ML19242B099: Difference between revisions
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
StriderTol (talk | contribs) (StriderTol Bot change) |
||
| (One intermediate revision by the same user not shown) | |||
| Line 13: | Line 13: | ||
| document type = CORRESPONDENCE-LETTERS, INCOMING CORRESPONDENCE, UTILITY TO NRC | | document type = CORRESPONDENCE-LETTERS, INCOMING CORRESPONDENCE, UTILITY TO NRC | ||
| page count = 1 | | page count = 1 | ||
| project = | |||
| stage = Other | |||
}} | }} | ||
=Text= | =Text= | ||
{{#Wiki_filter:7'1 POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FIT 2 PATRICK NUCLEAR POWER PLANT JOHN D. LEONARD, JR. | {{#Wiki_filter:7'1 POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FIT 2 PATRICK NUCLEAR POWER PLANT S | ||
JOHN D. LEONARD, JR. | |||
P.O. BOX 41 Resident Manager Lycoming, New York 13093 315-342-3840 June 28, 1979 JAFP-79-337 Mr. Boyce H. Grier, Di rector United States Nuclear Regulatory Commission Region 1 631 Park Avenue King of Prussia, Pennsylvania 19406 | |||
==SUBJECT:== | ==SUBJECT:== | ||
| Line 26: | Line 29: | ||
==Dear Mr. Grier:== | ==Dear Mr. Grier:== | ||
In reference (1) the Power Authority responded to NRC isE Bulletin 79-09 concerning the failures of General Electric AK-2 breakers in other nuclear power generating stations. | |||
In reference (1) the Power Authority responded to NRC isE Bulletin 79-09 concerning the failures of General Electric AK-2 breakers in other nuclear power generating stations. | Reference (1) outlined the preven'.ative maintenance program for GE AK-2 breakers in effect at the James A. | ||
FitzPatrick Nuclear Power Plant. | FitzPatrick Nuclear Power Plant. | ||
As committed to in reference (1), preventative maintenance in accordance with procedure EP-008 ' as been performed on all GE AK-2 | As committed to in reference (1), preventative maintenance in accordance with procedure EP-008 ' as been performed on all GE AK-2 breakers in safety-related applications at JAFNPP. There were no conditions found during the performance of this preventative maintenance which would have prevented any of these breakers from performing its intended function. | ||
Also, the causes for breaker failures described in l&E Bulletin 79-09 were not found to exist in any of the safety-related breakers which were examined. | |||
breakers in safety-related applications at JAFNPP. There were no conditions found during the performance of this preventative maintenance which would have prevented any of these breakers from performing its intended function. | |||
The preventative maintenance program for AK-2 breckers outlined in the Power Authority's previous response will continue to be followed to ensure that these breakers continue to perform as designed. | The preventative maintenance program for AK-2 breckers outlined in the Power Authority's previous response will continue to be followed to ensure that these breakers continue to perform as designed. | ||
Very truly yours, 62 | Very truly yours, 62 m x JOHN D. LEONARD, JR. | ||
519 245 RESIDENT MANAGER JDL:VMW:Jvw cc: | |||
RESIDENT MANAGER | G. T. Berry, PASNY, NY0 G. A. Wilverding, PASNY, NY0 | ||
(< | |||
Document Cor. trol Center}} | P. W. Lyon, PASNY, NY0 4 | ||
M. C. Cosgrove, SQAE, JAF 7908070 7 01_ | |||
R. J. Pasternak, JAF Document Cor. trol Center}} | |||
Latest revision as of 13:45, 4 January 2025
| ML19242B099 | |
| Person / Time | |
|---|---|
| Site: | FitzPatrick |
| Issue date: | 06/28/1979 |
| From: | Leonard J POWER AUTHORITY OF THE STATE OF NEW YORK (NEW YORK |
| To: | Grier B NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I) |
| References | |
| JAFP-79-337, NUDOCS 7908070501 | |
| Download: ML19242B099 (1) | |
Text
7'1 POWER AUTHORITY OF THE STATE OF NEW YORK JAMES A. FIT 2 PATRICK NUCLEAR POWER PLANT S
JOHN D. LEONARD, JR.
P.O. BOX 41 Resident Manager Lycoming, New York 13093 315-342-3840 June 28, 1979 JAFP-79-337 Mr. Boyce H. Grier, Di rector United States Nuclear Regulatory Commission Region 1 631 Park Avenue King of Prussia, Pennsylvania 19406
SUBJECT:
NRC 16E BULLETIN 79-09 FAILURES OF GE AK-2 BREAKERS IN SAFETY-RELATED SYSTEMS
REFERENCE:
(1) Power Authority letter JAFP-79-247 dated May 18, 1979
Dear Mr. Grier:
In reference (1) the Power Authority responded to NRC isE Bulletin 79-09 concerning the failures of General Electric AK-2 breakers in other nuclear power generating stations.
Reference (1) outlined the preven'.ative maintenance program for GE AK-2 breakers in effect at the James A.
FitzPatrick Nuclear Power Plant.
As committed to in reference (1), preventative maintenance in accordance with procedure EP-008 ' as been performed on all GE AK-2 breakers in safety-related applications at JAFNPP. There were no conditions found during the performance of this preventative maintenance which would have prevented any of these breakers from performing its intended function.
Also, the causes for breaker failures described in l&E Bulletin 79-09 were not found to exist in any of the safety-related breakers which were examined.
The preventative maintenance program for AK-2 breckers outlined in the Power Authority's previous response will continue to be followed to ensure that these breakers continue to perform as designed.
Very truly yours, 62 m x JOHN D. LEONARD, JR.
519 245 RESIDENT MANAGER JDL:VMW:Jvw cc: