=Text=
{{#Wiki_filter:-
,
        *                  *                                                                                                                                                                                                                                                                                                                                  '
          .                  .
                                                                                    ,
                                                                                                                                                                  APPENDIX A
                                                                                                                                                    NOTICE OF VIOLATION
                                            Baltimore Gas and Electric Company                                                                                                                                          Docket / License: 50-317; DPR-53
                                            Calvert Cliffs Units 1 and 2                                                                                                                                                                                                          50-318; DPR-69
                                          As a result of the inspection conducted on May 6 - June 17,1985, and in accordance
                                          with the NRC Enforcement Policy (10 CFR 2 Appendix C) the following violation was
                                            identified:
                                                            Technical Specification 6.8.la requires that procedures be established, im-
                                                            plemented, and maintained covering the applicable procedures referenced in
                                                            Appendix A to Regulatory Guide 1.33, Revision 2, February 1978. Appendix A
                                                            of Regulatory Guide 1.33, Revision 2, 1978 requires plant procedures for
                                                            changing operating modes from Cold Shutdown to Hot Standby and performing
                                                            surveillance tests.
                                                            Calvert Cliffs Operating Procedure OP-1, Revision 26, " Plant Startup from Cold
                                                            Shutdown" requires (General Precaution I.E. and Initial Condition II.A.4) that                                                                                                                                                                                                                      i
                                                            whenever the shutdown cooling system is in operation, Reactor Coolant System
                                                            (RCS) pressure shall not exceed 270 psia.
                                                            Contrary to the above, at 10:45 a.m. on June 2,1985, Unit 1 shutdown cooling
                                                            flow was lost when RCS pressure was allowed to increase above 284 psia which,
                                                            as designed, caused automatic closure of a shutdown cooling return isolation
                                                            valve.
                                                            Section V of Calvert Cliffs Surveillance Test Procedure STP M-220-2, Revision
                                                            10, "ESFAS (Engineered Safety Features Actuation System) Functional Test",
              '                                            requires removal of each Refueling Water Tank (RWT) level switch channel, one
                                                            at a time, for testing. General Precaution 8 of the STP emphasizes that only
                                                            one channel is to be affected by the test ("be in a test mode") at any one
                                                            time.
                                                            Contrary to the above on May 23, 1985, STP M-220-2 was conducted on Unit 2
                                                            in such a manner that two of four RWT level switch channels were affected
                                                            (tripped) at one time. With one channel under test and in a tripped condi-
                                                            tion, the cover was removed from a second channel's level switch. That action
                                                            caused the second channel to trip and generated a Recirculation Actuation
                                                            Signal (RAS).
                                                            This is a Severity Level IV Violation (Supplement I).
                                            Pursuant to the provisions of 10 CFR2.201, Baltimore Gas and Electric Company is
                                            hereby required to submit to this office within thirty days of the date of this
                                          Notice, a written statement or explanation in reply, including: (1) the corrective
                                            steps which have been taken and the results achieved; (2) corrective steps which
                                          will be taken to avoid further violations; and (3) the date when full compliance
                                          will be achieved. Where good cause is shown, consideration will be given to ex-
                                            tending the response time.
                                                      0507160337 050700
                                                      PDR                  ADOCK 05000317
                                                      G                                                              PDR
                                                                                                                                                ,
u _ _ _ _ _ . _ _ _ _ . _ . _ _ _ _ _ _ _ _ _ . . _ _ _ _ . _ . _ _ _ _ _ _ _ _ . _ _ . _ _ _ _ _ _ _ _ _ _ _ . _ _ . _ _ _ . _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ . _ _ _ _ . _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ . _ _ _ . . _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ . . _ _ _ _ _ _ . _ _ _ _ _ . _ . _ _ _ _ . _ _ _ _ _ _ _ _ _ _ _ . _ _ _ _ _ _ _ . _ _ _ _ _ _ _ _ _ _ . _
}}