{{#Wiki_filter:Revision 1January 1975U.S. NUCLEAR REGULATORY COMMISSION* REGULATORY GUIDEREGULATORY GUIDE 1.75PHYSICAL INDEPENDENCE OF ELECTRIC SYSTEMS
{{#Wiki_filter:U.S. NUCLEAR REGULATORY COMMISSION
Revision 2 Septsmber 1978 REGULATORY GUIDE
OFFICE OF STANDARDS DEVELOPMENT
REGULATORY GUIDE 1.75 PHYSICAL INDEPENDENCE OF ELECTRIC SYSTEMS
A.


==A. INTRODUCTION==
INTRODUCTION  
Section 505.5a. "Codes and Standards," of l0 CFRPart 50. "Licensing of Production arid Utiliz.ationFacilities," requires in paragraph (hi) that protectihonsystems incel (tie requirenments set forth in tihe Instituteofl Electrical and Electronics Engineers Standard,"'Criteria for Protectiun Systemis fur Nuclear PowerGenerating StatiolnS." (li'lE 271W .Section 4.6 of IEEEStd 279-1971 (also designated ANSI N42.7-1972)requires. in part. that channels that provide signals forthe same protective function be independent aridphysically separated. General Design Criterion 3. "FireProtection.'" it' Appendix A. "(Gencinal DXsiwi Criteriafur Nuclear Power Plants." to 10 CFR Part 50 requires.in part. that structuress, systems. and componentsimportant to safety be desitgned anid located toI miniriZe , consistent with other safety requiremen ts, theprobability and effect of fires. General Design Criterion1 7. "Electric Power Systeins," requires. in part. that theonsite electric power supplies, including the batteries.and the onsite electric distribution system havesufficient independence to performn their safety flunc-tions assuming a single failure. General Design Criterion21, "Protection System Reliability and Testability,"requires, in part. that independence desiLued intoprotection systems be sufficient to ensure that no singlefailure results in loss of the protection function. Thisguide describes a method acceptable to the Regulatorystaff of complying with IEEE Std 279-1971 and Criteria3. 17. and 21 of Appendix A to 10 CFR Part 50 withrespect to thie physical independence of the circuits andelectric equipment comprising or associated with theClass IE power system, the protection system, systemsactuated or controlled by the protection system, and'Copies may be obtained froemthe Institute ot' Electrical andElectronics Engineers, United Engineering Center, 345 East 47thStreet, New York. New York 10017.auxiliary or supporting systems that must be operablefor the protection system and the systemls it actLuaeCs toperlform their saf'ety-related I'ulctions. This guide a pplicsto all types of niclear power plants.
Section 50.55a, "Codes and Standards," of 10
CFR Part 50, "Domestic Licensing of Production and Utilization Facilities,"  
requires in paragraph (h) that protection systems meet the requirements set forth in the Institute of Electrical and Electronics Engineers Standard,  
"Criteria for Protection Systems for Nuclear Power Generating Stations" (IEEE 279).1 Sec tion 4.6 of IEEE Std 279-1971 (also designated ANSI N42.7-1972) requires, in part, that chan nels that provide signals for the same protec tive function be independent and physically separated. General Design Criterion 3, "Fire Protection," of Appendix A,
"General Design Criteria for Nuclear Power Plants," to I0 CFR  
Part 50 requires, in part, that structures, systems, and components important to safety be designed and located to minimize, consistent with other safety requirements, the probability and effect of fires. General Design Criterion
17,
"Electric Power Systems," requires, in part, that the onsite electric power supplies, including the batteries, and the onsite electric distribution system have sufficient in dependence to perform their safety functions assuming a single failure. General Design Cri terion 21,  
"Protection System Reliability and Testability," reqxiires, in part, that independ ence designed into protection systems be suffi cient to ensure that no single failure results in loss of the protective function.


==B. DISCUSSION==
This guide describes a method acceptable to the NRC staff of complying with IEEE Std 279
Draft II'I"E Standard. "'Criteria t or Separation otClass IE IEquipnment and Circuits," dated July 20. 1973.was prepared by Ad 1l0c Subcomnmnittee 0 of the NudearPower Enghieering Comlmittee (NPE(") of the lInstituteof Electrical and Electronics Enilneers. The dralft wassubsequently miodified by NPEC in August 1973incident to the normnal process of' developing itstechnical content. The modified draft standard providedcriteria for the separation of redundant Class IFIequipment and circuits installed at nuclear power plants.Inasnmuch as there was an urgent need for explicitguidance in the area of physical independence of electticsystems and in view of the considerable guidance alreadyavailable from tile modified IE-E draf't standard, theRegulatory staff prepared a document entitled, "Appen-dix I to Regulatory Guide 1.75--Physical Independenceof Electric Systenms." This Appendix, which wasessentially the nmodified IEEE draft standard furthermodified to (a) address acceptably those portions of thestandard on which there was not complete agreement.(b) describe logical extensions of the standard'sprovisions that were acceptable to tile Regulatory staff.and (c) provide clarification where necessary. wasendorsed by the February 1974 version of this guide.Subsequent to the issuance of the February 1974version of this guide, the modified IEEE draft standardupon which the guide and its Appendix were basedevolved, in the normal course of standard developnment.into IEEE Std 384-1974, "IEEE Trial-Use StandardCriteria for Separation of Class IE Equipment atidCircuits," (also designated ANSI N41.14). IEEE Sid384-1974 has undergone balloting within Ad HocSubcommittee 6 arid NPEC and was approved by tileUSNRC REGULATORY GUIDES Copies of published quides may be obtained byV equest indicating the divisionsfdett ited to the U.S, Nucle,,, Reguatinty Commiiveon. Washir.glot,. 0 C 20b55.Regulatory Guides ae kt~ild Io des~cribe and matke available to the public Altelmn Director of Standards Oeveelopme.nt Commentts and %utgeest-inis tInmethod% acceptable to the NRC staff of impfrrntenling specific parts of Iliae in these guides are encoutraged and hIe sent to the.Commisslion's regutaiotr,, to detinatet ftchni.hitueS ust.t1 by the staff in srcetlatv of the? Comlmiisin. U.S Nucleart Regulatorv Comtnlitssll.evaluating specific ptoblemls or postulated accidents. or to provide guidance to Washingtotn. 0 C 20555. Attention Oockeling and Service Sectionapplicants Regulatery Guides sre ntof %ubslitutes fot tegllation$ and compliancewith them is not tegqired. Methods aid soluftons different from those set out irn The guides ate issued its the fallowing feti broad division%the guides wtll be acceptable if Ihey provide a ba$si$i for the findings requisite tothe issuance or continuance of A permit or license by the Commission. "i Power Reactots 6. Products2. Reearch and Toes Reacturs 7. rtiansporinaort3. Fuels and Materiail lactlilies 8 Occupational HealthPublished guides will be tevised periodicitlly. as appropriate. to accommodale 4 Envitonmental and Silinit 9 Antitrust Reviewcomments and to reflect new informatlort or esperience 5. Materials and Plant Protection 10. Genteral IEEE Standards Bfoard on February 28, 1974. Thisrevision to tile guide endorses, with certain exceptions.IEEE Std 384-1974.The Regulatory staff does not agree with certainproisions of the trial-use standard such as thosepertaining to the definition of "raceway." the routing ofpower cables through the cable spreading area(s) andcontrol room, and the status of non-Class It: circuits thatare not separated from associated circuits by acceptabledistance or barriers. This lack of agreement is reflectedin Regulator)y lositions C.1. 2. 4. 6. 7, 9. 10. and 12;There are also several regulatory positions that arelogical extensions of the Standard's provisions andreflect current Regulatory staff review practice. Forexample, a provision of the standard which addresses the"'degree of separation commensurate with the damagepotential of the hai.ard" does not specifically cover cabletunnels which, in the event of a fire. may not effectivelyseparate redundant circuits or equipment. As anotherexample. the standard requires that methods ofidentification distinguish between redundant Class IEsystems, associated circuits, and non-Class IE systems.By implication, associated circuits assiged to differentredundant divisions should also be identified. However.the provision is implicit. An explicit provision should beprovided.I.)tailed bases are included herein for thoseregulatory positions that are significantly at variancewith the standard's provisions. The remaining regulatorypositions are logical extensions. or clarifications. of thestandard's provisions.
1971 and Criteria 3, 17, and 21 of Appendix A  
to 10 CFR Part 50 with respect to the physical independence of the circuits and electric equipment comprising or associanted with the  
'Copies may be obtained from the Institute of Eectrical and Electronics Engineers.


==C. REGULATORY POSITION==
United Engintering Center. 345 East
IEEE Std 384-1974 sets forth criteria for theseparation of circuits and equipment that are redundant.The determination of which circuits and equipment areredundant and the degree of redundancy required isoutside, the scope of this guide and the standard. Thestandard also sets forth criteria relating to tests andanalyses for determining the flame-retardant character-istics of proposed cable installations. The criteria areacceptable provided such tests and analyses are based onrealistic premises and are otherwise fully applicable tothe actual cable installations.The guidance in IEEE Std 384-1974, "IEEE Trial-UseStandard Criteria for Separation of Class IE Equipmentand Circuits," dated Match 15, 1974, is generallyacceptable to the Regulatory staff and provides anadequate basis for complying with IEEE Std 279-1971and the Commission's General Criteria 3, 17, and 21 ofAppendix A to 10 CFR Part 50 with respect to thephysical independence of the circuits and electricequipment comprising or associated with the Class IEpower system, the protection system, systems actuatedor controlled by the protection system, and auxiliary orsupporting systems that must be operable for theprotection system and the systems it actuates to perform.their safety-related functions, subject to the following:I. Section 3, Isolation Device, should be supplementedas follows: "(Interrupting devices actuated only by faultcurrent are not considered to be isolation devices withinthe context of this document.)"Basis: Loigcal extension of the Standard ' prow isons.The standard defines "isolation device'" in terms ofpreventing ,nalfinct ions in one section of a circuit fromcausing unzacceptable influences in other sections of thecircuit or other circuits. Under the postulated conditionsof a loss-of coolant accident, loss of offsite power, and acable tray' fire. the proximity of circuits energi2ed fromre'dundant Class IE power sources could lead toconcurrent high fault currents (e.g. short to ground)which, in turn, threaten the redundant main circuitbreakers. Also. the susceptibilityv of non-Class I1:" loadsetrergized fromi redundant Class IE power sources todesign basis event (e.g., seismic events) could similarly'threaten the redundant main circuit breakers. 7Tippingof the mttain circcuit breakers wouhld cause f/ie loss ofelercgen'c, pow'er to redundant "divisionss" of equip-ni'nf. It is rec-ognized that proper breaker or fiisecoordination would preclude such an event. However,because the main breakers are in series with the fault andcould experience monmentaryv currents above theirsetpoints, it is pnrdent to preclude the use of inter-rupqting devices actuated onl' by fault current asacceptable devices for isolating non-Class A1 circuitsfrom Class IE or A ssociated circuits.Breakers that trip on receipt of a signal other thanone derived from the flhult crurrentt or its effects (e.g.. anaccident sigital) are acceptable since the downstreamcircuits would already be isolated from their respectivepower sources under accident conditions and could posenro threat to these sources.2. Section 3, Raceway: Interlocked armor enclosingcable should not be construed as a "raceway".Basis: There is no precedent or other ktrown validreason for consideritig such cable to be a "raceway"77Tis regulatory position is consistent with currentindustry practice includinig the provisions of theNational Electric Code.3. Section 4.3 should be supplemented as follows: "Ingeneral, locating redundant circuits and equipment inseparate safety class structures affords a greater degreeof assurance that a single event will not affect redundantsystems. This method of separation should be usedwhenever practicable and where its use does not conflictwith other safety objectives."4. Associated circuits installed in accordance withSection 4.5(1) should be subject to all requirementsplaced on Class IE circuits such as cable derating,environmental qualification, flame retardance, splicingrestrictions, and raceway fill unless it can bedemonstiated that the absence of such requirementscould not significantly reduce the availability c,f theClass IE circuits.1.75-2 Basis: This is a logical extension of the standard sprovisions. The specified minimum acceptable separationdistances for raceways carrying Class IE circuits arepredicated on assumptions related to flame r?,tardawce,cable derating. etc. The placement of cables of lesserqualification in these raceways would nullify theseassumptions.5. The "Note" following Section 4.5 should besupplemented as follows: "This exemption is limited anddoes not extend to other requirements such as those ofGeneral Design Criterion 17."6. Analyses performed in accordance with Sections4.5(3), 4.6.2, and 5.1.1.2 should be submitted as part ofthe Safety Analysis Report and should identify thosecircuits installed in accordance with these sections.Basis: Extension of Regulatory Guide 1. 70 to providethe information needed in order for the staff toindependently verify conformance to the standard.7. Non-Class IE instrumentation and control circuitsshould not be exempted from the provisions of Section4.6.2.Basis: There is no firm technical basis for anunrestricted exemption of these circuits. Exetnptionsshould be justified by analysis.8. Section 5.1.1.1 should not be construed to imply thatadequate separation of redundant circuits can beachieved within a confined space such as a cable tunnelthat is effectively unventilated.9. Section 5.1.1.3 should be supplemented as follows:"(4) Cable splices in raceways should be prohibited."Basis: Splices have been identified as the initiatingcause of several fires in raceways. Even where theseparation distance is adequate to prevent a fire in theraceways of one division from affecting cables in aredundant division, all practicable means should be usedto prevent the occurrence of a fire. This position againstsplices in raceways is therefore prudent. Splices are nrot,by themselves, unacceptable. If they exist, the resultingdesign should be justified by analyses. The analysesshould be submitted as part of the Safety AnalysisReport.10. Section 5.1.2, the phrase -at a sufficient number ofpoints" should be understood to mean at intervals not toexceed 5 ft throughout the entire cable length. Also thepreferred method of marking cable is color coding.Basis: 7This is a logical extension of the standard'sprovisions. A 5 ft maximum marking distance isconsidered necessary to facilitate visual verification thatthe cable installation is in conformance with separationcriteria.I1. Section 5.1.2 should be supplemented as follows:"The method of identification used should be simpleand should preclude the need to consult any referencematerial to distinguish between Class IE and Non-ClassIE circuits, between Non-Class IF circuits associatedwith different redundant Class-IE systenms, and betweenredundant Class IE systems.'12. Pending issuance of other acceptable criteria, thoseportions of Section 5.1.3 (exclusive of the NOTEfollowing the second paragraph) that permvi the routingof power cables through the cable spreading area(s) and.by implication, the control room. should not heconstrued as accepiwble. Also. Section 5.1.3 should besupplemented as follows: "WWhere feasible, redundantcable spreading areas should be utilized.-Basis: This is a pnident specific interpretation o" thcstandard's provisions in thi absncee sPcciic guidan.wc.The Regulator' staff recognizes that vibset,qentinvestigation may, prove that this approach is tooconservative, however, in the absence of supporti,:eevidence to the contrarY, this cotisern'ative apprroach isdesirable.The use of redundant cable sprcading art-as is a logicalextension of the standard's pr.'f)isions (relf Scction5.1.1.1).13, No significance should be attached to the differenttray widths illustrated in Figure 2.14. Section 5.2.1 should be supplemented as follows:"And should have independent air supplies."15. Where ventilation is required, the separate safetyclass structures required by Section 5.3.1 should heserved by independent ventilation systems.16. The first paragraph of Section 5.7 should beaugmented as follows: "The separation requirements .of5.6 apply to instrumentation cabinets."
47th Street. New York, New York 10017.


==D. IMPLEMENTATION==
Class 1E power system, the protection system, systems actuated or controlled by the protec tion system, and auxiliary or supporting sys tems that must be operable for the protection system and the systems it actuates to perform their safety-related functions. This guide ap plies to all types of nuclear power plants.
The purpose of this section is to provide informationto applicants and licensees regarding the Regulatorystaffs plans for utilizing this regulatory guidu.This guide reflects current regulatory practice.Therefore, except in those cases in which the applicantproposes an acceptable alternative method for comn-plying with specified portions of the Commission'sregulations, this guide will be used by the Regulatorystaff in evaluating all construction permit applicationsfor which the issue date of the Safety Evaluation Reportis February I, 1974, or after.1.75.3}}
 
This guide addresses only some aspects of defense against the effects of fires. Additional criteria for protection against the effects of fires are provided in Regulatory Guide 1-120,
"Fire Protection Guidelines for Nuclear Power Plants.,
B.
 
DISCUSSION
Draft IEEE Standard, "Criteria for Separa tion of Class
1E Equipment and Circuits,"
dated July 20, 1973, was prepared by Ad Hoc Subcommittee
6 of the Nuclear Power Engineering Committee (NPEC) of the Institute of Electrical and Electronics Engineers. The draft was -subsequently modified by NPEC in August. 1973 incident to the normal process of developing its technical content. The modified draft standard provided criteria for the separation of redundant Class IE equipment and circuits installed at nuclear power plants.
 
Inasmuch as there was an urgent need for explicit guidance in the area of physical inde pendence of electric systems and in view of the considerable guidance already available from the modified -IEEE draft standard, the staff prepared a document entitled "Appendix 1 to Regulatory Guide 1.75 - Physical Independence of Electric Systems." This- Appendix, which was essentially the modified IEEE
draft standardi further modified to (a) address ac ceptably those portions of the standard on which there was not complete agreement, (b)
*Lines indicate substantive changes from previous issue.
 
USNRC REGULATORY GUIDES
1egmatumy Guidee am band to &oxbo mid ruW
WsHIMl
&M
Ie pt*1c nietodsoospable to la NRC eteff Of knmoain
0
e- c WW
-
lie Se0ef prob poei*dted
*
e*derm or so po"
gAdence 10
ml e
I
tdpMry GAd we not hedtfuftn fW mqs, aid arm V1 with lambI not requke. Melsad end sa&udmw ebrn
10
o
*-oee K ut
& In tho s p ud b e to cepbo ah N lt v ro s a bob fore ta *W
usgmIb~ pw bounnce or earitirwnsoe pe1 i
&
kOr @OWN
b Canuiets aid euggeelion for harovenientah In 0-
gidsa we encoasgjac at eld Oim&oWd rgde w be etwbed. as ep te Pr
 
====c.  o d ====
o th w4d to re~ct ume Inonilon or axpelence. This ii was meted ma mult of eslienei receitved *rom to pidec ond eddkonad gaff rviw.
 
a imw dsid be em W W In ft liCowN
a Wo ied N eo I. Poum RcOtMrs
 
====s. vmrxon ====
2. ReeahwdimdTeat Revmo~
7. Traiopution S. Fukl m
od Metmkba F~im
::o
=o M
4. Esikonmiirm mid 1::hig
5.ari~itR~
& Mstmwih mid ProectW
a eral feqoast for uhig egooes of bmaed dMn Wkhd noy be uprOduce) or tar i
ancemen aien asmaswefc detkution kt f *de cone of kftns gides
""ons ei*Id be nod& In ug W"
W
U,& Nuch Reg.Aty Comnakn. Wi*kns
.
D.C. Z.
 
AtmnW
Dkocw.
 
Dmiden Of Tedhad bInu.on mid Documeo Caga.
 
I
*
 
describe logical extensions of the standard's.
 
provisions that were acceptable to the staff, and (a) provide clarification where necessary,. 
was endorsed by the February 1974 version of this guide.
 
Subsequent to the issuance of the February
1974 version of this guide, the modified MEEE
draft standard upon which the guide and its Appendix were based evolved, in the normal course of standard development, into IEEE Std
384-1974,
"IEEE Trial-Use Standard Criteria for Separation of Cuss JR Xupmen-
-Cir- cults" (also designated ANSI N41.14). IEEE Std
384-1974 has undergone balloting within Ad Hoc Subcommittee .6 and NPEC and was approved by the IEEE Standards' Board on February 28,
1974. This revision to the guide endorses, with certain exceptions, IEEE Ptd 384-1974.
 
The NRC staff does not agree with certain"
provisions of the trial-use standard such as those pertaining to the definition of "raceway,"
the routing of power cables through the cable spreading area(s) and control room', and tie status of non-Class-lI circuits that are. not separated from associated circuits by accept able distance or bairiers. This lack of agree ment is reflected in Regulatory Positions C. 1,
2, 4, 6, 7, 9, 10, and 12.
 
There are also several regulatory positions that are logical extensions of the standard's provisions and reflect current staff review practice.
 
For example, a provision of the standard that addresses the
"degree of separation commensurate with the damage
3otential of the hazard" does not specifically zover cable tunnels which, in the event of a fire, may not effectively separate redundant circuits or equipment. As another example, the standard requires that methods of identification distinguish between redundant Class
1E
systems, associated circuits, and non-Class-IX
systems.
 
By implication, associated circuits assigned to different redundant divisions should also be identified.
 
However, the provision is implicit.
 
An explicit provision should be provided.
 
Detailid bases are included herein for those regulatory positions that are significantly at iariance with the standard's provisions. The remaining regulatory positions are logical ex tensions or clarifications of the standard's pro visions.
 
C.
 
REGULATORY POSITION
IEEE Std 384-1974 sets forth criteria for the separation of circuits and equipment. that are redundant. The determination of which circuits and equipment are redundant and the degree of redundancy required is outside the scope of this guide and the standard. The standard also sets forth criteria relating to tests and analyses for determining the flame-retardant characteristics of proposed cable installations.
 
The criteria are acceptable provided such tests and analyses are based on realistic premises and are otherwise fully applicable to the actual.
 
cable installations.
 
The guidance in IEEE Std 384-1974, "IEEE
Trial-Use Standard Criteria for Separation of Class IR
Equipment and Circuits,"
dated
,farch 15, 1974, is generally acceptable to the NRC staff and provides an adequate basis for complying with IEEE Std 279-1971 and the Commission's General Design Criteria 3, 17, an& 21- of Appendix A to 10 CFR Part. 50 with.
 
respect to the physical independence of the circuits and electric equipment comprising or associated with the Class 1E power system, the protection system, systems actuated or controlled by the protection system, and auxiliary or supporting systems that must be operable for the protection system and the systems it actuates to perform their safety related functions, subject to the following:
1. Section 3,
"Isolation Device," should be supplemented as follows:
"(Interrupting de vices actuated only by fault current are not considered to be isolation devices within the context of this document.)"
Basis: Logical extension of the standard's provisions. The standard defines "isolation device" in terms of preventing malfunctions in one section of a circuit from causing un acceptable influences in other sections of the circuit or other circuits. Under the postu lated conditions of a loss-of-coolant accident,. 
loss of offsite power, and a cable tray fire, the proximity of circuits energized from re dundant Class 1E power sources could lead to concurrent high fault currents (e.g., short to ground) which, in turn, threaten the re dundant main circuit breakers.
 
Also, the susceptibility of non-Class-IE loads ener gized from redundant Class 1E power sources to design basis events (e.g., seismic events)
could similarly threaten the redundant main circuit breakers. Tripping of the main circuit breakers would cause the. loss of emergency power to redundant "divisions" of equipment.
 
It is recognized that proper breaker or fuse coordination would preclude such an event.
 
However, because the main breakers are in series with the fault and could experience momentary currents above their setpoints, it is prudent to preclude the use of inter rupting devices actuated only by fault cur rent as acceptable devices for isolating non Class-IE circuits from Class 1E or associated circuits.
 
Breakers that trip on receipt of a signal other than one derived from the fault current or its effects (e.g., an accident signal) are acceptable since the downstream circuits would. already be isolated from their respec tive power sources under accident conditions and could pose no threat to these sources.
 
1.75-2 KYý
 
2. Section 3,
"Raceway". Interlocked armor
"enclosing cable should not be construed as a
"raceway". 
Basis: There is no precedent or other known R
reason for considering such cable to be a "raceway". This regulatory position is con sistent with current industry practice, including the provisions of the National Elec tric Code.
 
3. Section 4.3 should be supplemented as.
 
follows: "In general, locating redundant cir cuits and equipment in separate safety class structures affords a greater degree of assur ance that a single event will not affect redun dant systems.
 
This method of separation should be used whenever practicable and where its use does not conflict with other safety objectives."
4. Associated circuits installed in accordance with Section 4.5(1) should be subject to all re quirementa placed on Class lE circuits such as cable derating, environmental qualification, flame retardance, splicing restrictions, and raceway fill unless it can be demonstrated that the absence of such requirements could not significantly reduce the availability of the Class IE circuits.
 
Basis: This is a logical extension of the stanaard's provisions. The specified minimum acceptable separation distances for raceways carrying Class 1E circuits are predicated on assumptions related to flame retardance, cable derating, etc. The placement of cables of lesser qualification in these raceways would nullify these assumptions.
 
5. The "Note" following Section 4.5 should be supplemented as follows: "This exemption is limited and does not extend to other require ments such as those of General Design Criter ion 17."
6. Analyses performed in accordance with Sections 4.5(3), 4.6.2, and 5.1.1.2 should be submitted as part of the Safety Analysis Report and should identify those circuits installed in accordance with these sections.
 
Basis: Extension of Regulatory Guide 1.70,
'Sfhdard Format and Content of Safety Ana lysis Reports for Nuclear Power Plants,"
to provide the information needed in order for the staff to independently verify conformance to the standard.
 
7. Non-Class-lE instrumentation and control circuits should not be exempted from the pro visions of Section 4.6.2.
 
Basis: There is no firm technical basis for an unrestricted exemption of these circuits.
 
Exemptions should be justified by analysis.
 
8. Section 5.1.1.1 should not be construed to imply that adequate separation of redundant circuits can be achieved within a confined space such as a cable tunnel that Is effectively unventilated.
 
9. Section 5.1.1.3 should be supplemented as follows: "(4) Cable splices in raceways should be prohibited."
Basis: Splices have been identified as the n--iUting cause of several fires in raceway$. 
Even where the separation distance is adequate to prevent a fire in the raceways of one division from affecting cables in a
redundant division, all practicable means should be used to prevent the occurrence of a fire. This position against splices in race ways is therefore prudent. Splices are not, by themselves, unacceptable. If they exist, the resulting design should be justified by analyses. The analyses should be submitted as part of the Safety Analysis Report.
 
10. Section 5.1.2, the phrase "at a sufficient number of points" should be understood to mean at intervals not to exceed 5 ft throughout the entire cable length.
 
Also, the preferred method of marking cable is color coding.
 
Basis: This is a logical extension of the nsn-ard's provisions.
 
A
5-ft maximum marking distance is considered necessary to facilitate visual verification that the cable installation is in conformance with separation criteria.
 
11. Section 5.1.2 should be supplemented as follows: "The method of identification used should be simple and should preclude the need to consult any reference material to distinguish between Class 1E and Non-Class-lE circuits, between Non-Class-lE circuits associated with different redundant Class 1E systems, and between redundant Class lE systems."
12. Pending issuance of other acceptable criteria, those portions of Section 5.1.3 (ex clusive of the Note following the second para graph) that permit the routing of power cables through the cable spreading area(s) and, by implication, the control room, should not be construed as acceptable.
 
Also, 'Section 5.1.3 should be supplemented as follows: "Where feasible, redundant cable spreading areas should be utilized."
Basis: This is a prudent specific interpreta
-n--of the standard's provisions in the ab sence of specific guidance. The staff recog nizes that subsequent investigation may prove that this approach is too conservative;
however, in the absence of supporting evidence to the contrary, this conservative approach is desirable.
 
1.75-3
 
The use of redundant cable spreading areas Is aloic" extension of the standard's provi sions re. Section 5.1.1.1). 
13. No significance should be attached to the different tray widths Illustrated in Figure 2.
 
14. Section 5.2.1 should be supplemented as follows:
"And should have independent air supplies,
15. Where ventilation is required, the sepa rate safety. class structures required by Sec tion 5.3.1 should be served by independent.
 
ventilation systems.
 
16. The first paragraph of Section 5.7 should be augmented as follows, "The separation re UNITED STATES
NUCLEAR REGULATORY COMMISSION
WASHINGTON. 0. C. 20551 O*FI*IAL
MJSI NESS
PENALTY FOR PRIVATE USE. 3300
quirements of 5.6 apply to instrumentation cabinets."
D.
 
IMPLEMENTATION  
The purpose o this section is to provide in formation to applicants and licensees regarding the NRC staff's plans for using this regulatory guide. This guide reflects current NRC staff practice. Therefore, except in those cases in which the applicant proposes an acceptable alternative method for complying with specified portions of the Commission's regulations, this guide will he used by the NRC staff in evaluat ing all construction permit applications for which the issue date of the Safety Evaluation Report is February 1, 1974, or after.
 
POSTAGI AN: PIECE PAID
U.S. NUCLIAN UEDULATO1"
COMU15gS6ON
1.75-4}}


{{RG-Nav}}
{{RG-Nav}}

Latest revision as of 02:06, 17 January 2025

Physical Independence of Electric Systems
ML003740265
Person / Time
Issue date: 09/30/1978
From:
Office of Nuclear Regulatory Research
To:
References
RG-1.75, Rev 2
Download: ML003740265 (4)


U.S. NUCLEAR REGULATORY COMMISSION

Revision 2 Septsmber 1978 REGULATORY GUIDE

OFFICE OF STANDARDS DEVELOPMENT

REGULATORY GUIDE 1.75 PHYSICAL INDEPENDENCE OF ELECTRIC SYSTEMS

A.

INTRODUCTION

Section 50.55a, "Codes and Standards," of 10

CFR Part 50, "Domestic Licensing of Production and Utilization Facilities,"

requires in paragraph (h) that protection systems meet the requirements set forth in the Institute of Electrical and Electronics Engineers Standard,

"Criteria for Protection Systems for Nuclear Power Generating Stations" (IEEE 279).1 Sec tion 4.6 of IEEE Std 279-1971 (also designated ANSI N42.7-1972) requires, in part, that chan nels that provide signals for the same protec tive function be independent and physically separated. General Design Criterion 3, "Fire Protection," of Appendix A,

"General Design Criteria for Nuclear Power Plants," to I0 CFR

Part 50 requires, in part, that structures, systems, and components important to safety be designed and located to minimize, consistent with other safety requirements, the probability and effect of fires. General Design Criterion 17,

"Electric Power Systems," requires, in part, that the onsite electric power supplies, including the batteries, and the onsite electric distribution system have sufficient in dependence to perform their safety functions assuming a single failure. General Design Cri terion 21,

"Protection System Reliability and Testability," reqxiires, in part, that independ ence designed into protection systems be suffi cient to ensure that no single failure results in loss of the protective function.

This guide describes a method acceptable to the NRC staff of complying with IEEE Std 279

1971 and Criteria 3, 17, and 21 of Appendix A

to 10 CFR Part 50 with respect to the physical independence of the circuits and electric equipment comprising or associanted with the

'Copies may be obtained from the Institute of Eectrical and Electronics Engineers.

United Engintering Center. 345 East

47th Street. New York, New York 10017.

Class 1E power system, the protection system, systems actuated or controlled by the protec tion system, and auxiliary or supporting sys tems that must be operable for the protection system and the systems it actuates to perform their safety-related functions. This guide ap plies to all types of nuclear power plants.

This guide addresses only some aspects of defense against the effects of fires. Additional criteria for protection against the effects of fires are provided in Regulatory Guide 1-120,

"Fire Protection Guidelines for Nuclear Power Plants.,

B.

DISCUSSION

Draft IEEE Standard, "Criteria for Separa tion of Class

1E Equipment and Circuits,"

dated July 20, 1973, was prepared by Ad Hoc Subcommittee

6 of the Nuclear Power Engineering Committee (NPEC) of the Institute of Electrical and Electronics Engineers. The draft was -subsequently modified by NPEC in August. 1973 incident to the normal process of developing its technical content. The modified draft standard provided criteria for the separation of redundant Class IE equipment and circuits installed at nuclear power plants.

Inasmuch as there was an urgent need for explicit guidance in the area of physical inde pendence of electric systems and in view of the considerable guidance already available from the modified -IEEE draft standard, the staff prepared a document entitled "Appendix 1 to Regulatory Guide 1.75 - Physical Independence of Electric Systems." This- Appendix, which was essentially the modified IEEE

draft standardi further modified to (a) address ac ceptably those portions of the standard on which there was not complete agreement, (b)

  • Lines indicate substantive changes from previous issue.

USNRC REGULATORY GUIDES

1egmatumy Guidee am band to &oxbo mid ruW

WsHIMl

&M

Ie pt*1c nietodsoospable to la NRC eteff Of knmoain

0

e- c WW

-

lie Se0ef prob poei*dted

e*derm or so po"

gAdence 10

ml e

I

tdpMry GAd we not hedtfuftn fW mqs, aid arm V1 with lambI not requke. Melsad end sa&udmw ebrn

10

o

  • -oee K ut

& In tho s p ud b e to cepbo ah N lt v ro s a bob fore ta *W

usgmIb~ pw bounnce or earitirwnsoe pe1 i

&

kOr @OWN

b Canuiets aid euggeelion for harovenientah In 0-

gidsa we encoasgjac at eld Oim&oWd rgde w be etwbed. as ep te Pr

c. o d

o th w4d to re~ct ume Inonilon or axpelence. This ii was meted ma mult of eslienei receitved *rom to pidec ond eddkonad gaff rviw.

a imw dsid be em W W In ft liCowN

a Wo ied N eo I. Poum RcOtMrs

s. vmrxon

2. ReeahwdimdTeat Revmo~

7. Traiopution S. Fukl m

od Metmkba F~im

o

=o M

4. Esikonmiirm mid 1::hig

5.ari~itR~

& Mstmwih mid ProectW

a eral feqoast for uhig egooes of bmaed dMn Wkhd noy be uprOduce) or tar i

ancemen aien asmaswefc detkution kt f *de cone of kftns gides

""ons ei*Id be nod& In ug W"

W

U,& Nuch Reg.Aty Comnakn. Wi*kns

.

D.C. Z.

AtmnW

Dkocw.

Dmiden Of Tedhad bInu.on mid Documeo Caga.

I

describe logical extensions of the standard's.

provisions that were acceptable to the staff, and (a) provide clarification where necessary,.

was endorsed by the February 1974 version of this guide.

Subsequent to the issuance of the February

1974 version of this guide, the modified MEEE

draft standard upon which the guide and its Appendix were based evolved, in the normal course of standard development, into IEEE Std 384-1974,

"IEEE Trial-Use Standard Criteria for Separation of Cuss JR Xupmen-

-Cir- cults" (also designated ANSI N41.14). IEEE Std 384-1974 has undergone balloting within Ad Hoc Subcommittee .6 and NPEC and was approved by the IEEE Standards' Board on February 28,

1974. This revision to the guide endorses, with certain exceptions, IEEE Ptd 384-1974.

The NRC staff does not agree with certain"

provisions of the trial-use standard such as those pertaining to the definition of "raceway,"

the routing of power cables through the cable spreading area(s) and control room', and tie status of non-Class-lI circuits that are. not separated from associated circuits by accept able distance or bairiers. This lack of agree ment is reflected in Regulatory Positions C. 1,

2, 4, 6, 7, 9, 10, and 12.

There are also several regulatory positions that are logical extensions of the standard's provisions and reflect current staff review practice.

For example, a provision of the standard that addresses the

"degree of separation commensurate with the damage

3otential of the hazard" does not specifically zover cable tunnels which, in the event of a fire, may not effectively separate redundant circuits or equipment. As another example, the standard requires that methods of identification distinguish between redundant Class

1E

systems, associated circuits, and non-Class-IX

systems.

By implication, associated circuits assigned to different redundant divisions should also be identified.

However, the provision is implicit.

An explicit provision should be provided.

Detailid bases are included herein for those regulatory positions that are significantly at iariance with the standard's provisions. The remaining regulatory positions are logical ex tensions or clarifications of the standard's pro visions.

C.

REGULATORY POSITION

IEEE Std 384-1974 sets forth criteria for the separation of circuits and equipment. that are redundant. The determination of which circuits and equipment are redundant and the degree of redundancy required is outside the scope of this guide and the standard. The standard also sets forth criteria relating to tests and analyses for determining the flame-retardant characteristics of proposed cable installations.

The criteria are acceptable provided such tests and analyses are based on realistic premises and are otherwise fully applicable to the actual.

cable installations.

The guidance in IEEE Std 384-1974, "IEEE

Trial-Use Standard Criteria for Separation of Class IR

Equipment and Circuits,"

dated

,farch 15, 1974, is generally acceptable to the NRC staff and provides an adequate basis for complying with IEEE Std 279-1971 and the Commission's General Design Criteria 3, 17, an& 21- of Appendix A to 10 CFR Part. 50 with.

respect to the physical independence of the circuits and electric equipment comprising or associated with the Class 1E power system, the protection system, systems actuated or controlled by the protection system, and auxiliary or supporting systems that must be operable for the protection system and the systems it actuates to perform their safety related functions, subject to the following:

1. Section 3,

"Isolation Device," should be supplemented as follows:

"(Interrupting de vices actuated only by fault current are not considered to be isolation devices within the context of this document.)"

Basis: Logical extension of the standard's provisions. The standard defines "isolation device" in terms of preventing malfunctions in one section of a circuit from causing un acceptable influences in other sections of the circuit or other circuits. Under the postu lated conditions of a loss-of-coolant accident,.

loss of offsite power, and a cable tray fire, the proximity of circuits energized from re dundant Class 1E power sources could lead to concurrent high fault currents (e.g., short to ground) which, in turn, threaten the re dundant main circuit breakers.

Also, the susceptibility of non-Class-IE loads ener gized from redundant Class 1E power sources to design basis events (e.g., seismic events)

could similarly threaten the redundant main circuit breakers. Tripping of the main circuit breakers would cause the. loss of emergency power to redundant "divisions" of equipment.

It is recognized that proper breaker or fuse coordination would preclude such an event.

However, because the main breakers are in series with the fault and could experience momentary currents above their setpoints, it is prudent to preclude the use of inter rupting devices actuated only by fault cur rent as acceptable devices for isolating non Class-IE circuits from Class 1E or associated circuits.

Breakers that trip on receipt of a signal other than one derived from the fault current or its effects (e.g., an accident signal) are acceptable since the downstream circuits would. already be isolated from their respec tive power sources under accident conditions and could pose no threat to these sources.

1.75-2 KYý

2. Section 3,

"Raceway". Interlocked armor

"enclosing cable should not be construed as a

"raceway".

Basis: There is no precedent or other known R

reason for considering such cable to be a "raceway". This regulatory position is con sistent with current industry practice, including the provisions of the National Elec tric Code.

3. Section 4.3 should be supplemented as.

follows: "In general, locating redundant cir cuits and equipment in separate safety class structures affords a greater degree of assur ance that a single event will not affect redun dant systems.

This method of separation should be used whenever practicable and where its use does not conflict with other safety objectives."

4. Associated circuits installed in accordance with Section 4.5(1) should be subject to all re quirementa placed on Class lE circuits such as cable derating, environmental qualification, flame retardance, splicing restrictions, and raceway fill unless it can be demonstrated that the absence of such requirements could not significantly reduce the availability of the Class IE circuits.

Basis: This is a logical extension of the stanaard's provisions. The specified minimum acceptable separation distances for raceways carrying Class 1E circuits are predicated on assumptions related to flame retardance, cable derating, etc. The placement of cables of lesser qualification in these raceways would nullify these assumptions.

5. The "Note" following Section 4.5 should be supplemented as follows: "This exemption is limited and does not extend to other require ments such as those of General Design Criter ion 17."

6. Analyses performed in accordance with Sections 4.5(3), 4.6.2, and 5.1.1.2 should be submitted as part of the Safety Analysis Report and should identify those circuits installed in accordance with these sections.

Basis: Extension of Regulatory Guide 1.70,

'Sfhdard Format and Content of Safety Ana lysis Reports for Nuclear Power Plants,"

to provide the information needed in order for the staff to independently verify conformance to the standard.

7. Non-Class-lE instrumentation and control circuits should not be exempted from the pro visions of Section 4.6.2.

Basis: There is no firm technical basis for an unrestricted exemption of these circuits.

Exemptions should be justified by analysis.

8. Section 5.1.1.1 should not be construed to imply that adequate separation of redundant circuits can be achieved within a confined space such as a cable tunnel that Is effectively unventilated.

9. Section 5.1.1.3 should be supplemented as follows: "(4) Cable splices in raceways should be prohibited."

Basis: Splices have been identified as the n--iUting cause of several fires in raceway$.

Even where the separation distance is adequate to prevent a fire in the raceways of one division from affecting cables in a

redundant division, all practicable means should be used to prevent the occurrence of a fire. This position against splices in race ways is therefore prudent. Splices are not, by themselves, unacceptable. If they exist, the resulting design should be justified by analyses. The analyses should be submitted as part of the Safety Analysis Report.

10. Section 5.1.2, the phrase "at a sufficient number of points" should be understood to mean at intervals not to exceed 5 ft throughout the entire cable length.

Also, the preferred method of marking cable is color coding.

Basis: This is a logical extension of the nsn-ard's provisions.

A

5-ft maximum marking distance is considered necessary to facilitate visual verification that the cable installation is in conformance with separation criteria.

11. Section 5.1.2 should be supplemented as follows: "The method of identification used should be simple and should preclude the need to consult any reference material to distinguish between Class 1E and Non-Class-lE circuits, between Non-Class-lE circuits associated with different redundant Class 1E systems, and between redundant Class lE systems."

12. Pending issuance of other acceptable criteria, those portions of Section 5.1.3 (ex clusive of the Note following the second para graph) that permit the routing of power cables through the cable spreading area(s) and, by implication, the control room, should not be construed as acceptable.

Also, 'Section 5.1.3 should be supplemented as follows: "Where feasible, redundant cable spreading areas should be utilized."

Basis: This is a prudent specific interpreta

-n--of the standard's provisions in the ab sence of specific guidance. The staff recog nizes that subsequent investigation may prove that this approach is too conservative;

however, in the absence of supporting evidence to the contrary, this conservative approach is desirable.

1.75-3

The use of redundant cable spreading areas Is aloic" extension of the standard's provi sions re. Section 5.1.1.1).

13. No significance should be attached to the different tray widths Illustrated in Figure 2.

14. Section 5.2.1 should be supplemented as follows:

"And should have independent air supplies,

15. Where ventilation is required, the sepa rate safety. class structures required by Sec tion 5.3.1 should be served by independent.

ventilation systems.

16. The first paragraph of Section 5.7 should be augmented as follows, "The separation re UNITED STATES

NUCLEAR REGULATORY COMMISSION

WASHINGTON. 0. C. 20551 O*FI*IAL

MJSI NESS

PENALTY FOR PRIVATE USE. 3300

quirements of 5.6 apply to instrumentation cabinets."

D.

IMPLEMENTATION

The purpose o this section is to provide in formation to applicants and licensees regarding the NRC staff's plans for using this regulatory guide. This guide reflects current NRC staff practice. Therefore, except in those cases in which the applicant proposes an acceptable alternative method for complying with specified portions of the Commission's regulations, this guide will he used by the NRC staff in evaluat ing all construction permit applications for which the issue date of the Safety Evaluation Report is February 1, 1974, or after.

POSTAGI AN: PIECE PAID

U.S. NUCLIAN UEDULATO1"

COMU15gS6ON

1.75-4