05000416/FIN-2018001-03: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
 
(Created page by program invented by StriderTol)
 
(One intermediate revision by the same user not shown)
Line 5: Line 5:
| finding integer = 03
| finding integer = 03
| quarter = 2018Q1
| quarter = 2018Q1
| IR section = HUMAN PERFORMANCE
| IR section = 1R19
| finding type = NCV
| finding type = NCV
| significance =  
| significance = Green
| cornerstone = Mitigating Systems
| cornerstone = Mitigating Systems
| violation of = Technical Specification
| violation of = Technical Specification
| identified by = NRC
| identified by = NRC
| Inspection procedure = IP 1R19
| Inspection procedure = IP 71111.19
| Inspector = 71111.1
| Inspector = M Young, N Day, A Athar, J Kozal
| CCA = QA.4
| CCA =  
| INPO aspect = NO SL
| INPO aspect = QA.4
| description = The inspectors reviewed a self-revealed non-cited violation of Technical Specification 5.4.1.a, Procedures, for the licensees failure to have adequate procedural guidance while performing a standby service water surveillance procedure. Specifically, the licensees procedural guidance was not adequate to prevent the control room air conditioning subsystem B compressor from starting while condenser cooling water was isolated, which caused damage and rendered the subsystem inoperable and unavailable.
| description = The inspectors reviewed a self-revealed non-cited violation of Technical Specification 5.4.1.a, Procedures, for the licensees failure to have adequate procedural guidance while performing a standby service water surveillance procedure. Specifically, the licensees procedural guidance was not adequate to prevent the control room air conditioning subsystem B compressor from starting while condenser cooling water was isolated, which caused damage and rendered the subsystem inoperable and unavailable.
}}
}}

Latest revision as of 17:34, 10 September 2018

03
Site: Grand Gulf Entergy icon.png
Report IR 05000416/2018001 Section 1R19
Date counted Mar 31, 2018 (2018Q1)
Type: NCV: Green
cornerstone Mitigating Systems
Identified by: NRC identified
Inspection Procedure: IP 71111.19
Inspectors (proximate) M Young
N Day
A Athar
J Kozal
Violation of: Technical Specification
INPO aspect QA.4
'