{{Adams
#REDIRECT [[HNP-97-109, Communicates Change in Util Plans Re Implementation of GL 88-17 Requirements for Plant.Procedures Will Be Revised & Operations Personnel Will Be Briefed on Evolution Prior to Conducting Vacuum Fill,Should Util Decide to Use Vacuum]]
| number = ML18012A779
| issue date = 05/12/1997
| title = Communicates Change in Util Plans Re Implementation of GL 88-17 Requirements for Plant.Procedures Will Be Revised & Operations Personnel Will Be Briefed on Evolution Prior to Conducting Vacuum Fill,Should Util Decide to Use Vacuum
| author name = Robinson W
| author affiliation = CAROLINA POWER & LIGHT CO.
| addressee name =
| addressee affiliation = NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
| docket = 05000400
| license number =
| contact person =
| document report number = GL-88-17, HNP-97-109, NUDOCS 9705190172
| document type = CORRESPONDENCE-LETTERS, INCOMING CORRESPONDENCE
| page count = 6
}}
 
=Text=
{{#Wiki_filter:CATEGORY 1 REGULAT  .. INFORMATION DISTRIBUTION          STEM  (RIDS)
ACCESGION NBR: 9705190172          DOC.DATE:    97/05/12    NOTARIZED: NO              DOCKET  I FACIL:50-400 Shearon Harris Nuclear Power Plant, Unit 1, Carolina                      05000400 AUTH. NAME            AUTHOR AFFILIATION ROBINSONIW.R.        Carolina Power      & Light Co.
RECIP.NAME            RECIPIENT AFFILIATION Document Control Branch (Document          Control Desk)
 
==SUBJECT:==
Communicates change in util plans re implementaion of GL 88-17 requirements for plant. Procedures will be revised a operations personnel will be briefed on evolution prior to conducting vacuum    fill,  should util decide to use vacuum.
DISTRIBUTION CODE: A001D        COPIES RECEIVED:LTR          ENCL        SIZE:
TITLE:  OR  Submittal: General Distribution NOTES:Application for permit- renewal          filed.                                  05000400 RECIPIENT          COPIES              RECIPIENT          COPIES ID CODE/NAME        LTTR ENCL          ID  CODE/NAME        LTTR ENCL                0 PD2-1 LA                                PD2-1 PD LE,N INTERNAL: ACRS                                      F      QENZ~
NRR/DE/ECGB/A                          NRR/DE/EMCB NRR/DRCH/HICB                          NRR/DSSA/SPLB NRR/DSSA/SRXB                          NUDOCS-ABSTRACT OGC/HDS2 EXTERNAL: NOAC                                      NRC PDR D
0 E
N NOTE TO ALL "RIDS" RECIPIENTS:
PLEASE HELP US TO REDUCE WASTE. TO HAVE YOUR NAME OR ORGANIZATION REMOVED FROM DISTRIBUTION LISTS OR REDUCE THE NUMBER OF COPIES RECEIVED BY YOU OR YOUR ORGANIZATION, CONTACT THE DOCUMENT CONTROL DESK (DCD) ON EXTENSION 415-2083 TOTAL NUMBER OF COPTER REQUTRED: LTTR              14  ENCL  Q
 
(a I
 
Carolina Power & Light Company                                                          William R. Robinson PO Box 165                                                                              Vice President New Hill NC 27562                                                                        Harris Nuclear Plant MAY    1 2 1997 SERIAL: HNP-97-109 United States Nuclear Regulatory Commission ATTENTION: Document Control Desk Washington, DC 20555 SHEARON HARRIS NUCLEAR POWER PLANT DOCKET NO. 50-400/LICENSE NO. NPF-63 GENERIC LETTER 88-17, "LOSS OF DECAY HEAT REMOVAL" RESPONSE MODIFICATION
 
==Dear Sir or Madam:==
 
The purpose of this letter is to communicate a change in Carolina Power & Light Company's (CP&L) plans regarding implementation of Generic Letter 8S-17 requirements for the Harris Nuclear Plant (HNP).
By letter dated January 3, 19S9, CP&L informed the NRC of plans to implement each expeditious recommendation contained in the generic letter at HNP. To address recommended action P6 of the generic letter, which required two available or operable means of adding inventory to the Reactor Coolant System (RCS), the letter stated that "Technical Specifications require that one high pressure injection pump be operable during cold shutdown" and "Since the generic letter specifically disallows credit for inventory addition via the decay heat removal pumps, a second path must necessarily be passive in nature; for example, a gravity feed from the refueling water storage tank to the RCS could be used." HNP had later implemented a further restriction to require that the pressurizer manway be removed when the refueling water storage tank (RWST) was being relied upon as the second means of adding water.
By letter dated April 4, 1997, HNP informed the NRC that during the RCS vacuum fillprocess, which would be used for the first time during refueling outage 7, the pressurizer manway.would be bolted in place. This, coupled with other malfunctions, could render gravity feed from the RWST ineffective. Therefore, CP&L stated that during this time period, the racked out, but available, Charging/Safety Injection Pump (CSIP) would be consider'ed the second means of adding inventory into the RCS in the event of a loss of decay heat removal capability. CP&L planned to revise applicable operating procedures and brief Operations personnel regarding this change.
9705i90f72 970512 PDR  ADOCK      05000400'f.      ''        ff!ffff!fill!Illllf Ill fill lllll/I/lfll P                      PDR State Road113st NewHill NC    Tel 919362-2502            Fax 919362-2095
 
f'!
. KLcument Control Desk
, SEIUAL: HNP-97-109 At management's discretion, the vacuum fill process will not        be used during recovery from refueling outage 7. Therefore, the applicable operating procedures may not be revised at this time to designate the racked out CSIP as a second means for RCS inventory control. During recovery from refueling outage 7,  CPS'ill    rely on gravity feed from the RWST as the second water addition means of RCS inventory control in the event of a loss of decay heat removal capability as discussed inthe January 3, 1989 letter. Should HNP decideto use the vacuum fill process in the future, the procedures will be revised and Operations personnel will be briefed on the evolution prior to conducting the vacuum  fill.
Questions regarding this matter may be referred to Ms. D. B. Alexander at (919) 362-3190.
Sincerely, W. R. Robinson Vice President Harris Nuclear Plant MGW c:      Mr. J. B. Brady (NRC Senior Resident Inspector, HNP)
Mr. N. B. Le (NRR Project Manager, HNP)
Mr. L. A. Reyes (NRC Regional Administrator, Region II)
 