~      3. Performance location specified. (in-plant, control room, or simulator)
 \y md            4. Initial setup conditions are identified.

Vv N'l A/ 5. Initiating and terminating Cues are properly identified.

\JV Md            6. Task standards identified and verified by SME review.

\f\ M / 7. Critical steps meet the criteria for critical steps and are identified with an asterisk(*).

 ~ N"\ d          8. Verify the procedure referenced by this JPM matches the most current revision of that procedure: Procedure Rev. Jj_ Date t./* z. i. ' t IP
                                                           /C, N'\~         9. Pilot test the JPM:
a. verify Cues both verbal and visual are free of conflict, and
b. ensure performance time is accurate.

____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructor: ~ Date: ,,z. ~I.I SME/lnstructoro {)fLtj ~;l{Vcl J._q_hb_ Date: _ ' \.___{ SME/lnstructor: _ _ _ _ _ _ _ _ _ _ _ __ Date: _ _ _ _ __ Page 6 of 7 PSEG Restricted- Possession Requires Specific Permission From Nuclear Training

INITIAL CONDITIONS: Unit 2 is operating at 100% power, steady state, SOL. At 0015, OHA C-2 CNTMT SUMP PMP START unexpectedly annunciates, along with OHA A-41. The Aux typewriter shows 21 containment sump pump has started. 2 minutes later, OHA C-2 clears, OHA A-41 annunciates, and the Aux typewriter shows 21 containment sump pump has stopped. The plant remains stable, no indications of a RCS leak are apparent, and no operations have been performed which would cause containment sump level to rise. INITIATING CUE: You are the RO. Calculate the leak rate into the Containment Sump by performing Section 5.3 of S2.0P-SO.RC-0004, Identifying and Measuring Leakage. Page 7 of 7 PSEG Restricted- Possession Requires Specific Permission From Nuclear Training

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION: SALEM SYSTEM: Conduct of Operations TASK: Calculate Shutdown Margin TASK NUMBER: N1200030301 JPM NUMBER: 15-01 NRC RO A1-2 ALTERNATE PATH: D KIA NUMBER: ~~~~~~~~~~ 2.1.43 IMPORTANCE FACTOR: 4.1 APPLICABILITY: RO SRO EOCJ R0[8J STAL] SROCJ EVALUATION SETTING/METHOD: Classroom

REFERENCES:

SC.RE-ST.ZZ-0002(0), Rev. 23 SHUTDOWN MARGIN CALCULATION S2.RE-RA.ZZ-0016(Q), Rev. 8 CURVE BOOK (both checked 8-9-16) TOOLS AND EQUIPMENT: None VALIDATED JPM COMPLETION TIME: 30 min TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: 50 minutes Developed By: G Gauding Date: 8-9-16 Instructor Validated By: R Evans I N Mulford Date: 9-22-16 I 9-29-16 SME or lnstructo~l Approved By: Tra~1ent Approved By: Operbrtment ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY: EVALUATOR'S SIGNATURE: DATE: PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 1 of 7

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: ~~~~~~~~~~~~~~- DATE: SYSTEM: Conduct of Operations TASK: Calculate Shutdown Margin TASK NUMBER: N1200030301 INITIAL CONDITIONS: - Unit 2 Reactor Power is 100%.

                      -  All Control Rod Group Demand Counters are at 227 steps.
                      -  Current boron concentration is 300 ppm.
                      -  Current core burn up is 10,000 EFPH.
                      -  Control Rod 105 was been declared INOPERABLE at 1000 today due to not moving out during a rod exercise test. You have been directed to perform a Shutdown Margin Calculation IAW SC.RE-ST.ZZ-0002 to satisfy the action requirement of TSAS 3.1.3.1 Action c.3.
                      - Control Rod 105 has been identified as trippable and is currently at 214 steps.

INITIATING CUE: The current time is 1010. This is a time critical JPM. Time will commence when you are provided with the applicable procedures. When performing calculation, the CRS directs you to use only the tables as directed by SC.RE-ST.ZZ-0002, do not use Figures. Successful Completion Criteria:

1. All critical steps completed
2. All sequential steps completed in order
3. All time-critical steps completed within allotted time
4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made.

Task Standard for Successful Completion:

1. Perform SOM calculation and determine SOM is -2441 (+/- 5 pcm) and SAT.

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 2 of 7

OPERATOR TRAINING PROGRAM NAME: ~~~~~~~~~~- JOB PERFORMANCE MEASURE DATE: ~~~~~~~~~~- System: Conduct of Operations Task: Calculate Shutdown Margin

  • STEP NO. STEP STANDARD EVAL COMMENTS

(*Denotes a Critical Step) SIU (Required for UNSAT evaluation) Obtains copy of procedure SC.RE- Provide Rev. 23 of surveillance. ST.ZZ-0002(0). Obtains copy of 82.RE-RA.ZZ-0016 I Curve Book. Provide Rev. 8 of Curve Book. I Evaluator: MARK start time of JPM: 3.0 Reviews and signs off Precautions and Reviews Precautions & Limitations and Limitations Section 3.0 signs off Steps 3.1 - 3.7. 5.1 SELECT the applicable step below (e.g. Determines 5.1.1.C is the correct step 5.1.1.A): for the current conditions, which is to complete Attachment 3. 5.1.1.C !E SOM is to be verified (per T/S Refers to Attachment 3. 4.1.1.1.1.a) with reactor critical (Mode 1 or 2) and one or more control rods are inoperable, THEN COMPLETE Attachment 3. Att. 3 The reactor is in Mode 1 or Mode 2 Determines Unit is in Mode 1. with kett .:::. 1.0 2.1 Att. 3 Precautions and Limitations: Section Reviews and signs steps 3.1-3.5. 3.0 3.0 I PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 3 of 7

OPERATOR TRAINING PROGRAM NAME: _ _ _ _ _ _ _ _ _ __ JOB PERFORMANCE MEASURE DATE: _ _ _ _ _ _ _ _ _ __ System: Conduct of Operations Task: Calculate Shutdown Margin

  • STEP NO. STEP STANDARD EVAL COMMENTS

(*Denotes a Critical Step) S/U (Required for UNSAT evaluation) Att.3 Section 4 contains the data points Determines the following data and

  • Section required and the calculations to calculations:

4.1 determine shutdown margin. 4.1.1 100% 4.1.2 300 ppm 4.1.3 D@ 227 steps 4.1.4 10,000 EFPH 4.1.5 0 I 4.1.6 1 Att. 3 4.2.1 -3841

  • Section 4.2.2 -3335 4.2 4.2.3 728 4.2.4 0 4.2.5 500 4.2.6 0 4.2.7 -5948 Att. 3 4.3.1 -5948
  • Section 4.3.2 645 4.3 4.3.3 120 4.3.4 2742 4.3.5 -2441 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 4 of 7
                                                                                                                                .

OPERATOR TRAINING PROGRAM NAME: _ _ _ _ _ _ _ _ _ __ JOB PERFORMANCE MEASURE DATE: _ _ _ _ _ _ _ _ _ __ System: Conduct of Operations Task: Calculate Shutdown Margin

  • STEP NO. STEP STANDARD EVAL COMMENTS

(*Denotes a Critical Step) SIU (Required for UNSAT evaluation) 4.4 Att 4 Acceptance Criteria Reviews required SOM in MODE 1 or 2 of -1300 pcm and initials 4.4.1.

  • 4.4.1 IS THE SOM (Item 4.3.5) EQUAL I

TO OR MORE NEGATIVE THAN Determines calculated SOM is SAT and I (-)1300 PCM? initials SAT. Evaluator: MARK stop time of JPM: when procedures are returned to proctor.

  • Total time from START to STOP is 50 minutes or less.

Terminating Cue: Once operator has returned procedures to proctor, terminate JPM. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 5 of 7

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below. f\M. ~ 1. Task description and number, JPM description and number are identified. f'M. -( 2. Knowledge and Abilities (KIA) references are included. N"' / 3. Performance location specified. (in-plant, control room, or simulator) N"\ / 4. Initial setup conditions are identified.

5. Initiating and terminating Cues are properly identified.
6. Task standards identified and verified by SME review.
7. Critical steps meet the criteria for critical steps and are identified with an asterisk (*).
8. Verify the procedure referenced by this JPM matches the most current revision of that procedure: Procedure Rev.~ Date 7- z-z- 1 11>

13

9. Pilot test the JPM:
a. verify Cues both verbal and visual are free of conflict, and
b. ensure performance time is accurate.

____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.

                      ~                                              Date:   )- 2 <: -t/,
                       ~:_,.,(,

SME/lnstructor: SME/lnstructor:C/ 1£,(A Date: _q~/~_q_/1b__ SME/lnstructor: Date: - - - - - -

                   -------------

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 6 of 7

INITIAL CONDITIONS: - Unit 2 Reactor Power is 100%. - All Control Rod Group Demand Counters are at 227 steps. - Current boron concentration is 300 ppm. - Current core burnup is 10,000 EFPH. - Control Rod 105 was been declared INOPERABLE at 1000 today due to

- -not moving out during a rod exercise test. You have been directed to perform a Shutdown Margin Calculation IAW SC.RE-ST.ZZ-0002 to satisfy the action requirement of TSAS 3.1.3.1 Action c.3.

- Control Rod 105 has been identified as trippable and is currently at 214 steps. INITIATING CUE: The current time is 1010. This is a time critical JPM. Time will commence when you are provided with the applicable procedures. When performing calculation, the CRS directs you to use only the Tables as directed by SC.RE-ST.ZZ-0002, do not use Figures. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 7 of 7

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION: SALEM 1 & 2 SYSTEM: Chemical and Volume Control TASK: Demonstrate the Operability of the RWST and/or the BASTs TASK NUMBER: N0040420201 JPM NUMBER: 15-01 NRC RO Admin A2 ALTERNATE PATH: I....._ _.I KIA NUMBER: 2.2.37

                                                                          ~~~~-~--~~

IMPORTANCE FACTOR: 3.6 4.6 APPLICABILITY:

                                                                          - -RO- -        SRO EOLJ          ROITJ              STAD              SROO]

EVALUATION SETTING/METHOD: ,~,~~*- n/11:ihb Perform S2.0P-ST.CVC-0010, Rev. 10 (checked 9-28-16)

REFERENCES:

Salem Tech Specs TOOLS AND EQUIPMENT: None VALIDATED JPM COMPLETION TIME: 11 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: N/A Developed By: G Gauding Date: 8-9-16 Instructor Validated By: S Harris I J Pierce Date: 9-28-16 SME or lnstruc J\l, Approved By: Training partme~ Date: 1*) ,/, Approved By: Operatic~! Date: /6jfl/1c, ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY: EVALUATOR'S SIGNATURE: DATE: PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 1 of 8

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: ~~~~~~~~~~~~~~ DATE: ~~~~~~~~~~~~~~ SYSTEM: Chemical and Volume Control TASK: Demonstrate the Operability of the RWST and/or the BASTs TASK NUMBER: N0040420201 SIMULATOR SETUP: N/A INITIAL CONDITIONS:

  • Salem Unit 2 is at 100% power.
  • 21 BAT pump developed a leak that went unnoticed until the cross-connected BAST's reached their low level alarm setpoint.
  • 21 BAT pump, and the leak, are isolated.
  • 21 BAST level - 49.5%
  • 22 BAST level - 49.5%
  • 21 BAST temp - 98.2°F
  • 22 BAST temp - 97.1°F
  • RWST temperature - 70°F
  • RWST levels are:
  • CHl-41.4'
  • CH II - 41.4'
  • CH 111-41.4'
  • CH IV-41.5'
  • Chemistry reports current RWST and BAST boron concentrations are:
  • 21 BAST - 6610 ppm
  • 22 BAST - 6610 ppm
  • RWST - 2350 ppm
  • Off Normal and Off-Normal Tagged list review has been performed SAT.

INITIATING CUE: You are the Reactor Operator. Perform S2.0P-ST.CVC-0010, Borated Water Sources. Successful Completion Criteria:

1. All critical steps completed.
2. All sequential steps completed in order.
3. All time-critical steps completed within allotted time.
4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made.

Task Standard for Successful Completion:

1. Complete Attachment 2 of S2.0P-ST.CVC-0010 per key and determine the Surveillance is SAT PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 2 of 8

OPERATOR TRAINING PROGRAM NAME: ~~~~~~~~- JOB PERFORMANCE MEASURE DATE: ~~~~~~~~- SYSTEM: Chemical and Volume Control TASK: Demonstrate the Operability of the RWST and/or the BASTs STEP COMMENTS STEP (* Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD S/U evaluation)

Provide marked up copy of S2.0P-ST.CVC-0010, Borated Water Sources and Tech Spec 3.1.2.6 (2 pa~es) 3.0 Precautions and Limitations Reads and initials steps. 5.1.1 COMPLETE Attachment 2 per the Completes Attachment 2 with the below data. following:

  • RECORD Data .
  • RECORD Test Results by initialing SAT or UNSAT column using the stated Acceptance Criteria.
  • Att. 2 RWST Level Records RWST level with channel for which calibration data was obtained RWST levels are:

CH I: 41.4 CH II: 41.4 CH Ill: 41.4 CH IV: 41.5 Initials SAT for RWST Level and inserts date.

  • Att. 2 RWSTTemp Refers to initial conditions for RWST temperature 70°F. Initials SAT for RWST Temp and inserts date.

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 3 of 8

OPERATOR TRAINING PROGRAM NAME: ~~~~~~~~- JOB PERFORMANCE MEASURE DATE: ~~~~~~~~- SYSTEM: Chemical and Volume Control TASK- Demonstrate the Operability of the RWST and/or the BASTs STEP COMMENTS STEP (* Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD S/U evaluation)
  • Att. 2 RWST Cone Refers to initial conditions for RWST boron concentration and enters 2350 ppm. Initials SAT for RWST boron concentration and inserts date.
  • Att. 2 21 BAST Vol AND/OR 22 BAST Vol Refers to initial conditions for 21 and 22 BAST level and enters:

21 BAST vol- 49.5% 22 BAST vol - 49.5% Uses Tech Spec 3.1.2.6.a, 3.1.2.6.b, and Figure 3.1-2 and determines 21 BAST Vol AND/OR 22 BAST Vol is SAT. Initials SAT for BAST volume and inserts date.

  • Att. 2 21 BAST Temp AND/OR 22 BAST Temp Refers to initial conditions for 21 and 22 BAST temp and records:

21 BAST temp - 98.2°F 22 BAST temp - 97.1°F Initials SAT for 21 BAST Temp AND/OR 22 BAST Temp and inserts date. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 4 of 8

OPERATOR TRAINING PROGRAM NAME:

                                                                                                                    --------~

JOB PERFORMANCE MEASURE DATE:

                                                                                                                    ---------

SYSTEM: Chemical and Volume Control TASK: Demonstrate the Operability of the RWST and/or the BASTs STEP COMMENTS STEP (*Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD S/U evaluation)

Refers to initial conditions for BAST boron

  • Att. 2 21 BAST Cone AND/OR 22 BAST Cone concentrations and enters 6610 ppm for 21 BAST and 6610 ppm for 22 BAST.

Uses Tech Spec 3.1.2.6.a, 3.1.2.6.b, and Figure 3.1-2 and determines 21 and 22 BAST boron concentration is SAT. Initials and inserts date. 5.3.1 This surveillance is considered satisfactory when Attachments 2 and 3 Initials step 5.3.1 (as applicable) are complete with components listed meeting Acceptance Criteria stated in each Attachment. OR 5.3.2 This surveillance is unsatisfactory. N/A's 5.3.2. A. INITIATE Notification(s) to correct the unsatisfactory condition. B. RECORD Notification number(s) and reason for unsatisfactory completion on Attachment 4 in the Comments Section. 5.4.1 COMPLETE Attachment 4, Sections 1.0 Completes Attachment 4, Sections 1.0 and and 2.0, AND FORWARD this procedure 2.0, and returns procedure to JPM Evaluator. to the SM/CRS for review. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 5 of 8

OPERATOR TRAINING PROGRAM NAME:

                                                                                                                ---------

JOB PERFORMANCE MEASURE DATE:

                                                                                                                ---------

SYSTEM: Chemical and Volume Control TASK: Demonstrate the Operability of the RWST and/or the BASTs STEP COMMENTS STEP (* Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD S/U evaluation)

JPM is complete when procedure is returned to evaluator. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 6 of 8

' . JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below.

   \;v ' ~             1. Task description and number, JPM description and number are identified.
     \j-J    Jl         2. Knowledge and Abilities (KIA) references are included.
     \Y      7 h~       3. Performance location specified. (in-plant, control room, or simulator)
     \;J       J        4. Initial setup conditions are identified.
      \j'1    'A        5. Initiating and terminating Cues are properly identified.
               ~
        \jJ             6. Task standards identified and verified by SME review.
     ~                  7. Critical steps meet the criteria for critical steps and are identified with an asterisk(*).
        ~      /l       8. Verify the procedure referenced by this JPM matchys the most current revision of that procedure: Procedure Rev. _1_0_ Date 4-f IJ., l 13
       \)      ~        9. Pilot test the JPM:
a. verify Cues both verbal and visual are free of conflict, and
b. ensure performance time is accurate.

____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructo~JOL~ t.,, :J * "?,<'/<"'- Date: ~ [ 2-~ 1i <o

                                                                                      ------

SME/lnstructor;,A JJlJA,I.<% £1 S- il..6(n* ~ Date: - -c, /-i,g (l(.o

                                                                                                ----

SM Ell nstructor: Date: - - - - - -

                              ------------~

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 7 of 8

INITIAL CONDITIONS:

  • Salem Unit 2 is at 100% power.
  • 21 BAT pump developed a leak that went unnoticed until the cross-connected BAST's reached their low level alarm setpoint.
  • 21 BAT pump, and the leak, are isolated.
  • 21 BAST level - 49.5%
  • 22 BAST level - 49.5%
  • 21 BAST temp - 98.2°F
  • 22 BAST temp - 97.1°F
  • RWST temperature - 70°F
  • RWST levels are:
  • CH 1- 41.4'
  • CH 11 - 41 .4'
  • CH 111 - 41.4'
  • CH IV-41.5'
  • Chemistry reports current RWST and BAST boron concentrations are:
  • 21 BAST - 6610 ppm
  • 22 BAST - 6610 ppm
  • RWST - 2350 ppm
  • Off Normal and Off-Normal Tagged list review has been performed SAT.

INITIATING CUE: You are the Reactor Operator. Perform S2.0P-ST.CVC-0010, Borated Water Sources Data. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 8 of 8

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION: SALEM SYSTEM: ADMINISTRATIVE (ALARA) TASK: Perform Stay Time Calculation for Emergency Condition. TASK NUMBER: N1200100104 JPM NUMBER: 15-01 NRC RO A3 ALTERNATE PATH: D KIA NUMBER:

                                                             ----------i 2.3.4 IMPORTANCE FACTOR: - -      3.2
                                                                    --

APPLICABILITY: RO SRO EoD Ro[K] STAD SROD EVALUATION SETTING/METHOD: Classroom

REFERENCES:

Radiological Survey Maps, RP-AA-203 Rev. 6, NC.EP-EP.ZZ-0304 Rev. 16 TOOLS AND EQUIPMENT: Calculator VALIDATED JPM COMPLETION TIME: 10 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: N/A Developed By: G Gauding Date: 8-9-16 Instructor Validated By: R Evans IN Mulford Date: 9-22-16 I 9-29-16 SME or lnst:t~~l Approved By: T~ent Date: /0 )1/1 \_p Approved By: O~rtment Date: !b/11//(~ ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY: EVALUATOR'S SIGNATURE: DATE:

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: ~~~~~~~~~~~~~~ DATE: SYSTEM: ADMINISTRATIVE (ALARA) TASK: Perform Stay Time Calculation for Emergency Condition. TASK NUMBER: N1200100104 INITIAL CONDITIONS:

1. Unit 1 experienced Rx trip with a small RCS leak from 100% power.
2. The Rx failed to automatically trip on a valid trip demand, and was tripped successfully with the Rx trip handle.
3. Salem is currently in an Alert.
4. Your TEDE dose for the year is 1925 mrem.

INITIATING CUE: You have been directed to perform a detailed inspection of 22 RHR pump room prior to starting the pump. You will NOT be going into the 22 RHR HX area. Your job is estimated to take 2 hours to complete. Using the correct survey map, and conservatively using the HIGHEST dose rate anywhere in the pump room for your ENTIRE exposure, determine:

1. Can you complete the job without exceeding your current dose authorization
2. What would be your new TEDE dose for the year after performing the job (or as much as possible) WITHOUT exceeding your current dose authorization?

Successful Completion Criteria:

1. All critical steps completed.
2. All sequential steps completed in order.
3. All time-critical steps completed within allotted time.
4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made.

Task Standard for Successful Completion: Determines: YES job can be performed

2. Calculates new TEDE dose of 2005 mrem.

OPERATOR TRAINING PROGRAM NAME:

                                                                                                          ----------

JOB PERFORMANCE MEASURE DATE:

                                                                                                          ----------

SYSTEM: ADMINISTRATIVE (ALARA) TASK: Determine Radiological Conditions For Personnel Exposure STEP COMMENTS STEP (*Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD S/U evaluation)

Provide the attached survey maps of 21 and 22 RHR rooms, and S1 and S2 55 Selects the Survey Map General area. Also have blank copies of "S2 AUX 045' 22 RHR ROOMS" RP-AA-203, Exposure Control and 1 Map# 21045Z2 Authorization and NC.EP-EP.ZZ-0304, Operational Support Center (OSC) Radiation Protection Response if asked for. START TIME: If asked, provide NC.EP-EP.ZZ-0304, Note: Contains guidance for automatic OSC Radiation Protection Response. increase in allowed dose to 4500 mrem. (Section 5.0 Note.) Determines dose limit is automatically raised to 4500 mrem upon the declaration of an ALERT or higher Emergency. Page 3 of 6

OPERATOR TRAINING PROGRAM NAME:

                                                                                                             ~---------

JOB PERFORMANCE MEASURE DATE: - - - - - - - - - - SYSTEM: ADMINISTRATIVE (ALARA) TASK: Determine Radiological

                           -

Conditions For Personnel Exposure STEP COMMENTS STEP (*Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD S/U evaluation) 2 Determine highest dose rate in room. Per the survey map, squares are dose
  • rates in mrem/hr, and circles are smear locations. The highest square is located under the words "22RH37" on the map and indicates 40 mrem/hr.

Note: The square with "250" inside it is in the RHR HX room, and is not in the area which the operator will go. 3 Calculate TEDE dose for year Subtracts year to date TEDE dose from

  • Emergency Dose limit of 4,500 mrem, and gets 2575 mrem. Determines 2 hours of work will result in 80 mrem dose, and new TEDE dose is 2005 mrem, which does NOT exceed 4,500 mrem authorized in an Emergency.

Terminate JPM when candidate has returned paperwork. 4 STOP TIME: Page 4 of 6

JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below. Vv N'\ d 1. Task description and number, JPM description and number are identified. \}-' N'\ ~ 2. Knowledge and Abilities (KIA) references are included. vN'\-t 3. Performance location specified. (in-plant, control room, or simulator) V M ~ 4. Initial setup conditions are identified. v rt\ ~ 5. Initiating and terminating Cues are properly identified. vMf 6. Task standards identified and verified by SME review. v- N1 / 7. Critical steps meet the criteria for critical steps and are identified with an asterisk (*).

\J  N1 -(        8. Verify the procedure referenced by this JPM matches the most current revision of that procedure: Procedure Rev.-~-- Date S'~"Z"'-* '"'

N1 £ 9. Pilot test the JPM:

                                                                      '"'
a. verify Cues both verbal and visual are free of conflict, and
b. ensure performance time is accurate.

____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructor: ~ Date: 9- 2. ~ - '"" SME/lnstructor: ~lfw-J Date: q /q.ci/1b SME/lnstructor: Date:

                       -------------                                            ------

Page 5 of 6

INITIAL CONDITIONS:

1. Unit 1 experienced Rx trip with a small RCS leak from 100% power.
2. The Rx failed to automatically trip on a valid trip demand, and was tripped successfully with the Rx trip handle.
3. Salem is currently in an Alert.
4. Your TEDE dose for the year is 1925 mrem.

INITIATING CUE: You have been directed to perform a detailed inspection of 22 RHR pump room prior to starting the pump. You will NOT be going into the 22 RHR HX area. Your job is estimated to take 2 hours to complete. Using the correct survey map, and conservatively using the HIGHEST dose rate anywhere in the pump room for your ENTIRE exposure, determine:

1. Can you complete the job without exceeding your current dose authorization
2. What would be your new TEDE dose for the year after performing the job (or as much as possible) WITHOUT exceeding your current dose authorization?

1. 2. Page 6 of 6

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION: SALEM SYSTEM: ADMINISTRATIVE TASK: Review a completed surveillance to demonstrate Operability of 21 CFCU TASK NUMBER: N1230300302 JPM NUMBER: 15-01 NRC SRO Admin A1-1 ALTERNATE PATH: ._I_ _.I KIA NUMBER: ~~~~~~~~~~ 2.1.25 IMPORTANCE FACTOR: 4.2 APPLICABILITY: RO SRO EOCJ ROCJ STAL] SROCK] EVALUATION SETTING/METHOD: Classroom

REFERENCES:

S2.0P-ST.CBV-0003, Rev. 19 (checked 8-10-16) TOOLS AND EQUIPMENT: VALIDATED JPM COMPLETION TIME: 12 min TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: N/A Developed By: G Gauding Date: 8-10-16 Instructor Validated By: R Boyer I P Williams Date: 9-28-16 / 10-4-16 SME or Instructor~ Approved By:

                                     . .
                                . Trammg rt;t.f<Vlt pa men Date:    1~//r0 Approved By:*

Op~artment Date: 10)/;1, ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY: EVALUATOR'S SIGNATURE: DATE: Page 1 of 5 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

OPERATORTRAININGPROGRAM JOB PERFORMANCE MEASURE NAME: ~~~~~~~~~~~~- DATE: SYSTEM: Administrative TASK: Review a completed surveillance to demonstrate Operability of 21 CFCU TASK NUMBER: N1230300302 INITIAL CONDITIONS: 21 CFCU was returned from corrective maintenance. S2.0P-ST.CBV-0003, Containment Systems - Containment Cooling was performed for the Operability Retest. INITIATING CUE: You have been directed to review the surveillance for completeness and accuracy IAW Step 5.3.4. If any discrepancies are identified, note them and any actions that you would take on Attachment 8, Section 1.0, Comments. Successful Completion Criteria:

1. All critical steps completed
2. All sequential steps completed in order
3. All time-critical steps completed within allotted time
4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made (and NRC concurrence is obtained).

Task Standard for Successful Completion:

1. Identify that the Minimum Flow Rate recorded on Attachment 1, Section 3.0, for 87 psid is incorrectly recorded as 1592. Identify the correct Minimum Flow Rate should be 1638.
2. Identify that the actual Cooling Water Flow Rate (1625) is below the Minimum Flow Rate required as shown on Attachment 1 and Exhibit 1, and the surveillance is UNSAT vs SAT.

Page 2 of 5 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

OPERATOR TRAINING PROGRAM NAME: _ _ _ _ _ _ _ _ _ __ JOB PERFORMANCE MEASURE DATE: _ _ _ _ _ _ _ _ _ __ System: ADMINISTRATIVE Task: Review a completed surveillance to demonstrate Operability of 21 CFCU

  • STEP STEP STANDARD EVAL COMMENTS NO. (* Denotes a Critical Step) S/U (Required for UNSAT evaluation)

Provide completed S2.0P-ST.CBV-0003 surveillance. Reviews procedure. Identifies that the Minimum Flow Rate recorded on Attachment 1, 21 CFCU Data Sheet,

  • Section 3.0, for 87 psid is incorrectly recorded as 1592. (This was due to operator performing ST rounding down as opposed to rounding up IAW P&L 3.4.)

Identifies correct value for Minimum Flow Required as 1638.

  • Cue: IF candidate only determines flow is wrong, THEN ask candidate to determine correct flow.
  • Identifies that the actual Cooling Water Flow Rate of 1625 gpm is below the Minimum Flow Rate of 1638 as shown on Exhibit 1 and the ST is UNSAT.

When candidate turns in JPM, ensure they have provided correct flow as per Cue above, then state JPM is complete. Page 3 of5 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE TQ-AA-106-0303 Revision 4 JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below. V/ ~Task description and number, JPM description and number are identified. IJ ./ £?2. Knowledge and Abilities (KIA) references are included.

\J /  /J ~Performance            location specified. (in-plant, control room, or simulator)

V. I tf/-V4. *Initial setup conditions are identified. ~ </!-A~nitiating and terminating Cues are properly identified. U. 9 6. Task standards identified and verified by SME review. \J I fj:) 7. Critical steps meet the criteria for critical steps and are identified with an asterisk (*).

   ~Verify the procedure referenced by this JPM matches the most current revision of that procedure: Procedure Rev. _j_!J_ Date              s/u/1 L L~t test the JPM:                                                          '
a. verify Cues both verbal and visual are free of conflict, and
b. ensure performance time is accurate.

____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.

                                                                                     ; ._. =:. . !~

Date: -+--o/ a'--'----1/f,_ Date:_/~~.____*"4-~~{b=--- SME/lnstructor: Date: _ _ _ _ __

                     --------------

Page 4 of5 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

INITIAL CONDITIONS: 21 CFCU was returned from corrective maintenance. S2.0P-ST.CBV-0003, Containment Systems - Containment Cooling was performed for the Operability Retest. INITIATING CUE: You have been directed to review the surveillance for completeness and accuracy IAW Step 5.3.4. If any discrepancies are identified, note them and any actions that you would take on , Section 1.0, Comments. Page5of5 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION: SALEM SYSTEM: ADMINISTRATIVE TASK: Direct Actions for Spent Fuel Movement (Determine equipment allowed to be removed from service while SFP manipulations are in progress) TASK NUMBER: N1120760102 JPM NUMBER: 15-01 NRC SRO A 1-2 ALTERNATE PATH: D KIA NUMBER:

                                                                        ~--------~

2.1.42 IMPORTANCE FACTOR: 3.4

                                                                       ----

APPLICABILITY: RO SRO EOCJ ROCJ STAL] SRO[TI EVALUATION SETTING/METHOD: Classroom or Simulator

REFERENCES:

S2.0P-IO.ZZ-0010, Rev. 33, S2.0P-SO.CH-0001 Rev 32, S2.0P-SO.SW-0005 Rev 42 S2.0P-SO.DG-0005, Rev. 6 (all rev checked 8-10-16) Salem Tech Specs TOOLS AND EQUIPMENT: VALIDATED JPM COMPLETION TIME: 30 min TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: N/A Developed By: G Gauding Date: 8-10-16 Instructor Validated By: R Boyer IP Williams Date: 9-28-16110-4-16 SME or Instructor Approved By: AA /J Date: 100~ Traini;~rtm~-,{(ft-t, Approved By: ~ Date: 10/1j1t, Op-;rations Depa"nt ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY: EVALUATOR'S SIGNATURE: DATE: Page 1 of 7 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME:

                                                                      ~~~~~~~~~~~~~~~

DATE: SYSTEM: Administrative TASK: Direct Actions for Spent Fuel Movement (Determine equipment allowed to be removed from service while SFP manipulations are in progress) TASK NUMBER: N1120760102 INITIAL Salem Unit 2 is operating at199% power, coasting down into a refueling outage CONDITIONS: which will start in 2 weeks. Irradiated fuel movement is in progress in the Spent Fuel Pool IAW S2.0P-IO.ZZ-0010, Spent Fuel Pool Manipulations, and will continue without interruption for the next 8 hours, at which time it will terminate. The unit has no active Tech Spec LCOs. 21 SW pump is CIT for emergent strainer work. The current time is 0800. INITIATING CUE: You have been directed to review the upcoming work for the shift and determine which activities may proceed as scheduled while continuing the fuel movement in the Spent Fuel Pool uninterrupted. Work scheduled for today Circle whether each activity may or may not be performed lE any of the activities cannot proceed, explain your reason(s) 0900- 22 SW pump packing replacement MAY MAY NOT 1000- 2A EOG tagout for maintenance MAY MAY NOT 1300- 21 Chiller compressor oil change MAY MAY NOT 1400- Delivery of New Fuel into the Fuel MAY MAY NOT Handling Building for upcoming refueling outage. Successful Completion Criteria:

1. All critical steps completed
2. All sequential steps completed in order
3. All time-critical steps completed within allotted time
4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made (and NRC concurrence is obtained).

Task Standard for Successful Completion:

1. Determines that 22 SW pp work, 2A EOG surveillance, and 21 Chiller work MAY be performed.
2. Determines that New Fuel delivery may NOT be performed.

Page 2 of 7 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

                                                                                                                                     '.'ii OPERATOR TRAINING PROGRAM                       NAME: _ _ _ _ _ _ _ _ _ __

JOB PERFORMANCE MEASURE DATE: _ _ _ _ _ _ _ _ _ __ System: ADMINISTRATIVE Task: Direct Actions for Spent Fuel Movement (Determine equipment allowed to be removed from service while SFP manipulations are in progress)

  • STEP STEP STANDARD EVAL COMMENTS NO. (* Denotes a Critical Step) SIU (Required for UNSAT evaluation)

Provide blank copies of: S2.0P-IO.ZZ-0010, Spent Fuel Pool Manipulations. S2.0P-SO.DG-0005, Preparation for Removing a Diesel Generator from Service. S2.0P-SO.SW-0005, Service Water System Operation. S2.0P-SO.CH-0001, Chilled Water System Operation. Provide copies of Tech Specs. Page 3 of7 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

OPERATOR TRAINING PROGRAM NAME: ~~~~~~~~~~~ JOB PERFORMANCE MEASURE DATE: ~~~~~~~~~~~ System: ADMINISTRATIVE Task: Direct Actions for Spent Fuel Movement (Determine equipment allowed to be removed from service while SFP manipulations are in progress)

  • STEP STEP STANDARD EVAL COMMENTS NO. (*Denotes a Critical Step) S/U (Required for UNSAT evaluation)

Notes: TSAS 3.8.1.2 applies during Modes 5 and 6 and during movement of irradiated fuel, and only requires two EDGs. Only one FHB exhaust fan is required to be backed by an operable EOG (IOP-10 P&L 3. 7 and page 17) Operable SFP pumps only need one of them backed by operable EOG. (IOP-10 P&L 3.4 and page 17) TSAS 3. 7 .10 allows a chiller to be taken out of service if movement of irradiated fuel is already on-going, and gives 14 days to restore it. Two SW pumps are required to be operable, one of which is EOG backed. (IOP-10 page 18.) The four remaining SW pumps are powered from Band C vital and their EDGs remain operable. TSAS 3.7.4 will be entered for less than two operable SW loops, but is a 72 hour action. Page 4 of7 PSEG Restricted - Possession Requires Specific Pennission from Nuclear Training

                                                                                                                                      ~

OPERATOR TRAINING PROGRAM NAME:

                                                                                                           -----------

JOB PERFORMANCE MEASURE 0 ATE: _ _ _ _ _ _ _ _ _ __ System: ADMINISTRATIVE Task: Direct Actions for Spent Fuel Movement (Determine equipment allowed to be removed from service while SFP manipulations are in progress)

  • STEP STEP STANDARD EVAL COMMENTS NO. (* Denotes a Critical Step) S/U (Required for UNSAT evaluation)

Notes: (cont) FHB Truck Bay Door is required to be closed. (IOP-10 paqe 19) Determines that:

  • 22 SW pump work MAY be performed.
  • 2A EOG surveillance MAY be performed.
  • 21 Chiller oil replacement MAY be performed.
  • New Fuel delivery may NOT be performed because FHB Truck Bay door is required to be closed per IOP-10, page 19.

Evaluator ensure tear off sheet has candidates name and status for each of the four work activities, then terminate JPM. Page 5 of7 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

Name: OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE TQ-AA-106-0303 Revision 4 JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below .

.Id' 01.        Task description and number, JPM description and number are identified.
~Knowledge and Abilities (KIA) references are included.

,/._ d ~Performance location specified. (in-plant, control room, or simulator) 1.d<f:Z--4. Initial setup conditions are identified.

/ A~.           Initiating and terminating Cues are properly identified.

j ff ~-Task standards identified and verified by SME review. I a~ Critical steps meet the criteria for critical steps and are identified with an asterisk (*).

 ~erify the procedure referenced by this JPM matches the most current revision of that procedure: Procedure Rev. ilei,y1J'.,S Date        1h.!J I<,
 ~at test the JPM:
a. verify Cues both verbal and visual are free of conflict, and
b. ensure performance time is accurate.

____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructor: Date: - - - - - -

                   ~-------------

Page 6 of7 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

INITIAL CONDITIONS: Salem Unit 2 is operating at 99% power, coasting down into a refueling outage which will start in 2 weeks. Irradiated fuel movement is in progress in the Spent Fuel Pool IAW S2.0P-IO.ZZ-0010, Spent Fuel Pool Manipulations, and will continue without interruption for the next 8 hours, at which time it will terminate. The unit has no active Tech Spec LCOs. 21 SW pump is C/T for emergent strainer work. The current time is 0800. INITIATING CUE: You have been directed to review the upcoming work for the shift and determine which activities may proceed as scheduled while continuing the fuel movement in the Spent Fuel Pool uninterrupted. Work scheduled for today Circle whether each activity may or may not be performed lE any of the activities cannot proceed, explain your reason(s) 0900- 22 SW pump packing replacement MAY MAY NOT 1000- 2A EOG tag out for maintenance MAY MAY NOT 1300- 21 Chiller compressor oil change MAY MAY NOT 1400- Delivery of New Fuel into the Fuel MAY MAY NOT Handling Building for upcoming refueling outage. Page 7 of7 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION: SALEM SYSTEM: ADMINISTRATIVE TASK: Review a completed surveillance to calculate Shutdown Margin TASK NUMBER: 1200030301 JPM NUMBER: 15-01 NRC SRO A2 ALTERNATE PATH: D KIA NUMBER: ~~~~~~~~~~ 2.2.12 IMPORTANCE FACTOR: 4.1 APPLICABILITY: RO SRO EoD ROD STAD sRo[KJ EVALUATION SETTING/METHOD: Classroom

REFERENCES:

SC.RE-ST.ZZ-0002, Rev. 23 Shutdown Margin Calculation S2.RE-RA.ZZ-0016, Rev. 8 Figures Salem Unit 2 Technical Specifications TSAS 3.1.3.1 Movable Control Assemblies TOOLS AND EQUIPMENT: Calculator VALIDATED JPM COMPLETION TIME: 20 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: 30 minutes Developed By: G Gauding Date: 8-10-16 Instructor Validated: R Boyer I P Williams Date: 9-28-16 / 10-4-16 Approved By: s~:~f;( Date: 10//rl. Tra/1:~nment Approved By: Date: 1oj1~r., Operations Repr entative ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY: EVALUATOR'S SIGNATURE: DATE: PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 1 of 6

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: ~~~~~~~~~~~~~~~ DATE: SYSTEM: Administrative TASK: Review a completed surveillance to calculate Shutdown Margin TASK 1200030301 NUMBER: INITIAL CONDITIONS:

          -   Unit 2 Reactor Power is 100%.
          -   All Control Rod Group Demand Counters are at 227 steps.
          -   Current boron concentration is 300 ppm.
          -   Current core burnup is 10,000 EFPH.
          -   Control Rod 105 was declared INOPERABLE at 1000 today due to not moving out during a rod exercise test. A Shutdown Margin Calculation has been performed IAW SC.RE-ST.ZZ-0002, Shutdown Margin Calculation, to satisfy the action requirement of TSAS 3.1.3.1 Action c.3.
          - Control Rod 105 has been identified as trippable and is currently at 214 steps.
         - The current time is 1030.

INITIATING CUE:

1. Review the attached SOM calculation procedure SC.RE-ST.ZZ-0002 for completeness and accuracy.
2. Note any discrepancies found by the review on Attachment 7.
3. Determine if SOM is SAT.

This is a time critical JPM. Time will start when procedures are given to you. Time will stop when procedures are returned to proctor. Successful Completion Criteria:

1. All critical steps completed.
2. All sequential steps completed in order.
3. All time-critical steps completed within allotted time.
4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made Task Standard for Successful Completion:
1. Determines the incorrect value for Control Bank Worth and Shutdown Bank Worth have been used.
2. Determines SOM with correct values used is SAT.
3. Completes review within 30 minutes.

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 2 of 6

OPERATOR TRAINING PROGRAM NAME: _ _ _ _ _ _ _ _ __ JOB PERFORMANCE MEASURE DATE: _ _ _ _ _ _ _ _ __ System: ADMINISTRATIVE Task: Review a completed surveillance to calculate Shutdown Margin STEP COMMENTS STEP (*Denotes a Critical Step) STANDARD EVAL (Required for UNSAT

  • NO. SIU Evaluation)

Note to Evaluator: The time critical aspect refers to the time required when the Shutdown Margin requirement of TSAS 3.1.3.1.c must be met. 1 Provide the marked up copy of SC.RE- Ensures Sections 3 and 4 are completed. ST.ZZ-0002 and copy of S2.RE-RA.ZZ-0016, Curve Book. Time Start: 2 Review Section 5 to ensure the correct Reviews Section 5 and determines the correct Attachment was performed. Attachment (3) was performed. 3 Review the completed Shutdown Reviews SOM and determines:

  • Margin Calculation: 1. An incorrect value for Total Control Bank Worth (Step 4.2.1) has been used (0 EFPH value vs current
  • 10,000 EFPH value)
2. An incorrect value for Total Shutdown Bank Worth (Step 4.2.2)has been used (0 EFPH value vs current 10,000 EFPH value)

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 3 of 6

OPERATOR TRAINING PROGRAM NAME: _ _ _ _ _ _ _ _ _ __ JOB PERFORMANCE MEASURE DATE:- - - - - - - - - - - System: ADMINISTRATIVE Task: Review a completed surveillance to calculate Shutdown Margin STEP COMMENTS STEP (*Denotes a Critical Step) STANDARD EVAL (Required for UNSAT

  • NO. S/U Evaluation)
  • 3 3. Determines Trippable Rod Worth is can't incorrect based on incorrect steps 4.2.1 and 4.2.2)
  • 4. Determines Ten Percent Rod Worth Penalty (step 4.3.2) is incorrect based on incorrect steps 4.2.1 and 4.2.2)
  • 5. Determines SOM is incorrect based on incorrect steps 4.2.1 and 4.2.2 and 4.3.2)

Correct Values are: 4.2.1 -3841 4.3.1 -5948 4.2.2 -3335 4.3.2 645 4.2.3 728 4.3.4 2742 4.2.4 0 4.3.5 -2441 4.2.5 500 4.2.6 0 4.2.7 -5948

  • 4 Acceptance Criteria Determines Acceptance Criteria are still met with correct values used.
  • Turns in procedures within 30 minutes of start time.

Time Stop:

                                                         ****Total time to complete JPM MUST be 30 minutes or less.****

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 4 of 6

I

 .

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below. v ~ 1. Task description and number, JPM description and number are identified. v / }t; 2. Knowledge and Abilities (KIA) references are included.

     "'- /    ; ~3. Performance location specified. (in-plant, control room, or simulator) v   ~4. Initial setup conditions are identified.
      \r I  J~       5. Initiating and terminating Cues are properly identified.

v- / P/ 9--6. Task standards identified and verified by SME review.

   \]'-
         ~Critical steps meet the criteria for critical steps and are identified with an asterisk (').
          ~Verify the procedure referenced by this JPM matches the most current revision of that procedure: Procedure Rev.~ Date _1:;~/"'~l'_'*-_ __

J D9. Pilot test the JPM:

a. verify Cues both verbal and visual are free of conflict, and
b. ensure performance time is accurate.

____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. Date: r6yj,£_ Date: --./9f---<Tm~~-- SME/lnstructor: Date: - - - - - -

                           -------------

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 5 of 6

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE INITIAL CONDITIONS:

         -  Unit 2 Reactor Power is 100%.
         -  All Control Rod Group Demand Counters are at 227 steps.
         -  Current boron concentration is 300 ppm.
         -  Current core burnup is 10,000 EFPH.
         -  Control Rod 105 was declared INOPERABLE at 1000 today due to not moving out during a rod exercise test. A Shutdown Margin Calculation has been performed IAW SC.RE-ST.ZZ-0002, Shutdown Margin Calculation, to satisfy the action requirement of TSAS 3.1.3.1 Action c.3.
         - Control Rod 105 has been identified as trippable and is currently at 214 steps.
        - The current time is 1030.

INITIATING CUE:

1. Review the attached SOM calculation procedure SC.RE-ST.ZZ-0002 for completeness and accuracy.
2. Note any discrepancies found by the review on Attachment 7.
3. Determine if SOM is SAT.

This is a time critical JPM. Time will start when procedures are given to you. Time will stop when procedures are returned to proctor. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 6 of 6

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION: SALEM SYSTEM: ADMINISTRATIVE TASK: Determine required actions upon Radioactive Effluent Monitor failure TASK NUMBER: N1200010301 JPM NUMBER: 15-01 NRC SRO Admin A3 ALTERNATE PATH: CJ KIA NUMBER: _________ 2.3.11 _, IMPORTANCE FACTOR: 4.3

                                                                             - -RO- -            SRO APPLICABILITY:

EOCJ ROCJ STAL] SRO[ZJ EVALUATION SETTING/METHOD: Classroom Salem ODCM, Salem Tech Specs, S1 .OP-SO.WL-0001, Rev. 27, S1 .OP-SO.WG-

REFERENCES:

0011, Rev. 31, S1 .OP-SO.CBV-0002, Rev. 21 (All checked 8-10-16) TOOLS AND EQUIPMENT: VALIDATED JPM COMPLETION TIME: 25 min TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: N/A Developed By: G Gauding Date: 8-10-16 Instructor Validated By: Date: 9-28-16 / 10-4-16 Approved By: Approved By: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY: EVALUATOR'S SIGNATURE: DATE: PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 1 of 8

,. OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: DATE: SYSTEM: Administrative TASK: Determine required actions upon Radioactive Effluent Monitor failure TASK NUMBER: N1200010301 INITIAL Unit 1 is operating at 100% power. CONDITIONS: Radiation Monitor 1R12A, Containment Noble Gas, failed its Source Check when preparing to perform a normal Containment Pressure Relief IAW S1 .OP-SO.CBV-0002, Containment Pressure-Vacuum Relief System Operation. 11 CVCS Monitor Tank is ready for release. 14 Gas Decay Tank (GOT) is ready for release. INITIATING Prior to initiating the Containment Pressure Relief, Rad Monitor 1R41 D, Plant Vent CUE: Release Rate, indication fails high, and is confirmed as an instrument failure. For the following radiological releases, determine:

1) Can the release be performed with the failed monitors described above, and,
2) If the release can be performed, what compensatory actions are required, if any.

Assume each release will be performed individually. RELEASES CAN BE RELEASED? COMP ACTION REQ

  • 14 GOT release YES I NO
  • Containment Pressure Relief YES I NO
  • 11 CVCS Monitor Tank release YES I NO Successful Completion Criteria:
1. All critical steps completed
2. All sequential steps completed in order
3. All time-critical steps completed within allotted time
4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made (and NRC concurrence is obtained).

Task Standard for Successful Completion:

1. Determines ALL the releases may be performed.
2. Determines additional compensatory measures apply for the Waste Gas Release and the Containment Pressure Relief per key, and no additional compensatory actions are required for Liquid Release.

OPERATOR TRAINING PROGRAM NAME:

                                                                                                        ----------

JOB PERFORMANCE MEASURE DATE: _ _ _ _ _ _ _ _ __ System: ADMINISTRATIVE Task: Determine required actions upon Radioactive Effluent Monitor failure

  • STEP STEP STANDARD EVAL COMMENTS NO.
  • Denotes a Critical Step S/U (Required for UNSAT evaluation)

Provide blank copies of: S1 .OP-SO.WG-0011 S1 .OP-SO.CBV-0002 S1 .OP-SO.WL-0001 Salem ODCM Waste Gas Release Determines ODCM 3.3.3.9 applies to S1 .OP-SO.WG-0011 Gaseous Effluent which directs actions per Table 3.3-13. Determines Table 3.3-13, Instrument #1, Waste Gas Holdup System is applicable, which requires (1) 1R41A~ D. Action 31 applies. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 3 of 8

OPERATOR TRAINING PROGRAM NAME:

                                                                                                        ----------

DATE: _ _ _ _ _ _ _ _ __ JOB PERFORMANCE MEASURE System: ADMINISTRATIVE Task: Determine required actions upon Radioactive Effluent Monitor failure

  • STEP STEP STANDARD EVAL COMMENTS NO.
  • Denotes a Critical Step S/U (Required for UNSAT evaluation)

Action 31 states that with less than the minimum required Operable channels, the contents of the tank may be released provided that prior to the initiating the release:

  • a. At least two independent samples of the tanks contents are analyzed,
  • and
b. At least two technically qualified members of the facility Staff independently verify the release rate calculations and discharge valving lineup; otherwise suspend release of radioactive effluents via this pathway.
  • Additionally, S1.0P-SO.WG-0011, Discharge of 14 Gas Decay Tank to Plant Vent, Attachment 2, Section 3.0, Dose Estimates and Approval, Step 3.4.C (on page 18) states ... " Grab samples are being obtained at least once per 8 hours AND analyzed for gaseous principal
                                         ~amma emitters within 24 hours PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 4 of 8

OPERATOR TRAINING PROGRAM NAME: _ _ _ _ _ _ _ _ _ __ JOB PERFORMANCE MEASURE DATE: _ _ _ _ _ _ _ _ _ __ System: ADMINISTRATIVE Task: Determine required actions upon Radioactive Effluent Monitor failure STEP STEP STANDARD EVAL COMMENTS

  • NO.
  • Denotes a Critical Step S/U (Required for UNSAT evaluation)

Containment Pressure Relief Determines that Precaution and Limitation S1 .OP-SO.CBV-0002 2.3 of S1 .OP-SO.CBV-0001 directs operator to notify Chemistry to comply with the contingency actions associated with the ODCM prior to performing a Containment Pressure Relief. Determines Table 3.3-13, Instrument #3, applies to the Containment Pressure Relief. With both channels (1 R41A ~DOR 1R12A) inoperable, Action 37 applies. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 5 of 8

OPERATOR TRAINING PROGRAM NAME: _ _ _ _ _ _ _ _ _ __ JOB PERFORMANCE MEASURE DATE: _ _ _ _ _ _ _ _ _ __ System: ADMINISTRATIVE Task: Determine required actions upon Radioactive Effluent Monitor failure STEP STEP STANDARD EVAL COMMENTS

  • NO.
  • Denotes a Critical Step S/U (Required for UNSAT evaluation)

Action 37 states that with less than the minimum required Operable channels, Containment Pressure Reliefs may be performed provided that prior to initiating the release:

  • a. At least two independent samples of the tanks contents are analyzed, and
  • b. At least two technically qualified members of the facility Staff independently verify the release rate calculations, otherwise suspend release of radioactive effluents via this pathway.

Note: Applicant may identify compensatory actions per P&L 3.11

  • Waste Liquid Release Determines no compensatory actions are S1 .OP-SO.WL-0001 required to initiate the Liquid Release.

Terminate JPM when all paperwork is handed in. Note to Evaluator: JPM modeled after Pilgrim Jan 2011 NRC Exam SRO Admin JPM RC. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 6 of 8

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below.

\}v /  ~ 1f1*. Task description and number, JPM description and number are identified.

\j- / ~~- Knowledge and Abilities (KIA) references are included. Vv / ~<{Ji;j. Performance location specified. (in-plant, control room, or simulator)

~ I ~ ~- Initial setup conditions are identified.
'-J ./- r- ~-         Initiating and terminating Cues are properly identified.
      /r P6.          Task standards identified and verified by SME review.

l""'-[;?7. Critical steps meet the criteria for critical steps and are identified with an asterisk (*).

         ,eA-- ~*Verify the procedure referenced        by this JPM matches the most current revision of that procedure: Procedure Rev. _ _ Date----..,----
              /)_.,,-                                         A\\    N-v:t.:JJ'~ ~w ~fz.<1;ltio
          ~ 9. Pilot test the JPM:
a. verify Cues both verbal and visual are free of conflict, and
b. ensure performance time is accurate.

r-Jft/8;;-(i_Dthe JPM cannot be performed as written with proper responses, then revise the JPM .

         . . w'fT11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.

SM81nstructo~-~(t;_ Date: ci /2$} lb SME/lnstructor: ~/ fv; ~J--L Date: l~C SME/lnstructor: Date: - - - - - -

                         -------------

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 7 of 8

INITIAL CONDITIONS: Unit 1 is operating at 100% power. Radiation Monitor 1R12A, Containment Noble Gas, failed its Source Check when preparing to perform a normal Containment Pressure Relief IAW S1 .OP-SO.CBV-0002, Containment Pressure-Vacuum Relief System Operation. 11 CVCS Monitor Tank is ready for release. 14 Gas Decay Tank (GOT) is ready for release. INITIATING CUE: Prior to initiating the Containment Pressure Relief, Rad Monitor 1R41 D, Plant Vent Release Rate, indication fails high, and is confirmed as an instrument failure. For the following radiological releases, determine:

1) Can the release be performed with the failed monitors described above, and,
2) If the release can be performed, what compensatory actions are required, if any.

Assume each release will be performed individually. RELEASES CAN BE RELEASED? COMP ACTION REQ

  • 14 GOT release YES I NO
  • Containment Pressure Relief YES/ NO
  • 11 CVCS Monitor Tank release YES I NO PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 8 of 8

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION: SALEM SYSTEM: Emergency Plan TASK: Classify an event and complete an ICMF within the regulatory committed time limit (ESG-1) TASK NUMBER: 1240020502 JPM NUMBER: 15-01 NRC SRO Admin A4-1 (ESG-1) ALTERNATE PATH: _ I_ _I KIA NUMBER: ~~~~~~~~~~ 2.4.41 IMPORTANCE FACTOR: 4.6 APPLICABILITY: RO SRO EoD ROD STAD SRO[K] EVALUATION SETTING/METHOD: Simulate (Simulator or Classroom)

REFERENCES:

EP-SA-111-F2 Rev. 2 (ALERT) TOOLS AND EQUIPMENT: Inform Simulator Operators - DO NOT ERASE ANY PROCEDURES UNTIL THE SRO EVALUATOR APPROVES VALIDATED JPM COMPLETION TIME: 12 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: 15 minutes Developed By: G Gauding Date: 9-19-15 Instructor Validated By: C Davis IP Williams Date: 9-21-16110-4-16 SME or Ins ruct~ Approved By: Traini epaUent Date: 1ff u Approved By: Date: 1oj;j1r, obepartment ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY: EVALUATOR'S SIGNATURE: DATE: PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 1 of 8

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: ~~~~~~~~~~~~~~- DATE: SYSTEM: Emergency Plan TASK: Classify an event and complete an ICMF within the regulatory committed time limit (ESG-1) TASK NUMBER: 1240020502 INITIAL CONDITIONS:

1. You have a maximum of 5 minutes to review the Emergency Operating Procedures used during this scenario to refresh your memory of all events/paths. At the end of your review you will become the Shift Manager (SM). Inform the Evaluator when you are ready to assume SM duties. You may continue to reference the procedures or to look at the control board but "the clock will be running." If there are multiple ECG calls, classify the most severe.

INITIATING CUE: You are the Duty SM. Classify the event, complete the correct ECG Attachment and provide an ICMF to the Primary Communicator. This is a Time Critical JPM. Successful Completion Criteria:

1. All critical steps completed.
2. All sequential steps completed in order.
3. All time-critical steps completed within allotted time.
4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made.

Task Standard for Successful Completion:

1. Declare an ALERT under EAL RB3.P within 15 minutes of start time, and provide ICMF to the Primary Communicator within the next 15 minutes.

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 2 of 8

OPERATOR TRAINING PROGRAM NAME:

                                                                                                               ------

JOB PERFORMANCE MEASURE DATE: - - - - - - SYSTEM: Emergency Plan TASK: Classify an event and complete an ICMF within the regulatory committed time limit (ESG-1) COMMENTS STEP STEP (Required (*Denotes a Critical Step) EVAL

  • NO. STANDARD for UNSAT S/U evaluation)

Provide candidate with 'Tear-off sheet" Reviews initial conditions and EOP's (as and Blank Copies of EP-SA-111-F1 necessary - 5 minute limit prior to starting) through F4 (UE, ALERT, SAE, GE)

                *START TIME:
                *Start time begins when candidate          Cue: The regulatory commitment time reports he/she is ready to assume SM       clock has started.

duties Reviews ECG to classify event Note: It is acceptable to use the laminated tables in the simulator, rather than the ECG Classifies the event Determines the classification of the event and refers to ECG Attachment 2 (Alert) Att 2 CALL communicators to the Control Pages communicators and initials as SM A.1 Room Cue: I am the Primary Communicator PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 3 of 8

OPERATOR TRAINING PROGRAM NAME:

                                                                                                              ------

JOB PERFORMANCE MEASURE DATE: - - - - - - SYSTEM: Emergency Plan TASK: Classify an event and complete an ICMF within the regulatory committed time limit (ESG-1) COMMENTS STEP STEP (Required (*Denotes a Critical Step) EVAL

  • NO. STANDARD for UNSAT S/U evaluation)

Att 2 IF a Security Event is in progress, THEN Determines Security Event is not in A.2 IMPLEMENT the prompt actions of progress. NC.EP-EP.ZZ-0102, EC Response, Attachment 10, prior to the classification. If time allows, DIRECT Classification Att 2 Cue: No independent verification will be A.3 Independent Verification to be performed. performed. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 4 of 8

OPERATOR TRAINING PROGRAM NAME:

                                                                                                              ------

JOB PERFORMANCE MEASURE DATE: - - - - - - SYSTEM: Emergency Plan TASK: Classify an event and complete an ICMF within the regulatory committed time limit (ESG-1) COMMENTS STEP STEP (Required (*Denotes a Critical Step) EVAL

  • NO. STANDARD for UNSAT S/U evaluation)

Att 2 After Classification Independent Declares an ALERT under RB3.P within A.4 Verification is obtained: 15 minutes of Start Time:

*
  • DECLARE the ALERT (enter time and date on ICMF)

Completes and Approves the ICMF as

*               *COMPLETE I APPROVE the ICMF follows:

EAL#(s): RB3.P Description of Event: Potential Loss of the Reactor Coolant System Boundary Note: Description of Event is found in EAL Description Table Fills out Section Ill: Checks IS NOT for a Radiological Release in progress. Fills out Section IV: Retrieves wind speed (10)and direction (160) data from SPDS Initials for a1212roval to transmit Att 2 ' I i A.5 If time allows OBTAIN accuracy peer check of the completed ICMF Cue: No peer check will be performed. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 5 of 8

OPERATOR TRAINING PROGRAM NAME: - - - - - - JOB PERFORMANCE MEASURE DATE: - - - - - - SYSTEM: Emergency Plan TASK: Classify an event and complete an ICMF within the regulatory committed time limit (ESG-1) COMMENTS STEP STEP (Required (*Denotes a Critical Step) EVAL

  • NO. STANDARD forUNSAT S/U evaluation)

Att 2 A.6 Continue with NOTIFICATION AND ACTIVATION as follows:

  • If not previously performed, ACTIVATE I DIRECT ACTIVATION of ERO Cue: Activation of ERO Emergency Callout is not required for this JPM.

Emergency Callout (EP 96-003)

  • DIRECT the Primary Communicator to Provides ICMF to Primary Communicator
  • implement ECG Attachment 6 within 15 minutes of event declaration Terminate JPM when ICMF is given to the Evaluator.

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 6 of 8

TQ-AA-106-0303 JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below. \,tJ /~~Task description and number, JPM description and number are identified.

      / 1),-.._~- Knowledge and Abilities (KJA) references are included.
      /  ~ Performance location specified. (in-plant, control room, or simulator)
    /      ~-            Initial setup conditions are identified.
    /     ~4--s.         Initiating and terminating Cues are properly identified.
          ~-Task standards identified and verified                  by SME review.

l-.... <fh. Critical steps meet the criteria for critical steps and are identified with an asterisk(*). t,_tfi> 8. Verify the procedure referenced by this JPM matches the most current revision of

                    ~hat procedure: Procedure Rev. __1_ Date '\ -'lf. { 6 f/\..,,   9. Pilot test the JPM:
a. verify Cues both verbal and visual are free of conflict, and
b. ensure performance time is accurate.
           ~-~. If the JPM cannot be performed as written with proper responses, then revise the JPM.

(,,,.._ ~When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructor~Af° Date:~ SME/lnstructor: /~~J Date:~ SME/lnstructor: _ _ _ _ _ _ _ _ _ _ _ __ Date: _ _ _ _ __ PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 7 of 8

INITIAL CONDITIONS:

1. You have a maximum of 5 minutes to review the Emergency Operating Procedures used during this scenario to refresh your memory of all events/paths. At the end of your review you will become the Shift Manager (SM). Inform the Evaluator when you are ready to assume SM duties.

You may continue to reference the procedures or to look at the control board but "the clock will be running."-lf there are multiple ECG calls, classify the most severe. INITIATING CUE: You are the Duty SM. Classify the event, complete the correct ECG Attachment and provide an ICMF to the Primary Communicator. This is a Time Critical JPM. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 8 of 8

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION: SALEM SYSTEM: Emergency Plan TASK: Classify an event and complete an ICMF within the regulatory committed time limit (ESG-2) TASK NUMBER: 1240020502 JPM NUMBER: 15-01 NRC SRO Admin A4-1 (ESG-2) ALTERNATE PATH: KIA NUMBER: ~~~~~~~~~~ 2.4.41 IMPORTANCE FACTOR: 4.6 APPLICABILITY: RO SRO EOCJ ROCJ STAC] SRO[IJ EVALUATION SETTING/METHOD: Simulate (Simulator or Classroom)

REFERENCES:

EP-SA-111-F2 Rev. 2 (ALERT) TOOLS AND EQUIPMENT: Inform Simulator Operators - DO NOT ERASE ANY PROCEDURES UNTIL THE SRO EVALUATOR APPROVES VALIDATED JPM COMPLETION TIME: 12 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: 15 minutes Developed By: G Gauding Date: 9-19-15 Instructor Validated By: Date: 9-21-16110-4-16 Approved By: Approved By: ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY: EVALUATOR'S SIGNATURE: DATE: PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 1of8

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: ~~~~~~~~~~~~~~- DATE: SYSTEM: Emergency Plan TASK: Classify an event and complete an ICMF within the regulatory committed time limit (ESG-2) TASK NUMBER: 1240020502 INITIAL CONDITIONS:

1. You have a maximum of 5 minutes to review the Emergency Operating Procedures used during this scenario to refresh your memory of all events/paths. At the end of your review you will become the Shift Manager (SM). Inform the Evaluator when you are ready to assume SM duties. You may continue to reference the procedures or to look at the control board but "the clock will be running." If there are multiple ECG calls, classify the most severe.

INITIATING CUE: You are the Duty SM. Classify the event, complete the correct ECG Attachment and provide an ICMF to the Primary Communicator. This is a Time Critical JPM. Successful Completion Criteria:

1. All critical steps completed.
2. All sequential steps completed in order.
3. All time-critical steps completed within allotted time.
4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made.

Task Standard for Successful Completion:

1. Declare an ALERT under EAL RB3.L within 15 minutes of start time, and provide ICMF to the Primary Communicator within the next 15 minutes.

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 2 of 8

OPERATOR TRAINING PROGRAM NAME:

                                                                                                               ------

JOB PERFORMANCE MEASURE DATE: - - - - - - SYSTEM: Emergency Plan TASK: Classify an event and complete an ICMF within the regulatory committed time limit (ESG-2) COMMENTS STEP STEP (Required (*Denotes a Critical Step) EVAL

  • NO. STANDARD for UNSAT S/U evaluation)

Provide candidate with "Tear-off sheet" Reviews initial conditions and EOP's (as and Blank Copies of EP-SA-111-F1 necessary - 5 minute limit prior to starting) through F4 (UE, ALERT, SAE, GE)

                *START TIME:
                *Start time begins when candidate          Cue: The regulatory commitment time reports he/she is ready to assume SM       clock has started.

duties Reviews ECG to classify event Note: It is acceptable to use the laminated tables in the simulator, rather than the ECG Classifies the event Determines the classification of the event and refers to ECG Attachment 2 (Alert) Att 2 CALL communicators to the Control Pages communicators and initials as SM A.1 Room Cue: I am the Primary Communicator PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 3 of 8

OPERATOR TRAINING PROGRAM NAME:

                                                                                                              ------

JOB PERFORMANCE MEASURE DATE: - - - - - - SYSTEM: Emergency Plan TASK: Classify an event and complete an ICMF within the regulatory committed time limit (ESG-2) COMMENTS STEP STEP (Required (*Denotes a Critical Step) EVAL

  • NO. STANDARD for UNSAT S/U evaluation)

Att 2 IF a Security Event is in progress, THEN Determines Security Event is not in A.2 IMPLEMENT the prompt actions of progress. NC.EP-EP.ZZ-0102, EC Response, Attachment 10, prior to the classification. If time allows, DIRECT Classification Att 2 Cue: No independent verification will be A.3 Independent Verification to be performed. performed. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 4 of 8

OPERATOR TRAINING PROGRAM NAME: - - - - - - JOB PERFORMANCE MEASURE DATE: - - - - - - SYSTEM: Emergency Plan TASK: Classify an event and complete an ICMF within the regulatory committed time limit (ESG-2) COMMENTS STEP STEP (Required (*Denotes a Critical Step) EVAL

  • NO. STANDARD for UNSAT S/U evaluation)

Att 2 After Classification Independent Declares an ALERT under RB3.L within A.4 Verification is obtained: 15 minutes of Start Time:

*
  • DECLARE the ALERT (enter time and date on ICMF)

Completes and Approves the ICMF as

*               *COMPLETE I APPROVE the ICMF follows:

EAL#(s): RB3.L Description of Event: Loss of the Reactor Coolant System Boundary Note: Description of Event is found in EAL Description Table Fills out Section Ill: Checks IS for a Radiological Release in progress. Fills out Section IV: Retrieves wind speed (10)and direction (160) data from SPDS Initials for aggroval to transmit Att 2 A.5 lftime allows OBTAIN accuracy peer check of the completed ICMF Cue: No peer check will be performed. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 5 of 8

OPERATOR TRAINING PROGRAM NAME: - - - - - - JOB PERFORMANCE MEASURE DATE: - - - - - - SYSTEM: Emergency Plan TASK: Classify an event and complete an ICMF within the regulatory committed time limit (ESG-2) COMMENTS STEP STEP (Required (*Denotes a Critical Step) EVAL

  • NO. STANDARD for UNSAT S/U evaluation)

Att 2 A.6 Continue with NOTIFICATION AND ACTIVATION as follows:

  • If not previously performed, ACTIVATE I DIRECT ACTIVATION of ERO Cue: Activation of ERO Emergency Callout is not required for this JPM.

Emergency Callout (EP 96-003)

*
  • DIRECT the Primary Communicator to Provides ICMF to Primary Communicator implement ECG Attachment 6 within 15 minutes of event declaration Terminate JPM when ICMF is given to the Evaluator.

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 6 of 8

TQ-AA-106-0303 JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below. l-... ~Task description and number, JPM description and number are identified.

  ~Q.*Knowledge and Abilities (KIA) references are included.

0 U°3:'Performance location specified. (in-plant, control room, or simulator)

 &-t& Initial setup conditions are identified.

V\ Qs.-lnitiating and terminating Cues are properly identified. 0, ~Task standards identified and verified by SME review.

 ~CM_ Critical steps meet the criteria for critical steps and are identified with an asterisk (*).
 ~ {/)s. Verify the procedure referenced by this JPM matches the m2st current revision of
  • that procedure: Procedure Rev.~ Date fl, it.[(.,,_
 ~BPilot test the JPM:
a. verify Cues both verbal and visual are free of conflict, and
b. ensure performance time is accurate.

{/\_ ~- If the JPM cannot be performed as written with proper responses, then revise the JPM.

 ~Q        11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.

SME/lnstructor: ~ SME/lnstructor~/lt~ SME/lnstructor: _ _ _ _ _ _ _ _ _ _ _ __ Date: _ _ _ _ __ PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 7 of 8

INITIAL CONDITIONS:

1. You have a maximum of 5 minutes to review the Emergency Operating Procedures used during this scenario to refresh your memory of all events/paths. At the end of your review you will become the Shift Manager (SM). Inform the Evaluator when you are ready to assume SM duties.

You may continue to reference the procedures or to look at the control board but "the clock will be running." If there are multiple ECG calls, classify the most severe. INITIATING CUE: You are the Duty SM. Classify the event, complete the correct ECG Attachment and provide an ICMF to the Primary Communicator. This is a Time Critical JPM. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 8 of 8

OPERATOR TRArnING PROGRAM JOB PERFORlVIAl~CE MEASURE STATION: SALEM SYSTEM: Rod Control TASK: Perform a Control Rod Operability Verification TASK NUMBER: N0010070101 JPM NUMBER: 15-01 NRC Sim a ALTERNATE PATH: I x I K/A NUMBER: 001 A4.03

                                                                           ~~~~~~~~~~~

IMPORTANCE FACTOR: 4.0 3.7 APPLICABILITY: RO SRO EoO ROCK] STAD SROCK] EVALUATION SETTING/METHOD: Simulator

REFERENCES:

S2.0P-ST.RCS-0001, Rev. 22 (checked 8-3-16) TOOLS AND EQUIPMENT: None VALIDATED JPM COMPLETION TIME: 10 min TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: N/A Developed By: G Gauding Date: 8-3-16 Instructor Validated By: M Lutek I W Russell Date: 8-22-16 SME or Instructor Approved By: tv'\ ~ Ffl'-\ Train in partment Approved By: Ope~ment ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY: EVALUATOR'S SIGNATURE: DATE:

OPERATOR TRAINING PROGRAlVI JOB PERFORMAl~CE MEASURE JOB PERFORMANCE MEASURE SIMULATOR SETUP INSTRUCTIONS SYSTEM: Rod Control TASK: Perform a Control Rod Operability Verification TASK NUMBER: N0010070101 SIMULATOR IC: IC-251 in 15-01 NRC JPMs MALFUNCTIONS REQUIRED: RT-1 will trip 21 SGFP MALF: BF0105A, 21 STM GEN FEED PUMP TRIP, Final Value: 3 OVERRIDES REQUIRED: None SPECIAL INSTRUCTIONS: None Note to Evaluator: OP-AP-300-1001 required a peer check for all non-emergency manual rod motion. Do NOT correct operator if a mistake is made when performing a peer check. For all required peer checks simply state "Peer check SAT".

OPERATOR TRAINING PROGRANI JOB PERFORMANCE MEASURE NAME: ~~~~~~~~~~~~~~~~ DATE: ~~~~~~~~~~~~~~~ SYSTEM: Rod Control TASK: Perform a Control Rod Operability Verification TASK NUMBER: N0010070101 INITIAL CONDITIONS: Unit 2 is operating at steady state, 100% power. Power has been at 100% for 30 days. INITIATING CUE:

  • You are directed to perform S2.0P-ST.RCS-0001, Reactivity Control System Rod Control Assemblies.
  • A Maintenance Technician is stationed at the Rod Control System Power Cabinets .
  • Communications are established via plant page between the Control Room and Jeff Stevens, NEO, at the Rod Control System Power Cabinets.
  • The CRS has directed that steps 5.1.2 through 5.1.9 are to be performed in order .
  • The CRS directs that 15 steps of rod insertion are to be performed for each bank to ensure that each rod moves at least 10 steps.
  • Initial Control Rod Positions are:

SDA SOB SOC SOD F-04 229 G-03 229 E-03 229 C-05 229 D-10 228 C-09 227 C-11 223 E-13 223 K-12 227 J-13 227 L-13 224 N-11 224 M-06 227 N-07 229 N-05 224 L-03 227 B-04 230 J-02 223 D-14 224 C-06 223 P-12 229 G-13 227 M-02 230 N-09 230 Successful Completion Criteria:

1. All critical steps completed.
2. All sequential steps completed in order.
3. All time-critical steps completed within allotted time.
4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made (and NRG concurrence is obtained).

Task Standard for Successful Completion: Operator trips the Rx when Shutdown Bank B is inserted in the core and a SGFP trips.

OPERATOR TRAINING PROGRAM NAME: JOB PERFORMANCE MEASURE DATE: SYSTEM: Rod Control TASK: Perform a Control Rod Operability Verification STEP COMMENTS STEP (*Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD S/U Evaluation)

Provide marked up copy of S2.0P-ST.RCS- Reviews Prerequisites. 0001, Rev. 22, with Prerequisite Sections 2.1-2.8 filled out. Provide copy of OP-AP-300-1001, PWR Control Reviews OP-AP-300-1001, PWR Control Rod Movement Requirements. Rod Movement Requirements. Reviews and signs Precautions and Limitations. Cue: lE ASKED, state that no special contingency actions have been briefed other than what is in the P&L's. 5.1.1 IF this surveillance is to be performed .... Determines step is N/A based on steady state 100% operation. 5.1.2 PERFORM Attachment 2, Rod Control System Performs Attachment 2 Rod Control Voltage Checks as follows: System Voltage Checks by: A. PLACE Rod Bank Selector Switch to A. Places Rod Bank Selector Switch

                  -
                           "MANUAL".                                            to manual.
                  -     B. Direct Maintenance to COMPLETE                  B. Directs Direct Maintenance to Attachment 2, Rod Control System                     complete Attachment 2, Rod Voltage Checks.                                      Control System Voltage Checks.

Cue: Maintenance reports Attachment 2 Rod Control System Voltage Checks are complete SAT.

OPERATOR TRAINING PROGRAM NAME: JOB PERFORMANCE MEASURE DATE: ~~~~~~~~~~- SYSTEM: Rod Control TASK: Perform a Control Rod Operability Verification STEP COMMENTS STEP (*Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD SIU Evaluation)

Note _The Shutdown Rod Insertion Limit (TS Initials both notes. 3.1.3.4) is not applicable during the performance of this test for rods actually undergoing testing. _Steps 5.1.3 through 5.1.10 may be performed in anv order.

OPERATOR TRAINING PROGRAM NAME: ~~~~~~~~~~ JOB PERFORMANCE MEASURE DATE: ~~~~~~~~~~- SYSTEM: Rod Control TASK: Perform a Control Rod Operability Verification STEP COMMENTS STEP (*Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD S/U Evaluation) 5.1.3 PERFORM Shutdown Bank A testing as follows:

A. lE the Rx is critical, THEN ENSURE T avg Checks Tave/Tref recorder on 2RP4 and is within +/-1°F of Tret* notes Tavg is within 1°F of Tref .. B. PLACE Bank Selector Switch in the Rotates Bank Selector Switch fully counter

*                        "SBA" position.                             clockwise to the SBA position.

C. ENSURE GRP. SELECT "C" lights are Contacts NEO and directs him to verify illuminated on Rod Control System GRP. SELECT "C" lights are illuminated Power Cabinets 21AC and 22AC. on Rod Control System Power Cabinets 21 AC and 22AC. Cue: GRP SELECT "C" lights are illuminated at Rod Control System Power Cabinets 21 AC and 22AC. D. Maneuver Shutdown Bank A at least 10 IAW OP-AA-300-1001, prior to rod

  • steps in any one direction. movement, operator states initial Shutdown Bank A position, target control rod position, and direction of rod movement, then inserts SBA at least 10 steps to stated target position.

E. ENSURE each rod in Shutdown Bank A Verifies rod movement by viewing rod indicated rod movement of at least 10 position on P-250 computer. steps. F. RECORD Shutdown Bank A "Test Initials SAT for Groups 1 and 2 for SBA on Results" by initialing in Attachment 1. Att 1. G. RESTORE Shutdown Bank A to pre-test Operator states initial Shutdown Bank A

  • condition. position, target control rod position, and direction of rod movement, then withdraws SBA to stated target ARO position.

Continuous rod withdrawal is acceptable.

OPERATOR TRAINING PROGRAM NAME: ~~~~~~~~~~- JOB PERFORMANCE MEASURE DATE: ~~~~~~~~~~ SYSTEM: Rod Control TASK: Perform a Control Rod Operability Verification STEP COMMENTS STEP (*Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD S/U Evaluation) 5.1.4 PERFORM Shutdown Bank B testing as follows:

A. lE the Rx is critical, THEN ENSURE Tavg Checks Tave/Tref recorder on 2RP4 and is within +/-1°F of Tref* notes Tavg is within 1°F of Tref. B. PLACE Bank Selector Switch in the Rotates Bank Selector Switch clockwise to

*                         "SBB" position.                           the SBB position.

C. ENSURE GRP. SELECT "C" lights are Contacts NEO and directs him to verify illuminated on Rod Control System GRP. SELECT "C" lights are illuminated Power Cabinets 21 BD and 22BD. on Rod Control System Power Cabinets 21 BD and 22BD. Cue: GRP SELECT "C" lights are illuminated at Rod Control System Power Cabinets 21 BD and 22BD. D. MANUEVER Shutdown Bank B at least Operator states initial Shutdown Bank B

  • 10 steps in any one direction. position, target control rod position, and direction of rod movement, then inserts SBB at least 10 steps to stated target position.

E. ENSURE each rod in Shutdown Bank B SIMULATOR OPERATOR: INSERT RT-1 indicated rod movement of at least 1O when the operator is checking rod position steps. after insertion. This will trip 21 SGFP. Responds to 21 SGFP trip by tripping the

  • Rx IAW P&L 3.13. (This is Alternate Path)

Movement of the Rod Bank Selector Switch to MAN or AUTO under these conditions is incorrect. When the operator has either tripped the Rx or initiated rod insertion in MAN or AUTO, state JPM is complete.

OPERATOR TRAINING PROGRAM JOB PERFORlVIAl~CE MEASURE TQ-AA-106-0303 Revision 4 JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below. V / 'd-lJ'll1. Task description and number, JPM description and number are identified. (,A I rlfll 2. Knowledge and Abilities (KIA) references are included. V ./ ~ ltQl3. Performance location specified. (in-plant, control room, or simulator) V I '?r-lft. Initial setup conditions are identified. V I (;- L£1. Initiating and terminating Cues are properly identified. (/"' I (r- ~.Task standards identified and verified by SME review. v I §-~. Critical steps meet the criteria for critical steps and are identified with an asterisk (*). (, I ~ ~. Verify the procedure referenced by th is J PM matches thepost current revision of iJ1 that procedure: Procedure Rev. _21_ Date ~/ 1 :e, ti ~

          ~       9. Pilot test the JPM:
                /{/\     a. verify Cues both verbal and visual are free of conflict, and 1

wu \ b. ensure performance time is accurate. 0 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructor: _ _ f_V\_L_v_t_-t..-_L_____ Date: ~f ,_,_)If::, SM E/I nstructor:~f/i~* -'~IL4(~-"--+--~£~.=f.=~*=e1/"'-'-

                                                  . __                   Date: _ _  f" /~-z:i--+L_,__d~o*_

r ' SME/lnstructor: _ _ _ _ _ _ _ _ _ _ _ __ Date: - - - - - -

OPERATOR TRAINING PROGRA1"VI JOB PERFORMANCE MEASURE INITIAL CONDITIONS: Unit 2 is operating at steady state, 100% power. Power has been at 100% for 30 days. INITIATING CUE:

  • You are directed to perform S2.0P-ST.RCS-0001, Reactivity Control System Rod Control Assemblies.
  • A Maintenance Technician is stationed at the Rod Control System Power Cabinets .
  • Communications are established via plant page between the Control Room and Jeff Stevens, NEO, at the Rod Control System Power Cabinets.
  • The CRS has directed that steps 5.1.2 through 5.1.9 are to be performed in order .
  • The CRS directs that 15 steps of rod insertion are to be performed for each bank to ensure that each rod moves at least 10 steps.
  • Initial Control Rod Positions are:

SDA SOB SOC SOD F-04 229 G-03 229 E-03 229 C-05 229 D-10 228 C-09 227 C-11 223 E-13 223 K-12 227 J-13 227 L-13 224 N-11 224 M-06 227 N-07 229 N-05 224 L-03 227 8-04 230 J-02 223 D-14 224 C-06 223 P-12 229 G-13 227 M-02 230 N-09 230

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE: STATION: SALEM SYSTEM: Emergency Operating Procedures TASK: Perform Actions for Containment Sump blockage TASK NUMBER: N 1150900501 JPM NUMBER: 15-01 NRC Sim b ALTERNATE PATH: I x I KIA NUMBER:

                                                                       ------------!2.4.4 IMPORTANCE FACTOR:            4.5            4.7 APPLICABILITY:                                                               RO            SRO EOr=J         RO[KJ           STAD            SRO[KJ EVALUATION SETTING/METHOD:              Simulator I Perform 2-EOP-LOCA-1, REV. 30, 2-EOP-LOCA-3, Rev. 30, 2-EOP-APPX-7, Rev. 0, OP-

REFERENCES:

AA-101-111-1003, Rev. 6 (All rev checked 5/9/16) TOOLS AND EQUIPMENT: None VALIDATED JPM COMPLETION TIME: 5 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: NIA Developed By: G Gauding Date: 5-9-16 Instructor Validated By: D Cox I M Lutek Date: 8-22-16 SME or Instructor Approved By: Tra~~~j{'t Date: lo lo/" Approved By: Oper~ent Date: /o /1Dj;r., ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY: EVALUATOR'S SIGNATURE: DATE: PSEG Restricted-Possession Requires Specific Permission from Nuclear Training

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE: NAME: ~~~~~~~~~~~~~- DATE: SYSTEM: Emergency Operating Procedures TASK: Perform Actions for Containment Sump blockage TASK NUMBER: N1150900501 SIMULATOR SETUP: RT-1 MALFS: VL0120 21SJ44 fails to position (0-100%) Severity 1.0 VL0121 22SJ44 fails to position (0-100%) Severity 2.0 I/O's: AA04 B LO 21SJ44 SIS SUMP VALVE OPEN: ON AAOS B LO 21SJ44 SIS SUMP VALVE OPEN: ON AAOS CLO 22SJ44 SIS SUMP VALVE CLOSED: OFF AA04 CLO 21SJ44 SIS SUMP VALVE CLOSED: OFF ET-1 KAA01TPN 21 RHR pump STOP PB, tied to delete VL0120 ET-3 KAA01TPN 21 RHR pump STOP PB, tied to delete VL0121

                              ***Check SJ44 OPEN lights are lit.***

Mark up LOCA-3 up to step 21. INITIAL CONDITIONS:

  • A LBLOCA has occurred.
  • The crew has responded by performing TRIP-1 and LOCA-1.
  • The crew is performing LOCA-3 with all AC buses energized from off-site power, and is waiting at step 21 for RWST lo-lo level alarm.
  • All ECCS pumps are operating except 22 CS pump which was stopped at step 8.

INITIATING CUE: You are the Reactor Operator. Continue performing LOCA-3. Successful Completion Criteria:

1. All critical steps completed.
2. All sequential steps completed in order.
3. All time-critical steps completed within allotted time.
4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made.

Task Standard for Successful Completion:

1. Secure all ECCS pumps.
2. Reestablish recirculation flow with ONE RHR pump and ONE charging OR SI pump.

PSEG Restricted-Possession Requires Specific Permission from Nuclear Training

OPERATOR TRAINING PROGRAM NAME:

                                                                                                                 ----------

JOB PERFORMANCE MEASURE DATE:

                                                                                                                 ----------

SYSTEM: Emergency Operating Procedures TASK: Perform Actions for Containment Sumo block STEP COMMENTS STEP (*Denotes a Critical Step) EVAL (Required for

  • NO. STANDARD S/U UNSAT evaluation)

Simulator Operator: Insert RT-1 to cause cavitation of both RHR pumps. Determines ECCS pumps are exhibiting signs of cavitation and recognizes entry into APPX-7 is warranted from Continuous Action Summary. Evaluator: IF the intention to stop the cavitating RHR pumps is voiced, THEN FOR RO APPLICANT ONL Y1 IMMEDIATELY CUE: The CRS directs you to implement Appendix-7. (This is to prevent activation of Event Trigger when 21 RHR pump is stopped. CUE IF REQUIRED: The CRS directs you to implement Appendix-?. Note: Operator may go to EOP-LOCA-5, but first step of LOCA-5 will direct performance of APPX-7. Use above cue if required in LOCA-5. Evaluator: Provide paper copy of 2-EOP-APPX-7. PSEG Restricted-Possession Requires Specific Permission from Nuclear Training

OPERATOR TRAINING PROGRAM NAME:

                                                                                                                   ----------

JOB PERFORMANCE MEASURE DATE:

                                                                                                                   ----------

SYSTEM: Emergency Operating Procedures TASK: Perform Actions for Containment Sumo block -*- - STEP COMMENTS STEP (*Denotes a Critical Step) EVAL (Required for

  • NO. STANDARD S/U UNSAT evaluation}

APPX-7 CAUTION

  • Any pump receiving suction from Evaluator: Stopping RHR pumps here an RHR pump should be stopped WITHOUT first stopping any SI or Charging before stopping the RHR pump. pumps receiving suction from RHR pump
  • If any Charging Pump, SI Pump, discharge is failure criteria.

or Containment Spray Pump loses suction or shows indication of cavitation, the pump should be stopped. 1 (CAS) MONITOR RHR Pump suction conditions:

a. CHECK NO indications of Determines BOTH RHR pumps exhibit signs cavitation. of cavitation, as well as ALL ECCS pumps
  • Pump Amps - stable and normal being supplied from RHR pumps.

for discharge pressure and flow.

  • Flow - stable and normal for discharge pressure.
  • Discharge Pressure - stable and normal for flow
  • Oscillations - none indicated PSEG Restricted-Possession Requires Specific Permission from Nuclear Training

OPERATOR TRAINING PROGRAM NAME: ~~~~~~~~~- JOB PERFORMANCE MEASURE DATE: ~~~~~~~~~- SYSTEM: Emergency Operating Procedures TASK Perform Actions

                     --     for Containment
                                  --- --- --- S -- - - - block
                                                             -- --

STEP COMMENTS STEP (*Denotes a Critical Step) EVAL (Required for

  • NO. STANDARD S/U UNSAT evaluation) 1.a a. PERFORM the following:

RNO 1. ENSURE 21 RH29 AND 22RH29 Places 21 RH29 and 22RH29 in AUTO. in AUTO.

  • 2. STOP ANY Charging Pump or SI Stops 21 and 22 Charging pumps and 21 and Pump taking suction from 22 SI pumps.

affected RHR Pump(s)

3. IF indications of cavitation Determines pump cavitation is continuing, continue, THEN CLOSE 21 CS36 verifies 21 CS36 and 22CS36 are shut.

AND 22CS36, RHR TO CS VALVE.

4. lE indications of cavitation continue AND radiological conditions permit, THEN PERFORM the following: CUE: Radiation Protection has determined
a. SEND an operator to release both RHR pump rooms to be unavailable for tags and restore CA to access due to high radiation levels.

RH18(s).

b. CLOSE affected RH18(s).
  • 5. lE indications of cavitation Determines RHR pump cavitation is continue, THEN REMOVE continuing, and removes lockout from 21 SJ49 LOCKOUT(s) AND CLOSE and 22SJ49 RHR TO COLD LEG and shuts affected SJ49(s), RHR TO COLD 21 SJ49 and 22SJ49.

LEG.

  • 6. lE indications of cavitation Determines indications of cavitation continue, continue, THEN STOP affected and stops 21 and 22 RHR pump.

RHR Pump(s). Simulator Operator: Ensure ET-1 and ET-3 are TRUE when 21 and 22 RHR pump STOP PBs are depressed. This removes the SJ44 failures. PSEG Restricted-Possession Requires Specific Permission from Nuclear Training

OPERATOR TRAINING PROGRAM NAME:

                                                                                                                 ---------

JOB PERFORMANCE MEASURE DATE: SYSTEM: Emergency Operating Procedures TASK: Perform Actions for Containment Sumo block STEP COMMENTS STEP (*Denotes a Critical Step) EVAL (Required for

  • NO. STANDARD S/U UNSAT evaluation) 2 CHECK ALL AVAILABLE CFCUs Determines all CFCUs are running in Low running in Low Speed. Speed.
3. SECURE Containment Spray flow path:
  • a. STOP ALL Containment Spray Stops 21 CS pump.

Pumps.

b. CHECK 21CS36 AND 22CS36 Determines 21 CS36 and 22CS36 are shut.

CLOSED.

4. (CAS) CHECK RWST level >1.2 feet. Determines RWST level is >1.2 feet.
5. ATTEMPT to establish RHR Pump suction:
a. CHECK 21 SJ44 AND 22SJ44 Determines 21 SJ44 AND 22SJ44 are open.

OPEN.

b. CHECK AT LEAST ONE RHR Determines NEITHER RHR Pumps is running Pump running, with suction with suction aligned to Containment Sump.

aligned to Containment Sump. 5.b b. PERFORM the following: RNO 5.b 1. REMOVE LOCKOUT(s) AND Determines 21 SJ49 and 22SJ49 previously RNO CLOSE affected SJ49(s) RHR shut. DISCH TO COLD LEG. 5.b 2. ENSURE 21 RH29 AND 22RH29 Determines 21 RH29 and 22RH29 are in RNO in AUTO AUTO.

  • 5.b 3. START ONE RHR Pump. Starts 21 OR 22 RHR pump.

RNO PSEG Restricted-Possession Requires Specific Permission from Nuclear Training

OPERATOR TRAINING PROGRAM NAME: ~~~~~~~~~- JOB PERFORMANCE MEASURE DATE: ~~~~~~~~~- SYSTEM: Emergency Operating Procedures TASK Perform Actions for Containment

                                   - -      S       block STEP                                                                                COMMENTS STEP

(*Denotes a Critical Step) EVAL (Required for

  • NO. STANDARD SIU UNSAT evaluation) 5.b 4. !E indications of cavitation occur, Determines cavitation is NOT occurring.

RNO THEN STOP the running RHR pump, AND START the other RHR pump. 5.b 5. !E NO RHR Pumps can be run Determines RHR pump can be run without RNO without cavitation, THEN STOP cavitation. any running RHR Pumps AND GO TO Step 8.

5. c) CHECK 21 RH29 AND 22RH29 Determines 21 RH29 and 22RH29 are in in AUTO. AUTO.

d) REMOVE LOCKOUT(s) AND Determines BOTH SJ49's are shut. CLOSE affected SJ49(s) RHR DISCH TO COLD LEG. e) CHECK ONLY ONE RHR Pump Determines only one RHR pumps is running. running with suction from Containment Sump.

6. ATTEMPT to establish Charging Pump or SI Pump flow in recirculation mode: Checks Charging Pump and SI Pump suction
a. CHECK Charging Pump and SI aligned to running RHR pump by:

Pump suction aligned to running a.1. Checks 2SJ67 and 2SJ68 SHUT RHR pump. a.2 Checks 22SJ45 OPEN a.3 Checks 21 SJ45 OPEN a.4 Checks 21 SJ113 and 22SJ113 OPEN a.5 Checks 2SJ1 and 2SJ2 OPEN a.6 Checks 2SJ30 SHUT

b. CHECK ONLY ONE Charging Determine NO Charging or SI pumps are Pump OR SI Pump running. running.

PSEG Restricted-Possession Requires Specific Permission from Nuclear Training

OPERATOR TRAINING PROGRAM NAME: ~~~~~~~~~- JOB PERFORMANCE MEASURE DATE: ~~~~~~~~~- SYSTEM: Emergency Operating Procedures TASK: Perform Actions for Containment Sumo block -- STEP COMMENTS STEP (*Denotes a Critical Step) EVAL (Required for

  • NO. STANDARD S/U UNSAT evaluation)
  • 6.b START OR STOP, Charging and SI Starts ONLY ONE Charging or SI pump.

RNO Pumps, as required, to obtain ONLY ONE pump running in recirculation Note: Per the NOTE at top of page 3, the alignment. intent of Step 6 is to start only a single pump (Charging or SI), and it is preferable to start a Charging pump. SAT performance of Step 6 does not require starting a Charging pump, just one of the 4 available charqinq or SI pumps. 6 c. CHECK Charging Pump or SI Determines Charging or SI pump is running in Pump running in recirculation recirculation alignment. alignment.

d. GO TO Step 9 Terminate JPM when operator goes to Step 9.

PSEG Restricted-Possession Requires Specific Permission from Nuclear Training

JOB PERFORMANCE MEASURE TQ-AA-106-0303 JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below. 1 J I ~/ 1. Task description and number, JPM description and number are identified. V  !~I r /2. 1 Knowledge and Abilities (KIA) references are included. CA /~ 0 J 3. Performance location specified. (in-plant, control room, or simulator) lll ~4. Initial setup conditions are identified. 1.rv ~5. Initiating and terminating Cues are properly identified.

\. 7},
  '\.. ~6. Task standards identified and verified by SME review.
 \J    µ         7. Critical steps meet the criteria for critical steps and are identified with an asterisk (*).
       ~8. Verify the procedure referenced by this JPM mat£hes the n;iost current revision of
         ~/        that procedure: Procedure Rev.      _i2__ Date        8
  • 2'2-- I t.,.
       - - - - 9. Pilot test the JPM:
a. verify Cues both verbal and visual are free of conflict, and
b. ensure performance time is accurate.

____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructore}:> SME/lnstructor: C, .* ( / tff' N\1..,.. v:n[.U-- Date: Date: 8-22-lb 6-/ 7, ,_,I 110 SME/lnstructor: Date:

                       -------------                                            ------

PSEG Restricted-Possession Requires Specific Permission from Nuclear Training

JOB PERFORMANCE MEASURE INITIAL CONDITIONS:

  • A LBLOCA has occurred.
  • The crew has responded by performing TRIP-1 and LOCA-1.
  • The crew is performing LOCA-3 with all AC buses energized from off-site power, and is waiting at step 21 for RWST lo-lo level alarm.
  • All ECCS pumps are operating except 22 CS pump which was stopped at step 8.

INITIATING CUE: You are the Reactor Operator. Continue performing LOCA-3. PSEG Restricted-Possession Requires Specific Permission from Nuclear Training

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION: SALEM SYSTEM: ECCS TASK: Isolate the ECCS Accumulators IAW TRIP-6 TASK NUMBER: 1150070501 JPM NUMBER: 15-01 NRC Sim c ALTERNATE PATH: I x I KIA NUMBER: ~~~~~~~~~~~ E09 EA1 .1 IMPORTANCE FACTOR: 3.5 3.5 APPLICABILITY: RO SRO EoD RO[]:] STAL] SROITJ EVALUATION SETTING/METHOD: Simulator I Perform

REFERENCES:

2-EOP-TRIP-6 Rev. 30 (Rev checked 8-3-16) TOOLS AND EQUIPMENT: None VALIDATED JPM COMPLETION TIME: 8 Minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: N/A Developed By: G Gauding Date: 8-3-16 Instructor Validated By: W Russell / D Cox SME or Instructor i Date: 8-22-16 Approved By: Train~~('-;; Date: 10/;/v Approved By: Op rations De rtment Date: /D;/1f r, ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY: EVALUATOR'S SIGNATURE: DATE: PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 1 of 6

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: DATE: SYSTEM: ECCS TASK: Isolate the ECCS Accumulators IAW TRIP-6 TASK NUMBER: 1150070501 SIMULATOR SETUP:

1. Trip RCP's
2. Perform EOP's to TRIP-6, Step 12 - SI ACCUM ISOLATION
3. Override 24SJ54, Acc. Isolation Valve, close PB in the OFF position.
4. Place SPDS on Press/Temp Display
5. Put RCS Tcolds on trend on console.
6. Provide marked up copy of TRIP-6 INITIAL CONDITIONS:

A reactor trip occurred when a 500KV grid perturbation occurred, which also caused all RCPs to trip. The operating crew has progressed through the EOP's and is now in 2-EOP-TRIP-6, NATURAL CIRCULATION RAPID COOLDOWN WITH RVLIS. The RCPs will NOT be restarted. INITIATING CUE: Begin performing 2-EOP-TRIP-6, NATURAL CIRCULATION RAPID COOLDOWN WITH RVLIS at step 12. Successful Completion Criteria:

1. All critical steps completed.
2. All sequential steps completed in order.
3. All time-critical steps completed within allotted time.
4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made.

Task Standard for Successful Completion:

1. Shut 21, 22, and 23 SJ54's.
2. Vent 24 Accumulator to atmospheric pressure.

PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 2 of 6

OPERATOR TRAINING PROGRAM NAME: ~~~~~~~~~- JOB PERFORMANCE MEASURE DATE: SYSTEM: ECCS TASK: Isolate the ECCS Accumulators IAW TRIP-6 STEP COMMENTS STEP (*Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD S/U evaluation)

Reviews conditions and the marked up EOP-TRIP-6 Natural Circ Cooldown With RVLIS 12 IS RCS PRESSURE <1000 PSIG Verifies RCS pressure <1000 psig. 12.1 REMOVE LOCKOUT FROM 21-24SJ54 At 2RP4 Panel, selects VALVE OPERABLE on (ACCUMULATOR OUTLET VALVES) 21-24SJ54 ACCUMULATOR OUTLET VALVES LOCKOUT switches.

  • 12.1 CLOSE 21-24SJ54 Depresses CLOSE PB on 21-24SJ54, noting that 21, 22, and 23SJ54 begin to stroke closed.

12.1 ARE 21-24SJ54 CLOSED Determines 24SJ54 is OPEN. Alternate path actions start here. VENT ANY AFFECTED ACCUMULATORS: 12.2

  • MAINTAIN RCS PRESSURE Verifies RCS Pressure >24 Accumulator GREATER THAN ACCUMULATOR Pressure NITROGEN PRESSURE
*
  • OPEN 2NT35 (N2 HOR VALVE) Opens 2NT35 (N2 HOR VALVE)
*
  • OPEN AFFECTED SJ93 (N2 Opens 24SJ93 (N2 SUPPLY VAL VE) and SUPPLY VALVE) observes 24 Accumulator pressure lowering PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 3 of 6

OPERATOR TRAINING PROGRAM NAME: ~~~~~~~~~- JOB PERFORMANCE MEASURE DATE: SYSTEM: ECCS TASK: Isolate the ECCS Accumulators IAW TRIP-6 STEP COMMENTS STEP (*Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD S/U evaluation) 12.3 WHEN ACCUMULATOR VENTING IS Cue: 24 Accumulator has been completely COMPLETE THEN CLOSE: vented and 24 Accumulator pressure is now reading ZERO.
*
  • 2NT35 Closes 2NT35 N2 HOR VALVE
*
  • 21 THRU 24 SJ93 Closes 24SJ93 N2 SUPPLY VALVE Cue: JPM is complete PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 4 of 6

JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, rev~lidate JPM using steps 8 and 11 below .

                   . Task description and number, JPM description and number are identified.

(; / 5. Initiating and terminating cues are properly identified. V / ~ 6. Task standards identified and verified by SME review. (/ ~ 7. Critical steps meet the criteria for critical steps and are identified with an asterisk n

                   . Verify the procedure referenced by this JPM mate es the most current revision of that procedure: Procedure Rev. ~Date 8" t2 lo
                   . Pilot test the JPM:
a. verify cues both verbal and visual are free of conflict, and
b. ensure performance time is accurate.

____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructor:. (J/ ~ SME/lnstructor: ~, { i>/' I SME/lnstructor: _ _ _ _ _ _ _ _ _ _ _ __ Date: _ _ _ _ __ PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 5 of 6

INITIAL CONDITIONS: A reactor trip occurred when a 500KV grid perturbation occurred, which also caused all RCPs to trip. The operating crew has progressed through the EOP's and is now in 2-EOP-TRIP-6, NATURAL CIRCULATION RAPID COOLDOWN WITH RVLIS. The RCPs will NOT be restarted. INITIATING CUE: Begin performing 2-EOP-TRIP-6, NATURAL CIRCULATION RAPID COOLDOWN WITH RVLIS at step 12. PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 6 of 6

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION: SALEM 1 & 2 SYSTEM: Emergency Operating Procedures TASK: Respond to a Loss of Heat Sink (Initiate Bleed and Feed with SI pumps and Rx Head Vents) TASK NUMBER: N 1150290501 JPM NUMBER: 15-01 NRC Sim d ALTERNATE PATH: I x I KIA NUMBER: EPE E05 EA 1.1

                                                                        ---~---~-~

IMPORTANCE FACTOR:

                                                                        - -4.1- -             4.0 APPLICABILITY:                                                                RO              SRO EOCJ          RO[KJ          STACJ            SRO[KJ EVALUATION SETTING/METHOD:              Simulator - Perform

REFERENCES:

2-EOP-FRHS-1, Loss of Secondary Heat Sink, Rev.~ 61 At- 1-:Jf',~,<c TOOLS AND EQUIPMENT: None VALIDATED JPM COMPLETION TIME: 6 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: N/A Developed By: G Gauding Date: 8-2-16 Instructor Validated By: S Harris I J Pierce Date: 9-28-16 Approved By:

                            ~ru~~{l Traini~Department 1o)j1t,,

Approved By: Ope~ment Date: ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY: EVALUATOR'S SIGNATURE: DATE: PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 1 of 8

.. OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: ~~~~~~~~~~~~~~ DATE: ~~~~~~~~~~~~~~ SYSTEM: Emerqencv Operatinq Procedures TASK: TCAF a Loss of Heat Sink (Initiate Bleed and Feed with SI pumps and Rx Head Vents) TASK NUMBER: N1150290501 SIMULATOR SETUP: RX HEAD VENT KEYS ARE LOCATED IN SIM BOOTH IC-254 developed by: MSL rupture (1 Oo/o)downstream of MS IVs. Fail all MSIVs open. All AFW pumps failed. Fail 2PR2 shut. Performed TRIP-1 through Step 20. SG WR levels <32%. INITIAL CONDITIONS:

  • Unit 2 initiated a Rx trip from 100% power in response to a Main Steam line break at the mixing bottle.
  • An automatic Safety Injection initiated.
  • The Main Turbine failed to trip automatically, and was manually tripped from the control console.
  • MSLI failed, and all MSIV's remain open.
  • All AFW flow has been lost. --- - - - - ----- --*** - ---- -
  • EOP-TRIP-1 was performed and a transition to FRHS-1, Loss of Secondary Heat Sink was made at Step 20.1 INITIATING CUE:

You are the Reactor Operator. Perform FRHS-1 starting at Step 1. Successful Completion Criteria:

1. All critical steps completed.
2. All sequential steps completed in order.
3. All time-critical steps completed within allotted time.
4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made.

Task Standard for Successful Completion:

1. Stop ALL RCPs.
2. Open 2PR1.
3. Open Rx Head Vent Valves 2RC40-2RC43.

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 2 of 8

OPERATOR TRAINING PROGRAM NAME: ~~~~~~~~ JOB PERFORMANCE MEASURE DATE: ~~~~~~~~~ SYSTEM: Emergency Operating Procedures TASK: Respond to a Loss of Heat Sink (Initiate Bleed and Feed with SI pumps and Rx Head Vents) STEP COMMENTS STEP (* Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD S/U evaluation) 1 IS TOTAL AFW FLOW LESS THAN Determines it was not operator action which 22E04 LB/HR DUE TO OPERATOR caused total AFW flow to be less than 22E04 ACTIONS lb/hr.

2 !E AT LEAST ONE INTACT OR Recognizes ALL SGs are faulted. RUPTURED SG IS AVAILABLE, THEN DO NOT FEED A FAULTED SG 3 IS RCS PRESSURE GREATER THAN Checks RCS pressure on control console ANY INTACT OR RUPTURED SG and determines it is greater than all SG PRESSURE pressures checked on control console. 3.1 ARE RCS T-HOTS GREATER THAN Checks RCS Thot indication on control 350°F console and determines that RCS Thots are greater than 350°F. 4 !E WR LEVELS IN AT LEAST TWO SG's Determines at least 2 SG WR levels < 32% ARE LESS THAN 32% (37% ADVERSE), and goes to Step 21. THEN IMMEDIATELY GO TO STEP 21 TO INITIATE RCS BLEED AND FEED PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 3 of 8

                                                                                                                                      .

OPERATOR TRAINING PROGRAM NAME: - - - - - - - - - JOB PERFORMANCE MEASURE DATE: - - - - - - - - - SYSTEM: Emergency Operating Procedures TASK: Respond to a Loss of Heat Sink (Initiate Bleed and Feed with SI pumps and Rx Head Vents) STEP COMMENTS STEP (* Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD S/U evaluation) 21 CAUTION TO ESTABLISH RCS HEAT REMOVAL Reads Step.

BY RCS BLEED AND FEED, STEPS 24 THRU 29 MUST BE PERFORMED QUICKLY AND WITHOUT INTERRUPTION

  • 23 STOP ALL RCPS Depresses STOP PB for 21-24 RCPs and verifies green stop light illuminates and red start light extinguishes.

22 INITIATE SI Uses Safeguards key and initiates SI on at least one train of Safeguards initiation. 23 ARE SI VALVES IN SAFEGUARDS Checks 2RP4 and/or console indication to POSITION determine that all valves listed in Table B are in Safeguards position. Table B valves are: 2SJ4 OPEN BIT INLET 2SJ5 OPEN BIT INLET 2SJ12 OPEN BIT OUTLET 2SJ13 OPEN BIT OUTLET 2CV68 CLOSED CHARGING DISCHARGE 2CV69 CLOSED CHARGING DISCHARGE (continued next paqe) PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 4 of 8

OPERATOR TRAINING PROGRAM NAME: - - - - - - - - - JOB PERFORMANCE MEASURE DATE: - - - - - - - - - SYSTEM: Emergency Operating Procedures TASK: Respond to a Loss of Heat Sink (Initiate Bleed and Feed with SI pumps and Rx Head Vents) STEP COMMENTS STEP (* Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD S/U evaluation)

Table B Valves (can't): 21-24SJ54 OPEN ACCUMULATOR OUTLET 2SJ1 OPEN RWST TO CHARGING 2SJ2 OPEN RWST TO CHARGING 2CV40 CLOSED DISCHARGE STOP 2CV41 CLOSED DISCHARGE STOP 23.1 IS 21 OR 22 CHARGING PUMP Checks control console and determines 21 RUNNING and 22 charging pump are running. IS BIT FLOW ESTABLISHED Checks console and determines BIT flow is established. 23.2 IS ANY SI PUMP RUNNING Checks control console and determines 21 and 22 SI pumps are running. ARE VALVES IN TABLE COPEN FOR Checks control console indication for valves AT LEAST ONE RUNNING SI PUMP listed in Table C and determines the valves are open for at least one running SI pump. Table C valves are: 21 /22 SI PUMPS 2SJ30 (FROM RWST) 21/22SJ33 (SI PUMP SUCTION) 2SJ135 (COLD LEG DISCHARGE) 21/22SJ134 (COLD LEG DISCHARGE) PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 5 of 8

OPERATOR TRAINING PROGRAM NAME: - - - - - - - - - JOB PERFORMANCE MEASURE DATE: - - - - - - - - - SYSTEM: Emergency Operating Procedures TASK: Respond to a Loss of Heat Sink (Initiate Bleed and Feed with SI pumps and Rx Head Vents) STEP COMMENTS STEP (* Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD S/U evaluation)

ARE ALL CHARGING AND SI PUMPS Determines all charging and SI pumps are RUNNING AND ALIGNED TO DELIVER running and aligned to deliver flow. FLOW 24 OPEN BOTH PZR PORV STOP VALVES Checks control console and determines BOTH 2PR6 and 2PR7 PORV STOP VALVES are open.

  • OPEN BOTH PZR PORVS Places 2PR1 in manual and depresses 2PR1 PZR PORV open PB and verifies green closed light extinguishes and red open light illuminates.

Places 2PR2 in manual and depresses 2PR2 PZR PORV open PB and reports that 2PR2 will not open. 24.1 ARE BOTH PZR PORV STOP VALVES Checks control console and determines BOTH OPEN 2PR6 and 2PR7 PORV STOP VALVES are open. AREBOTHPZRPORVSOPEN Determines 2PR2 PZR PORV is not open. Alternate path actions start here.

  • 24.2 OPEN 2RC40 THRU 2RC43 (REACTOR Inserts key into each 2RC40 THRU 2RC43 HEAD VENTS) (REACTOR HEAD VENTS) switch on 2RP3, turns to open, and verifies each valve opens.

Terminate JPM when operator has opened 2RC40 thru 2RC43 Reactor Head Vents. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 6 of 8

JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below. V / ,Y ~ 1. Task description and number, JPM description and number are identified. If: ~ 2. Knowledge and Abilities (KIA) references are included. Lt ~ 3. Performance location specified. (in-plant, control room, or simulator) Ir' I ,!Jr ~ 4. Initial setup conditions are identified. I 1-= "1 s. Initiating and terminating Cues are properly identified.

           /
      / 7\            6. Task standards identified and verified by SME review.

v I -t' ~ 7. Critical steps meet the criteria for critical steps and are identified with an asterisk(*). I

          !1.,, \     8. Verify the procedure referenced by this JPM matches the most current revision of I      *v'    that procedure: Procedure Rev. 20            Date    .,12t/1-'

V \ 9. Pilot test the JPM:

      ---,----             a. verify Cues both verbal and visual are free of conflict, and
b. ensure performance time is accurate.

____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructor:

                                ~.~\~a-r~                         Date:    7)9)£ SME/lnstructor:         5 . Linn'~          'Jvjk                       Date:   ;, /~s */1~

SME/lnstructor: Date: PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 7 of 8

INITIAL CONDITIONS:

  • Unit 2 initiated a Rx trip from 100% power in response to a Main Steamline break at the mixing bottle.
  • An automatic Safety Injection initiated.
  • The Main Turbine failed to trip automatically, and was manually tripped from the control console.
  • MSLI failed, and all MSIV's remain open.
  • All AFW flow has been lost.
  • EOP-TRIP-1 was performed and a transition to FRHS-1, Loss of Secondary Heat Sink was made at Step 20.1 INITIATING CUE:

You are the Reactor Operator. Perform FRHS-1 starting at Step 1. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 8 of 8

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION: Salem Generating Station SYSTEM: Emergency Operating Procedures TASK: TCAF Total Loss of All Service Water TASK NUMBER: N1140380401 JPM NUMBER: 15-01 NRC Sim e ALTERNATE PATH: CJ KIA NUMBER:

                                                                    - - - -076 A2.01
                                                                              -- ----l IMPORTANCE FACTOR:         3.5           3.7
                                                                    --    --

APPLICABILITY: RO SRO EOCJ RO[[] STAC] SRO[[] EVALUATION SETTING/METHOD: Simulator I Perform S2.0P-AB.SW-0001, Loss of SW Header Pressure, Rev. 16 S2.0P-AB.SW-0005, Loss of All Service Water Rev. 4 S2.0P-AR.ZZ-0002, Overhead Annunciator Window B Rev. 36

REFERENCES:

(All rev checked 8-3-16) TOOLS AND EQUIPMENT: None VALIDATED JPM COMPLETION TIME: 5 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: N/A Developed By: G Gauding Date: 3-23-16 Instructor Validated By: W Russell I D Cox Date: 8-22-16 SME or Instructor Approved By: Date: Approved By: Date: ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY: EVALUATOR'S SIGNATURE: DATE: PSEG Confidential- Possession Requires Specific Approval from Nuclear Training

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: ~~~~~~~~~~~~~~ DATE: SYSTEM: Abnormal Operating Procedures TASK: TCAF a Total Loss of All Service Water TASK: N1140380401 Simulator Setup: IC-255 100% power. 21 charging pump in service 2 SW bay removed from service IAW S2.0P-AB.SW-003, Service Water Bay Leak. All 4 bay pumps in service. S2.0P-AB.SW-003 out and marked up. MALFS: Tied to RT-1 24 SW pump trip 25 SW pump trip 26 SW pump trip INITIAL CONDITIONS: Unit 2 is operating at 100% power. 21 charging pump is in service. 23 charging pump is aligned for Normal operation IAW Section 4.1 of S2.0P-SO.CVC-0002, Charging Pump Operation.

  1. 2 SW Bay has been removed from service to isolate a leak in the bay IAW S2.0P-AB.SW-0003, Service Water Bay Leak.

All #4 Service Water Bay pumps are in service. INITIATING CUE: You are the Reactor Operator. Respond to all indications and alarms. Successful Completion Criteria

1. All critical steps completed.
2. All sequential steps completed in order.
3. All time-critical steps completed within allotted time.
4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made Task Standard for Successful Completion:
1. Trip the Rx
2. Stop all RCPs prior to or within 3 minutes of any RCP bearing temperature reaching 175°F or any other RCP trip criteria being met in S2.0P-AB.RCP-001.
3. Place 23 Charging pump in service.
4. Reduce operating CCW pumps to one.

PSEG Confidential- Possession Requires Specific Approval from Nuclear Training

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: DATE: SYSTEM: Abnormal Operating Procedures TASK: TCAF a Loss of all Service Water STEP STEP STANDARD EVAL COMMENTS

  • No. S/U Simulator Operator: Insert RT-1 after operator assumes watch. This trips all 4 Bay SW pumps.

Recognizes that all SW pumps have tripped. Enters S2.0P-AB.SW-0005, Loss of All Service Water directly, or responds IAW ARP for [ow service water header pressures. ARP steps are after AB.SW-5 steps here in JPM. AB.SW-1 steps are after ARP steps here in JPM.

  • AB.SW-5 TRIP the reactor, AND CONFIRM the Trips the Rx using either trip handle, and 3.1 Reactor Trip. confirms the Rx trip.
  • AB.SW-5 STOP all RCPs. Depresses stop PBs for all RCPs.

3.2 GO TO 2-EOP-TRIP-1, Reactor Trip or Cue: You are to continue with S2.0P-AB.SW-Safety Injection, AND CONTINUE with this 0005 while other operators perform TRIP-1. procedure. Evaluator: Silence OHA's as not associated with loss of SW. AB.SW-5 CLOSE the following valves to isolate

3.4 letdown

*
  • 2CV3, 45 GPM ORIFACE Shuts the open orifice isolation valve and PSEG Confidential- Possession Requires Specific Approval from Nuclear Training

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STEP STEP STANDARD EVAL COMMENTS

  • No. S/U
  • 2CV4, 75 GPM ORIFICE ensures the remaining orifice isolation valves
  • 2CV5, 75 GPM ORIFICE are shut.

AB.SW-5 INITIATE Attachment 1, Continuous Action Initiates Attachment 1, Continuous Action 3.5 Summary. Summary. AB.SW-5 3.6 IF a Centrifugal Charging Pump is in Determines a centrifugal charging pump is in service AND the 23 Charging Pump is service and 23 charging pump is immediately IMMEDIATELY available to be placed in available to be placed in service. service, THEN PERFORM the following: A VERIFY ALL 21-24 RCP Seal Inlet Temperatures <225°F as indicated on 2CC1 or the Plant Computer B. ENSURE 23 Charging Pump is aligned for Normal Operation IAW S2.0P-SO.CVC-0002(Q) Charging Pump Operation. C. PLACE 23 Charging Pump in MANUAL.

  • D. PLACE Charging Master Flow Controller in MANUAL.
  • E. SET 23 Charging Pump Speed Demand to 10-12%.
  • F. START 23 Charging Pump AND immediately INCREASE Speed Demand to approximately 20% to couple pump.

G. ADJUST 23 Charging Pump Speed Demand to obtain desired flow. H. ENSURE Seal Injection Flow 6-12 gpm to each Reactor Coolant Pump not to exceed 40 gpm total Seal PSEG Confidential- Possession Requires Specific Approval from Nuclear Training

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STEP STEP STANDARD EVAL COMMENTS

  • No. S/U Injection Flow.
  • I. STOP 21 and 22 Centrifugal Charging Pumps.

J. DISPATCH an Operator to monitor operation of 23 Charging Pump due to the potential for rising Component Cooling Water System temperature. AB.SW-5 !E a Centrifugal Charging Pump is in Determines a Centrifugal Charging Pump is not 3.7 service AND the 23 Charging Pump is NOT in service IMMEDIATELY available to be placed in service, THEN STOP 21 and 22 Centrifugal Charging Pumps. AB.SW-5 PLACE 2CC131, RCP THERMAL Places 2CC131, RCP THERMAL BARRIER, in 3.8 BARRIER, in MANUAL. MANUAL. AB.SW-5 PLACE Component Cooling Pumps in Places all Component Cooling Pumps in

  • 3.9 MANUAL AND REDUCE the number of MANUAL AND stops all but one Component operating Component Cooling Water Cooling Water Pumps.

Pumps to one. Terminate JPM. ARP 3.1 VERIFY header low pressure using Determines header pressure is low. OHA's 2PA5373 on 2CC1. B-13,14 3.2 !E low pressure conditions exists due to Determines loss of SW system pressure does known system configuration, THEN GO TO not conditions exists due to known system S2.0P-SO.SW-0001 (Q) Service water configuration. Pump operation, to adjust system pressure. 3.3 IF a valid low pressure condition exists, Determines valid low pressure condition exists, THEN GO TO 82.0P-AB.SW-0001 (Q), and goes to $2.0P-AB.SW-0001, Loss of PSEG Confidential- Possession Requires Specific Approval from Nuclear Training

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STEP STEP STANDARD EVAL COMMENTS

  • No. S/U Loss of Service Water Header Pressure. Service Water Header Pressure.

AB.SW-1 INITIATE Attachment 1, Continuous Action Initiates Attachment 1, Continuous Action 3.1 Summary. Summary. AB.SW-1 Is there indication of a leak in a Service Determines there is no unisolated leak (SW 3.2 Water Bay per the following? Bay 2 has been isolated)

  • Visual indication
  • OHA B-29, 21-23 SW PMP SMP AREA LVL HI
  • OHA B-30, 24-26 SW PMP SMP AREA LVL HI AB.SW-1 START Service Water pumps to maintain Determines no SW pumps are available to be 3.4 header pressure between 95 and 105 psig. started.

AB.SW-1 Is there a leak or valve malfunction on the Determines the cause of low SW header 3.5 turbine header as indicated by any of the pressure is from loss of all SW pumps. following? AB.SW-1 Are both nuclear Service Water headers in Determines neither nuclear SW header is in 3.6 service? service. AB.SW-1 IF the Unit is in a Service Water Header Determines the Unit is not in a Service Water 3.7 Outage ... Header Outage. AB.SW-1 lE the Unit is NOT in a Service Water Determines the Unit is not in a Service Water 3.8 Header Outage, THEN GO TO S2.0P- Header Outage, and goes to S2.0P-AB,SW-AB.SW-0005 (Q), Loss of All Service Water 0005. TERMINATING CUE: After reduction of CCW pumps to one, terminate JPM. PSEG Confidential- Possession Requires Specific Approval from Nuclear Training

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE TQ-AA-106-0303 Revision 5 JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below. \,l 1.11111 ~ 1. Task description and number, J PM description and number a re identified. It /WI\ / 2. Knowledge and Abilities (KIA) references are included.

\}. ,/~* 3. Performance location specified. (in-plant, control room, or simulator)

V/ 4. Initial setup conditions are identified. l

 \f (             5. Initiating and terminating Cues are. properly identified.
 \.r / ~6. Task standards 1dent1f1ed and venfled              by SME review.
         /JA     {Critical steps meet the criteria for critical steps and are identified with an asterisk(').
       ~~*8. Verify the procedure referenced by this JPM matches the most current revision of that procedure: Procedure Rev.      _'i_*_Date    8'}I i.Z-bro I

W't\ J9. Pilot test the JPM:

a. verify Cues both verbal and visual are free of conflict, and
b. ensure performance time is accurate.

____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructor: Date: --=-g+-=/i;,'-=zji'l--'-1-=~ I SME/lnstructor: Date: ~ -z_z ~;L SME/lnstructor: Date: ------

                        -------------

PSEG Confidential- Possession Requires Specific Approval from Nuclear Training

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE INITIAL CONDITIONS: Unit 2 is operating at 100% power. 21 charging pump is in service. 23 charging pump is aligned for Normal operation IAW Section 4.1 of S2.0P-SO.CVC-0002, Charging Pump Operation.

  1. 2 SW Bay has been removed from service to isolate a leak in the bay IAW S2.0P-AB.SW-0003, Service Water Bay Leak.

All #4 Service Water Bay pumps are in service. INITIATING CUE: You are the Reactor Operator. Respond to all indications and alarms. PSEG Confidential- Possession Requires Specific Approval from Nuclear Training

OPERATOR TRAINING PROGRAlVI JOB PERFORMANCE MEASURE STATION: SALEM SYSTEM: Pressurizer and PRT TASK: Adjust PRT level and pressure TASK NUMBER: N0100110101 JPM NUMBER: 15-01 NRC Sim f ALTERNATE PATH: K/ANUMBER: 007 A4.04

                                                                                 ----------~

IMPORTANCE FACTOR: 2.6

                                                                                 - - 2.6---

APPLICABILITY: RO SRO EoO RO[ZJ STAD SRO[Z] EVALUATION SETTING/METHOD: Simulator I Perform

REFERENCES:

S2.0P-SO.PZR-0003, Rev. 15 (checked 8-5-16) TOOLS AND EQUIPMENT: None VALIDATED JPM COMPLETION TIME: 8 min TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: N/A Developed By: G Gauding Date: 8-5-16 Instructor Validated By: M Lutek I W Russell SME or Instructor i, Date: 8-22-16 Approved By: Tra~CrJ* 4 Date: Approved By: obartment ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY: EVALUATOR'S SIGNATURE: DATE: PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 1 of7

OPERATOR TRAINING PROGRAM JOB PERFORMAL~CE MEASURE NAME: ~~~~~~~~~~~~~~~~ DATE: ~~~~~~~~~~~~~~~~ SYSTEM: Pressurizer and PRT TASK: Adjust PRT level and pressure TASK NUMBER: N0450040101 SIMULATOR SETUP: 15-01 NRC IC-256 PRT level 56.2% (or low enough for the PRT Hi-Lo Lvl alarm to be locked in) with PRT pressure 9.8 psig. Paper copies of procedure needed. INITIAL CONDITIONS: Unit 2 is at 100% power. 2PR1 is leaking and 2PR6 is shut with power applied. Operators have been attempting to determine the leak rate through 2PR1. Console alarm PRT Level Hi-Lo is in alarm (lo) with PRT level at 56.2%. INITIATING CUE: You are directed to raise PRT level to 60% IAW S2.0P-SO.PZR-0003, Pressurizer Relief Tank Operation, Section 5.1. Successful Completion Criteria:

1. All critical steps completed.
2. All sequential steps completed in order.
3. All time-critical steps completed within allotted time.
4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made (and NRC concurrence is obtained).

Task Standard for Successful Completion:

1. Raise PRT level to > 60% while maintaining PRT pressure ~10 psig.

PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 2 of7

OPERATOR TRAINING PROGRAM NAME: JOB PERFORMANCE MEASURE DATE: SYSTEM: PZR and PRT TASK: Adjust PRT level and pressure STEP STEP EVAL COMMENTS

  • NO. (*Denotes a Critical Step) STANDARD S/U (Required for UNSAT Evaluation)

Provide marked up paper copy of S2.0P- Reviews Precautions and Limitations. SO.PZR-0003. 5.1.1 IF PRT level is low, THEN PERFORM the Note: The step for reducing PRT pressure following: may be performed prior to raising level, since pressure is close to the maximum allowed. (See Step 5.1.1.D) IF PRT pressure reduction is performed first, THEN Cue if PRT pressure is lowered past 7 psig ... " CRS states that the pressure reduction is sufficient to allow filling of the PRT now."

  • 5.1.1.A !E required, THEN ST ART 21 or 22 Primary Depresses start pushbutton for 22 Primary Water Pump. Water Pump. (aligned for manual start)

OR Places 21 Primary Water Pump in manual and depresses start pushbutton for 21 Primary Water Pump. IF operator does not start a Primary Water Pump and will gravity feed to makeup to the PRT, THEN Cue: The CRS directs you to use a Primary Water pump to makeup to the PRT. PSEG Restricted-Possession Requires Specific Pem1ission from Nuclear Training Page 3 of7

OPERATOR TRAINING PROGRAM NAME: ~~~~~~~~~~ JOB PERFORMANCE MEASURE DATE: ~~~~~~~~~~ SYSTEM: PZR and PRT TASK: Adjust PRT level and pressure STEP STEP EVAL COMMENTS

  • NO. (*Denotes a Critical Step) STANDARD S/U (Required for UNSAT Evaluation)
  • 5.1.1.B OPEN 2WR80, CONT PRI WATER STOP. Depresses open pushbutton for 2WR80 CONT PRI WATER STOP and verifies open light lit.
  • 5.1.1.C OPEN 2WR82, PRT WATER SUPPLY. Depresses open pushbutton for 2WR82, PRT WATER SUPPLY and verifies open light lit.
  • 5.1.1.D !E PRT pressure approaches 10 psig, THEN Depresses open pushbutton for 2PR15, OPEN 2PR15, VENT, as necessary, to maintain VENT prior to PRT pressure rising PRT pressure at >3 psig and _:::10 psig. above 10.0 psig, and depresses close pushbutton prior to PRT pressure lowering below 3.1 psig.

Note: IF PRT Hi Pressure alarm is received, it prevents the 2PR15 from opening, and pressure cannot be reduced. When operator has demonstrated that they can raise level without exceeding 10 psig, then Cue: PRT level is now 60% PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 4 of7

OPERATOR TRAINING PROGRAM NAME: JOB PERFORMANCE MEASURE DATE: SYSTEM: PZR and PRT TASK: Adjust PRT level and pressure STEP STEP EVAL COMMENTS

  • NO. (*Denotes a Critical Step) STANDARD S/U (Required for UNSAT Evaluation) 5.1.1.E When PRT level increases to between 59% and When PRT level rises to 60%:
  • 86%:

Closes 2WR80, CONT PRI WATER

  • 1. CLOSE 2WR80, CONT PRI WATER STOP.

STOP.

2. CLOSE 2WR82, PRT WATER SUPPLY Closes 2WR82, PRT WATER SUPPLY.
  • 3. ENSURE 2PR15, VENT is closed. Ensures 2PR15, VENT is closed.
4. lE Primary Water Pump is in service Depresses stop pushbutton for running Primary Water Pump. lE 21 Primary IAW Step 5.1.1.A, AND is NOT required Water pump was used to fill PRT, THEN to be in service for any other reason, places 21 or 22 Primary Water pump in THEN STOP running Primary Water auto.

Pump. 5.1.1.F DIRECT a second Operator to perform an Independent Verification of component position in Attachment 1, Section 1.0 TERMINATING CUE: After operator reads Step 5.1.1.F, state JPM is complete. PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 5 of7

OPERATOR TRAINING PROGRA1"\1 JOB PERFORMAl~CE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below.

\A I     (r ldh1. Task description and number, JPM description and number are identified.
 "' / wt~           2. Knowledge and Abilities (KIA) references are included.

II- / d"- l#fl 3. Performance location specified. (in-plant, control room, or simulator)

 \,. / d-- l6'?1 4. Initial setup conditions are identified.
  ~ / (f"" VJ/15. Initiating and terminating Cues are properly identified.

(J.i / ~ l}JI\, 6. Task standards identified and verified by SME review. v )'- ~ 7. Critical steps meet the criteria for critical steps and are identified with an asterisk(*).

       }"   ~       8. Verify the procedure referenced by this JPM matches the most current revision of that procedure: Procedure Rev. IS                    Date 3/2;i./11,;

f \Ml 9. Pilot test the JPM:

a. verify Cues both verbal and visual are free of conflict, and
b. ensure performance time is accurate.

____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructor: 4Lv~1t---/ ~ Date:

                                      '-'lUJr-=--"'--=---'-----'-R-'-u-'-~-s SMEii nstructor:__.h/......._,_'                           ~=---~*
                                                                        '---         Date:

SME/lnstructor: Date: _ _ _ _ __

                           -------------

PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 6 of 7

OPERATOR TRAINll'IG PROGRAM JOB PERFOR.L\IIANCE MEASURE INITIAL CONDITIONS: Unit 2 is at 100% power. 2PR1 is leaking and 2PR6 is shut with power applied. Operators have been attempting to determine the leak rate through 2PR1. Console alarm PRT Level Hi-Lo is in alarm (lo) with PRT level at 56.2%. INITIATING CUE: You are directed to raise PRT level to 60% IAW S2.0P-SO.PZR-0003, Pressurizer Relief Tank Operation, Section 5.1. PSEG Restricted-Possession Requires Specific Permission from Nuclear Training Page 7 of 7

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION: Salem Generating Station SYSTEM: Emergency Operating Procedures TASK: Perform Actions for a Loss of All AC Power (Energize a 4KV Vital Bus from a Station Power Transformer) TASK NUMBER: 1150140501 JPM NUMBER: 15-01 NRC Sim g ALTERNATE PATH: D KIA NUMBER: EPE 055 EA 1.07

                                                                      ~~~~~~~~--1 IMPORTANCE FACTOR:             4.3             4.5 APPLICABILITY:                                                              RO             SRO EoD          RO[ZJ          STAD            SRO[Z]

EVALUATION SETTING/METHOD: Simulator I Perform

REFERENCES:

S2.0P-SO.DG-0001, Rev. 39, S2.0P-S0.4KV-0001, Rev. 32 TOOLS AND EQUIPMENT: None VALIDATED JPM COMPLETION TIME: 10 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: NIA Developed By: G Gauding Date: 4-18-16 Instructor Validated By: Hancock I Russell Date: 8-16-16 SME or Instructor Approved By: Tra~ment Approved By: Operbsentative ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY: EVALUATOR'S SIGNATURE: DATE: PSEG Confidential- Possession Requires Specific Approval from Nuclear Training Page 1 of 7

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: ~~~~~~~~~~~~~~ DATE: ~~~~~~~~~~~~~~ SYSTEM: Emergency Operating Procedures TASK: Perform Actions for a Loss of All AC Power (Energize a 4KV Vital Bus from a Station Power Transformer) TASK 1150140501 NUMBER: Simulator Setup: IC-256 (with 24ASO racked down and control power off) INITIAL CONDITIONS:

1. Unit 2 is recovering from a loss of all AC Power.
2. The crew is performing step 16 of 2-EOP-LOPA-1.
3. 23 AFW pump is supplying all required AFW flow.
4. 2A EOG was started first and is providing power to 2A Vital Bus
5. 2B EOG was just started and is powering 2B 4KV vital bus.
6. 2C 4KV Vital Bus remains deenergized and unavailable.
7. 24 Station Power Transformer (SPT) has just been energized.
8. With 24 SPT now available, the CRS has directed that S2.0P-SO.DG-0001 Section 5.8 and S2.0P-S0.4KV-0001 Section 5.3.6 be utilized to swap 2A Vital Bus from 2A EOG to 24 SPT.

INITIATING CUE: You are the Control Board Operator. Complete Section 5.8 of S2.0P-SO.OG-0001, and then utilize Section 5.3.6 of S2.0P-S0.4KV-0001 to restore power to 2A Vital Bus from 24 SPT. Prerequisites and Precautions and Limitations have been reviewed and signed. Successful Completion Criteria

1. All critical steps completed.
2. All sequential steps completed in order.
3. All time-critical steps completed within allotted time.
4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made Task Standard for Successful Completion:

- Energize 2A 4KV vital bus using 24 SPT PSEG Confidential- Possession Requires Specific Approval from Nuclear Training Page 2 of 7

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: DATE: SYSTEM: Emergency Operating Procedures TASK: Perform Actions for a Loss of All AC Power (Energize a 4KV Vital Bus from a Station Power Transformer) STEP STEP STANDARD EVAL COMMENTS No. (* denotes critical task) S/U Provide marked up copies of S2.0P-SO.DG-0001 and S2.0P-S0.4KV-0001. SO.DG-1 !E 2A EOG is paralleled on 2A 4KV Vital Determines 2A Diesel Generator is not 5.8.1 Bus .... paralleled on 2A 4KV Vital Bus. 5.8.2 !E 2A Vital Bus is isolated and energized from 2A EOG, THEN: Places redundant equipment in service as

  • PLACE redundant equipment in needed:

service as necessary to support deenergizing 2A Vital Bus

  • 22 CCW pump Note: 1 SW pump with the TGA isolated is
  • STOP all 2A Vital Bus loads using sufficient for maintaining SW header pressure Attachment 1 Stops the following equipment (if running):
  • 21 CCW pump
  • 21 SW pump
  • 21 CFCU
  • 21 Aux Building Exhaust Fan
  • 21 SWGR Room Supply Fan
  • 21 SWGR Room Exhaust Fan
  • 21 BAT pump
  • 21 FHB Exhaust Fan
  • 21 AFW pump
  • 21 SI I 21 CS pumps PSEG Confidential- Possession Requires Specific Approval from Nuclear Training Page 3 of 7

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STEP STEP EVAL STANDARD COMMENTS No. (* denotes critical task) S/U 5.8.3 OPEN 2A DIESEL GENERATOR BREAKER Opens 2A DIESEL GENERATOR BREAKER by performing one of the following: by performing one of the following:

  • OPEN 2AD1AX6D, 2A DIESEL
  • Directs opening of 2AD1AX6D, 2A GENERATOR BREAKER (64' Swgr DIESEL GENERATOR BREAKER (64' Rm), or Swgr Rm), or
  • PRESS 2A BREAKER OPEN
  • Presses 2A BREAKER OPEN pushbutton (2CC3), or pushbutton (2CC3), or
  • PLACE 2A-DF-GCP-3, GENERATOR
  • Directs placing 2A-DF-GCP-3, CIRCUIT (BCS), to TRIP (2A DIG GENERATOR CIRCUIT (BCS), to Control Panel). TRIP (2A DIG Control Panel).

5.8.4 ALLOW Diesel to run unloaded for~ 3 Cue: 2A EOG will be shutdown by local minutes prior to stopping the EOG. operator. 5.8.5 If diesel unloading ... Determines step is NIA S0.4KV-1 IF 2A 4KV Vital Bus is to be energized from 5.3.6 24 SPT,THEN: 5.3.6.A Direct NEO to RACK UP 2AD1AX24ASD, Contacts NEO and directs them to rack up 24 STATION POWER TRANSFORMER 2AD1AX24ASD, 24 STATION POWER INFEED BREAKER (64' Swgr Rm). TRANSFORMER INFEED BREAKER. Simulator Operator: MODIFY REMOTE ED21D to ON, then report 2AD1AX24ASD, 24 STATION POWER TRANSFORMER INFEED BREAKER is racked up.

  • 5.3.6.B PRESS Mimic Bus 2A VITAL INFEED 24ASD Depresses Mimic Bus 2A VITAL INFEED pushbutton AND ENSURE Console Bezel 24ASD pushbutton AND determines the 24ASD MIMIC BUS INTLK CLOSE Console Bezel 24ASD MIMIC BUS INTLK SELECTION illuminates. CLOSE SELECTION illuminates.

PSEG Confidential- Possession Requires Specific Approval from Nuclear Training Page 4 of 7

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE 5.3.6.C PERFORM the following:

  • 1. PRESS AND HOLD control console Presses and Holds control console 24ASD 24ASD CLOSE pushbutton. CLOSE pushbutton, then releases pushbutton
2. RELEASE pushbutton when 24ASD when 24ASD indicates closed.

indicates CLOSED.

3. ENSURE the following: Checks Console bezel 24ASD MIMIC BUS
a. Console bezel 24ASD MIMIC BUS INTLK INTLK CLOSE SELECTION is extinguished.

CLOSE SELECTION is extinguished.

b. 2A 4KV Vital Bus voltage is 4.275 -

4.336KV (normal) OR 4.330 - 4.417KV (single source of off-site Determines 2A Vital Bus voltage is 4.275 - power). 4.385KV (single source of off-site power.

c. OHA J-17, 2A 4KV VTL BUS Determines OHA J-17 2A 4KV VTL BUS UNDRVOLT, is clear. UNDRVOLT is clear.

Terminate JPM. PSEG Confidential- Possession Requires Specific Approval from Nuclear Training Page 5 of 7

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below. I! /  ;:J- 1. Task description and number, JPM description and number are identified.

 "  ./   (),   2. Knowledge and Abilities (KJA) references are included.

v I~

    ~ 3. Performance location specified. (in-plant, control room, or simulator) v    ~ 4. Initial setup conditions are identified.

v ~ 5. Initiating and terminating Cues are properly identified. v ~ 6. Task standards identified and verified by SME review .

 .v --9--      7. Critical steps meet the criteria for critical steps and are identified with an asterisk (*).

V ___Q_ 8. Verify the procedure referenced bl_ this JPM matchei the most current revision of

       ~         that procedure: Procedure Rev.      2j_ Date <3/Jvlllo fJ 9. Pilot test the JPM:                     . ] z_
    -C- a. verify Cues both verbal and visual are free of conflict, and
b. ensure performance time is accurate.
    ~ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM
    /          11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.
    ~nstructo?!IL~"""'k_.-                                             Date:   $> J(L /1~
    's-M(;lnstructor,.~              ~l(                                Date:   S I/ i G /J I

6 SME/lnstructor: Date: - - - - - -

                     ~-----------~

PSEG Confidential- Possession Requires Specific Approval from Nuclear Training Page 6 of 7

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE INITIAL CONDITIONS:

1. Unit 2 is recovering from a loss of all AC Power.
2. The crew is performing step 16 of 2-EOP-LOPA-1.
3. 23 AFW pump is supplying all required AFW flow.
4. 2A EOG was started first and is providing power to 2A Vital Bus
5. 2B EOG was just started and is powering 2B 4KV vital bus.
6. 2C 4KV Vital Bus remains deenergized and unavailable.
7. 24 Station Power Transformer (SPT) has just been energized.
8. With 24 SPT now available, the CRS has directed that S2.0P-SO.DG-0001 Section 5.8 and S2.0P-S0.4KV-0001 Section 5.3.6 be utilized to swap 2A Vital Bus from 2A EOG to 24 SPT.

INITIATING CUE: You are the Control Board Operator. Complete Section 5.8 of S2.0P-SO.OG-0001, and then utilize Section 5.3.6 of S2.0P-S0.4KV-0001 to restore power to 2A Vital Bus from 24 SPT. Prerequisites and Precautions and Limitations have been reviewed and signed. PSEG Confidential- Possession Requires Specific Approval from Nuclear Training Page 7 of 7

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION: SALEM 1 & 2 SYSTEM: Loss of Control Air TASK: TCAF a Loss of Control Air TASK NUMBER: N1140070401 JPM NUMBER: 15-01 NRC Sim h ALTERNATE PATH: I x I KIA NUMBER: APE 065 AA2.06

                                                                       ~~~~~~~~~~

IMPORTANCE FACTOR: 3.6 4.2 APPLICABILITY: RO SRO EOCJ RO[KJ STACJ SRO[KJ EVALUATION SETTING/METHOD: Simulator - Perform S2.0P-AB.CA-0001, Rev. 21 Loss of Control Air (both rev checked 8-5-16)

REFERENCES:

S2.0P-AR.ZZ-0011, Rev. 60, pages 118-128 TOOLS AND EQUIPMENT: None VALIDATED JPM COMPLETION TIME: 8 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: N/A Developed By: G Gauding Date: 8-5-16 Instructor Validated By: M Lutek I W Russell Date: 8-22-16 SME or Instructor fJL_ Approved By: Trai~:n;v Date: Approved By: Date: Operbrtment ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY: EVALUATOR'S SIGNATURE: DATE: PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 1 of 13

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: ~~~~~~~~~~~~~- DATE: ~~~~~~~~~~~~~- SYSTEM: Loss of Control air TASK: TCAF Loss of Control Air TASK NUMBER: N1140070401 SIMULATOR SETUP: Check 2WG41 is open 15-01 NRC IC-258 RT-1 MALF: CA0221 #2 STATION AIR CMPRSSR TRIP REM: CA13D LOCKOUT #1 STATION AIR CMPRSR, Delay 1:30 1/0 : AQ01 OVLO COMP 1 TROUBLE ALARM, Fin Val: ON, Delay 1:30 Other setup: REM: CA15D LOCKOUT #3 STATION AIR CMPRSR CA11D #1 EMERGENCY AIR COMPRSR IN AUTO Fin Val: MANUAL CA 12M #1 EMRGENCY AIR CMPRSR SWITCH Fin Val: Stop 1/0 : AQ01 OVLO COMP 3 TROUBLE ALARM, Fin Val: ON INITIAL CONDITIONS:

  • Unit 2 is operating at 100% power.
  • A WG release is in progress from 21 GOT.
   *   #3 SAC is CIT for scheduled maintenance.
  • Unit 1 is operating at 100% power.

INITIATING CUE: You are the Unit 2 Reactor Operator. Respond to all indications and alarms. Successful Completion Criteria:

1. All critical steps completed.
2. All sequential steps completed in order.
3. All time-critical steps completed within allotted time.
4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made.

Task Standard for Successful Completion:

1. Isolate Letdown
2. Terminate Gaseous Release
3. Trip the Rx prior to auto trip on lo lo SG NR level.

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 2of13

OPERATOR TRAINING PROGRAM NAME: - - - - - - - - - JOB PERFORMANCE MEASURE DATE: - - - - - - - - - SYSTEM: Loss of Control Air TASK: TCAF a Loss of Control Air STEP COMMENTS STEP (* Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD SIU evaluation)

Note: The #1 and #3 Compressor Trouble alarms on 2CC1 do NOT have audible or flash capabilities (S2.0P-AR.ZZ-0011 page 120). Simulator Operator: Insert RT-1 after operator assumes watch. Determines #2 Station Air Compressor (SAC) has tripped, and the Unit 2 Emergency Control Air Compressor (ECAC) has automatically started. Note: All 3 SAC supply breakers open is an auto start signal for both ECAC's. The Unit 2 ECAC will auto start, (Unit 1 will not). By design, the ECAC will not load until its control air header pressure lowers to 85 psig. 2A control air header is supplied from #2 ECAC, 2B control air header is supplied from #1 ECAC. Note: The next-to-load SAC (follow) will not immediately start. It requires Station Air header pressure to drop to 5 psig below the follow setpoint ( 105 psig) for - 5 seconds. Refers to the S2.0P-AR.ZZ-0011, Control Console 2CC1, ARP for COMPR 2 TROUBLE. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 3 of 13

OPERATOR TRAINING PROGRAM NAME:

                                                                                                                   ---------

JOB PERFORMANCE MEASURE 0 ATE:

                                                                                                                   ---------

SYSTEM: Loss of Control Air TASK: TCAF a Loss of Control Air STEP COMMENTS STEP (*Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD S/U evaluation)

ARP 3.1 lE SAC 2 trips, THEN: A. COORDINATE (as necessary) Coordinates with Unit 1 to start at least one with Unit 1 SAC IAW SC.OP-SO.SA-0001{Z), Station Air B. ENSURE operating OR START at System Operation. least one SAC IAW SC.OP-SO.SA-0001(Z), Station Air Cue when contacted as Unit 1: Unit 1 will System Operation. ensure #1 SAC is placed in service. ARP 3.2 IF AT ANY TIME Station Air pressure GOES TO S2.0P-AB.CA-0001(Q), Loss of cannot be maintained .:::,100 psig, THEN Control Air, when Station Air pressure lowers GO TO S2.0P-AB.CA-0001(Q), Loss of to 100 psig if AB not entered previously. Control Air. Simulator Operator: Ensure #1 SAC locks out 1:30 after insertion of RT-1, then announce twice on plant page: "#1 Station Air Compressor Trip." Recognizes that no SAC's are running, and enters S2.0P-AB.CA-0001 if not entered previously. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 4of13

OPERATOR TRAINING PROGRAM NAME:

                                                                                                                  ---------

JOB PERFORMANCE MEASURE DATE: - - - - - - - - - SYSTEM: Loss of Control Air TASK: TCAF a Loss of Control Air STEP COMMENTS STEP (* Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD S/U evaluation)

Note: Approximate event times are listed below from insertion of RT-1. 1 min - 1 SAC auto starts. 1 min 30 sec - 1 SAC trips. 3 min 50 sec - 2 ECAC begins loading. 4 min 10 sec - 28 Control Air header pressure reaches 80 PSIG, and SA low pressure alarm. 4 min 25 sec - CA low pressure alarm. 6.5 min 24BF19 Feed Reg Valves begin ' closing. 7 min 10 sec - G-15 OHA ADFCS TRBL. AB.CA INITIATE Attachment 1, Continuous Initiates Attachment 1, Continuous Action 3.1 Action Summary. Summary. Cue IF Required: If CAS Step 8.0 action is being taken to refer to Attachment 2 for valve fail positions and for further action to be taken, then: Cue: The CRS will refer to Attachment 2 3.2 EITHER of the following conditions exist? Determines all SAC's are stopped or

  • ALL Station Air Compressors determines Station Air Header pressure is stopped <100 psig.
  • EITHER Station Air Header <100 psig PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 5of13

OPERATOR TRAINING PROGRAM NAME:

                                                                                                                   ---------

JOB PERFORMANCE MEASURE DATE: - - - - - - - - - SYSTEM: Loss of Control Air TASK: TCAF a Loss of Control Air STEP COMMENTS STEP (* Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD S/U evaluation) 3.3 lE a loss of 1 F Group Bus has occurred, Determines a loss of 1F Group Bus has not AND 1H Group Bus is available, THEN occurred.

SEND an Operator to restore power to #1 SAC Auxiliary Oil pump by transferring 11 Turbine West 230V Control Center IAW Attachment 14, Section 1.0. 3.4 IF a loss of 2F Group Bus has occurred, Determines a loss of 2F Group Bus has not AND 2H Group Bus is available, occurred. THEN SEND an Operator to restore power to #2 SAC Auxiliary Oil pump by i transferring 21 Turbine West 230V Control Center IAW Attachment 14, Section 2.0. 3.5 lE a loss of 1H Group Bus has occurred, Determines a loss of 1H Group Bus has not AND 1F Group Bus is available, occurred. THEN SEND an Operator to restore power to #3 SAC Auxiliary Oil pump by transferring 11 Turbine East 230V Control Center IAW Attachment 14, Section 3.0. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 6of13

OPERATOR TRAINING PROGRAM NAME:

                                                                                                                    ---------

JOB PERFORMANCE MEASURE DATE: - - - - - - - - - SYSTEM: Loss of Control Air TASK" TCAF a Loss of Control Air STEP COMMENTS STEP (*Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD evaluation)

S/U 3.6 START or have Unit One Control Room Determines no SAC's are available. START Next to Load Station Air Compressor. Cue if required: If Unit 1 is contacted, report that #3 Station Air Compressor is tagged out and #1 Station Air Compressor has tripped, and that an operator has been dispatched to the Station Air Compressors. 3.7 Either Station Air Header indicating less Determines both Station Air Headers are than100 psig? indicating less than 100 psig. 3.8 Attempt to START, or have Unit One Determines no SAC's can be started. Control Room START, remaining Station Air Compressor. 3.9 NOTIFY the CRS/SM to evaluate use of Cue: CRS will evaluate use of temporary air temporary air compressors. compressors. 3.10/3.11 2A Control Air Header less than or equal Determines 2A control air header pressure is: to 88 psig? less than or equal to 88 psig and determines

                                                             #2 ECAC is in service OR
                                                             >88 psig.

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 7 of 13

OPERATOR TRAINING PROGRAM NAME: - - - - - - - - - JOB PERFORMANCE MEASURE DATE: - - - - - - - - - SYSTEM: Loss of Control Air TASK

  -          TCAF a Loss of Control Air STEP                                                                                    COMMENTS STEP                                                                                                               (Required for UNSAT

(*Denotes a Critical Step) EVAL

  • NO. STANDARD S/U evaluation) 3.12/3.13 2B Control Air Header less than or equal Determines 2B control air header pressure is:

to 88 psig? less than or equal to 88 psig and contacts Unit 1 to place #1 ECAC in service OR

                                                               >88 psig.

Cue: When Unit 1 is contacted to start #1 ECAC, state: " # 1 ECAC has tripped. " 3.14 SEND operators to: Dispatches operators to:

  • LOCATE AND ISOLATE ANY air
  • LOCATE AND ISOLATE any air system leaks. system leaks.
  • INVESTIGATE cause of ANY air
  • INVESTIGATE cause of air compressor trip/trouble. compressor trip/trouble.

3.15 IF Station Air is lost, AND EITHER of the Determines Station Air is lost, and neither of following are in service: the following are in service:

  • Spent Fuel Pool Transfer Pool
  • Spent Fuel Pool Transfer Pool Weir Weir Gate Seals Gate Seals
  • SG Nozzle Dams
  • SG Nozzle Dams THEN:

A. EVACUATE personnel from areas subject to leakage/flooding. B. INITIATE monitoring of Fuel Pool or Reactor Vessel levels for the need to makeup due to leakage. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 8 of 13

OPERATOR TRAINING PROGRAM NAME: - - - - - - - - - JOB PERFORMANCE MEASURE DATE: - - - - - - - - - SYSTEM: Loss of Control Air TASK: TCAF a Loss of Control Air STEP COMMENTS STEP (*Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD S/U evaluation) 3.16 !E cooling water to the Station or Determines cooling water to the Station or Emergency Air Compressors is lost, Emergency Air Compressors is not lost.

THEN INITIATE the applicable portion of Attachment 6. 3.17 BOTH 2A and 2B Control Air Headers Determines both 2A and 2B Control Air less than 80 psig? Headers are not <80 psig. 3.18 ANY Excess Flow Check Valve closed as indicated by at least one of the following? (Attachment 5, Excess Flow Check Valve Determines NO Excess Flow Check Valve Table) [INPO IER L2 15-16] closed.

  • Groups of valves repositioning with normal air pressure indicated in Control Room
  • Local observation of low pressure downstream of an Excess Flow Check Valve 3.19 2B Control Air Header less than 80 psig? Determines 28 Control Air Header is <80 psig.

Alternate Path actions start here. 3.57 CONTINUE

  • 3.58 CLOSE the following valves: Closes the following valves:

A. 2CV3, LTDWN ORIFICE !SOL VALVE A. 2CV3, LTOWN ORIFICE !SOL VALVE B. 2CV4, LTDWN ORIFICE !SOL VALVE B. 2CV4, LTDWN ORIFICE !SOL VALVE C. 2CV5, LTDWN ORIFICE ISOL VALVE C. 2CV5, LTDWN ORIFICE !SOL VALVE D. 2CV2 LETDOWN LINE !SOL VALVE D. 2CV2 LETDOWN LINE !SOL VALVE E. 2CV277 LTDWN LINE !SOL VALVE E. 2CV277 LTDWN LINE ISOL VALVE F. 2CV7 LTDWN HX INLET VALVE F. 2CV7 LTDWN HX INLET VALVE PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 9of13

OPERATOR TRAINING PROGRAM NAME:

                                                                                                                    ---------

JOB PERFORMANCE MEASURE DATE:

                                                                                                                    ---------

SYSTEM: Loss of Control Air TASK: TCAF a Loss of Control Air STEP COMMENTS STEP (*Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD S/U evaluation) 3.57 VERIFY ANY Liquid or Gaseous release Determines 2WG41, GAS DECAY TK TO
  • is stopped by ensuring the following PLANT VENT is open, and shuts 2WG41, valves CLOSED: GAS DECAY TK TO PLANT VENT.
  • 2WL51, TO CIRC WTR DISCHARGE Verifies 2WL51 is shut.
  • 2WG41, GAS DECAY TK TO PLANT VENT CAS IF AT ANY TIME Station Air is lost, 6.0 THEN:
  • INITIATE monitoring of 21- Identifies all BF19 valves closing.

24BF19 SG FW CONT VALVE,

  • operation. Trips the Reactor.
                    *  !E ANY BF19 SG FW CONT VALVE closes AND Applicable SG water level CANNOT be maintained, THEN:

A. TRIP the Reactor B. CONTINUE with this procedure C. GO TO 2-EOP-TRIP-1, Reactor Trip Or Safety Injection. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 10of13

OPERATOR TRAINING PROGRAM NAME:

                                                                                                                ---------

JOB PERFORMANCE MEASURE DATE: - - - - - - - - - SYSTEM: Loss of Control Air TASK TCAF a Loss of Control Air STEP COMMENTS STEP (Required for UNSAT (* Denotes a Critical Step) EVAL

  • NO. STANDARD S/U evaluation)

TRIP-1 Performs Immediate Actions of EOP-TRIP-1: Confirms the Rx trip Trips the Main turbine Checks at least 1 4KV vital bus energized Determines SI is not initiated or required. Cue after Immediate Actions have been performed: The CRS and another operator will continue performing the EOPs. You are to continue in current procedure. Terminate JPM once Rx has been tripped, letdown isolated, and the WG release terminated. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 11 of 13

JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below. / ~tut] Task description and number, JPM description and number are identified. / )-- ~-Knowledge and Abilities (KIA) references are included. I ~- Performance location specified. (in-plant, control room, or simulator) / G~. Initial setup conditions are identified. I . Initiating and terminating Cues are properly identified.

/ M.            Task standards identified and verified by SME review.

0 ~- Critical steps meet the criteria for critical steps and are identified with an asterisk(*).

  }-Lil. 8. Verify the procedure referenced 2rs JPM mate es th                 most current revision of that procedure: Procedure Rev.                  Date    "'l--, _
  '(s:\J./!'g_ Pilot test the JPM:
a. verify Cues both verbal and visual are free of conflict, and
b. ensure performance time is accurate.

____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page.

                                                       --

SME/lnstructor: __~_~L....,.......,_v_~~.r~~~----'P.+--=-,.cAr---- __ SME/lnstructor:~A~~-"'-~~~-~-~_u_ss-_*_t_l_ _ SME/lnstructor: Date: - - - - - -

                   --------------

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 12 of 13

INITIAL CONDITIONS:

  • Unit 2 is operating at 100% power.
  • A WG release is in progress from 21 GOT.
   *  #3 SAC is CIT for scheduled maintenance.
  • Unit 1 is operating at 100% power.

INITIATING CUE: You are the Unit 2 Reactor Operator. Respond to all indications and alarms. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 13 of 13

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION: SALEM SYSTEM: Pressurizer/Pressure Relief TASK: Transfer Pressurizer 22 Backup Heaters to Emergency Power Supply TASK NUMBER: 115 043 05 01 JPM NUMBER: 15-01 NRC Annual IP-i ALTERNATE PATH: D KIA NUMBER: 010 A4.02

                                                                     ~~~~~~~~---!

IMPORTANCE FACTOR: 3.6 3.4 APPLICABILITY: RO SRO EOCJ RO[D STAC] SRO[D EVALUATION SETTING/METHOD: In Plant, Simulate

REFERENCES:

S2.0P-SO.PZR-0010 Rev. 10 (Rev. checked 8-5-16) TOOLS AND EQUIPMENT: None VALIDATED JPM COMPLETION TIME: 20 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: N/A Developed By: G Gauding Date: 8-5-16 Instructor Validated By: S Bickhart I J Hancock Date: 9-30-16 SME or lnstruc~:{~ 10~0~<.., Tr~rtment Approved By: Date: Jo/10/1t.~ Approved By: Ope~ons Dep~1ent Date: ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY: EVALUATOR'S SIGNATURE: DATE: Page 1of6

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM: Pressurizer/Pressure Relief TASK: Transfer Pressurizer 22 Backup Heaters to Emergency Power Supply TASK 1150430501 NUMBER: INITIAL CONDITIONS: Due to a loss of power to the group buses it is necessary to energize the PZR Backup Heaters from their emergency power supply. INITIATING CUE: The CRS directs you to perform S2.0P-SO.PZR-0010(Q), Section 5.3, Transferring Pzr Htr 22 BU Group To The Emergency Power Supply. All prerequisites and Precautions and Limitations have been reviewed and completed. 2A EOG is carrying 2A Vital Bus and is loaded to 2400 KW. You have a JAM key. Successful Completion Criteria:

1. All critical steps completed.
2. All sequential steps completed in order.
3. All time-critical steps completed within allotted time.
4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made (and NRC concurrence is obtained).

Task Standard for Successful Completion:

1. Simulate opening all but three PZR heater disconnects.
2. Simulate aligning emergency power to PZR heater bus from 2A vital bus.

Page 2of6 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME:~~~~~~~~~~ SYSTEM: Pressurizer/Pressure Relief DATE:~~~~~~~~~~ TASK: Transfer 22 Backup Heaters to Emergency Power Supply STEP COMMENTS

  • STEP (*Denotes a Critical Step) EVAL (Required for UNSAT NO. STANDARD S/U Evaluation)

Operator obtains procedure S2.0P- Provide marked up copy of S2.0P-SO.PZR-0010, Pressurizer Backup Heaters SO.PZR-0010, Pressurizer Backup Power Supply Transfer. Heaters Power Supply Transfer 5.3.1 ENSURE 2AX1AX14X, 2EP Locates breaker 2AX1AX14X 2EP PRESSURIZER HEATER BUS FEED PRESSURIZER HEATER BUS FEED (EMERGENCY) is OPEN (84' Swgr Rm). (EMERGENCY) on 2A 460V Vital Bus, Elev. 84' Swgr Rm and determines current breaker position. Cue: 2AX1AX14X Breaker indicates OPEN. 5.3.2 Request NCO to PERFORM the following: Locates nearest means of A. PLACE 22 Backup Group in communications and requests NCO to MANUAL. place 22 B/U Htrs in MANUAL and B. PRESS the 22 BACKUP OFF press the 22 BACKUP OFF pushbutton pushbutton. Cue: NCO reports 22 B/U Htrs are in MANUAL and 22 BACKUP OFF pushbutton has been depressed.

  • 5.3.3 ENSURE 2EX1 EP2EPX, 2EP 480V Locates 2EX1 EP2EPX, 2EP 480V PRESSURIZER HEATER BUS MAIN PRESSURIZER HEATER BUS MAIN BREAKER is OPEN (78' Electrical BREAKER on El. 78 Electrical Pen.

Penetration). Cue: 2EX1EP2EPX, 2EP 480V PRESSURIZER HEATER BUS MAIN BREAKER is OPEN. Page 3of6 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE NAME: _ _ _ _ _ _ _ _ _~ SYSTEM: Pressurizer/Pressure Relief DATE: TASK: Transfer 22 Backup Heaters to Emergency Power Supply

                                                                                                                     ----------

STEP COMMENTS

  • STEP (*Denotes a Critical Step) EVAL (Required for UNSAT NO. STANDARD S/U Evaluation)
  • 5.3.4 REMOVE interlock key from breaker Describes turning key and removing 2EX1 EP2EPX. interlock key from breaker 2EX1 EP2EPX.

Note: Tab must be pushed in to rotate key to allow its removal.

  • 5.3.5 PLACE any eleven of the following Operator locates individual heater disconnects in OFF (only three disconnects disconnects, places all but three are to remain ON) AND MARK the disconnects in OFF and notes remaining disconnects as N/A: disconnects left ON as N/A in procedure.
  • 5.3.6 PLACE, 2AX1AX14X-1, 2EP PZR HTR Operator locates 2AX1AX14X-1, 2EP BUS EMERGENCY FEED DISCONNECT PZR HTR BUS EMERGENCY FEED SWITCH, in the ON position (Elev 78' DISCONNECT SWITCH, and places it Electrical Penetration). in the ON position (Elev 78' Electrical Penetration).
  • 5.3.7 INSERT interlock key, AND UNLOCK Locates Corry Key Interlock on breaker 2AX1AX14X. 2AX1AX14X breaker, inserts and turns key.

5.3.8 NOTIFY NCO that PZR Htr 22 B/U Group Candidate makes report to the Control has been transferred to the emergency Room. power supply (2A 460V Vital Bus). Repeat back notification and state: JPM is comolete. Page 4 of6 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

., OPERATIONS TRAINING PROGRAM JOB PERFORMANCE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below.

  ~1. Task description and number, JPM description and number are identified.

W 2. Knowledge and Abilities (KIA) references are included.

  ~3. Performance location specified. (in-plant, control room, or simulator)
  ~4. Initial setup conditions are identified.
  ~5. Initiating and terminating Cues are properly identified.

J 16. Task standards identified and verified by SME review.

  ~7. Critical steps meet the criteria for critical steps and are identified with an asterisk(').

J..--4

       <     8. Verify the procedure referenced by this JPM mat9hEis the most current revision of that procedure: Procedure Rev. __J.._ Date H L'11      S

_); } 9. Pilot test the JPM:

a. verify Cues both verbal and visual are free of conflict, and
b. ensure performance time is accurate.

____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructor: ~&..II ... ~ Date: '/Jo/1" SME/lnstruct~ __..-1$fdt~~ Date: 'lf3v,h6 SME/lnstructor: Date: - - - - - -

                   -------------

OPERATIONS TRAINING PROGRAM JOB PERFORMANCE MEASURE INITIAL CONDITIONS: Due to a loss of power to the group buses it is necessary to energize the PZR Backup Heaters from their emergency power supply. INITIATING CUE: The CRS directs you to perform S2.0P-SO.PZR-0010(Q), Section 5.3, Transferring Pzr Htr 22 BU Group To The Emergency Power Supply. All prerequisites and Precautions and Limitations have been reviewed and completed. 2A EOG is carrying 2A Vital Bus and is loaded to 2400 KW. You have a JAM key. Page 6of6 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE: STATION: SALEM SYSTEM: Auxiliary Feedwater TASK: Perform Auxiliary Feedwater Back Leakage Test TASK NUMBER: N0610160204 JPM NUMBER: 15-01 NRC IP-j ALTERNATE PATH: I I KIA NUMBER: 061 K1 .02

                                                                        ~----------.,

IMPORTANCE FACTOR:

                                                                        - -3.4--            3.7 APPLICABILITY:                                                               RO             SRO EOLJ           RO[KJ           STALJ           SRO[KJ EVALUATION SETTING/METHOD:               lnplant- Simulate

REFERENCES:

S1 .OP-PT.AF-0002, Rev. 7, Auxiliary Feedwater Backleakage (checked 8-5-16) TOOLS AND EQUIPMENT: Calculator VALIDATED JPM COMPLETION TIME: 5 minutes TIME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: NIA Developed By: G Gauding Date: 8-5-16 Instructor Validated By: S Bickhart I J Hancock Date: 9-30-16 SME or Instructor Approved By: ~ Mvff(W\ Date: tojof 0 Training~partment Approved By: Date: /ofcf~ Opebrtment ACTUAL JPM COMPLETION TIME: ACTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: D SAT D UNSAT REASON, IF UNSATISFACTORY: EVALUATOR'S SIGNATURE: DATE: Page 1 of 8 PSEG Restricted-Possession Requires Specific Permission from Nuclear Training

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE: NAME: ~~~~~~~~~~~~~~ DATE: ~~~~~~~~~~~~~~ SYSTEM: Auxiliary Feedwater System TASK: Perform Auxiliary Feedwater Back Leakage Test TASK NUMBER: N0610160204 INITIAL CONDITIONS: Unit 1 is operating at 100% power. 11 AFW pump was secured 30 minutes ago after its normally scheduled quarterly surveillance run. INITIATING CUE: You are directed to perform S1 .OP-PT.AF-0002, Auxiliary Feedwater Backleakage. Successful Completion Criteria:

1. All critical steps completed.
2. All sequential steps completed in order.
3. All time-critical steps completed within allotted time.
4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made.

Task Standard for Successful Completion:

1. Determine 11 AFW pump and piping requires venting.
2. Vents 11 AFW pump and piping.

Page 2 of 8 PSEG Restricted-Possession Requires Specific Permission from Nuclear Training

                                                                                                                                     "'

OPERATOR TRAINING PROGRAM NAME: ~~~~~~~~~- JOB PERFORMANCE MEASURE DATE: ~~~~~~~~~- SYSTEM: AFW TASK Perform Auxiliary Feedwater Back Leakaae Test STEP COMMENTS STEP (*Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD S/U evaluation)

Provide operator with blank copy of S1 .OP- Reviews and initial all Prerequisites PT.AF-0002, Rev. 7, and a calculator. and Precautions and Limitations. 5.1.1 RECORD following on Attachment 1, Section 1.0: After locating 1TA165551, provide

  • AFW Line Temperatures (1TA165551) the following AFW line
  • Highest line temperature temperatures:

11-104

  • Average line temperature 12- 106
  • Temperature difference 13- 161 14- 108
  • On Attachment 1, records AFW temperatures, calculates total of 479,
  • divides that by 4 and determines
  • highest line temp is 161 and average line temp is 119. 75.
  • Determines Temp Diff 161- 119.75 =

41.25. 5.1.2 IF temperature in each line is <120°F, AND temperature difference between highest Determines highest temp is >120°F and average line temp is .:::_10°F, THEN RECORD Test Results in Attachment 1, Section 5.0. Page 3 of 8 PSEG Restricted-Possession Requires Specific Permission from Nuclear Training

OPERATOR TRAINING PROGRAM NAME: ~~~~~~~~~- JOB PERFORMANCE MEASURE DATE: ~~~~~~~~~- SYSTEM: AFW TASK Perform Auxiliarv Feedwater Back Leakaae Test STEP COMMENTS STEP (*Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD S/U evaluation) 5.1.3 IF temperature in any line is .'.:'._120°F AND <160°F, THEN: Determines highest temp is >160°F A. RECORD Auxiliary Feedwater System piping temperatures every hour in Control Room Narrative Log.

B. RECORD Test Results in Attachment 1, Section 5.0. 5.1.4 IF temperature difference between highest and average line temp is >10°F, THEN Determines temperature difference RECORD Test Results in Attachment 1, between highest and average line

  • Section 5.0. temp is >10°F, and records Test Results in Attachment 1, Section 5.0.,

as UNSAT for all three categories. 5.1.6 I IF temperature in any line is .'.::160°F THEN: A. RECORD findings in Control Room Narrative Log. B. VENT Auxiliary Feedwater pumps/piping IAW Section 5.2. Page 4 of 8 PSEG Restricted-Possession Requires Specific Permission from Nuclear Training

'

OPERATOR TRAINING PROGRAM NAME: ~~~~~~~~~- JOB PERFORMANCE MEASURE DATE: ~~~~~~~~~- SYSTEM: AFW TASK: Perform Auxiliarv Feedwater B --

                                        -       --- - T STEP                                                                            COMMENTS STEP

(*Denotes a Critical Step) EVAL (Required for UNSAT

  • NO. STANDARD S/U evaluation)
  • 5.2.1 IF 11 Auxiliary Feedwater Pump and piping is affected, THEN:

A. SLOWLY THROTTLE OPEN 11AF83, AF Locates and opens 11 AF83, AF PUMP VENT, until a solid stream of water is PUMP VENT, until a solid stream of observed. water is observed. Cue: A solid stream of water is observed. B. CLOSE 11 AF83. Closes 11 AF83 Locates and opens 11 AF114, AF C. SLOWLY THROTTLE OPEN 11AF114, PUMP DISCH VENT, until a solid AF PUMP DISCH VENT, until a solid stream stream of water is observed. of water is observed. Cue: A solid stream of water is observed. D. CLOSE 11AF114. Closes 11AF114. Terminate JPM I Page 5 of 8 PSEG Restricted-Possession Requires Specific Permission from Nuclear Training

This page intentionally blank. Page 6 of 8

JOB PERFORMANCE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below.

    ~ ~1. Task description and number, JPM description and number are identified.

U~ 2. Knowledge and Abilities (KIA) references are included. V ;I- ')I 3. Performance location specified. (in-plant, control room, or simulator) V/ 'S / 4_ Initial setup conditions are identified.

  \/ erL2L5.          Initiating and terminating Cues are properly identified.
  \J'~/6. Task standards identified and verified by SME review.

I> /7. Critical steps meet the criteria for critical steps and are identified with an asterisk n \!'- d 18. Verify the procedure referenced by this JPM maJchfs the most current rev1s1on of that procedure: Procedure Rev. :f- Date /,ffJ{-fJ.

       ~           9. Pilot test the JPM:
a. verify Cues both verbal and visual are free of conflict, and
b. ensure performance time is accurate.

____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstructor: ~~ Date: 9/.Jo//h SME/lnstructo~cft!Mll t- Date: 9/~ ~JI co. SME/lnstructor: Date:

                         -------------                                          ------

Page 7 of 8 PSEG Restricted-Possession Requires Specific Permission from Nuclear Training

JOB PERFORMANCE MEASURE INITIAL CONDITIONS: Unit 1 is operating at 100% power. 11 AFW pump was secured 30 minutes ago after its normally scheduled quarterly surveillance run. INITIATING CUE: You are directed to perform S1 .OP-PT.AF-0002, Auxiliary Feedwater Backleakage. Page 8 of 8 PSEG Restricted-Possession Requires Specific Permission from Nuclear Training

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE STATION: SALEM SYSTEM: Emergency Diesel Generator Start and synchronize an Emergency Diesel Generator ASK NUMBER: 113 0010501 PM NUMBER: 15-01 NRC IP-k L TERNATE PATH: D KIA NUMBER: IMPORTANCE FACTOR: 064 A2.09

                                                                           ~----------!

3.1 3.3

                                                                           --     --

PPLICABILITY: RO SRO EoD ROW STAD sRoW EVALUATION SETTING/METHOD: In Plant I Simulate

REFERENCES:

2A Diesel Generator Operation, S2.0P-SO.DG-0001 (Q)Rev. 39 (checked 8-5-16) OOLS AND EQUIPMENT: None ALIDATED JPM COMPLETION TIME: 20 min IME PERIOD IDENTIFIED FOR TIME CRITICAL STEPS: N/A Developed By: G Gauding Date: 8-5-16 Instructor alidated By: S Bickhart I J Hancock Date: 9-30-16 pproved By: Date: 10/o/c... pproved By: CTUAL JPM COMPLETION TIME: CTUAL TIME CRITICAL COMPLETION TIME: PERFORMED BY: GRADE: DsAT OuNSAT REASON, IF UNSATISFACTORY: EVALUATOR'S SIGNATURE: DATE: PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 1 of 12

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM: EOG TASK: Start and synchronize an Emergency Diesel Generator TASK 113 0010501 NUMBER: INITIAL Unit 2 is operating at 100% power, with no equipment OOS. Engineering has CONDITIONS: requested a loaded run of 2A EOG. INITIATING CUE: The Unit 2 CRS has directed you to locally start and parallel load 2A DIG IAW S2.0P-SO.DG-0001 (Q), Section 5.2. & 5.4 Prerequisites, Precautions and Limitations, and Section 5.1, Diesel Generator Startup Checks have been performed. Successful Completion Criteria:

1. All critical steps completed.
2. All sequential steps completed in order.
3. All time-critical steps completed within allotted time.
4. JPM completed within validated time. Completion time may exceed the validated time if satisfactory progress is being made (and NRC concurrence is obtained).

Task Standard for Successful Completion: Perform S2.0P-SO.DG-0001 Sections 5.2 and 5.4 in correct order and to completion. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 2 of 12

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM: Emergency Diesel Generator NAME:~~~~~~~~~~~~~ TASK: Locally start and load an Emergency Diesel Generator DATE:~~~~~~~~~~~~~ COMMENTS STEP EVAL STEP STANDARD (Required for UNSAT (*Denotes a Critical Step) S/U

  • NO. Evaluation)

Provide marked up copy of S2.0P-SO.DG-0001 2A Diesel Generator Operation 5.2.1 NOTIFY NCO that 2A Diesel Generator is Locates nearest page. to be locally started. Cue: NCO acknowledqes. 5.2.2 CHECK voltage permissive indicator light Points out voltage permissive indicator 2DAE4-LT2, EDG VOLT AGE, on light 2DAE4-LT2, EOG VOLTAGE, on Generator Control Panel is OFF Generator Control Panel. Cue: Liqht is off 5.2.3 CHECK speed permissive indicator light Points out speed permissive indicator 2DAE4-LT3, EOG SPEED, on Generator light 2DAE4-LT3, EOG SPEED, on Control Panel is OFF. Generator Control Panel. Cue: Liqht is off

  • 5.2.4 !E 2A 4KV Vital Bus is currently energized, (Diesel Generator is to be parallel loaded),

THEN: Points out 2A-DF-GCP-1, 2A DIESEL A. PLACE 2A-DF-GCP-1, 2A DIESEL GEN LOADING SW., and simulates GEN LOADING SW in MANUAL rotating to DROOP position. (DROOP). B. ENSURE B-9, GENERATOR LOADING Cue: Annunciator B-9, Generator IN DROOP MODE, is in alarm. loading in Droop Mode annunciates. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 3of12

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM: Emergency Diesel Generator NAME:~~~~~~~~~~~~ TASK: Locally start and load an Emergency Diesel Generator DATE:~~~~~~~~~~~~ COMMENTS STEP EVAL STEP STANDARD (Required for UNSAT (*Denotes a Critical Step) S/U

  • NO. Evaluation)
  • 5.2.5 PLACE 2A-DF-SS, 2A DG STOP/START Points out 2A-DF-SS, 2A DG SWITCH in START. STOP/START SWITCH, and simulates placing in START.

Cue: 2A Diesel is acceleratinq.

  • 5.2.6 !E Diesel Generator Speed is NOT 900 rpm, THEN SET speed to 900 rpm using Cue when Speed indicator is the SPEED CONTROL SWITCH (GS). checked: Speed is 880 rpm.

Points out SPEED CONTROL SWITCH (GS) and simulates turning in RAISE direction. Cue: 2A Diesel Speed is 900 rpm. 5.2.7 !E 2AD1AX6D*, 2A Diesel Generator 125VDC breaker is closed, THEN:

  • CHECK voltage permissive Points out voltage permissive indicator indicator light 2DAE4-LT2, EOG light 2DAE4-LT2, EOG VOLTAGE.

VOLTAGE, on Generator Control Cue: Voltage permissive indicator light Panel is ON. 2DAE4-LT2, EOG VOLTAGE Light is on

  • CHECK speed permissive indicator Points out speed permissive indicator light 2DAE4-LT3, EOG SPEED, on light 2DAE4-LT3, EOG SPEED Generator Control Panel is ON. Cue: Speed permissive indicator light 2DAE4-LT3, EOG SPEED light is on I

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 4of12

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM: Emergency Diesel Generator NAME: DATE:~~~~~~~~~~~~~ TASK: Locally start and load an Emergency Diesel Generator COMMENTS STEP EVAL STEP STANDARD (Required for UNSAT (*Denotes a Critical Step) S/U

  • NO. Evaluation) 5.2.8 IF Field Ground Relay 64/G white indicating light is OFF, AND C-6, GENERATOR FIELD GROUND, is clear, Points out Field Ground Relay 64/G THEN: white indicating light.

A. RESET 64/G relay B. ENSURE 64/G white indicating Cue: Field Ground Relay 64/G white light is illuminated. indicating light is illuminated. 5.2.9 ENSURE 2A Diesel Generator K1 C Field Points out 2A Diesel Generator K1 C Flashing Relay Supervisory Light is OFF. Field Flashing Relay Supervisory Light Cue: 2A Diesel Generator K1 C Field Flashing Relay Supervisory Light is off. 5.2.10 RECORD the following Diesel Generator Points out gages and switches to Start Readings: determine readings. Cue when proper gauge is pointed out: 2VM189 Gen. Volts - 4160 Volts on all 3 phases 2FM186 Gen. Frequency - 60 Hz 2PL6429 LO Hdr. Press - 80 psig 2PL6449 JW Hdr. Press - 45 psig 2PL7209 Air Manifold Press - 0 psig 2TA16524 Gen. Stator Temp - 187° PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 5of12

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM: Emergency Diesel Generator NAME:~~~~~~~~~~~~~ TASK: Locally start and load an Emergency Diesel Generator DATE: ~~~~~~~~~~~~~ COMMENTS STEP EVAL STEP STANDARD (Required for UNSAT (*Denotes a Critical Step) S/U

  • NO. Evaluation) 5.2.11 lE 2A Diesel Generator is to be operated Determines from initiating cue that 2A unloaded for an extended period of EOG is to be parallel loaded.

time(>30 minutes), THEN INITIATE Section 5.7, Diesel Generator Running Checks. 5.2.12 lE Diesel Generator is to be parallel Initiates Section 5.4, Diesel Generator loaded, THEN INITIATE Section 5.4, Parallel Loading. Diesel Generator Parallel Loading. 5.4.1 lE Section 5.1 Diesel Generator Startup Verifies Section 5.1 is complete. Checks, was NOT performed, THEN at 2A DG 4KV cabinet cubicle breaker 2AD1AX60, PLACE selector switch 2A DG SYNC ENABLE in ENABLE. 5.4.2 NOTIFY NCO that 2A EOG is to be Cue: NCO acknowledges 2A DG is to synchronized and loaded locally. be synchronized and loaded locally. 5.4.3 ENSURE 2A-DF-GCP-1, 2A DIESEL GEN Verifies 2A-DF-GCP-1, 2A DIESEL LOADING SW, in MANUAL (DROOP) GEN LOADING SW, is in MANUAL (DROOP) PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 6of12

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM: Emergency Diesel Generator NAME:~~~~~~~~~~~~ TASK: Locally start and load an Emergency Diesel Generator DATE:~~~~~~~~~~~~- COMMENTS STEP EVAL STEP STANDARD (Required for UNSAT (*Denotes a Critical Step) S/U

  • NO. Evaluation)
  • 5.4.4 ADJUST 2A EOG output voltage, as indicated on VOLTMETER-GEN (2VM189) When operator points out 2VM189 to 50 - 100 Volts higher than that of 2A and 2VM190, then Cue: 2VM189 reads 4KV Vital Bus voltage, as indicated by 4150, and 2VM190 reads 4150.

VOLTMETER-BUS (2VM190), using the VOLTAGE CONTROL SWITCH (VCS). Points out VOLTAGE CONTROL SWITCH (VCS) and simulates going to RAISE. Cue: 2VM189 reads 4210, and 2VM190 reads 4150. 5.4.5 ENSURE generator terminal voltage is Points out VOLTMETER SWITCH - present on all 3 phases by rotating GEN (VS-G), simulates rotating through VOLTMETER SWITCH - GEN (VS-G) each position, while observing 2VM189 through each position AND OBSERVING voltmeter 2VM189. Cue: Voltage is present on all three phases. 5.4.6 ENSURE 2A 4KV Vital Bus voltage is Points out VOLTMETER SWITCH - present on all 3 phases by rotating BUS (VS-B), simulates rotating through VOLTMETER SWITCH - BUS (VS-B) each position, while observing 2VM190 through each position AND OBSERVING voltmeter 2VM190. Cue: Voltage is present on all three phases. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 7of12

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM: Emergency Diesel Generator NAME: ~~~~~~~~~~~~- TASK: Locally start and load an Emergency Diesel Generator DATE: ~~~~~~~~~~~~- COMMENTS STEP EVAL STEP STANDARD (Required for UNSAT (*Denotes a Critical Step) S/U

  • NO. Evaluation) 5.4.7 PLACE the following switches in "1-2": Points out VOLTMETER SWITCH -

GEN (VS-G) and VOLTMETER

  • VOLTMETER SWITCH - GEN SWITCH - BUS (VS-B)

(VS-G)

  • VOLTMETER SWITCH - BUS (VS-B) Cue: Switches are in 1-2.

5.4.8 ENSURE 2DAE4-LT2, EOG Voltage Points out 2DAE4-LT2, EOG Voltage indication light is ON. indication light. Cue: 2DAE4-LT2, EOG Voltage indication liqht is on. 5.4.9 ENSURE 2DAE4-LT3, EOG Speed Points out 2DAE4-LT3, EOG Speed indication light is ON. indication light. Cue: 2DAE4-LT2, EOG Voltage indication liaht is on. 5.4.10 SYNCHRONIZE 2A Diesel Generator to 2A 4KV Vital Bus as follows:

  • 5.4.10 PLACE 2A-DF-SYNCH, 2A DG SYNC A. SWITCH (SS) to ON. Points out 2A-DF-SYNCH, 2A DG SYNC SWITCH (SS), and simulates placing in ON position.

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 8of12

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM: Emergency Diesel Generator NAME:~~~~~~~~~~~~ TASK: Locally start and load an Emergency Diesel Generator DATE:~~~~~~~~~~~~- COMMENTS STEP EVAL STEP STANDARD (Required for UNSAT (*Denotes a Critical Step) S/U

  • NO. Evaluation)
  • 5.4.10 ADJUST Diesel speed using the SPEED When operator points out B. CONTROL SWITCH (GS) such that synchroscope, then Cue: Scope is Synchroscope pointer rotates slowly in the going in the slow direction.

FAST (clockwise) direction. Points out SPEED CONTROL SWITCH (GS)and simulates going to RAISE. Cue Synchroscope pointer rotating slowly in the FAST direction. 5.4.10 ENSURE the following four SYNC CHECK Points out four SYNC CHECK RELAY C. RELAY 25 UPPER AND LOWER 25 UPPER AND LOWER VOLTAGE VOLTAGE LIMIT LEDS are ON. LIMIT LEDS.

                    "Upper Voltage Limit" "L OK" "B OK" "Lower Voltage Limit" "LOK" "B OK"               Cue as each LED is located: Light is on.

5.4.10 IF the SYNC CHK RELAY 25 i'.1F OK LED Points out SYNC CHK RELAY 25 i'.1F D. is OFF, THEN ADJUST 2A Diesel OK LED. Generator speed using the SPEED CONTROL SWITCH (GS) until the i'.1F OK Cue Light is on. LED is ON. 5.4.10 ENSURE DG SYNC PERMISSIVE green E. indicating light is ON each time the Cue DG SYNC PERMISSIVE green synchroscope indicator is near 12 o'clock indicating light is ON each time the position ( +/- approximately 3 minutes), synchroscope indicator is near 12 AND is OFF in any other position of the o'clock position ( +/- approximately 3 synchroscope. minutes), AND is OFF in any other position of the svnchroscope. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 9of12

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE SYSTEM: Emergency Diesel Generator NAME:~~~~~~~~~~~~~ TASK: Locally start and load an Emergency Diesel Generator DATE:~~~~~~~~~~~~- COMMENTS STEP EVAL STEP STANDARD (Required for UNSAT (*Denotes a Critical Step) S/U

  • NO. Evaluation)
  • 5.4.10 COORDINATE the following when the F synchroscope is at "12 o'clock" (+zero, -2 minutes):
1. CLOSE 2A-DF-GCP-3 Points out 2A-DF-GCP-3 GENERATOR GENERATOR CIRCUIT CIRCUIT BREAKER SWITCH (BCS)

BREAKER SWITCH (BCS) and simulates taking to the CLOSE position when the synch scope is at 12

2. RAISE 2A Diesel Generator load to o'clock.
                             .:::_ 500KW using SPEED CONTROL SWITCH (GS) to                    Cue 2A Diesel Generator Breaker has prevent tripping the Diesel               closed.

Generator Breaker on reverse power. Points out SPEED CONTROL SWITCH (GS) simulates going to RAISE while observing KW meter. Cue Load is 500 KW. 5.4.10 PLACE 2A-DF-SYNCH, 2A DG SYNCH Points out 2A-DF-SYNCH, 2A DG G SWITCH (SS) to OFF. SYNCH SWITCH (SS), and simulates placing it in OFF position. Cue: JPM is complete. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 10of12

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE JOB PERFORMANCE MEASURE VALIDATION CHECKLIST NOTE: All steps of this checklist should be performed upon initial validation. Prior to JPM usage, revalidate JPM using steps 8 and 11 below. t,, ~1. Task description and number, JPM description and number are identified. e.. ~2. Knowledge and Abilities (KIA) references are included. ~ ~3. Performance location specified. (in-plant, control room, or simulator)

~4. Initial setup conditions are identified.
     ~5.             Initiating and terminating Cues are properly identified .
     ~
      .J ) /6. Task standards identified and verified by SME review.
            /
     "

J JI 7. Critical steps meet the criteria for critical steps and are identified with an asterisk(*). c-r-r") ) 8. Verify the procedure referenced by this JPM matches the most current revision of that procedure: Procedure Rev. _n_ Date !i/3ohlo _ci____f9. Pilot test the JPM:

      /                a. verify Cues both verbal and visual are free of conflict, and
b. ensure performance time is accurate.

____ 10. If the JPM cannot be performed as written with proper responses, then revise the JPM. ____ 11. When JPM is revalidated, SME or Instructor sign and date JPM cover page. SME/lnstruc~~ c,l..., Date: 1 /Jo U'2 SME/lnstruc . Pt :t- Date: q~//6 SME/lnstructor: Date: - - - - - -

                        --------------

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 11 of 12

OPERATOR TRAINING PROGRAM JOB PERFORMANCE MEASURE INITIAL CONDITIONS: Unit 2 is operating at 100% power, with no equipment OOS. Engineering has requested a loaded run of 2A EOG. INITIATING CUE: The Unit 2 CRS has directed you to locally start and parallel load 2A DIG IAW S2.0P-SO.DG-0001 (Q), Section 5.2. & 5.4 Prerequisites, Precautions and Limitations, and Section 5.1, Diesel Generator Startup Checks have been performed. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training Page 12of12

TQ-AA-106-0204 Page 1of27 SIMULATOR EXAMINATION SCENARIO GUIDE SCENARIO TITLE: 15-01 NRC ESG-1 SCENARIO NUMBER: 15-01 NRC ESG-1 EFFECTIVE DATE: See Approval Dates EXPECTED DURATION: 60 minutes REVISION NUMBER: 00 PROGRAM: .___ _.I LO. REQUAL X j INITIAL LICENSE

                               .___ _.I   STA
                               ~-~'OTHER Revision Summary New issue for 15-01 !LOT NRC exam PREPARED BY:                     G Gauding                                  7-18-16 Lead Regulatory Exam Author                          Date
                                                                  --------- -;ri . .

APPROVED BY: (~ Oat APPROVED BY: PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 2 of 27 A. Given the order or indications of a charging system malfunction, perform actions as the nuclear control operator to RESPOND to the loss or malfunction of the charging system in accordance with S2.0P-AB.CVC-0001. B. Given indication of a loss or malfunction of the Charging system DIRECT corrective action for a Charging System malfunction in accordance with S2. OP-AB. CVC-0001. C. Given the indications of a reactor coolant system (RCS) malfunction or leak, perform actions as the nuclear control operator to RESPOND to the malfunctioning accordance with S2.0P-AB.RC-0001. D. Given the indications of a reactor coolant system (RCS) malfunction or leak, DIRECT the response to the malfunction in accordance with S2.0P-AB.RC-0001. E. Given the order or indications of a reactor trip, perform actions as the nuclear control operator to RESPOND to the reactor trip in accordance with 2-EOP-TRIP-1. F. Given indication of a reactor trip, DIRECT the response to the reactor trip in accordance with 2-EOP-TRIP-1. G. Given the order or indications of a safety injection, perform actions as the nuclear control operator to RESPOND to the safety injection in accordance with the approved station procedures. H. Given indication of a safety injection, DIRECT the response to the safety injection in accordance with the approved station procedures. I. Given a safety injection has occurred and inadequate ECCS flow exists, ALIGN equipment to obtain required ECCS flow in accordance with station procedures. J. Given the order or indications of a loss of coolant accident (LOCA), complete actions as the nuclear control operator to PERFORM the immediate response to the LOCA in accordance with the approved station procedures. K. Given indication of a loss of coolant accident (LOCA), DIRECT the immediate response to the LOCA in accordance with the approved station procedures. L. Given conditions that allow SI termination, perform actions as the nuclear control operator to TERMINATE safety injection in accordance with the approved station procedures. M. Given conditions that allow SI termination, DIRECT the response to the safety injection termination in accordance with the approved station procedures.

  • MAJb .::i,E:N

.....".... *v"* ~:. '.\ ..'.. A. Controlling PZR Level Channel fails low B. 20 gpm RCS leak C. 150 gpm SBLOCA D. SBLOCA escalation during SI termination PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 3 of 27 A. The crew will take the watch with the unit at 100% power, MOL. PZR Pressure Channel Ill is selected for Control. B. After the crew assumes the watch, the controlling PZR level channel will fail low. eves Letdown will isolate, and the Master Flow Controller will raise charging flow. The crew will enter S2.0P-AB.CVC-0001, Loss of Charging. The crew will take manual control of charging flow and return PZR level to program. The crew will remove the failed channel from service. The crew will restore normal letdown. The CRS will identify Tech Specs. C. After the PZR level channel failure has been addressed, a 20 gpm RCS leak will occur. The crew will diagnose the leak. The crew will swap to a centrifugal charging pump and a 45 gpm orifice, and estimate the leak rate. The CRS will identify Tech Specs. D. The CRS will determine a unit shutdown is required based on the RCS leak. The crew ill initiate a controlled shutdown. E. After the downpower has commenced, the RCS leak rate will rise to 150 gpm. The crew will diagnose deteriorating primary conditions. When it is determined that PZR level will be unable to be maintained >11 %, the crew will take the CAS action to trip the reactor and initiate Safety Injection. F. The crew will perform plant stabilization and diagnostics in EOP-TRIP-1, Reactor Trip or Safety Injection. The crew will identify no AFW flow. 2A SEC will not reset, and will require deenergization to start 21 AFW pump. The crew will establish at least 22E4 lbm/hr AFW flow. (CT#1) G. The crew will determine there is no High Head ECCS flow, and open the BIT Isolation Valves to establish High Head ECCS Injection (CT#2). H. The crew will transition to EOP-LOCA-1, Loss of Reactor Coolant when directed in TRIP-1. I. The crew will reset Safeguards in LOCA-1, and determine SI termination criteria are met to transition to EOP-TRIP-3, SI Termination. J. The crew will stop all but one Charging pump and align CVCS for normal charging. When evaluating the leak, the SBLOCA will get significantly larger. The crew will diagnose degrading conditions and take the CAS action to start ECCS pumps as necessary, and go to EOP-LOCA-2. K. The scenario will terminate when the transition to LOCA-2 has been made. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 4 of 27 IC-231 PREP FOR TRAINING (i.e.,computerset~oints, 1 procedures',be~el ~gver~';te1gged equipment)

                                          '.    '    '*-           ,            ;<       '   ',       ..   ..    ,    ',

Initial I Description 1 VC1 and VC4 CIT 2 RCPs (SELF CHECK) _ 3 RTBs (SELF CHECK) _ 4 MS167s (SELF CHECK) _ 5 500 KV SWYD (SELF CHECK) _ 6 SGFP Trip (SELF CHECK) _ 7 23 CV PP (SELF CHECK) 8 PZR Pressure Channel Ill selected for Control. g Complete Attachment 2 "Simulator Ready-for-Training/Examination Checklist." Note: Tables with blue headings may be populated by external program, do not change column name without consulting Simulator Support group PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 5 of 27 ET# Description 1 1 EVENT-ACTION: I COMMAND: PURPOSE: SELF- Description Delay Initial Ramp Trigger Severity CHECK Time Value Time 01 PR0017A PZR LEVEL CH I LT459 FAILS H/L NIA N/A RT-1 0 RC0002 RCS LEAK INTO CONTAINMENT (equiv to 0-02 N/A N/A ~J/A RT-3 20 4 inches 03 RP0342 2SJ12 FAILS TO AUTO OPEN ON SEC N/A N/A N/A N/A 04 RP0343 2SJ13 FAILS TO AUTO OPEN ON SEC NIA NIA N/A N/A 05 RP318E1 Aux Feed Pum 21 Fails to Start on SEC NIA NIA NIA N/A 06 RP318E2 Aux Feed Pump 22 Fails to Start on SEC NIA NIA NIA N/A AF0353A 21 AFP FAILURE TO AUTO START ON ANY 07 NIA NIA NIA N/A (ALL SIGNALS AF0353B 22 AFP FAILURE TO AUTO START ON ANY 08 N/A NIA NIA NIA ALL SIGNALS SELF- Description Delay Initial Ramp Trigger Condition CHECK Time Value Time 01 DG01 D DE ENERGIZE "A" SEC CABINET N/A N/A NIA RT-9 YES 02 SP01A1 Prevailin Wind S eed N/A N/A NIA N/A 10 03 SP01A2 Prevailin Wind Direction NIA N/A N/A NIA 160 04 MS05A 21 MS45 21 STM GEN STM SUP-23 AFP NIA NIA N/A NIA 0 05 MS06A 23MS45 23 STM GEN STM SUP-23 AFP NIA N/;\ N/A NIA 0 SELF-CHECK 01 Description CB09 A DI KCB09ASE 2A SFGD EMER OPR-EMERG Delay Time NIA Initial Value N/A Ramp Time i'JIA Trigger i'J/A Condition/ Sem;ty j OFF LOADING RESET PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 6 of 27 Description 1. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 7 of 27 A. State shift job assignments. B. Hold a shift briefing, detailing instruction to the shift: (provide crew members a copy of the shift turnover sheet). C. Inform the crew "The simulator is running. You may commence panel walkdowns at this time. CRS please inform me when your crew is ready to assume the shift". D. Allow sufficient time for panel walk-downs. When informed by the CRS that the crew is ready to assume the shift, ensure the simulator is cleared of unauthorized personnel. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 8 of 27 Jfv~fUatpW1nstr:dctqr Activily ,@: ... ' ;if:'ex{.tlctecJ'~,ia{lt/Sfodel)t:Rlsponse; J::SBT

                                                  .
1. Controlling PZR Level Channel Fails LOW
  ,simulafor Oper:at~r: Insert RT*1
      • on direction from L.ead Evaluator.
 .MALF~PR0017APZRtVLCH I
   ,(LT459)FAH.:5H/L **' .

Severity: 0 .

  • RO reports unexpected OHA E-36, PZR HTR OFF LVL LO.

RO diagnoses controlling PZR level channel failure. RO may request permission to place the Master Flow Controller in manual prior to direction in AB.eve to do so. CRS enters 82.0P-AB.CVC-0001, Loss of Charging. CRS directs initiation of Attachment 1 CAS. RO reports charging pumps are running, and no indication of cavitation. RO reports PZR level channel I has failed low. If not previously performed, RO takes manual control of charging and maintains PZR level within band assigned by CRS. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 9 of 27 .* ',ri<e;ta1uator/lnstfucli

    *,' '1i-;'. )~J' ;+/-}*.':. I .?:.:'.,~* -. '

exriected, i>1ant/s~lltl~nt:R~spO,ose,&:, . .SBTi

                                                                                                     ~.

RO selects operable channel for Control, Alarm, and Recorders. RO restores PZR heaters to pre-event condition. RO announces OHA E-20 PZR HTR ON LVL HI as expected when it annunciates due to no letdown with charging flow established. PO restores letdown by:

                                                          - Ensuring open 2CV7
                                                          - Placing 2CV18 in manual and closing, then opening until close PB extinguishes.
                                                          - Opening 2CV2 and 2CV277, then placing both in auto.
                                                          - Ensuring charging flow is 90 gpm.
                                                          - Opening a 75 gpm orifice isolation valve while adjusting 2CV18 to control letdown pressure -300 psig.
                                                          - Placing 2CV18 in auto.

RO returns Master Flow Controller to auto when PZR level returns to proqram. CRS contacts IC for assistance in removing channel from service. CRS enter LCO 3.3.1.1 action 6. Proceed to next event after Tech Spec call at direction from Lead evaluator. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 10 of 27 eva1u*at0rlfrndruclor Activity ~.,*'

  ~?Jf"': ,,.,! ~:,~.?'-- '.*~,f,;;\ !~;,~'**+_ ~~-:;::( ,~?;~fe:'~,. ;{('f,(<<:e i:r""'~*
                                                                                                   'F!xpeq~ed:(P~~nt/Student.Re'ipdnse
                                                                                                     , ;~:c~~

1

                                                                                                              . ,,,,,, **____,. *"*---- *--, ;,*.*.*' *'"t ,_, '""""'""
                                                                                                                                                                        ~ssf,'.

LOG't

                                                                                                                                                                                &c~,M~"t:>~;r' . 11t"
3. 20 gpm RCS leak Simulator Operator: Insert RT-3 orfdirection from Lead Evaluator
  • MALF: RC0002 ,.;.. ~cs Le~k into containment..
  • Final Value: 20 gpm*

RO reports that charging flow is rising (if MFC has been returned to auto) and PZR level is lowering slowly. Crew reports reading on 2R11A containment radiation monitor is rising. RO reports unexpected OHA C-2 CNTMT SUMP PMP START when it occurs. CRS enters S2. OP-AB. RC-0001, Reactor Coolant System Leak. CRS directs initiation of Attachment 1 CAS. RO reports RCS temperature > 350°F in Mode 1. RO reports PZR level is lowering. Note: PZR level is above program, and charging flow will be lower than normal to reduce PZR level. If charging flow is raised here to stabilize level, then step to place a centrifugal charging pump in PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 11of27

    .EvaluatofJl~itrii(;tf>riActivitY                                        * * . '.l:xJ)~ctiJ.~f J'lafntJStuderlt Rispori~~ ,,,-,c
                                                                                                                                     .li'SBT        <fomment:.;~¥<1,
                                                                                                                                                    ~kr "'~~( /~~/
 ,.'A,*, )~ '- C), i'.' ,} /"!~, *,,0/?f',, ~)/'. >~>j/ t ,* '- )7           ,;;#  ,    4 ',, .**~' "'"'- "     '  '.<<*'*
                                                                                                                                                       ,,"J,,

service may not be performed. CRS enters S2.0P-AB.RAD-0001, Abnormal Radiation after OHA A-6 unexpected annunciation. RO swaps to a centrifugal charging pump IAW Step 3.14, and raises charging flow to stabilize PZR level. PO reduces letdown flow to minimum by opening 2CV3, maintaining letdown pressure

                                                                          -300 psig with 2CV18 in manual, then closing the open 75 gpm orifice and returning 2CV18 to auto.

RO stabilizes PZR level and estimates leak rate. CRS initiates S2.0P-ST.RC-0008, Reactor Coolant System Water Inventory Balance. CRS contacts Rad Pro for recommendation on CFCU operation. Role Play: If contacted state Rad Pro recommends placing 2 CFCU's in Low Speed and 2 CFCU's in High Speed. PO places 2 CFCU's in Low Speed and 2 CFCU's in High Speed. CRS initiates actions to locate and isolate the leak IAW Attachment 2. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 12 of 27

   .*.;~~E'laluc:ilor/lh$ltuetoJ;~£Act1VitY
   ,v~. A~" ~ .. i :._,.-~, ~ ~, ~,1tr:* J' , ,'§' . "~,AL
                                                                         *.;'lt,
                                                               ' ~ ,, ' ;.~;*
                                                                                     ~ Exi>&cted*Ptant1stuaenl
                                                                                         ~;J, .; wj. iJt            ResPtlnse*
                                                                                                               , __A[.!*, : >~t<*'
                                                                                                                                   .,,,"s***a**Tc * * * *
                                                                                                                                    .*. *a_,51(           !rco'l)r~J"lr:;:* ***

... CRS enters TSAS 3.4.7.2.b action b for RCS leakage, and 3.6.1.4 for containment pressure if it has reached 0.3 psiq. Role Play: After RCS leakage Tech Spec has been identified, if CRS does not initiate a power reduction to bring the unit offline, call Control Room as Operations Director and instruct the CRS to initiate a 30% per hour load reduction to 20% in preparation for taking Unit 2 offline to investigate and repair the RCS leak. CRS briefs power reduction. RO initiates boration. PO initiates turbine load reduction at 30% per hour. CRS may enter S2.0P-AB.LOAD-0001 Rapid Load Reduction to perform the power reduction. Proceed to next event on direction from Lead Evaluator.

3. SBLOCA Simulator Operator: .MODIFY MALF RC0002 from 20 to 150 on direction from Lead Evaluator.

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 13 of 27 eval,uatb.rtlnstructor ActivitY;'* . Expict~CI PlantlsfodeijfRespoJ\sef"" '/\'$'81 Commeilf *

                                                             ..                                                      . *7*.  .."t*

. .* i'. ... ****, F ',.\.,~ J > 37' * ;1* LOG* *i RO reports PZR level trending down and adjusts charging flow to maintain PZR level. RO reports PZR level will not be able to be maintained >17%. CRS directs Rx trip and Safety Injection RO trips the reactor and confirms the reactor trip. RO initiates Safety Injection. RO continues Immediate Actions of TRIP-1

                                                - Trips the Main Turbine
                                                - Reports at least one 4KV vital bus energized.
                                                - Reports SI initiated.

CRS and RO verify performance of immediate actions.

4. AFW fails to initiate PO reports SEC loading is not complete for 2A and 28 vital buses, 21 and 22 AFW pumps have failed to start. Reports 23 AFW pump started but is not providinq any AFW flow.

RO blocks 2A and 28 SECs. PO resets 2A and 28 SECs. PO reports 2A SEC will not reset. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 14 of 27

*<r .. evafo~lotll~stru~o~.A,ctijitf'              5~:';expected.:P1a11tf5tudent Resp<>n$e,,
                                                     '"Y"  .      ,,.,     '*" ,, . ' .
                                                                                                   .,;,sBT1;:S
  • corl)ment,~:,
                                               .                                                      ---
                                                                                              >
,;',-  :' .*. .. *. ... ...  :~

CRS dispatches operator to deenergize 2A SEC. Simulator Operator: 2 minutes

~fter being dispatched, jnsert RT-9 to deenergize 2A SEC:

RO starts 22 AFW pump. CT#1 (cr.:s) Establish atleast

  • 22E4 lbl11/hr AFWflowto the *
  • SG's prior to a transition to FRHS*1 being required. *
                                         .....
 '>\'

SAT UNSAT

                                    '

PO reports AFW pump status, and starts 21 AFW pump when 2A SEC is deenergized. PO reports not all valve groups in Table B are in safequards position. PO reports 2SJ 12 and 2SJ 13 BIT isolation valves have not opened. RO opens 2SJ12 and 2SJ13 and reports BIT flow is established. CT#2 {CT*6) Establish flow from 'atleastone charging pump prior to transition out ofTRIP-1. SAT UNSAT PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 15 of 27

           ~-         ~                                                                                                              7 Commenf"   *
 ..,, ", ~

JS;.. iJ! ~t~fii y;:: .* ,cklJ:ii, ft :fd;. ;~~jt r* ... **** <*

                                                                                  ;)  t:cf<'      t**    Y,'.;Jw .:0:. LOGt I

RO reports 21 and 22CA330s are shut. RO reports containment pressure has remained <15 psig. PO reports no high steam flow condition. CRS directs implementation of the ECG. PO reports all 4KV vital buses enerqized. RO reports CAV in AP mode. RO reports 2 switchgear supply and one exhaust fan are running. RO reports 2 or more CCW pumps running. RO reports RCS not aligned for Cold Leg Recirc. RO reports charging flow is at least 100 gpm on SI systems charc::iinq flow meter. RO reports RCS pressure is not <1540 psiq. PO reports total AFW flow is 22E4 lbm/hr or 9% level in at least one SG NR level, then maintains 19-33% level. RO reports all RCPs running, and RCS temperature is stable at or trending to 547°F. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 16 of 27

'f,Evaluator!lnst~ctor Acdvlfy                   " 7~:~ Expebted, Plaht/Student RespoHse  **      SBT                  . r Comment .\.Bn* ....

i~;,:cr~ :>}".\~*~(,,.c ,,.,, RO reports both RTBs are open. RO reports both PZR PORVs are shut with their Block Valves open. RO reports all RCPs in service and PZR spray operating as expected for current plant conditions. RO reports RCS pressure >1350 psig and maintains seal injection flow to all RCPs. PO reports no indication of faulted SGs. PO/RO report no indications of a steam generator tube rupture. RO reports radiation monitor channel status in Table F. PO reports 2 or more channels rising or in warninq or alarm. CRS transitions to EOP-LOCA-1, Loss of Reactor Coolant. Note: CFST monitoring will commence after the transition out of TRI P-1. STA will report to the control room 10 minutes after being paged. PO reports no faulted SGs. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 17 of 27 .,.~e:valuatCff!(~~tructorAcUvify 1

                                                    'Sxpd~ted 'f>1aflt/StuBent Respo*nse ".ii'*IV' ;.,sat               ,,vi "Cofumerii.'7 r,, *
                                                                                                                      '{7~>
'h AT~:!'~ ,~,**'!~J:JF;~;~;,,,

PO reports total AFW flow is 22E4 lbm/hr or 9% level in at least one SG NR level, then maintains 19-33% level. PO reports no ruptured SGs. RO resets SI, Phase A, and Phase B isolations. RO opens 21 and 22CA330s. PO resets 2C SEC, and reports 230V control centers reset. RO resets SGBD Sample Isolation Bypass and opens 21-24SS94s. CRS directs chemistry to sample SGs for activity and boron. RO reports PORVs are shut with Block valves open. RO reports subcoolinq > 0°F. PO reports AFW flow >22E4 lbm/hr or SG NR level >9%. RO reports RCS pressure is stable or risinq. RO reports PZR level >11 %. CRS transitions to EOP-TRIP-3, SI Termination. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 18 of 27 Evaiuator/lnstfocfor A'ctivitY . . E;xp~Cfe(ltPlant/StuCle*nt Resp(mse~"": SBT comment *,*M*\ 5

                                                                                                                                  £ *, *
   '1 .il'0'lft , ,, ';~ ~;*   i2t*'*5              ' v";>'..*;     '  .~J'.'.)RQ{)t/"'- "'

LOG RO resets SI, Phase A, and Phase B isolations if not previously reset. RO opens 21 and 22CA330s if not previously performed. RO reports spray valves are not failed open. PO resets 2C SEC and reports 230V control centers reset if not previously performed. RO stops all but one charqinq pump. RO reports RCS pressure is stable or risinq. RO reports charging pump suction is aligned to the RWST. RO opens 2CV139 and 2CV140 if shut. RO shuts BIT isolation valves 2SJ4, 2SJ5, 2SJ12, 2SJ13. RO shuts 2CV55 Charqinq Flow Control valve. RO opens 2CV68 and 2CV69 Charging Discharqe valves. Simulator Operator: MODIFY MALF RC0002 from . 150 to 2000 when 2CV68 and 2CV69 are ooen. RO adjusts 2CV55 to maintain PZR level PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 19 of 27

  Evaluatortl'nstruct.6r
      ',; /,, :. .
             ~:     )~{' ,}:>*:**

Activity::'

                                      ~:*.;',
                                                           "!1ft1c.pected* Plant/Student' Response ..

A". ~ T:3*;. SB ,.~§~~'.. > Commen'f *)J&:J1!:~r *.

                                                                                                          ..
                                                   .,,,:;;  1n~*7 '*     .s  >d'.>: '*
                                                                                        '.~* fr,: . :t' :    .*. L;\;l\.;J ..   .j
                                                     >25%.

RO reports PZR level is not stable or risinq. PO reports no faulted SGs. RO opens BIT isolation valves 2SJ4,5, 12, 13, and shuts normal charging line isolation valves 2CV68 and 69. CRS goes to EOP-LOCA-2, Post LOCA Cooldown and Depressurization. Terminate scenario on direction from Lead Evaluator after the transition to LOCA-2 is made. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 20 of 27 A. Alarm Response Procedures (Various) B. Technical Specifications C. Emergency Plan (ECG) D. OP-AA-101-111-1003, Use of Procedures E. S2.0P-10.ZZ-0004, Power Operation F. S2.0P-AB.CVC-0001, Loss of Charging G. S2.0P-AB.RC-0001, Reactor Coolant System Leak H. 2-EOP-TRIP-1, Reactor Trip or Safety Injection I. 2-EOP-TRIP-3, Safety Injection Termination J. 2-EOP-LOCA-1, Loss of Reactor Coolant K. 2-EOP-LOCA-2, Post LOCA Cooldown and Depressurization PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 21of27 ATTACHMENT 1 UNIT TWO PLANT STATUS TODAY MODE: 1 POWER: 100% RCS BORON: 857 MWe 1220 SHUTDOWN SAFETY SYSTEM STATUS (5, 6 & DEFUELED): NA REACTIVITY PARAMETERS MOST LIMITING LCO AND DATEfflME OF EXPIRATION: EVOLUTIONS/PROCEDURES/SURVEILLANCES IN PROGRESS: ABNORMAL PLANT CONFIGURATIONS: PZR Pressure Channel Ill is selected for Control CONTROL ROOM: Unit 1 and Hope Creek at 100% power. No penalty minutes in the last 24 hrs. PRIMARY: SECONDARY: RADWASTE: No discharges in progress CIRCULATING WATER/SERVICE WATER: PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 22 of 27 ATTACHMENT 2 SIMULATOR READY FOR TRAINING CHECKLIST

1. Verify simulator is in "TRAIN" Load
2. Simulator is in RUN
3. Overhead Annunciator Horns ON
4. All required computer terminals in operation
5. Simulator clocks synchronized
6. All tagged equipment properly secured and documented
7. TSAS Status Board up-to-date
8. Shift manning sheet available
9. Procedures in progress open and signed-off to proper step
10. All OHA lamps operating (OHA Test) and burned out lamps replaced
11. Required chart recorders advanced and ON (proper paper installed)
12. All printers have adequate paper AND functional ribbon
13. Required procedures clean
14. Multiple color procedure pens available
15. Required keys available
16. Simulator cleared of unauthorized material/personnel
17. All charts advanced to clean traces and chart recorders are on.
18. Rod step counters correct (channel check) and reset as necessary
19. Exam security set for simulator
20. Ensure a current RCS Leak Rate Worksheet is placed by Aux Alarm Typewriter with Baseline Data filled out
21. Shift logs available if required
22. Recording Media available (if applicable)
23. Ensure ECG classification is correct
24. Reference verification performed with required documents available
25. Verify phones disconnected from plant after drill.
26. Verify EGC paperwork is marked "Training Use Only" and is current revision.
27. Ensure sufficient copies of ECG paperwork are available.

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 23 of 27 ATTACHMENT 3 CRITICAL TASK METHODOLOGY In reviewing each proposed CT, the examination team assesses the task to ensure, that it is essential to safety. A task is essential to safety if, in the judgment of the examination team, the improper performance or omission of this task by a licensee will result in direct adverse consequences or in significant degradation in the mitigative capability of the plant. The examination team determines if an automatically actuated plant system would have been required to mitigate the consequences of an individual's incorrect performance. If incorrect performance of a task by an individual necessitates the crew taking compensatory action that would complicate the event mitigation strategy, the task is safety significant. I. Examples of CTs involving essential safety actions include those for which operation or correct performance prevents ...

  • degradation of any barrier to fission product release
  • degraded emergency core cooling system (ECCS) or emergency power capacity
  • a violation of a safety limit
  • a violation of the facility license condition
  • incorrect reactivity control (such as failure to initiate Emergency Boration or Standby Liquid Control, or manually insert control rods)
  • a significant reduction of safety margin beyond that irreparably introduced by the scenario II. Examples of CTs involving essential safety actions include those for which a crew demonstrates the ability to ...
  • effectively direct or manipulate engineered safety feature (ESF) controls that would prevent any condition described in the previous paragraph.
  • recognize a failure or an incorrect automatic actuation of an ESF system or component.
  • take one or more actions that would prevent a challenge to plant safety.
  • prevent inappropriate actions that create a challenge to plant safety (such as an unintentional Reactor Protection System (RPS) or ESF actuation.

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 24 of 27 SCENARIO IDENTIFIER: 15-01 ILOT NRC ESG-1 REVIEWER: C Recchione Initials Qualitative Attributes CR 1. The scenario has clearly stated objectives in the scenario. CR 2. The initial conditions are realistic, in that some equipment and/or instrumentation may be out of service, but it does not cue crew into expected events. CR 3. The scenario consists mostly of related events. CR 4. Each event description consists of:

  • the point in the scenario when it is to be initiated
  • the malfunction(s) that are entered to initiate the event
  • the symptoms/cues that will be visible to the crew
  • the expected operator actions (by shift position)
  • the event termination point CR 5. No more than one non-mechanistic failure (e.g., pipe break) is incorporated into the scenario without a credible preceding incident such as a seismic event.

CR 6. The events are valid with regard to physics and thermodynamics. CR 7. Sequencing/timing of events is reasonable, and allows for the examination team to obtain complete evaluation results commensurate with the scenario objectives. CR 8. The simulator modeling is not altered. CR 9. All crew competencies can be evaluated. CR 10. The scenario has been validated. CR 11. If the sampling plan indicates that the scenario was used for training during the requalification cycle, evaluate the need to modify or replace the scenario. CR 12. ESG-PSA Evaluation Form is completed for the scenario at the applicable facility. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 25 of 27 Initial Quantitative Attributes (as per ES-301-4, and ES-301 Section 0.5.d) GG 3 Malfunctions after EOP entry: 1-2 GG 2 Abnormal Events: 2-4 GG 1 Major Transients: 1-2 GG 2 EOPs entered/requiring substantive actions: 1-2 GG 0 EOP contingencies requiring substantive actions: 0-2 GG 2 EOP based Critical tasks: 2-3 COMMENTS: PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 26 of 27 15-01 NRC ESG-1 CT#1 (CT-4) Establish the minimum required feed flow prior to a transition to FRHS-1 being required. Basis: Failure to establish the required minimum feed flow rate under the postulated plant conditions, results in "adverse consequence(s) or significant degradation in the mitigative capability of the plant." Failure to perform the critical task represents a "demonstrated inability of the crew to: Take an action or combination of actions that would prevent a challenge to plant safety Recognize a failure I incorrect auto actuation of an ESF system or component." CT#2 (CT-6) Establish flow from at least one high-head ECCS pump before transition out of TRIP-1. Basis: Failure to manually start at least one Charging pump under the postulated conditions constitutes misoperation or incorrect crew performance in which the crew does not prevent "degraded emergency core cooling system (ECCS) ... capacity." In this case, at least one Charging/SI pump (high-head SI pump for LP plants) can be manually started from the control room. Therefore, failure to manually start a Charging/SI pump (high-head SI pump for LP plants) also represents a failure by the crew to "demonstrate the following abilities: Effectively direct or manipulate engineered safety feature (ESF) controls that would prevent a significant reduction of safety margin beyond that irreparably introduced by the scenario Recognize a failure or an incorrect automatic actuation of an ESF system or component" Additionally, under the postulated plant conditions, failure to manually start a Charging/SI pump (high-head SI pump for LP plants) (when it is possible to do so) is a "violation of the facility license condition." Note to Evaluators: CT numbers in parentheses are the corresponding Westinghouse ERG Rev. 2- based Critical Task procedure WCAP-17711-NP PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 27 of 27

                                      '*

ATTACHMENT6:

                                             ...         '       .       '

ESG-PRA ~ELATIONSHIP: E~A~UATION EVENTS LEADING TO CORE DAMAGE Y/N Event Y/N Event N TRANSIENTS with PCS Unavailable N Loss of Service Water N Steam Generator Tube Rupture N Loss ofCCW N Loss of Offsite Power N Loss of Control Air N Loss of Switchgear and Pen Area Ventilation N Station Black Out y LOCA COMPONENT/TRAIN/SYSTEM UNAVAILABILITY THAT INCREASES CORE DAMAGE FREQUENCY Y/N COMPONENT, SYSTEM, OR TRAIN Y/N COMPONENT, SYSTEM, OR TO~lll.I N Containment Sump Strainers N Gas Turbine N SSWS Valves to Turbine Generator Area N Any Diesel Generator N RHR Suction Line valves from Hot Leg y Auxiliary Feed Pump N CVCS Letdown line Control and Isolation Valves N SBO Air Compressor OPERATOR ACTIONS IMPORTANT IN PREVENTING CORE DAMAGE Y/N OPERATOR ACTION N Restore AC power during SBO N Connect to gas turbine N Trip Reactor and RCPs after loss of component cooling system N Re-align RHR system for re-circulation N Un-isolate the available CCW Heat Exchanger N Isolate the CVCS letdown path and transfer charging suction to RWST N Cooldown the RCS and depressurize the system N Isolate the affected Steam Generator that has the tube rupture(s) N Early depressurize the RCS N Initiate feed and bleed Complete this evaluation form for each ESG.

TQ-AA-106-0204 Page 1 of 32 SIMULATOR EXAMINATION SCENARIO GUIDE SCENARIO TITLE: 15-01 NRC ESG-2 SCENARIO NUMBER: 15-01 NRC ESG-2 EFFECTIVE DATE: See Approval Dates EXPECTED DURATION: 60 minutes REVISION NUMBER: 00 PROGRAM: ,____ ___,\ LO. REQUAL X \ INITIAL LICENSE

                               ..________,\ STA
                               ~-~'OTHER Revision Summary New issue for 15-01 !LOT NRC exam PREPARED BY:                      G Gauding                               8-3-16 Lead Regulatory Exam Author                        Date APPROVED BY:                                      JVivFl raining Manager

("~?late 4 APPROVED BY:

                        ~  aClHty  Repre    ~ .i.f/LA.ifij atlve

{J)/,, IL~

                                                                     'Tdate PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 2 of 32

TQ-AA-106-0204 Page 3 of 32 A. Given a loss of a heater drain pump or condensate pump, take corrective action IAW S2.0P-AB.CN-0001. B. Given the order or indications of a feedwater or condensate system malfunction, perform actions as the nuclear control operator to RESPOND to the malfunction in accordance with S2.0P-AB.CN-0001. C. Given indication of a feedwater or condensate system malfunction, DIRECT the response to the malfunction in accordance with S2.0P-AB.CN-0001. D. Given a steam generator tube leak, take corrective action, IAW S2.0P-AB.SG-0001. E. Given the order or indications of a steam generator tube leak (SGTL), perform actions as the nuclear control operator to RESPOND to the tube leak in accordance with S1/S2.0P-AB.SG-0001. F. Given the order or indications of a steam generator tube leak (SGTL), DIRECT the response to the tube leak, in accordance with S2.0P-AB.SG-0001. G. Given the order or indications of a reactor trip, perform actions as the nuclear control operator to RESPOND to the reactor trip in accordance with 2-EOP-TRIP-1. H. Given indication of a reactor trip, DIRECT the response to the reactor trip in accordance with 2-EOP-TRIP-1. I. Given the order or indications of a safety injection, perform actions as the nuclear control operator to RESPOND to the safety injection in accordance with the approved station procedures. J. Given indication of a safety injection, DIRECT the response to the safety injection in accordance with the approved station procedures. K. Given the order or indications of a steam generator tube rupture (SGTR), perform actions as the nuclear control operator to RESPOND to the tube rupture in accordance with the approved station procedures. L. Given indication of a steam generator tube rupture (SGTR), DIRECT the response to the SGTR in accordance with the approved station procedures. A. 2C EDG Pre-lube pump failure (TS) B. 23 Condensate pump trip /Power Reduction C. 21 SGTL I 21 SGTR D. Loss of Spray during RCS depressurization E. Stuck open PZR PORV during RCS depressurization PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 4 of 32 A. The crew will take the watch with the unit at 89.4% power, BOL. Power was reduced last shift in preparation for performing Main Turbine Valve testing later this shift. 2C EOG Jacket Water heater failed last shift. Condensate Polisher is in service. B. After the crew assumes the watch, the 2C EOG Pre-lube pump will fail. The CRS will identify 2C EOG is now inoperable, and enter the appropriate LCO. The CRS will initiate actions to ensure S2.0P-ST.500-0001, Electrical Power Systems AC Sources Alignment is performed within one hour. C. After the EOG failure has been addressed, 23 Condensate pump will trip. The crew will enter S2.0P-AB.CN-0001, Main Feedwater I Condensate System Abnormality, and perform actions to bypass the polisher and feedwater heaters strings as required to maintain SGFP suction pressure. D. The crew will perform a power reduction to~ 85% power and ensure SGFP suction pressure remains above 320 psig. E. During the power reduction, a SGTL will occur on 21 SG. The crew will enter S2.0P-AB.SG-0001, Steam Generator Tube Leak. The crew will perform actions to minimize the spread of secondary contamination and minimize the potential for steam release from the affected SG. The crew will isolate the steam supply to 23 AFW pump from 21 SG, and the CRS will identify 23 AFW is inoperable and enter the appropriate LCO. F. After the AFW pump LCO is identified, the SG tube will rupture. The crew will identify the SGTR, and initiate a Rx trip and Safety Injection based on the uncontrolled rise in 21 SG NR or WR level. G. The crew will perform plant stabilization and diagnostics in EOP-TRIP-1, Reactor Trip or Safety Injection. 21 AFW pump will trip shortly after starting. The crew will isolate AFW flow to and steam flow from 21 SG. (CT-1 ). H. The crew will transition to EOP-SGTR-1, Steam Generator Tube Rupture to address the tube rupture. The crew will perform a cooldown to target temperature and demonstrate the ability to maintain RCS temperature< Target temperature (CT-2). The crew will initiate a RCS depressurization. During the depressurization the RCP providing driving head for Spray flow will trip. The crew will open a PZR PORV to continue the depressurization. If 2PR1 is the selected PORV, it will not open, and 2PR2 will be used. I. The PZR PORV opened to depressurize the RCS will fail to shut when demanded after the depressurization is complete. The crew will attempt to terminate the depressurization by closing the PORV Block valve, which will not shut. J. The scenario will be terminated after the CRS transitions to EOP-SGTR-3, SGTR with LOCA - Subcooled Recovery, to address the loss of RCS pressure with the stuck open PORV. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 5 of 32 IC-232

                                                                    ,,

PREP FOR<TRAINl~G (i.e,~ computer setpoint~~,proc~dure!), l:>~zel C()V~~s ,tagged equipment) Initial I Description 1 VC1 and VC4 CIT 2 RCPs (SELF CHECK) _ 3 RTBs (SELF CHECK) _ 4 MS167s (SELF CHECK) _ 5 500 KV SWYD (SELF CHECK) _ 6 SGFP Trip (SELF CHECK) _ 7 23 CV PP (SELF CHECK) 8 Complete Attachment 2 "Simulator Ready-for-Training/Examination Checklist." Note: Tables with blue headings may be populated by external program, do not change column name without consulting Simulator Support group PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page.6 of 32 Description

             - -~*        - -                                               -        --

EVENT ACTION: MONP254 <10. //CONTROL BANK C GROUP POSITION 1 COMMAND: PURPOSE: <update as needed>

                                                    -              -      -

EVENT ACTION: KB202LCI //2PR7 RELIEF VALVE-22 STOP VALVE 3 COMMAND: PURPOSE: <update as needed> SELF- Description Delay Initial Ramp Trigger Severity CHECK Time Value Time SER POINT AN0266 SER 266 FAILS - :J20 2C DIESEL 01 N/A N/A N/A RT-1 FAILS/OVRD GENERATOR URGENT TROUBLE TOON 02 CN0117C 23 CONDENSATE PUMP TRIP N/A NIA NIA RT-3 03 SG0078A 21 STEAM GENERATOR TUBE RUPTURE N/A NIA N/A RT-5 5 AAS POINT 04 AN3735 AAS 735 FAILS - :21 TGA SUMP LEVEL HIGH 00:03:00 N/A N/A RT-11 FAILS/OVRD TOON AAS POINT 05 AN3736 AAS 736 FAILS - :22 TGA SUMP LEVEL HIGH 00:03:10 N/A NIA RT-11 FAILS/OVRD TOON AAS POINT 06 AN3737 AAS 737 FAILS - :23 TGA SUMP LEVEL HIGH 00:03:20 N/A N/A RT-11 FAILS/OVRD TOON AAS POINT 07 AN3738 AAS 738 FAILS - :24 TGA SUMP LEVEL HIGH 00:03:30 N/A N/A RT-11 FAILS/OVRD TOON AAS POINT 08 AN3739 AAS 739 FAILS - :25 TGA SUMP LEVEL HIGH 00:03:50 N/A NIA RT-11 FAILS/OVRD TOON 09 AF0181A 21 AUX FEEDWATER PUMP TRIP 00:04:00 NIA N/A ET-1 10 VL0297 2PR1 Fails to Position 0-100%) NIA N/A N/A N/A 0 11 VL0298 2PR2 Fails to Position 0-100% NIA N/A N/A RT-13 100 12 RC0003C 23 RC PUMP ELECTRICAL TRIP N/A NIA NIA RT-7 13 RC0003A 21 RC PUMP ELECTRICAL TRIP NIA NIA N/A RT-9 14 VL0123 2PR7 Fails to Position ( 0-100%) NIA NIA NIA ET-3 90 15 CV0035 CHRG MASTER FLO CNTRLR FAILS H/L N/A NIA t'11A RT-15 26 SELF- Description Delay Initial Ramp Trigger Condition CHECK Time Value Time 01 SP01A1 Prevailing Wind Speed NIA NIA NIA NIA 10 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 7 of 32 02 GP01A2 Prevailing Wind Direction NIA N/A NIA SELF- Description Delay Initial Ramp Trigger Condition/ CHECK Time Value Time Severity C201 A LO QC201AY3 2C DIESEL GEN-TROUBLE 01 NIA NIA NIA ON ALARM Description

1. None PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 8 of 32 \j\1,i '"'--

   -*<gq A. State shift job assignments.

B. Hold a shift briefing, detailing instruction to the shift: (provide crew members a copy of the shift turnover sheet). C. Inform the crew "The simulator is running. You may commence panel walkdowns at this time. CRS please inform me when your crew is ready to assume the shift". D. Allow sufficient time for panel walk-downs. When informed by the CRS that the crew is ready to assume the shift, ensure the simulator is cleared of unauthorized personnel. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 9 of 32

 ,.lEva'u~tptr11il'structor Activ'lty ...                                             {~:~'Exp,~te~"'plawnt/Stu~1enf R~!e#fise
  • comment****
.,Y':, *,     )~i j c:~,f,~4 > ~', ~?:/,'>;*~, ;',:;,~L,~, ~= ~, . , ", d, ,_.~,
                                                                                       ! ;. ;,HJ 7,r,. i1# 1. . ;tt .> . ; ;;,1lN: *.. . *.
1. 2C EOG Pre-Lube pump failure Simulator Operator: Insert RT-1 oh direction from Lead.Evaluator.

.MALF: lAN0266 SER,266 Fails;... J20 2C~DlESEL GENERATOR:: URGENT TROUBLE PO announces unexpected OHA J-20, 2C DG URGENT TRBL. The crew refers to the ARP and dispatches an operator to investiaate. Role play: 2 minutes after being dispatched call control room and report 2C EOG Alarm Window A-7 PRE-LUBE PUMP FAILURE is in alarm. You have checked the Pre-lube pump and it is NOT running. The Pre-lube pump breaker remains shut. CRS refers to S2.0P-SO.DG-0003, 2C Diesel Generator Operation and recognizes 2C EOG is now inoperable with the Jacket Water Heater and Pre-lube pump inoperable, and enters LCO 3.8.1.1.b, action b. CRS determines that S2.0P-ST.500-0001, Electrical Power Systems AC Sources Alianment must be oerformed within one hour PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 10 of 32

     ~.*  E\(alii'atofl:ln:stiuctor ActivltY,; .                  .ExReCted PlanflStudent,Response c" .* ;J 1?s'er                        Commeot1t          1
                                                                                                                                                               ,. *
 , , '. *:~~i~ ~r;;* *~.*rt ! iJ.:;,:.li> ;<ii~; ,   -~,-k   . t ~>>~gJ~~i\1f _*. , .:i1~:'** .';**?:- *,P~*~;;;: 1<:?; - :J~~~ zf LoG. ,,;~t~k ~,:~~TI:-; -~

to demonstrate the operability of the independent AC Sources (action b.1) Proceed to next event on direction from Lead Evaluator.

2. 23 Condensate pump trip I down power Simulator Operator: Insert RT-3 on dfrection from Lead Evaluator.

1 MALF:CN0117C 23 Condensate pump trip* PO announces 23 Condensate pump trip. CRS enters S2.0P-AB.CN-0001, Main Feedwater I Condensate System Abnormality. PO reports no SGFP tripped. PO reports 23 Condensate pump tripped. PO bypasses condensate polisher by opening 21 thru 23 CN108 if SGFP suction pressure is

                                                            <320 psiQ.

Role Play: If dispatched, after 3 minutes report as NEO that you can't see anything wrong with 21 condensate pump. If dispatched to 4KV breaker, report after 2 minutes that there is an overcurrent relay flag dropped. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 11 of 32

  . J;yaluat0rl1fistr4c(orActivity ~
  • Expec!id;~1ant1~tudent Response .
  • Comment1f!t:
  ,; J\t~t, , , '. ':::Y~~>ilZ,r *:  ,'~ ,',
                                             ..
                                             *;:7~~  , , ,'*ltc;;,;hf1t~ ,;'~*:, i~l~'., ,c '~~~,' +1~,*:~g~;

PO reports SGFP suction pressure. Note: Crew should discuss power increase expected when the CN47 is opened. (Note in AB.CN-1 ). CRS directs 2CN47 opened if suction pressure remains< 320 psig. PO isolates letdown by closing 21-24BG4 and 21-24GB185 if 2CN47 is open. CRS directs power reduction to 85% at

                                                  ~5%/min        with 2 Condensate pumps and 3 Heater Drain pumps in service IAW Attachment 4.

CRS enters S2.0P-AB.LOAD-0001, Rapid Load Reduction, to perform the load reduction. CRS directs initiation of AB.LOAD CAS. RO calculates boron addition and rate for power reduction. RO initiates boration. PO initiates turbine load reduction to 85% at rate directed by CRS.

3. Master Flow Controller failure I Simulator Operator: Once the PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 12 of 32

                  .~.~~?~tivi,,f        *
  • Expe'eted~planOStudent Res~onse'.*
  • mment . f;w
                                             ,': tr r~' ' :t' ,,  ~,{]~~;'.' , !;:( ' ;;,!~' / ,                     ;,, )',

power reduction is underway, insert RT-15 to fail the. Master F.low Controller. MALF: CV0035' CHRG Master Flow Controller fails H/L . . Severitv: 26 ** RO reports unexpected low seal injection flow alarms on all RCP's. RO reports Master Flow Controller is failed based on lower than expected Charging flow 75 apm vs 87 aom CRS enters S2.0P-AB.CVC-0001, Loss of Charaina. RO may use Alarm Response Procedure initially in response to Low Seal Injection Flow to adjust 2CV71 to restore seal injection flow to above the alarm setpoint, but this will not restore normal charaina flow. RO reports:

                                     - A charging pump is running with no indication of cavitation RO reports neither a PZR level nor a VCT level channel has failed.

No indication of charaina svstem leak RO reports the Charging Master Flow Controller has failed. RO takes manual control of 23 charain PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 13 of 32 ccfmme'nf * *

  • s \j .* !* *.di?/ ::/ r:r, .~0* ff .:.I *; ;xtfi.ffil,&.§'LUl:i ';r~l\1".*

J/}., ,,f; pump, and adjusts speed to maintain PZR level on proqram IAW Att. 2. RO reports PZR level can be maintained stable or rising. RO announces auto rod motion when it occurs. Proceed to next event on direction from Lead Evaluator.

4. 21 SG Tube Leak Simulator Operator; Insert RT-5 on direction from Lead evaluator.

.* MALF: SG00078A 21 STEAM

 .GENERATOR TUBE RUPTURE Severity: 5         ;

RO reports unexpected OHA A-6 and identifies 2R53A 21 Main Steamline N2 monitor from CRT indication in alarm. RO reports 2R53A level >1000 qpd. CRS enters S2.0P-AB.SG-0001, Steam Generator Tube Leak, and S2.0P-AB.RAD-0001, Abnormal Radiation. RO reports OHA A-6 reflash is 2R15 Condenser Air Ejector monitor in alarm. CRS directs initiation of AB.SG CAS. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 14 of 32

 **1i;Evalqator/1nstructor
             <'            n J(ct1v1fy:i!f!!!J;.                *ExnecteCl,fr>..~*.
                                                                                                             . 0 fant/student Rijspo1lae'.l11:*.~~*.***
                                                                                                          , N.r:~::             *       ,        :,~~~>>' ,,

sar:

                                                                                                                                                            ,,,,                  ' if~-~
                                                                                                                                          ..*...

b,f';;~*:J ';f.:d.i', ~.,.Zd .. , .~~.c0 ,, .... * ,; , "l c

                              ;::t                          *.. ,.~ ...*       ~***  ,;'c ,.*                     **~   . **                              -*- ._.,,c, *:W '

RO reports when 2R 19A is in warning and alarm. PO reports when SGBD isolation occurs on hiqh radiation. CRS dispatches operator to isolate TGA and Condensate Polisher area sump pumps. Simulator Operator:. When dispatched to.* isolatetfGA and polisher building sum'ps, insert RT- ,11. This deenergizes 21 :25 TGA sump pumps after a 3 minute time delay. RO reports PZR level being maintained stable by risinq charqinq flow. Note: Initial charging flow with stable PZR level is -89 gpm. 23 charging pump will deliver -99 gpm at full flow and seal injection of -26 gpm. IF RO reports PZR level is lowering (due to lag in Master Flow control response,) then RO will swap to a centrifugal charging pump at Step 3.6. RO reports PZR level can be maintained stable or risinq. Note: SGBD will isolate -2.5 minutes after 2R53D alarms. This PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 15 of 32

  *E\/alUator11nstn.ictor ActNitY                                                                                          comment:"'*            *
   ;,I <~~rj~'f *;;~:-, ,j,J;;, ,~.J~~t~,-                                                                                      ,"~
                                                                                                                              ~wr   -,

will cause RCS temp and PZR level to rise. PO reports when load reduction is complete. RO reports unit 2 is in MODE 1. RO reports 21 SG is affected SG. PO sets 21MS10 to 1045 psig, and ensures 21GB4, 21MS18, and 21MS7 are shut. CRS dispatches an operator to shut 21 MS45 steam supply to 23 AFW pump. Note: Do NOT report the 21 MS45 is shut until AFTER 23 AFW pump has been tripped at step 4. 7 of SGTR-1. CRS enters LCO 3. 7 .1.2 for less than 3 operable AFW pumps, and LCO 3.4.7.2.c for

                                                 >150 gpd primary to secondary leakage though 21 SG.

CRS determines (Action Level 3) the unit must be less than 50% in less than one hour, the unit placed in Hot Standby within 6 hours. CRS dispatches an operator to realign SGBD and Samplinq. Proceed to next event on direction from Lead Evaluator after Tech Specs have been addressed. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 16 of 32

    'eva1    ;Jr          Ai ...               e**      d1]>1ant1Student R,               SBT                   *;;~rc~:0,1m~~~,;~r**
5. SGTR Simulator Operator: MODIFY

. MALF SG00078A from 5 to 650 on direction from Lead Evaluator. RO reports indications of worsening tube leak/rupture, with lowering PZR level and pressure. CRS directs RO to trip the Rx, confirm the Rx trip, and initiate a Safety Injection, then enter TRIP-1. RO trips the Rx, confirms the Rx trip, and initiates Safety Injection. Simulator Operator: Ensure ET*1 is true when the* rx is tripped., This trips 21 AFW pump after a 4 minute delay. RO backs up the Main Turbine trip, reports 4KV vital buses energized, and reports SI manually initiated. CRS and RO verify TRIP-1 immediate actions. PO receives CRS concurrence and isolates AFW to 21 SG by closing 21AF11 and 21AF21. CT#1 (CT-18) Isolate feed flow into (oart 1) and steam flow from PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 17 of 32

                                        *. E~pected Pliint/s~µaenf Res~onse **
                                         <' :7,£}: '~' , ;, _'*' . ~t00,,', ' ;~f~:~;- '
                                                                                                             .Co~;;",~:!~~if!I ~:: iiw,*1"'**
                                                                                                                                  !           ,

(part 2) 21SG prior to a transition to SGTR-3 being required ..(steamflow isolation will be perform~~ on page 19) Part*1 UNSAT_ _ SAT

    --

PO receives CRS concurrence and reduces total AFW flow to no less than 22E04 lbm/hr until at least one SG NR level is> 9%, then maintains NR levels 19-33%.

6. 21 AFW pump trip PO reports when 21 AFW pump trips, and adjusts flow from 22 and 23 AFW pumps as reauired based on current SG NR levels.

Note: 21 AFW pp supplies 23/24 SGs 22 AFW pp supplies 21/22 SGs 23 AFW pump supplies all SGs Simulator Operator: Use

  • REMOTE AF20 to OFF 2 minutes after being dispatched to remove **

control power from 21 AFW pump breaker. PO reports all available equipment started on SEC loadina. PO reoorts which AFW oumps are runnin PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 18 of 32 ' *Evaluator/fnsln1ctor Acti~ityw*

   - '.-:~?f~~- ~rr ~ _,,,,>AL , ;;v~:, ,,,,, , 'l~','
                                                             *;i~1Expe~te& Pla'nt/Studenf Response            $BT . '                . Comment , . ~' *~tt
                                                                                              ..      .

PO reports correct safeguards valve alignment. RO reports 21 and 22CA330s are shut. RO reports containment pressure remains less than 15 psig. PO reports no indication of hi steam flow. PO reports all 4KV vital buses enerqized. RO reports ventilation systems lineups correct for current plant conditions. RO reports at least 2 CCW pumps are running. RO reports proper ECCS flow indicated for current plant conditions. PO reports AFW status, and maintains at least 22E4 lbm/hr flow until at least one SG NR level is >9%, then maintains SG NR levels 19-33%. RO reports RCP status, and RCS temperature stable at or trendinq to 547°. RO reports both RTBs are open. RO reports PZR PORVs are shut with Block valves open. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 19 of 32

 *e,,~ruator/rr;1str~Pf6r,e.ctivi~x~..                           Expecte'tl .Plant/StuClenr Respons~,f" *                               **~.e'f*     :    ir*gomJQPnF
                                                                                                                                                       .118
   ~l r,,;. _ ,,,,,,;'Jt* *;:(f~f( ,,'.l"< ~c,j~),, ' "'*       !;;/:;~* ~\f~~* ~ff;* f~~f-~t 1 ';;. ,~'.~~P' *,;,:~i?f' 1 J.'./,, ., J.r:OG; ..,.

RO reports PZR spray status for current plant conditions. RO reports RCS pressure is >1350 psig. RO maintains seal injection flow to RCPs. PO reports no SGs are faulted. PO reports NR or WR level is risinq in 21 SG. CRS transitions to EOP-SGTR-1, Steam Generator Tube Rupture. Note: STA will report to Control Room 10 minutes after being paged to report, and initiate monitoring of CFSTs. RO maintains seal injection flow to all RCPs. PO reports 21 SG is ruptured, and ensures 21MS10 is set at 1045 psiq. PO reports 21 MS10 operating as expected for current pressure. PO shuts 21MS167, and verifies 21MS7, 21MS18, and 21GB4 are shut. Note: These steps complete CT#1 CT#1 (CT-18) Isolate feed flow into and steam flow from 21 SG prior to a transition to SGTR-3 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 20 of 32 1:). Eipedted' Plant/Student Re$poose' * *set

                            , ~f ,,'~j;f,'._ , *:1; 1
                                                     ,*:J <("",_ , : *, >f:/:\., : ,.,/\:iL  t '

bOG being required. SAT UNSAT PO reoorts 21 SG is ruotured. PO reports 23 AFW pump is not the only source of AFW. PO ensures 23 AFW pump speed at minimum and trios 23 AFW oumo. CRS dispatches operator to shut 21 MS45 if not oreviouslv oerformed. CRS dispatches operator to shut 2SS321 sample valve. PO reports 21 SG is isolated from all intact SGs. PO controls AFW flow if required to maintain 21 SG NR level >9%. PO reports when 21MS10 opens for pressure control av 1045 osia. PO reoorts 21 SG oressure is >375 osi CRS determines target temperature from Table D. (503°F for ruptured SG pressure

                         ~1000 osia.

PO reports intact SGs are available for cooldown. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 21of32 "r :At';E'181uator1tnstrucJq( Activity;{...

  • of/Student
                                                                                                                ,

Response *** {- ???-; c~nnment * ~'. ** -:-1 F~rn: :':", >, ;; *c~ ,* -),:; ~; -, ;l9fi:,'":~,'.' *' , J 1:~'., t -,~dat~_.:._...:.=..--'-"-"--=-~

                                                                      -
                                                                                                                  'ij~~:r c'.Y

PO reports steam dumps are available, and places in MS Pressure Control-Manual at 25% to perform cooldown. PO bypasses Tavg when Tavg Low-Low is reached. Crew monitors hottest CET temperature while continuina in procedure. Note: When hottest CET is <503°F, crew will stop cooldown with steps on next page. RO reports power is available to both PZR PORV Stop valves, both PZR PORVs are shut, and both PZR PORV Stop valves are ooen. RO resets SI and Phase A isolation, and reoorts Phase B isolation reset. RO ooens 21 and 22CA330. PO resets each SEC and reports 230V control centers are reset. RO reports RHR suction is aligned to the RWST and no RHR oumo discharae flow. RO stoos both RHR s. PO reports 21 SG is ruptured and 21MS167 is shut. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 22 of 32 c<>mmr'nt"' . . ?qlf ~*

                                                                                     ', *lloG*z
                                                                                          '. cf+rJ?+                 ,,,,

RO shuts charging pump mini flows when RCS ressure is < 1500 si . RO reports when hottest CET is less than RCS cooldown tar et tern . CT#2 (CT-19) Establish and maintain an RCS temperature so that transition from SGTR-1 does** not qccur because temperature is too high to maintain minimum suocooling,. or: so lowJt causes transition to FRTS or FRSM. *

  • SAT UNSAT PO re orts 21 SG ressure is stable or risin RO re RO re orts normal PZR s ra is available.

RO full o ens both PZR S ra Valves. RO reports PZR Spray is reducing RCS ressure. Crew continues de ressurization.

7. 23 RCP trip PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 23 of 32

                                    *'*i      TEipectea'Pla'nt/S$dent Resji'onsef ,                              '!; SBtW' ,1J~Pl>>1if;Qenl" '?]*,~   .

(\~<,_,L, cT ;~:;~_,// *;;>'/, ,.;, ,v';f/i[~"; ' ' 1 ~~:i~< '. ,/ LOG, Simulator Operator: Insert RT-7 on.directionJrom Lead Evaluator once.RO reports spray effectiveness. MALF: 23 RCP tri RO reoorts 23 RCP tri~. Note: The crew is in a "do loop" when reducing RCS pressure using spray, and will return to Step 19.2 RO reports with loss of 23 RCP, spray is no lonaer effectivelv reducina RCS pressure. Simulator Operator: IF crew continues to use spray flow to lower RCS pressure, .THEN insert RT*9 on direction from Lead Evaluator to trio 21 RCP. RO shuts both PZR Sorav valves. RO reoorts both PZR PORVs are available. Crew reviews depressurization criteria. IF 2PR1 is selected as the PORV to deoressurize, RO reports 2PR1 will not open. RO opens 2PR2. Simulator Ooerator: Insert RT-13 PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 24 of 32

                                                                                                                                    
   *'E.valuaterir * *                    '    * ¥\' 1" { ' '  *  ,,'  ' ' \"      <l"
                                         +~4 E:xpe~ted ,Plant/Student,Re$ponse" j / , 111~
                                                                                          ;>  Yj",Y""-~'~       ' ,1§""~      'v/  '."""~"t'<t' 11 ;!SBT:, *
                                                                                                                                                           ,-;C*'""

tYci1;iJ:2f11C~m~'~t;i)-1 , ,. ,

  • -~,,~J:,f~}~\(ic'*,*,);i$~).~  :* '.% t.f14 I'"'!  ;;.J ;Pf'.*11 ,;,. " * . * . *1c,(1P'1 . LOG;'

as soon as 2PR2 is open. MALF:. 2PR2.fails to 100%. RO reoorts when condition in Table E is met.

8. PZR PORV fails to shut RO reoorts 2PR2 will not shut.

CRS directs closure of 2PR7 PZR PORV Block Valve. Simulator Operator: Ensure ~ is TRUE when 2PR7 shut PB is depressed. This fails 2PR7 90% ooen. RO reports that after initiating closed on 2PR7, the open limit extinguished but the closed limit has not illuminated. CRS transitions to EOP-SGTR-3, SGTR with LOCA- Subcooled Recoverv. Terminate the scenario when the transition to SGTR-3 is announced. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 25 of 32 A. Alarm Response Procedures (Various) B. Technical Specifications C. Emergency Plan (ECG) D. OP-AA-101-111-1003, Use of Procedures E. S2.0P-10.ZZ-0004, Power Operation F. S2.0P-SO.DG-0003, 2C Diesel Generator Operation G. S2.0P-ST.500-0001, Electrical Power Systems AC Sources Alignment H. S2.0P-AB.SG-0001, Steam Generator Tube Leak I. S2.0P-AB.LOAD-0001, Rapid Load Reduction J. 2-EOP-TRIP-1, Reactor Trip or Safety Injection K. 2-EOP-SGTR-1, Steam Generator Tube Rupture PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 26 of 32 ATTACHMENT 1 UNIT TWO PLANT STATUS TODAY MODE: 1 POWER: 89.4% RCS BORON: 1114 MWe 1080 SHUTDOWN SAFETY SYSTEM STATUS (5, 6 & DEFUELED): NA REACTIVITY PARAMETERS Control Bank D is at 193 steps. Xenon is building in at 25 pcm I hr following downpower last shift MOST LIMITING LCO AND DATE/TIME OF EXPIRATION: EVOLUTIONS/PROCEDURES/SURVEILLANCES IN PROGRESS: S2.0P-PT.TRB-0003, Main Turbine Valve testing is being briefed by a dedicated test team to be performed in one hour. ABNORMAL PLANT CONFIGURATIONS: 2C EOG Jacket Water heater is failed and CIT. CONTROL ROOM: Unit 1 and Hope Creek at 100% power. No penalty minutes in the last 24 hrs. PRIMARY: SECONDARY: Condensate Polisher is in service RADWASTE: No discharges in progress CIRCULATING WATER/SERVICE WATER: PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 27 of 32 ATTACHMENT 2 SIMULATOR READY FOR TRAINING CHECKLIST

1. Verify simulator is in "TRAIN" Load
2. Simulator is in RUN
3. Overhead Annunciator Horns ON
4. All required computer terminals in operation
5. Simulator clocks synchronized
6. All tagged equipment properly secured and documented
7. TSAS Status Board up-to-date
8. Shift manning sheet available
9. Procedures in progress open and signed-off to proper step
10. All OHA lamps operating (OHA Test) and burned out lamps replaced
11. Required chart recorders advanced and ON (proper paper installed)
12. All printers have adequate paper AND functional ribbon
13. Required procedures clean
14. Multiple color procedure pens available
15. Required keys available
16. Simulator cleared of unauthorized material/personnel
17. All charts advanced to clean traces and chart recorders are on.
18. Rod step counters correct (channel check) and reset as necessary
19. Exam security set for simulator
20. Ensure a current RCS Leak Rate Worksheet is placed by Aux Alarm Typewriter with Baseline Data filled out
21. Shift logs available if required
22. Recording Media available (if applicable)
23. Ensure ECG classification is correct
24. Reference verification performed with required documents available
25. Verify phones disconnected from plant after drill.
26. Verify EGC paperwork is marked "Training Use Only" and is current revision.
27. Ensure sufficient copies of ECG paperwork are available.

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 28 of 32 ATTACHMENT 3 CRITICAL TASK METHODOLOGY In reviewing each proposed CT, the examination team assesses the task to ensure, that it is essential to safety. A task is essential to safety if, in the judgment of the examination team, the improper performance or omission of this task by a licensee will result in direct adverse consequences or in significant degradation in the mitigative capability of the plant. The examination team determines if an automatically actuated plant system would have been required to mitigate the consequences of an individual's incorrect performance. If incorrect performance of a task by an individual necessitates the crew taking compensatory action that would complicate the event mitigation strategy, the task is safety significant. I. Examples of CTs involving essential safety actions include those for which operation or correct performance prevents ...

  • degradation of any barrier to fission product release
  • degraded emergency core cooling system (ECCS) or emergency power capacity
  • a violation of a safety limit
  • a violation of the facility license condition
  • incorrect reactivity control (such as failure to initiate Emergency Boration or Standby Liquid Control, or manually insert control rods)
  • a significant reduction of safety margin beyond that irreparably introduced by the scenario II. Examples of CTs involving essential safety actions include those for which a crew demonstrates the ability to ...
  • effectively direct or manipulate engineered safety feature (ESF) controls that would prevent any condition described in the previous paragraph.
  • recognize a failure or an incorrect automatic actuation of an ESF system or component.
  • take one or more actions that would prevent a challenge to plant safety.
  • prevent inappropriate actions that create a challenge to plant safety (such as an unintentional Reactor Protection System (RPS) or ESF actuation.

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 29 of 32 SCENARIO IDENTIFIER: 15-01 ILOT NRC ESG-2 REVIEWER: C Recchione Initials Qualitative Attributes CR 1. The scenario has clearly stated objectives in the scenario. CR 2. The initial conditions are realistic, in that some equipment and/or instrumentation may be out of service, but it does not cue crew into expected events. CR 3. The scenario consists mostly of related events. CR 4. Each event description consists of:

  • the point in the scenario when it is to be initiated
  • the malfunction(s) that are entered to initiate the event
  • the symptoms/cues that will be visible to the crew
  • the expected operator actions (by shift position)
  • the event termination point CR 5. No more than one non-mechanistic failure (e.g., pipe break) is incorporated into the scenario without a credible preceding incident such as a seismic event.

CR 6. The events are valid with regard to physics and thermodynamics. CR 7. Sequencing/timing of events is reasonable, and allows for the examination team to obtain complete evaluation results commensurate with the scenario objectives. CR 8. The simulator modeling is not altered. CR 9. All crew competencies can be evaluated. CR 10. The scenario has been validated. CR 11. If the sampling plan indicates that the scenario was used for training during the requalification cycle, evaluate the need to modify or replace the scenario. CR 12. ESG-PSA Evaluation Form is completed for the scenario at the applicable facility. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 30 of 32 Initial Quantitative Attributes (as per ES-301-4, and ES-301 Section D.5.d) GG 2 Malfunctions after EOP entry: 1-2 GG 3 Abnormal Events: 2-4 GG 1 Major Transients: 1-2 GG 1 EOPs entered/requiring substantive actions: 1-2 GG 0 EOP contingencies requiring substantive actions: 0-2 GG 2 EOP based Critical tasks: 2-3 COMMENTS: PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 31of32 15-01 ILOT NRC ESG-2 CT#1 (CT-18) Isolate feed flow into and steam flow from 21 SG prior to a transition to SGTR-3 being required. Basis: Failure to isolate the ruptured SG causes a loss of differential pressure between the ruptured SG and the intact SGs. The fact that the crew allows the differential pressure to dissipate and, as a result, are then forced to transition to a contingency ERG constitutes an incorrect performance that "necessitates the crew taking compensating action that would complicate the event mitigation strategy .... " CT #2: {CT-19) Establish and maintain an RCS temperature so that transition from SGTR does not occur because temperature is too high to maintain minimum subcooling, or so low it causes transition to FRTS or FRSM. Basis: Failure to establish and maintain the correct RCS temperature during a SGTR leads to a transition from E-3 to a contingency ERG. This failure constitutes an incorrect performance that "necessitates the crew taking compensating action that would complicate the event mitigation strategy .... " Note to Evaluator: CT numbers in parentheses are the corresponding Westinghouse ERG Rev. 2- based Critical Tasks procedure WCAP-17711-NP PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 32 of 32 ATTACHMENT6 - - ESG~PRA REl..ATIONSHIP E~AlUATION EVENTS LEADING TO CORE DAMAGE Y/N Event Y/N Event N TRANSIENTS with PCS Unavailable N Loss of Service Water y Steam Generator Tube Rupture N Loss ofCCW N Loss of Offsite Power N Loss of Control Air N Loss of Switchgear and Pen Area Ventilation N Station Black Out N LOCA COMPONENT/TRAIN/SYSTEM UNAVAILABILITY THAT INCREASES CORE DAMAGE FREQUENCY COMPONENT, SYSTEM, OR TRAIN Y/N COMPONENT, SYSTEM, OR Tc:>~lll.I N Containment Sump Strainers N Gas Turbine N SSWS Valves to Turbine Generator Area Y Any Diesel Generator N RHR Suction Line valves from Hot Leg Y Auxiliary Feed Pump N CVCS Letdown line Control and Isolation Valves N SBO Air Compressor OPERATOR ACTIONS IMPORTANT IN PREVENTING CORE DAMAGE Y/N OPERATOR ACTION N Restore AC power during SBO N Connect to gas turbine N Trip Reactor and RCPs after loss of component cooling system N Re-align RHR system for re-circulation N Un-isolate the available CCW Heat Exchanger N Isolate the CVCS letdown path and transfer charging suction to RWST Y Cooldown the RCS and depressurize the system Y Isolate the affected Steam Generator that has the tube rupture(s) N Early depressurize the RCS N Initiate feed and bleed Complete this evaluation form for each ESG.

TQ-AA-106-0204 Page 1of29 SIMULATOR EXAMINATION SCENARIO GUIDE SCENARIO TITLE: 15-01 NRC ESG-3 SCENARIO NUMBER: 15-01 NRC ESG-3 EFFECTIVE DATE: See Approval Dates EXPECTED DURATION: 60 minutes REVISION NUMBER: 00 PROGRAM: ~-~' LO. REQUAL X  ! INITIAL LICENSE

                               ~~!STA
                               ~-~'OTHER Revision Summary New issue for 15-01 ILOT NRC exam PREPARED BY:                     G Gauding                              8-11-16 Lead Regulatory Exam Author                       Date APPROVED BY:                                ~V\                        (o/,/c,
                                                                        'oate APPROVED BY:
                        ~ JdllkUlj aciiifyResentative 1ofit!afc, ate PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 2 of 29

TQ-AA-106-0204 Page 3 of 29 A. Given the order or indications of a pressurizer control system malfunction, perform actions as the nuclear control operator to RESPOND to the malfunction in accordance with S1/S2.0P-S2.0P-AB.PZR-0001. B. Given indication of a pressurizer control system malfunction, DIRECT the response to the malfunction in accordance with S2.0P-AB.PZR-0001. C. Given indication of a dropped control rod perform actions as the nuclear control operator to RESPOND to the malfunction in accordance with S2.0P-AB.ROD-0002. D. Given indication of a dropped control rod DIRECT the response to the malfunction in accordance with S2.0P-AB.ROD-0002. E. Given the order or indications of a loss of secondary coolant, perform actions as the nuclear control operator to RESPOND to the coolant loss in accordance with EOP-LOSC-1. F. Given indication of a loss of secondary coolant, DIRECT the response to the loss of secondary coolant, in accordance with EOP-LOSC-1. G. Given the order or indications of a reactor trip, perform actions as the nuclear control operator to RESPOND to the reactor trip in accordance with 2-EOP-TRIP-1. H. Given indication of a reactor trip, DIRECT the response to the reactor trip in accordance with 2-EOP-TRIP-1. I. Given the order or indications of a safety injection, perform actions as the nuclear control operator to RESPOND to the safety injection in accordance with the approved station procedures. J. Given indication of a safety injection, DIRECT the response to the safety injection in accordance with the approved station procedures. K. Given the order or indications of a multiple steam generator depressurization, perform actions as the nuclear control operator to RESPOND to the generator depressurization in accordance with EOP-LOSC-2. L. Given indication of a multiple steam generator depressurization, DIRECT the response to the generator depressurization in accordance with EOP-LOSC-2. A. Power Ascension B. Controlling PZR Pressure Instrument fails high C. Dropped control rod D. Steam Leak/Rupture in containment PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 4 of 29 A. The crew will take the watch with the unit stable at 1x1 o-s Amps during a plant startup, BOL. 21 SGFP is in service and 22 SGFP is O/S. Steam dumps are in MS Pressure Control - Auto

  @ 1,000 psig. 25 CFCU is CIT for maintenance. 23 charging pump is CIT for emergent maintenance. The crew will be instructed to raise power to 2%.

B. The crew will initiate a power ascension to 2% using Main Steam Dumps and control rods. C. After the power ascension is started the controlling PZR Pressure instrument will fail high, deenergizing PZR heaters and causing both PZR Spray valves to open fully. The crew will respond IAW S2.0P-AB.PZR-0001, Pressurizer Pressure Malfunction to establish manual control of PZR pressure control and restore pressure to normal, swap to an operable channel, and remove the failed channel from service. The CRS will identify applicable LCO's. D. After the Pressurizer Pressure control system failure has been addressed, a control rod will drop fully into the core. The crew will respond IAW S2.0P-AB.ROD-0002, Dropped Rod. The crew will identify the Rx is subcritical, and initiate control rod insertion to fully insert all Control and Shutdown rods. The CRS will identify applicable LCO's. E. During the rod insertion, a steam leak in containment will occur on 21 SG. The crew will diagnose changing containment conditions, and determine a Rx trip is required and MSLI will be required in an attempt to isolate the steam leak. F. The crew will trip the Rx. The steamline will rupture. MSLI (auto and manual) will fail to shut any MSIV. The crew will initiate Safety Injection when it is identified that the source of the steam leak is not isolated. G. The crew will perform plant stabilization actions in EOP-TRIP-1, Reactor Trip or Safety Injection. With all SGs faulted, the crew will maintain AFW flow to each SG. 21 AFW pump will trip during TRIP-1 performance. Containment Spray pumps will not automatically start when demanded on hi-hi containment pressure, and the crew will manually start at least one CS pump (CT-1 ). The crew will transition to EOP-LOSC-1, Loss of Secondary Coolant. H. The crew will transition to EOP-LOSC-2, Multiple Steam Generator Depressurization with all SG's faulted. I. The crew will identify the RCS cooldown rate of >100°F I hr, and control AFW flow to minimize RCS cooldown (CT-2). The crew will reset Safeguards. When evaluating SI Flow Reduction Criteria, local operators will successfully shut a MSIV. The crew will recognize rising pressure in that SG, and transition to LOSC-1. J. The scenario will be terminated upon transition to LOSC-1. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 5 of 29 IC-233 PREP FOR' TRAINH~G

                      ,,  '

(i.e. ,,computer

                                           ,, '

setpoints,

                                                   -      '

procedures,

                                                             ,,

bezel

                                                                        '

e~vers

                                                                              . - >'
                                                                                       ,tagged eqt1ipment)
                                                                                     ',,

Initial I Description 1 VC1 and VC4 CIT 2 RCPs (SELF CHECK) _ 3 RTBs (SELF CHECK) _ 4 MS167s (SELF CHECK) _ 5 500 KV SWYD (SELF CHECK) _ 6 SGFP Trip (SELF CHECK) _ 7 23 CV PP (SELF CHECK) __ 8 21 Charging pump in service 9 25 CFCU CIT _ 10 23 Charging pump CIT 11 IOP-3 open and complete up to Section 4.3, Power Operation. 12 Complete Attachment 2 "Simulator Ready-for-Training/Examination Checklist." PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 6 of 29 Note: Tables with blue headings may be populated by external program, do not change column name without consulting Simulator Support group Description

                    --- ---         -                          -              --  - ---                -     ---*

EVENT ACTION: MONP254 <10 II CONT ROD BANK C < 10 ( RX TRIP ) 1 COMMAND: PURPOSE: <update as needed> SELF- Description Delay Initial Ramp Trigger Severity CHECK Time Value Time 01 PR0016A PZR PRESS CH I PT455 FAILS H/L N/A N/A N/A RT-1 2500 02 RD0267 ANY ROD S INADVERTENTLY DROPS NIA N/A N/A RT-3 3 MS0090Ar 21 Main Steam Line Leak Inside Cont 03 N/A N/A N/A RT-5 2 AFTER orifice 04 RP0279A AUTO MSLIS FAILS TO ACT, TRNA NIA NIA NIA NIA 05 RP0279B AUTO MSLIS FAILS TO ACT, TRN B N/A N/A NIA NIA 06 MS0092E 21MS167 FAILS OPEN N/A NIA NIA NIA 07 MS0092F 22MS167 FAILS OPEN Ni A NIA N/A N/A 08 MS0092G 23MS167 FAILS OPEN NiA NIA NIA N/A 09 MS0092H 24MS167 FAILS OPEN N/A NIA N/A NIA 10 RP0274A AUTO SI FAILS TO ACT, TRNA NIA N/A N/A N/A 11 RP0274B AUTO SI FAILS TO ACT, TRN B NIA NIA N/A NiA 12 AF0181A 21 AUX FEEDWATER PUMP TRIP 00:05:00 N/A NIA ET-1 13 RP318L 1 21 CS Pum Fails to Start on SEC NIA N/A NIA NIA 14 RP318L2 22 CS Pum Fails to Start on SEC NIA NIA NIA NIA SELF- Description Delay Initial Ramp Trigger Condition CHECK Time Value Time 01 CV52D 23 CHG PUMP BKR CONTROL POWER N/A N/A N/A NIA OFF 02 PR34D PORV STOP VALVE 2PR6 TAGGED N/A NIA N/A RT-7 TAGGED 03 SP01A1 Prevailing Wind Speed NIA N/A N/A N/A 10 04 SP01A2 Prevailin Wind Direction N/A N/A NIA NIA 160 05 CT195-1D 25 CFCU BKR #1 Hi h S eed 125VDC N/A N/A NIA NIA OFF 06 CT195-2D 25 CFCU BKR #2 Hi h Speed 125VDC N/A NIA NIA NIA OFF

                                                                                                                                -----*

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 7 of 29 07 I CT195-3D 25 CFCU BKR #3 Low Speed 125VDC NIA N/A N/A N/A I ___OFF_] SELF- Description Delay Initial Ramp Trigger Condition/ CHECK Time Value Time Severity 01 Cl11 CLO QCl11HR2 TURNING GEAR-ENGAGED N/A N/A N/A NIA ON 02 Cl11 E LO QCl11PR2 TURNING GEAR-STARTED N/A NIA N/A NIA ON 03 Cl11 FLO QCl11TG2 TURNING GEAR-STOPPED N/A NIA N/A NIA OFF 04 Cl11 D LO QCl11LG2 TURNING GEAR-DISENGAGED NIA ~~!A NIA WA OFF

1. None PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 8 of 29 A. State shift job assignments. B. Hold a shift briefing, detailing instruction to the shift: (provide crew members a copy of the shift turnover sheet). C. Inform the crew "The simulator is running. You may commence panel walkdowns at this time. CRS please inform me when your crew is ready to assume the shift". D. Allow sufficient time for panel walk-downs. When informed by the CRS that the crew is ready to assume the shift, ensure the simulator is cleared of unauthorized personnel. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 9 of 29 Eva'1aitodln$fructQr~ActivitY' , 'Ex'Pected 1?lan,t1stildi;tnt Response SBT' *.*'#'~

,wv' 0 vommen< '"t*".
                                                                                                                  *~t        //**1i~'~
                                          ,. 'w  */'.; ;(f' ; ;"'   *./ : 'we -*Y0J'o' .~il!i ~'Ir' l!OG, ,*
1. Power ascension CRS directs power ascension using Main Steam Dumps and control rods.

PO raises steam dump demand. RO adjusts control rods to maintain Tave on program. RO announces when POAH is observed. Continue to next event on direction from Lead evaluator.

2. Controlling PZR pressure instrument fails HIGH SimulatQr Operato,r: Insert RT-1 on directiOn from Lead EvalUatOr:° MALF: MALF: PR0016A PZR Press CHI (PT-455) fails H/L Final Value: 2500
  • RO announces unexpected OHA alarms D-8 RC Press HI, and E-42 2PR1 Yz Trip.

RO determines actual pressure is not high and reports spray valves open, and recommends placinq Master Pressure Controller in manual. CRS directs RO to place Master Pressure Controller in manual. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Pag.e 10 of 29 Evafuatoilinsfructor,~ctlvi~ Eii>ec\iae1antl~tua~.111*. Response **seT l i'g~j /il q :i; .*~** .1t~** ,. ,)ii, . : ;*r/*' J*~ LOG/ . RO takes manual control of Master Pressure controller, and lowers demand (increase pressure) to close sprays. CRS enters S2.0P-AB.PZR-001, Pressurizer Pressure Malfunction. CRS directs initiation of AB.PZR CAS. CRS gives band for control of PZR pressure. RO identifies PZR Press Channel I failed high. RO selects Channel Ill for control. RO matches master pressure controller demand to current pressure and returns Master Pressure Controller to AUTO. RO shuts 2PR6. Note: The requirement to shut 2PR6 and deenergize it is within one hour of the PZR Pressure Channel I instrument failure IAW Tech Specs. CRS directs WCC to remove power from 2PR6. Simulator Operator: Insert RT-7 2 minutes after being directed to remove power from 2PR6. REMOTE: PR340 PORV Stop PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 11of29

1~pwev:a1uatc>rnat1tructor Aottiify 'Tuexpected)>fiint/~tudenf Response  ;;iffS'BT iiii'!iv}}r*** *~!:'aorri'ment ,}}}}Tu.~ **
  ""'"*-. . '"   . w-, .,     ~,,
                                               '~" '                                                               ,"*c;-ilii0)i'.f> * ,J::

Valve 2PR6 taaaed CRS directs PO to initiate removing failed channel from service and contact l&C for support IAW S2.0P-SO.RPS-003. PO checks that tripping associated bistables will not result in an ESF or RPS actuation. Note: Crew may wait for l&C response before performing any actions in S2. OP-SO. RPS-0003. PO verifies that Channel Ill is selected for Master Pressure Control. PO selects PZR Pressure recorder to channel other than I. CRS enters TSAS 3.3.1.1 Action 6, 3.3.2.1.b Action 19*, 3.4.5.b, and 3.2.5. Proceed to next event on direction from Lead Evaluator.

3. Dropped control rod Simulator Operator: Insert RT-3 1: oh direction from Lead Evaluator.
               -          . ~

MALF: .RD0064.ANY.ROD INADVERTENTLY DROPS Severitv: 3 RO reports unexpected OHA E-48 ROD PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 12 of 29

                  . . !h:t8~,~~ivi.tJ#~,                                                   .
                                                        ~,;*a~iJsi'ud ftl~rnSRT               *v* 1iL "'
                                                                                           'C. Ltr6i.

BOTTOM, and reports Shutdown Bank rod 1SA3 rod bottom liaht is illuminated. CRS enters S2.0P-AB.ROD-0002, Dropped Rod. RO reoorts control rods are in manual. PO reoorts Main Turbine is S/D. RO reports the reactor is subcritical as a result of the droooed rod. CRS directs RO to insert all control and shutdown bank rods. RO initiates insertion of control rods in manual. Simulator Operator: Once rod insertion has commenced, insert RT-5 on direction from Lead Evaluator' MALF: MS0090Ar . Severitv: 2

4. 21 SG steam leak I rupture in containment PO announces OHA C-38, CFCU LK DET HI as unexpected, and shortly after, OHA C-30, CFCU LK DET HI-HI as well.

PO refers to ARP for OHA C-38 and C-30. PO reoorts indications of a steam leak inside PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 13 of 29 Evaluator/Instructor Activity Expected Plant/Student Response SBT Comment LOG containment including:

                                             - Containment pressure rising
                                             - Tavg slowly lowering
                                             - Rising steam flows on all loops
                                             - Steam dump demand lowerinq CRS enters S2.0P-AB.STM-0001, Excessive Steam Flow.

CRS directs monitorinq of AB.STM CAS. CRS notifies Emergency Services of the steam leak. PO reports that the Main Turbine is not latched. PO reports no indication of MS10 or steam dump valves malfunction. RO reports no indication of a SG Safety Valve partially open or leakinq. RO reports Rx power and RCS temperature are NOT stable. CRS directs the RO to trip the Rx. Note: A MSLI will be required to attempt to isolate the steam leak in containment. The CRS can use the CAS of AB.STM for direction, or will use Step 11 in TRIP-1 when containment pressure exceeds 15 psig. Auto and Manual MSLI are PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 14 of 29

   ,e~~~~at~Zlir**                                         *nf/Stuaent Rel onsef/ .                                      L ~4'
                                                                                           *¥¥>~~~:rz:I
                                                                                                                      *v>.1 ;>
                                                         ;Jltf \¥*': l~l ~I,, r.0~~i!f *
                                                                                                                               ~*

I .*I I

      , ~,:;\*                                                                                                  I failed and will not actuate.

Simulator Operator: After the Rx is tripped, then MODIFY MALF MS0090Ar to 100 with a 5 minute ramo. RO trios the Rx and confirms the Rx tri~ . .Simulator .op.erafo6'Ellsure ET~f is true upon the Rxtrip.' Thistrips 21 AFW.pump after a 5 minute delav.

5. All MSIVs fail to shut IF using AB.STM CAS, then RO will attempt a MSLI, and reoorts it did not actuate.

IF using AB.STM CAS, RO reports the steam leak is NOT isolated. RO continues Immediate Actions of TRIP-1: Reports the Main Turbine is tripped. Reports all 4KV vital buses are energized. Reports a demand for Safety Injection is present and Safety Injection has NOT actuated (or reports Safety injection was manuallv initiated as described in PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 15 of 29 .J,;><.~:eva1uator1fr:l$t

       , ~* ~~gsi : 'j.}~,r~ , ~

r Atilvity~*** ~t'1'? ;!'\

        =

bf' i~df i ~,~:!I: y

                                                        <'i jt§JI[ .*J ,,;,. *Ai./ 1 if" j** * ..* .;/ {ii * /1'"' * : ... ,**,,,. * <>lP' LU\.:J .j previous step).

RO initiates Safety Injection (if not previously performed.) Note: With all SGs faulted, AFW flow should not be isolated to any SG. PO reports SEC loading is not complete. PO reports all available equipment started. PO reports 21 and 22 AFW pumps are running, and if not previously performed, receives permission to throttle total AFW flow to no less than 22E4 lbm/hr. PO reports valve groups in Table B are in Safequards position. RO reports 21 and 22CA330 are shut.

6. 21 AFW pump trip PO reports when 21 AFW pump trips, and adjusts AFW flow if required.
7. Containment Spray pumps fail to start RO reports containment pressure has not remained less than 15 psig.

RO initiates Phase B and Spray actuation. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 16 of 29

   *evat$la~or11o*struciofActi'!JtY"
       % .;, -l'.i : /,'%§'   ;-,_'t#lf~' ,, , ,,, \(",

Ex'ecteci1'Plant1studenlResz~on$e

  • p '/W ;1 :'.
                                                                                 .
                                                                                   .1: .i;'.tt >.;;bf' .p ..:.lJil* '
                                                                                               '" ,,.. ..

l"'"set:: LOG ...

                                                                                                                                    .~*co~.ie~:;w. A*:
  • RO reports neither Containment Spray pump has started.

RO blocks 2A and 2C SECs. PO resets 2A and 2C SEC's. RO starts 21 and 22 CS pumps. CT#.1 (CT-3) Manually start at least one Containment Spray . pump before a red path

  • challenge develops c>n'thEt containment CSF. '
     .

SAT UNSAT RO reports MSLI has failed to close any MSIV. RO stops all RCPs. RO reports MSLI has failed to close any MSIV. CRS dispatches operators to place valves from Table D {locally close MSIVs) in safeguards position if not previously performed. PO reports all 4KV vital buses are energized. RO reports control room ventilation is in Accident Pressurized mode. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 17 of 29

  • <\.Eva11 i, 1. Y$[
            *         * t'ExpectedPl~nt/Student"Re~ponse            i:;SBT +1trw*           cbr~;pnegt ..
                                                                                               ~J&> )#~,,~

i .. RO reports 2 switchgear supply and 1 exhaust fan are runninq. RO reports 2 CCW pumps runninq. RO reports ECCS flow as expected for current RCS pressure. PO maintains total AFW flow greater than 22E4 lbm/hr until at least one SG NR level is

                    >15% (adverse), then maintains SG NR level 19-33%.

RO reports no RCPs are runninq. RO reports RCS Tcolds are droppinq. PO reports no dumpinq steam. RO reports MSLI failed to isolate anv MSIV. RO reports both RTBs are open. RO reports both PZR PORVs are closed. RO reports 2PR6 is shut, and 2PR7 is open. CRS dispatches operator to restore power to 2PR6 if deenerqized. RO reports no RCPs are running. RO maintains seal injection flow to all RCPs. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 18 of 29

   ;.,;i:Ev Iv; .;y**<*
  • 5~m ,nt 1

14f:1t *X;; tlf~3J()r[!  :<Jr A,cih1ity ~' ', '~ .~ .J'.~t", :{' ' ,; '.";;,t;t~ ~>' v,,,ir<~f' : ','.\~~J;,,, '. .. ,...., . .....

                                                                           "'     '"                    ~-,.

d ~* PO reports all SG pressures are dropping in an uncontrolled manner or completely depressurized with MSLI failure. CRS transitions to EOP-LOSC-1, Loss of Secondary Coolant. Note: CFSTs are in effect when transition out of TRIP-1 occurs. STA will report to control room 10 minutes after being summoned via page to monitor CFSTs. RO reports MSLI failed to shut any MSIV, all MS? and MS18 valves are shut, and action has been directed to locally shut MSIVs. PO reports all SG pressures are dropping in an uncontrolled manner. CRS transitions to EOP-LOSC-2, Multiple Steam Generator Depressurization. PO reports all valves in table A are shut except for all MSIVs. CRS dispatches operators, if not previously performed, to locally shut valves in Table A one loop at a time. CRS determines 23 AFW pump in service, and either stops 23 AFW pump or leaves it in service. Note: 23 AFW pump may be left in PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 19 of 29 EvalMe1f8r~1,nitructo~Ac** * ,, E"pe,c:;ted PlanfiStuCleQtResp'onse , ,p;;'?:SBT1;.iiir' co.mment 4.i;;

.f',~,:/~\* ,,~{/'": '~;' c;;,~1;'

service if it is determined it is necessary to maintain minimum AFW flow to keep SG tubes wet. IF required, PO lowers 23 AFW pump speed to minimum, trips then stops 23 AFW pump. IF required, CRS dispatches operator to shut 21 and 23MS45 steam supplies to 23 AFW pump. RO reports RCS cooldown rate is >100°F I hr. PO reduces AFW flow to each SG to no less than 1.0E4 lbm I hr. CT#2 (CT.;33) Control the AFW rate to notless'than 1E4 lbm/hr to minimize the cooldownrate. SAT UNSAT When STA reports RED path on Heat Sink, CRS transitions to FRHS-1, verifies operator action was cause of RED path, and returns to procedure in effect. RO reports RCS Thots are dropping. RO reports RCS pressure, and reports a cooldown is in progress or RCPs are secured. RO reports both PZR PORVs are closed. RO reports 2PR6 is shut, and 2PR7 is open. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 20 of 29

        , EvaluatorUnstructor Aalvi~}t                                                    E;xpecteCl.:.PJanllSfUdenf Re,sponse     SBT                    '?rii%;:,~3;f:~+t/:, . .

, ;'.;,l~Jti ) 1,' /,;t(~J:},~ (~;~; / 'i!~{'~'""" ;;{ :~<thl~'~ ' "";';'"",~}>~t"' RO resets SI, Phase A, and Phase B. RO opens 21 and 22CA330. PO reports all SECs are reset. PO reports all 230V Control Centers reset. RO resets SGBD Sample Isolation Bypass, and opens 21-24SS94s. CRS directs Chemistry to sample SGs for activity and boron. PO reports no indication of any SGTR. RO reports RHR pumps running with suction from RWST, and no discharqe flow. RO reports RCS pressure is stable or rising, and stops both RHR pumps .. RO reports both CS pumps are runninq. RO reports containment pressure. If/when containment pressure is <13 psig, then RO:

  • Resets Spray actuation
  • Stops both CS pumps
  • Shuts 21 and 22CS2 CS pump discharge valves PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 21of29 ,1;1ir"evii'uatorlinstrllctoFActi~itY'::;* ** ffEx.lfe'l:t ianffstuUenf"'ResP'Qose SSTi7i!l corii'riient'1i1ft** v~~r:: [;  ; J' 3' , ,,01": *.~:rz 1:tz LO(J" :: *~ ',;-\' RO reports RWST lo level alarm has not actuated. RO reports RCS Thats status. IF <375, PO removes lockouts for 21-24SJ54's, and RO shuts 21-24SJ54's. RO reports subcoolinQ is >0°F. RO reports RCS pressure and trend. RO reports RCS pressure is stable or rising and:

  • Realigns charging pump through normal charging line and adjusts 2CV55 to maintain PZR level >33%.
  • Reports PZR level trend .

Simulator Operator: When Step 20 is complete then shut 23MS167 by deleting MAL.F MS0092G and . ensurino 23MS167 shuts. PO reports indication of 23MS 167 being shut. CRS determines pressure rise in 23 SG requires transition to LOSC-1. CRS transitions to LOSC-1. Terminate the scenario when the transition to LOSC-1 is announced. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 22 of 29 A. Alarm Response Procedures (Various) B. Technical Specifications C. Emergency Plan (ECG) D. OP-AA-101-111-1003, Use of Procedures E. S2.0P-IO.ZZ-0003, Hot Standby to Minimum Load F. S2.0P-AB.PZR-0001, Pressurizer Pressure Malfunction G. S2.0P-AB.ROD-0002, Dropped Rod H. S2.0P-AB.STM-0001, Excessive Steam Flow I. 2-EOP-TRIP-1, Reactor Trip or Safety Injection J. 2-EOP-LOSC-1 Loss of Secondary Coolant K. 2-EOP-LOSC-2 Multiple Steam Generator Depressurization PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 23 of 29 ATTACHMENT 1 UNIT TWO PLANT STATUS TODAY MODE: 1 POWER: 1x10-8 A RCS BORON: 1711 MWe 0 SHUTDOWN SAFETY SYSTEM STATUS (5, 6 & DEFUELED): NA REACTIVITY PARAMETERS Control Bank D at 130 steps withdrawn. Core burnup 500 EFPH. MOST LIMITING LCO AND DATE/TIME OF EXPIRATION: 3.6.2.3 for 25 CFCU action a expires in 165 hours. EVOLUTIONS/PROCEDURES/SURVEILLANCES IN PROGRESS: S2.0P-IO.ZZ-0003, Hot Standby to Minimum Load complete up to Section 4.3, Power Operation. ABNORMAL PLANT CONFIGURATIONS: CONTROL ROOM: Unit 1 and Hope Creek at 100% power. PRIMARY: 21 Charging pump in service 23 Charging pump CIT for emergent repair, expected return in 2 hours 25 CFCU CIT for breaker replacement SECONDARY: 21 SGFP in service 22 SGFP O/S with steam supply valves shut RADWASTE: No discharges in progress CIRCULATING WATER/SERVICE WATER: PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 24 of 29 ATTACHMENT 2 SIMULATOR READY FOR TRAINING CHECKLIST

1. Verify simulator is in "TRAIN" Load
2. Simulator is in RUN
3. Overhead Annunciator Horns ON
4. All required computer terminals in operation
5. Simulator clocks synchronized
6. All tagged equipment properly secured and documented
7. TSAS Status Board up-to-date
8. Shift manning sheet available
9. Procedures in progress open and signed-off to proper step
10. All OHA lamps operating (OHA Test) and burned out lamps replaced
11. Required chart recorders advanced and ON (proper paper installed)
12. All printers have adequate paper AND functional ribbon
13. Required procedures clean
14. Multiple color procedure pens available
15. Required keys available
16. Simulator cleared of unauthorized material/personnel
17. All charts advanced to clean traces and chart recorders are on.
18. Rod step counters correct (channel check) and reset as necessary
19. Exam security set for simulator
20. Ensure a current RCS Leak Rate Worksheet is placed by Aux Alarm Typewriter with Baseline Data filled out
21. Shift logs available if required
22. Recording Media available (if applicable)
23. Ensure ECG classification is correct
24. Reference verification performed with required documents available
25. Verify phones disconnected from plant after drill.
26. Verify EGC paperwork is marked "Training Use Only" and is current revision.
27. Ensure sufficient copies of ECG paperwork are available.

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 25 of 29 ATTACHMENT3 CRITICAL TASK METHODOLOGY In reviewing each proposed CT, the examination team assesses the task to ensure, that it is essential to safety. A task is essential to safety if, in the judgment of the examination team, the improper performance or omission of this task by a licensee will result in direct adverse consequences or in significant degradation in the mitigative capability of the plant. The examination team determines if an automatically actuated plant system would have been required to mitigate the consequences of an individual's incorrect performance. If incorrect performance of a task by an individual necessitates the crew taking compensatory action that would complicate the event mitigation strategy, the task is safety significant. I. Examples of CTs involving essential safety actions include those for which operation or correct performance prevents ...

  • degradation of any barrier to fission product release
  • degraded emergency core cooling system (ECCS) or emergency power capacity
  • a violation of a safety limit
  • a violation of the facility license condition
  • incorrect reactivity control (such as failure to initiate Emergency Boration or Standby Liquid Control, or manually insert control rods)
  • a significant reduction of safety margin beyond that irreparably introduced by the scenario II. Examples of CTs involving essential safety actions include those for which a crew demonstrates the ability to ...
  • effectively direct or manipulate engineered safety feature (ESF) controls that would prevent any condition described in the previous paragraph.
  • recognize a failure or an incorrect automatic actuation of an ESF system or component.
  • take one or more actions that would prevent a challenge to plant safety.
  • prevent inappropriate actions that create a challenge to plant safety (such as an unintentional Reactor Protection System (RPS) or ESF actuation.

PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 26 of 29 SCENARIO IDENTIFIER: 15-01 NRC ESG-3 REVIEWER: C Recchione Initials Qualitative Attributes CR 1. The scenario has clearly stated objectives in the scenario. CR 2. The initial conditions are realistic, in that some equipment and/or instrumentation may be out of service, but it does not cue crew into expected events. CR 3. The scenario consists mostly of related events. CR 4. Each event description consists of:

  • the point in the scenario when it is to be initiated
  • the malfunction(s) that are entered to initiate the event
  • the symptoms/cues that will be visible to the crew
  • the expected operator actions (by shift position)
  • the event termination point CR 5. No more than one non-mechanistic failure (e.g., pipe break) is incorporated into the scenario without a credible preceding incident such as a seismic event.

CR 6. The events are valid with regard to physics and thermodynamics. CR 7. Sequencing/timing of events is reasonable, and allows for the examination team to obtain complete evaluation results commensurate with the scenario objectives. CR 8. The simulator modeling is not altered. CR 9. All crew competencies can be evaluated. CR 10. The scenario has been validated. CR 11. If the sampling plan indicates that the scenario was used for training during the requalification cycle, evaluate the need to modify or replace the scenario. CR 12. ESG-PSA Evaluation Form is completed for the scenario at the applicable facility. PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 27 of 29 Initial Quantitative Attributes (as per ES-301-4, and ES-301 Section 0.5.d) GG 2 Malfunctions after EOP entry: 1-2 GG 3 Abnormal Events: 2-4 GG 1 Major Transients: 1-2 GG 2 EOPs entered/requiring substantive actions: 1-2 GG 0 EOP contingencies requiring substantive actions: 0-2 GG 2 EOP based Critical tasks: 2-3 COMMENTS: PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 28 of 29 15-01 NRC ESG-3 CT#1 (CT-3) Manually actuate at least one Containment Spray pump before an extreme challenge develops to the containment CSF. Basis: Failure to manually actuate the minimum required complement of containment cooling equipment under the postulated conditions demonstrates the inability of the crew to "recognize a failure or an incorrect automatic actuation of an ESF system or component." CT#2 (CT-33) Control the AFW rate to not less than 1E4 lbm/hr to minimize the cooldown rate. Basis: Failure to control the AFW flow rate to the SGs leads to an unnecessary and avoidable severe challenge to the integrity CSF. Also, failure to perform the critical task increases the challenges to the subcriticality and the containment CSFs beyond those irreparably introduced by the postulated plant conditions. Thus, failure to perform the critical task constitutes a demonstrated inability by the crew to "take one or more actions that would prevent a challenge to plant safety." It also fails to prevent "a significant reduction of safety margin beyond that irreparably introduced by the scenario." Note to Evaluator: CT numbers in parentheses are the corresponding Westinghouse ERG Rev. 2- based Critical Tasks procedure WCAP-17711-NP PSEG Restricted - Possession Requires Specific Permission from Nuclear Training

TQ-AA-106-0204 Page 29 of 29 ATTACHMENT 6

                                                       -      -

ESG.;PRA RELATIONSHIP EVALUATION EVENTS LEADING TO CORE DAMAGE Y/N Event Y/N Event N TRANSIENTS with PCS Unavailable N Loss of Service Water N Steam Generator Tube Rupture N Loss ofCCW N Loss of Offsite Power N Loss of Control Air N Loss of Switchgear and Pen Area Ventilation N Station Black Out N LOCA COMPONENT/TRAIN/SYSTEM UNAVAILABILITY THAT INCREASES CORE DAMAGE FREQUENCY Y/N COMPONENT, SYSTEM, OR TRAIN Y/N COMPONENT, SYSTEM, OR TD~ll\I N Containment Sump Strainers N Gas Turbine N SSWS Valves to Turbine Generator Area N Any Diesel Generator N RHR Suction Line valves from Hot Leg y Auxiliary Feed Pump N CVCS Letdown line Control and Isolation Valves N SBO Air Compressor OPERATOR ACTIONS IMPORTANT IN PREVENTING CORE DAMAGE Y/N OPERATOR ACTION N Restore AC power during SBO N Connect to gas turbine N Trip Reactor and RCPs after loss of component cooling system N Re-align RHR system for re-circulation N Un-isolate the available CCW Heat Exchanger N Isolate the CVCS letdown path and transfer charging suction to RWST N Cooldown the RCS and depressurize the system N Isolate the affected Steam Generator that has the tube rupture(s) N Early depressurize the RCS N Initiate feed and bleed Complete this evaluation form for each ESG.}}