ENS 46807: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by Mark Hawes)
 
(Created page by program invented by StriderTol)
 
Line 16: Line 16:
| event date = 05/02/2011 EDT
| event date = 05/02/2011 EDT
| last update date = 09/28/2011
| last update date = 09/28/2011
| title = Notification Of Potential Defect In Solid State Relay
| title = Notification of Potential Defect in Solid State Relay
| event text = Identification of the subject component is as follows: SS5 Solid State Relay, Part Number 611130-T13-N.
| event text = Identification of the subject component is as follows: SS5 Solid State Relay, Part Number 611130-T13-N.
The instantaneous trip function of the relay may actuate at 16 times normal current instead of the design value of 24 times normal current.
The instantaneous trip function of the relay may actuate at 16 times normal current instead of the design value of 24 times normal current.

Latest revision as of 21:05, 1 March 2018

ENS 46807 +/-
Where
Abb Inc
Florence, South Carolina (NRC Region 1)
Organization: Abb Inc
Reporting
10 CFR 21.21
Time - Person (Reporting Time:+13.2 h0.55 days <br />0.0786 weeks <br />0.0181 months <br />)
Opened: Dennis Batovsky
17:12 May 2, 2011
NRC Officer: Bill Huffman
Last Updated: Sep 28, 2011
46807 - NRC Website