{{#Wiki_filter:LPDES PERMIT NO. LA0007374 LPDES FACT SHEET and RATIONALE  FOR THE DRAFT LOUISIANA POLLUTANT DISCHARGE ELIMINATION SYSTEM (LPDES) PERMIT TO DISCHARGE TO WATERS OF LOUISIANA
{{#Wiki_filter:LPDES PERMIT NO. LA0007374  


I. Company/Facility Name: Entergy Operations, Inc. Waterford 3 Steam Electric Station Post Office Box B Killona, Louisiana 70066 II. Issuing Office:  Louisiana Department of Environmental Quality (LDEQ)
LPDES FACT SHEET and RATIONALE FOR THE DRAFT LOUISIANA POLLUTANT DISCHARGE ELIMINATION SYSTEM (LPDES) PERMIT TO DISCHARGE TO WATERS OF LOUISIANA
Office of Water Resources Post Office Box 82215 Baton Rouge, Louisiana  70884-2215 III. Prepared By:  Elizabeth A. Ballard Industrial Permits Section Water Pollution Control Division Phone #: 504-765-0543 Fax #: 504-765-0635 Date Prepared:  July 22, 1998 IV. Permit Action/Status:
 
A. Reason For Permit Action:   Proposed reissuance of an expired Louisiana Pollutant Discharge Elimination System (LPDES) permit for a 5-year term following regulations promulgated at LAC 33:IX.2365/40 CFR 122.46*.
I. Company/Facility Name:
* In order to ease the transition from NPDES to LPDES permits, dual regulatory references are provided where applicable. The LAC references are the legal references while the 40 CFR references are presented for informational purposes only. In most cases, LAC language is based on and is identical to the 40 CFR language. 40 CFR Parts 401-402, and 404-471 have been adopted by reference at LAC 33:IX.2533 and will not have dual references. In addition, state standards (LAC Chapter 11) will not have dual references. LAC 33:IX Citations: Unless otherwise stated, citations to LAC 33:IX refer to promulgated regulations listed at Louisiana Administrative Code, Title 33, Part IX. 40 CFR Citations: Unless otherwise stated, citations to 40 CFR refer to promulgated regulations listed at Title 40, Code of Federal Regulations in accordance with the dates specified at LAC 33:IX.2531, 2533, and 2301.F. B. NPDES permit - NPDES permit effective date: May 20, 1991     NPDES permit expiration date: May 19, 1996                 EPA has not retained enforcement authority.
Entergy Operations, Inc.
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 2  C. LWDPS permit - Louisiana Stream Control Commission letter dated  WP4832  September 27, 1973 D. LWDPS permit - Class I Sanitary General Permit LAG530192    Authorization date:  April 29, 1998        Permit expiration date: November 18, 2002 F. Original application received on November 17, 1995, with revised applications received on February 25, 1998, an addendum received on June 15, 1998, and a letter with revised flow diagram received on July 29, 1998.
Waterford 3 Steam Electric Station  
V. Facility Information: A. Location - LA Highway 18 (River Road) in Killona (11/4 miles west of the intersection of LA Highway 3142, and LA Highway 18), St. Charles Parish B. Applicant Activity -   According to the application, Entergy Waterford 3 Steam Electric Station is a nuclear fueled steam electric generating station with a net output of 1,104 megawatts (MWe). This Office does not have authority to regulate radioactive materials in water discharge permits. Jurisdiction for regulation of these materials is held by the Nuclear Regulatory Commission (NRC) under the Atomic Energy Act, 42 U.S.C. 2021, et seq.
 
Therefore, the permittee must comply with radiation standards established and regulated by the NRC. Furthermore, this permit will not address those radiation standards. C. Technology Basis - (40 CFR Chapter 1, Subchapter N/Parts 401-402, and 404-471 have been adopted by reference at LAC 33:IX.2533) Guideline    Reference Steam Electric Power Generating Point Source Category  40 CFR 423 Max 30 Day Average Continuous Flow - 1,346 MGD Other sources of technology based limits: LA0007374 Certification of NPDES Permit Modification, dated    6/16/95, by Percy V. Harris (LDEQ) LA0007374 EPA Fact Sheet public noticed on June 3, 1995 LA0007374 NPDES Permit effective 5/20/91, and modification    effective on July 21, 1995 LDEQ Stormwater Guidance, letter dated 6/17/87, from J. Dale    Givens (LDEQ) to Myron Knudson (EPA Region 6)
Post Office Box B  
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 3  Final Environmental Statement, Louisiana Power & Light Co.(LP&L),  September 1981 Demonstration Under Section 316(a) of the CWA, Louisiana Power & Light Co., April 1979 Hydrologic and Quality Characteristics of the Lower Mississippi    River, Technical Report Number 5 LDEQ Sanitary General Permits Best Professional Judgement using: Letter from LDEQ to Entergy dated 6/23/98 Letter from Entergy to LDEQ dated 6/13/97 Letter from LDEQ to Entergy dated 8/26/96 Letter from EPA Region 6 to Entergy dated 4/16/96 Letter from EPA Region 6 to Entergy dated 1/23/96 Letter from Entergy to EPA Region 6 dated 10/25/94 Letter from Entergy to LDEQ dated 9/9/94 Letter from EPA Region 6 to LP&L dated 5/30/85 Letter from LP&L to EPA Region 6 dated 3/1/85 D. Fee Rate -  1. Fee Rating Facility Type:  Major  
 
Killona, Louisiana 70066  
 
II. Issuing Office:  Louisiana Department of Environmental Quality (LDEQ)
Office of Water Resources  
 
Post Office Box 82215  
 
Baton Rouge, Louisiana  70884-2215  
 
III. Prepared By:  Elizabeth A. Ballard Industrial Permits Section  
 
Water Pollution Control Division Phone #: 504-765-0543 Fax #: 504-765-0635 Date Prepared:  July 22, 1998  
 
IV. Permit Action/Status:
 
A. Reason For Permit Action:
Proposed reissuance of an expired Louisiana Pollutant Discharge  
 
Elimination System (LPDES) permit for a 5-year term following  
 
regulations promulgated at LAC 33:IX.2365/40 CFR 122.46*.
* In order to ease the transition from NPDES to LPDES permits, dual regulatory references are provided where applicable. The LAC  
 
references are the legal references while the 40 CFR references  
 
are presented for informational purposes only. In most cases, LAC  
 
language is based on and is identical to the 40 CFR language. 40  
 
CFR Parts 401-402, and 404-471 have been adopted by reference at  
 
LAC 33:IX.2533 and will not have dual references. In addition,  
 
state standards (LAC Chapter 11) will not have dual references.
LAC 33:IX Citations:
Unless otherwise stated, citations to LAC 33:IX refer to promulgated regulations listed at Louisiana Administrative  
 
Code, Title 33, Part IX.
40 CFR Citations:
Unless otherwise stated, citations to 40 CFR refer to promulgated regulations listed at Title 40, Code of Federal Regulations  
 
in accordance with the dates specified at LAC 33:IX.2531, 2533, and  
 
2301.F.
B. NPDES permit - NPDES permit effective date: May 20, 1991 NPDES permit expiration date: May 19, 1996 EPA has not retained enforcement authority.
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 2  C. LWDPS permit - Louisiana Stream Control Commission letter dated  WP4832  September 27, 1973  
 
D. LWDPS permit - Class I Sanitary General Permit LAG530192    Authorization date:  April 29, 1998        Permit expiration date: November 18, 2002  
 
F. Original application received on November 17, 1995, with revised applications received on February 25, 1998, an addendum received  
 
on June 15, 1998, and a letter with revised flow diagram received  
 
on July 29, 1998.  
 
V. Facility Information:
A. Location - LA Highway 18 (River Road) in Killona (11/4 miles west of the intersection of LA Highway 3142, and LA Highway  
 
18), St. Charles Parish B. Applicant Activity -
According to the application, Entergy Waterford 3 Steam Electric  
 
Station is a nuclear fueled steam electric generating station with  
 
a net output of 1,104 megawatts (MWe).
This Office does not have authority to regulate radioactive  
 
materials in water discharge permits. Jurisdiction for regulation  
 
of these materials is held by the Nuclear Regulatory Commission  
 
(NRC) under the Atomic Energy Act, 42 U.S.C. 2021, et seq.
 
Therefore, the permittee must comply with radiation standards  
 
established and regulated by the NRC. Furthermore, this permit  
 
will not address those radiation standards.
C. Technology Basis - (40 CFR Chapter 1, Subchapter N/Parts 401-402, and 404-471 have been adopted by reference at LAC 33:IX.2533)
Guideline    Reference Steam Electric Power Generating Point Source Category  40 CFR 423 Max 30 Day Average Continuous Flow - 1,346 MGD Other sources of technology based limits:
LA0007374 Certification of NPDES Permit Modification, dated    6/16/95, by Percy V. Harris (LDEQ)
LA0007374 EPA Fact Sheet public noticed on June 3, 1995  
 
LA0007374 NPDES Permit effective 5/20/91, and modification    effective on July 21, 1995 LDEQ Stormwater Guidance, letter dated 6/17/87, from J. Dale    Givens (LDEQ) to Myron Knudson (EPA Region 6)
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 3  Final Environmental Statement, Louisiana Power & Light Co.(LP&L),  September 1981 Demonstration Under Section 316(a) of the CWA, Louisiana Power &
Light Co., April 1979 Hydrologic and Quality Characteristics of the Lower Mississippi    River, Technical Report Number 5 LDEQ Sanitary General Permits
 
Best Professional Judgement using:
Letter from LDEQ to Entergy dated 6/23/98  
 
Letter from Entergy to LDEQ dated 6/13/97  
 
Letter from LDEQ to Entergy dated 8/26/96  
 
Letter from EPA Region 6 to Entergy dated 4/16/96  
 
Letter from EPA Region 6 to Entergy dated 1/23/96  
 
Letter from Entergy to EPA Region 6 dated 10/25/94  
 
Letter from Entergy to LDEQ dated 9/9/94  
 
Letter from EPA Region 6 to LP&L dated 5/30/85  
 
Letter from LP&L to EPA Region 6 dated 3/1/85 D. Fee Rate -   
: 1. Fee Rating Facility Type:  Major  
: 2. Complexity Type:  V   
: 2. Complexity Type:  V   
: 3. Wastewater Type:  I  
: 3. Wastewater Type:  I  
: 4. SIC code:  4911 E. Continuous Facility Effluent Flow (Max 30-Day) - 1,346 MGD VI. Receiving Waters: Mississippi River (Outfall 001):   1. TSS (15%), mg/L: 25.0  
: 4. SIC code:  4911 E. Continuous Facility Effluent Flow (Max 30-Day) - 1,346 MGD  
: 2. Average Hardness, mg/L CaCO3: 149.70  3. Critical Flow, cfs: 141,955  
 
VI. Receiving Waters:
Mississippi River (Outfall 001):  
: 1. TSS (15%), mg/L: 25.0  
: 2. Average Hardness, mg/L CaCO 3: 149.70   
: 3. Critical Flow, cfs: 141,955  
: 4. Mixing Zone Fraction: 0.333  
: 4. Mixing Zone Fraction: 0.333  
: 5. Harmonic Mean Flow, cfs: 366,748  
: 5. Harmonic Mean Flow, cfs: 366,748  
: 6. River Basin: Mississippi River, Segment No. 070301  
: 6. River Basin: Mississippi River, Segment No. 070301  
: 7. Designated Uses: The designated uses are primary contact recreation, secondary contact recreation, fish and wildlife propagation, and drinking water supply. Information based on the following: Water Quality Management Plan, Volume 5A, 1994; LAC 33:IX Chapter 11;/Recommendation(s) from the Engineering Section. Hardness and 15% TSS data come from monitoring station 58010321 on the Mississippi River listed in Hardness and TSS Data for All LDEQ Ambient Stations for the Period of Record as of March 1998, LeBlanc.
: 7. Designated Uses:
The designated uses are primary contact recreation,  
 
secondary contact recreation, fish and wildlife propagation,  
 
and drinking water supply.
Information based on the following: Water Quality Management Plan,  
 
Volume 5A, 1994; LAC 33:IX Chapter 11;/Recommendation(s) from the  
 
Engineering Section. Hardness and 15% TSS data come from  
 
monitoring station 58010321 on the Mississippi River listed in  
 
Hardness and TSS Data for All LDEQ Ambient Stations for the Period of Record as of March 1998
, LeBlanc.  
 
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
 
LA0007374
 
Page 4 40 Arpent Canal thence to Lac Des Allemands (Outfalls 004 & 005):
: 1. River Basin: Barataria Basin, Segment No. 020202
: 2. Designated Uses:
The designated uses are primary contact recreation,
 
secondary contact recreation, and fish and wildlife
 
propagation.


Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 4 40 Arpent Canal thence to Lac Des Allemands (Outfalls 004 & 005):  1. River Basin: Barataria Basin, Segment No. 020202
: 2. Designated Uses: The designated uses are primary contact recreation, secondary contact recreation, and fish and wildlife propagation.
VII. Outfall Information:
VII. Outfall Information:
Outfall 001 A. Type of wastewater - the continuous discharge from the turbine condenser cooling system to the Mississippi River. The turbine condenser cooling system receives once-through non-contact cooling water from the Mississippi River that flows through the main condenser, the steam generator blowdown heat exchangers, and the turbine building closed cooling heat exchanger. Previously monitored low volume discharges from Internal Outfalls 101 (former 01A), 201 (former 01B), 301 (former 01C), 401 (former 01D), 501, 601, 701, 801, and 901 also exit the facility via Outfall 001.
 
B. Location - at the point of discharge from the turbine condenser cooling system where the once-through non-contact cooling water, and the previously monitored effluents discharge prior to entering the Mississippi River at Latitude 2959'47", Longitude 9028'8", +129.5 M.A.H.P. C. Treatment - treatment of once-through non-contact cooling water consists of: - intake screening  
Outfall 001 A. Type of wastewater - the continuous discharge from the turbine condenser cooling system to the Mississippi River. The turbine  
 
condenser cooling system receives once-through non-contact cooling  
 
water from the Mississippi River that flows through the main  
 
condenser, the steam generator blowdown heat exchangers, and the  
 
turbine building closed cooling heat exchanger. Previously  
 
monitored low volume discharges from Internal Outfalls 101 (former  
 
01A), 201 (former 01B), 301 (former 01C), 401 (former 01D), 501,  
 
601, 701, 801, and 901 also exit the facility via Outfall 001.  
 
B. Location - at the point of discharge from the turbine condenser cooling system where the once-through non-contact cooling water,  
 
and the previously monitored effluents discharge prior to entering  
 
the Mississippi River at Latitude 2959'47", Longitude 9028'8", +129.5 M.A.H.P.
C. Treatment - treatment of once-through non-contact cooling water consists of:  
- intake screening  
 
- chlorination, when required  
- chlorination, when required  
- LDEQ approved mussels treatment, when required  
- LDEQ approved mussels treatment, when required  
- addition of dispersant/polymer, when required D. Flow - Continuous, (Max 30-Day) 1,346 MGD. E. Receiving waters - Mississippi River   F. Basin and segment - Mississippi River Basin, Segment 070301 G. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA Form 2C) received on June 15, 1998. POLLUTANT    EFFLUENT Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 5  PART A    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand  <2.0  <2.0  ---
 
- addition of dispersant/polymer, when required  
 
D. Flow - Continuous, (Max 30-Day) 1,346 MGD.
E. Receiving waters - Mississippi River F. Basin and segment - Mississippi River Basin, Segment 070301 G. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA  
 
Form 2C) received on June 15, 1998.
POLLUTANT    EFFLUENT    
 
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 5  PART A    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand  <2.0  <2.0  ---
Chemical Oxygen Demand    46.1  46.1  ---
Chemical Oxygen Demand    46.1  46.1  ---
Total Organic Carbon    6.7  6.7  ---
Total Organic Carbon    6.7  6.7  ---
Total Suspended Solids  269  269  ---
Total Suspended Solids  269  269  ---
Ammonia (as N)    <0.05  <0.05  --- Temperature (Winter)  21.1C  29.7C  --- (Summer)  41.1C  42.7C  --- pH (Standard Units)  NA  NA  ---    (min)    (max) PART B    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Bromide    BA  BA  ---
Ammonia (as N)    <0.05  <0.05  --- Temperature (Winter)  21.1C  29.7C  --- (Summer)  41.1C  42.7C  --- pH (Standard Units)  NA  NA  ---    (min)    (max)
PART B    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Bromide    BA  BA  ---
Chlorine, Total Residual  BA  BA  ---
Chlorine, Total Residual  BA  BA  ---
Color (nM Units)    BA  BA  ---
Color (nM Units)    BA  BA  ---
Line 54: Line 236:
Organic Nitrogen, Total as (N) BA  BA  ---
Organic Nitrogen, Total as (N) BA  BA  ---
Oil and Grease    <5.0  <5.0  ---
Oil and Grease    <5.0  <5.0  ---
Phosphorous, Total as (P)  BA  BA  ---
Phosphorous, Total as (P)  BA  BA  ---  
 
Radioactivity:
Radioactivity:
Alpha, Total (pCi/L)  0.0129  0.0129  ---
Alpha, Total (pCi/L)  0.0129  0.0129  ---
Beta, Total (pCi/L)  4.2  4.2  ---
Beta, Total (pCi/L)  4.2  4.2  ---
Radium, Total (pCi/L)  BA  BA  ---
Radium, Total (pCi/L)  BA  BA  ---
Radium 226, Total (pCi/L)  BA  BA  ---
Radium 226, Total (pCi/L)  BA  BA  ---  
Sulfate (as SO4)    84.2  84.2  --- Sulfide (as S)    BA  BA  ---
 
Sulfite (as SO3)    BA  BA  --- Surfactants    <0.1  <0.1  ---
Sulfate (as SO
: 4)    84.2  84.2  --- Sulfide (as S)    BA  BA  ---  
 
Sulfite (as SO
: 3)    BA  BA  --- Surfactants    <0.1  <0.1  ---
Aluminum  (Total)    BA  BA  ---
Aluminum  (Total)    BA  BA  ---
Barium    (Total)    <0.2  <0.2  ---
Barium    (Total)    <0.2  <0.2  ---
Line 70: Line 257:
Manganese (Total)    BA  BA  ---
Manganese (Total)    BA  BA  ---
Tin      (Total)    BA  BA  ---
Tin      (Total)    BA  BA  ---
Titanium  (Total)    BA  BA  --- METALS, CYANIDE & TOTAL PHENOL(g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Antimony  (Total)    BA  BA  60 Arsenic  (Total)    <10  <10  10 Beryllium (Total)    <5  <5  5 Cadmium  (Total)    <1  <1  1 Chromium  (Total)    <10  <10  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 6  Chromium  (3+)    NA  NA  10 Chromium  (6+)    NA  NA  10 Copper    (Total)    <10  <10  10 Lead      (Total)    <3  <3  5 Mercury  (Total)    <0.2  <0.2  0.2 Molybdenum (Total)  BA  BA  30 Nickel    (Total) Freshwater  <40  <40  40 Nickel    (Total) Marine  NA  NA  5 Selenium  (Total)    <5  <5  5 Silver    (Total)    <2  <2  2 Thallium  (Total)    <10  <10  10 Zinc      (Total)    25.2  25.2  20 Cyanide  (Total)    <10  <10  10 Phenolics, Total Recoverable (4AAP)  <50  <50  5 DIOXIN    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD    BA  BA  0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acrolein    <10  <10  50 Acrylonitrile    <10  <10  50 Benzene    <5  <5  10 Bis(Chloromethyl)Ether  BA  BA  10 Bromoform    <5  <5  10 Carbon Tetrachloride  <5  <5  10 Chlorobenzene    <5  <5  10 Chlorodibromomethane  <5  <5  10 Chloroethane    <10  <10  50 2-Chloroethylvinylether  <5  <5  10 Chloroform    <5  <5  10 Dichlorobromomethane  <5  <5  10 Dichlorodifluoromethane  BA  BA  10 1,1-Dichloroethane  <5  <5  10 1,2-Dichloroethane  <5  <5  10 1,1-Dichloroethylene  <5  <5  10 1,2-Dichloropropane  <5  <5  10 1,3-Dichloropropylene  <5  <5  10 Ethylbenzene    <5  <5  10 Methyl Bromide [Bromomethane]  <10  <10  50 Methyl Chloride [Chloromethane] <10  <10  50 Methylene Chloride  <5  <5  20 1,1,2,2-Tetrachloroethane  <5  <5  10 Tetrachloroethylene  <5  <5  10 Toluene    <5  <5  10 1,2-trans-Dichloroethylene  <5  <5  10 1,1,1-Trichloroethane  <5  <5  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 7  1,1,2-Trichloroethane  <5  <5  10 Trichloroethylene    <5  <5  10 Trichlorofluoromethane  BA  BA  10 Vinyl Chloride    <10  <10  10 ACID COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol    <10  <10  10 2,4-Dichlorophenol  <10  <10  10 2,4-Dimethylphenol  <10  <10  10 4,6-Dinitro-o-Cresol  <50  <50  50 2,4-Dinitrophenol    <50  <50  50 2-Nitrophenol    <10  <10  20 4-Nitrophenol    <50  <50  50 p-Chloro-m-Cresol    <10  <10  10 Pentachlorophenol    <50  <50  50 Phenol    <10  <10  10 2,4,6-Trichlorophenol  <10  <10  10 BASE/NEUTRAL COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acenaphthene    <10  <10  10 Acenaphthylene    <10  <10  10 Anthracene    <10  <10  10 Benzidine    <30  <30  50 Benzo(a)anthracene  <10  <10  10 Benzo(a)pyrene    <10  <10  10 3,4-Benzofluoranthene  <10  <10  10 Benzo(ghi)perylene  <10  <10  20 Benzo(k)fluoranthene  <10  <10  10 Bis(2-chloroethoxy) Methane  <10  <10  10 Bis(2-chloroethyl) Ether  <10  <10  10 Bis(2-chloroisopropyl) Ether  <10  <10  10 Bis(2-ethylhexyl) Phthalate  <10  <10  10 4-Bromophenyl Phenyl Ether  <10  <10  10 Butylbenzyl Phthalate  <10  <10  10 2-Chloronaphthalene  <10  <10  10 4-Chlorophenyl Phenyl Ether  <10  <10  10 Chrysene    <10  <10  10 Dibenzo(a,h)anthracene  <10  <10  20 1,2-Dichlorobenzene  <10  <10  10 1,3-Dichlorobenzene  <10  <10  10 1,4-Dichlorobenzene  <10  <10  10 3,3'-Dichlorobenzidine  <20  <20  50 Diethyl Phthalate    <10  <10  10 Dimethyl Phthalate  <10  <10  10 Di-n-Butyl Phthalate  <10  <10  10 2,4-Dinitrotoluene  <10  <10  10 2,6-Dinitrotoluene  <10  <10  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 8  Di-n-octyl Phthalate  <10  <10  10 1,2-Diphenylhydrazine  <10  <10  20 Fluoranthene    <10  <10  10 Fluorene    <10  <10  10 Hexachlorobenzene    <10  <10  10 Hexachlorobutadiene  <10  <10  10 Hexachlorocyclopentadiene  <10  <10  10 Hexachloroethane    <10  <10  20 Indeno(1,2,3-cd)pyrene    <10  <10  20 Isophorone    <10  <10  10 Naphthalene    <10  <10  10 Nitrobenzene    <10  <10  10 n-Nitrosodimethylamine  <20  <20  50 n-Nitrosodi-n-Propylamine  <10  <10  20 n-Nitrosodiphenylamine  <10  <10  20 Phenanthrene    <10  <10  10 Pyrene    <10  <10  10 1,2,4-Trichlorobenzene  <10  <10  10 PESTICIDES    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Aldrin    BA  BA  0.05 Alpha-BHC    BA  BA  0.05 Beta-BHC    BA  BA  0.05 Gamma-BHC [Lindane]  BA  BA  0.05 Delta-BHC    BA  BA  0.05 Chlordane    BA  BA  0.2 4,4'-DDT    BA  BA  0.1 4,4'-DDE [p,p-DDX]  BA  BA  0.1 4,4'-DDD [p,p-TDE]  BA  BA  0.1 Dieldrin    BA  BA  0.1 Alpha-Endosulfan    BA  BA  0.1 Beta-Endosulfan    BA  BA  0.1 Endosulfan Sulfate  BA  BA  0.1 Endrin    BA  BA  0.1 Endrin Aldehyde    BA  BA  0.1 Heptachlor    BA  BA  0.05 Heptachlor Epoxide    BA  BA  0.05 PCB-1242    BA  BA  1.0 PCB-1254    BA  BA  1.0 PCB-1221    BA  BA  1.0 PCB-1232    BA  BA  1.0 PCB-1248    BA  BA  1.0 PCB-1260    BA  BA  1.0 PCB-1016    BA  BA  1.0 Toxaphene    BA  BA  5.0 BA - Believed Absent NA - Not Available  
Titanium  (Total)    BA  BA  ---
METALS, CYANIDE & TOTAL PHENOL (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Antimony  (Total)    BA  BA  60 Arsenic  (Total)    <10  <10  10 Beryllium (Total)    <5  <5  5 Cadmium  (Total)    <1  <1  1 Chromium  (Total)    <10  <10  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 6  Chromium  (3+)    NA  NA  10 Chromium  (6+)    NA  NA  10 Copper    (Total)    <10  <10  10 Lead      (Total)    <3  <3  5 Mercury  (Total)    <0.2  <0.2  0.2 Molybdenum (Total)  BA  BA  30 Nickel    (Total) Freshwater  <40  <40  40 Nickel    (Total) Marine  NA  NA  5 Selenium  (Total)    <5  <5  5 Silver    (Total)    <2  <2  2 Thallium  (Total)    <10  <10  10 Zinc      (Total)    25.2  25.2  20 Cyanide  (Total)    <10  <10  10  
 
Phenolics, Total Recoverable (4AAP)  <50  <50  5 DIOXIN    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD    BA  BA  0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acrolein    <10  <10  50 Acrylonitrile    <10  <10  50 Benzene    <5  <5  10 Bis(Chloromethyl)Ether  BA  BA  10 Bromoform    <5  <5  10 Carbon Tetrachloride  <5  <5  10 Chlorobenzene    <5  <5  10 Chlorodibromomethane  <5  <5  10 Chloroethane    <10  <10  50 2-Chloroethylvinylether  <5  <5  10 Chloroform    <5  <5  10 Dichlorobromomethane  <5  <5  10 Dichlorodifluoromethane  BA  BA  10 1,1-Dichloroethane  <5  <5  10 1,2-Dichloroethane  <5  <5  10 1,1-Dichloroethylene  <5  <5  10 1,2-Dichloropropane  <5  <5  10 1,3-Dichloropropylene  <5  <5  10 Ethylbenzene    <5  <5  10 Methyl Bromide [Bromomethane]  <10  <10  50 Methyl Chloride [Chloromethane] <10  <10  50 Methylene Chloride  <5  <5  20 1,1,2,2-Tetrachloroethane  <5  <5  10 Tetrachloroethylene  <5  <5  10 Toluene    <5  <5  10 1,2-trans-Dichloroethylene  <5  <5  10 1,1,1-Trichloroethane  <5  <5  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 7  1,1,2-Trichloroethane  <5  <5  10 Trichloroethylene    <5  <5  10 Trichlorofluoromethane  BA  BA  10 Vinyl Chloride    <10  <10  10 ACID COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol    <10  <10  10 2,4-Dichlorophenol  <10  <10  10 2,4-Dimethylphenol  <10  <10  10 4,6-Dinitro-o-Cresol  <50  <50  50 2,4-Dinitrophenol    <50  <50  50 2-Nitrophenol    <10  <10  20 4-Nitrophenol    <50  <50  50 p-Chloro-m-Cresol    <10  <10  10 Pentachlorophenol    <50  <50  50 Phenol    <10  <10  10 2,4,6-Trichlorophenol  <10  <10  10 BASE/NEUTRAL COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acenaphthene    <10  <10  10 Acenaphthylene    <10  <10  10 Anthracene    <10  <10  10 Benzidine    <30  <30  50 Benzo(a)anthracene  <10  <10  10 Benzo(a)pyrene    <10  <10  10 3,4-Benzofluoranthene  <10  <10  10 Benzo(ghi)perylene  <10  <10  20 Benzo(k)fluoranthene  <10  <10  10 Bis(2-chloroethoxy) Methane  <10  <10  10 Bis(2-chloroethyl) Ether  <10  <10  10 Bis(2-chloroisopropyl) Ether  <10  <10  10 Bis(2-ethylhexyl) Phthalate  <10  <10  10 4-Bromophenyl Phenyl Ether  <10  <10  10 Butylbenzyl Phthalate  <10  <10  10 2-Chloronaphthalene  <10  <10  10 4-Chlorophenyl Phenyl Ether  <10  <10  10 Chrysene    <10  <10  10 Dibenzo(a,h)anthracene  <10  <10  20 1,2-Dichlorobenzene  <10  <10  10 1,3-Dichlorobenzene  <10  <10  10 1,4-Dichlorobenzene  <10  <10  10 3,3'-Dichlorobenzidine  <20  <20  50 Diethyl Phthalate    <10  <10  10 Dimethyl Phthalate  <10  <10  10 Di-n-Butyl Phthalate  <10  <10  10 2,4-Dinitrotoluene  <10  <10  10 2,6-Dinitrotoluene  <10  <10  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 8  Di-n-octyl Phthalate  <10  <10  10 1,2-Diphenylhydrazine  <10  <10  20 Fluoranthene    <10  <10  10 Fluorene    <10  <10  10 Hexachlorobenzene    <10  <10  10 Hexachlorobutadiene  <10  <10  10 Hexachlorocyclopentadiene  <10  <10  10 Hexachloroethane    <10  <10  20 Indeno(1,2,3-cd)pyrene    <10  <10  20 Isophorone    <10  <10  10 Naphthalene    <10  <10  10 Nitrobenzene    <10  <10  10 n-Nitrosodimethylamine  <20  <20  50 n-Nitrosodi-n-Propylamine  <10  <10  20 n-Nitrosodiphenylamine  <10  <10  20 Phenanthrene    <10  <10  10 Pyrene    <10  <10  10 1,2,4-Trichlorobenzene  <10  <10  10 PESTICIDES    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Aldrin    BA  BA  0.05 Alpha-BHC    BA  BA  0.05 Beta-BHC    BA  BA  0.05 Gamma-BHC [Lindane]  BA  BA  0.05 Delta-BHC    BA  BA  0.05 Chlordane    BA  BA  0.2 4,4'-DDT    BA  BA  0.1 4,4'-DDE [p,p-DDX]  BA  BA  0.1 4,4'-DDD [p,p-TDE]  BA  BA  0.1 Dieldrin    BA  BA  0.1 Alpha-Endosulfan    BA  BA  0.1 Beta-Endosulfan    BA  BA  0.1 Endosulfan Sulfate  BA  BA  0.1 Endrin    BA  BA  0.1 Endrin Aldehyde    BA  BA  0.1 Heptachlor    BA  BA  0.05 Heptachlor Epoxide    BA  BA  0.05 PCB-1242    BA  BA  1.0 PCB-1254    BA  BA  1.0 PCB-1221    BA  BA  1.0 PCB-1232    BA  BA  1.0 PCB-1248    BA  BA  1.0 PCB-1260    BA  BA  1.0 PCB-1016    BA  BA  1.0 Toxaphene    BA  BA  5.0 BA - Believed Absent  
 
NA - Not Available  
 
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
 
LA0007374
 
Page 9  Internal Outfall 101 (Former 01A)
A. Type of wastewater - the intermittent internal discharge from the liquid waste management system to Final Outfall 001 via the
 
turbine condenser cooling system. The liquid waste management
 
system receives low volume wastewater from the following sources,
 
including but not limited to:  the turbine and reactor building
 
equipment and floor drains, primary plant water makeup, laboratory
 
drains, and other low volume wastewater sources as defined in 40
 
CFR 423.
 
B. Location - at the point of discharge from the liquid waste management system prior to combining with the waters of Final
 
Outfall 001 at Latitude 2959'40", Longitude 9028'16". C. Treatment - treatment of these low volume wastewaters consists of:
- filtering/screening


Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 9  Internal Outfall 101 (Former 01A)  A. Type of wastewater - the intermittent internal discharge from the liquid waste management system to Final Outfall 001 via the turbine condenser cooling system. The liquid waste management system receives low volume wastewater from the following sources, including but not limited to:  the turbine and reactor building equipment and floor drains, primary plant water makeup, laboratory drains, and other low volume wastewater sources as defined in 40 CFR 423.
B. Location - at the point of discharge from the liquid waste management system prior to combining with the waters of Final Outfall 001 at Latitude 2959'40", Longitude 9028'16". C. Treatment - treatment of these low volume wastewaters consists of: - filtering/screening
- cationic and anionic polymer injection  
- cationic and anionic polymer injection  
- ion exchange  
- ion exchange  
- neutralization/pH adjustment, when required  
- neutralization/pH adjustment, when required  
- distillation, when required D. Flow - Intermittent, (Max 30-Day) 0.0129 MGD E. Receiving waters - Discharge to Outfall 001 F. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA Form 2C) received on June 15, 1998. POLLUTANT    EFFLUENT     PART A    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand  <10.0  <10.0  ---
 
- distillation, when required D. Flow - Intermittent, (Max 30-Day) 0.0129 MGD E. Receiving waters - Discharge to Outfall 001 F. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA  
 
Form 2C) received on June 15, 1998.
POLLUTANT    EFFLUENT PART A    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand  <10.0  <10.0  ---
Chemical Oxygen Demand    38.0  38.0  ---
Chemical Oxygen Demand    38.0  38.0  ---
Total Organic Carbon    10  10  ---
Total Organic Carbon    10  10  ---
Total Suspended Solids  17.4  28.3  ---
Total Suspended Solids  17.4  28.3  ---
Ammonia (as N)    3.0  3.0  ---
Ammonia (as N)    3.0  3.0  ---
Temperature (Winter)  NA  NA  --- (Summer)  NA  NA  --- pH (Standard Units)  6.04  8.98  ---    (min)    (max)
Temperature (Winter)  NA  NA  --- (Summer)  NA  NA  --- pH (Standard Units)  6.04  8.98  ---    (min)    (max)  


PART B    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Bromide    BA  BA  ---
PART B    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Bromide    BA  BA  ---
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 10  Chlorine, Total Residual  BA  BA  ---
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 10  Chlorine, Total Residual  BA  BA  ---
Color (nM Units)    15.0  15.0  ---
Color (nM Units)    15.0  15.0  ---
Fecal Coliform (col/100 mL)  BA  BA  ---
Fecal Coliform (col/100 mL)  BA  BA  ---
Line 92: Line 328:
Organic Nitrogen, Total as (N) BA  BA  ---
Organic Nitrogen, Total as (N) BA  BA  ---
Oil and Grease    5.91  11.4  ---
Oil and Grease    5.91  11.4  ---
Phosphorous, Total as (P)  0.44  0.44  ---
Phosphorous, Total as (P)  0.44  0.44  ---  
 
Radioactivity:
Radioactivity:
Alpha, Total (pCi/L)  259  259  ---
Alpha, Total (pCi/L)  259  259  ---
Beta, Total (pCi/L)  84,000 84,000  ---
Beta, Total (pCi/L)  84,000 84,000  ---
Radium, Total (pCi/L)  BA  BA  ---
Radium, Total (pCi/L)  BA  BA  ---
Radium 226, Total (pCi/L)  BA  BA  ---
Radium 226, Total (pCi/L)  BA  BA  ---  
Sulfate (as SO4)    2.0  2.0  --- Sulfide (as S)    BA  BA  ---
 
Sulfite (as SO3)    BA  BA  --- Surfactants    <0.1  <0.1  ---
Sulfate (as SO
: 4)    2.0  2.0  --- Sulfide (as S)    BA  BA  ---  
 
Sulfite (as SO
: 3)    BA  BA  --- Surfactants    <0.1  <0.1  ---
Aluminum  (Total)    <0.5  <0.5  ---
Aluminum  (Total)    <0.5  <0.5  ---
Barium    (Total)    <0.2  <0.2  ---
Barium    (Total)    <0.2  <0.2  ---
Line 108: Line 349:
Manganese (Total)    BA  BA  ---
Manganese (Total)    BA  BA  ---
Tin      (Total)    BA  BA  ---
Tin      (Total)    BA  BA  ---
Titanium  (Total)    BA  BA  --- METALS, CYANIDE & TOTAL PHENOL(g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Antimony  (Total)    <600  <600  60 Arsenic  (Total)    <10  <10  10 Beryllium (Total)    <50  <50  5 Cadmium  (Total)    <1  <1  1 Chromium  (Total)    <2  <2  10 Chromium  (3+)    NA  NA  10 Chromium  (6+)    NA  NA  10 Copper    (Total)    <100  <100  10 Lead      (Total)    <31  <31  5 Mercury  (Total)    3.9  3.9  0.2 Molybdenum (Total)  <100  <100  30 Nickel    (Total) Freshwater  <400  <400  40 Nickel    (Total) Marine  NA  NA  5 Selenium  (Total)    <5  <5  5 Silver    (Total)    <2  <2  2 Thallium  (Total)    <10  <10  10 Zinc      (Total)    <200  <200  20 Cyanide  (Total)    25  25  10 Phenolics, Total Recoverable (4AAP)  14  14  5 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 11  DIOXIN    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD    BA  BA  0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acrolein    BA  BA  50 Acrylonitrile    BA  BA  50 Benzene    <5  <5  10 Bis(Chloromethyl)Ether  BA  BA  10 Bromoform    <5  <5  10 Carbon Tetrachloride  <5  <5  10 Chlorobenzene    <5  <5  10 Chlorodibromomethane  <5  <5  10 Chloroethane    <10  <10  50 2-Chloroethylvinylether  <5  <5  10 Chloroform    15  15  10 Dichlorobromomethane  <5  <5  10 Dichlorodifluoromethane  <10  <10  10 1,1-Dichloroethane  <5  <5  10 1,2-Dichloroethane  <5  <5  10 1,1-Dichloroethylene  <5  <5  10 1,2-Dichloropropane  <5  <5  10 1,3-Dichloropropylene  <5  <5  10 Ethylbenzene    <5  <5  10 Methyl Bromide [Bromomethane]  <10  <10  50 Methyl Chloride [Chloromethane] <10  <10  50 Methylene Chloride  <5  <5  20 1,1,2,2-Tetrachloroethane  <5  <5  10 Tetrachloroethylene  <5  <5  10 Toluene    <5  <5  10 1,2-trans-Dichloroethylene  BA  BA  10 1,1,1-Trichloroethane  <5  <5  10 1,1,2-Trichloroethane  <5  <5  10 Trichloroethylene    <5  <5  10 Trichlorofluoromethane  <10  <10  10 Vinyl Chloride    <10  <10  10 ACID COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol    <5  <5  10 2,4-Dichlorophenol  <5  <5  10 2,4-Dimethylphenol  <5  <5  10 4,6-Dinitro-o-Cresol  <25  <25  50 2,4-Dinitrophenol    <25  <25  50 2-Nitrophenol    <5  <5  20 4-Nitrophenol    <25  <25  50 p-Chloro-m-Cresol    <5  <5  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 12  Pentachlorophenol    <20  <20  50 Phenol    <5  <5  10 2,4,6-Trichlorophenol  <5  <5  10 BASE/NEUTRAL COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acenaphthene    <5  <5  10 Acenaphthylene    <5  <5  10 Anthracene    <5  <5  10 Benzidine    <50  <50  50 Benzo(a)anthracene  <5  <5  10 Benzo(a)pyrene    <5  <5  10 3,4-Benzofluoranthene  <5  <5  10 Benzo(ghi)perylene  <5  <5  20 Benzo(k)fluoranthene  <5  <5  10 Bis(2-chloroethoxy) Methane  <5  <5  10 Bis(2-chloroethyl) Ether  <5  <5  10 Bis(2-chloroisopropyl) Ether  BA  BA  10 Bis(2-ethylhexyl) Phthalate  6.8  6.8  10 4-Bromophenyl Phenyl Ether  <5  <5  10 Butylbenzyl Phthalate  <5  <5  10 2-Chloronaphthalene  <5  <5  10 4-Chlorophenyl Phenyl Ether  <5  <5  10 Chrysene    <5  <5  10 Dibenzo(a,h)anthracene  <5  <5  20 1,2-Dichlorobenzene  <5  <5  10 1,3-Dichlorobenzene  <5  <5  10 1,4-Dichlorobenzene  <5  <5  10 3,3'-Dichlorobenzidine  <10  <10  50 Diethyl Phthalate    <5  <5  10 Dimethyl Phthalate  <5  <5  10 Di-n-Butyl Phthalate  <5  <5  10 2,4-Dinitrotoluene  <5  <5  10 2,6-Dinitrotoluene  <5  <5  10 Di-n-octyl Phthalate  <5  <5  10 1,2-Diphenylhydrazine  BA  BA  20 Fluoranthene    <5  <5  10 Fluorene    <5  <5  10 Hexachlorobenzene    <5  <5  10 Hexachlorobutadiene  <5  <5  10 Hexachlorocyclopentadiene  <5  <5  10 Hexachloroethane    <5  <5  20 Indeno(1,2,3-cd)pyrene    <5  <5  20 Isophorone    <5  <5  10 Naphthalene    <5  <5  10 Nitrobenzene    <5  <5  10 n-Nitrosodimethylamine  BA  BA  50 n-Nitrosodi-n-Propylamine  <25  <25  20 n-Nitrosodiphenylamine  <5  <5  20 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 13  Phenanthrene    <5  <5  10 Pyrene    <5  <5  10 1,2,4-Trichlorobenzene  <5  <5  10 PESTICIDES    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Aldrin    BA  BA  0.05 Alpha-BHC    BA  BA  0.05 Beta-BHC    BA  BA  0.05 Gamma-BHC [Lindane]  BA  BA  0.05 Delta-BHC    BA  BA  0.05 Chlordane    BA  BA  0.2 4,4'-DDT    BA  BA  0.1 4,4'-DDE [p,p-DDX]  BA  BA  0.1 4,4'-DDD [p,p-TDE]  BA  BA  0.1 Dieldrin    BA  BA  0.1 Alpha-Endosulfan    BA  BA  0.1 Beta-Endosulfan    BA  BA  0.1 Endosulfan Sulfate  BA  BA  0.1 Endrin    BA  BA  0.1 Endrin Aldehyde    BA  BA  0.1 Heptachlor    BA  BA  0.05 Heptachlor Epoxide    BA  BA  0.05 PCB-1242    BA  BA  1.0 PCB-1254    BA  BA  1.0 PCB-1221    BA  BA  1.0 PCB-1232    BA  BA  1.0 PCB-1248    BA  BA  1.0 PCB-1260    BA  BA  1.0 PCB-1016    BA  BA  1.0 Toxaphene    BA  BA  5.0 BA - Believed Absent NA - Not Available  
Titanium  (Total)    BA  BA  ---
METALS, CYANIDE & TOTAL PHENOL (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Antimony  (Total)    <600  <600  60 Arsenic  (Total)    <10  <10  10 Beryllium (Total)    <50  <50  5 Cadmium  (Total)    <1  <1  1 Chromium  (Total)    <2  <2  10 Chromium  (3+)    NA  NA  10 Chromium  (6+)    NA  NA  10 Copper    (Total)    <100  <100  10 Lead      (Total)    <31  <31  5 Mercury  (Total)    3.9  3.9  0.2 Molybdenum (Total)  <100  <100  30 Nickel    (Total) Freshwater  <400  <400  40 Nickel    (Total) Marine  NA  NA  5 Selenium  (Total)    <5  <5  5 Silver    (Total)    <2  <2  2 Thallium  (Total)    <10  <10  10 Zinc      (Total)    <200  <200  20 Cyanide  (Total)    25  25  10  
 
Phenolics, Total Recoverable (4AAP)  14  14  5 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 11  DIOXIN    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD    BA  BA  0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acrolein    BA  BA  50 Acrylonitrile    BA  BA  50 Benzene    <5  <5  10 Bis(Chloromethyl)Ether  BA  BA  10 Bromoform    <5  <5  10 Carbon Tetrachloride  <5  <5  10 Chlorobenzene    <5  <5  10 Chlorodibromomethane  <5  <5  10 Chloroethane    <10  <10  50 2-Chloroethylvinylether  <5  <5  10 Chloroform    15  15  10 Dichlorobromomethane  <5  <5  10 Dichlorodifluoromethane  <10  <10  10 1,1-Dichloroethane  <5  <5  10 1,2-Dichloroethane  <5  <5  10 1,1-Dichloroethylene  <5  <5  10 1,2-Dichloropropane  <5  <5  10 1,3-Dichloropropylene  <5  <5  10 Ethylbenzene    <5  <5  10 Methyl Bromide [Bromomethane]  <10  <10  50 Methyl Chloride [Chloromethane] <10  <10  50 Methylene Chloride  <5  <5  20 1,1,2,2-Tetrachloroethane  <5  <5  10 Tetrachloroethylene  <5  <5  10 Toluene    <5  <5  10 1,2-trans-Dichloroethylene  BA  BA  10 1,1,1-Trichloroethane  <5  <5  10 1,1,2-Trichloroethane  <5  <5  10 Trichloroethylene    <5  <5  10 Trichlorofluoromethane  <10  <10  10 Vinyl Chloride    <10  <10  10 ACID COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol    <5  <5  10 2,4-Dichlorophenol  <5  <5  10 2,4-Dimethylphenol  <5  <5  10 4,6-Dinitro-o-Cresol  <25  <25  50 2,4-Dinitrophenol    <25  <25  50 2-Nitrophenol    <5  <5  20 4-Nitrophenol    <25  <25  50 p-Chloro-m-Cresol    <5  <5  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 12  Pentachlorophenol    <20  <20  50 Phenol    <5  <5  10 2,4,6-Trichlorophenol  <5  <5  10 BASE/NEUTRAL COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acenaphthene    <5  <5  10 Acenaphthylene    <5  <5  10 Anthracene    <5  <5  10 Benzidine    <50  <50  50 Benzo(a)anthracene  <5  <5  10 Benzo(a)pyrene    <5  <5  10 3,4-Benzofluoranthene  <5  <5  10 Benzo(ghi)perylene  <5  <5  20 Benzo(k)fluoranthene  <5  <5  10 Bis(2-chloroethoxy) Methane  <5  <5  10 Bis(2-chloroethyl) Ether  <5  <5  10 Bis(2-chloroisopropyl) Ether  BA  BA  10 Bis(2-ethylhexyl) Phthalate  6.8  6.8  10 4-Bromophenyl Phenyl Ether  <5  <5  10 Butylbenzyl Phthalate  <5  <5  10 2-Chloronaphthalene  <5  <5  10 4-Chlorophenyl Phenyl Ether  <5  <5  10 Chrysene    <5  <5  10 Dibenzo(a,h)anthracene  <5  <5  20 1,2-Dichlorobenzene  <5  <5  10 1,3-Dichlorobenzene  <5  <5  10 1,4-Dichlorobenzene  <5  <5  10 3,3'-Dichlorobenzidine  <10  <10  50 Diethyl Phthalate    <5  <5  10 Dimethyl Phthalate  <5  <5  10 Di-n-Butyl Phthalate  <5  <5  10 2,4-Dinitrotoluene  <5  <5  10 2,6-Dinitrotoluene  <5  <5  10 Di-n-octyl Phthalate  <5  <5  10 1,2-Diphenylhydrazine  BA  BA  20 Fluoranthene    <5  <5  10 Fluorene    <5  <5  10 Hexachlorobenzene    <5  <5  10 Hexachlorobutadiene  <5  <5  10 Hexachlorocyclopentadiene  <5  <5  10 Hexachloroethane    <5  <5  20 Indeno(1,2,3-cd)pyrene    <5  <5  20 Isophorone    <5  <5  10 Naphthalene    <5  <5  10 Nitrobenzene    <5  <5  10 n-Nitrosodimethylamine  BA  BA  50 n-Nitrosodi-n-Propylamine  <25  <25  20 n-Nitrosodiphenylamine  <5  <5  20 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 13  Phenanthrene    <5  <5  10 Pyrene    <5  <5  10 1,2,4-Trichlorobenzene  <5  <5  10 PESTICIDES    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Aldrin    BA  BA  0.05 Alpha-BHC    BA  BA  0.05 Beta-BHC    BA  BA  0.05 Gamma-BHC [Lindane]  BA  BA  0.05 Delta-BHC    BA  BA  0.05 Chlordane    BA  BA  0.2 4,4'-DDT    BA  BA  0.1 4,4'-DDE [p,p-DDX]  BA  BA  0.1 4,4'-DDD [p,p-TDE]  BA  BA  0.1 Dieldrin    BA  BA  0.1 Alpha-Endosulfan    BA  BA  0.1 Beta-Endosulfan    BA  BA  0.1 Endosulfan Sulfate  BA  BA  0.1 Endrin    BA  BA  0.1 Endrin Aldehyde    BA  BA  0.1 Heptachlor    BA  BA  0.05 Heptachlor Epoxide    BA  BA  0.05 PCB-1242    BA  BA  1.0 PCB-1254    BA  BA  1.0 PCB-1221    BA  BA  1.0 PCB-1232    BA  BA  1.0 PCB-1248    BA  BA  1.0 PCB-1260    BA  BA  1.0 PCB-1016    BA  BA  1.0 Toxaphene    BA  BA  5.0  
 
BA - Believed Absent  
 
NA - Not Available  
 
Internal Outfall 201 (Former 01B)
A. Type of wastewater - the intermittent internal discharge from the boron management system to Final Outfall 001 via the turbine
 
condenser cooling system. The boron management system
 
concentrates and recovers boron from low volume wastewaters for
 
reuse within the plant. The boron management system receives low
 
volume wastewater from the following sources, including but not
 
limited to:  the turbine and reactor building equipment and floor
 
drains, primary plant water makeup, laboratory drains, and other
 
low volume wastewater sources as defined in 40 CFR 423.
 
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
 
LA0007374
 
Page 14  B. Location - at the point of discharge from the boron management system prior to combining with the waters of Final Outfall 001 at
 
Latitude 2959'40", Longitude 9028'16". C. Treatment - treatment of these low volume wastewaters consists of:
- filtering/screening


Internal Outfall 201 (Former 01B)  A. Type of wastewater - the intermittent internal discharge from the boron management system to Final Outfall 001 via the turbine condenser cooling system. The boron management system concentrates and recovers boron from low volume wastewaters for reuse within the plant. The boron management system receives low volume wastewater from the following sources, including but not limited to:  the turbine and reactor building equipment and floor drains, primary plant water makeup, laboratory drains, and other low volume wastewater sources as defined in 40 CFR 423.
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 14  B. Location - at the point of discharge from the boron management system prior to combining with the waters of Final Outfall 001 at Latitude 2959'40", Longitude 9028'16". C. Treatment - treatment of these low volume wastewaters consists of: - filtering/screening
- ion exchange  
- ion exchange  
- neutralization/pH adjustment, when required  
- neutralization/pH adjustment, when required  
- distillation, when required D. Flow - Intermittent, (Max 30-Day) 0.0134 MGD E. Receiving waters - Discharge to Outfall 001 F. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA Form 2C) received on June 15, 1998. POLLUTANT    EFFLUENT     PART A    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand  <10.0  <10.0  ---
 
- distillation, when required D. Flow - Intermittent, (Max 30-Day) 0.0134 MGD E. Receiving waters - Discharge to Outfall 001 F. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA  
 
Form 2C) received on June 15, 1998.
POLLUTANT    EFFLUENT PART A    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand  <10.0  <10.0  ---
Chemical Oxygen Demand    <1.0  <1.0  ---
Chemical Oxygen Demand    <1.0  <1.0  ---
Total Organic Carbon    <1.0  <1.0  ---
Total Organic Carbon    <1.0  <1.0  ---
Total Suspended Solids  <4.0  <4.0  ---
Total Suspended Solids  <4.0  <4.0  ---
Ammonia (as N)    <0.1  <0.1  ---
Ammonia (as N)    <0.1  <0.1  ---
Temperature (Winter)  NA  NA  --- (Summer)  NA  NA  --- pH (Standard Units)  6.05  7.71  ---    (min)    (max) PART B    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Bromide    BA  BA  ---
Temperature (Winter)  NA  NA  --- (Summer)  NA  NA  --- pH (Standard Units)  6.05  7.71  ---    (min)    (max)
PART B    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Bromide    BA  BA  ---
Chlorine, Total Residual  BA  BA  ---
Chlorine, Total Residual  BA  BA  ---
Color (nM Units)    <5.0  <5.0  ---
Color (nM Units)    <5.0  <5.0  ---
Line 127: Line 417:
Organic Nitrogen, Total as (N) BA  BA  ---
Organic Nitrogen, Total as (N) BA  BA  ---
Oil and Grease    5.5  9.2  ---
Oil and Grease    5.5  9.2  ---
Phosphorous, Total as (P)  <0.25  <0.25  ---
Phosphorous, Total as (P)  <0.25  <0.25  ---  
 
Radioactivity:
Radioactivity:
Alpha, Total (pCi/L)  0.5  0.5  ---
Alpha, Total (pCi/L)  0.5  0.5  ---
Beta, Total (pCi/L)  875  875  ---
Beta, Total (pCi/L)  875  875  ---
Radium, Total (pCi/L)  BA  BA  ---
Radium, Total (pCi/L)  BA  BA  ---
Radium 226, Total (pCi/L)  BA  BA  ---
Radium 226, Total (pCi/L)  BA  BA  ---  
Sulfate (as SO4)    <1.0  <1.0  ---
 
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 15  Sulfide (as S)    BA  BA  ---
Sulfate (as SO
Sulfite (as SO3)    BA  BA  --- Surfactants    BA  BA  ---
: 4)    <1.0  <1.0  ---
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 15  Sulfide (as S)    BA  BA  ---  
 
Sulfite (as SO
: 3)    BA  BA  --- Surfactants    BA  BA  ---
Aluminum  (Total)    <0.25  <0.25  ---
Aluminum  (Total)    <0.25  <0.25  ---
Barium    (Total)    <0.1  <0.1  ---
Barium    (Total)    <0.1  <0.1  ---
Line 144: Line 443:
Manganese (Total)    <0.05  <0.05  ---
Manganese (Total)    <0.05  <0.05  ---
Tin      (Total)    BA  BA  ---
Tin      (Total)    BA  BA  ---
Titanium  (Total)    BA  BA  --- METALS, CYANIDE & TOTAL PHENOL(g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Antimony  (Total)    <300  <300  60 Arsenic  (Total)    <10  <10  10 Beryllium (Total)    <25  <25  5 Cadmium  (Total)    <1  <1  1 Chromium  (Total)    <2  <2  10 Chromium  (3+)    NA  NA  10 Chromium  (6+)    NA  NA  10 Copper    (Total)    <50  <50  10 Lead      (Total)    <31  <31  5 Mercury  (Total)    <0.2  <0.2  0.2 Molybdenum (Total)  <50  <50  30 Nickel    (Total) Freshwater  <200  <200  40 Nickel    (Total) Marine  NA  NA  5 Selenium  (Total)    <5  <5  5 Silver    (Total)    <2  <2  2 Thallium  (Total)    <10  <10  10 Zinc      (Total)    <100  <100  20 Cyanide  (Total)    10  10  10 Phenolics, Total Recoverable (4AAP)  <10  <10  5 DIOXIN    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD    BA  BA  0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acrolein    BA  BA  50 Acrylonitrile    BA  BA  50 Benzene    <5  <5  10 Bis(Chloromethyl)Ether  BA  BA  10 Bromoform    <5  <5  10 Carbon Tetrachloride  <5  <5  10 Chlorobenzene    <5  <5  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 16  Chlorodibromomethane  <5  <5  10 Chloroethane    <10  <10  50 2-Chloroethylvinylether  <5  <5  10 Chloroform    <5  <5  10 Dichlorobromomethane  <5  <5  10 Dichlorodifluoromethane  <10  <10  10 1,1-Dichloroethane  <5  <5  10 1,2-Dichloroethane  <5  <5  10 1,1-Dichloroethylene  <5  <5  10 1,2-Dichloropropane  <5  <5  10 1,3-Dichloropropylene  <5  <5  10 Ethylbenzene    <5  <5  10 Methyl Bromide [Bromomethane]  <10  <10  50 Methyl Chloride [Chloromethane] <10  <10  50 Methylene Chloride  <5  <5  20 1,1,2,2-Tetrachloroethane  <5  <5  10 Tetrachloroethylene  <5  <5  10 Toluene    <5  <5  10 1,2-trans-Dichloroethylene  BA  BA  10 1,1,1-Trichloroethane  <5  <5  10 1,1,2-Trichloroethane  <5  <5  10 Trichloroethylene    <5  <5  10 Trichlorofluoromethane  <10  <10  10 Vinyl Chloride    <10  <10  10 ACID COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol    <5  <5  10 2,4-Dichlorophenol  <5  <5  10 2,4-Dimethylphenol  <5  <5  10 4,6-Dinitro-o-Cresol  <25  <25  50 2,4-Dinitrophenol    <25  <25  50 2-Nitrophenol    <5  <5  20 4-Nitrophenol    <25  <25  50 p-Chloro-m-Cresol    <5  <5  10 Pentachlorophenol    <20  <20  50 Phenol    <5  <5  10 2,4,6-Trichlorophenol  <5  <5  10 BASE/NEUTRAL COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acenaphthene    <5  <5  10 Acenaphthylene    <5  <5  10 Anthracene    <5  <5  10 Benzidine    <50  <50  50 Benzo(a)anthracene  <5  <5  10 Benzo(a)pyrene    <5  <5  10 3,4-Benzofluoranthene  <5  <5  10 Benzo(ghi)perylene  <5  <5  20 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 17  Benzo(k)fluoranthene  <5  <5  10 Bis(2-chloroethoxy) Methane  <5  <5  10 Bis(2-chloroethyl) Ether  <5  <5  10 Bis(2-chloroisopropyl) Ether  BA  BA  10 Bis(2-ethylhexyl) Phthalate  <5  <5  10 4-Bromophenyl Phenyl Ether  <5  <5  10 Butylbenzyl Phthalate  <5  <5  10 2-Chloronaphthalene  <5  <5  10 4-Chlorophenyl Phenyl Ether  <5  <5  10 Chrysene    <5  <5  10 Dibenzo(a,h)anthracene  <5  <5  20 1,2-Dichlorobenzene  <5  <5  10 1,3-Dichlorobenzene  <5  <5  10 1,4-Dichlorobenzene  <5  <5  10 3,3'-Dichlorobenzidine  <10  <10  50 Diethyl Phthalate    <5  <5  10 Dimethyl Phthalate  <5  <5  10 Di-n-Butyl Phthalate  <5  <5  10 2,4-Dinitrotoluene  <5  <5  10 2,6-Dinitrotoluene  <5  <5  10 Di-n-octyl Phthalate  <5  <5  10 1,2-Diphenylhydrazine  BA  BA  20 Fluoranthene    <5  <5  10 Fluorene    <5  <5  10 Hexachlorobenzene    <5  <5  10 Hexachlorobutadiene  <5  <5  10 Hexachlorocyclopentadiene  <5  <5  10 Hexachloroethane    <5  <5  20 Indeno(1,2,3-cd)pyrene    <5  <5  20 Isophorone    <5  <5  10 Naphthalene    <5  <5  10 Nitrobenzene    <5  <5  10 n-Nitrosodimethylamine  BA  BA  50 n-Nitrosodi-n-Propylamine  <25  <25  20 n-Nitrosodiphenylamine  <5  <5  20 Phenanthrene    <5  <5  10 Pyrene    <5  <5  10 1,2,4-Trichlorobenzene  <5  <5  10 PESTICIDES    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Aldrin    BA  BA  0.05 Alpha-BHC    BA  BA  0.05 Beta-BHC    BA  BA  0.05 Gamma-BHC [Lindane]  BA  BA  0.05 Delta-BHC    BA  BA  0.05 Chlordane    BA  BA  0.2 4,4'-DDT    BA  BA  0.1 4,4'-DDE [p,p-DDX]  BA  BA  0.1 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 18  4,4'-DDD [p,p-TDE]  BA  BA  0.1 Dieldrin    BA  BA  0.1 Alpha-Endosulfan    BA  BA  0.1 Beta-Endosulfan    BA  BA  0.1 Endosulfan Sulfate  BA  BA  0.1 Endrin    BA  BA  0.1 Endrin Aldehyde    BA  BA  0.1 Heptachlor    BA  BA  0.05 Heptachlor Epoxide    BA  BA  0.05 PCB-1242    BA  BA  1.0 PCB-1254    BA  BA  1.0 PCB-1221    BA  BA  1.0 PCB-1232    BA  BA  1.0 PCB-1248    BA  BA  1.0 PCB-1260    BA  BA  1.0 PCB-1016    BA  BA  1.0 Toxaphene    BA  BA  5.0 BA - Believed Absent NA - Not Available  
Titanium  (Total)    BA  BA  ---
METALS, CYANIDE & TOTAL PHENOL (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Antimony  (Total)    <300  <300  60 Arsenic  (Total)    <10  <10  10 Beryllium (Total)    <25  <25  5 Cadmium  (Total)    <1  <1  1 Chromium  (Total)    <2  <2  10 Chromium  (3+)    NA  NA  10 Chromium  (6+)    NA  NA  10 Copper    (Total)    <50  <50  10 Lead      (Total)    <31  <31  5 Mercury  (Total)    <0.2  <0.2  0.2 Molybdenum (Total)  <50  <50  30 Nickel    (Total) Freshwater  <200  <200  40 Nickel    (Total) Marine  NA  NA  5 Selenium  (Total)    <5  <5  5 Silver    (Total)    <2  <2  2 Thallium  (Total)    <10  <10  10 Zinc      (Total)    <100  <100  20 Cyanide  (Total)    10  10  10  
 
Phenolics, Total Recoverable (4AAP)  <10  <10  5 DIOXIN    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD    BA  BA  0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acrolein    BA  BA  50 Acrylonitrile    BA  BA  50 Benzene    <5  <5  10 Bis(Chloromethyl)Ether  BA  BA  10 Bromoform    <5  <5  10 Carbon Tetrachloride  <5  <5  10 Chlorobenzene    <5  <5  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 16  Chlorodibromomethane  <5  <5  10 Chloroethane    <10  <10  50 2-Chloroethylvinylether  <5  <5  10 Chloroform    <5  <5  10 Dichlorobromomethane  <5  <5  10 Dichlorodifluoromethane  <10  <10  10 1,1-Dichloroethane  <5  <5  10 1,2-Dichloroethane  <5  <5  10 1,1-Dichloroethylene  <5  <5  10 1,2-Dichloropropane  <5  <5  10 1,3-Dichloropropylene  <5  <5  10 Ethylbenzene    <5  <5  10 Methyl Bromide [Bromomethane]  <10  <10  50 Methyl Chloride [Chloromethane] <10  <10  50 Methylene Chloride  <5  <5  20 1,1,2,2-Tetrachloroethane  <5  <5  10 Tetrachloroethylene  <5  <5  10 Toluene    <5  <5  10 1,2-trans-Dichloroethylene  BA  BA  10 1,1,1-Trichloroethane  <5  <5  10 1,1,2-Trichloroethane  <5  <5  10 Trichloroethylene    <5  <5  10 Trichlorofluoromethane  <10  <10  10 Vinyl Chloride    <10  <10  10 ACID COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol    <5  <5  10 2,4-Dichlorophenol  <5  <5  10 2,4-Dimethylphenol  <5  <5  10 4,6-Dinitro-o-Cresol  <25  <25  50 2,4-Dinitrophenol    <25  <25  50 2-Nitrophenol    <5  <5  20 4-Nitrophenol    <25  <25  50 p-Chloro-m-Cresol    <5  <5  10 Pentachlorophenol    <20  <20  50 Phenol    <5  <5  10 2,4,6-Trichlorophenol  <5  <5  10 BASE/NEUTRAL COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acenaphthene    <5  <5  10 Acenaphthylene    <5  <5  10 Anthracene    <5  <5  10 Benzidine    <50  <50  50 Benzo(a)anthracene  <5  <5  10 Benzo(a)pyrene    <5  <5  10 3,4-Benzofluoranthene  <5  <5  10 Benzo(ghi)perylene  <5  <5  20 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 17  Benzo(k)fluoranthene  <5  <5  10 Bis(2-chloroethoxy) Methane  <5  <5  10 Bis(2-chloroethyl) Ether  <5  <5  10 Bis(2-chloroisopropyl) Ether  BA  BA  10 Bis(2-ethylhexyl) Phthalate  <5  <5  10 4-Bromophenyl Phenyl Ether  <5  <5  10 Butylbenzyl Phthalate  <5  <5  10 2-Chloronaphthalene  <5  <5  10 4-Chlorophenyl Phenyl Ether  <5  <5  10 Chrysene    <5  <5  10 Dibenzo(a,h)anthracene  <5  <5  20 1,2-Dichlorobenzene  <5  <5  10 1,3-Dichlorobenzene  <5  <5  10 1,4-Dichlorobenzene  <5  <5  10 3,3'-Dichlorobenzidine  <10  <10  50 Diethyl Phthalate    <5  <5  10 Dimethyl Phthalate  <5  <5  10 Di-n-Butyl Phthalate  <5  <5  10 2,4-Dinitrotoluene  <5  <5  10 2,6-Dinitrotoluene  <5  <5  10 Di-n-octyl Phthalate  <5  <5  10 1,2-Diphenylhydrazine  BA  BA  20 Fluoranthene    <5  <5  10 Fluorene    <5  <5  10 Hexachlorobenzene    <5  <5  10 Hexachlorobutadiene  <5  <5  10 Hexachlorocyclopentadiene  <5  <5  10 Hexachloroethane    <5  <5  20 Indeno(1,2,3-cd)pyrene    <5  <5  20 Isophorone    <5  <5  10 Naphthalene    <5  <5  10 Nitrobenzene    <5  <5  10 n-Nitrosodimethylamine  BA  BA  50 n-Nitrosodi-n-Propylamine  <25  <25  20 n-Nitrosodiphenylamine  <5  <5  20 Phenanthrene    <5  <5  10 Pyrene    <5  <5  10 1,2,4-Trichlorobenzene  <5  <5  10 PESTICIDES    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Aldrin    BA  BA  0.05 Alpha-BHC    BA  BA  0.05 Beta-BHC    BA  BA  0.05 Gamma-BHC [Lindane]  BA  BA  0.05 Delta-BHC    BA  BA  0.05 Chlordane    BA  BA  0.2 4,4'-DDT    BA  BA  0.1 4,4'-DDE [p,p-DDX]  BA  BA  0.1 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 18  4,4'-DDD [p,p-TDE]  BA  BA  0.1 Dieldrin    BA  BA  0.1 Alpha-Endosulfan    BA  BA  0.1 Beta-Endosulfan    BA  BA  0.1 Endosulfan Sulfate  BA  BA  0.1 Endrin    BA  BA  0.1 Endrin Aldehyde    BA  BA  0.1 Heptachlor    BA  BA  0.05 Heptachlor Epoxide    BA  BA  0.05 PCB-1242    BA  BA  1.0 PCB-1254    BA  BA  1.0 PCB-1221    BA  BA  1.0 PCB-1232    BA  BA  1.0 PCB-1248    BA  BA  1.0 PCB-1260    BA  BA  1.0 PCB-1016    BA  BA  1.0 Toxaphene    BA  BA  5.0  
 
BA - Believed Absent  
 
NA - Not Available  
 
Internal Outfall 301 (Former 01C)
A. Type of wastewater - the intermittent internal discharge of filter flush water from the primary water treatment system to Final
 
Outfall 001 via the turbine condenser cooling system. The primary
 
water treatment system filters river water for various plant uses.
 
The filters of this system are flushed periodically with
 
untreated river water to remove solids trapped in the filter beds.
 
B. Location - at the point of discharge from the primary water treatment system prior to combining with the waters of Final
 
Outfall 001 at Latitude 2959'40", Longitude 9028'16". C. Treatment - filter/screening
    - separation
 
    - polymer injection, when required D. Flow - Intermittent, (Max 30-Day) 0.0029 MGD E. Receiving waters - Discharge to Outfall 001 F. Effluent Data -Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit


Internal Outfall 301 (Former 01C)  A. Type of wastewater - the intermittent internal discharge of filter flush water from the primary water treatment system to Final Outfall 001 via the turbine condenser cooling system. The primary water treatment system filters river water for various plant uses.
application (EPA Form 2C) received on June 15, 1998.
The filters of this system are flushed periodically with untreated river water to remove solids trapped in the filter beds.
POLLUTANT    EFFLUENT PART A    (mg/L, UNLESS STATED)  MQL (g/L)
B. Location - at the point of discharge from the primary water treatment system prior to combining with the waters of Final Outfall 001 at Latitude 2959'40", Longitude 9028'16". C. Treatment - filter/screening    - separation
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
    - polymer injection, when required  D. Flow - Intermittent, (Max 30-Day) 0.0029 MGD  E. Receiving waters - Discharge to Outfall 001  F. Effluent Data -Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA Form 2C) received on June 15, 1998. POLLUTANT    EFFLUENT     PART A    (mg/L, UNLESS STATED)  MQL (g/L)
 
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 19  30-Day Max Daily Max Biochemical Oxygen Demand  33.5  33.5  ---
LA0007374  
 
Page 19  30-Day Max Daily Max Biochemical Oxygen Demand  33.5  33.5  ---
Chemical Oxygen Demand    <5.0  <5.0  ---
Chemical Oxygen Demand    <5.0  <5.0  ---
Total Organic Carbon    4.4  4.4  ---
Total Organic Carbon    4.4  4.4  ---
Total Suspended Solids  46  46  ---
Total Suspended Solids  46  46  ---
Ammonia (as N)    0.828  0.828  ---
Ammonia (as N)    0.828  0.828  ---
Temperature (Winter)  NA  NA  --- (Summer)  NA  NA  --- pH (Standard Units)  7.30  7.90  ---    (min)    (max) PART B    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Bromide    BA  BA  ---
Temperature (Winter)  NA  NA  --- (Summer)  NA  NA  --- pH (Standard Units)  7.30  7.90  ---    (min)    (max)
PART B    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Bromide    BA  BA  ---
Chlorine, Total Residual  BA  BA  ---
Chlorine, Total Residual  BA  BA  ---
Color (nM Units)    25  25  ---
Color (nM Units)    25  25  ---
Line 163: Line 502:
Organic Nitrogen, Total as (N) BA  BA  ---
Organic Nitrogen, Total as (N) BA  BA  ---
Oil and Grease    BA  BA  ---
Oil and Grease    BA  BA  ---
Phosphorous, Total as (P)  0.53  0.53  ---
Phosphorous, Total as (P)  0.53  0.53  ---  
 
Radioactivity:
Radioactivity:
Alpha, Total (pCi/L)  BA  BA  ---
Alpha, Total (pCi/L)  BA  BA  ---
Beta, Total (pCi/L)  BA  BA  ---
Beta, Total (pCi/L)  BA  BA  ---
Radium, Total (pCi/L)  BA  BA  ---
Radium, Total (pCi/L)  BA  BA  ---
Radium 226, Total (pCi/L)  BA  BA  ---
Radium 226, Total (pCi/L)  BA  BA  ---  
Sulfate (as SO4)    79.1  79.1  --- Sulfide (as S)    <0.02  <0.02  ---
 
Sulfite (as SO3)    <2.0  <2.0  --- Surfactants    <0.04  <0.04  ---
Sulfate (as SO
: 4)    79.1  79.1  --- Sulfide (as S)    <0.02  <0.02  ---  
 
Sulfite (as SO
: 3)    <2.0  <2.0  --- Surfactants    <0.04  <0.04  ---
Aluminum  (Total)    0.478  0.478  ---
Aluminum  (Total)    0.478  0.478  ---
Barium    (Total)    <0.2  <0.2  ---
Barium    (Total)    <0.2  <0.2  ---
Line 179: Line 523:
Manganese (Total)    BA  BA  ---
Manganese (Total)    BA  BA  ---
Tin      (Total)    BA  BA  ---
Tin      (Total)    BA  BA  ---
Titanium  (Total)    BA  BA  --- METALS, CYANIDE & TOTAL PHENOL(g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Antimony  (Total)    BA  BA  60 Arsenic  (Total)    <10  <10  10 Beryllium (Total)    <5  <5  5 Cadmium  (Total)    <1  <1  1 Chromium  (Total)    <10  <10  10 Chromium  (3+)    NA  NA  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 20  Chromium  (6+)    NA  NA  10 Copper    (Total)    <10  <10  10 Lead      (Total)    <3  <3  5 Mercury  (Total)    <0.2  <0.2  0.2 Molybdenum (Total)  BA  BA  30 Nickel    (Total) Freshwater  <40  <40  40 Nickel    (Total) Marine  NA  NA  5 Selenium  (Total)    <5  <5  5 Silver    (Total)    <2  <2  2 Thallium  (Total)    <10  <10  10 Zinc      (Total)    85.1  85.1  20 Cyanide  (Total)    <10  <10  10 Phenolics, Total Recoverable (4AAP)  <50  <50  5 DIOXIN    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD    BA  BA  0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acrolein    <10  <10  50 Acrylonitrile    <10  <10  50 Benzene    <5  <5  10 Bis(Chloromethyl)Ether  BA  BA  10 Bromoform    <5  <5  10 Carbon Tetrachloride  <5  <5  10 Chlorobenzene    <5  <5  10 Chlorodibromomethane  <5  <5  10 Chloroethane    <10  <10  50 2-Chloroethylvinylether  <5  <5  10 Chloroform    35.9  35.9  10 Dichlorobromomethane  16.3  16.3  10 Dichlorodifluoromethane  BA  BA  10 1,1-Dichloroethane  <5  <5  10 1,2-Dichloroethane  <5  <5  10 1,1-Dichloroethylene  <5  <5  10 1,2-Dichloropropane  <5  <5  10 1,3-Dichloropropylene  <5  <5  10 Ethylbenzene    <5  <5  10 Methyl Bromide [Bromomethane]  <10  <10  50 Methyl Chloride [Chloromethane] <10  <10  50 Methylene Chloride  <5  <5  20 1,1,2,2-Tetrachloroethane  <5  <5  10 Tetrachloroethylene  <5  <5  10 Toluene    <5  <5  10 1,2-trans-Dichloroethylene  <5  <5  10 1,1,1-Trichloroethane  <5  <5  10 1,1,2-Trichloroethane  <5  <5  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 21  Trichloroethylene    <5  <5  10 Trichlorofluoromethane  BA  BA  10 Vinyl Chloride    <10  <10  10 ACID COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol    <10  <10  10 2,4-Dichlorophenol  <10  <10  10 2,4-Dimethylphenol  <10  <10  10 4,6-Dinitro-o-Cresol  <50  <50  50 2,4-Dinitrophenol    <50  <50  50 2-Nitrophenol    <10  <10  20 4-Nitrophenol    <50  <50  50 p-Chloro-m-Cresol    <10  <10  10 Pentachlorophenol    <50  <50  50 Phenol    <10  <10  10 2,4,6-Trichlorophenol  <10  <10  10 BASE/NEUTRAL COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acenaphthene    <10  <10  10 Acenaphthylene    <10  <10  10 Anthracene    <10  <10  10 Benzidine    <30  <30  50 Benzo(a)anthracene  <10  <10  10 Benzo(a)pyrene    <10  <10  10 3,4-Benzofluoranthene  <10  <10  10 Benzo(ghi)perylene  <10  <10  20 Benzo(k)fluoranthene  <10  <10  10 Bis(2-chloroethoxy) Methane  <10  <10  10 Bis(2-chloroethyl) Ether  <10  <10  10 Bis(2-chloroisopropyl) Ether  <10  <10  10 Bis(2-ethylhexyl) Phthalate  <10  <10  10 4-Bromophenyl Phenyl Ether  <10  <10  10 Butylbenzyl Phthalate  <10  <10  10 2-Chloronaphthalene  <10  <10  10 4-Chlorophenyl Phenyl Ether  <10  <10  10 Chrysene    <10  <10  10 Dibenzo(a,h)anthracene  <10  <10  20 1,2-Dichlorobenzene  <10  <10  10 1,3-Dichlorobenzene  <10  <10  10 1,4-Dichlorobenzene  <10  <10  10 3,3'-Dichlorobenzidine  <20  <20  50 Diethyl Phthalate    <10  <10  10 Dimethyl Phthalate  <10  <10  10 Di-n-Butyl Phthalate  <10  <10  10 2,4-Dinitrotoluene  <10  <10  10 2,6-Dinitrotoluene  <10  <10  10 Di-n-octyl Phthalate  <10  <10  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 22  1,2-Diphenylhydrazine  <10  <10  20 Fluoranthene    <10  <10  10 Fluorene    <10  <10  10 Hexachlorobenzene    <10  <10  10 Hexachlorobutadiene  <10  <10  10 Hexachlorocyclopentadiene  <10  <10  10 Hexachloroethane    <10  <10  20 Indeno(1,2,3-cd)pyrene    <10  <10  20 Isophorone    <10  <10  10 Naphthalene    <10  <10  10 Nitrobenzene    <10  <10  10 n-Nitrosodimethylamine  <20  <20  50 n-Nitrosodi-n-Propylamine  <10  <10  20 n-Nitrosodiphenylamine  <10  <10  20 Phenanthrene    <10  <10  10 Pyrene    <10  <10  10 1,2,4-Trichlorobenzene  <10  <10  10 PESTICIDES    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Aldrin    BA  BA  0.05 Alpha-BHC    BA  BA  0.05 Beta-BHC    BA  BA  0.05 Gamma-BHC [Lindane]  BA  BA  0.05 Delta-BHC    BA  BA  0.05 Chlordane    BA  BA  0.2 4,4'-DDT    BA  BA  0.1 4,4'-DDE [p,p-DDX]  BA  BA  0.1 4,4'-DDD [p,p-TDE]  BA  BA  0.1 Dieldrin    BA  BA  0.1 Alpha-Endosulfan    BA  BA  0.1 Beta-Endosulfan    BA  BA  0.1 Endosulfan Sulfate  BA  BA  0.1 Endrin    BA  BA  0.1 Endrin Aldehyde    BA  BA  0.1 Heptachlor    BA  BA  0.05 Heptachlor Epoxide    BA  BA  0.05 PCB-1242    BA  BA  1.0 PCB-1254    BA  BA  1.0 PCB-1221    BA  BA  1.0 PCB-1232    BA  BA  1.0 PCB-1248    BA  BA  1.0 PCB-1260    BA  BA  1.0 PCB-1016    BA  BA  1.0 Toxaphene    BA  BA  5.0 BA - Believed Absent NA - Not Available  
Titanium  (Total)    BA  BA  ---
METALS, CYANIDE & TOTAL PHENOL (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Antimony  (Total)    BA  BA  60 Arsenic  (Total)    <10  <10  10 Beryllium (Total)    <5  <5  5 Cadmium  (Total)    <1  <1  1 Chromium  (Total)    <10  <10  10 Chromium  (3+)    NA  NA  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 20  Chromium  (6+)    NA  NA  10 Copper    (Total)    <10  <10  10 Lead      (Total)    <3  <3  5 Mercury  (Total)    <0.2  <0.2  0.2 Molybdenum (Total)  BA  BA  30 Nickel    (Total) Freshwater  <40  <40  40 Nickel    (Total) Marine  NA  NA  5 Selenium  (Total)    <5  <5  5 Silver    (Total)    <2  <2  2 Thallium  (Total)    <10  <10  10 Zinc      (Total)    85.1  85.1  20 Cyanide  (Total)    <10  <10  10  
 
Phenolics, Total Recoverable (4AAP)  <50  <50  5 DIOXIN    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD    BA  BA  0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acrolein    <10  <10  50 Acrylonitrile    <10  <10  50 Benzene    <5  <5  10 Bis(Chloromethyl)Ether  BA  BA  10 Bromoform    <5  <5  10 Carbon Tetrachloride  <5  <5  10 Chlorobenzene    <5  <5  10 Chlorodibromomethane  <5  <5  10 Chloroethane    <10  <10  50 2-Chloroethylvinylether  <5  <5  10 Chloroform    35.9  35.9  10 Dichlorobromomethane  16.3  16.3  10 Dichlorodifluoromethane  BA  BA  10 1,1-Dichloroethane  <5  <5  10 1,2-Dichloroethane  <5  <5  10 1,1-Dichloroethylene  <5  <5  10 1,2-Dichloropropane  <5  <5  10 1,3-Dichloropropylene  <5  <5  10 Ethylbenzene    <5  <5  10 Methyl Bromide [Bromomethane]  <10  <10  50 Methyl Chloride [Chloromethane] <10  <10  50 Methylene Chloride  <5  <5  20 1,1,2,2-Tetrachloroethane  <5  <5  10 Tetrachloroethylene  <5  <5  10 Toluene    <5  <5  10 1,2-trans-Dichloroethylene  <5  <5  10 1,1,1-Trichloroethane  <5  <5  10 1,1,2-Trichloroethane  <5  <5  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 21  Trichloroethylene    <5  <5  10 Trichlorofluoromethane  BA  BA  10 Vinyl Chloride    <10  <10  10 ACID COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol    <10  <10  10 2,4-Dichlorophenol  <10  <10  10 2,4-Dimethylphenol  <10  <10  10 4,6-Dinitro-o-Cresol  <50  <50  50 2,4-Dinitrophenol    <50  <50  50 2-Nitrophenol    <10  <10  20 4-Nitrophenol    <50  <50  50 p-Chloro-m-Cresol    <10  <10  10 Pentachlorophenol    <50  <50  50 Phenol    <10  <10  10 2,4,6-Trichlorophenol  <10  <10  10 BASE/NEUTRAL COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acenaphthene    <10  <10  10 Acenaphthylene    <10  <10  10 Anthracene    <10  <10  10 Benzidine    <30  <30  50 Benzo(a)anthracene  <10  <10  10 Benzo(a)pyrene    <10  <10  10 3,4-Benzofluoranthene  <10  <10  10 Benzo(ghi)perylene  <10  <10  20 Benzo(k)fluoranthene  <10  <10  10 Bis(2-chloroethoxy) Methane  <10  <10  10 Bis(2-chloroethyl) Ether  <10  <10  10 Bis(2-chloroisopropyl) Ether  <10  <10  10 Bis(2-ethylhexyl) Phthalate  <10  <10  10 4-Bromophenyl Phenyl Ether  <10  <10  10 Butylbenzyl Phthalate  <10  <10  10 2-Chloronaphthalene  <10  <10  10 4-Chlorophenyl Phenyl Ether  <10  <10  10 Chrysene    <10  <10  10 Dibenzo(a,h)anthracene  <10  <10  20 1,2-Dichlorobenzene  <10  <10  10 1,3-Dichlorobenzene  <10  <10  10 1,4-Dichlorobenzene  <10  <10  10 3,3'-Dichlorobenzidine  <20  <20  50 Diethyl Phthalate    <10  <10  10 Dimethyl Phthalate  <10  <10  10 Di-n-Butyl Phthalate  <10  <10  10 2,4-Dinitrotoluene  <10  <10  10 2,6-Dinitrotoluene  <10  <10  10 Di-n-octyl Phthalate  <10  <10  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 22  1,2-Diphenylhydrazine  <10  <10  20 Fluoranthene    <10  <10  10 Fluorene    <10  <10  10 Hexachlorobenzene    <10  <10  10 Hexachlorobutadiene  <10  <10  10 Hexachlorocyclopentadiene  <10  <10  10 Hexachloroethane    <10  <10  20 Indeno(1,2,3-cd)pyrene    <10  <10  20 Isophorone    <10  <10  10 Naphthalene    <10  <10  10 Nitrobenzene    <10  <10  10 n-Nitrosodimethylamine  <20  <20  50 n-Nitrosodi-n-Propylamine  <10  <10  20 n-Nitrosodiphenylamine  <10  <10  20 Phenanthrene    <10  <10  10 Pyrene    <10  <10  10 1,2,4-Trichlorobenzene  <10  <10  10 PESTICIDES    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Aldrin    BA  BA  0.05 Alpha-BHC    BA  BA  0.05 Beta-BHC    BA  BA  0.05 Gamma-BHC [Lindane]  BA  BA  0.05 Delta-BHC    BA  BA  0.05 Chlordane    BA  BA  0.2 4,4'-DDT    BA  BA  0.1 4,4'-DDE [p,p-DDX]  BA  BA  0.1 4,4'-DDD [p,p-TDE]  BA  BA  0.1 Dieldrin    BA  BA  0.1 Alpha-Endosulfan    BA  BA  0.1 Beta-Endosulfan    BA  BA  0.1 Endosulfan Sulfate  BA  BA  0.1 Endrin    BA  BA  0.1 Endrin Aldehyde    BA  BA  0.1 Heptachlor    BA  BA  0.05 Heptachlor Epoxide    BA  BA  0.05 PCB-1242    BA  BA  1.0 PCB-1254    BA  BA  1.0 PCB-1221    BA  BA  1.0 PCB-1232    BA  BA  1.0 PCB-1248    BA  BA  1.0 PCB-1260    BA  BA  1.0 PCB-1016    BA  BA  1.0 Toxaphene    BA  BA  5.0 BA - Believed Absent  
 
NA - Not Available  


Internal Outfall 401 (Former 01D)
Internal Outfall 401 (Former 01D)
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 23  A. Type of wastewater - the intermittent internal discharge of steam generator blowdown and other low volume wastewaters to Final Outfall 001 via the turbine condenser cooling system. In addition to steam generator blowdown, low volume wastewater from other sources as defined in 40 CFR 423 are discharged from this outfall.
 
B. Location - at the point of discharge from the secondary steam plant system prior to combining with the waters of Final Outfall 001 at Latitude 2959'41", Longitude 9028'15". C. Treatment - treatment of these wastewaters consists of: - filtration  
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 23  A. Type of wastewater - the intermittent internal discharge of steam generator blowdown and other low volume wastewaters to Final  
 
Outfall 001 via the turbine condenser cooling system. In addition  
 
to steam generator blowdown, low volume wastewater from other  
 
sources as defined in 40 CFR 423 are discharged from this outfall.  
 
B. Location - at the point of discharge from the secondary steam plant system prior to combining with the waters of Final Outfall  
 
001 at Latitude 2959'41", Longitude 9028'15". C. Treatment - treatment of these wastewaters consists of:  
- filtration  
 
- ion exchange  
- ion exchange  
- neutralization/pH adjustment, when required D. Flow - Intermittent, (Max 30-Day) 0.72 MGD E. Receiving waters - Discharge to Outfall 001 F. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA Form 2C) received on June 15, 1998. POLLUTANT    EFFLUENT     PART A    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand  <2.0  <2.0  ---
 
- neutralization/pH adjustment, when required D. Flow - Intermittent, (Max 30-Day) 0.72 MGD E. Receiving waters - Discharge to Outfall 001 F. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA  
 
Form 2C) received on June 15, 1998.
POLLUTANT    EFFLUENT PART A    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand  <2.0  <2.0  ---
Chemical Oxygen Demand    <5.0  <5.0  ---
Chemical Oxygen Demand    <5.0  <5.0  ---
Total Organic Carbon    <1.0  <1.0  ---
Total Organic Carbon    <1.0  <1.0  ---
Total Suspended Solids  4.14  4.14  ---
Total Suspended Solids  4.14  4.14  ---
Ammonia (as N)    0.086  0.086  ---
Ammonia (as N)    0.086  0.086  ---
Temperature (Winter)  NA  NA  --- (Summer)  NA  NA  --- pH (Standard Units)  6.30  8.06  ---    (min)    (max) PART B    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Bromide    BA  BA  ---
Temperature (Winter)  NA  NA  --- (Summer)  NA  NA  --- pH (Standard Units)  6.30  8.06  ---    (min)    (max)
PART B    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Bromide    BA  BA  ---
Chlorine, Total Residual  BA  BA  ---
Chlorine, Total Residual  BA  BA  ---
Color (nM Units)    BA  BA  ---
Color (nM Units)    BA  BA  ---
Line 199: Line 581:
Oil and Grease    BA  BA  ---
Oil and Grease    BA  BA  ---
Phosphorous, Total as (P)  BA  BA  ---
Phosphorous, Total as (P)  BA  BA  ---
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 24  Radioactivity:
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 24  Radioactivity:
Alpha, Total (pCi/L)  NA  NA  ---
Alpha, Total (pCi/L)  NA  NA  ---
Beta, Total (pCi/L)  NA  NA  ---
Beta, Total (pCi/L)  NA  NA  ---
Radium, Total (pCi/L)  BA  BA  ---
Radium, Total (pCi/L)  BA  BA  ---
Radium 226, Total (pCi/L)  BA  BA  ---
Radium 226, Total (pCi/L)  BA  BA  ---  
Sulfate (as SO4)    <10.0  <10.0  --- Sulfide (as S)    BA  BA  ---
 
Sulfite (as SO3)    BA  BA  --- Surfactants    <0.1  <0.1  ---
Sulfate (as SO
: 4)    <10.0  <10.0  --- Sulfide (as S)    BA  BA  ---  
 
Sulfite (as SO
: 3)    BA  BA  --- Surfactants    <0.1  <0.1  ---
Aluminum  (Total)    BA  BA  ---
Aluminum  (Total)    BA  BA  ---
Barium    (Total)    BA  BA  ---
Barium    (Total)    BA  BA  ---
Line 214: Line 604:
Manganese (Total)    BA  BA  ---
Manganese (Total)    BA  BA  ---
Tin      (Total)    BA  BA  ---
Tin      (Total)    BA  BA  ---
Titanium  (Total)    BA  BA  --- METALS, CYANIDE & TOTAL PHENOL(g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Antimony  (Total)    BA  BA  60 Arsenic  (Total)    <10  <10  10 Beryllium (Total)    <5  <5  5 Cadmium  (Total)    <1  <1  1 Chromium  (Total)    <10  <10  10 Chromium  (3+)    NA  NA  10 Chromium  (6+)    NA  NA  10 Copper    (Total)    <10  <10  10 Lead      (Total)    <3  <3  5 Mercury  (Total)    <0.2  <0.2  0.2 Molybdenum (Total)  BA  BA  30 Nickel    (Total) Freshwater  <40  <40  40 Nickel    (Total) Marine  NA  NA  5 Selenium  (Total)    <5  <5  5 Silver    (Total)    <2  <2  2 Thallium  (Total)    <10  <10  10 Zinc      (Total)    <20  <20  20 Cyanide  (Total)    <10  <10  10 Phenolics, Total Recoverable (4AAP)  <50  <50  5 DIOXIN    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD    BA  BA  0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acrolein    <10  <10  50 Acrylonitrile    <10  <10  50 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 25  Benzene    <5  <5  10 Bis(Chloromethyl)Ether  BA  BA  10 Bromoform    <5  <5  10 Carbon Tetrachloride  <5  <5  10 Chlorobenzene    <5  <5  10 Chlorodibromomethane  <5  <5  10 Chloroethane    <10  <10  50 2-Chloroethylvinylether  <5  <5  10 Chloroform    <5  <5  10 Dichlorobromomethane  <5  <5  10 Dichlorodifluoromethane  BA  BA  10 1,1-Dichloroethane  <5  <5  10 1,2-Dichloroethane  <5  <5  10 1,1-Dichloroethylene  <5  <5  10 1,2-Dichloropropane  <5  <5  10 1,3-Dichloropropylene  <5  <5  10 Ethylbenzene    <5  <5  10 Methyl Bromide [Bromomethane]  <10  <10  50 Methyl Chloride [Chloromethane] <10  <10  50 Methylene Chloride  <5  <5  20 1,1,2,2-Tetrachloroethane  <5  <5  10 Tetrachloroethylene  <5  <5  10 Toluene    <5  <5  10 1,2-trans-Dichloroethylene  <5  <5  10 1,1,1-Trichloroethane  <5  <5  10 1,1,2-Trichloroethane  <5  <5  10 Trichloroethylene    <5  <5  10 Trichlorofluoromethane  BA  BA  10 Vinyl Chloride    <10  <10  10 ACID COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol    <10  <10  10 2,4-Dichlorophenol  <10  <10  10 2,4-Dimethylphenol  <10  <10  10 4,6-Dinitro-o-Cresol  <50  <50  50 2,4-Dinitrophenol    <50  <50  50 2-Nitrophenol    <10  <10  20 4-Nitrophenol    <50  <50  50 p-Chloro-m-Cresol    <10  <10  10 Pentachlorophenol    <50  <50  50 Phenol    <10  <10  10 2,4,6-Trichlorophenol  <10  <10  10 BASE/NEUTRAL COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acenaphthene    <10  <10  10 Acenaphthylene    <10  <10  10 Anthracene    <10  <10  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 26  Benzidine    <30  <30  50 Benzo(a)anthracene  <10  <10  10 Benzo(a)pyrene    <10  <10  10 3,4-Benzofluoranthene  <10  <10  10 Benzo(ghi)perylene  <10  <10  20 Benzo(k)fluoranthene  <10  <10  10 Bis(2-chloroethoxy) Methane  <10  <10  10 Bis(2-chloroethyl) Ether  <10  <10  10 Bis(2-chloroisopropyl) Ether  <10  <10  10 Bis(2-ethylhexyl) Phthalate  23.4  23.4  10 4-Bromophenyl Phenyl Ether  <10  <10  10 Butylbenzyl Phthalate  <10  <10  10 2-Chloronaphthalene  <10  <10  10 4-Chlorophenyl Phenyl Ether  <10  <10  10 Chrysene    <10  <10  10 Dibenzo(a,h)anthracene  <10  <10  20 1,2-Dichlorobenzene  <10  <10  10 1,3-Dichlorobenzene  <10  <10  10 1,4-Dichlorobenzene  <10  <10  10 3,3'-Dichlorobenzidine  <20  <20  50 Diethyl Phthalate    <10  <10  10 Dimethyl Phthalate  <10  <10  10 Di-n-Butyl Phthalate  <10  <10  10 2,4-Dinitrotoluene  <10  <10  10 2,6-Dinitrotoluene  <10  <10  10 Di-n-octyl Phthalate  <10  <10  10 1,2-Diphenylhydrazine  <10  <10  20 Fluoranthene    <10  <10  10 Fluorene    <10  <10  10 Hexachlorobenzene    <10  <10  10 Hexachlorobutadiene  <10  <10  10 Hexachlorocyclopentadiene  <10  <10  10 Hexachloroethane    <10  <10  20 Indeno(1,2,3-cd)pyrene    <10  <10  20 Isophorone    <10  <10  10 Naphthalene    <10  <10  10 Nitrobenzene    <10  <10  10 n-Nitrosodimethylamine  <20  <20  50 n-Nitrosodi-n-Propylamine  <10  <10  20 n-Nitrosodiphenylamine  <10  <10  20 Phenanthrene    <10  <10  10 Pyrene    <10  <10  10 1,2,4-Trichlorobenzene  <10  <10  10 PESTICIDES    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Aldrin    BA  BA  0.05 Alpha-BHC    BA  BA  0.05 Beta-BHC    BA  BA  0.05 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 27  Gamma-BHC [Lindane]  BA  BA  0.05 Delta-BHC    BA  BA  0.05 Chlordane    BA  BA  0.2 4,4'-DDT    BA  BA  0.1 4,4'-DDE [p,p-DDX]  BA  BA  0.1 4,4'-DDD [p,p-TDE]  BA  BA  0.1 Dieldrin    BA  BA  0.1 Alpha-Endosulfan    BA  BA  0.1 Beta-Endosulfan    BA  BA  0.1 Endosulfan Sulfate  BA  BA  0.1 Endrin    BA  BA  0.1 Endrin Aldehyde    BA  BA  0.1 Heptachlor    BA  BA  0.05 Heptachlor Epoxide    BA  BA  0.05 PCB-1242    BA  BA  1.0 PCB-1254    BA  BA  1.0 PCB-1221    BA  BA  1.0 PCB-1232    BA  BA  1.0 PCB-1248    BA  BA  1.0 PCB-1260    BA  BA  1.0 PCB-1016    BA  BA  1.0 Toxaphene    BA  BA  5.0 BA - Believed Absent NA - Not Available  
Titanium  (Total)    BA  BA  ---
METALS, CYANIDE & TOTAL PHENOL (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Antimony  (Total)    BA  BA  60 Arsenic  (Total)    <10  <10  10 Beryllium (Total)    <5  <5  5 Cadmium  (Total)    <1  <1  1 Chromium  (Total)    <10  <10  10 Chromium  (3+)    NA  NA  10 Chromium  (6+)    NA  NA  10 Copper    (Total)    <10  <10  10 Lead      (Total)    <3  <3  5 Mercury  (Total)    <0.2  <0.2  0.2 Molybdenum (Total)  BA  BA  30 Nickel    (Total) Freshwater  <40  <40  40 Nickel    (Total) Marine  NA  NA  5 Selenium  (Total)    <5  <5  5 Silver    (Total)    <2  <2  2 Thallium  (Total)    <10  <10  10 Zinc      (Total)    <20  <20  20 Cyanide  (Total)    <10  <10  10  
 
Phenolics, Total Recoverable (4AAP)  <50  <50  5 DIOXIN    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD    BA  BA  0.00001  
 
VOLATILE COMPOUNDS (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acrolein    <10  <10  50 Acrylonitrile    <10  <10  50 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 25  Benzene    <5  <5  10 Bis(Chloromethyl)Ether  BA  BA  10 Bromoform    <5  <5  10 Carbon Tetrachloride  <5  <5  10 Chlorobenzene    <5  <5  10 Chlorodibromomethane  <5  <5  10 Chloroethane    <10  <10  50 2-Chloroethylvinylether  <5  <5  10 Chloroform    <5  <5  10 Dichlorobromomethane  <5  <5  10 Dichlorodifluoromethane  BA  BA  10 1,1-Dichloroethane  <5  <5  10 1,2-Dichloroethane  <5  <5  10 1,1-Dichloroethylene  <5  <5  10 1,2-Dichloropropane  <5  <5  10 1,3-Dichloropropylene  <5  <5  10 Ethylbenzene    <5  <5  10 Methyl Bromide [Bromomethane]  <10  <10  50 Methyl Chloride [Chloromethane] <10  <10  50 Methylene Chloride  <5  <5  20 1,1,2,2-Tetrachloroethane  <5  <5  10 Tetrachloroethylene  <5  <5  10 Toluene    <5  <5  10 1,2-trans-Dichloroethylene  <5  <5  10 1,1,1-Trichloroethane  <5  <5  10 1,1,2-Trichloroethane  <5  <5  10 Trichloroethylene    <5  <5  10 Trichlorofluoromethane  BA  BA  10 Vinyl Chloride    <10  <10  10 ACID COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol    <10  <10  10 2,4-Dichlorophenol  <10  <10  10 2,4-Dimethylphenol  <10  <10  10 4,6-Dinitro-o-Cresol  <50  <50  50 2,4-Dinitrophenol    <50  <50  50 2-Nitrophenol    <10  <10  20 4-Nitrophenol    <50  <50  50 p-Chloro-m-Cresol    <10  <10  10 Pentachlorophenol    <50  <50  50 Phenol    <10  <10  10 2,4,6-Trichlorophenol  <10  <10  10 BASE/NEUTRAL COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acenaphthene    <10  <10  10 Acenaphthylene    <10  <10  10 Anthracene    <10  <10  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 26  Benzidine    <30  <30  50 Benzo(a)anthracene  <10  <10  10 Benzo(a)pyrene    <10  <10  10 3,4-Benzofluoranthene  <10  <10  10 Benzo(ghi)perylene  <10  <10  20 Benzo(k)fluoranthene  <10  <10  10 Bis(2-chloroethoxy) Methane  <10  <10  10 Bis(2-chloroethyl) Ether  <10  <10  10 Bis(2-chloroisopropyl) Ether  <10  <10  10 Bis(2-ethylhexyl) Phthalate  23.4  23.4  10 4-Bromophenyl Phenyl Ether  <10  <10  10 Butylbenzyl Phthalate  <10  <10  10 2-Chloronaphthalene  <10  <10  10 4-Chlorophenyl Phenyl Ether  <10  <10  10 Chrysene    <10  <10  10 Dibenzo(a,h)anthracene  <10  <10  20 1,2-Dichlorobenzene  <10  <10  10 1,3-Dichlorobenzene  <10  <10  10 1,4-Dichlorobenzene  <10  <10  10 3,3'-Dichlorobenzidine  <20  <20  50 Diethyl Phthalate    <10  <10  10 Dimethyl Phthalate  <10  <10  10 Di-n-Butyl Phthalate  <10  <10  10 2,4-Dinitrotoluene  <10  <10  10 2,6-Dinitrotoluene  <10  <10  10 Di-n-octyl Phthalate  <10  <10  10 1,2-Diphenylhydrazine  <10  <10  20 Fluoranthene    <10  <10  10 Fluorene    <10  <10  10 Hexachlorobenzene    <10  <10  10 Hexachlorobutadiene  <10  <10  10 Hexachlorocyclopentadiene  <10  <10  10 Hexachloroethane    <10  <10  20 Indeno(1,2,3-cd)pyrene    <10  <10  20 Isophorone    <10  <10  10 Naphthalene    <10  <10  10 Nitrobenzene    <10  <10  10 n-Nitrosodimethylamine  <20  <20  50 n-Nitrosodi-n-Propylamine  <10  <10  20 n-Nitrosodiphenylamine  <10  <10  20 Phenanthrene    <10  <10  10 Pyrene    <10  <10  10 1,2,4-Trichlorobenzene  <10  <10  10 PESTICIDES    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Aldrin    BA  BA  0.05 Alpha-BHC    BA  BA  0.05 Beta-BHC    BA  BA  0.05 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 27  Gamma-BHC [Lindane]  BA  BA  0.05 Delta-BHC    BA  BA  0.05 Chlordane    BA  BA  0.2 4,4'-DDT    BA  BA  0.1 4,4'-DDE [p,p-DDX]  BA  BA  0.1 4,4'-DDD [p,p-TDE]  BA  BA  0.1 Dieldrin    BA  BA  0.1 Alpha-Endosulfan    BA  BA  0.1 Beta-Endosulfan    BA  BA  0.1 Endosulfan Sulfate  BA  BA  0.1 Endrin    BA  BA  0.1 Endrin Aldehyde    BA  BA  0.1 Heptachlor    BA  BA  0.05 Heptachlor Epoxide    BA  BA  0.05 PCB-1242    BA  BA  1.0 PCB-1254    BA  BA  1.0 PCB-1221    BA  BA  1.0 PCB-1232    BA  BA  1.0 PCB-1248    BA  BA  1.0 PCB-1260    BA  BA  1.0 PCB-1016    BA  BA  1.0 Toxaphene    BA  BA  5.0  
 
BA - Believed Absent  
 
NA - Not Available  
 
Internal Outfall 501 A. Type of wastewater - the intermittent internal discharge from Auxiliary Component Cooling Water Basin A to Final Outfall 001 via
 
the turbine condenser cooling system. Low volume wastewater
 
sources contributing to the flow monitored at this outfall
 
include, but are not limited to, auxiliary component cooling
 
water, component cooling water, Mississippi River water used for
 
flow testing, and stormwater.
 
B. Location - at the point of discharge from Auxiliary Component Cooling Water Basin A prior to combining with the waters of Final
 
Outfall 001 at Latitude 2959'44", Longitude 9028'13". C. Treatment - treatment of these low volume wastewaters consists of:
- sedimentation


Internal Outfall 501  A. Type of wastewater - the intermittent internal discharge from Auxiliary Component Cooling Water Basin A to Final Outfall 001 via the turbine condenser cooling system. Low volume wastewater sources contributing to the flow monitored at this outfall include, but are not limited to, auxiliary component cooling water, component cooling water, Mississippi River water used for flow testing, and stormwater.
B. Location - at the point of discharge from Auxiliary Component Cooling Water Basin A prior to combining with the waters of Final Outfall 001 at Latitude 2959'44", Longitude 9028'13". C. Treatment - treatment of these low volume wastewaters consists of: - sedimentation
- neutralization/pH adjustment, when required  
- neutralization/pH adjustment, when required  
- side stream ionization, when required  
- side stream ionization, when required  
- filtration, when required D. Flow - Intermittent, (Max 30-Day) 0.26 MGD E. Receiving waters - Discharge to Outfall 001 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 28  F. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA Form 2C) received on June 15, 1998. POLLUTANT    EFFLUENT     PART A    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand  <2.0  <2.0  ---
 
- filtration, when required D. Flow - Intermittent, (Max 30-Day) 0.26 MGD E. Receiving waters - Discharge to Outfall 001 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 28  F. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA  
 
Form 2C) received on June 15, 1998.
POLLUTANT    EFFLUENT PART A    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand  <2.0  <2.0  ---
Chemical Oxygen Demand    26.0  26.0  ---
Chemical Oxygen Demand    26.0  26.0  ---
Total Organic Carbon    7.0  7.0  ---
Total Organic Carbon    7.0  7.0  ---
Total Suspended Solids  4.3  4.3  ---
Total Suspended Solids  4.3  4.3  ---
Ammonia (as N)    <0.1  <0.1  ---
Ammonia (as N)    <0.1  <0.1  ---
Temperature (Winter)  NA  NA  --- (Summer)  NA  NA  --- pH (Standard Units)  7.47  7.71  ---    (min)    (max) PART B    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Bromide    BA  BA  ---
Temperature (Winter)  NA  NA  --- (Summer)  NA  NA  --- pH (Standard Units)  7.47  7.71  ---    (min)    (max)
PART B    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Bromide    BA  BA  ---
Chlorine, Total Residual  BA  BA  ---
Chlorine, Total Residual  BA  BA  ---
Color (nM Units)    15.0  15.0  ---
Color (nM Units)    15.0  15.0  ---
Line 233: Line 669:
Organic Nitrogen, Total as (N) BA  BA  ---
Organic Nitrogen, Total as (N) BA  BA  ---
Oil and Grease    <1.0  <1.0  ---
Oil and Grease    <1.0  <1.0  ---
Phosphorous, Total as (P)  2.5  2.5  ---
Phosphorous, Total as (P)  2.5  2.5  ---  
 
Radioactivity:
Radioactivity:
Alpha, Total (pCi/L)  0.5  0.5  ---
Alpha, Total (pCi/L)  0.5  0.5  ---
Beta, Total (pCi/L)  11.0  11.0  ---
Beta, Total (pCi/L)  11.0  11.0  ---
Radium, Total (pCi/L)  BA  BA  ---
Radium, Total (pCi/L)  BA  BA  ---
Radium 226, Total (pCi/L)  BA  BA  ---
Radium 226, Total (pCi/L)  BA  BA  ---  
Sulfate (as SO4)    11.0  11.0  --- Sulfide (as S)    BA  BA  ---
 
Sulfite (as SO3)    BA  BA  --- Surfactants    BA  BA  ---
Sulfate (as SO
: 4)    11.0  11.0  --- Sulfide (as S)    BA  BA  ---  
 
Sulfite (as SO
: 3)    BA  BA  --- Surfactants    BA  BA  ---
Aluminum  (Total)    0.09  0.09  ---
Aluminum  (Total)    0.09  0.09  ---
Barium    (Total)    <0.02  <0.02  ---
Barium    (Total)    <0.02  <0.02  ---
Line 249: Line 690:
Manganese (Total)    BA  BA  ---
Manganese (Total)    BA  BA  ---
Tin      (Total)    BA  BA  ---
Tin      (Total)    BA  BA  ---
Titanium  (Total)    BA  BA  ---
Titanium  (Total)    BA  BA  ---  
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 29  METALS, CYANIDE & TOTAL PHENOL(g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Antimony  (Total)    <50  <50  60 Arsenic  (Total)    <3  <3  10 Beryllium (Total)    <4  <4  5 Cadmium  (Total)    <1  <1  1 Chromium  (Total)    10  10  10 Chromium  (3+)    NA  NA  10 Chromium  (6+)    NA  NA  10 Copper    (Total)    20  20  10 Lead      (Total)    6  6  5 Mercury  (Total)    2.0  2.0  0.2 Molybdenum (Total)  <10  <10  30 Nickel    (Total) Freshwater  <40  <40  40 Nickel    (Total) Marine  NA  NA  5 Selenium  (Total)    <5  <5  5 Silver    (Total)    <0.5  <0.5  2 Thallium  (Total)    <5  <5  10 Zinc      (Total)    1,720  1,720  20 Cyanide  (Total)    <10  <10  10 Phenolics, Total Recoverable (4AAP)  <10  <10  5 DIOXIN    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD    BA  BA  0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acrolein    BA  BA  50 Acrylonitrile    BA  BA  50 Benzene    <5  <5  10 Bis(Chloromethyl)Ether  BA  BA  10 Bromoform    <5  <5  10 Carbon Tetrachloride  <5  <5  10 Chlorobenzene    <5  <5  10 Chlorodibromomethane  <5  <5  10 Chloroethane    <10  <10  50 2-Chloroethylvinylether  <5  <5  10 Chloroform    <5  <5  10 Dichlorobromomethane  <5  <5  10 Dichlorodifluoromethane  <10  <10  10 1,1-Dichloroethane  <5  <5  10 1,2-Dichloroethane  <5  <5  10 1,1-Dichloroethylene  <5  <5  10 1,2-Dichloropropane  <5  <5  10 1,3-Dichloropropylene  <5  <5  10 Ethylbenzene    <5  <5  10 Methyl Bromide [Bromomethane]  <10  <10  50 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 30  Methyl Chloride [Chloromethane] <10  <10  50 Methylene Chloride  <5  <5  20 1,1,2,2-Tetrachloroethane  <5  <5  10 Tetrachloroethylene  <5  <5  10 Toluene    <5  <5  10 1,2-trans-Dichloroethylene  BA  BA  10 1,1,1-Trichloroethane  <5  <5  10 1,1,2-Trichloroethane  <5  <5  10 Trichloroethylene    <5  <5  10 Trichlorofluoromethane  <10  <10  10 Vinyl Chloride    <10  <10  10 ACID COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol    <5  <5  10 2,4-Dichlorophenol  <5  <5  10 2,4-Dimethylphenol  <5  <5  10 4,6-Dinitro-o-Cresol  <50  <50  50 2,4-Dinitrophenol    <50  <50  50 2-Nitrophenol    <5  <5  20 4-Nitrophenol    <50  <50  50 p-Chloro-m-Cresol    <5  <5  10 Pentachlorophenol    <50  <50  50 Phenol    <5  <5  10 2,4,6-Trichlorophenol  <5  <5  10 BASE/NEUTRAL COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acenaphthene    <5  <5  10 Acenaphthylene    <5  <5  10 Anthracene    <5  <5  10 Benzidine    <50  <50  50 Benzo(a)anthracene  <5  <5  10 Benzo(a)pyrene    <5  <5  10 3,4-Benzofluoranthene  <5  <5  10 Benzo(ghi)perylene  <5  <5  20 Benzo(k)fluoranthene  <5  <5  10 Bis(2-chloroethoxy) Methane  <5  <5  10 Bis(2-chloroethyl) Ether  <5  <5  10 Bis(2-chloroisopropyl) Ether  <5  <5  10 Bis(2-ethylhexyl) Phthalate  <5  <5  10 4-Bromophenyl Phenyl Ether  <5  <5  10 Butylbenzyl Phthalate  <5  <5  10 2-Chloronaphthalene  <5  <5  10 4-Chlorophenyl Phenyl Ether  <5  <5  10 Chrysene    <5  <5  10 Dibenzo(a,h)anthracene  <5  <5  20 1,2-Dichlorobenzene  <5  <5  10 1,3-Dichlorobenzene  <5  <5  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 31  1,4-Dichlorobenzene  <5  <5  10 3,3'-Dichlorobenzidine  <5  <5  50 Diethyl Phthalate    <5  <5  10 Dimethyl Phthalate  <5  <5  10 Di-n-Butyl Phthalate  <5  <5  10 2,4-Dinitrotoluene  <5  <5  10 2,6-Dinitrotoluene  <5  <5  10 Di-n-octyl Phthalate  <5  <5  10 1,2-Diphenylhydrazine  <5  <5  20 Fluoranthene    <5  <5  10 Fluorene    <5  <5  10 Hexachlorobenzene    <5  <5  10 Hexachlorobutadiene  <5  <5  10 Hexachlorocyclopentadiene  <5  <5  10 Hexachloroethane    <5  <5  20 Indeno(1,2,3-cd)pyrene    <5  <5  20 Isophorone    <5  <5  10 Naphthalene    <5  <5  10 Nitrobenzene    <5  <5  10 n-Nitrosodimethylamine  <5  <5  50 n-Nitrosodi-n-Propylamine  <5  <5  20 n-Nitrosodiphenylamine  <5  <5  20 Phenanthrene    <5  <5  10 Pyrene    <5  <5  10 1,2,4-Trichlorobenzene  <5  <5  10 PESTICIDES    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Aldrin    BA  BA  0.05 Alpha-BHC    BA  BA  0.05 Beta-BHC    BA  BA  0.05 Gamma-BHC [Lindane]  BA  BA  0.05 Delta-BHC    BA  BA  0.05 Chlordane    BA  BA  0.2 4,4'-DDT    BA  BA  0.1 4,4'-DDE [p,p-DDX]  BA  BA  0.1 4,4'-DDD [p,p-TDE]  BA  BA  0.1 Dieldrin    BA  BA  0.1 Alpha-Endosulfan    BA  BA  0.1 Beta-Endosulfan    BA  BA  0.1 Endosulfan Sulfate  BA  BA  0.1 Endrin    BA  BA  0.1 Endrin Aldehyde    BA  BA  0.1 Heptachlor    BA  BA  0.05 Heptachlor Epoxide    BA  BA  0.05 PCB-1242    BA  BA  1.0 PCB-1254    BA  BA  1.0 PCB-1221    BA  BA  1.0 PCB-1232    BA  BA  1.0 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 32  PCB-1248    BA  BA  1.0 PCB-1260    BA  BA  1.0 PCB-1016    BA  BA  1.0 Toxaphene    BA  BA  5.0 BA - Believed Absent NA - Not Available  
 
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 29  METALS, CYANIDE & TOTAL PHENOL (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Antimony  (Total)    <50  <50  60 Arsenic  (Total)    <3  <3  10 Beryllium (Total)    <4  <4  5 Cadmium  (Total)    <1  <1  1 Chromium  (Total)    10  10  10 Chromium  (3+)    NA  NA  10 Chromium  (6+)    NA  NA  10 Copper    (Total)    20  20  10 Lead      (Total)    6  6  5 Mercury  (Total)    2.0  2.0  0.2 Molybdenum (Total)  <10  <10  30 Nickel    (Total) Freshwater  <40  <40  40 Nickel    (Total) Marine  NA  NA  5 Selenium  (Total)    <5  <5  5 Silver    (Total)    <0.5  <0.5  2 Thallium  (Total)    <5  <5  10 Zinc      (Total)    1,720  1,720  20 Cyanide  (Total)    <10  <10  10  
 
Phenolics, Total Recoverable (4AAP)  <10  <10  5 DIOXIN    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD    BA  BA  0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acrolein    BA  BA  50 Acrylonitrile    BA  BA  50 Benzene    <5  <5  10 Bis(Chloromethyl)Ether  BA  BA  10 Bromoform    <5  <5  10 Carbon Tetrachloride  <5  <5  10 Chlorobenzene    <5  <5  10 Chlorodibromomethane  <5  <5  10 Chloroethane    <10  <10  50 2-Chloroethylvinylether  <5  <5  10 Chloroform    <5  <5  10 Dichlorobromomethane  <5  <5  10 Dichlorodifluoromethane  <10  <10  10 1,1-Dichloroethane  <5  <5  10 1,2-Dichloroethane  <5  <5  10 1,1-Dichloroethylene  <5  <5  10 1,2-Dichloropropane  <5  <5  10 1,3-Dichloropropylene  <5  <5  10 Ethylbenzene    <5  <5  10 Methyl Bromide [Bromomethane]  <10  <10  50 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 30  Methyl Chloride [Chloromethane] <10  <10  50 Methylene Chloride  <5  <5  20 1,1,2,2-Tetrachloroethane  <5  <5  10 Tetrachloroethylene  <5  <5  10 Toluene    <5  <5  10 1,2-trans-Dichloroethylene  BA  BA  10 1,1,1-Trichloroethane  <5  <5  10 1,1,2-Trichloroethane  <5  <5  10 Trichloroethylene    <5  <5  10 Trichlorofluoromethane  <10  <10  10 Vinyl Chloride    <10  <10  10 ACID COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol    <5  <5  10 2,4-Dichlorophenol  <5  <5  10 2,4-Dimethylphenol  <5  <5  10 4,6-Dinitro-o-Cresol  <50  <50  50 2,4-Dinitrophenol    <50  <50  50 2-Nitrophenol    <5  <5  20 4-Nitrophenol    <50  <50  50 p-Chloro-m-Cresol    <5  <5  10 Pentachlorophenol    <50  <50  50 Phenol    <5  <5  10 2,4,6-Trichlorophenol  <5  <5  10 BASE/NEUTRAL COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acenaphthene    <5  <5  10 Acenaphthylene    <5  <5  10 Anthracene    <5  <5  10 Benzidine    <50  <50  50 Benzo(a)anthracene  <5  <5  10 Benzo(a)pyrene    <5  <5  10 3,4-Benzofluoranthene  <5  <5  10 Benzo(ghi)perylene  <5  <5  20 Benzo(k)fluoranthene  <5  <5  10 Bis(2-chloroethoxy) Methane  <5  <5  10 Bis(2-chloroethyl) Ether  <5  <5  10 Bis(2-chloroisopropyl) Ether  <5  <5  10 Bis(2-ethylhexyl) Phthalate  <5  <5  10 4-Bromophenyl Phenyl Ether  <5  <5  10 Butylbenzyl Phthalate  <5  <5  10 2-Chloronaphthalene  <5  <5  10 4-Chlorophenyl Phenyl Ether  <5  <5  10 Chrysene    <5  <5  10 Dibenzo(a,h)anthracene  <5  <5  20 1,2-Dichlorobenzene  <5  <5  10 1,3-Dichlorobenzene  <5  <5  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 31  1,4-Dichlorobenzene  <5  <5  10 3,3'-Dichlorobenzidine  <5  <5  50 Diethyl Phthalate    <5  <5  10 Dimethyl Phthalate  <5  <5  10 Di-n-Butyl Phthalate  <5  <5  10 2,4-Dinitrotoluene  <5  <5  10 2,6-Dinitrotoluene  <5  <5  10 Di-n-octyl Phthalate  <5  <5  10 1,2-Diphenylhydrazine  <5  <5  20 Fluoranthene    <5  <5  10 Fluorene    <5  <5  10 Hexachlorobenzene    <5  <5  10 Hexachlorobutadiene  <5  <5  10 Hexachlorocyclopentadiene  <5  <5  10 Hexachloroethane    <5  <5  20 Indeno(1,2,3-cd)pyrene    <5  <5  20 Isophorone    <5  <5  10 Naphthalene    <5  <5  10 Nitrobenzene    <5  <5  10 n-Nitrosodimethylamine  <5  <5  50 n-Nitrosodi-n-Propylamine  <5  <5  20 n-Nitrosodiphenylamine  <5  <5  20 Phenanthrene    <5  <5  10 Pyrene    <5  <5  10 1,2,4-Trichlorobenzene  <5  <5  10 PESTICIDES    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Aldrin    BA  BA  0.05 Alpha-BHC    BA  BA  0.05 Beta-BHC    BA  BA  0.05 Gamma-BHC [Lindane]  BA  BA  0.05 Delta-BHC    BA  BA  0.05 Chlordane    BA  BA  0.2 4,4'-DDT    BA  BA  0.1 4,4'-DDE [p,p-DDX]  BA  BA  0.1 4,4'-DDD [p,p-TDE]  BA  BA  0.1 Dieldrin    BA  BA  0.1 Alpha-Endosulfan    BA  BA  0.1 Beta-Endosulfan    BA  BA  0.1 Endosulfan Sulfate  BA  BA  0.1 Endrin    BA  BA  0.1 Endrin Aldehyde    BA  BA  0.1 Heptachlor    BA  BA  0.05 Heptachlor Epoxide    BA  BA  0.05 PCB-1242    BA  BA  1.0 PCB-1254    BA  BA  1.0 PCB-1221    BA  BA  1.0 PCB-1232    BA  BA  1.0 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 32  PCB-1248    BA  BA  1.0 PCB-1260    BA  BA  1.0 PCB-1016    BA  BA  1.0 Toxaphene    BA  BA  5.0  
 
BA - Believed Absent  
 
NA - Not Available  
 
Internal Outfall 601 A. Type of wastewater - the intermittent internal discharge from Auxiliary Component Cooling Water Basin B to Final Outfall 001 via
 
the turbine condenser cooling system. Low volume wastewater
 
sources contributing to the flow monitored at this outfall
 
include, but are not limited to, auxiliary component cooling
 
water, component cooling water, Mississippi River water used for
 
flow testing, and stormwater.
 
B. Location - at the point of discharge from Auxiliary Component Cooling Water Basin B prior to combining with the waters of Final
 
Outfall 001 at Latitude 2959'44", Longitude 9028'13". C. Treatment - treatment of these low volume wastewaters consists of:
- sedimentation


Internal Outfall 601  A. Type of wastewater - the intermittent internal discharge from Auxiliary Component Cooling Water Basin B to Final Outfall 001 via the turbine condenser cooling system. Low volume wastewater sources contributing to the flow monitored at this outfall include, but are not limited to, auxiliary component cooling water, component cooling water, Mississippi River water used for flow testing, and stormwater.
B. Location - at the point of discharge from Auxiliary Component Cooling Water Basin B prior to combining with the waters of Final Outfall 001 at Latitude 2959'44", Longitude 9028'13". C. Treatment - treatment of these low volume wastewaters consists of: - sedimentation
- neutralization/pH adjustment, when required  
- neutralization/pH adjustment, when required  
- side stream ionization, when required  
- side stream ionization, when required  
- filtration, when required D. Flow - Intermittent, (Max 30-Day) 0.26 MGD E. Receiving waters - Discharge to Outfall 001 F. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA Form 2C) received on June 15, 1998. POLLUTANT    EFFLUENT     PART A    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand  <2.0  <2.0  ---
 
- filtration, when required D. Flow - Intermittent, (Max 30-Day) 0.26 MGD E. Receiving waters - Discharge to Outfall 001 F. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA  
 
Form 2C) received on June 15, 1998.
POLLUTANT    EFFLUENT PART A    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand  <2.0  <2.0  ---
Chemical Oxygen Demand    26.0  26.0  ---
Chemical Oxygen Demand    26.0  26.0  ---
Total Organic Carbon    7.0  7.0  ---
Total Organic Carbon    7.0  7.0  ---
Line 262: Line 746:
Ammonia (as N)    <0.1  <0.1  ---
Ammonia (as N)    <0.1  <0.1  ---
Temperature (Winter)  NA  NA  --- (Summer)  NA  NA  --- pH (Standard Units)  7.47  7.71  ---    (min)    (max)
Temperature (Winter)  NA  NA  --- (Summer)  NA  NA  --- pH (Standard Units)  7.47  7.71  ---    (min)    (max)
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 33  PART B    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Bromide    BA  BA  ---
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 33  PART B    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Bromide    BA  BA  ---
Chlorine, Total Residual  BA  BA  ---
Chlorine, Total Residual  BA  BA  ---
Color (nM Units)    15.0  15.0  ---
Color (nM Units)    15.0  15.0  ---
Line 270: Line 758:
Organic Nitrogen, Total as (N) BA  BA  ---
Organic Nitrogen, Total as (N) BA  BA  ---
Oil and Grease    <1.0  <1.0  ---
Oil and Grease    <1.0  <1.0  ---
Phosphorous, Total as (P)  2.5  2.5  ---
Phosphorous, Total as (P)  2.5  2.5  ---  
 
Radioactivity:
Radioactivity:
Alpha, Total (pCi/L)  0.5  0.5  ---
Alpha, Total (pCi/L)  0.5  0.5  ---
Beta, Total (pCi/L)  11.0  11.0  ---
Beta, Total (pCi/L)  11.0  11.0  ---
Radium, Total (pCi/L)  BA  BA  ---
Radium, Total (pCi/L)  BA  BA  ---
Radium 226, Total (pCi/L)  BA  BA  ---
Radium 226, Total (pCi/L)  BA  BA  ---  
Sulfate (as SO4)    11.0  11.0  --- Sulfide (as S)    BA  BA  ---
 
Sulfite (as SO3)    BA  BA  --- Surfactants    BA  BA  ---
Sulfate (as SO
: 4)    11.0  11.0  --- Sulfide (as S)    BA  BA  ---  
 
Sulfite (as SO
: 3)    BA  BA  --- Surfactants    BA  BA  ---
Aluminum  (Total)    0.09  0.09  ---
Aluminum  (Total)    0.09  0.09  ---
Barium    (Total)    <0.02  <0.02  ---
Barium    (Total)    <0.02  <0.02  ---
Line 286: Line 779:
Manganese (Total)    BA  BA  ---
Manganese (Total)    BA  BA  ---
Tin      (Total)    BA  BA  ---
Tin      (Total)    BA  BA  ---
Titanium  (Total)    BA  BA  --- METALS, CYANIDE & TOTAL PHENOL(g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Antimony  (Total)    <50  <50  60 Arsenic  (Total)    <3  <3  10 Beryllium (Total)    <4  <4  5 Cadmium  (Total)    <1  <1  1 Chromium  (Total)    10  10  10 Chromium  (3+)    NA  NA  10 Chromium  (6+)    NA  NA  10 Copper    (Total)    20  20  10 Lead      (Total)    6  6  5 Mercury  (Total)    2.0  2.0  0.2 Molybdenum (Total)  <10  <10  30 Nickel    (Total) Freshwater  <40  <40  40 Nickel    (Total) Marine  NA  NA  5 Selenium  (Total)    <5  <5  5 Silver    (Total)    <0.5  <0.5  2 Thallium  (Total)    <5  <5  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 34  Zinc      (Total)    1,720  1,720  20 Cyanide  (Total)    <10  <10  10 Phenolics, Total Recoverable (4AAP)  <10  <10  5 DIOXIN    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD    BA  BA  0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acrolein    BA  BA  50 Acrylonitrile    BA  BA  50 Benzene    <5  <5  10 Bis(Chloromethyl)Ether  BA  BA  10 Bromoform    <5  <5  10 Carbon Tetrachloride  <5  <5  10 Chlorobenzene    <5  <5  10 Chlorodibromomethane  <5  <5  10 Chloroethane    <10  <10  50 2-Chloroethylvinylether  <5  <5  10 Chloroform    <5  <5  10 Dichlorobromomethane  <5  <5  10 Dichlorodifluoromethane  <10  <10  10 1,1-Dichloroethane  <5  <5  10 1,2-Dichloroethane  <5  <5  10 1,1-Dichloroethylene  <5  <5  10 1,2-Dichloropropane  <5  <5  10 1,3-Dichloropropylene  <5  <5  10 Ethylbenzene    <5  <5  10 Methyl Bromide [Bromomethane]  <10  <10  50 Methyl Chloride [Chloromethane] <10  <10  50 Methylene Chloride  <5  <5  20 1,1,2,2-Tetrachloroethane  <5  <5  10 Tetrachloroethylene  <5  <5  10 Toluene    <5  <5  10 1,2-trans-Dichloroethylene  BA  BA  10 1,1,1-Trichloroethane  <5  <5  10 1,1,2-Trichloroethane  <5  <5  10 Trichloroethylene    <5  <5  10 Trichlorofluoromethane  <10  <10  10 Vinyl Chloride    <10  <10  10 ACID COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol    <5  <5  10 2,4-Dichlorophenol  <5  <5  10 2,4-Dimethylphenol  <5  <5  10 4,6-Dinitro-o-Cresol  <50  <50  50 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 35  2,4-Dinitrophenol    <50  <50  50 2-Nitrophenol    <5  <5  20 4-Nitrophenol    <50  <50  50 p-Chloro-m-Cresol    <5  <5  10 Pentachlorophenol    <50  <50  50 Phenol    <5  <5  10 2,4,6-Trichlorophenol  <5  <5  10 BASE/NEUTRAL COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acenaphthene    <5  <5  10 Acenaphthylene    <5  <5  10 Anthracene    <5  <5  10 Benzidine    <50  <50  50 Benzo(a)anthracene  <5  <5  10 Benzo(a)pyrene    <5  <5  10 3,4-Benzofluoranthene  <5  <5  10 Benzo(ghi)perylene  <5  <5  20 Benzo(k)fluoranthene  <5  <5  10 Bis(2-chloroethoxy) Methane  <5  <5  10 Bis(2-chloroethyl) Ether  <5  <5  10 Bis(2-chloroisopropyl) Ether  <5  <5  10 Bis(2-ethylhexyl) Phthalate  <5  <5  10 4-Bromophenyl Phenyl Ether  <5  <5  10 Butylbenzyl Phthalate  <5  <5  10 2-Chloronaphthalene  <5  <5  10 4-Chlorophenyl Phenyl Ether  <5  <5  10 Chrysene    <5  <5  10 Dibenzo(a,h)anthracene  <5  <5  20 1,2-Dichlorobenzene  <5  <5  10 1,3-Dichlorobenzene  <5  <5  10 1,4-Dichlorobenzene  <5  <5  10 3,3'-Dichlorobenzidine  <5  <5  50 Diethyl Phthalate    <5  <5  10 Dimethyl Phthalate  <5  <5  10 Di-n-Butyl Phthalate  <5  <5  10 2,4-Dinitrotoluene  <5  <5  10 2,6-Dinitrotoluene  <5  <5  10 Di-n-octyl Phthalate  <5  <5  10 1,2-Diphenylhydrazine  <5  <5  20 Fluoranthene    <5  <5  10 Fluorene    <5  <5  10 Hexachlorobenzene    <5  <5  10 Hexachlorobutadiene  <5  <5  10 Hexachlorocyclopentadiene  <5  <5  10 Hexachloroethane    <5  <5  20 Indeno(1,2,3-cd)pyrene    <5  <5  20 Isophorone    <5  <5  10 Naphthalene    <5  <5  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 36  Nitrobenzene    <5  <5  10 n-Nitrosodimethylamine  <5  <5  50 n-Nitrosodi-n-Propylamine  <5  <5  20 n-Nitrosodiphenylamine  <5  <5  20 Phenanthrene    <5  <5  10 Pyrene    <5  <5  10 1,2,4-Trichlorobenzene  <5  <5  10 PESTICIDES    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Aldrin    BA  BA  0.05 Alpha-BHC    BA  BA  0.05 Beta-BHC    BA  BA  0.05 Gamma-BHC [Lindane]  BA  BA  0.05 Delta-BHC    BA  BA  0.05 Chlordane    BA  BA  0.2 4,4'-DDT    BA  BA  0.1 4,4'-DDE [p,p-DDX]  BA  BA  0.1 4,4'-DDD [p,p-TDE]  BA  BA  0.1 Dieldrin    BA  BA  0.1 Alpha-Endosulfan    BA  BA  0.1 Beta-Endosulfan    BA  BA  0.1 Endosulfan Sulfate  BA  BA  0.1 Endrin    BA  BA  0.1 Endrin Aldehyde    BA  BA  0.1 Heptachlor    BA  BA  0.05 Heptachlor Epoxide    BA  BA  0.05 PCB-1242    BA  BA  1.0 PCB-1254    BA  BA  1.0 PCB-1221    BA  BA  1.0 PCB-1232    BA  BA  1.0 PCB-1248    BA  BA  1.0 PCB-1260    BA  BA  1.0 PCB-1016    BA  BA  1.0 Toxaphene    BA  BA  5.0 BA - Believed Absent NA - Not Available  
Titanium  (Total)    BA  BA  ---
METALS, CYANIDE & TOTAL PHENOL (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Antimony  (Total)    <50  <50  60 Arsenic  (Total)    <3  <3  10 Beryllium (Total)    <4  <4  5 Cadmium  (Total)    <1  <1  1 Chromium  (Total)    10  10  10 Chromium  (3+)    NA  NA  10 Chromium  (6+)    NA  NA  10 Copper    (Total)    20  20  10 Lead      (Total)    6  6  5 Mercury  (Total)    2.0  2.0  0.2 Molybdenum (Total)  <10  <10  30 Nickel    (Total) Freshwater  <40  <40  40 Nickel    (Total) Marine  NA  NA  5 Selenium  (Total)    <5  <5  5 Silver    (Total)    <0.5  <0.5  2 Thallium  (Total)    <5  <5  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 34  Zinc      (Total)    1,720  1,720  20 Cyanide  (Total)    <10  <10  10  
 
Phenolics, Total Recoverable (4AAP)  <10  <10  5 DIOXIN    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD    BA  BA  0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acrolein    BA  BA  50 Acrylonitrile    BA  BA  50 Benzene    <5  <5  10 Bis(Chloromethyl)Ether  BA  BA  10 Bromoform    <5  <5  10 Carbon Tetrachloride  <5  <5  10 Chlorobenzene    <5  <5  10 Chlorodibromomethane  <5  <5  10 Chloroethane    <10  <10  50 2-Chloroethylvinylether  <5  <5  10 Chloroform    <5  <5  10 Dichlorobromomethane  <5  <5  10 Dichlorodifluoromethane  <10  <10  10 1,1-Dichloroethane  <5  <5  10 1,2-Dichloroethane  <5  <5  10 1,1-Dichloroethylene  <5  <5  10 1,2-Dichloropropane  <5  <5  10 1,3-Dichloropropylene  <5  <5  10 Ethylbenzene    <5  <5  10 Methyl Bromide [Bromomethane]  <10  <10  50 Methyl Chloride [Chloromethane] <10  <10  50 Methylene Chloride  <5  <5  20 1,1,2,2-Tetrachloroethane  <5  <5  10 Tetrachloroethylene  <5  <5  10 Toluene    <5  <5  10 1,2-trans-Dichloroethylene  BA  BA  10 1,1,1-Trichloroethane  <5  <5  10 1,1,2-Trichloroethane  <5  <5  10 Trichloroethylene    <5  <5  10 Trichlorofluoromethane  <10  <10  10 Vinyl Chloride    <10  <10  10 ACID COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol    <5  <5  10 2,4-Dichlorophenol  <5  <5  10 2,4-Dimethylphenol  <5  <5  10 4,6-Dinitro-o-Cresol  <50  <50  50 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 35  2,4-Dinitrophenol    <50  <50  50 2-Nitrophenol    <5  <5  20 4-Nitrophenol    <50  <50  50 p-Chloro-m-Cresol    <5  <5  10 Pentachlorophenol    <50  <50  50 Phenol    <5  <5  10 2,4,6-Trichlorophenol  <5  <5  10 BASE/NEUTRAL COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acenaphthene    <5  <5  10 Acenaphthylene    <5  <5  10 Anthracene    <5  <5  10 Benzidine    <50  <50  50 Benzo(a)anthracene  <5  <5  10 Benzo(a)pyrene    <5  <5  10 3,4-Benzofluoranthene  <5  <5  10 Benzo(ghi)perylene  <5  <5  20 Benzo(k)fluoranthene  <5  <5  10 Bis(2-chloroethoxy) Methane  <5  <5  10 Bis(2-chloroethyl) Ether  <5  <5  10 Bis(2-chloroisopropyl) Ether  <5  <5  10 Bis(2-ethylhexyl) Phthalate  <5  <5  10 4-Bromophenyl Phenyl Ether  <5  <5  10 Butylbenzyl Phthalate  <5  <5  10 2-Chloronaphthalene  <5  <5  10 4-Chlorophenyl Phenyl Ether  <5  <5  10 Chrysene    <5  <5  10 Dibenzo(a,h)anthracene  <5  <5  20 1,2-Dichlorobenzene  <5  <5  10 1,3-Dichlorobenzene  <5  <5  10 1,4-Dichlorobenzene  <5  <5  10 3,3'-Dichlorobenzidine  <5  <5  50 Diethyl Phthalate    <5  <5  10 Dimethyl Phthalate  <5  <5  10 Di-n-Butyl Phthalate  <5  <5  10 2,4-Dinitrotoluene  <5  <5  10 2,6-Dinitrotoluene  <5  <5  10 Di-n-octyl Phthalate  <5  <5  10 1,2-Diphenylhydrazine  <5  <5  20 Fluoranthene    <5  <5  10 Fluorene    <5  <5  10 Hexachlorobenzene    <5  <5  10 Hexachlorobutadiene  <5  <5  10 Hexachlorocyclopentadiene  <5  <5  10 Hexachloroethane    <5  <5  20 Indeno(1,2,3-cd)pyrene    <5  <5  20 Isophorone    <5  <5  10 Naphthalene    <5  <5  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 36  Nitrobenzene    <5  <5  10 n-Nitrosodimethylamine  <5  <5  50 n-Nitrosodi-n-Propylamine  <5  <5  20 n-Nitrosodiphenylamine  <5  <5  20 Phenanthrene    <5  <5  10 Pyrene    <5  <5  10 1,2,4-Trichlorobenzene  <5  <5  10 PESTICIDES    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Aldrin    BA  BA  0.05 Alpha-BHC    BA  BA  0.05 Beta-BHC    BA  BA  0.05 Gamma-BHC [Lindane]  BA  BA  0.05 Delta-BHC    BA  BA  0.05 Chlordane    BA  BA  0.2 4,4'-DDT    BA  BA  0.1 4,4'-DDE [p,p-DDX]  BA  BA  0.1 4,4'-DDD [p,p-TDE]  BA  BA  0.1 Dieldrin    BA  BA  0.1 Alpha-Endosulfan    BA  BA  0.1 Beta-Endosulfan    BA  BA  0.1 Endosulfan Sulfate  BA  BA  0.1 Endrin    BA  BA  0.1 Endrin Aldehyde    BA  BA  0.1 Heptachlor    BA  BA  0.05 Heptachlor Epoxide    BA  BA  0.05 PCB-1242    BA  BA  1.0 PCB-1254    BA  BA  1.0 PCB-1221    BA  BA  1.0 PCB-1232    BA  BA  1.0 PCB-1248    BA  BA  1.0 PCB-1260    BA  BA  1.0 PCB-1016    BA  BA  1.0 Toxaphene    BA  BA  5.0  
 
BA - Believed Absent  
 
NA - Not Available  
 
Internal Outfall 701 A. Type of wastewater - the intermittent internal discharge of cooling tower blowdown and low volume wastewaters from Dry Cooling
 
Tower Sump #1 to Final Outfall 001 via the turbine condenser
 
cooling system. In addition to the wet cooling tower blowdown,
 
low volume wastewater from various sources as defined in 40 CFR
 
423 are discharged from this outfall. Low volume wastewater
 
sources contributing to this monitored flow include, but are not
 
limited to, wet cooling tower leakage, auxiliary component cooling Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
 
LA0007374
 
Page 37  water, component cooling water, and stormwater. Previously
 
monitored effluent from the Yard Oil Separator System (Internal
 
Outfall 104) is infrequently discharged through this outfall as a
 
result of maintenance activities. Optional discharge to Final
 
Outfall 004 via the plant drainage ditches may occur during
 
periods when the circulating water system is unavailable. 
 
B. Location - at the point of discharge from Dry Cooling Tower Sump
#1 prior to combining with the waters of Final Outfall 001 or
 
Final Outfall 004 at Latitude 2959'44", Longitude 9028'13". C. Treatment - treatment of these wastewaters consists of:
- sedimentation


Internal Outfall 701  A. Type of wastewater - the intermittent internal discharge of cooling tower blowdown and low volume wastewaters from Dry Cooling Tower Sump #1 to Final Outfall 001 via the turbine condenser cooling system. In addition to the wet cooling tower blowdown, low volume wastewater from various sources as defined in 40 CFR 423 are discharged from this outfall. Low volume wastewater sources contributing to this monitored flow include, but are not limited to, wet cooling tower leakage, auxiliary component cooling Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 37  water, component cooling water, and stormwater. Previously monitored effluent from the Yard Oil Separator System (Internal Outfall 104) is infrequently discharged through this outfall as a result of maintenance activities. Optional discharge to Final Outfall 004 via the plant drainage ditches may occur during periods when the circulating water system is unavailable.
B. Location - at the point of discharge from Dry Cooling Tower Sump #1 prior to combining with the waters of Final Outfall 001 or Final Outfall 004 at Latitude 2959'44", Longitude 9028'13". C. Treatment - treatment of these wastewaters consists of: - sedimentation
- neutralization/pH adjustment, when required  
- neutralization/pH adjustment, when required  
- side stream ionization, when required  
- side stream ionization, when required  
- filtration, when required D. Flow - Intermittent, (Max 30-Day) 0.01 MGD E. Receiving waters - Discharge to Outfall 001 or the optional discharge to Outfall 004 F. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA Form 2C) received on June 15, 1998. POLLUTANT    EFFLUENT     PART A    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand  <2.0  <2.0  ---
 
- filtration, when required D. Flow - Intermittent, (Max 30-Day) 0.01 MGD E. Receiving waters - Discharge to Outfall 001 or the optional discharge to Outfall 004 F. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA  
 
Form 2C) received on June 15, 1998.
POLLUTANT    EFFLUENT PART A    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand  <2.0  <2.0  ---
Chemical Oxygen Demand    26.0  26.0  ---
Chemical Oxygen Demand    26.0  26.0  ---
Total Organic Carbon    7.0  7.0  ---
Total Organic Carbon    7.0  7.0  ---
Total Suspended Solids  4.3  4.3  ---
Total Suspended Solids  4.3  4.3  ---
Ammonia (as N)    <0.1  <0.1  ---
Ammonia (as N)    <0.1  <0.1  ---
Temperature (Winter)  NA  NA  --- (Summer)  NA  NA  --- pH (Standard Units)  7.47  7.71  ---    (min)    (max) PART B    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Bromide    BA  BA  ---
Temperature (Winter)  NA  NA  --- (Summer)  NA  NA  --- pH (Standard Units)  7.47  7.71  ---    (min)    (max)
PART B    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Bromide    BA  BA  ---
Chlorine, Total Residual  BA  BA  ---
Chlorine, Total Residual  BA  BA  ---
Color (nM Units)    15.0  15.0  ---
Color (nM Units)    15.0  15.0  ---
Line 304: Line 854:
Nitrate-Nitrite (N)  0.9  0.9  ---
Nitrate-Nitrite (N)  0.9  0.9  ---
Organic Nitrogen, Total as (N) BA  BA  ---
Organic Nitrogen, Total as (N) BA  BA  ---
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 38  Oil and Grease    <1.0  <1.0  ---
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
Phosphorous, Total as (P)  2.5  2.5  ---
 
LA0007374  
 
Page 38  Oil and Grease    <1.0  <1.0  ---
Phosphorous, Total as (P)  2.5  2.5  ---  
 
Radioactivity:
Radioactivity:
Alpha, Total (pCi/L)  0.5  0.5  ---
Alpha, Total (pCi/L)  0.5  0.5  ---
Beta, Total (pCi/L)  11.0  11.0  ---
Beta, Total (pCi/L)  11.0  11.0  ---
Radium, Total (pCi/L)  BA  BA  ---
Radium, Total (pCi/L)  BA  BA  ---
Radium 226, Total (pCi/L)  BA  BA  ---
Radium 226, Total (pCi/L)  BA  BA  ---  
Sulfate (as SO4)    11.0  11.0  --- Sulfide (as S)    BA  BA  ---
 
Sulfite (as SO3)    BA  BA  --- Surfactants    BA  BA  ---
Sulfate (as SO
: 4)    11.0  11.0  --- Sulfide (as S)    BA  BA  ---  
 
Sulfite (as SO
: 3)    BA  BA  --- Surfactants    BA  BA  ---
Aluminum  (Total)    0.09  0.09  ---
Aluminum  (Total)    0.09  0.09  ---
Barium    (Total)    <0.02  <0.02  ---
Barium    (Total)    <0.02  <0.02  ---
Line 321: Line 880:
Manganese (Total)    BA  BA  ---
Manganese (Total)    BA  BA  ---
Tin      (Total)    BA  BA  ---
Tin      (Total)    BA  BA  ---
Titanium  (Total)    BA  BA  --- METALS, CYANIDE & TOTAL PHENOL(g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Antimony  (Total)    <50  <50  60 Arsenic  (Total)    <3  <3  10 Beryllium (Total)    <4  <4  5 Cadmium  (Total)    <1  <1  1 Chromium  (Total)    10  10  10 Chromium  (3+)    NA  NA  10 Chromium  (6+)    NA  NA  10 Copper    (Total)    20  20  10 Lead      (Total)    6  6  5 Mercury  (Total)    2.0  2.0  0.2 Molybdenum (Total)  <10  <10  30 Nickel    (Total) Freshwater  <40  <40  40 Nickel    (Total) Marine  NA  NA  5 Selenium  (Total)    <5  <5  5 Silver    (Total)    <0.5  <0.5  2 Thallium  (Total)    <5  <5  10 Zinc      (Total)    1,720  1,720  20 Cyanide  (Total)    <10  <10  10 Phenolics, Total Recoverable (4AAP)  <10  <10  5 DIOXIN    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD    BA  BA  0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED)  MQL (g/L)
Titanium  (Total)    BA  BA  ---
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 39  30-Day Max Daily Max Acrolein    BA  BA  50 Acrylonitrile    BA  BA  50 Benzene    <5  <5  10 Bis(Chloromethyl)Ether  BA  BA  10 Bromoform    <5  <5  10 Carbon Tetrachloride  <5  <5  10 Chlorobenzene    <5  <5  10 Chlorodibromomethane  <5  <5  10 Chloroethane    <10  <10  50 2-Chloroethylvinylether  <5  <5  10 Chloroform    <5  <5  10 Dichlorobromomethane  <5  <5  10 Dichlorodifluoromethane  <10  <10  10 1,1-Dichloroethane  <5  <5  10 1,2-Dichloroethane  <5  <5  10 1,1-Dichloroethylene  <5  <5  10 1,2-Dichloropropane  <5  <5  10 1,3-Dichloropropylene  <5  <5  10 Ethylbenzene    <5  <5  10 Methyl Bromide [Bromomethane]  <10  <10  50 Methyl Chloride [Chloromethane] <10  <10  50 Methylene Chloride  <5  <5  20 1,1,2,2-Tetrachloroethane  <5  <5  10 Tetrachloroethylene  <5  <5  10 Toluene    <5  <5  10 1,2-trans-Dichloroethylene  BA  BA  10 1,1,1-Trichloroethane  <5  <5  10 1,1,2-Trichloroethane  <5  <5  10 Trichloroethylene    <5  <5  10 Trichlorofluoromethane  <10  <10  10 Vinyl Chloride    <10  <10  10 ACID COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol    <5  <5  10 2,4-Dichlorophenol  <5  <5  10 2,4-Dimethylphenol  <5  <5  10 4,6-Dinitro-o-Cresol  <50  <50  50 2,4-Dinitrophenol    <50  <50  50 2-Nitrophenol    <5  <5  20 4-Nitrophenol    <50  <50  50 p-Chloro-m-Cresol    <5  <5  10 Pentachlorophenol    <50  <50  50 Phenol    <5  <5  10 2,4,6-Trichlorophenol  <5  <5  10 BASE/NEUTRAL COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 40  Acenaphthene    <5  <5  10 Acenaphthylene    <5  <5  10 Anthracene    <5  <5  10 Benzidine    <50  <50  50 Benzo(a)anthracene  <5  <5  10 Benzo(a)pyrene    <5  <5  10 3,4-Benzofluoranthene  <5  <5  10 Benzo(ghi)perylene  <5  <5  20 Benzo(k)fluoranthene  <5  <5  10 Bis(2-chloroethoxy) Methane  <5  <5  10 Bis(2-chloroethyl) Ether  <5  <5  10 Bis(2-chloroisopropyl) Ether  <5  <5  10 Bis(2-ethylhexyl) Phthalate  <5  <5  10 4-Bromophenyl Phenyl Ether  <5  <5  10 Butylbenzyl Phthalate  <5  <5  10 2-Chloronaphthalene  <5  <5  10 4-Chlorophenyl Phenyl Ether  <5  <5  10 Chrysene    <5  <5  10 Dibenzo(a,h)anthracene  <5  <5  20 1,2-Dichlorobenzene  <5  <5  10 1,3-Dichlorobenzene  <5  <5  10 1,4-Dichlorobenzene  <5  <5  10 3,3'-Dichlorobenzidine  <5  <5  50 Diethyl Phthalate    <5  <5  10 Dimethyl Phthalate  <5  <5  10 Di-n-Butyl Phthalate  <5  <5  10 2,4-Dinitrotoluene  <5  <5  10 2,6-Dinitrotoluene  <5  <5  10 Di-n-octyl Phthalate  <5  <5  10 1,2-Diphenylhydrazine  <5  <5  20 Fluoranthene    <5  <5  10 Fluorene    <5  <5  10 Hexachlorobenzene    <5  <5  10 Hexachlorobutadiene  <5  <5  10 Hexachlorocyclopentadiene  <5  <5  10 Hexachloroethane    <5  <5  20 Indeno(1,2,3-cd)pyrene    <5  <5  20 Isophorone    <5  <5  10 Naphthalene    <5  <5  10 Nitrobenzene    <5  <5  10 n-Nitrosodimethylamine  <5  <5  50 n-Nitrosodi-n-Propylamine  <5  <5  20 n-Nitrosodiphenylamine  <5  <5  20 Phenanthrene    <5  <5  10 Pyrene    <5  <5  10 1,2,4-Trichlorobenzene  <5  <5  10 PESTICIDES    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 41  Aldrin    BA  BA  0.05 Alpha-BHC    BA  BA  0.05 Beta-BHC    BA  BA  0.05 Gamma-BHC [Lindane]  BA  BA  0.05 Delta-BHC    BA  BA  0.05 Chlordane    BA  BA  0.2 4,4'-DDT    BA  BA  0.1 4,4'-DDE [p,p-DDX]  BA  BA  0.1 4,4'-DDD [p,p-TDE]  BA  BA  0.1 Dieldrin    BA  BA  0.1 Alpha-Endosulfan    BA  BA  0.1 Beta-Endosulfan    BA  BA  0.1 Endosulfan Sulfate  BA  BA  0.1 Endrin    BA  BA  0.1 Endrin Aldehyde    BA  BA  0.1 Heptachlor    BA  BA  0.05 Heptachlor Epoxide    BA  BA  0.05 PCB-1242    BA  BA  1.0 PCB-1254    BA  BA  1.0 PCB-1221    BA  BA  1.0 PCB-1232    BA  BA  1.0 PCB-1248    BA  BA  1.0 PCB-1260    BA  BA  1.0 PCB-1016    BA  BA  1.0 Toxaphene    BA  BA  5.0 BA - Believed Absent NA - Not Available  
METALS, CYANIDE & TOTAL PHENOL (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Antimony  (Total)    <50  <50  60 Arsenic  (Total)    <3  <3  10 Beryllium (Total)    <4  <4  5 Cadmium  (Total)    <1  <1  1 Chromium  (Total)    10  10  10 Chromium  (3+)    NA  NA  10 Chromium  (6+)    NA  NA  10 Copper    (Total)    20  20  10 Lead      (Total)    6  6  5 Mercury  (Total)    2.0  2.0  0.2 Molybdenum (Total)  <10  <10  30 Nickel    (Total) Freshwater  <40  <40  40 Nickel    (Total) Marine  NA  NA  5 Selenium  (Total)    <5  <5  5 Silver    (Total)    <0.5  <0.5  2 Thallium  (Total)    <5  <5  10 Zinc      (Total)    1,720  1,720  20 Cyanide  (Total)    <10  <10  10  
 
Phenolics, Total Recoverable (4AAP)  <10  <10  5 DIOXIN    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD    BA  BA  0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED)  MQL (g/L)
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 39  30-Day Max Daily Max Acrolein    BA  BA  50 Acrylonitrile    BA  BA  50 Benzene    <5  <5  10 Bis(Chloromethyl)Ether  BA  BA  10 Bromoform    <5  <5  10 Carbon Tetrachloride  <5  <5  10 Chlorobenzene    <5  <5  10 Chlorodibromomethane  <5  <5  10 Chloroethane    <10  <10  50 2-Chloroethylvinylether  <5  <5  10 Chloroform    <5  <5  10 Dichlorobromomethane  <5  <5  10 Dichlorodifluoromethane  <10  <10  10 1,1-Dichloroethane  <5  <5  10 1,2-Dichloroethane  <5  <5  10 1,1-Dichloroethylene  <5  <5  10 1,2-Dichloropropane  <5  <5  10 1,3-Dichloropropylene  <5  <5  10 Ethylbenzene    <5  <5  10 Methyl Bromide [Bromomethane]  <10  <10  50 Methyl Chloride [Chloromethane] <10  <10  50 Methylene Chloride  <5  <5  20 1,1,2,2-Tetrachloroethane  <5  <5  10 Tetrachloroethylene  <5  <5  10 Toluene    <5  <5  10 1,2-trans-Dichloroethylene  BA  BA  10 1,1,1-Trichloroethane  <5  <5  10 1,1,2-Trichloroethane  <5  <5  10 Trichloroethylene    <5  <5  10 Trichlorofluoromethane  <10  <10  10 Vinyl Chloride    <10  <10  10 ACID COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol    <5  <5  10 2,4-Dichlorophenol  <5  <5  10 2,4-Dimethylphenol  <5  <5  10 4,6-Dinitro-o-Cresol  <50  <50  50 2,4-Dinitrophenol    <50  <50  50 2-Nitrophenol    <5  <5  20 4-Nitrophenol    <50  <50  50 p-Chloro-m-Cresol    <5  <5  10 Pentachlorophenol    <50  <50  50 Phenol    <5  <5  10 2,4,6-Trichlorophenol  <5  <5  10 BASE/NEUTRAL COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max
 
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 40  Acenaphthene    <5  <5  10 Acenaphthylene    <5  <5  10 Anthracene    <5  <5  10 Benzidine    <50  <50  50 Benzo(a)anthracene  <5  <5  10 Benzo(a)pyrene    <5  <5  10 3,4-Benzofluoranthene  <5  <5  10 Benzo(ghi)perylene  <5  <5  20 Benzo(k)fluoranthene  <5  <5  10 Bis(2-chloroethoxy) Methane  <5  <5  10 Bis(2-chloroethyl) Ether  <5  <5  10 Bis(2-chloroisopropyl) Ether  <5  <5  10 Bis(2-ethylhexyl) Phthalate  <5  <5  10 4-Bromophenyl Phenyl Ether  <5  <5  10 Butylbenzyl Phthalate  <5  <5  10 2-Chloronaphthalene  <5  <5  10 4-Chlorophenyl Phenyl Ether  <5  <5  10 Chrysene    <5  <5  10 Dibenzo(a,h)anthracene  <5  <5  20 1,2-Dichlorobenzene  <5  <5  10 1,3-Dichlorobenzene  <5  <5  10 1,4-Dichlorobenzene  <5  <5  10 3,3'-Dichlorobenzidine  <5  <5  50 Diethyl Phthalate    <5  <5  10 Dimethyl Phthalate  <5  <5  10 Di-n-Butyl Phthalate  <5  <5  10 2,4-Dinitrotoluene  <5  <5  10 2,6-Dinitrotoluene  <5  <5  10 Di-n-octyl Phthalate  <5  <5  10 1,2-Diphenylhydrazine  <5  <5  20 Fluoranthene    <5  <5  10 Fluorene    <5  <5  10 Hexachlorobenzene    <5  <5  10 Hexachlorobutadiene  <5  <5  10 Hexachlorocyclopentadiene  <5  <5  10 Hexachloroethane    <5  <5  20 Indeno(1,2,3-cd)pyrene    <5  <5  20 Isophorone    <5  <5  10 Naphthalene    <5  <5  10 Nitrobenzene    <5  <5  10 n-Nitrosodimethylamine  <5  <5  50 n-Nitrosodi-n-Propylamine  <5  <5  20 n-Nitrosodiphenylamine  <5  <5  20 Phenanthrene    <5  <5  10 Pyrene    <5  <5  10 1,2,4-Trichlorobenzene  <5  <5  10 PESTICIDES    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max
 
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 41  Aldrin    BA  BA  0.05 Alpha-BHC    BA  BA  0.05 Beta-BHC    BA  BA  0.05 Gamma-BHC [Lindane]  BA  BA  0.05 Delta-BHC    BA  BA  0.05 Chlordane    BA  BA  0.2 4,4'-DDT    BA  BA  0.1 4,4'-DDE [p,p-DDX]  BA  BA  0.1 4,4'-DDD [p,p-TDE]  BA  BA  0.1 Dieldrin    BA  BA  0.1 Alpha-Endosulfan    BA  BA  0.1 Beta-Endosulfan    BA  BA  0.1 Endosulfan Sulfate  BA  BA  0.1 Endrin    BA  BA  0.1 Endrin Aldehyde    BA  BA  0.1 Heptachlor    BA  BA  0.05 Heptachlor Epoxide    BA  BA  0.05 PCB-1242    BA  BA  1.0 PCB-1254    BA  BA  1.0 PCB-1221    BA  BA  1.0 PCB-1232    BA  BA  1.0 PCB-1248    BA  BA  1.0 PCB-1260    BA  BA  1.0 PCB-1016    BA  BA  1.0 Toxaphene    BA  BA  5.0  
 
BA - Believed Absent  
 
NA - Not Available  
 
Internal Outfall 801 A. Type of wastewater - the intermittent internal discharge of cooling tower blowdown and low volume wastewaters from Dry Cooling
 
Tower Sump #2 to Final Outfall 001 via the turbine condenser
 
cooling system. In addition to the wet cooling tower blowdown,
 
low volume wastewater from various sources as defined in 40 CFR
 
423 are discharged from this outfall. Low volume wastewater
 
sources contributing to this monitored flow include, but are not
 
limited to, wet cooling tower leakage, auxiliary component cooling
 
water, component cooling water, and stormwater. Previously
 
monitored effluent from the Yard Oil Separator System (Internal
 
Outfall 104) is infrequently discharged through this outfall as a
 
result of maintenance activities. Optional discharge to Final
 
Outfall 004 via the plant drainage ditches may occur during
 
periods when the circulating water system is unavailable.
 
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
 
LA0007374
 
Page 42  B. Location - at the point of discharge from Dry Cooling Tower Sump
#2 prior to combining with the waters of Final Outfall 001 or
 
Final Outfall 004 at Latitude 2959'44", Longitude 9028'13". C. Treatment - treatment of these wastewaters consists of:
- sedimentation


Internal Outfall 801  A. Type of wastewater - the intermittent internal discharge of cooling tower blowdown and low volume wastewaters from Dry Cooling Tower Sump #2 to Final Outfall 001 via the turbine condenser cooling system. In addition to the wet cooling tower blowdown, low volume wastewater from various sources as defined in 40 CFR 423 are discharged from this outfall. Low volume wastewater sources contributing to this monitored flow include, but are not limited to, wet cooling tower leakage, auxiliary component cooling water, component cooling water, and stormwater. Previously monitored effluent from the Yard Oil Separator System (Internal Outfall 104) is infrequently discharged through this outfall as a result of maintenance activities. Optional discharge to Final Outfall 004 via the plant drainage ditches may occur during periods when the circulating water system is unavailable.
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 42  B. Location - at the point of discharge from Dry Cooling Tower Sump #2 prior to combining with the waters of Final Outfall 001 or Final Outfall 004 at Latitude 2959'44", Longitude 9028'13". C. Treatment - treatment of these wastewaters consists of: - sedimentation
- neutralization/pH adjustment, when required  
- neutralization/pH adjustment, when required  
- side stream ionization, when required  
- side stream ionization, when required  
- filtration, when required D. Flow - Intermittent, (Max 30-Day) 0.01 MGD E. Receiving waters - Discharge to Outfall 001 or the optional discharge to Outfall 004 F. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA Form 2C) received on June 15, 1998. POLLUTANT    EFFLUENT     PART A    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand  <2.0  <2.0  ---
 
- filtration, when required D. Flow - Intermittent, (Max 30-Day) 0.01 MGD E. Receiving waters - Discharge to Outfall 001 or the optional discharge to Outfall 004 F. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA  
 
Form 2C) received on June 15, 1998.
POLLUTANT    EFFLUENT PART A    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand  <2.0  <2.0  ---
Chemical Oxygen Demand    26.0  26.0  ---
Chemical Oxygen Demand    26.0  26.0  ---
Total Organic Carbon    7.0  7.0  ---
Total Organic Carbon    7.0  7.0  ---
Total Suspended Solids  4.3  4.3  ---
Total Suspended Solids  4.3  4.3  ---
Ammonia (as N)    <0.1  <0.1  ---
Ammonia (as N)    <0.1  <0.1  ---
Temperature (Winter)  NA  NA  --- (Summer)  NA  NA  --- pH (Standard Units)  7.47  7.71  ---    (min)    (max) PART B    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Bromide    BA  BA  ---
Temperature (Winter)  NA  NA  --- (Summer)  NA  NA  --- pH (Standard Units)  7.47  7.71  ---    (min)    (max)
PART B    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Bromide    BA  BA  ---
Chlorine, Total Residual  BA  BA  ---
Chlorine, Total Residual  BA  BA  ---
Color (nM Units)    15.0  15.0  ---
Color (nM Units)    15.0  15.0  ---
Line 341: Line 963:
Organic Nitrogen, Total as (N) BA  BA  ---
Organic Nitrogen, Total as (N) BA  BA  ---
Oil and Grease    <1.0  <1.0  ---
Oil and Grease    <1.0  <1.0  ---
Phosphorous, Total as (P)  2.5  2.5  ---
Phosphorous, Total as (P)  2.5  2.5  ---  
 
Radioactivity:
Radioactivity:
Alpha, Total (pCi/L)  0.5  0.5  ---
Alpha, Total (pCi/L)  0.5  0.5  ---
Beta, Total (pCi/L)  11.0  11.0  ---
Beta, Total (pCi/L)  11.0  11.0  ---
Radium, Total (pCi/L)  BA  BA  ---
Radium, Total (pCi/L)  BA  BA  ---
Radium 226, Total (pCi/L)  BA  BA  ---
Radium 226, Total (pCi/L)  BA  BA  ---  
Sulfate (as SO4)    11.0  11.0  ---
 
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 43  Sulfide (as S)    BA  BA  ---
Sulfate (as SO
Sulfite (as SO3)    BA  BA  --- Surfactants    BA  BA  ---
: 4)    11.0  11.0  ---
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 43  Sulfide (as S)    BA  BA  ---  
 
Sulfite (as SO
: 3)    BA  BA  --- Surfactants    BA  BA  ---
Aluminum  (Total)    0.09  0.09  ---
Aluminum  (Total)    0.09  0.09  ---
Barium    (Total)    <0.02  <0.02  ---
Barium    (Total)    <0.02  <0.02  ---
Line 358: Line 989:
Manganese (Total)    BA  BA  ---
Manganese (Total)    BA  BA  ---
Tin      (Total)    BA  BA  ---
Tin      (Total)    BA  BA  ---
Titanium  (Total)    BA  BA  --- METALS, CYANIDE & TOTAL PHENOL(g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Antimony  (Total)    <50  <50  60 Arsenic  (Total)    <3  <3  10 Beryllium (Total)    <4  <4  5 Cadmium  (Total)    <1  <1  1 Chromium  (Total)    10  10  10 Chromium  (3+)    NA  NA  10 Chromium  (6+)    NA  NA  10 Copper    (Total)    20  20  10 Lead      (Total)    6  6  5 Mercury  (Total)    2.0  2.0  0.2 Molybdenum (Total)  <10  <10  30 Nickel    (Total) Freshwater  <40  <40  40 Nickel    (Total) Marine  NA  NA  5 Selenium  (Total)    <5  <5  5 Silver    (Total)    <0.5  <0.5  2 Thallium  (Total)    <5  <5  10 Zinc      (Total)    1,720  1,720  20 Cyanide  (Total)    <10  <10  10 Phenolics, Total Recoverable (4AAP)  <10  <10  5 DIOXIN    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD    BA  BA  0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acrolein    BA  BA  50 Acrylonitrile    BA  BA  50 Benzene    <5  <5  10 Bis(Chloromethyl)Ether  BA  BA  10 Bromoform    <5  <5  10 Carbon Tetrachloride  <5  <5  10 Chlorobenzene    <5  <5  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 44  Chlorodibromomethane  <5  <5  10 Chloroethane    <10  <10  50 2-Chloroethylvinylether  <5  <5  10 Chloroform    <5  <5  10 Dichlorobromomethane  <5  <5  10 Dichlorodifluoromethane  <10  <10  10 1,1-Dichloroethane  <5  <5  10 1,2-Dichloroethane  <5  <5  10 1,1-Dichloroethylene  <5  <5  10 1,2-Dichloropropane  <5  <5  10 1,3-Dichloropropylene  <5  <5  10 Ethylbenzene    <5  <5  10 Methyl Bromide [Bromomethane]  <10  <10  50 Methyl Chloride [Chloromethane] <10  <10  50 Methylene Chloride  <5  <5  20 1,1,2,2-Tetrachloroethane  <5  <5  10 Tetrachloroethylene  <5  <5  10 Toluene    <5  <5  10 1,2-trans-Dichloroethylene  BA  BA  10 1,1,1-Trichloroethane  <5  <5  10 1,1,2-Trichloroethane  <5  <5  10 Trichloroethylene    <5  <5  10 Trichlorofluoromethane  <10  <10  10 Vinyl Chloride    <10  <10  10 ACID COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol    <5  <5  10 2,4-Dichlorophenol  <5  <5  10 2,4-Dimethylphenol  <5  <5  10 4,6-Dinitro-o-Cresol  <50  <50  50 2,4-Dinitrophenol    <50  <50  50 2-Nitrophenol    <5  <5  20 4-Nitrophenol    <50  <50  50 p-Chloro-m-Cresol    <5  <5  10 Pentachlorophenol    <50  <50  50 Phenol    <5  <5  10 2,4,6-Trichlorophenol  <5  <5  10 BASE/NEUTRAL COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acenaphthene    <5  <5  10 Acenaphthylene    <5  <5  10 Anthracene    <5  <5  10 Benzidine    <50  <50  50 Benzo(a)anthracene  <5  <5  10 Benzo(a)pyrene    <5  <5  10 3,4-Benzofluoranthene  <5  <5  10 Benzo(ghi)perylene  <5  <5  20 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 45  Benzo(k)fluoranthene  <5  <5  10 Bis(2-chloroethoxy) Methane  <5  <5  10 Bis(2-chloroethyl) Ether  <5  <5  10 Bis(2-chloroisopropyl) Ether  <5  <5  10 Bis(2-ethylhexyl) Phthalate  <5  <5  10 4-Bromophenyl Phenyl Ether  <5  <5  10 Butylbenzyl Phthalate  <5  <5  10 2-Chloronaphthalene  <5  <5  10 4-Chlorophenyl Phenyl Ether  <5  <5  10 Chrysene    <5  <5  10 Dibenzo(a,h)anthracene  <5  <5  20 1,2-Dichlorobenzene  <5  <5  10 1,3-Dichlorobenzene  <5  <5  10 1,4-Dichlorobenzene  <5  <5  10 3,3'-Dichlorobenzidine  <5  <5  50 Diethyl Phthalate    <5  <5  10 Dimethyl Phthalate  <5  <5  10 Di-n-Butyl Phthalate  <5  <5  10 2,4-Dinitrotoluene  <5  <5  10 2,6-Dinitrotoluene  <5  <5  10 Di-n-octyl Phthalate  <5  <5  10 1,2-Diphenylhydrazine  <5  <5  20 Fluoranthene    <5  <5  10 Fluorene    <5  <5  10 Hexachlorobenzene    <5  <5  10 Hexachlorobutadiene  <5  <5  10 Hexachlorocyclopentadiene  <5  <5  10 Hexachloroethane    <5  <5  20 Indeno(1,2,3-cd)pyrene    <5  <5  20 Isophorone    <5  <5  10 Naphthalene    <5  <5  10 Nitrobenzene    <5  <5  10 n-Nitrosodimethylamine  <5  <5  50 n-Nitrosodi-n-Propylamine  <5  <5  20 n-Nitrosodiphenylamine  <5  <5  20 Phenanthrene    <5  <5  10 Pyrene    <5  <5  10 1,2,4-Trichlorobenzene  <5  <5  10 PESTICIDES    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Aldrin    BA  BA  0.05 Alpha-BHC    BA  BA  0.05 Beta-BHC    BA  BA  0.05 Gamma-BHC [Lindane]  BA  BA  0.05 Delta-BHC    BA  BA  0.05 Chlordane    BA  BA  0.2 4,4'-DDT    BA  BA  0.1 4,4'-DDE [p,p-DDX]  BA  BA  0.1 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 46  4,4'-DDD [p,p-TDE]  BA  BA  0.1 Dieldrin    BA  BA  0.1 Alpha-Endosulfan    BA  BA  0.1 Beta-Endosulfan    BA  BA  0.1 Endosulfan Sulfate  BA  BA  0.1 Endrin    BA  BA  0.1 Endrin Aldehyde    BA  BA  0.1 Heptachlor    BA  BA  0.05 Heptachlor Epoxide    BA  BA  0.05 PCB-1242    BA  BA  1.0 PCB-1254    BA  BA  1.0 PCB-1221    BA  BA  1.0 PCB-1232    BA  BA  1.0 PCB-1248    BA  BA  1.0 PCB-1260    BA  BA  1.0 PCB-1016    BA  BA  1.0 Toxaphene    BA  BA  5.0 BA - Believed Absent NA - Not Available  
Titanium  (Total)    BA  BA  ---
METALS, CYANIDE & TOTAL PHENOL (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Antimony  (Total)    <50  <50  60 Arsenic  (Total)    <3  <3  10 Beryllium (Total)    <4  <4  5 Cadmium  (Total)    <1  <1  1 Chromium  (Total)    10  10  10 Chromium  (3+)    NA  NA  10 Chromium  (6+)    NA  NA  10 Copper    (Total)    20  20  10 Lead      (Total)    6  6  5 Mercury  (Total)    2.0  2.0  0.2 Molybdenum (Total)  <10  <10  30 Nickel    (Total) Freshwater  <40  <40  40 Nickel    (Total) Marine  NA  NA  5 Selenium  (Total)    <5  <5  5 Silver    (Total)    <0.5  <0.5  2 Thallium  (Total)    <5  <5  10 Zinc      (Total)    1,720  1,720  20 Cyanide  (Total)    <10  <10  10  
 
Phenolics, Total Recoverable (4AAP)  <10  <10  5 DIOXIN    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD    BA  BA  0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acrolein    BA  BA  50 Acrylonitrile    BA  BA  50 Benzene    <5  <5  10 Bis(Chloromethyl)Ether  BA  BA  10 Bromoform    <5  <5  10 Carbon Tetrachloride  <5  <5  10 Chlorobenzene    <5  <5  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 44  Chlorodibromomethane  <5  <5  10 Chloroethane    <10  <10  50 2-Chloroethylvinylether  <5  <5  10 Chloroform    <5  <5  10 Dichlorobromomethane  <5  <5  10 Dichlorodifluoromethane  <10  <10  10 1,1-Dichloroethane  <5  <5  10 1,2-Dichloroethane  <5  <5  10 1,1-Dichloroethylene  <5  <5  10 1,2-Dichloropropane  <5  <5  10 1,3-Dichloropropylene  <5  <5  10 Ethylbenzene    <5  <5  10 Methyl Bromide [Bromomethane]  <10  <10  50 Methyl Chloride [Chloromethane] <10  <10  50 Methylene Chloride  <5  <5  20 1,1,2,2-Tetrachloroethane  <5  <5  10 Tetrachloroethylene  <5  <5  10 Toluene    <5  <5  10 1,2-trans-Dichloroethylene  BA  BA  10 1,1,1-Trichloroethane  <5  <5  10 1,1,2-Trichloroethane  <5  <5  10 Trichloroethylene    <5  <5  10 Trichlorofluoromethane  <10  <10  10 Vinyl Chloride    <10  <10  10 ACID COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol    <5  <5  10 2,4-Dichlorophenol  <5  <5  10 2,4-Dimethylphenol  <5  <5  10 4,6-Dinitro-o-Cresol  <50  <50  50 2,4-Dinitrophenol    <50  <50  50 2-Nitrophenol    <5  <5  20 4-Nitrophenol    <50  <50  50 p-Chloro-m-Cresol    <5  <5  10 Pentachlorophenol    <50  <50  50 Phenol    <5  <5  10 2,4,6-Trichlorophenol  <5  <5  10 BASE/NEUTRAL COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acenaphthene    <5  <5  10 Acenaphthylene    <5  <5  10 Anthracene    <5  <5  10 Benzidine    <50  <50  50 Benzo(a)anthracene  <5  <5  10 Benzo(a)pyrene    <5  <5  10 3,4-Benzofluoranthene  <5  <5  10 Benzo(ghi)perylene  <5  <5  20 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 45  Benzo(k)fluoranthene  <5  <5  10 Bis(2-chloroethoxy) Methane  <5  <5  10 Bis(2-chloroethyl) Ether  <5  <5  10 Bis(2-chloroisopropyl) Ether  <5  <5  10 Bis(2-ethylhexyl) Phthalate  <5  <5  10 4-Bromophenyl Phenyl Ether  <5  <5  10 Butylbenzyl Phthalate  <5  <5  10 2-Chloronaphthalene  <5  <5  10 4-Chlorophenyl Phenyl Ether  <5  <5  10 Chrysene    <5  <5  10 Dibenzo(a,h)anthracene  <5  <5  20 1,2-Dichlorobenzene  <5  <5  10 1,3-Dichlorobenzene  <5  <5  10 1,4-Dichlorobenzene  <5  <5  10 3,3'-Dichlorobenzidine  <5  <5  50 Diethyl Phthalate    <5  <5  10 Dimethyl Phthalate  <5  <5  10 Di-n-Butyl Phthalate  <5  <5  10 2,4-Dinitrotoluene  <5  <5  10 2,6-Dinitrotoluene  <5  <5  10 Di-n-octyl Phthalate  <5  <5  10 1,2-Diphenylhydrazine  <5  <5  20 Fluoranthene    <5  <5  10 Fluorene    <5  <5  10 Hexachlorobenzene    <5  <5  10 Hexachlorobutadiene  <5  <5  10 Hexachlorocyclopentadiene  <5  <5  10 Hexachloroethane    <5  <5  20 Indeno(1,2,3-cd)pyrene    <5  <5  20 Isophorone    <5  <5  10 Naphthalene    <5  <5  10 Nitrobenzene    <5  <5  10 n-Nitrosodimethylamine  <5  <5  50 n-Nitrosodi-n-Propylamine  <5  <5  20 n-Nitrosodiphenylamine  <5  <5  20 Phenanthrene    <5  <5  10 Pyrene    <5  <5  10 1,2,4-Trichlorobenzene  <5  <5  10 PESTICIDES    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Aldrin    BA  BA  0.05 Alpha-BHC    BA  BA  0.05 Beta-BHC    BA  BA  0.05 Gamma-BHC [Lindane]  BA  BA  0.05 Delta-BHC    BA  BA  0.05 Chlordane    BA  BA  0.2 4,4'-DDT    BA  BA  0.1 4,4'-DDE [p,p-DDX]  BA  BA  0.1 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 46  4,4'-DDD [p,p-TDE]  BA  BA  0.1 Dieldrin    BA  BA  0.1 Alpha-Endosulfan    BA  BA  0.1 Beta-Endosulfan    BA  BA  0.1 Endosulfan Sulfate  BA  BA  0.1 Endrin    BA  BA  0.1 Endrin Aldehyde    BA  BA  0.1 Heptachlor    BA  BA  0.05 Heptachlor Epoxide    BA  BA  0.05 PCB-1242    BA  BA  1.0 PCB-1254    BA  BA  1.0 PCB-1221    BA  BA  1.0 PCB-1232    BA  BA  1.0 PCB-1248    BA  BA  1.0 PCB-1260    BA  BA  1.0 PCB-1016    BA  BA  1.0 Toxaphene    BA  BA  5.0  
 
BA - Believed Absent  
 
NA - Not Available  
 
Internal Outfall 901 A. Type of wastewater - the intermittent internal discharge of metal cleaning wastewaters from internal components of plant equipment
 
to Final Outfall 001 via the turbine condenser cooling system. 
 
Metal cleaning wastewaters (both chemical and non-chemical) result
 
from the cleaning washes/rinses of various plant equipment
 
components including, but not limited to, the steam generator, the
 
cooling water heat exchangers, and piping.
 
B. Location - at the point of discharge from the mobile cleaning process unit(s) prior to combining with the waters of Final
 
Outfall 001 at Latitude 2959'47", Longitude 9028'8". C. Treatment - treatment of these wastewaters consists of:
- chemical precipitation


Internal Outfall 901  A. Type of wastewater - the intermittent internal discharge of metal cleaning wastewaters from internal components of plant equipment to Final Outfall 001 via the turbine condenser cooling system.
Metal cleaning wastewaters (both chemical and non-chemical) result from the cleaning washes/rinses of various plant equipment components including, but not limited to, the steam generator, the cooling water heat exchangers, and piping.
B. Location - at the point of discharge from the mobile cleaning process unit(s) prior to combining with the waters of Final Outfall 001 at Latitude 2959'47", Longitude 9028'8". C. Treatment - treatment of these wastewaters consists of: - chemical precipitation
- neutralization  
- neutralization  
- sedimentation  
- sedimentation  
- pre-aeration, when required  
- pre-aeration, when required  
- flocculation, when required  
- flocculation, when required  
- ion exchange, when required D. Flow - Intermittent, (Max 30-Day) 0.36 MGD E. Receiving waters - Discharge to Outfall 001 F. Effluent Data - not available, new outfall Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 47  Outfall 004 A. Type of wastewater - the intermittent discharge from the plant drainage ditch system to 40 Arpent Canal. Outfall 004 is a new outfall that consolidates Outfalls 04A and 04B from former NPDES Permit LA0007374. Most of the effluent monitored at this outfall is 85% stormwater runoff. Besides stormwater, potable water from the fire water system, maintenance wastewaters including, but not limited to:  hydrostatic test water, air conditioning condensate, low volume wastewaters from various sources as defined in 40 CFR 423, and previously monitored effluents exit the facility via Outfall 004. Low volume sources contributing wastewater to this outfall include, but are not limited to, reverse osmosis reject water and demineralized water. The plant drainage ditch system receives treated discharge from the yard oil separator system (Internal Outfall 104), untreated vehicle wash wastewater (Internal Outfall 204), and during maintenance activities discharges from Dry Cooling Tower Sump #1 (Internal Outfall 701) and Dry Cooling Tower Sump #2 (Internal Outfall 801).
 
B. Location - at the point of discharge from the plant drainage ditch system where the plant stormwater runoff, the previously monitored effluents, and other infrequently discharged low volume wastewaters discharge at Latitude 2959'19", Longitude 9028'25" prior to entering 40 Arpent Canal. C. Treatment - none. D. Flow - Intermittent, (Max 30-Day) 0.784 MGD E. Receiving waters - 40 Arpent Canal thence to Lac Des Allemands   F. Basin and segment - Barataria Basin, Segment 020202 G. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA Form 2C) received on June 15, 1998. POLLUTANT    EFFLUENT     PART A    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand  <2.0  <2.0  ---
- ion exchange, when required  
 
D. Flow - Intermittent, (Max 30-Day) 0.36 MGD E. Receiving waters - Discharge to Outfall 001 F. Effluent Data - not available, new outfall  
 
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 47  Outfall 004 A. Type of wastewater - the intermittent discharge from the plant drainage ditch system to 40 Arpent Canal. Outfall 004 is a new  
 
outfall that consolidates Outfalls 04A and 04B from former NPDES  
 
Permit LA0007374. Most of the effluent monitored at this outfall  
 
is 85% stormwater runoff. Besides stormwater, potable water from  
 
the fire water system, maintenance wastewaters including, but not  
 
limited to:  hydrostatic test water, air conditioning condensate,  
 
low volume wastewaters from various sources as defined in 40 CFR  
 
423, and previously monitored effluents exit the facility via  
 
Outfall 004. Low volume sources contributing wastewater to this  
 
outfall include, but are not limited to, reverse osmosis reject  
 
water and demineralized water. The plant drainage ditch system  
 
receives treated discharge from the yard oil separator system  
 
(Internal Outfall 104), untreated vehicle wash wastewater  
 
(Internal Outfall 204), and during maintenance activities  
 
discharges from Dry Cooling Tower Sump #1 (Internal Outfall 701)  
 
and Dry Cooling Tower Sump #2 (Internal Outfall 801).  
 
B. Location - at the point of discharge from the plant drainage ditch system where the plant stormwater runoff, the previously monitored  
 
effluents, and other infrequently discharged low volume  
 
wastewaters discharge at Latitude 2959'19", Longitude 9028'25" prior to entering 40 Arpent Canal.
C. Treatment - none.
D. Flow - Intermittent, (Max 30-Day) 0.784 MGD  
 
E. Receiving waters - 40 Arpent Canal thence to Lac Des Allemands F. Basin and segment - Barataria Basin, Segment 020202 G. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA  
 
Form 2C) received on June 15, 1998.
POLLUTANT    EFFLUENT PART A    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand  <2.0  <2.0  ---
Chemical Oxygen Demand    <5.0  <5.0  ---
Chemical Oxygen Demand    <5.0  <5.0  ---
Total Organic Carbon    3.7  3.7  ---
Total Organic Carbon    3.7  3.7  ---
Line 374: Line 1,092:
Ammonia (as N)    0.230  0.230  ---
Ammonia (as N)    0.230  0.230  ---
Temperature (Winter)  NA  NA  ---
Temperature (Winter)  NA  NA  ---
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 48  (Summer)  NA  NA  --- pH (Standard Units)  6.88  8.30  ---    (min)    (max) PART B    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Bromide    BA  BA  ---
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 48  (Summer)  NA  NA  --- pH (Standard Units)  6.88  8.30  ---    (min)    (max)
PART B    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Bromide    BA  BA  ---
Chlorine, Total Residual  BA  BA  ---
Chlorine, Total Residual  BA  BA  ---
Color (nM Units)    15.0  15.0  ---
Color (nM Units)    15.0  15.0  ---
Line 382: Line 1,105:
Organic Nitrogen, Total as (N) BA  BA  ---
Organic Nitrogen, Total as (N) BA  BA  ---
Oil and Grease    <5.9  <5.9  ---
Oil and Grease    <5.9  <5.9  ---
Phosphorous, Total as (P)  0.186  0.186  ---
Phosphorous, Total as (P)  0.186  0.186  ---  
 
Radioactivity:
Radioactivity:
Alpha, Total (pCi/L)  NA  NA  ---
Alpha, Total (pCi/L)  NA  NA  ---
Beta, Total (pCi/L)  NA  NA  ---
Beta, Total (pCi/L)  NA  NA  ---
Radium, Total (pCi/L)  BA  BA  ---
Radium, Total (pCi/L)  BA  BA  ---
Radium 226, Total (pCi/L)  BA  BA  ---
Radium 226, Total (pCi/L)  BA  BA  ---  
Sulfate (as SO4)    38.7  38.7  --- Sulfide (as S)    <1.0  <1.0  ---
 
Sulfite (as SO3)    <2.0  <2.0  --- Surfactants    <0.04  <0.04  ---
Sulfate (as SO
: 4)    38.7  38.7  --- Sulfide (as S)    <1.0  <1.0  ---  
 
Sulfite (as SO
: 3)    <2.0  <2.0  --- Surfactants    <0.04  <0.04  ---
Aluminum  (Total)    0.415  0.415  ---
Aluminum  (Total)    0.415  0.415  ---
Barium    (Total)    <0.2  <0.2  ---
Barium    (Total)    <0.2  <0.2  ---
Line 398: Line 1,126:
Manganese (Total)    BA  BA  ---
Manganese (Total)    BA  BA  ---
Tin      (Total)    BA  BA  ---
Tin      (Total)    BA  BA  ---
Titanium  (Total)    BA  BA  --- METALS, CYANIDE & TOTAL PHENOL(g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Antimony  (Total)    BA  BA  60 Arsenic  (Total)    BA  BA  10 Beryllium (Total)    <5  <5  5 Cadmium  (Total)    BA  BA  1 Chromium  (Total)    <10  <10  10 Chromium  (3+)    NA  NA  10 Chromium  (6+)    NA  NA  10 Copper    (Total)    <10  <10  10 Lead      (Total)    BA  BA  5 Mercury  (Total)    <0.2  <0.2  0.2 Molybdenum (Total)  <10  <10  30 Nickel    (Total) Freshwater  <40  <40  40 Nickel    (Total) Marine  NA  NA  5 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 49  Selenium  (Total)    BA  BA  5 Silver    (Total)    BA  BA  2 Thallium  (Total)    BA  BA  10 Zinc      (Total)    39.2  39.2  20 Cyanide  (Total)    <10  <10  10 Phenolics, Total Recoverable (4AAP)  <50  <50  5 DIOXIN    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD    BA  BA  0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acrolein    <10  <10  50 Acrylonitrile    <10  <10  50 Benzene    <5  <5  10 Bis(Chloromethyl)Ether  BA  BA  10 Bromoform    <5  <5  10 Carbon Tetrachloride  <5  <5  10 Chlorobenzene    <5  <5  10 Chlorodibromomethane  <5  <5  10 Chloroethane    <10  <10  50 2-Chloroethylvinylether  <5  <5  10 Chloroform    <5  <5  10 Dichlorobromomethane  <5  <5  10 Dichlorodifluoromethane  BA  BA  10 1,1-Dichloroethane  <5  <5  10 1,2-Dichloroethane  <5  <5  10 1,1-Dichloroethylene  <5  <5  10 1,2-Dichloropropane  <5  <5  10 1,3-Dichloropropylene  <5  <5  10 Ethylbenzene    <5  <5  10 Methyl Bromide [Bromomethane]  <10  <10  50 Methyl Chloride [Chloromethane] <10  <10  50 Methylene Chloride  <5  <5  20 1,1,2,2-Tetrachloroethane  <5  <5  10 Tetrachloroethylene  <5  <5  10 Toluene    <5  <5  10 1,2-trans-Dichloroethylene  BA  BA  10 1,1,1-Trichloroethane  <5  <5  10 1,1,2-Trichloroethane  <5  <5  10 Trichloroethylene    <5  <5  10 Trichlorofluoromethane  BA  BA  10 Vinyl Chloride    <10  <10  10 ACID COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol    <10  <10  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 50  2,4-Dichlorophenol  <10  <10  10 2,4-Dimethylphenol  <10  <10  10 4,6-Dinitro-o-Cresol  <25  <25  50 2,4-Dinitrophenol    <25  <25  50 2-Nitrophenol    <10  <10  20 4-Nitrophenol    <25  <25  50 p-Chloro-m-Cresol    <10  <10  10 Pentachlorophenol    <25  <25  50 Phenol    <10  <10  10 2,4,6-Trichlorophenol  <10  <10  10 BASE/NEUTRAL COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acenaphthene    <10  <10  10 Acenaphthylene    <10  <10  10 Anthracene    <10  <10  10 Benzidine    <30  <30  50 Benzo(a)anthracene  <10  <10  10 Benzo(a)pyrene    <10  <10  10 3,4-Benzofluoranthene  <10  <10  10 Benzo(ghi)perylene  <10  <10  20 Benzo(k)fluoranthene  <10  <10  10 Bis(2-chloroethoxy) Methane  <10  <10  10 Bis(2-chloroethyl) Ether  <10  <10  10 Bis(2-chloroisopropyl) Ether  <10  <10  10 Bis(2-ethylhexyl) Phthalate  <10  <10  10 4-Bromophenyl Phenyl Ether  <10  <10  10 Butylbenzyl Phthalate  <10  <10  10 2-Chloronaphthalene  <10  <10  10 4-Chlorophenyl Phenyl Ether  <10  <10  10 Chrysene    <10  <10  10 Dibenzo(a,h)anthracene  <10  <10  20 1,2-Dichlorobenzene  <10  <10  10 1,3-Dichlorobenzene  <10  <10  10 1,4-Dichlorobenzene  <10  <10  10 3,3'-Dichlorobenzidine  <20  <20  50 Diethyl Phthalate    <10  <10  10 Dimethyl Phthalate  <10  <10  10 Di-n-Butyl Phthalate  <10  <10  10 2,4-Dinitrotoluene  <10  <10  10 2,6-Dinitrotoluene  <10  <10  10 Di-n-octyl Phthalate  <10  <10  10 1,2-Diphenylhydrazine  <10  <10  20 Fluoranthene    <10  <10  10 Fluorene    <10  <10  10 Hexachlorobenzene    <10  <10  10 Hexachlorobutadiene  <10  <10  10 Hexachlorocyclopentadiene  <10  <10  10 Hexachloroethane    <10  <10  20 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 51  Indeno(1,2,3-cd)pyrene    <10  <10  20 Isophorone    <10  <10  10 Naphthalene    <10  <10  10 Nitrobenzene    <10  <10  10 n-Nitrosodimethylamine  <10  <10  50 n-Nitrosodi-n-Propylamine  <10  <10  20 n-Nitrosodiphenylamine  <10  <10  20 Phenanthrene    <10  <10  10 Pyrene    <10  <10  10 1,2,4-Trichlorobenzene  <10  <10  10 PESTICIDES    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Aldrin    BA  BA  0.05 Alpha-BHC    BA  BA  0.05 Beta-BHC    BA  BA  0.05 Gamma-BHC [Lindane]  BA  BA  0.05 Delta-BHC    BA  BA  0.05 Chlordane    BA  BA  0.2 4,4'-DDT    BA  BA  0.1 4,4'-DDE [p,p-DDX]  BA  BA  0.1 4,4'-DDD [p,p-TDE]  BA  BA  0.1 Dieldrin    BA  BA  0.1 Alpha-Endosulfan    BA  BA  0.1 Beta-Endosulfan    BA  BA  0.1 Endosulfan Sulfate  BA  BA  0.1 Endrin    BA  BA  0.1 Endrin Aldehyde    BA  BA  0.1 Heptachlor    BA  BA  0.05 Heptachlor Epoxide    BA  BA  0.05 PCB-1242    BA  BA  1.0 PCB-1254    BA  BA  1.0 PCB-1221    BA  BA  1.0 PCB-1232    BA  BA  1.0 PCB-1248    BA  BA  1.0 PCB-1260    BA  BA  1.0 PCB-1016    BA  BA  1.0 Toxaphene    BA  BA  5.0 BA - Believed Absent NA - Not Available  
Titanium  (Total)    BA  BA  ---
METALS, CYANIDE & TOTAL PHENOL (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Antimony  (Total)    BA  BA  60 Arsenic  (Total)    BA  BA  10 Beryllium (Total)    <5  <5  5 Cadmium  (Total)    BA  BA  1 Chromium  (Total)    <10  <10  10 Chromium  (3+)    NA  NA  10 Chromium  (6+)    NA  NA  10 Copper    (Total)    <10  <10  10 Lead      (Total)    BA  BA  5 Mercury  (Total)    <0.2  <0.2  0.2 Molybdenum (Total)  <10  <10  30 Nickel    (Total) Freshwater  <40  <40  40 Nickel    (Total) Marine  NA  NA  5 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 49  Selenium  (Total)    BA  BA  5 Silver    (Total)    BA  BA  2 Thallium  (Total)    BA  BA  10 Zinc      (Total)    39.2  39.2  20 Cyanide  (Total)    <10  <10  10  
 
Phenolics, Total Recoverable (4AAP)  <50  <50  5 DIOXIN    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD    BA  BA  0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acrolein    <10  <10  50 Acrylonitrile    <10  <10  50 Benzene    <5  <5  10 Bis(Chloromethyl)Ether  BA  BA  10 Bromoform    <5  <5  10 Carbon Tetrachloride  <5  <5  10 Chlorobenzene    <5  <5  10 Chlorodibromomethane  <5  <5  10 Chloroethane    <10  <10  50 2-Chloroethylvinylether  <5  <5  10 Chloroform    <5  <5  10 Dichlorobromomethane  <5  <5  10 Dichlorodifluoromethane  BA  BA  10 1,1-Dichloroethane  <5  <5  10 1,2-Dichloroethane  <5  <5  10 1,1-Dichloroethylene  <5  <5  10 1,2-Dichloropropane  <5  <5  10 1,3-Dichloropropylene  <5  <5  10 Ethylbenzene    <5  <5  10 Methyl Bromide [Bromomethane]  <10  <10  50 Methyl Chloride [Chloromethane] <10  <10  50 Methylene Chloride  <5  <5  20 1,1,2,2-Tetrachloroethane  <5  <5  10 Tetrachloroethylene  <5  <5  10 Toluene    <5  <5  10 1,2-trans-Dichloroethylene  BA  BA  10 1,1,1-Trichloroethane  <5  <5  10 1,1,2-Trichloroethane  <5  <5  10 Trichloroethylene    <5  <5  10 Trichlorofluoromethane  BA  BA  10 Vinyl Chloride    <10  <10  10 ACID COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol    <10  <10  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 50  2,4-Dichlorophenol  <10  <10  10 2,4-Dimethylphenol  <10  <10  10 4,6-Dinitro-o-Cresol  <25  <25  50 2,4-Dinitrophenol    <25  <25  50 2-Nitrophenol    <10  <10  20 4-Nitrophenol    <25  <25  50 p-Chloro-m-Cresol    <10  <10  10 Pentachlorophenol    <25  <25  50 Phenol    <10  <10  10 2,4,6-Trichlorophenol  <10  <10  10 BASE/NEUTRAL COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acenaphthene    <10  <10  10 Acenaphthylene    <10  <10  10 Anthracene    <10  <10  10 Benzidine    <30  <30  50 Benzo(a)anthracene  <10  <10  10 Benzo(a)pyrene    <10  <10  10 3,4-Benzofluoranthene  <10  <10  10 Benzo(ghi)perylene  <10  <10  20 Benzo(k)fluoranthene  <10  <10  10 Bis(2-chloroethoxy) Methane  <10  <10  10 Bis(2-chloroethyl) Ether  <10  <10  10 Bis(2-chloroisopropyl) Ether  <10  <10  10 Bis(2-ethylhexyl) Phthalate  <10  <10  10 4-Bromophenyl Phenyl Ether  <10  <10  10 Butylbenzyl Phthalate  <10  <10  10 2-Chloronaphthalene  <10  <10  10 4-Chlorophenyl Phenyl Ether  <10  <10  10 Chrysene    <10  <10  10 Dibenzo(a,h)anthracene  <10  <10  20 1,2-Dichlorobenzene  <10  <10  10 1,3-Dichlorobenzene  <10  <10  10 1,4-Dichlorobenzene  <10  <10  10 3,3'-Dichlorobenzidine  <20  <20  50 Diethyl Phthalate    <10  <10  10 Dimethyl Phthalate  <10  <10  10 Di-n-Butyl Phthalate  <10  <10  10 2,4-Dinitrotoluene  <10  <10  10 2,6-Dinitrotoluene  <10  <10  10 Di-n-octyl Phthalate  <10  <10  10 1,2-Diphenylhydrazine  <10  <10  20 Fluoranthene    <10  <10  10 Fluorene    <10  <10  10 Hexachlorobenzene    <10  <10  10 Hexachlorobutadiene  <10  <10  10 Hexachlorocyclopentadiene  <10  <10  10 Hexachloroethane    <10  <10  20 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 51  Indeno(1,2,3-cd)pyrene    <10  <10  20 Isophorone    <10  <10  10 Naphthalene    <10  <10  10 Nitrobenzene    <10  <10  10 n-Nitrosodimethylamine  <10  <10  50 n-Nitrosodi-n-Propylamine  <10  <10  20 n-Nitrosodiphenylamine  <10  <10  20 Phenanthrene    <10  <10  10 Pyrene    <10  <10  10 1,2,4-Trichlorobenzene  <10  <10  10 PESTICIDES    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Aldrin    BA  BA  0.05 Alpha-BHC    BA  BA  0.05 Beta-BHC    BA  BA  0.05 Gamma-BHC [Lindane]  BA  BA  0.05 Delta-BHC    BA  BA  0.05 Chlordane    BA  BA  0.2 4,4'-DDT    BA  BA  0.1 4,4'-DDE [p,p-DDX]  BA  BA  0.1 4,4'-DDD [p,p-TDE]  BA  BA  0.1 Dieldrin    BA  BA  0.1 Alpha-Endosulfan    BA  BA  0.1 Beta-Endosulfan    BA  BA  0.1 Endosulfan Sulfate  BA  BA  0.1 Endrin    BA  BA  0.1 Endrin Aldehyde    BA  BA  0.1 Heptachlor    BA  BA  0.05 Heptachlor Epoxide    BA  BA  0.05 PCB-1242    BA  BA  1.0 PCB-1254    BA  BA  1.0 PCB-1221    BA  BA  1.0 PCB-1232    BA  BA  1.0 PCB-1248    BA  BA  1.0 PCB-1260    BA  BA  1.0 PCB-1016    BA  BA  1.0 Toxaphene    BA  BA  5.0  
 
BA - Believed Absent  
 
NA - Not Available  
 
Internal Outfall 104 (Former 002)
A. Type of wastewater - the intermittent internal discharge from the yard oil separator system to Final Outfall 004 via a plant
 
drainage ditch. Wastewater sources contributing to the flow
 
monitored at Outfall 104 include auxiliary boiler blowdown,
 
stormwater, and low volume wastewaters from various sources as Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
 
LA0007374
 
Page 52  defined by 40 CFR 423. Low volume sources contributing wastewater
 
to this outfall include, but are not limited to, secondary water
 
system drains, system leakage, auxiliary boiler sumps, turbine
 
building equipment and floor drains, turbine building floor wash
 
downs, and laboratory drains. Optional discharge to Internal
 
Outfall 701 or 801 may occur during maintenance periods.
 
B. Location - at the point of discharge from the yard oil separator system prior to combining with the waters of Final Outfall 004 or
 
Internal Outfall 701 or Internal Outfall 801 at
 
Latitude 2959'37", Longitude 9028'15". C. Treatment - treatment of these wastewaters consists of:
- sedimentation


Internal Outfall 104 (Former 002)  A. Type of wastewater - the intermittent internal discharge from the yard oil separator system to Final Outfall 004 via a plant drainage ditch. Wastewater sources contributing to the flow monitored at Outfall 104 include auxiliary boiler blowdown, stormwater, and low volume wastewaters from various sources as Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 52  defined by 40 CFR 423. Low volume sources contributing wastewater to this outfall include, but are not limited to, secondary water system drains, system leakage, auxiliary boiler sumps, turbine building equipment and floor drains, turbine building floor wash downs, and laboratory drains. Optional discharge to Internal Outfall 701 or 801 may occur during maintenance periods.
B. Location - at the point of discharge from the yard oil separator system prior to combining with the waters of Final Outfall 004 or Internal Outfall 701 or Internal Outfall 801 at Latitude 2959'37", Longitude 9028'15". C. Treatment - treatment of these wastewaters consists of: - sedimentation
- flotation  
- flotation  
- oil/water separation  
- oil/water separation  
- polymer injection, when required  
- polymer injection, when required  
- neutralization/pH adjustment, when required  
- neutralization/pH adjustment, when required  
- flocculation, when required  
- flocculation, when required  
- filtration, when required D. Flow - Intermittent, (Max 30-Day) 0.0221 MGD E. Receiving waters - Discharge to Outfall 004, with option to discharge to either Internal Outfall 701, or Internal Outfall 801 during maintenance activities. F. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA Form 2C) received on June 15, 1998. POLLUTANT    EFFLUENT     PART A    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand  <2.0  <2.0  ---
 
- filtration, when required D. Flow - Intermittent, (Max 30-Day) 0.0221 MGD E. Receiving waters - Discharge to Outfall 004, with option to discharge to either Internal Outfall 701, or Internal Outfall 801  
 
during maintenance activities.
F. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA  
 
Form 2C) received on June 15, 1998.
POLLUTANT    EFFLUENT PART A    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand  <2.0  <2.0  ---
Chemical Oxygen Demand    9.1  9.1  ---
Chemical Oxygen Demand    9.1  9.1  ---
Total Organic Carbon    3.0  3.0  ---
Total Organic Carbon    3.0  3.0  ---
Total Suspended Solids  23.9  29.6  ---
Total Suspended Solids  23.9  29.6  ---
Ammonia (as N)    0.197  0.197  ---
Ammonia (as N)    0.197  0.197  ---
Temperature (Winter)  NA  NA  --- (Summer)  NA  NA  --- pH (Standard Units)  6.62  8.24  ---    (min)    (max) PART B    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Bromide    BA  BA  ---
Temperature (Winter)  NA  NA  --- (Summer)  NA  NA  --- pH (Standard Units)  6.62  8.24  ---    (min)    (max)
PART B    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Bromide    BA  BA  ---
Chlorine, Total Residual  BA  BA  ---
Chlorine, Total Residual  BA  BA  ---
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 53  Color (nM Units)    10  10  ---
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 53  Color (nM Units)    10  10  ---
Fecal Coliform (col/100 mL)  BA  BA  ---
Fecal Coliform (col/100 mL)  BA  BA  ---
Fluoride    BA  BA  ---
Fluoride    BA  BA  ---
Line 420: Line 1,211:
Organic Nitrogen, Total as (N) BA  BA  ---
Organic Nitrogen, Total as (N) BA  BA  ---
Oil and Grease    10.1  18.5  ---
Oil and Grease    10.1  18.5  ---
Phosphorous, Total as (P)  0.23  0.23  ---
Phosphorous, Total as (P)  0.23  0.23  ---  
 
Radioactivity:
Radioactivity:
Alpha, Total (pCi/L)  0.05  0.05  ---
Alpha, Total (pCi/L)  0.05  0.05  ---
Beta, Total (pCi/L)  0.01  0.01  ---
Beta, Total (pCi/L)  0.01  0.01  ---
Radium, Total (pCi/L)  BA  BA  ---
Radium, Total (pCi/L)  BA  BA  ---
Radium 226, Total (pCi/L)  BA  BA  ---
Radium 226, Total (pCi/L)  BA  BA  ---  
Sulfate (as SO4)    <10.0  <10.0  --- Sulfide (as S)    <0.020  <0.020  ---
 
Sulfite (as SO3)    <2.0  <2.0  --- Surfactants    <0.1  <0.1  ---
Sulfate (as SO
: 4)    <10.0  <10.0  --- Sulfide (as S)    <0.020  <0.020  ---  
 
Sulfite (as SO
: 3)    <2.0  <2.0  --- Surfactants    <0.1  <0.1  ---
Aluminum  (Total)    <0.2  <0.2  ---
Aluminum  (Total)    <0.2  <0.2  ---
Barium    (Total)    <0.2  <0.2  ---
Barium    (Total)    <0.2  <0.2  ---
Line 436: Line 1,232:
Manganese (Total)    BA  BA  ---
Manganese (Total)    BA  BA  ---
Tin      (Total)    BA  BA  ---
Tin      (Total)    BA  BA  ---
Titanium  (Total)    BA  BA  --- METALS, CYANIDE & TOTAL PHENOL(g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Antimony  (Total)    BA  BA  60 Arsenic  (Total)    <10  <10  10 Beryllium (Total)    <5  <5  5 Cadmium  (Total)    <1  <1  1 Chromium  (Total)    <10  <10  10 Chromium  (3+)    NA  NA  10 Chromium  (6+)    NA  NA  10 Copper    (Total)    <10  <10  10 Lead      (Total)    <3  <3  5 Mercury  (Total)    <0.2  <0.2  0.2 Molybdenum (Total)  <50  <50  30 Nickel    (Total) Freshwater  <40  <40  40 Nickel    (Total) Marine  NA  NA  5 Selenium  (Total)    <5  <5  5 Silver    (Total)    <2  <2  2 Thallium  (Total)    <10  <10  10 Zinc      (Total)    84.5  84.5  20 Cyanide  (Total)    <10  <10  10 Phenolics, Total Recoverable (4AAP)  <50  <50  5 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 54  DIOXIN    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD    BA  BA  0.00001  VOLATILE COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acrolein    <10  <10  50 Acrylonitrile    <10  <10  50 Benzene    <5  <5  10 Bis(Chloromethyl)Ether  BA  BA  10 Bromoform    <5  <5  10 Carbon Tetrachloride  <5  <5  10 Chlorobenzene    <5  <5  10 Chlorodibromomethane  <5  <5  10 Chloroethane    <10  <10  50 2-Chloroethylvinylether  <5  <5  10 Chloroform    <5  <5  10 Dichlorobromomethane  <5  <5  10 Dichlorodifluoromethane  BA  BA  10 1,1-Dichloroethane  <5  <5  10 1,2-Dichloroethane  <5  <5  10 1,1-Dichloroethylene  <5  <5  10 1,2-Dichloropropane  <5  <5  10 1,3-Dichloropropylene  <5  <5  10 Ethylbenzene    <5  <5  10 Methyl Bromide [Bromomethane]  <10  <10  50 Methyl Chloride [Chloromethane] <10  <10  50 Methylene Chloride  <5  <5  20 1,1,2,2-Tetrachloroethane  <5  <5  10 Tetrachloroethylene  <5  <5  10 Toluene    <5  <5  10 1,2-trans-Dichloroethylene  <5  <5  10 1,1,1-Trichloroethane  <5  <5  10 1,1,2-Trichloroethane  <5  <5  10 Trichloroethylene    <5  <5  10 Trichlorofluoromethane  BA  BA  10 Vinyl Chloride    <10  <10  10  ACID COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol    <10  <10  10 2,4-Dichlorophenol  <10  <10  10 2,4-Dimethylphenol  <10  <10  10 4,6-Dinitro-o-Cresol  <50  <50  50 2,4-Dinitrophenol    <50  <50  50 2-Nitrophenol    <10  <10  20 4-Nitrophenol    <50  <50  50 p-Chloro-m-Cresol    <10  <10  10 Pentachlorophenol    <50  <50  50 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 55  Phenol    <10  <10  10 2,4,6-Trichlorophenol  <10  <10  10  BASE/NEUTRAL COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acenaphthene    <10  <10  10 Acenaphthylene    <10  <10  10 Anthracene    <10  <10  10 Benzidine    <30  <30  50 Benzo(a)anthracene  <10  <10  10 Benzo(a)pyrene    <10  <10  10 3,4-Benzofluoranthene  <10  <10  10 Benzo(ghi)perylene  <10  <10  20 Benzo(k)fluoranthene  <10  <10  10 Bis(2-chloroethoxy) Methane  <10  <10  10 Bis(2-chloroethyl) Ether  <10  <10  10 Bis(2-chloroisopropyl) Ether  <10  <10  10 Bis(2-ethylhexyl) Phthalate  <10  <10  10 4-Bromophenyl Phenyl Ether  <10  <10  10 Butylbenzyl Phthalate  <10  <10  10 2-Chloronaphthalene  <10  <10  10 4-Chlorophenyl Phenyl Ether  <10  <10  10 Chrysene    <10  <10  10 Dibenzo(a,h)anthracene  <10  <10  20 1,2-Dichlorobenzene  <10  <10  10 1,3-Dichlorobenzene  <10  <10  10 1,4-Dichlorobenzene  <10  <10  10 3,3'-Dichlorobenzidine  <20  <20  50 Diethyl Phthalate    <10  <10  10 Dimethyl Phthalate  <10  <10  10 Di-n-Butyl Phthalate  <10  <10  10 2,4-Dinitrotoluene  <10  <10  10 2,6-Dinitrotoluene  <10  <10  10 Di-n-octyl Phthalate  <10  <10  10 1,2-Diphenylhydrazine  <10  <10  20 Fluoranthene    <10  <10  10 Fluorene    <10  <10  10 Hexachlorobenzene    <10  <10  10 Hexachlorobutadiene  <10  <10  10 Hexachlorocyclopentadiene  <10  <10  10 Hexachloroethane    <10  <10  20 Indeno(1,2,3-cd)pyrene    <10  <10  20 Isophorone    <10  <10  10 Naphthalene    <10  <10  10 Nitrobenzene    <10  <10  10 n-Nitrosodimethylamine  <20  <20  50 n-Nitrosodi-n-Propylamine  <10  <10  20 n-Nitrosodiphenylamine  <10  <10  20 Phenanthrene    <10  <10  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 56  Pyrene    <10  <10  10 1,2,4-Trichlorobenzene  <10  <10  10  PESTICIDES    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Aldrin    BA  BA  0.05 Alpha-BHC    BA  BA  0.05 Beta-BHC    BA  BA  0.05 Gamma-BHC [Lindane]  BA  BA  0.05 Delta-BHC    BA  BA  0.05 Chlordane    BA  BA  0.2 4,4'-DDT    BA  BA  0.1 4,4'-DDE [p,p-DDX]  BA  BA  0.1 4,4'-DDD [p,p-TDE]  BA  BA  0.1 Dieldrin    BA  BA  0.1 Alpha-Endosulfan    BA  BA  0.1 Beta-Endosulfan    BA  BA  0.1 Endosulfan Sulfate  BA  BA  0.1 Endrin    BA  BA  0.1 Endrin Aldehyde    BA  BA  0.1 Heptachlor    BA  BA  0.05 Heptachlor Epoxide    BA  BA  0.05 PCB-1242    BA  BA  1.0 PCB-1254    BA  BA  1.0 PCB-1221    BA  BA  1.0 PCB-1232    BA  BA  1.0 PCB-1248    BA  BA  1.0 PCB-1260    BA  BA  1.0 PCB-1016    BA  BA  1.0 Toxaphene    BA  BA  5.0 BA - Believed Absent NA - Not Available
Titanium  (Total)    BA  BA  ---
METALS, CYANIDE & TOTAL PHENOL (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Antimony  (Total)    BA  BA  60 Arsenic  (Total)    <10  <10  10 Beryllium (Total)    <5  <5  5 Cadmium  (Total)    <1  <1  1 Chromium  (Total)    <10  <10  10 Chromium  (3+)    NA  NA  10 Chromium  (6+)    NA  NA  10 Copper    (Total)    <10  <10  10 Lead      (Total)    <3  <3  5 Mercury  (Total)    <0.2  <0.2  0.2 Molybdenum (Total)  <50  <50  30 Nickel    (Total) Freshwater  <40  <40  40 Nickel    (Total) Marine  NA  NA  5 Selenium  (Total)    <5  <5  5 Silver    (Total)    <2  <2  2 Thallium  (Total)    <10  <10  10 Zinc      (Total)    84.5  84.5  20 Cyanide  (Total)    <10  <10  10  
 
Phenolics, Total Recoverable (4AAP)  <50  <50  5  
 
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  


Internal Outfall 204 (New Outfall) A. Type of wastewater - the intermittent internal discharge of vehicle wash wastewater.
LA0007374
B. Location - at the point of discharge from the area where vehicles will be washed prior to combining with the waters of Final Outfall 004. C. Treatment - none. D. Flow - Intermittent. E. Receiving waters - Discharge to Outfall 004. F. Effluent Data - not available, new outfall.
 
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 57 Outfall 005 A. Type of wastewater - the intermittent discharge from the Entergy Energy Education Center sewage treatment plant to 40 Arpent Canal.
Page 54  DIOXIN    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD    BA  BA  0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acrolein    <10  <10  50 Acrylonitrile    <10  <10  50 Benzene    <5  <5  10 Bis(Chloromethyl)Ether  BA  BA  10 Bromoform    <5  <5  10 Carbon Tetrachloride  <5  <5  10 Chlorobenzene    <5  <5  10 Chlorodibromomethane  <5  <5  10 Chloroethane    <10  <10  50 2-Chloroethylvinylether  <5  <5  10 Chloroform    <5  <5  10 Dichlorobromomethane  <5  <5  10 Dichlorodifluoromethane  BA  BA  10 1,1-Dichloroethane  <5  <5  10 1,2-Dichloroethane  <5  <5  10 1,1-Dichloroethylene  <5  <5  10 1,2-Dichloropropane  <5  <5  10 1,3-Dichloropropylene  <5  <5  10 Ethylbenzene    <5  <5  10 Methyl Bromide [Bromomethane]  <10  <10  50 Methyl Chloride [Chloromethane] <10  <10  50 Methylene Chloride  <5  <5  20 1,1,2,2-Tetrachloroethane  <5  <5  10 Tetrachloroethylene  <5  <5  10 Toluene    <5  <5  10 1,2-trans-Dichloroethylene  <5  <5  10 1,1,1-Trichloroethane  <5  <5  10 1,1,2-Trichloroethane  <5  <5  10 Trichloroethylene    <5  <5  10 Trichlorofluoromethane  BA  BA  10 Vinyl Chloride    <10  <10  10 ACID COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol    <10  <10  10 2,4-Dichlorophenol  <10  <10  10 2,4-Dimethylphenol  <10  <10  10 4,6-Dinitro-o-Cresol  <50  <50  50 2,4-Dinitrophenol    <50  <50  50 2-Nitrophenol    <10  <10  20 4-Nitrophenol    <50  <50  50 p-Chloro-m-Cresol    <10  <10  10 Pentachlorophenol    <50  <50  50 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
In addition to the sanitary wastewater, a de minimis discharge from the HVAC unit enters the sewage treatment plant.
 
B. Location - at the point of discharge from the sewage treatment plant prior to combining with the waters of the 40 Arpent Canal at Latitude 2958'53", Longitude 9028'35". C. Treatment - a package sewage treatment plant with chlorination used for disinfection. D. Flow - Intermittent, (Max 30-Day) 0.0018 MGD. E. Receiving waters - 40 Arpent Canal thence to Lac Des Allemands   F. Basin and segment - Barataria Basin, Segment 020202 G. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA Form 2C) received on June 15, 1998. POLLUTANT    EFFLUENT     PART A    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand  28.0  28.0  ---
LA0007374
 
Page 55  Phenol    <10  <10  10 2,4,6-Trichlorophenol  <10  <10  10 BASE/NEUTRAL COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acenaphthene    <10  <10  10 Acenaphthylene    <10  <10  10 Anthracene    <10  <10  10 Benzidine    <30  <30  50 Benzo(a)anthracene  <10  <10  10 Benzo(a)pyrene    <10  <10  10 3,4-Benzofluoranthene  <10  <10  10 Benzo(ghi)perylene  <10  <10  20 Benzo(k)fluoranthene  <10  <10  10 Bis(2-chloroethoxy) Methane  <10  <10  10 Bis(2-chloroethyl) Ether  <10  <10  10 Bis(2-chloroisopropyl) Ether  <10  <10  10 Bis(2-ethylhexyl) Phthalate  <10  <10  10 4-Bromophenyl Phenyl Ether  <10  <10  10 Butylbenzyl Phthalate  <10  <10  10 2-Chloronaphthalene  <10  <10  10 4-Chlorophenyl Phenyl Ether  <10  <10  10 Chrysene    <10  <10  10 Dibenzo(a,h)anthracene  <10  <10  20 1,2-Dichlorobenzene  <10  <10  10 1,3-Dichlorobenzene  <10  <10  10 1,4-Dichlorobenzene  <10  <10  10 3,3'-Dichlorobenzidine  <20  <20  50 Diethyl Phthalate    <10  <10  10 Dimethyl Phthalate  <10  <10  10 Di-n-Butyl Phthalate  <10  <10  10 2,4-Dinitrotoluene  <10  <10  10 2,6-Dinitrotoluene  <10  <10  10 Di-n-octyl Phthalate  <10  <10  10 1,2-Diphenylhydrazine  <10  <10  20 Fluoranthene    <10  <10  10 Fluorene    <10  <10  10 Hexachlorobenzene    <10  <10  10 Hexachlorobutadiene  <10  <10  10 Hexachlorocyclopentadiene  <10  <10  10 Hexachloroethane    <10  <10  20 Indeno(1,2,3-cd)pyrene    <10  <10  20 Isophorone    <10  <10  10 Naphthalene    <10  <10  10 Nitrobenzene    <10  <10  10 n-Nitrosodimethylamine  <20  <20  50 n-Nitrosodi-n-Propylamine  <10  <10  20 n-Nitrosodiphenylamine  <10  <10  20 Phenanthrene    <10  <10  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
 
LA0007374
 
Page 56  Pyrene    <10  <10  10 1,2,4-Trichlorobenzene  <10  <10  10 PESTICIDES    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Aldrin    BA  BA  0.05 Alpha-BHC    BA  BA  0.05 Beta-BHC    BA  BA  0.05 Gamma-BHC [Lindane]  BA  BA  0.05 Delta-BHC    BA  BA  0.05 Chlordane    BA  BA  0.2 4,4'-DDT    BA  BA  0.1 4,4'-DDE [p,p-DDX]  BA  BA  0.1 4,4'-DDD [p,p-TDE]  BA  BA  0.1 Dieldrin    BA  BA  0.1 Alpha-Endosulfan    BA  BA  0.1 Beta-Endosulfan    BA  BA  0.1 Endosulfan Sulfate  BA  BA  0.1 Endrin    BA  BA  0.1 Endrin Aldehyde    BA  BA  0.1 Heptachlor    BA  BA  0.05 Heptachlor Epoxide    BA  BA  0.05 PCB-1242    BA  BA  1.0 PCB-1254    BA  BA  1.0 PCB-1221    BA  BA  1.0 PCB-1232    BA  BA  1.0 PCB-1248    BA  BA  1.0 PCB-1260    BA  BA  1.0 PCB-1016    BA  BA  1.0 Toxaphene    BA  BA  5.0 BA - Believed Absent
 
NA - Not Available
 
Internal Outfall 204 (New Outfall)
A. Type of wastewater - the intermittent internal discharge of vehicle wash wastewater.  
 
B. Location - at the point of discharge from the area where vehicles will be washed prior to combining with the waters of Final Outfall  
 
004. C. Treatment - none.
D. Flow - Intermittent.
E. Receiving waters - Discharge to Outfall 004.
F. Effluent Data - not available, new outfall.
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 57 Outfall 005 A. Type of wastewater - the intermittent discharge from the Entergy Energy Education Center sewage treatment plant to 40 Arpent Canal.  
 
In addition to the sanitary wastewater, a de minimis discharge  
 
from the HVAC unit enters the sewage treatment plant.  
 
B. Location - at the point of discharge from the sewage treatment plant prior to combining with the waters of the 40 Arpent Canal at  
 
Latitude 2958'53", Longitude 9028'35". C. Treatment - a package sewage treatment plant with chlorination used for disinfection.
D. Flow - Intermittent, (Max 30-Day) 0.0018 MGD.
E. Receiving waters - 40 Arpent Canal thence to Lac Des Allemands F. Basin and segment - Barataria Basin, Segment 020202 G. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA  
 
Form 2C) received on June 15, 1998.
POLLUTANT    EFFLUENT PART A    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand  28.0  28.0  ---
Chemical Oxygen Demand    56.9  56.9  ---
Chemical Oxygen Demand    56.9  56.9  ---
Total Organic Carbon    18.6  18.6  ---
Total Organic Carbon    18.6  18.6  ---
Total Suspended Solids  24  27  ---
Total Suspended Solids  24  27  ---
Ammonia (as N)    17.9  17.9  ---
Ammonia (as N)    17.9  17.9  ---
Temperature (Winter)  NA  NA  --- (Summer)  NA  NA  --- pH (Standard Units)  7.20  8.27  ---    (min)    (max) PART B    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Bromide    BA  BA  ---
Temperature (Winter)  NA  NA  --- (Summer)  NA  NA  --- pH (Standard Units)  7.20  8.27  ---    (min)    (max)
PART B    (mg/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Bromide    BA  BA  ---
Chlorine, Total Residual  BA  BA  ---
Chlorine, Total Residual  BA  BA  ---
Color (nM Units)    25  25  ---
Color (nM Units)    25  25  ---
Line 455: Line 1,293:
Organic Nitrogen, Total as (N) BA  BA  ---
Organic Nitrogen, Total as (N) BA  BA  ---
Oil and Grease    <5.60  <5.60  ---
Oil and Grease    <5.60  <5.60  ---
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 58  Phosphorous, Total as (P)  2.8  2.8  ---
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 58  Phosphorous, Total as (P)  2.8  2.8  ---  
 
Radioactivity:
Radioactivity:
Alpha, Total (pCi/L)  BA  BA  ---
Alpha, Total (pCi/L)  BA  BA  ---
Beta, Total (pCi/L)  BA  BA  ---
Beta, Total (pCi/L)  BA  BA  ---
Radium, Total (pCi/L)  BA  BA  ---
Radium, Total (pCi/L)  BA  BA  ---
Radium 226, Total (pCi/L)  BA  BA  ---
Radium 226, Total (pCi/L)  BA  BA  ---  
Sulfate (as SO4)    1,510  1,510  --- Sulfide (as S)    <1.0  <1.0  ---
 
Sulfite (as SO3)    <2.0  <2.0  --- Surfactants    <0.04  <0.04  ---
Sulfate (as SO
: 4)    1,510  1,510  --- Sulfide (as S)    <1.0  <1.0  ---  
 
Sulfite (as SO
: 3)    <2.0  <2.0  --- Surfactants    <0.04  <0.04  ---
Aluminum  (Total)    BA  BA  ---
Aluminum  (Total)    BA  BA  ---
Barium    (Total)    BA  BA  ---
Barium    (Total)    BA  BA  ---
Line 471: Line 1,318:
Manganese (Total)    BA  BA  ---
Manganese (Total)    BA  BA  ---
Tin      (Total)    BA  BA  ---
Tin      (Total)    BA  BA  ---
Titanium  (Total)    BA  BA  --- METALS, CYANIDE & TOTAL PHENOL(g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Antimony  (Total)    BA  BA  60 Arsenic  (Total)    <10  <10  10 Beryllium (Total)    <5  <5  5 Cadmium  (Total)    0.161  0.161  1 Chromium  (Total)    <10  <10  10 Chromium  (3+)    NA  NA  10 Chromium  (6+)    NA  NA  10 Copper    (Total)    118  118  10 Lead      (Total)    <3  <3  5 Mercury  (Total)    <0.2  <0.2  0.2 Molybdenum (Total)  BA  BA  30 Nickel    (Total) Freshwater  <40  <40  40 Nickel    (Total) Marine  NA  NA  5 Selenium  (Total)    <5  <5  5 Silver    (Total)    <1  <1  2 Thallium  (Total)    <10  <10  10 Zinc      (Total)    <20  <20  20 Cyanide  (Total)    19  19  10 Phenolics, Total Recoverable (4AAP)  <50  <50  5 DIOXIN    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD    BA  BA  0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 59  Acrolein    <10  <10  50 Acrylonitrile    <10  <10  50 Benzene    <5  <5  10 Bis(Chloromethyl)Ether  BA  BA  10 Bromoform    <5  <5  10 Carbon Tetrachloride  <5  <5  10 Chlorobenzene    <5  <5  10 Chlorodibromomethane  <5  <5  10 Chloroethane    <10  <10  50 2-Chloroethylvinylether  <5  <5  10 Chloroform    19.7  19.7  10 Dichlorobromomethane  <5  <5  10 Dichlorodifluoromethane  BA  BA  10 1,1-Dichloroethane  <5  <5  10 1,2-Dichloroethane  <5  <5  10 1,1-Dichloroethylene  <5  <5  10 1,2-Dichloropropane  <5  <5  10 1,3-Dichloropropylene  <5  <5  10 Ethylbenzene    <5  <5  10 Methyl Bromide [Bromomethane]  <10  <10  50 Methyl Chloride [Chloromethane] <10  <10  50 Methylene Chloride  13.9  13.9  20 1,1,2,2-Tetrachloroethane  <5  <5  10 Tetrachloroethylene  <5  <5  10 Toluene    <5  <5  10 1,2-trans-Dichloroethylene  BA  BA  10 1,1,1-Trichloroethane  <5  <5  10 1,1,2-Trichloroethane  <5  <5  10 Trichloroethylene    <5  <5  10 Trichlorofluoromethane  BA  BA  10 Vinyl Chloride    <10  <10  10 ACID COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol    <10  <10  10 2,4-Dichlorophenol  <10  <10  10 2,4-Dimethylphenol  <10  <10  10 4,6-Dinitro-o-Cresol  <25  <25  50 2,4-Dinitrophenol    <25  <25  50 2-Nitrophenol    <10  <10  20 4-Nitrophenol    <25  <25  50 p-Chloro-m-Cresol    <10  <10  10 Pentachlorophenol    <25  <25  50 Phenol    <10  <10  10 2,4,6-Trichlorophenol  <10  <10  10 BASE/NEUTRAL COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acenaphthene    <10  <10  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 60  Acenaphthylene    <10  <10  10 Anthracene    <10  <10  10 Benzidine    <30  <30  50 Benzo(a)anthracene  <10  <10  10 Benzo(a)pyrene    <10  <10  10 3,4-Benzofluoranthene  <10  <10  10 Benzo(ghi)perylene  <10  <10  20 Benzo(k)fluoranthene  <10  <10  10 Bis(2-chloroethoxy) Methane  <10  <10  10 Bis(2-chloroethyl) Ether  <10  <10  10 Bis(2-chloroisopropyl) Ether  <10  <10  10 Bis(2-ethylhexyl) Phthalate  <10  <10  10 4-Bromophenyl Phenyl Ether  <10  <10  10 Butylbenzyl Phthalate  <10  <10  10 2-Chloronaphthalene  <10  <10  10 4-Chlorophenyl Phenyl Ether  <10  <10  10 Chrysene    <10  <10  10 Dibenzo(a,h)anthracene  <10  <10  20 1,2-Dichlorobenzene  <10  <10  10 1,3-Dichlorobenzene  <10  <10  10 1,4-Dichlorobenzene  <10  <10  10 3,3'-Dichlorobenzidine  <20  <20  50 Diethyl Phthalate    <10  <10  10 Dimethyl Phthalate  <10  <10  10 Di-n-Butyl Phthalate  <10  <10  10 2,4-Dinitrotoluene  <10  <10  10 2,6-Dinitrotoluene  <10  <10  10 Di-n-octyl Phthalate  <10  <10  10 1,2-Diphenylhydrazine  <10  <10  20 Fluoranthene    <10  <10  10 Fluorene    <10  <10  10 Hexachlorobenzene    <10  <10  10 Hexachlorobutadiene  <10  <10  10 Hexachlorocyclopentadiene  <10  <10  10 Hexachloroethane    <10  <10  20 Indeno(1,2,3-cd)pyrene    <10  <10  20 Isophorone    <10  <10  10 Naphthalene    <10  <10  10 Nitrobenzene    <10  <10  10 n-Nitrosodimethylamine  <10  <10  50 n-Nitrosodi-n-Propylamine  <10  <10  20 n-Nitrosodiphenylamine  <10  <10  20 Phenanthrene    <10  <10  10 Pyrene    <10  <10  10 1,2,4-Trichlorobenzene  <10  <10  10 PESTICIDES    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Aldrin    BA  BA  0.05 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 61  Alpha-BHC    BA  BA  0.05 Beta-BHC    BA  BA  0.05 Gamma-BHC [Lindane]  BA  BA  0.05 Delta-BHC    BA  BA  0.05 Chlordane    BA  BA  0.2 4,4'-DDT    BA  BA  0.1 4,4'-DDE [p,p-DDX]  BA  BA  0.1 4,4'-DDD [p,p-TDE]  BA  BA  0.1 Dieldrin    BA  BA  0.1 Alpha-Endosulfan    BA  BA  0.1 Beta-Endosulfan    BA  BA  0.1 Endosulfan Sulfate  BA  BA  0.1 Endrin    BA  BA  0.1 Endrin Aldehyde    BA  BA  0.1 Heptachlor    BA  BA  0.05 Heptachlor Epoxide    BA  BA  0.05 PCB-1242    BA  BA  1.0 PCB-1254    BA  BA  1.0 PCB-1221    BA  BA  1.0 PCB-1232    BA  BA  1.0 PCB-1248    BA  BA  1.0 PCB-1260    BA  BA  1.0 PCB-1016    BA  BA  1.0 Toxaphene    BA  BA  5.0 BA - Believed Absent NA - Not Available  
Titanium  (Total)    BA  BA  ---
METALS, CYANIDE & TOTAL PHENOL (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Antimony  (Total)    BA  BA  60 Arsenic  (Total)    <10  <10  10 Beryllium (Total)    <5  <5  5 Cadmium  (Total)    0.161  0.161  1 Chromium  (Total)    <10  <10  10 Chromium  (3+)    NA  NA  10 Chromium  (6+)    NA  NA  10 Copper    (Total)    118  118  10 Lead      (Total)    <3  <3  5 Mercury  (Total)    <0.2  <0.2  0.2 Molybdenum (Total)  BA  BA  30 Nickel    (Total) Freshwater  <40  <40  40 Nickel    (Total) Marine  NA  NA  5 Selenium  (Total)    <5  <5  5 Silver    (Total)    <1  <1  2 Thallium  (Total)    <10  <10  10 Zinc      (Total)    <20  <20  20 Cyanide  (Total)    19  19  10  
 
Phenolics, Total Recoverable (4AAP)  <50  <50  5 DIOXIN    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD    BA  BA  0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max
 
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 59  Acrolein    <10  <10  50 Acrylonitrile    <10  <10  50 Benzene    <5  <5  10 Bis(Chloromethyl)Ether  BA  BA  10 Bromoform    <5  <5  10 Carbon Tetrachloride  <5  <5  10 Chlorobenzene    <5  <5  10 Chlorodibromomethane  <5  <5  10 Chloroethane    <10  <10  50 2-Chloroethylvinylether  <5  <5  10 Chloroform    19.7  19.7  10 Dichlorobromomethane  <5  <5  10 Dichlorodifluoromethane  BA  BA  10 1,1-Dichloroethane  <5  <5  10 1,2-Dichloroethane  <5  <5  10 1,1-Dichloroethylene  <5  <5  10 1,2-Dichloropropane  <5  <5  10 1,3-Dichloropropylene  <5  <5  10 Ethylbenzene    <5  <5  10 Methyl Bromide [Bromomethane]  <10  <10  50 Methyl Chloride [Chloromethane] <10  <10  50 Methylene Chloride  13.9  13.9  20 1,1,2,2-Tetrachloroethane  <5  <5  10 Tetrachloroethylene  <5  <5  10 Toluene    <5  <5  10 1,2-trans-Dichloroethylene  BA  BA  10 1,1,1-Trichloroethane  <5  <5  10 1,1,2-Trichloroethane  <5  <5  10 Trichloroethylene    <5  <5  10 Trichlorofluoromethane  BA  BA  10 Vinyl Chloride    <10  <10  10 ACID COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol    <10  <10  10 2,4-Dichlorophenol  <10  <10  10 2,4-Dimethylphenol  <10  <10  10 4,6-Dinitro-o-Cresol  <25  <25  50 2,4-Dinitrophenol    <25  <25  50 2-Nitrophenol    <10  <10  20 4-Nitrophenol    <25  <25  50 p-Chloro-m-Cresol    <10  <10  10 Pentachlorophenol    <25  <25  50 Phenol    <10  <10  10 2,4,6-Trichlorophenol  <10  <10  10 BASE/NEUTRAL COMPOUNDS  (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Acenaphthene    <10  <10  10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 60  Acenaphthylene    <10  <10  10 Anthracene    <10  <10  10 Benzidine    <30  <30  50 Benzo(a)anthracene  <10  <10  10 Benzo(a)pyrene    <10  <10  10 3,4-Benzofluoranthene  <10  <10  10 Benzo(ghi)perylene  <10  <10  20 Benzo(k)fluoranthene  <10  <10  10 Bis(2-chloroethoxy) Methane  <10  <10  10 Bis(2-chloroethyl) Ether  <10  <10  10 Bis(2-chloroisopropyl) Ether  <10  <10  10 Bis(2-ethylhexyl) Phthalate  <10  <10  10 4-Bromophenyl Phenyl Ether  <10  <10  10 Butylbenzyl Phthalate  <10  <10  10 2-Chloronaphthalene  <10  <10  10 4-Chlorophenyl Phenyl Ether  <10  <10  10 Chrysene    <10  <10  10 Dibenzo(a,h)anthracene  <10  <10  20 1,2-Dichlorobenzene  <10  <10  10 1,3-Dichlorobenzene  <10  <10  10 1,4-Dichlorobenzene  <10  <10  10 3,3'-Dichlorobenzidine  <20  <20  50 Diethyl Phthalate    <10  <10  10 Dimethyl Phthalate  <10  <10  10 Di-n-Butyl Phthalate  <10  <10  10 2,4-Dinitrotoluene  <10  <10  10 2,6-Dinitrotoluene  <10  <10  10 Di-n-octyl Phthalate  <10  <10  10 1,2-Diphenylhydrazine  <10  <10  20 Fluoranthene    <10  <10  10 Fluorene    <10  <10  10 Hexachlorobenzene    <10  <10  10 Hexachlorobutadiene  <10  <10  10 Hexachlorocyclopentadiene  <10  <10  10 Hexachloroethane    <10  <10  20 Indeno(1,2,3-cd)pyrene    <10  <10  20 Isophorone    <10  <10  10 Naphthalene    <10  <10  10 Nitrobenzene    <10  <10  10 n-Nitrosodimethylamine  <10  <10  50 n-Nitrosodi-n-Propylamine  <10  <10  20 n-Nitrosodiphenylamine  <10  <10  20 Phenanthrene    <10  <10  10 Pyrene    <10  <10  10 1,2,4-Trichlorobenzene  <10  <10  10 PESTICIDES    (g/L, UNLESS STATED)  MQL (g/L) 30-Day Max Daily Max Aldrin    BA  BA  0.05 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 61  Alpha-BHC    BA  BA  0.05 Beta-BHC    BA  BA  0.05 Gamma-BHC [Lindane]  BA  BA  0.05 Delta-BHC    BA  BA  0.05 Chlordane    BA  BA  0.2 4,4'-DDT    BA  BA  0.1 4,4'-DDE [p,p-DDX]  BA  BA  0.1 4,4'-DDD [p,p-TDE]  BA  BA  0.1 Dieldrin    BA  BA  0.1 Alpha-Endosulfan    BA  BA  0.1 Beta-Endosulfan    BA  BA  0.1 Endosulfan Sulfate  BA  BA  0.1 Endrin    BA  BA  0.1 Endrin Aldehyde    BA  BA  0.1 Heptachlor    BA  BA  0.05 Heptachlor Epoxide    BA  BA  0.05 PCB-1242    BA  BA  1.0 PCB-1254    BA  BA  1.0 PCB-1221    BA  BA  1.0 PCB-1232    BA  BA  1.0 PCB-1248    BA  BA  1.0 PCB-1260    BA  BA  1.0 PCB-1016    BA  BA  1.0 Toxaphene    BA  BA  5.0 BA - Believed Absent  
 
NA - Not Available  
 
VIII. Proposed Permit Limits:
The specific effluent limitations and/or conditions will be found in the
 
draft permit. Development and calculation of permit limits are detailed
 
in the Permit Limit Rationale section below.
Summary of Proposed Changes From the Current NPDES Permit:
A. Final Outfall 001:
: 1. Increase the instantaneous daily maximum temperature limit from 110F to 118F. 2. Increase the daily maximum heat limit from 8.5 x 10 9 BTU/hr to 9.5 x 10 9 BTU/hr.
: 3. Change the acute freshwater whole effluent toxicity biomonitoring frequency from quarterly to once per year.
B. Internal Outfall 101 (Former 01A):
 
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
 
LA0007374
 
Page 62  1. Only daily maximum reporting of flow in MGD rather than the daily average flow limit of 0.0288 MGD is proposed due to
 
the intermittent nature of the wastestream.
: 2. Only daily maximum limitations are proposed due to the intermittent nature of the wastestream.
C. Internal Outfall 201 (Former 01B):
: 1. Only daily maximum reporting of flow in MGD rather than the daily average flow limit of 0.0288 MGD is proposed due to
 
the intermittent nature of the wastestream.
: 2. Only daily maximum limitations are proposed due to the intermittent nature of the wastestream.
D. Internal Outfall 301 (Former 01C):
: 1. Only daily maximum reporting of flow in MGD is proposed due to the intermittent nature of the wastestream.
: 2. Change the reporting requirement for clarifying agents.
E. Internal Outfall 401 (Former 01D):
: 1. Only daily maximum reporting of flow in MGD is proposed due to the intermittent nature of the wastestream.
: 2. Only daily maximum limitation for Total Suspended Solids is proposed due to the intermittent nature of the wastestream.
: 3. Establish daily maximum limitation for oil and grease (O&G) at 20 mg/l.
: 4. Establish monitoring frequency of 1/week for TSS, Oil &
Grease, and pH, when discharging.
F. Internal Outfall 501 (New Outfall):
: 1. Add Internal Outfall 501 for the intermittent discharge from Auxiliary Component Cooling Water Basin A to Final Outfall
 
001 via the turbine condenser cooling system. 
: 2. The daily maximum reporting of flow in MGD is proposed due to the intermittent nature of the wastestream.
: 3. Establish daily maximum limitation for total organic carbon (TOC) at 50 mg/l.
 
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
 
LA0007374
 
Page 63  4. Establish daily maximum limitation for total suspended solids (TSS) at 100 mg/l.
: 5. Establish daily maximum limitation for oil and grease (O&G) at 20 mg/l. 
: 6. Establish limitation for pH of not less than 6.0  standard units nor greater than 9.0 standard units.
: 7. Establish monitoring frequency of 1/week for TOC, TSS, Oil &
Grease, and pH, when discharging.
G. Internal Outfall 601 (New Outfall):
: 1. Add Internal Outfall 601 for the intermittent discharge from Auxiliary Component Cooling Water Basin B to Final Outfall
 
001 via the turbine condenser cooling system.
: 2. The daily maximum reporting of flow in MGD is proposed due to the intermittent nature of the wastestream.
: 3. Establish daily maximum limitation for total organic carbon (TOC) at 50 mg/l.
: 4. Establish daily maximum limitation for total suspended solids (TSS) at 100 mg/l.
: 5. Establish daily maximum limitation for oil and grease (O&G) at 20 mg/l. 
: 6. Establish limitation for pH of not less than 6.0  standard units nor greater than 9.0 standard units.
: 7. Establish monitoring frequency of 1/week for TOC, TSS, Oil &
Grease, and pH, when discharging.
H. Internal Outfall 701 (New Outfall):
: 1. Add Internal Outfall 701 for the intermittent discharge of cooling tower blowdown and low volume wastewaters from Dry
 
Cooling Tower Sump #1 and the occasional discharge of
 
previously monitored effluent from Internal Outfall 104 to
 
Final Outfall 001 via the turbine condenser cooling system
 
or Final Outfall 004.
: 2. The daily maximum reporting of flow in MGD is proposed due to the intermittent nature of the wastestream.
 
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
 
LA0007374
 
Page 64  3. Establish daily maximum limitation for total organic carbon (TOC) at 50 mg/l.
: 4. Establish daily maximum limitation for total suspended solids (TSS) at 100 mg/l.
: 5. Establish daily maximum limitation for oil and grease (O&G) at 20 mg/l. 
: 6. Establish limitation for pH of not less than 6.0  standard units nor greater than 9.0 standard units.
: 7. Establish daily maximum limitation for free available chlorine (FAC) at 0.5 mg/l, when discharging cooling tower
 
blowdown.
: 8. Establish daily maximum limitation for total chromium at 0.2 mg/l, when discharging cooling tower blowdown.
: 9. Establish daily maximum limitation for total zinc at 1.0 mg/l, when discharging cooling tower blowdown.
: 10. Establish monitoring frequency of 1/month for TOC, TSS, Oil
& Grease, pH, FAC, total chromium, and total zinc, when
 
discharging.
 
I. Internal Outfall 801 (New Outfall):
: 1. Add Internal Outfall 801 for the intermittent discharge of cooling tower blowdown and low volume wastewaters from Dry
 
Cooling Tower Sump #2 and the occasional discharge of
 
previously monitored effluent from Internal Outfall 104 to
 
Final Outfall 001 via the turbine condenser cooling system
 
or Final Outfall 004.
: 2. The daily maximum reporting of flow in MGD is proposed due to the intermittent nature of the wastestream.
: 3. Establish daily maximum limitation for total organic carbon (TOC) at 50 mg/l.
: 4. Establish daily maximum limitation for total suspended solids (TSS) at 100 mg/l.
: 5. Establish daily maximum limitation for oil and grease (O&G) at 20 mg/l. 
: 6. Establish limitation for pH of not less than 6.0  standard units nor greater than 9.0 standard units.
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
 
LA0007374
 
Page 65  7. Establish daily maximum limitation for free available chlorine (FAC) at 0.5 mg/l, when discharging cooling tower
 
blowdown.
: 8. Establish daily maximum limitation for total chromium at 0.2 mg/l, when discharging cooling tower blowdown.
: 9. Establish daily maximum limitation for total zinc at 1.0 mg/l, when discharging cooling tower blowdown.
: 10. Establish monitoring frequency of 1/month for TOC, TSS, Oil
& Grease, pH, FAC, total chromium, and total zinc, when
 
discharging.
J. Internal Outfall 901 (New Outfall):
: 1. Add Internal Outfall 901 for the intermittent, mobile discharge of metal cleaning wastewaters from internal
 
components of plant equipment to Final Outfall 001 via the
 
turbine condenser cooling system.
: 2. The daily maximum reporting of flow in MGD is proposed due to the intermittent nature of the wastestream.
: 3. Establish daily maximum limitation for total suspended solids (TSS) at 100 mg/l.
: 4. Establish daily maximum limitation for oil and grease (O&G) at 20 mg/l. 
: 5. Establish limitation for pH of not less than 6.0  standard units nor greater than 9.0 standard units.
: 6. Establish daily maximum limitation for total copper at 1.0 mg/l. 7. Establish daily maximum limitation for total iron at 1.0 mg/l. 8. Establish monitoring frequency of 1/week for TSS, Oil &
Grease, pH, total copper, and total iron, when discharging.
K. Final Outfall 004 (New Outfall):
: 1. Add Final Outfall 004 for the intermittent discharge from the plant drainage ditch system to 40 Arpent Canal and the
 
occasional discharge from Internal Outfall 701 and Internal
 
Outfall 801.
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
 
LA0007374
 
Page 66  2. The daily maximum reporting of flow in MGD is proposed due to the intermittent nature of the wastestream.
: 3. Establish daily maximum limitation for total organic carbon (TOC) at 50 mg/l.
: 4. Establish daily maximum limitation for oil and grease (O&G) at 15 mg/l.
: 5. Require discharge limits for total suspended solids (TSS) of 100 mg/l for daily maximum, when discharging low volume
 
wastewaters during maintenance activities.
: 6. Establish limitation for pH of not less than 6.0  standard units nor greater than 9.0 standard units.
: 7. Establish monitoring frequency for TOC, O&G, and pH at once per quarter.
: 8. Establish monitoring frequency for TSS at once per quarter, when discharging low volume wastewaters. L. Internal Outfall 104 (Former 002): 
: 1. Add an optional flow path for occasional discharges from the yard oil separator system to Dry Cooling Tower Sump #1
 
(Internal Outfall 701) and/or Dry Cooling Tower Sump #2
 
(Internal Outfall 801) as a result of maintenance


VIII. Proposed Permit Limits:  The specific effluent limitations and/or conditions will be found in the draft permit. Development and calculation of permit limits are detailed in the Permit Limit Rationale section below. Summary of Proposed Changes From the Current NPDES Permit:  A. Final Outfall 001:  1. Increase the instantaneous daily maximum temperature limit from 110F to 118F. 2. Increase the daily maximum heat limit from 8.5 x 109 BTU/hr to 9.5 x 109 BTU/hr. 3. Change the acute freshwater whole effluent toxicity biomonitoring frequency from quarterly to once per year. B. Internal Outfall 101 (Former 01A):
activities.  
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 62  1. Only daily maximum reporting of flow in MGD rather than the daily average flow limit of 0.0288 MGD is proposed due to the intermittent nature of the wastestream. 2. Only daily maximum limitations are proposed due to the intermittent nature of the wastestream. C. Internal Outfall 201 (Former 01B): 1. Only daily maximum reporting of flow in MGD rather than the daily average flow limit of 0.0288 MGD is proposed due to the intermittent nature of the wastestream. 2. Only daily maximum limitations are proposed due to the intermittent nature of the wastestream. D. Internal Outfall 301 (Former 01C):  1. Only daily maximum reporting of flow in MGD is proposed due to the intermittent nature of the wastestream. 2. Change the reporting requirement for clarifying agents. E. Internal Outfall 401 (Former 01D):  1. Only daily maximum reporting of flow in MGD is proposed due to the intermittent nature of the wastestream. 2. Only daily maximum limitation for Total Suspended Solids is proposed due to the intermittent nature of the wastestream. 3. Establish daily maximum limitation for oil and grease (O&G) at 20 mg/l. 4. Establish monitoring frequency of 1/week for TSS, Oil & Grease, and pH, when discharging. F. Internal Outfall 501 (New Outfall):  1. Add Internal Outfall 501 for the intermittent discharge from Auxiliary Component Cooling Water Basin A to Final Outfall 001 via the turbine condenser cooling system. 2. The daily maximum reporting of flow in MGD is proposed due to the intermittent nature of the wastestream. 3. Establish daily maximum limitation for total organic carbon (TOC) at 50 mg/l.
: 2. Only daily maximum limitations are proposed due to the intermittent nature of the wastestream.  
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 63  4. Establish daily maximum limitation for total suspended solids (TSS) at 100 mg/l. 5. Establish daily maximum limitation for oil and grease (O&G) at 20 mg/l. 6. Establish limitation for pH of not less than 6.0  standard units nor greater than 9.0 standard units. 7. Establish monitoring frequency of 1/week for TOC, TSS, Oil & Grease, and pH, when discharging. G. Internal Outfall 601 (New Outfall):  1. Add Internal Outfall 601 for the intermittent discharge from Auxiliary Component Cooling Water Basin B to Final Outfall 001 via the turbine condenser cooling system. 2. The daily maximum reporting of flow in MGD is proposed due to the intermittent nature of the wastestream. 3. Establish daily maximum limitation for total organic carbon (TOC) at 50 mg/l. 4. Establish daily maximum limitation for total suspended solids (TSS) at 100 mg/l. 5. Establish daily maximum limitation for oil and grease (O&G) at 20 mg/l. 6. Establish limitation for pH of not less than 6.0  standard units nor greater than 9.0 standard units. 7. Establish monitoring frequency of 1/week for TOC, TSS, Oil & Grease, and pH, when discharging. H. Internal Outfall 701 (New Outfall):  1. Add Internal Outfall 701 for the intermittent discharge of cooling tower blowdown and low volume wastewaters from Dry Cooling Tower Sump #1 and the occasional discharge of previously monitored effluent from Internal Outfall 104 to Final Outfall 001 via the turbine condenser cooling system or Final Outfall 004. 2. The daily maximum reporting of flow in MGD is proposed due to the intermittent nature of the wastestream.
: 3. Change the monitoring frequency for TSS, O&G, and pH to once per month.
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 64  3. Establish daily maximum limitation for total organic carbon (TOC) at 50 mg/l. 4. Establish daily maximum limitation for total suspended solids (TSS) at 100 mg/l. 5. Establish daily maximum limitation for oil and grease (O&G) at 20 mg/l. 6. Establish limitation for pH of not less than 6.0  standard units nor greater than 9.0 standard units. 7. Establish daily maximum limitation for free available chlorine (FAC) at 0.5 mg/l, when discharging cooling tower blowdown. 8. Establish daily maximum limitation for total chromium at 0.2 mg/l, when discharging cooling tower blowdown. 9. Establish daily maximum limitation for total zinc at 1.0 mg/l, when discharging cooling tower blowdown. 10. Establish monitoring frequency of 1/month for TOC, TSS, Oil & Grease, pH, FAC, total chromium, and total zinc, when discharging.
M. Internal Outfall 204 (New Outfall):  
I. Internal Outfall 801 (New Outfall): 1. Add Internal Outfall 801 for the intermittent discharge of cooling tower blowdown and low volume wastewaters from Dry Cooling Tower Sump #2 and the occasional discharge of previously monitored effluent from Internal Outfall 104 to Final Outfall 001 via the turbine condenser cooling system or Final Outfall 004. 2. The daily maximum reporting of flow in MGD is proposed due to the intermittent nature of the wastestream. 3. Establish daily maximum limitation for total organic carbon (TOC) at 50 mg/l. 4. Establish daily maximum limitation for total suspended solids (TSS) at 100 mg/l. 5. Establish daily maximum limitation for oil and grease (O&G) at 20 mg/l. 6. Establish limitation for pH of not less than 6.0  standard units nor greater than 9.0 standard units.
: 1. Add Internal Outfall 204 for the intermittent discharge of vehicle wash wastewaters to Final Outfall 004.  
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 65  7. Establish daily maximum limitation for free available chlorine (FAC) at 0.5 mg/l, when discharging cooling tower blowdown. 8. Establish daily maximum limitation for total chromium at 0.2 mg/l, when discharging cooling tower blowdown. 9. Establish daily maximum limitation for total zinc at 1.0 mg/l, when discharging cooling tower blowdown. 10. Establish monitoring frequency of 1/month for TOC, TSS, Oil & Grease, pH, FAC, total chromium, and total zinc, when discharging. J. Internal Outfall 901 (New Outfall):  1. Add Internal Outfall 901 for the intermittent, mobile discharge of metal cleaning wastewaters from internal components of plant equipment to Final Outfall 001 via the turbine condenser cooling system. 2. The daily maximum reporting of flow in MGD is proposed due to the intermittent nature of the wastestream. 3. Establish daily maximum limitation for total suspended solids (TSS) at 100 mg/l. 4. Establish daily maximum limitation for oil and grease (O&G) at 20 mg/l. 5. Establish limitation for pH of not less than 6.0  standard units nor greater than 9.0 standard units. 6. Establish daily maximum limitation for total copper at 1.0 mg/l. 7. Establish daily maximum limitation for total iron at 1.0 mg/l. 8. Establish monitoring frequency of 1/week for TSS, Oil & Grease, pH, total copper, and total iron, when discharging. K. Final Outfall 004 (New Outfall):  1. Add Final Outfall 004 for the intermittent discharge from the plant drainage ditch system to 40 Arpent Canal and the occasional discharge from Internal Outfall 701 and Internal Outfall 801.
: 2. The monthly average and daily maximum reporting of flow in MGD is proposed.  
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 66  2. The daily maximum reporting of flow in MGD is proposed due to the intermittent nature of the wastestream. 3. Establish daily maximum limitation for total organic carbon (TOC) at 50 mg/l. 4. Establish daily maximum limitation for oil and grease (O&G) at 15 mg/l. 5. Require discharge limits for total suspended solids (TSS) of 100 mg/l for daily maximum, when discharging low volume wastewaters during maintenance activities. 6. Establish limitation for pH of not less than 6.0  standard units nor greater than 9.0 standard units. 7. Establish monitoring frequency for TOC, O&G, and pH at once per quarter. 8. Establish monitoring frequency for TSS at once per quarter, when discharging low volume wastewaters. L. Internal Outfall 104 (Former 002):  1. Add an optional flow path for occasional discharges from the yard oil separator system to Dry Cooling Tower Sump #1 (Internal Outfall 701) and/or Dry Cooling Tower Sump #2 (Internal Outfall 801) as a result of maintenance activities. 2. Only daily maximum limitations are proposed due to the intermittent nature of the wastestream. 3. Change the monitoring frequency for TSS, O&G, and pH to once per month. M. Internal Outfall 204 (New Outfall): 1. Add Internal Outfall 204 for the intermittent discharge of vehicle wash wastewaters to Final Outfall 004. 2. The monthly average and daily maximum reporting of flow in MGD is proposed. 3. Establish limitations for chemical oxygen demand (COD) at 200 mg/l and 300 mg/l, monthly average and daily maximum respectively.
: 3. Establish limitations for chemical oxygen demand (COD) at 200 mg/l and 300 mg/l, monthly average and daily maximum  
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 67  4. Establish daily maximum limitation for total suspended solids (TSS) at 45 mg/l. 5. Establish daily maximum limitation for oil and grease (O&G) at 15 mg/l. 6. Establish limitation for pH of not less than 6.0  standard units nor greater than 9.0 standard units. 7. Establish inventory requirement for the soaps and/or detergents used. 8. Establish monitoring frequency for COD, TSS, O&G, and pH at once per quarter. N. Final Outfall 005 (New Outfall):  1. Add Final Outfall 005 for the intermittent discharge from the Entergy Energy Education Center sewage treatment plant to 40 Arpent Canal. 2. The weekly average reporting of flow in MGD is proposed due to the intermittent nature of the wastestream. 3. Establish weekly average limitation for total suspended solids (TSS) at 45 mg/l. 4. Establish weekly average limitation for biological oxygen demand (5 days) (BOD5) at 45 mg/l. 5. Establish weekly average limitation for fecal coliform at 400 colonies/100 ml. 6. Establish limitation for pH of not less than 6.0  standard units nor greater than 9.0 standard units. 7. Establish monitoring frequency for TSS, pH, BOD5, and fecal coliform at once per six months. O. Part II:  1. Specify that the 126 priority pollutants as listed in 40 CFR 423 Appendix A, other than total chromium and total zinc, will not be detected in the effluent in accordance with 40 CFR 423.
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 68  IX. Permit Limit Rationale:
The following section sets forth the principal facts and the significant factual, legal, methodological, and policy questions considered in preparing the draft permit. Also set forth are any calculations or other explanations of the derivation of specific effluent limitations and conditions, including a citation to the applicable effluent limitation guideline or performance standard provisions as required under LAC 33:IX.2361/40 CFR Part 122.44 and reasons why they are applicable or an explanation of how the alternate effluent limitations were developed.
A. TECHNOLOGY-BASED VERSUS WATER QUALITY STANDARDS-BASED EFFLUENT LIMITATIONS AND CONDITIONS Following regulations promulgated at LAC 33:IX.2361.L.2.b/40 CFR Part 122.44(l)(2)(ii), the draft permit limits are based on either technology-based effluent limits pursuant to LAC 33:IX.2361.A/40 CFR Part 122.44(a) or on State water quality standards and requirements pursuant to LAC 33:IX.2361.D/40 CFR Part 122.44(d), whichever are more stringent.
B. TECHNOLOGY-BASED EFFLUENT LIMITATIONS AND CONDITIONS Regulations promulgated at LAC 33:IX.2361.A/40 CFR Part 122.44(a) require technology-based effluent limitations to be placed in LPDES permits based on effluent limitations guidelines where applicable, on best professional judgement (BPJ) in the absence of guidelines, or on a combination of the two.


The permittee is subject to Best Practicable Control Technology Currently Available (BPT) and Best Available Technology Economically Achievable (BAT) effluent limitation guidelines listed below:
respectively.  
Manufacturing Operation  Guideline Steam Electric Power Generating Point Source Category  40 CFR 423 Outfall 001 This outfall is the continuous discharge from the turbine condenser cooling system to the Mississippi River. The turbine condenser cooling system receives once-through non-contact cooling water from the Mississippi River that flows through the main condenser, the steam generator blowdown heat exchangers, and the turbine building closed cooling heat exchanger.
Previously monitored discharges from Internal Outfalls 101 (former 01A), 201 (former 01B), 301 (former 01C), 401 (former 01D), 501, 601, 701, 801, and 901 also are discharged via Outfall 001. The combined flow volume of these intermittent internal outfalls (estimated at 1.65 MGD) is significantly less than the maximum 30 day average flow of the once-through non-contact cooling water through Outfall 001 (1,346 MGD). The effluent limitations proposed for Outfall 001 in the draft LPDES permit are as follows:
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 69  Parameter  Monthly Daily Average Maximum    Flow    Report                                                          1,518 MGD Temperature (F)  Report                                                            118F Heat    N/A  9.5 x 109 BTU/Hour Boron    N/A      0.2 mg/l Total Residual Chlorine N/A    211 lbs/day Flow


The flow limitation of 1,518 MGD for daily maximum at Outfall 001 is retained from the current NPDES permit. This maximum daily flow limit was requested by Louisiana Power and Light Company (LP&L, predecessor to Entergy) in a letter to EPA Region 6 dated March 1, 1985. This letter requested an increase in the daily maximum flow of the once-through non-contact cooling water from the limit of 1,445 MGD then in effect to 1,518 MGD which LP&L described as the "maximum hydraulic capability" of the turbine condenser cooling system. This request was granted in a letter from EPA Region 6 to LP&L dated May 30, 1985.
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
Discharge flow is to be determined from calibrated pumping curves or calculated using appropriate heat balance methodology.
 
Boron The current NPDES permit established a calculated daily maximum discharge limit of 0.2 mg/l for boron at Outfall 001. The fact sheet for this NPDES permit stated this boron limitation was based on BPJ since boron is for reactivity control in the reactor. The limit is retained on the same basis.   
LA0007374
 
Page 67  4. Establish daily maximum limitation for total suspended solids (TSS) at 45 mg/l.
: 5. Establish daily maximum limitation for oil and grease (O&G) at 15 mg/l.
: 6. Establish limitation for pH of not less than 6.0  standard units nor greater than 9.0 standard units.
: 7. Establish inventory requirement for the soaps and/or detergents used.
: 8. Establish monitoring frequency for COD, TSS, O&G, and pH at once per quarter.
N. Final Outfall 005 (New Outfall):
: 1. Add Final Outfall 005 for the intermittent discharge from the Entergy Energy Education Center sewage treatment plant
 
to 40 Arpent Canal.
: 2. The weekly average reporting of flow in MGD is proposed due to the intermittent nature of the wastestream. 3. Establish weekly average limitation for total suspended solids (TSS) at 45 mg/l.
: 4. Establish weekly average limitation for biological oxygen demand (5 days) (BOD
: 5) at 45 mg/l.
: 5. Establish weekly average limitation for fecal coliform at 400 colonies/100 ml.
: 6. Establish limitation for pH of not less than 6.0  standard units nor greater than 9.0 standard units.
: 7. Establish monitoring frequency for TSS, pH, BOD 5, and fecal coliform at once per six months.
O. Part II:
: 1. Specify that the 126 priority pollutants as listed in 40 CFR 423 Appendix A, other than total chromium and total zinc,
 
will not be detected in the effluent in accordance with 40
 
CFR 423.
 
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
 
LA0007374
 
Page 68  IX. Permit Limit Rationale:
 
The following section sets forth the principal facts and the significant
 
factual, legal, methodological, and policy questions considered in preparing
 
the draft permit. Also set forth are any calculations or other explanations
 
of the derivation of specific effluent limitations and conditions, including a
 
citation to the applicable effluent limitation guideline or performance
 
standard provisions as required under LAC 33:IX.2361/40 CFR Part 122.44 and
 
reasons why they are applicable or an explanation of how the alternate
 
effluent limitations were developed.
 
A. TECHNOLOGY-BASED VERSUS WATER QUALITY STANDARDS-BASED EFFLUENT LIMITATIONS AND CONDITIONS
 
Following regulations promulgated at LAC 33:IX.2361.L.2.b/40 CFR Part
 
122.44(l)(2)(ii), the draft permit limits are based on either technology-based
 
effluent limits pursuant to LAC 33:IX.2361.A/40 CFR Part 122.44(a) or on State
 
water quality standards and requirements pursuant to LAC 33:IX.2361.D/40 CFR
 
Part 122.44(d), whichever are more stringent.
 
B. TECHNOLOGY-BASED EFFLUENT LIMITATIONS AND CONDITIONS
 
Regulations promulgated at LAC 33:IX.2361.A/40 CFR Part 122.44(a) require
 
technology-based effluent limitations to be placed in LPDES permits based on
 
effluent limitations guidelines where applicable, on best professional
 
judgement (BPJ) in the absence of guidelines, or on a combination of the two.
 
The permittee is subject to Best Practicable Control Technology Currently
 
Available (BPT) and Best Available Technology Economically Achievable (BAT)
 
effluent limitation guidelines listed below:
 
Manufacturing Operation  Guideline Steam Electric Power Generating Point Source Category  40 CFR 423
 
Outfall 001
 
This outfall is the continuous discharge from the turbine condenser cooling
 
system to the Mississippi River. The turbine condenser cooling system
 
receives once-through non-contact cooling water from the Mississippi River
 
that flows through the main condenser, the steam generator blowdown heat
 
exchangers, and the turbine building closed cooling heat exchanger. 
 
Previously monitored discharges from Internal Outfalls 101 (former 01A), 201
 
(former 01B), 301 (former 01C), 401 (former 01D), 501, 601, 701, 801, and 901
 
also are discharged via Outfall 001. The combined flow volume of these
 
intermittent internal outfalls (estimated at 1.65 MGD) is significantly less
 
than the maximum 30 day average flow of the once-through non-contact cooling
 
water through Outfall 001 (1,346 MGD). The effluent limitations proposed for
 
Outfall 001 in the draft LPDES permit are as follows:
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
 
LA0007374
 
Page 69  Parameter  Monthly Daily Average Maximum    Flow    Report 1,518 MGD Temperature (F)  Report 118F Heat    N/A  9.5 x 10 9 BTU/Hour Boron    N/A      0.2 mg/l Total Residual Chlorine N/A    211 lbs/day
 
Flow
 
The flow limitation of 1,518 MGD for daily maximum at Outfall 001 is retained  
 
from the current NPDES permit. This maximum daily flow limit was requested by  
 
Louisiana Power and Light Company (LP&L, predecessor to Entergy) in a letter  
 
to EPA Region 6 dated March 1, 1985. This letter requested an increase in the  
 
daily maximum flow of the once-through non-contact cooling water from the  
 
limit of 1,445 MGD then in effect to 1,518 MGD which LP&L described as the  
 
"maximum hydraulic capability" of the turbine condenser cooling system. This  
 
request was granted in a letter from EPA Region 6 to LP&L dated May 30, 1985.  
 
Discharge flow is to be determined from calibrated pumping curves or  
 
calculated using appropriate heat balance methodology.  
 
Boron The current NPDES permit established a calculated daily maximum discharge  
 
limit of 0.2 mg/l for boron at Outfall 001. The fact sheet for this NPDES  
 
permit stated this boron limitation was based on BPJ since boron is for  
 
reactivity control in the reactor. The limit is retained on the same basis.   


Total Residual Chlorine  
Total Residual Chlorine  


The current NPDES permit established daily maximum discharge limits of 211 lbs/day and 0.2 mg/l for total residual chlorine (TRC) at Outfall 001. The limit is based on 40 CFR 423.13(b)(1)(BAT). Since the discharge from Outfall 001 is continuous and not significantly variable, only the mass limitation is continued.
The current NPDES permit established daily maximum discharge limits of 211  


Site-Specific Consideration  Temperature and Heat In an application addendum submitted June 15, 1998, the permittee requested that the temperature and heat discharge limits included in the current NPDES permit, 110F and 8.5 x 109 BTU/Hour, be increased to 118 F and 9.5 x 109 BTU/Hour, respectively, or removed from the new permit entirely.
lbs/day and 0.2 mg/l for total residual chlorine (TRC) at Outfall 001. The
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 70  The permittee bases the request for an increase in temperature and heat discharge limits on a planned "power uprate" to be implemented in the near future at Waterford 3. On August 26, 1996, this Office issued a letter of no objection to the permittee's request for a power uprate. However, the permit limitations and conditions in the current permit were not adjusted to accommodate a power uprate and compliance with those limitations was still required. Current limits can not be met with a production increase, especially during months when customer demand for electricity is high. This increase in the megawatt output of the facility will result in more waste heat that will need to be transferred from the turbine condenser to the once-through non-contact cooling water. Because the turbine condenser cooling system will continue to operate within its current hydraulic capability, the removal of this additional waste heat will result in higher discharge temperatures for the once-through non-contact cooling water. Due to the Nuclear Regulatory Commission (NRC) approved design of the plant itself,  full power operation, following a power uprate, would result in an increase in temperature and heat discharged in once-through non-contact cooling water. The following is an explanation of how this occurs.
 
Thermal energy is generated from the nuclear fuel inside a reactor. Reactor coolant is circulated inside the reactor coolant system to carry that thermal energy  to the secondary coolant via a non-contact steam generator. Steam produced from the steam generator drives the turbine-generator producing electricity. Exhaust steam from the outlet of the turbine is condensed by the non-contact cooling water in the circulating water system. Approximately one-third of the heat produced by the reactor is absorbed by the non-contact cooling water in the circulating water system which discharges through Outfall 001 to the Mississippi River. Therefore to increase the electrical output, the thermal energy produced by the reactor must increase proportionally to the increase of electricity. As a result of the increase in reactor thermal power, more heat is absorbed by the non-contact cooling water in the circulating water system. Both the temperature and heat limitations included in the current permit are technology-based limitations. 40 CFR 423 promulgated as commanded by Section 304 of the Clean Water Act did not establish temperature or heat limitations. Therefore, best professional judgment (BPJ) was used by EPA, Region VI, to establish the Best Available Technology (BAT), economically achievable, for the current temperature and heat limitations contained in the NPDES permit.
limit is based on 40 CFR 423.13(b)(1)(BAT). Since the discharge from Outfall
The heat limit currently in effect, 8.5 x 109 BTU/Hour, resulted from the Demonstration under Section 316(a) of the Clean Water Act submitted by LP&L in April 1979. On page 35 of this document, LP&L requested that EPA establish 8.5 x 109 BTU/Hour as an alternative thermal limitation for Waterford 3. An internal EPA Region 6 memo dated August 24, 1979 discussed the EPA review of this 316(a) demonstration. In this memo, the EPA reviewer concurred with LP&L's conclusion that the alternative thermal limitation "adequately Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 71  regulates the amount of heat discharged to the Mississippi River from this facility such that it protects the balanced indigenous population". However, the EPA reviewer continued "although the demonstration requests no maximum thermal limitation be placed in the permit, I recommend an instantaneous thermal maximum of 110 F be placed in the permit to further insure protection of the aquatic species". The 110 F stems from a maximum instantaneous heat discharge of 8.5 x 109 BTU/Hour, an instantaneous flow rate of 1,000 MGD for the once-through non-contact cooling water, and a typical maximum stream temperature of 86 F. The definition of a British thermal unit (BTU) is the amount of heat required to raise the temperature of one pound of water one degree Fahrenheit at or near 39.2F. Ignoring the slight variation in thermal conductivity of water due to its ambient temperature, the temperature increase of the cooling water conveying the waste heat from the turbine condenser can be estimated by dividing the waste heat in BTU/hour by the cooling water flow in pounds per hour (lbs/hour). The conversion of the cooling water flow from MGD to lbs/hour is accomplished as follows:  
 
  [(1,000 x 106 gal/day) x (8.337 lbs/gal)]  [24 hr/day] = 347,375,000 lbs/hour Dividing the alternative heat limit by the converted cooling water flow yields:  
001 is continuous and not significantly variable, only the mass limitation is
  (8.5 x 109 BTU/Hour)  (347,375,000 lbs/hour) = 24.5F  Adding this to the typical maximum stream temperature produces the following discharge temperature:
 
86F + 24.5F = 110.5F or approximately 110F  Applying the same methodology for a heat limit of 9.5 x 109 BTU/Hour and a maximum fresh water stream temperature of 90F (specified in LAC 33:IX.1113.C.4) produces a discharge temperature of approximately 118F. Using a flow of 1,000 MGD in these calculations is reasonable because the long term average flow for Outfall 001 is 1,085 MGD according to the permit application.
continued.  
To further ensure attainment of LAC 33:IX.1113.C.4.b.i.(a), the 5F allowable rise of temperature above ambient was applied at the edge of the mixing zone. Appendix A illustrates that a violation of the above citation would not occur with a discharge limitation for temperature at 118F. The Demonstration under Section 316(a) of the Clean Water Act classified the Mississippi River near Waterford 3 as "an area of low potential impact for Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 72  thermal discharges". This classification resulted from: (1) the determination that this stretch of the Mississippi River was not "unique" for any shellfish, fish, or wildlife; and (2) the realization that most of the cross-sectional area available for flow in the river would be unaffected by the thermal plume. Therefore, the indigenous population of shellfish, fish, and wildlife, which are present in abundance in areas away from Waterford 3, either would have ample opportunity to pass by the facility without encountering elevated stream temperatures or would only experience the higher temperatures for such brief periods that no deleterious effects would result. The 316(a) demonstration found that no threatened or endangered species were present near Waterford 3. The species that were present also were abundant in other areas of the Mississippi River. The study also determined that no special fish spawning habitat existed near the facility.
 
The 316(a) demonstration documented thermal model results for various flow and temperature conditions reflecting seasonal variations in this stretch of the Mississippi River. The models accounted for the historically calibrated thermal discharges for the nearby Waterford 1 and 2 and Little Gypsy steam electric generating plants, as well as for the 8.5 x 109 BTU/Hour anticipated for Waterford 3. A worst case scenario of an extreme low flow of 100,000 cubic feet per second (cfs) was modeled in the study. This minimum flow in the lower Mississippi River is maintained by the Old River Control Structure operated by the U.S. Army Corps of Engineers and is less than the 7Q10 flow for this segment of the river (141,955 cfs). Under this worst case, extreme low flow situation, the model determined that less than 15% of the cross-sectional area of the river would experience temperature increases of 5 F. This thermal plume also stayed near the surface of the river extending no deeper than 10 feet. In the Final Environmental Statement Related to the Operation of Waterford Steam Electric Station, Unit No. 3, the Nuclear Regulatory Commission (NRC) documented model studies conducted by their staff to independently confirm the results presented by LP&L in the 316(a) demonstration. Using a different model, the NRC produced results that were "generally in agreement" with those presented by LP&L. The NRC model produced a slightly larger combined thermal plume or mixing zone, but the environmental statement concluded that operation of Waterford 3 would be "in compliance with the Louisiana Water Quality Criteria relating to temperature". With all three plants operating at peak loads during extreme low flow conditions, an adequate zone of passage (83% of the river cross-sectional area) will still remain for aquatic species to pass by facilities without entering the combined thermal mixing zone. Species entering the mixing zone probably would pass through it in one hour or less, minimizing the impact of the elevated temperatures. Also natural ambient river surface temperatures above 86 F should only occur about 2.5% of the time. Applying the percentage increase of thermal discharge at Waterford 3 to the model worst case, extreme low flow thermal plume should provide a conservative Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 73  estimate of the combined thermal mixing zone that would result from the planned power uprate. This should be very conservative due to Waterford 3 contributing less heat to the river than Waterford 1 and 2 and Little Gypsy combined. Increasing the heat discharge to 9.5 x 109 BTU/Hour from 8.5 x 109 BTU/Hour constitutes a 12% gain. Applying this proportional gain to the worst case combined thermal plume (17% of river cross-sectional area) yields an anticipated combined thermal mixing zone of 19%. This leaves approximately 81% of the river flow unaffected by the temperature increase after the Waterford 3 power uprate, even under extreme low flow conditions. LAC 33:IX.1115.C.7 specifies the mixing zone for streams with 7Q10 flow greater than 100 cfs as either 100 cfs or 1/3 of the flow, whichever is greater. The anticipated thermal mixing zone of 19% is substantially less than 33% of cross-sectional area or 1/3 of the flow. Therefore, the increased heat discharge and temperature limits requested for Outfall 001 are expected to meet Louisiana Water Quality Criteria for temperature.
Site-Specific Consideration Temperature and Heat
In response to this Office's concern expressed in the August 26, 1996 letter, the combined thermal discharges from Waterford 1 and 2, Waterford 3, and Little Gypsy were evaluated in respect to the cooling tower operations of a downstream facility, Union Carbide. This facility is 1.6 river miles down from Waterford 3. In 1971, the U.S. Department of Interior, Geological Survey in cooperation with Louisiana Department of Public Works, prepared Hydrologic and Quality Characteristics of the Lower Mississippi River, Technical Report Number 5. The purpose of the report was to further an understanding of the hydrologic and quality characteristics of the lower Mississippi River, including the effects of industrial development on water quality and the ability of the river to assimilate wastes. In evaluating the effects of heated effluent, the report states "Very little vertical mixing occurred because the heated water was less dense and floated on the surface."   Because the heated water is less dense than the cooler ambient river water, the combined thermal mixing zone remains near the surface. As mentioned earlier, the worst case thermal plume extends no more than about 10 feet deep.
 
Since the intake structure for Union Carbide is 3 feet below mean sea level, no rise in temperature above ambient would be detected. Additionally, Union Carbide's cooling water enters the facility via an internal canal. This canal would effectively return river water to ambient temperature prior to entering the facility's cooling system.
In an application addendum submitted June 15, 1998, the permittee requested that the temperature and heat discharge limits included in the current NPDES permit, 110F and 8.5 x 10 9 BTU/Hour, be increased to 118 F and 9.5 x 10 9 BTU/Hour, respectively, or removed from the new permit entirely.
Technology to achieve the current limitations for temperature and heat does exist through the use of cooling towers. However, that technology is not economically achievable for Waterford 3. This facility is regulated by the NRC and any change in the operation or equipment must be approved by that agency. For the relatively small increase in temperature and heat caused by the power uprate, modifying the plant itself is not economically justified.
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
In conclusion, this permit proposes to increase the temperature to 118F and heat to  9.5 x 109 BTU/hour as requested by the permittee.
 
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 74 Internal Outfalls In accordance with 40 CFR 122.56(b)(1)(ii), the following is an explanation for the establishment of Internal Outfalls 101, 201, 301, 401, 501, 601, 701, 801, 901, 104, and 204. Certain permit effluent limitations at the point of discharge are impractical because at the final discharge point the wastes at the point discharge are so diluted as to make monitoring impracticable. pH must be monitored internally at the outfalls internal to Outfall 001 because the design of the plant does not allow for the measurement to be taken prior to entering the Mississippi River. Therefore, in accordance with 40 CFR 122.46(h)(2) the internal outfalls described below are established.
LA0007374  
 
Page 70  The permittee bases the request for an increase in temperature and heat discharge limits on a planned "power uprate" to be implemented in the near future at Waterford 3. On August 26, 1996, this Office issued a letter of no objection to the permittee's request for a power uprate. However, the permit limitations and conditions in the current permit were not adjusted to accommodate a power uprate and compliance with those limitations was still required. Current limits can not be met with a production increase, especially during months when customer demand for electricity is high. This increase in the megawatt output of the facility will result in more waste heat that will need to be transferred from the turbine condenser to the once-through non-contact cooling water. Because the turbine condenser cooling system will continue to operate within its current hydraulic capability, the removal of this additional waste heat will result in higher discharge temperatures for the once-through non-contact cooling water.
Due to the Nuclear Regulatory Commission (NRC) approved design of the plant itself,  full power operation, following a power uprate, would result in an increase in temperature and heat discharged in once-through non-contact cooling water. The following is an explanation of how this occurs.  
 
Thermal energy is generated from the nuclear fuel inside a reactor.
Reactor coolant is circulated inside the reactor coolant system to carry that thermal energy  to the secondary coolant via a non-contact steam generator. Steam produced from the steam generator drives the turbine-generator producing electricity. Exhaust steam from the outlet of the turbine is condensed by the non-contact cooling water in the circulating water system. Approximately one-third of the heat produced by the reactor is absorbed by the non-contact cooling water in the circulating water system which discharges through Outfall 001 to the Mississippi River. Therefore to increase the electrical output, the thermal energy produced by the reactor must increase proportionally to the increase of electricity. As a result of the increase in reactor thermal power, more heat is absorbed by the non-contact cooling water in the circulating water system.
Both the temperature and heat limitations included in the current permit are technology-based limitations. 40 CFR 423 promulgated as commanded by Section 304 of the Clean Water Act did not establish temperature or heat limitations.
Therefore, best professional judgment (BPJ) was used by EPA, Region VI, to establish the Best Available Technology (BAT), economically achievable, for the current temperature and heat limitations contained in the NPDES permit.  
 
The heat limit currently in effect, 8.5 x 10 9 BTU/Hour, resulted from the Demonstration under Section 316(a) of the Clean Water Act submitted by LP&L in April 1979. On page 35 of this document, LP&L requested that EPA establish 8.5 x 109 BTU/Hour as an alternative thermal limitation for Waterford 3. An internal EPA Region 6 memo dated August 24, 1979 discussed the EPA review of this 316(a) demonstration. In this memo, the EPA reviewer concurred with LP&L's conclusion that the alternative thermal limitation "adequately Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 71  regulates the amount of heat discharged to the Mississippi River from this facility such that it protects the balanced indigenous population". However, the EPA reviewer continued "although the demonstration requests no maximum thermal limitation be placed in the permit, I recommend an instantaneous thermal maximum of 110 F be placed in the permit to further insure protection of the aquatic species". The 110 F stems from a maximum instantaneous heat discharge of 8.5 x 10 9 BTU/Hour, an instantaneous flow rate of 1,000 MGD for the once-through non-contact cooling water, and a typical maximum stream temperature of 86 F. The definition of a British thermal unit (BTU) is the amount of heat required to raise the temperature of one pound of water one degree Fahrenheit at or near 39.2F. Ignoring the slight variation in thermal conductivity of water due to its ambient temperature, the temperature increase of the cooling water conveying the waste heat from the turbine condenser can be estimated by dividing the waste heat in BTU/hour by the cooling water flow in pounds per hour (lbs/hour).
The conversion of the cooling water flow from MGD to lbs/hour is accomplished as follows:  
 
  [(1,000 x 10 6 gal/day) x (8.337 lbs/gal)]  [24 hr/day] = 347,375,000 lbs/hour Dividing the alternative heat limit by the converted cooling water flow yields:  
  (8.5 x 10 9 BTU/Hour)  (347,375,000 lbs/hour) = 24.5F  Adding this to the typical maximum stream temperature produces the following discharge temperature:  
 
86F + 24.5F = 110.5F or approximately 110F  Applying the same methodology for a heat limit of 9.5 x 10 9 BTU/Hour and a maximum fresh water stream temperature of 90F (specified in LAC 33:IX.1113.C.4) produces a discharge temperature of approximately 118F. Using a flow of 1,000 MGD in these calculations is reasonable because the long term average flow for Outfall 001 is 1,085 MGD according to the permit application.  
 
To further ensure attainment of LAC 33:IX.1113.C.4.b.i.(a), the 5F allowable rise of temperature above ambient was applied at the edge of the mixing zone.
Appendix A illustrates that a violation of the above citation would not occur with a discharge limitation for temperature at 118F. The Demonstration under Section 316(a) of the Clean Water Act classified the Mississippi River near Waterford 3 as "an area of low potential impact for Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 72  thermal discharges". This classification resulted from: (1) the determination that this stretch of the Mississippi River was not "unique" for any shellfish, fish, or wildlife; and (2) the realization that most of the cross-sectional area available for flow in the river would be unaffected by the thermal plume.
Therefore, the indigenous population of shellfish, fish, and wildlife, which are present in abundance in areas away from Waterford 3, either would have ample opportunity to pass by the facility without encountering elevated stream temperatures or would only experience the higher temperatures for such brief periods that no deleterious effects would result.
The 316(a) demonstration found that no threatened or endangered species were present near Waterford 3. The species that were present also were abundant in other areas of the Mississippi River. The study also determined that no special fish spawning habitat existed near the facility.  
 
The 316(a) demonstration documented thermal model results for various flow and temperature conditions reflecting seasonal variations in this stretch of the Mississippi River. The models accounted for the historically calibrated thermal discharges for the nearby Waterford 1 and 2 and Little Gypsy steam electric generating plants, as well as for the 8.5 x 10 9 BTU/Hour anticipated for Waterford 3. A worst case scenario of an extreme low flow of 100,000 cubic feet per second (cfs) was modeled in the study. This minimum flow in the lower Mississippi River is maintained by the Old River Control Structure operated by the U.S. Army Corps of Engineers and is less than the 7Q10 flow for this segment of the river (141,955 cfs). Under this worst case, extreme low flow situation, the model determined that less than 15% of the cross-sectional area of the river would experience temperature increases of 5 F. This thermal plume also stayed near the surface of the river extending no deeper than 10 feet.
In the Final Environmental Statement Related to the Operation of Waterford Steam Electric Station, Unit No. 3
, the Nuclear Regulatory Commission (NRC) documented model studies conducted by their staff to independently confirm the results presented by LP&L in the 316(a) demonstration. Using a different model, the NRC produced results that were "generally in agreement" with those presented by LP&L. The NRC model produced a slightly larger combined thermal plume or mixing zone, but the environmental statement concluded that operation of Waterford 3 would be "in compliance with the Louisiana Water Quality Criteria relating to temperature". With all three plants operating at peak loads during extreme low flow conditions, an adequate zone of passage (83% of the river cross-sectional area) will still remain for aquatic species to pass by facilities without entering the combined thermal mixing zone. Species entering the mixing zone probably would pass through it in one hour or less, minimizing the impact of the elevated temperatures. Also natural ambient river surface temperatures above 86 F should only occur about 2.5% of the time. Applying the percentage increase of thermal discharge at Waterford 3 to the model worst case, extreme low flow thermal plume should provide a conservative Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 73  estimate of the combined thermal mixing zone that would result from the planned power uprate. This should be very conservative due to Waterford 3 contributing less heat to the river than Waterford 1 and 2 and Little Gypsy combined. Increasing the heat discharge to 9.5 x 10 9 BTU/Hour from 8.5 x 10 9 BTU/Hour constitutes a 12% gain. Applying this proportional gain to the worst case combined thermal plume (17% of river cross-sectional area) yields an anticipated combined thermal mixing zone of 19%. This leaves approximately 81% of the river flow unaffected by the temperature increase after the Waterford 3 power uprate, even under extreme low flow conditions.
LAC 33:IX.1115.C.7 specifies the mixing zone for streams with 7Q10 flow greater than 100 cfs as either 100 cfs or 1/3 of the flow, whichever is greater. The anticipated thermal mixing zone of 19% is substantially less than 33% of cross-sectional area or 1/3 of the flow. Therefore, the increased heat discharge and temperature limits requested for Outfall 001 are expected to meet Louisiana Water Quality Criteria for temperature.  
 
In response to this Office's concern expressed in the August 26, 1996 letter, the combined thermal discharges from Waterford 1 and 2, Waterford 3, and Little Gypsy were evaluated in respect to the cooling tower operations of a downstream facility, Union Carbide. This facility is 1.6 river miles down from Waterford 3. In 1971, the U.S. Department of Interior, Geological Survey in cooperation with Louisiana Department of Public Works, prepared Hydrologic and Quality Characteristics of the Lower Mississippi River, Technical Report Number 5. The purpose of the report was to further an understanding of the hydrologic and quality characteristics of the lower Mississippi River, including the effects of industrial development on water quality and the ability of the river to assimilate wastes. In evaluating the effects of heated effluent, the report states "Very little vertical mixing occurred because the heated water was less dense and floated on the surface."
Because the heated water is less dense than the cooler ambient river water, the combined thermal mixing zone remains near the surface. As mentioned earlier, the worst case thermal plume extends no more than about 10 feet deep.  
 
Since the intake structure for Union Carbide is 3 feet below mean sea level, no rise in temperature above ambient would be detected. Additionally, Union Carbide's cooling water enters the facility via an internal canal. This canal would effectively return river water to ambient temperature prior to entering the facility's cooling system.  
 
Technology to achieve the current limitations for temperature and heat does exist through the use of cooling towers. However, that technology is not economically achievable for Waterford 3. This facility is regulated by the NRC and any change in the operation or equipment must be approved by that agency. For the relatively small increase in temperature and heat caused by the power uprate, modifying the plant itself is not economically justified.  
 
In conclusion, this permit proposes to increase the temperature to 118F and heat to  9.5 x 10 9 BTU/hour as requested by the permittee.
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 74 Internal Outfalls
 
In accordance with 40 CFR 122.56(b)(1)(ii), the following is an explanation  
 
for the establishment of Internal Outfalls 101, 201, 301, 401, 501, 601, 701,  
 
801, 901, 104, and 204. Certain permit effluent limitations at the point of  
 
discharge are impractical because at the final discharge point the wastes at  
 
the point discharge are so diluted as to make monitoring impracticable. pH  
 
must be monitored internally at the outfalls internal to Outfall 001 because  
 
the design of the plant does not allow for the measurement to be taken prior
 
to entering the Mississippi River. Therefore, in accordance with 40 CFR
 
122.46(h)(2) the internal outfalls described below are established.
 
Internal Outfall 101 (Former 01A) - Liquid Waste Management System
 
This outfall is the intermittent internal discharge from the liquid waste
 
management system to Final Outfall 001 via the turbine condenser cooling
 
system. The liquid waste management system receives low volume wastewater
 
from the following sources, including but not limited to:  the turbine and
 
reactor building equipment and floor drains, primary plant water makeup,
 
laboratory drains, and other low volume wastewater sources as defined in 40
 
CFR 423. The effluent limitations proposed for Outfall 101 in the draft LPDES
 
permit are as follows:
 
Parameter  Monthly  Daily Average Maximum  mg/L    mg/L Flow, MGD  N/A  Report Total Suspended Solids N/A  100 Oil and Grease  N/A  20 Boron    N/A  Report pH, standard units 6.0 (min) 9.0 (max)  


Internal Outfall 101 (Former 01A) - Liquid Waste Management System This outfall is the intermittent internal discharge from the liquid waste management system to Final Outfall 001 via the turbine condenser cooling system. The liquid waste management system receives low volume wastewater from the following sources, including but not limited to:  the turbine and reactor building equipment and floor drains, primary plant water makeup, laboratory drains, and other low volume wastewater sources as defined in 40 CFR 423. The effluent limitations proposed for Outfall 101 in the draft LPDES permit are as follows:
Parameter  Monthly  Daily Average Maximum  mg/L    mg/L Flow, MGD  N/A  Report Total Suspended Solids N/A  100 Oil and Grease  N/A  20 Boron    N/A  Report pH, standard units 6.0 (min) 9.0 (max)
Flow  
Flow  


The permittee has requested to change the daily average flow limitation from 0.0288 MGD to Report. The daily average flow limitation of 0.0288 MGD at Internal Outfall 101 (former 01A) is in the current NPDES permit. This average daily flow limit was requested by LP&L in a letter to EPA Region 6 dated March 1, 1985. This letter requested an increase in the daily average flow of the liquid waste management system from the limit of 0.0093 MGD then in effect to 0.0288 MGD which LP&L described as necessary "to accommodate efficient operation of the plant". This request was granted in a letter from EPA Region 6 to LP&L dated May 30, 1985.  
The permittee has requested to change the daily average flow limitation from  
 
0.0288 MGD to Report. The daily average flow limitation of 0.0288 MGD at  
 
Internal Outfall 101 (former 01A) is in the current NPDES permit. This  
 
average daily flow limit was requested by LP&L in a letter to EPA Region 6  
 
dated March 1, 1985. This letter requested an increase in the daily average  
 
flow of the liquid waste management system from the limit of 0.0093 MGD then  
 
in effect to 0.0288 MGD which LP&L described as necessary "to accommodate  
 
efficient operation of the plant". This request was granted in a letter from  
 
EPA Region 6 to LP&L dated May 30, 1985.  
 
The permittee contends that this flow limit at Internal Outfall 101
 
unnecessarily restricts plant operations without adding to the quality of the


The permittee contends that this flow limit at Internal Outfall 101 unnecessarily restricts plant operations without adding to the quality of the discharges from the facility. Because discharges from the liquid waste management system occur in batches and each batch requires monitoring prior to Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 75  discharge, all the effluent conveyed past Internal Outfall 101 meets the discharge criteria specified in the permit, regardless of flow quantity.
discharges from the facility. Because discharges from the liquid waste  


Given that a power uprate at Waterford 3 will require additional operation of the liquid waste management system to support the increased generation of electricity, the permittee's request to remove the daily average flow limit of 0.0288 MGD is granted. Discharge flow is totalized when the discharge occurs.  
management system occur in batches and each batch requires monitoring prior to Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
 
LA0007374
 
Page 75  discharge, all the effluent conveyed past Internal Outfall 101 meets the
 
discharge criteria specified in the permit, regardless of flow quantity.
 
Given that a power uprate at Waterford 3 will require additional operation of  
 
the liquid waste management system to support the increased generation of  
 
electricity, the permittee's request to remove the daily average flow limit of  
 
0.0288 MGD is granted. Discharge flow is totalized when the discharge occurs.  


Total Suspended Solids  
Total Suspended Solids  


The current NPDES permit established a daily average discharge limit of 30 mg/l and a daily maximum discharge limit of 100 mg/l for total suspended solids at Internal Outfall 101 (former 01A). Since the flow to this outfall is intermittent only the daily maximum limitation is continued from the current permit. This limit is based on 40 CFR 423.12(b)(3)(BPT).  
The current NPDES permit established a daily average discharge limit of 30  
 
mg/l and a daily maximum discharge limit of 100 mg/l for total suspended  
 
solids at Internal Outfall 101 (former 01A). Since the flow to this outfall  
 
is intermittent only the daily maximum limitation is continued from the  
 
current permit. This limit is based on 40 CFR 423.12(b)(3)(BPT).  


Oil and Grease  
Oil and Grease  


The current NPDES permit established a daily average discharge limit of 15 mg/l and a daily maximum discharge limit of 20 mg/l for oil and grease at Internal Outfall 101 (former 01A). Since the flow to this outfall is intermittent only the daily maximum limitation is continued from the current permit. This limit is based on 40 CFR 423.12(b)(3)(BPT).  
The current NPDES permit established a daily average discharge limit of 15  
 
mg/l and a daily maximum discharge limit of 20 mg/l for oil and grease at  
 
Internal Outfall 101 (former 01A). Since the flow to this outfall is  
 
intermittent only the daily maximum limitation is continued from the current  
 
permit. This limit is based on 40 CFR 423.12(b)(3)(BPT).  


Boron  
Boron  


The current NPDES permit established Report for both the daily average discharge limit and daily maximum discharge limit for boron at Internal Outfall 101 (former 01A). Since the flow to this outfall is intermittent only the daily maximum reporting requirement is continued from the current permit.
The current NPDES permit established Report for both the daily average  
 
discharge limit and daily maximum discharge limit for boron at Internal  
 
Outfall 101 (former 01A). Since the flow to this outfall is intermittent only  
 
the daily maximum reporting requirement is continued from the current permit.  
 
This requirement is based on the current permit.  
This requirement is based on the current permit.  


pH  
pH  


The current NPDES permit established a minimum discharge limit of 6.0 standard units and a maximum discharge limit of 9.0 standard units for pH at Outfall 101 (former 01A). These limits are based on 40 CFR 423.12(b)(1)(BPT) and are retained from the current permit.  
The current NPDES permit established a minimum discharge limit of 6.0 standard  
 
units and a maximum discharge limit of 9.0 standard units for pH at Outfall  
 
101 (former 01A). These limits are based on 40 CFR 423.12(b)(1)(BPT) and are  
 
retained from the current permit.  
 
Internal Outfall 201 (Former 01B) - Boron Management System
 
This outfall is the intermittent internal discharge from the boron management
 
system to Final Outfall 001 via the turbine condenser cooling system. The
 
boron management system concentrates and recovers boron from low volume
 
wastewaters for reuse within the plant. The boron management system receives
 
low volume wastewater from the following sources, including but not limited
 
to:  the turbine and reactor building equipment and floor drains, primary
 
plant water makeup, laboratory drains, and other low volume wastewater sources Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
 
LA0007374
 
Page 76  as defined in 40 CFR 423. The effluent limitations proposed for Internal
 
Outfall 201 in the draft LPDES permit are as follows:
 
Parameter  Monthly  Daily Average Maximum  mg/L    mg/L Flow, MGD  N/A  Report Total Suspended Solids N/A  100 Oil and Grease  N/A  20 Boron    N/A  Report pH, standard units 6.0 (min) 9.0 (max)


Internal Outfall 201 (Former 01B) - Boron Management System This outfall is the intermittent internal discharge from the boron management system to Final Outfall 001 via the turbine condenser cooling system. The boron management system concentrates and recovers boron from low volume wastewaters for reuse within the plant. The boron management system receives low volume wastewater from the following sources, including but not limited to:  the turbine and reactor building equipment and floor drains, primary plant water makeup, laboratory drains, and other low volume wastewater sources Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 76  as defined in 40 CFR 423. The effluent limitations proposed for Internal Outfall 201 in the draft LPDES permit are as follows:
Parameter  Monthly  Daily Average Maximum  mg/L    mg/L Flow, MGD  N/A  Report Total Suspended Solids N/A  100 Oil and Grease  N/A  20 Boron    N/A  Report pH, standard units 6.0 (min) 9.0 (max)
Flow  
Flow  


The permittee has requested to change the daily average flow limitation from 0.0288 MGD to Report. The daily average flow limitation of 0.0288 MGD at Internal Outfall 201 (former 01B) is included in the current NPDES permit.
The permittee has requested to change the daily average flow limitation from  
This average daily flow limit was requested by LP&L in a letter to EPA Region 6 dated March 1, 1985. This letter requested an increase in the daily average flow of the boron management system from the limit of 0.0144 MGD then in effect to 0.0288 MGD which LP&L described as necessary "to accommodate efficient operation of the plant". This request was granted in a letter from EPA Region 6 to LP&L dated May 30, 1985.  
 
0.0288 MGD to Report. The daily average flow limitation of 0.0288 MGD at  
 
Internal Outfall 201 (former 01B) is included in the current NPDES permit.
 
This average daily flow limit was requested by LP&L in a letter to EPA Region  
 
6 dated March 1, 1985. This letter requested an increase in the daily average  
 
flow of the boron management system from the limit of 0.0144 MGD then in  
 
effect to 0.0288 MGD which LP&L described as necessary "to accommodate  
 
efficient operation of the plant". This request was granted in a letter from  
 
EPA Region 6 to LP&L dated May 30, 1985.  
 
The permittee contends that this flow limit at Internal Outfall 201
 
unnecessarily restricts plant operations without adding to the quality of the
 
discharges from the facility. Because discharges from the boron management


The permittee contends that this flow limit at Internal Outfall 201 unnecessarily restricts plant operations without adding to the quality of the discharges from the facility. Because discharges from the boron management system occur in batches and each batch requires monitoring prior to discharge, all the effluent conveyed past Internal Outfall 201 meets the discharge criteria specified in the permit, regardless of flow quantity.
system occur in batches and each batch requires monitoring prior to discharge,  


Given that a power uprate at Waterford 3 will require additional operation of the boron management system to support the increased generation of electricity, the permitee's request to remove the daily average flow limit of 0.0288 MGD is granted. Discharge flow is totalized when the discharge occurs.  
all the effluent conveyed past Internal Outfall 201 meets the discharge
 
criteria specified in the permit, regardless of flow quantity.
 
Given that a power uprate at Waterford 3 will require additional operation of  
 
the boron management system to support the increased generation of  
 
electricity, the permitee's request to remove the daily average flow limit of  
 
0.0288 MGD is granted. Discharge flow is totalized when the discharge occurs.  


Total Suspended Solids  
Total Suspended Solids  


The current NPDES permit established a daily average discharge limit of 30 mg/l and a daily maximum discharge limit of 100 mg/l for total suspended solids at Internal Outfall 201 (former 01B). Since the flow to this outfall is intermittent only the daily maximum limitation is continued from the current permit. This limit is based on 40 CFR 423.12(b)(3)(BPT).  
The current NPDES permit established a daily average discharge limit of 30  
 
mg/l and a daily maximum discharge limit of 100 mg/l for total suspended  
 
solids at Internal Outfall 201 (former 01B). Since the flow to this outfall  
 
is intermittent only the daily maximum limitation is continued from the  
 
current permit. This limit is based on 40 CFR 423.12(b)(3)(BPT).  


Oil and Grease  
Oil and Grease  


The current NPDES permit established a daily average discharge limit of 15 mg/l and a daily maximum discharge limit of 20 mg/l for oil and grease at Internal Outfall 201 (former 01B). Since the flow to this outfall is Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 77  intermittent only the daily maximum limitation is continued from the current permit. This limit is based on 40 CFR 423.12(b)(3)(BPT).  
The current NPDES permit established a daily average discharge limit of 15  
 
mg/l and a daily maximum discharge limit of 20 mg/l for oil and grease at  
 
Internal Outfall 201 (former 01B). Since the flow to this outfall is Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 77  intermittent only the daily maximum limitation is continued from the current  
 
permit. This limit is based on 40 CFR 423.12(b)(3)(BPT).  


Boron  
Boron  


The current NPDES permit established Report for both the daily average discharge limit and daily maximum discharge limit for boron at Internal Outfall 201 (former 01B). Since the flow to this outfall is intermittent only the daily maximum reporting requirement is continued from the current permit.
The current NPDES permit established Report for both the daily average  
 
discharge limit and daily maximum discharge limit for boron at Internal  
 
Outfall 201 (former 01B). Since the flow to this outfall is intermittent only  
 
the daily maximum reporting requirement is continued from the current permit.  
 
This requirement is based on the current permit.  
This requirement is based on the current permit.  


pH  
pH  


The current NPDES permit established a minimum discharge limit of 6.0 standard units and a maximum discharge limit of 9.0 standard units for pH at Internal Outfall 201 (former 01B). These limits are based on 40 CFR 423.12(b)(1)(BPT) and are retained from the current permit.  
The current NPDES permit established a minimum discharge limit of 6.0 standard  
 
units and a maximum discharge limit of 9.0 standard units for pH at Internal  
 
Outfall 201 (former 01B). These limits are based on 40 CFR 423.12(b)(1)(BPT)  
 
and are retained from the current permit.  
 
Internal Outfall 301 (Former 01C) - Filter Flush System This outfall is the intermittent internal discharge of filter flush water from
 
the primary water treatment system to Final Outfall 001 via the turbine
 
condenser cooling system. The primary water treatment system filters river
 
water for various plant uses. The filters of this system are flushed
 
periodically with untreated river water to remove solids trapped in the filter
 
beds. The effluent limitations proposed for Internal Outfall 301 in the draft
 
LPDES permit are as follows:
 
Parameter  Monthly  Daily Average Maximum    Flow, MGD  N/A  Report
 
Clarifying Agents Used
 
Flow
 
The current NPDES permit required the daily average flow and daily maximum
 
flow to be reported at Internal Outfall 301 (former 01C). Since the flow to


Internal Outfall 301 (Former 01C) - Filter Flush System This outfall is the intermittent internal discharge of filter flush water from the primary water treatment system to Final Outfall 001 via the turbine condenser cooling system. The primary water treatment system filters river water for various plant uses. The filters of this system are flushed periodically with untreated river water to remove solids trapped in the filter beds. The effluent limitations proposed for Internal Outfall 301 in the draft LPDES permit are as follows:
this outfall is intermittent, the daily maximum flow is to be reported.   
Parameter  Monthly  Daily Average Maximum    Flow, MGD  N/A Report Clarifying Agents Used Flow


The current NPDES permit required the daily average flow and daily maximum flow to be reported at Internal Outfall 301 (former 01C). Since the flow to this outfall is intermittent, the daily maximum flow is to be reported.
Discharge flow is totalized when the discharge occurs.  
Discharge flow is totalized when the discharge occurs.  


Clarifying Agents Used  
Clarifying Agents Used  


The current NPDES permit specified the recording of the monthly amount of clarifying agents used at Internal Outfall 301 (former 01C). This requirement is continued from the current permit. However, no reporting on Discharge Monitoring Reports (DMRs) will be required. The permittee is required to keep these monthly records onsite, available to DEQ or EPA anytime or upon request.
The current NPDES permit specified the recording of the monthly amount of  
The draft permit establishes a permit requirement for the onsite maintenance of this information in Part I.
 
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 78 Internal Outfall 401 (Former 01D) - Low Volume Wastewaters This outfall is the intermittent internal discharge of steam generator blowdown and other low volume wastewaters to Final Outfall 001 via the turbine condenser cooling system. In addition to steam generator blowdown, low volume wastewater from other sources as defined in 40 CFR 423 are discharged from this outfall. The effluent limitations proposed for Internal Outfall 401 in the draft LPDES permit are as follows:
clarifying agents used at Internal Outfall 301 (former 01C). This requirement  
Parameter  Monthly  Daily Average Maximum  mg/L    mg/L Flow, MGD  N/A  Report Total Suspended Solids N/A  100 Oil and Grease  N/A  20 pH, standard units 6.0 (min) 9.0 (max)
 
is continued from the current permit. However, no reporting on Discharge  
 
Monitoring Reports (DMRs) will be required. The permittee is required to keep  
 
these monthly records onsite, available to DEQ or EPA anytime or upon request.  
 
The draft permit establishes a permit requirement for the onsite maintenance  
 
of this information in Part I.
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 78 Internal Outfall 401 (Former 01D) - Low Volume Wastewaters
 
This outfall is the intermittent internal discharge of steam generator  
 
blowdown and other low volume wastewaters to Final Outfall 001 via the turbine  
 
condenser cooling system. In addition to steam generator blowdown, low volume  
 
wastewater from other sources as defined in 40 CFR 423 are discharged from  
 
this outfall. The effluent limitations proposed for Internal Outfall 401 in  
 
the draft LPDES permit are as follows:  
 
Parameter  Monthly  Daily Average Maximum  mg/L    mg/L Flow, MGD  N/A  Report Total Suspended Solids N/A  100 Oil and Grease  N/A  20 pH, standard units 6.0 (min) 9.0 (max)  
 
Flow  
Flow  


The current NPDES permit requires the daily average flow and daily maximum flow to be reported at Internal Outfall 401 (former 01D). Since the flow to this outfall is intermittent, only the daily maximum flow is to be reported.
The current NPDES permit requires the daily average flow and daily maximum  
Discharge flow is totalized when the discharge occurs during periods of blowdown. When low volume wastewaters are discharged, the flow must be estimated.  
 
flow to be reported at Internal Outfall 401 (former 01D). Since the flow to  
 
this outfall is intermittent, only the daily maximum flow is to be reported.
 
Discharge flow is totalized when the discharge occurs during periods of  
 
blowdown. When low volume wastewaters are discharged, the flow must be  
 
estimated.  


Total Suspended Solids  
Total Suspended Solids  


The current NPDES permit established a daily average discharge limit of 30 mg/l and a daily maximum discharge limit of 100 mg/l for total suspended solids at Internal Outfall 401 (former 01D). Since the flow to this outfall is intermittent the daily maximum limitation is continued from the current permit. This limit are based on 40 CFR 423.12(b)(3)(BPT).  
The current NPDES permit established a daily average discharge limit of 30  
 
mg/l and a daily maximum discharge limit of 100 mg/l for total suspended  
 
solids at Internal Outfall 401 (former 01D). Since the flow to this outfall  
 
is intermittent the daily maximum limitation is continued from the current  
 
permit. This limit are based on 40 CFR 423.12(b)(3)(BPT).  


Oil and Grease  
Oil and Grease  


This draft permit establishes a daily maximum discharge limit of 20 mg/l for oil and grease at Internal Outfall 401. This limit is based on 40 CFR 423.12(b)(3)(BPT).  
This draft permit establishes a daily maximum discharge limit of 20 mg/l for  
 
oil and grease at Internal Outfall 401. This limit is based on 40 CFR  
 
423.12(b)(3)(BPT).  


pH  
pH  


The current NPDES permit established a minimum discharge limit of 6.0 standard units and a maximum discharge limit of 9.0 standard units for pH at Internal Outfall 401 (former 01D). These limits are based on 40 CFR 423.12(b)(1)(BPT) and are retained from the current permit.
The current NPDES permit established a minimum discharge limit of 6.0 standard  


Internal Outfall 501 - Auxiliary Component Cooling Water Basin A Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 79 Plant systems have been modified to allow effluent from the auxiliary component cooling water basins to be directly discharged via the turbine condenser cooling system, leaving the facility through Final Outfall 001.  
units and a maximum discharge limit of 9.0 standard units for pH at Internal
 
Outfall 401 (former 01D). These limits are based on 40 CFR 423.12(b)(1)(BPT)
 
and are retained from the current permit.
 
Internal Outfall 501 - Auxiliary Component Cooling Water Basin A
 
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 79 Plant systems have been modified to allow effluent from the auxiliary  
 
component cooling water basins to be directly discharged via the turbine  
 
condenser cooling system, leaving the facility through Final Outfall 001.  
 
This new outfall monitors the intermittent internal discharge from Auxiliary
 
Component Cooling Water Basin A to Final Outfall 001 via the turbine condenser
 
cooling system. Low volume wastewater sources contributing to the flow
 
monitored at this outfall include, but are not limited to, auxiliary component
 
cooling water, component cooling water, Mississippi River water, and
 
stormwater. The effluent limitations proposed for Internal Outfall 501 in the
 
draft LPDES permit are as follows:
 
Parameter  Monthly  Daily Average Maximum  mg/L    mg/L Flow, MGD  N/A  Report Total Organic Carbon N/A  50 Total Suspended Solids N/A  100 Oil and Grease  N/A  20 pH, standard units 6.0 (min) 9.0 (max)


This new outfall monitors the intermittent internal discharge from Auxiliary Component Cooling Water Basin A to Final Outfall 001 via the turbine condenser cooling system. Low volume wastewater sources contributing to the flow monitored at this outfall include, but are not limited to, auxiliary component cooling water, component cooling water, Mississippi River water, and stormwater. The effluent limitations proposed for Internal Outfall 501 in the draft LPDES permit are as follows:
Parameter  Monthly  Daily Average Maximum  mg/L    mg/L Flow, MGD  N/A  Report Total Organic Carbon N/A  50 Total Suspended Solids N/A  100 Oil and Grease  N/A  20 pH, standard units 6.0 (min) 9.0 (max)
Flow  
Flow  


This draft permit requires the daily maximum flow to be reported at Internal Outfall 501 by estimating using best engineering judgement. This requirement is based on 40 CFR 122.44(i)(1)(iii).  
This draft permit requires the daily maximum flow to be reported at Internal  
 
Outfall 501 by estimating using best engineering judgement. This requirement  
 
is based on 40 CFR 122.44(i)(1)(iii).  


Total Organic Carbon  
Total Organic Carbon  


This draft permit establishes a daily maximum discharge limit of 50 mg/l for total organic carbon at Internal Outfall 501. Total Organic Carbon is established because stormwater could be discharged via this outfall. The limitation is based on BPJ in accordance with this Office's guidance on stormwater, letter dated 6/17/87, from J. Dale Givens (LDEQ) to Myron Knudson (EPA Region 6). Total Suspended Solids  
This draft permit establishes a daily maximum discharge limit of 50 mg/l for  
 
total organic carbon at Internal Outfall 501. Total Organic Carbon is  
 
established because stormwater could be discharged via this outfall. The  
 
limitation is based on BPJ in accordance with this Office's guidance on  
 
stormwater, letter dated 6/17/87, from J. Dale Givens (LDEQ) to Myron Knudson  
 
(EPA Region 6).
Total Suspended Solids  
 
This draft permit establishes a daily maximum discharge limit of 100 mg/l for
 
total suspended solids at Internal Outfall 501. This limit is based on 40 CFR
 
423.12(b)(3)(BPT). When the circulating water flow test is performed, TSS is
 
not limited due to Mississippi River water being used for this test. This


This draft permit establishes a daily maximum discharge limit of 100 mg/l for total suspended solids at Internal Outfall 501. This limit is based on 40 CFR 423.12(b)(3)(BPT). When the circulating water flow test is performed, TSS is not limited due to Mississippi River water being used for this test. This test is infrequently done, historically only during times of refueling outages.  
test is infrequently done, historically only during times of refueling  
 
outages.  


Oil and Grease  
Oil and Grease  


Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 80  This draft permit establishes a daily maximum discharge limit of 20 mg/l for oil and grease at Internal Outfall 501. This limit is based on 40 CFR 423.12(b)(3)(BPT).  
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 80  This draft permit establishes a daily maximum discharge limit of 20 mg/l for  
 
oil and grease at Internal Outfall 501. This limit is based on 40 CFR  
 
423.12(b)(3)(BPT).  


pH  
pH  


This draft permit establishes a minimum discharge limit of 6.0 standard units and a maximum discharge limit of 9.0 standard units for pH at Internal Outfall 501. These limits are based on 40 CFR 423.12(b)(1)(BPT).  
This draft permit establishes a minimum discharge limit of 6.0 standard units  
 
and a maximum discharge limit of 9.0 standard units for pH at Internal Outfall  
 
501. These limits are based on 40 CFR 423.12(b)(1)(BPT).  
 
Internal Outfall 601 - Auxiliary Component Cooling Water Basin B
 
Plant systems have been modified to allow effluent from the auxiliary
 
component cooling water basins to be directly discharged via the turbine
 
condenser cooling system, leaving the facility through Final Outfall 001.
 
This new outfall monitors the intermittent internal discharge from Auxiliary
 
Component Cooling Water Basin B to Final Outfall 001 via the turbine condenser
 
cooling system. Low volume wastewater sources contributing to the flow
 
monitored at this outfall include, but are not limited to, auxiliary component
 
cooling water, component cooling water, Mississippi River water, and
 
stormwater. The effluent limitations proposed for Internal Outfall 601 in the


Internal Outfall 601 - Auxiliary Component Cooling Water Basin B Plant systems have been modified to allow effluent from the auxiliary component cooling water basins to be directly discharged via the turbine condenser cooling system, leaving the facility through Final Outfall 001.  
draft LPDES permit are as follows: Parameter  Monthly  Daily Average Maximum  mg/L    mg/L Flow, MGD  N/A  Report Total Organic Carbon N/A  50 Total Suspended Solids N/A  100 Oil and Grease  N/A  20 pH, standard units 6.0 (min) 9.0 (max)


This new outfall monitors the intermittent internal discharge from Auxiliary Component Cooling Water Basin B to Final Outfall 001 via the turbine condenser cooling system. Low volume wastewater sources contributing to the flow monitored at this outfall include, but are not limited to, auxiliary component cooling water, component cooling water, Mississippi River water, and stormwater. The effluent limitations proposed for Internal Outfall 601 in the draft LPDES permit are as follows: Parameter  Monthly  Daily Average Maximum  mg/L    mg/L Flow, MGD  N/A  Report Total Organic Carbon N/A  50 Total Suspended Solids N/A  100 Oil and Grease  N/A  20 pH, standard units 6.0 (min) 9.0 (max)
Flow  
Flow  


This draft permit requires the daily maximum flow to be reported at Internal Outfall 601 by estimating using best engineering judgement. This requirement is based on 40 CFR 122.44(i)(1)(iii).  
This draft permit requires the daily maximum flow to be reported at Internal  
 
Outfall 601 by estimating using best engineering judgement. This requirement  
 
is based on 40 CFR 122.44(i)(1)(iii).  


Total Organic Carbon  
Total Organic Carbon  


This draft permit establishes a daily maximum discharge limit of 50 mg/l for total organic carbon at Internal Outfall 501. Total Organic Carbon is established because stormwater could be discharged via this outfall. The limitation is based on BPJ in accordance with this Office's guidance on stormwater, letter dated 6/17/87, from J. Dale Givens (LDEQ) to Myron Knudson (EPA Region 6). Total Suspended Solids  
This draft permit establishes a daily maximum discharge limit of 50 mg/l for  
 
total organic carbon at Internal Outfall 501. Total Organic Carbon is  
 
established because stormwater could be discharged via this outfall. The  
 
limitation is based on BPJ in accordance with this Office's guidance on  
 
stormwater, letter dated 6/17/87, from J. Dale Givens (LDEQ) to Myron Knudson  
 
(EPA Region 6).
Total Suspended Solids  
 
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
 
LA0007374


Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 81  This draft permit establishes a daily maximum discharge limit of 100 mg/l for total suspended solids at Internal Outfall 601. This limit is based on 40 CFR 423.12(b)(3)(BPT). When the circulating water flow test is performed, TSS is not limited due to Mississippi River water being used for this test. This test is infrequently done, historically only during times of refueling outages.  
Page 81  This draft permit establishes a daily maximum discharge limit of 100 mg/l for  
 
total suspended solids at Internal Outfall 601. This limit is based on 40 CFR  
 
423.12(b)(3)(BPT). When the circulating water flow test is performed, TSS is  
 
not limited due to Mississippi River water being used for this test. This  
 
test is infrequently done, historically only during times of refueling  
 
outages.  


Oil and Grease  
Oil and Grease  


This draft permit establishes a daily maximum discharge limit of 20 mg/l for oil and grease at Internal Outfall 601. This limit is based on 40 CFR 423.12(b)(3)(BPT).  
This draft permit establishes a daily maximum discharge limit of 20 mg/l for  
 
oil and grease at Internal Outfall 601. This limit is based on 40 CFR  
 
423.12(b)(3)(BPT).  


pH  
pH  


This draft permit establishes a minimum discharge limit of 6.0 standard units and a maximum discharge limit of 9.0 standard units for pH at Internal Outfall 601. These limits are based on 40 CFR 423.12(b)(1)(BPT).  
This draft permit establishes a minimum discharge limit of 6.0 standard units  
 
and a maximum discharge limit of 9.0 standard units for pH at Internal Outfall  
 
601. These limits are based on 40 CFR 423.12(b)(1)(BPT).  


Internal Outfall 701 - Dry Cooling Tower Sump #1 Plant systems have been modified to allow effluent from the dry cooling tower sumps to be directly discharged via the turbine condenser cooling system, leaving the facility through Final Outfall 001.  
Internal Outfall 701 - Dry Cooling Tower Sump #1
 
Plant systems have been modified to allow effluent from the dry cooling tower  
 
sumps to be directly discharged via the turbine condenser cooling system,  
 
leaving the facility through Final Outfall 001.  
 
This outfall monitors the intermittent internal discharge which is comprised
 
of greater than 85% stormwater, in addition to cooling tower blowdown and low
 
volume wastewaters from Dry Cooling Tower Sump #1 to Final Outfall 001 via the
 
turbine condenser cooling system or to Final Outfall 004 via the plant
 
drainage ditches. In addition to the wet cooling tower blowdown, low volume
 
wastewater from various sources as defined in 40 CFR 423 are discharged from
 
this outfall. Low volume wastewater sources contributing to this monitored
 
flow include, but are not limited to, wet cooling tower leakage, auxiliary
 
component cooling water, component cooling water, and stormwater. Previously
 
monitored effluent from the Yard Oil Separator System (Internal Outfall 104)
 
is infrequently discharged through this outfall as a result of maintenance
 
activities. The effluent limitations proposed for Internal Outfall 701 in the
 
draft LPDES permit are as follows:
 
Parameter  Monthly  Daily Average Maximum  mg/L    mg/L Flow, MGD  N/A  Report Total Organic Carbon N/A  50 Total Suspended Solids N/A  100 Oil and Grease  N/A  20 Free Available Chlorine N/A  0.5 Chromium, Total  N/A  0.2 Zinc, Total  N/A  1.0 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
 
LA0007374
 
Page 82  pH, standard units 6.0 (min) 9.0 (max)


This outfall monitors the intermittent internal discharge which is comprised of greater than 85% stormwater, in addition to cooling tower blowdown and low volume wastewaters from Dry Cooling Tower Sump #1 to Final Outfall 001 via the turbine condenser cooling system or to Final Outfall 004 via the plant drainage ditches. In addition to the wet cooling tower blowdown, low volume wastewater from various sources as defined in 40 CFR 423 are discharged from this outfall. Low volume wastewater sources contributing to this monitored flow include, but are not limited to, wet cooling tower leakage, auxiliary component cooling water, component cooling water, and stormwater. Previously monitored effluent from the Yard Oil Separator System (Internal Outfall 104) is infrequently discharged through this outfall as a result of maintenance activities. The effluent limitations proposed for Internal Outfall 701 in the draft LPDES permit are as follows:
Parameter  Monthly  Daily Average Maximum  mg/L    mg/L Flow, MGD  N/A  Report Total Organic Carbon N/A  50 Total Suspended Solids N/A  100 Oil and Grease  N/A  20 Free Available Chlorine N/A  0.5 Chromium, Total  N/A  0.2 Zinc, Total  N/A  1.0 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 82  pH, standard units 6.0 (min) 9.0 (max)
Flow  
Flow  


This draft permit requires the daily maximum flow to be reported at Internal Outfall 701 by estimating using best engineering judgement. This requirement is based on 40 CFR 122.44(i)(1)(iii).  
This draft permit requires the daily maximum flow to be reported at Internal  
 
Outfall 701 by estimating using best engineering judgement. This requirement  
 
is based on 40 CFR 122.44(i)(1)(iii).  


Total Organic Carbon  
Total Organic Carbon  


This draft permit establishes a daily maximum discharge limit of 50 mg/l for total organic carbon at Internal Outfall 501. Total Organic Carbon is established because stormwater is discharged via this outfall. The limitation is based on BPJ in accordance with this Office's guidance on stormwater, letter dated 6/17/87, from J. Dale Givens (LDEQ) to Myron Knudson (EPA Region 6).  
This draft permit establishes a daily maximum discharge limit of 50 mg/l for  
 
total organic carbon at Internal Outfall 501. Total Organic Carbon is  
 
established because stormwater is discharged via this outfall. The limitation  
 
is based on BPJ in accordance with this Office's guidance on stormwater,  
 
letter dated 6/17/87, from J. Dale Givens (LDEQ) to Myron Knudson (EPA Region  
 
6).  


Total Suspended Solids  
Total Suspended Solids  


This draft permit establishes a daily maximum discharge limit of 100 mg/l for total suspended solids at Internal Outfall 701. This limit is based on 40 CFR 423.12(b)(3)(BPT).  
This draft permit establishes a daily maximum discharge limit of 100 mg/l for  
 
total suspended solids at Internal Outfall 701. This limit is based on 40 CFR  
 
423.12(b)(3)(BPT).  


Oil and Grease  
Oil and Grease  


This draft permit establishes a daily maximum discharge limit of 20 mg/l for oil and grease at Internal Outfall 701. This limit is based on 40 CFR 423.12(b)(3)(BPT).  
This draft permit establishes a daily maximum discharge limit of 20 mg/l for  
 
oil and grease at Internal Outfall 701. This limit is based on 40 CFR  
 
423.12(b)(3)(BPT).  


Free Available Chlorine  
Free Available Chlorine  


This draft permit establishes a daily maximum discharge limit of 0.5 mg/l for free available chlorine at Internal Outfall 701, when the discharge includes cooling tower blowdown. This limit is based on 40 CFR 423.13(d)(1)(BAT).  
This draft permit establishes a daily maximum discharge limit of 0.5 mg/l for  
 
free available chlorine at Internal Outfall 701, when the discharge includes  
 
cooling tower blowdown. This limit is based on 40 CFR 423.13(d)(1)(BAT).  


Total Chromium  
Total Chromium  


This draft permit establishes a daily maximum discharge limit of 0.2 mg/l for total chromium at Internal Outfall 701, when the discharge includes cooling tower blowdown. This limit is based on 40 CFR 423.13(d)(1)(BAT).  
This draft permit establishes a daily maximum discharge limit of 0.2 mg/l for  
 
total chromium at Internal Outfall 701, when the discharge includes cooling  
 
tower blowdown. This limit is based on 40 CFR 423.13(d)(1)(BAT).  


Total Zinc  
Total Zinc  


This draft permit establishes a daily maximum discharge limit of 1.0 mg/l for total zinc at Internal Outfall 701, when the discharge includes cooling tower blowdown. This limit is based on 40 CFR 423.13(d)(1)(BAT).  
This draft permit establishes a daily maximum discharge limit of 1.0 mg/l for  
 
total zinc at Internal Outfall 701, when the discharge includes cooling tower  
 
blowdown. This limit is based on 40 CFR 423.13(d)(1)(BAT).  


pH  
pH  


Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 83  This draft permit establishes a minimum discharge limit of 6.0 standard units and a maximum discharge limit of 9.0 standard units for pH at Internal Outfall 701. These limits are based on 40 CFR 423.12(b)(1)(BPT).  
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 83  This draft permit establishes a minimum discharge limit of 6.0 standard units  
 
and a maximum discharge limit of 9.0 standard units for pH at Internal Outfall  
 
701. These limits are based on 40 CFR 423.12(b)(1)(BPT).  
 
Internal Outfall 801 - Dry Cooling Tower Sump #2 Plant systems have been modified to allow effluent from the dry cooling tower
 
sumps to be directly discharged via the turbine condenser cooling system,
 
leaving the facility through Final Outfall 001.
 
This outfall monitors the intermittent internal discharge which is comprised
 
of greater than 85% stormwater, in addition to cooling tower blowdown and low
 
volume wastewaters from Dry Cooling Tower Sump #2 to Final Outfall 001 via the
 
turbine condenser cooling system or to Final Outfall 004 via the plant
 
drainage ditches. In addition to the wet cooling tower blowdown, low volume
 
wastewater from various sources as defined in 40 CFR 423 are discharged from
 
this outfall. Low volume wastewater sources contributing to this monitored
 
flow include, but are not limited to, wet cooling tower leakage, auxiliary
 
component cooling water, component cooling water, and stormwater. Previously
 
monitored effluent from the Yard Oil Separator System (Internal Outfall 104)
 
is infrequently discharged through this outfall as a result of maintenance
 
activities. The effluent limitations proposed for Internal Outfall 801 in the
 
draft LPDES permit are as follows:
 
Parameter  Monthly  Daily Average Maximum  mg/L    mg/L Flow, MGD  N/A  Report Total Organic Carbon N/A  50 Total Suspended Solids N/A  100 Oil and Grease  N/A  20 Free Available Chlorine N/A  0.5 Chromium, Total  N/A  0.2 Zinc, Total  N/A  1.0 pH, standard units 6.0 (min) 9.0 (max)


Internal Outfall 801 - Dry Cooling Tower Sump #2 Plant systems have been modified to allow effluent from the dry cooling tower sumps to be directly discharged via the turbine condenser cooling system, leaving the facility through Final Outfall 001.
This outfall monitors the intermittent internal discharge which is comprised of greater than 85% stormwater, in addition to cooling tower blowdown and low volume wastewaters from Dry Cooling Tower Sump #2 to Final Outfall 001 via the turbine condenser cooling system or to Final Outfall 004 via the plant drainage ditches. In addition to the wet cooling tower blowdown, low volume wastewater from various sources as defined in 40 CFR 423 are discharged from this outfall. Low volume wastewater sources contributing to this monitored flow include, but are not limited to, wet cooling tower leakage, auxiliary component cooling water, component cooling water, and stormwater. Previously monitored effluent from the Yard Oil Separator System (Internal Outfall 104) is infrequently discharged through this outfall as a result of maintenance activities. The effluent limitations proposed for Internal Outfall 801 in the draft LPDES permit are as follows:
Parameter  Monthly  Daily Average Maximum  mg/L    mg/L Flow, MGD  N/A  Report Total Organic Carbon N/A  50 Total Suspended Solids N/A  100 Oil and Grease  N/A  20 Free Available Chlorine N/A  0.5 Chromium, Total  N/A  0.2 Zinc, Total  N/A  1.0 pH, standard units 6.0 (min) 9.0 (max)
Flow  
Flow  


This draft permit requires the daily maximum flow to be reported at Internal Outfall 801 by estimating using best engineering judgement. This requirement is based on 40 CFR 122.44(i)(1)(iii).  
This draft permit requires the daily maximum flow to be reported at Internal  
 
Outfall 801 by estimating using best engineering judgement. This requirement  
 
is based on 40 CFR 122.44(i)(1)(iii).  


Total Organic Carbon  
Total Organic Carbon  


This draft permit establishes a daily maximum discharge limit of 50 mg/l for total organic carbon at Internal Outfall 501. Total Organic Carbon is established because stormwater is discharged via this outfall. The limitation is based on BPJ in accordance with this Office's guidance on stormwater, letter dated 6/17/87, from J. Dale Givens (LDEQ) to Myron Knudson (EPA Region 6).
This draft permit establishes a daily maximum discharge limit of 50 mg/l for  
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 84  Total Suspended Solids
 
total organic carbon at Internal Outfall 501. Total Organic Carbon is  
 
established because stormwater is discharged via this outfall. The limitation  


This draft permit establishes a daily maximum discharge limit of 100 mg/l for total suspended solids at Internal Outfall 801. This limit is based on 40 CFR 423.12(b)(3)(BPT).  
is based on BPJ in accordance with this Office's guidance on stormwater,
 
letter dated 6/17/87, from J. Dale Givens (LDEQ) to Myron Knudson (EPA Region
 
6).
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
 
LA0007374
 
Page 84  Total Suspended Solids
 
This draft permit establishes a daily maximum discharge limit of 100 mg/l for  
 
total suspended solids at Internal Outfall 801. This limit is based on 40 CFR  
 
423.12(b)(3)(BPT).  


Oil and Grease  
Oil and Grease  


This draft permit establishes a daily maximum discharge limit of 20 mg/l for oil and grease at Internal Outfall 801. This limit is based on 40 CFR 423.12(b)(3)(BPT).  
This draft permit establishes a daily maximum discharge limit of 20 mg/l for  
 
oil and grease at Internal Outfall 801. This limit is based on 40 CFR  
 
423.12(b)(3)(BPT).  


Free Available Chlorine  
Free Available Chlorine  


This draft permit establishes a daily maximum discharge limit of 0.5 mg/l for free available chlorine at Internal Outfall 801, when the discharge includes cooling tower blowdown. This limit is based on 40 CFR 423.13(d)(1)(BAT).
This draft permit establishes a daily maximum discharge limit of 0.5 mg/l for  
 
free available chlorine at Internal Outfall 801, when the discharge includes  
 
cooling tower blowdown. This limit is based on 40 CFR 423.13(d)(1)(BAT).
Total Chromium  
Total Chromium  


This draft permit establishes a daily maximum discharge limit of 0.2 mg/l for total chromium at Internal Outfall 801, when the discharge includes cooling tower blowdown. These limits are based on 40 CFR 423.13(d)(1)(BAT).  
This draft permit establishes a daily maximum discharge limit of 0.2 mg/l for  
 
total chromium at Internal Outfall 801, when the discharge includes cooling  
 
tower blowdown. These limits are based on 40 CFR 423.13(d)(1)(BAT).  


Total Zinc  
Total Zinc  


This draft permit establishes a daily maximum discharge limit of 1.0 mg/l for total zinc at Internal Outfall 801, when the discharge includes cooling tower blowdown. These limits are based on 40 CFR 423.13(d)(1)(BAT).  
This draft permit establishes a daily maximum discharge limit of 1.0 mg/l for  
 
total zinc at Internal Outfall 801, when the discharge includes cooling tower  
 
blowdown. These limits are based on 40 CFR 423.13(d)(1)(BAT).  


pH  
pH  


This draft permit establishes a minimum discharge limit of 6.0 standard units and a maximum discharge limit of 9.0 standard units for pH at Internal Outfall 801. These limits are based on 40 CFR 423.12(b)(1)(BPT).  
This draft permit establishes a minimum discharge limit of 6.0 standard units  
 
and a maximum discharge limit of 9.0 standard units for pH at Internal Outfall  
 
801. These limits are based on 40 CFR 423.12(b)(1)(BPT).  
 
Internal Outfall 901 - Metal Cleaning Wastewater
 
This new mobile outfall monitors the intermittent internal discharge of metal
 
cleaning wastewaters from internal components of plant equipment to Final
 
Outfall 001 via the turbine condenser cooling system. Metal cleaning
 
wastewaters (both chemical and non-chemical) result from the cleaning
 
washes/rinses of various plant equipment components including, but not limited
 
to, the steam generator and the cooling water heat exchangers and piping. The
 
effluent limitations proposed for Internal Outfall 901 in the draft LPDES
 
permit are as follows:
 
Parameter  Monthly  Daily Average Maximum  mg/L    mg/L Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
 
LA0007374
 
Page 85  Flow, MGD  N/A  Report Total Suspended Solids N/A  100 Oil and Grease  N/A  20 Copper, Total  N/A  1.0 Iron, Total  N/A  1.0 pH, standard units 6.0 (min) 9.0 (max)


Internal Outfall 901 - Metal Cleaning Wastewater This new mobile outfall monitors the intermittent internal discharge of metal cleaning wastewaters from internal components of plant equipment to Final Outfall 001 via the turbine condenser cooling system. Metal cleaning wastewaters (both chemical and non-chemical) result from the cleaning washes/rinses of various plant equipment components including, but not limited to, the steam generator and the cooling water heat exchangers and piping. The effluent limitations proposed for Internal Outfall 901 in the draft LPDES permit are as follows:
Parameter  Monthly  Daily Average Maximum  mg/L    mg/L Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 85  Flow, MGD  N/A  Report Total Suspended Solids N/A  100 Oil and Grease  N/A  20 Copper, Total  N/A  1.0 Iron, Total  N/A  1.0 pH, standard units 6.0 (min) 9.0 (max)
Flow  
Flow  


This draft permit requires the daily maximum flow to be reported at Internal Outfall 901 by estimating using best engineering judgement. This requirement is based on 40 CFR 122.44(i)(1)(iii).  
This draft permit requires the daily maximum flow to be reported at Internal  
 
Outfall 901 by estimating using best engineering judgement. This requirement  
 
is based on 40 CFR 122.44(i)(1)(iii).  


Total Suspended Solids  
Total Suspended Solids  


This draft permit establishes a daily maximum discharge limit of 100 mg/l for total suspended solids at Internal Outfall 901. These limits are based on 40 CFR 423.12(b)(5)(BPT).  
This draft permit establishes a daily maximum discharge limit of 100 mg/l for  
 
total suspended solids at Internal Outfall 901. These limits are based on 40  
 
CFR 423.12(b)(5)(BPT).  


Oil and Grease  
Oil and Grease  


This draft permit establishes a daily maximum discharge limit of 20 mg/l for oil and grease at Internal Outfall 901. These limits are based on 40 CFR 423.12(b)(5)(BPT).  
This draft permit establishes a daily maximum discharge limit of 20 mg/l for  
 
oil and grease at Internal Outfall 901. These limits are based on 40 CFR  
 
423.12(b)(5)(BPT).  


Total Copper  
Total Copper  


This draft permit establishes a daily maximum discharge limit of 1.0 mg/l for total copper at Internal Outfall 901. These limits are based on 40 CFR 423.12(b)(5)(BPT).  
This draft permit establishes a daily maximum discharge limit of 1.0 mg/l for  
 
total copper at Internal Outfall 901. These limits are based on 40 CFR  
 
423.12(b)(5)(BPT).  


Total Iron  
Total Iron  


This draft permit establishes a daily maximum discharge limit of 1.0 mg/l for total iron at Internal Outfall 901. These limits are based on 40 CFR 423.12(b)(5)(BPT).  
This draft permit establishes a daily maximum discharge limit of 1.0 mg/l for  
 
total iron at Internal Outfall 901. These limits are based on 40 CFR  
 
423.12(b)(5)(BPT).  


pH  
pH  


This draft permit establishes a minimum discharge limit of 6.0 standard units and a maximum discharge limit of 9.0 standard units for pH at Internal Outfall 901. These limits are based on 40 CFR 423.12(b)(1)(BPT).  
This draft permit establishes a minimum discharge limit of 6.0 standard units  
 
and a maximum discharge limit of 9.0 standard units for pH at Internal Outfall  
 
901. These limits are based on 40 CFR 423.12(b)(1)(BPT).  
 
Outfall 004 - Stormwater
 
Outfall 004 is a new outfall that consolidates Outfalls 04A and 04B from the
 
current NPDES Permit LA0007374. Most of the effluent monitored at this
 
outfall is 85% stormwater runoff. Besides stormwater, potable water from the
 
fire water system, maintenance wastewaters including, but not limited to:
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
 
LA0007374
 
Page 86  hydrostatic test water, air conditioning condensate, low volume wastewaters
 
from various sources as defined in 40 CFR 423, and previously monitored
 
effluents exit the facility via Outfall 004. Low volume sources contributing
 
wastewater to this outfall include, but are not limited to, reverse osmosis
 
reject water and demineralized water. The plant drainage ditch system
 
receives treated discharge from the yard oil separator system (Internal
 
Outfall 104), untreated vehicle wash wastewater (Internal Outfall 204) and
 
during maintenance activities discharges from Dry Cooling Tower Sump #1
 
(Internal Outfall 701) and Dry Cooling Tower Sump #2 (Internal Outfall 801). 
 
The effluent limitations proposed for Outfall 004 in the draft LPDES permit
 
are as follows:
 
Parameter  Monthly  Daily Average Maximum  mg/L    mg/L Flow, MGD  N/A  Report Total Organic Carbon N/A  50 Total Suspended Solids N/A  100 Oil and Grease  N/A  15 pH, standard units 6.0 (min) 9.0 (max)


Outfall 004 - Stormwater Outfall 004 is a new outfall that consolidates Outfalls 04A and 04B from the current NPDES Permit LA0007374. Most of the effluent monitored at this outfall is 85% stormwater runoff. Besides stormwater, potable water from the fire water system, maintenance wastewaters including, but not limited to:
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 86  hydrostatic test water, air conditioning condensate, low volume wastewaters from various sources as defined in 40 CFR 423, and previously monitored effluents exit the facility via Outfall 004. Low volume sources contributing wastewater to this outfall include, but are not limited to, reverse osmosis reject water and demineralized water. The plant drainage ditch system receives treated discharge from the yard oil separator system (Internal Outfall 104), untreated vehicle wash wastewater (Internal Outfall 204) and during maintenance activities discharges from Dry Cooling Tower Sump #1 (Internal Outfall 701) and Dry Cooling Tower Sump #2 (Internal Outfall 801).
The effluent limitations proposed for Outfall 004 in the draft LPDES permit are as follows:
Parameter  Monthly  Daily Average Maximum  mg/L    mg/L Flow, MGD  N/A  Report Total Organic Carbon N/A  50 Total Suspended Solids N/A  100 Oil and Grease  N/A  15 pH, standard units 6.0 (min) 9.0 (max)
Flow  
Flow  


This draft permit requires the daily maximum flow to be reported at Outfall 004 by estimating using best engineering judgement. This requirement is based on 40 CFR 122.44(i)(1)(iii) and the current permit.  
This draft permit requires the daily maximum flow to be reported at Outfall  
 
004 by estimating using best engineering judgement. This requirement is based  
 
on 40 CFR 122.44(i)(1)(iii) and the current permit.  


Total Organic Carbon  
Total Organic Carbon  


This draft permit establishes a daily maximum discharge limit of 50 mg/l for total organic carbon at Outfall 004. Total Organic Carbon is established because stormwater is discharged via this outfall. The limitation is based on BPJ in accordance with this Office's guidance on stormwater, letter dated 6/17/87, from J. Dale Givens (LDEQ) to Myron Knudson (EPA Region 6). Total Suspended Solids
This draft permit establishes a daily maximum discharge limit of 50 mg/l for  
 
total organic carbon at Outfall 004. Total Organic Carbon is established  
 
because stormwater is discharged via this outfall. The limitation is based on  
 
BPJ in accordance with this Office's guidance on stormwater, letter dated  


This draft permit establishes a daily maximum discharge limit of 100 mg/l for total suspended solids at Outfall 004, when the discharge includes low volume wastewaters as defined by 40 CFR 423 (excludes Mississippi River water that accumulates in the condenser water boxes). This limit is based on 40 CFR 423.12(b)(3)(BPT) and the current permit.  
6/17/87, from J. Dale Givens (LDEQ) to Myron Knudson (EPA Region 6).
Total Suspended Solids
 
This draft permit establishes a daily maximum discharge limit of 100 mg/l for  
 
total suspended solids at Outfall 004, when the discharge includes low volume  
 
wastewaters as defined by 40 CFR 423 (excludes Mississippi River water that  
 
accumulates in the condenser water boxes). This limit is based on 40 CFR  
 
423.12(b)(3)(BPT) and the current permit.  


Oil and Grease  
Oil and Grease  


This draft permit establishes a daily maximum discharge limit of 15 mg/l for oil and grease at Outfall 004. The limitation is based on BPJ in accordance with this Office's guidance on stormwater, letter dated 6/17/87, from J. Dale Givens (LDEQ) to Myron Knudson (EPA Region 6).
This draft permit establishes a daily maximum discharge limit of 15 mg/l for  
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 87 pH  
 
oil and grease at Outfall 004. The limitation is based on BPJ in accordance  
 
with this Office's guidance on stormwater, letter dated 6/17/87, from J. Dale  
 
Givens (LDEQ) to Myron Knudson (EPA Region 6).
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 87 pH  
 
This draft permit establishes a minimum discharge limit of 6.0 standard units
 
and a maximum discharge limit of 9.0 standard units for pH at Outfall 004. 


This draft permit establishes a minimum discharge limit of 6.0 standard units and a maximum discharge limit of 9.0 standard units for pH at Outfall 004.
These limits are based on 40 CFR 423.12(b)(1)(BPT) and the current permit.  
These limits are based on 40 CFR 423.12(b)(1)(BPT) and the current permit.  


Internal Outfall 104 (Formerly 002) - Yard Oil Separator This outfall is currently Outfall 002. It is being redesignated Internal Outfall 104 because it exits the facility through Final Outfall 004 via a plant drainage ditch. It is the intermittent internal discharge from the yard oil separator system. Occasionally monitored effluent from the yard oil separator system is discharged to Dry Cooling Tower Sump #1 (Internal Outfall 701) or Dry Cooling Tower Sump #2 (Internal Outfall 801) as a result of maintenance activities. Wastewater sources contributing to the flow monitored at Outfall 104 include auxiliary boiler blowdown, stormwater, and low volume wastewaters from various sources as defined by 40 CFR 423. Low volume sources contributing wastewater to this outfall include, but are not limited to, secondary water system drains, system leakage, auxiliary boiler sumps, turbine building equipment and floor drains, turbine building floor wash downs, and laboratory drains. The effluent limitations proposed for Internal Outfall 104 in the draft LPDES permit are as follows:
Internal Outfall 104 (Formerly 002) - Yard Oil Separator
Parameter  Monthly  Daily Average Maximum  mg/L    mg/L Flow, MGD  N/A  Report Total Suspended Solids N/A  100 Oil and Grease  N/A  20 pH    6.0 (min) 9.0 (max)
 
This outfall is currently Outfall 002. It is being redesignated Internal  
 
Outfall 104 because it exits the facility through Final Outfall 004 via a  
 
plant drainage ditch. It is the intermittent internal discharge from the yard  
 
oil separator system. Occasionally monitored effluent from the yard oil  
 
separator system is discharged to Dry Cooling Tower Sump #1 (Internal Outfall  
 
701) or Dry Cooling Tower Sump #2 (Internal Outfall 801) as a result of  
 
maintenance activities. Wastewater sources contributing to the flow monitored  
 
at Outfall 104 include auxiliary boiler blowdown, stormwater, and low volume  
 
wastewaters from various sources as defined by 40 CFR 423. Low volume sources  
 
contributing wastewater to this outfall include, but are not limited to,  
 
secondary water system drains, system leakage, auxiliary boiler sumps, turbine  
 
building equipment and floor drains, turbine building floor wash downs, and  
 
laboratory drains. The effluent limitations proposed for Internal Outfall 104  
 
in the draft LPDES permit are as follows:  
 
Parameter  Monthly  Daily Average Maximum  mg/L    mg/L Flow, MGD  N/A  Report Total Suspended Solids N/A  100 Oil and Grease  N/A  20 pH    6.0 (min) 9.0 (max)  
 
Flow  
Flow  


This draft permit requires the daily maximum flow to be reported at Internal Outfall 104 by estimating using best engineering judgement. This requirement is based on 40 CFR 122.44(i)(1)(iii) and the current permit. Total Suspended Solids
This draft permit requires the daily maximum flow to be reported at Internal  


This draft permit establishes a daily maximum discharge limit of 100 mg/l for total suspended solids at Internal Outfall 104. This limit is based on 40 CFR 423.12(b)(3)(BPT) and the current permit.  
Outfall 104 by estimating using best engineering judgement. This requirement
 
is based on 40 CFR 122.44(i)(1)(iii) and the current permit.
Total Suspended Solids
 
This draft permit establishes a daily maximum discharge limit of 100 mg/l for  
 
total suspended solids at Internal Outfall 104. This limit is based on 40 CFR  
 
423.12(b)(3)(BPT) and the current permit.  


Oil and Grease  
Oil and Grease  


This draft permit establishes a daily maximum discharge limit of 20 mg/l for oil and grease at Internal Outfall 104. This limit is based on 40 CFR 423.12(b)(3)(BPT) and the current permit.
This draft permit establishes a daily maximum discharge limit of 20 mg/l for  
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 88 pH  
 
oil and grease at Internal Outfall 104. This limit is based on 40 CFR  
 
423.12(b)(3)(BPT) and the current permit.
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 88 pH  
 
This draft permit establishes a minimum discharge limit of 6.0 standard units
 
and a maximum discharge limit of 9.0 standard units for pH at Outfall 004. 


This draft permit establishes a minimum discharge limit of 6.0 standard units and a maximum discharge limit of 9.0 standard units for pH at Outfall 004.
These limits are based on 40 CFR 423.12(b)(1)(BPT) and the current permit.  
These limits are based on 40 CFR 423.12(b)(1)(BPT) and the current permit.  


Internal Outfall 204 (New Outfall) - Vehicle Wash Wastewater This outfall is the intermittent internal discharge from the area where vehicles will be externally washed. The effluent limitations proposed for Internal Outfall 204 in the draft LPDES permit are as follows:
Internal Outfall 204 (New Outfall) - Vehicle Wash Wastewater
Parameter  Monthly  Daily Average Maximum  mg/L    mg/L Flow, MGD  Report Report Chemical Oxygen Demand 200  300 Total Suspended Solids N/A  45 Oil and Grease  N/A  15 pH    6.0 (min) 9.0 (max)
 
This outfall is the intermittent internal discharge from the area where  
 
vehicles will be externally washed. The effluent limitations proposed for  
 
Internal Outfall 204 in the draft LPDES permit are as follows:  
 
Parameter  Monthly  Daily Average Maximum  mg/L    mg/L Flow, MGD  Report Report Chemical Oxygen Demand 200  300 Total Suspended Solids N/A  45 Oil and Grease  N/A  15 pH    6.0 (min) 9.0 (max)  
 
Flow  
Flow  


This draft permit requires the daily maximum flow to be reported at Internal Outfall 204 by estimating using best engineering judgement. This requirement is based on 40 CFR 122.44(i)(1)(iii). Chemical Oxygen Demand
This draft permit requires the daily maximum flow to be reported at Internal  


This draft permit establishes a monthly average discharge limit of 200 mg/l and a daily maximum discharge limit of 300 mg/l for chemical oxygen demand at Internal Outfall 204. This limit is based on LAG750000, the general permit for exterior vehicle wash wastewater, effective on July 1, 1998.  
Outfall 204 by estimating using best engineering judgement. This requirement
 
is based on 40 CFR 122.44(i)(1)(iii).
Chemical Oxygen Demand
 
This draft permit establishes a monthly average discharge limit of 200 mg/l  
 
and a daily maximum discharge limit of 300 mg/l for chemical oxygen demand at  
 
Internal Outfall 204. This limit is based on LAG750000, the general permit  
 
for exterior vehicle wash wastewater, effective on July 1, 1998.  


Total Suspended Solids  
Total Suspended Solids  


This draft permit establishes a daily maximum discharge limit of 45 mg/l for total suspended solids at Internal Outfall 204. This limit is based on LAG75000, the general permit for exterior vehicle wash wastewater, effective on July 1, 1998.
This draft permit establishes a daily maximum discharge limit of 45 mg/l for  
 
total suspended solids at Internal Outfall 204. This limit is based on  
 
LAG75000, the general permit for exterior vehicle wash wastewater, effective  
 
on July 1, 1998.
Oil and Grease  
Oil and Grease  


This draft permit establishes a daily maximum discharge limit of 15 mg/l for oil and grease at Internal Outfall 204. This limit is based on LAG750000, the general permit for exterior vehicle wash wastewater, effective on July 1, 1998.
This draft permit establishes a daily maximum discharge limit of 15 mg/l for  
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 89  pH
 
oil and grease at Internal Outfall 204. This limit is based on LAG750000, the  


This draft permit establishes a minimum discharge limit of 6.0 standard units and a maximum discharge limit of 9.0 standard units for pH at Internal Outfall 204. This limit is based on LAG75000, the general permit for exterior vehicle wash wastewater, effective on July 1, 1998.  
general permit for exterior vehicle wash wastewater, effective on July 1,
 
1998.
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
 
LA0007374
 
Page 89  pH
 
This draft permit establishes a minimum discharge limit of 6.0 standard units  
 
and a maximum discharge limit of 9.0 standard units for pH at Internal Outfall  
 
204. This limit is based on LAG75000, the general permit for exterior vehicle  
 
wash wastewater, effective on July 1, 1998.  


Soaps and/or Detergents  
Soaps and/or Detergents  


This draft permit specifies an inventory record of soaps and/or detergents following the provision in Part III.C.3. The quantity and types of all soaps and/or detergents used during the sampling month shall be recorded. Records of the quantity and types of soaps and/or detergents used shall be retained for three (3) years. Additionally, a Material Safety Data Sheet for each material used shall be retained. No DMR reporting shall be required.  
This draft permit specifies an inventory record of soaps and/or detergents  
 
following the provision in Part III.C.3. The quantity and types of all soaps  
 
and/or detergents used during the sampling month shall be recorded. Records  
 
of the quantity and types of soaps and/or detergents used shall be retained  
 
for three (3) years. Additionally, a Material Safety Data Sheet for each  
 
material used shall be retained. No DMR reporting shall be required.  
 
Outfall 005 - Energy Education Center Sewage Treatment Plant
 
This outfall is currently permitted by LAG530192  It is the intermittent
 
discharge from the Entergy Energy Education Center sewage treatment plant to
 
40 Arpent Canal. In addition to the sanitary wastewater, a de minimis
 
discharge from the HVAC unit enters the sewage treatment plant. The effluent
 
limitations proposed for Outfall 005 are transferred from the general permit
 
to this draft LPDES permit. The limitations are as follows:
 
Parameter  Monthly  Weekly Average  Average mg/L    mg/L Flow, MGD  N/A  Report
 
BOD5  N/A  45 TSS  N/A  45
 
Fecal Coliform colonies/100 ml N/A  400 pH, Std. Units 6.0 (min)  9.0 (max)
C. WATER QUALITY-BASED EFFLUENT LIMITATIONS
 
Technology-based effluent limitations were screened against state water
 
quality numerical standard based limits by following guidance procedures
 
established in the Permitting Guidance Document for Implementing Louisiana Surface Water Quality Standards
, LDEQ, October 30, 1995. Calculations, results, and documentation are given in Appendix B.
 
The following pollutants received water quality based effluent limits:
 
None Minimum quantification levels (MQL's) for state water quality numerical
 
standards-based effluent limitations are set at the values listed in the Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
 
LA0007374
 
Page 90  Permitting Guidance Document for Implementing Louisiana Surface Water Quality Standards
, LDEQ, October 30, 1995. They are also listed in Part II of the permit.
 
The nearest drinking water intake, St. Charles Parish Number 2, is located on
 
the east bank at 125.1 M.A.H.P., 4.4 miles downstream from the discharge
 
point. According to a fax received on 9/26/96 from Leslie Lemon of the
 
Department of Health and Hospitals, Office of Public Health, there have been
 
no toxic exceedences of drinking water Maximum Contaminant Levels at this
 
drinking water intake. Nearby potable water industrial intakes include Union


Outfall 005 - Energy Education Center Sewage Treatment Plant This outfall is currently permitted by LAG530192  It is the intermittent discharge from the Entergy Energy Education Center sewage treatment plant to 40 Arpent Canal. In addition to the sanitary wastewater, a de minimis discharge from the HVAC unit enters the sewage treatment plant. The effluent limitations proposed for Outfall 005 are transferred from the general permit to this draft LPDES permit. The limitations are as follows:
Carbide Corporation.  
Parameter  Monthly  Weekly Average  Average mg/L    mg/L Flow, MGD  N/A  Report BOD5  N/A  45 TSS  N/A  45 Fecal Coliform colonies/100 ml N/A  400 pH, Std. Units 6.0 (min)  9.0 (max)  C. WATER QUALITY-BASED EFFLUENT LIMITATIONS Technology-based effluent limitations were screened against state water quality numerical standard based limits by following guidance procedures established in the Permitting Guidance Document for Implementing Louisiana Surface Water Quality Standards, LDEQ, October 30, 1995. Calculations, results, and documentation are given in Appendix B.  


The following pollutants received water quality based effluent limits:
D. Biomonitoring Requirements
None Minimum quantification levels (MQL's) for state water quality numerical standards-based effluent limitations are set at the values listed in the Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 90  Permitting Guidance Document for Implementing Louisiana Surface Water Quality Standards, LDEQ, October 30, 1995. They are also listed in Part II of the permit.  


The nearest drinking water intake, St. Charles Parish Number 2, is located on the east bank at 125.1 M.A.H.P., 4.4 miles downstream from the discharge point. According to a fax received on 9/26/96 from Leslie Lemon of the Department of Health and Hospitals, Office of Public Health, there have been no toxic exceedences of drinking water Maximum Contaminant Levels at this drinking water intake. Nearby potable water industrial intakes include Union Carbide Corporation.
It has been determined that there may be pollutants present in the effluent  
D. Biomonitoring Requirements It has been determined that there may be pollutants present in the effluent which may have the potential to cause toxic conditions in the receiving stream. The State of Louisiana has established a narrative criteria which states, "toxic substances shall not be present in quantities that alone or in combination will be toxic to plant or animal life."  The Office of Water Resources requires the use of the most recent EPA biomonitoring protocols.


Whole effluent biomonitoring is the most direct measure of potential toxicity which incorporates both the effects of synergism of effluent components and receiving stream water quality characteristics. Biomonitoring of the effluent is, therefore, required as a condition of this permit to assess potential toxicity. See Appendix C for the permittee's biomonitoring history and biomonitoring frequency recommendation. The biomonitoring procedures stipulated as a condition of this permit for Outfall 001 are as follows:
which may have the potential to cause toxic conditions in the receiving
TOXICITY TESTS    FREQUENCY  Acute static renewal 48-hour  once per year definitive toxicity test using Daphnia pulex Acute static renewal 48-hour  once per year definitive toxicity test using fathead minnow (Pimephales promelas)
Toxicity tests shall be performed in accordance with protocols described in the latest revision of the "Methods for Measuring the Acute Toxicity of Effluents and Receiving Waters to Freshwater and Marine Organisms."  The stipulated test species are appropriate to measure the toxicity of the effluent consistent with the requirements of the State water quality standards. The biomonitoring frequency has been established to reflect the likelihood of ambient toxicity and to provide data representative of the toxic potential of the facility's discharge in accordance with regulations promulgated at LAC 33:IX.2369/40 CFR Part 122.48.
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 91 Results of all dilutions as well as the associated chemical monitoring of pH, temperature, hardness, dissolved oxygen, conductivity, and alkalinity shall be documented in a full report according to the test method publication mentioned in the previous paragraph. The permittee shall submit a copy of the first full report to this Office. The full report and subsequent reports are to be retained for three (3) years following the provisions of Part III.C.3 of this permit. The permit requires the submission of certain toxicity testing information as an attachment to the Discharge Monitoring Report.


This permit may be reopened to require effluent limits, additional testing, and/or other appropriate actions to address toxicity if biomonitoring data show actual or potential ambient toxicity to be the result of the permittee's discharge to the receiving stream or water body. Modification or revocation of the permit is subject to the provisions of LAC 33:IX.2407/40 CFR 124.5.
stream. The State of Louisiana has established a narrative criteria which
Accelerated or intensified toxicity testing may be required in accordance with Section 308 of the Clean Water Act.


Dilution Series The permit requires five (5) dilutions in addition to the control (0%
states, "toxic substances shall not be present in quantities that alone or in  
effluent) to be used in the toxicity tests. These additional effluent concentrations shall be 56%, 42%, 32%, 24%, and 18%. The low-flow effluent concentration (critical dilution) is defined as 42% effluent.
E. MONITORING FREQUENCIES Regulations require permits to establish monitoring requirements to yield data representative of the monitored activity [LAC 33:IX.2369/40 CFR 122.48(b)] and to assure compliance with permit limitations [LAC 33:IX.2361.I./40 CFR 122.44(I)]. The following section(s) explain the rationale for the monitoring frequencies stated in the draft permit. See outfall information for associated outfalls concerning the type of wastewaters in Section VII.


Outfall 001 Monitoring frequencies for all effluent characteristics, except the biomonitoring which was discussed above in Section IX.D, are retained from the current permit. Flow, Temperature (F), and Heat (BTU/hour) are continuous with a sample type of record. Boron is calculated daily. Total Residual Chlorine is measured once per week by grab sample, during periods of chlorination.
combination will be toxic to plant or animal life."  The Office of Water


Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 92  Internal Outfall 101 (Former 01A) - Liquid Waste Management System Monitoring frequencies for all effluent characteristics are retained from the current permit. Flow, TSS, Oil and Grease, Boron, and pH are once per batch.  
Resources requires the use of the most recent EPA biomonitoring protocols.  


Flow is totalized by a flow meter not estimated as the current permit states.
Whole effluent biomonitoring is the most direct measure of potential toxicity
Therefore this permit proposes to change the sample type for flow to totalized. Sampling for TSS, Oil and Grease, Boron, and pH are by grab sampling.


Internal Outfall 201 (Former 01B) - Boron Management System Monitoring frequencies for all effluent characteristics are retained from the current permit. Flow, TSS, Oil and Grease, Boron, and pH are once per batch.
which incorporates both the effects of synergism of effluent components and  


Flow is totalized by a flow meter not estimated as the current permit states.
receiving stream water quality characteristics. Biomonitoring of the effluent
Therefore this permit proposes to change the sample type for flow to totalized. Sampling for TSS, Oil and Grease, Boron, and pH are by grab sampling.


Internal Outfall 301 (Former 01C) - Filter Flush System Flow is totalized weekly by a flow meter not estimated as the current permit states. Therefore this permit proposes to change the sample type for flow to totalized. The monthly recording based on an inventory calculation of the clarifying agents used is retained from the current permit. However, no DMR reporting is required. This permit proposes a requirement for the permittee to maintain these records onsite.
is, therefore, required as a condition of this permit to assess potential


Internal Outfall 401 (Former 01D) - Low Volume Wastewaters The measurement frequency and sample type for flow, TSS, Oil and Grease, and pH are retained from the current permit. Flow is daily by a totalized sample type. TSS, Oil and Grease, and pH are by a grab sample.
toxicity. See Appendix C for the permittee's biomonitoring history and  


Internal Outfall 501 - Auxiliary Component Cooling Water Basin A This permit proposes a monitoring frequency of once per week for all parameters, when discharging. The sample type for flow is estimate and the sample type for TOC, TSS, Oil and Grease, and pH are by a grab sample.
biomonitoring frequency recommendation. The biomonitoring procedures
During circulating water flow testing, sampling for TSS is not required (when Mississippi River water is used for the flow test).


Internal Outfall 601 - Auxiliary Component Cooling Water Basin B This permit proposes a monitoring frequency of once per week for all parameters, when discharging. The sample type for flow is estimate and the sample type for TOC, TSS, Oil and Grease, and pH are by a grab sample.
stipulated as a condition of this permit for Outfall 001 are as follows:
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 93  During circulating water flow testing, sampling for TSS is not required (when Mississippi River water is used for the flow test).


Internal Outfall 701 - Dry Cooling Tower Sump #1 This outfall is comprised of greater than 85% stormwater, therefore this permit proposes a monitoring frequency of once per month for all parameters, when discharging. The sample type for flow is estimate and the sample type for TOC, TSS, Oil and Grease, Free Available Chlorine, Total Chromium, Total Zinc, and pH are by a grab sample. Free Available Chlorine, Total Chromium, and Total Zinc are analyzed when the discharge includes cooling tower blowdown.
TOXICITY TESTS    FREQUENCY Acute static renewal 48-hour  once per year


Internal Outfall 801 - Dry Cooling Tower Sump #2 This outfall is comprised of greater than 85% stormwater, therefore this permit proposes a monitoring frequency of once per month for all parameters, when discharging. The sample type for flow is estimate and the sample type for TOC, TSS, Oil and Grease, Free Available Chlorine, Total Chromium, Total Zinc, and pH are by a grab sample. Free Available Chlorine, Total Chromium, and Total Zinc are analyzed when the discharge includes cooling tower blowdown.
definitive toxicity test


Internal Outfall 901 - Metal Cleaning Wastewater This permit proposes a monitoring frequency of once per week for all parameters, when discharging. The sample type for flow is estimate and the sample type for TSS, Oil and Grease, Total Copper, Total Iron, and pH are by a grab sample.
using Daphnia pulex Acute static renewal 48-hour  once per year


Outfall 004 - Stormwater This permit proposes a monitoring frequency for all parameters of once per quarter, when discharging. The sample type for flow is estimate and the sample type for TOC, Oil and Grease, TSS, and pH are by a grab sample.
definitive toxicity test


Internal Outfall 104 - Yard Oil Separator This permit proposes a monitoring frequency of once per month for all parameters, when discharging. The sample type for flow is estimate and the sample type for TSS, Oil and Grease, and pH is by a grab sample.
using fathead minnow (Pimephales promelas)
Toxicity tests shall be performed in accordance with protocols described in


Internal Outfall 204 - Vehicle Wash Wastewater The monitoring frequency of vehicle wash wastewater follows LDEQ's vehicle wash wastewater general permit. The monitoring frequency is once per quarter for all parameters, when discharging. The sample type for flow is estimate and the sample type for COD, TSS, Oil and Grease, pH, and soaps and/or detergents is by grab sample. 
the latest revision of the "Methods for Measuring the Acute Toxicity of


Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 94  Outfall 005 - Energy Education Center Sewage Treatment Plant All parameters will be monitored once per six months based on monitoring frequencies established for similar discharges. The sample type for flow is estimate and the sample type for BOD5, TSS, Fecal Coliform, and pH is by a grab sample.  
Effluents and Receiving Waters to Freshwater and Marine Organisms."  The
 
stipulated test species are appropriate to measure the toxicity of the
 
effluent consistent with the requirements of the State water quality
 
standards. The biomonitoring frequency has been established to reflect the
 
likelihood of ambient toxicity and to provide data representative of the toxic
 
potential of the facility's discharge in accordance with regulations
 
promulgated at LAC 33:IX.2369/40 CFR Part 122.48.
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
 
LA0007374
 
Page 91 Results of all dilutions as well as the associated chemical monitoring of pH,
 
temperature, hardness, dissolved oxygen, conductivity, and alkalinity shall be
 
documented in a full report according to the test method publication mentioned
 
in the previous paragraph. The permittee shall submit a copy of the first
 
full report to this Office. The full report and subsequent reports are to be
 
retained for three (3) years following the provisions of Part III.C.3 of this
 
permit. The permit requires the submission of certain toxicity testing
 
information as an attachment to the Discharge Monitoring Report.
 
This permit may be reopened to require effluent limits, additional testing,
 
and/or other appropriate actions to address toxicity if biomonitoring data
 
show actual or potential ambient toxicity to be the result of the permittee's
 
discharge to the receiving stream or water body. Modification or revocation
 
of the permit is subject to the provisions of LAC 33:IX.2407/40 CFR 124.5. 
 
Accelerated or intensified toxicity testing may be required in accordance with
 
Section 308 of the Clean Water Act.
 
Dilution Series
 
The permit requires five (5) dilutions in addition to the control (0%
 
effluent) to be used in the toxicity tests. These additional effluent
 
concentrations shall be 56%, 42%, 32%, 24%, and 18%. The low-flow effluent
 
concentration (critical dilution) is defined as 42% effluent.
 
E. MONITORING FREQUENCIES
 
Regulations require permits to establish monitoring requirements to yield data
 
representative of the monitored activity [LAC 33:IX.2369/40 CFR 122.48(b)] and
 
to assure compliance with permit limitations [LAC 33:IX.2361.I./40 CFR
 
122.44(I)]. The following section(s) explain the rationale for the monitoring
 
frequencies stated in the draft permit. See outfall information for associated
 
outfalls concerning the type of wastewaters in Section VII.
 
Outfall 001
 
Monitoring frequencies for all effluent characteristics, except the
 
biomonitoring which was discussed above in Section IX.D, are retained from the
 
current permit. Flow, Temperature (F), and Heat (BTU/hour) are continuous with a sample type of record. Boron is calculated daily. Total Residual
 
Chlorine is measured once per week by grab sample, during periods of
 
chlorination.
 
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
 
LA0007374
 
Page 92  Internal Outfall 101 (Former 01A) - Liquid Waste Management System
 
Monitoring frequencies for all effluent characteristics are retained from the
 
current permit. Flow, TSS, Oil and Grease, Boron, and pH are once per batch.
 
Flow is totalized by a flow meter not estimated as the current permit states.
 
Therefore this permit proposes to change the sample type for flow to
 
totalized. Sampling for TSS, Oil and Grease, Boron, and pH are by grab
 
sampling.
 
Internal Outfall 201 (Former 01B) - Boron Management System
 
Monitoring frequencies for all effluent characteristics are retained from the
 
current permit. Flow, TSS, Oil and Grease, Boron, and pH are once per batch.
 
Flow is totalized by a flow meter not estimated as the current permit states.
 
Therefore this permit proposes to change the sample type for flow to
 
totalized. Sampling for TSS, Oil and Grease, Boron, and pH are by grab
 
sampling.
 
Internal Outfall 301 (Former 01C) - Filter Flush System
 
Flow is totalized weekly by a flow meter not estimated as the current permit
 
states. Therefore this permit proposes to change the sample type for flow to
 
totalized. The monthly recording based on an inventory calculation of the
 
clarifying agents used is retained from the current permit. However, no DMR
 
reporting is required. This permit proposes a requirement for the permittee
 
to maintain these records onsite.
 
Internal Outfall 401 (Former 01D) - Low Volume Wastewaters
 
The measurement frequency and sample type for flow, TSS, Oil and Grease, and
 
pH are retained from the current permit. Flow is daily by a totalized sample
 
type. TSS, Oil and Grease, and pH are by a grab sample.
 
Internal Outfall 501 - Auxiliary Component Cooling Water Basin A
 
This permit proposes a monitoring frequency of once per week for all
 
parameters, when discharging. The sample type for flow is estimate and the
 
sample type for TOC, TSS, Oil and Grease, and pH are by a grab sample.
 
During circulating water flow testing, sampling for TSS is not required (when
 
Mississippi River water is used for the flow test).
 
Internal Outfall 601 - Auxiliary Component Cooling Water Basin B
 
This permit proposes a monitoring frequency of once per week for all
 
parameters, when discharging. The sample type for flow is estimate and the
 
sample type for TOC, TSS, Oil and Grease, and pH are by a grab sample.
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
 
LA0007374
 
Page 93  During circulating water flow testing, sampling for TSS is not required (when
 
Mississippi River water is used for the flow test).
 
Internal Outfall 701 - Dry Cooling Tower Sump #1
 
This outfall is comprised of greater than 85% stormwater, therefore this
 
permit proposes a monitoring frequency of once per month for all parameters,
 
when discharging. The sample type for flow is estimate and the sample type
 
for TOC, TSS, Oil and Grease, Free Available Chlorine, Total Chromium, Total
 
Zinc, and pH are by a grab sample. Free Available Chlorine, Total Chromium,
 
and Total Zinc are analyzed when the discharge includes cooling tower
 
blowdown.
 
Internal Outfall 801 - Dry Cooling Tower Sump #2
 
This outfall is comprised of greater than 85% stormwater, therefore this
 
permit proposes a monitoring frequency of once per month for all parameters,
 
when discharging. The sample type for flow is estimate and the sample type for
 
TOC, TSS, Oil and Grease, Free Available Chlorine, Total Chromium, Total Zinc,
 
and pH are by a grab sample. Free Available Chlorine, Total Chromium, and
 
Total Zinc are analyzed when the discharge includes cooling tower blowdown.
 
Internal Outfall 901 - Metal Cleaning Wastewater
 
This permit proposes a monitoring frequency of once per week for all
 
parameters, when discharging. The sample type for flow is estimate and the
 
sample type for TSS, Oil and Grease, Total Copper, Total Iron, and pH are by a
 
grab sample.
 
Outfall 004 - Stormwater
 
This permit proposes a monitoring frequency for all parameters of once per
 
quarter, when discharging. The sample type for flow is estimate and the
 
sample type for TOC, Oil and Grease, TSS, and pH are by a grab sample.
 
Internal Outfall 104 - Yard Oil Separator
 
This permit proposes a monitoring frequency of once per month for all
 
parameters, when discharging. The sample type for flow is estimate and the
 
sample type for TSS, Oil and Grease, and pH is by a grab sample.
 
Internal Outfall 204 - Vehicle Wash Wastewater
 
The monitoring frequency of vehicle wash wastewater follows LDEQ's vehicle
 
wash wastewater general permit. The monitoring frequency is once per quarter
 
for all parameters, when discharging. The sample type for flow is estimate
 
and the sample type for COD, TSS, Oil and Grease, pH, and soaps and/or
 
detergents is by grab sample. 
 
Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station  
 
LA0007374  
 
Page 94  Outfall 005 - Energy Education Center Sewage Treatment Plant
 
All parameters will be monitored once per six months based on monitoring  
 
frequencies established for similar discharges. The sample type for flow is  
 
estimate and the sample type for BOD 5, TSS, Fecal Coliform, and pH is by a grab sample.  


X. Endangered Species:
X. Endangered Species:
The receiving waterbody, Subsegment 070301 of the Mississippi River Basin is not listed in Section II.2 of the Implementation Strategy as requiring consultation with the U.S. Fish and Wildlife Service (FWS). This strategy was submitted with a letter dated September 26, 1997 from Fruge (FWS) to Aydell (LDEQ). Therefore, in accordance with the Memorandum of Understanding between the LDEQ and the FWS, no further informal (Section 7, Endangered Species Act) consultation is required. It was determined that the issuance of the LPDES permit is not likely to have an adverse effect on any endangered or candidate species or the critical habitat. The effluent limitations established in the permit ensure protection of aquatic life and maintenance of the receiving water as aquatic habitat.  
 
The receiving waterbody, Subsegment 070301 of the Mississippi River Basin is  
 
not listed in Section II.2 of the Implementation Strategy as requiring  
 
consultation with the U.S. Fish and Wildlife Service (FWS). This strategy was  
 
submitted with a letter dated September 26, 1997 from Fruge (FWS) to Aydell  
 
(LDEQ). Therefore, in accordance with the Memorandum of Understanding between  
 
the LDEQ and the FWS, no further informal (Section 7, Endangered Species Act)  
 
consultation is required. It was determined that the issuance of the LPDES  
 
permit is not likely to have an adverse effect on any endangered or candidate  
 
species or the critical habitat. The effluent limitations established in the  
 
permit ensure protection of aquatic life and maintenance of the receiving  
 
water as aquatic habitat.  


XI. Historic Sites:  
XI. Historic Sites:  


The discharge is from an existing facility location, which does not include an expansion on undisturbed soils. Therefore, there should be no potential effect to sites or properties on or eligible for listing on the National Register of Historic Places, and in accordance with the "Memorandum of Understanding for the Protection of Historic Properties in Louisiana Regarding LPDES Permits" no consultation with the Louisiana State Historic Preservation Officer is required.  
The discharge is from an existing facility location, which does not include an  
 
expansion on undisturbed soils. Therefore, there should be no potential  
 
effect to sites or properties on or eligible for listing on the National  
 
Register of Historic Places, and in accordance with the "Memorandum of  
 
Understanding for the Protection of Historic Properties in Louisiana Regarding  
 
LPDES Permits" no consultation with the Louisiana State Historic Preservation  
 
Officer is required.  


XII. Tentative Determination:
XII. Tentative Determination:
On the basis of preliminary staff review, the Department of Environmental Quality has made a tentative determination to reissue a permit for the discharge described in the application.  
 
On the basis of preliminary staff review, the Department of Environmental  
 
Quality has made a tentative determination to reissue a permit for the  
 
discharge described in the application.  


XIII. Variances:
XIII. Variances:
No requests for variances have been received by this Office.  
No requests for variances have been received by this Office.  


XIV. Public Notices:
XIV. Public Notices:
Upon publication of the public notice, a public comment period shall begin on the date of publication and last for at least 30 days thereafter. During this period, any interested persons may submit written comments on the draft permit and may request a public hearing to clarify issues involved in the permit decision at this Office's address on the first page of the fact sheet. A Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station LA0007374 Page 95  request for a public hearing shall be in writing and shall state the nature of the issues proposed to be raised in the hearing.


Public notice published in:
Upon publication of the public notice, a public comment period shall begin on
ST. CHARLES HERALD-GUIDE of Boutte Office of Water Resources Public Notice Mailing List Appendix A
 
the date of publication and last for at least 30 days thereafter. During this
 
period, any interested persons may submit written comments on the draft permit
 
and may request a public hearing to clarify issues involved in the permit
 
decision at this Office's address on the first page of the fact sheet. A Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station
 
LA0007374
 
Page 95  request for a public hearing shall be in writing and shall state the nature of
 
the issues proposed to be raised in the hearing.
 
Public notice published in:    
 
ST. CHARLES HERALD-GUIDE of Boutte Office of Water Resources Public Notice Mailing List Appendix A
 
Appendix B


Appendix B Appendix C}}
Appendix C}}

Revision as of 23:08, 29 June 2018

Aquatic Resources (AR) RAI AR-7 WF3 1998_WF3 LPDES Fact Sheet and Rationale for Draft LPDES Permit
ML17037C997
Person / Time
Site: Waterford Entergy icon.png
Issue date: 02/07/2017
From:
Entergy Operations
To: Keegan E M
Division of License Renewal
ELAINE KEEGAN, NRR/DLR, 415-8517
Shared Package
ML17018A143 List:
References
Download: ML17037C997 (98)


Text

LPDES PERMIT NO. LA0007374

LPDES FACT SHEET and RATIONALE FOR THE DRAFT LOUISIANA POLLUTANT DISCHARGE ELIMINATION SYSTEM (LPDES) PERMIT TO DISCHARGE TO WATERS OF LOUISIANA

I. Company/Facility Name:

Entergy Operations, Inc.

Waterford 3 Steam Electric Station

Post Office Box B

Killona, Louisiana 70066

II. Issuing Office: Louisiana Department of Environmental Quality (LDEQ)

Office of Water Resources

Post Office Box 82215

Baton Rouge, Louisiana 70884-2215

III. Prepared By: Elizabeth A. Ballard Industrial Permits Section

Water Pollution Control Division Phone #: 504-765-0543 Fax #: 504-765-0635 Date Prepared: July 22, 1998

IV. Permit Action/Status:

A. Reason For Permit Action:

Proposed reissuance of an expired Louisiana Pollutant Discharge

Elimination System (LPDES) permit for a 5-year term following

regulations promulgated at LAC 33:IX.2365/40 CFR 122.46*.

  • In order to ease the transition from NPDES to LPDES permits, dual regulatory references are provided where applicable. The LAC

references are the legal references while the 40 CFR references

are presented for informational purposes only. In most cases, LAC

language is based on and is identical to the 40 CFR language. 40

CFR Parts 401-402, and 404-471 have been adopted by reference at

LAC 33:IX.2533 and will not have dual references. In addition,

state standards (LAC Chapter 11) will not have dual references.

LAC 33:IX Citations:

Unless otherwise stated, citations to LAC 33:IX refer to promulgated regulations listed at Louisiana Administrative

Code, Title 33, Part IX.

40 CFR Citations:

Unless otherwise stated, citations to 40 CFR refer to promulgated regulations listed at Title 40, Code of Federal Regulations

in accordance with the dates specified at LAC 33:IX.2531, 2533, and

2301.F.

B. NPDES permit - NPDES permit effective date: May 20, 1991 NPDES permit expiration date: May 19, 1996 EPA has not retained enforcement authority.

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 2 C. LWDPS permit - Louisiana Stream Control Commission letter dated WP4832 September 27, 1973

D. LWDPS permit - Class I Sanitary General Permit LAG530192 Authorization date: April 29, 1998 Permit expiration date: November 18, 2002

F. Original application received on November 17, 1995, with revised applications received on February 25, 1998, an addendum received

on June 15, 1998, and a letter with revised flow diagram received

on July 29, 1998.

V. Facility Information:

A. Location - LA Highway 18 (River Road) in Killona (11/4 miles west of the intersection of LA Highway 3142, and LA Highway

18), St. Charles Parish B. Applicant Activity -

According to the application, Entergy Waterford 3 Steam Electric

Station is a nuclear fueled steam electric generating station with

a net output of 1,104 megawatts (MWe).

This Office does not have authority to regulate radioactive

materials in water discharge permits. Jurisdiction for regulation

of these materials is held by the Nuclear Regulatory Commission

(NRC) under the Atomic Energy Act, 42 U.S.C. 2021, et seq.

Therefore, the permittee must comply with radiation standards

established and regulated by the NRC. Furthermore, this permit

will not address those radiation standards.

C. Technology Basis - (40 CFR Chapter 1, Subchapter N/Parts 401-402, and 404-471 have been adopted by reference at LAC 33:IX.2533)

Guideline Reference Steam Electric Power Generating Point Source Category 40 CFR 423 Max 30 Day Average Continuous Flow - 1,346 MGD Other sources of technology based limits:

LA0007374 Certification of NPDES Permit Modification, dated 6/16/95, by Percy V. Harris (LDEQ)

LA0007374 EPA Fact Sheet public noticed on June 3, 1995

LA0007374 NPDES Permit effective 5/20/91, and modification effective on July 21, 1995 LDEQ Stormwater Guidance, letter dated 6/17/87, from J. Dale Givens (LDEQ) to Myron Knudson (EPA Region 6)

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 3 Final Environmental Statement, Louisiana Power & Light Co.(LP&L), September 1981 Demonstration Under Section 316(a) of the CWA, Louisiana Power &

Light Co., April 1979 Hydrologic and Quality Characteristics of the Lower Mississippi River, Technical Report Number 5 LDEQ Sanitary General Permits

Best Professional Judgement using:

Letter from LDEQ to Entergy dated 6/23/98

Letter from Entergy to LDEQ dated 6/13/97

Letter from LDEQ to Entergy dated 8/26/96

Letter from EPA Region 6 to Entergy dated 4/16/96

Letter from EPA Region 6 to Entergy dated 1/23/96

Letter from Entergy to EPA Region 6 dated 10/25/94

Letter from Entergy to LDEQ dated 9/9/94

Letter from EPA Region 6 to LP&L dated 5/30/85

Letter from LP&L to EPA Region 6 dated 3/1/85 D. Fee Rate -

1. Fee Rating Facility Type: Major
2. Complexity Type: V
3. Wastewater Type: I
4. SIC code: 4911 E. Continuous Facility Effluent Flow (Max 30-Day) - 1,346 MGD

VI. Receiving Waters:

Mississippi River (Outfall 001):

1. TSS (15%), mg/L: 25.0
2. Average Hardness, mg/L CaCO 3: 149.70
3. Critical Flow, cfs: 141,955
4. Mixing Zone Fraction: 0.333
5. Harmonic Mean Flow, cfs: 366,748
6. River Basin: Mississippi River, Segment No. 070301
7. Designated Uses:

The designated uses are primary contact recreation,

secondary contact recreation, fish and wildlife propagation,

and drinking water supply.

Information based on the following: Water Quality Management Plan,

Volume 5A, 1994; LAC 33:IX Chapter 11;/Recommendation(s) from the

Engineering Section. Hardness and 15% TSS data come from

monitoring station 58010321 on the Mississippi River listed in

Hardness and TSS Data for All LDEQ Ambient Stations for the Period of Record as of March 1998

, LeBlanc.

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 4 40 Arpent Canal thence to Lac Des Allemands (Outfalls 004 & 005):

1. River Basin: Barataria Basin, Segment No. 020202
2. Designated Uses:

The designated uses are primary contact recreation,

secondary contact recreation, and fish and wildlife

propagation.

VII. Outfall Information:

Outfall 001 A. Type of wastewater - the continuous discharge from the turbine condenser cooling system to the Mississippi River. The turbine

condenser cooling system receives once-through non-contact cooling

water from the Mississippi River that flows through the main

condenser, the steam generator blowdown heat exchangers, and the

turbine building closed cooling heat exchanger. Previously

monitored low volume discharges from Internal Outfalls 101 (former

01A), 201 (former 01B), 301 (former 01C), 401 (former 01D), 501,

601, 701, 801, and 901 also exit the facility via Outfall 001.

B. Location - at the point of discharge from the turbine condenser cooling system where the once-through non-contact cooling water,

and the previously monitored effluents discharge prior to entering

the Mississippi River at Latitude 2959'47", Longitude 9028'8", +129.5 M.A.H.P.

C. Treatment - treatment of once-through non-contact cooling water consists of:

- intake screening

- chlorination, when required

- LDEQ approved mussels treatment, when required

- addition of dispersant/polymer, when required

D. Flow - Continuous, (Max 30-Day) 1,346 MGD.

E. Receiving waters - Mississippi River F. Basin and segment - Mississippi River Basin, Segment 070301 G. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA

Form 2C) received on June 15, 1998.

POLLUTANT EFFLUENT

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 5 PART A (mg/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand <2.0 <2.0 ---

Chemical Oxygen Demand 46.1 46.1 ---

Total Organic Carbon 6.7 6.7 ---

Total Suspended Solids 269 269 ---

Ammonia (as N) <0.05 <0.05 --- Temperature (Winter) 21.1C 29.7C --- (Summer) 41.1C 42.7C --- pH (Standard Units) NA NA --- (min) (max)

PART B (mg/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Bromide BA BA ---

Chlorine, Total Residual BA BA ---

Color (nM Units) BA BA ---

Fecal Coliform (col/100 mL) BA BA ---

Fluoride BA BA ---

Nitrate-Nitrite (N) BA BA ---

Organic Nitrogen, Total as (N) BA BA ---

Oil and Grease <5.0 <5.0 ---

Phosphorous, Total as (P) BA BA ---

Radioactivity:

Alpha, Total (pCi/L) 0.0129 0.0129 ---

Beta, Total (pCi/L) 4.2 4.2 ---

Radium, Total (pCi/L) BA BA ---

Radium 226, Total (pCi/L) BA BA ---

Sulfate (as SO

4) 84.2 84.2 --- Sulfide (as S) BA BA ---

Sulfite (as SO

3) BA BA --- Surfactants <0.1 <0.1 ---

Aluminum (Total) BA BA ---

Barium (Total) <0.2 <0.2 ---

Boron (Total) 0.111 0.111 ---

Cobalt (Total) BA BA ---

Iron (Total) 0.795 0.795 ---

Magnesium (Total) BA BA ---

Manganese (Total) BA BA ---

Tin (Total) BA BA ---

Titanium (Total) BA BA ---

METALS, CYANIDE & TOTAL PHENOL (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Antimony (Total) BA BA 60 Arsenic (Total) <10 <10 10 Beryllium (Total) <5 <5 5 Cadmium (Total) <1 <1 1 Chromium (Total) <10 <10 10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 6 Chromium (3+) NA NA 10 Chromium (6+) NA NA 10 Copper (Total) <10 <10 10 Lead (Total) <3 <3 5 Mercury (Total) <0.2 <0.2 0.2 Molybdenum (Total) BA BA 30 Nickel (Total) Freshwater <40 <40 40 Nickel (Total) Marine NA NA 5 Selenium (Total) <5 <5 5 Silver (Total) <2 <2 2 Thallium (Total) <10 <10 10 Zinc (Total) 25.2 25.2 20 Cyanide (Total) <10 <10 10

Phenolics, Total Recoverable (4AAP) <50 <50 5 DIOXIN (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD BA BA 0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Acrolein <10 <10 50 Acrylonitrile <10 <10 50 Benzene <5 <5 10 Bis(Chloromethyl)Ether BA BA 10 Bromoform <5 <5 10 Carbon Tetrachloride <5 <5 10 Chlorobenzene <5 <5 10 Chlorodibromomethane <5 <5 10 Chloroethane <10 <10 50 2-Chloroethylvinylether <5 <5 10 Chloroform <5 <5 10 Dichlorobromomethane <5 <5 10 Dichlorodifluoromethane BA BA 10 1,1-Dichloroethane <5 <5 10 1,2-Dichloroethane <5 <5 10 1,1-Dichloroethylene <5 <5 10 1,2-Dichloropropane <5 <5 10 1,3-Dichloropropylene <5 <5 10 Ethylbenzene <5 <5 10 Methyl Bromide [Bromomethane] <10 <10 50 Methyl Chloride [Chloromethane] <10 <10 50 Methylene Chloride <5 <5 20 1,1,2,2-Tetrachloroethane <5 <5 10 Tetrachloroethylene <5 <5 10 Toluene <5 <5 10 1,2-trans-Dichloroethylene <5 <5 10 1,1,1-Trichloroethane <5 <5 10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 7 1,1,2-Trichloroethane <5 <5 10 Trichloroethylene <5 <5 10 Trichlorofluoromethane BA BA 10 Vinyl Chloride <10 <10 10 ACID COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol <10 <10 10 2,4-Dichlorophenol <10 <10 10 2,4-Dimethylphenol <10 <10 10 4,6-Dinitro-o-Cresol <50 <50 50 2,4-Dinitrophenol <50 <50 50 2-Nitrophenol <10 <10 20 4-Nitrophenol <50 <50 50 p-Chloro-m-Cresol <10 <10 10 Pentachlorophenol <50 <50 50 Phenol <10 <10 10 2,4,6-Trichlorophenol <10 <10 10 BASE/NEUTRAL COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Acenaphthene <10 <10 10 Acenaphthylene <10 <10 10 Anthracene <10 <10 10 Benzidine <30 <30 50 Benzo(a)anthracene <10 <10 10 Benzo(a)pyrene <10 <10 10 3,4-Benzofluoranthene <10 <10 10 Benzo(ghi)perylene <10 <10 20 Benzo(k)fluoranthene <10 <10 10 Bis(2-chloroethoxy) Methane <10 <10 10 Bis(2-chloroethyl) Ether <10 <10 10 Bis(2-chloroisopropyl) Ether <10 <10 10 Bis(2-ethylhexyl) Phthalate <10 <10 10 4-Bromophenyl Phenyl Ether <10 <10 10 Butylbenzyl Phthalate <10 <10 10 2-Chloronaphthalene <10 <10 10 4-Chlorophenyl Phenyl Ether <10 <10 10 Chrysene <10 <10 10 Dibenzo(a,h)anthracene <10 <10 20 1,2-Dichlorobenzene <10 <10 10 1,3-Dichlorobenzene <10 <10 10 1,4-Dichlorobenzene <10 <10 10 3,3'-Dichlorobenzidine <20 <20 50 Diethyl Phthalate <10 <10 10 Dimethyl Phthalate <10 <10 10 Di-n-Butyl Phthalate <10 <10 10 2,4-Dinitrotoluene <10 <10 10 2,6-Dinitrotoluene <10 <10 10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 8 Di-n-octyl Phthalate <10 <10 10 1,2-Diphenylhydrazine <10 <10 20 Fluoranthene <10 <10 10 Fluorene <10 <10 10 Hexachlorobenzene <10 <10 10 Hexachlorobutadiene <10 <10 10 Hexachlorocyclopentadiene <10 <10 10 Hexachloroethane <10 <10 20 Indeno(1,2,3-cd)pyrene <10 <10 20 Isophorone <10 <10 10 Naphthalene <10 <10 10 Nitrobenzene <10 <10 10 n-Nitrosodimethylamine <20 <20 50 n-Nitrosodi-n-Propylamine <10 <10 20 n-Nitrosodiphenylamine <10 <10 20 Phenanthrene <10 <10 10 Pyrene <10 <10 10 1,2,4-Trichlorobenzene <10 <10 10 PESTICIDES (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Aldrin BA BA 0.05 Alpha-BHC BA BA 0.05 Beta-BHC BA BA 0.05 Gamma-BHC [Lindane] BA BA 0.05 Delta-BHC BA BA 0.05 Chlordane BA BA 0.2 4,4'-DDT BA BA 0.1 4,4'-DDE [p,p-DDX] BA BA 0.1 4,4'-DDD [p,p-TDE] BA BA 0.1 Dieldrin BA BA 0.1 Alpha-Endosulfan BA BA 0.1 Beta-Endosulfan BA BA 0.1 Endosulfan Sulfate BA BA 0.1 Endrin BA BA 0.1 Endrin Aldehyde BA BA 0.1 Heptachlor BA BA 0.05 Heptachlor Epoxide BA BA 0.05 PCB-1242 BA BA 1.0 PCB-1254 BA BA 1.0 PCB-1221 BA BA 1.0 PCB-1232 BA BA 1.0 PCB-1248 BA BA 1.0 PCB-1260 BA BA 1.0 PCB-1016 BA BA 1.0 Toxaphene BA BA 5.0 BA - Believed Absent

NA - Not Available

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 9 Internal Outfall 101 (Former 01A)

A. Type of wastewater - the intermittent internal discharge from the liquid waste management system to Final Outfall 001 via the

turbine condenser cooling system. The liquid waste management

system receives low volume wastewater from the following sources,

including but not limited to: the turbine and reactor building

equipment and floor drains, primary plant water makeup, laboratory

drains, and other low volume wastewater sources as defined in 40

CFR 423.

B. Location - at the point of discharge from the liquid waste management system prior to combining with the waters of Final

Outfall 001 at Latitude 2959'40", Longitude 9028'16". C. Treatment - treatment of these low volume wastewaters consists of:

- filtering/screening

- cationic and anionic polymer injection

- ion exchange

- neutralization/pH adjustment, when required

- distillation, when required D. Flow - Intermittent, (Max 30-Day) 0.0129 MGD E. Receiving waters - Discharge to Outfall 001 F. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA

Form 2C) received on June 15, 1998.

POLLUTANT EFFLUENT PART A (mg/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand <10.0 <10.0 ---

Chemical Oxygen Demand 38.0 38.0 ---

Total Organic Carbon 10 10 ---

Total Suspended Solids 17.4 28.3 ---

Ammonia (as N) 3.0 3.0 ---

Temperature (Winter) NA NA --- (Summer) NA NA --- pH (Standard Units) 6.04 8.98 --- (min) (max)

PART B (mg/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Bromide BA BA ---

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 10 Chlorine, Total Residual BA BA ---

Color (nM Units) 15.0 15.0 ---

Fecal Coliform (col/100 mL) BA BA ---

Fluoride BA BA ---

Nitrate-Nitrite (N) 7.3 7.3 ---

Organic Nitrogen, Total as (N) BA BA ---

Oil and Grease 5.91 11.4 ---

Phosphorous, Total as (P) 0.44 0.44 ---

Radioactivity:

Alpha, Total (pCi/L) 259 259 ---

Beta, Total (pCi/L) 84,000 84,000 ---

Radium, Total (pCi/L) BA BA ---

Radium 226, Total (pCi/L) BA BA ---

Sulfate (as SO

4) 2.0 2.0 --- Sulfide (as S) BA BA ---

Sulfite (as SO

3) BA BA --- Surfactants <0.1 <0.1 ---

Aluminum (Total) <0.5 <0.5 ---

Barium (Total) <0.2 <0.2 ---

Boron (Total) 598 1,425 ---

Cobalt (Total) BA BA ---

Iron (Total) <1.0 <1.0 ---

Magnesium (Total) <1.0 <1.0 ---

Manganese (Total) BA BA ---

Tin (Total) BA BA ---

Titanium (Total) BA BA ---

METALS, CYANIDE & TOTAL PHENOL (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Antimony (Total) <600 <600 60 Arsenic (Total) <10 <10 10 Beryllium (Total) <50 <50 5 Cadmium (Total) <1 <1 1 Chromium (Total) <2 <2 10 Chromium (3+) NA NA 10 Chromium (6+) NA NA 10 Copper (Total) <100 <100 10 Lead (Total) <31 <31 5 Mercury (Total) 3.9 3.9 0.2 Molybdenum (Total) <100 <100 30 Nickel (Total) Freshwater <400 <400 40 Nickel (Total) Marine NA NA 5 Selenium (Total) <5 <5 5 Silver (Total) <2 <2 2 Thallium (Total) <10 <10 10 Zinc (Total) <200 <200 20 Cyanide (Total) 25 25 10

Phenolics, Total Recoverable (4AAP) 14 14 5 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 11 DIOXIN (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD BA BA 0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Acrolein BA BA 50 Acrylonitrile BA BA 50 Benzene <5 <5 10 Bis(Chloromethyl)Ether BA BA 10 Bromoform <5 <5 10 Carbon Tetrachloride <5 <5 10 Chlorobenzene <5 <5 10 Chlorodibromomethane <5 <5 10 Chloroethane <10 <10 50 2-Chloroethylvinylether <5 <5 10 Chloroform 15 15 10 Dichlorobromomethane <5 <5 10 Dichlorodifluoromethane <10 <10 10 1,1-Dichloroethane <5 <5 10 1,2-Dichloroethane <5 <5 10 1,1-Dichloroethylene <5 <5 10 1,2-Dichloropropane <5 <5 10 1,3-Dichloropropylene <5 <5 10 Ethylbenzene <5 <5 10 Methyl Bromide [Bromomethane] <10 <10 50 Methyl Chloride [Chloromethane] <10 <10 50 Methylene Chloride <5 <5 20 1,1,2,2-Tetrachloroethane <5 <5 10 Tetrachloroethylene <5 <5 10 Toluene <5 <5 10 1,2-trans-Dichloroethylene BA BA 10 1,1,1-Trichloroethane <5 <5 10 1,1,2-Trichloroethane <5 <5 10 Trichloroethylene <5 <5 10 Trichlorofluoromethane <10 <10 10 Vinyl Chloride <10 <10 10 ACID COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol <5 <5 10 2,4-Dichlorophenol <5 <5 10 2,4-Dimethylphenol <5 <5 10 4,6-Dinitro-o-Cresol <25 <25 50 2,4-Dinitrophenol <25 <25 50 2-Nitrophenol <5 <5 20 4-Nitrophenol <25 <25 50 p-Chloro-m-Cresol <5 <5 10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 12 Pentachlorophenol <20 <20 50 Phenol <5 <5 10 2,4,6-Trichlorophenol <5 <5 10 BASE/NEUTRAL COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Acenaphthene <5 <5 10 Acenaphthylene <5 <5 10 Anthracene <5 <5 10 Benzidine <50 <50 50 Benzo(a)anthracene <5 <5 10 Benzo(a)pyrene <5 <5 10 3,4-Benzofluoranthene <5 <5 10 Benzo(ghi)perylene <5 <5 20 Benzo(k)fluoranthene <5 <5 10 Bis(2-chloroethoxy) Methane <5 <5 10 Bis(2-chloroethyl) Ether <5 <5 10 Bis(2-chloroisopropyl) Ether BA BA 10 Bis(2-ethylhexyl) Phthalate 6.8 6.8 10 4-Bromophenyl Phenyl Ether <5 <5 10 Butylbenzyl Phthalate <5 <5 10 2-Chloronaphthalene <5 <5 10 4-Chlorophenyl Phenyl Ether <5 <5 10 Chrysene <5 <5 10 Dibenzo(a,h)anthracene <5 <5 20 1,2-Dichlorobenzene <5 <5 10 1,3-Dichlorobenzene <5 <5 10 1,4-Dichlorobenzene <5 <5 10 3,3'-Dichlorobenzidine <10 <10 50 Diethyl Phthalate <5 <5 10 Dimethyl Phthalate <5 <5 10 Di-n-Butyl Phthalate <5 <5 10 2,4-Dinitrotoluene <5 <5 10 2,6-Dinitrotoluene <5 <5 10 Di-n-octyl Phthalate <5 <5 10 1,2-Diphenylhydrazine BA BA 20 Fluoranthene <5 <5 10 Fluorene <5 <5 10 Hexachlorobenzene <5 <5 10 Hexachlorobutadiene <5 <5 10 Hexachlorocyclopentadiene <5 <5 10 Hexachloroethane <5 <5 20 Indeno(1,2,3-cd)pyrene <5 <5 20 Isophorone <5 <5 10 Naphthalene <5 <5 10 Nitrobenzene <5 <5 10 n-Nitrosodimethylamine BA BA 50 n-Nitrosodi-n-Propylamine <25 <25 20 n-Nitrosodiphenylamine <5 <5 20 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 13 Phenanthrene <5 <5 10 Pyrene <5 <5 10 1,2,4-Trichlorobenzene <5 <5 10 PESTICIDES (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Aldrin BA BA 0.05 Alpha-BHC BA BA 0.05 Beta-BHC BA BA 0.05 Gamma-BHC [Lindane] BA BA 0.05 Delta-BHC BA BA 0.05 Chlordane BA BA 0.2 4,4'-DDT BA BA 0.1 4,4'-DDE [p,p-DDX] BA BA 0.1 4,4'-DDD [p,p-TDE] BA BA 0.1 Dieldrin BA BA 0.1 Alpha-Endosulfan BA BA 0.1 Beta-Endosulfan BA BA 0.1 Endosulfan Sulfate BA BA 0.1 Endrin BA BA 0.1 Endrin Aldehyde BA BA 0.1 Heptachlor BA BA 0.05 Heptachlor Epoxide BA BA 0.05 PCB-1242 BA BA 1.0 PCB-1254 BA BA 1.0 PCB-1221 BA BA 1.0 PCB-1232 BA BA 1.0 PCB-1248 BA BA 1.0 PCB-1260 BA BA 1.0 PCB-1016 BA BA 1.0 Toxaphene BA BA 5.0

BA - Believed Absent

NA - Not Available

Internal Outfall 201 (Former 01B)

A. Type of wastewater - the intermittent internal discharge from the boron management system to Final Outfall 001 via the turbine

condenser cooling system. The boron management system

concentrates and recovers boron from low volume wastewaters for

reuse within the plant. The boron management system receives low

volume wastewater from the following sources, including but not

limited to: the turbine and reactor building equipment and floor

drains, primary plant water makeup, laboratory drains, and other

low volume wastewater sources as defined in 40 CFR 423.

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 14 B. Location - at the point of discharge from the boron management system prior to combining with the waters of Final Outfall 001 at

Latitude 2959'40", Longitude 9028'16". C. Treatment - treatment of these low volume wastewaters consists of:

- filtering/screening

- ion exchange

- neutralization/pH adjustment, when required

- distillation, when required D. Flow - Intermittent, (Max 30-Day) 0.0134 MGD E. Receiving waters - Discharge to Outfall 001 F. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA

Form 2C) received on June 15, 1998.

POLLUTANT EFFLUENT PART A (mg/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand <10.0 <10.0 ---

Chemical Oxygen Demand <1.0 <1.0 ---

Total Organic Carbon <1.0 <1.0 ---

Total Suspended Solids <4.0 <4.0 ---

Ammonia (as N) <0.1 <0.1 ---

Temperature (Winter) NA NA --- (Summer) NA NA --- pH (Standard Units) 6.05 7.71 --- (min) (max)

PART B (mg/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Bromide BA BA ---

Chlorine, Total Residual BA BA ---

Color (nM Units) <5.0 <5.0 ---

Fecal Coliform (col/100 mL) BA BA ---

Fluoride BA BA ---

Nitrate-Nitrite (N) <0.1 <0.1 ---

Organic Nitrogen, Total as (N) BA BA ---

Oil and Grease 5.5 9.2 ---

Phosphorous, Total as (P) <0.25 <0.25 ---

Radioactivity:

Alpha, Total (pCi/L) 0.5 0.5 ---

Beta, Total (pCi/L) 875 875 ---

Radium, Total (pCi/L) BA BA ---

Radium 226, Total (pCi/L) BA BA ---

Sulfate (as SO

4) <1.0 <1.0 ---

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 15 Sulfide (as S) BA BA ---

Sulfite (as SO

3) BA BA --- Surfactants BA BA ---

Aluminum (Total) <0.25 <0.25 ---

Barium (Total) <0.1 <0.1 ---

Boron (Total) 1,391 1,614 ---

Cobalt (Total) BA BA ---

Iron (Total) NA NA ---

Magnesium (Total) <0.5 <0.5 ---

Manganese (Total) <0.05 <0.05 ---

Tin (Total) BA BA ---

Titanium (Total) BA BA ---

METALS, CYANIDE & TOTAL PHENOL (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Antimony (Total) <300 <300 60 Arsenic (Total) <10 <10 10 Beryllium (Total) <25 <25 5 Cadmium (Total) <1 <1 1 Chromium (Total) <2 <2 10 Chromium (3+) NA NA 10 Chromium (6+) NA NA 10 Copper (Total) <50 <50 10 Lead (Total) <31 <31 5 Mercury (Total) <0.2 <0.2 0.2 Molybdenum (Total) <50 <50 30 Nickel (Total) Freshwater <200 <200 40 Nickel (Total) Marine NA NA 5 Selenium (Total) <5 <5 5 Silver (Total) <2 <2 2 Thallium (Total) <10 <10 10 Zinc (Total) <100 <100 20 Cyanide (Total) 10 10 10

Phenolics, Total Recoverable (4AAP) <10 <10 5 DIOXIN (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD BA BA 0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Acrolein BA BA 50 Acrylonitrile BA BA 50 Benzene <5 <5 10 Bis(Chloromethyl)Ether BA BA 10 Bromoform <5 <5 10 Carbon Tetrachloride <5 <5 10 Chlorobenzene <5 <5 10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 16 Chlorodibromomethane <5 <5 10 Chloroethane <10 <10 50 2-Chloroethylvinylether <5 <5 10 Chloroform <5 <5 10 Dichlorobromomethane <5 <5 10 Dichlorodifluoromethane <10 <10 10 1,1-Dichloroethane <5 <5 10 1,2-Dichloroethane <5 <5 10 1,1-Dichloroethylene <5 <5 10 1,2-Dichloropropane <5 <5 10 1,3-Dichloropropylene <5 <5 10 Ethylbenzene <5 <5 10 Methyl Bromide [Bromomethane] <10 <10 50 Methyl Chloride [Chloromethane] <10 <10 50 Methylene Chloride <5 <5 20 1,1,2,2-Tetrachloroethane <5 <5 10 Tetrachloroethylene <5 <5 10 Toluene <5 <5 10 1,2-trans-Dichloroethylene BA BA 10 1,1,1-Trichloroethane <5 <5 10 1,1,2-Trichloroethane <5 <5 10 Trichloroethylene <5 <5 10 Trichlorofluoromethane <10 <10 10 Vinyl Chloride <10 <10 10 ACID COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol <5 <5 10 2,4-Dichlorophenol <5 <5 10 2,4-Dimethylphenol <5 <5 10 4,6-Dinitro-o-Cresol <25 <25 50 2,4-Dinitrophenol <25 <25 50 2-Nitrophenol <5 <5 20 4-Nitrophenol <25 <25 50 p-Chloro-m-Cresol <5 <5 10 Pentachlorophenol <20 <20 50 Phenol <5 <5 10 2,4,6-Trichlorophenol <5 <5 10 BASE/NEUTRAL COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Acenaphthene <5 <5 10 Acenaphthylene <5 <5 10 Anthracene <5 <5 10 Benzidine <50 <50 50 Benzo(a)anthracene <5 <5 10 Benzo(a)pyrene <5 <5 10 3,4-Benzofluoranthene <5 <5 10 Benzo(ghi)perylene <5 <5 20 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 17 Benzo(k)fluoranthene <5 <5 10 Bis(2-chloroethoxy) Methane <5 <5 10 Bis(2-chloroethyl) Ether <5 <5 10 Bis(2-chloroisopropyl) Ether BA BA 10 Bis(2-ethylhexyl) Phthalate <5 <5 10 4-Bromophenyl Phenyl Ether <5 <5 10 Butylbenzyl Phthalate <5 <5 10 2-Chloronaphthalene <5 <5 10 4-Chlorophenyl Phenyl Ether <5 <5 10 Chrysene <5 <5 10 Dibenzo(a,h)anthracene <5 <5 20 1,2-Dichlorobenzene <5 <5 10 1,3-Dichlorobenzene <5 <5 10 1,4-Dichlorobenzene <5 <5 10 3,3'-Dichlorobenzidine <10 <10 50 Diethyl Phthalate <5 <5 10 Dimethyl Phthalate <5 <5 10 Di-n-Butyl Phthalate <5 <5 10 2,4-Dinitrotoluene <5 <5 10 2,6-Dinitrotoluene <5 <5 10 Di-n-octyl Phthalate <5 <5 10 1,2-Diphenylhydrazine BA BA 20 Fluoranthene <5 <5 10 Fluorene <5 <5 10 Hexachlorobenzene <5 <5 10 Hexachlorobutadiene <5 <5 10 Hexachlorocyclopentadiene <5 <5 10 Hexachloroethane <5 <5 20 Indeno(1,2,3-cd)pyrene <5 <5 20 Isophorone <5 <5 10 Naphthalene <5 <5 10 Nitrobenzene <5 <5 10 n-Nitrosodimethylamine BA BA 50 n-Nitrosodi-n-Propylamine <25 <25 20 n-Nitrosodiphenylamine <5 <5 20 Phenanthrene <5 <5 10 Pyrene <5 <5 10 1,2,4-Trichlorobenzene <5 <5 10 PESTICIDES (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Aldrin BA BA 0.05 Alpha-BHC BA BA 0.05 Beta-BHC BA BA 0.05 Gamma-BHC [Lindane] BA BA 0.05 Delta-BHC BA BA 0.05 Chlordane BA BA 0.2 4,4'-DDT BA BA 0.1 4,4'-DDE [p,p-DDX] BA BA 0.1 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 18 4,4'-DDD [p,p-TDE] BA BA 0.1 Dieldrin BA BA 0.1 Alpha-Endosulfan BA BA 0.1 Beta-Endosulfan BA BA 0.1 Endosulfan Sulfate BA BA 0.1 Endrin BA BA 0.1 Endrin Aldehyde BA BA 0.1 Heptachlor BA BA 0.05 Heptachlor Epoxide BA BA 0.05 PCB-1242 BA BA 1.0 PCB-1254 BA BA 1.0 PCB-1221 BA BA 1.0 PCB-1232 BA BA 1.0 PCB-1248 BA BA 1.0 PCB-1260 BA BA 1.0 PCB-1016 BA BA 1.0 Toxaphene BA BA 5.0

BA - Believed Absent

NA - Not Available

Internal Outfall 301 (Former 01C)

A. Type of wastewater - the intermittent internal discharge of filter flush water from the primary water treatment system to Final

Outfall 001 via the turbine condenser cooling system. The primary

water treatment system filters river water for various plant uses.

The filters of this system are flushed periodically with

untreated river water to remove solids trapped in the filter beds.

B. Location - at the point of discharge from the primary water treatment system prior to combining with the waters of Final

Outfall 001 at Latitude 2959'40", Longitude 9028'16". C. Treatment - filter/screening

- separation

- polymer injection, when required D. Flow - Intermittent, (Max 30-Day) 0.0029 MGD E. Receiving waters - Discharge to Outfall 001 F. Effluent Data -Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit

application (EPA Form 2C) received on June 15, 1998.

POLLUTANT EFFLUENT PART A (mg/L, UNLESS STATED) MQL (g/L)

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 19 30-Day Max Daily Max Biochemical Oxygen Demand 33.5 33.5 ---

Chemical Oxygen Demand <5.0 <5.0 ---

Total Organic Carbon 4.4 4.4 ---

Total Suspended Solids 46 46 ---

Ammonia (as N) 0.828 0.828 ---

Temperature (Winter) NA NA --- (Summer) NA NA --- pH (Standard Units) 7.30 7.90 --- (min) (max)

PART B (mg/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Bromide BA BA ---

Chlorine, Total Residual BA BA ---

Color (nM Units) 25 25 ---

Fecal Coliform (col/100 mL) BA BA ---

Fluoride BA BA ---

Nitrate-Nitrite (N) 1.28 1.28 ---

Organic Nitrogen, Total as (N) BA BA ---

Oil and Grease BA BA ---

Phosphorous, Total as (P) 0.53 0.53 ---

Radioactivity:

Alpha, Total (pCi/L) BA BA ---

Beta, Total (pCi/L) BA BA ---

Radium, Total (pCi/L) BA BA ---

Radium 226, Total (pCi/L) BA BA ---

Sulfate (as SO

4) 79.1 79.1 --- Sulfide (as S) <0.02 <0.02 ---

Sulfite (as SO

3) <2.0 <2.0 --- Surfactants <0.04 <0.04 ---

Aluminum (Total) 0.478 0.478 ---

Barium (Total) <0.2 <0.2 ---

Boron (Total) BA BA ---

Cobalt (Total) BA BA ---

Iron (Total) 0.716 0.716 ---

Magnesium (Total) 15.0 15.0 ---

Manganese (Total) BA BA ---

Tin (Total) BA BA ---

Titanium (Total) BA BA ---

METALS, CYANIDE & TOTAL PHENOL (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Antimony (Total) BA BA 60 Arsenic (Total) <10 <10 10 Beryllium (Total) <5 <5 5 Cadmium (Total) <1 <1 1 Chromium (Total) <10 <10 10 Chromium (3+) NA NA 10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 20 Chromium (6+) NA NA 10 Copper (Total) <10 <10 10 Lead (Total) <3 <3 5 Mercury (Total) <0.2 <0.2 0.2 Molybdenum (Total) BA BA 30 Nickel (Total) Freshwater <40 <40 40 Nickel (Total) Marine NA NA 5 Selenium (Total) <5 <5 5 Silver (Total) <2 <2 2 Thallium (Total) <10 <10 10 Zinc (Total) 85.1 85.1 20 Cyanide (Total) <10 <10 10

Phenolics, Total Recoverable (4AAP) <50 <50 5 DIOXIN (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD BA BA 0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Acrolein <10 <10 50 Acrylonitrile <10 <10 50 Benzene <5 <5 10 Bis(Chloromethyl)Ether BA BA 10 Bromoform <5 <5 10 Carbon Tetrachloride <5 <5 10 Chlorobenzene <5 <5 10 Chlorodibromomethane <5 <5 10 Chloroethane <10 <10 50 2-Chloroethylvinylether <5 <5 10 Chloroform 35.9 35.9 10 Dichlorobromomethane 16.3 16.3 10 Dichlorodifluoromethane BA BA 10 1,1-Dichloroethane <5 <5 10 1,2-Dichloroethane <5 <5 10 1,1-Dichloroethylene <5 <5 10 1,2-Dichloropropane <5 <5 10 1,3-Dichloropropylene <5 <5 10 Ethylbenzene <5 <5 10 Methyl Bromide [Bromomethane] <10 <10 50 Methyl Chloride [Chloromethane] <10 <10 50 Methylene Chloride <5 <5 20 1,1,2,2-Tetrachloroethane <5 <5 10 Tetrachloroethylene <5 <5 10 Toluene <5 <5 10 1,2-trans-Dichloroethylene <5 <5 10 1,1,1-Trichloroethane <5 <5 10 1,1,2-Trichloroethane <5 <5 10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 21 Trichloroethylene <5 <5 10 Trichlorofluoromethane BA BA 10 Vinyl Chloride <10 <10 10 ACID COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol <10 <10 10 2,4-Dichlorophenol <10 <10 10 2,4-Dimethylphenol <10 <10 10 4,6-Dinitro-o-Cresol <50 <50 50 2,4-Dinitrophenol <50 <50 50 2-Nitrophenol <10 <10 20 4-Nitrophenol <50 <50 50 p-Chloro-m-Cresol <10 <10 10 Pentachlorophenol <50 <50 50 Phenol <10 <10 10 2,4,6-Trichlorophenol <10 <10 10 BASE/NEUTRAL COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Acenaphthene <10 <10 10 Acenaphthylene <10 <10 10 Anthracene <10 <10 10 Benzidine <30 <30 50 Benzo(a)anthracene <10 <10 10 Benzo(a)pyrene <10 <10 10 3,4-Benzofluoranthene <10 <10 10 Benzo(ghi)perylene <10 <10 20 Benzo(k)fluoranthene <10 <10 10 Bis(2-chloroethoxy) Methane <10 <10 10 Bis(2-chloroethyl) Ether <10 <10 10 Bis(2-chloroisopropyl) Ether <10 <10 10 Bis(2-ethylhexyl) Phthalate <10 <10 10 4-Bromophenyl Phenyl Ether <10 <10 10 Butylbenzyl Phthalate <10 <10 10 2-Chloronaphthalene <10 <10 10 4-Chlorophenyl Phenyl Ether <10 <10 10 Chrysene <10 <10 10 Dibenzo(a,h)anthracene <10 <10 20 1,2-Dichlorobenzene <10 <10 10 1,3-Dichlorobenzene <10 <10 10 1,4-Dichlorobenzene <10 <10 10 3,3'-Dichlorobenzidine <20 <20 50 Diethyl Phthalate <10 <10 10 Dimethyl Phthalate <10 <10 10 Di-n-Butyl Phthalate <10 <10 10 2,4-Dinitrotoluene <10 <10 10 2,6-Dinitrotoluene <10 <10 10 Di-n-octyl Phthalate <10 <10 10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 22 1,2-Diphenylhydrazine <10 <10 20 Fluoranthene <10 <10 10 Fluorene <10 <10 10 Hexachlorobenzene <10 <10 10 Hexachlorobutadiene <10 <10 10 Hexachlorocyclopentadiene <10 <10 10 Hexachloroethane <10 <10 20 Indeno(1,2,3-cd)pyrene <10 <10 20 Isophorone <10 <10 10 Naphthalene <10 <10 10 Nitrobenzene <10 <10 10 n-Nitrosodimethylamine <20 <20 50 n-Nitrosodi-n-Propylamine <10 <10 20 n-Nitrosodiphenylamine <10 <10 20 Phenanthrene <10 <10 10 Pyrene <10 <10 10 1,2,4-Trichlorobenzene <10 <10 10 PESTICIDES (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Aldrin BA BA 0.05 Alpha-BHC BA BA 0.05 Beta-BHC BA BA 0.05 Gamma-BHC [Lindane] BA BA 0.05 Delta-BHC BA BA 0.05 Chlordane BA BA 0.2 4,4'-DDT BA BA 0.1 4,4'-DDE [p,p-DDX] BA BA 0.1 4,4'-DDD [p,p-TDE] BA BA 0.1 Dieldrin BA BA 0.1 Alpha-Endosulfan BA BA 0.1 Beta-Endosulfan BA BA 0.1 Endosulfan Sulfate BA BA 0.1 Endrin BA BA 0.1 Endrin Aldehyde BA BA 0.1 Heptachlor BA BA 0.05 Heptachlor Epoxide BA BA 0.05 PCB-1242 BA BA 1.0 PCB-1254 BA BA 1.0 PCB-1221 BA BA 1.0 PCB-1232 BA BA 1.0 PCB-1248 BA BA 1.0 PCB-1260 BA BA 1.0 PCB-1016 BA BA 1.0 Toxaphene BA BA 5.0 BA - Believed Absent

NA - Not Available

Internal Outfall 401 (Former 01D)

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 23 A. Type of wastewater - the intermittent internal discharge of steam generator blowdown and other low volume wastewaters to Final

Outfall 001 via the turbine condenser cooling system. In addition

to steam generator blowdown, low volume wastewater from other

sources as defined in 40 CFR 423 are discharged from this outfall.

B. Location - at the point of discharge from the secondary steam plant system prior to combining with the waters of Final Outfall

001 at Latitude 2959'41", Longitude 9028'15". C. Treatment - treatment of these wastewaters consists of:

- filtration

- ion exchange

- neutralization/pH adjustment, when required D. Flow - Intermittent, (Max 30-Day) 0.72 MGD E. Receiving waters - Discharge to Outfall 001 F. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA

Form 2C) received on June 15, 1998.

POLLUTANT EFFLUENT PART A (mg/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand <2.0 <2.0 ---

Chemical Oxygen Demand <5.0 <5.0 ---

Total Organic Carbon <1.0 <1.0 ---

Total Suspended Solids 4.14 4.14 ---

Ammonia (as N) 0.086 0.086 ---

Temperature (Winter) NA NA --- (Summer) NA NA --- pH (Standard Units) 6.30 8.06 --- (min) (max)

PART B (mg/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Bromide BA BA ---

Chlorine, Total Residual BA BA ---

Color (nM Units) BA BA ---

Fecal Coliform (col/100 mL) BA BA ---

Fluoride BA BA ---

Nitrate-Nitrite (N) BA BA ---

Organic Nitrogen, Total as (N) BA BA ---

Oil and Grease BA BA ---

Phosphorous, Total as (P) BA BA ---

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 24 Radioactivity:

Alpha, Total (pCi/L) NA NA ---

Beta, Total (pCi/L) NA NA ---

Radium, Total (pCi/L) BA BA ---

Radium 226, Total (pCi/L) BA BA ---

Sulfate (as SO

4) <10.0 <10.0 --- Sulfide (as S) BA BA ---

Sulfite (as SO

3) BA BA --- Surfactants <0.1 <0.1 ---

Aluminum (Total) BA BA ---

Barium (Total) BA BA ---

Boron (Total) BA BA ---

Cobalt (Total) BA BA ---

Iron (Total) BA BA ---

Magnesium (Total) BA BA ---

Manganese (Total) BA BA ---

Tin (Total) BA BA ---

Titanium (Total) BA BA ---

METALS, CYANIDE & TOTAL PHENOL (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Antimony (Total) BA BA 60 Arsenic (Total) <10 <10 10 Beryllium (Total) <5 <5 5 Cadmium (Total) <1 <1 1 Chromium (Total) <10 <10 10 Chromium (3+) NA NA 10 Chromium (6+) NA NA 10 Copper (Total) <10 <10 10 Lead (Total) <3 <3 5 Mercury (Total) <0.2 <0.2 0.2 Molybdenum (Total) BA BA 30 Nickel (Total) Freshwater <40 <40 40 Nickel (Total) Marine NA NA 5 Selenium (Total) <5 <5 5 Silver (Total) <2 <2 2 Thallium (Total) <10 <10 10 Zinc (Total) <20 <20 20 Cyanide (Total) <10 <10 10

Phenolics, Total Recoverable (4AAP) <50 <50 5 DIOXIN (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD BA BA 0.00001

VOLATILE COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Acrolein <10 <10 50 Acrylonitrile <10 <10 50 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 25 Benzene <5 <5 10 Bis(Chloromethyl)Ether BA BA 10 Bromoform <5 <5 10 Carbon Tetrachloride <5 <5 10 Chlorobenzene <5 <5 10 Chlorodibromomethane <5 <5 10 Chloroethane <10 <10 50 2-Chloroethylvinylether <5 <5 10 Chloroform <5 <5 10 Dichlorobromomethane <5 <5 10 Dichlorodifluoromethane BA BA 10 1,1-Dichloroethane <5 <5 10 1,2-Dichloroethane <5 <5 10 1,1-Dichloroethylene <5 <5 10 1,2-Dichloropropane <5 <5 10 1,3-Dichloropropylene <5 <5 10 Ethylbenzene <5 <5 10 Methyl Bromide [Bromomethane] <10 <10 50 Methyl Chloride [Chloromethane] <10 <10 50 Methylene Chloride <5 <5 20 1,1,2,2-Tetrachloroethane <5 <5 10 Tetrachloroethylene <5 <5 10 Toluene <5 <5 10 1,2-trans-Dichloroethylene <5 <5 10 1,1,1-Trichloroethane <5 <5 10 1,1,2-Trichloroethane <5 <5 10 Trichloroethylene <5 <5 10 Trichlorofluoromethane BA BA 10 Vinyl Chloride <10 <10 10 ACID COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol <10 <10 10 2,4-Dichlorophenol <10 <10 10 2,4-Dimethylphenol <10 <10 10 4,6-Dinitro-o-Cresol <50 <50 50 2,4-Dinitrophenol <50 <50 50 2-Nitrophenol <10 <10 20 4-Nitrophenol <50 <50 50 p-Chloro-m-Cresol <10 <10 10 Pentachlorophenol <50 <50 50 Phenol <10 <10 10 2,4,6-Trichlorophenol <10 <10 10 BASE/NEUTRAL COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Acenaphthene <10 <10 10 Acenaphthylene <10 <10 10 Anthracene <10 <10 10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 26 Benzidine <30 <30 50 Benzo(a)anthracene <10 <10 10 Benzo(a)pyrene <10 <10 10 3,4-Benzofluoranthene <10 <10 10 Benzo(ghi)perylene <10 <10 20 Benzo(k)fluoranthene <10 <10 10 Bis(2-chloroethoxy) Methane <10 <10 10 Bis(2-chloroethyl) Ether <10 <10 10 Bis(2-chloroisopropyl) Ether <10 <10 10 Bis(2-ethylhexyl) Phthalate 23.4 23.4 10 4-Bromophenyl Phenyl Ether <10 <10 10 Butylbenzyl Phthalate <10 <10 10 2-Chloronaphthalene <10 <10 10 4-Chlorophenyl Phenyl Ether <10 <10 10 Chrysene <10 <10 10 Dibenzo(a,h)anthracene <10 <10 20 1,2-Dichlorobenzene <10 <10 10 1,3-Dichlorobenzene <10 <10 10 1,4-Dichlorobenzene <10 <10 10 3,3'-Dichlorobenzidine <20 <20 50 Diethyl Phthalate <10 <10 10 Dimethyl Phthalate <10 <10 10 Di-n-Butyl Phthalate <10 <10 10 2,4-Dinitrotoluene <10 <10 10 2,6-Dinitrotoluene <10 <10 10 Di-n-octyl Phthalate <10 <10 10 1,2-Diphenylhydrazine <10 <10 20 Fluoranthene <10 <10 10 Fluorene <10 <10 10 Hexachlorobenzene <10 <10 10 Hexachlorobutadiene <10 <10 10 Hexachlorocyclopentadiene <10 <10 10 Hexachloroethane <10 <10 20 Indeno(1,2,3-cd)pyrene <10 <10 20 Isophorone <10 <10 10 Naphthalene <10 <10 10 Nitrobenzene <10 <10 10 n-Nitrosodimethylamine <20 <20 50 n-Nitrosodi-n-Propylamine <10 <10 20 n-Nitrosodiphenylamine <10 <10 20 Phenanthrene <10 <10 10 Pyrene <10 <10 10 1,2,4-Trichlorobenzene <10 <10 10 PESTICIDES (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Aldrin BA BA 0.05 Alpha-BHC BA BA 0.05 Beta-BHC BA BA 0.05 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 27 Gamma-BHC [Lindane] BA BA 0.05 Delta-BHC BA BA 0.05 Chlordane BA BA 0.2 4,4'-DDT BA BA 0.1 4,4'-DDE [p,p-DDX] BA BA 0.1 4,4'-DDD [p,p-TDE] BA BA 0.1 Dieldrin BA BA 0.1 Alpha-Endosulfan BA BA 0.1 Beta-Endosulfan BA BA 0.1 Endosulfan Sulfate BA BA 0.1 Endrin BA BA 0.1 Endrin Aldehyde BA BA 0.1 Heptachlor BA BA 0.05 Heptachlor Epoxide BA BA 0.05 PCB-1242 BA BA 1.0 PCB-1254 BA BA 1.0 PCB-1221 BA BA 1.0 PCB-1232 BA BA 1.0 PCB-1248 BA BA 1.0 PCB-1260 BA BA 1.0 PCB-1016 BA BA 1.0 Toxaphene BA BA 5.0

BA - Believed Absent

NA - Not Available

Internal Outfall 501 A. Type of wastewater - the intermittent internal discharge from Auxiliary Component Cooling Water Basin A to Final Outfall 001 via

the turbine condenser cooling system. Low volume wastewater

sources contributing to the flow monitored at this outfall

include, but are not limited to, auxiliary component cooling

water, component cooling water, Mississippi River water used for

flow testing, and stormwater.

B. Location - at the point of discharge from Auxiliary Component Cooling Water Basin A prior to combining with the waters of Final

Outfall 001 at Latitude 2959'44", Longitude 9028'13". C. Treatment - treatment of these low volume wastewaters consists of:

- sedimentation

- neutralization/pH adjustment, when required

- side stream ionization, when required

- filtration, when required D. Flow - Intermittent, (Max 30-Day) 0.26 MGD E. Receiving waters - Discharge to Outfall 001 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 28 F. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA

Form 2C) received on June 15, 1998.

POLLUTANT EFFLUENT PART A (mg/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand <2.0 <2.0 ---

Chemical Oxygen Demand 26.0 26.0 ---

Total Organic Carbon 7.0 7.0 ---

Total Suspended Solids 4.3 4.3 ---

Ammonia (as N) <0.1 <0.1 ---

Temperature (Winter) NA NA --- (Summer) NA NA --- pH (Standard Units) 7.47 7.71 --- (min) (max)

PART B (mg/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Bromide BA BA ---

Chlorine, Total Residual BA BA ---

Color (nM Units) 15.0 15.0 ---

Fecal Coliform (col/100 mL) BA BA ---

Fluoride BA BA ---

Nitrate-Nitrite (N) 0.9 0.9 ---

Organic Nitrogen, Total as (N) BA BA ---

Oil and Grease <1.0 <1.0 ---

Phosphorous, Total as (P) 2.5 2.5 ---

Radioactivity:

Alpha, Total (pCi/L) 0.5 0.5 ---

Beta, Total (pCi/L) 11.0 11.0 ---

Radium, Total (pCi/L) BA BA ---

Radium 226, Total (pCi/L) BA BA ---

Sulfate (as SO

4) 11.0 11.0 --- Sulfide (as S) BA BA ---

Sulfite (as SO

3) BA BA --- Surfactants BA BA ---

Aluminum (Total) 0.09 0.09 ---

Barium (Total) <0.02 <0.02 ---

Boron (Total) 0.2 0.2 ---

Cobalt (Total) BA BA ---

Iron (Total) 0.5 0.5 ---

Magnesium (Total) 0.5 0.5 ---

Manganese (Total) BA BA ---

Tin (Total) BA BA ---

Titanium (Total) BA BA ---

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 29 METALS, CYANIDE & TOTAL PHENOL (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Antimony (Total) <50 <50 60 Arsenic (Total) <3 <3 10 Beryllium (Total) <4 <4 5 Cadmium (Total) <1 <1 1 Chromium (Total) 10 10 10 Chromium (3+) NA NA 10 Chromium (6+) NA NA 10 Copper (Total) 20 20 10 Lead (Total) 6 6 5 Mercury (Total) 2.0 2.0 0.2 Molybdenum (Total) <10 <10 30 Nickel (Total) Freshwater <40 <40 40 Nickel (Total) Marine NA NA 5 Selenium (Total) <5 <5 5 Silver (Total) <0.5 <0.5 2 Thallium (Total) <5 <5 10 Zinc (Total) 1,720 1,720 20 Cyanide (Total) <10 <10 10

Phenolics, Total Recoverable (4AAP) <10 <10 5 DIOXIN (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD BA BA 0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Acrolein BA BA 50 Acrylonitrile BA BA 50 Benzene <5 <5 10 Bis(Chloromethyl)Ether BA BA 10 Bromoform <5 <5 10 Carbon Tetrachloride <5 <5 10 Chlorobenzene <5 <5 10 Chlorodibromomethane <5 <5 10 Chloroethane <10 <10 50 2-Chloroethylvinylether <5 <5 10 Chloroform <5 <5 10 Dichlorobromomethane <5 <5 10 Dichlorodifluoromethane <10 <10 10 1,1-Dichloroethane <5 <5 10 1,2-Dichloroethane <5 <5 10 1,1-Dichloroethylene <5 <5 10 1,2-Dichloropropane <5 <5 10 1,3-Dichloropropylene <5 <5 10 Ethylbenzene <5 <5 10 Methyl Bromide [Bromomethane] <10 <10 50 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 30 Methyl Chloride [Chloromethane] <10 <10 50 Methylene Chloride <5 <5 20 1,1,2,2-Tetrachloroethane <5 <5 10 Tetrachloroethylene <5 <5 10 Toluene <5 <5 10 1,2-trans-Dichloroethylene BA BA 10 1,1,1-Trichloroethane <5 <5 10 1,1,2-Trichloroethane <5 <5 10 Trichloroethylene <5 <5 10 Trichlorofluoromethane <10 <10 10 Vinyl Chloride <10 <10 10 ACID COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol <5 <5 10 2,4-Dichlorophenol <5 <5 10 2,4-Dimethylphenol <5 <5 10 4,6-Dinitro-o-Cresol <50 <50 50 2,4-Dinitrophenol <50 <50 50 2-Nitrophenol <5 <5 20 4-Nitrophenol <50 <50 50 p-Chloro-m-Cresol <5 <5 10 Pentachlorophenol <50 <50 50 Phenol <5 <5 10 2,4,6-Trichlorophenol <5 <5 10 BASE/NEUTRAL COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Acenaphthene <5 <5 10 Acenaphthylene <5 <5 10 Anthracene <5 <5 10 Benzidine <50 <50 50 Benzo(a)anthracene <5 <5 10 Benzo(a)pyrene <5 <5 10 3,4-Benzofluoranthene <5 <5 10 Benzo(ghi)perylene <5 <5 20 Benzo(k)fluoranthene <5 <5 10 Bis(2-chloroethoxy) Methane <5 <5 10 Bis(2-chloroethyl) Ether <5 <5 10 Bis(2-chloroisopropyl) Ether <5 <5 10 Bis(2-ethylhexyl) Phthalate <5 <5 10 4-Bromophenyl Phenyl Ether <5 <5 10 Butylbenzyl Phthalate <5 <5 10 2-Chloronaphthalene <5 <5 10 4-Chlorophenyl Phenyl Ether <5 <5 10 Chrysene <5 <5 10 Dibenzo(a,h)anthracene <5 <5 20 1,2-Dichlorobenzene <5 <5 10 1,3-Dichlorobenzene <5 <5 10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 31 1,4-Dichlorobenzene <5 <5 10 3,3'-Dichlorobenzidine <5 <5 50 Diethyl Phthalate <5 <5 10 Dimethyl Phthalate <5 <5 10 Di-n-Butyl Phthalate <5 <5 10 2,4-Dinitrotoluene <5 <5 10 2,6-Dinitrotoluene <5 <5 10 Di-n-octyl Phthalate <5 <5 10 1,2-Diphenylhydrazine <5 <5 20 Fluoranthene <5 <5 10 Fluorene <5 <5 10 Hexachlorobenzene <5 <5 10 Hexachlorobutadiene <5 <5 10 Hexachlorocyclopentadiene <5 <5 10 Hexachloroethane <5 <5 20 Indeno(1,2,3-cd)pyrene <5 <5 20 Isophorone <5 <5 10 Naphthalene <5 <5 10 Nitrobenzene <5 <5 10 n-Nitrosodimethylamine <5 <5 50 n-Nitrosodi-n-Propylamine <5 <5 20 n-Nitrosodiphenylamine <5 <5 20 Phenanthrene <5 <5 10 Pyrene <5 <5 10 1,2,4-Trichlorobenzene <5 <5 10 PESTICIDES (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Aldrin BA BA 0.05 Alpha-BHC BA BA 0.05 Beta-BHC BA BA 0.05 Gamma-BHC [Lindane] BA BA 0.05 Delta-BHC BA BA 0.05 Chlordane BA BA 0.2 4,4'-DDT BA BA 0.1 4,4'-DDE [p,p-DDX] BA BA 0.1 4,4'-DDD [p,p-TDE] BA BA 0.1 Dieldrin BA BA 0.1 Alpha-Endosulfan BA BA 0.1 Beta-Endosulfan BA BA 0.1 Endosulfan Sulfate BA BA 0.1 Endrin BA BA 0.1 Endrin Aldehyde BA BA 0.1 Heptachlor BA BA 0.05 Heptachlor Epoxide BA BA 0.05 PCB-1242 BA BA 1.0 PCB-1254 BA BA 1.0 PCB-1221 BA BA 1.0 PCB-1232 BA BA 1.0 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 32 PCB-1248 BA BA 1.0 PCB-1260 BA BA 1.0 PCB-1016 BA BA 1.0 Toxaphene BA BA 5.0

BA - Believed Absent

NA - Not Available

Internal Outfall 601 A. Type of wastewater - the intermittent internal discharge from Auxiliary Component Cooling Water Basin B to Final Outfall 001 via

the turbine condenser cooling system. Low volume wastewater

sources contributing to the flow monitored at this outfall

include, but are not limited to, auxiliary component cooling

water, component cooling water, Mississippi River water used for

flow testing, and stormwater.

B. Location - at the point of discharge from Auxiliary Component Cooling Water Basin B prior to combining with the waters of Final

Outfall 001 at Latitude 2959'44", Longitude 9028'13". C. Treatment - treatment of these low volume wastewaters consists of:

- sedimentation

- neutralization/pH adjustment, when required

- side stream ionization, when required

- filtration, when required D. Flow - Intermittent, (Max 30-Day) 0.26 MGD E. Receiving waters - Discharge to Outfall 001 F. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA

Form 2C) received on June 15, 1998.

POLLUTANT EFFLUENT PART A (mg/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand <2.0 <2.0 ---

Chemical Oxygen Demand 26.0 26.0 ---

Total Organic Carbon 7.0 7.0 ---

Total Suspended Solids 4.3 4.3 ---

Ammonia (as N) <0.1 <0.1 ---

Temperature (Winter) NA NA --- (Summer) NA NA --- pH (Standard Units) 7.47 7.71 --- (min) (max)

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 33 PART B (mg/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Bromide BA BA ---

Chlorine, Total Residual BA BA ---

Color (nM Units) 15.0 15.0 ---

Fecal Coliform (col/100 mL) BA BA ---

Fluoride BA BA ---

Nitrate-Nitrite (N) 0.9 0.9 ---

Organic Nitrogen, Total as (N) BA BA ---

Oil and Grease <1.0 <1.0 ---

Phosphorous, Total as (P) 2.5 2.5 ---

Radioactivity:

Alpha, Total (pCi/L) 0.5 0.5 ---

Beta, Total (pCi/L) 11.0 11.0 ---

Radium, Total (pCi/L) BA BA ---

Radium 226, Total (pCi/L) BA BA ---

Sulfate (as SO

4) 11.0 11.0 --- Sulfide (as S) BA BA ---

Sulfite (as SO

3) BA BA --- Surfactants BA BA ---

Aluminum (Total) 0.09 0.09 ---

Barium (Total) <0.02 <0.02 ---

Boron (Total) 0.2 0.2 ---

Cobalt (Total) BA BA ---

Iron (Total) 0.5 0.5 ---

Magnesium (Total) 0.5 0.5 ---

Manganese (Total) BA BA ---

Tin (Total) BA BA ---

Titanium (Total) BA BA ---

METALS, CYANIDE & TOTAL PHENOL (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Antimony (Total) <50 <50 60 Arsenic (Total) <3 <3 10 Beryllium (Total) <4 <4 5 Cadmium (Total) <1 <1 1 Chromium (Total) 10 10 10 Chromium (3+) NA NA 10 Chromium (6+) NA NA 10 Copper (Total) 20 20 10 Lead (Total) 6 6 5 Mercury (Total) 2.0 2.0 0.2 Molybdenum (Total) <10 <10 30 Nickel (Total) Freshwater <40 <40 40 Nickel (Total) Marine NA NA 5 Selenium (Total) <5 <5 5 Silver (Total) <0.5 <0.5 2 Thallium (Total) <5 <5 10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 34 Zinc (Total) 1,720 1,720 20 Cyanide (Total) <10 <10 10

Phenolics, Total Recoverable (4AAP) <10 <10 5 DIOXIN (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD BA BA 0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Acrolein BA BA 50 Acrylonitrile BA BA 50 Benzene <5 <5 10 Bis(Chloromethyl)Ether BA BA 10 Bromoform <5 <5 10 Carbon Tetrachloride <5 <5 10 Chlorobenzene <5 <5 10 Chlorodibromomethane <5 <5 10 Chloroethane <10 <10 50 2-Chloroethylvinylether <5 <5 10 Chloroform <5 <5 10 Dichlorobromomethane <5 <5 10 Dichlorodifluoromethane <10 <10 10 1,1-Dichloroethane <5 <5 10 1,2-Dichloroethane <5 <5 10 1,1-Dichloroethylene <5 <5 10 1,2-Dichloropropane <5 <5 10 1,3-Dichloropropylene <5 <5 10 Ethylbenzene <5 <5 10 Methyl Bromide [Bromomethane] <10 <10 50 Methyl Chloride [Chloromethane] <10 <10 50 Methylene Chloride <5 <5 20 1,1,2,2-Tetrachloroethane <5 <5 10 Tetrachloroethylene <5 <5 10 Toluene <5 <5 10 1,2-trans-Dichloroethylene BA BA 10 1,1,1-Trichloroethane <5 <5 10 1,1,2-Trichloroethane <5 <5 10 Trichloroethylene <5 <5 10 Trichlorofluoromethane <10 <10 10 Vinyl Chloride <10 <10 10 ACID COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol <5 <5 10 2,4-Dichlorophenol <5 <5 10 2,4-Dimethylphenol <5 <5 10 4,6-Dinitro-o-Cresol <50 <50 50 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 35 2,4-Dinitrophenol <50 <50 50 2-Nitrophenol <5 <5 20 4-Nitrophenol <50 <50 50 p-Chloro-m-Cresol <5 <5 10 Pentachlorophenol <50 <50 50 Phenol <5 <5 10 2,4,6-Trichlorophenol <5 <5 10 BASE/NEUTRAL COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Acenaphthene <5 <5 10 Acenaphthylene <5 <5 10 Anthracene <5 <5 10 Benzidine <50 <50 50 Benzo(a)anthracene <5 <5 10 Benzo(a)pyrene <5 <5 10 3,4-Benzofluoranthene <5 <5 10 Benzo(ghi)perylene <5 <5 20 Benzo(k)fluoranthene <5 <5 10 Bis(2-chloroethoxy) Methane <5 <5 10 Bis(2-chloroethyl) Ether <5 <5 10 Bis(2-chloroisopropyl) Ether <5 <5 10 Bis(2-ethylhexyl) Phthalate <5 <5 10 4-Bromophenyl Phenyl Ether <5 <5 10 Butylbenzyl Phthalate <5 <5 10 2-Chloronaphthalene <5 <5 10 4-Chlorophenyl Phenyl Ether <5 <5 10 Chrysene <5 <5 10 Dibenzo(a,h)anthracene <5 <5 20 1,2-Dichlorobenzene <5 <5 10 1,3-Dichlorobenzene <5 <5 10 1,4-Dichlorobenzene <5 <5 10 3,3'-Dichlorobenzidine <5 <5 50 Diethyl Phthalate <5 <5 10 Dimethyl Phthalate <5 <5 10 Di-n-Butyl Phthalate <5 <5 10 2,4-Dinitrotoluene <5 <5 10 2,6-Dinitrotoluene <5 <5 10 Di-n-octyl Phthalate <5 <5 10 1,2-Diphenylhydrazine <5 <5 20 Fluoranthene <5 <5 10 Fluorene <5 <5 10 Hexachlorobenzene <5 <5 10 Hexachlorobutadiene <5 <5 10 Hexachlorocyclopentadiene <5 <5 10 Hexachloroethane <5 <5 20 Indeno(1,2,3-cd)pyrene <5 <5 20 Isophorone <5 <5 10 Naphthalene <5 <5 10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 36 Nitrobenzene <5 <5 10 n-Nitrosodimethylamine <5 <5 50 n-Nitrosodi-n-Propylamine <5 <5 20 n-Nitrosodiphenylamine <5 <5 20 Phenanthrene <5 <5 10 Pyrene <5 <5 10 1,2,4-Trichlorobenzene <5 <5 10 PESTICIDES (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Aldrin BA BA 0.05 Alpha-BHC BA BA 0.05 Beta-BHC BA BA 0.05 Gamma-BHC [Lindane] BA BA 0.05 Delta-BHC BA BA 0.05 Chlordane BA BA 0.2 4,4'-DDT BA BA 0.1 4,4'-DDE [p,p-DDX] BA BA 0.1 4,4'-DDD [p,p-TDE] BA BA 0.1 Dieldrin BA BA 0.1 Alpha-Endosulfan BA BA 0.1 Beta-Endosulfan BA BA 0.1 Endosulfan Sulfate BA BA 0.1 Endrin BA BA 0.1 Endrin Aldehyde BA BA 0.1 Heptachlor BA BA 0.05 Heptachlor Epoxide BA BA 0.05 PCB-1242 BA BA 1.0 PCB-1254 BA BA 1.0 PCB-1221 BA BA 1.0 PCB-1232 BA BA 1.0 PCB-1248 BA BA 1.0 PCB-1260 BA BA 1.0 PCB-1016 BA BA 1.0 Toxaphene BA BA 5.0

BA - Believed Absent

NA - Not Available

Internal Outfall 701 A. Type of wastewater - the intermittent internal discharge of cooling tower blowdown and low volume wastewaters from Dry Cooling

Tower Sump #1 to Final Outfall 001 via the turbine condenser

cooling system. In addition to the wet cooling tower blowdown,

low volume wastewater from various sources as defined in 40 CFR

423 are discharged from this outfall. Low volume wastewater

sources contributing to this monitored flow include, but are not

limited to, wet cooling tower leakage, auxiliary component cooling Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 37 water, component cooling water, and stormwater. Previously

monitored effluent from the Yard Oil Separator System (Internal

Outfall 104) is infrequently discharged through this outfall as a

result of maintenance activities. Optional discharge to Final

Outfall 004 via the plant drainage ditches may occur during

periods when the circulating water system is unavailable.

B. Location - at the point of discharge from Dry Cooling Tower Sump

  1. 1 prior to combining with the waters of Final Outfall 001 or

Final Outfall 004 at Latitude 2959'44", Longitude 9028'13". C. Treatment - treatment of these wastewaters consists of:

- sedimentation

- neutralization/pH adjustment, when required

- side stream ionization, when required

- filtration, when required D. Flow - Intermittent, (Max 30-Day) 0.01 MGD E. Receiving waters - Discharge to Outfall 001 or the optional discharge to Outfall 004 F. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA

Form 2C) received on June 15, 1998.

POLLUTANT EFFLUENT PART A (mg/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand <2.0 <2.0 ---

Chemical Oxygen Demand 26.0 26.0 ---

Total Organic Carbon 7.0 7.0 ---

Total Suspended Solids 4.3 4.3 ---

Ammonia (as N) <0.1 <0.1 ---

Temperature (Winter) NA NA --- (Summer) NA NA --- pH (Standard Units) 7.47 7.71 --- (min) (max)

PART B (mg/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Bromide BA BA ---

Chlorine, Total Residual BA BA ---

Color (nM Units) 15.0 15.0 ---

Fecal Coliform (col/100 mL) BA BA ---

Fluoride BA BA ---

Nitrate-Nitrite (N) 0.9 0.9 ---

Organic Nitrogen, Total as (N) BA BA ---

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 38 Oil and Grease <1.0 <1.0 ---

Phosphorous, Total as (P) 2.5 2.5 ---

Radioactivity:

Alpha, Total (pCi/L) 0.5 0.5 ---

Beta, Total (pCi/L) 11.0 11.0 ---

Radium, Total (pCi/L) BA BA ---

Radium 226, Total (pCi/L) BA BA ---

Sulfate (as SO

4) 11.0 11.0 --- Sulfide (as S) BA BA ---

Sulfite (as SO

3) BA BA --- Surfactants BA BA ---

Aluminum (Total) 0.09 0.09 ---

Barium (Total) <0.02 <0.02 ---

Boron (Total) 0.2 0.2 ---

Cobalt (Total) BA BA ---

Iron (Total) 0.5 0.5 ---

Magnesium (Total) 0.5 0.5 ---

Manganese (Total) BA BA ---

Tin (Total) BA BA ---

Titanium (Total) BA BA ---

METALS, CYANIDE & TOTAL PHENOL (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Antimony (Total) <50 <50 60 Arsenic (Total) <3 <3 10 Beryllium (Total) <4 <4 5 Cadmium (Total) <1 <1 1 Chromium (Total) 10 10 10 Chromium (3+) NA NA 10 Chromium (6+) NA NA 10 Copper (Total) 20 20 10 Lead (Total) 6 6 5 Mercury (Total) 2.0 2.0 0.2 Molybdenum (Total) <10 <10 30 Nickel (Total) Freshwater <40 <40 40 Nickel (Total) Marine NA NA 5 Selenium (Total) <5 <5 5 Silver (Total) <0.5 <0.5 2 Thallium (Total) <5 <5 10 Zinc (Total) 1,720 1,720 20 Cyanide (Total) <10 <10 10

Phenolics, Total Recoverable (4AAP) <10 <10 5 DIOXIN (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD BA BA 0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED) MQL (g/L)

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 39 30-Day Max Daily Max Acrolein BA BA 50 Acrylonitrile BA BA 50 Benzene <5 <5 10 Bis(Chloromethyl)Ether BA BA 10 Bromoform <5 <5 10 Carbon Tetrachloride <5 <5 10 Chlorobenzene <5 <5 10 Chlorodibromomethane <5 <5 10 Chloroethane <10 <10 50 2-Chloroethylvinylether <5 <5 10 Chloroform <5 <5 10 Dichlorobromomethane <5 <5 10 Dichlorodifluoromethane <10 <10 10 1,1-Dichloroethane <5 <5 10 1,2-Dichloroethane <5 <5 10 1,1-Dichloroethylene <5 <5 10 1,2-Dichloropropane <5 <5 10 1,3-Dichloropropylene <5 <5 10 Ethylbenzene <5 <5 10 Methyl Bromide [Bromomethane] <10 <10 50 Methyl Chloride [Chloromethane] <10 <10 50 Methylene Chloride <5 <5 20 1,1,2,2-Tetrachloroethane <5 <5 10 Tetrachloroethylene <5 <5 10 Toluene <5 <5 10 1,2-trans-Dichloroethylene BA BA 10 1,1,1-Trichloroethane <5 <5 10 1,1,2-Trichloroethane <5 <5 10 Trichloroethylene <5 <5 10 Trichlorofluoromethane <10 <10 10 Vinyl Chloride <10 <10 10 ACID COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol <5 <5 10 2,4-Dichlorophenol <5 <5 10 2,4-Dimethylphenol <5 <5 10 4,6-Dinitro-o-Cresol <50 <50 50 2,4-Dinitrophenol <50 <50 50 2-Nitrophenol <5 <5 20 4-Nitrophenol <50 <50 50 p-Chloro-m-Cresol <5 <5 10 Pentachlorophenol <50 <50 50 Phenol <5 <5 10 2,4,6-Trichlorophenol <5 <5 10 BASE/NEUTRAL COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 40 Acenaphthene <5 <5 10 Acenaphthylene <5 <5 10 Anthracene <5 <5 10 Benzidine <50 <50 50 Benzo(a)anthracene <5 <5 10 Benzo(a)pyrene <5 <5 10 3,4-Benzofluoranthene <5 <5 10 Benzo(ghi)perylene <5 <5 20 Benzo(k)fluoranthene <5 <5 10 Bis(2-chloroethoxy) Methane <5 <5 10 Bis(2-chloroethyl) Ether <5 <5 10 Bis(2-chloroisopropyl) Ether <5 <5 10 Bis(2-ethylhexyl) Phthalate <5 <5 10 4-Bromophenyl Phenyl Ether <5 <5 10 Butylbenzyl Phthalate <5 <5 10 2-Chloronaphthalene <5 <5 10 4-Chlorophenyl Phenyl Ether <5 <5 10 Chrysene <5 <5 10 Dibenzo(a,h)anthracene <5 <5 20 1,2-Dichlorobenzene <5 <5 10 1,3-Dichlorobenzene <5 <5 10 1,4-Dichlorobenzene <5 <5 10 3,3'-Dichlorobenzidine <5 <5 50 Diethyl Phthalate <5 <5 10 Dimethyl Phthalate <5 <5 10 Di-n-Butyl Phthalate <5 <5 10 2,4-Dinitrotoluene <5 <5 10 2,6-Dinitrotoluene <5 <5 10 Di-n-octyl Phthalate <5 <5 10 1,2-Diphenylhydrazine <5 <5 20 Fluoranthene <5 <5 10 Fluorene <5 <5 10 Hexachlorobenzene <5 <5 10 Hexachlorobutadiene <5 <5 10 Hexachlorocyclopentadiene <5 <5 10 Hexachloroethane <5 <5 20 Indeno(1,2,3-cd)pyrene <5 <5 20 Isophorone <5 <5 10 Naphthalene <5 <5 10 Nitrobenzene <5 <5 10 n-Nitrosodimethylamine <5 <5 50 n-Nitrosodi-n-Propylamine <5 <5 20 n-Nitrosodiphenylamine <5 <5 20 Phenanthrene <5 <5 10 Pyrene <5 <5 10 1,2,4-Trichlorobenzene <5 <5 10 PESTICIDES (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 41 Aldrin BA BA 0.05 Alpha-BHC BA BA 0.05 Beta-BHC BA BA 0.05 Gamma-BHC [Lindane] BA BA 0.05 Delta-BHC BA BA 0.05 Chlordane BA BA 0.2 4,4'-DDT BA BA 0.1 4,4'-DDE [p,p-DDX] BA BA 0.1 4,4'-DDD [p,p-TDE] BA BA 0.1 Dieldrin BA BA 0.1 Alpha-Endosulfan BA BA 0.1 Beta-Endosulfan BA BA 0.1 Endosulfan Sulfate BA BA 0.1 Endrin BA BA 0.1 Endrin Aldehyde BA BA 0.1 Heptachlor BA BA 0.05 Heptachlor Epoxide BA BA 0.05 PCB-1242 BA BA 1.0 PCB-1254 BA BA 1.0 PCB-1221 BA BA 1.0 PCB-1232 BA BA 1.0 PCB-1248 BA BA 1.0 PCB-1260 BA BA 1.0 PCB-1016 BA BA 1.0 Toxaphene BA BA 5.0

BA - Believed Absent

NA - Not Available

Internal Outfall 801 A. Type of wastewater - the intermittent internal discharge of cooling tower blowdown and low volume wastewaters from Dry Cooling

Tower Sump #2 to Final Outfall 001 via the turbine condenser

cooling system. In addition to the wet cooling tower blowdown,

low volume wastewater from various sources as defined in 40 CFR

423 are discharged from this outfall. Low volume wastewater

sources contributing to this monitored flow include, but are not

limited to, wet cooling tower leakage, auxiliary component cooling

water, component cooling water, and stormwater. Previously

monitored effluent from the Yard Oil Separator System (Internal

Outfall 104) is infrequently discharged through this outfall as a

result of maintenance activities. Optional discharge to Final

Outfall 004 via the plant drainage ditches may occur during

periods when the circulating water system is unavailable.

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 42 B. Location - at the point of discharge from Dry Cooling Tower Sump

  1. 2 prior to combining with the waters of Final Outfall 001 or

Final Outfall 004 at Latitude 2959'44", Longitude 9028'13". C. Treatment - treatment of these wastewaters consists of:

- sedimentation

- neutralization/pH adjustment, when required

- side stream ionization, when required

- filtration, when required D. Flow - Intermittent, (Max 30-Day) 0.01 MGD E. Receiving waters - Discharge to Outfall 001 or the optional discharge to Outfall 004 F. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA

Form 2C) received on June 15, 1998.

POLLUTANT EFFLUENT PART A (mg/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand <2.0 <2.0 ---

Chemical Oxygen Demand 26.0 26.0 ---

Total Organic Carbon 7.0 7.0 ---

Total Suspended Solids 4.3 4.3 ---

Ammonia (as N) <0.1 <0.1 ---

Temperature (Winter) NA NA --- (Summer) NA NA --- pH (Standard Units) 7.47 7.71 --- (min) (max)

PART B (mg/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Bromide BA BA ---

Chlorine, Total Residual BA BA ---

Color (nM Units) 15.0 15.0 ---

Fecal Coliform (col/100 mL) BA BA ---

Fluoride BA BA ---

Nitrate-Nitrite (N) 0.9 0.9 ---

Organic Nitrogen, Total as (N) BA BA ---

Oil and Grease <1.0 <1.0 ---

Phosphorous, Total as (P) 2.5 2.5 ---

Radioactivity:

Alpha, Total (pCi/L) 0.5 0.5 ---

Beta, Total (pCi/L) 11.0 11.0 ---

Radium, Total (pCi/L) BA BA ---

Radium 226, Total (pCi/L) BA BA ---

Sulfate (as SO

4) 11.0 11.0 ---

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 43 Sulfide (as S) BA BA ---

Sulfite (as SO

3) BA BA --- Surfactants BA BA ---

Aluminum (Total) 0.09 0.09 ---

Barium (Total) <0.02 <0.02 ---

Boron (Total) 0.2 0.2 ---

Cobalt (Total) BA BA ---

Iron (Total) 0.5 0.5 ---

Magnesium (Total) 0.5 0.5 ---

Manganese (Total) BA BA ---

Tin (Total) BA BA ---

Titanium (Total) BA BA ---

METALS, CYANIDE & TOTAL PHENOL (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Antimony (Total) <50 <50 60 Arsenic (Total) <3 <3 10 Beryllium (Total) <4 <4 5 Cadmium (Total) <1 <1 1 Chromium (Total) 10 10 10 Chromium (3+) NA NA 10 Chromium (6+) NA NA 10 Copper (Total) 20 20 10 Lead (Total) 6 6 5 Mercury (Total) 2.0 2.0 0.2 Molybdenum (Total) <10 <10 30 Nickel (Total) Freshwater <40 <40 40 Nickel (Total) Marine NA NA 5 Selenium (Total) <5 <5 5 Silver (Total) <0.5 <0.5 2 Thallium (Total) <5 <5 10 Zinc (Total) 1,720 1,720 20 Cyanide (Total) <10 <10 10

Phenolics, Total Recoverable (4AAP) <10 <10 5 DIOXIN (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD BA BA 0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Acrolein BA BA 50 Acrylonitrile BA BA 50 Benzene <5 <5 10 Bis(Chloromethyl)Ether BA BA 10 Bromoform <5 <5 10 Carbon Tetrachloride <5 <5 10 Chlorobenzene <5 <5 10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 44 Chlorodibromomethane <5 <5 10 Chloroethane <10 <10 50 2-Chloroethylvinylether <5 <5 10 Chloroform <5 <5 10 Dichlorobromomethane <5 <5 10 Dichlorodifluoromethane <10 <10 10 1,1-Dichloroethane <5 <5 10 1,2-Dichloroethane <5 <5 10 1,1-Dichloroethylene <5 <5 10 1,2-Dichloropropane <5 <5 10 1,3-Dichloropropylene <5 <5 10 Ethylbenzene <5 <5 10 Methyl Bromide [Bromomethane] <10 <10 50 Methyl Chloride [Chloromethane] <10 <10 50 Methylene Chloride <5 <5 20 1,1,2,2-Tetrachloroethane <5 <5 10 Tetrachloroethylene <5 <5 10 Toluene <5 <5 10 1,2-trans-Dichloroethylene BA BA 10 1,1,1-Trichloroethane <5 <5 10 1,1,2-Trichloroethane <5 <5 10 Trichloroethylene <5 <5 10 Trichlorofluoromethane <10 <10 10 Vinyl Chloride <10 <10 10 ACID COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol <5 <5 10 2,4-Dichlorophenol <5 <5 10 2,4-Dimethylphenol <5 <5 10 4,6-Dinitro-o-Cresol <50 <50 50 2,4-Dinitrophenol <50 <50 50 2-Nitrophenol <5 <5 20 4-Nitrophenol <50 <50 50 p-Chloro-m-Cresol <5 <5 10 Pentachlorophenol <50 <50 50 Phenol <5 <5 10 2,4,6-Trichlorophenol <5 <5 10 BASE/NEUTRAL COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Acenaphthene <5 <5 10 Acenaphthylene <5 <5 10 Anthracene <5 <5 10 Benzidine <50 <50 50 Benzo(a)anthracene <5 <5 10 Benzo(a)pyrene <5 <5 10 3,4-Benzofluoranthene <5 <5 10 Benzo(ghi)perylene <5 <5 20 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 45 Benzo(k)fluoranthene <5 <5 10 Bis(2-chloroethoxy) Methane <5 <5 10 Bis(2-chloroethyl) Ether <5 <5 10 Bis(2-chloroisopropyl) Ether <5 <5 10 Bis(2-ethylhexyl) Phthalate <5 <5 10 4-Bromophenyl Phenyl Ether <5 <5 10 Butylbenzyl Phthalate <5 <5 10 2-Chloronaphthalene <5 <5 10 4-Chlorophenyl Phenyl Ether <5 <5 10 Chrysene <5 <5 10 Dibenzo(a,h)anthracene <5 <5 20 1,2-Dichlorobenzene <5 <5 10 1,3-Dichlorobenzene <5 <5 10 1,4-Dichlorobenzene <5 <5 10 3,3'-Dichlorobenzidine <5 <5 50 Diethyl Phthalate <5 <5 10 Dimethyl Phthalate <5 <5 10 Di-n-Butyl Phthalate <5 <5 10 2,4-Dinitrotoluene <5 <5 10 2,6-Dinitrotoluene <5 <5 10 Di-n-octyl Phthalate <5 <5 10 1,2-Diphenylhydrazine <5 <5 20 Fluoranthene <5 <5 10 Fluorene <5 <5 10 Hexachlorobenzene <5 <5 10 Hexachlorobutadiene <5 <5 10 Hexachlorocyclopentadiene <5 <5 10 Hexachloroethane <5 <5 20 Indeno(1,2,3-cd)pyrene <5 <5 20 Isophorone <5 <5 10 Naphthalene <5 <5 10 Nitrobenzene <5 <5 10 n-Nitrosodimethylamine <5 <5 50 n-Nitrosodi-n-Propylamine <5 <5 20 n-Nitrosodiphenylamine <5 <5 20 Phenanthrene <5 <5 10 Pyrene <5 <5 10 1,2,4-Trichlorobenzene <5 <5 10 PESTICIDES (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Aldrin BA BA 0.05 Alpha-BHC BA BA 0.05 Beta-BHC BA BA 0.05 Gamma-BHC [Lindane] BA BA 0.05 Delta-BHC BA BA 0.05 Chlordane BA BA 0.2 4,4'-DDT BA BA 0.1 4,4'-DDE [p,p-DDX] BA BA 0.1 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 46 4,4'-DDD [p,p-TDE] BA BA 0.1 Dieldrin BA BA 0.1 Alpha-Endosulfan BA BA 0.1 Beta-Endosulfan BA BA 0.1 Endosulfan Sulfate BA BA 0.1 Endrin BA BA 0.1 Endrin Aldehyde BA BA 0.1 Heptachlor BA BA 0.05 Heptachlor Epoxide BA BA 0.05 PCB-1242 BA BA 1.0 PCB-1254 BA BA 1.0 PCB-1221 BA BA 1.0 PCB-1232 BA BA 1.0 PCB-1248 BA BA 1.0 PCB-1260 BA BA 1.0 PCB-1016 BA BA 1.0 Toxaphene BA BA 5.0

BA - Believed Absent

NA - Not Available

Internal Outfall 901 A. Type of wastewater - the intermittent internal discharge of metal cleaning wastewaters from internal components of plant equipment

to Final Outfall 001 via the turbine condenser cooling system.

Metal cleaning wastewaters (both chemical and non-chemical) result

from the cleaning washes/rinses of various plant equipment

components including, but not limited to, the steam generator, the

cooling water heat exchangers, and piping.

B. Location - at the point of discharge from the mobile cleaning process unit(s) prior to combining with the waters of Final

Outfall 001 at Latitude 2959'47", Longitude 9028'8". C. Treatment - treatment of these wastewaters consists of:

- chemical precipitation

- neutralization

- sedimentation

- pre-aeration, when required

- flocculation, when required

- ion exchange, when required

D. Flow - Intermittent, (Max 30-Day) 0.36 MGD E. Receiving waters - Discharge to Outfall 001 F. Effluent Data - not available, new outfall

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 47 Outfall 004 A. Type of wastewater - the intermittent discharge from the plant drainage ditch system to 40 Arpent Canal. Outfall 004 is a new

outfall that consolidates Outfalls 04A and 04B from former NPDES

Permit LA0007374. Most of the effluent monitored at this outfall

is 85% stormwater runoff. Besides stormwater, potable water from

the fire water system, maintenance wastewaters including, but not

limited to: hydrostatic test water, air conditioning condensate,

low volume wastewaters from various sources as defined in 40 CFR

423, and previously monitored effluents exit the facility via

Outfall 004. Low volume sources contributing wastewater to this

outfall include, but are not limited to, reverse osmosis reject

water and demineralized water. The plant drainage ditch system

receives treated discharge from the yard oil separator system

(Internal Outfall 104), untreated vehicle wash wastewater

(Internal Outfall 204), and during maintenance activities

discharges from Dry Cooling Tower Sump #1 (Internal Outfall 701)

and Dry Cooling Tower Sump #2 (Internal Outfall 801).

B. Location - at the point of discharge from the plant drainage ditch system where the plant stormwater runoff, the previously monitored

effluents, and other infrequently discharged low volume

wastewaters discharge at Latitude 2959'19", Longitude 9028'25" prior to entering 40 Arpent Canal.

C. Treatment - none.

D. Flow - Intermittent, (Max 30-Day) 0.784 MGD

E. Receiving waters - 40 Arpent Canal thence to Lac Des Allemands F. Basin and segment - Barataria Basin, Segment 020202 G. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA

Form 2C) received on June 15, 1998.

POLLUTANT EFFLUENT PART A (mg/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand <2.0 <2.0 ---

Chemical Oxygen Demand <5.0 <5.0 ---

Total Organic Carbon 3.7 3.7 ---

Total Suspended Solids 7.0 7.0 ---

Ammonia (as N) 0.230 0.230 ---

Temperature (Winter) NA NA ---

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 48 (Summer) NA NA --- pH (Standard Units) 6.88 8.30 --- (min) (max)

PART B (mg/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Bromide BA BA ---

Chlorine, Total Residual BA BA ---

Color (nM Units) 15.0 15.0 ---

Fecal Coliform (col/100 mL) BA BA ---

Fluoride BA BA ---

Nitrate-Nitrite (N) 0.614 0.614 ---

Organic Nitrogen, Total as (N) BA BA ---

Oil and Grease <5.9 <5.9 ---

Phosphorous, Total as (P) 0.186 0.186 ---

Radioactivity:

Alpha, Total (pCi/L) NA NA ---

Beta, Total (pCi/L) NA NA ---

Radium, Total (pCi/L) BA BA ---

Radium 226, Total (pCi/L) BA BA ---

Sulfate (as SO

4) 38.7 38.7 --- Sulfide (as S) <1.0 <1.0 ---

Sulfite (as SO

3) <2.0 <2.0 --- Surfactants <0.04 <0.04 ---

Aluminum (Total) 0.415 0.415 ---

Barium (Total) <0.2 <0.2 ---

Boron (Total) NA NA ---

Cobalt (Total) BA BA ---

Iron (Total) 0.795 0.795 ---

Magnesium (Total) 11.3 11.3 ---

Manganese (Total) BA BA ---

Tin (Total) BA BA ---

Titanium (Total) BA BA ---

METALS, CYANIDE & TOTAL PHENOL (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Antimony (Total) BA BA 60 Arsenic (Total) BA BA 10 Beryllium (Total) <5 <5 5 Cadmium (Total) BA BA 1 Chromium (Total) <10 <10 10 Chromium (3+) NA NA 10 Chromium (6+) NA NA 10 Copper (Total) <10 <10 10 Lead (Total) BA BA 5 Mercury (Total) <0.2 <0.2 0.2 Molybdenum (Total) <10 <10 30 Nickel (Total) Freshwater <40 <40 40 Nickel (Total) Marine NA NA 5 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 49 Selenium (Total) BA BA 5 Silver (Total) BA BA 2 Thallium (Total) BA BA 10 Zinc (Total) 39.2 39.2 20 Cyanide (Total) <10 <10 10

Phenolics, Total Recoverable (4AAP) <50 <50 5 DIOXIN (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD BA BA 0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Acrolein <10 <10 50 Acrylonitrile <10 <10 50 Benzene <5 <5 10 Bis(Chloromethyl)Ether BA BA 10 Bromoform <5 <5 10 Carbon Tetrachloride <5 <5 10 Chlorobenzene <5 <5 10 Chlorodibromomethane <5 <5 10 Chloroethane <10 <10 50 2-Chloroethylvinylether <5 <5 10 Chloroform <5 <5 10 Dichlorobromomethane <5 <5 10 Dichlorodifluoromethane BA BA 10 1,1-Dichloroethane <5 <5 10 1,2-Dichloroethane <5 <5 10 1,1-Dichloroethylene <5 <5 10 1,2-Dichloropropane <5 <5 10 1,3-Dichloropropylene <5 <5 10 Ethylbenzene <5 <5 10 Methyl Bromide [Bromomethane] <10 <10 50 Methyl Chloride [Chloromethane] <10 <10 50 Methylene Chloride <5 <5 20 1,1,2,2-Tetrachloroethane <5 <5 10 Tetrachloroethylene <5 <5 10 Toluene <5 <5 10 1,2-trans-Dichloroethylene BA BA 10 1,1,1-Trichloroethane <5 <5 10 1,1,2-Trichloroethane <5 <5 10 Trichloroethylene <5 <5 10 Trichlorofluoromethane BA BA 10 Vinyl Chloride <10 <10 10 ACID COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol <10 <10 10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 50 2,4-Dichlorophenol <10 <10 10 2,4-Dimethylphenol <10 <10 10 4,6-Dinitro-o-Cresol <25 <25 50 2,4-Dinitrophenol <25 <25 50 2-Nitrophenol <10 <10 20 4-Nitrophenol <25 <25 50 p-Chloro-m-Cresol <10 <10 10 Pentachlorophenol <25 <25 50 Phenol <10 <10 10 2,4,6-Trichlorophenol <10 <10 10 BASE/NEUTRAL COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Acenaphthene <10 <10 10 Acenaphthylene <10 <10 10 Anthracene <10 <10 10 Benzidine <30 <30 50 Benzo(a)anthracene <10 <10 10 Benzo(a)pyrene <10 <10 10 3,4-Benzofluoranthene <10 <10 10 Benzo(ghi)perylene <10 <10 20 Benzo(k)fluoranthene <10 <10 10 Bis(2-chloroethoxy) Methane <10 <10 10 Bis(2-chloroethyl) Ether <10 <10 10 Bis(2-chloroisopropyl) Ether <10 <10 10 Bis(2-ethylhexyl) Phthalate <10 <10 10 4-Bromophenyl Phenyl Ether <10 <10 10 Butylbenzyl Phthalate <10 <10 10 2-Chloronaphthalene <10 <10 10 4-Chlorophenyl Phenyl Ether <10 <10 10 Chrysene <10 <10 10 Dibenzo(a,h)anthracene <10 <10 20 1,2-Dichlorobenzene <10 <10 10 1,3-Dichlorobenzene <10 <10 10 1,4-Dichlorobenzene <10 <10 10 3,3'-Dichlorobenzidine <20 <20 50 Diethyl Phthalate <10 <10 10 Dimethyl Phthalate <10 <10 10 Di-n-Butyl Phthalate <10 <10 10 2,4-Dinitrotoluene <10 <10 10 2,6-Dinitrotoluene <10 <10 10 Di-n-octyl Phthalate <10 <10 10 1,2-Diphenylhydrazine <10 <10 20 Fluoranthene <10 <10 10 Fluorene <10 <10 10 Hexachlorobenzene <10 <10 10 Hexachlorobutadiene <10 <10 10 Hexachlorocyclopentadiene <10 <10 10 Hexachloroethane <10 <10 20 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 51 Indeno(1,2,3-cd)pyrene <10 <10 20 Isophorone <10 <10 10 Naphthalene <10 <10 10 Nitrobenzene <10 <10 10 n-Nitrosodimethylamine <10 <10 50 n-Nitrosodi-n-Propylamine <10 <10 20 n-Nitrosodiphenylamine <10 <10 20 Phenanthrene <10 <10 10 Pyrene <10 <10 10 1,2,4-Trichlorobenzene <10 <10 10 PESTICIDES (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Aldrin BA BA 0.05 Alpha-BHC BA BA 0.05 Beta-BHC BA BA 0.05 Gamma-BHC [Lindane] BA BA 0.05 Delta-BHC BA BA 0.05 Chlordane BA BA 0.2 4,4'-DDT BA BA 0.1 4,4'-DDE [p,p-DDX] BA BA 0.1 4,4'-DDD [p,p-TDE] BA BA 0.1 Dieldrin BA BA 0.1 Alpha-Endosulfan BA BA 0.1 Beta-Endosulfan BA BA 0.1 Endosulfan Sulfate BA BA 0.1 Endrin BA BA 0.1 Endrin Aldehyde BA BA 0.1 Heptachlor BA BA 0.05 Heptachlor Epoxide BA BA 0.05 PCB-1242 BA BA 1.0 PCB-1254 BA BA 1.0 PCB-1221 BA BA 1.0 PCB-1232 BA BA 1.0 PCB-1248 BA BA 1.0 PCB-1260 BA BA 1.0 PCB-1016 BA BA 1.0 Toxaphene BA BA 5.0

BA - Believed Absent

NA - Not Available

Internal Outfall 104 (Former 002)

A. Type of wastewater - the intermittent internal discharge from the yard oil separator system to Final Outfall 004 via a plant

drainage ditch. Wastewater sources contributing to the flow

monitored at Outfall 104 include auxiliary boiler blowdown,

stormwater, and low volume wastewaters from various sources as Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 52 defined by 40 CFR 423. Low volume sources contributing wastewater

to this outfall include, but are not limited to, secondary water

system drains, system leakage, auxiliary boiler sumps, turbine

building equipment and floor drains, turbine building floor wash

downs, and laboratory drains. Optional discharge to Internal

Outfall 701 or 801 may occur during maintenance periods.

B. Location - at the point of discharge from the yard oil separator system prior to combining with the waters of Final Outfall 004 or

Internal Outfall 701 or Internal Outfall 801 at

Latitude 2959'37", Longitude 9028'15". C. Treatment - treatment of these wastewaters consists of:

- sedimentation

- flotation

- oil/water separation

- polymer injection, when required

- neutralization/pH adjustment, when required

- flocculation, when required

- filtration, when required D. Flow - Intermittent, (Max 30-Day) 0.0221 MGD E. Receiving waters - Discharge to Outfall 004, with option to discharge to either Internal Outfall 701, or Internal Outfall 801

during maintenance activities.

F. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA

Form 2C) received on June 15, 1998.

POLLUTANT EFFLUENT PART A (mg/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand <2.0 <2.0 ---

Chemical Oxygen Demand 9.1 9.1 ---

Total Organic Carbon 3.0 3.0 ---

Total Suspended Solids 23.9 29.6 ---

Ammonia (as N) 0.197 0.197 ---

Temperature (Winter) NA NA --- (Summer) NA NA --- pH (Standard Units) 6.62 8.24 --- (min) (max)

PART B (mg/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Bromide BA BA ---

Chlorine, Total Residual BA BA ---

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 53 Color (nM Units) 10 10 ---

Fecal Coliform (col/100 mL) BA BA ---

Fluoride BA BA ---

Nitrate-Nitrite (N) 0.05 0.05 ---

Organic Nitrogen, Total as (N) BA BA ---

Oil and Grease 10.1 18.5 ---

Phosphorous, Total as (P) 0.23 0.23 ---

Radioactivity:

Alpha, Total (pCi/L) 0.05 0.05 ---

Beta, Total (pCi/L) 0.01 0.01 ---

Radium, Total (pCi/L) BA BA ---

Radium 226, Total (pCi/L) BA BA ---

Sulfate (as SO

4) <10.0 <10.0 --- Sulfide (as S) <0.020 <0.020 ---

Sulfite (as SO

3) <2.0 <2.0 --- Surfactants <0.1 <0.1 ---

Aluminum (Total) <0.2 <0.2 ---

Barium (Total) <0.2 <0.2 ---

Boron (Total) BA BA ---

Cobalt (Total) BA BA ---

Iron (Total) 0.249 0.249 ---

Magnesium (Total) <5.0 <5.0 ---

Manganese (Total) BA BA ---

Tin (Total) BA BA ---

Titanium (Total) BA BA ---

METALS, CYANIDE & TOTAL PHENOL (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Antimony (Total) BA BA 60 Arsenic (Total) <10 <10 10 Beryllium (Total) <5 <5 5 Cadmium (Total) <1 <1 1 Chromium (Total) <10 <10 10 Chromium (3+) NA NA 10 Chromium (6+) NA NA 10 Copper (Total) <10 <10 10 Lead (Total) <3 <3 5 Mercury (Total) <0.2 <0.2 0.2 Molybdenum (Total) <50 <50 30 Nickel (Total) Freshwater <40 <40 40 Nickel (Total) Marine NA NA 5 Selenium (Total) <5 <5 5 Silver (Total) <2 <2 2 Thallium (Total) <10 <10 10 Zinc (Total) 84.5 84.5 20 Cyanide (Total) <10 <10 10

Phenolics, Total Recoverable (4AAP) <50 <50 5

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 54 DIOXIN (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD BA BA 0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Acrolein <10 <10 50 Acrylonitrile <10 <10 50 Benzene <5 <5 10 Bis(Chloromethyl)Ether BA BA 10 Bromoform <5 <5 10 Carbon Tetrachloride <5 <5 10 Chlorobenzene <5 <5 10 Chlorodibromomethane <5 <5 10 Chloroethane <10 <10 50 2-Chloroethylvinylether <5 <5 10 Chloroform <5 <5 10 Dichlorobromomethane <5 <5 10 Dichlorodifluoromethane BA BA 10 1,1-Dichloroethane <5 <5 10 1,2-Dichloroethane <5 <5 10 1,1-Dichloroethylene <5 <5 10 1,2-Dichloropropane <5 <5 10 1,3-Dichloropropylene <5 <5 10 Ethylbenzene <5 <5 10 Methyl Bromide [Bromomethane] <10 <10 50 Methyl Chloride [Chloromethane] <10 <10 50 Methylene Chloride <5 <5 20 1,1,2,2-Tetrachloroethane <5 <5 10 Tetrachloroethylene <5 <5 10 Toluene <5 <5 10 1,2-trans-Dichloroethylene <5 <5 10 1,1,1-Trichloroethane <5 <5 10 1,1,2-Trichloroethane <5 <5 10 Trichloroethylene <5 <5 10 Trichlorofluoromethane BA BA 10 Vinyl Chloride <10 <10 10 ACID COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol <10 <10 10 2,4-Dichlorophenol <10 <10 10 2,4-Dimethylphenol <10 <10 10 4,6-Dinitro-o-Cresol <50 <50 50 2,4-Dinitrophenol <50 <50 50 2-Nitrophenol <10 <10 20 4-Nitrophenol <50 <50 50 p-Chloro-m-Cresol <10 <10 10 Pentachlorophenol <50 <50 50 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 55 Phenol <10 <10 10 2,4,6-Trichlorophenol <10 <10 10 BASE/NEUTRAL COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Acenaphthene <10 <10 10 Acenaphthylene <10 <10 10 Anthracene <10 <10 10 Benzidine <30 <30 50 Benzo(a)anthracene <10 <10 10 Benzo(a)pyrene <10 <10 10 3,4-Benzofluoranthene <10 <10 10 Benzo(ghi)perylene <10 <10 20 Benzo(k)fluoranthene <10 <10 10 Bis(2-chloroethoxy) Methane <10 <10 10 Bis(2-chloroethyl) Ether <10 <10 10 Bis(2-chloroisopropyl) Ether <10 <10 10 Bis(2-ethylhexyl) Phthalate <10 <10 10 4-Bromophenyl Phenyl Ether <10 <10 10 Butylbenzyl Phthalate <10 <10 10 2-Chloronaphthalene <10 <10 10 4-Chlorophenyl Phenyl Ether <10 <10 10 Chrysene <10 <10 10 Dibenzo(a,h)anthracene <10 <10 20 1,2-Dichlorobenzene <10 <10 10 1,3-Dichlorobenzene <10 <10 10 1,4-Dichlorobenzene <10 <10 10 3,3'-Dichlorobenzidine <20 <20 50 Diethyl Phthalate <10 <10 10 Dimethyl Phthalate <10 <10 10 Di-n-Butyl Phthalate <10 <10 10 2,4-Dinitrotoluene <10 <10 10 2,6-Dinitrotoluene <10 <10 10 Di-n-octyl Phthalate <10 <10 10 1,2-Diphenylhydrazine <10 <10 20 Fluoranthene <10 <10 10 Fluorene <10 <10 10 Hexachlorobenzene <10 <10 10 Hexachlorobutadiene <10 <10 10 Hexachlorocyclopentadiene <10 <10 10 Hexachloroethane <10 <10 20 Indeno(1,2,3-cd)pyrene <10 <10 20 Isophorone <10 <10 10 Naphthalene <10 <10 10 Nitrobenzene <10 <10 10 n-Nitrosodimethylamine <20 <20 50 n-Nitrosodi-n-Propylamine <10 <10 20 n-Nitrosodiphenylamine <10 <10 20 Phenanthrene <10 <10 10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 56 Pyrene <10 <10 10 1,2,4-Trichlorobenzene <10 <10 10 PESTICIDES (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Aldrin BA BA 0.05 Alpha-BHC BA BA 0.05 Beta-BHC BA BA 0.05 Gamma-BHC [Lindane] BA BA 0.05 Delta-BHC BA BA 0.05 Chlordane BA BA 0.2 4,4'-DDT BA BA 0.1 4,4'-DDE [p,p-DDX] BA BA 0.1 4,4'-DDD [p,p-TDE] BA BA 0.1 Dieldrin BA BA 0.1 Alpha-Endosulfan BA BA 0.1 Beta-Endosulfan BA BA 0.1 Endosulfan Sulfate BA BA 0.1 Endrin BA BA 0.1 Endrin Aldehyde BA BA 0.1 Heptachlor BA BA 0.05 Heptachlor Epoxide BA BA 0.05 PCB-1242 BA BA 1.0 PCB-1254 BA BA 1.0 PCB-1221 BA BA 1.0 PCB-1232 BA BA 1.0 PCB-1248 BA BA 1.0 PCB-1260 BA BA 1.0 PCB-1016 BA BA 1.0 Toxaphene BA BA 5.0 BA - Believed Absent

NA - Not Available

Internal Outfall 204 (New Outfall)

A. Type of wastewater - the intermittent internal discharge of vehicle wash wastewater.

B. Location - at the point of discharge from the area where vehicles will be washed prior to combining with the waters of Final Outfall

004. C. Treatment - none.

D. Flow - Intermittent.

E. Receiving waters - Discharge to Outfall 004.

F. Effluent Data - not available, new outfall.

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 57 Outfall 005 A. Type of wastewater - the intermittent discharge from the Entergy Energy Education Center sewage treatment plant to 40 Arpent Canal.

In addition to the sanitary wastewater, a de minimis discharge

from the HVAC unit enters the sewage treatment plant.

B. Location - at the point of discharge from the sewage treatment plant prior to combining with the waters of the 40 Arpent Canal at

Latitude 2958'53", Longitude 9028'35". C. Treatment - a package sewage treatment plant with chlorination used for disinfection.

D. Flow - Intermittent, (Max 30-Day) 0.0018 MGD.

E. Receiving waters - 40 Arpent Canal thence to Lac Des Allemands F. Basin and segment - Barataria Basin, Segment 020202 G. Effluent Data - The following is a summary of the effluent characteristics reported in the revised permit application (EPA

Form 2C) received on June 15, 1998.

POLLUTANT EFFLUENT PART A (mg/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Biochemical Oxygen Demand 28.0 28.0 ---

Chemical Oxygen Demand 56.9 56.9 ---

Total Organic Carbon 18.6 18.6 ---

Total Suspended Solids 24 27 ---

Ammonia (as N) 17.9 17.9 ---

Temperature (Winter) NA NA --- (Summer) NA NA --- pH (Standard Units) 7.20 8.27 --- (min) (max)

PART B (mg/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Bromide BA BA ---

Chlorine, Total Residual BA BA ---

Color (nM Units) 25 25 ---

Fecal Coliform (col/100 mL) <2.0 <2.0 ---

Fluoride BA BA ---

Nitrate-Nitrite (N) 3.77 3.77 ---

Organic Nitrogen, Total as (N) BA BA ---

Oil and Grease <5.60 <5.60 ---

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 58 Phosphorous, Total as (P) 2.8 2.8 ---

Radioactivity:

Alpha, Total (pCi/L) BA BA ---

Beta, Total (pCi/L) BA BA ---

Radium, Total (pCi/L) BA BA ---

Radium 226, Total (pCi/L) BA BA ---

Sulfate (as SO

4) 1,510 1,510 --- Sulfide (as S) <1.0 <1.0 ---

Sulfite (as SO

3) <2.0 <2.0 --- Surfactants <0.04 <0.04 ---

Aluminum (Total) BA BA ---

Barium (Total) BA BA ---

Boron (Total) BA BA ---

Cobalt (Total) BA BA ---

Iron (Total) BA BA ---

Magnesium (Total) BA BA ---

Manganese (Total) BA BA ---

Tin (Total) BA BA ---

Titanium (Total) BA BA ---

METALS, CYANIDE & TOTAL PHENOL (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Antimony (Total) BA BA 60 Arsenic (Total) <10 <10 10 Beryllium (Total) <5 <5 5 Cadmium (Total) 0.161 0.161 1 Chromium (Total) <10 <10 10 Chromium (3+) NA NA 10 Chromium (6+) NA NA 10 Copper (Total) 118 118 10 Lead (Total) <3 <3 5 Mercury (Total) <0.2 <0.2 0.2 Molybdenum (Total) BA BA 30 Nickel (Total) Freshwater <40 <40 40 Nickel (Total) Marine NA NA 5 Selenium (Total) <5 <5 5 Silver (Total) <1 <1 2 Thallium (Total) <10 <10 10 Zinc (Total) <20 <20 20 Cyanide (Total) 19 19 10

Phenolics, Total Recoverable (4AAP) <50 <50 5 DIOXIN (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max 2,3,7,8-TCDD BA BA 0.00001 VOLATILE COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 59 Acrolein <10 <10 50 Acrylonitrile <10 <10 50 Benzene <5 <5 10 Bis(Chloromethyl)Ether BA BA 10 Bromoform <5 <5 10 Carbon Tetrachloride <5 <5 10 Chlorobenzene <5 <5 10 Chlorodibromomethane <5 <5 10 Chloroethane <10 <10 50 2-Chloroethylvinylether <5 <5 10 Chloroform 19.7 19.7 10 Dichlorobromomethane <5 <5 10 Dichlorodifluoromethane BA BA 10 1,1-Dichloroethane <5 <5 10 1,2-Dichloroethane <5 <5 10 1,1-Dichloroethylene <5 <5 10 1,2-Dichloropropane <5 <5 10 1,3-Dichloropropylene <5 <5 10 Ethylbenzene <5 <5 10 Methyl Bromide [Bromomethane] <10 <10 50 Methyl Chloride [Chloromethane] <10 <10 50 Methylene Chloride 13.9 13.9 20 1,1,2,2-Tetrachloroethane <5 <5 10 Tetrachloroethylene <5 <5 10 Toluene <5 <5 10 1,2-trans-Dichloroethylene BA BA 10 1,1,1-Trichloroethane <5 <5 10 1,1,2-Trichloroethane <5 <5 10 Trichloroethylene <5 <5 10 Trichlorofluoromethane BA BA 10 Vinyl Chloride <10 <10 10 ACID COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max 2-Chlorophenol <10 <10 10 2,4-Dichlorophenol <10 <10 10 2,4-Dimethylphenol <10 <10 10 4,6-Dinitro-o-Cresol <25 <25 50 2,4-Dinitrophenol <25 <25 50 2-Nitrophenol <10 <10 20 4-Nitrophenol <25 <25 50 p-Chloro-m-Cresol <10 <10 10 Pentachlorophenol <25 <25 50 Phenol <10 <10 10 2,4,6-Trichlorophenol <10 <10 10 BASE/NEUTRAL COMPOUNDS (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Acenaphthene <10 <10 10 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 60 Acenaphthylene <10 <10 10 Anthracene <10 <10 10 Benzidine <30 <30 50 Benzo(a)anthracene <10 <10 10 Benzo(a)pyrene <10 <10 10 3,4-Benzofluoranthene <10 <10 10 Benzo(ghi)perylene <10 <10 20 Benzo(k)fluoranthene <10 <10 10 Bis(2-chloroethoxy) Methane <10 <10 10 Bis(2-chloroethyl) Ether <10 <10 10 Bis(2-chloroisopropyl) Ether <10 <10 10 Bis(2-ethylhexyl) Phthalate <10 <10 10 4-Bromophenyl Phenyl Ether <10 <10 10 Butylbenzyl Phthalate <10 <10 10 2-Chloronaphthalene <10 <10 10 4-Chlorophenyl Phenyl Ether <10 <10 10 Chrysene <10 <10 10 Dibenzo(a,h)anthracene <10 <10 20 1,2-Dichlorobenzene <10 <10 10 1,3-Dichlorobenzene <10 <10 10 1,4-Dichlorobenzene <10 <10 10 3,3'-Dichlorobenzidine <20 <20 50 Diethyl Phthalate <10 <10 10 Dimethyl Phthalate <10 <10 10 Di-n-Butyl Phthalate <10 <10 10 2,4-Dinitrotoluene <10 <10 10 2,6-Dinitrotoluene <10 <10 10 Di-n-octyl Phthalate <10 <10 10 1,2-Diphenylhydrazine <10 <10 20 Fluoranthene <10 <10 10 Fluorene <10 <10 10 Hexachlorobenzene <10 <10 10 Hexachlorobutadiene <10 <10 10 Hexachlorocyclopentadiene <10 <10 10 Hexachloroethane <10 <10 20 Indeno(1,2,3-cd)pyrene <10 <10 20 Isophorone <10 <10 10 Naphthalene <10 <10 10 Nitrobenzene <10 <10 10 n-Nitrosodimethylamine <10 <10 50 n-Nitrosodi-n-Propylamine <10 <10 20 n-Nitrosodiphenylamine <10 <10 20 Phenanthrene <10 <10 10 Pyrene <10 <10 10 1,2,4-Trichlorobenzene <10 <10 10 PESTICIDES (g/L, UNLESS STATED) MQL (g/L) 30-Day Max Daily Max Aldrin BA BA 0.05 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 61 Alpha-BHC BA BA 0.05 Beta-BHC BA BA 0.05 Gamma-BHC [Lindane] BA BA 0.05 Delta-BHC BA BA 0.05 Chlordane BA BA 0.2 4,4'-DDT BA BA 0.1 4,4'-DDE [p,p-DDX] BA BA 0.1 4,4'-DDD [p,p-TDE] BA BA 0.1 Dieldrin BA BA 0.1 Alpha-Endosulfan BA BA 0.1 Beta-Endosulfan BA BA 0.1 Endosulfan Sulfate BA BA 0.1 Endrin BA BA 0.1 Endrin Aldehyde BA BA 0.1 Heptachlor BA BA 0.05 Heptachlor Epoxide BA BA 0.05 PCB-1242 BA BA 1.0 PCB-1254 BA BA 1.0 PCB-1221 BA BA 1.0 PCB-1232 BA BA 1.0 PCB-1248 BA BA 1.0 PCB-1260 BA BA 1.0 PCB-1016 BA BA 1.0 Toxaphene BA BA 5.0 BA - Believed Absent

NA - Not Available

VIII. Proposed Permit Limits:

The specific effluent limitations and/or conditions will be found in the

draft permit. Development and calculation of permit limits are detailed

in the Permit Limit Rationale section below.

Summary of Proposed Changes From the Current NPDES Permit:

A. Final Outfall 001:

1. Increase the instantaneous daily maximum temperature limit from 110F to 118F. 2. Increase the daily maximum heat limit from 8.5 x 10 9 BTU/hr to 9.5 x 10 9 BTU/hr.
3. Change the acute freshwater whole effluent toxicity biomonitoring frequency from quarterly to once per year.

B. Internal Outfall 101 (Former 01A):

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 62 1. Only daily maximum reporting of flow in MGD rather than the daily average flow limit of 0.0288 MGD is proposed due to

the intermittent nature of the wastestream.

2. Only daily maximum limitations are proposed due to the intermittent nature of the wastestream.

C. Internal Outfall 201 (Former 01B):

1. Only daily maximum reporting of flow in MGD rather than the daily average flow limit of 0.0288 MGD is proposed due to

the intermittent nature of the wastestream.

2. Only daily maximum limitations are proposed due to the intermittent nature of the wastestream.

D. Internal Outfall 301 (Former 01C):

1. Only daily maximum reporting of flow in MGD is proposed due to the intermittent nature of the wastestream.
2. Change the reporting requirement for clarifying agents.

E. Internal Outfall 401 (Former 01D):

1. Only daily maximum reporting of flow in MGD is proposed due to the intermittent nature of the wastestream.
2. Only daily maximum limitation for Total Suspended Solids is proposed due to the intermittent nature of the wastestream.
3. Establish daily maximum limitation for oil and grease (O&G) at 20 mg/l.
4. Establish monitoring frequency of 1/week for TSS, Oil &

Grease, and pH, when discharging.

F. Internal Outfall 501 (New Outfall):

1. Add Internal Outfall 501 for the intermittent discharge from Auxiliary Component Cooling Water Basin A to Final Outfall

001 via the turbine condenser cooling system.

2. The daily maximum reporting of flow in MGD is proposed due to the intermittent nature of the wastestream.
3. Establish daily maximum limitation for total organic carbon (TOC) at 50 mg/l.

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 63 4. Establish daily maximum limitation for total suspended solids (TSS) at 100 mg/l.

5. Establish daily maximum limitation for oil and grease (O&G) at 20 mg/l.
6. Establish limitation for pH of not less than 6.0 standard units nor greater than 9.0 standard units.
7. Establish monitoring frequency of 1/week for TOC, TSS, Oil &

Grease, and pH, when discharging.

G. Internal Outfall 601 (New Outfall):

1. Add Internal Outfall 601 for the intermittent discharge from Auxiliary Component Cooling Water Basin B to Final Outfall

001 via the turbine condenser cooling system.

2. The daily maximum reporting of flow in MGD is proposed due to the intermittent nature of the wastestream.
3. Establish daily maximum limitation for total organic carbon (TOC) at 50 mg/l.
4. Establish daily maximum limitation for total suspended solids (TSS) at 100 mg/l.
5. Establish daily maximum limitation for oil and grease (O&G) at 20 mg/l.
6. Establish limitation for pH of not less than 6.0 standard units nor greater than 9.0 standard units.
7. Establish monitoring frequency of 1/week for TOC, TSS, Oil &

Grease, and pH, when discharging.

H. Internal Outfall 701 (New Outfall):

1. Add Internal Outfall 701 for the intermittent discharge of cooling tower blowdown and low volume wastewaters from Dry

Cooling Tower Sump #1 and the occasional discharge of

previously monitored effluent from Internal Outfall 104 to

Final Outfall 001 via the turbine condenser cooling system

or Final Outfall 004.

2. The daily maximum reporting of flow in MGD is proposed due to the intermittent nature of the wastestream.

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 64 3. Establish daily maximum limitation for total organic carbon (TOC) at 50 mg/l.

4. Establish daily maximum limitation for total suspended solids (TSS) at 100 mg/l.
5. Establish daily maximum limitation for oil and grease (O&G) at 20 mg/l.
6. Establish limitation for pH of not less than 6.0 standard units nor greater than 9.0 standard units.
7. Establish daily maximum limitation for free available chlorine (FAC) at 0.5 mg/l, when discharging cooling tower

blowdown.

8. Establish daily maximum limitation for total chromium at 0.2 mg/l, when discharging cooling tower blowdown.
9. Establish daily maximum limitation for total zinc at 1.0 mg/l, when discharging cooling tower blowdown.
10. Establish monitoring frequency of 1/month for TOC, TSS, Oil

& Grease, pH, FAC, total chromium, and total zinc, when

discharging.

I. Internal Outfall 801 (New Outfall):

1. Add Internal Outfall 801 for the intermittent discharge of cooling tower blowdown and low volume wastewaters from Dry

Cooling Tower Sump #2 and the occasional discharge of

previously monitored effluent from Internal Outfall 104 to

Final Outfall 001 via the turbine condenser cooling system

or Final Outfall 004.

2. The daily maximum reporting of flow in MGD is proposed due to the intermittent nature of the wastestream.
3. Establish daily maximum limitation for total organic carbon (TOC) at 50 mg/l.
4. Establish daily maximum limitation for total suspended solids (TSS) at 100 mg/l.
5. Establish daily maximum limitation for oil and grease (O&G) at 20 mg/l.
6. Establish limitation for pH of not less than 6.0 standard units nor greater than 9.0 standard units.

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 65 7. Establish daily maximum limitation for free available chlorine (FAC) at 0.5 mg/l, when discharging cooling tower

blowdown.

8. Establish daily maximum limitation for total chromium at 0.2 mg/l, when discharging cooling tower blowdown.
9. Establish daily maximum limitation for total zinc at 1.0 mg/l, when discharging cooling tower blowdown.
10. Establish monitoring frequency of 1/month for TOC, TSS, Oil

& Grease, pH, FAC, total chromium, and total zinc, when

discharging.

J. Internal Outfall 901 (New Outfall):

1. Add Internal Outfall 901 for the intermittent, mobile discharge of metal cleaning wastewaters from internal

components of plant equipment to Final Outfall 001 via the

turbine condenser cooling system.

2. The daily maximum reporting of flow in MGD is proposed due to the intermittent nature of the wastestream.
3. Establish daily maximum limitation for total suspended solids (TSS) at 100 mg/l.
4. Establish daily maximum limitation for oil and grease (O&G) at 20 mg/l.
5. Establish limitation for pH of not less than 6.0 standard units nor greater than 9.0 standard units.
6. Establish daily maximum limitation for total copper at 1.0 mg/l. 7. Establish daily maximum limitation for total iron at 1.0 mg/l. 8. Establish monitoring frequency of 1/week for TSS, Oil &

Grease, pH, total copper, and total iron, when discharging.

K. Final Outfall 004 (New Outfall):

1. Add Final Outfall 004 for the intermittent discharge from the plant drainage ditch system to 40 Arpent Canal and the

occasional discharge from Internal Outfall 701 and Internal

Outfall 801.

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 66 2. The daily maximum reporting of flow in MGD is proposed due to the intermittent nature of the wastestream.

3. Establish daily maximum limitation for total organic carbon (TOC) at 50 mg/l.
4. Establish daily maximum limitation for oil and grease (O&G) at 15 mg/l.
5. Require discharge limits for total suspended solids (TSS) of 100 mg/l for daily maximum, when discharging low volume

wastewaters during maintenance activities.

6. Establish limitation for pH of not less than 6.0 standard units nor greater than 9.0 standard units.
7. Establish monitoring frequency for TOC, O&G, and pH at once per quarter.
8. Establish monitoring frequency for TSS at once per quarter, when discharging low volume wastewaters. L. Internal Outfall 104 (Former 002):
1. Add an optional flow path for occasional discharges from the yard oil separator system to Dry Cooling Tower Sump #1

(Internal Outfall 701) and/or Dry Cooling Tower Sump #2

(Internal Outfall 801) as a result of maintenance

activities.

2. Only daily maximum limitations are proposed due to the intermittent nature of the wastestream.
3. Change the monitoring frequency for TSS, O&G, and pH to once per month.

M. Internal Outfall 204 (New Outfall):

1. Add Internal Outfall 204 for the intermittent discharge of vehicle wash wastewaters to Final Outfall 004.
2. The monthly average and daily maximum reporting of flow in MGD is proposed.
3. Establish limitations for chemical oxygen demand (COD) at 200 mg/l and 300 mg/l, monthly average and daily maximum

respectively.

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 67 4. Establish daily maximum limitation for total suspended solids (TSS) at 45 mg/l.

5. Establish daily maximum limitation for oil and grease (O&G) at 15 mg/l.
6. Establish limitation for pH of not less than 6.0 standard units nor greater than 9.0 standard units.
7. Establish inventory requirement for the soaps and/or detergents used.
8. Establish monitoring frequency for COD, TSS, O&G, and pH at once per quarter.

N. Final Outfall 005 (New Outfall):

1. Add Final Outfall 005 for the intermittent discharge from the Entergy Energy Education Center sewage treatment plant

to 40 Arpent Canal.

2. The weekly average reporting of flow in MGD is proposed due to the intermittent nature of the wastestream. 3. Establish weekly average limitation for total suspended solids (TSS) at 45 mg/l.
4. Establish weekly average limitation for biological oxygen demand (5 days) (BOD
5) at 45 mg/l.
5. Establish weekly average limitation for fecal coliform at 400 colonies/100 ml.
6. Establish limitation for pH of not less than 6.0 standard units nor greater than 9.0 standard units.
7. Establish monitoring frequency for TSS, pH, BOD 5, and fecal coliform at once per six months.

O. Part II:

1. Specify that the 126 priority pollutants as listed in 40 CFR 423 Appendix A, other than total chromium and total zinc,

will not be detected in the effluent in accordance with 40

CFR 423.

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 68 IX. Permit Limit Rationale:

The following section sets forth the principal facts and the significant

factual, legal, methodological, and policy questions considered in preparing

the draft permit. Also set forth are any calculations or other explanations

of the derivation of specific effluent limitations and conditions, including a

citation to the applicable effluent limitation guideline or performance

standard provisions as required under LAC 33:IX.2361/40 CFR Part 122.44 and

reasons why they are applicable or an explanation of how the alternate

effluent limitations were developed.

A. TECHNOLOGY-BASED VERSUS WATER QUALITY STANDARDS-BASED EFFLUENT LIMITATIONS AND CONDITIONS

Following regulations promulgated at LAC 33:IX.2361.L.2.b/40 CFR Part

122.44(l)(2)(ii), the draft permit limits are based on either technology-based

effluent limits pursuant to LAC 33:IX.2361.A/40 CFR Part 122.44(a) or on State

water quality standards and requirements pursuant to LAC 33:IX.2361.D/40 CFR

Part 122.44(d), whichever are more stringent.

B. TECHNOLOGY-BASED EFFLUENT LIMITATIONS AND CONDITIONS

Regulations promulgated at LAC 33:IX.2361.A/40 CFR Part 122.44(a) require

technology-based effluent limitations to be placed in LPDES permits based on

effluent limitations guidelines where applicable, on best professional

judgement (BPJ) in the absence of guidelines, or on a combination of the two.

The permittee is subject to Best Practicable Control Technology Currently

Available (BPT) and Best Available Technology Economically Achievable (BAT)

effluent limitation guidelines listed below:

Manufacturing Operation Guideline Steam Electric Power Generating Point Source Category 40 CFR 423

Outfall 001

This outfall is the continuous discharge from the turbine condenser cooling

system to the Mississippi River. The turbine condenser cooling system

receives once-through non-contact cooling water from the Mississippi River

that flows through the main condenser, the steam generator blowdown heat

exchangers, and the turbine building closed cooling heat exchanger.

Previously monitored discharges from Internal Outfalls 101 (former 01A), 201

(former 01B), 301 (former 01C), 401 (former 01D), 501, 601, 701, 801, and 901

also are discharged via Outfall 001. The combined flow volume of these

intermittent internal outfalls (estimated at 1.65 MGD) is significantly less

than the maximum 30 day average flow of the once-through non-contact cooling

water through Outfall 001 (1,346 MGD). The effluent limitations proposed for

Outfall 001 in the draft LPDES permit are as follows:

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 69 Parameter Monthly Daily Average Maximum Flow Report 1,518 MGD Temperature (F) Report 118F Heat N/A 9.5 x 10 9 BTU/Hour Boron N/A 0.2 mg/l Total Residual Chlorine N/A 211 lbs/day

Flow

The flow limitation of 1,518 MGD for daily maximum at Outfall 001 is retained

from the current NPDES permit. This maximum daily flow limit was requested by

Louisiana Power and Light Company (LP&L, predecessor to Entergy) in a letter

to EPA Region 6 dated March 1, 1985. This letter requested an increase in the

daily maximum flow of the once-through non-contact cooling water from the

limit of 1,445 MGD then in effect to 1,518 MGD which LP&L described as the

"maximum hydraulic capability" of the turbine condenser cooling system. This

request was granted in a letter from EPA Region 6 to LP&L dated May 30, 1985.

Discharge flow is to be determined from calibrated pumping curves or

calculated using appropriate heat balance methodology.

Boron The current NPDES permit established a calculated daily maximum discharge

limit of 0.2 mg/l for boron at Outfall 001. The fact sheet for this NPDES

permit stated this boron limitation was based on BPJ since boron is for

reactivity control in the reactor. The limit is retained on the same basis.

Total Residual Chlorine

The current NPDES permit established daily maximum discharge limits of 211

lbs/day and 0.2 mg/l for total residual chlorine (TRC) at Outfall 001. The

limit is based on 40 CFR 423.13(b)(1)(BAT). Since the discharge from Outfall

001 is continuous and not significantly variable, only the mass limitation is

continued.

Site-Specific Consideration Temperature and Heat

In an application addendum submitted June 15, 1998, the permittee requested that the temperature and heat discharge limits included in the current NPDES permit, 110F and 8.5 x 10 9 BTU/Hour, be increased to 118 F and 9.5 x 10 9 BTU/Hour, respectively, or removed from the new permit entirely.

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 70 The permittee bases the request for an increase in temperature and heat discharge limits on a planned "power uprate" to be implemented in the near future at Waterford 3. On August 26, 1996, this Office issued a letter of no objection to the permittee's request for a power uprate. However, the permit limitations and conditions in the current permit were not adjusted to accommodate a power uprate and compliance with those limitations was still required. Current limits can not be met with a production increase, especially during months when customer demand for electricity is high. This increase in the megawatt output of the facility will result in more waste heat that will need to be transferred from the turbine condenser to the once-through non-contact cooling water. Because the turbine condenser cooling system will continue to operate within its current hydraulic capability, the removal of this additional waste heat will result in higher discharge temperatures for the once-through non-contact cooling water.

Due to the Nuclear Regulatory Commission (NRC) approved design of the plant itself, full power operation, following a power uprate, would result in an increase in temperature and heat discharged in once-through non-contact cooling water. The following is an explanation of how this occurs.

Thermal energy is generated from the nuclear fuel inside a reactor.

Reactor coolant is circulated inside the reactor coolant system to carry that thermal energy to the secondary coolant via a non-contact steam generator. Steam produced from the steam generator drives the turbine-generator producing electricity. Exhaust steam from the outlet of the turbine is condensed by the non-contact cooling water in the circulating water system. Approximately one-third of the heat produced by the reactor is absorbed by the non-contact cooling water in the circulating water system which discharges through Outfall 001 to the Mississippi River. Therefore to increase the electrical output, the thermal energy produced by the reactor must increase proportionally to the increase of electricity. As a result of the increase in reactor thermal power, more heat is absorbed by the non-contact cooling water in the circulating water system.

Both the temperature and heat limitations included in the current permit are technology-based limitations. 40 CFR 423 promulgated as commanded by Section 304 of the Clean Water Act did not establish temperature or heat limitations.

Therefore, best professional judgment (BPJ) was used by EPA, Region VI, to establish the Best Available Technology (BAT), economically achievable, for the current temperature and heat limitations contained in the NPDES permit.

The heat limit currently in effect, 8.5 x 10 9 BTU/Hour, resulted from the Demonstration under Section 316(a) of the Clean Water Act submitted by LP&L in April 1979. On page 35 of this document, LP&L requested that EPA establish 8.5 x 109 BTU/Hour as an alternative thermal limitation for Waterford 3. An internal EPA Region 6 memo dated August 24, 1979 discussed the EPA review of this 316(a) demonstration. In this memo, the EPA reviewer concurred with LP&L's conclusion that the alternative thermal limitation "adequately Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 71 regulates the amount of heat discharged to the Mississippi River from this facility such that it protects the balanced indigenous population". However, the EPA reviewer continued "although the demonstration requests no maximum thermal limitation be placed in the permit, I recommend an instantaneous thermal maximum of 110 F be placed in the permit to further insure protection of the aquatic species". The 110 F stems from a maximum instantaneous heat discharge of 8.5 x 10 9 BTU/Hour, an instantaneous flow rate of 1,000 MGD for the once-through non-contact cooling water, and a typical maximum stream temperature of 86 F. The definition of a British thermal unit (BTU) is the amount of heat required to raise the temperature of one pound of water one degree Fahrenheit at or near 39.2F. Ignoring the slight variation in thermal conductivity of water due to its ambient temperature, the temperature increase of the cooling water conveying the waste heat from the turbine condenser can be estimated by dividing the waste heat in BTU/hour by the cooling water flow in pounds per hour (lbs/hour).

The conversion of the cooling water flow from MGD to lbs/hour is accomplished as follows:

[(1,000 x 10 6 gal/day) x (8.337 lbs/gal)] [24 hr/day] = 347,375,000 lbs/hour Dividing the alternative heat limit by the converted cooling water flow yields:

(8.5 x 10 9 BTU/Hour) (347,375,000 lbs/hour) = 24.5F Adding this to the typical maximum stream temperature produces the following discharge temperature:

86F + 24.5F = 110.5F or approximately 110F Applying the same methodology for a heat limit of 9.5 x 10 9 BTU/Hour and a maximum fresh water stream temperature of 90F (specified in LAC 33:IX.1113.C.4) produces a discharge temperature of approximately 118F. Using a flow of 1,000 MGD in these calculations is reasonable because the long term average flow for Outfall 001 is 1,085 MGD according to the permit application.

To further ensure attainment of LAC 33:IX.1113.C.4.b.i.(a), the 5F allowable rise of temperature above ambient was applied at the edge of the mixing zone.

Appendix A illustrates that a violation of the above citation would not occur with a discharge limitation for temperature at 118F. The Demonstration under Section 316(a) of the Clean Water Act classified the Mississippi River near Waterford 3 as "an area of low potential impact for Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 72 thermal discharges". This classification resulted from: (1) the determination that this stretch of the Mississippi River was not "unique" for any shellfish, fish, or wildlife; and (2) the realization that most of the cross-sectional area available for flow in the river would be unaffected by the thermal plume.

Therefore, the indigenous population of shellfish, fish, and wildlife, which are present in abundance in areas away from Waterford 3, either would have ample opportunity to pass by the facility without encountering elevated stream temperatures or would only experience the higher temperatures for such brief periods that no deleterious effects would result.

The 316(a) demonstration found that no threatened or endangered species were present near Waterford 3. The species that were present also were abundant in other areas of the Mississippi River. The study also determined that no special fish spawning habitat existed near the facility.

The 316(a) demonstration documented thermal model results for various flow and temperature conditions reflecting seasonal variations in this stretch of the Mississippi River. The models accounted for the historically calibrated thermal discharges for the nearby Waterford 1 and 2 and Little Gypsy steam electric generating plants, as well as for the 8.5 x 10 9 BTU/Hour anticipated for Waterford 3. A worst case scenario of an extreme low flow of 100,000 cubic feet per second (cfs) was modeled in the study. This minimum flow in the lower Mississippi River is maintained by the Old River Control Structure operated by the U.S. Army Corps of Engineers and is less than the 7Q10 flow for this segment of the river (141,955 cfs). Under this worst case, extreme low flow situation, the model determined that less than 15% of the cross-sectional area of the river would experience temperature increases of 5 F. This thermal plume also stayed near the surface of the river extending no deeper than 10 feet.

In the Final Environmental Statement Related to the Operation of Waterford Steam Electric Station, Unit No. 3

, the Nuclear Regulatory Commission (NRC) documented model studies conducted by their staff to independently confirm the results presented by LP&L in the 316(a) demonstration. Using a different model, the NRC produced results that were "generally in agreement" with those presented by LP&L. The NRC model produced a slightly larger combined thermal plume or mixing zone, but the environmental statement concluded that operation of Waterford 3 would be "in compliance with the Louisiana Water Quality Criteria relating to temperature". With all three plants operating at peak loads during extreme low flow conditions, an adequate zone of passage (83% of the river cross-sectional area) will still remain for aquatic species to pass by facilities without entering the combined thermal mixing zone. Species entering the mixing zone probably would pass through it in one hour or less, minimizing the impact of the elevated temperatures. Also natural ambient river surface temperatures above 86 F should only occur about 2.5% of the time. Applying the percentage increase of thermal discharge at Waterford 3 to the model worst case, extreme low flow thermal plume should provide a conservative Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 73 estimate of the combined thermal mixing zone that would result from the planned power uprate. This should be very conservative due to Waterford 3 contributing less heat to the river than Waterford 1 and 2 and Little Gypsy combined. Increasing the heat discharge to 9.5 x 10 9 BTU/Hour from 8.5 x 10 9 BTU/Hour constitutes a 12% gain. Applying this proportional gain to the worst case combined thermal plume (17% of river cross-sectional area) yields an anticipated combined thermal mixing zone of 19%. This leaves approximately 81% of the river flow unaffected by the temperature increase after the Waterford 3 power uprate, even under extreme low flow conditions.

LAC 33:IX.1115.C.7 specifies the mixing zone for streams with 7Q10 flow greater than 100 cfs as either 100 cfs or 1/3 of the flow, whichever is greater. The anticipated thermal mixing zone of 19% is substantially less than 33% of cross-sectional area or 1/3 of the flow. Therefore, the increased heat discharge and temperature limits requested for Outfall 001 are expected to meet Louisiana Water Quality Criteria for temperature.

In response to this Office's concern expressed in the August 26, 1996 letter, the combined thermal discharges from Waterford 1 and 2, Waterford 3, and Little Gypsy were evaluated in respect to the cooling tower operations of a downstream facility, Union Carbide. This facility is 1.6 river miles down from Waterford 3. In 1971, the U.S. Department of Interior, Geological Survey in cooperation with Louisiana Department of Public Works, prepared Hydrologic and Quality Characteristics of the Lower Mississippi River, Technical Report Number 5. The purpose of the report was to further an understanding of the hydrologic and quality characteristics of the lower Mississippi River, including the effects of industrial development on water quality and the ability of the river to assimilate wastes. In evaluating the effects of heated effluent, the report states "Very little vertical mixing occurred because the heated water was less dense and floated on the surface."

Because the heated water is less dense than the cooler ambient river water, the combined thermal mixing zone remains near the surface. As mentioned earlier, the worst case thermal plume extends no more than about 10 feet deep.

Since the intake structure for Union Carbide is 3 feet below mean sea level, no rise in temperature above ambient would be detected. Additionally, Union Carbide's cooling water enters the facility via an internal canal. This canal would effectively return river water to ambient temperature prior to entering the facility's cooling system.

Technology to achieve the current limitations for temperature and heat does exist through the use of cooling towers. However, that technology is not economically achievable for Waterford 3. This facility is regulated by the NRC and any change in the operation or equipment must be approved by that agency. For the relatively small increase in temperature and heat caused by the power uprate, modifying the plant itself is not economically justified.

In conclusion, this permit proposes to increase the temperature to 118F and heat to 9.5 x 10 9 BTU/hour as requested by the permittee.

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 74 Internal Outfalls

In accordance with 40 CFR 122.56(b)(1)(ii), the following is an explanation

for the establishment of Internal Outfalls 101, 201, 301, 401, 501, 601, 701,

801, 901, 104, and 204. Certain permit effluent limitations at the point of

discharge are impractical because at the final discharge point the wastes at

the point discharge are so diluted as to make monitoring impracticable. pH

must be monitored internally at the outfalls internal to Outfall 001 because

the design of the plant does not allow for the measurement to be taken prior

to entering the Mississippi River. Therefore, in accordance with 40 CFR

122.46(h)(2) the internal outfalls described below are established.

Internal Outfall 101 (Former 01A) - Liquid Waste Management System

This outfall is the intermittent internal discharge from the liquid waste

management system to Final Outfall 001 via the turbine condenser cooling

system. The liquid waste management system receives low volume wastewater

from the following sources, including but not limited to: the turbine and

reactor building equipment and floor drains, primary plant water makeup,

laboratory drains, and other low volume wastewater sources as defined in 40

CFR 423. The effluent limitations proposed for Outfall 101 in the draft LPDES

permit are as follows:

Parameter Monthly Daily Average Maximum mg/L mg/L Flow, MGD N/A Report Total Suspended Solids N/A 100 Oil and Grease N/A 20 Boron N/A Report pH, standard units 6.0 (min) 9.0 (max)

Flow

The permittee has requested to change the daily average flow limitation from

0.0288 MGD to Report. The daily average flow limitation of 0.0288 MGD at

Internal Outfall 101 (former 01A) is in the current NPDES permit. This

average daily flow limit was requested by LP&L in a letter to EPA Region 6

dated March 1, 1985. This letter requested an increase in the daily average

flow of the liquid waste management system from the limit of 0.0093 MGD then

in effect to 0.0288 MGD which LP&L described as necessary "to accommodate

efficient operation of the plant". This request was granted in a letter from

EPA Region 6 to LP&L dated May 30, 1985.

The permittee contends that this flow limit at Internal Outfall 101

unnecessarily restricts plant operations without adding to the quality of the

discharges from the facility. Because discharges from the liquid waste

management system occur in batches and each batch requires monitoring prior to Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 75 discharge, all the effluent conveyed past Internal Outfall 101 meets the

discharge criteria specified in the permit, regardless of flow quantity.

Given that a power uprate at Waterford 3 will require additional operation of

the liquid waste management system to support the increased generation of

electricity, the permittee's request to remove the daily average flow limit of

0.0288 MGD is granted. Discharge flow is totalized when the discharge occurs.

Total Suspended Solids

The current NPDES permit established a daily average discharge limit of 30

mg/l and a daily maximum discharge limit of 100 mg/l for total suspended

solids at Internal Outfall 101 (former 01A). Since the flow to this outfall

is intermittent only the daily maximum limitation is continued from the

current permit. This limit is based on 40 CFR 423.12(b)(3)(BPT).

Oil and Grease

The current NPDES permit established a daily average discharge limit of 15

mg/l and a daily maximum discharge limit of 20 mg/l for oil and grease at

Internal Outfall 101 (former 01A). Since the flow to this outfall is

intermittent only the daily maximum limitation is continued from the current

permit. This limit is based on 40 CFR 423.12(b)(3)(BPT).

Boron

The current NPDES permit established Report for both the daily average

discharge limit and daily maximum discharge limit for boron at Internal

Outfall 101 (former 01A). Since the flow to this outfall is intermittent only

the daily maximum reporting requirement is continued from the current permit.

This requirement is based on the current permit.

pH

The current NPDES permit established a minimum discharge limit of 6.0 standard

units and a maximum discharge limit of 9.0 standard units for pH at Outfall

101 (former 01A). These limits are based on 40 CFR 423.12(b)(1)(BPT) and are

retained from the current permit.

Internal Outfall 201 (Former 01B) - Boron Management System

This outfall is the intermittent internal discharge from the boron management

system to Final Outfall 001 via the turbine condenser cooling system. The

boron management system concentrates and recovers boron from low volume

wastewaters for reuse within the plant. The boron management system receives

low volume wastewater from the following sources, including but not limited

to: the turbine and reactor building equipment and floor drains, primary

plant water makeup, laboratory drains, and other low volume wastewater sources Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 76 as defined in 40 CFR 423. The effluent limitations proposed for Internal

Outfall 201 in the draft LPDES permit are as follows:

Parameter Monthly Daily Average Maximum mg/L mg/L Flow, MGD N/A Report Total Suspended Solids N/A 100 Oil and Grease N/A 20 Boron N/A Report pH, standard units 6.0 (min) 9.0 (max)

Flow

The permittee has requested to change the daily average flow limitation from

0.0288 MGD to Report. The daily average flow limitation of 0.0288 MGD at

Internal Outfall 201 (former 01B) is included in the current NPDES permit.

This average daily flow limit was requested by LP&L in a letter to EPA Region

6 dated March 1, 1985. This letter requested an increase in the daily average

flow of the boron management system from the limit of 0.0144 MGD then in

effect to 0.0288 MGD which LP&L described as necessary "to accommodate

efficient operation of the plant". This request was granted in a letter from

EPA Region 6 to LP&L dated May 30, 1985.

The permittee contends that this flow limit at Internal Outfall 201

unnecessarily restricts plant operations without adding to the quality of the

discharges from the facility. Because discharges from the boron management

system occur in batches and each batch requires monitoring prior to discharge,

all the effluent conveyed past Internal Outfall 201 meets the discharge

criteria specified in the permit, regardless of flow quantity.

Given that a power uprate at Waterford 3 will require additional operation of

the boron management system to support the increased generation of

electricity, the permitee's request to remove the daily average flow limit of

0.0288 MGD is granted. Discharge flow is totalized when the discharge occurs.

Total Suspended Solids

The current NPDES permit established a daily average discharge limit of 30

mg/l and a daily maximum discharge limit of 100 mg/l for total suspended

solids at Internal Outfall 201 (former 01B). Since the flow to this outfall

is intermittent only the daily maximum limitation is continued from the

current permit. This limit is based on 40 CFR 423.12(b)(3)(BPT).

Oil and Grease

The current NPDES permit established a daily average discharge limit of 15

mg/l and a daily maximum discharge limit of 20 mg/l for oil and grease at

Internal Outfall 201 (former 01B). Since the flow to this outfall is Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 77 intermittent only the daily maximum limitation is continued from the current

permit. This limit is based on 40 CFR 423.12(b)(3)(BPT).

Boron

The current NPDES permit established Report for both the daily average

discharge limit and daily maximum discharge limit for boron at Internal

Outfall 201 (former 01B). Since the flow to this outfall is intermittent only

the daily maximum reporting requirement is continued from the current permit.

This requirement is based on the current permit.

pH

The current NPDES permit established a minimum discharge limit of 6.0 standard

units and a maximum discharge limit of 9.0 standard units for pH at Internal

Outfall 201 (former 01B). These limits are based on 40 CFR 423.12(b)(1)(BPT)

and are retained from the current permit.

Internal Outfall 301 (Former 01C) - Filter Flush System This outfall is the intermittent internal discharge of filter flush water from

the primary water treatment system to Final Outfall 001 via the turbine

condenser cooling system. The primary water treatment system filters river

water for various plant uses. The filters of this system are flushed

periodically with untreated river water to remove solids trapped in the filter

beds. The effluent limitations proposed for Internal Outfall 301 in the draft

LPDES permit are as follows:

Parameter Monthly Daily Average Maximum Flow, MGD N/A Report

Clarifying Agents Used

Flow

The current NPDES permit required the daily average flow and daily maximum

flow to be reported at Internal Outfall 301 (former 01C). Since the flow to

this outfall is intermittent, the daily maximum flow is to be reported.

Discharge flow is totalized when the discharge occurs.

Clarifying Agents Used

The current NPDES permit specified the recording of the monthly amount of

clarifying agents used at Internal Outfall 301 (former 01C). This requirement

is continued from the current permit. However, no reporting on Discharge

Monitoring Reports (DMRs) will be required. The permittee is required to keep

these monthly records onsite, available to DEQ or EPA anytime or upon request.

The draft permit establishes a permit requirement for the onsite maintenance

of this information in Part I.

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 78 Internal Outfall 401 (Former 01D) - Low Volume Wastewaters

This outfall is the intermittent internal discharge of steam generator

blowdown and other low volume wastewaters to Final Outfall 001 via the turbine

condenser cooling system. In addition to steam generator blowdown, low volume

wastewater from other sources as defined in 40 CFR 423 are discharged from

this outfall. The effluent limitations proposed for Internal Outfall 401 in

the draft LPDES permit are as follows:

Parameter Monthly Daily Average Maximum mg/L mg/L Flow, MGD N/A Report Total Suspended Solids N/A 100 Oil and Grease N/A 20 pH, standard units 6.0 (min) 9.0 (max)

Flow

The current NPDES permit requires the daily average flow and daily maximum

flow to be reported at Internal Outfall 401 (former 01D). Since the flow to

this outfall is intermittent, only the daily maximum flow is to be reported.

Discharge flow is totalized when the discharge occurs during periods of

blowdown. When low volume wastewaters are discharged, the flow must be

estimated.

Total Suspended Solids

The current NPDES permit established a daily average discharge limit of 30

mg/l and a daily maximum discharge limit of 100 mg/l for total suspended

solids at Internal Outfall 401 (former 01D). Since the flow to this outfall

is intermittent the daily maximum limitation is continued from the current

permit. This limit are based on 40 CFR 423.12(b)(3)(BPT).

Oil and Grease

This draft permit establishes a daily maximum discharge limit of 20 mg/l for

oil and grease at Internal Outfall 401. This limit is based on 40 CFR

423.12(b)(3)(BPT).

pH

The current NPDES permit established a minimum discharge limit of 6.0 standard

units and a maximum discharge limit of 9.0 standard units for pH at Internal

Outfall 401 (former 01D). These limits are based on 40 CFR 423.12(b)(1)(BPT)

and are retained from the current permit.

Internal Outfall 501 - Auxiliary Component Cooling Water Basin A

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 79 Plant systems have been modified to allow effluent from the auxiliary

component cooling water basins to be directly discharged via the turbine

condenser cooling system, leaving the facility through Final Outfall 001.

This new outfall monitors the intermittent internal discharge from Auxiliary

Component Cooling Water Basin A to Final Outfall 001 via the turbine condenser

cooling system. Low volume wastewater sources contributing to the flow

monitored at this outfall include, but are not limited to, auxiliary component

cooling water, component cooling water, Mississippi River water, and

stormwater. The effluent limitations proposed for Internal Outfall 501 in the

draft LPDES permit are as follows:

Parameter Monthly Daily Average Maximum mg/L mg/L Flow, MGD N/A Report Total Organic Carbon N/A 50 Total Suspended Solids N/A 100 Oil and Grease N/A 20 pH, standard units 6.0 (min) 9.0 (max)

Flow

This draft permit requires the daily maximum flow to be reported at Internal

Outfall 501 by estimating using best engineering judgement. This requirement

is based on 40 CFR 122.44(i)(1)(iii).

Total Organic Carbon

This draft permit establishes a daily maximum discharge limit of 50 mg/l for

total organic carbon at Internal Outfall 501. Total Organic Carbon is

established because stormwater could be discharged via this outfall. The

limitation is based on BPJ in accordance with this Office's guidance on

stormwater, letter dated 6/17/87, from J. Dale Givens (LDEQ) to Myron Knudson

(EPA Region 6).

Total Suspended Solids

This draft permit establishes a daily maximum discharge limit of 100 mg/l for

total suspended solids at Internal Outfall 501. This limit is based on 40 CFR

423.12(b)(3)(BPT). When the circulating water flow test is performed, TSS is

not limited due to Mississippi River water being used for this test. This

test is infrequently done, historically only during times of refueling

outages.

Oil and Grease

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 80 This draft permit establishes a daily maximum discharge limit of 20 mg/l for

oil and grease at Internal Outfall 501. This limit is based on 40 CFR

423.12(b)(3)(BPT).

pH

This draft permit establishes a minimum discharge limit of 6.0 standard units

and a maximum discharge limit of 9.0 standard units for pH at Internal Outfall

501. These limits are based on 40 CFR 423.12(b)(1)(BPT).

Internal Outfall 601 - Auxiliary Component Cooling Water Basin B

Plant systems have been modified to allow effluent from the auxiliary

component cooling water basins to be directly discharged via the turbine

condenser cooling system, leaving the facility through Final Outfall 001.

This new outfall monitors the intermittent internal discharge from Auxiliary

Component Cooling Water Basin B to Final Outfall 001 via the turbine condenser

cooling system. Low volume wastewater sources contributing to the flow

monitored at this outfall include, but are not limited to, auxiliary component

cooling water, component cooling water, Mississippi River water, and

stormwater. The effluent limitations proposed for Internal Outfall 601 in the

draft LPDES permit are as follows: Parameter Monthly Daily Average Maximum mg/L mg/L Flow, MGD N/A Report Total Organic Carbon N/A 50 Total Suspended Solids N/A 100 Oil and Grease N/A 20 pH, standard units 6.0 (min) 9.0 (max)

Flow

This draft permit requires the daily maximum flow to be reported at Internal

Outfall 601 by estimating using best engineering judgement. This requirement

is based on 40 CFR 122.44(i)(1)(iii).

Total Organic Carbon

This draft permit establishes a daily maximum discharge limit of 50 mg/l for

total organic carbon at Internal Outfall 501. Total Organic Carbon is

established because stormwater could be discharged via this outfall. The

limitation is based on BPJ in accordance with this Office's guidance on

stormwater, letter dated 6/17/87, from J. Dale Givens (LDEQ) to Myron Knudson

(EPA Region 6).

Total Suspended Solids

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 81 This draft permit establishes a daily maximum discharge limit of 100 mg/l for

total suspended solids at Internal Outfall 601. This limit is based on 40 CFR

423.12(b)(3)(BPT). When the circulating water flow test is performed, TSS is

not limited due to Mississippi River water being used for this test. This

test is infrequently done, historically only during times of refueling

outages.

Oil and Grease

This draft permit establishes a daily maximum discharge limit of 20 mg/l for

oil and grease at Internal Outfall 601. This limit is based on 40 CFR

423.12(b)(3)(BPT).

pH

This draft permit establishes a minimum discharge limit of 6.0 standard units

and a maximum discharge limit of 9.0 standard units for pH at Internal Outfall

601. These limits are based on 40 CFR 423.12(b)(1)(BPT).

Internal Outfall 701 - Dry Cooling Tower Sump #1

Plant systems have been modified to allow effluent from the dry cooling tower

sumps to be directly discharged via the turbine condenser cooling system,

leaving the facility through Final Outfall 001.

This outfall monitors the intermittent internal discharge which is comprised

of greater than 85% stormwater, in addition to cooling tower blowdown and low

volume wastewaters from Dry Cooling Tower Sump #1 to Final Outfall 001 via the

turbine condenser cooling system or to Final Outfall 004 via the plant

drainage ditches. In addition to the wet cooling tower blowdown, low volume

wastewater from various sources as defined in 40 CFR 423 are discharged from

this outfall. Low volume wastewater sources contributing to this monitored

flow include, but are not limited to, wet cooling tower leakage, auxiliary

component cooling water, component cooling water, and stormwater. Previously

monitored effluent from the Yard Oil Separator System (Internal Outfall 104)

is infrequently discharged through this outfall as a result of maintenance

activities. The effluent limitations proposed for Internal Outfall 701 in the

draft LPDES permit are as follows:

Parameter Monthly Daily Average Maximum mg/L mg/L Flow, MGD N/A Report Total Organic Carbon N/A 50 Total Suspended Solids N/A 100 Oil and Grease N/A 20 Free Available Chlorine N/A 0.5 Chromium, Total N/A 0.2 Zinc, Total N/A 1.0 Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 82 pH, standard units 6.0 (min) 9.0 (max)

Flow

This draft permit requires the daily maximum flow to be reported at Internal

Outfall 701 by estimating using best engineering judgement. This requirement

is based on 40 CFR 122.44(i)(1)(iii).

Total Organic Carbon

This draft permit establishes a daily maximum discharge limit of 50 mg/l for

total organic carbon at Internal Outfall 501. Total Organic Carbon is

established because stormwater is discharged via this outfall. The limitation

is based on BPJ in accordance with this Office's guidance on stormwater,

letter dated 6/17/87, from J. Dale Givens (LDEQ) to Myron Knudson (EPA Region

6).

Total Suspended Solids

This draft permit establishes a daily maximum discharge limit of 100 mg/l for

total suspended solids at Internal Outfall 701. This limit is based on 40 CFR

423.12(b)(3)(BPT).

Oil and Grease

This draft permit establishes a daily maximum discharge limit of 20 mg/l for

oil and grease at Internal Outfall 701. This limit is based on 40 CFR

423.12(b)(3)(BPT).

Free Available Chlorine

This draft permit establishes a daily maximum discharge limit of 0.5 mg/l for

free available chlorine at Internal Outfall 701, when the discharge includes

cooling tower blowdown. This limit is based on 40 CFR 423.13(d)(1)(BAT).

Total Chromium

This draft permit establishes a daily maximum discharge limit of 0.2 mg/l for

total chromium at Internal Outfall 701, when the discharge includes cooling

tower blowdown. This limit is based on 40 CFR 423.13(d)(1)(BAT).

Total Zinc

This draft permit establishes a daily maximum discharge limit of 1.0 mg/l for

total zinc at Internal Outfall 701, when the discharge includes cooling tower

blowdown. This limit is based on 40 CFR 423.13(d)(1)(BAT).

pH

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 83 This draft permit establishes a minimum discharge limit of 6.0 standard units

and a maximum discharge limit of 9.0 standard units for pH at Internal Outfall

701. These limits are based on 40 CFR 423.12(b)(1)(BPT).

Internal Outfall 801 - Dry Cooling Tower Sump #2 Plant systems have been modified to allow effluent from the dry cooling tower

sumps to be directly discharged via the turbine condenser cooling system,

leaving the facility through Final Outfall 001.

This outfall monitors the intermittent internal discharge which is comprised

of greater than 85% stormwater, in addition to cooling tower blowdown and low

volume wastewaters from Dry Cooling Tower Sump #2 to Final Outfall 001 via the

turbine condenser cooling system or to Final Outfall 004 via the plant

drainage ditches. In addition to the wet cooling tower blowdown, low volume

wastewater from various sources as defined in 40 CFR 423 are discharged from

this outfall. Low volume wastewater sources contributing to this monitored

flow include, but are not limited to, wet cooling tower leakage, auxiliary

component cooling water, component cooling water, and stormwater. Previously

monitored effluent from the Yard Oil Separator System (Internal Outfall 104)

is infrequently discharged through this outfall as a result of maintenance

activities. The effluent limitations proposed for Internal Outfall 801 in the

draft LPDES permit are as follows:

Parameter Monthly Daily Average Maximum mg/L mg/L Flow, MGD N/A Report Total Organic Carbon N/A 50 Total Suspended Solids N/A 100 Oil and Grease N/A 20 Free Available Chlorine N/A 0.5 Chromium, Total N/A 0.2 Zinc, Total N/A 1.0 pH, standard units 6.0 (min) 9.0 (max)

Flow

This draft permit requires the daily maximum flow to be reported at Internal

Outfall 801 by estimating using best engineering judgement. This requirement

is based on 40 CFR 122.44(i)(1)(iii).

Total Organic Carbon

This draft permit establishes a daily maximum discharge limit of 50 mg/l for

total organic carbon at Internal Outfall 501. Total Organic Carbon is

established because stormwater is discharged via this outfall. The limitation

is based on BPJ in accordance with this Office's guidance on stormwater,

letter dated 6/17/87, from J. Dale Givens (LDEQ) to Myron Knudson (EPA Region

6).

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 84 Total Suspended Solids

This draft permit establishes a daily maximum discharge limit of 100 mg/l for

total suspended solids at Internal Outfall 801. This limit is based on 40 CFR

423.12(b)(3)(BPT).

Oil and Grease

This draft permit establishes a daily maximum discharge limit of 20 mg/l for

oil and grease at Internal Outfall 801. This limit is based on 40 CFR

423.12(b)(3)(BPT).

Free Available Chlorine

This draft permit establishes a daily maximum discharge limit of 0.5 mg/l for

free available chlorine at Internal Outfall 801, when the discharge includes

cooling tower blowdown. This limit is based on 40 CFR 423.13(d)(1)(BAT).

Total Chromium

This draft permit establishes a daily maximum discharge limit of 0.2 mg/l for

total chromium at Internal Outfall 801, when the discharge includes cooling

tower blowdown. These limits are based on 40 CFR 423.13(d)(1)(BAT).

Total Zinc

This draft permit establishes a daily maximum discharge limit of 1.0 mg/l for

total zinc at Internal Outfall 801, when the discharge includes cooling tower

blowdown. These limits are based on 40 CFR 423.13(d)(1)(BAT).

pH

This draft permit establishes a minimum discharge limit of 6.0 standard units

and a maximum discharge limit of 9.0 standard units for pH at Internal Outfall

801. These limits are based on 40 CFR 423.12(b)(1)(BPT).

Internal Outfall 901 - Metal Cleaning Wastewater

This new mobile outfall monitors the intermittent internal discharge of metal

cleaning wastewaters from internal components of plant equipment to Final

Outfall 001 via the turbine condenser cooling system. Metal cleaning

wastewaters (both chemical and non-chemical) result from the cleaning

washes/rinses of various plant equipment components including, but not limited

to, the steam generator and the cooling water heat exchangers and piping. The

effluent limitations proposed for Internal Outfall 901 in the draft LPDES

permit are as follows:

Parameter Monthly Daily Average Maximum mg/L mg/L Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 85 Flow, MGD N/A Report Total Suspended Solids N/A 100 Oil and Grease N/A 20 Copper, Total N/A 1.0 Iron, Total N/A 1.0 pH, standard units 6.0 (min) 9.0 (max)

Flow

This draft permit requires the daily maximum flow to be reported at Internal

Outfall 901 by estimating using best engineering judgement. This requirement

is based on 40 CFR 122.44(i)(1)(iii).

Total Suspended Solids

This draft permit establishes a daily maximum discharge limit of 100 mg/l for

total suspended solids at Internal Outfall 901. These limits are based on 40

CFR 423.12(b)(5)(BPT).

Oil and Grease

This draft permit establishes a daily maximum discharge limit of 20 mg/l for

oil and grease at Internal Outfall 901. These limits are based on 40 CFR

423.12(b)(5)(BPT).

Total Copper

This draft permit establishes a daily maximum discharge limit of 1.0 mg/l for

total copper at Internal Outfall 901. These limits are based on 40 CFR

423.12(b)(5)(BPT).

Total Iron

This draft permit establishes a daily maximum discharge limit of 1.0 mg/l for

total iron at Internal Outfall 901. These limits are based on 40 CFR

423.12(b)(5)(BPT).

pH

This draft permit establishes a minimum discharge limit of 6.0 standard units

and a maximum discharge limit of 9.0 standard units for pH at Internal Outfall

901. These limits are based on 40 CFR 423.12(b)(1)(BPT).

Outfall 004 - Stormwater

Outfall 004 is a new outfall that consolidates Outfalls 04A and 04B from the

current NPDES Permit LA0007374. Most of the effluent monitored at this

outfall is 85% stormwater runoff. Besides stormwater, potable water from the

fire water system, maintenance wastewaters including, but not limited to:

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 86 hydrostatic test water, air conditioning condensate, low volume wastewaters

from various sources as defined in 40 CFR 423, and previously monitored

effluents exit the facility via Outfall 004. Low volume sources contributing

wastewater to this outfall include, but are not limited to, reverse osmosis

reject water and demineralized water. The plant drainage ditch system

receives treated discharge from the yard oil separator system (Internal

Outfall 104), untreated vehicle wash wastewater (Internal Outfall 204) and

during maintenance activities discharges from Dry Cooling Tower Sump #1

(Internal Outfall 701) and Dry Cooling Tower Sump #2 (Internal Outfall 801).

The effluent limitations proposed for Outfall 004 in the draft LPDES permit

are as follows:

Parameter Monthly Daily Average Maximum mg/L mg/L Flow, MGD N/A Report Total Organic Carbon N/A 50 Total Suspended Solids N/A 100 Oil and Grease N/A 15 pH, standard units 6.0 (min) 9.0 (max)

Flow

This draft permit requires the daily maximum flow to be reported at Outfall

004 by estimating using best engineering judgement. This requirement is based

on 40 CFR 122.44(i)(1)(iii) and the current permit.

Total Organic Carbon

This draft permit establishes a daily maximum discharge limit of 50 mg/l for

total organic carbon at Outfall 004. Total Organic Carbon is established

because stormwater is discharged via this outfall. The limitation is based on

BPJ in accordance with this Office's guidance on stormwater, letter dated

6/17/87, from J. Dale Givens (LDEQ) to Myron Knudson (EPA Region 6).

Total Suspended Solids

This draft permit establishes a daily maximum discharge limit of 100 mg/l for

total suspended solids at Outfall 004, when the discharge includes low volume

wastewaters as defined by 40 CFR 423 (excludes Mississippi River water that

accumulates in the condenser water boxes). This limit is based on 40 CFR

423.12(b)(3)(BPT) and the current permit.

Oil and Grease

This draft permit establishes a daily maximum discharge limit of 15 mg/l for

oil and grease at Outfall 004. The limitation is based on BPJ in accordance

with this Office's guidance on stormwater, letter dated 6/17/87, from J. Dale

Givens (LDEQ) to Myron Knudson (EPA Region 6).

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 87 pH

This draft permit establishes a minimum discharge limit of 6.0 standard units

and a maximum discharge limit of 9.0 standard units for pH at Outfall 004.

These limits are based on 40 CFR 423.12(b)(1)(BPT) and the current permit.

Internal Outfall 104 (Formerly 002) - Yard Oil Separator

This outfall is currently Outfall 002. It is being redesignated Internal

Outfall 104 because it exits the facility through Final Outfall 004 via a

plant drainage ditch. It is the intermittent internal discharge from the yard

oil separator system. Occasionally monitored effluent from the yard oil

separator system is discharged to Dry Cooling Tower Sump #1 (Internal Outfall

701) or Dry Cooling Tower Sump #2 (Internal Outfall 801) as a result of

maintenance activities. Wastewater sources contributing to the flow monitored

at Outfall 104 include auxiliary boiler blowdown, stormwater, and low volume

wastewaters from various sources as defined by 40 CFR 423. Low volume sources

contributing wastewater to this outfall include, but are not limited to,

secondary water system drains, system leakage, auxiliary boiler sumps, turbine

building equipment and floor drains, turbine building floor wash downs, and

laboratory drains. The effluent limitations proposed for Internal Outfall 104

in the draft LPDES permit are as follows:

Parameter Monthly Daily Average Maximum mg/L mg/L Flow, MGD N/A Report Total Suspended Solids N/A 100 Oil and Grease N/A 20 pH 6.0 (min) 9.0 (max)

Flow

This draft permit requires the daily maximum flow to be reported at Internal

Outfall 104 by estimating using best engineering judgement. This requirement

is based on 40 CFR 122.44(i)(1)(iii) and the current permit.

Total Suspended Solids

This draft permit establishes a daily maximum discharge limit of 100 mg/l for

total suspended solids at Internal Outfall 104. This limit is based on 40 CFR

423.12(b)(3)(BPT) and the current permit.

Oil and Grease

This draft permit establishes a daily maximum discharge limit of 20 mg/l for

oil and grease at Internal Outfall 104. This limit is based on 40 CFR

423.12(b)(3)(BPT) and the current permit.

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 88 pH

This draft permit establishes a minimum discharge limit of 6.0 standard units

and a maximum discharge limit of 9.0 standard units for pH at Outfall 004.

These limits are based on 40 CFR 423.12(b)(1)(BPT) and the current permit.

Internal Outfall 204 (New Outfall) - Vehicle Wash Wastewater

This outfall is the intermittent internal discharge from the area where

vehicles will be externally washed. The effluent limitations proposed for

Internal Outfall 204 in the draft LPDES permit are as follows:

Parameter Monthly Daily Average Maximum mg/L mg/L Flow, MGD Report Report Chemical Oxygen Demand 200 300 Total Suspended Solids N/A 45 Oil and Grease N/A 15 pH 6.0 (min) 9.0 (max)

Flow

This draft permit requires the daily maximum flow to be reported at Internal

Outfall 204 by estimating using best engineering judgement. This requirement

is based on 40 CFR 122.44(i)(1)(iii).

Chemical Oxygen Demand

This draft permit establishes a monthly average discharge limit of 200 mg/l

and a daily maximum discharge limit of 300 mg/l for chemical oxygen demand at

Internal Outfall 204. This limit is based on LAG750000, the general permit

for exterior vehicle wash wastewater, effective on July 1, 1998.

Total Suspended Solids

This draft permit establishes a daily maximum discharge limit of 45 mg/l for

total suspended solids at Internal Outfall 204. This limit is based on

LAG75000, the general permit for exterior vehicle wash wastewater, effective

on July 1, 1998.

Oil and Grease

This draft permit establishes a daily maximum discharge limit of 15 mg/l for

oil and grease at Internal Outfall 204. This limit is based on LAG750000, the

general permit for exterior vehicle wash wastewater, effective on July 1,

1998.

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 89 pH

This draft permit establishes a minimum discharge limit of 6.0 standard units

and a maximum discharge limit of 9.0 standard units for pH at Internal Outfall

204. This limit is based on LAG75000, the general permit for exterior vehicle

wash wastewater, effective on July 1, 1998.

Soaps and/or Detergents

This draft permit specifies an inventory record of soaps and/or detergents

following the provision in Part III.C.3. The quantity and types of all soaps

and/or detergents used during the sampling month shall be recorded. Records

of the quantity and types of soaps and/or detergents used shall be retained

for three (3) years. Additionally, a Material Safety Data Sheet for each

material used shall be retained. No DMR reporting shall be required.

Outfall 005 - Energy Education Center Sewage Treatment Plant

This outfall is currently permitted by LAG530192 It is the intermittent

discharge from the Entergy Energy Education Center sewage treatment plant to

40 Arpent Canal. In addition to the sanitary wastewater, a de minimis

discharge from the HVAC unit enters the sewage treatment plant. The effluent

limitations proposed for Outfall 005 are transferred from the general permit

to this draft LPDES permit. The limitations are as follows:

Parameter Monthly Weekly Average Average mg/L mg/L Flow, MGD N/A Report

BOD5 N/A 45 TSS N/A 45

Fecal Coliform colonies/100 ml N/A 400 pH, Std. Units 6.0 (min) 9.0 (max)

C. WATER QUALITY-BASED EFFLUENT LIMITATIONS

Technology-based effluent limitations were screened against state water

quality numerical standard based limits by following guidance procedures

established in the Permitting Guidance Document for Implementing Louisiana Surface Water Quality Standards

, LDEQ, October 30, 1995. Calculations, results, and documentation are given in Appendix B.

The following pollutants received water quality based effluent limits:

None Minimum quantification levels (MQL's) for state water quality numerical

standards-based effluent limitations are set at the values listed in the Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 90 Permitting Guidance Document for Implementing Louisiana Surface Water Quality Standards

, LDEQ, October 30, 1995. They are also listed in Part II of the permit.

The nearest drinking water intake, St. Charles Parish Number 2, is located on

the east bank at 125.1 M.A.H.P., 4.4 miles downstream from the discharge

point. According to a fax received on 9/26/96 from Leslie Lemon of the

Department of Health and Hospitals, Office of Public Health, there have been

no toxic exceedences of drinking water Maximum Contaminant Levels at this

drinking water intake. Nearby potable water industrial intakes include Union

Carbide Corporation.

D. Biomonitoring Requirements

It has been determined that there may be pollutants present in the effluent

which may have the potential to cause toxic conditions in the receiving

stream. The State of Louisiana has established a narrative criteria which

states, "toxic substances shall not be present in quantities that alone or in

combination will be toxic to plant or animal life." The Office of Water

Resources requires the use of the most recent EPA biomonitoring protocols.

Whole effluent biomonitoring is the most direct measure of potential toxicity

which incorporates both the effects of synergism of effluent components and

receiving stream water quality characteristics. Biomonitoring of the effluent

is, therefore, required as a condition of this permit to assess potential

toxicity. See Appendix C for the permittee's biomonitoring history and

biomonitoring frequency recommendation. The biomonitoring procedures

stipulated as a condition of this permit for Outfall 001 are as follows:

TOXICITY TESTS FREQUENCY Acute static renewal 48-hour once per year

definitive toxicity test

using Daphnia pulex Acute static renewal 48-hour once per year

definitive toxicity test

using fathead minnow (Pimephales promelas)

Toxicity tests shall be performed in accordance with protocols described in

the latest revision of the "Methods for Measuring the Acute Toxicity of

Effluents and Receiving Waters to Freshwater and Marine Organisms." The

stipulated test species are appropriate to measure the toxicity of the

effluent consistent with the requirements of the State water quality

standards. The biomonitoring frequency has been established to reflect the

likelihood of ambient toxicity and to provide data representative of the toxic

potential of the facility's discharge in accordance with regulations

promulgated at LAC 33:IX.2369/40 CFR Part 122.48.

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 91 Results of all dilutions as well as the associated chemical monitoring of pH,

temperature, hardness, dissolved oxygen, conductivity, and alkalinity shall be

documented in a full report according to the test method publication mentioned

in the previous paragraph. The permittee shall submit a copy of the first

full report to this Office. The full report and subsequent reports are to be

retained for three (3) years following the provisions of Part III.C.3 of this

permit. The permit requires the submission of certain toxicity testing

information as an attachment to the Discharge Monitoring Report.

This permit may be reopened to require effluent limits, additional testing,

and/or other appropriate actions to address toxicity if biomonitoring data

show actual or potential ambient toxicity to be the result of the permittee's

discharge to the receiving stream or water body. Modification or revocation

of the permit is subject to the provisions of LAC 33:IX.2407/40 CFR 124.5.

Accelerated or intensified toxicity testing may be required in accordance with

Section 308 of the Clean Water Act.

Dilution Series

The permit requires five (5) dilutions in addition to the control (0%

effluent) to be used in the toxicity tests. These additional effluent

concentrations shall be 56%, 42%, 32%, 24%, and 18%. The low-flow effluent

concentration (critical dilution) is defined as 42% effluent.

E. MONITORING FREQUENCIES

Regulations require permits to establish monitoring requirements to yield data

representative of the monitored activity [LAC 33:IX.2369/40 CFR 122.48(b)] and

to assure compliance with permit limitations [LAC 33:IX.2361.I./40 CFR

122.44(I)]. The following section(s) explain the rationale for the monitoring

frequencies stated in the draft permit. See outfall information for associated

outfalls concerning the type of wastewaters in Section VII.

Outfall 001

Monitoring frequencies for all effluent characteristics, except the

biomonitoring which was discussed above in Section IX.D, are retained from the

current permit. Flow, Temperature (F), and Heat (BTU/hour) are continuous with a sample type of record. Boron is calculated daily. Total Residual

Chlorine is measured once per week by grab sample, during periods of

chlorination.

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 92 Internal Outfall 101 (Former 01A) - Liquid Waste Management System

Monitoring frequencies for all effluent characteristics are retained from the

current permit. Flow, TSS, Oil and Grease, Boron, and pH are once per batch.

Flow is totalized by a flow meter not estimated as the current permit states.

Therefore this permit proposes to change the sample type for flow to

totalized. Sampling for TSS, Oil and Grease, Boron, and pH are by grab

sampling.

Internal Outfall 201 (Former 01B) - Boron Management System

Monitoring frequencies for all effluent characteristics are retained from the

current permit. Flow, TSS, Oil and Grease, Boron, and pH are once per batch.

Flow is totalized by a flow meter not estimated as the current permit states.

Therefore this permit proposes to change the sample type for flow to

totalized. Sampling for TSS, Oil and Grease, Boron, and pH are by grab

sampling.

Internal Outfall 301 (Former 01C) - Filter Flush System

Flow is totalized weekly by a flow meter not estimated as the current permit

states. Therefore this permit proposes to change the sample type for flow to

totalized. The monthly recording based on an inventory calculation of the

clarifying agents used is retained from the current permit. However, no DMR

reporting is required. This permit proposes a requirement for the permittee

to maintain these records onsite.

Internal Outfall 401 (Former 01D) - Low Volume Wastewaters

The measurement frequency and sample type for flow, TSS, Oil and Grease, and

pH are retained from the current permit. Flow is daily by a totalized sample

type. TSS, Oil and Grease, and pH are by a grab sample.

Internal Outfall 501 - Auxiliary Component Cooling Water Basin A

This permit proposes a monitoring frequency of once per week for all

parameters, when discharging. The sample type for flow is estimate and the

sample type for TOC, TSS, Oil and Grease, and pH are by a grab sample.

During circulating water flow testing, sampling for TSS is not required (when

Mississippi River water is used for the flow test).

Internal Outfall 601 - Auxiliary Component Cooling Water Basin B

This permit proposes a monitoring frequency of once per week for all

parameters, when discharging. The sample type for flow is estimate and the

sample type for TOC, TSS, Oil and Grease, and pH are by a grab sample.

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 93 During circulating water flow testing, sampling for TSS is not required (when

Mississippi River water is used for the flow test).

Internal Outfall 701 - Dry Cooling Tower Sump #1

This outfall is comprised of greater than 85% stormwater, therefore this

permit proposes a monitoring frequency of once per month for all parameters,

when discharging. The sample type for flow is estimate and the sample type

for TOC, TSS, Oil and Grease, Free Available Chlorine, Total Chromium, Total

Zinc, and pH are by a grab sample. Free Available Chlorine, Total Chromium,

and Total Zinc are analyzed when the discharge includes cooling tower

blowdown.

Internal Outfall 801 - Dry Cooling Tower Sump #2

This outfall is comprised of greater than 85% stormwater, therefore this

permit proposes a monitoring frequency of once per month for all parameters,

when discharging. The sample type for flow is estimate and the sample type for

TOC, TSS, Oil and Grease, Free Available Chlorine, Total Chromium, Total Zinc,

and pH are by a grab sample. Free Available Chlorine, Total Chromium, and

Total Zinc are analyzed when the discharge includes cooling tower blowdown.

Internal Outfall 901 - Metal Cleaning Wastewater

This permit proposes a monitoring frequency of once per week for all

parameters, when discharging. The sample type for flow is estimate and the

sample type for TSS, Oil and Grease, Total Copper, Total Iron, and pH are by a

grab sample.

Outfall 004 - Stormwater

This permit proposes a monitoring frequency for all parameters of once per

quarter, when discharging. The sample type for flow is estimate and the

sample type for TOC, Oil and Grease, TSS, and pH are by a grab sample.

Internal Outfall 104 - Yard Oil Separator

This permit proposes a monitoring frequency of once per month for all

parameters, when discharging. The sample type for flow is estimate and the

sample type for TSS, Oil and Grease, and pH is by a grab sample.

Internal Outfall 204 - Vehicle Wash Wastewater

The monitoring frequency of vehicle wash wastewater follows LDEQ's vehicle

wash wastewater general permit. The monitoring frequency is once per quarter

for all parameters, when discharging. The sample type for flow is estimate

and the sample type for COD, TSS, Oil and Grease, pH, and soaps and/or

detergents is by grab sample.

Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 94 Outfall 005 - Energy Education Center Sewage Treatment Plant

All parameters will be monitored once per six months based on monitoring

frequencies established for similar discharges. The sample type for flow is

estimate and the sample type for BOD 5, TSS, Fecal Coliform, and pH is by a grab sample.

X. Endangered Species:

The receiving waterbody, Subsegment 070301 of the Mississippi River Basin is

not listed in Section II.2 of the Implementation Strategy as requiring

consultation with the U.S. Fish and Wildlife Service (FWS). This strategy was

submitted with a letter dated September 26, 1997 from Fruge (FWS) to Aydell

(LDEQ). Therefore, in accordance with the Memorandum of Understanding between

the LDEQ and the FWS, no further informal (Section 7, Endangered Species Act)

consultation is required. It was determined that the issuance of the LPDES

permit is not likely to have an adverse effect on any endangered or candidate

species or the critical habitat. The effluent limitations established in the

permit ensure protection of aquatic life and maintenance of the receiving

water as aquatic habitat.

XI. Historic Sites:

The discharge is from an existing facility location, which does not include an

expansion on undisturbed soils. Therefore, there should be no potential

effect to sites or properties on or eligible for listing on the National

Register of Historic Places, and in accordance with the "Memorandum of

Understanding for the Protection of Historic Properties in Louisiana Regarding

LPDES Permits" no consultation with the Louisiana State Historic Preservation

Officer is required.

XII. Tentative Determination:

On the basis of preliminary staff review, the Department of Environmental

Quality has made a tentative determination to reissue a permit for the

discharge described in the application.

XIII. Variances:

No requests for variances have been received by this Office.

XIV. Public Notices:

Upon publication of the public notice, a public comment period shall begin on

the date of publication and last for at least 30 days thereafter. During this

period, any interested persons may submit written comments on the draft permit

and may request a public hearing to clarify issues involved in the permit

decision at this Office's address on the first page of the fact sheet. A Fact Sheet and Rationale for Entergy, Waterford 3 Steam Electric Station

LA0007374

Page 95 request for a public hearing shall be in writing and shall state the nature of

the issues proposed to be raised in the hearing.

Public notice published in:

ST. CHARLES HERALD-GUIDE of Boutte Office of Water Resources Public Notice Mailing List Appendix A

Appendix B

Appendix C