OPERATING DATA REPORT DOCKET NO. 50-333 DATE November 1982 C051PLETED BY J. Cook TELEPilONE (315)342-3840 OPERATING STATUS
: 1. Unit Name:
FITZPATRICK Notes 821001 - 821031
: 2. Reporting Period:
: 3. Licensed Thermal Power (51WI):
2436 883
: 4. Nameplate Rating (Gross MWe):
821
: 5. Design Electrical Rating (Net 51We):
830
: 6. Maximum Dependable Capacity (Gross MWe):.
810
: 7. Masimum Dependable Capacity (Net MWe):
: 8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7)Since Last Report, Give Reasons:
NONE
: 9. Power Lesel To Which Restricted,If Any (Net MWe):
: 10. Reasons For Restrictions,If Any:
This Month Yr..to.Date Cumulatise
: 11. Ilours In Reporting Period 745 7296 63673
: 12. Number Ofilours Reactor Was Critical 494.5 5376.9 44928.1
: 13. Reactor Resene Shutdown flours 0
0 0
478.5 5258.1 43701.7
: 14. Ilours Generator On.Line 0
0 0
: 15. Unit Reserve Shutdown Hours
: 16. Gross Thermal Energy Generated (MWH) 1015776 12061416 90462730
: 17. Gross Electrical Energy Generated (MWil) 339140 4081040 30841650 329095 3960240 29864970
: 18. Net Electrical Energy Generated (MWil)
: 19. Unit Senice Factor 64.2%
72.1%
68.6%
: 20. Unit Availability Factor 64.2%
72.1%
68.6%
: 21. Unit Capacity Factor (Using MDC Net) 54.5%
67.0%
62.0%
: 22. Unit Capacity Factor (Using DER Net) 53.8%
66.1%
57.1%
: 23. Unit Forced Outage Rate 35.8%
7.2%
15.9%
: 24. Shutdowns Scheduled Oser Next 6 Months (Type.Date.and Duration of Each1:
: 25. If Shut Down At End Of Report Period. Estimated Date d Startup:
: 26. Units In Test Status (Prior to Commercial Operation):
Forcust Achieved INITIA L CRITICALITY INITIA L ELECTRICITY COMMERCIAL OPERATION
~
521'1090221 '821104 PDR ADOCK 05000333 PDR
- R.
m
-J
 
AVER AGE DAILY UNIT POWER LEVEL DOCKET NO.
. 50-133 JAFNPP UNIT NOVEMBER 1982 DATE J. COOK COMPLETED BY TELEPilONE CL151142-38.40 MONHI OCTOBER 1982 DAY AVER AGE DAILY POWER LEVE(.
DAY AVER AGE DAILY POWER LEVEL (MWe Ne:)
(MWe Net) i 19.2 17 67 795 is 2
367 799 19 3
442 797 20 4
450 5
797 21 512 795 22 6
636 393 23 7
730 g
24 785
'~~
9 25 791 io 26 11 27 794 794 12 28 788 13 29 628 34 39 767
~~~
15 31
 
==SUMMARY==
The FitzPatrick plant operated at near full thermal power during this reporting period with one outage due to main steam isolation failure and one power reduction for condensate booster pump repair.
 
(.
50-333 UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO.
JAFN FI' UNIT N AME ~
NOVEMBER 1982 DATE COMPLETED BY J.
COOK REPORT.MONTil OCTOBER 1982 TELEPIIONE (315)342-3840 n.
.! ?
3
).E Licensee Eg Cause & Currective o
No.
Date i
3?
i
.s i 5 Event g?
g3 Action to 5
5 ;5 =!
Report a mV o'
Prevent Recurrence e
u 6
7 821007 F
266.5 A
3 82-047 HB VALVEX "D" inboard MSIV failure due to disc seperation from stem.
Repaired valve with two anti-rotation pins.
8 821030 S
0 H
4 N/A HH PUMPXX Reduced power for "A" condensate booster pump repair I
2 3
4 F: Forced Reason:
Method:
Exlubit G. Inst:uctions S: ScheJ ufed A Equipment Failure (Explain) 1-Manual for Preparation of Data B Maintenance or Test 2-Manual Scram.
Entry Sheets for Licensee C. Refueling 3 Automatic Scram.
Event Report (LER) File INUREG.
D Regulatory Restriction 4-Other (Explain) 0161)
E-Operator Training & License Examination F. Administrative 5
G Operational Error (Explain)
Estubit I. Same Source Il Other (Explain)
+
 
PdWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT
-NARRATIVE
 
==SUMMARY==
OF OPERATING EXPERIENCE NOVEMBER, 1982 The unit operated at near full thermal power _.for the first six days of the rep'D" inboard main steam isolation valve and onthe unit tripped due orting period..On 821007 to failure of the 821030 power was reduced for "A" condensate booster pump repai?r.
At the end of the reporting period the unit is operating at approximately 767 MWe.
s t
.N.
\\
\\.
1 i
%g i
a t
3 4
 
POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT SAFETY RELATED ELECTRICAL a MECHANICAL MAINTENANCE
 
==SUMMARY==
OCTOBER 1982 WORK REOUEST#
REPAIR DATE SYSTEM HOW DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE TIME PON #
HOURS l'0/15 23 21810 VISUAL Worn packing Repacked 6
HPI-52 10/15 10 18317 OPS Using pipe wrenches and Replaced valve stems and RHR-755B, channel locks on valve handwheels, repacked 32 756B,757B, stems 758B 10/15 10 18758 OPS Handwheels vibrated off Replaced handwheels 2
RHR-755A, 756A,757A, 758A 10/16 27 18760 OPS Air line worn through Replaced damaged portion of air 8
'L' Target line, wrapped to prevent further Rock abrasion 10/15 23 21801 VISUAL Blown bonnet gasket Replaced bonnet gasket 16 AOV-53 10/15 10 16209 N/A N/A Replaced carbon steel cetter pin 3
RHR-14D with stainless steel 10/15 10 16208 RHR-14B N/A N/A Replaced carbon steel cotter pin 3
with stainless steel 10/14 23 20947 VISUAL Worn packing Repacked 2
Steam Trap Drain Valve 10/14 23 18342 VISUAL Worn packing Repacked 2
HPI-900 1
 
POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT SAFETY RELATED ELECTRICAL & h ECHANICAL MAINTENANCE
 
==SUMMARY==
OCTOBER 1982 OR EQ EST DATE SYSTEM HOW DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE T
10/16 29 18806 OPS Maintenance work on Adjusted limit switches 2.5 MSIV valve A0V-86D LO/16 29 14976 N/A N/A Installed new 90% limit switches 95
* MSIV per MI-82-80 A0V-80-A-D IO/15 46 16222 N/A N/A Replaced carbon steel cotter pin 3
ESW-1B with stainless steel LO/13 02-2 16375 VISUAL Oil leaks Visual inspection 3
Grinnell snubbers LO/7 01-125 18235 OPS Depleted charcoal Replaced charcoal 60 Standby Gas absorption capacity Filter F-2A LO/13 02 20857 TEMPERATURE Leaking first stage Replaced first stage 116 RV-71F INDICATION valve LO/10 10 17710 VISUAL Deteriorated sealtite Replaced sealtite with NWC type 7
MOV-21A 10/10 23 20995 VISUAL Eroded / corroded Replaced fitting 12 HPCI drain-fitting line 10/12 27 11360 N/A N/A Completed Step 8 (1-4) of ECR 6
Primary 80-16-34 containment Hi-Hi-Rad relays
 
POWER AUTHORITY OF THE STATE OF NEW YORK 1
JAMES A. FITZPATRICK NUCLEAR POWER PLANT 2
SAFETY RELATED ELECTRICAL a MECHANICAL MAINTENANCE
 
==SUMMARY==
OCTOBER 1982 EO S DATE SYSTEM HOW DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE T
10/12 29 16380 OPS Pilot disk to stem Installed two interference fit 192 MSIV Caused locking pin sheared pins instead of one, in both A0V-80D shutdown pilot to stem and piston to main disc
' 10/73 29 18796 OPS Testing No malfunction. This Installed two interference fit 170 MSIV indicated valve was not broken lock pins instead of one, in both A0V-860 valve was pilot to stem and piston to main seperated disc 10/9 7:
17126 N/A N/A Traced circuits to correct 25 AC-A2, B2 drawings i
10/13 71 14975 N/A N/A Drilled t" weepholes in boxes per 16 lE Junction MI-82-082 Boxes 10/15 23 14312 VISUAL Broken nipple Replaced nipple 3
P-1 10/14 23 18330 VISUAL W'orn packing Repacked 20 MOV-14 10/17 71 14891 N/A N/A Performed preventative 10 Bkr-10404 maintenance 10/15 71 I4392 N/A N/A Performed preventative 12 Bkr-10614 maintenance 10/16 71 14893 N/A N/A Performed preventative 5
Bkr-10612 maintenance 10/15 71 14894 N/A N/A Performed preventative 5
Bkr-10602 maintenance
 
POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT SAFETY RELATED ELECTRICAL a MECHANICAL MAINTENANCE
 
==SUMMARY==
OCTOBER 1982 R
O DATE SYSTEM HOW DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE T ME E
HOURS l'0/15 71 14895 N/A N/A Performed preventative 5
Bkr-10604 maintenance 10/15 71 14896 N/A N/A Performed preventative 13 Bkr-10660 maintenance 10/16 71 14816 N/A N/A Connected temporary power supply 6
IBC-3, 4 to nuclear instruments for bus outage and disconnected 10/16 13 19122 VISUAL Worn packing Repacked 6
MOV-16 10/16 13 18537 VISUAL Worn packing and Repacked and replaced pressure 6
MOV-131 thermal cycling seal 10/16 02 20884 OPS Worn packing MOV-53B torqued packing 10 MOV-53B,54B MOV-54B repacked 10/19 27 18870 OPS Limit switch out of Adjusted limit switch 4
AOV-132A adjustment 10/20 93 18861 OPS No power indication Replaced lamp
.5 ECP-D 10/20 27 18869 OPS Relief valve out of Reset valve 17 SV-ll4B adj ustment 10/16 34 18801 VISUAL Blown bonnet gasket f4achined bonnet to' remove steam 34 FWS-28B cut-replaced gasket 10/16 02 19246 PRESSURE Worn seal-some Replaced shaft seal with a 306 P-1B INDICATION evidence of thermal rebuilt cartridge shock
 
POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT MAINTENANCE
 
==SUMMARY==
T&C OCTOBER 1982 DATE SYSTEM HOW DETECTED CAUSE OF RESULTS OF ACTION TAKEN REPAIR WORK REQUEST #
COMPONENT #
MALFUNCTION MALFUNCTION TO PRECLUDE TIME RECURRENCE HOURS 18219 Use, normal Drain valve Replaced 10/12 02 PS-134C IGC wear leaks drain valve 2
18234 Use, normal Test valve Replaced test 10/12 02 PS-128B I&C wear leaks valve
.5 20326 Possible loose Red pen Tightened all 10/11 02 TR-165 OPS connection indicating connections 18 downscale 20826 Defective pre No bias Replaced pre 10/14 02 VRM-71F I&C amp adjustment amp 4
18142 Defective Indicat6r Replaced amp, 10/16 02-3 LI-85A OPS amplifier board failed re-aligned 20 downscale un2.t 18191 Recorder Recorder Cleaned and 10/08 02-3 FR/PR-95 OPS dirty sticks calibrated 3
18215 Instrument Scale out of Per ISP-3.5 9/30 02-3
'LI-85B OPS drift calibration adjusted span 20 and zero 18225 Use, normal Test valve Replaced 10/12 02-3 PS-52A I&C wear leaks valve 1
20332 Vent valves on Replaced vent 10/13 02-3 LIS-72A-D I&C Use yarways worn valves 10 18186 Defective rod Unable to Replaced select 10/11 03 34-39 OPS select switch select rod 34-push button 10 m
18666 Broken wire on Unable t 10/17 03 26-51 OPS select switch select rod 26-Replaced broken wire 3
26-si 51
 
POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT MAINTENANCE
 
==SUMMARY==
I&C OCTOBER 1982 WORK REQUEST #
CAUSE OF RESULTS OF ACTIO?: TAKEN REPAIR DATE SYSTEM HOW DETECTED COMPONENT #
MALFUNCTION MALFUNCTION TO PRECLUDE TIME RECURRENCE HOURS 18866 Broken wire on Unable t Replaced 10/17 03 26-51 OPS rod select select rod 26-broken wire 3
switch 51 Tests indicated Performed IMP-20829 Tested units need to reset on various 10/11 03 HCU (var)
I&C per WRED 50 18126 Corrosion on Full in/ full Cleaned 10/14 07 10-39 OPS connector pins out light connector 21 inop 18237 Verify core Hand probed tops for D tip tubes for 10/17 07 Tip D RXA None 8
machine tops 18243 VR2 in mean No downscale aced IRM B I&C sqyare analog trip on 10/08 07 14 unit IRM B Connector 18425 28-21A Replaced rV 10/11 07 LPRM 28-21 OPS d wnscale connector 9
en 18511 Dirty 12-45D Gleaned and 10/11 07
'LPRM 12-45 OPS connector downscale tightened 5
under vessel connector 18901 Recorder not
. n set t PR-46B OPS indicating Adjusted gain 2
10/29 07 normal 18969 No lights Replaced bulbs, 10/25 07 34-07 OPS Bad bulbs for rod 34-07, ran IMP-3.7 3
26-15 Reset inop 18972
]j 10/21 07 APRM E OPS None None 1
e rod 18988 Checked as APRMS RXA None requested 11.5 10/26 07 se@o M s
 
POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT MAINTENANCE
 
==SUMMARY==
I&C OCTOBER 1982 CO PONENT ] #
ES A
DATE SYSTEM HOW DETECTED LFUNC ON ML Cl REC S
18990 Momentum of None, rec.
~
Re d light 10/24 07 Tip D OPS selector switch chng 1 ch at a 4'
time 19544 Rod select RBM A won't Replaced 10/12 07 26-47 OPS push button select for select push 7
failed 26-47 button 19654 Dirty 10/11 07 LPRM 20-29 OPS connector c
or 3
under vessel Rod select RBM B won't Replaced 19738 Push button select for s6 lect push 10/12 07 10-35 OPS 5
failed 10-35 button 21752 Disch. press 10/01 08 Air Comp OPS Vibration gauge broken Replaced gauge 4
18987 Possible Lower than Charged X-104D 10/27 16 Elec Pens OPS leakage normal pressure C/X-101C/X-15 103A 18928 MV outpot at R
d 10/26 16-1
-DPIT-102 I&C zero, n eg b
changes 18759 V2 voltage Spurious Calibrated 10/17 17 RM-150B OPS high from power downscale per ISP-19 6
srg trips Defective Chart paper Replaced 18810 10/12 17 chart drive not chart drive RR-433 OPS 4
motor advancing motor 20934 ImPr Per probe Set Proper OPS Ins drift 8/13 17 RIS-459 hi voltage voltage 4
18158 Br during Br indicator Replaced 9/22 20 FR-528 I&C ISP-15 arm indicator arm 8
 
POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT MAINTENANCE
 
==SUMMARY==
I&C OCTOBER 1982 DATE SYSTEM HOW DETECTED CAUSE OF RESULTS OF ACTION TAKEN REPAIR WORK REQUEST #
COMPONENT #
MALFUNCTION MALFUNCTION TO PRECLUDE TIME RECURRENCE HOURS 20834 Numerous adj Several Reca11brateo 10/14 20 DWL sumps I&C during instruments out all sump operation of calibration loops 300 18218 Analyzer Hydrogen Calibrated 10/06 27
"**d*d analyzer Per ISP-30 12 '
HfAZ-101A OPS calibration downscale L
se guide switen not 14856 n 90%
e t,
Tightened bar' 10/16 29 A0V-86D OPS set switch 10 r
e 14976 Modification of Post work Calibrated 90%
10/16 29 A0V-80A-D OPS 90% limit calibration suitches 30 switch 18865 90% switch Relays not Corrected A0V-80A OPS wiring energized with 10/16 29 wiring error 15 error valve open 18867 Cam upper 90% switch hk
""U 10/17 29 A0V-86D OPS plate loose won't reset setpoint 6
22001 Check 10/26 46
~PI-ll2A OPS None calibration None required 1
22059 Rear cable Recorder will Installed cable 10/27 68 TR-103 OPS disconnected not operate calibrated 6
14863 V61tmeter out Station battery Calibrated 10/04 71 Bat. A vm OPS of calibration low volts indicator 4
20831 Verified 10/08 71 RPS-EPA I&C None None setpoints 2
Routine 20836 Calibrated ation of 10/17 71 10600 BUS I&C None 10600 BUS relays 198
 
POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT MAINTENANCE
 
==SUMMARY==
I&C OCTOBER 1982 DATE SYSTEM HOW DETECTED CAUSE OF RESULTS OF Tl K
REPAIR WORK REQUEST #
COMPONENT #
MALFUNCTION MALFUNCTION RECURRENCE HOURS 22104 Check relay Checked as 10/28 71 10614 OPS None set points directed 8*
18814 Defective Supervisory Replaced 10/22 76 Zone 2 OPS input module alarm in module 32,
18973 Defective Supervisory Replaced 10/26 76 Zone 12 OPS input module alarm in module 16 17610 Loose pointer Select switch Tightened as 10/12 93 Temp Selec OPS dial out of synch required 12}}

Latest revision as of 18:40, 16 December 2024

Monthly Operating Rept for Oct 1982
ML20066B865
Person / Time
Site: FitzPatrick Constellation icon.png
Issue date: 11/04/1982
From: Jackie Cook
POWER AUTHORITY OF THE STATE OF NEW YORK (NEW YORK
To:
Shared Package
ML20066B861 List:
References
NUDOCS 8211090221
Download: ML20066B865 (13)


Text

.

OPERATING DATA REPORT DOCKET NO. 50-333 DATE November 1982 C051PLETED BY J. Cook TELEPilONE (315)342-3840 OPERATING STATUS

1. Unit Name:

FITZPATRICK Notes 821001 - 821031

2. Reporting Period:
3. Licensed Thermal Power (51WI):

2436 883

4. Nameplate Rating (Gross MWe):

821

5. Design Electrical Rating (Net 51We):

830

6. Maximum Dependable Capacity (Gross MWe):.

810

7. Masimum Dependable Capacity (Net MWe):
8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7)Since Last Report, Give Reasons:

NONE

9. Power Lesel To Which Restricted,If Any (Net MWe):
10. Reasons For Restrictions,If Any:

This Month Yr..to.Date Cumulatise

11. Ilours In Reporting Period 745 7296 63673
12. Number Ofilours Reactor Was Critical 494.5 5376.9 44928.1
13. Reactor Resene Shutdown flours 0

0 0

478.5 5258.1 43701.7

14. Ilours Generator On.Line 0

0 0

15. Unit Reserve Shutdown Hours
16. Gross Thermal Energy Generated (MWH) 1015776 12061416 90462730
17. Gross Electrical Energy Generated (MWil) 339140 4081040 30841650 329095 3960240 29864970
18. Net Electrical Energy Generated (MWil)
19. Unit Senice Factor 64.2%

72.1%

68.6%

20. Unit Availability Factor 64.2%

72.1%

68.6%

21. Unit Capacity Factor (Using MDC Net) 54.5%

67.0%

62.0%

22. Unit Capacity Factor (Using DER Net) 53.8%

66.1%

57.1%

23. Unit Forced Outage Rate 35.8%

7.2%

15.9%

24. Shutdowns Scheduled Oser Next 6 Months (Type.Date.and Duration of Each1:
25. If Shut Down At End Of Report Period. Estimated Date d Startup:
26. Units In Test Status (Prior to Commercial Operation):

Forcust Achieved INITIA L CRITICALITY INITIA L ELECTRICITY COMMERCIAL OPERATION

~

521'1090221 '821104 PDR ADOCK 05000333 PDR

- R.

m

-J

AVER AGE DAILY UNIT POWER LEVEL DOCKET NO.

. 50-133 JAFNPP UNIT NOVEMBER 1982 DATE J. COOK COMPLETED BY TELEPilONE CL151142-38.40 MONHI OCTOBER 1982 DAY AVER AGE DAILY POWER LEVE(.

DAY AVER AGE DAILY POWER LEVEL (MWe Ne:)

(MWe Net) i 19.2 17 67 795 is 2

367 799 19 3

442 797 20 4

450 5

797 21 512 795 22 6

636 393 23 7

730 g

24 785

'~~

9 25 791 io 26 11 27 794 794 12 28 788 13 29 628 34 39 767

~~~

15 31

SUMMARY

The FitzPatrick plant operated at near full thermal power during this reporting period with one outage due to main steam isolation failure and one power reduction for condensate booster pump repair.

(.

50-333 UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO.

JAFN FI' UNIT N AME ~

NOVEMBER 1982 DATE COMPLETED BY J.

COOK REPORT.MONTil OCTOBER 1982 TELEPIIONE (315)342-3840 n.

.! ?

3

).E Licensee Eg Cause & Currective o

No.

Date i

3?

i

.s i 5 Event g?

g3 Action to 5

5 ;5 =!

Report a mV o'

Prevent Recurrence e

u 6

7 821007 F

266.5 A

3 82-047 HB VALVEX "D" inboard MSIV failure due to disc seperation from stem.

Repaired valve with two anti-rotation pins.

8 821030 S

0 H

4 N/A HH PUMPXX Reduced power for "A" condensate booster pump repair I

2 3

4 F: Forced Reason:

Method:

Exlubit G. Inst:uctions S: ScheJ ufed A Equipment Failure (Explain) 1-Manual for Preparation of Data B Maintenance or Test 2-Manual Scram.

Entry Sheets for Licensee C. Refueling 3 Automatic Scram.

Event Report (LER) File INUREG.

D Regulatory Restriction 4-Other (Explain) 0161)

E-Operator Training & License Examination F. Administrative 5

G Operational Error (Explain)

Estubit I. Same Source Il Other (Explain)

+

PdWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT

-NARRATIVE

SUMMARY

OF OPERATING EXPERIENCE NOVEMBER, 1982 The unit operated at near full thermal power _.for the first six days of the rep'D" inboard main steam isolation valve and onthe unit tripped due orting period..On 821007 to failure of the 821030 power was reduced for "A" condensate booster pump repai?r.

At the end of the reporting period the unit is operating at approximately 767 MWe.

s t

.N.

\\

\\.

1 i

%g i

a t

3 4

POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT SAFETY RELATED ELECTRICAL a MECHANICAL MAINTENANCE

SUMMARY

OCTOBER 1982 WORK REOUEST#

REPAIR DATE SYSTEM HOW DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE TIME PON #

HOURS l'0/15 23 21810 VISUAL Worn packing Repacked 6

HPI-52 10/15 10 18317 OPS Using pipe wrenches and Replaced valve stems and RHR-755B, channel locks on valve handwheels, repacked 32 756B,757B, stems 758B 10/15 10 18758 OPS Handwheels vibrated off Replaced handwheels 2

RHR-755A, 756A,757A, 758A 10/16 27 18760 OPS Air line worn through Replaced damaged portion of air 8

'L' Target line, wrapped to prevent further Rock abrasion 10/15 23 21801 VISUAL Blown bonnet gasket Replaced bonnet gasket 16 AOV-53 10/15 10 16209 N/A N/A Replaced carbon steel cetter pin 3

RHR-14D with stainless steel 10/15 10 16208 RHR-14B N/A N/A Replaced carbon steel cotter pin 3

with stainless steel 10/14 23 20947 VISUAL Worn packing Repacked 2

Steam Trap Drain Valve 10/14 23 18342 VISUAL Worn packing Repacked 2

HPI-900 1

POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT SAFETY RELATED ELECTRICAL & h ECHANICAL MAINTENANCE

SUMMARY

OCTOBER 1982 OR EQ EST DATE SYSTEM HOW DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE T

10/16 29 18806 OPS Maintenance work on Adjusted limit switches 2.5 MSIV valve A0V-86D LO/16 29 14976 N/A N/A Installed new 90% limit switches 95

ESW-1B with stainless steel LO/13 02-2 16375 VISUAL Oil leaks Visual inspection 3

Grinnell snubbers LO/7 01-125 18235 OPS Depleted charcoal Replaced charcoal 60 Standby Gas absorption capacity Filter F-2A LO/13 02 20857 TEMPERATURE Leaking first stage Replaced first stage 116 RV-71F INDICATION valve LO/10 10 17710 VISUAL Deteriorated sealtite Replaced sealtite with NWC type 7

MOV-21A 10/10 23 20995 VISUAL Eroded / corroded Replaced fitting 12 HPCI drain-fitting line 10/12 27 11360 N/A N/A Completed Step 8 (1-4) of ECR 6

Primary 80-16-34 containment Hi-Hi-Rad relays

POWER AUTHORITY OF THE STATE OF NEW YORK 1

JAMES A. FITZPATRICK NUCLEAR POWER PLANT 2

SAFETY RELATED ELECTRICAL a MECHANICAL MAINTENANCE

SUMMARY

OCTOBER 1982 EO S DATE SYSTEM HOW DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE T

10/12 29 16380 OPS Pilot disk to stem Installed two interference fit 192 MSIV Caused locking pin sheared pins instead of one, in both A0V-80D shutdown pilot to stem and piston to main disc

' 10/73 29 18796 OPS Testing No malfunction. This Installed two interference fit 170 MSIV indicated valve was not broken lock pins instead of one, in both A0V-860 valve was pilot to stem and piston to main seperated disc 10/9 7:

17126 N/A N/A Traced circuits to correct 25 AC-A2, B2 drawings i

10/13 71 14975 N/A N/A Drilled t" weepholes in boxes per 16 lE Junction MI-82-082 Boxes 10/15 23 14312 VISUAL Broken nipple Replaced nipple 3

P-1 10/14 23 18330 VISUAL W'orn packing Repacked 20 MOV-14 10/17 71 14891 N/A N/A Performed preventative 10 Bkr-10404 maintenance 10/15 71 I4392 N/A N/A Performed preventative 12 Bkr-10614 maintenance 10/16 71 14893 N/A N/A Performed preventative 5

Bkr-10612 maintenance 10/15 71 14894 N/A N/A Performed preventative 5

Bkr-10602 maintenance

POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT SAFETY RELATED ELECTRICAL a MECHANICAL MAINTENANCE

SUMMARY

OCTOBER 1982 R

O DATE SYSTEM HOW DETECTED CAUSE OF MALFUNCTION ACTION TAKEN TO PRECLUDE RECURRENCE T ME E

HOURS l'0/15 71 14895 N/A N/A Performed preventative 5

Bkr-10604 maintenance 10/15 71 14896 N/A N/A Performed preventative 13 Bkr-10660 maintenance 10/16 71 14816 N/A N/A Connected temporary power supply 6

IBC-3, 4 to nuclear instruments for bus outage and disconnected 10/16 13 19122 VISUAL Worn packing Repacked 6

MOV-16 10/16 13 18537 VISUAL Worn packing and Repacked and replaced pressure 6

MOV-131 thermal cycling seal 10/16 02 20884 OPS Worn packing MOV-53B torqued packing 10 MOV-53B,54B MOV-54B repacked 10/19 27 18870 OPS Limit switch out of Adjusted limit switch 4

AOV-132A adjustment 10/20 93 18861 OPS No power indication Replaced lamp

.5 ECP-D 10/20 27 18869 OPS Relief valve out of Reset valve 17 SV-ll4B adj ustment 10/16 34 18801 VISUAL Blown bonnet gasket f4achined bonnet to' remove steam 34 FWS-28B cut-replaced gasket 10/16 02 19246 PRESSURE Worn seal-some Replaced shaft seal with a 306 P-1B INDICATION evidence of thermal rebuilt cartridge shock

POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT MAINTENANCE

SUMMARY

T&C OCTOBER 1982 DATE SYSTEM HOW DETECTED CAUSE OF RESULTS OF ACTION TAKEN REPAIR WORK REQUEST #

COMPONENT #

MALFUNCTION MALFUNCTION TO PRECLUDE TIME RECURRENCE HOURS 18219 Use, normal Drain valve Replaced 10/12 02 PS-134C IGC wear leaks drain valve 2

18234 Use, normal Test valve Replaced test 10/12 02 PS-128B I&C wear leaks valve

.5 20326 Possible loose Red pen Tightened all 10/11 02 TR-165 OPS connection indicating connections 18 downscale 20826 Defective pre No bias Replaced pre 10/14 02 VRM-71F I&C amp adjustment amp 4

18142 Defective Indicat6r Replaced amp, 10/16 02-3 LI-85A OPS amplifier board failed re-aligned 20 downscale un2.t 18191 Recorder Recorder Cleaned and 10/08 02-3 FR/PR-95 OPS dirty sticks calibrated 3

18215 Instrument Scale out of Per ISP-3.5 9/30 02-3

'LI-85B OPS drift calibration adjusted span 20 and zero 18225 Use, normal Test valve Replaced 10/12 02-3 PS-52A I&C wear leaks valve 1

20332 Vent valves on Replaced vent 10/13 02-3 LIS-72A-D I&C Use yarways worn valves 10 18186 Defective rod Unable to Replaced select 10/11 03 34-39 OPS select switch select rod 34-push button 10 m

18666 Broken wire on Unable t 10/17 03 26-51 OPS select switch select rod 26-Replaced broken wire 3

26-si 51

POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT MAINTENANCE

SUMMARY

I&C OCTOBER 1982 WORK REQUEST #

CAUSE OF RESULTS OF ACTIO?: TAKEN REPAIR DATE SYSTEM HOW DETECTED COMPONENT #

MALFUNCTION MALFUNCTION TO PRECLUDE TIME RECURRENCE HOURS 18866 Broken wire on Unable t Replaced 10/17 03 26-51 OPS rod select select rod 26-broken wire 3

switch 51 Tests indicated Performed IMP-20829 Tested units need to reset on various 10/11 03 HCU (var)

I&C per WRED 50 18126 Corrosion on Full in/ full Cleaned 10/14 07 10-39 OPS connector pins out light connector 21 inop 18237 Verify core Hand probed tops for D tip tubes for 10/17 07 Tip D RXA None 8

machine tops 18243 VR2 in mean No downscale aced IRM B I&C sqyare analog trip on 10/08 07 14 unit IRM B Connector 18425 28-21A Replaced rV 10/11 07 LPRM 28-21 OPS d wnscale connector 9

en 18511 Dirty 12-45D Gleaned and 10/11 07

'LPRM 12-45 OPS connector downscale tightened 5

under vessel connector 18901 Recorder not

. n set t PR-46B OPS indicating Adjusted gain 2

10/29 07 normal 18969 No lights Replaced bulbs, 10/25 07 34-07 OPS Bad bulbs for rod 34-07, ran IMP-3.7 3

26-15 Reset inop 18972

]j 10/21 07 APRM E OPS None None 1

e rod 18988 Checked as APRMS RXA None requested 11.5 10/26 07 se@o M s

POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT MAINTENANCE

SUMMARY

I&C OCTOBER 1982 CO PONENT ] #

ES A

DATE SYSTEM HOW DETECTED LFUNC ON ML Cl REC S

18990 Momentum of None, rec.

~

Re d light 10/24 07 Tip D OPS selector switch chng 1 ch at a 4'

time 19544 Rod select RBM A won't Replaced 10/12 07 26-47 OPS push button select for select push 7

failed 26-47 button 19654 Dirty 10/11 07 LPRM 20-29 OPS connector c

or 3

under vessel Rod select RBM B won't Replaced 19738 Push button select for s6 lect push 10/12 07 10-35 OPS 5

failed 10-35 button 21752 Disch. press 10/01 08 Air Comp OPS Vibration gauge broken Replaced gauge 4

18987 Possible Lower than Charged X-104D 10/27 16 Elec Pens OPS leakage normal pressure C/X-101C/X-15 103A 18928 MV outpot at R

d 10/26 16-1

-DPIT-102 I&C zero, n eg b

changes 18759 V2 voltage Spurious Calibrated 10/17 17 RM-150B OPS high from power downscale per ISP-19 6

srg trips Defective Chart paper Replaced 18810 10/12 17 chart drive not chart drive RR-433 OPS 4

motor advancing motor 20934 ImPr Per probe Set Proper OPS Ins drift 8/13 17 RIS-459 hi voltage voltage 4

18158 Br during Br indicator Replaced 9/22 20 FR-528 I&C ISP-15 arm indicator arm 8

POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT MAINTENANCE

SUMMARY

I&C OCTOBER 1982 DATE SYSTEM HOW DETECTED CAUSE OF RESULTS OF ACTION TAKEN REPAIR WORK REQUEST #

COMPONENT #

MALFUNCTION MALFUNCTION TO PRECLUDE TIME RECURRENCE HOURS 20834 Numerous adj Several Reca11brateo 10/14 20 DWL sumps I&C during instruments out all sump operation of calibration loops 300 18218 Analyzer Hydrogen Calibrated 10/06 27

"**d*d analyzer Per ISP-30 12 '

HfAZ-101A OPS calibration downscale L

se guide switen not 14856 n 90%

e t,

Tightened bar' 10/16 29 A0V-86D OPS set switch 10 r

e 14976 Modification of Post work Calibrated 90%

10/16 29 A0V-80A-D OPS 90% limit calibration suitches 30 switch 18865 90% switch Relays not Corrected A0V-80A OPS wiring energized with 10/16 29 wiring error 15 error valve open 18867 Cam upper 90% switch hk

""U 10/17 29 A0V-86D OPS plate loose won't reset setpoint 6

22001 Check 10/26 46

~PI-ll2A OPS None calibration None required 1

22059 Rear cable Recorder will Installed cable 10/27 68 TR-103 OPS disconnected not operate calibrated 6

14863 V61tmeter out Station battery Calibrated 10/04 71 Bat. A vm OPS of calibration low volts indicator 4

20831 Verified 10/08 71 RPS-EPA I&C None None setpoints 2

Routine 20836 Calibrated ation of 10/17 71 10600 BUS I&C None 10600 BUS relays 198

POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FITZPATRICK NUCLEAR POWER PLANT MAINTENANCE

SUMMARY

I&C OCTOBER 1982 DATE SYSTEM HOW DETECTED CAUSE OF RESULTS OF Tl K

REPAIR WORK REQUEST #

COMPONENT #

MALFUNCTION MALFUNCTION RECURRENCE HOURS 22104 Check relay Checked as 10/28 71 10614 OPS None set points directed 8*

18814 Defective Supervisory Replaced 10/22 76 Zone 2 OPS input module alarm in module 32,

18973 Defective Supervisory Replaced 10/26 76 Zone 12 OPS input module alarm in module 16 17610 Loose pointer Select switch Tightened as 10/12 93 Temp Selec OPS dial out of synch required 12