ENS 46807: Difference between revisions
Jump to navigation
Jump to search
StriderTol (talk | contribs) (Created page by program invented by Mark Hawes) |
StriderTol (talk | contribs) (Created page by program invented by StriderTol) |
||
| Line 16: | Line 16: | ||
| event date = 05/02/2011 EDT | | event date = 05/02/2011 EDT | ||
| last update date = 09/28/2011 | | last update date = 09/28/2011 | ||
| title = Notification | | title = Notification of Potential Defect in Solid State Relay | ||
| event text = Identification of the subject component is as follows: SS5 Solid State Relay, Part Number 611130-T13-N. | | event text = Identification of the subject component is as follows: SS5 Solid State Relay, Part Number 611130-T13-N. | ||
The instantaneous trip function of the relay may actuate at 16 times normal current instead of the design value of 24 times normal current. | The instantaneous trip function of the relay may actuate at 16 times normal current instead of the design value of 24 times normal current. | ||
Latest revision as of 21:05, 1 March 2018
| Where | |
|---|---|
| Abb Inc Florence, South Carolina (NRC Region 1) | |
| Organization: | Abb Inc |
| Reporting | |
| 10 CFR 21.21 | |
| Time - Person (Reporting Time:+13.2 h0.55 days <br />0.0786 weeks <br />0.0181 months <br />) | |
| Opened: | Dennis Batovsky 17:12 May 2, 2011 |
| NRC Officer: | Bill Huffman |
| Last Updated: | Sep 28, 2011 |
| 46807 - NRC Website | |