ML20216F018: Difference between revisions
StriderTol (talk | contribs) (StriderTol Bot insert) |
StriderTol (talk | contribs) (StriderTol Bot change) |
||
| Line 17: | Line 17: | ||
=Text= | =Text= | ||
{{#Wiki_filter:LOIA | {{#Wiki_filter:l LOIA REV 07 (MC) | ||
l | AP-470 l | ||
!O l | !O l | ||
LOSS OF INSTRUMENT AIR l | |||
O | 1.0 ENTRY CONDITIONS INFORMATION 1E IA PRESS is s 90 psig, ONLY l | ||
l | JREN use this procedure. | ||
L 2.0 IMMEDIATE ACTIONS HOIE There are no imediate actions for this procedure. | |||
l I | |||
AP-470 | O i | ||
l A | |||
Approved by NNP0 | |||
[e[U/b-Date 04/08/98 | |||
'' (SIGNATURE ON FILE) | |||
AP-470 PAGE 1 of 27 LOIA l | |||
9804160378 980409 PDR ADOCK 05000302 P | |||
PDR | |||
l l | l l | ||
I O | I O | ||
O i | |||
BLANK PAGE p | BLANK PAGE p | ||
(' | (' | ||
O | V O | ||
o AP-470 REV 07 (MC) | |||
PAGE 2 0F 27 LOIA | |||
3.0 | 3.0 FOLLOW-UP ACTIONS r) | ||
't | |||
/ | |||
ACTIONS DETAILS 3.1 Ensure in-house air g g-compressors are running. | |||
SAP-1B IAP-1A IAP-1B i | SAP-1B IAP-1A IAP-1B i | ||
3.2 Notify personnel of plant STA conditions. | |||
1 Plant operators NSM e | |||
HP (notify of degraded IA conditions as a precaution for personnel using breathing air) k.) | |||
Announce on PA " Terminate all use of station air". | |||
l l | l l | ||
l | i l | ||
AP-470 REV 07 (MC) | |||
l | PAGE 3 0F 27 LOIA l | ||
l O | l O | ||
Oi I | |||
l | l c-1 l | ||
c-1 | 1 l | ||
l l | l l | ||
l | l | ||
) | |||
'O | 'O C | ||
AP-470 REV 07 (MC) | |||
PAGE 4 0F 27 LOIA l | |||
3.0 FOLLOW-UP ACTIONS (CONT'D) | 3.0 FOLLOW-UP ACTIONS (CONT'D) | ||
ACTIONS | ACTIONS DETAILS 3.3 Notify SP0 to start berm l | ||
air compressors. | |||
SAP-lC SAP-ID l | |||
SAP-lE | |||
'I 1 | |||
control of DHR cooling, l | i I | ||
3.4 __ J1 at any time, DHR is in 1 | |||
l | J1 A DHR Train is in service, i | ||
!N | : service, M notify PP0 to manually l | ||
DCV-18 "B DH Cooler Bypass Control" | E IA PRESS < 80 psig, throttle the following valves l | ||
DCV-178 "B DH Cooler Outlet l | l M establish manual (75 ft AB A DH Room): | ||
l 3.5 | control of DHR cooling, l | ||
3 | M GO TO Step 3.27 in DCV-17 "A DH Cooler Bypass this procedure Control" DCV-177 "A DH Cooler Outlet Control" l | ||
O AP-470 | l 2 | ||
JF B DHR Train is in service, | |||
!N M notify PP0 to manually throttle the following valves l | |||
(75 ft AB B DH Room): | |||
DCV-18 "B DH Cooler Bypass Control" DCV-178 "B DH Cooler Outlet l | |||
Control" 3 | |||
GO TO Step 3.27 in this procedure. | |||
l 3.5 JF at any time, IA PRESS 1 | |||
Depress Rx trip push button is < 80 psig, E any abnormal system 2 | |||
CONCURRENTLY PERFORM E0P-2, operation exists, Vital System Status M trip Rx and Verification, beginning with I | |||
GO TO Step 3.11 in this Step 2.1 procedure. | |||
3 GO TO Step 3.11 in this procedure. | |||
O AP-470 REV 07 (MC) | |||
PAGE 5 0F 27 LOIA | |||
i Applicable carry-over steps: | i Applicable carry-over steps: | ||
CN | CN 4, 'j E DHR is in service AND IA PRESS < 80 psig... | ||
' | 3.4 | ||
4 | : i. ;. r l | ||
3.5 E lA PRESS is < 80 psig MQ abnormal system operation exists... | |||
1 l | 1 l | ||
l l | l l | ||
l l | l l | ||
, ' ~ | |||
v f | |||
t l | |||
l l | l l | ||
l l | l l | ||
l l | l l | ||
l t | l t | ||
i v | |||
\ | t AP-470 REV 07 (MC) | ||
PAGE 6 0F 27 LOIA | |||
\\ | |||
L4 FOLLOW-UP ACTIONS (CONT'D) | L4 FOLLOW-UP ACTIONS (CONT'D) | ||
Ob ACTIONS DETAILS 3.6 1E at any time, IA PRESS is > 90 psig, IliEt{ EXIT this procedure. | |||
3.7 | 3.7 Bypass IA dryers. | ||
* Notify SP0 to open IAV-31 "IADR-1 & | * Notify SP0 to open IAV-31 "IADR-1 & | ||
1ADR-1). | j IADR-2 Bypass Iso" (95 ft TB behind 1ADR-1). | ||
3.8 | 3.8 Place both IA dryer | ||
* Notify SP0 to ensure all the prefilters and | * Notify SP0 to ensure all the prefilters and following valves are open afterfilters in service. | ||
(95 ft TB by IADR-1): | |||
IAV-Il "Prefilter IAFL-2A Inlet Iso" IAV-12 "Prefilter IAFL-2B Inlet | IAV-Il "Prefilter IAFL-2A Inlet Iso" IAV-12 "Prefilter IAFL-2B Inlet | ||
\pj | \\pj Iso" IAV-14 "Prefilter IAFL-2B Outlet Iso" IAV-544 "Prefilter IAFL-2A Outlet Iso" IAV-18 "Afterfilter IAFL-3B Inlet Iso" IAV-545 "Afterfilter IAFL-3A Inlet Iso" IAV-19 "Afterfilter IAFL-3A Outlet Iso" | ||
__ IAV-20 "Afterfilter IAFL-3B Outlet Iso" O | __ IAV-20 "Afterfilter IAFL-3B Outlet Iso" O | ||
AP-470 | AP-470 REV 07 (MC) | ||
PAGE 7 0F 27 LOIA | |||
r | r 1 | ||
i Applicable carry-over steps: | i Applicable carry-over steps: | ||
I p] | I p] | ||
3.4 | 3.4 | ||
[E DHR is in service AND IA PRESS < 80 psig... | |||
1E 1A PRESS is < 80 psig a.NJ) abnormal system operation exists... | |||
f i | |||
1 | 3.5 N | ||
1 4 | |||
3.6 1E IA PRESS is > 90 psig THEN, EXIT this procedure. | |||
v | 1 O | ||
V | v | ||
AP-470 | (, | ||
V | |||
('' | |||
AP-470 REV 07 (MC) | |||
PAGE 8 0F 27 LOIA | |||
I 3.0 FOLLOW-UP ACTIONS (CONT'D1 ACTIONS | I 3.0 FOLLOW-UP ACTIONS (CONT'D1 ACTIONS DETAILS 3.9 jf IA PRESS does NOT e Notify available personnel to i | ||
: recover, isolate individual air supply root l | |||
l' | Itifh inspect IA and SA valves on loop headers with leaks: | ||
TB Loop 119 ft TB Loop 95 ft | l' loops for leaks. | ||
AB Loop 95 ft | TB Loop 119 ft l | ||
TB Loop 95 ft AB Loop 95 ft 3.10 WBIE IA PRESS is | |||
> 90 psig, l | |||
l | THEN EXIT this procedure. | ||
i | l i | ||
l | i l | ||
O | O | ||
[ | [ | ||
| Line 135: | Line 165: | ||
l l | l l | ||
l t | l t | ||
o AP-470 | o AP-470 REV 07 (MC) | ||
PAGE 9 0F 27 LOIA l | |||
O. | O. | ||
i l | i%.,.* | ||
l l | |||
l. | |||
BLANK PAGE | BLANK PAGE | ||
. ~. | |||
fw. | |||
l | l l | ||
? | ? | ||
l l | l l | ||
t | |||
*i: | |||
1 AP-470 REV 07 (MC) | |||
AP-470 REV 07 (MC) | PAGE 10 0F 27 LOIA J | ||
l 3.0 FOLLOW-UP ACTIONS (CONT'D) n l C/ | l 3.0 FOLLOW-UP ACTIONS (CONT'D) n 1 | ||
l C/ | |||
The following conditions exists: | ACTIONS DETAILS l | ||
e Rx is tripped e IA PRESS is :s; 80 psig and any abnormal system operation exists 3.11 | STATUS i | ||
1 The following conditions exists: | |||
e Rx is tripped e IA PRESS is :s; 80 psig and any abnormal system operation exists 3.11 Initiate EFIC. | |||
1 Depress both "EFW INITIATE" push buttons on EFIC channels A and B. | |||
2 Ensure at least one EFWP running: | 2 Ensure at least one EFWP running: | ||
EFP-1 EFP-2 O | EFP-1 EFP-2 O | ||
is at or trending toward required level. | 3 Ensure level in available OTSGs is at or trending toward required level. | ||
(Rule 3, EFW Control) l l | (Rule 3, EFW Control) l l | ||
l O | l O | ||
AP-470 | AP-470 REV 07 (MC) | ||
PAGE 11 0F 27 LOIA | |||
1 | 1 l | ||
l | |||
l l | l l | ||
1 P | |||
BLANK PAGE Q | |||
: t...,, | |||
: t. . ., , | |||
0 (s | 0 (s | ||
AP-470 REV 07 (MC) | AP-470 REV 07 (MC) | ||
PAGE 12 0F 27 LOIA | |||
3.0 F0LLOW-UP ACTIONS (CONT'D) | 3.0 F0LLOW-UP ACTIONS (CONT'D) | ||
ACTIONS | ACTIONS DETAILS 3.12 Initiate MSLI and MFLI. | ||
1 Depress " MAIN STM ISOLATION" push buttons on EFIC channels A and B for both OTSGs. | |||
2 ___ Depress " MAIN FEED ISOLATION" push buttons on EFIC channels A and B for both OT9Gs. | 2 ___ Depress " MAIN FEED ISOLATION" push buttons on EFIC channels A and B for both OT9Gs. | ||
3 Select MBVs to " MAN" and select all FW isolation valves to "CLOSE": | 3 Select MBVs to " MAN" and select all FW isolation valves to "CLOSE": | ||
FW valve | FW valve A OTSG B OTSG LLBV FWV-31 FWV-32 MBV toggle | ||
A OTSG | " MAN" | ||
A OTSG | " MAN" MBV FWV-30 FWV-29 SUBV FWV-36 FWV-33 Cross-tie FWV-28 Suction FWV-14 FWV-15 4 Ensure both MFWPs are tripped: | ||
AP-470 | A OTSG B OTSG FWP-2A FWP-2B 5 Ensure all MSIVs closed: | ||
A OTSG B OTSG MSV-412 MSV-413 MSV-411 MSV-414 O | |||
AP-470 REV 07 (MC) | |||
PAGE 13 0F 27 LOIA | |||
j l | O j | ||
l i | |||
r l | r l | ||
I l | I l | ||
l 6 | l 6 | ||
l BLANK PAGE | l BLANK PAGE | ||
..e l | |||
s4 / | |||
l l | l l | ||
l i | l i | ||
| Line 196: | Line 233: | ||
{ | { | ||
l l | l l | ||
I | I t | ||
4 s | |||
AP-470 REV 07 (MC) | |||
PAGE 14 0F 27 LOIA 1 | |||
\\ | |||
I l | I l | ||
3.0 FOLLOW-UP ACTIONS (CONT'D) | 3.0 FOLLOW-UP ACTIONS (CONT'D) | ||
ACTIONS | ACTIONS DETAILS | ||
? 13 Align backup air supply to e Notify SP0 to open IAV-676 "ADV ADVs. | |||
3.14 | Backup Air Supply Iso" (119 ft TB behind FWHE-38). | ||
* Cycle appropriate BWST to MVP valve 2 55 in, | 3.14 Isolate letdown. | ||
MUV-73 MVV-58 3.17 | 1 Close MUV-49 2 | ||
If MUV-49 will NOT close, IE!i close MUV-567 3.15 Isolate normal makeup. | |||
1 Maintain PZR level > 80 in with MUV-24 2 | |||
Close MUV-27 1 | |||
O 3.16 Maintain MUT level | |||
* Cycle appropriate BWST to MVP valve 2 55 in, to raise MUT level: | |||
MUV-73 MVV-58 3.17 If at any time, RCP CB0 is | |||
: lost, RCP-1A IE!! trip all RCPs. | |||
RCP-lC RCP-1B RCP-10 O | RCP-lC RCP-1B RCP-10 O | ||
AP-470 | AP-470 REV 07 (MC) | ||
PAGE 15 0F 27 LOIA | |||
} | } | ||
Applicable carry-over steps: | Applicable carry-over steps: | ||
3.17 | 3.17 If RCP CB0 is lost, I!!EH trip All RCPs. | ||
{- | {- | ||
1 l | 1 l | ||
| Line 218: | Line 265: | ||
l i | l i | ||
1 I | 1 I | ||
] | |||
l AP-470 REV 07 (MC) | |||
PAGE 16 0F 27 LOIA l | |||
l | l | ||
L9 FOLLOW-UP ACTIONS (CONT'D) | \\ | ||
L9 FOLLOW-UP ACTIONS (CONT'D) | |||
ACTIONS DETAILS | |||
1 3.19 | '8 E at any time, SW low i | ||
l flow for an RCP is RCP-1A indicated by either of the ~ollowing: | |||
RCP-lc "PP SEAL & WTR FLOW" RCP-1B l | |||
lamp extinguished on RCP control switch RCP-1D "RC PUMP CLG WTR FLOW LOW" annunciator alarm is illuminated T!i@ trip affected RCP. | |||
1 3.19 E at any time, all RCPs e | |||
Ensure level in available OTSGs are tripped, is at or trending toward Nat IEW establish Nat Circ. | |||
Circ level. | |||
[ Rule 3, EFW Control] | [ Rule 3, EFW Control] | ||
e | e Monitor all 4 Tems for Nat Circ indications. | ||
e Indications of Nat Circ: | l e Indications of Nat Circ: | ||
Thet tracking Tinese Tem tracking OTSG Tset AT (That - IcW) stable or lowering l | Thet tracking Tinese Tem tracking OTSG Tset AT (That - IcW) stable or lowering l | ||
.O AP-470 REV 07 (MC) | |||
PAGE 17 0F 27 LOIA | |||
Applicable carry-over steps: | Applicable carry-over steps: | ||
3.17 | 3.17 IE RCP CB0 is lost, ItiEH trip all RCPs. | ||
3.18 | 3.18 lE SW low flow on any RCP, I!!EH trip affected RCP. | ||
3.19 | 3.19 LE all RCPs are tripped, lHEN establish Nat Circ. | ||
i l | i l | ||
l O | l O | ||
e AP-470 REV 07 (MC) | |||
PAGE 18 0F 27 LOIA I | |||
3.0 FOLLOW-UP ACTIONS (CONT'D) i | 3.0 FOLLOW-UP ACTIONS (CONT'D) i [ | ||
[ | l \\ | ||
l \ | ACTIONS DETAILS l | ||
3.20 | 3.20 Reduce RCP seal injection e Notify PP0 to perform the following l | ||
to 2: 3 gpm per pump. | |||
\ | in order (95 ft AB MU valve alley): | ||
\\ | |||
Open MUV-34 " Seal Injection Control Bypass Outlet Iso". | Open MUV-34 " Seal Injection Control Bypass Outlet Iso". | ||
Open MUV-35 " Seal Injection Control Bypass Inlet Iso". | Open MUV-35 " Seal Injection Control Bypass Inlet Iso". | ||
Throttle MUV-17 " Seal Injection Control Bypass". | Throttle MUV-17 " Seal Injection Control Bypass". | ||
Close MVV-14 " Seal Infection Control Inlet Iso". | Close MVV-14 " Seal Infection Control Inlet Iso". | ||
3.21 Control RCS TEMP using ADVs. | |||
oO V | oO V | ||
I | I lV AP-470 REV 07 (MC) | ||
lV AP-470 | PAGE 19 0F 27 LOIA | ||
Applicable carry-over steps: | Applicable carry-over steps: | ||
3.17 11 RCP CB0 is lost, THEN trip 111 RCPs. | |||
{ | { | ||
3.19 | 3.18 lE SW low flow on any RCP, IEN trip affected RCP. | ||
1 O | 3.19 If all RCPs are tripped, IMH establish Nat Circ. | ||
1 O | |||
c-l lO AP-470 REV 07 (MC) | |||
PAGE 20 0F 27 LOIA | |||
{ | { | ||
\ | \\ | ||
3.0 FOLLOW-UP ACTIONS (CONT'D) | 3.0 FOLLOW-UP ACTIONS (CONT'D) | ||
ACTIONS | ACTIONS DETAILS 3.22 Ensure emergency RB 1 At least 1 Emergency SW Pump cooling is in service, running: | ||
(Rule 5, EDG Control] | (Rule 5, EDG Control] | ||
SWP-1A SWP-18 2 At least 1 Emergency SW Raw Water Pump running: | |||
RWP-2A RWP-2B 3 Proper RB cooling unit operation: | RWP-2A RWP-2B 3 Proper RB cooling unit operation: | ||
1E ES has NOT actuated, ItiEN ensure both ES selected RB cooling units running in slow speed. | 1E ES has NOT actuated, ItiEN ensure both ES selected RB cooling units running in slow speed. | ||
1E c.S has actuated, | O 1E c.S has actuated, ItiEH ensure only 1 ES selected RB cooling unit running in slow speed. | ||
4 CI valves to RB cooling units closed: | 4 CI valves to RB cooling units closed: | ||
SWV-151 SWV-152 SWV-355 5 SW valves to RB cooling units open: | SWV-151 SWV-152 SWV-355 5 SW valves to RB cooling units open: | ||
l | l SWV-353 SWV-354 l | ||
>O AP-470 | >O AP-470 REV 07 (MC) | ||
PAGE 21 0F 27 LOIA | |||
I Applicable carry-over steps: | I Applicable carry-over steps: | ||
r) | r) 3.17 E RCP CB0 is lost, THEN trip all RCPs. | ||
,(g | ,(g 3.18 E SW low flow on any RCP, THEN trip affected RCP. | ||
3.18 | 3.19 E G RCPs are tripped, J_HG establish Nat Cire. | ||
3.19 | /^s l | ||
l ln | |||
l | () | ||
AP-470 REV 07 (MC) | |||
AP-470 | PAGE 22 0F 27 LOIA | ||
3.0 FOLLOW-UP ACTIONS (CONT'D1 | 3.0 FOLLOW-UP ACTIONS (CONT'D1 | ||
) | |||
O | O ACTIONS DETAILS 3.23 IE at any time, PZR level e | ||
3.23 | Control cooldown using ADVs. | ||
is > 250 in, THW control PZR level by CONCURRENTLY PERFORM E0P 14, starting an RCS cooldown. 5, E0P Temperature i | |||
starting an RCS cooldown. | I Log. | ||
i 3.24 | i 3.24 Break condenser vacuum. | ||
1 Select condenser ARPs to | |||
" PULL TO LOCK": | |||
ARP-1A ARP-18 2 Open condenser vacuum Bkrs: | ARP-1A ARP-18 2 Open condenser vacuum Bkrs: | ||
ARV-48 ARV-49 O | ARV-48 ARV-49 O | ||
3.25 | 3.25 Ensure WG compressors are e Notify PPO to select WG compressors stopped. | ||
WDP-1A | to " PULL TO LOCK" (WDCP-3 Radwaste Control Panel): | ||
3.26 | WDP-1A f | ||
* Notify SP0 to close ASV-53 "GS desuperheater. | WDP-1B 3.26 Isolate GW to AS | ||
* Notify SP0 to close ASV-53 "GS desuperheater. | |||
DESUPERHEATER OUTLET 150" (119 ft TB at AS Hdr). | |||
l l | l l | ||
l l | l l | ||
AP-470 | AP-470 REV 07 (HC) | ||
PAGE 23 0F 27 LOIA | |||
i Applicable carry-over steps: | i Applicable carry-over steps: | ||
'() | '() | ||
is' 3.17 | is' 3.17 E RCP CB0 is lost, THEN trip all RCPs. | ||
3.18 | 3.18 E SW low flow on any RCP, THEN trip affected RCP. | ||
3.19 | 3.19 E all RCPs are tripped, THEN establish Nat Circ. | ||
3.23 | 3.23 E PZR level is > 250 in, THEN control PZR level... | ||
i | i OQ i | ||
l O | |||
AP-470 REV 07 (MC) | |||
i | PAGE 24 0F 27 LOIA | ||
l | |||
O | |||
AP-470 | |||
h l | h l | ||
l | l 3.0 FOLLOW-UP ACTIONS (CONT'D) l ACTIONS DETAILS 3.27 E at any time, IA valves | ||
See OP-411, Instrument and Station Air, Enclosure 4, Loss of IA Equipment Failure Modes | : fail, THEN select failed valves to their failed position. | ||
3.28 | See OP-411, Instrument and Station Air, Enclosure 4, Loss of IA Equipment Failure Modes 3.28 E at any time, SC cooling SAP-1A | ||
' SAP-1B is lost, 3 | |||
THEN stop SC cooled | THEN stop SC cooled components. | ||
components. | M.P48 p* | ||
(FWP-2A FWP-2B TFWP-1A FWPllB | |||
!. CDP-1 A | |||
' CDP-1B | |||
''J "ARP'2A | |||
#ARP-2B 3.29 E at any time, IA PRESS is > 90 psig, EJE GO TO OP-411, Instrument and Station Air System, Section 4.8, Restoration From AP-470 3.30 Bypass IA dryers. | |||
* Notify SP0 to open IAV-31 "IADR-1 & | * Notify SP0 to open IAV-31 "IADR-1 & | ||
IADR-2 Bypass Iso" (95 ft TB behind 1ADR-1). | IADR-2 Bypass Iso" (95 ft TB behind 1ADR-1). | ||
I,a AP-470 | I,a AP-470 REV 07 (MC) | ||
PAGE 25 0F 27 LOIA j | |||
i | |||
l l | l l | ||
l Applicable carry over steps: | l Applicable carry over steps: | ||
3.17 | 3.17 E RCP CB0 is lost, M trip all RCPs. | ||
p | |||
l 3.19 | ...j 1 | ||
3.27 | 3.18 E SW low flow on any RCP, THEN trip affected RCP. | ||
3.28 | l 3.19 E All RCPs are tripped, THEN establish Nat Cire. | ||
4 3.29 | 3.23 E PZR level is > 250 in, THEN control PZR level... | ||
3.27 E IA valves fail, M select failed valves to... | |||
3.28 1E SC cooling is lost, E stop SC cooled components. | |||
4 3.29 IE IA PRESS is > 90 psig, THEN GO TO OP-411... | |||
I i | I i | ||
j i | j i | ||
| Line 345: | Line 413: | ||
f I | f I | ||
l | l | ||
) | |||
AP-470 REV 07 (MC) | |||
PAGE 26 0F 27 LOIA | |||
3.0 FOLLOW-UP ACTIONS (CONT'D) | 3.0 FOLLOW-UP ACTIONS (CONT'D) | ||
OV ACTIONS DETAILS 3.31 Place both IA dryer e Notify SP0 to ensure the following prefilters and are open (95 ft TB by IADR-1): | |||
afterfilters in service. | afterfilters in service. | ||
IAV-Il "Prefilter IAFL-2A Inlet Iso" I AV-12 "Prefilter I AFL-2B Inlet Iso" IAV-14 "Prefilter IAFL-2B Outlet Iso" IAV-544 "Prefilter IAFL-2A Outlet Iso" IAV-18 "Afterfilter IAFL-3B Inlet Iso" IAV-545 "Afterfilter IAFL-3A Inlet Iso" IAV-19 "Afterfilter IAFL-3A Outlet Iso" IAV-20 "Afterfilter IAFL-3B Outlet Iso" 3.32 | IAV-Il "Prefilter IAFL-2A Inlet Iso" I AV-12 "Prefilter I AFL-2B Inlet Iso" IAV-14 "Prefilter IAFL-2B Outlet Iso" IAV-544 "Prefilter IAFL-2A Outlet Iso" IAV-18 "Afterfilter IAFL-3B Inlet Iso" IAV-545 "Afterfilter IAFL-3A Inlet Iso" IAV-19 "Afterfilter IAFL-3A Outlet Iso" IAV-20 "Afterfilter IAFL-3B Outlet Iso" 3.32 JE IA PRESS does NOT e Notify available personnel to | ||
: recover, isolate individual air supply root 111@ inspect IA and SA valves on loop headers with leaks: | |||
loops for leaks. | loops for leaks. | ||
TB Loop 119 ft TB Loop 95 ft AB Loop 95 ft 3.33 | TB Loop 119 ft TB Loop 95 ft AB Loop 95 ft 3.33 WH._@ IA PRESS is | ||
_> 90 psig, I11@ GO TO OP-411, Instrument and Station Air System, Section 4.8, O | _> 90 psig, I11@ GO TO OP-411, Instrument and Station Air System, Section 4.8, O | ||
Restoration From AP-470 AP-470 REV 07 (MC) | |||
PAGE 27 0F 27 (LAST PAGE) | |||
LOIA}} | |||
Latest revision as of 10:28, 3 December 2024
| ML20216F018 | |
| Person / Time | |
|---|---|
| Site: | Crystal River |
| Issue date: | 04/08/1998 |
| From: | FLORIDA POWER CORP. |
| To: | |
| Shared Package | |
| ML20216F000 | List: |
| References | |
| AP-470, NUDOCS 9804160378 | |
| Download: ML20216F018 (27) | |
Text
l LOIA REV 07 (MC)
AP-470 l
!O l
LOSS OF INSTRUMENT AIR l
1.0 ENTRY CONDITIONS INFORMATION 1E IA PRESS is s 90 psig, ONLY l
JREN use this procedure.
L 2.0 IMMEDIATE ACTIONS HOIE There are no imediate actions for this procedure.
l I
O i
l A
Approved by NNP0
[e[U/b-Date 04/08/98
(SIGNATURE ON FILE)
AP-470 PAGE 1 of 27 LOIA l
9804160378 980409 PDR ADOCK 05000302 P
l l
I O
O i
BLANK PAGE p
('
V O
o AP-470 REV 07 (MC)
PAGE 2 0F 27 LOIA
3.0 FOLLOW-UP ACTIONS r)
't
/
ACTIONS DETAILS 3.1 Ensure in-house air g g-compressors are running.
3.2 Notify personnel of plant STA conditions.
1 Plant operators NSM e
HP (notify of degraded IA conditions as a precaution for personnel using breathing air) k.)
Announce on PA " Terminate all use of station air".
l l
i l
AP-470 REV 07 (MC)
PAGE 3 0F 27 LOIA l
l O
Oi I
l c-1 l
1 l
l l
l
)
'O C
AP-470 REV 07 (MC)
PAGE 4 0F 27 LOIA l
3.0 FOLLOW-UP ACTIONS (CONT'D)
ACTIONS DETAILS 3.3 Notify SP0 to start berm l
air compressors.
'I 1
i I
3.4 __ J1 at any time, DHR is in 1
J1 A DHR Train is in service, i
- service, M notify PP0 to manually l
E IA PRESS < 80 psig, throttle the following valves l
l M establish manual (75 ft AB A DH Room):
control of DHR cooling, l
M GO TO Step 3.27 in DCV-17 "A DH Cooler Bypass this procedure Control" DCV-177 "A DH Cooler Outlet Control" l
l 2
!N M notify PP0 to manually throttle the following valves l
(75 ft AB B DH Room):
DCV-18 "B DH Cooler Bypass Control" DCV-178 "B DH Cooler Outlet l
Control" 3
GO TO Step 3.27 in this procedure.
l 3.5 JF at any time, IA PRESS 1
Depress Rx trip push button is < 80 psig, E any abnormal system 2
CONCURRENTLY PERFORM E0P-2, operation exists, Vital System Status M trip Rx and Verification, beginning with I
GO TO Step 3.11 in this Step 2.1 procedure.
3 GO TO Step 3.11 in this procedure.
O AP-470 REV 07 (MC)
PAGE 5 0F 27 LOIA
i Applicable carry-over steps:
CN 4, 'j E DHR is in service AND IA PRESS < 80 psig...
3.4
- i. ;. r l
3.5 E lA PRESS is < 80 psig MQ abnormal system operation exists...
1 l
l l
l l
, ' ~
v f
t l
l l
l l
l l
l t
i v
t AP-470 REV 07 (MC)
PAGE 6 0F 27 LOIA
\\
L4 FOLLOW-UP ACTIONS (CONT'D)
Ob ACTIONS DETAILS 3.6 1E at any time, IA PRESS is > 90 psig, IliEt{ EXIT this procedure.
3.7 Bypass IA dryers.
- Notify SP0 to open IAV-31 "IADR-1 &
j IADR-2 Bypass Iso" (95 ft TB behind 1ADR-1).
3.8 Place both IA dryer
- Notify SP0 to ensure all the prefilters and following valves are open afterfilters in service.
(95 ft TB by IADR-1):
IAV-Il "Prefilter IAFL-2A Inlet Iso" IAV-12 "Prefilter IAFL-2B Inlet
\\pj Iso" IAV-14 "Prefilter IAFL-2B Outlet Iso" IAV-544 "Prefilter IAFL-2A Outlet Iso" IAV-18 "Afterfilter IAFL-3B Inlet Iso" IAV-545 "Afterfilter IAFL-3A Inlet Iso" IAV-19 "Afterfilter IAFL-3A Outlet Iso"
__ IAV-20 "Afterfilter IAFL-3B Outlet Iso" O
AP-470 REV 07 (MC)
PAGE 7 0F 27 LOIA
r 1
i Applicable carry-over steps:
I p]
3.4
[E DHR is in service AND IA PRESS < 80 psig...
1E 1A PRESS is < 80 psig a.NJ) abnormal system operation exists...
f i
3.5 N
1 4
3.6 1E IA PRESS is > 90 psig THEN, EXIT this procedure.
1 O
v
(,
V
(
AP-470 REV 07 (MC)
PAGE 8 0F 27 LOIA
I 3.0 FOLLOW-UP ACTIONS (CONT'D1 ACTIONS DETAILS 3.9 jf IA PRESS does NOT e Notify available personnel to i
- recover, isolate individual air supply root l
Itifh inspect IA and SA valves on loop headers with leaks:
l' loops for leaks.
TB Loop 119 ft l
TB Loop 95 ft AB Loop 95 ft 3.10 WBIE IA PRESS is
> 90 psig, l
THEN EXIT this procedure.
l i
i l
O
[
1 l
l l
l l
l t
o AP-470 REV 07 (MC)
PAGE 9 0F 27 LOIA l
O.
i%.,.*
l l
l.
BLANK PAGE
. ~.
fw.
l l
?
l l
t
- i:
1 AP-470 REV 07 (MC)
PAGE 10 0F 27 LOIA J
l 3.0 FOLLOW-UP ACTIONS (CONT'D) n 1
l C/
ACTIONS DETAILS l
STATUS i
1 The following conditions exists:
e Rx is tripped e IA PRESS is :s; 80 psig and any abnormal system operation exists 3.11 Initiate EFIC.
1 Depress both "EFW INITIATE" push buttons on EFIC channels A and B.
2 Ensure at least one EFWP running:
EFP-1 EFP-2 O
3 Ensure level in available OTSGs is at or trending toward required level.
(Rule 3, EFW Control) l l
l O
AP-470 REV 07 (MC)
PAGE 11 0F 27 LOIA
1 l
l l
1 P
BLANK PAGE Q
- t...,,
0 (s
AP-470 REV 07 (MC)
PAGE 12 0F 27 LOIA
3.0 F0LLOW-UP ACTIONS (CONT'D)
ACTIONS DETAILS 3.12 Initiate MSLI and MFLI.
1 Depress " MAIN STM ISOLATION" push buttons on EFIC channels A and B for both OTSGs.
2 ___ Depress " MAIN FEED ISOLATION" push buttons on EFIC channels A and B for both OT9Gs.
3 Select MBVs to " MAN" and select all FW isolation valves to "CLOSE":
FW valve A OTSG B OTSG LLBV FWV-31 FWV-32 MBV toggle
" MAN"
" MAN" MBV FWV-30 FWV-29 SUBV FWV-36 FWV-33 Cross-tie FWV-28 Suction FWV-14 FWV-15 4 Ensure both MFWPs are tripped:
A OTSG B OTSG FWP-2A FWP-2B 5 Ensure all MSIVs closed:
A OTSG B OTSG MSV-412 MSV-413 MSV-411 MSV-414 O
AP-470 REV 07 (MC)
PAGE 13 0F 27 LOIA
O j
l i
r l
I l
l 6
l BLANK PAGE
..e l
s4 /
l l
l i
i
{
l l
I t
4 s
AP-470 REV 07 (MC)
PAGE 14 0F 27 LOIA 1
\\
I l
3.0 FOLLOW-UP ACTIONS (CONT'D)
ACTIONS DETAILS
? 13 Align backup air supply to e Notify SP0 to open IAV-676 "ADV ADVs.
Backup Air Supply Iso" (119 ft TB behind FWHE-38).
3.14 Isolate letdown.
1 Close MUV-49 2
If MUV-49 will NOT close, IE!i close MUV-567 3.15 Isolate normal makeup.
1 Maintain PZR level > 80 in with MUV-24 2
Close MUV-27 1
O 3.16 Maintain MUT level
- Cycle appropriate BWST to MVP valve 2 55 in, to raise MUT level:
MUV-73 MVV-58 3.17 If at any time, RCP CB0 is
RCP-lC RCP-1B RCP-10 O
AP-470 REV 07 (MC)
PAGE 15 0F 27 LOIA
}
Applicable carry-over steps:
3.17 If RCP CB0 is lost, I!!EH trip All RCPs.
{-
1 l
i l
l i
1 I
]
l AP-470 REV 07 (MC)
PAGE 16 0F 27 LOIA l
l
\\
L9 FOLLOW-UP ACTIONS (CONT'D)
ACTIONS DETAILS
'8 E at any time, SW low i
l flow for an RCP is RCP-1A indicated by either of the ~ollowing:
RCP-lc "PP SEAL & WTR FLOW" RCP-1B l
lamp extinguished on RCP control switch RCP-1D "RC PUMP CLG WTR FLOW LOW" annunciator alarm is illuminated T!i@ trip affected RCP.
1 3.19 E at any time, all RCPs e
Ensure level in available OTSGs are tripped, is at or trending toward Nat IEW establish Nat Circ.
Circ level.
[ Rule 3, EFW Control]
e Monitor all 4 Tems for Nat Circ indications.
l e Indications of Nat Circ:
Thet tracking Tinese Tem tracking OTSG Tset AT (That - IcW) stable or lowering l
.O AP-470 REV 07 (MC)
PAGE 17 0F 27 LOIA
Applicable carry-over steps:
3.17 IE RCP CB0 is lost, ItiEH trip all RCPs.
3.18 lE SW low flow on any RCP, I!!EH trip affected RCP.
3.19 LE all RCPs are tripped, lHEN establish Nat Circ.
i l
l O
e AP-470 REV 07 (MC)
PAGE 18 0F 27 LOIA I
3.0 FOLLOW-UP ACTIONS (CONT'D) i [
l \\
ACTIONS DETAILS l
3.20 Reduce RCP seal injection e Notify PP0 to perform the following l
to 2: 3 gpm per pump.
in order (95 ft AB MU valve alley):
\\
Open MUV-34 " Seal Injection Control Bypass Outlet Iso".
Open MUV-35 " Seal Injection Control Bypass Inlet Iso".
Throttle MUV-17 " Seal Injection Control Bypass".
Close MVV-14 " Seal Infection Control Inlet Iso".
3.21 Control RCS TEMP using ADVs.
oO V
I lV AP-470 REV 07 (MC)
PAGE 19 0F 27 LOIA
Applicable carry-over steps:
3.17 11 RCP CB0 is lost, THEN trip 111 RCPs.
{
3.18 lE SW low flow on any RCP, IEN trip affected RCP.
3.19 If all RCPs are tripped, IMH establish Nat Circ.
1 O
c-l lO AP-470 REV 07 (MC)
PAGE 20 0F 27 LOIA
{
\\
3.0 FOLLOW-UP ACTIONS (CONT'D)
ACTIONS DETAILS 3.22 Ensure emergency RB 1 At least 1 Emergency SW Pump cooling is in service, running:
(Rule 5, EDG Control]
SWP-1A SWP-18 2 At least 1 Emergency SW Raw Water Pump running:
RWP-2A RWP-2B 3 Proper RB cooling unit operation:
1E ES has NOT actuated, ItiEN ensure both ES selected RB cooling units running in slow speed.
O 1E c.S has actuated, ItiEH ensure only 1 ES selected RB cooling unit running in slow speed.
4 CI valves to RB cooling units closed:
SWV-151 SWV-152 SWV-355 5 SW valves to RB cooling units open:
l SWV-353 SWV-354 l
>O AP-470 REV 07 (MC)
PAGE 21 0F 27 LOIA
I Applicable carry-over steps:
r) 3.17 E RCP CB0 is lost, THEN trip all RCPs.
,(g 3.18 E SW low flow on any RCP, THEN trip affected RCP.
3.19 E G RCPs are tripped, J_HG establish Nat Cire.
/^s l
l ln
()
AP-470 REV 07 (MC)
PAGE 22 0F 27 LOIA
3.0 FOLLOW-UP ACTIONS (CONT'D1
)
O ACTIONS DETAILS 3.23 IE at any time, PZR level e
Control cooldown using ADVs.
is > 250 in, THW control PZR level by CONCURRENTLY PERFORM E0P 14, starting an RCS cooldown. 5, E0P Temperature i
I Log.
i 3.24 Break condenser vacuum.
1 Select condenser ARPs to
" PULL TO LOCK":
ARP-1A ARP-18 2 Open condenser vacuum Bkrs:
ARV-48 ARV-49 O
3.25 Ensure WG compressors are e Notify PPO to select WG compressors stopped.
to " PULL TO LOCK" (WDCP-3 Radwaste Control Panel):
WDP-1A f
WDP-1B 3.26 Isolate GW to AS
- Notify SP0 to close ASV-53 "GS desuperheater.
DESUPERHEATER OUTLET 150" (119 ft TB at AS Hdr).
l l
l l
AP-470 REV 07 (HC)
PAGE 23 0F 27 LOIA
i Applicable carry-over steps:
'()
is' 3.17 E RCP CB0 is lost, THEN trip all RCPs.
3.18 E SW low flow on any RCP, THEN trip affected RCP.
3.19 E all RCPs are tripped, THEN establish Nat Circ.
3.23 E PZR level is > 250 in, THEN control PZR level...
i OQ i
l O
AP-470 REV 07 (MC)
PAGE 24 0F 27 LOIA
h l
l 3.0 FOLLOW-UP ACTIONS (CONT'D) l ACTIONS DETAILS 3.27 E at any time, IA valves
- fail, THEN select failed valves to their failed position.
See OP-411, Instrument and Station Air, Enclosure 4, Loss of IA Equipment Failure Modes 3.28 E at any time, SC cooling SAP-1A
' SAP-1B is lost, 3
THEN stop SC cooled components.
M.P48 p*
(FWP-2A FWP-2B TFWP-1A FWPllB
!. CDP-1 A
' CDP-1B
J "ARP'2A
- ARP-2B 3.29 E at any time, IA PRESS is > 90 psig, EJE GO TO OP-411, Instrument and Station Air System, Section 4.8, Restoration From AP-470 3.30 Bypass IA dryers.
- Notify SP0 to open IAV-31 "IADR-1 &
IADR-2 Bypass Iso" (95 ft TB behind 1ADR-1).
I,a AP-470 REV 07 (MC)
PAGE 25 0F 27 LOIA j
i
l l
l Applicable carry over steps:
3.17 E RCP CB0 is lost, M trip all RCPs.
p
...j 1
3.18 E SW low flow on any RCP, THEN trip affected RCP.
l 3.19 E All RCPs are tripped, THEN establish Nat Cire.
3.23 E PZR level is > 250 in, THEN control PZR level...
3.27 E IA valves fail, M select failed valves to...
3.28 1E SC cooling is lost, E stop SC cooled components.
4 3.29 IE IA PRESS is > 90 psig, THEN GO TO OP-411...
I i
j i
1 i
f I
l
)
AP-470 REV 07 (MC)
PAGE 26 0F 27 LOIA
3.0 FOLLOW-UP ACTIONS (CONT'D)
OV ACTIONS DETAILS 3.31 Place both IA dryer e Notify SP0 to ensure the following prefilters and are open (95 ft TB by IADR-1):
afterfilters in service.
IAV-Il "Prefilter IAFL-2A Inlet Iso" I AV-12 "Prefilter I AFL-2B Inlet Iso" IAV-14 "Prefilter IAFL-2B Outlet Iso" IAV-544 "Prefilter IAFL-2A Outlet Iso" IAV-18 "Afterfilter IAFL-3B Inlet Iso" IAV-545 "Afterfilter IAFL-3A Inlet Iso" IAV-19 "Afterfilter IAFL-3A Outlet Iso" IAV-20 "Afterfilter IAFL-3B Outlet Iso" 3.32 JE IA PRESS does NOT e Notify available personnel to
- recover, isolate individual air supply root 111@ inspect IA and SA valves on loop headers with leaks:
loops for leaks.
TB Loop 119 ft TB Loop 95 ft AB Loop 95 ft 3.33 WH._@ IA PRESS is
_> 90 psig, I11@ GO TO OP-411, Instrument and Station Air System, Section 4.8, O
Restoration From AP-470 AP-470 REV 07 (MC)
PAGE 27 0F 27 (LAST PAGE)
LOIA