=Text= | =Text= | ||
{{#Wiki_filter:Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.9 Ventilation Filter Testinq Progqram (VFTP) (continued) | {{#Wiki_filter:Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.9 Ventilation Filter Testinq Progqram (VFTP) (continued) | ||
ESF Ventilation System Face Velocity (fpm) Penetration | ESF Ventilation System Face Velocity (fpm) Penetration (%) RH CREV System ESF Ventilation System FHAEV System NA 1 | ||
(%) RH CREV System ESF Ventilation System FHAEV System NA 1 45.5 46.8 5 5 95 95 95 In addition, the carbon samples not obtained from test canisters shall be prepared by either: 1. Emptying one entire bed from a removed adsorber tray, mixing the adsorbent thoroughly, and obtaining samples at least two inches in diameter and with a length equal to the thickness of the bed; or 2. Emptying a longitudinal sample from an adsorber tray, mixing the adsorbent thoroughly, and obtaining samples at least two inches in diameter and with a length equal to the thickness of the bed.d. Demonstrate for each of the ESF systems that the pressure drop across the combined HEPA filters and the charcoal adsorbers is less than the value specified below when tested at the system flowrate specified below: ESF Ventilation System CREV System ESF Ventilation System FHAEV System Delta P (inches water .qaugqe)Flowrate (cfm)4 4 | 45.5 46.8 5 | ||
ESF Ventilation System Face Velocity (fpm) Penetration | 5 95 95 95 In addition, the carbon samples not obtained from test canisters shall be prepared by either: | ||
(%) RH (%)CREV System ESF Ventilation System FHAEV System NA 1 45.5 46.8 5 5 95 95 95 In addition, the carbon samples not obtained from test canisters shall be prepared by either: 1. Emptying one entire bed from a removed adsorber tray, mixing the adsorbent thoroughly, and obtaining samples at least two inches in diameter and with a length equal to the thickness of the bed; or 2. Emptying a longitudinal sample from an adsorber tray, mixing the adsorbent thoroughly, and obtaining samples at least two inches in diameter and with a length equal to the thickness of the bed.d. Demonstrate for each of the ESF systems that the pressure drop across the combined HEPA filters and the charcoal adsorbers is less than the value specified below when tested at the system flowrate specified below: ESF Ventilation System CREV System ESF Ventilation System FHAEV System Delta P (inches water gauge)Flowrate (cfm)4 4 | : 1. | ||
Emptying one entire bed from a removed adsorber tray, mixing the adsorbent thoroughly, and obtaining samples at least two inches in diameter and with a length equal to the thickness of the bed; or | |||
: 2. | |||
Emptying a longitudinal sample from an adsorber tray, mixing the adsorbent thoroughly, and obtaining samples at least two inches in diameter and with a length equal to the thickness of the bed. | |||
: d. | |||
Demonstrate for each of the ESF systems that the pressure drop across the combined HEPA filters and the charcoal adsorbers is less than the value specified below when tested at the system flowrate specified below: | |||
ESF Ventilation System CREV System ESF Ventilation System FHAEV System Delta P (inches water.qaugqe) | |||
Flowrate (cfm) 4 4 | |||
4 | |||
_>5,400 and _<6,600 | |||
Ž22,500 and <27,500 | |||
_27,000 and _<33,000 | |||
.Cook Nuclear Plant Unit 1 5.5-9 Amendment No. 287, 2-98, 305 | |||
Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.9 Ventilation Filter Testing Program (VFTP) (continued) | |||
ESF Ventilation System Face Velocity (fpm) Penetration (%) | |||
RH (%) | |||
CREV System ESF Ventilation System FHAEV System NA 1 | |||
45.5 46.8 5 | |||
5 95 95 95 In addition, the carbon samples not obtained from test canisters shall be prepared by either: | |||
: 1. | |||
Emptying one entire bed from a removed adsorber tray, mixing the adsorbent thoroughly, and obtaining samples at least two inches in diameter and with a length equal to the thickness of the bed; or | |||
: 2. | |||
Emptying a longitudinal sample from an adsorber tray, mixing the adsorbent thoroughly, and obtaining samples at least two inches in diameter and with a length equal to the thickness of the bed. | |||
: d. | |||
Demonstrate for each of the ESF systems that the pressure drop across the combined HEPA filters and the charcoal adsorbers is less than the value specified below when tested at the system flowrate specified below: | |||
ESF Ventilation System CREV System ESF Ventilation System FHAEV System Delta P (inches water gauge) | |||
Flowrate (cfm) 4 4 | |||
4 | |||
_>5,400 and _<6,600 | |||
Ž_22,500 and <27,500 | |||
->27,000 and <33,000 Cook Nuclear Plant Unit 2 5.5-9 Amendment No. 269, 2-7-9, 288}} | |||
Latest revision as of 16:57, 14 January 2025
| ML081230269 | |
| Person / Time | |
|---|---|
| Site: | Cook |
| Issue date: | 04/28/2008 |
| From: | NRC/NRR/ADRO/DORL/LPLIII-1 |
| To: | |
| tam P, NRR/DORL, 415-1451 | |
| References | |
| TAC MD5931, TAC MD5932 | |
| Download: ML081230269 (2) | |
Text
Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.9 Ventilation Filter Testinq Progqram (VFTP) (continued)
ESF Ventilation System Face Velocity (fpm) Penetration (%) RH CREV System ESF Ventilation System FHAEV System NA 1
45.5 46.8 5
5 95 95 95 In addition, the carbon samples not obtained from test canisters shall be prepared by either:
- 1.
Emptying one entire bed from a removed adsorber tray, mixing the adsorbent thoroughly, and obtaining samples at least two inches in diameter and with a length equal to the thickness of the bed; or
- 2.
Emptying a longitudinal sample from an adsorber tray, mixing the adsorbent thoroughly, and obtaining samples at least two inches in diameter and with a length equal to the thickness of the bed.
- d.
Demonstrate for each of the ESF systems that the pressure drop across the combined HEPA filters and the charcoal adsorbers is less than the value specified below when tested at the system flowrate specified below:
ESF Ventilation System CREV System ESF Ventilation System FHAEV System Delta P (inches water.qaugqe)
Flowrate (cfm) 4 4
4
_>5,400 and _<6,600
Ž22,500 and <27,500
_27,000 and _<33,000
.Cook Nuclear Plant Unit 1 5.5-9 Amendment No. 287, 2-98, 305
Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.9 Ventilation Filter Testing Program (VFTP) (continued)
ESF Ventilation System Face Velocity (fpm) Penetration (%)
RH (%)
CREV System ESF Ventilation System FHAEV System NA 1
45.5 46.8 5
5 95 95 95 In addition, the carbon samples not obtained from test canisters shall be prepared by either:
- 1.
Emptying one entire bed from a removed adsorber tray, mixing the adsorbent thoroughly, and obtaining samples at least two inches in diameter and with a length equal to the thickness of the bed; or
- 2.
Emptying a longitudinal sample from an adsorber tray, mixing the adsorbent thoroughly, and obtaining samples at least two inches in diameter and with a length equal to the thickness of the bed.
- d.
Demonstrate for each of the ESF systems that the pressure drop across the combined HEPA filters and the charcoal adsorbers is less than the value specified below when tested at the system flowrate specified below:
ESF Ventilation System CREV System ESF Ventilation System FHAEV System Delta P (inches water gauge)
Flowrate (cfm) 4 4
4
_>5,400 and _<6,600
Ž_22,500 and <27,500
->27,000 and <33,000 Cook Nuclear Plant Unit 2 5.5-9 Amendment No. 269, 2-7-9, 288