{{#Wiki_filter:Nine Mile Point Unit 2 Primary Containment 305' 9"          3, 660,000 gal 298' 6" (TAF) 288' 3 1/4"                                                                                                                                         3, 260,000 gal 267' 11 7/8" 261' 0"                                                                                                                                                      2, 440,000 gal 1, 990,000 gal
{{#Wiki_filter:This region ~ 46,000 gal/ft 176' 0 3/8" 190' 0" 200' 0" Normal SP Level 232' 6" 240' 6" 267' 11 7/8" 261' 0" 227' 0" 288' 3 1/4" 305' 9" 181' 0" Indicated level range 192' to 217' 1, 650,000 gal 0 (199' 6") TS LL 1, 990,000 gal 2, 440,000 gal 3, 260,000 gal 3, 660,000 gal P
                                                                                              ~ 6  downcomer                                                                  240' 6" 1, 650,000 gal spillover height Vacuum Breaker (4) 232' 6" Loss of Wetwell Vent Function - 1,242,000 Gallons                                                 227' 0" 224' 0"      P Top of Wetwell Level Instrument - 782,000 Gallons This region ~ 46,000 gal/ft Estimated Maximum SAWM Level at 168 hours - 276,000 Gallons Indicated level range 192' to 217' 200' 0" 0 (199' 6") TS LL Normal SP Level Rate of rise with SAWA flow at 300 gpm is 0.39 feet per hour*
224' 0" 298' 6" (TAF)
Vacuum Breaker (4)
Nine Mile Point Unit 2 Primary Containment
~ 6 downcomer spillover height Estimated Maximum SAWM Level at 168 hours - 276,000 Gallons Top of Wetwell Level Instrument - 782,000 Gallons Loss of Wetwell Vent Function - 1,242,000 Gallons Rate of rise with SAWA flow at 300 gpm is 0.39 feet per hour*
Rate of rise with SAWA flow at 100 gpm is 0.13 feet per hour*
Rate of rise with SAWA flow at 100 gpm is 0.13 feet per hour*
* Does not consider mass loss rate of steam leaving containment through wetwell vent path.
* Does not consider mass loss rate of steam leaving containment through wetwell vent path.
190' 0" Nominal Water Volume - 1,104,000 Gallons 181' 0" 176' 0 3/8"
Nominal Water Volume - 1,104,000 Gallons


DISTRIBUTION MANIFOLD TO BE OPERATED FROM THE RB TRACK BAY OR HOIST WELL AREA ON ELEVATION 261' 2 Inlets:
SFP Make Up (Monitor Nozzle can be used on this connection)
2.5" NH(m) x 2" NPT adaptor and 2" gate valve Discharge Manifold Inlet = 3" 350# flange, Outlet = 2.5" NST (f)        4 Outlets:
SFP From Discharge Bay From CWS 2SWP*V900 2SWP-V902 2SWP-TV512 2SWP-V905 2SWP-V904 2SWP-V903 CROSS TIE BELOW LOW LAKE LEVEL TO ENSURE EACH SUCTION POINT REMAINS SUBMERGED 2RHS*MOV40A 2RHS*MOV24A 2RHS*16A 2RHS*39A 2RHS*V304 2RHS*V248 2RHS*V249 TO DIV 2 SFP SPARGER SIZED TO SUPPLY SFP (FLEX/SAWA)
1-1/2 NH (female) x 2" NPT adaptor with 2" globe valve to RPV (FLEX)
DISTRIBUTION MANIFOLD TO BE OPERATED FROM THE RB TRACK BAY OR HOIST WELL AREA ON ELEVATION 261' New Penetrations through Screenwell Wall below grade (Typ - 2) 3" Hose w/ 2.5" NST (m x f) ends Estimated L = 800 feet By Pump Vendor 3" Hose w/ 2.5" NST(f x m) end Estimated Length = 1,200 feet 2 Inlets:
Note that a pressure        1-1/2 NH (female) x 1-1/2 NPT adaptor with 1-1/2" globe valve to SFP (FLEX/SAWA) gauge can be installed        2-1/2 NH (female) x 3" NPT adaptor with 3" globe valve to RPV (SAWA)
2.5" NH(m) x 2" NPT adaptor and 2" gate valve 4 Outlets:
By Pump                at one of the available        2-1/2 NH(m) x 2" NPT adaptor and 2" gate valve to Recirculation Line Screenwell Wall Below                            4" Flange x 6" Cam      Vendor                  outlets to monitor                                                                                                                                                                                                              PID 004-B Grade Elevation                              and Groove Adaptor pump discharge pressure.
1-1/2 NH (female) x 2" NPT adaptor with 2" globe valve to RPV (FLEX) 1-1/2 NH (female) x 1-1/2 NPT adaptor with 1-1/2" globe valve to SFP (FLEX/SAWA) 2-1/2 NH (female) x 3" NPT adaptor with 3" globe valve to RPV (SAWA) 2-1/2 NH(m) x 2" NPT adaptor and 2" gate valve to Recirculation Line 2SWP-V906 (3/4 Drain)
3" Check                                                                                                                                                                                              1-1/2 NHS (male) / THREADED CAP Valve                                                                                                                                                                                              NORMALLY INSTALLED MISSILLE BARRIER Priming System                                                                            SIZED TO                                                    2" Hose w/ 1.5" NST                                LOOP B / DIVISION 2                    2-RHS-003-120-2 (B-)
Perforated Pipe (Total of 80 x 1" Holes)
New Penetrations through Screenwell Wall                      2SWP-V1268                                                                                                                                                                                                                                                        2RHS*V79 SUPPLY SFP                                                        (m x f) ends below grade (Typ - 2)
Intake Structure Wall 2-SWP-016-01H-4 (SHUTDOWN TEMPERING) 2-SWP-016-01G-4 2CNS-V621 2-RHS-003-117-2 (A-)
(FLEX/SAWA)                                                        Estimated L = 200 feet PID 004-B BDB-P2A (B, C, D, E) 3" Hose w/ 2.5" NST                                                                                                                                2-CNS-003-905-4 Single Pump 300 GPM Capacity                                              (m x f) ends Estimated L = 800 feet                SIZED TO SUPPLY RPV 2CNS-V622 FOR FLEX                              2-1/2 NHS (male) /
2-CNS-003-080-4 2-RHS-016-005-2 (A-)
6" Male CAM                                                                                                                                                  3" Hose w/                                                                    PID 031-A                                                  PID 031-A / 031-B 2.5" NST        THREADED CAP and Groove                                                                                                                                                                    NORMALLY INSTALLED                                                          2ICS*V157      2ICS*V156 ADAPTER X                                                                                                                                                  (m x f) ends FEMALE NPT                                                                                                                                                    Estimated 2RHS*MOV104 6" Hose w/ cam                                                                                                                    L = 200 feet                                                                                                                            2-RHS-006-141-2 (B-)
NOTE ON FITTINGS:
and groove fittings Estimated                                                                                                          SIZED TO L = 50 feet                                                                                                      SUPPLY RPV                                                                    2-RHS-016-005-2 (A-)
FOR SAWA Minimum Flow /                                                                      2-RHS-003-117-2 (A-)
Freeze                                                                                                      2RHS*MOV24A    2RHS*16A                        2RHS*16B Protection                  FLOW METER                                                  LOOP A /
6" PIPE                                                                                                                                                                                                                                    DIVISION 1                                                                      2RHS*MOV24B 2SWP-V1269                                                                                                                                    1                      2                3            2RHS*V70                  4 2RHS*MOV40A 5
2RHS*39A                        2RHS*39B 2RHS*MOV40B 2-CNS-003-080-4 2CNS-V621 BDB-P2B (A, C, D, E)                                                                                                                                                            2RHS*V304 CROSS TIE BELOW LOW LAKE LEVEL TO ENSURE EACH SUCTION POINT                                                                                                                                                                                                                                                                                                                                        2RHS*V249 REMAINS SUBMERGED                                                                                                                                                                                  3" Hose w/ 2.5" NST(f x m) end Outside Screenwell                                                                                          Estimated Length = 1,200 feet                                                                                    2-RHS-008-297-2(B-)
Basement              Two Pump 500 GPM Capacity                                                                                                                                                                                                                                          2-RHS-008-287-2(B-)
2RHS*V309                                  2RHS*V248 3" Hose w/ 2.5" NST(f x m) end Estimated Length = 200 feet each 2SWP-V1267 From CWS                                                                                                                                                                                                                                                                                        SFP Make Up (Monitor Nozzle can be used on this connection) 2SWP-V902                        2SWP-V1266 2-SWP-016-01G-4                                                2SWP-V905          Intake Structure Wall OPERATOR ACTIONS ON PID 011-H 2SWP*V900                                                                                                                                                                                                                                                                                                                                                    SFP OPEN BARRIER DOOR From Discharge                                                                                                                                            OPEN VACUUM BREAKER VALVES 2SWP-V1268 AND 2SWP-V1269 Bay                                                                                                                                                  REMOVE CAPS AND ATTACH SUCTION HOSE                                                                            Valved Splitter 2SWP-V903                                                                                                            CLOSE VACUUM BREAKER VALVES 2SWP-V1268 AND 2SWP-V1269                                                          2.5" NST(f) inlet, 2-SWP-016-01H-4                                                                                                                                                                                                                                                      2 x 2.5" NST(m)                      TO DIV 1 SFP SPARGER                    TO DIV 2 SFP SPARGER Perforated Pipe                                                                                                                                                                      outlets (SHUTDOWN TEMPERING) 2SWP-V904          (Total of 80 x 1" Holes)                                        OPERATOR ACTIONS ON PID 004-B 2SWP-V906                                                                                                                                                                                                                                                                              PID 038-A                             PID 038-B (3/4 Drain)    2SWP-TV512 SAWA PATH TO RPV VIA LOOP A / DIV 1 RHS PIPING MANUALLY REMOVE THREADED CAP AND INSTALL HOSE FITTING(S)
MANUALLY CLOSE VALVE 2CNS-V621                                                                                                                    LEGEND - SAWA FLOW PATHS MANUALLY OPEN VALVE 2RHS*V70 PID 011-H SAWA PATH TO RPV VIA LOOP A / DIVISION 1 RHS OPERATOR ACTIONS ON PID 031-A / 031-B
: 1. SAWA in-line flow meter                                                                                                                            SAWA PATH TO RPV PIPING AND VALVE 2RHS*MOV24A Remote Manual - Open 2RHS*MOV24A
: 2. 200' of 3" hose TWO PUMP SAWA CONFIGURATION (OPTIONAL)
: 3. Local manual valve - Open 4 Power operated remote manual valve - Open                                                                                                                                                                                                                            NOTE ON FITTINGS:
NH = NHS = Threaded fitting sealed with gasket.
NH = NHS = Threaded fitting sealed with gasket.
: 5. SAWA backflow prevention check valve - PCIV                                                                                                                                                                                                                        Typical fire hose connection NPT = Threaded fitting where threads do the sealing.
Typical fire hose connection NPT = Threaded fitting where threads do the sealing.
Storz = Latching hose fitting
Storz = Latching hose fitting 6" Hose w/ cam and groove fittings Estimated L = 50 feet 6" Male CAM and Groove ADAPTER X FEMALE NPT Screenwell Wall Below Grade Elevation Outside Screenwell Basement PID 011-H PID 004-B PID 031-A 2RHS*MOV24B 2RHS*16B 2RHS*MOV40B 2RHS*39B 2RHS*MOV104 2ICS*V156 2ICS*V157 2-RHS-006-141-2 (B-)
2-RHS-003-120-2 (B-)
2CNS-V622 2-CNS-003-905-4 PID 004-B PID 031-A / 031-B 2-RHS-008-287-2(B-)
2RHS*V309 2-RHS-008-297-2(B-)
TO DIV 1 SFP SPARGER SIZED TO SUPPLY RPV FOR SAWA 3" Check Valve Priming System BDB-P2A (B, C, D, E) 4" Flange x 6" Cam and Groove Adaptor 2" Hose w/ 1.5" NST (m x f) ends Estimated L = 200 feet 3" Hose w/
2.5" NST (m x f) ends Estimated L = 200 feet 1-1/2 NHS (male) / THREADED CAP NORMALLY INSTALLED 2-1/2 NHS (male) /
THREADED CAP NORMALLY INSTALLED PID 038-B PID 038-A MISSILLE BARRIER BDB-P2B (A, C, D, E)
Minimum Flow /
Freeze Protection SAWA PATH TO RPV VIA LOOP A / DIVISION 1 RHS PIPING AND VALVE 2RHS*MOV24A LEGEND - SAWA FLOW PATHS OPERATOR ACTIONS ON PID 004-B SAWA PATH TO RPV VIA LOOP A / DIV 1 RHS PIPING MANUALLY REMOVE THREADED CAP AND INSTALL HOSE FITTING(S)
MANUALLY CLOSE VALVE 2CNS-V621 MANUALLY OPEN VALVE 2RHS*V70 OPERATOR ACTIONS ON PID 031-A / 031-B SAWA PATH TO RPV Remote Manual - Open 2RHS*MOV24A 2SWP-V1267 2SWP-V1266 LOOP A /
DIVISION 1 2RHS*V70 LOOP B / DIVISION 2 2RHS*V79 Discharge Manifold Inlet = 3" 350# flange, Outlet = 2.5" NST (f)
Note that a pressure gauge can be installed at one of the available outlets to monitor pump discharge pressure.
2SWP-V1269 2SWP-V1268 OPERATOR ACTIONS ON PID 011-H OPEN BARRIER DOOR OPEN VACUUM BREAKER VALVES 2SWP-V1268 AND 2SWP-V1269 REMOVE CAPS AND ATTACH SUCTION HOSE CLOSE VACUUM BREAKER VALVES 2SWP-V1268 AND 2SWP-V1269 SIZED TO SUPPLY RPV FOR FLEX 6" PIPE FLOW METER Valved Splitter 2.5" NST(f) inlet, 2 x 2.5" NST(m) outlets 3" Hose w/ 2.5" NST(f x m) end Estimated Length = 200 feet each Single Pump 300 GPM Capacity Two Pump 500 GPM Capacity
: 1. SAWA in-line flow meter
: 2. 200' of 3" hose
: 3. Local manual valve - Open 4 Power operated remote manual valve - Open
: 5. SAWA backflow prevention check valve - PCIV 1
2 3
4 5
TWO PUMP SAWA CONFIGURATION (OPTIONAL)


NMP Unit 2 FLEX DG Connection Control Building, Elevation 261'                                                                                     600VAC 2EJS*US1 BCD                            600A                                600A                                600A*                                600A*                            600A*
SARGENT & LUNDY LLC MASTER DIAGRAM 450kW/562.5kVA Portable DG South Corridor of the Control Building Control Building, Elevation 261' Portable DG to be located in the courtyard (El. 261' Southeast of Standby SWGR Rooms) 600VAC 2EJS*US1 BCD (Note 1) 600A*
(Note 1)
600A Portable Cable consist of three parallel sets of 2 - 1/C #4/0 AWG and 1/C 500 MCM TPC cables 2LAC*PNL100A 2EJS*PNL100A 2EHS*MCC103 Option 1 (Primary)
South Corridor of the Control Building Note 2 Female Locking Connector Portable DG to be located in the                                                                                                 (Typ. For Portable Cables courtyard (El. 261' Southeast of                                                                                                 Connecting End at BCDs) 2-1/C #4/0 TPC cables Standby SWGR Rooms)                                 (240') per phase Male Locking 2EHS*MCC102                    2EHS*MCC101 2LAC*PNL100A Connectors 2EJS*PNL100A                        2EHS*MCC103 Option 1 450kW/562.5kVA                                          (Primary)
Option 2 (Alternate)
Portable DG Cable Splitter 1/C 500MCM TPC cable per phase (10')
Female Locking Connectors
* 2EHS*MCC101, 2EHS*MCC102 Option 2                                                                                                                                                                                                                                                                                                            and 2EHS*MCC103 are each fed by (Alternate)                    Standby SWGR Room Div. I                                                                                                        1/C #4/0 neutral/ground                                                                                                                            two (2) separate 600A breakers (one MASTER DIAGRAM (250')                                                                                                                                              normally open and one normally closed)
Portable Cable Lengths:                                                                              Standby SWGR Room Div. II                                                                                                                                                                                                                                                            ** 2EHS*MCC301, 2EHS*MCC302 and 2EHS*MCC303 are each fed by Option 1: Total estimated length of 250'                                                                                                                                                                                                                                                                                                                                                  two (2) separate 600A breakers (one 600VAC 2EJS*US3                                                                                                                                                                                        normally open and one normally Option 2: Total estimated length of 200'                                                                                                                                                                                                                                                                                                                                                  closed)
BCD                                      600A                                600A                              600A**                              600A**                          600A**
2-1/C #4/0 TPC cables                                                                                                 (Note 1)
(190') per phase Note 2 Female Locking Connector (Typ. For Portable Cables Connecting End at BCDs) 2EHS*MCC302                    2EHS*MCC301 2LAC*PNL300B                        2EJS*PNL300B                        2EHS*MCC303 1/C 500MCM TPC cable Cable Splitter          per phase (10')
SARGENT & LUNDY LLC 1/C #4/0 neutral/ground (250')
LEGEND:
LEGEND:
Note:
Note:
1.) Existing future space , cubicle 5C will be used for connection via a Bus Connection Device (BCD).
1.) Existing future space, cubicle 5C will be used for connection via a Bus Connection Device (BCD).
Portable Cable consist of three parallel sets of 2 - 1/C #4/0 AWG and  The BCD is non-safety related (NSR) and will be equipped with (1) TPC male locking receptacle, Model 1/C 500 MCM TPC cables                                                  # PA22MR, per phase.
The BCD is non-safety related (NSR) and will be equipped with (1) TPC male locking receptacle, Model  
# PA22MR, per phase.
2.) Portable DG neutral to be grounded at the Switchgear neutral/ground bus.
2.) Portable DG neutral to be grounded at the Switchgear neutral/ground bus.
1/C #4/0 AWG TPC Cables for portable DG system grounding
Female Locking Connector (Typ. For Portable Cables Connecting End at BCDs)
                                                                                  .}}
Female Locking Connectors Male Locking Connectors Portable Cable Lengths:
Option 1: Total estimated length of 250' Option 2: Total estimated length of 200' 2EHS*MCC102 2EHS*MCC101 600A 600A*
600A*
600VAC 2EJS*US3 BCD (Note 1) 600A**
600A 2LAC*PNL300B 2EJS*PNL300B 2EHS*MCC303 2EHS*MCC302 2EHS*MCC301 600A 600A**
600A**
Female Locking Connector (Typ. For Portable Cables Connecting End at BCDs)
Standby SWGR Room Div. I Standby SWGR Room Div. II Cable Splitter Cable Splitter 2-1/C #4/0 TPC cables (190') per phase 2-1/C #4/0 TPC cables (240') per phase 1/C 500MCM TPC cable per phase (10')
1/C 500MCM TPC cable per phase (10')
1/C #4/0 neutral/ground (250')
1/C #4/0 neutral/ground (250')
Note 2 Note 2 1/C #4/0 AWG TPC Cables for portable DG system grounding
* 2EHS*MCC101, 2EHS*MCC102 and 2EHS*MCC103 are each fed by two (2) separate 600A breakers (one normally open and one normally closed)
** 2EHS*MCC301, 2EHS*MCC302 and 2EHS*MCC303 are each fed by two (2) separate 600A breakers (one normally open and one normally closed)
NMP Unit 2 FLEX DG Connection}}

Latest revision as of 09:20, 10 January 2025

Diagrams - August 25, 2015 Meeting
ML15237A014
Person / Time
Site: Nine Mile Point Constellation icon.png
Issue date: 08/25/2015
From:
Niagara Mohawk Power Corp
To:
Office of Nuclear Reactor Regulation
Auluck R, NRR/JLD, 415-1025
References
Download: ML15237A014 (3)


Text

This region ~ 46,000 gal/ft 176' 0 3/8" 190' 0" 200' 0" Normal SP Level 232' 6" 240' 6" 267' 11 7/8" 261' 0" 227' 0" 288' 3 1/4" 305' 9" 181' 0" Indicated level range 192' to 217' 1, 650,000 gal 0 (199' 6") TS LL 1, 990,000 gal 2, 440,000 gal 3, 260,000 gal 3, 660,000 gal P

224' 0" 298' 6" (TAF)

Vacuum Breaker (4)

Nine Mile Point Unit 2 Primary Containment

~ 6 downcomer spillover height Estimated Maximum SAWM Level at 168 hours0.00194 days <br />0.0467 hours <br />2.777778e-4 weeks <br />6.3924e-5 months <br /> - 276,000 Gallons Top of Wetwell Level Instrument - 782,000 Gallons Loss of Wetwell Vent Function - 1,242,000 Gallons Rate of rise with SAWA flow at 300 gpm is 0.39 feet per hour*

Rate of rise with SAWA flow at 100 gpm is 0.13 feet per hour*

  • Does not consider mass loss rate of steam leaving containment through wetwell vent path.

Nominal Water Volume - 1,104,000 Gallons

SFP Make Up (Monitor Nozzle can be used on this connection)

SFP From Discharge Bay From CWS 2SWP*V900 2SWP-V902 2SWP-TV512 2SWP-V905 2SWP-V904 2SWP-V903 CROSS TIE BELOW LOW LAKE LEVEL TO ENSURE EACH SUCTION POINT REMAINS SUBMERGED 2RHS*MOV40A 2RHS*MOV24A 2RHS*16A 2RHS*39A 2RHS*V304 2RHS*V248 2RHS*V249 TO DIV 2 SFP SPARGER SIZED TO SUPPLY SFP (FLEX/SAWA)

DISTRIBUTION MANIFOLD TO BE OPERATED FROM THE RB TRACK BAY OR HOIST WELL AREA ON ELEVATION 261' New Penetrations through Screenwell Wall below grade (Typ - 2) 3" Hose w/ 2.5" NST (m x f) ends Estimated L = 800 feet By Pump Vendor 3" Hose w/ 2.5" NST(f x m) end Estimated Length = 1,200 feet 2 Inlets:

2.5" NH(m) x 2" NPT adaptor and 2" gate valve 4 Outlets:

1-1/2 NH (female) x 2" NPT adaptor with 2" globe valve to RPV (FLEX) 1-1/2 NH (female) x 1-1/2 NPT adaptor with 1-1/2" globe valve to SFP (FLEX/SAWA) 2-1/2 NH (female) x 3" NPT adaptor with 3" globe valve to RPV (SAWA) 2-1/2 NH(m) x 2" NPT adaptor and 2" gate valve to Recirculation Line 2SWP-V906 (3/4 Drain)

Perforated Pipe (Total of 80 x 1" Holes)

Intake Structure Wall 2-SWP-016-01H-4 (SHUTDOWN TEMPERING) 2-SWP-016-01G-4 2CNS-V621 2-RHS-003-117-2 (A-)

2-CNS-003-080-4 2-RHS-016-005-2 (A-)

NOTE ON FITTINGS:

NH = NHS = Threaded fitting sealed with gasket.

Typical fire hose connection NPT = Threaded fitting where threads do the sealing.

Storz = Latching hose fitting 6" Hose w/ cam and groove fittings Estimated L = 50 feet 6" Male CAM and Groove ADAPTER X FEMALE NPT Screenwell Wall Below Grade Elevation Outside Screenwell Basement PID 011-H PID 004-B PID 031-A 2RHS*MOV24B 2RHS*16B 2RHS*MOV40B 2RHS*39B 2RHS*MOV104 2ICS*V156 2ICS*V157 2-RHS-006-141-2 (B-)

2-RHS-003-120-2 (B-)

2CNS-V622 2-CNS-003-905-4 PID 004-B PID 031-A / 031-B 2-RHS-008-287-2(B-)

2RHS*V309 2-RHS-008-297-2(B-)

TO DIV 1 SFP SPARGER SIZED TO SUPPLY RPV FOR SAWA 3" Check Valve Priming System BDB-P2A (B, C, D, E) 4" Flange x 6" Cam and Groove Adaptor 2" Hose w/ 1.5" NST (m x f) ends Estimated L = 200 feet 3" Hose w/

2.5" NST (m x f) ends Estimated L = 200 feet 1-1/2 NHS (male) / THREADED CAP NORMALLY INSTALLED 2-1/2 NHS (male) /

THREADED CAP NORMALLY INSTALLED PID 038-B PID 038-A MISSILLE BARRIER BDB-P2B (A, C, D, E)

Minimum Flow /

Freeze Protection SAWA PATH TO RPV VIA LOOP A / DIVISION 1 RHS PIPING AND VALVE 2RHS*MOV24A LEGEND - SAWA FLOW PATHS OPERATOR ACTIONS ON PID 004-B SAWA PATH TO RPV VIA LOOP A / DIV 1 RHS PIPING MANUALLY REMOVE THREADED CAP AND INSTALL HOSE FITTING(S)

MANUALLY CLOSE VALVE 2CNS-V621 MANUALLY OPEN VALVE 2RHS*V70 OPERATOR ACTIONS ON PID 031-A / 031-B SAWA PATH TO RPV Remote Manual - Open 2RHS*MOV24A 2SWP-V1267 2SWP-V1266 LOOP A /

DIVISION 1 2RHS*V70 LOOP B / DIVISION 2 2RHS*V79 Discharge Manifold Inlet = 3" 350# flange, Outlet = 2.5" NST (f)

Note that a pressure gauge can be installed at one of the available outlets to monitor pump discharge pressure.

2SWP-V1269 2SWP-V1268 OPERATOR ACTIONS ON PID 011-H OPEN BARRIER DOOR OPEN VACUUM BREAKER VALVES 2SWP-V1268 AND 2SWP-V1269 REMOVE CAPS AND ATTACH SUCTION HOSE CLOSE VACUUM BREAKER VALVES 2SWP-V1268 AND 2SWP-V1269 SIZED TO SUPPLY RPV FOR FLEX 6" PIPE FLOW METER Valved Splitter 2.5" NST(f) inlet, 2 x 2.5" NST(m) outlets 3" Hose w/ 2.5" NST(f x m) end Estimated Length = 200 feet each Single Pump 300 GPM Capacity Two Pump 500 GPM Capacity

1. SAWA in-line flow meter
2. 200' of 3" hose
3. Local manual valve - Open 4 Power operated remote manual valve - Open
5. SAWA backflow prevention check valve - PCIV 1

2 3

4 5

TWO PUMP SAWA CONFIGURATION (OPTIONAL)

SARGENT & LUNDY LLC MASTER DIAGRAM 450kW/562.5kVA Portable DG South Corridor of the Control Building Control Building, Elevation 261' Portable DG to be located in the courtyard (El. 261' Southeast of Standby SWGR Rooms) 600VAC 2EJS*US1 BCD (Note 1) 600A*

600A Portable Cable consist of three parallel sets of 2 - 1/C #4/0 AWG and 1/C 500 MCM TPC cables 2LAC*PNL100A 2EJS*PNL100A 2EHS*MCC103 Option 1 (Primary)

Option 2 (Alternate)

LEGEND:

Note:

1.) Existing future space, cubicle 5C will be used for connection via a Bus Connection Device (BCD).

The BCD is non-safety related (NSR) and will be equipped with (1) TPC male locking receptacle, Model

  1. PA22MR, per phase.

2.) Portable DG neutral to be grounded at the Switchgear neutral/ground bus.

Female Locking Connector (Typ. For Portable Cables Connecting End at BCDs)

Female Locking Connectors Male Locking Connectors Portable Cable Lengths:

Option 1: Total estimated length of 250' Option 2: Total estimated length of 200' 2EHS*MCC102 2EHS*MCC101 600A 600A*

600A*

600VAC 2EJS*US3 BCD (Note 1) 600A**

600A 2LAC*PNL300B 2EJS*PNL300B 2EHS*MCC303 2EHS*MCC302 2EHS*MCC301 600A 600A**

600A**

Female Locking Connector (Typ. For Portable Cables Connecting End at BCDs)

Standby SWGR Room Div. I Standby SWGR Room Div. II Cable Splitter Cable Splitter 2-1/C #4/0 TPC cables (190') per phase 2-1/C #4/0 TPC cables (240') per phase 1/C 500MCM TPC cable per phase (10')

1/C 500MCM TPC cable per phase (10')

1/C #4/0 neutral/ground (250')

1/C #4/0 neutral/ground (250')

Note 2 Note 2 1/C #4/0 AWG TPC Cables for portable DG system grounding

  • 2EHS*MCC101, 2EHS*MCC102 and 2EHS*MCC103 are each fed by two (2) separate 600A breakers (one normally open and one normally closed)
    • 2EHS*MCC301, 2EHS*MCC302 and 2EHS*MCC303 are each fed by two (2) separate 600A breakers (one normally open and one normally closed)

NMP Unit 2 FLEX DG Connection