IR 05000413/2019010: Difference between revisions

From kanterella
Jump to navigation Jump to search
(StriderTol Bot change)
(StriderTol Bot change)
 
(One intermediate revision by the same user not shown)
Line 1: Line 1:
{{Adams
{{Adams
| number = ML20028D021
| number = ML19354A856
| issue date = 01/09/2020
| issue date = 12/20/2019
| title = Reissue Catawba - Design Basis Assurance Inspection (Programs) Inspection Report 05000413/2019010 and 05000414/2019010
| title = Design Basis Assurance Inspection (Programs) Inspection Report 0500413/2019010 and 05000414/2019010
| author name = Baptist J
| author name = Baptist J
| author affiliation = NRC/RGN-II/DRS/EB1
| author affiliation = NRC/RGN-II/DRS/EB2
| addressee name = Simril R
| addressee name = Simril R
| addressee affiliation = Duke Energy Carolinas, LLC
| addressee affiliation = Duke Energy Carolinas, LLC
Line 12: Line 12:
| document report number = IR 2019010
| document report number = IR 2019010
| document type = Inspection Report, Letter
| document type = Inspection Report, Letter
| page count = 23
| page count = 22
}}
}}


Line 18: Line 18:


=Text=
=Text=
{{#Wiki_filter:ary 9, 2020
{{#Wiki_filter:December 20, 2019
 
==SUBJECT:==
REISSUE - CATAWBA NUCLEAR STATION - DESIGN BASIS ASSURANCE INSPECTION (PROGRAMS) INSPECTION REPORT 05000413/2019010 AND 05000414/2019010
 
==Dear Mr. Simril:==
On December 20, 2019 the U.S. Nuclear Regulatory Commission (NRC) issued the Design Basis Assurance Inspection (Programs) report for Catawba Nuclear Station, Units 1 and 2 (ADAMS Accession No. ML19354A856). In review of this report, it was identified that administrative (typographical) errors were present. Specifically, Non-cited Violations (NCVs)
05000413,05000414/2019010-02 and 05000413,05000414/2019010-03 (pages 7 and 9 of the report, respectively) contained incomplete action request (AR) numbers. AR 023011 (page 7)
and AR 0203601 (page 9) have been corrected to ARs 02300311 and 02303601. We request that the cover letter and report be replaced with the Enclosures to this letter.
 
In accordance with Title 10 of the Code of Federal Regulations (10 CFR) 2.390 Public inspection, exemptions, requests for withholding of the NRCs Agency Rules of Practice and Procedure, a copy of this letter will be available electronically for public inspection in the NRC Public Document Room, of the Publicly Available Records (PARS) component of NRCs ADAMS; accessible from the NRC Website at https://www.nrc.gov/reading-rm/adams.html (the Public Electronic Reading Room).
 
Please contact me at 404-997-4506 with any questions you have regarding this letter.
 
Sincerely,
/RA/
James B. Baptist, Chief Engineering Branch 1 Division of Reactor Safety ber 20, 2019


==SUBJECT:==
==SUBJECT:==
Line 49: Line 33:
If you disagree with a cross-cutting aspect assignment in this report, you should provide a response within 30 days of the date of this inspection report, with the basis for your disagreement, to the U.S. Nuclear Regulatory Commission, ATTN: Document Control Desk, Washington, DC 20555-0001; with copies to the Regional Administrator, Region II; and the NRC Resident Inspector at Catawba Nuclear Station.
If you disagree with a cross-cutting aspect assignment in this report, you should provide a response within 30 days of the date of this inspection report, with the basis for your disagreement, to the U.S. Nuclear Regulatory Commission, ATTN: Document Control Desk, Washington, DC 20555-0001; with copies to the Regional Administrator, Region II; and the NRC Resident Inspector at Catawba Nuclear Station.


This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the Enclosure NRC Public Document Room in accordance with Title 10 of the Code of Federal Regulations 2.390, Public Inspections, Exemptions, Requests for Withholding.
This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with Title 10 of the Code of Federal Regulations 2.390, Public Inspections, Exemptions, Requests for Withholding.


Sincerely,
Sincerely,
/RA/
/RA/ Brian R. Bonser for/
James B. Baptist, Chief Engineering Branch 1 Division of Reactor Safety Docket Nos. 05000413 and 05000414 License Nos. NPF-35 and NPF-52
 
James B. Baptist, Chief Engineering Branch 1 Division of Reactor Safety  
 
Docket Nos. 05000413 and 05000414 License Nos. NPF-35 and NPF-52  


===Enclosure:===
===Enclosure:===
As stated
As stated  


==Inspection Report==
==Inspection Report==
Docket Numbers: 05000413 and 05000414 License Numbers: NPF-35 and NPF-52 Report Numbers: 05000413/2019010 and 05000414/2019010 Enterprise Identifier: I-2019-010-0029 Licensee: Duke Energy Carolina, LLC Facility: Catawba Nuclear Station Location: York, SC Inspection Dates: October 28, 2019 to November 21, 2019 Inspectors: B. Collins, Senior Reactor Inspector C. Franklin, Reactor Inspector M. Greenleaf, Senior Reactor Inspector M. Riley, Reactor Inspector Approved By: James B. Baptist, Chief Engineering Branch 1 Division of Reactor Safety Enclosure 2
Enclosure
 
Docket Numbers:
05000413 and 05000414  
 
License Numbers:
NPF-35 and NPF-52  
 
Report Numbers:
05000413/2019010 and 05000414/2019010  
 
Enterprise Identifier: I-2019-010-0029  
 
Licensee:
Duke Energy Carolina, LLC  
 
Facility:
Catawba Nuclear Station  
 
Location:
York, SC  
 
Inspection Dates:
October 28, 2019 to November 21, 2019  
 
Inspectors:
B. Collins, Senior Reactor Inspector  
 
C. Franklin, Reactor Inspector  
 
M. Greenleaf, Senior Reactor Inspector  
 
M. Riley, Reactor Inspector  
 
Approved By:
James B. Baptist, Chief
Engineering Branch 1
Division of Reactor Safety  


=SUMMARY=
=SUMMARY=
The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees performance by conducting a design basis assurance inspection (programs) inspection at Catawba Nuclear Station, in accordance with the Reactor Oversight Process. The Reactor Oversight Process is the NRCs program for overseeing the safe operation of commercial nuclear power reactors. Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information.
The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees performance by conducting a design basis assurance inspection (programs) inspection at Catawba Nuclear Station, in accordance with the Reactor Oversight Process. The Reactor Oversight Process is the NRCs program for overseeing the safe operation of commercial nuclear power reactors. Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information.


List of Findings and Violations Failure to Qualify GEMS Level Transmitters for Submergence Cornerstone         Significance                               Cross-Cutting     Report Aspect            Section Mitigating           Green                                       None (NPP)        71111.21N Systems              NCV 05000413,05000414/2019010-01 Open The inspectors identified a Green finding and Non-cited Violation (NCV) of 10 CFR 50.49(f)when the licensee failed to demonstrate the GEMS containment sump level transmitter NILT5270 would meet its specified values for one year post-accident during submerged conditions in accordance with Section 6.5.4 of IEEE 323-1974, the standard the licensee chose in order to meet environmental qualification requirements.
===List of Findings and Violations===
Failure to Qualify GEMS Level Transmitters for Submergence Cornerstone Significance Cross-Cutting Aspect Report Section Mitigating Systems Green NCV 05000413,05000414/2019010-01 Open/Closed
 
None (NPP)71111.21N The inspectors identified a Green finding and Non-cited Violation (NCV) of 10 CFR 50.49(f)when the licensee failed to demonstrate the GEMS containment sump level transmitter NILT5270 would meet its specified values for one year post-accident during submerged conditions in accordance with Section 6.5.4 of IEEE 323-1974, the standard the licensee chose in order to meet environmental qualification requirements.
 
Failure to Demonstrate Qualification of Conduit Sealant Compatibility for Electrical Wires and Cables Cornerstone Significance Cross-Cutting Aspect Report Section Mitigating Systems Green NCV 05000413,05000414/2019010-02 Open/Closed


Failure to Demonstrate Qualification of Conduit Sealant Compatibility for Electrical Wires and Cables Cornerstone          Significance                                Cross-Cutting      Report Aspect            Section Mitigating          Green                                      None (NPP)         71111.21N Systems              NCV 05000413,05000414/2019010-02 Open The inspectors identified a Green finding and associated Non-cited Violation (NCV) of 10 CFR 50.49(f) when the licensee failed to demonstrate the qualification of the conduit sealant and cable/wire interfaces utilizing Scotchcast Epoxy 9 in accordance with NUREG-0588 Section 2.2(7).
None (NPP)71111.21N The inspectors identified a Green finding and associated Non-cited Violation (NCV) of 10 CFR 50.49(f) when the licensee failed to demonstrate the qualification of the conduit sealant and cable/wire interfaces utilizing Scotchcast Epoxy 9 in accordance with NUREG-0588 Section 2.2(7).


Failure to Assess Radiation and Thermal Degradation Effects of Replacement Sealant Equivalency Cornerstone         Significance                               Cross-Cutting     Report Aspect            Section Mitigating           Green                                       [H.8] -            71111.21N Systems              NCV 05000413,05000414/2019010-03           Procedure Open                                       Adherence The inspectors identified a Green finding and Non-cited Violation (NCV) of 10 CFR 50.49(f)when the licensee failed to demonstrate that the qualification of Scotchcast Epoxy 9 was applicable to Scotchcast Epoxy 9N in accordance with Section 5.5.7 of procedure AD-EG-ALL-1612.
Failure to Assess Radiation and Thermal Degradation Effects of Replacement Sealant Equivalency Cornerstone Significance Cross-Cutting Aspect Report Section Mitigating Systems Green NCV 05000413,05000414/2019010-03 Open/Closed


Additional Tracking Items None
[H.8] -
Procedure Adherence 71111.21N The inspectors identified a Green finding and Non-cited Violation (NCV) of 10 CFR 50.49(f)when the licensee failed to demonstrate that the qualification of Scotchcast Epoxy 9 was applicable to Scotchcast Epoxy 9N in accordance with Section 5.5.7 of procedure AD-EG-ALL-1612.
 
===Additional Tracking Items===
None.


=INSPECTION SCOPES=
=INSPECTION SCOPES=
Line 77: Line 110:


==REACTOR SAFETY==
==REACTOR SAFETY==
===71111.21N - Design Bases Assurance Inspection (Programs)


===71111.21N - Design Bases Assurance Inspection (Programs)
The inspectors evaluated Environmental Qualification program implementation through the sampling of the following components:  
The inspectors evaluated Environmental Qualification program implementation through the sampling of the following components:
 
Select Sample Components to Review - Risk Significant/Low Design (Inside/Outside Containment) (IP Section 02.01) ===
Select Sample Components to Review - Risk Significant/Low Design (Inside/Outside Containment) (IP Section 02.01)===
{{IP sample|IP=IP 71111.21|count=8}}
{{IP sample|IP=IP 71111.21|count=8}}
: (1) 1NDPUAMR, 1A Residual Heat Removal Pump Motor (Westinghouse)
 
(1)1NDPUAMR, 1A Residual Heat Removal Pump Motor (Westinghouse)
: (2) Commodity Item, Okozel Low Voltage Power/I&C Cable (Okenite)
: (2) Commodity Item, Okozel Low Voltage Power/I&C Cable (Okenite)
: (3) Commodity Item, Scotchcast 9 and 9N Epoxies (3M)
: (3) Commodity Item, Scotchcast 9 and 9N Epoxies (3M)
: (4) Commodity Item, Terminal Blocks (States- and Stanwick-types)
: (4) Commodity Item, Terminal Blocks (States-and Stanwick-types)  
: (5) 1TBOX0019, Terminal Block Enclosure (Hoffman)
(5)1TBOX0019, Terminal Block Enclosure (Hoffman)  
: (6) 2TBOX0656, Terminal Block Enclosure (Hoffman)
(6)2TBOX0656, Terminal Block Enclosure (Hoffman)  
: (7) 2CFHP0330, Main Feedwater Pneumatic-Hydraulic Isolation Valve (Borg-Warner)
(7)2CFHP0330, Main Feedwater Pneumatic-Hydraulic Isolation Valve (Borg-Warner)  
: (8) 1YC362/MO, Hot Gas Bypass Valve Actuator (Jamesbury)
(8)1YC362/MO, Hot Gas Bypass Valve Actuator (Jamesbury)  
Select Sample Components to Review - Primary Containment (Inside Containment) (IP Section 02.01) (2 Samples)
 
: (1) 1NILT5270, Unit 1 Containment Sump Level Transmitter (DeLaval/GEMS)
Select Sample Components to Review - Primary Containment (Inside Containment) (IP Section 02.01) (2 Samples)  
: (2) 2VXPS5110, Pressure Switch (Solon)
 
(1)1NILT5270, Unit 1 Containment Sump Level Transmitter (DeLaval/GEMS)  
(2)2VXPS5110, Pressure Switch (Solon)


==INSPECTION RESULTS==
==INSPECTION RESULTS==
Failure to Qualify GEMS Level Transmitters for Submergence Cornerstone           Significance                             Cross-Cutting       Report Aspect              Section Mitigating             Green                                   None (NPP)          71111.21N Systems                NCV 05000413,05000414/2019010-01 Open The inspectors identified a Green finding and Non-cited Violation (NCV) of 10 CFR 50.49(f)when the licensee failed to demonstrate the GEMS containment sump level transmitter NILT5270 would meet its specified values for one year post-accident during submerged conditions in accordance with Section 6.5.4 of IEEE 323-1974, the standard the licensee chose in order to meet environmental qualification requirements.
Failure to Qualify GEMS Level Transmitters for Submergence Cornerstone Significance Cross-Cutting Aspect Report Section Mitigating Systems
 
Green NCV 05000413,05000414/2019010-01 Open/Closed
 
None (NPP)71111.21N The inspectors identified a Green finding and Non-cited Violation (NCV) of 10 CFR 50.49(f)when the licensee failed to demonstrate the GEMS containment sump level transmitter NILT5270 would meet its specified values for one year post-accident during submerged conditions in accordance with Section 6.5.4 of IEEE 323-1974, the standard the licensee chose in order to meet environmental qualification requirements.


=====Description:=====
=====Description:=====
Line 110: Line 151:
Corrective Actions: The licensee entered this issue into their corrective action program and performed an operability evaluation which determined that there was reasonable assurance that the transmitter could perform its intended safety function based on operating experience and the military specification of the wire which demonstrated the insulations ability to withstand different adverse chemicals.
Corrective Actions: The licensee entered this issue into their corrective action program and performed an operability evaluation which determined that there was reasonable assurance that the transmitter could perform its intended safety function based on operating experience and the military specification of the wire which demonstrated the insulations ability to withstand different adverse chemicals.


Corrective Action References: AR 02303851
Corrective Action References: AR 02303851  


=====Performance Assessment:=====
=====Performance Assessment:=====
Line 132: Line 173:
Enforcement Action: This violation is being treated as a non-cited violation, consistent with Section 2.3.2 of the Enforcement Policy.
Enforcement Action: This violation is being treated as a non-cited violation, consistent with Section 2.3.2 of the Enforcement Policy.


Failure to Demonstrate Qualification of Conduit Sealant Compatibility for Electrical Wires and Cables Cornerstone           Significance                               Cross-Cutting       Report Aspect              Section Mitigating             Green                                     None (NPP)          71111.21N Systems                NCV 05000413,05000414/2019010-02 Open The inspectors identified a Green finding and associated Non-cited Violation (NCV) of 10 CFR 50.49(f) when the licensee failed to demonstrate the qualification of the conduit sealant and cable/wire interfaces utilizing Scotchcast Epoxy 9 in accordance with NUREG-0588 Section 2.2(7).
Failure to Demonstrate Qualification of Conduit Sealant Compatibility for Electrical Wires and Cables Cornerstone Significance Cross-Cutting Aspect Report Section Mitigating Systems
 
Green NCV 05000413,05000414/2019010-02 Open/Closed
 
None (NPP)71111.21N The inspectors identified a Green finding and associated Non-cited Violation (NCV) of 10 CFR 50.49(f) when the licensee failed to demonstrate the qualification of the conduit sealant and cable/wire interfaces utilizing Scotchcast Epoxy 9 in accordance with NUREG-0588 Section 2.2(7).


=====Description:=====
=====Description:=====
Line 139: Line 184:
For the conduit sealant locations in the station scoped into the licensee's EQ program, the licensee adhered to Category II requirements of NRC NUREG-0588 for qualification and qualification testing to meet 10 CFR 50.49. Section 2.2(7) of the NUREG states that "performance characteristics be verified before, after, and periodically during testing throughout the range of required operability." By testing the sealant's mechanical sealing function without confirming that the epoxy and wire/cable did not adversely impact their electrical function of passing power/signals to/from important to safety equipment, the licensee failed to demonstrate that the sealant was qualified for the installed configurations in the field.
For the conduit sealant locations in the station scoped into the licensee's EQ program, the licensee adhered to Category II requirements of NRC NUREG-0588 for qualification and qualification testing to meet 10 CFR 50.49. Section 2.2(7) of the NUREG states that "performance characteristics be verified before, after, and periodically during testing throughout the range of required operability." By testing the sealant's mechanical sealing function without confirming that the epoxy and wire/cable did not adversely impact their electrical function of passing power/signals to/from important to safety equipment, the licensee failed to demonstrate that the sealant was qualified for the installed configurations in the field.


Corrective Actions: The station entered this into their Corrective Action Program (CAP) as ARs 02300311 and 02303697. Although environmental qualification had not been demonstrated and documented, the licensee identified other tests that had been performed on other wire types with Scotchcast Epoxy 9 (e.g. NAMCO limit switch lead wire and Mark WPA 14 gauge hookup wire). The licensee's review of this additional testing provided reasonable assurance that the installed configurations in the plant would be capable of performing their intended safety functions.
Corrective Actions: The station entered this into their Corrective Action Program (CAP) as ARs 023011 and 02303697. Although environmental qualification had not been demonstrated and documented, the licensee identified other tests that had been performed on other wire types with Scotchcast Epoxy 9 (e.g. NAMCO limit switch lead wire and Mark WPA 14 gauge hookup wire). The licensee's review of this additional testing provided reasonable assurance that the installed configurations in the plant would be capable of performing their intended safety functions.


Corrective Action References: AR 02300311 and 02303697
Corrective Action References: AR 023011 and 02303697  


=====Performance Assessment:=====
=====Performance Assessment:=====
Line 163: Line 208:
Enforcement Action: This violation is being treated as a non-cited violation, consistent with Section 2.3.2 of the Enforcement Policy.
Enforcement Action: This violation is being treated as a non-cited violation, consistent with Section 2.3.2 of the Enforcement Policy.


Failure to Assess Radiation and Thermal Degradation Effects of Replacement Sealant Equivalency Cornerstone           Significance                               Cross-Cutting     Report Aspect            Section Mitigating           Green                                     [H.8] -            71111.21N Systems              NCV 05000413,05000414/2019010-03 Procedure Open                                      Adherence The inspectors identified a Green finding and Non-cited Violation (NCV) of 10 CFR 50.49(f)when the licensee failed to demonstrate that the qualification of Scotchcast Epoxy 9 was applicable to Scotchcast Epoxy 9N in accordance with Section 5.5.7 of procedure AD-EG-ALL-1612.
Failure to Assess Radiation and Thermal Degradation Effects of Replacement Sealant Equivalency Cornerstone Significance Cross-Cutting Aspect Report Section Mitigating Systems
 
Green NCV 05000413,05000414/2019010-03 Open/Closed
 
[H.8] -
Procedure Adherence 71111.21N The inspectors identified a Green finding and Non-cited Violation (NCV) of 10 CFR 50.49(f)when the licensee failed to demonstrate that the qualification of Scotchcast Epoxy 9 was applicable to Scotchcast Epoxy 9N in accordance with Section 5.5.7 of procedure AD-EG-ALL-1612.


=====Description:=====
=====Description:=====
3M Corporation changed the chemical composition of the Part B of its Scotchcast Epoxy 9 two-part formulation from a nonylphenol component to formulation of cashew, nutshell liq.ccidentale, anacardiaceae, and toluene components. In 2018, the licensee generated an equivalency evaluation in engineering change EC 144757, Rev. 0 to evaluate the differences between the original formulation (Scotchcast Epoxy 9) and the new formulation (i.e. Scotchcast Epoxy 9N). The focus of the evaluation was to determine if the environmental qualification (EQ) performed for the original epoxy was applicable to the new epoxy. The licensee reviewed the material safety data sheets (MSDSs) of the two epoxies, performed durometer testing of representative samples of both epoxies, and performed Fourier Transform Infrared (FTIR) Spectroscopy to determine if the materials were similar enough to warrant the use of the Scotchcast Epoxy 9's qualification file to that of the Scotchcast 9N's. Based on a FTIR high percentage match (>80%) and similar durometer testing, the licensee concluded that the materials were similar enough and qualification of Scotchcast Epoxy 9 was applicable to Scotchcast Epoxy 9N.
3M Corporation changed the chemical composition of the Part B of its Scotchcast Epoxy 9 two-part formulation from a nonylphenol component to formulation of cashew, nutshell liq.ccidentale, anacardiaceae, and toluene components. In 2018, the licensee generated an equivalency evaluation in engineering change EC 144757, Rev. 0 to evaluate the differences between the original formulation (Scotchcast Epoxy 9) and the new formulation (i.e. Scotchcast Epoxy 9N). The focus of the evaluation was to determine if the environmental qualification (EQ) performed for the original epoxy was applicable to the new epoxy. The licensee reviewed the material safety data sheets (MSDSs) of the two epoxies, performed durometer testing of representative samples of both epoxies, and performed Fourier Transform Infrared (FTIR) Spectroscopy to determine if the materials were similar enough to warrant the use of the Scotchcast Epoxy 9's qualification file to that of the Scotchcast 9N's. Based on a FTIR high percentage match (>80%) and similar durometer testing, the licensee concluded that the materials were similar enough and qualification of Scotchcast Epoxy 9 was applicable to Scotchcast Epoxy 9N.


The inspectors reviewed the engineering change and noted that FTIR spectroscopy and durometer testing would provide information showing similarity between the chemical constituents and discrepancies in hardness between the two epoxies (respectively), but neither test individually (nor combined) could provide detailed information on how these different epoxies would behave when subjected to the deleterious effects of nuclear radiation and thermal degradation (i.e. aging). Inspectors reviewed the licensee's EQ procedure, AD-EG-ALL-1612, Revs. 3 and 4, and noted that Section 5.5.7(11)(b)(4)(a) stated, in part, that:
The inspectors reviewed the engineering change and noted that FTIR spectroscopy and durometer testing would provide information showing similarity between the chemical constituents and discrepancies in hardness between the two epoxies (respectively), but neither test individually (nor combined) could provide detailed information on how these different epoxies would behave when subjected to the deleterious effects of nuclear radiation and thermal degradation (i.e. aging). Inspectors reviewed the licensee's EQ procedure, AD-EG-ALL-1612, Revs. 3 and 4 and noted that Section 5.5.7(11)(b)(4)(a) stated, in part, that:  
"materials of construction shall either be the same or equivalent and differences shall be shown not to adversely affect performance of the safety function." Furthermore, the procedure states that the evaluations should, "evaluate the differences in material properties.
"materials of construction shall either be the same or equivalent and differences shall be shown not to adversely affect performance of the safety function." Furthermore, the procedure states that the evaluations should, "evaluate the differences in material properties.


Line 175: Line 225:
The licensee's technical review of the differences between the two epoxies lacked the necessary level of detail to demonstrate that the Scotchcast Epoxy 9N - which is chemically different - will age and withstand nuclear radiation in the same (or better) manner than the qualified Scotchcast Epoxy 9. As a result of the inspection, the licensee contacted 3M and determined that mechanical and electrical properties were similar between the two epoxies, however, no radiation or thermal degradation comparisons had been made between the materials.
The licensee's technical review of the differences between the two epoxies lacked the necessary level of detail to demonstrate that the Scotchcast Epoxy 9N - which is chemically different - will age and withstand nuclear radiation in the same (or better) manner than the qualified Scotchcast Epoxy 9. As a result of the inspection, the licensee contacted 3M and determined that mechanical and electrical properties were similar between the two epoxies, however, no radiation or thermal degradation comparisons had been made between the materials.


Corrective Actions: The licensee entered this issue into their corrective action program (CAP)as AR 02303601. The licensee determined that the Scotchcast Epoxy 9N had only been used in four recent work orders and based on a review of the material data sheets and on the technical opinion of the licensee's subject matter experts, the licensee concluded that the four seals in question were capable of performing their safety function.
Corrective Actions: The licensee entered this issue into their corrective action program (CAP)as AR 0203601. The licensee determined that the Scotchcast Epoxy 9N had only been used in four recent work orders and based on a review of the material data sheets and on the technical opinion of the licensee's subject matter experts, the licensee concluded that the four seals in question were capable of performing their safety function.


Corrective Action References: AR 02303601
Corrective Action References: AR 0203601


=====Performance Assessment:=====
=====Performance Assessment:=====
Line 205: Line 255:
=DOCUMENTS REVIEWED=
=DOCUMENTS REVIEWED=


Inspection Type       Designation     Description or Title                                     Revision or
Inspection
Procedure                                                                                        Date
Procedure
71111.21N Calculations CGD-3007.02-04- Acton Environmental Testing Corporation Test Report:     Rev. 5
Type
0001 Attachment States Terminal Blocks and Test Switches
Designation
CNC-1206.03-00- Flood Level for Structures Outside the Reactor Building  Rev. 26
Description or Title
Revision or
Date
71111.21N Calculations
CGD-3007.02-04-
0001 Attachment
Acton Environmental Testing Corporation Test Report:
States Terminal Blocks and Test Switches
Rev. 5
CNC-1206.03-00-
0001
0001
CNC-1206.03-00- Environmental Effects Due to Pipe Rupture Outside         Rev. 3
Flood Level for Structures Outside the Reactor Building
0004            Containment
Rev. 26
CNC-1381.05-00- FWIV Life Extension                                      Rev. 3
CNC-1206.03-00-
0004
Environmental Effects Due to Pipe Rupture Outside
Containment
Rev. 3
CNC-1381.05-00-
0158
0158
CNS-1465.00-00- Design Basis Specification for the Flooding from Internal Rev. 1
FWIV Life Extension
20            Sources
Rev. 3
CNS-1591.CF-00- DESIGN BASIS SPECIFICATION FOR THE FEEDWATER             Rev. 34
CNS-1465.00-00-
0001            (CF) SYSTEM
20
DPC-1381.05-00- Qualified Life of AGASTAT E7000 Series Timing Relays      Rev. 5
Design Basis Specification for the Flooding from Internal
Sources
Rev. 1
CNS-1591.CF-00-
0001
DESIGN BASIS SPECIFICATION FOR THE FEEDWATER  
(CF) SYSTEM
Rev. 34
DPC-1381.05-00-
0009
0009
DPC-1381.05-00- Electrical Enclosure Latching Environmental Qualification Rev. 0
Qualified Life of AGASTAT E7000 Series Timing Relays
0017            Analysis
Rev. 5
DPC-1381.05-00- Qualified Life Analysis for Brand Rex Flame Retardant     Rev. 2
DPC-1381.05-00-
0032            Cross-Linked Polyethylene Insulated Instrument Cable
0017
DPC-1381.05-00- Environmental Qualification (EQ) Evaluation of Equipment Rev. 1
Electrical Enclosure Latching Environmental Qualification
0050            Installed in the Doghouse Buildings
Analysis
DPC-1381.05-00- Environmental Qualification (EQ) Qualified Life Analysis Rev. 0
Rev. 0
0077            (TLAA) for Trane Chiller Controls Supporting CNS License
DPC-1381.05-00-
0032
Qualified Life Analysis for Brand Rex Flame Retardant
Cross-Linked Polyethylene Insulated Instrument Cable
Rev. 2
DPC-1381.05-00-
0050
Environmental Qualification (EQ) Evaluation of Equipment
Installed in the Doghouse Buildings
Rev. 1
DPC-1381.05-00-
0077
Environmental Qualification (EQ) Qualified Life Analysis  
(TLAA) for Trane Chiller Controls Supporting CNS License
Renewal
Renewal
DPC-1381.05-00- Environmental Qualification (EQ) Qualified Life Analysis Rev. 0
Rev. 0
0082            (TLAA) for DeLaval, GEMS Level Transmitters Supporting
DPC-1381.05-00-
0082
Environmental Qualification (EQ) Qualified Life Analysis  
(TLAA) for DeLaval, GEMS Level Transmitters Supporting
MNS and CNS License Renewal
MNS and CNS License Renewal
71111.21N Calculations      DPC-1381.05-00- Environmental Qualification (EQ) Qualified Life Analysis Rev. 1
Rev. 0
0087            (TLAA) for Okonite Flame Retardant Ethylene Propolene
DPC-1381.05-00-
                                            (Okonite-FMR) Low Voltage, Control and Instrument Cable
0087
Environmental Qualification (EQ) Qualified Life Analysis  
(TLAA) for Okonite Flame Retardant Ethylene Propolene  
(Okonite-FMR) Low Voltage, Control and Instrument Cable
Rev. 1
 
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
Supporting MNS and CNS License Renewal
Supporting MNS and CNS License Renewal
DPC-1381.05-00- Environmental Qualification (EQ) Qualified Life Analysis Rev. 0
DPC-1381.05-00-
0093            (TLAA) for Scotch 130C Insulating/Jacketing Tapes
0093
Environmental Qualification (EQ) Qualified Life Analysis  
(TLAA) for Scotch 130C Insulating/Jacketing Tapes
Supporting MNS and CNS License Renewal
Supporting MNS and CNS License Renewal
DPC-1381.05-00- Environmental Qualification (EQ) Qualified Life Analysis Rev. 000
Rev. 0
0104            (TLAA) for Terminal Blocks Supporting MNS and CNS
DPC-1381.05-00-
0104
Environmental Qualification (EQ) Qualified Life Analysis  
(TLAA) for Terminal Blocks Supporting MNS and CNS
License Renewal
License Renewal
Corrective Action AR01528008     At Risk Procurement of 3M Scotchcast Resin No. 9         11/13/2014
Rev. 000
Documents        AR02016420     EQ Rev Tracking                                         03/31/2016
Corrective Action
AR02096602     2017 NRC EQ Program Inspection - Cable/Splice EQML       02/01/2017
Documents
AR01528008
At Risk Procurement of 3M Scotchcast Resin No. 9
11/13/2014
AR02016420
EQ Rev Tracking
03/31/2016
AR02096602
2017 NRC EQ Program Inspection - Cable/Splice EQML
Question
Question
AR02149240-01
2/01/2017
AR02165587     Fleet License Renewal EQ TLAA Additional Action Tracking 11/14/2017
AR02149240-01  
AR02172829     Tracking of FLRIT EQ TLAA questions to Fleet EQ         12/18/2017
 
AR022242460     PE-003, Environmental Qualification (EQ) Transformation 11/09/2018
AR02165587
AR02233927     EQ Program Documentation Inefficiencies                 09/29/2018
Fleet License Renewal EQ TLAA Additional Action Tracking 11/14/2017
AR02235165     Assignment 1: Develop and execute an EQMM deficiency     10/11/2018
AR02172829
Tracking of FLRIT EQ TLAA questions to Fleet EQ
2/18/2017
AR022242460
PE-003, Environmental Qualification (EQ) Transformation
11/09/2018
AR02233927
EQ Program Documentation Inefficiencies
09/29/2018
AR02235165
Assignment 1: Develop and execute an EQMM deficiency
recovery plan
recovery plan
AR02253701     EQ Equipment in a Non-EQ Zone                           01/22/2019
10/11/2018
AR02275149     Evaluation of WL Sump Pumps Support of CA Operability   05/30/2019
AR02253701
AR02275671     Complete all prep activities associated with CNS EQ NRC 06/04/2019
EQ Equipment in a Non-EQ Zone
01/22/2019
AR02275149
Evaluation of WL Sump Pumps Support of CA Operability
05/30/2019
AR02275671
Complete all prep activities associated with CNS EQ NRC
DBAI
DBAI
AR02275676     EQ DBAI Self-Assessment - EQML Deficiency               06/04/2019
06/04/2019
AR02275676     EQ DBAI Self-Assessment - EQML Deficiency               06/04/2019
AR02275676
AR02275785     2019 CNS EQ DBAI Self-Assessment - EQ Master List       06/05/2019
EQ DBAI Self-Assessment - EQML Deficiency
06/04/2019
AR02275676
EQ DBAI Self-Assessment - EQML Deficiency
06/04/2019
AR02275785
2019 CNS EQ DBAI Self-Assessment - EQ Master List
Data Gaps
Data Gaps
AR02276144     EDB discrepancy found during EQ program self-           06/06/2019
06/05/2019
AR02276144
EDB discrepancy found during EQ program self-
assessment
assessment
AR02280114     2019 CNS EQ DBAI Focused Self-Assessment AFI#1           07/02/2019
06/06/2019
AR02280116     2019 CNS EQ DBAI Focused Self-Assessment AFI#2           07/02/2019
AR02280114
AR02280118     2019 CNS EQ DBAI Focused Self-Assessment AFI#3           07/02/2019
2019 CNS EQ DBAI Focused Self-Assessment AFI#1
AR02280121     2019 CNS EQ DBAI Focused Self-Assessment AFI#4           07/02/2019
07/02/2019
71111.21N Corrective Action AR02280125 2019 CNS EQ DBAI Focused Self-Assessment AFI#5         07/02/2019
AR02280116
Documents        AR02283803 2019 CNS EQ DBAI Focused Self-Assessment AFI#8         07/25/2019
2019 CNS EQ DBAI Focused Self-Assessment AFI#2
AR02284923 2019 CNS EQ DBAI Focused Self-Assessment AFI#6         08/01/2019
07/02/2019
Corrective Action AR02294978 2019 DBAI EQ Mechanical Components Incorrectly         10/02/2019
AR02280118
Documents                    Labeled EQ=H
2019 CNS EQ DBAI Focused Self-Assessment AFI#3
Resulting from    AR02295176 2019 DBAI EQ Housekeeping and Material Condition in U2 10/02/2019
07/02/2019
Inspection                  DH
AR02280121
AR02296270 Update EQMMs to Incorporate EQ Document Package       10/09/2019
2019 CNS EQ DBAI Focused Self-Assessment AFI#4
AR02296584 Items Listed in EQMM not in EDB                       10/10/2019
07/02/2019  
AR02298945 1CFHP0660, Armored Cable Pulled out of Junction Box   10/24/2019
 
AR02298957 2CA-66B; Armored Cable Pulled from Junction Box       10/24/2019
Inspection
AR02298964 2BB-148B, Connector Pulled back from Elbolet           10/24/2019
Procedure
AR02298990 2CF SV 0901; Missing Screw on Junction Box Cover Panel 10/24/2019
Type
AR02299853 2019 NRC DBAI EQ - DPC-1381.05-00-0104                 10/29/2019
Designation
Description or Title
Revision or
Date
AR02280125
2019 CNS EQ DBAI Focused Self-Assessment AFI#5
07/02/2019
AR02283803
2019 CNS EQ DBAI Focused Self-Assessment AFI#8
07/25/2019
AR02284923
2019 CNS EQ DBAI Focused Self-Assessment AFI#6
08/01/2019
Corrective Action
Documents
Resulting from
Inspection
AR02294978
2019 DBAI EQ Mechanical Components Incorrectly
Labeled EQ=H
10/02/2019
AR02295176
2019 DBAI EQ Housekeeping and Material Condition in U2
DH
10/02/2019
AR02296270
Update EQMMs to Incorporate EQ Document Package
10/09/2019
AR02296584
Items Listed in EQMM not in EDB
10/10/2019
AR02298945
1CFHP0660, Armored Cable Pulled out of Junction Box
10/24/2019
AR02298957
2CA-66B; Armored Cable Pulled from Junction Box
10/24/2019
AR02298964
2BB-148B, Connector Pulled back from Elbolet
10/24/2019
AR02298990
2CF SV 0901; Missing Screw on Junction Box Cover Panel
10/24/2019
AR02299853
2019 NRC DBAI EQ - DPC-1381.05-00-0104
Documentation Error
Documentation Error
AR02299853 2019 NRC DBAI EQ - DPC-1381.05-00-0104                 10/29/2019
10/29/2019
AR02299853
2019 NRC DBAI EQ - DPC-1381.05-00-0104
Documentation Error
Documentation Error
AR02299853 2019 NRC DBAI EQ - DBC-1381-05-00-0104                 10/29/2019
10/29/2019
AR02299853
2019 NRC DBAI EQ - DBC-1381-05-00-0104
Documentation Error
Documentation Error
AR02300081 2019 NRC DBAI EQ - NCR 02233927 Screened Incorrectly   10/30/2019
10/29/2019
AR02300307 2019 NRC DBAI EQ - EQ procedure Issues with Sealant   10/31/2019
AR02300081
2019 NRC DBAI EQ - NCR 02233927 Screened Incorrectly
10/30/2019
AR02300307
2019 NRC DBAI EQ - EQ procedure Issues with Sealant
Use
Use
AR02300311 2019 NRC DBAI EQ Scotchcast 9 Resin Testing Issues     10/31/2019
10/31/2019
AR02300347 2019 NRC DBAI EQ: Lack of EQMM for TBOX enclosures     10/31/2019
AR02300311
AR02300347 CNS 2019 NRC DBAI EQ - EQ Documentation for           10/31/2019
2019 NRC DBAI EQ Scotchcast 9 Resin Testing Issues
10/31/2019
AR02300347
2019 NRC DBAI EQ: Lack of EQMM for TBOX enclosures
10/31/2019
AR02300347
CNS 2019 NRC DBAI EQ - EQ Documentation for
Electrical Enclosure Latches Missing Information
Electrical Enclosure Latches Missing Information
AR02300415 2019 NRC DBAI EQ: EQMM clarification report for       11/01/2019
10/31/2019
AR02300415
2019 NRC DBAI EQ: EQMM clarification report for
submergence
submergence
AR02300438 2019 NRC DBAI EQ, DPC 1381.05-00-0104 has error in     11/01/2019
11/01/2019
AR02300438
2019 NRC DBAI EQ, DPC 1381.05-00-0104 has error in
table
table
AR02300438 2019 NRC DBAI EQ - DPC 1381.05-00-0104 Error in       11/01/2019
11/01/2019
AR02300438
2019 NRC DBAI EQ - DPC 1381.05-00-0104 Error in
Tabled Data
Tabled Data
AR0230081 2019 NRC DBAI EQ - NCR 02233927 Screened Incorrectly   10/30/2019
11/01/2019
71111.21N Corrective Action AR02303599       2019 NRC DBAI EQ - EQMM-1393.01-P04-00, DeLaval,       11/20/2019
 
Documents                          Gems
Inspection
Resulting from    AR02303601      2019 NRC DBAI EQ Scotchcast 9N Equivalency             11/20/2019
Procedure
Inspection        AR02303602       2019 NRC DBAI EQ - EQMM-1393.01-G04-00,                 11/20/2019
Type
Designation
Description or Title
Revision or
Date
AR0230081
2019 NRC DBAI EQ - NCR 02233927 Screened Incorrectly
10/30/2019
AR02303599
2019 NRC DBAI EQ - EQMM-1393.01-P04-00, DeLaval,
Gems
11/20/2019
AR02303601
2019 NRC DBAI EQ Scotchcast 9N Equivalency
11/20/2019
AR02303602
2019 NRC DBAI EQ - EQMM-1393.01-G04-00,
Westinghouse Motors
Westinghouse Motors
AR02303697       2019 NRC DBAI EQ Electrical Continuity Testing Not     11/20/2019
11/20/2019
AR02303697
2019 NRC DBAI EQ Electrical Continuity Testing Not
Performed
Performed
AR02303697       2019 NRC DBAI EQ Electrical Continuity Testing Not     11/20/2019
11/20/2019
AR02303697
2019 NRC DBAI EQ Electrical Continuity Testing Not
Performed
Performed
AR02303851       2019 NRC DBAI EQ: Raychem Spec 44 Wire No               11/21/2019
11/20/2019
AR02303851
2019 NRC DBAI EQ: Raychem Spec 44 Wire No
Submergence Qualification
Submergence Qualification
AR02306022       2019 NRC DBAI EQ - Scotchcast 9/9N EQ File             12/05/2019
11/21/2019
AR02306022       2019 NRC DBAI EQ - Scotchcast 9/9N EQ File             12/05/2019
AR02306022
Drawings         CN-1499-CF.12-00 SG Feedwater Isolation Instrument Detail               Rev. 9
2019 NRC DBAI EQ - Scotchcast 9/9N EQ File
CN-1702-02.01   One-Line Diagram 4160V Essential Auxiliary Power System Rev. 18
2/05/2019
                                            (EPC) 4160V Switchgear No. 1ETA
AR02306022
CN-1721-21.09   Catawba Nuclear Station Panel Cutout Sheet, Stanwick-   Rev. 7
2019 NRC DBAI EQ - Scotchcast 9/9N EQ File
2/05/2019
Drawings
CN-1499-CF.12-00
SG Feedwater Isolation Instrument Detail
Rev. 9
CN-1702-02.01
One-Line Diagram 4160V Essential Auxiliary Power System  
(EPC) 4160V Switchgear No. 1ETA
Rev. 18
CN-1721-21.09
Catawba Nuclear Station Panel Cutout Sheet, Stanwick-
Type DG Sliding Link Terminal Blocks
Type DG Sliding Link Terminal Blocks
CN-1721-21.21   Catawba Nuclear Station Panel Cutout Sheet, States Co. Rev. 1
Rev. 7
CN-1721-21.21
Catawba Nuclear Station Panel Cutout Sheet, States Co.
Type-ZWM-Sliding Link Terminal Block
Type-ZWM-Sliding Link Terminal Block
CN-1734-01.04   Connection Diagram Safety Injection System (NI) B-Train Rev. 15
Rev. 1
CN-1734-01.04
Connection Diagram Safety Injection System (NI) B-Train
Motor Operated Valves 1NI010B, 1NI005B, 1NI178B,
Motor Operated Valves 1NI010B, 1NI005B, 1NI178B,
1NI183B & 1TBOX0019
1NI183B & 1TBOX0019
CN-2747-01.02-16 Connection Diagram Feedwater System (CF) Doghouse       Rev. 001
Rev. 15
CN-2747-01.02-16
Connection Diagram Feedwater System (CF) Doghouse
Level Switches
Level Switches
CNEE-0151-01.03 Elementary Diagram Safety Injection System (NI) B.I.T. Rev. 10
Rev. 001
CNEE-0151-01.03
Elementary Diagram Safety Injection System (NI) B.I.T.
Discharge Isolation Valve 1NI010B
Discharge Isolation Valve 1NI010B
CNEE-0151-01.45 Elementary Diagram Safety Injection System (NI) ND HDR Rev. 13
Rev. 10
CNEE-0151-01.45
Elementary Diagram Safety Injection System (NI) ND HDR
to N.C. Cold Legs A and B Valve 1NI178B
to N.C. Cold Legs A and B Valve 1NI178B
CNEE-0151-01.46 Elementary Diagram Safety Injection System (NI) NS HDR Rev. 12
Rev. 13
CNEE-0151-01.46
Elementary Diagram Safety Injection System (NI) NS HDR
to N.C. Hot Leg Isolation Valve 1NI183B
to N.C. Hot Leg Isolation Valve 1NI183B
CNEE-0245-01.05- Elementary Diagram Main Feedwater Sys. (CF) Doghouse   Rev. 9
Rev. 12
 
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
CNEE-0245-01.05-
Elementary Diagram Main Feedwater Sys. (CF) Doghouse
Safety Level Switches Train A
Safety Level Switches Train A
CNM 1210.04-     323 Transmitter Bottoming/Transfer Type, Bracket MTD., 12/16/1993
Rev. 9
0434 001        J/Box Output
CNM 1210.04-
71111.21N Drawings      CNM 1210.04-   Installation Specifications Transmitter Wiring and Mounting 7/27/1995
0434 001
23 Transmitter Bottoming/Transfer Type, Bracket MTD.,
J/Box Output
2/16/1993
CNM 1210.04-
0438 001
0438 001
CNM-1205.12-   Operator Pneumatic Hydraulic                                Rev. 6
Installation Specifications Transmitter Wiring and Mounting
7/27/1995
CNM-1205.12-
0050.002
0050.002
CNM-1205.12-   Operator Pneumatic Hydraulic Unit 1&2 Valves               Rev. 9
Operator Pneumatic Hydraulic
0050.003        1(2)CF33,42,51,60
Rev. 6
CNM-1205.12-   Cylinder Assembly Hydraulic Operator                        Rev. 3
CNM-1205.12-
0050.003
Operator Pneumatic Hydraulic Unit 1&2 Valves
1(2)CF33,42,51,60
Rev. 9
CNM-1205.12-
0050.004
0050.004
CNM-1205.12-   Reservoir Assembly Hydraulic Operator                      Rev. 7
Cylinder Assembly Hydraulic Operator
Rev. 3
CNM-1205.12-
0050.005
0050.005
MCM 1210.04-   Splicing & Sealing Procedure                                Rev. DC
Reservoir Assembly Hydraulic Operator
Rev. 7
MCM 1210.04-
215 001
215 001
Engineering   EC0000094280   CD201315 - CMP - Revise FWST Level Set-Points and           Rev. 3
Splicing & Sealing Procedure
Changes                      Annunciators
Rev. DC
EC0000408141    Revise EQMM to Include New Sections for EQ Cables &         Rev. 0
Engineering
Changes
EC0000094280
CD201315 - CMP - Revise FWST Level Set-Points and
Annunciators
Rev. 3
EC0000408141
Revise EQMM to Include New Sections for EQ Cables &
Splices
Splices
EC0000408781000 CN/MC/ON, CGI, PQL2, various Type ZWM Terminal             Rev. 0
Rev. 0
EC0000408781000 CN/MC/ON, CGI, PQL2, various Type ZWM Terminal
Blocks, States, MIR/RWF
Blocks, States, MIR/RWF
EC0000411757   CN/M/
Rev. 0
: [[contact::O. EE. PQL2]], 9230027814, Electrical Resin, 3M,         Rev. 0
EC0000411757
CN/M/
: [[contact::O. EE. PQL2]], 9230027814, Electrical Resin, 3M,
WB/DT
WB/DT
EC400046       C, CGI, Q2, Various, Enclosures, Hoffman, LFC/KCM           Rev. 0
Rev. 0
EC400046
C, CGI, Q2, Various, Enclosures, Hoffman, LFC/KCM
Hoffman Enclosures
Hoffman Enclosures
Engineering   CGD-3007.02-00- Stanwick Electrical Products, Terminal Block Pole           Rev. 0
Rev. 0
Evaluations  0004
Engineering
CGD-3010.02-06- 3M Company Scotchcast Electrical Resin No. 9               Rev. 19
Evaluations
CGD-3007.02-00-
0004
Stanwick Electrical Products, Terminal Block Pole
Rev. 0
CGD-3010.02-06-
0001
3M Company Scotchcast Electrical Resin No. 9
Rev. 19
CGD-3010.02-13-
0001
0001
CGD-3010.02-13- Attachment 7: Environmental Qualification Parameter         Rev. 1
7: Environmental Qualification Parameter
0001            Summaries for the various Dow Corning products
Summaries for the various Dow Corning products
CGD-3015.01-01- Technical Evaluation: Commercial Grade Evaluation -         Rev. 2
Rev. 1
0001            Enclosures
 
Miscellaneous ADAMS Accession Potential Part 21 on Wyle Laboratories Test Report Nos. 04/25/2016
Inspection
No. ML16155A354 45700-1 Rev. A dated November 21, 1988, and 45700-2
Procedure
Type
Designation
Description or Title
Revision or
Date
CGD-3015.01-01-
0001
Technical Evaluation: Commercial Grade Evaluation -
Enclosures
Rev. 2
Miscellaneous
ADAMS Accession
No. ML16155A354
Potential Part 21 on Wyle Laboratories Test Report Nos.
45700-1 Rev. A dated November 21, 1988, and 45700-2
Rev. A dated November 21, 1988, Submergence Test of
Rev. A dated November 21, 1988, Submergence Test of
Gems Liquid Level Transmitter
Gems Liquid Level Transmitter
CNLT-1780-03.02 Response to NUREG-0588                                     Rev. 8
04/25/2016
71111.21N Miscellaneous CNLT-1780-03.03 Environmental Qualification Criteria Manual (EQCM)           Rev. 35
CNLT-1780-03.02
CNM 1210.04-   Wyle Labs Test Report 45700-2                                Rev. 2
Response to NUREG-0588
Rev. 8
CNLT-1780-03.03
Environmental Qualification Criteria Manual (EQCM)
Rev. 35
CNM 1210.04-
0433.001
0433.001
CNM 1211.00-   Qualification Report for Traine CH531 Chiller Controls        Rev. 3
Wyle Labs Test Report 45700-2
Rev. 2
CNM 1211.00-
2492.037
2492.037
CNM 1318.00-   Motor Qualification Report, WCAP 8754                        Rev. 4
Qualification Report for Traine CH531 Chiller Controls
Rev. 3
CNM 1318.00-
0004.001
0004.001
CNM 1354.00-   Qualification Test of Instrument Cable in a Simulated SLB &   Rev. 2
Motor Qualification Report, WCAP 8754
0070.001        LOCA Environment
Rev. 4
CNM 1362.00-   Test Report on the Environmental Evaluation of Terminal       Rev. 02
CNM 1354.00-
0004, TR-028    Blocks for McGuire Nuclear Station
0070.001
CNM 1364.00-   Environmental Qualification of Electrical Insulating Tape for Rev. 1
Qualification Test of Instrument Cable in a Simulated SLB &
0005.001        McGuire and Catawba Nuclear Stations
LOCA Environment
CNM 1364.00-   EQR of Quick-Connect Fittings Used as Cable Entrance       Rev. D3
Rev. 2
0007.001        Seals
CNM 1362.00-
CNM-1205.12-   Feedwater Isolation Valve Pneumatic-Hydraulic Operator       Rev. 26
0004, TR-028
0013.001        O&M Manual
Test Report on the Environmental Evaluation of Terminal
CNM-1205.12-   Environmental Qualification Report for BWFC FWIV             Rev. 7
Blocks for McGuire Nuclear Station
26.001        Actuators
Rev. 02
CNM-1354.00-   Engineering Report No. 344 - Main Steam Line Break           Rev. 1
CNM 1364.00-
26            Qualification Test on Okozel Insulation
0005.001
CNM-1399.05-   3m Scotchcast Electrical Resin 9N Data Sheet                  Rev. 0
Environmental Qualification of Electrical Insulating Tape for
McGuire and Catawba Nuclear Stations
Rev. 1
CNM 1364.00-
0007.001
EQR of Quick-Connect Fittings Used as Cable Entrance
Seals
Rev. D3
CNM-1205.12-
0013.001
Feedwater Isolation Valve Pneumatic-Hydraulic Operator
O&M Manual
Rev. 26
CNM-1205.12-
26.001
Environmental Qualification Report for BWFC FWIV
Actuators
Rev. 7
CNM-1354.00-
26
Engineering Report No. 344 - Main Steam Line Break
Qualification Test on Okozel Insulation
Rev. 1
CNM-1399.05-
0366.001
0366.001
CNS-           Elector-Hydraulic-Pneumatic Actuator and Spare Parts for     Rev. 2
3m Scotchcast Electrical Resin 9N Data Sheet
205.12.00.0002 Feedwater Isolation Valves
Rev. 0
CNS-1354.04-00- Specification: Shielded and Unshielded 600 Volt               Rev. 0
CNS-
0006            Switchboard and Hook up Wire
205.12.00.0002
DPM-1393.01-   Environmental Qualification Package For Raychem               Rev. D04
Elector-Hydraulic-Pneumatic Actuator and Spare Parts for
0001            Corporation WCSF-U Heat Shrink Tubing
Feedwater Isolation Valves
DPM-1393.01-   EQ Test Summary for Solon Pressure Switches                  Rev. 000
Rev. 2  
 
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
CNS-1354.04-00-
0006
Specification: Shielded and Unshielded 600 Volt
Switchboard and Hook up Wire
Rev. 0
DPM-1393.01-
0001
Environmental Qualification Package For Raychem
Corporation WCSF-U Heat Shrink Tubing
Rev. D04
DPM-1393.01-
0040.001
0040.001
DPM1393.01-     Duke Power Test Summary For: Equipment Type: EGS             Rev. 1
EQ Test Summary for Solon Pressure Switches
0019.001        Tape Splices Manufacturer: SAIC/EGS Division
Rev. 000
DPM1393.01-
0019.001
Duke Power Test Summary For: Equipment Type: EGS
Tape Splices Manufacturer: SAIC/EGS Division
Model/Series No: SCOTCH 130C Insulating/Jacketing
Model/Series No: SCOTCH 130C Insulating/Jacketing
Tapes Report #EGS-TR-399.16-16
Tapes Report #EGS-TR-399.16-16
71111.21N Miscellaneous EGS-TR-880707- Test Report for Submergence Qualification of Raychem     10/05/1990
Rev. 1
EGS-TR-880707-
Test Report for Submergence Qualification of Raychem
WCSF-N Nuclear Line Cable Splice Assemblies for
WCSF-N Nuclear Line Cable Splice Assemblies for
Shearon Harris Nuclear Plant
Shearon Harris Nuclear Plant
EQMM-1393.01- ENVIRONMENTAL QUALIFICATION MAINTENANCE                 Rev. 10
10/05/1990
A04-00        MANUAL EQUIPMENT TYPE: FWIV ELECTRO-
EQMM-1393.01-
A04-00
ENVIRONMENTAL QUALIFICATION MAINTENANCE
MANUAL EQUIPMENT TYPE: FWIV ELECTRO-
HYDRAULIC-PNEUMATIC-ACTUATOR:
HYDRAULIC-PNEUMATIC-ACTUATOR:
MANUFACTURER: BORG-WARNER MODEL/SERIES:
MANUFACTURER: BORG-WARNER MODEL/SERIES:
PART NO. 37981
PART NO. 37981
EQMM-1393.01- Environmental Qualification Maintenance Manual - Low     Rev. 0
Rev. 10
C03-00        Voltage Power, Control and Instrumentation Cable /
EQMM-1393.01-
C03-00
Environmental Qualification Maintenance Manual - Low
Voltage Power, Control and Instrumentation Cable /
Okenite / Okozel Tefzel (280) Extruded Insulation System
Okenite / Okozel Tefzel (280) Extruded Insulation System
EQMM-1393.01- Environmental Qualification Maintenance Manual           Rev. 3
Rev. 0
M01-00        Equipment Type: Commercial Grade/Approved Vendor
EQMM-1393.01-
M01-00
Environmental Qualification Maintenance Manual
Equipment Type: Commercial Grade/Approved Vendor
Items
Items
EQMM-1393.01- Environmental Qualification Maintenance Manual           Rev. 3
Rev. 3
M01-01        Equipment Type: Connector Manufacturer: Swagelok Model
EQMM-1393.01-
M01-01
Environmental Qualification Maintenance Manual
Equipment Type: Connector Manufacturer: Swagelok Model
Series: QF Series Quick-Connect
Series: QF Series Quick-Connect
EQMM-1393.01- Environmental Qualification Maintenance Manual           Rev. 2
Rev. 3
M01-04        Equipment Type: Electrical Enclosure Latches -
EQMM-1393.01-
M01-04
Environmental Qualification Maintenance Manual
Equipment Type: Electrical Enclosure Latches -
Manufacturer: Hoffman - Model/Series: A-L31, A-
Manufacturer: Hoffman - Model/Series: A-L31, A-
FC412SS, A-FT44XSS
FC412SS, A-FT44XSS
EQMM-1393.01- Environmental Qualification Maintenance Manual           Rev. 8
Rev. 2
N04-00         Equipment Type: Differential Pressure Switch Inside
EQMM-1393.01-
Environmental Qualification Maintenance Manual
Rev. 8  
 
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
N04-00
Equipment Type: Differential Pressure Switch Inside
Containment; Manufacturer: Solon; Model/Series:
Containment; Manufacturer: Solon; Model/Series:
7PS1ADW / 7PS11DW / 7PSW11D2 / 7PSW1AD2
7PS1ADW / 7PS11DW / 7PSW11D2 / 7PSW1AD2
EQMM-1393.01- Devals, GEMS Level Transmitter Environmental             Rev. 10
EQMM-1393.01-
P04-00        Qualification Maintenance Manual
P04-00
EQMM-1393.01- ENVIRONMENTAL QUALIFICATION MAINTENANCE                 Rev. 2
Devals, GEMS Level Transmitter Environmental
R02-00        MANUAL - EQUIPMENT TYPE: CHILLER CONTROLS -
Qualification Maintenance Manual
Rev. 10
EQMM-1393.01-
R02-00
ENVIRONMENTAL QUALIFICATION MAINTENANCE
MANUAL - EQUIPMENT TYPE: CHILLER CONTROLS -
MANUFACTURER: TRANE (SUPPLIED BY: NUCLEAR
MANUFACTURER: TRANE (SUPPLIED BY: NUCLEAR
LOGISTICS, INC. (NLI)) - MODEL / SERIES: CH531 &
LOGISTICS, INC. (NLI)) - MODEL / SERIES: CH531 &
ASSOCIATED COMPONENTS
ASSOCIATED COMPONENTS
MCM 1211.00-   Nuclear Environmental Qualification Report: Solon       Rev. 0
Rev. 2
1505-001      Differential Pressure Switches for McGuire Nuclear Power
MCM 1211.00-
1505-001
Nuclear Environmental Qualification Report: Solon
Differential Pressure Switches for McGuire Nuclear Power
Station, Units 1 & 2
Station, Units 1 & 2
71111.21N Miscellaneous    MCM 1211.00-     Addendum 1 to CCL Report on Envir. Qual. of Solon DP       Rev. 002
Rev. 0
1505-002          Switch
MCM 1211.00-
MCM 1393.02-     Test Report on the Effects of Radiation Exposure on Some   Rev. 00
1505-002
0007, TR-047      Class 1E Electrical Components for the McGuire Nuclear
Addendum 1 to CCL Report on Envir. Qual. of Solon DP
Switch
Rev. 002
MCM 1393.02-
0007, TR-047
Test Report on the Effects of Radiation Exposure on Some
Class 1E Electrical Components for the McGuire Nuclear
Station
Station
Procedures       AD-EG-ALL-1103   Procurement Engineering Products                           Rev. 4
Rev. 00
AD-EG-ALL-1612   Environmental Qualification (EQ) Program                   Rev. 4
Procedures
AD-EG-ALL-1612   Environmental Qualification (EQ) Program                   Rev. 3
AD-EG-ALL-1103
AD-PI-ALL-0100   Corrective Action Program                                 Rev. 21
Procurement Engineering Products
IP-0-A-3010-021   Nitrogen System Charging for Main Feedwater (CF) Isolation Rev. 23
Rev. 4
Valve Operators
AD-EG-ALL-1612
IP-0-A-3010-022   Removal and Installation of                               Rev. 9
Environmental Qualification (EQ) Program
Rev. 4
AD-EG-ALL-1612
Environmental Qualification (EQ) Program
Rev. 3
AD-PI-ALL-0100
Corrective Action Program
Rev. 21
IP-0-A-3010-021
Nitrogen System Charging for Main Feedwater (CF)
Isolation Valve Operators
Rev. 23
IP-0-A-3010-022
Removal and Installation of
Main Feedwater (CF) Isolation Valve Operators
Main Feedwater (CF) Isolation Valve Operators
IP-0-A-3190-004   Maintenance Procedure for YC System Hot Gas Bypass Valve   Rev. 5
Rev. 9
Actuator
IP-0-A-3190-004
IP-2-A-3010-020   Unit 2 Main Feedwater (CF) System Calibration of Feedwater Rev. 10
Maintenance Procedure for YC System Hot Gas Bypass
Isolation Valves Pneumatic-Hydraulic Operators
Valve Actuator
IP/0/A/0200/029 A Sealing Cable Entrance Fittings on Class 1E Devices       Rev. 35
Rev. 5
IP/0/A/3820/020 Q Namco Limit Switch Replacement for Utilizing Quick         Rev. 13
IP-2-A-3010-020
Unit 2 Main Feedwater (CF) System Calibration of
Feedwater Isolation Valves Pneumatic-Hydraulic Operators
Rev. 10
IP/0/A/0200/029 A
Sealing Cable Entrance Fittings on Class 1E Devices
Rev. 35
IP/0/A/3820/020 Q
Namco Limit Switch Replacement for Utilizing Quick
Rev. 13  
 
Inspection
Procedure
Type
Designation
Description or Title
Revision or
Date
Connectors
Connectors
IP/0/A/3850/013 A Procedure for Cable Termination Sealing                   Rev. 64
IP/0/A/3850/013 A
IP/0/A/3850/013 B Procedure for Sealing Rigid Steel Field Run Conduit       Rev. 13
Procedure for Cable Termination Sealing
MP-0-A-7200-008   Feedwater Isolation Valve Corrective Maintenance           Rev. 22
Rev. 64
MP-0-A-7450-024   YC CHILLER HOT GAS BYPASS VALVE REMOVAL AND               Rev. 11
IP/0/A/3850/013 B
Procedure for Sealing Rigid Steel Field Run Conduit
Rev. 13
MP-0-A-7200-008
Feedwater Isolation Valve Corrective Maintenance
Rev. 22
MP-0-A-7450-024
YC CHILLER HOT GAS BYPASS VALVE REMOVAL AND
REPLACEMENT
REPLACEMENT
OP.0.A.6450.011   Control Room Ventilation/Chilled Water System             Rev. 146
Rev. 11
PT-2-A-4200-009   Engineered Safety Features Actuation Periodic Test         Rev. 170
OP.0.A.6450.011
PT-2-A-4200-018B CF Valve Inservice Test (CS)                               Rev. 21
Control Room Ventilation/Chilled Water System
Self-Assessments 02276400         Focused SAST: CNS EQ Program DBAI NRC inspection           06/06/2019
Rev. 146
Work Orders     01713620
PT-2-A-4200-009
01810701
Engineered Safety Features Actuation Periodic Test
2073010
Rev. 170
2079985
PT-2-A-4200-018B
CF Valve Inservice Test (CS)
Rev. 21
Self-Assessments 02276400
Focused SAST: CNS EQ Program DBAI NRC inspection
06/06/2019
Work Orders
01713620  
 
01810701  
 
2073010  
 
2079985  
 
20033963
20033963
18
}}
}}

Latest revision as of 16:48, 23 December 2024

Design Basis Assurance Inspection (Programs) Inspection Report 0500413/2019010 and 05000414/2019010
ML19354A856
Person / Time
Site: Catawba  Duke Energy icon.png
Issue date: 12/20/2019
From: James Baptist
NRC/RGN-II/DRS/EB2
To: Simril R
Duke Energy Carolinas
References
IR 2019010
Download: ML19354A856 (22)


Text

December 20, 2019

SUBJECT:

CATAWBA NUCLEAR STATION - DESIGN BASIS ASSURANCE INSPECTION (PROGRAMS) INSPECTION REPORT 05000413/2019010 AND 05000414/2019010

Dear Mr. Simril:

On November 21, 2019, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at Catawba Nuclear Station and discussed the results of this inspection with you and other members of your staff. The results of this inspection are documented in the enclosed report.

Three findings of very low safety significance (Green) are documented in this report. Three of these findings involved violations of NRC requirements. We are treating these violations as non-cited violations (NCVs) consistent with Section 2.3.2 of the Enforcement Policy.

If you contest the violations or the significance or severity of the violations documented in this inspection report, you should provide a response within 30 days of the date of this inspection report, with the basis for your denial, to the U.S. Nuclear Regulatory Commission, ATTN:

Document Control Desk, Washington, DC 20555-0001; with copies to the Regional Administrator, Region II; the Director, Office of Enforcement; and the NRC Resident Inspector at Catawba Nuclear Station.

If you disagree with a cross-cutting aspect assignment in this report, you should provide a response within 30 days of the date of this inspection report, with the basis for your disagreement, to the U.S. Nuclear Regulatory Commission, ATTN: Document Control Desk, Washington, DC 20555-0001; with copies to the Regional Administrator, Region II; and the NRC Resident Inspector at Catawba Nuclear Station.

This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with Title 10 of the Code of Federal Regulations 2.390, Public Inspections, Exemptions, Requests for Withholding.

Sincerely,

/RA/ Brian R. Bonser for/

James B. Baptist, Chief Engineering Branch 1 Division of Reactor Safety

Docket Nos. 05000413 and 05000414 License Nos. NPF-35 and NPF-52

Enclosure:

As stated

Inspection Report

Enclosure

Docket Numbers:

05000413 and 05000414

License Numbers:

NPF-35 and NPF-52

Report Numbers:

05000413/2019010 and 05000414/2019010

Enterprise Identifier: I-2019-010-0029

Licensee:

Duke Energy Carolina, LLC

Facility:

Catawba Nuclear Station

Location:

York, SC

Inspection Dates:

October 28, 2019 to November 21, 2019

Inspectors:

B. Collins, Senior Reactor Inspector

C. Franklin, Reactor Inspector

M. Greenleaf, Senior Reactor Inspector

M. Riley, Reactor Inspector

Approved By:

James B. Baptist, Chief

Engineering Branch 1

Division of Reactor Safety

SUMMARY

The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees performance by conducting a design basis assurance inspection (programs) inspection at Catawba Nuclear Station, in accordance with the Reactor Oversight Process. The Reactor Oversight Process is the NRCs program for overseeing the safe operation of commercial nuclear power reactors. Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information.

List of Findings and Violations

Failure to Qualify GEMS Level Transmitters for Submergence Cornerstone Significance Cross-Cutting Aspect Report Section Mitigating Systems Green NCV 05000413,05000414/2019010-01 Open/Closed

None (NPP)71111.21N The inspectors identified a Green finding and Non-cited Violation (NCV) of 10 CFR 50.49(f)when the licensee failed to demonstrate the GEMS containment sump level transmitter NILT5270 would meet its specified values for one year post-accident during submerged conditions in accordance with Section 6.5.4 of IEEE 323-1974, the standard the licensee chose in order to meet environmental qualification requirements.

Failure to Demonstrate Qualification of Conduit Sealant Compatibility for Electrical Wires and Cables Cornerstone Significance Cross-Cutting Aspect Report Section Mitigating Systems Green NCV 05000413,05000414/2019010-02 Open/Closed

None (NPP)71111.21N The inspectors identified a Green finding and associated Non-cited Violation (NCV) of 10 CFR 50.49(f) when the licensee failed to demonstrate the qualification of the conduit sealant and cable/wire interfaces utilizing Scotchcast Epoxy 9 in accordance with NUREG-0588 Section 2.2(7).

Failure to Assess Radiation and Thermal Degradation Effects of Replacement Sealant Equivalency Cornerstone Significance Cross-Cutting Aspect Report Section Mitigating Systems Green NCV 05000413,05000414/2019010-03 Open/Closed

[H.8] -

Procedure Adherence 71111.21N The inspectors identified a Green finding and Non-cited Violation (NCV) of 10 CFR 50.49(f)when the licensee failed to demonstrate that the qualification of Scotchcast Epoxy 9 was applicable to Scotchcast Epoxy 9N in accordance with Section 5.5.7 of procedure AD-EG-ALL-1612.

Additional Tracking Items

None.

INSPECTION SCOPES

Inspections were conducted using the appropriate portions of the inspection procedures (IPs) in effect at the beginning of the inspection unless otherwise noted. Currently approved IPs with their attached revision histories are located on the public website at http://www.nrc.gov/reading-rm/doc-collections/insp-manual/inspection-procedure/index.html. Samples were declared complete when the IP requirements most appropriate to the inspection activity were met consistent with Inspection Manual Chapter (IMC) 2515, Light-Water Reactor Inspection Program - Operations Phase. The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel to assess licensee performance and compliance with Commission rules and regulations, license conditions, site procedures, and standards.

REACTOR SAFETY

===71111.21N - Design Bases Assurance Inspection (Programs)

The inspectors evaluated Environmental Qualification program implementation through the sampling of the following components:

Select Sample Components to Review - Risk Significant/Low Design (Inside/Outside Containment) (IP Section 02.01)===

(1)1NDPUAMR, 1A Residual Heat Removal Pump Motor (Westinghouse)

(2) Commodity Item, Okozel Low Voltage Power/I&C Cable (Okenite)
(3) Commodity Item, Scotchcast 9 and 9N Epoxies (3M)
(4) Commodity Item, Terminal Blocks (States-and Stanwick-types)

(5)1TBOX0019, Terminal Block Enclosure (Hoffman)

(6)2TBOX0656, Terminal Block Enclosure (Hoffman)

(7)2CFHP0330, Main Feedwater Pneumatic-Hydraulic Isolation Valve (Borg-Warner)

(8)1YC362/MO, Hot Gas Bypass Valve Actuator (Jamesbury)

Select Sample Components to Review - Primary Containment (Inside Containment) (IP Section 02.01) (2 Samples)

(1)1NILT5270, Unit 1 Containment Sump Level Transmitter (DeLaval/GEMS)

(2)2VXPS5110, Pressure Switch (Solon)

INSPECTION RESULTS

Failure to Qualify GEMS Level Transmitters for Submergence Cornerstone Significance Cross-Cutting Aspect Report Section Mitigating Systems

Green NCV 05000413,05000414/2019010-01 Open/Closed

None (NPP)71111.21N The inspectors identified a Green finding and Non-cited Violation (NCV) of 10 CFR 50.49(f)when the licensee failed to demonstrate the GEMS containment sump level transmitter NILT5270 would meet its specified values for one year post-accident during submerged conditions in accordance with Section 6.5.4 of IEEE 323-1974, the standard the licensee chose in order to meet environmental qualification requirements.

Description:

The purpose of GEMS level transmitter 1NILT5270 is to provide post-accident monitoring of Unit 1 containment sump level. EQMM-1393.01-P04-00, Environmental Qualification Maintenance Manual Equipment Type: Level Transmitter Manufacturer: Delaval, Gems Model/Series: XM54852, XM54853, XM60620, XM60625, Rev. 0, stated that the post-accident operating time for the transmitter was one year. The transmitters could be submerged in the containment sump solution during the one-year post-accident requirement.

During the review of the qualification package for the transmitter, the inspectors identified that the loss of coolant accident (LOCA) testing did not simulate submerged conditions and that the post-LOCA testing only simulated a submerged condition for 30 minutes. The inspectors also identified that the EQMM did not analyze how failing to submerge the transmitter during the LOCA test and for only 30 minutes during Post-LOCA testing proved the transmitters could perform their intended function for up to one year post accident.

Additionally, on August 25, 2016, a 10 CFR Part 21 Notification was supplied to the NRC by NTS Huntsville notifying NRC that the qualification tests for the GEMS transmitters did not simulate the submergence depth of 15-16 ft. to the junction box as stated during the 30 minute submergence test. The Part 21 notification stated that the wire conduit was not sealed to the test chamber, but instead was left unattached to the test chamber accident environment. As a result, the submergence test did not demonstrate the junction box gaskets ability to prevent moisture intrusion into the internal components of the GEMs transmitter. In response to the Part 21, the licensee completed an evaluation in AR 02149240 which stated that the GEMS transmitter remained qualified due to the silicon oil fluid in the transmitter acting as a general barrier between any potential moisture intrusion into the transmitter junction box and the junction box wiring internals and that the wiring and splices used in the junction box were installed using Raychem splice products which had been qualified as an EQ environmental seal boundary. Due to questions from the inspectors, the licensee reviewed their evaluation of the Part 21 notification and determined that the failure of the unqualified junction box seal could allow sump fluid to displace the oil and submerge subcomponents of the transmitter. The licensee determined that of the subcomponents installed, only the Raychem Spec 44-insulated transmitter lead wires were not demonstrated to be qualified for submergence in post-LOCA sump conditions by other test reports or analysis.

The EQMM stated that the transmitter was qualified in accordance with IEEE 323-1974.

Section 6.5.4 of IEEE 323 states, The electric equipment type shall be considered to be qualified by demonstrating that the equipment performance will meet or exceed its specified values for the most severe environment or sequence of environments in the equipment specification during its qualified life. The inspectors determined that the qualification package for the GEMS 1NILT5270 transmitter did not demonstrate its ability to perform its function under the most severe conditions (e.g., submergence).

Corrective Actions: The licensee entered this issue into their corrective action program and performed an operability evaluation which determined that there was reasonable assurance that the transmitter could perform its intended safety function based on operating experience and the military specification of the wire which demonstrated the insulations ability to withstand different adverse chemicals.

Corrective Action References: AR 02303851

Performance Assessment:

Performance Deficiency: The failure to demonstrate the GEMS level transmitter would meet its specified values for one year post-accident during submerged conditions in accordance with Section 6.5.4 of IEEE 323-1974, the standard the licensee chose in order to meet environmental qualification requirements.

Screening: The inspectors determined the performance deficiency was more than minor because it was associated with the Equipment Performance attribute of the Mitigating Systems cornerstone and adversely affected the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, the failure to qualify the transmitter lead wires by testing or analysis for submergence did not ensure the wires could perform their function under wetted conditions for up to a year post accident.

Significance: The inspectors assessed the significance of the finding using Appendix A, The Significance Determination Process (SDP) for Findings At-Power. The inspectors assessed the significance of the finding using Inspection Manual Chapter (IMC) 0609, Att. 4, "Initial Characterization of Findings," issued October 7, 2016, for the Mitigating Systems cornerstone, and IMC 0609, App. A, "The Significance Determination Process (SDP) for Findings At-Power," issued June 19, 2012, and determined the finding was of very low safety significance (Green) because the finding was a deficiency affecting the qualification of a mitigating structure, system, or component (SSC) and the SSC maintained its operability.

Cross-Cutting Aspect: Not Present Performance. No cross-cutting aspect was assigned to this finding because the inspectors determined the finding did not reflect present licensee performance.

Enforcement:

Violation: 10 CFR 50.49(f) required, "Each item of electric equipment important to safety must be qualified by one of the following methods:

(1) Testing an identical item of equipment under identical conditions or under similar conditions with a supporting analysis to show that the equipment to be qualified is acceptable.
(2) Testing a similar item of equipment with a supporting analysis to show that the equipment to be qualified is acceptable.
(3) Experience with identical or similar equipment under similar conditions with a supporting analysis to show that the equipment to be qualified is acceptable.
(4) Analysis in combination with partial type test data that supports the analytical assumptions and conclusions."

Contrary to the above, since the earliest date of record for the EQMM package in 1991, the licensee failed to qualify the GEMS containment sump level transmitter NILT5270 for submergence by test or analysis for post-accident conditions of one year.

Enforcement Action: This violation is being treated as a non-cited violation, consistent with Section 2.3.2 of the Enforcement Policy.

Failure to Demonstrate Qualification of Conduit Sealant Compatibility for Electrical Wires and Cables Cornerstone Significance Cross-Cutting Aspect Report Section Mitigating Systems

Green NCV 05000413,05000414/2019010-02 Open/Closed

None (NPP)71111.21N The inspectors identified a Green finding and associated Non-cited Violation (NCV) of 10 CFR 50.49(f) when the licensee failed to demonstrate the qualification of the conduit sealant and cable/wire interfaces utilizing Scotchcast Epoxy 9 in accordance with NUREG-0588 Section 2.2(7).

Description:

Duke EQ Files EQMM-1391.01-M01-01, Rev. 3 and CNM 1364.00-0007.001, Rev. D3 contained the licensee's basis for environmental qualification (EQ) of conduit seals utilizing Scotchcast Epoxy 9. In the EQ files, the licensee documented a test report that utilized the epoxy as a sealant to prevent moisture intrusion into equipment electrical conduits in accordance with Category II of NRC NUREG-0588. The focus of the testing was to demonstrate the sealing ability of the epoxy around a pair of tefzel-insulated wires in a Swagelock QF quick-connect pipe fitting by testing a mock-up conduit sealing configuration. The testing generally demonstrated the capability of the epoxy to provide a moisture barrier - but due to the use of de-energized wiring - failed to demonstrate that the interface between the epoxy and wires/cables installed in the field were compatible and capable of performing their functions of providing for the necessary transmission of signals or power. By not demonstrating that the sealant was compatible (i.e. did not adversely impact the electrical function of the wire/cable) with the field configurations, the licensee failed to demonstrate that the field configurations were qualified in accordance with 10 CFR 50.49.

For the conduit sealant locations in the station scoped into the licensee's EQ program, the licensee adhered to Category II requirements of NRC NUREG-0588 for qualification and qualification testing to meet 10 CFR 50.49. Section 2.2(7) of the NUREG states that "performance characteristics be verified before, after, and periodically during testing throughout the range of required operability." By testing the sealant's mechanical sealing function without confirming that the epoxy and wire/cable did not adversely impact their electrical function of passing power/signals to/from important to safety equipment, the licensee failed to demonstrate that the sealant was qualified for the installed configurations in the field.

Corrective Actions: The station entered this into their Corrective Action Program (CAP) as ARs 023011 and 02303697. Although environmental qualification had not been demonstrated and documented, the licensee identified other tests that had been performed on other wire types with Scotchcast Epoxy 9 (e.g. NAMCO limit switch lead wire and Mark WPA 14 gauge hookup wire). The licensee's review of this additional testing provided reasonable assurance that the installed configurations in the plant would be capable of performing their intended safety functions.

Corrective Action References: AR 023011023011and 02303697

Performance Assessment:

Performance Deficiency: The failure to verify the Scotchast Epoxy 9 sealant cable/wire interface would meet its electrical performance characteristics before, after, and periodically during testing throughout the range of its required operability in accordance with Section 2.2.7 of NUREG-0588 (Category II) was a performance deficiency.

Screening: The inspectors determined the performance deficiency was more than minor because it was associated with the Equipment Performance attribute of the Mitigating Systems cornerstone and adversely affected the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, the failure to ensure that the cable/wire interface with the sealant would not adversely impact the safety function fails to ensure the availability, reliability, and capability of the electrical equipment important to safety that must send or receive power/signals when challenged with the deleterious effects of aging and harsh environmental conditions.

Significance: The inspectors assessed the significance of the finding using Appendix A, The Significance Determination Process (SDP) for Findings At-Power. The inspectors assessed the significance of the finding using Inspection Manual Chapter (IMC) 0609, Att. 4, "Initial Characterization of Findings," issued October 7, 2016, for the Mitigating Systems cornerstone, and IMC 0609, App. A, "The Significance Determination Process (SDP) for Findings At-Power," issued June 19, 2012, and determined the finding was of very low safety significance (Green) because the finding was a deficiency affecting the qualification of a mitigating structure, system, or component (SSC) and the SSC maintained its operability.

Cross-Cutting Aspect: Not Present Performance. No cross-cutting aspect was assigned to this finding because the inspectors determined the finding did not reflect present licensee performance.

Enforcement:

Violation: 10 CFR 50.49(f) required, "Each item of electric equipment important to safety must be qualified by one of the following methods:

(1) Testing an identical item of equipment under identical conditions or under similar conditions with a supporting analysis to show that the equipment to be qualified is acceptable.
(2) Testing a similar item of equipment with a supporting analysis to show that the equipment to be qualified is acceptable.
(3) Experience with identical or similar equipment under similar conditions with a supporting analysis to show that the equipment to be qualified is acceptable.
(4) Analysis in combination with partial type test data that supports the analytical assumptions and conclusions."

Contrary to the above, since the qualification file for Scotchcast Epoxy 9 had been performed in 2001, the licensee failed to qualify the epoxy by any of the four methods described above.

Enforcement Action: This violation is being treated as a non-cited violation, consistent with Section 2.3.2 of the Enforcement Policy.

Failure to Assess Radiation and Thermal Degradation Effects of Replacement Sealant Equivalency Cornerstone Significance Cross-Cutting Aspect Report Section Mitigating Systems

Green NCV 05000413,05000414/2019010-03 Open/Closed

[H.8] -

Procedure Adherence 71111.21N The inspectors identified a Green finding and Non-cited Violation (NCV) of 10 CFR 50.49(f)when the licensee failed to demonstrate that the qualification of Scotchcast Epoxy 9 was applicable to Scotchcast Epoxy 9N in accordance with Section 5.5.7 of procedure AD-EG-ALL-1612.

Description:

3M Corporation changed the chemical composition of the Part B of its Scotchcast Epoxy 9 two-part formulation from a nonylphenol component to formulation of cashew, nutshell liq.ccidentale, anacardiaceae, and toluene components. In 2018, the licensee generated an equivalency evaluation in engineering change EC 144757, Rev. 0 to evaluate the differences between the original formulation (Scotchcast Epoxy 9) and the new formulation (i.e. Scotchcast Epoxy 9N). The focus of the evaluation was to determine if the environmental qualification (EQ) performed for the original epoxy was applicable to the new epoxy. The licensee reviewed the material safety data sheets (MSDSs) of the two epoxies, performed durometer testing of representative samples of both epoxies, and performed Fourier Transform Infrared (FTIR) Spectroscopy to determine if the materials were similar enough to warrant the use of the Scotchcast Epoxy 9's qualification file to that of the Scotchcast 9N's. Based on a FTIR high percentage match (>80%) and similar durometer testing, the licensee concluded that the materials were similar enough and qualification of Scotchcast Epoxy 9 was applicable to Scotchcast Epoxy 9N.

The inspectors reviewed the engineering change and noted that FTIR spectroscopy and durometer testing would provide information showing similarity between the chemical constituents and discrepancies in hardness between the two epoxies (respectively), but neither test individually (nor combined) could provide detailed information on how these different epoxies would behave when subjected to the deleterious effects of nuclear radiation and thermal degradation (i.e. aging). Inspectors reviewed the licensee's EQ procedure, AD-EG-ALL-1612, Revs. 3 and 4 and noted that Section 5.5.7(11)(b)(4)(a) stated, in part, that:

"materials of construction shall either be the same or equivalent and differences shall be shown not to adversely affect performance of the safety function." Furthermore, the procedure states that the evaluations should, "evaluate the differences in material properties.

Minor chemical differences can cause significant variations in properties (e.g. radiation-withstand capability, dielectric strength, thermal aging, chemical interactions, and changes in material activation energy."

The licensee's technical review of the differences between the two epoxies lacked the necessary level of detail to demonstrate that the Scotchcast Epoxy 9N - which is chemically different - will age and withstand nuclear radiation in the same (or better) manner than the qualified Scotchcast Epoxy 9. As a result of the inspection, the licensee contacted 3M and determined that mechanical and electrical properties were similar between the two epoxies, however, no radiation or thermal degradation comparisons had been made between the materials.

Corrective Actions: The licensee entered this issue into their corrective action program (CAP)as AR 0203601. The licensee determined that the Scotchcast Epoxy 9N had only been used in four recent work orders and based on a review of the material data sheets and on the technical opinion of the licensee's subject matter experts, the licensee concluded that the four seals in question were capable of performing their safety function.

Corrective Action References: AR 0203601

Performance Assessment:

Performance Deficiency: The inspectors determined that the failure to perform an evaluation that appropriately considered the effects of nuclear radiation and thermal aging in accordance with procedure AD-EG-ALL-1612, Section 5.5.7(11)(b)(4)(a) was a performance deficiency.

Screening: The inspectors determined the performance deficiency was more than minor because it was associated with the Equipment Performance attribute of the Mitigating Systems cornerstone and adversely affected the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, the failure to perform the necessary evaluation of Scotchcast 9N's capability to withstand nuclear radiation and thermal aging failed to ensure the reliability and capability of the Scotchcast Epoxy 9N to perform its safety function of protecting equipment important to safety from the deleterious effects of potential steam and moisture intrusion in the four locations where it had been applied to electrical conduits for the span of their designated life.

Significance: The inspectors assessed the significance of the finding using Appendix A, The Significance Determination Process (SDP) for Findings At-Power. The inspectors assessed the significance of the finding using Inspection Manual Chapter (IMC) 0609, Att. 4, "Initial Characterization of Findings," issued October 7, 2016, for the Mitigating Systems cornerstone, and IMC 0609, App. A, "The Significance Determination Process (SDP) for Findings At-Power," issued June 19, 2012, and determined the finding was of very low safety significance (Green) because the finding was a deficiency affecting the qualification of a mitigating structure, system, or component (SSC) and the SSC maintained its operability.

Cross-Cutting Aspect: H.8 - Procedure Adherence: Individuals follow processes, procedures, and work instructions. This finding is indicative of current performance because the finding occurred within the last 3 years. This finding was assigned a cross-cutting aspect of H.8 because the licensee's failure to adhere to their EQ procedure AD-EG-ALL-1612, Section 5.5.7(11)(b)(4)(a) was the most significant contributor to the performance deficiency.

Enforcement:

Violation: 10 CFR 50.49(f) required, "Each item of electric equipment important to safety must be qualified by one of the following methods:

(1) Testing an identical item of equipment under identical conditions or under similar conditions with a supporting analysis to show that the equipment to be qualified is acceptable.
(2) Testing a similar item of equipment with a supporting analysis to show that the equipment to be qualified is acceptable.
(3) Experience with identical or similar equipment under similar conditions with a supporting analysis to show that the equipment to be qualified is acceptable.
(4) Analysis in combination with partial type test data that supports the analytical assumptions and conclusions."

Contrary to the above, since the issuance of EC 144757 in 2018, the licensee failed to qualify the Scotchcast Epoxy 9N by any of the four methods described above.

Enforcement Action: This violation is being treated as a non-cited violation, consistent with Section 2.3.2 of the Enforcement Policy.

EXIT MEETINGS AND DEBRIEFS

The inspectors verified no proprietary information was retained or documented in this report.

  • On November 21, 2019, the inspectors presented the design basis assurance inspection (programs) inspection results to Robert Simril and other members of the licensee staff.

DOCUMENTS REVIEWED

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

71111.21N Calculations

CGD-3007.02-04-

0001 Attachment

Acton Environmental Testing Corporation Test Report:

States Terminal Blocks and Test Switches

Rev. 5

CNC-1206.03-00-

0001

Flood Level for Structures Outside the Reactor Building

Rev. 26

CNC-1206.03-00-

0004

Environmental Effects Due to Pipe Rupture Outside

Containment

Rev. 3

CNC-1381.05-00-

0158

FWIV Life Extension

Rev. 3

CNS-1465.00-00-

20

Design Basis Specification for the Flooding from Internal

Sources

Rev. 1

CNS-1591.CF-00-

0001

DESIGN BASIS SPECIFICATION FOR THE FEEDWATER

(CF) SYSTEM

Rev. 34

DPC-1381.05-00-

0009

Qualified Life of AGASTAT E7000 Series Timing Relays

Rev. 5

DPC-1381.05-00-

0017

Electrical Enclosure Latching Environmental Qualification

Analysis

Rev. 0

DPC-1381.05-00-

0032

Qualified Life Analysis for Brand Rex Flame Retardant

Cross-Linked Polyethylene Insulated Instrument Cable

Rev. 2

DPC-1381.05-00-

0050

Environmental Qualification (EQ) Evaluation of Equipment

Installed in the Doghouse Buildings

Rev. 1

DPC-1381.05-00-

0077

Environmental Qualification (EQ) Qualified Life Analysis

(TLAA) for Trane Chiller Controls Supporting CNS License

Renewal

Rev. 0

DPC-1381.05-00-

0082

Environmental Qualification (EQ) Qualified Life Analysis

(TLAA) for DeLaval, GEMS Level Transmitters Supporting

MNS and CNS License Renewal

Rev. 0

DPC-1381.05-00-

0087

Environmental Qualification (EQ) Qualified Life Analysis

(TLAA) for Okonite Flame Retardant Ethylene Propolene

(Okonite-FMR) Low Voltage, Control and Instrument Cable

Rev. 1

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

Supporting MNS and CNS License Renewal

DPC-1381.05-00-

0093

Environmental Qualification (EQ) Qualified Life Analysis

(TLAA) for Scotch 130C Insulating/Jacketing Tapes

Supporting MNS and CNS License Renewal

Rev. 0

DPC-1381.05-00-

0104

Environmental Qualification (EQ) Qualified Life Analysis

(TLAA) for Terminal Blocks Supporting MNS and CNS

License Renewal

Rev. 000

Corrective Action

Documents

AR01528008

At Risk Procurement of 3M Scotchcast Resin No. 9

11/13/2014

AR02016420

EQ Rev Tracking

03/31/2016

AR02096602

2017 NRC EQ Program Inspection - Cable/Splice EQML

Question

2/01/2017

AR02149240-01

AR02165587

Fleet License Renewal EQ TLAA Additional Action Tracking 11/14/2017

AR02172829

Tracking of FLRIT EQ TLAA questions to Fleet EQ

2/18/2017

AR022242460

PE-003, Environmental Qualification (EQ) Transformation

11/09/2018

AR02233927

EQ Program Documentation Inefficiencies

09/29/2018

AR02235165

Assignment 1: Develop and execute an EQMM deficiency

recovery plan

10/11/2018

AR02253701

EQ Equipment in a Non-EQ Zone

01/22/2019

AR02275149

Evaluation of WL Sump Pumps Support of CA Operability

05/30/2019

AR02275671

Complete all prep activities associated with CNS EQ NRC

DBAI

06/04/2019

AR02275676

EQ DBAI Self-Assessment - EQML Deficiency

06/04/2019

AR02275676

EQ DBAI Self-Assessment - EQML Deficiency

06/04/2019

AR02275785

2019 CNS EQ DBAI Self-Assessment - EQ Master List

Data Gaps

06/05/2019

AR02276144

EDB discrepancy found during EQ program self-

assessment

06/06/2019

AR02280114

2019 CNS EQ DBAI Focused Self-Assessment AFI#1

07/02/2019

AR02280116

2019 CNS EQ DBAI Focused Self-Assessment AFI#2

07/02/2019

AR02280118

2019 CNS EQ DBAI Focused Self-Assessment AFI#3

07/02/2019

AR02280121

2019 CNS EQ DBAI Focused Self-Assessment AFI#4

07/02/2019

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

AR02280125

2019 CNS EQ DBAI Focused Self-Assessment AFI#5

07/02/2019

AR02283803

2019 CNS EQ DBAI Focused Self-Assessment AFI#8

07/25/2019

AR02284923

2019 CNS EQ DBAI Focused Self-Assessment AFI#6

08/01/2019

Corrective Action

Documents

Resulting from

Inspection

AR02294978

2019 DBAI EQ Mechanical Components Incorrectly

Labeled EQ=H

10/02/2019

AR02295176

2019 DBAI EQ Housekeeping and Material Condition in U2

DH

10/02/2019

AR02296270

Update EQMMs to Incorporate EQ Document Package

10/09/2019

AR02296584

Items Listed in EQMM not in EDB

10/10/2019

AR02298945

1CFHP0660, Armored Cable Pulled out of Junction Box

10/24/2019

AR02298957

2CA-66B; Armored Cable Pulled from Junction Box

10/24/2019

AR02298964

2BB-148B, Connector Pulled back from Elbolet

10/24/2019

AR02298990

2CF SV 0901; Missing Screw on Junction Box Cover Panel

10/24/2019

AR02299853

2019 NRC DBAI EQ - DPC-1381.05-00-0104

Documentation Error

10/29/2019

AR02299853

2019 NRC DBAI EQ - DPC-1381.05-00-0104

Documentation Error

10/29/2019

AR02299853

2019 NRC DBAI EQ - DBC-1381-05-00-0104

Documentation Error

10/29/2019

AR02300081

2019 NRC DBAI EQ - NCR 02233927 Screened Incorrectly

10/30/2019

AR02300307

2019 NRC DBAI EQ - EQ procedure Issues with Sealant

Use

10/31/2019

AR02300311

2019 NRC DBAI EQ Scotchcast 9 Resin Testing Issues

10/31/2019

AR02300347

2019 NRC DBAI EQ: Lack of EQMM for TBOX enclosures

10/31/2019

AR02300347

CNS 2019 NRC DBAI EQ - EQ Documentation for

Electrical Enclosure Latches Missing Information

10/31/2019

AR02300415

2019 NRC DBAI EQ: EQMM clarification report for

submergence

11/01/2019

AR02300438

2019 NRC DBAI EQ, DPC 1381.05-00-0104 has error in

table

11/01/2019

AR02300438

2019 NRC DBAI EQ - DPC 1381.05-00-0104 Error in

Tabled Data

11/01/2019

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

AR0230081

2019 NRC DBAI EQ - NCR 02233927 Screened Incorrectly

10/30/2019

AR02303599

2019 NRC DBAI EQ - EQMM-1393.01-P04-00, DeLaval,

Gems

11/20/2019

AR02303601

2019 NRC DBAI EQ Scotchcast 9N Equivalency

11/20/2019

AR02303602

2019 NRC DBAI EQ - EQMM-1393.01-G04-00,

Westinghouse Motors

11/20/2019

AR02303697

2019 NRC DBAI EQ Electrical Continuity Testing Not

Performed

11/20/2019

AR02303697

2019 NRC DBAI EQ Electrical Continuity Testing Not

Performed

11/20/2019

AR02303851

2019 NRC DBAI EQ: Raychem Spec 44 Wire No

Submergence Qualification

11/21/2019

AR02306022

2019 NRC DBAI EQ - Scotchcast 9/9N EQ File

2/05/2019

AR02306022

2019 NRC DBAI EQ - Scotchcast 9/9N EQ File

2/05/2019

Drawings

CN-1499-CF.12-00

SG Feedwater Isolation Instrument Detail

Rev. 9

CN-1702-02.01

One-Line Diagram 4160V Essential Auxiliary Power System

(EPC) 4160V Switchgear No. 1ETA

Rev. 18

CN-1721-21.09

Catawba Nuclear Station Panel Cutout Sheet, Stanwick-

Type DG Sliding Link Terminal Blocks

Rev. 7

CN-1721-21.21

Catawba Nuclear Station Panel Cutout Sheet, States Co.

Type-ZWM-Sliding Link Terminal Block

Rev. 1

CN-1734-01.04

Connection Diagram Safety Injection System (NI) B-Train

Motor Operated Valves 1NI010B, 1NI005B, 1NI178B,

1NI183B & 1TBOX0019

Rev. 15

CN-2747-01.02-16

Connection Diagram Feedwater System (CF) Doghouse

Level Switches

Rev. 001

CNEE-0151-01.03

Elementary Diagram Safety Injection System (NI) B.I.T.

Discharge Isolation Valve 1NI010B

Rev. 10

CNEE-0151-01.45

Elementary Diagram Safety Injection System (NI) ND HDR

to N.C. Cold Legs A and B Valve 1NI178B

Rev. 13

CNEE-0151-01.46

Elementary Diagram Safety Injection System (NI) NS HDR

to N.C. Hot Leg Isolation Valve 1NI183B

Rev. 12

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

CNEE-0245-01.05-

Elementary Diagram Main Feedwater Sys. (CF) Doghouse

Safety Level Switches Train A

Rev. 9

CNM 1210.04-

0434 001

23 Transmitter Bottoming/Transfer Type, Bracket MTD.,

J/Box Output

2/16/1993

CNM 1210.04-

0438 001

Installation Specifications Transmitter Wiring and Mounting

7/27/1995

CNM-1205.12-

0050.002

Operator Pneumatic Hydraulic

Rev. 6

CNM-1205.12-

0050.003

Operator Pneumatic Hydraulic Unit 1&2 Valves

1(2)CF33,42,51,60

Rev. 9

CNM-1205.12-

0050.004

Cylinder Assembly Hydraulic Operator

Rev. 3

CNM-1205.12-

0050.005

Reservoir Assembly Hydraulic Operator

Rev. 7

MCM 1210.04-

215 001

Splicing & Sealing Procedure

Rev. DC

Engineering

Changes

EC0000094280

CD201315 - CMP - Revise FWST Level Set-Points and

Annunciators

Rev. 3

EC0000408141

Revise EQMM to Include New Sections for EQ Cables &

Splices

Rev. 0

EC0000408781000 CN/MC/ON, CGI, PQL2, various Type ZWM Terminal

Blocks, States, MIR/RWF

Rev. 0

EC0000411757

CN/M/

O. EE. PQL2, 9230027814, Electrical Resin, 3M,

WB/DT

Rev. 0

EC400046

C, CGI, Q2, Various, Enclosures, Hoffman, LFC/KCM

Hoffman Enclosures

Rev. 0

Engineering

Evaluations

CGD-3007.02-00-

0004

Stanwick Electrical Products, Terminal Block Pole

Rev. 0

CGD-3010.02-06-

0001

3M Company Scotchcast Electrical Resin No. 9

Rev. 19

CGD-3010.02-13-

0001

7: Environmental Qualification Parameter

Summaries for the various Dow Corning products

Rev. 1

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

CGD-3015.01-01-

0001

Technical Evaluation: Commercial Grade Evaluation -

Enclosures

Rev. 2

Miscellaneous

ADAMS Accession

No. ML16155A354

Potential Part 21 on Wyle Laboratories Test Report Nos.

45700-1 Rev. A dated November 21, 1988, and 45700-2

Rev. A dated November 21, 1988, Submergence Test of

Gems Liquid Level Transmitter

04/25/2016

CNLT-1780-03.02

Response to NUREG-0588

Rev. 8

CNLT-1780-03.03

Environmental Qualification Criteria Manual (EQCM)

Rev. 35

CNM 1210.04-

0433.001

Wyle Labs Test Report 45700-2

Rev. 2

CNM 1211.00-

2492.037

Qualification Report for Traine CH531 Chiller Controls

Rev. 3

CNM 1318.00-

0004.001

Motor Qualification Report, WCAP 8754

Rev. 4

CNM 1354.00-

0070.001

Qualification Test of Instrument Cable in a Simulated SLB &

LOCA Environment

Rev. 2

CNM 1362.00-

0004, TR-028

Test Report on the Environmental Evaluation of Terminal

Blocks for McGuire Nuclear Station

Rev. 02

CNM 1364.00-

0005.001

Environmental Qualification of Electrical Insulating Tape for

McGuire and Catawba Nuclear Stations

Rev. 1

CNM 1364.00-

0007.001

EQR of Quick-Connect Fittings Used as Cable Entrance

Seals

Rev. D3

CNM-1205.12-

0013.001

Feedwater Isolation Valve Pneumatic-Hydraulic Operator

O&M Manual

Rev. 26

CNM-1205.12-

26.001

Environmental Qualification Report for BWFC FWIV

Actuators

Rev. 7

CNM-1354.00-

26

Engineering Report No. 344 - Main Steam Line Break

Qualification Test on Okozel Insulation

Rev. 1

CNM-1399.05-

0366.001

3m Scotchcast Electrical Resin 9N Data Sheet

Rev. 0

CNS-

205.12.00.0002

Elector-Hydraulic-Pneumatic Actuator and Spare Parts for

Feedwater Isolation Valves

Rev. 2

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

CNS-1354.04-00-

0006

Specification: Shielded and Unshielded 600 Volt

Switchboard and Hook up Wire

Rev. 0

DPM-1393.01-

0001

Environmental Qualification Package For Raychem

Corporation WCSF-U Heat Shrink Tubing

Rev. D04

DPM-1393.01-

0040.001

EQ Test Summary for Solon Pressure Switches

Rev. 000

DPM1393.01-

0019.001

Duke Power Test Summary For: Equipment Type: EGS

Tape Splices Manufacturer: SAIC/EGS Division

Model/Series No: SCOTCH 130C Insulating/Jacketing

Tapes Report #EGS-TR-399.16-16

Rev. 1

EGS-TR-880707-

Test Report for Submergence Qualification of Raychem

WCSF-N Nuclear Line Cable Splice Assemblies for

Shearon Harris Nuclear Plant

10/05/1990

EQMM-1393.01-

A04-00

ENVIRONMENTAL QUALIFICATION MAINTENANCE

MANUAL EQUIPMENT TYPE: FWIV ELECTRO-

HYDRAULIC-PNEUMATIC-ACTUATOR:

MANUFACTURER: BORG-WARNER MODEL/SERIES:

PART NO. 37981

Rev. 10

EQMM-1393.01-

C03-00

Environmental Qualification Maintenance Manual - Low

Voltage Power, Control and Instrumentation Cable /

Okenite / Okozel Tefzel (280) Extruded Insulation System

Rev. 0

EQMM-1393.01-

M01-00

Environmental Qualification Maintenance Manual

Equipment Type: Commercial Grade/Approved Vendor

Items

Rev. 3

EQMM-1393.01-

M01-01

Environmental Qualification Maintenance Manual

Equipment Type: Connector Manufacturer: Swagelok Model

Series: QF Series Quick-Connect

Rev. 3

EQMM-1393.01-

M01-04

Environmental Qualification Maintenance Manual

Equipment Type: Electrical Enclosure Latches -

Manufacturer: Hoffman - Model/Series: A-L31, A-

FC412SS, A-FT44XSS

Rev. 2

EQMM-1393.01-

Environmental Qualification Maintenance Manual

Rev. 8

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

N04-00

Equipment Type: Differential Pressure Switch Inside

Containment; Manufacturer: Solon; Model/Series:

7PS1ADW / 7PS11DW / 7PSW11D2 / 7PSW1AD2

EQMM-1393.01-

P04-00

Devals, GEMS Level Transmitter Environmental

Qualification Maintenance Manual

Rev. 10

EQMM-1393.01-

R02-00

ENVIRONMENTAL QUALIFICATION MAINTENANCE

MANUAL - EQUIPMENT TYPE: CHILLER CONTROLS -

MANUFACTURER: TRANE (SUPPLIED BY: NUCLEAR

LOGISTICS, INC. (NLI)) - MODEL / SERIES: CH531 &

ASSOCIATED COMPONENTS

Rev. 2

MCM 1211.00-

1505-001

Nuclear Environmental Qualification Report: Solon

Differential Pressure Switches for McGuire Nuclear Power

Station, Units 1 & 2

Rev. 0

MCM 1211.00-

1505-002

Addendum 1 to CCL Report on Envir. Qual. of Solon DP

Switch

Rev. 002

MCM 1393.02-

0007, TR-047

Test Report on the Effects of Radiation Exposure on Some

Class 1E Electrical Components for the McGuire Nuclear

Station

Rev. 00

Procedures

AD-EG-ALL-1103

Procurement Engineering Products

Rev. 4

AD-EG-ALL-1612

Environmental Qualification (EQ) Program

Rev. 4

AD-EG-ALL-1612

Environmental Qualification (EQ) Program

Rev. 3

AD-PI-ALL-0100

Corrective Action Program

Rev. 21

IP-0-A-3010-021

Nitrogen System Charging for Main Feedwater (CF)

Isolation Valve Operators

Rev. 23

IP-0-A-3010-022

Removal and Installation of

Main Feedwater (CF) Isolation Valve Operators

Rev. 9

IP-0-A-3190-004

Maintenance Procedure for YC System Hot Gas Bypass

Valve Actuator

Rev. 5

IP-2-A-3010-020

Unit 2 Main Feedwater (CF) System Calibration of

Feedwater Isolation Valves Pneumatic-Hydraulic Operators

Rev. 10

IP/0/A/0200/029 A

Sealing Cable Entrance Fittings on Class 1E Devices

Rev. 35

IP/0/A/3820/020 Q

Namco Limit Switch Replacement for Utilizing Quick

Rev. 13

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

Connectors

IP/0/A/3850/013 A

Procedure for Cable Termination Sealing

Rev. 64

IP/0/A/3850/013 B

Procedure for Sealing Rigid Steel Field Run Conduit

Rev. 13

MP-0-A-7200-008

Feedwater Isolation Valve Corrective Maintenance

Rev. 22

MP-0-A-7450-024

YC CHILLER HOT GAS BYPASS VALVE REMOVAL AND

REPLACEMENT

Rev. 11

OP.0.A.6450.011

Control Room Ventilation/Chilled Water System

Rev. 146

PT-2-A-4200-009

Engineered Safety Features Actuation Periodic Test

Rev. 170

PT-2-A-4200-018B

CF Valve Inservice Test (CS)

Rev. 21

Self-Assessments 02276400

Focused SAST: CNS EQ Program DBAI NRC inspection

06/06/2019

Work Orders

01713620

01810701

2073010

2079985

20033963