ML20069F917: Difference between revisions

From kanterella
Jump to navigation Jump to search
(StriderTol Bot change)
(StriderTol Bot change)
 
Line 17: Line 17:


=Text=
=Text=
{{#Wiki_filter:.           . _ _ _                        . . .      _ _ _            _ _ .  . . _ - _ _ . _ -    - __                ~ _ . . _ . . . _
{{#Wiki_filter:.
      *                **                                                                                                                                                          Bull 3 tin 2.0.1 - 2A
~ _.. _... _
:.  .!~
Bull 3 tin 2.0.1 - 2A
!                                                                                                                                                                                      Gould I-T-E Molded Case O                                                                                                                                                       Circuit Breakers Testing and Maintenance Procedures i
.!~
1                                                                                                                                                                                                                              ,
Gould I-T-E Molded Case
; O Circuit Breakers Testing and Maintenance Procedures i
1 O
1 O
i l
1 i
i O
l i
j                          O                                                 .o
: O j
                                  - - --.4 Y'                      . _ . .
O
                                                      !                          l
.o Y'
                                                                                              ~                                                                                  =
- - --.4!
c
l
:e"
=
                                                                                                                                                                                                  ^
~
O ll1                                                     &                                                                   .                    ..
:e c
M.!;                                  iuda
^
                                                                            $                                                                    ' . I,,                  ,
O ll1 &
i.
M.
I liA E-                                                             w                 -
'. I,,
                                                                                                                                                              ~
iuda i.
                                                  ~"~~"~'                                                   ^~'                            ~~
I liA E-w
O B209280282 820922 PDR ADOCK 05000368
~ " ~ ~ " ~ '
                                                                                                                                                                                  "}  GOUL s P                                                          PDR
~
~~
O
^~'
"} GOUL s B209280282 820922 PDR ADOCK 05000368 P
PDR


              .l.T-E MOLDED CASE CIRCulT BREAKERS TESTING AND MAINTENANCE PROCEDURES e
.l.T-E MOLDED CASE CIRCulT BREAKERS TESTING AND MAINTENANCE PROCEDURES e
YOU'LL FIND MANY REASONS                 dreamed were possible with any               tampering, and that the breaker may be FOR CHOOSING I-T.E                   protective device.                           expected to perform according to the MOLDED CASE CIRCUlT BREAKERS                 The utmost in reliability, based on           UL specifications. A broken seal voids I-T E's quality construction-               the UL label and jeopardizes the quick make, quick-break                       warranty.
YOU'LL FIND MANY REASONS dreamed were possible with any tampering, and that the breaker may be FOR CHOOSING I-T.E protective device.
Her2 Ars Just a Few:
expected to perform according to the MOLDED CASE CIRCUlT BREAKERS The utmost in reliability, based on UL specifications. A broken seal voids I-T E's quality construction-the UL label and jeopardizes the Her2 Ars Just a Few:
Maximum protection for equipment and            peration, silver alloy contactr, high c ntact pressure, extra-wide pole           1 T E molded case c,rcu,t i   i breakers have personntl. Minimum maintenance and                                                         an excellent record of reliability which spacing, individually calibrated poles on downtime.                                                                                 to a great exte11t is due to the enclosed all breakers. These and many other design and construction features are         design which minimizes tampering and Lower total cost over the many years of checked constantly to meet 1 T-E's           exposure to dirt, dust, and other service you'll get from I T E breakers.
quick make, quick-break warranty.
Because they're resettable, take less         quality requirements and those of           contaminants. This reliability also space, consume less power and prever.t       Underwriters' Laboratories, Inc. All of     depends on proper installation following these measures of dependeable               careful application, particularly with single phasing as compared to fusible devices.                                     protection are the natural results of       reference to the maximum available I-T E's many years of technical             short circuit current of the circuit to A selection to meet any need you may         leadership in circuit breakers,             which the circuit breaker is applied.
peration, silver alloy contactr, high Maximum protection for equipment and c ntact pressure, extra-wide pole 1 T E molded case c,rcu,t breakers have i
havr. From a 4000-ampere systems             For testing procedures on GFI and             Reliability after application also bre:ker to a 15 ampere ground fault           Systems Breakers, consult appropriate inttrrupter, an instantaneous trip                                                         depends upon environment and IS-breaker for motor protection, a special                                                   maintenance. All devices with moving fire pump breaker, or-the most               1-T E molded case circuit breakers           parts require periodic check ups. A demanding of all-breakers to meet U.S.       undergo extensive production testing         circuit breaker is no exception. It is not Navy requirements.                           and calibration at the factory. These       unusual for a circuit breaker to be in tests are based on Underwriters
i personntl. Minimum maintenance and spacing, individually calibrated poles on an excellent record of reliability which downtime.
* service for extended periods and never Capability to do virtually anything you       Laboratories, Inc. " Safety Standard for     be called upon to carry out its overload want, anywhere you want. With over           Branch Circuit and Service Circuit           or short-circuit functions. Therefore,it 800 brtakers to choose from, you also         Breakers" No. 489. Circuit breakers         should be exercised and tested at times have a complete variety of accessories,       carrying the UL label have factory           to assure proper funct;oning. The auxiliaries, enclosures and mounting         sealed calibrated elements; an unbroken     procedures outlined in this bulletin are arrangements. You may find you can do         seal assures that the mechanism has not     accepted methods of testing to verify things with an I-T E breaker you never       been subjected to alteration or             circuit breaker performance in the field.
all breakers. These and many other to a great exte11t is due to the enclosed Lower total cost over the many years of design and construction features are design which minimizes tampering and service you'll get from I T E breakers.
l O
checked constantly to meet 1 T-E's exposure to dirt, dust, and other Because they're resettable, take less quality requirements and those of contaminants. This reliability also space, consume less power and prever.t Underwriters' Laboratories, Inc. All of depends on proper installation following single phasing as compared to fusible these measures of dependeable careful application, particularly with devices.
protection are the natural results of reference to the maximum available I-T E's many years of technical short circuit current of the circuit to A selection to meet any need you may leadership in circuit breakers, which the circuit breaker is applied.
havr. From a 4000-ampere systems For testing procedures on GFI and bre:ker to a 15 ampere ground fault Reliability after application also Systems Breakers, consult appropriate depends upon environment and inttrrupter, an instantaneous trip IS-breaker for motor protection, a special maintenance. All devices with moving fire pump breaker, or-the most 1-T E molded case circuit breakers parts require periodic check ups. A demanding of all-breakers to meet U.S.
undergo extensive production testing circuit breaker is no exception. It is not Navy requirements.
and calibration at the factory. These unusual for a circuit breaker to be in tests are based on Underwriters
* service for extended periods and never Capability to do virtually anything you Laboratories, Inc. " Safety Standard for be called upon to carry out its overload want, anywhere you want. With over Branch Circuit and Service Circuit or short-circuit functions. Therefore,it 800 brtakers to choose from, you also Breakers" No. 489. Circuit breakers should be exercised and tested at times have a complete variety of accessories, carrying the UL label have factory to assure proper funct;oning. The auxiliaries, enclosures and mounting sealed calibrated elements; an unbroken procedures outlined in this bulletin are arrangements. You may find you can do seal assures that the mechanism has not accepted methods of testing to verify things with an I-T E breaker you never been subjected to alteration or circuit breaker performance in the field.
O l
l l
l l
l l
l l
i l
i l
l O
O l
l l                                                                 C A U TION
l l
\                                   Molded Case Circuit Breakers must always be completely de-energized, disconnected and isolated before any tests or maintenance are attempted.
C A U TION
\\
Molded Case Circuit Breakers must always be completely de-energized, disconnected and isolated before any tests or maintenance are attempted.
+
+


s
s PERIODIC FIELD TESTING AND MAINTENANCE PROCEDURES r
              ,                          PERIODIC FIELD TESTING AND MAINTENANCE PROCEDURES r                                                                   '
Qualified, authorized personnel can line and load terminals of each pole of insulation. The most common method perform routine field testing and the unit with the circuit breaker employs a "megger'' type instrument.
Qualified, authorized personnel can         line and load terminals of each pole of       insulation. The most common method perform routine field testing and           the unit with the circuit breaker             employs a "megger'' type instrument.
O' maintenance to assure the circuit contacts closed.
O'         maintenance to assure the circuit breaker is providing proper protection, contacts closed.
Most of such devices in use have outputs breaker is providing proper protection, l-T.E will provide allowable voltage f 500 voltes or less, whereas, much These procedures are based on accepted drop data on request for circuit breakers more reliability will be derived if 1000 practices. Note the caution below under test. It is recommended that this von insuuments are used because they before beginning any tests.
l-T.E will provide allowable voltage Most of such devices in use have outputs f 500 voltes or less, whereas, much These procedures are based on accepted       drop data on request for circuit breakers     more reliability will be derived if 1000 practices. Note the caution below             under test. It is recommended that this       von insuuments are used because they before beginning any tests.                   test be made with a de current               are more likely to pick up tracked approximating 50 percent of the circuit       inw!ation wrfaces. Resinanm values breaker continuous current rating;             below one megohm are considered
test be made with a de current are more likely to pick up tracked approximating 50 percent of the circuit inw!ation wrfaces. Resinanm values breaker continuous current rating; below one megohm are considered
: 1) Connections Test                           however, currents for the larger circuit     unsafe and should be investigated.
: 1) Connections Test however, currents for the larger circuit unsafe and should be investigated.
The connections to the circuit breaker       breakers may be as low as 50 amperes if       An insulation resistance test should be terminals should be inspected to             the millivoltmeter is of suf fic,ent i            made:
The connections to the circuit breaker breakers may be as low as 50 amperes if An insulation resistance test should be terminals should be inspected to the millivoltmeter is of suf fic,ent made:
determine proper conductor ampacity          sensitivity he mWivoh drop across each pole ;s i measured and recorded for
i sensitivity he mWivoh drop across determine proper conductor ampacity each pole ;s measured and recorded for
                                                                                                                -Between line and load terminals of and that proper electrical joints exist. If                                                       individual poles with the circuit overheating of connections is evident by c mpa s n aga s         e data mWed                 breaker contacts open.
-Between line and load terminals of i
Y           discoloration or arcing, the surfaces                               *
and that proper electrical joints exist. If individual poles with the circuit c mpa s n aga s e data mWed overheating of connections is evident by breaker contacts open.
* be practical to compare values with "Y            -Between adjacent poles and from must be cleaned before testing and                                                                 poles to metallic supporting structure reinstallation. As stated before,it is those of poles of other circuit breakers f sin at size and nyk.                           with the circuit breaker contacts essential that electrica! connections be                                                           closed. The latter may be done with made properly to prevent overheating.                                                             the circuit breaker in place af ter the Refer to Table #2 on page 7 for               4) Overload Tripping Test                           line and load conductors are recommended torque values. Aluminum           This test provides assurance the                     removed, or with the circuit breaker lug connectors are plated and should         overload component of the circuit                   bolted to a metallic base which not be cleaned with abrasives.               breaker is operating. This is NOT a                 simulates the in-service mounting.
Y "Y
verification test of 1-T.E's published test data. To perform the test, apply 300%         7) Summary
discoloration or arcing, the surfaces
: 2) Mechanical Operation Check                 of the breaker rating. The breaker             it is again emphasized that common Manual mechanical exercising of a             should open automatically. This proves       maintenance practices for electrical circuit breaker is a recommended             the overload component is functioning.       equipment should be adhered to in field procedure. A few operations of the           To determine actual tripping                 testing both new and installed molded handle performed periodically, together       characteristics, refer to page 5.             case circuit breakers, and usually the with a careful visual inspection of                                                         standard routine operating checks listed terminal connections, for tightness,                                                       above will be sufficient to assure proper
-Between adjacent poles and from be practical to compare values with must be cleaned before testing and poles to metallic supporting structure those of poles of other circuit breakers reinstallation. As stated before,it is with the circuit breaker contacts f sin at size and nyk.
: 5) Instantaneous Magnetic Tripping physical damage or evidence of                                                             functionmg of the circuit breaker. It is overheating are considered good               This test provides assurance that the         further recommended that since molded practice. This will keep mechanical           instantaneous magnetic component of           case circuit breakers have factory sealed linkages free, while the wiping action by     the circuit breaker is functioning. This     calibrated elements, that THIS SEAL contacts tends to avoid resistance           test does NOT determine exact tripping       SHOULD NOT BE BROKEN AND THE build-up and thereby minimizes heating.       values. To perform the test, use either       CIRCUlT BREAKER ITSELF Circuit breakers applied and specified       the Runup or Pulse method described           SHOULD NOT BE TAMPERED WITH.
essential that electrica! connections be closed. The latter may be done with made properly to prevent overheating.
for switching duty do not need regular       on page 6.
the circuit breaker in place af ter the Refer to Table #2 on page 7 for
Adjustment or repair c' molded case exercising.                                                                                 circuit breakers in * . eld is not
: 4) Overload Tripping Test line and load conductors are recommended torque values. Aluminum This test provides assurance the removed, or with the circuit breaker lug connectors are plated and should overload component of the circuit bolted to a metallic base which not be cleaned with abrasives.
: 6) Insulation Resistance                     recommended. The orcuit breaker An insulation resistance test is used to     should be replaced, or its parts should
breaker is operating. This is NOT a simulates the in-service mounting.
: 3) Individual Pole Resistance Test           determine the quality of insulation           be replaced or repaired at the f actory.
verification test of 1-T.E's published test data. To perform the test, apply 300%
(Millivolt Drop)                         between adjacent poles of a circuit           After performing any of the above tests, The detrimental effect of operating a       breaker and from its poles to ground.
: 7) Summary
be certain to account for all hardware circuit breaker in a manner for which it     The resistance test is made with higher       and tools and make certain all test was not intended can be detected by           de voltage than the rated voltage, to         instruments are disconnected before making a millivolt drop test across the     determine the actual resistance of the       re-energizing the circuit breaker.
: 2) Mechanical Operation Check of the breaker rating. The breaker it is again emphasized that common Manual mechanical exercising of a should open automatically. This proves maintenance practices for electrical circuit breaker is a recommended the overload component is functioning.
equipment should be adhered to in field procedure. A few operations of the To determine actual tripping testing both new and installed molded handle performed periodically, together characteristics, refer to page 5.
case circuit breakers, and usually the with a careful visual inspection of standard routine operating checks listed terminal connections, for tightness,
: 5) Instantaneous Magnetic Tripping above will be sufficient to assure proper physical damage or evidence of functionmg of the circuit breaker. It is overheating are considered good This test provides assurance that the further recommended that since molded practice. This will keep mechanical instantaneous magnetic component of case circuit breakers have factory sealed linkages free, while the wiping action by the circuit breaker is functioning. This calibrated elements, that THIS SEAL contacts tends to avoid resistance test does NOT determine exact tripping SHOULD NOT BE BROKEN AND THE build-up and thereby minimizes heating.
values. To perform the test, use either CIRCUlT BREAKER ITSELF Circuit breakers applied and specified the Runup or Pulse method described SHOULD NOT BE TAMPERED WITH.
for switching duty do not need regular on page 6.
Adjustment or repair c' molded case exercising.
circuit breakers in *. eld is not
: 6) Insulation Resistance recommended. The orcuit breaker An insulation resistance test is used to should be replaced, or its parts should
: 3) Individual Pole Resistance Test determine the quality of insulation be replaced or repaired at the f actory.
(Millivolt Drop) between adjacent poles of a circuit After performing any of the above tests, The detrimental effect of operating a breaker and from its poles to ground.
be certain to account for all hardware circuit breaker in a manner for which it The resistance test is made with higher and tools and make certain all test was not intended can be detected by de voltage than the rated voltage, to instruments are disconnected before making a millivolt drop test across the determine the actual resistance of the re-energizing the circuit breaker.
O
O
    %.)
%.)
C A U TION
C A U TION Molded Case Circruit Breakers must always be completely de-energized, disconnected and isolated before any tests or main tenance are attempted.
<                                              Molded Case Circruit Breakers must always be completely de-energized, disconnected and isolated before any tests or main tenance are attempted.
3
'                                                                                                                                                        3


VERIFICATION TEST PROCEDURES                                                                 .
VERIFICATION TEST PROCEDURES Underwriters Laboratories, Inc.
Underwriters Laboratories, Inc.                       screw and cable set screw should be       conductor in order to reduce heating
screw and cable set screw should be conductor in order to reduce heating
  ''StandIrd for Molded Case Circuit                     properly secured.                         and voltage drop.
''StandIrd for Molded Case Circuit properly secured.
Breakers and Circuit-Breaker                     4. Current must be held constant and           Other frequently encountered problems Enclosures," UL 489, is the basis for                 accurately over the erstire test time. are the inability to uit the required performance standards for all molded                 The heat generated in the trip unit of     time for the circuit b -takers to cont to case circuit breakers bearing the UL                 a thermal trip circuit breaker is         room tamperature and a room libel. Verification of molded case                     proportional to the sciuare of the       temperature other than 25 C (77*F). If circuit breakers to UL test standards is               current. A small variation of current     tests are made while thermal trip circuit intended to permit the checking of                     can cause a large variation in total     breakers are still warm, the trip time circuit breakers in accordance with                   heat generated.                           will be shorter than if they were allowed published data under carefully                         Example-if a 10 ampere current (la )     to cool completely. When testing controlled conditions. The published                   is allowed to change only 10 percent     ind.vidual poles, successive tests can be data are based upon the UL standard                   to 11 amperes (Is), the heat             run on adjacent poles,with no and,if verification of these data or                   generated will be:                       cool down periods between tests without application curves is desired from tests,             (12 )*       11* , 121 , g                resulting in more than a 10 percent error.         9 the tests should be performed under                   (1, )2       10 3      100               The recommended method of carefully controlled conditions as                                                               determining whether a circuit breaker This shows that an increase of 10 specifically instructed by Gould 1 T-E.               percent in current will cause a 21       has been calibrated in accordance with if circuit breaker performance '                      percent variation in heat and a          Gould I-T E's limits is to meet all of the charactzristics are to be tested in the               corresponding error in trip time.         UL specified conditions outlined in this field, there are many variables that must       NOTE-To get field test results                 publication.
and voltage drop.
be recognized and taken into account.           comparable to those obtained wi4en             Molded Case Circuit Breaker Trip Some simplifications are necessary;             circuit breakers are factory tested to UL       Characteristics however, even simplified testing must           Standards, ammeters must be carefully           Gould I T-E molded case circuit recognize variations that can and do           checked to a precise standard. Most             breakers employ the inverse time exist between one test setup and                 panelinstruments are accurate to a 12           element principle as the design basis for another. These variations can account           percent of fu// sca/e reading. This means       protecting against overloads without for differences in test results, and it         that a 500-ampere meter may have an             nuisance tripping. With the inverse time must be recognized that a circuit               error of i 10 amperes (+ 0.02 X 500 =           element concept, the time between the breaker may furnish adequate                     10 amperes). This same 10-ampere error         occurrence of an overload and the protection, but appear defective because       can exist during measurements at all           moment of tripping varies inversely with of the test procedure used.                     points on the scale. For example, the         the magnitude of the overload current.
Breakers and Circuit-Breaker
Underwriters Laboratories Standards           error at 100 amperes or 1/5 scale may           Thus, optimum overload protection is Calibration standards and the trip-time         still be 10 amperes,i.e.,10 percent.           achieved without nuisance tripping from values for circuit breakers tested in           From the previous example, a                   momentary higher overload currents.
: 4. Current must be held constant and Other frequently encountered problems Enclosures," UL 489, is the basis for accurately over the erstire test time.
accordance with UL 489 are based on             10-percent change in current can cause a       The speed of the breaker's response the following conditions:                       21 percent change in heat in the circuit       dependson the magnitude of theoverload.
are the inability to uit the required performance standards for all molded The heat generated in the trip unit of time for the circuit b -takers to cont to case circuit breakers bearing the UL a thermal trip circuit breaker is room tamperature and a room libel. Verification of molded case proportional to the sciuare of the temperature other than 25 C (77*F). If circuit breakers to UL test standards is current. A small variation of current tests are made while thermal trip circuit intended to permit the checking of can cause a large variation in total breakers are still warm, the trip time circuit breakers in accordance with heat generated.
: 1. Circuit breakers are tested in ope,n a.ir    breaker under test and a corresponding         The basic Gould 1-T E thermal magnetic at an ambient temperature of 25 C change in trip time. In order to               molded case circuit breaker combines (77 F).                                   minimize this effect, meter scales should     the inverse time element or thermal         .
will be shorter than if they were allowed published data under carefully Example-if a 10 ampere current (la )
a  ea be chosen so that readings are taken in
to cool completely. When testing controlled conditions. The published is allowed to change only 10 percent ind.vidual poles, successive tests can be data are based upon the UL standard to 11 amperes (Is), the heat run on adjacent poles,with no and,if verification of these data or generated will be:
[,,t          ,
cool down periods between tests without application curves is desired from tests, (1 )*
                                      ,                                                            action design for low level overloads, before tests are started, circuit the upper half of the scale.                   and instantaneous magnetic action for         j Testing Limitations                          short circuits.
11*
breakers must have been in a 25'C i 3 C (77 F i 5'F) ambient long               in field testing it will not be practical to   Thermal Overcurrent Trip Test meet all of the test conditions specified     When testing molded case circuit enough for all parts to have reached the same temperature (at least 2           by UL Standards. In many cases, NONE           breakers in the field,it is recommended hours for circuit breakers rated 100         f the UL standard factory test               that the thermal overcurrent tests be amperes and below, and 4 hours for         conditions may be fully met.                   performed on individual poles at 300%
121 resulting in more than a 10 percent error.
those rated above 100 amperes).             One of the most frequently encountered         of rated current. The reaction of the
2 g
: 3. Calibration tests are made with               problems is the fact that a circuit           circuit breaker to this overload will be conductors of the size specified in         breaker may have to be tested in the           indicative of its reaction throughout its the UL Standard connected to line           enclosure in which it is mounted, rather       entire overcurrent tripping range. This and load terminals. If, in field           than in open air as specified by UL.           load has been chosen as the test point testing, the circuit breaker is             Consequently, the difference in ambient       because it is relatively easy to generate connected with wire or bus other           temperature will result in trippin9           the required current in the field and the than that specified, results will vary     characteristics different from those           wattage per pole from line to load is from published riata. The wire should     which would be experienced in open air.       large enough so that the dissipation of be connected with the lug                 Temporary test connections call for           heat in the adjacent pole is minor and specifically intended for that             extra care with respect to the tightness       does not affect the test results breaker, and both the lug mounting         of the connections and the size of the         appreciably.
9 the tests should be performed under (1, )2 10 100 The recommended method of 3
carefully controlled conditions as This shows that an increase of 10 determining whether a circuit breaker has been calibrated in accordance with specifically instructed by Gould 1 T-E.
percent in current will cause a 21 Gould I-T E's limits is to meet all of the if circuit breaker performance '
percent variation in heat and a UL specified conditions outlined in this charactzristics are to be tested in the corresponding error in trip time.
field, there are many variables that must NOTE-To get field test results publication.
be recognized and taken into account.
comparable to those obtained wi4en Molded Case Circuit Breaker Trip Some simplifications are necessary; circuit breakers are factory tested to UL Characteristics however, even simplified testing must Standards, ammeters must be carefully Gould I T-E molded case circuit recognize variations that can and do checked to a precise standard. Most breakers employ the inverse time exist between one test setup and panelinstruments are accurate to a 12 element principle as the design basis for another. These variations can account percent of fu// sca/e reading. This means protecting against overloads without for differences in test results, and it that a 500-ampere meter may have an nuisance tripping. With the inverse time must be recognized that a circuit error of i 10 amperes (+ 0.02 X 500 =
element concept, the time between the breaker may furnish adequate 10 amperes). This same 10-ampere error occurrence of an overload and the protection, but appear defective because can exist during measurements at all moment of tripping varies inversely with of the test procedure used.
points on the scale. For example, the the magnitude of the overload current.
Underwriters Laboratories Standards error at 100 amperes or 1/5 scale may Thus, optimum overload protection is Calibration standards and the trip-time still be 10 amperes,i.e.,10 percent.
achieved without nuisance tripping from values for circuit breakers tested in From the previous example, a momentary higher overload currents.
accordance with UL 489 are based on 10-percent change in current can cause a The speed of the breaker's response the following conditions:
21 percent change in heat in the circuit dependson the magnitude of theoverload.
: 1. Circuit breakers are tested in ope,n a.
breaker under test and a corresponding The basic Gould 1-T E thermal magnetic ir at an ambient temperature of 25 C change in trip time. In order to molded case circuit breaker combines (77 F).
minimize this effect, meter scales should the inverse time element or thermal
[,,t be chosen so that readings are taken in action design for low level overloads, a
ea the upper half of the scale.
and instantaneous magnetic action for j
before tests are started, circuit breakers must have been in a 25'C i Testing Limitations short circuits.
3 C (77 F i 5'F) ambient long in field testing it will not be practical to Thermal Overcurrent Trip Test meet all of the test conditions specified When testing molded case circuit enough for all parts to have reached the same temperature (at least 2 by UL Standards. In many cases, NONE breakers in the field,it is recommended hours for circuit breakers rated 100 f the UL standard factory test that the thermal overcurrent tests be amperes and below, and 4 hours for conditions may be fully met.
performed on individual poles at 300%
those rated above 100 amperes).
One of the most frequently encountered of rated current. The reaction of the
: 3. Calibration tests are made with problems is the fact that a circuit circuit breaker to this overload will be conductors of the size specified in breaker may have to be tested in the indicative of its reaction throughout its the UL Standard connected to line enclosure in which it is mounted, rather entire overcurrent tripping range. This and load terminals. If, in field than in open air as specified by UL.
load has been chosen as the test point testing, the circuit breaker is Consequently, the difference in ambient because it is relatively easy to generate connected with wire or bus other temperature will result in trippin9 the required current in the field and the than that specified, results will vary characteristics different from those wattage per pole from line to load is from published riata. The wire should which would be experienced in open air.
large enough so that the dissipation of be connected with the lug Temporary test connections call for heat in the adjacent pole is minor and specifically intended for that extra care with respect to the tightness does not affect the test results breaker, and both the lug mounting of the connections and the size of the appreciably.
C A U TION Molded Case Circuit Breakers must always be completely de-energized, disconnected and isolated before any tests or maintenance are attempted.
C A U TION Molded Case Circuit Breakers must always be completely de-energized, disconnected and isolated before any tests or maintenance are attempted.


9 VERIFICATION TEST RESULTS Test values are based on 300% o' breaker rating on ind'ividual poles at 25*C (77'F) using four feet of copper wire or cable as indicated.
9 VERIFICATION TEST RESULTS Test values are based on 300% o' breaker rating on ind'ividual poles at 25*C (77'F) using four feet of copper wire or cable as indicated.
Tripping Time In Seconds Wire Sire                                                                               Man. For O            Bresher                  Ampere Frame                     Rating                 Per Pole                             Mmimum                   Maximum                 Cable Prot.
Tripping Time In Seconds O
EQ                           15-20                 1- #12                                 4                       45                   100 1 Pole                       30-50                 1-e6                                   4                       45                   100 TO                             If20                 1-si2                                 4                       35                   100 2,3 Pole                     30-40                 1- #8                                 4                       35                   100 50-100                 1-s1                                   5                       45                   200 125                     1 - e 1/0                             10                       50                   200 BOC                           15-20                 1- 812                                 4                       35                   100 30                     1- s10                                 4                       35                   100 OJ                         12f225                 1-e470                               25                       155                   300 E                             1020                 1- #12                                 8                       50                   100 3040                   1- #8                                 8                       50                   100 50-100                 1-et                                   0                         50                   200 EH,EF,HE                     15 20                 1- s12                               to                         50                   100 HE                           3040                 1- 88                                 10                         50                   100 50-100                 1-at                                   9                         75                   200 EH                         110 150                 1- s t /0                             25                       180                   300 FJ                            70!iDO               1-e1                                 3d                       13d                   200 125-225 ~
Bresher Ampere Wire Sire Man. For Frame Rating Per Pole Mmimum Maximum Cable Prot.
1 - #4 /0                             35                       170                   300 JD,JJ                         7dTO0                 1-#1                                 50                       130                   200 JL,HJ                       124225                 1- s4/0                               40                       160                   300 250 400                 2-#3/0                               30                       200                   300 LL, H L                     450                     2- #4/0                               25                       250                   300 500 000                 2-350 MCM                             25                       250                   350 KM                         25d~450                 2-a4to                               70                       250                   300 500 600                 2-350 MCM                             45                       250                   350 700 400                 3-300 MCM                             55                       280                   600 HM                         400450                 2-s4/0                               45                       250                   300 500-600                 2-350 MCM                             45                       250                     350 700E00                 3-300 MCM                             45                       280                   600 KP, H K                    600                  ~2!356~MCM                             25                       250                     350 700 800                 3-300 MCM                             25                       450                     600 900-1200               4-350 MCM                             25                       450                     600 HP                         600                     2-350 MCM                             35                       250                     350 800-1200               4-350 MCM                             35                       350                     600 1400_-1_600             5-400 MCM                           100                       400                     750 HH                       1800 2000               5-600 MCM                           170                       450                     750 HS                       2560                     F4ddIMCM                             25                       600                     750 3000                     9-400 MCM                             25                       000                     750 4000                   12-400 MCM                             25                       600                   750 CC                            T 20 15                    1- #12                                 5                       40                   100 30                     1- *10                                 5                       _40                   100 CE                           15Tf0                 1-#12                                 7                         35                   100 3040                   1- s8                                 7                         35                   100 50 100                 1-#1                                   9                       100                   200 CJ                         150-225                 1- #4/0                               45                       200                   300 250 400                 2- m3/0                               35                       200                   300 CM                         400 450                 2- #4/0                               30                       280                   300 500 000                 2-350 MCM                             30                       280                   350
EQ 15-20 1- #12 4
  )                                           700E00                 3-300 MCM
45 100 1 Pole 30-50 1-e6 4
                                                                              ~
45 100 TO If20 1-si2 4
70                       400                   600
35 100 2,3 Pole 30-40 1- #8 4
                  'CP                         600                     2ZMOMCM                               35                       250                   350
35 100 50-100 1-s1 5
        !                                    800 1200                 4-350 MCM                             75                       430                   600 1400-1600                 5-400 MCM                           230                       550                   750 CR                       1800-2000                 5-600 MCM                           260                       550                   750 EVALUATION OF FIELD TEST RESULTS Minimum Tiipping Times                             Maximum Tripping Times                                 Maximum Tripping Times For Cable The minimum values shown in the                   Under normal conditions, the circuit                     Protection above table should not be considered               breaker will trip in less time than the                 N the test value exceeds the maximum tripping time shown m the above table, significant in field testing unless               maximum values shown in the table.
45 200 125 1 - e 1/0 10 50 200 BOC 15-20 1-812 4
nuisance tripping has been experienced.           Under improper test conditions, the                     but falls below the maximum tripping maximum values may exceed those                          time for cable damage, the circuit These values are provided as a guideline breaker is providing an acceptable level only, if minimum tripping times are               given in the table.
35 100 30 1-s10 4
of protection. Coordination with other lower than those shown in the table, the protective devices shoufd be considered O           breaker shoul be retested after being de-energized and cooled for the required time.
35 100 OJ 12f225 1-e470 25 155 300 E
before replacing a circuit breaker which trips beyond the time-current curve.
1020 1- #12 8
50 100 3040 1- #8 8
50 100 50-100 1-et 0
50 200 EH,EF,HE 15 20 1-s12 to 50 100 HE 3040 1-88 10 50 100 50-100 1-at 9
75 200 EH 110 150 1-s t /0 25 180 300 70 iDO 1-e1 3d 13d 200 FJ 125-225 1 - #4 /0 35 170 300 JD,JJ 7dTO0 1-#1 50 130 200
~
JL,HJ 124225 1-s4/0 40 160 300 250 400 2-#3/0 30 200 300 LL, H L 450 2- #4/0 25 250 300 500 000 2-350 MCM 25 250 350 KM 25d~450 2-a4to 70 250 300 500 600 2-350 MCM 45 250 350 700 400 3-300 MCM 55 280 600 HM 400450 2-s4/0 45 250 300 500-600 2-350 MCM 45 250 350 700E00 3-300 MCM 45 280 600
~ !356~MCM 25 250 350 2
KP, H K 600 700 800 3-300 MCM 25 450 600 900-1200 4-350 MCM 25 450 600 HP 600 2-350 MCM 35 250 350 800-1200 4-350 MCM 35 350 600 1400_-1_600 5-400 MCM 100 400 750 HH 1800 2000 5-600 MCM 170 450 750 HS 2560 F4ddIMCM 25 600 750 3000 9-400 MCM 25 000 750 4000 12-400 MCM 25 600 750 T
15 20 1- #12 5
40 100 CC 30 1- *10 5
_40 100 CE 15Tf0 1-#12 7
35 100 3040 1-s8 7
35 100 50 100 1-#1 9
100 200 CJ 150-225 1- #4/0 45 200 300 250 400 2-m3/0 35 200 300 CM 400 450 2- #4/0 30 280 300 500 000 2-350 MCM 30 280 350
)
700E00 3-300 MCM 70 400 600
'CP 600 2ZMOMCM 35 250 350
~
800 1200 4-350 MCM 75 430 600 1400-1600 5-400 MCM 230 550 750 CR 1800-2000 5-600 MCM 260 550 750 EVALUATION OF FIELD TEST RESULTS Minimum Tiipping Times Maximum Tripping Times Maximum Tripping Times For Cable The minimum values shown in the Under normal conditions, the circuit Protection N the test value exceeds the maximum above table should not be considered breaker will trip in less time than the tripping time shown m the above table, significant in field testing unless maximum values shown in the table.
but falls below the maximum tripping nuisance tripping has been experienced.
Under improper test conditions, the time for cable damage, the circuit These values are provided as a guideline maximum values may exceed those breaker is providing an acceptable level only, if minimum tripping times are given in the table.
of protection. Coordination with other lower than those shown in the table, the protective devices shoufd be considered O
breaker shoul be retested after being before replacing a circuit breaker which de-energized and cooled for the required trips beyond the time-current curve.
time.
C A U TION Molded Case Circuit Breakers must always be completely de-energized, disconnectai and isolated before any tests or maintenance are attempted.
C A U TION Molded Case Circuit Breakers must always be completely de-energized, disconnectai and isolated before any tests or maintenance are attempted.
5
5


o =
INSTANTANEOUS MAGNETIC OVERCUR R ENT TRIP TEST
INSTANTANEOUS MAGNETIC OVERCUR R ENT TRIP TEST breaker trips. The recommended                     Although this method is a more These tIsts are intended to simulate short. circuit conditions, but it must be           time for increasing the current is                 accurate procedure, it is subject to an between 2 and 5 seconds. If the                   error introduced by current of fset.                 i i remembered that in the field it is practictity impossible to impose the               current is increased too slowly,                   Figure #1 depicts the distortion of the                 '
=
5000 amperes (or more) pulse that is               tripping may be due to the time-                   pulse current, commonly called of f set imposed in the laboratory,                         delay element, especially if more                 or asymmetrical.
o These tIsts are intended to simulate breaker trips. The recommended Although this method is a more short. circuit conditions, but it must be time for increasing the current is accurate procedure, it is subject to an i remembered that in the field it is between 2 and 5 seconds. If the error introduced by current of fset.
than one test is run at a high current In routine tests it is more important to                                     ,
i practictity impossible to impose the current is increased too slowly, Figure #1 depicts the distortion of the 5000 amperes (or more) pulse that is tripping may be due to the time-pulse current, commonly called of f set imposed in the laboratory, delay element, especially if more or asymmetrical.
level. If the current is increased too determine that the magnetic trip feature rapidly, an erroneous current reading is operating and will trip the circuit
than one test is run at a high current In routine tests it is more important to level. If the current is increased too determine that the magnetic trip feature rapidly, an erroneous current reading is operating and will trip the circuit may be obtamed because the meter breaker, rather than determmmg the results in an asymmetrical current.
                                    ..                  may be obtamed because the meter breaker, rather than determmmg the                                                                     results in an asymmetrical current.
ndication lags behind the actal extet current value at which the Experience with field test equipment current vabe due to meter damping.
ndication lags behind the actal extet current value at which the                                                                       Experience with field test equipment current vabe due to meter damping.
mzgnetic trip feature operates. To indicates that tu cffset may be as high duplicate Gould I-T-E's published data, The runup method requires skill on as 20 percent. A circuit breaker can be exact d1 termination of trip current the part of the operator in tripped by the offset peak rather than values een be obtained, but the recognizing the relationship between the steady-state current so the etfect of necessary precise control of test actual current and the meter the error is such that the indicated trip conditions will probably prove indication.
mzgnetic trip feature operates. To                                                                     indicates that tu cffset may be as high duplicate Gould I-T-E's published data,             The runup method requires skill on                 as 20 percent. A circuit breaker can be exact d1 termination of trip current               the part of the operator in                       tripped by the offset peak rather than values een be obtained, but the                     recognizing the relationship between               the steady-state current so the etfect of             ,
current may be as much as 20 percent impractical. It must be recognized that CAUTION-If the circuit breaker lower than the peak offset current on circuit breakers in the larger frame does not open within 10 seconds, the which tripped the circuit breaker. In siris the instantaneous magnetic loading circuit must be de-energized factory testing, this error is avoided by cvsrcurrsnt trips have adjustable to protect it from damage.
necessary precise control of test                   actual current and the meter                       the error is such that the indicated trip conditions will probably prove                     indication.                                       current may be as much as 20 percent impractical. It must be recognized that             CAUTION-If the circuit breaker                     lower than the peak offset current on circuit breakers in the larger frame             does not open within 10 seconds, the               which tripped the circuit breaker. In siris the instantaneous magnetic                   loading circuit must be de-energized               factory testing, this error is avoided by cvsrcurrsnt trips have adjustable                   to protect it from damage.                         (1) using synchronous closing of the settings, usually from 6 (Lo) to 10 (Hi)                                                               current control to make contact at a times the continuous current rating.            2. Pulse Af&d-This Mod MI N                           point on the 60-hertz wave so that no more accurate than the runup Since the magnetic trip characteristics                                                                        e mmn c       n, aM G madng method if done properly, but it of tha circuit breaker can be influenced           requires that the test equipment be a n va            n a cabaW by stray magnetic fields, the test setup                                                               imag      abbg caMe ray oschscop equipped with a pointer-stop must be made in such a way that the                                                                       r a graph,c recorder.
(1) using synchronous closing of the settings, usually from 6 (Lo) to 10 (Hi) current control to make contact at a
ammeter or a calibrated image-fields caused by the test equipment               retaining oscilloscope. It involves the itself, by steel enclosures, or by the             following steps:
: 2. Pulse Af&d-This Mod MI N times the continuous current rating.
conductors to the circuit breaker, do                                                                   Interpretat. ion of Test Results                     '
point on the 60-hertz wave so that no more accurate than the runup e mmn c n, aM G madng Since the magnetic trip characteristics method if done properly, but it a n va n a cabaW of tha circuit breaker can be influenced requires that the test equipment be imag abbg caMe ray oschscop by stray magnetic fields, the test setup equipped with a pointer-stop r a graph,c recorder.
: a. After the circuit breaker is not af fect the test results. Results can also be greatly influenced by the wave                 connected, current is applied in                 The principal purpose of field testing is shape of the ctarrent and, therefore, it is           short pulses of 5 to 10 cycles.                 to permit the user to safely determine desirable to have sinusoidal output from           b. The current is increased on each                 whether the circuit breaker is furnishing the loading equipment.                                 succeeding pulse until the circuit               the protection for which it is intendd, breaker trips.                                   or whether it should be replaced. Field Testing of the instantaneous magnetic                                                                  testing is not intended to determine trip feature may be by the ,,runup,,               c. The current is then reduced to                   whether the circuit breaker exactly method or the pulse method:                           Just below that point and, by                   meets the published curves. A circuit
must be made in such a way that the ammeter or a calibrated image-fields caused by the test equipment retaining oscilloscope. It involves the itself, by steel enclosures, or by the following steps:
: 1. Ranup Afethod-in this method, one                 repeated pulses, the pointer stop               breaker that trips in less than the pola of the circuit breaker to be                 on the ammeter is adjusted until                 minimum time shown by the time the pointer movement is barely                   current characteristic curves may tzsted is connected to the test tquipment, and the current control is             perceptible when the current is                 furnish more protection than is set at a point where approximately               pulsed.                                         expected. System coordination of 70 percent of the expected tripping           d. The current can then be raised                   tripping times should be considered currant will flow when energized.                 slightly and rechecked at the                   before replacing a circuit breaker that The power is then turned on and the               current at which the circuit                     trips at a value outside of the current increased until thc circuit               breaker trips.                                   time-current curve.
conductors to the circuit breaker, do Interpretat. ion of Test Results
: a. After the circuit breaker is not af fect the test results. Results can also be greatly influenced by the wave connected, current is applied in The principal purpose of field testing is shape of the ctarrent and, therefore, it is short pulses of 5 to 10 cycles.
to permit the user to safely determine desirable to have sinusoidal output from
: b. The current is increased on each whether the circuit breaker is furnishing the loading equipment.
succeeding pulse until the circuit the protection for which it is intendd, Testing of the instantaneous magnetic breaker trips.
or whether it should be replaced. Field testing is not intended to determine trip feature may be by the,,runup,,
: c. The current is then reduced to whether the circuit breaker exactly method or the pulse method:
Just below that point and, by meets the published curves. A circuit
: 1. Ranup Afethod-in this method, one repeated pulses, the pointer stop breaker that trips in less than the pola of the circuit breaker to be on the ammeter is adjusted until minimum time shown by the time tzsted is connected to the test the pointer movement is barely current characteristic curves may tquipment, and the current control is perceptible when the current is furnish more protection than is set at a point where approximately pulsed.
expected. System coordination of 70 percent of the expected tripping
: d. The current can then be raised tripping times should be considered currant will flow when energized.
slightly and rechecked at the before replacing a circuit breaker that The power is then turned on and the current at which the circuit trips at a value outside of the current increased until thc circuit breaker trips.
time-current curve.
1 O
1 O
CA U TION Afolded Case Circuit Breakers must always be completely de+nergized.
CA U TION Afolded Case Circuit Breakers must always be completely de+nergized.
Line 133: Line 219:
6 i
6 i


RECOMMENDED TOROUE VALUES
RECOMMENDED TOROUE VALUES e
          '                                                                                                            e Breaker Frame                                                                             Lug Cat. No. or Wire Range               Cable Set Screws               Lug Mounting Screws OT                                                                                         #14 to #10 AWG. CU (15-30A)               20 in. Ibs.                       -
Breaker Frame Lug Cat. No. or Wire Range Cable Set Screws Lug Mounting Screws OT
                                                                                                        #12 to #8 AWG. AL (15-30A)                 20 in. Ibs.                       -
#14 to #10 AWG. CU (15-30A) 20 in. Ibs.
p                                                                                                   #8 AWG. CU; #6 AWG. AL (40A)               35 in. Ibs.                       -
#12 to #8 AWG. AL (15-30A) 20 in. Ibs.
g       Load Lugs                                                                                 #14 to s8 AWG. CU (15-30A)                 20 in. Ibs.
p
                                                                                                                                                    ~
#8 AWG. CU; #6 AWG. AL (40A) 35 in. Ibs.
OP, HQ                                                                                     #12 to #8 AWG. AL (15-30W                 20 in. Ibs.                       -
g Load Lugs
l 30, H8                                                                                   s8 to #1 AWG. CU/AL (46'70A)               50 in. tbs.                       -
#14 to s8 AWG. CU (15-30A) 20 in. Ibs.
s4 to 1/0 AWG. CU/AL (90-125A) 50 in. Ibs.                       -
OP, HQ
Line Luq BO, HB                                                                           TCid1                     ~
#12 to #8 AWG. AL (15-30W 20 in. Ibs.
50 in. Ibs.                       -
~
Load Lug                                                                                   #14 to #10 AWG. CU (15TOA)                 70 in. Ibs.                       -
l 0, H8 s8 to #1 AWG. CU/AL (46'70A) 50 in. tbs.
CC                                                                                         #12 to #8%WG AL (153uA)                   20 in. ibs.                       -
3 s4 to 1/0 AWG. CU/AL (90-125A) 50 in. Ibs.
Line Lug                                                                                   #14 to #10 AWG. (15-30A)                   20 in. Ibs.                   25 en. Ibs.         _
Line Luq BO, HB TCid1 50 in. Ibs.
CC                                                                                         #12 to #8 AWG (15 30A)                     20 in. Ibs.                   25 in. Ibs.
Load Lug
OJ                                                                                         T E1 E 00                                 250 in. Ibs.                   96 in. Ibs.
#14 to #10 AWG. CU (15TOA) 70 in. Ibs.
TC1-Q250                                 250 in. Ibs.                   96 in. Ibs.
~
E, EH, EF, HE, CE                                                                         TA1-E010 (15-25A)                         20 in. Ibs.
CC
TA1-E 100 (30100Al                         50 in. Ibs.                   55 in. Ibs.
#12 to #8%WG AL (153uA) 20 in. ibs.
150 Amp EH,150 Arnp EF                                                                   TA 1-E 150                               100 in. Ibs.                   50 in. Ibs.
Line Lug
TC1.E150                                 100 in. Ibs.                   50 in. tbs.
#14 to #10 AWG. (15-30A) 20 in. Ibs.
f~S     FJ                                                                                         T A1.F 300                               250 in. Ibs.                   96 in. Ibs.
25 en. Ibs.
TC1.F 250                                 250 in. Ibs.                   96 in. Ibs.
CC
JJ, JL, HJ, CJ                                                                             T A 1-J300                               250 in. Ibs.                   210 in. Ibs.
#12 to #8 AWG (15 30A) 20 in. Ibs.
TA1.J500                                 300 in. Ibs.                   210 in. Ibs.
25 in. Ibs.
JP                                                                                         TA21250                                   250 in. Ibs.                   96 in. Ibs.
OJ T E1 E 00 250 in. Ibs.
LL, HL                                                                                     TXfl500                                   300 in. Ibs.                   240 in. Ibs.
96 in. Ibs.
RM                                                                                         TA2.K5d0                                 300 in. abs.                   96 in. Ibs.
TC1-Q250 250 in. Ibs.
TA3 K350                                 250 in. Ibs.                   96 in. Ibs.
96 in. Ibs.
TA3-K400                                 250 in. Ibs.                   96 in. Ibs.
E, EH, EF, HE, CE TA1-E010 (15-25A) 20 in. Ibs.
TC2-K500                                 300 in. Ibs.                   96 in. Ibs.
TA1-E 100 (30100Al 50 in. Ibs.
TC3-K 350                                 250 in. Ibs.                   96 in. Ibs.
55 in. Ibs.
HM, CM                                                                                     TA2-M350                                 250 in. Ibs.                   240 in. Ibs.
150 Amp EH,150 Arnp EF TA 1-E 150 100 in. Ibs.
TA3-M400                                 250 in. Ibs.                   240 in. Ibs.
50 in. Ibs.
TA4.M350                                 250 in. Ibs.                   240 in. Ibs.
TC1.E150 100 in. Ibs.
TA4-M500                                 300 in. Ibs.                   240 in. Ibs.
50 in. tbs.
TC2-M400                                 250 in. Ibs.                   240 in. Ibs.
f~S FJ T A1.F 300 250 in. Ibs.
TC2-M500                                 300 in. Ibs.                   240 in. Ibs.
96 in. Ibs.
TC3-M400                                 250 in. Ibs.                   240 in. Ibs.
TC1.F 250 250 in. Ibs.
[,                                                                                                 TC3-M500                                 300 in. Ibs.                   240 in. Ibs.
96 in. Ibs.
KP, H K                                                                                   TA4P500                                   250 in. Ibs.                   240 in. Ibs HP, H R, CP, CR                                                                             TAS-P600                                 300 in. Ibs.                   300 in. Ibs.
JJ, JL, HJ, CJ T A 1-J300 250 in. Ibs.
210 in. Ibs.
TA1.J500 300 in. Ibs.
210 in. Ibs.
JP TA21250 250 in. Ibs.
96 in. Ibs.
LL, HL TXfl500 300 in. Ibs.
240 in. Ibs.
RM TA2.K5d0 300 in. abs.
96 in. Ibs.
TA3 K350 250 in. Ibs.
96 in. Ibs.
TA3-K400 250 in. Ibs.
96 in. Ibs.
TC2-K500 300 in. Ibs.
96 in. Ibs.
TC3-K 350 250 in. Ibs.
96 in. Ibs.
HM, CM TA2-M350 250 in. Ibs.
240 in. Ibs.
TA3-M400 250 in. Ibs.
240 in. Ibs.
TA4.M350 250 in. Ibs.
240 in. Ibs.
TA4-M500 300 in. Ibs.
240 in. Ibs.
TC2-M400 250 in. Ibs.
240 in. Ibs.
TC2-M500 300 in. Ibs.
240 in. Ibs.
TC3-M400 250 in. Ibs.
240 in. Ibs.
[,
TC3-M500 300 in. Ibs.
240 in. Ibs.
KP, H K TA4P500 250 in. Ibs.
240 in. Ibs HP, H R, CP, CR TAS-P600 300 in. Ibs.
300 in. Ibs.
Values Shown Are t5 in. Ibs.
Values Shown Are t5 in. Ibs.
O O
O O
Line 183: Line 306:
l O
l O
O 1
O 1
Gould Inc Circust Protection Division Spr.ng House. PA 19477 Tetephone 215-628-7400 E
Gould Inc Circust Protection Division Spr.ng House. PA 19477 E
;          Dunetin 2 0.1 - 2 A 7 SHG377 l
Tetephone 215-628-7400 Du etin 2 0.1 - 2 A 7 SHG377 n
_- _ .    -  _ _}}
l
_ _}}

Latest revision as of 10:52, 16 December 2024

Gould I-T-E Molded Case Circuit Breakers Testing & Maint Procedures
ML20069F917
Person / Time
Site: Arkansas Nuclear Entergy icon.png
Issue date: 09/22/1982
From:
GOULD, INC.
To:
Shared Package
ML20069F872 List:
References
2.0.1-2A, NUDOCS 8209280282
Download: ML20069F917 (8)


Text

.

~ _.. _... _

Bull 3 tin 2.0.1 - 2A

.!~

Gould I-T-E Molded Case

O Circuit Breakers Testing and Maintenance Procedures i

1 O

1 i

l i

O j

O

.o Y'

- - --.4!

l

=

~

e c

^

O ll1 &

M.

'. I,,

iuda i.

I liA E-w

~ " ~ ~ " ~ '

~

~~

O

^~'

"} GOUL s B209280282 820922 PDR ADOCK 05000368 P

PDR

.l.T-E MOLDED CASE CIRCulT BREAKERS TESTING AND MAINTENANCE PROCEDURES e

YOU'LL FIND MANY REASONS dreamed were possible with any tampering, and that the breaker may be FOR CHOOSING I-T.E protective device.

expected to perform according to the MOLDED CASE CIRCUlT BREAKERS The utmost in reliability, based on UL specifications. A broken seal voids I-T E's quality construction-the UL label and jeopardizes the Her2 Ars Just a Few:

quick make, quick-break warranty.

peration, silver alloy contactr, high Maximum protection for equipment and c ntact pressure, extra-wide pole 1 T E molded case c,rcu,t breakers have i

i personntl. Minimum maintenance and spacing, individually calibrated poles on an excellent record of reliability which downtime.

all breakers. These and many other to a great exte11t is due to the enclosed Lower total cost over the many years of design and construction features are design which minimizes tampering and service you'll get from I T E breakers.

checked constantly to meet 1 T-E's exposure to dirt, dust, and other Because they're resettable, take less quality requirements and those of contaminants. This reliability also space, consume less power and prever.t Underwriters' Laboratories, Inc. All of depends on proper installation following single phasing as compared to fusible these measures of dependeable careful application, particularly with devices.

protection are the natural results of reference to the maximum available I-T E's many years of technical short circuit current of the circuit to A selection to meet any need you may leadership in circuit breakers, which the circuit breaker is applied.

havr. From a 4000-ampere systems For testing procedures on GFI and bre:ker to a 15 ampere ground fault Reliability after application also Systems Breakers, consult appropriate depends upon environment and inttrrupter, an instantaneous trip IS-breaker for motor protection, a special maintenance. All devices with moving fire pump breaker, or-the most 1-T E molded case circuit breakers parts require periodic check ups. A demanding of all-breakers to meet U.S.

undergo extensive production testing circuit breaker is no exception. It is not Navy requirements.

and calibration at the factory. These unusual for a circuit breaker to be in tests are based on Underwriters

  • service for extended periods and never Capability to do virtually anything you Laboratories, Inc. " Safety Standard for be called upon to carry out its overload want, anywhere you want. With over Branch Circuit and Service Circuit or short-circuit functions. Therefore,it 800 brtakers to choose from, you also Breakers" No. 489. Circuit breakers should be exercised and tested at times have a complete variety of accessories, carrying the UL label have factory to assure proper funct;oning. The auxiliaries, enclosures and mounting sealed calibrated elements; an unbroken procedures outlined in this bulletin are arrangements. You may find you can do seal assures that the mechanism has not accepted methods of testing to verify things with an I-T E breaker you never been subjected to alteration or circuit breaker performance in the field.

O l

l l

l l

i l

O l

l l

C A U TION

\\

Molded Case Circuit Breakers must always be completely de-energized, disconnected and isolated before any tests or maintenance are attempted.

+

s PERIODIC FIELD TESTING AND MAINTENANCE PROCEDURES r

Qualified, authorized personnel can line and load terminals of each pole of insulation. The most common method perform routine field testing and the unit with the circuit breaker employs a "megger type instrument.

O' maintenance to assure the circuit contacts closed.

Most of such devices in use have outputs breaker is providing proper protection, l-T.E will provide allowable voltage f 500 voltes or less, whereas, much These procedures are based on accepted drop data on request for circuit breakers more reliability will be derived if 1000 practices. Note the caution below under test. It is recommended that this von insuuments are used because they before beginning any tests.

test be made with a de current are more likely to pick up tracked approximating 50 percent of the circuit inw!ation wrfaces. Resinanm values breaker continuous current rating; below one megohm are considered

1) Connections Test however, currents for the larger circuit unsafe and should be investigated.

The connections to the circuit breaker breakers may be as low as 50 amperes if An insulation resistance test should be terminals should be inspected to the millivoltmeter is of suf fic,ent made:

i sensitivity he mWivoh drop across determine proper conductor ampacity each pole ;s measured and recorded for

-Between line and load terminals of i

and that proper electrical joints exist. If individual poles with the circuit c mpa s n aga s e data mWed overheating of connections is evident by breaker contacts open.

Y "Y

discoloration or arcing, the surfaces

-Between adjacent poles and from be practical to compare values with must be cleaned before testing and poles to metallic supporting structure those of poles of other circuit breakers reinstallation. As stated before,it is with the circuit breaker contacts f sin at size and nyk.

essential that electrica! connections be closed. The latter may be done with made properly to prevent overheating.

the circuit breaker in place af ter the Refer to Table #2 on page 7 for

4) Overload Tripping Test line and load conductors are recommended torque values. Aluminum This test provides assurance the removed, or with the circuit breaker lug connectors are plated and should overload component of the circuit bolted to a metallic base which not be cleaned with abrasives.

breaker is operating. This is NOT a simulates the in-service mounting.

verification test of 1-T.E's published test data. To perform the test, apply 300%

7) Summary
2) Mechanical Operation Check of the breaker rating. The breaker it is again emphasized that common Manual mechanical exercising of a should open automatically. This proves maintenance practices for electrical circuit breaker is a recommended the overload component is functioning.

equipment should be adhered to in field procedure. A few operations of the To determine actual tripping testing both new and installed molded handle performed periodically, together characteristics, refer to page 5.

case circuit breakers, and usually the with a careful visual inspection of standard routine operating checks listed terminal connections, for tightness,

5) Instantaneous Magnetic Tripping above will be sufficient to assure proper physical damage or evidence of functionmg of the circuit breaker. It is overheating are considered good This test provides assurance that the further recommended that since molded practice. This will keep mechanical instantaneous magnetic component of case circuit breakers have factory sealed linkages free, while the wiping action by the circuit breaker is functioning. This calibrated elements, that THIS SEAL contacts tends to avoid resistance test does NOT determine exact tripping SHOULD NOT BE BROKEN AND THE build-up and thereby minimizes heating.

values. To perform the test, use either CIRCUlT BREAKER ITSELF Circuit breakers applied and specified the Runup or Pulse method described SHOULD NOT BE TAMPERED WITH.

for switching duty do not need regular on page 6.

Adjustment or repair c' molded case exercising.

circuit breakers in *. eld is not

6) Insulation Resistance recommended. The orcuit breaker An insulation resistance test is used to should be replaced, or its parts should
3) Individual Pole Resistance Test determine the quality of insulation be replaced or repaired at the f actory.

(Millivolt Drop) between adjacent poles of a circuit After performing any of the above tests, The detrimental effect of operating a breaker and from its poles to ground.

be certain to account for all hardware circuit breaker in a manner for which it The resistance test is made with higher and tools and make certain all test was not intended can be detected by de voltage than the rated voltage, to instruments are disconnected before making a millivolt drop test across the determine the actual resistance of the re-energizing the circuit breaker.

O

%.)

C A U TION Molded Case Circruit Breakers must always be completely de-energized, disconnected and isolated before any tests or main tenance are attempted.

3

VERIFICATION TEST PROCEDURES Underwriters Laboratories, Inc.

screw and cable set screw should be conductor in order to reduce heating

StandIrd for Molded Case Circuit properly secured.

and voltage drop.

Breakers and Circuit-Breaker

4. Current must be held constant and Other frequently encountered problems Enclosures," UL 489, is the basis for accurately over the erstire test time.

are the inability to uit the required performance standards for all molded The heat generated in the trip unit of time for the circuit b -takers to cont to case circuit breakers bearing the UL a thermal trip circuit breaker is room tamperature and a room libel. Verification of molded case proportional to the sciuare of the temperature other than 25 C (77*F). If circuit breakers to UL test standards is current. A small variation of current tests are made while thermal trip circuit intended to permit the checking of can cause a large variation in total breakers are still warm, the trip time circuit breakers in accordance with heat generated.

will be shorter than if they were allowed published data under carefully Example-if a 10 ampere current (la )

to cool completely. When testing controlled conditions. The published is allowed to change only 10 percent ind.vidual poles, successive tests can be data are based upon the UL standard to 11 amperes (Is), the heat run on adjacent poles,with no and,if verification of these data or generated will be:

cool down periods between tests without application curves is desired from tests, (1 )*

11*

121 resulting in more than a 10 percent error.

2 g

9 the tests should be performed under (1, )2 10 100 The recommended method of 3

carefully controlled conditions as This shows that an increase of 10 determining whether a circuit breaker has been calibrated in accordance with specifically instructed by Gould 1 T-E.

percent in current will cause a 21 Gould I-T E's limits is to meet all of the if circuit breaker performance '

percent variation in heat and a UL specified conditions outlined in this charactzristics are to be tested in the corresponding error in trip time.

field, there are many variables that must NOTE-To get field test results publication.

be recognized and taken into account.

comparable to those obtained wi4en Molded Case Circuit Breaker Trip Some simplifications are necessary; circuit breakers are factory tested to UL Characteristics however, even simplified testing must Standards, ammeters must be carefully Gould I T-E molded case circuit recognize variations that can and do checked to a precise standard. Most breakers employ the inverse time exist between one test setup and panelinstruments are accurate to a 12 element principle as the design basis for another. These variations can account percent of fu// sca/e reading. This means protecting against overloads without for differences in test results, and it that a 500-ampere meter may have an nuisance tripping. With the inverse time must be recognized that a circuit error of i 10 amperes (+ 0.02 X 500 =

element concept, the time between the breaker may furnish adequate 10 amperes). This same 10-ampere error occurrence of an overload and the protection, but appear defective because can exist during measurements at all moment of tripping varies inversely with of the test procedure used.

points on the scale. For example, the the magnitude of the overload current.

Underwriters Laboratories Standards error at 100 amperes or 1/5 scale may Thus, optimum overload protection is Calibration standards and the trip-time still be 10 amperes,i.e.,10 percent.

achieved without nuisance tripping from values for circuit breakers tested in From the previous example, a momentary higher overload currents.

accordance with UL 489 are based on 10-percent change in current can cause a The speed of the breaker's response the following conditions:

21 percent change in heat in the circuit dependson the magnitude of theoverload.

1. Circuit breakers are tested in ope,n a.

breaker under test and a corresponding The basic Gould 1-T E thermal magnetic ir at an ambient temperature of 25 C change in trip time. In order to molded case circuit breaker combines (77 F).

minimize this effect, meter scales should the inverse time element or thermal

[,,t be chosen so that readings are taken in action design for low level overloads, a

ea the upper half of the scale.

and instantaneous magnetic action for j

before tests are started, circuit breakers must have been in a 25'C i Testing Limitations short circuits.

3 C (77 F i 5'F) ambient long in field testing it will not be practical to Thermal Overcurrent Trip Test meet all of the test conditions specified When testing molded case circuit enough for all parts to have reached the same temperature (at least 2 by UL Standards. In many cases, NONE breakers in the field,it is recommended hours for circuit breakers rated 100 f the UL standard factory test that the thermal overcurrent tests be amperes and below, and 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> for conditions may be fully met.

performed on individual poles at 300%

those rated above 100 amperes).

One of the most frequently encountered of rated current. The reaction of the

3. Calibration tests are made with problems is the fact that a circuit circuit breaker to this overload will be conductors of the size specified in breaker may have to be tested in the indicative of its reaction throughout its the UL Standard connected to line enclosure in which it is mounted, rather entire overcurrent tripping range. This and load terminals. If, in field than in open air as specified by UL.

load has been chosen as the test point testing, the circuit breaker is Consequently, the difference in ambient because it is relatively easy to generate connected with wire or bus other temperature will result in trippin9 the required current in the field and the than that specified, results will vary characteristics different from those wattage per pole from line to load is from published riata. The wire should which would be experienced in open air.

large enough so that the dissipation of be connected with the lug Temporary test connections call for heat in the adjacent pole is minor and specifically intended for that extra care with respect to the tightness does not affect the test results breaker, and both the lug mounting of the connections and the size of the appreciably.

C A U TION Molded Case Circuit Breakers must always be completely de-energized, disconnected and isolated before any tests or maintenance are attempted.

9 VERIFICATION TEST RESULTS Test values are based on 300% o' breaker rating on ind'ividual poles at 25*C (77'F) using four feet of copper wire or cable as indicated.

Tripping Time In Seconds O

Bresher Ampere Wire Sire Man. For Frame Rating Per Pole Mmimum Maximum Cable Prot.

EQ 15-20 1- #12 4

45 100 1 Pole 30-50 1-e6 4

45 100 TO If20 1-si2 4

35 100 2,3 Pole 30-40 1- #8 4

35 100 50-100 1-s1 5

45 200 125 1 - e 1/0 10 50 200 BOC 15-20 1-812 4

35 100 30 1-s10 4

35 100 OJ 12f225 1-e470 25 155 300 E

1020 1- #12 8

50 100 3040 1- #8 8

50 100 50-100 1-et 0

50 200 EH,EF,HE 15 20 1-s12 to 50 100 HE 3040 1-88 10 50 100 50-100 1-at 9

75 200 EH 110 150 1-s t /0 25 180 300 70 iDO 1-e1 3d 13d 200 FJ 125-225 1 - #4 /0 35 170 300 JD,JJ 7dTO0 1-#1 50 130 200

~

JL,HJ 124225 1-s4/0 40 160 300 250 400 2-#3/0 30 200 300 LL, H L 450 2- #4/0 25 250 300 500 000 2-350 MCM 25 250 350 KM 25d~450 2-a4to 70 250 300 500 600 2-350 MCM 45 250 350 700 400 3-300 MCM 55 280 600 HM 400450 2-s4/0 45 250 300 500-600 2-350 MCM 45 250 350 700E00 3-300 MCM 45 280 600

~ !356~MCM 25 250 350 2

KP, H K 600 700 800 3-300 MCM 25 450 600 900-1200 4-350 MCM 25 450 600 HP 600 2-350 MCM 35 250 350 800-1200 4-350 MCM 35 350 600 1400_-1_600 5-400 MCM 100 400 750 HH 1800 2000 5-600 MCM 170 450 750 HS 2560 F4ddIMCM 25 600 750 3000 9-400 MCM 25 000 750 4000 12-400 MCM 25 600 750 T

15 20 1- #12 5

40 100 CC 30 1- *10 5

_40 100 CE 15Tf0 1-#12 7

35 100 3040 1-s8 7

35 100 50 100 1-#1 9

100 200 CJ 150-225 1- #4/0 45 200 300 250 400 2-m3/0 35 200 300 CM 400 450 2- #4/0 30 280 300 500 000 2-350 MCM 30 280 350

)

700E00 3-300 MCM 70 400 600

'CP 600 2ZMOMCM 35 250 350

~

800 1200 4-350 MCM 75 430 600 1400-1600 5-400 MCM 230 550 750 CR 1800-2000 5-600 MCM 260 550 750 EVALUATION OF FIELD TEST RESULTS Minimum Tiipping Times Maximum Tripping Times Maximum Tripping Times For Cable The minimum values shown in the Under normal conditions, the circuit Protection N the test value exceeds the maximum above table should not be considered breaker will trip in less time than the tripping time shown m the above table, significant in field testing unless maximum values shown in the table.

but falls below the maximum tripping nuisance tripping has been experienced.

Under improper test conditions, the time for cable damage, the circuit These values are provided as a guideline maximum values may exceed those breaker is providing an acceptable level only, if minimum tripping times are given in the table.

of protection. Coordination with other lower than those shown in the table, the protective devices shoufd be considered O

breaker shoul be retested after being before replacing a circuit breaker which de-energized and cooled for the required trips beyond the time-current curve.

time.

C A U TION Molded Case Circuit Breakers must always be completely de-energized, disconnectai and isolated before any tests or maintenance are attempted.

5

INSTANTANEOUS MAGNETIC OVERCUR R ENT TRIP TEST

=

o These tIsts are intended to simulate breaker trips. The recommended Although this method is a more short. circuit conditions, but it must be time for increasing the current is accurate procedure, it is subject to an i remembered that in the field it is between 2 and 5 seconds. If the error introduced by current of fset.

i practictity impossible to impose the current is increased too slowly, Figure #1 depicts the distortion of the 5000 amperes (or more) pulse that is tripping may be due to the time-pulse current, commonly called of f set imposed in the laboratory, delay element, especially if more or asymmetrical.

than one test is run at a high current In routine tests it is more important to level. If the current is increased too determine that the magnetic trip feature rapidly, an erroneous current reading is operating and will trip the circuit may be obtamed because the meter breaker, rather than determmmg the results in an asymmetrical current.

ndication lags behind the actal extet current value at which the Experience with field test equipment current vabe due to meter damping.

mzgnetic trip feature operates. To indicates that tu cffset may be as high duplicate Gould I-T-E's published data, The runup method requires skill on as 20 percent. A circuit breaker can be exact d1 termination of trip current the part of the operator in tripped by the offset peak rather than values een be obtained, but the recognizing the relationship between the steady-state current so the etfect of necessary precise control of test actual current and the meter the error is such that the indicated trip conditions will probably prove indication.

current may be as much as 20 percent impractical. It must be recognized that CAUTION-If the circuit breaker lower than the peak offset current on circuit breakers in the larger frame does not open within 10 seconds, the which tripped the circuit breaker. In siris the instantaneous magnetic loading circuit must be de-energized factory testing, this error is avoided by cvsrcurrsnt trips have adjustable to protect it from damage.

(1) using synchronous closing of the settings, usually from 6 (Lo) to 10 (Hi) current control to make contact at a

2. Pulse Af&d-This Mod MI N times the continuous current rating.

point on the 60-hertz wave so that no more accurate than the runup e mmn c n, aM G madng Since the magnetic trip characteristics method if done properly, but it a n va n a cabaW of tha circuit breaker can be influenced requires that the test equipment be imag abbg caMe ray oschscop by stray magnetic fields, the test setup equipped with a pointer-stop r a graph,c recorder.

must be made in such a way that the ammeter or a calibrated image-fields caused by the test equipment retaining oscilloscope. It involves the itself, by steel enclosures, or by the following steps:

conductors to the circuit breaker, do Interpretat. ion of Test Results

a. After the circuit breaker is not af fect the test results. Results can also be greatly influenced by the wave connected, current is applied in The principal purpose of field testing is shape of the ctarrent and, therefore, it is short pulses of 5 to 10 cycles.

to permit the user to safely determine desirable to have sinusoidal output from

b. The current is increased on each whether the circuit breaker is furnishing the loading equipment.

succeeding pulse until the circuit the protection for which it is intendd, Testing of the instantaneous magnetic breaker trips.

or whether it should be replaced. Field testing is not intended to determine trip feature may be by the,,runup,,

c. The current is then reduced to whether the circuit breaker exactly method or the pulse method:

Just below that point and, by meets the published curves. A circuit

1. Ranup Afethod-in this method, one repeated pulses, the pointer stop breaker that trips in less than the pola of the circuit breaker to be on the ammeter is adjusted until minimum time shown by the time tzsted is connected to the test the pointer movement is barely current characteristic curves may tquipment, and the current control is perceptible when the current is furnish more protection than is set at a point where approximately pulsed.

expected. System coordination of 70 percent of the expected tripping

d. The current can then be raised tripping times should be considered currant will flow when energized.

slightly and rechecked at the before replacing a circuit breaker that The power is then turned on and the current at which the circuit trips at a value outside of the current increased until thc circuit breaker trips.

time-current curve.

1 O

CA U TION Afolded Case Circuit Breakers must always be completely de+nergized.

disconnected and isola ted before any tests or maintenance are attempted.

6 i

RECOMMENDED TOROUE VALUES e

Breaker Frame Lug Cat. No. or Wire Range Cable Set Screws Lug Mounting Screws OT

  1. 14 to #10 AWG. CU (15-30A) 20 in. Ibs.
  1. 12 to #8 AWG. AL (15-30A) 20 in. Ibs.

p

  1. 8 AWG. CU; #6 AWG. AL (40A) 35 in. Ibs.

g Load Lugs

  1. 14 to s8 AWG. CU (15-30A) 20 in. Ibs.

OP, HQ

  1. 12 to #8 AWG. AL (15-30W 20 in. Ibs.

~

l 0, H8 s8 to #1 AWG. CU/AL (46'70A) 50 in. tbs.

3 s4 to 1/0 AWG. CU/AL (90-125A) 50 in. Ibs.

Line Luq BO, HB TCid1 50 in. Ibs.

Load Lug

  1. 14 to #10 AWG. CU (15TOA) 70 in. Ibs.

~

CC

  1. 12 to #8%WG AL (153uA) 20 in. ibs.

Line Lug

  1. 14 to #10 AWG. (15-30A) 20 in. Ibs.

25 en. Ibs.

CC

  1. 12 to #8 AWG (15 30A) 20 in. Ibs.

25 in. Ibs.

OJ T E1 E 00 250 in. Ibs.

96 in. Ibs.

TC1-Q250 250 in. Ibs.

96 in. Ibs.

E, EH, EF, HE, CE TA1-E010 (15-25A) 20 in. Ibs.

TA1-E 100 (30100Al 50 in. Ibs.

55 in. Ibs.

150 Amp EH,150 Arnp EF TA 1-E 150 100 in. Ibs.

50 in. Ibs.

TC1.E150 100 in. Ibs.

50 in. tbs.

f~S FJ T A1.F 300 250 in. Ibs.

96 in. Ibs.

TC1.F 250 250 in. Ibs.

96 in. Ibs.

JJ, JL, HJ, CJ T A 1-J300 250 in. Ibs.

210 in. Ibs.

TA1.J500 300 in. Ibs.

210 in. Ibs.

JP TA21250 250 in. Ibs.

96 in. Ibs.

LL, HL TXfl500 300 in. Ibs.

240 in. Ibs.

RM TA2.K5d0 300 in. abs.

96 in. Ibs.

TA3 K350 250 in. Ibs.

96 in. Ibs.

TA3-K400 250 in. Ibs.

96 in. Ibs.

TC2-K500 300 in. Ibs.

96 in. Ibs.

TC3-K 350 250 in. Ibs.

96 in. Ibs.

HM, CM TA2-M350 250 in. Ibs.

240 in. Ibs.

TA3-M400 250 in. Ibs.

240 in. Ibs.

TA4.M350 250 in. Ibs.

240 in. Ibs.

TA4-M500 300 in. Ibs.

240 in. Ibs.

TC2-M400 250 in. Ibs.

240 in. Ibs.

TC2-M500 300 in. Ibs.

240 in. Ibs.

TC3-M400 250 in. Ibs.

240 in. Ibs.

[,

TC3-M500 300 in. Ibs.

240 in. Ibs.

KP, H K TA4P500 250 in. Ibs.

240 in. Ibs HP, H R, CP, CR TAS-P600 300 in. Ibs.

300 in. Ibs.

Values Shown Are t5 in. Ibs.

O O

CA U TION Atolded Case Circuit Breakers must always be completely de-energized, disconnected and isolated before any tests or maintenance are attempted.

7

O 0;

l l

l O

O 1

Gould Inc Circust Protection Division Spr.ng House. PA 19477 E

Tetephone 215-628-7400 Du etin 2 0.1 - 2 A 7 SHG377 n

l

_ _