ML030770832: Difference between revisions
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
||
| Line 3: | Line 3: | ||
| issue date = 03/18/2003 | | issue date = 03/18/2003 | ||
| title = Review of TSTF-445 Revision 1 | | title = Review of TSTF-445 Revision 1 | ||
| author name = Beckner W | | author name = Beckner W | ||
| author affiliation = NRC/NRR/DRIP/RORP | | author affiliation = NRC/NRR/DRIP/RORP | ||
| addressee name = Pietrangelo A | | addressee name = Pietrangelo A | ||
| addressee affiliation = Nuclear Energy Institute (NEI) | | addressee affiliation = Nuclear Energy Institute (NEI) | ||
| docket = | | docket = | ||
Revision as of 05:55, 14 July 2019
| ML030770832 | |
| Person / Time | |
|---|---|
| Issue date: | 03/18/2003 |
| From: | Beckner W NRC/NRR/DRIP/RORP |
| To: | Pietrangelo A Nuclear Energy Institute |
| Kavanagh, k. NRR, 415-3743 | |
| References | |
| Download: ML030770832 (4) | |
Text
March 18, 2003Mr. Anthony PietrangeloNuclear Energy Institute 1776 I Street, N. W.
Suite 400 Washington, DC 20006-3708
Dear Mr. Pietrangelo:
The Nuclear Regulatory Commission (NRC) has completed its review of the Nuclear EnergyInstitute Technical Specification Change Traveler, TSTF-445 Revision 1, "Revision to Peak Linear Heat Rate Safety Limit" proposed changes to NUREG-1432, Rev. 2, "Standard Technical Specifications Combustion Engineering Plants."TSTF-445 Revision 1 proposes to replace Technical Specification (TS) Safety Limit 2.1.1.2,"Peak Linear Heat Rate" with a "Peak Fuel Centerline Temperature" Safety Limit. This change is necessary such that the Safety Limit adequately conforms to 10 CFR 50.36(c)(1)(ii)(A) which requires that Limiting Safety System Settings prevent a Safety Limit from being exceeded during normal operations and Anticipated Operational Occurrences. This proposed change is consistent with the Westinghouse and B&W improved Standard Technical Specifications. The staff finds the proposed changes acceptable and applicable to both analog and digital plants.
The staff issued its safety evaluation approving TSTF-445 for plant-specific license amendment requests and for incorporation into NUREG-1432, Rev. 2, "Standard Technical Specifications Combustion Engineering Plants" by letter dated December 23, 2002. TSTF-445 Revision 1 provides a minor editorial change to the wording of the Safety Limit which does not result in a change to the staff's safety evaluation. As a matter of efficiency, the staff has chosen not to process TSTF-445 Revision 1 through the Consolidated Line Item Improvement Process (CLIIP) since there are relatively few licensees remaining that have not adopted this change.Please contact me at (301) 415-1161 or e-mail wdb@nrc.gov if you have any questions or needfurther information on these proposed changes.Sincerely,/RA/William D. Beckner, Program Director Operating Reactor Improvements Program Division of Regulatory Improvement Programs Office of Nuclear Reactor Regulationcc:T. Silko, BWROGD. Bice, CEOG P. Infanger, BWOG S. Wideman, WOG D. Hoffman, EXCEL B. Mann, EXCEL
ML030770832DOCUMENT NAME: G:\RORP\TSS\KAVANAGH\TSTF-445 R1 dispositionOFFICETSS:RORP:DRIPTSS:RORP:DRIPBC:PDIV:DLPMSC:TSS:DRIPPD:RORP:DRIPNAMEKAKavanaghLAHillHBerkowRLDennigWDBecknerDATE03/13/200303/13/200303/13/200303/14/200303/18/2003