| issue date = 08/07/2013 | | issue date = 08/07/2013 | ||
| title = | | title = MF0497 Request for Additional Information for Fermi 2 Proposed License Amendment to Revise the Fermi 2 Licensing Bases for Protection from Tornado-Generated Missiles | ||
| author name = Dion J | | author name = Dion J | ||
| author affiliation = NRC/NRR/DORL/LPLIII-1 | | author affiliation = NRC/NRR/DORL/LPLIII-1 | ||
| Line 12: | Line 12: | ||
| document type = E-Mail | | document type = E-Mail | ||
| page count = 3 | | page count = 3 | ||
| project = | |||
| stage = RAI | |||
}} | }} | ||
Revision as of 01:35, 8 February 2019
| ML13219A643 | |
| Person / Time | |
|---|---|
| Site: | Fermi |
| Issue date: | 08/07/2013 |
| From: | Dion J Plant Licensing Branch III |
| To: | Hassoun A I DTE Electric Company |
| References | |
| Download: ML13219A643 (3) | |
Text
1 NRR-PMDAPEm Resource From: Dion, Jeanne Sent: Wednesday, August 07, 2013 1:09 PM To: hassouna@dteenergy.com Cc: Wall, Scott; Smith, Edward; Re isifard, Mehdi; Dinsmore, Stephen
Subject:
MF0497 Request for Additional Information for Fermi 2 Proposed License Amendment to Revise the Fermi 2 Licensing Bases for Protection from Tornado-Generated Missiles Attachments:
MF0497_RAI.pdf Mr. Hassoun, By letter dated January 11, 2013, (Agencywide Documents Access and Management System (ADAMS) Accession No. ML13011A377), DTE Electr ic Company submitted its proposed license amendment to revise the Fermi 2 Licensing Bases for protection from tornado-generated missiles. The NRC staff in the Balance of Plant Branch (SBPB) and the Probabilistic Risk Assessment Licensing Branch (APLA) have ident ified areas in which additional information is needed to complete the Technical Review. The staff's Request for A dditional Information (RAI) is provided as an attachment to this email.
You may accept this as a formal request for additi onal information and respon d to the questions by September 20, 2013. Alte rnatively, you may request to discuss the content of t he RAIs with the NRC staff in a conference call, including any change to the proposed response date. Please let me know if you have any questions or concerns.
Jeanne Dion Project Manager (Rotation) NRR/DORL/LPL3-1 OWFN 8F8 301-415-1349
Hearing Identifier: NRR_PMDA Email Number: 798 Mail Envelope Properties (0B8884532E5C074E972B443F6E8F592E7DE6014CD9)
Subject:
MF0497 Request for Additional Information for Fermi 2 Proposed License Amendment to Revise the Fermi 2 Licensing Bases for Protection from Tornado-Generated Missiles Sent Date: 8/7/2013 1:09:29 PM Received Date: 8/7/2013 1:09:00 PM From: Dion, Jeanne Created By: Jeanne.Dion@nrc.gov Recipients: "Wall, Scott" <Scott.Wall@nrc.gov> Tracking Status: None "Smith, Edward" <Edward.Smith@nrc.gov> Tracking Status: None "Reisifard, Mehdi" <Mehdi.Reisifard@nrc.gov>
Tracking Status: None "Dinsmore, Stephen" <Stephen.Dinsmore@nrc.gov> Tracking Status: None "hassouna@dteenergy.com" <hassouna@dteenergy.com> Tracking Status: None
Post Office: HQCLSTR01.nrc.gov Files Size Date & Time MESSAGE 1050 8/7/2013 1:09:00 PM MF0497_RAI.pdf 74961
Options Priority: Standard Return Notification: No Reply Requested: No Sensitivity: Normal Expiration Date: Recipients Received:
REQUEST FOR ADDITIONAL INFORMATION FERMI NUCLEAR POWER STATION, UNIT 2 PROPOSED LICENSE AMENDMENT TO REVISE THE LICENSING BASES FOR PROTECTION FROM TORNADO-GENERATED MISSILES DOCKET NUMBERS 50-341 RAI 1 Section 2.0, 2nd paragraph states: methodology, the probability of multiple missile strikes causing unacceptable damage to unprotected, safety-related plant features Describe what Fermi has done to address the potential damage of safety-related equipment caused by the failure of non-safety related equipment due to a tornado missile strike.
An example would be a tornado missile that damages a non-safety related tank and causes water leakage which subsequently damages safety-related cables.
RAI 2 Section 3.0, page 6, states Missile sources (building) were catalogued and modeled to a distance of approximately 2,500 feet.
What is the basis of 2,500 feet? RAI 3 Section 3.0, page 13 states: the EDG fuel oil tank vents and the EDG exhaust stacks, which are located on the roof of the RHR complex. Both of these rooftop features are provided with tornado missile shield protection specifically designed to prevent vertically traveling missiles from entering the RHR complex and damaging the EDG fuel oil tanks and diesel engines.
Are the vent stacks protected from horizontally traveling missiles? A missile traveling horizontally could crimp the vent to significantly reduce air flow and prevent the EDG fuel oil tanks and diesel engines from functioning properly. RAI 4 Clarify if the methodology used in this submittal for calculating the mean aggregate tornado missile damage probability uses any logic (e.g., AND gates) that requires damaging multiple targets simultaneously for establishing a damaged state. If multiple targets need to be simultaneously struck, please summarize the guidelines used to identify such groups and explain how they are modeled in TORMIS.