SVP-05-049, Day Post Outage ISI Letter
| ML052080106 | |
| Person / Time | |
|---|---|
| Site: | Quad Cities |
| Issue date: | 07/18/2005 |
| From: | Tulon T Exelon Generation Co |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| FOIA/PA-2010-0209, SVP-05-049 | |
| Download: ML052080106 (96) | |
Text
Exekln.
Exelon Generation Company. LLC wwwexeloncorp.com NucleaT Quad Cities Nuclear Power Station 22710 206'" Avenue North Cordova, IL 61242-9740 1 OCFR50.55a SVP-05-049 July 18, 2005 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C. 20555-0001 Quad Cities Nuclear Power Station Unit 1 Renewed Facility Operating License No. DPR-29 NRC Docket No. 50-254
Subject:
90-Day Post Outage ISI Letter Enclosed is the Quad Cities Nuclear Power Station Unit 1 Post-Outage (90 day) Summary Report for Inservice Inspection examinations and Repair/Replacement activities conducted from the end of the November 2002 refueling outage through the April 2005 refueling outage.
This report is due July 18, 2005, within 90 days after the end of the Unit 1 April 2005 refueling outage. This report documents examinations credited to the third period of the third inspection interval and the first period of the fourth inspection interval.
This report is submitted in accordance with the requirements of ASME Section Xi, Article IWA-6200, "Requirements."
If there are any questions or comments concerning this letter, please refer them to Mr. Wally Beck, Regulatory Assurance Manager, at (309) 227-2800.
Sincerely,
/
Timothy J. u n Site Vice President Quad Cities Nuclear Power Station
Attachment:
Quad Cities Nuclear Power Station - Unit 1 Post Outage (90 day) Summary Report cc:
Regional Administrator - NRC Region IlIl NRC Senior Resident Inspector - Quad Cities Nuclear Power Station
-I
ATTACHMENT Post Outage (90 day) Summary Report SVP-05-049
Quad Cities Nuclear Power Station - Unit 1 Post Outage (90 Day) Summary Report July 18, 2005 Refueling Outage QlR18 Outage Start Date: March 21, 2005 Outage End Date: April 19, 2005 Commercial Service Date: February 18, 1973 P.O. Box 216 Cordova, IL 61242 Exelon Generation Company, L.L.C.
200 Exelon Way Kennett Square, PA 19348 I~
7 -It- 0s-Prepared by:.
Reviewed by:
67 /' 0 Approved by:. 4"A/t 1I.14' 'c'5
Exelon Generation Company, L.L.C.
Quad Cities Nuclear Power Station 200 Exelon Way Unit I Kennett Square, PA 19348 P.O. Box 216 Commercial Service Date February 18, 1973 Cordova, IL 61242 Table of Contents
1.0 INTRODUCTION
3
- 1. 1.
OUTAGE, PERIOD AND INTERVAL START AND END DATES....................................................................... 3 1.2.
EXAMINATION PROGRAM REQUIREMENTS...............................................................................
4 2.0 NIS-1 FORM.......................................................................................................................................................
25 3.0 ABSTRACT OF EXAMINATIONS, CONDITIONS NOTED AND CORRECTIVE MEASURES
... 7 3.1.
SECTION XI EXAMINATIONS
SUMMARY
.7 3.2.
BWRVIP-75/GENERIc LETTER 88-01.
8 3.3.
INVESSEL INSPECTIONS (IVI).
9 Table 3.1-1 Quad Cities Unit I ASME Section XI Outage Scope.10 Table 3.1-lA Quad Cities Unit I ASME Section XI Limited Coverage Scope.14 Table 3.1-2 Quad Cities Unit I Pressure Testing SuIary..
15 Table 3.1-3 Quad Cities Unit I Snubber Functional Tests.16 Table 3.14 Quad Cities Unit I Conditions Noted and Corrective Actions
.17 Table 3.2-1 Quad Cities Unit I BWI'RVIP-75/GL 88-01 Outage Scope.18 4.0 REPAIR / REPLACEMIENT
SUMMARY
19 4.1.
NIS-2 INDEX.1...................................
19 Table 4.1-1...................................
19 4.2.
NIS-2 FORMS...................................
21 2 of 21
Exelon Generation Company, L.L.C.
Quad Cities Nuclear Power Station 200 Exelon Way Unit I Kennett Square, PA 19348 P.O. Box 216 Commercial Service Date February 18, 1973 Cordova, IL 61242 1.0 Introduction 1.1.
Outage, Period and Interval Start and End Dates This Inservice Inspection Summary Report addresses examinations performed between the end of the previous refueling outage November 26, 2002 through the end of the most recent refueling outage. This most recent refueling outage was the 18 1h refueling outage for Quad Cities Nuclear Power Station Unit 1. The outage started March 21, 2005 and was completed April 19, 2005 when the unit returned to service.
This refueling outage was the first outage during the first inspection period of the fourth inspection interval, which began on March 10, 2003. The first inspection period of the fourth inspection interval is scheduled to end on March 9, 2006 and may be extended as much as one (1) year as permitted by IWA-2430(d)(1) "Inspection Intervals".
In addition, this report addresses examinations performed to meet third period, third interval requirements. Specifically, sixteen (16) nozzle exams that were originally scheduled to be completed during the 17 th refueling outage (third interval) were completed during the 18th refueling outage. Exelon requested this scheduler exemption under letter from T. J.Tulon (Exelon Generation Company) to U. S. NRC, "Request for Schedular Exemption for Performance of Reactor Pressure Vessel Nozzle-to-Vessel Weld and Nozzle Inside Radius Section Examinations Required by 10 CFR 50.55a" dated July 10, 2002 and was approved by the Commission per letter dated September 16, 2002 (TAC NO.
MB5585).
Tests, examinations, repairs and/or replacements associated with American Society of Mechanical Engineers (ASME) Code,Section XI were witnessed or otherwise verified by the Authorized Nuclear Inservice Inspectors. Non-ASME Section XI or augmented examinations were not witnessed or otherwise verified by the Authorized Nuclear Inservice Inspectors and are marked "Not Required" or "N/A" on the applicable examination reports.
The Authorized Nuclear Inservice Inspectors are inspectors of the Hartford Steam Boiler Inspection & Insurance Company of Connecticut (HSB-CT). The HSB-CT Regional Office is located at 2443 Warrenville Road, Lisle, Illinois, 60532-9871.
3 of 21
Exelon Generation Company, L.L.C.
Quad Cities Nuclear Power Station 200 Exelon Way Unit I Kennett Square, PA 19348 P.O. Box 216 Commercial Service Date February 18, 1973 Cordova, IL 61242 1.2.
Examination Program Requirements The examination requirements of ASME Boiler and Pressure Vessel Code,Section XI, Division 1, "Rules for Inservice Inspection of Nuclear Power Plant Components", the 1995 Edition, 1996 Addenda (fourth ten year interval) were implemented for Class 1, 2 and 3 components except where written relief has been granted by the NRC. Written relief, in the form of Relief Request M4R-02 approving Risk Inservice Inspection (RISI) as an inspection program alternative for Code Categories B-F, B-J, C-F-I and C-F-2, was utilized during QIRI8. The ultrasonic examination volumes for RISI components were increased, from the Section XI requirements, to meet the RISI Program.
The ultrasonic examination requirements of ASME Boiler and Pressure Vessel Code,Section XI, Appendix VIII, 1995 Edition with Addenda through 1996, as required by 10 CFR 50.55a, "Codes and Standards", and amended by the Federal Register Notice 64 FR 51370 dated September 22, 1999 is executed through the Performance Demonstration Initiative (PDI) Program according to the schedule defined in 10 CFR 50.55a(g)(6)(ii)(C),
for wrought austenitic piping welds, ferritic piping welds, bolts/studs, reactor vessel welds, nozzle to vessel welds, nozzle inside radius sections and full structural overlaid wrought austenitic piping welds.
4 of 21
Exelon Generation Company, L.L.C.
200 Exelon Way Kennett Square, PA 19348 Commercial Service Date February 18, 1973 Quad Cities Nuclear Power Station Unit I P.O. Box 216 Cordova,IL 61242 2.0 NIS-1 Form FORM NIS-1 OWNER'S REPORT FOR INSER VICE INSPECTIONS As required by the Provisions of the ASME Code Rules
- 1. Owner Exelon Generation Company, L.L.C., 200 Exelon Way, Kennett Square, PA 19348 (Name and Address of Owner)
- 2. Plant Quad Cities Nuclear Power Station, P.O. Box 216, Cordova, IL 61242 (Name and Address of Owner)
- 3. Plant Unit One
- 4. Owner Certificate of Authorization (if required)
N/A
- 5. Commercial Service Date 2/18/73
- 6. National Board Number for Unit N/A
- 7. Components Inspected Component or Manufacturer Manufacturer State or National Appurtenance Or Installer or Installer Province No.
Board No.
Serial No.
Reactor Pressure Babcock & Wilcox 610-0122-51-52 B0075000 N-140 Vessel Reactor Recirculation Dravo Corp.
N/A - See Table 3.1 -I N/A N/A Core Spray Grinnell N/A - Scc Table 3.1 -I N/A N/A Feedwater Grinnell N/A - See Table 3.1-1 N/A N/A Main Steam Grinnell N/A - See Table 3.1-1 N/A N/A Residual Heat Grinnell N/A - See Table 3.1-1 N/A N/A Removal Control Rod Drive Grinnell N/A - See Table 3.1-1 N/A N/A High Pressure Coolant Grinnell N/A - See Table 3. 1 -I N/A NIA Injection Note: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8Y2 in. x 1 1%V in.,
(2) information in items I through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
5 of 21
Exelon Generation Company, L.L.C.
200 Exelon Way Kennett Square, PA 19348 Commercial Service Date February 18, 1973 Quad Cities Nuclear Power Station Unit I P.O. Box 216 Cordova, IL 61242 FORM NIS-1 (Back)
- 8. Examination Dates:
- 9. Inspection Period Identification:
11/27/02 to 04/19/05 15' Period - From 3/10/03 to 3/9/06 for the 4h Interval
- 10. Inspection Interval Identification:
4th Interval - From 3/10/03 to 3/9/13 I1. Applicable Edition of Section XI 1995, for the 4h Interval Exams Addenda 1996, for the 4th Interval Exams
- 12. Date/Revision of Inspection Plan:
10/04/04 Revision I (4th Interval)
- 13. Abstract of Examination and Tests. Include a list of examinations and tests and a statement concerning status of work required for the Inspection Plan. See Section 3.0 and Tables 3.1-I, 3.1-IA. 3.1-2, 3.1-3, 3.1-4, and 3.2-1.
- 14. Abstract of Results of Examinations and Tests. See Section 3.0 and Tables 3.1-1 3.1 -I A, 3.1-2, 3.1-3, 3.1-4. and 3.2-1
- 15. Abstract of Corrective Measures. See Section 3.0 and Table 3.1-4.
We certify that a) the statement made in this report are correct, b) the examinations and tests meet Inspection Plan as required by the ASME Code,Section XI, and c) corrective measures taken conform to the ASME Code,Section XI.
Certificate of Authorization No. (if applicable)
N/A ExT Date July Ito 20 O$
Signed Exelon Corporation Owner
)iration Date I
N/A By (Ca M4' I'
4 CERTIFICATE OF INSERVICE INSPECTION 1, the under signed, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of
- Illinois, and employed by Hartford Steam Boiler of Connecticut of Connecticut have inspected the components described in the Owner's Report during the period 11/27/02 To 04/19/05
, and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described in this Owner's Report in accordance with the Inspection Plan and as required by the ASME Code,Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations, tests, and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
6,
Commissions IL 1580 7
4nspector's Signature National Board, State, Province, and Endorsements Date Ja: t
/((
20 OrC5 6 of 21
Exelon Generation Company, L.L.C.
Quad Cities Nuclear Power Station 200 Exelon Way Unit I Kennett Square, PA 19348 P.O. Box 216 Commercial Service Date February 18, 1973 Cordova, IL 61242 3.0 Abstract of Examinations, Conditions Noted and Corrective Measures 3.1.
Section XI Examinations Summary A combination of ultrasonic (UT), liquid penetrant (PT), magnetic particle (MT) and visual (VT) testing was performed prior to and during the 18th refueling outage on ISI Program components. Examinations were performed by General Electric (GE), IHI Southwest Technologies (ISwT) and Exelon Nuclear personnel. Volumetric and surface examinations were compared with the recorded results of previous examinations for applicable Class 1, 2 and RISI components. ISI inspections comprised of 81 volumetric (sixteen (16) nozzle exams, originally scheduled to be completed during the third period, were inspected during QIRI8 per an approved Schedular Exemption), 9 surface examinations and 71 visual examinations (13 were due to scope expansion) were performed on Class 1, 2 and RISI components.
The expanded visual examinations were a result of the "As-Found" cold settings being out of tolerance for three (3) Spring Can Component Supports, five (5) Flued Head Anchors and one (1) Box Guide that did not meet acceptance criterion. The additional examinations were performed in accordance with the requirements of IWF-2430 "Additional Examinations". The following IR's documented the Spring Cans "As-Found" conditions:
IR #'s 320458, 320457 and 321103. The following IR's documented the Flued Head Anchors "As-Found" conditions: IR #'s 323022, 317480, 317215, 317227 and 317483.
The Box Guide "As-Found" condition was documented under IR # 314639. Corrective actions were implemented to restore the component supports to meet design requirements or an engineering evaluation accepted the condition as-is. Subsequent visual inspections confirmed the proper restoration of these supports.
Thirteen (13) "elective" visual exams were also performed during QiR18. Specifically, these examinations were electively performed as a result of conditions noted during the most recent Unit 2 refueling outage, Q2R17. Components inspected included various Class 1 Constant Spring Cans and Flued Head Anchor supports on the Main Steam and Feedwater systems. Results of these examinations are documented in Table 3.1-1.
Table 3.1-1A, "Quad Cities Unit I ASME Section XI Limited Coverage Summary" contains the volumetric examinations that did not meet coverage requirements of ASME Section XI Code (i.e. greater than 90 percent of the specified examination volume).
Supplemental examinations were performed on these components where practical to increase examination coverage. Relief requests will be generated and submitted within twelve (12) months following the end of the inspection interval as required by 10 CFR 50.55a(g)5(iii) and 50.55a(g)5(iv).
The reactor vessel vertical welds were examined during this outage in accordance with the requirements of IOCFR50.55a "Codes and Standards" regarding the section entitled "Augmented Examination of Reactor Vessel". Minor typographical and uniformity errors were noted in the final ISwT Invessel Inspection Report as documented in IR # 352900 7 of 21
Exelon Generation Company, L.L.C.
Quad Cities Nuclear Power Station 200 Exelon Way Unit I Kennett Square, PA 19348 P.O. Box 216 Commercial Service Date February 18, 1973 Cordova, IL 61242 Pressure testing VT-2 examinations not related to repair/replacement activities are documented in Table 3.1-2, "Quad Cities Unit 1 Pressure Testing Summary". The Class 1 Vessel Leakage Test and the Reactor Vessel Head Flange Seal Leak Detection System were performed using the 1995 edition 1996 Addenda of the ASME Code for the first period of the fourth Interval.
Exelon personnel performed functional tests on a total of fifteen (15) snubbers for operability per the Service Life Monitoring/Failure Trending Sample and ASME/ANSI OM Code, Subsection ISTD. Nine (9) of the fifteen (15) snubbers were ASME Section XI Code designated. Two (2) of the fifteen (15) sunbbers tested were considered an augmented sample and were tested at the request of the corporate engineering team investigating possible effects of vibration as a result of Extended Power Uprate (EPU). All snubbers were found acceptable for continued operation. Snubber testing activities are summarized in Table 3.1-3, "Quad Cities Unit 1 Snubber Functional Tests".
Table 3.1-4 "Quad Cities Unit 1 Conditions Noted and Corrective Actions" summarizes the conditions noted during the examinations and corrective measures taken prior to returning the unit to service.
3.2. BWRVI P-75/Generic Letter 88-01 Augmented examinations required by Generic Letter 88-01, "NRC Position on Intergranular Stress Corrosion Cracking (IGSCC) in BWR Austentic Stainless Steel Piping", were performed as listed in Table 3.2-1, "Quad Cities Unit 1 BWRVIP-75/GL 88-01 Outage Scope". BWRVIP-75 "BWR Vessel And Internals Project, Technical Basis For Revisions To Generic Letter 88-01 Inspection Schedules" (as modified by associated NRC Safety Evaluation dated May 14, 2002), was implemented this outage. The scope of the outage included 4 non-Category welds, which were examined within 3 outages of applying overlays, 2 Category "E" and 1 Category "F' weld(s).
The four (4) non-Category welds that had overlays applied during QIR15 were inspected to include them into the Category E population as directed by BWRVIP-75 "BWR Vessel and Internals Project Technical Basis for Revisions to Generic Letter 88-01 Inspection Schedules". Originally, three (3) weld overlays were planned for Q1R18. Specifically, welds 02AD-F12, 02AS-S4 and 02BS-F4. Weld overlays were applied to 02AD-F12 and 02BS-F4 in accordance with ASME Code Case N-504-2, "Alternative Rules for Repair of Classes 1, 2, and 3 Austenitic Stainless Steel Piping" as approved for use in Regulatory Guide 1.147, "Inservice Inspection Case Acceptability, ASME Section XI, Division 1",
Rev. 13, dated January 2004. However, no overlay was applied to 02AS-S4 based on UT examinations (performed during QIR 18), which concluded that no IGSCC signal characteristics were present in the area of the previously recorded indication.
8 of 21
Exelon Generation Company. L.L.C.
Quad Cities Nuclear Power Station 200 Exelon Way Unit I Kennett Square, PA 19348 P.O. Box 216 Commercial Service Date February 18, 1973 Cordova, IL 61242 3.3. Invessel Inspections (IVI)
To implement the requirements of the Boiling Water Reactor Vessel Internals Program (BWRVIP), General Electric (GE) was contracted to perform the invessel inspections. The following components and assemblies were examined:
Steam Dryer in accordance with the BWR Steam Dryer Inspection and Flaw Evaluation Guidelines (BWRVIP-139), Jet Pump Assemblies in accordance with the BWR Jet Pump Assembly Inspection and Flaw Evaluations Guidelines (BWRVIP-41), Core Spray Internal Piping in accordance with the BWR Core Spray Internals Inspection and Flaw Evaluation Guidelines (BWRVIP-18), Core Shroud Vertical Welds in accordance with the BWR Core Shroud Inspection and Flaw Inspection Guideline (BWRVIP-76), Top Guide in accordance with the BWR Top Guide Inspection and Flaw Evaluation Guidelines (BWRVIP-26),
Reactor Pressure Vessel attachments associated with the Feedwater Spargers, Core Spray Piping, Jet Pump Riser Braces, Separator Guide Rod Brackets, Surveillance Specimen Brackets, Steam Dryer Guide Rod Brackets and Steam Dryer Wall Support Lugs, in accordance with the BWR Vessel ID Weld Inspection and Flaw Evaluation Guidelines (BWRVIP-48), Lower Plenum areas (e.g. CRD stub tubes, shroud support, core support structure) made accessible during Bottom Head Drain cleaning and following Jet Pump 6, 7, 20 disassembly were examined to meet the BWRVIP commitment to examine these areas when made accessible. A surface examination (PT) of the Standby Liquid (SBLC)
Nozzle NIO Nozzle to Safe End Weld was performed in accordance with the BWR SBLC System Core Plate AP Inspection and Flaw Evaluation Guidelines (BWRVIP-27) as amended by letter 2000-002.
During the visual examinations, shroud support weld H12 at the 95-degree azimuth was found to have a recordable indication. An Indication Notification Report (INR-Q1R18 24 Rev. 1) and IR # 321017 was generated to document this condition. In addition, the RPV cladding was found to have a recordable indication, which was documented under INR-Q1R18-IVVI-05-26 Rev. 2 and IR# 322056. Both indications were evaluated as acceptable for continued service under EC# 354895.
There were two INRs (QlR18-IVVI-05-20 Rev I and QIR18-IVVI-05-21 RevI) which documented no significant changes in existing indications in several Jet Pump and Core Spray welds which were reexamined during this refuel outage and evaluated under IR#
322438 and EC# 354895 as acceptable for continued service.
In addition, during Core Shroud Ring Segment Welds visual examinations, several circumferential indications associated with the intersecting horizontal shroud weld were observed. The Core Shroud horizontal welds had been previously repaired by installation of tie rod assemblies. These indications were found to be acceptable for continued service and not associated with ring segment welds. This is documented in INR-Q1R18-IVVI 22 Rev 1, IR# 322438 and EC# 354895.
The Steam Dryer was visually examined in accordance with GE SIL 644 revision I and BWRVIP-139 Steam Dryer Inspection and Flaw Evaluation Guidelines. The results of the 9 of 21
Exelon Generation Company, L.L.C.
200 Exelon Way Kennett Square, PA 19348 Commercial Service Date February 18, 1973 Quad Cities Nuclear Power Station Unit I P.O. Box 216 Cordova, IL 61242 inspections are documented in various GE INRs and IR# 323062. The indications were repaired under EC# 354626 or evaluated for continued service under EC# 354915.
Table 3.1-1 Quad Cities Unit 1 ASNIE Section XI Outage Scope Drawing Component Class Category Item Inspection Date Results M-3121 Sht. I RPV-VSCI-55 I
B-A Bl.12 UT 4/3/05 NRI M-3121 Sht. I RPV-VSCI-77 I
B-A Bl.12 UT 4/3/05 NRI M-3121 Sht. I Rl'V-VSCI-197 I
B-A Bl.12 UT 4/2/05 NRI M-3121 Sht. I RPV-VSCI-317 I
B-A B1.12 UT 4/2/05 NRI M-3121 Sht. I RPV-VSC2-22 I
B-A B1.12 UT 4/2/05 NRI M-3121 Sht. I RPV-VSC2-141 I
B-A B1.12 UT 3/28/05 NRI N1-3121 Sht. I RPV-VSC2-261 I
B-A Bl.12 UT 3/28/05 NRI M-3121 Sht. I RPV-VSC2-323 I
B-A Bl.12 UT 3/28/05 NRI M-3121 Sht. I RPV-VSC3-77 I
1-A B1.12 UT 3/28/05 NRI M-3121 Sht. I RPV-VSC3-197 I
B-A 1B1.12 UT 3/28/05 NRI M-3121 Sht. I RPV-VSC3-317 I
B-A 1B1.12 UT 3/27/05 NRI N1-3121 Sht. I RPV-VSC4-99 I
B-A 1B1.12 UT 3/28/05 NRI N1-3121 Sht. I RPV-VSC4-219 I
13-A 1B1.12 UT 3/27/05 NRI N1-3121 Sht. I RPV-VSC4-261 I
B-A 1B1.12 UT 3/27/05 NRI NI-3121 Sht. I RPV-VSC4-339 I
B-A 1B1.12 UT 3/27/05 NRI N1-3121 Sht. I BNIR-016-295 I
B-A B1.51 UT 4/3/05 NRI N1-3121 Sht. I BNIR-017-318 I
B-A B11.51 UT 4/3/05 NRI NI-3121 Sht. I BNIR-018-310 I
B-A B1.51 UT 4/3/05 NRI M-3121 Sht. I BNIR-138-270 I
B-A B1.51 UT 3/28/05 NRI M-3121 Sht. I BMR-167-305 I
B-A B1.51 UT 3/28/05 NRI M-312_ Sht. I NIANOZ I
B-D 113.90 UT 4/7/5 NRI M-3121 Sht. I N2ANOZ I
B-D B3.90 UT 4n/05 NRI M-3121 Sht. I N2A IRS I
B-D 1B3.100 UT 4/11/OS NRI M-3121 Sht. I N2B NOZ I
B-D B3.90 UT 4/1/05 NRI M-3121 Sht. I N2B IRS I
B-D 1B3.100 UT 4/11/05 NRI M-3121 Sht. I N2D NOZ I
B-D B3.90 UT 4n/05 NRI M-3121 Sht. I N2D IRS I
B-D B3.100 UT 4/11/05 NRI N1-3121 Sht. 1 N2E NOZ I
B-D 113.90 UT 4n/05 NRI N1-3121 Sht. I N2E IRS I
B-D B3.100 UT 4/11/05 NRI N1-3121 Sht. I N3A NOZ I
B-D 113.90 UT 4/6/05 NRI M-3121 Sht. I N3A IRS 1
B-D B3.100 UT 4/11/05 NRI M-3121 Sht. I N31B NOZ I
B-D 113.90 UT 4/6/05 Acceptable M-3121 Sht. I N31B IRS I
B-D 1B3.100 UT 4/11/05 Acceptable N1-3121 Sht. I N5A NOZ I
B-D 113.90 UT 4n/05 NRI N1-3121 Sht. I NSA IRS I
B-D 1B3.100 UT 4/11/05 NRI M-3121 Sht. I N8A NOZ I
B-D 113.90 UT 4/6/05 NRI M-3121 Sht. I N8A IRS I
B-D 113.100 UT 4/11/05 NRI NA CLOSURE NUTS I
B-G-I 116.10 VT-I 3/27/05 Acceptable
_ _ _ _ _ _ (1-3 1)
NA CLOSURE STUDS I
B-G--I 16.20 UT 3/24/05 NRI N A ___________ L34(1-31)
NA LIGAMENTS (1 -3 1)
I I11-G-1 I116.40 UT 3/24/05 NRI 10 of 21
Exelon Generation Company, L.L.C.
200 Exelon Way Kennett Square, PA 19348 Commercial Service Date February 18, 1973 Quad Cities Nuclear Power Station Unit I P.O. Box 216 CordovaIL 61242 Table 3.1-1 Quad Cities Unit 1 ASNIE Section XI Outage Scope D)rawing Component Class Category Item Inspection T Date Results NA CLOSURE I
B-(-3 1T6.50 VT-I 3/22/05 NRI BUSHIING (1.31)
NA CLOS URE B -G-I B-G-I 136.50 VT-I 3/27/05 NRI N1-3103 Sht.3 PUMP STUDS 113 I
B-G-I B6.180 UT 4/6/05 NRI M-3103 Sht. 3 FLANGE SURFACE I
B-G-I B6.190 VT-I 4n/05 NRI N1-3103 Sht. 3 NUTS. ETC.
I B-G-I B6.200 VT-I 4/5/05 Acceptable M-3103 Sht. 3 DECON FLANGE 3" I
B-G-2 1B7.50 VT-I 3/23/05 NRI (0202A)
MI-3103 Sht. 3 (0202El)
B-G-2 B37.50 VT-I1 3/23/05 NRI I-3 103 Sht. 3 DECO FLANGE I
B-G-2 117.50 VT-I1 3/23/05 NR1 N1-3105 Sht. I N6A FLANGE I
B-G-2 117.50 VT-I 3/24/05 NRI M-3105 Sht. I N6B FLANGE I
B-G-2 B7.50 VT-I 3/24/05 NRI N1-3105 Sht. I N7 FLANGE I
B-G-2 117.50 VT-I 3/24/05 NRI M-3102 Sht. I 1-220-58A I
B-G-2 B7.70 VT-I 04/05/05 NRI NM-3105 Sht. 2 1012A-W-104A I
B-K B10.20 MT 3/29/05 NRI M -3104 Sht. I 1403-W-103A I
B-K B 10.20 PT 3/29/05 NRI N1-3101 Sht. I 3001A-W-103A I
B-K B10.20 MT 4/6/05 NRI N1-3101 Sht. I 3001B-W-IOIA I
B-K B110.20 MT 4/1/05 NRI N1-3103 Sht. 3 11B-202 PUMNP I
B-L_2 B112.20 VT-3 4/4/05 Acceptable M-3102 Sht. I I-220-58A I
B-M-2 1112.50 VT-3 4/2/05 NRI NA RPV INTERIOR I
B-N-I 1113.10 VT-3 4/6/05 Acceptable NA RPV INTERNALS I
B-N-2 B13.20 VT-I, VT-3 4/4/05 NRI M-3131 Sht. 13 IA-1003A-1 2
C-A CI.10 UT 3/18/05 NRI M-3131 Sht. 13 N6A-FI RHIRHX 2
C-B C2.31 NIT 3/17/05 NRI M-3131 Sht. 13 N6A-F2 RHRIIX 2
C-B C2.31 IT 3/17/05 NRI M-3131 Sht. 5 009B-W-211A 2
C-C C3.20 MT 3/16/05 NRI M-3131 Sht. 2 1015A-W-202A 2
C-C C3.20 MT 3/16/05 NRI M-3131 Sht. I 1016D-W-201A 2
C-C C3.20 MT 3/16/05 NRI N1-3105 Sht. 3 101211-M-105 I
F-A Fl.10 VT-3 3/10/05 NRI M-3105 Sht. 2 1012A-W-104 I
F-A Fl.10 VT-3 3/28/05 NRI N1-3105 Sht. 3 101213-W-104 I
F-A Fl.10 VT-3 3/28/05 NRI M-3104Sht. I 1403-M-105 I
F-A Fl.10 VT-3 3/16/05 NRI N1-3104 Sht. I 1403-W-103 A&B I
F-A Fl.10 VT-3 3/21/05 NRI M-3108 Sht. I 2305-M-103 I
F-A Fl.10 VT-3 3/10/05 NRI M-3101 Sht. I 3001A-M-102.1 I
F-A Fl.10 VT-3 3/28/05 NRI IM-3101 Sht. I 30011B-M-106 I
F-A Fl.10 VT-3 4/12/05 NRI M-3101 Sht. I 300IA-W-103 A&B I
F-A Fl.10 VT-3 4/6/05 NRI M-3101 Sht. I 30011B-W-101 A&B I
F-A Fl.10 VT-3 3/31/05 NRI N1-3101 Sht. I 300113-W-105 I
F-A Fl.10 VT-3 3/28/05 NRI N1-3101 Sht.2 3001C-M-102.19 I
F-A Fl.10 VT-3 3/21/05 NRI M-3101 Sht. 2 3001C-W-101 A&B I
F-A Fl.10 VT-3 3/30/05 NRI N1-3102 Sht. 2 3204B-M-104 I
F-A FI.10 VT-3 4/12/05 NRI N1-3102 Sht. 2 3204D-W-101 A&B I
F-A Fl.10 VT-3 3/31/05 NRI M-3103 Sht 4 0263-lM-101 I
F-A Fl.40 VT-3 4/11/05 NRI N1-3134 Sht. I 0318B-W-201 2
F-A Fl.20 VT-3 3/14/05 NRI N1-3134 Sht. 2 0380B-G-203 2
F-A F1.20 VT-3 3/11/05 NRI N1-3134 Sht. I 0380D-NI-201 2
F-A FI.20 VT-3 3/14/05 ACCEPTABLE N1-3131 Sht 5 1009B1-G-206.2 2
F-A FI.20 VT-3 3111/05 NRI 11 of2l
Exelon Generation Company. L.L.C.
200 Exelon Way Kennett Square, PA 19348 Commercial Service Date February 18, 1973 Quad Cities Nuclear Power Station Unit I P.O. Box 216 Cordova, IL 61242 Table 3.1-1 Quad Cities Unit 1 ASNIE Section XI Outage SconC I)rawing Component Class Category Itein Inspection I)atc Results
.M-3131 Sht.7 1009B-W-201 2
F-A FI.20 VT-3 3/14/05 NRI M-3131 Sht. 5 10091U-W-211 2
F-A FI.20 VT-3 3/28/05 NRI M-3131 Sht.7 1010-NI-207 2
F-A Fl.20 VT-3 3/11105 NRI M-3131 Sht. 2 1015A-W-202 A&B 2
F-A FI.20 VT-3 3/15/05 NRI N1-3132 Sht. I 2302-NI-204 2
F-A FI.20 VT-3 3/11/05 NRI N1-3130 Sht. 3 1401-W-204 2
F-A FI.40 VT-3 3/9/05 NRI N1-3104 Sht. 2 14B-F5R I
R-A RIl. I UT 4/3/05 NRI N1-3102 Sht. I 32A-F13 I
R-A RI.l I UT 4/1/05 NRI N1-3102 Sht. I 32A-SIO I
R-A RIA I UT 4/1/05 NRI M-3102 Sht. 2 32D-SO I
R-A RI. Il UT 4/1/05 NRI M-3102 Sht. 2 32D-S5 I
R-A RI.l UT 4/2/05 NRI M-3131 Sht. 8 1006A-6 2
R-A RI. I UT 3/16/05 NRI N1-3131 Sht. 8 10061B-4 2
R-A Rl.1 I UT 3/16/05 Acccptable M-3131 Sht. 8 IOOSA-5 2
R-A RI. I UT 3/16/05 NRI M-3131 Sht. 6 I008B-7 2
R-A Rl.1 I UT 3/16/05 Acceptable M-3131 Sht. 9 1009A-4 2
R-A RI.] I UT 3/16/05 NRI M -3131 Sht. 7 10091B-6 2
R-A RI. I UT 3/17/05 NRI M-3131 Sht. 9 1010-4 2
R-A RI.l I UT 3/17/05 NRI M-3131 Sht. 9 1010-5 2
R-A RI. I UT 3/17/05 NRI M-3131 Sht.3 1012A-1 2
R-A R.l I UT 3/25/05 NRI M-3131 Sht. 3 1012A-2 2
R-A R.l I UT 3/25/05 NRI N1-3131 Sht. 10 1024A-3 2
R-A R1.lI VT-2 04/14/05 NRI NI-3131 Sht. 10 1024A-4 2
R-A R1.1l VT-2 04/14/05 NRI NI-3109Sht. I 12S-Fl2R I
R-A R1.20 UT 4/1/05 NRI M-3101 Sht. I 30A-S0 I
R-A Rl.20 UT 4/1/05 NRI M-3101 Sht. I 30A-S II I
R-A R1.20 UT 4/3/05 NRI M-3101 Sht. I 30A-S12 I
R-A Rl.20 UT 4/3/05 NRI M-3I01 Sht.2 30D-F30 I
R-A Rl.20 UT 3/24/05 NRI M-3131 Sht.2 1016B-5 2
R-A Rl.20 UT 3/16/05 NRI M-3131 Sht. 2 101613-6 2
R-A RlI.20 UT 3/17/05 NRI M-3140Sht. I 1318-5 2
R-A RI.20 UT 3/19/05 NRI M-3130 Sht. 3 1401-8 2
R-A RI.20 UT 3/19/05 NRI lEpnddSoeinspections (See NOTSo etPge)-
M-3105 Sht. 2 1012A-N1-106 A&B' I
F-A FI.10 VT-3 4/11/05 Acceptable M-3131 Sht 3 1012A-W-104' I
F-A FlI.0 VT-3 4/11/05 Acceptable M-3101 Sht. 2 300IC-M-1062 I
F-A FlI.0 VT-3 4/4/05 NRI N1-3102Sht. I 3204A-W-1013 I
F-A FI.10 VT-3 4/6/05 NRI M-3.02Sht. I 3204F-W-103' I
F-A FIAO VT-3 4/6/05 NRI M-3102 Sht. I 3204A-W-102' I
F-A FI.10 VT-3 4/4/05 NRI N1-3102 Sht. 2 3204A-W-102' I
F-A Fl.10 VT-3 4/6/05 NRI M-3102 Sht. 2 3204D-W-1025 I
F-A FIl.0 YT-3 4/6/O5 NRI M-3102 Sht. 2 3204B-W-10I' I
F-A FLIOI VT-3 4/6/OS NRI M-3102 Sht. 2 3204B-W-1031 I
F-A Fl.I0 VT-3 4/4/05 NRI N1-3103 Sht. 4 0263-M-1026 I
F-A FI.40 VT-3 4/9/05 Acceptable M-3131 Sht. 5 1009B-M-2107 2
F-A Fl.20 VT-3 3/24/05 NRI N1-3132 Sht. 2 2304-W-210.1 2
F-A Fl.20 VT-3 4/8/05 NRI M-3132 Sht. 2 3204B-M-201' 2
F-A Fl.20 VT-3 4/4/05 NRI
-ElectiveExaminations-
.1 :.
M-3105 Sht. 2 11012A-M-105 I
I F-A I
FlI.
I VT-3 4/13/05 NRI 12 of 2i
Exelon Generation Company, L.L.C.
200 Exelon Way Kennett Square, PA 19348 Commercial Service Date February 18, 1973 Quad Cities Nuclear Power Station Unit 1 P.O. Box 216 Cordova, IL 61242 Tablc 3.1-1 Quad Cities Unit I ASME Section XI Outage Scope Drawing Component Class Category Item Inspection I)ate Results N1-3101 Sht. I 3001A-M-106 I
F-A Fl.10 VT-3 3/24105 NRI NI-3101 Sht. I 3001A-W-101 A&B I
F-A FI.10 VT-3 3/30/05 NRI NI-3101 Sht. I 3001B -W-102 A&B I
F-A FI.10 VT-3 3/28105 NRI N1-3101 Sht. I 300IB-W-I04 A&B I
F-A FI.10 VT-3 3/31/05 NRI M-3101 Sht. 2 3001C-N1-107 I
F-A Fl.10 VT-3 4/12/05 NRI N1-3101 Sht. 2 300IC-W-102 A&B I
F-A Fl.10 VT-3 3/30105 NRI N1-3101 Sht. 2 3001C-W-104 A&B I
F-A Fl.10 VT-3 3/28/05 NRI N1-3101 Sht. 2 300ID-M-106 I
F-A Fl.IO VT-3 3/24105 NRI N1-3101 Sht. 2 300ID-W-101 A&B I
F-A Fl.IO VT-3 4/12105 NRI N1-3102Sht. I 3204A-M-103 I
F-A FlI.
VT-3 4/12/05 NRI N1-3102 Sht. 2 3204C-W-101 A&B I
F-A FlI.
VT-3 4nl05 NRI M-3102Sht. I 3204E-W-101 A&B I
F-A Fl.10 VT-3 4n105 NRI N1-3102Sht. I 3204F-W-101 A&B I
F-A Fl.10 VT-3 3/31/05 NRI In 3
iterval Credited Exams Performed pei.SchedularExeimption &-. ',
7 N1-3121 Sht. I NIA IRS I
B-D l B3.100 UT 4/11/05 NRI NI-3121 Sht. I NIB NOZ I
B-D B3.90 UT 411/05 NRI N1-3121 Sht. I NIB IRS I
B-D B3.100 UT 4/11/05 NRI NI-3121 Sht. I N2FNOZ I
B-D B3.90 UT 4n/05 NRI M-3121 Sht. I N2F IRS I
B-D B3.100 UT 4/111/05 NRI N1-3121 Sht. I N2G NOZ I
B-D B3.90 UT 417/05 NRI N1-3121 Sht. I N2G IRS I
B-D B3.100 UT 4/11/05 NRI N1-3121 Sht. I N2H NOZ I
B-D B3.90 UT 4n/05.
NRI N1-3121 Sht. I N2H IRS I
B-D B3.100 UT 4/11/05 NRI Nl-3121 Sht. I N2J NOZ I
B-D B3.90 UT 4t7/05 NRI M-3121 Sht. I N2J IRS I
B-D B3.100 UT 4/11/05 NRI M-3121 Sht. I N2K NOZ I
B-D 1B3.90 UT 417/05 NRI M-3121 Sht. I N2K IRS I
B-D B3.100 UT 4/11/05 NRI M-3121 Sht. I N8B NOZ I
B-D B3.90 UT 4/6/05 NRI N1-3121 Sht. I N8B IRS I
B-D B3.100 UT 4/11/05 NRI Nt-312t Sht. I NIONOZ I
1B-D s3.90 UT 4/11/05 NRI For NOTES I thru 8. the components were visually inspected per the requirements of IWF-2430(a) "Additional Examinations".
Section Xl exam credit, regarding Table IWF-2500-1 is NOT being taken for these expanded scope components.
'NOTE: As a result of "As-Found" conditions noted regarding Fued lead Anchor 1012A-M-105 (IR #323022).
2 NOTE: As a result of "As-Found" conditions noted regarding Flued Head Anchor 3001C-M-107 (IR # 317480).
3 NOTE: As a result of "As-Found" conditions noted regarding 2 Constant Spring Cans 3204E-W-101 A&B (IR # 320458).
4NOTE: As a result of "As-Found" conditions noted regarding Flued Head Anchor 3204A-M-103 (IR # 317215).
5 NOTE: As a result of "As-Found" conditions noted regarding 2 Constant Spring Cans 3204C-W-101 A & B (IR # 320457).
6NOTE: As a result of "As-Found" conditions noted regarding I Variable Spring Can 0263-M-101 (IR # 321103).
7NOTE: As a result of "As-Found" conditions noted regarding I Box GuidelO09B-W-211 (IR # 314639).
SNOTE: As a result of "As-Found" conditions noted regarding Flued Hlead Anchor 3204B-M-104 (IR #317227).
9NOTE: This support was examined as follow up to maintenance performed in QIF51(11/03) see WO 00641321-01.
13 of 21
Exelon Generation Company, L.L.C.
200 Exelon Way Kennett Square, PA 19348 Commercial Service Date February 18, 1973 Quad Cities Nuclear Power Station Unit I P.O. Box 216 Cordova, IL 61242 Table 3.1-1A Quad Cities Unit 1 ASNME Section XI Limited Coverage Summary (4t1 Interval)
I)raving Component Class l Category item Inspection ASME % Coverage M-3121 Sht. I Rl'V-VSCI-317 I
B-A B1I.12 UT 85 M-3121 Sht. I RP'V-VSCI-55 I
Bl-A Bl.12 UT 78 M-3121 Sht. I Rl'V-VSC2-22 I
B-A Bl2 UT 66 Mf-3121 Sht. I Rl'V-VSC3-197 I
B-A B1.12 IT 72 M-3121 Sht. I RPV-VSC3-317 I
B-A B1.12 UT 80 M-3121 Sht. I RPV-VSC3-77 I
13-A B1.12 UT 80 M-3121 Sht. I RPV-VSCI-197 I
B-A B1.12 UT 36 M-3121 Sht. I RPV-VSCI-77 I
B-A 81.12 UT 85 N1-3121 Sht. I RPV-CW-C4FLG I
B-A B 1.30 UT 83 M-3121 Sht. I BNIR-167-305 I
B-A B1.51 UT 87 M1-3121 Sht. I BMR-016-295 I
B-A B1.51 UT 83 Mt-3121 Sht. I N2A NOZ I
B-D B3.90 tJT 43 M-3121 Sht. I NIB NOZ I
B-D B3.90 UT 24 M-3121 Sht. I N2K NOZ I
Il-D B3.90 UT 43 M-3121 Sht. I N5A NOZ I
B-D 113.90 UT 42 M-3121 Sht. I N3A NOZ I
B-D 83.90 UT 41 N1-3121 Sht. I N21 NOZ I
B-D B3.90 UT 43 N1-3121 Sht. I N2J NOZ I
B-D 83.90 UT 43 M-3121 Sht. I N3B NOZ I
B-D 83.90 UT 41 M-3121 Sht. I N2FNOZ I
B-D B3.90 UT 43 M -3121 Sht. I N2G NOZ I
B-D 113.90 UT 43 M-3121 Sht. I N2B NOZ I
B-D 83.90 UT 43 M-3121 Sht. I NIA NOZ I
B-D 83.90 UT 30 M.-3121 Sht. I N2E NOZ I
B-D B3.90 UT 43 M.-3121 Sht. I N2D NOZ I
B-D 83.90 UT 43 14 of 21
Exelon Generation Company, L.L.C.
200 Exelon Way Kennett Square, PA 19348 Commercial Service Date February 18, 1973 Quad Cities Nuclear Power Station Unit I P.O. Box 216 Cordova, IL 61242 Table 3.1-2 Quad Citics Unit 1 Pressure Testing Summary I
Item Procedure/
Completion Relief onent Inspection Category Number Report Date Request Remarks RX and Class I 1315.10.
QCOS 0201-08 Class I & 2
& 2 Visual. VT-2 11-1' 15.50, 15.60.
VT Report VT2-222 04115/05 14R-07 System Leakage 15.70 Test N10 IRS Visual. VT-2 13-D B3.100 QCOS 0201-08 04/15/05 14R-01 Class I System VT Report VT2-222 Leakage Test Reactor Vessel Line 1-0236-1" Visual. VT-2 C-1 C7.30, C7.70 VT Report VT2-099 03/30/2005 14R-05 Head Flange Seal and 1-0234-I-Leak Detection System IA Core Spray Visual. VT-2 C-Hl C.30. C7.50, VT Reports VT-2 248 9/13/2004 14R-07 Class 2 System
_______C7.70 Leakage Test HrCI MSIV Visual VT-2 C-H C7.30 C7.70 VT Reports VT2-224 4/14/2005 14R-07 Class 2 System Rm piping Leakage Test Rm piping Visual. VT-2 C-Hl C7.30, C7.70 VT Reports VT2-065 3/21/2005 14R-07 leakage Test SBLC Explosive Visual, VT-2 C-ll C7.30, C7.70 VT Reports VT2-106 3/30/2005 14R-07 Class 2 System V'alves to RX isa ps
-Leakage Test piping Scram C7. IO, C7.30 QT 0201 -02 Class 2 System Discharge Visual. VT-2 C-Il Cl,7.70, V ReCortI~
V222 04/15/2005 141R-07 Leakage Test VolumeC..0 VReot'1-2 15 of 21
Exelon Generation Company, L.L.C.
200 Exelon Way Kennett Square, PA 19348 Commercial Service Date February 18, 1973 Quad Cities Nuclear Power Station Unit I P.O. Box 216 Cordova, IL 61242 Table 3.1-3 Quad Cities Unit I Snubber Functional Tests (4th Interval)
Drawing Component Class categorv Item Inspection I)ate Tested Results N1-99OD-278 0200-NI-131 I
F-A 1.40 Fr 3/31/2005 Satisfactory N1M-99OD-259 0200-W-I 54 1
F-A 1.10 Fr 3/30/2005 Satisfactory M-994D-3l9 1012B-W-101 I
F-A 1.10 Fr 3/29/2005 Satisfactory NM-983D-260 1404-W-103B I
r-A 1.10 Fr 3/31/2005 Satisfactory N1-328A S6 3001A-N1M-101.2 I
F-A 1.10 Fr 3/23/2005 Satisfactory NM-328C S9' 300lC-N-1I02.1 I
F-A 1.10 Fr 3/22/2005 Satisfactory MN-329A s8 3035A-NM-101 I
F-A 1.10 Fr 3/22/2005 Satisfactory N1-1605-09 Io0sA-NM-204 2
F-A 1.20 FT 3/18/2005 Satisfactory NI-1602-24 1025-NI-218 2
F-A 1.20 Fr 3/18/2005 Satisfactory 2-98D-6 SI, 1-57 N/A N/A N/A Fr 3/21/2005 Satisfactory N1-32. B S I I '
1-66 NA NIA NIA FT 3/222005 Satisfactory NI-328D S17 1-78 N/A N/A N/A FT 3/22/2005 Satisfactory N-1607 SI I 1-107 N/A N/A N/A FT 3/17/2005 Satisfactory N1-I608-06SI 1-109 N/A N/A N/A FT 3/18/2005 Satisfactory N-9861D-121 1-119 N/A N/A N/A Fr 3/18/2005 Satisfactory
'NOTE: These snubbers were tested as an augmented sample required by EC 346515 Revision 2.
to Main Steam Line Vibration at Extended Power Up-Rate levels.
This EC is related 16 of 21
Exelon Generation Company, L.L.C.
200 Exelon Way Kennett Square, PA 19348 Commercial Service Date February 18, 1973 Quad Cities Nuclear Power Station Unit I P.O. Box 216 Cordova, IL 61242 Table 3.1-4 Quad Cities Unit I Conditions Noted and Corrective Actions Component ID Description / Resolution Pressure Test "A" Recirculation Pump Casing to During the Unit I Class I Leakage Test the listed components were identified to be Ieaking at Cover Connection.
bolted connections. Corrective actions were taken as required.
HCUs Corrective actions included:
0305-105-3027 Engineering evaluation (EC # 0000355008) was performed (as permitted by Relief 0305-101-2619 Request 14R-07) on the IA Recirculation Pump and determined the leakage to be within 0305-127-3043 acceptable limits.
0305-127-1047 Hydraulic Control units (HCU) were leaking I - 6 drops/minute (DPM). Engineering 0305-104-3003 evaluation (EC # 0000355007) was performed (as permitted by Relief Request 14R-07) 0305-122-3003 on the HCU's and determined the leakage noted at the body to bonnet joints to be within 0305-101-2603 acceptable limits.
0305-103-2203 0305-127-0647 0305-113-2255 0305-127-1047 Reference VT report # VT2-222 dated 04115/05 Risk ISI Inspections As a result of Issue Report (IR) # 303182 regarding inconsistencies between NDE procedure and Risk 1SI (RISI) requirements, five (5) previously inspected RISI welds were required to Circumferential Weld Examinations be re-inspected during QIR18. Specifically, three (3) Feedwater & two (2) RHR carbon steel welds, subject to thermal fatigue cracking, had circumferential examinations performed. since they were not performed during the original RISI exams (refer to IR #303198).
No indications were recorded during the circumferential examinations.
Visual Inspections As a result of "As-Found" conditions noted regarding Spring Cans Component Supports, Flued Head Anchors, and a Box Guide an additional eleven (I1) components were visually Spring Can Component Supports.
inspected. Non-conforming components were repaired as necessary or evaluated as Flued Hlead Anchors and Box Guide acceptable and the "As-Left" condition of components inspected were acceptable. Refer to IR
- 's 314639, 317215, 317480, 320457, 320458, 321103 and 323022. Section Xi examination credit, regarding Table IWF-2500- 1 is NOT being taken for these expanded scope components.
In Vessel Inspections When the lower plenum was made accessible for visual examinations, the Shroud Support Weld H12 at the 95-degree azimuth was found to have a recordable indication. INR-QIR18-Shroud Support Weld 1112 05-24 Rev. I and IR # 321017 were generated to document this condition. In addition, the RPV Cladding RPV cladding was found to have a recordable indication (e.g. ding), which was documented under INR-QIR18-IVVI-05-26 Rev. 2 and IR# 322056. Both indications were evaluated as acceptable for continued service under EC# 354895.
17 of 21
Exelon Generation Company, L.L.C.
200 Exelon Way Kennett Square, PA 19348 Commercial Service Date February 18, 1973 Quad Cities Nuclear Power Station Unit I P.O. Box 216 Cordova, IL 61242 Table 3.2-1 Quad Cities Unit 1 BWN'RVI I'-75/G1, 88-01 Outage Scope Pre/Post Draving Component Class Outage Inspection Date Results Category M-3103 Sht. 3 02AS-S4 I
E/C UT 4/1/05 ACCEPTABLE' M-3103 Sht. 3 02BS-F14 I
I/E UT 4/3/05 ACCElrrABLE 2 M-3103 Sht. 3 O2BS-r4 I
F/ E UT 4/12105 Weld Overlay Completed NM-3103 Sht. 2 02AD-F12 I
E/E UT 4/12/05 Weld Overlay Applied M-3103 Sht. 3 O2AS-F9 I
- / E UT 4/6/05 ACCEPTABLE 2 M-3103 Sht. 2 02AD-F8 I
- / E UT 4/4/05 ACCEPTABLE 2 M-3103 Sht. 3 02BS-F7 I
-/E UT 4/4/05 ACCEPTABLE 2 l NOTE:
A weld was originally planned for Q IR 18. However, based on UT examinations (performed during Q IR 18),
concluded that no IGSCC signal characteristics were present in the area of the previously recorded indication 2 NOTE: Weld overlays were applied during QIR15 (Nov. 1998) and inspected within three (3) outages to be placed in the Category E population.
3 NOTE: A partial weld overlay that was applied during Q I R 16 (Oct. 2000) was completed during Q I R 18.
18 of 21
Exelon Generation Company, L.L.C.
200 Exelon Way Kennett Square, PA 19348 Commercial Service Date February 18, 1973 4.0 Repair / Replacement Summary 4.1.
NIS-2 Index Quad Cities Nuclear Power Station Unit I P.O. Box 216 Cordova, IL 61242 Table 4.1-1 Quad Cities Unit I NIS-2 List Program Number Component EPN Work Request Number ASMIE XI Class or Purchase Order 03-003 1-1402-28A 003763S4-01 2
03-004 1-1407-1 1/2' 99203182 2
03-009,03-023 0-SPARE-V18 00510634-01 & 03 I
03-014,03-043 0-SPARE-V18 00510632 03-015 0-SPARE-V18 00510633-01 1
03-020 I -0203-3C 00343762 I
03-025 1-0203-3D 00548669 I
03-026 I-0203-3A 00548671 I
03-034 1-0215-211 00578219 2
03-035 S9R 00578855-01 2
03-049 SPARE 0-1003A 00604950-01 2
03-093 0-SPARE-V26 00510625 1
03-107.02-086. 02-107 0-SPARE-V26 00320899 I
03-122 1-0203-3D 00636986-01 O
03-123 I-3035A 00636986 G 03-126 I-305IC-'h"-B 00640103 2
03-127 I-305ID-3/3/4"-B 00640101 2
03-132 I-3001-C71 00641321 I
03-133 I-1402-28B 00557469 2
04-062,05-003 O-SPARE-HI15 00677706 2
04-068,04-061,04-123 0-SPARE-V26 00510623 I
04-071 1-0220-49 00606987 2
04-074,04-075.05-006 O-SPARE-V26 00573019 1
04-078 I-1402-28B 00676648 2
04-081,04-082,04-083.04-084, 04-085,04-086,04-139, 04-140,04-141,04-142, 04-143,04-144, 04-145,04-146,04-147,04-148, 04-149, 04-15 1,04-152, 04-153 Various Control Rod Drives 00590943 I
04-087 I -0203-4C 00577389 I
04-088 1-0203-4D 00569449 I
04-089 1-0203-411 00577391 I
04-090 I -0203-4G 00577390 I
04-091 1-2301-23 00588400-01 2
04-096.05-002 1-1 106-A 00543620-02 & 03 2
04-097 I-0203-3B 00673019 I
04-098.04-099,04-100 0-SPARE-V26 00665516 I
04-101,04-102,05-047,05-048 1-300 North & South 00598434 2
04-105 1-0203-3D 00671613 1
04-106 1-0201 00692313 I
04-108 I-0203-3C 00671614 I
04-109 1-0203-3E 00671611 I
19 of 21
Exelon Generation Company, L.L.C.
200 Exelon Way Kennett Square, PA 19348 Commercial Service Date February 18, 1973 Quad Cities Nuclear Power Station Unit I P.O. Box 216 Cordova, IL 61242 Table 4.1-1 Quad Cities Unit 1 NIS-2 List Program Number Component EPN Work Request Number ASNIE XI Class or Purchase Order 04-11l 1-0202-A28A 99225959 I
04-112 1-0202-B28A 99225960 04-118 1-0202 00686220 04-131.04-134 1-0220-58A 00632759 1
04-132,04-133 1-0220-58B 00466432 1
04-136 AO 1-0203-IA 00452546 I
04-137 AO 1-0203-2D 00448534 I
04-154 1-3007B -1.5 00688892 2
04-155 I-3007D-1.5 00688888 2
04-156 I-3007C-I.5 00688889 2
04-157 I-3007A-1.5 00688893 2
04-159 1-1402-81B 00493719-07 2
05-004 1-0203-3A 00578474 1
05-013.05-014 1-1003-B 00685172 2
05-015 1-0300-26-27 00590943 I
05-023 1-0202-B 00613959 1
05-024 1-0202-B 00613959 I
05-025 I-3001 -A58 99042806 I
05-028,05-046 1-0263 00784532 05-030 I-0220-62A 00795331 1
05-033 1-1012-118 00379905 I
05-037 1-1600-XO7B 00795495 1
05-038 I-1600-XO9A 00795500 1
05-039 I-I 600-XO9B 00795499 I
05-040 Spare CRD's Po # 707 I
05-041 Sparc CRD PO # 707 I
05-042 Spare CRD Po # 707 I
05-043 Spare CRD PO # 707 05-044 1-1003-B 00685172 2
05-049.05-51 I -1600-X 13A 00799763 N/A Spare valve PO # 71184 1
00-109 0-SPARE-V26 990042820 I
20 of 21
Exelon Generation Company, L.L.C.
200 Exelon Way Kennett Square, PA 19348 Commercial Service Date February IS, 1973 Quad Cities Nuclear Power Station Unit I P.O. Box 216 Cordova,IL 61242 4.2.
NIS-2 Forms (Attached) 21 of21
W I 1~. tMIv-4 1_Z1:1_-%
I iic-F M
!- ~1Tp.T M!deeioX
~A 'J.Oiter fEzxO-n Genratiion Compaz.
ti.
LJ DaLt:
6-1 2-2003 f
3 4300 Winfield Road Sheet:
1 or I j!
Wanvil.k, 11.
60355 Unit:
I "j Pue Quad Cities Generating Station Repair program 03-003 W. Of W0376340l - '
22710 206th Ave. North. Cordova, IL 61242 Rcpair Orpnfztioln P.O. No.(b No., tc.
Type Code Symbol Stamp:
N
'3. Wiok Performed by:
Quad Cities Gcnerating Station Authorization No.:
.Non 22710 206th Ave. North, Cordova. IL 61242 Expiration Date:
N/A
- 74. Atication of System: Core Spray. Class 2
(.(a)Apa)i A
icaWConstuntionCode:
USASB31.1 1967 Edition. None Addenda, N/A Code Case gS (b)ApplicP e Edition otSecion Xl Utilized for Repairs or ReplaccnwrnLs: j989 Edition, N/A Addenda. N/A CodeCase
- 6. I ikmo of Corponents Repaircd or Replaced. and Rcplacement Components:
j,..
l :.. 44t I
I I
I
$;
'6 2i
L1 N;: meof Name of Mfrs. %Cr.
Natl Other Year Rep"
- Cn.
Mfr.
No.
Bd.
Identification Built Replaced, or No.
Replac,..iement taiid Relief Valve ConsolidatedDreser]
TH78260 N/A 1-1402-28A N/A Replaced I'!}Ys 1.I 0.
51, iI11 I
I
,.a
,cf.
I.oj IFJ PI
,Tll
.1I14
-F I 1_1 LI I1 I 11 F
RRlif Valvc
[Consohidated/ressr I TL92166 I N/A I
1-1 402-28A N/A Replacement i -'
I i I fvy";
i i j
- 7.
ecripdoi of Work: Reolaced the relief valve as trquird by tt.
- ttt, S. Tests Conducted:
Hydrostatic 0 Pneumatic 0 Ntorrinal Operating Pressure 0
Odter 0 Pressur psi Test Tcmp.
' _F
- j.
Ž
- 9. Rcmarks: Nonc CERTIFICATE OF COMPLI[ANCE We cerify that the uaemenu mad in this repon aw correct and this conforms to th rules of ASME Code. Seion Xl, Type of Code Symbol Stamp N/A-Exelon Nuclear IOCFRS0 Ap B. 0 A Program i
I>
Certificate otAutb ization No.
N/A.
Expiration Date N/A Signed x)A-t6l Date K L)
E
/7 20 Z.Q.}
1 Y4 i
ii I
4
~'i 3.
-A 3.,
L CERTIFICATE OF INSERVICE INSPECTION
, T
- 1. the underigned. holding a valid commission issued by the National Board of Boler and PressureVessel Inspectors and the State of Jlliniis
. and employed by H5B_.CLof ConncicuL hav inspected the componens described in this Ownet Reot i the period CiAl'
/oz to jthr~eir,andstatethattotlhebestofimiknowdge and bief.theownerhas ft e
nJ taken corrmetive mrasures described in this Owner's Rtport in accorl3rice the rns.vuennts of theASME Code, Section Xl.
3 Hy signing this certificate. nither the inspector nor his employer ma'acs any wsmnty, exprtused or implied. concerning the examinations ad i~e nmj4uro s d-scribed in this Owner's Rpotn. Furthermore, neither tIe Invrpector ati his eqrloyer shall be liable in any manner for any p al tnjwyoi proxvrny darnmage or a loss (if any kind arising from or connected with &.is inspection.
l Commissionuis 4C45
/s TO 20imitv~l 1
_____'k.____Pe._
and V nf
_§.) §t_14-.J7 _______2(o0fi_ 1 3-II 1
iI III II i
li
jiI tII I
I II i
I I
4 J
II r.I ZI I
I1, I
I I
II r,I I11 Y...
Z
. +t.
I I
.1 I I
I I
I q
A;
. ;,All
+
. 'ji
. f 1, I
a
'.-1111'.
6,LjA ],,-q6 -.
il
. I
. ~.i"Z.I'l i0
171 11. -. 1 Uu:
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section Xi
- 1. Ov ner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenville. 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova, IL 61242 Date:
05/04/2005 Sheet:
I of I Unit:
I Program No.03-004 WO 99203182 Repair (rgani7ation P.O. No.. Job No.. etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova. IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Core Spray. Class 2
- 5. (a) Applicable Construction Code: Pipe: USAS B31.1 1967 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda. N/A Code Case
- 6. Identification of Components Repaired or Replaced, and R placement Components:
Name of Name of Mifrs. Ser.
Nat'l Other Year Repaired.
ASME Component M fr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Core Spray piping UNK.
UNK.
None 1-1407-1 '/z" UNK.
Replacement No
- 7. Description of Work: Rerouted pipe IAW WN.O.
- 8. Tests Conducted:
Hydrostatic E]
Pneumatic O Nominal Operating Pressure ED Other E Pressure psi Test Temp.
F
- 9. Remarks:
None CERTIFICATE OF COMPLIANCE
'e certily tlalt thle statemients niade in this report arc correct and tliis replacement coiforins to the rtilesof
-ASMIE Code. Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. O A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed P4 4 A
Supt Date
-j a 20OS
/
(lwner or Owner's Migliec. 'Kile CERTIFICATE OF INSERV[CE INSPECTION I. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressurc Vesscl Inspectors and the State of Illinois.
and cmployed by IISB CT. of Connecticut have inspected the components described in this Owner's Report during the period fC/C74/
to C71//T/OS -
and statc (hat to the best of my knowlcdge and belief tihc ow ner hals perlformed examiniationis nd taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code.Section XI.
By signing this certificate. neither the inspector nor his employer makes any warranty, expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
4-.X1//-
Commissions
'TI,- 15_YO"
/ C 1nlj1-r,&gna~l~ture Dalc
' e)s" C I3 Na~inl Nu13..id.
State. [Ta% i e. ird bid, rwnwnt 20 c7 5-
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date: 4-30-2004 Sheet:
I of I Unit:
0 Program No.03-009 & 023 WO 00510634-01 & 03 Repair Organization P.O. No., Job No., etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam, Class I
- 5. (a) Applicable Construction Code: USAS B31.1 1967 Edition, None Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Trim Set Crane N/A N/A 0-Spare-V 18 UNK.
Replacement No
- 7. Description of Work: Refurbished the trim set by welding and machining in accordance with the W.O.
- 8. Tests Conducted:
Hydrostatic Dl Pneumatic Dl Nominal Operating Pressure E Other E]
Pressure psi Test Temp. 'F
- 9. Remarks: None CERTIFICATE OF COMPLIANCE Ve certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Code, Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear IOCFR50 App B. 0 A Program Certificate of Aut rization No.
N/A Expiration Date N/A Signed 444 4 1 z5X-tA^,7Z[_Date 1n.,
Z 20rAt4
,er or Owner's Designee, Title x-J, CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
,and employed by IISB CT ofConnecticut have inspected the components described in this Owner's Report during the period (g7/t 7 /o? to i5%1 W6/o51 and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code,Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Zi Commissions rctom sibm Date 4/?vY
/,r P
Natxiral Soma State, Pwvir, and E-risenls 20 o
FORMI NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section Xi
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. IL 61242 Date:
6-15-2005 Sheet:
I of I Unit:
0 Program No.03-014.03-043 WO 00510632 Repair Organization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Spare, Class I
- 5. (a) Applicable Construction Code: USAS B31.1 1967 Edition, None Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of M9lfrs. Ser.
Nat'l Other Year Repaired.
ASME Component M fr.
No.
Bd.
Identification B uilt Replaced, or Code No.
Replacement Stamped (Yes or Trim Set Crane N/A N/A 0 -Spare-V818 UNK.
Replacement No
- 7. Description of Work: Refurbished valve (ise as required by the W.O.
- 8. Tests Conducted:
Hydrostatic El Pneumatic [5 Nominal Operating Pressure 5 Other a Pressure psi Test Temp. °1
- 9. Remarks: None.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASNME Code, Section Xi repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed Q APLf S
. Date Jul1 5 200S UVner 6C(w hcr' Dslcgnee.' Iife CERTIFICATE OF INSERVICE INSPECTION
- 1. the ulndersigflecl. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
, and employed by HSB CT of Connectictit have inspected the components described in this Owner's Rep)rt during the period C"/'/i /0 o to C7/d /oS, and state that to the best of my knowledge and belietf the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASNIE Code. Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examiniatiois and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
C 4
i Commissions c!L ISW-11~
f1Sqpimwo tKnio 13e-wl.1~rd, SMIC, Pnl~liMC.
3al0 I-.hwrewlent, Date It
'?
lo(
C: 5 Date
I.c
20 tS
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
6-18-2004 Sheet:
I of I Unit:
0 Program No.03-015 WO 00510633-01 Repair Organization P.O. No., Job No., etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Spare, Class 1
- 5. (a) Applicable Construction Code: USAS B31.1 1967 Edition, None Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Trim Set Crane NIA N/A 0-Spare-V 18 UNK.
Replacement No
- 7. Description of Work: Tack welding to the trim set in accordance with the W.O.
- 8. Tests Conducted:
Hydrostatic 5 Pneumatic EJ Nominal Operating Pressure 5 Other 5 Pressure psi Test Temp. 'F
- 9. Remarks: None.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Code,Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear IOCFR50 App B. 0 A Program Certificate of Au h iation No.
N/A Expiration Date N/A Signed iDate Zx3\\5J 7.2-.
200(
wfiner r Owner's Designee, Title r
4..
- 1 CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
,and employed by HSB CT of Connecticut have inspected the components described in this Owner's Report during the period 0 Y/l' /er to i6 /r I /
. and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code,Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damagepr a loss of any kind arising from or connected with this inspection.
4t Commissions JI.
6 AD Signature Nat ional Board. State. Province, zrAI Endorqenrnts Date M4-.A 20 ig
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Corclova. Il 61242
- 3. Work Performed by:
Quad Cities Generating Station 2271(0 206th Ave. North. Cordova, IL 61242 Date:
07/06/2005 Sheet:
I of I Unit:
I Program No. 03-02(0 WO 00343762 Repair Organization P.O. No.. Job No., etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam. Class I
- 5. (a) Applicable Construction Code: IISAS B3 1.1 1967 Edition.
N/A Addenda N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda. N/A Code Case
- 6. Identification of Co ponents Repaired or Replaced. and R placement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired.
ASME Component MIfr.
No.
Bd.
Identification Built Replaced. or Code No.
Replacement Stamped (Yes or
_N o)
Electromatic Relief Dresser Industries BK7072 No 1-0203-3C N/A Replacement No V a lv e I__
- 7. Description of Work: Replaced relief valve and inlet fiange bolts IAW W.O.
- 8. Tests Conducted:
Hydrostatic E Pneumatic E]
Nominal Operating Pressure ED Other a Pressure psi Test Temp.
°F
- 9. Remarks:
IR 35210 X)
CERTIFICATE OF COMPLIANCE Wve certify that ihe statcnents nIade in this report are correct and this replacement conforms to the niles of ASMIE Code. Section Xl repair or replacerent Type of Code Symbol Stamp NIA - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed AJlF dY JgM f
§Zr Date
-Jvt Is 20 05
/
(qvner or O ner's Des nt. Titlo II CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued hy the National Board of Boiler and Prcssure Vessel Inspectors and the State ol Illinois
. and employed by IISB (C. of Co'nnecticutt have inspected the components described in this Owner's Report during the period 64"i//3 to
. and state that to the best of ty knowledge and belief, the ow ner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code.Section XI.
By signing this certilicate. neither the inspector nor his cmployer makes any warranty, expressed or implied. conccrining thc cxaininatiois and correctivc mcasures described in this Owvner's Report. Furthermore. neither the Inspector nor his employer shall be liable in any manner lor any personal injury or property damiage or a loss of any kind arising front or connected with this inspection.
,~C,, <
1Commissions K-gS 0 r1ito
-11
cl
I 2()
i S-f l
i m
J L-~f
(
C t Z
FORNI NIS-2 OWNERS REPORT OF REPAIR OR REPLACEIMIENT As Required by the Provisions of ASME Code Section Xi
- 1. Owner:
Exelon Generation Company. LLC 43(J0 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova. IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
7/15/2005 Sheet:
I of I Unit:
I Program No.03-025 WO 00548669 Repair Organiation P.O. No.. Joh No.. etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam, Class I
- 5. (a) Applicable Construction Code: USAS B31.1 1967 Edition.
N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Co ponents Repaired or Replaced, and R placement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or N o )
Electromatic Relief Dresser Industries BX00293 N/A 1-0203-3D N/A Replacement No V a lv e I
_I_
- 7. Description of Work: Replaced relief valve lAW W.O.
- 8. Tests Conducted:
Hydrostatic [1 Pneumatic a
Nominal Operating Pressure E Other a Pressure psi Test Temp.
"F
- 9. Remarks:
IR 352180 CERTIFICATE OF COMPLIANCE We circify that the statemeints midc in Ihis report are conrcc anid this replacement coniorms to thc rules tr ASNIE Codc.Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OC R5() App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed A A&Lt P(
.714 Peel Dat JO IV 15; 200'5 V/
(vner or Owvner's tDesenieTcFilel CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vcsscl Inspectors and the State of
- Illinois, and cmployed by IISB CT. of Connecticut have inspected the components descrihed in this O tier's Report during the period cs /e 3' to t7/d.- /4
, anid state that to the best ot my knovwledge and beliel the owiner has perl'ormed examiiniationis anid taken corrective measires described in this Owner's Report in accordancc lhe requiremcnits or the ASME Code.Section XI.
By signing this certificate. neither the inspector nor his employer makes any warranty, expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall he liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
p1-.-...- 24L-2'7'?
Commissions Jl t5
- YO Iz~sxt~lr gil~ltureNai-l l
hr.
lllv.lSime. N-%ince.ml 1EMbilwimul Date A,4V
/6 2() OSV Date
/,
20 6.
FORMI NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASMIE Code Section XI
- 1. Owner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenville. II. 60555 Date:
Sheet:
Unit:
07/13/2005 I of I I
2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. IL 61242 Program No.03-026 WO 00548671 Repair Organization P.O. No.. Job No.. etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova. IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam. Class I
- 5. (a) Applicable Construction Code: USAS B331.1 1967 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced. and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component NMfr.
No.
Bd.
Identification Built Replaced. or Code No.
Replacement Stamped (Yes or Safety Relief Valve Target-Rock 120 N/A 1-0203-3A N/A Replacement No
- 7. Description of Work: Replaced relief valve and bolting lAW W.O.
- 8. Tests Conducted:
Hydrostatic fl Pneumatic []
Nominal Operating Pressure 0 Other [
Pressure psi Test Temp.
'F
- 9. Remarks:
None CERTIFICATE OF CONIPLIANCE We ccrtify that thc statements made in this report are correct alid this replacement conltorms to the riles ol ASIE Code. Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I 0CFR5() Ann B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Si-ned r9W;e r
(
ck7 cr vDate
\\J 1!
20 OS 0%° ner or swnd s DMsgned. Tfile CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board ol Boiler and Pressure Vessel Inspectors and the State of Illinois
. and employed by I ISB CT. or Connecticutl have inspected the components described in this Owner's Report during the period C
to l
_______o
__7/1___
. and state that to the best of my knoledge and belief, the owviner has perlo rmend examinations and taken corrective menasures described in this Owner's Rcport in accordance the requireatmenmts ol the ASMIE Code.Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty. expressed or implied. concerninilg tlie examinations and correcti'e measures described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall be liable in any manner For any personal injury or property dlamage or a loss of any kind arising from or connected with this inspection.
Commissions
?LS
/'
d Ddte laslui s "tilrc N.,Ih!fli f1.ti I sl tt. le. hI'ukC. JIM I id,.rwnll'A Date J&t
'M O g2(
)S-
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
05/09/2005 Sheet:
I of I Unit:
I ProgramNo.03-034 W000578219 Repair Organization P.O. No.. Job No., etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Reactor, Class 2
- 5. (a) Applicable Construction Code: ASME Section I11 Class A 1965 Edition, s-1965 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N416-1 Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or N o )
Piping Various N/A NI/A 1-0215-2B NIA Replaced No
- 7. Description of Work: Replace piping and fittings as required by the WO.
- 8. Tests Conducted:
Hydrostatic E]
Pneumatic a Nominal Operating Pressure E Other El Pressure psi Test Temp.
OF
- 9. Remarks: None CERTIFICATE OF COMPLIANCE Ve certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Code, Section Xl repair or replacemcnt Type of Code Symbol Stamp N/A - Exelon Nuclear IOCFR50 App B. 0 A Propram Certificate of thorization No.
N/A Expiration Date N/A Signed 1i
?
-Jr.7 Date j'
A.A--If 20M wner or Owner's Designee. Title CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
. and employed by I ISB ClT. of Connecticut hae inspected the components described in this Owner's Repon during the period SI-o h 3 to 51/" bos
, and state that to the best of my know ledge and belief. the o%.ner has performed cxaminations.urd taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code,Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
_Commissions
>/1 t7 )
Insp>rho Signature Njii-nal B-ird. Statue.
NIiinve. amd Endor'emrntr Date OfAY 1/
20 P s
FORM NIS-2 OWNERS REPORT OF REPAIR OR REI1LACENIENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
5-30-2003 Sheet:
I of I Unit:
I Program No.03-035 WO (X)578855-01 RepairOrgantat ion P.O. No., Job No.. etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Reactor Head Vent Line, Class 2
- 5. (a) Applicable Construction Code: USAS B31.1 1967 Edition. N/A Addenda. N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda. N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component M fr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Support Exelon N/A N/A S9R N/A Replacement No
- 7. Description of Work: Replaced the support as required by EC 342937 and the WN'O
- 8. Tests Conducted:
Hydrostatic a Pneumatic Cl Nominal Operating Pressure Other E Pressure psi Test Temp.
OF
- 9. Remarks: IR 00353086 CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the niles of ASME Code. Section Xl repair or replacement Type of Code Symbol Stamp N/A - ComEd I OCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed Date 20 0 V# O ner of Owtner's Dcsignee.Title CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Illinois
.and employed by IISB CT. of Connecticut have inspected the components described in this Owner's Report during the period L57Z to 7
to C W//b45
, and state that to the best of my knowledge and belief, the owner has perlirmed examnialtionls and taken corrective measures described in this Owner's Rcport in accordance the requirements of the ASME Code.Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied. concerning the examinations and corrective measures described in this Owkner's Report. Furthermore. neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
______________________Commissions A
bJ'O Ilk-, t -ws ninlurr Nalt lnal Poard. Stale, ~-ls. anld lrxto-renxint, liale Job-n {6 27() to S, fl:ifo J, 4.1 16
n
(,
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road WVarrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
6-24-2004 Sheet:
I of I Unit: 0 Program No.03-049 WO 00604950-01 Repair Organization P.O. No., Job No., etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Residual Heat Removal, Class 2
- 5. (a) Applicable Construction Code: ASME Section VIII 1968 Edition, None Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Floating Head Sweco N/A N/A Spare 0-1003A UNK.
Repair No
- 8. Tests Conducted:
Hydrostatic El Pneumatic El Nominal Operating Pressure Ea Other a Pressure _
psi Test Temp.
IF
- 9. Remarks: None CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this repair conforms to the rules of ASME Code, Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Au h ation No.
N/A Expiration Date N/A Signed A
Date J
Z 20 OV Pwneo wns ie's~ipneee Title CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
, and employed by FHSB CT. of Connecticut have inspected the components described in this Owner's Report during the period
/o:
to X2S-Y,andstate that to the bestofmy knowledge and belief. the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code, Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
D o
/
A
/Commissions
.EL ft $VC I
con Signature National Board. State. Province. wH Endornemnts Date 3^'-,
ZS 20 °0',
Program #
WRR#
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI I. Owner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
06/27/20()5 Sheet:
I of I Unit:
0 Pros ram No.03-093 WO 00510625 Repair Organization P.O. No.. Job No.. etc.
- 3. Work Performed by:
Quad Cities Generating Station 2271() 206th Ave. North, Cordova. IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam. Class I
- 5. (a) Applicable Construction Code:
USAS 1331.1 1967 Edition. N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year Repaired.
ASMIE Component rMfr.
No.
Bd.
Identification Built Replaced. or Code No.
Replacement Stamped (Yes or
_ _N o )
Electromatic Relief Dresser Industries B1K 7070 N/A 0-Spare V-26 N/A Replacment No Valve I
I
- 7. Description of Work: Refurbished the valve in accordance with W.O.
8.TestsConducted:
Hydrostatic n Pneumatic E Nominal Operating Pressure 0 Other a Pressure psi Test Temp.
'F
- 9. Remarks: None CERTIFICATE OF COMPLIANCE Wc certify that the statements made in this report arecoirect and this replacement conforms to thc miles of ASME Code.Section XI repair or replacement Type or Code Symbol Stamp N/A - Exelon Nuclear IOCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed p~
0L ate
- JcI, 2r~atkJv1n 5
20 05 V
Owt~crorOXkner'.,Desigii~c 'I'itic '
CERTIFICATE OF INSERIVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and thc State of Illinois
. and employed hy IISB CT. of Connectictit have inspected the components described in this Owner's Report during the period c' 1/53 13 X to C 7/e'/os. and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code.Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty. expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss ol' any kind arising from or connected with this inspection.
- 9.
_Commissions.
/ L /5 -(
ltv -ltr, Ss~etlture 1`11a1e
- t, 1vG NatI~jmIJ Boa~rd. sui. k., IXin, C. JIMl I` l4,/levvKIU l ) f
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required hy the Provisions of ASME Code Section Xi I. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville. 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. IL 61242 Date:
07-08-2005 Sheet:
I of I Unit:
0 Pro(gram # 02-()86.02-107. 03-107. W.O. 00320899 RLpair Organizationi P.O. No.. Job No., etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Electromatie Valve, Class I
- 5. (a) Applicable Construction Code: USAS B31.I 1967 Edition, N/A Addenda. N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced. and Replacement Components:
Name of Name of MIfrs. Ser.
Nat'l Other Year Repaired.
ASME Component N11fr.
No.
Bd.
Identification Built Replaced. or Code No.
Replacement Stamped (Yes or
_ _ _N o)
Electromatic Relief Dresser Industries BK7063 N/A 0-Spare-V26 N/A Replacement No V a lv e I
_I_
I__
I__
- 7. Description of Work: Refurbished valve lAW WO.
- 8. Tests Conducted:
Hydrostatic El Pneumatic 0 Nominal Operating Pressure E Other :
Pressure _
psi Test Temp.
1
- 9. Remarks: None CERTIFICATE OF COMPLIANCE Wc ccrtil'y hat the statemcnts maidc in this report are correct and this replacement conl;brms to the ritcs of ASME Code.Section XI repair or replace'ment Type of Code Symbol Stamp N/A - CoinEd I OCl1R50 Am B. 0 A Proeram Certificate of Authorization No.
N/A Expiration Date N/A Signed j
J L
OA2
'6M s
vpve Date _
_2)
O2 S
0%kiAlier or OX ner's Desrigdecc Td I
CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board ofi Boiler and Pressure Vessel Inspectors and the State or Illinois
. and employed by IISB CT. of Connecticut have inspected thc componients described in ihis Owner's Rcpor durinig the period C6'6ti l/o 2-t, C7/IV/dS-. and state that to the hest onimy knowledge and belief the owner has performeid examilnations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code. Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty. expressed or implied. conicerniing the examinations and corrective measures described in this Owner's Report. Furthcrmore. neither the Inspector nor his employer shall he liahle in any manner Ior any personal injury or property damage or a loss of any kind arisingi from or connected with this inspection.
,14117 Commissions 1Lt 5, e Irlix r, Sii xurjtrr Nmir -
I,,.ia Sul e. t.1rms-gn I i'l.-rs.nPtivt, Date J,,,V, (.%'-
20();
° S
Date J1Li
(
20
FORMI NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT AS Required by the Provisions of ASMIE Code Section XI
- 1. Owner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. IL 61242 Date:
05/10/2005 Sheet:
I of I Unit:
I Program No.03-122. WO 00636986-01 Repair Organization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 4. Identification of System: Main Steam. Class I
- 5. (a) Applicable Construction Code: USAS 1331.1 1965 Edition.
N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda, N/A Code Case 6h Identification of Comnonents Renaired or Replaced. and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component M fr.
No.
Bd.
Identification Built Replaced. or Code No.
Replacement Stamped (Yes or Relief valve Dresser BK7063 NoA 1-0203-3D N/A Replacement No
- 7. Description of Work: Replace(d relief valve ANV WO
- 8. Tests Conducted:
Hydrostatic 5 Pneumatic 5 Nominal Operating Pressure E Other 5 Pressure _
psi Test Temp.
OF
- 9. Remarks:
None CERTIFICATE OF COMPLIANCE We certify that the statements made in this rerort are correct and( this replacement conforms to the riles of ASIE Co(le.Section XI repair or replacenent Type of Code Symbol Stamp N/A - E xelon Nuclear I OCFR5() App B. 0 A Program Certificate of Au ization No.
N/A Expiration Date N/A Signed l
rf r.c;7 C
R Crt Date U
)
2-3 20 n5 O~nur or OAner's Designee. Title CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State ot Illinois
. and employed hy IISB CT. of Coninecticut have inspected the components descrihed in this Owner's Report during the period it 1I to /3 to t(
'(o i
. an( state thalt to the hcst oli my knowledge anid heliel the owner hals perlormed examiiiationis anid taken corrective measures described in this O%%ncr's Report in accordance the requirements ot the ASMN1E Code.Section XI.
By signing this certificate. neither the inspector nor his employer makes any warranty. expressed or implied. concerning the examinations and corrective measurcs described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall be liable in any manner for any persotial injury or property daimag or a loss of any kind arising from or connected with this inspection.
-- 7:'
Commissions rL- /5-s[3
/
1I9MvtI.-Is S grUtWLe /
JNjihmat Mm.oid. Slte. t'nnimee..IIk b
l-wmv Date Z Z'?
20 C
FORNI NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenville. ll. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
7/13/2005 Sheet:
I of I Unit:
I Program No.03-123, WO 00636986 Repair Organi7ation P.O. No., Job No.. etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova. IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam, Class I
- 5. (a) Applicable Construction Code: USAS B31.1 1965 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component MI fr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Flange UNK.
N/A N/A 1-3035A N/A Repair No
- 8. Tests Conducted:
Hydrostatic 51 Pneumatic 5 Nominal Operating Pressure 5 Other 5 Pressure psi Test Temp.
'F
- 9. Remarks:
None CERTIFICATE OF COMPLIANCE Ve certify that ihe statements made in Ihis repor are correct and ihis repair conforms to the riles of ASIE Code.Section XI rcpair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR5( App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed
,er or'Owfr's r i Date DeIv7 2()te CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued hy the National Board of Boiler and Pressure Vessel Inspectors and the State or Illinois
.and employed hy IISB CT. of Connecticut have inspected the components described hil this Owner's Report during the period I//5s4!2 to C'7/,I/O,'.and state that to the hest of my knowledge aid beliel the owtier has performed examinlatiois anld taken corrective measures described in this Owner's Report in accordance the requirements oflthe ASNIE Code, Section Xl.
By signing this certificate, neither the inspector nor his employer makes any wvarranty. expressed or implied. concerning the examniatiois anid corrective measures described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall be liable in any manier for any personal injury or property daamage or a loss of any kind arising from or connected with this inspection.
/1.....
Commissions TZ / S r
t Date Jl StJl. PLLV a
- 2. 1d l
Skl.wwwot, Date
~ c A
20)°
FORMI NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMIENT As Required by the Provisions of ASIME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, I. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. IL 61242 Date:
05/10/2005 Sheet:
I of I Unit:
I Program No.03-126 WO 0X)640103 Repair Organitauion P.O. No., Job No.. etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 T) pe Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam. Class 2
- 5. (a) Applicable Construction Code: USAS B31.1 1967 Edition.
N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda. N/A Code Case
- 6. Identification of Components Repaired or Replaced. and Replacement Components:
Name of Name of MIlfrs. Ser.
Nat'l Other Year Repaired.
ASME Component Nifr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Steam line drain N/A N/A N/A I -3015C-3/4"-B N/A Replacement No
- 7. Description of Work: Removed an(l replaced rw-I A on 2' X /4" reducer JAW WO
- 8. Tests Conducted:
Hyldrostatic 2
Pneumatic [:
Nominal Operating Pressure S
Other 2 Pressure psi Test Temp.
OF
- 9. Remarks:
None CERTIFICATE OF COMPLIANCE WeV crtify tli tthe stateinctits malde ih this repor-t are correct al)nd this replacement cnforins to the tiles of ASME C(de. Section Xl repair or replacemnent Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR5() Ap B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed Sn t 6r gv,,r Date JvLl1 15' 20 0.5 V owt er or Ov ner's VAigneez.lie il c CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
. and employed hy IISB CT. of Connecticut have inspected the comipoeCIts described in this Owvners Report durinhg the period I/t
/03 to.C7/1 /o S. and state tha to tile best of Ily kno Iedge aid belief, theownier has perloricied exalniniatiionis an"d taken correctivc mcasurcs described in this Owner's Report in accordaice the requiremeinis oflhc ASME Codc.Section XI.
By signing this certificate. neither the inspector nor his cmplo)er makes any %karranty. expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall be liable in any manner lor any personal injury or property damagc or a loss of any kind arising Irom or connected with this inspection.
Commissions
-7'L /'f-O D%.teal U.. Sixe.J1.it Yilk iS 2.01 I 1_.114111 Date tY/S2()
OS
FORNI NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI I. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
7/9/200)5 Sheet:
I of I Unit:
I Program No.03-127 WVO 00640 1(01 Repair Organization P.O. No.. Job No.. etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova. IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam, Class 2
- 5. (a) Applicable Construction Code: USAS B l1.1 1967 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda. N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or N o )
Steam line drain N/A N/A N/A 1-3015D-3/4"-B N/A Replacement No p i p I
I_
_I_
_I__
- 8. Tests Conducted:
Hydrostatic 5 Pneumatic 5 Nominal Operating Pressure S Other 5 Pressure psi Test Temp.
OF
- 9. Remarks:
None CERTIFICATE OF COMPLIANCE We certily tihat the statements madc in this reportarecorrcct and this replacement conforis to the riles of AS.NIE Code. Scction Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed m
ek.
4,1; p
pv!j Date jvt4 I,,
20 o5 V
o *er of Owner's Desigifee.-Fitle -
CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Illinois
.and employed by IISB CT'. or Connecticut have inspected the components described in this Owner's Report during the period t/Z I /4 to it)C_7______
.i ad state that to the best of my knowledge and belief thc owier has performed examinationls and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code.Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty. expressed or implied. concerning the cxaminations and corrective measures described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
___________________________Commissions 7> /
kS D 4ate xt,-r Signatl N.i iiai Nurd. SLat, Itllht,
.11kJ L.,
(r 20 Ollll Dale L*C t y 20 C )5-
FORM NIS-2 OWNERS RE1'ORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section Xi
- 1. Owner:
Exelon Generation Company. LLC 4300 Winfleld Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
6-2-2005 Sheet:
I of I Unit:
I Program No.03-132 W.O. 00641321 Repair Organization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Main Steam, Class I
- 5. (a) Applicable Constniction Code: I1SAS B31.1 1967 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mlfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or N o )
Snubber Lisega 61290/42 N/A 1-3001 -C7 I N/A Replacement No
- 7. Description of Work: Replaced the load pin as required by the W.O.
- 8. Tests Conducted:
Hydrostatic 5 Pneumatic O Nominal Operating Pressure 5 Other 5 Pressure _
psi Test Temp.
°F
- 9. Remarks: None CElRTIFICATE OF COMPLIANCEI We certify that the statements made in this report are correct and this replacement contiormis to the rules of ASNIE Code. Section Xl rcpair or replacement Type of Code Symbol Stamp N/A - Fxelon Nuclear IOCFR5() App B. 0 A Program Certificate of Auk orization No.
N/A Expiration Date N/A Signed l_
Date Z20 Qo (01r or Owner's Designec. Itle CElRTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board ot Boiler and Pressure Vessel Inspectors and the State of Illinois
. and employed by IISR (.7. or Connecticut have inspected the comiponents described in this Owncr's Report during the period
/I/Z S /C to
/ 7/6.*
, and state that to the best ofl my knowledge and belief, the ovtner has performed examinations and taken corrective meastires described in this Owner's Report in accordance the requirements or the ASSME Code, Section Xl.
By signing this certificate. neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal hijury or property damage or a loss of any kind arising from or connected with this inspection.
'1';Sg 7 7
____________Comniissions
. t
/E(C Da Intie v.r. Sil.1Ijrc N.,tiy..I 13.ir.I. 51.,w. I'Sl7ll2L0.11k! T,,i.rwliiegil Date 2()
b
FORNI NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 Date:
Sheet:
Unit:
05/11/2005 I of I I
2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Program No.03-133, WO 00557469 Repair Organization P.O. No.. Job No., ctc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 4. Identification of System: Core Spray, Class 2
- 5. (a) Applicable Construction Code: USAS B331.1 1967 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of MNfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Relief Valve Dresser N/A N/A 1-1402-28B N/A Replacement Yes
- 7. Description of Work: Replaced Relief Valve lAW WO
- 8. Tests Conducted:
Hydrostatic a Pneumatic E5 Nominal Operating Pressure S Other 5 Pressure psi Test Temp.
OF
- 9. Remarks:
None CERTIFICATE OF COMPLIANCE N'e certify that the statements made in this report are correct and this replacement to the rules of ASIE Code.Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. Q A Prog ram Certificate of Au rization No.
N/A Expiration Date N/A Signed l
n g
Date Off ii 20 DS w er or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
, and employed by HSB CT. of Connecticut have inspected the components described in this Owner's Report during the period tt /e {oF to
/i2I'/o'
. and state that to thebestof my knowledge and belief, theownerhas performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASNIE Code.Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions 1 (5'YO
/Im~pctor%
Sigaure Nalknal B-urd, StIate. t'nwvine. aW Endrornent%
Date J'-
it 1/
20 OS
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACENIENT As Required by the Provisions of ASMIE Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 430() Winfield Road Warrenville. II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. IL 61242 Date:
5-30-2005 Sheet:
I of I Unit: 0 Program No.04-062. 05-003 WO 00677706 Repair Organization P.O. No.. Job No.. etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. II. 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Residual Heat Removal, Class 2
- 5. (aI) Applicable Construction Code:
ASNME Section Vill 1968 Edition, None Addenda, N/A Code Case (b) Applicable E(lition of Section Xl Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N4 16-2 Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of NMfrs. Ser.
Nat'l Other Year Repaired.
ASME Component Mfr.
No.
Bd.
Identification Built Replaced. or Code No.
Replacement Stamped (Yes or Floating Head Sweco N/A N/A Spare 0-H15 UNK.
Replacement No
- 7. Description of Work: Refurbished the floating head by welding and machinint as required by the WO.
- 8. Tests Conducted:
Hydrostatic El Pneumatic [1 Nominal Operating Pressure S Other 1
Pressure psi Test Temp.
OF
- 9. Remarks: VT-2 performed by WO 00685172-14 CERTIFICATE OF COMPLIANCE Weccrtily that the staitelments made in this report arc correct ald this replacement conforms to the riles of ASNIE Code.Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. O A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed 0-jj n E Pv
-D a
te jV 1
12-20()5 V
UnerorOwncrs
.eignee. Title CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued hy the National Board of Boiler and Pressurc Vessel Inspectors and the Statc of Illinois
.and employed by IISB CT. of Connecticut have inspected the components described in this Owner's Report during the period GS-/YA %
to
- 7/1G Jo
. and state that to the best of my knowledge and helief. the owner has performed examinations and taken corrective measures descrihed in this Owner's Report in accor(dance the requirement.;s of the ASME Code. Section Xl.
By signintg this certilicate. neither the inspector nor his employer makes any warranty. expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall he liable in any manner for any personal injury or property damage or a, loss of any kind arising from or connected with this inspection.
X/ %
Commissions I i l til'O D IV t /
s..,4t-r dSl N uqn, 1 ll.1 StatSe. i. k iuki I iIirwnk-ni D.IIC I'Jt, /(
20()
C5
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI I. Owner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenville. 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. IL 61242 Date:
7/7/2(X)5 Sheet:
I of I Unit:
0 Pr-ogram No.04-123. 04-061,04-068 WO(00510623 Repair Organizalion P.O. No., Job No., etc.
- 3. Work Pertfrmed by:
Quad Cities Generating Station 22710 206th Ave. North. Cordova, IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Spare Relief Valve, Class I
- 5. (a) Applicable Construction Code: USAS B3 I.1 1965 Edition. N/A Addenda. N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda. N/A Code Case
- 6. Identification of Components Repaired or Replaced. and Replacement Components:
Name of Name of
,'flrs. Ser.
Nat'l Other Year
- Repaired, ASNIE Component Mfr.
No.
13d.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or N o )
ERV Dresser BK-706()
N/A
()-Spare-V26 N/A Replacement No
- 7. Description of Work: Refurbished, repaired bolt hole. machined the inlet tlange face to the spare ElectromaticRelief Valve in accordance with the W.O.
- 8. Tests Conducted:
Hydrostatic 5 Pnetimatic 5 Nominal Operating Pressure a Other 5 Pressure psi Test Temp.
_ CF
- 9. Remarks: None CERTIFICATE OF COMPLIANCE We certily thalt the statements maide in this report are correct anld this replacement conilorins to the rules ol ASME Code. Sectionl Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR5() App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed A
Ep"LI
£4 P
,jvsr Date Jul1 &
20)O 5
- j/Q\\
ner or Owner's Desi necc.1 tIe CERTIFICATE OF INSERVICE INSPECTION I. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel inspectors and the State of Illinois
. and employed by IISB (1. of Connecticut have inspected the componenis descrihed in this Owner's Report during the period l
'/I7 /o V to
__/__/_
. aind state thatl to the best Of my klno ledge and heliel; the owner has perlormed examina;itionis anld taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code. Section Xl.
By signing this crtificate. icither the inspector nor his employer makes any warranty. expressed or implied. concerining thc examiniatiois and corrective mcasures described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall he liable in any maiiner for any personal injury or property damage or a loss of any kind arising from or coniected with this inspection.
Comm
'i'-
('omlissions 7
i-dId
- Date,
-na M-ad. Sule. Im, ime.ard I
__e nk-_nf 20 Date i-t~ Y.
y 2()
6<!>
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
05/1012005 Sheet:
I of I Unit:
I Program No.04-071, WO 00606987 Repair Organization 1'.0. No.. Job No., etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Reactor Piping, Class 2
- 5. (a) Applicable Construction Code: USAS B31.1 1965 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N-416-2 Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or
_ _N o)
Reactor Head Vent Sigma, Inc N/A N/A 1-0220-49 N/A Replacement No bypass valve I _
- 7. Description of Work: Replaced valve lAW WO
- 8. Tests Conducted:
Hydrostatic El Pneumatic El Nominal Operating Pressure 3 Other Ea Pressure psi Test Temp.
F
- 9. Remarks:
None CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement to the rules of ASME Code,Section XI repair or rep acement Type of Code Symbol Stamp N/A - Exelon Nuclear IOCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed 9+/-,
A2 Date Jo. 1 3
200 A/ q(wncr 6r 03 cr's W~signcc. Title CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
, and employed by IISB CT. of Connecticut have inspected the components described in this Owner's Report during the period csl/t /0 to e 7/,S AS, and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code, Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
_Commissions J/
trs Signatrue Njtimnal BMarJ. State. Prnmirwe, H Emdrmrcns Date J-. 1
/ b 20 Of
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI I. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville. II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
05/06/2005 Sheet:
I of I Unit:
I Program No.04-074, 04-075,05-006 WO 00573019 Repair Organization P.O. No., Job No., etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam, Class I
- 5. (a) Applicable Construction Code: USAS B31.1 1965
- Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or
_N o )
- Spare relief valve Dresser BK-7069 N/A N/A N/A Replacement No
- 7. Description of Work: Welded insert ring disc retainer plate and various external connections lAW W.O.
- 8. Tests Conducted:
Hydrostatic Dl Pneumatic El Nominal Operating Pressure El Other El Pressure psi Test Temp.
OF
- 9. Remarks:
None CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Code. Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Autl ori\\n No.
N/A Expiration Date N/A Signed I6e C
Th0,9,0 Date 171 G.
20 OS Own or9ner s Designee, Title CERTIFICATE OF INSERVICE INSPECTION I. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
, and employed by HSB CT. of Connecticut have inspected the components described in this Owner's Report during the period OSW/i 1' Y to Cd/'r/oS-
. and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASNIE Code. Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
______________A____
Commissions
/
Inap(ciors Signatu&
Njtimal &.ard. State.
Pnvinme. ndu Endo)remennt Date iAt;y /-
20 Or5_
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova, 11. 61242
- 3. Work Pertormed by:
Quad Cities Generating Station 2271 0) 206th Ave. North. Cordova. IL 61242 Date:
05/13/2005 Sheet:
I of I Unit:
I Program No.04-078 WO 00676648 Repair Organization P.O. No.. Job No.. etc Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Core Spray, Class 2
- 5. (a) Applicable Construction Code: USAS 1331.1 1967 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized tor Repairs or Replacements:
1995 Edition.
1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Nifrs. Ser.
Nat'l Other Year
- Repaired, ASME Component rVtfr.
No.
Bd.
Iclentiflication Built Replaced, or Code No.
Replacement Stamped (Yes or Relief Valve Various N/A N/A 1-1402-28B N/A Replacement No Flange
- 8. Tests Conducted:
Hydrostatic E Pneumatic 2 Nominal Operating Pressure E Other E Pressure psi Test Temp.
F
- 9. Remarks:
IR 351897 documents traceability issues with mtuds.
CERTIFICATE OF COMPLIANCE We certily thlt the statemenlts ma(le in this report ate correct and this replacement contilrms to the niles ol ASME 'Code. Section Xl retpair or replacmennt Type of Code Symbol Stamp N/A - Exelon Nuclear IOCFR5() App B. 0 A Proram Certiticate ol Authorization No.
N/A lExpiration Date N/A Signed jt_'
reel OovpDate Jvl 13 20 °5 V
%4'r or iner's Designe5 l1tle CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Illinois
.andemployed by I ISB CT. of connectictit have inspected the component;ts described in this Owner's Report during the period t; /2
/ '? to
. and state that to the best of my knowIcdge anid bcliel the owner has pertorniedl examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASNME Code. Section Xl.
By signing this certilicate. neither the inspector nor his employer makes any warranty. expressed or implied. concerning the examinations and corrective measures descrihed in this Owner's Report. Furthermore, neither the Inspector nor his employer shall he liable in any manner for any personal injury or property danliage or a loss of any kiid arising from or connected with this inspection.
Coininissions Df 1.-
/y0 In~lr~l~l~ltllXi
/
I N~~~Ji.11.11 I1,,jd. Slite. h-i,,
ke~.. nd I,)dlr-.,'.rI Mite Jtv
/5-o)
C2%
V1111111P -
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section Xi
- 1. Owner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova. IL 61242 Date:
05/06/2005 Sheet:
I of 3 Unit:
I Program No. Various, WO 00590943 Repair Organization P.O. No.. Job No.. etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North. Cordova, IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Control Rod Drive, Class I
- 5. (a) Applicable Construction Code: Component: ASME Section III 1965 Edition, W-1965
- Addenda, 1361 Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda. N/A Code Case
- 6. Identification of ComPonents Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
NatIl Other Year
- Repaired, ASME Component M fr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or SeeA tt._A T__
N o)__
- 7. Description of Work: Replaced Control Rod Drives and bolting IAW W.O.
- 8. Tests Conducted:
Hydrostatic O Pneumatic O Nominal Operating Pressure 3
Other 2 Pressure psi Test Temp.
'F
- 9. Remarks:
None CERTIFICATE OF COMPLIANCE We certify that the statements iiiade in this report are correct and tlis replacement coniforms to lle rtiles of ASME Code,Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Aut orization No.
N/A Expiration Date N/A Signed b
Date 2 014, 0 t (Dwer or bwner's Designee. Tlitle 1-CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned. holding a valid commission issued by the National Board ot Boiler and Pressure Vessel Inspectors and the State of Illinois
, and employed by HSB CT. of Connecticut have inspected the components described in this Owner's Report during the period e ;'/e2k to ic L/Z-t /C,. anid state that to the best of miy knowledge and belief. ihe ouner has perforiied examiatl;iiolis alid taken corrective measures described in this Owner's Report in accordance the requirements of the ASNtE Code,Section XI.
By signing this certificate. neither the inspector nor his employer makes any warranty, expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
A y
-I
/A -
C"ommssIC
_Commissions I
I
- nitt, 4
Nit... nal 11,mid.Slaic.
20o :' '
FORM NIS-2 OWNNERS REPORT OF REPAIR OR REPLACENMENT (Supplement)
As Required by the Provisions of ASME Code Section Xi
- 1. Owner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova. IL 61242 Date:
05/06/2005 Sheet:
2 of 3 Unit:
I Program No. Various, WO 00590943 Repair Orgainization P.O. No.. Joh No.. etc.
Type Code Symbol Stamp:
None
- 3. Work Performed by:
Quad Cities Generating Station Authorization No.:
None 22710 206th Ave. North, Cordova. IL 61242 Expiration Date:
N/A
- 4. Identification of System: Control Rod Drive, Class I
- 5. (a) Applicable Construction Code: Component: ASME Section III 1965 Edition, W-1965
- Addenda, 1361 Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case Attachment A Name of Name of Mlfrs. Ser.
Nat'l Other Year
- Repaired, ASME Program Component M fr.
No.
Bd.
Identification Built Replaced, or Code No.
No.
Replacement Stamped (Yes or No)
Control Rod Drive GE Nuclear S/N: 738C N/A 1-0300-18-47 N/A Replacement Yes04-081 Energy Control Rod Drive GE Nuclear S/N: 301 N/A 1-0300-30-31 N/A Replacement Yes04-082 Energy Control Rod Drive GE Nuclear S/N: A3410 N/A 1-0300-06-19 N/A Replacement Yes04-083 Energy Control Rod Drive GE Nuclear S/N:A8734 N/A 1-0300-30-19 N/A Replacement Yes04-084 Energy Control Rod Drive GE Nuclear S/N:888 N/A 1-0300-34-11 N/A Replacement Yes04-085 Energy Control Rod Drive GE Nuclear S/N: 1029 N/A 1-0300-34-27 N/A Replacement Yes04-086 Energy Control Rod Drive GE Nuclear S/N: A8544 N/A 1-0300-18-35 N/A Replacement Yes04-139 Energy l
Control Rod Drive GE Nuclear S/N: A5028 N/A 1-0300-34-47 N/A Replacement Yes04-140 Energy Control Rod Drive GE Nuclear SIN: A3630 N/A 1-0300-22-43 N/A Replacement Yes04-141 Energy Control Rod Drive GE Nuclear S/N: 886A N/A 1-0300-46-07 N/A Replacement Yes04-142 Energy Control Rod Drive GE Nuclear S/N: A8337 N/A 1-0300-18-15 N/A Replacement Yes04-143 Energy Control Rod Drive GE Nuclear S/N: 9144 N/A 1-0300-06-31 N/A Replacement Yes04-144 Energy Control Rod Drive GE Nuclear S/N: 8466 N/A 1-0300-30-43 N/A Replacement Yes04-145 Energy Control Rod Drive GE Nuclear S/N: 7563A N/A 1-0300-42-43 N/A Replacement Yes (4-146 Energy Control Rod Drive GE Nuclear S/N: A8759 N/A 1 1-0300-)3-03 N/A Replacement Yes04-147 Energy
I FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT (Supplement)
As Required by the Provisions of ASME Code Section Xl
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville. II. 60555 1
2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova, IL 61242 Date:
05/06/2005 Sheet:
3 of 3 Unit:
I Program No. Various. WO 00590943 Repair Organization P.O. No.. Job No., etc.
Type Code Symbol Stamp:
None
- 3. Work Performed by:
Quad Cities Generating Station Authorization No.:
None 22710 206th Ave. North, Cordova. IL 61242 Expiration Date:
N/A
- 4. Identification of System: Control Rod Drive, Class I
- 5. (a) Applicable Construction Code: Component: ASME Section III 1965 Edition, W-1965
- Addenda, 1361 Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case Name of Name of
'Mfrs. Ser.
Nat'l Other Year Repaired.
ASME Program Component M fr.
No.
Bd.
Identification Built Replaced, or Code No.
No.
Replacement Stamped (Yes or
_ _ _ _N o )
Control Rod Drive GE Nuclear S/N: A2568 N/A 1-0300-26-03 N/A Replacement Yes04-148 Energy Control Rod Drive GE Nuclear S/N: 120 N/A 1-0300-30-39 NIA Replacement Yes04-149 Energy Control Rod Drive GE Nuclear S/N: A5405 N/A 1-0300-38-27 N/A Replacement Yes04-151 Energy Control Rod Drive GE Nuclear SIN: A2465 N/A 1-0300-14-07 N/A Replacement Yes04-152 Energy Control Rod Drive GE Nuclear S/N: 64 N/A 1-0300-34-23 N/A Replacement Yes04-153 Energy
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
05/19/2005 Sheet:
I of I Unit:
I Program No.04-087 WO 00577389 Repair Organization P.O. No., Job No., ctc Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam, Class I
- 5. (a) Applicable Construction Code: ASME Sect. III 1965. 1968 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Safety Valve Consolidated Valve BK7156 N/A 1-02034C N/A Replacement No
- 8. Tests Conducted:
Hydrostatic :l Pneumatic El Nominal Operating Pressure 0 Other El Pressure psi Test Temp.
F
- 9. Remarks:
None CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Code, Section Xl repair or rcplacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 ApD B. 0 A Program Certificate of orization No.
N/A Expiration Date N/A Signed r-C*,
- ,J7 Date c3(03D2 Z-20L67 0Incr or Owncr's Designee. Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
, and employed by HSB CT. of Connecticut have inspected the components described in this Owner's Report during the period Y vVId oC to T/hd & -
and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASMIE Code, Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manier for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
.e-- g1 ?
A Commissions ji
/SI?9 Iiirmt.1rignature I
Nalmntal Said. Slatc. Pr,,vinm. and Endwwincnt%
Date
.JL Ly
/0 20 e 15.
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 WN'infield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
7/13/2005 Sheet:
I of I Unit:
I Program No.04-088 WO 00569449 Repair Organization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam, Class I
- 5. (a) Applicable Construction Code: ASME Sec. 111 1965. 1968 Edition, NIA Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component VI fr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Relief Valve Target Rock BK 7159 N/A l-0203-4D UNK.
Replacement Yes
- 8. Tests Conducted:
Hydrostatic a Pneumatic 5 Nominal Operating Pressure s Other 5 Pressure psi Test Temp.
°1
- 9. Remarks: IR 351445.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the niles orASME Code. Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 AVV B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed f.f Ad Date JA-t4 20zo V
qerbr Owner'sDesignee, Title CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
. and employed by HSB Cl'. of Connecticut have inspected the components described in this Owner's Report during the period e '1/y o to
_7__
_5_
. and state that to the best or my knowledge and belietf the owner has performed examinationis anid taken corrective measures described in this Owner's Report in accordance the requirements of the ASNIE Code.Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss or any kind arising from or connected with this inspection.
-_Commissions
'LI tY&l D te 1 eLCtra si u Nu i 20ll Ord.
State. ISm%
inc and Fndorwnk",
Date Jr. Iq I 20 c 5S
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
07/13/2005 Sheet:
I of I Unit:
1 Program No.04-089 WO 00577391 Repair Organization P.O. No., Job No., etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Main Steam, Class l
- 5. (a) Applicable Construction Code: ASME Sect. III 1965. 1968 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Safety Valve Consolidated Valve BK 7158 N/A l-02034H N/A Replacement No
- 8. Tests Conducted:
Hydrostatic El Pneumatic n Nominal Operating Pressure 0 Other E]
Pressure
_ psi Test Temp.
F
- 9. Remarks:
IR 351445.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Code,Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I 0CT7R50 App B. G A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed ao f Daft tr
-Date Jvl 14 20 O A/
c
~}Tzfor Owhncr's DL~igdce, Titld I
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
, and employed by HSB CT. of Connecticut have inspected the components described in this Owner's Report during the period 03t2<'/O S to 07/o0 /05-
, and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code, Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions TL ty'o imunta Sitnature Natizml Board. State. Ptimince, aid EndWrsewents Date J__, {
20 _Lr_
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASMIE Code Section XI
- 1. Owner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
07/13/2005 Sheet:
I of I Unit:
I Program No.04-090 WO 00577390 Repair Organization P.O. No.. Job No.. etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam, Class I
- 5. (a) Applicable Construction Code: ASME Sect. III 1965. 1968 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Safety Valve Consolidated Valve I BK6306 N/A 1-0203-4G N/A Replacement No
- 8. Tests Conducted:
Hydrostatic a Pneumatic a
Nominal Operating Pressure E Other 0 Pressure psi Test Temp.
1
- 9. Remarks:
IR 351445 documents discrepancies identified durinp the review of WO 577390 CERTIFICATE OF COMPLIANCE We certify that the statcments made in this reoxrt are correct and this replacement conforms to the rules ofASME Code, Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR5() Aoo B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed _________
______________Date j V4 20 0
\\;
OwroOwncr's Desigr~ce!Tille' CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
. and employed by IISB 1(. of Connecticut have inspected the componcnts described in this Owner's Report during the period Mehv to _______s_
. andstatethat tothe bestofmy knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASNIE Code. Section Xl.
By signing this certificate. neither the inspector nor his employer makes any warranty, expressed or implied. conceming the examinations and corrective measures described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions JL
)
/ DIa Itiire Njiil~t lI..l.
St.e, Iny. i r20.5 e n d I iW.rn n-Us Date JLL.I /'1
- 20) OS
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
01/21/2005 Sheet:
I of I Unit:
I Program No.04-091 WO 00588400-01 Repair Organization P.O. No., Job No., etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: High Pressure Coolant Injection, Class 2
- 5. (a) Applicable Construction Code: ASME Sec.VIII Edition, 1967 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Relief Valve Dresser TJI 1872 N/A 1-2301-23 N/A Replaced Yes Relief Valve Consolidated TN64205 N/A 1-2301-23 N/A Replacement Yes
- 7. Description of Work: Replaced the relief valve in accordance with W.O.
- 8. Tests Conducted:
Hydrostatic E]
Pneumatic El Nominal Operating Pressure E Other E]
Pressure psi Test Temp. -
'F
- 9. Remarks: IR293764 CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Code,Section XI repaior replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of A thorization No.
N/A Expiration Date N/A Signed 5J CX)QD.uAJrt)Z-Date
-_V1h M T;--/
ZI 20 of er or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Prcssure Vessel Inspectors and the State of Illinois
, and employed by HSB CT. of Connecticut have inspected the components described in this Owner's Report during the period lb/
o i
o 4 to tDI/Zs/5,-
,and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code,Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
a Jr Cnmm;cc;nnc 7L. / S*L 1--
Uil&^JI......
Ingfamin Sipututl Date A)l, a
National Bard, State. Pnvwnie, and Encrsnemnenti 20 A>
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
05/16/2005 Sheet:
I of I Unit:
I Program No.05-002 & 04-096 WO 00543620-02 & 03 Repair Organization P.O. No.. Job No., etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Standby Liquid Control, Class 2
- 5. (a) Applicable Construction Code: USAS B331.1 1967 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Trigger Assembly Contax Bufflow Corp.
123 N/A I -I 106A UNK.
Replacement No Inlet Plug Contax Bufnow Corp.
N/A N/A I-I 106A UNK.
Replacement No
- 7. Description of Work: Replaced the Trigger assembly and inlet plug in accordance with W.O.
- 8. Tests Conducted:
Hydrostatic a Pneumatic 0 Nominal Operating Pressure E Other 0 Pressure psi Test Temp.
F
- 9. Remarks: None CERTIFICATE OF COMPLIANCE ve certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Code,Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Autl ization No.
N/A Expiration Date N/A Signed I
r Date 2F 1
i8 20 0 w9xn\\
or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
, and employed by HSB CT. of Connecticut have inspected the components described in this Owner's Report during the period t4/i87/0Y to o-hrl/oS and state that to the bestofmy knowledge and belief, theownerhas performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code, Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
_Commissions SL /r0O fins 5ignatur Ngiiyln' Board.
Shate, hM'nie. and Endorwmnts Date /
'9, IX 20 O L
FORNI NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville. II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. IL 61242 Date:
07/13/2005 Sheet:
I of I Unit:
I Program No.04-097 WO 00673019 Repair Organization P.O. No., Job No.. etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North. Cordova. IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam, Class I
- 5. (a) Applicable Construction Code: ASME Sect. II 1980.1995
- Edition, 1980, 1996fi
- Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda. N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component M fr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Relief Valve Dresser BY94633 N/A 1 -0203-3B N/A Replacement No
- 8. Tests Conducted:
Hydrostatic D Pneumatic 5 Nominal Operating Pressure 3
Other 5 Pressure psi Test Temp.
'F
- 9. Remarks:
See Issue Report # 00351442 on Hvydranut installation CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to thc niles of ASIE Codc. Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 Apo B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed ________L ______
_ ___P_
V_ r Date JUH 13 20 05.
gX wner or Owner's DesgnL-e.ritle CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois and employed by HSB CT. of Connecticut have inspected the components described in this Owner's Report during the period J3/
12 o S to 7Ii- /6S
. and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASNIE Code. Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions 7-" I-i5g) llbxtill Si axleNalti bnl Mwxl, Slade.
P'n-6vie. amk EmJdrvmenvnt Date Jets1 /S-20 OS
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 1I. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova, IL 61242
- 3. Work Pertfrmed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
05/11/2005 Sheet:
I of I Unit:
I Program No.04-100.04-099,04-098. WO 00665516 Repair Organization P.O. No.. Job No., etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Main Steam, Class I
- 5. (a) Applicable Construction Code: USAS B3 1.1 1965 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Comnonents Repaired or Replaced, and Replacement Components:
Name of Component Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or
_ _ _N o )
Electmomatic Relier Valve Dresser BY94632 N/A Spare N/A Repair No Electroniatic Relief Valve Dresser BY94633 N/A Spare N/A Repair No Electrornatic Relief Valve Dresser BY94637 N/A Spare N/A Repair No
- 7. Description of Work: Upgraded welded connections by adding EPRI 2:1 weld slone to pilot/main drain lAW WO.
- 8. Tests Conducted:
Hydrostatic E Pneumatic E1 Nominal Operating Pressure Other D Pressure psi Test Temp.
OF
- 9. Remarks:
None CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Codc,Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 Ann2 B. Q A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed
_"f; L
Z FpP s5 r
Date 4'
20 VS JOl°ner or Owner's Desigce.T 1ile CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
, and employed by HSB CT. of Connecticut have inspected the components described in this Owner's Report during the period C/i'( /O (
to 7/1l /0 S
, and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code. Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions
.ri 9
/r14VtorSipC tc Nit "mal BWard. Stt:e. ft'wvinc. and Endorrent, Date J - by //
20 P5
FORMI NIS-2 OWNERS REPORT OF REPAIR OR REPLACENIENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road WVarrenville, ll. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
7/8/2005 Sheet:
I of I Unit:
I Program No.04-101, 04-102,05-047. 05-048 WO 00598434 Repair Organization P.O. No., Job No., etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Control Rod Drive, Class 2
- 5. (a) Applicable Construction Code: USAS B31.1 1967 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or
_ _ _ _N o)
Scram Discharge UNK.
N/A N/A 1-0300 North N/A Replacement No Volume Flanges and South
- 8. Tests Conducted:
Hydrostatic 2 Pneumatic E1 Nominal Operating Pressure 3 Other E Pressure psi Test Temp._ °F
- 9. Remarks:
None CERTIFICATE OF COMPLIANCE Vc ccrtify that the statements made in this report arc corrc t and tiis replacement Lo the ilcs of ASME Co<de, Scction XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed A6 441 e
!fo-r Date 1o 18 200S w
hn& orO Wrer's Desi nee, r, te CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinoic
. and employed by HSB CT, of Connecticut have inspected the components described in this Owner's Report during the period 0O31/o S-5 to 0'7/16/05
.and statc that to the best of my knowledgc anJ belief, the owner has pcrformed examinitions ind taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code. Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions NZ
/5 C7 Da vter Siglune N.Amal Nr. Male. Nwhwe. and Eso (6
- 20nt, Date
.J>ty 16 20 OS
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACENIENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North. Cordova, IL 61242 Date:
07/14/2005 Sheet:
I of I Unit:
I Program No.04-105 WO 00671613 Repair Organization P.O. No., Job No., etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Main Steam, Class I
- 5. (a) Applicable Construction Code: ASME Sect. III1980. 1995 Edition, 1980. 1996 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced. and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Relief Valve Dresser BY94637 N/A 1-0203-3D N/A Replacement No
- 8. Tests Conducted:
Pneumatic z Nominal Operating Pressure 3 Other C Pressure psi Test Temp.
F
- 9. Remarks:
See Issue Report #351422 for installation of Hydranuts. #352729 for installation of Valve and #352738 for omission of signature on Revision 2 to package.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report arc correct and this replacement conforms to the rules or ASME Code. Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed k-t4,e Per Date xivk 14 20(05 V
wnci or Ownenr's D S g~c,'1 itV CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
. andr employed by IISB CF. of Connecticut have inspected the components descrihed in this Owner's Report during the period Q J/1d/Oe-to 0>/
a
/0
,;1tnd state that to the best or my knowledge and belief, the owner ias performed examiniationis and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code. Section Xl.
By signing this certificate. neither the inspector nor his employer makes any warranty. expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
___Commissions vl)_
mflVKs wSigiultimc I, ximil tI-onl. S1.1c. Ineintc..mxl I miidorsenmcils Date GJLLy (6 20 S_
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- l. Owner:
Exelon Generation Company, LLC 4300 WVinfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
07/14/2005 Sheet:
I of I Unit:
I Program No.04-106 WO 00692313 Repair Organization P.O. No.. Job No., etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Reactor Vessel, Class I
- 5. (a) Applicable Construction Code: ASME Sect.I11 1965 Edition, Summer 1965 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Co ponents Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Reactor Head Various N/A N/A 1-0201 N/A Replacement N or
Hydrostatic M Pneumatic a
Nominal Operating Pressure E Other a Pressure psi Test Temp.
F
- 9. Remarks:
None CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to thc rules of ASME Code.Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 Apo B. O A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed m
Date j i i
20 Os V
Owner or Owner's Ddkighee.'I Itr CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
. and emplyd by ISB CT. of Connecticut have inspected the components described in this Owner's Report during the period It/e/ 4i Y to O 0t//{14 and state that to the best of my knowledge and belief. the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code,Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Date :j*
-4 Commissions jt tI t
m hlrst-orSignawfl~
.NatimJI Boar. State. Nnlince. andl Eirsement, Date yuly (6-2n0 5
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACENIENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
07/13/2005 Sheet:
I of I Unit:
I Program No.04-108 WO 00671614 Repair Organization P.O. No.. Job No., etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam, Class 1
- 5. (a) Applicable Construction Code: ASME Sect. III 1980. 1995 Edition, 1980. 1996f Addenda. N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda, N/A Code Case
- 6. Identification of Co ponents Repaired or leplaced. and R placement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Relief Valve Dresser BY94637 N/A I -0203-3C N/A Replacement No
- 8. Tests Conducted:
Hydrostatic E Pneumatic a Nominal Operating Pressure 0 Other E Pressure psi Test Temp.
°F
- 9. Remarks:
See Issue Report # 00351442 on Hydrantit installation CERTIFICATE OF COMPLIANCE We ccrtify that the statemcnts made in this report are correct and this replacement confiorms to thc nilcs of ASME Codc. Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear IOCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed nblA&
re, 1 P 4vPr6r Date Jv6 I l 20 OS U
- wneror Owner'.s Ddif iec.Tc I
a 4
CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel inspectors and the State of Illinois
. and employed by HSB CT. of Connecticut have inspected the components described in this Owner's Rcport during the period J/2 C Mr to 7/1/W/0-
. and statc that to thc best of my knowledge and belief, thc owncr has peroirmed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code.Section XI.
By signing this certificate. neither the inspector nor his employer makes any warranty. expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall he liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions 7z- (o-5 0 NJti
.,iU BJrd. Slate. Ivulirne. arnd 1In,,drenivnt, Date J4 t IS 20 OS-
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
07/14/2005 Sheet:
I of I Unit:
I Program No.04-109 WO 00671611 Repair Organization '.O. No.. Job No.. etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam, Class I
- 5. (a) Applicable Construction Code: ASME Sect. III 1980. 1995 Edition.
1980. 1996 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 199X Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced. and R placement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASMAE Component M fr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Relief Valve Dresser BK7070 N/A 1-0203-3E N/A Replacement No
- 7. Description of Work: Replaced Relief Valve and bolting (including Hydrantits) AW WO 8.TestsConducted:
Hydrostatic Cl Pneumatic E Nominal Operating Pressure 0 Other E0 Pressure psi Test Temp.
'F
- 9. Remarks:
See Issue Report #351422 for installation of Hydrantits. #352724 for installation of Valve.
CERTIFICATE OF COMPLIANCE eve certiy that the statemcnts made in this report are correct and this replacement conforms to the rules of AStE Code. Scction Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR5() App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed Date J
4 20 O5 owbe cor Uwncr's Desig e.' tic CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Illinois
. and employed by IlSB (CT. of Connecticut have inspected the components described in this Owner's Report during the period as/5ol/ds5 to
(,/'7/OV
,and state that to the best of my know ledge and belief. the owner has performed exam.iniations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASMIE Code.Section XI.
By signing this certificate. neither the inspector nor his employer makes any warranty. expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall he liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
-a26t Commissions zL. /(SCVO
/
In crr Sigiowlure NSjijl thiard. Stilk. 'i%
rincc. abl En& *rwrnk.ai Date
.L., is/
20 Cow
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North. Cordova, IL 61242 Date:
07/16/2005 Sheet:
I of I Unit:
I Program No. 04-l l l WO 99225959 Repair Organization P.O. No.. Job No.. ctc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Reactor Recirculation. Class I
- 5. (a) Applicable Construction Code: Pipe: USAS B31.1 1967. ASME-Sect. 11966 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N-504-2 Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Weld 02AD-F12 N/A N/A No 1-0202-A28A N/A Repaired No
- 7. Description of Work: Performed weld overlay lAW W.O.
- 8. Tests Conducted:
Pneumatic a Nominal Operating Pressure 3 Other a Pressure psi Test Temp.
'F
- 9. Remarks:
Refer to report VT2-195 and see Issue Report 352737 for package discrepancies.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this air conforms to the niles ofASME Code. Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed SVDate
[yD J
20
°5 J
(1 nr or Owner's Wlsighcc.Iife CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
. and employed by lISB CT. of Connecticut have inspected the components described in this Owner's Report during the period
_?/LZIZ_
4' to
_'___6____
, and state that to the best ofmy knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code.Section XI.
By signing this certilicate. neither the inspector nor his employer makes any warranty. expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions e
t Iiil toi~ri~
5 arc JR I I
INj6,sI It Murd. State. huY a ikc. az rrJ,rwtnIetis Date I.. 1
/6 20 05£
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville. 11. 60555 Date:
07/16/2005 Sheet:
I of I Unit:
I 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Program No.04-112 WO 99225960 Repair Organization P.O. No.. Job No.. ctc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Reactor Recirculation, Class I
- 5. (a) Applicable Construction Code: Pipe: USAS B31.1 1967. ASME-Sect. 1 1966 Edition.
N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N-504-2 Code Case
- 6. Identification of Co ponents Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Weld 02BS-F4 N/A N/A No 1-0202-B28A N/A Repaired No
- 7. Description of Work: Performed weld overlay TAW WO.
- 8. Tests Conducted:
Hydrostatic E3 Pneumatic a Nominal Operating Pressure 3 Other 5 Pressure psi Test Temp.
OF
- 9. Remarks:
See Issue Report 352737 for nackage discrepancies.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this repair conforms to the niles of ASNIE Code. Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 Ann B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed (bsit 472 t
Date J_ ly 2005 CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
. and employed by IISB CT. Of Connecticut have inspected the components described in this Owner's Report during the period (a/"z/o C/
to CV/1/blO
.,anid state that to the bust of my knowledge and belief, the owner has performed examinations anld taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code. Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty. expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
I, Commissions 2' IrfaO D N.atier Si lure Nxil2l 0rd0.
Slle. ivime. and UJuh rwnwill Date JZ,,(,Y t6 20 OF6
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
05/11/2005 Sheet:
I of I Unit:
I Program No.04-118 WO 00686220 Repair Organization P.O. No.. Job No.. etc, Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Reactor vessel, Class I
- 5. (a) Applicable Construction Code: USAS B331.1 1967 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section Xi Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Co ponents Repaired or Replaced, and R placement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Decon Flanges Various N/A N/A 1-0202 N/Replacement No
- 8. Tests Conducted:
Hydrostatic E]
Pneumatic El Nominal Operating Pressure 0 Other El Pressure psi Test Temp.
F
- 9. Remarks:
None CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules or ASME Code, Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. Q A Program Certificate of Aut rization No.
N/A Expiration Date N/A Signed opr54
'*&TrZ Date
)A-1Z 20 l)5O cter or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
, and employed by HSB CT. f Connecticut have inspected the components described in this Owner's Report during the period D /tZ4o M to 0
f and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code. Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damag or a loss of any kind arising from or connected with this inspection.
,VZk Commissions Adz TSgO Dapte o2n si0lte Natininl Ward. State. ti'vimue.
and Emkirtments Date J"L' / t-20
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
6/23/2005 Sheet:
I of I Unit:
I Program No.04-131 & 04-134 WO 00632759 Repair Organization P.O. No., Job No.. etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Feed Water, Class 1
- 5. (a) Applicable Construction Code: USAS B31.1 1967 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Check Valve Crane N/A IN/A I
-0220-58A N/A Replacement I
No
- 7. Description of Work: Weld build up and machined on the valve body seating area and replaced the trim set in accordance with W.O.
- 8. Tests Conducted:
Hydrostatic E Pneumatic D Nominal Operating Pressure 5 Other 0 Pressure 43.9 psi Test Temp. N/A 'F
- 9. Remarks: Performed Appendix J Test.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASNIE Code,Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Proigram Certificate of A horization No.
N/A Expiration Date N/A Signed
' 0:cr y.
P;b Date J
_YZ' Zap 20 VT7 tnt~eor Owner's Lkcsignee, Title CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
. and employed by FISB CT. of Connecticut have inspected the components described in this Owner's Report during the period
,'Z o 4/' Y to tt/3 7/CS
, and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code,Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
L d Commissions d /j VO Date Sipture Niinal Board, S7 0e.
Prmine and Fix&minm.
Date I u,,c Z#
20
FORMI NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMIENT As Required by the Provisions of ASNIE Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 WVinfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
6/23/2005 Sheet:
I of I Unit:
I Program No.04-132 & 04-133 WO 00466432 Repair Organization P.O. No., Job No.. etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Feed Water, Class I
- 5. (a) Applicable Construction Code: USAS B31.1 1967 Edition, _N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda. N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component M fr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Check Valve Crane N/A N/A 1-0220-58B N/A Replacement No
- 7. Description of Work: -Weld build utp and machine on the valve body seating area and replaced the trim set in accordance with W.O.
- 8. Tests Conducted:
Hydrostatic S Pneumatic 5 Nominal Operating Pressure El Other 2 Pressure NLA psi Test Temp. N/A 'F
- 9. Remarks: Appendix J Testing by WO 466432-03 CERTIFICATE OF COMPLIANCE Ve certify that the statements made in this report are corrct and this replacement conforms to the rules of ASNIE Code Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of u\\orization No.
N/A Expiration Date N/A Signed fI' C a04R-,Wt71C Date
~)
t-I 200
- v. sr or Owner s Designee. Title CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois and employed by HSB CT. of Connecticut have inspected the components described in this Owner's Report during the period AZtAY-to
__t__________
, and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code,Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
.TA wimO Date JazzA e Z-7 20 6S7 Date JA
- 17 20 6S
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
05/09/2005 Sheet:
I of I Unit:
I Program No.04-136 WO 00452546 Repair Organization P.O. No.. Job No.. etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam, Class I
- 5. (a) Applicable Construction Code: ASA B31.1 1955 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mlfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Inboard MSIV plug Crane-Aloyco Inc.
UNK.
N/A AO 1-0203-IA N/A Replaced No assem b ly
- 7. Description of Work: Replaced plug assembly in accordance with W.O.
8.TestsConducted:
Hydrostatic E]
Pneumatic 5 Nominal Operating Pressure a Other 3
Pressure 43.9 psi Test Temp.
OF
- 9. Remarks:
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Code.Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear IOCFR5() Anp B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed
-(;h 7
C
'=>-t Date Ad1oA&
I D 20 C.L5 Owncr r ~wner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
,and employed by IISB CT. of Connecticut have inspected the components described in this Owner's Report during the period 1//,O/oe/
to C6 /ba /
, and state that to the best of my knowledge and belief. the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code,Section XI.
By signing this certificate. neither the inspector nor his employer makes any warranty, expressed or implied. conceming the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
A Commissions
'L //S
)
/Dit spe.Mr ignatur Niil~fl 13,cird. S(02e.
MmineaW E(0w2me0t, Date eJam c 1 0 20
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section Xi
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
07/06/2005 Sheet:
I of I Unit:
I Program No.04-137 WO 00448534 Repair Organization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam, Class I
- 5. (a) Applicable Construction Code: ASA B31.1 1955 Edition, N/A Addenda. N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda. N/A Code Case
- 6. Identification of Components Repaired or Replaced. and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification B uilt Replaced, or Code No.
Replacement Stamped (Yes or
_N o)
Main Steam Crane-Aloyco Inc.
N/A NA AO I-0203-2D N/A Replacement No Isolation Valve
- 7. Description of Work: Replaced plug assembly in accordance with W.O.
- 8. Tests Conducted:
Hydrostatic E Pneumatic a Nominal Operating Pressure 5 Other Z Pressure 43.9 psi Test Temp.
OF
- 9. Remarks:
Appendix J Testing WO 00448534.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASNIE Code. Section Xl rcpair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 Ann B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed(
d(kJ\\- t I
Add Fich e ejRtk Date July 7 20 O5 V VwncrorOwner'sDdsigncee.'tie1 CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
. and employed by IISB CT. or Connecticut have inspected the components described in this Owner's Report during the period
/t /or/e /
to 7/Il /o
., and state that to the best of my knowledge and beliel; the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASNIE Code.Section XI.
By signing this certificjte. neither the inspector nor his employer makes any warranty. expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall he liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions_
Dateknl J
r.U 0S __le
_ine.
in_ Umlirnni Date J b
{20 45-
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, ll. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
07/16/22005 Sheet:
I of I Unit:
I Program No.04-154 WO 00688892 Repair Organization P.O. No., Job No., etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam, Class 2
- 5. (a) Applicable Construction Code: USAS B31.1 1967 Edition, N/A Addenda. N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda. N-416-2 Code Case
- 6. Identification of Co ponents Repaired or Replaced, and R placement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or
_ _ _N o )
Steam Line Drains Consolidated Power N/A N/A 1-30071B-1.5 N/A Replacement No I _I_
Supply I
II
- 8. Tests Conducted:
Hydrostatic 01 Pneumatic E Nominal Operating Pressure E Other E Pressure psi Test Temp.
OF
- 9. Remarks:
IR# 353809 issued.
CERTIFICATE OF COMPLIANCE Ve certify that the statcments made in this report are correct and this replacement conforms to thc nilcs of ASME Cod.c Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear IOCFR50 App B. O A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed
~
I Date
\\pJ
/po Date Jo 2 n Oqner or Owner's lksiheE.
nIle/
CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
. and employed by IISB CT. of Connecticut have inspected the components described in this Owner's Report during the period t4 '0
/of to 7/14 /eS
, and state that to the best of my knowIcdgc and belic; the owier has performed cxaminations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code. Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty. expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
's...
.W 2 6' Commissions d/Z /S'SZ)
Diate Jtk rIJI O...,rd. Si20. i'n.iltte. a05 Enreiv'nt Datce
.. (L-v'
/6 20 C>
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
05/11/2005 Sheet:
I of I Unit:
I Program No.04-155 WO 00688888 Repair Organization P.O. No.. Job No., etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Main Steam, Class 2
- 5. (a) Applicable Construction Code: USAS 1331.1 1967 Edition, N/A Addenda, NIA Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Co ponents Repaired or Replaced, and R placement Components:
Name of Name of NMfrs. Ser.
Nat'l Other Year
- Repaired, ASMIE Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or N o )
Steam Line Drains Consolidated Power N/A N/A I1-3007D-1.5 N/A Replacement No I_
Supply
- 8. Tests Conducted:
Hydrostatic E]
Pneumatic El Nominal Operating Pressure 0 Other E Pressure
_ psi Test Temp.
'F
- 9. Remarks:
None CERTIFICATE OF COMPLIANCE We certify that the statemcnts made in this report are correct and this replacement conforms to the rules of ASME CodeSection Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFRso App B. 0 A Program Certificate of Au rization No.
N/A Expiration Date N/A Signed I
Z e --InmA (
Z Date 2 0 a,
20 Z L ner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
, and employed by HSB CTof Connecticut have inspected the components described in this Owner's Report during the period
..L/f 7Z4S to
____L,_S__
, and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code. Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty. expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
11,1 - 4' 1 Y~
om isson
- 71(
Yt
~Corrinissions.
7LC t5-Y6 In~rdt~r, SivNatuf -
17.Date-(A At
.,/
N.diorul B-ord:.%Stjle. RIamie. "Lun",dr~enx-nt
FORMS NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
07/16/2005 Sheet:
I of I Unit:
I Program No.04-156 WO 00688889 Repair Organization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam, Class 2
- 5. (a) Applicable Construction Code: USAS B31.1 1967 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or N o )
Steam Line Drains Consolidated Power N/A N/A 1-3007C-1.5 N/A Replacement No I
_I Supply
- 8. Tests Conducted:
Hydrostatic 5 Pneumatic 5 Nominal Operating Pressure 0 Other a Pressure psi Test Temp.
'F
- 9. Remarks:
IR# 353809 issued.
CERTIFICATE OF COMPLIANCE We certify that thc statements made in this report are correct and this replacement conforms to the ilcs of ASIE Code.Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed
/
p i,
A Date j vly I
le 2005 0*
Oer or'Owvner's Dusigmt, Title 7y CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinoi
. and employed by IISB CT. of Connecticut have inspected the components described in this Owner's Report during the period (lI /o to
.,and stale that to the best of my knowledge and belief the owner has perfonned examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code. Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty. expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
ommissions Z4/ /37'0 DateNall lk Ant State Pnime. a2d Undthmenri20 Date A
s /2()
0
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
07/15/2005 Sheet:
I of I Unit:
I Program No.04-157 WO 00688893 Repair Organization P.O. No.. Job No., etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam, Class 2
- 5. (a) Applicable Construction Code: USAS B31.1 1967 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or
_ _N o)
Steam Line Drains Consolidated Power N/A N/A 1-3007A-1.5 N/A Replacement No I_
Supp y I_
- 8. Tests Conducted:
Hydrostatic 51 Pneumatic E Nominal Operating Pressure E Other a Pressure psi Test Temp.
OF
- 9. Remarks:
IR# 353183 CERTIFICATE OF COMPLIANCE W ccrtify that the statements madc in this rcport arc correct and this replacement conforms to the rules of ASME Codc. Scction XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed Ijk oel?
rf Date JvIA 15 2005O V °ncr ir Ownc-r'sDesig rticalie I
CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
. and employed by HSB CT. of Connecticut have inspected the components described in this Owner's Report during the period
&1i0-7iZ /Sto ei
, and state that to the best of my knowledge and belief, the owner has performed examinations anid taken corrective measures described in this Owncr's Report in accordance the requirements of the ASMIE Code, Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
At___
__ _Commissions Ar TO Daittetil NJti-wiI*d. tn ince.aw rnd,,ri,.20,^
Date 1Judy 20 O -5
FORNI NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 WVinfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
05/03/2005 Sheet:
I of I Unit:
I Program No.04-159 WO 00493719-07 Repair Organization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Core Spray, Class 2
- 5. (a) Applicable Construction Code: USAS B31.1 1967 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements: 1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or N o)
Check Valve UNK.
UNK.
UNK.
1-1402-8B UNK.
Repaired UNK.
- 7. Description of Work: Repaired check valve guides in accordance with W.O.
- 8. Tests Conducted:
Hydrostatic El Pneumatic El Nominal Operating Pressure El Other a Pressure psi Test Temp.
OF
- 9. Remarks:
None CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this reoair conforms to the rules of ASME Code,Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of A thorization No.
N/A Expiration Date N/A Signed
.SX C.
-. JY ftrzrr Date rn f q
1 20 0.6 0er or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
, and employed by HSB CT. of Connecticut have inspected the components described in this Owner's Report during the period e/la C
/01-to c?
, and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASNIE Code,Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
- a. L -I __ _
_ _ _ __ _ _ _ _Commissions
,Z- /5-*o ID efit. Sig/ut Na20 ma l Boans. Ste
$cmvince.
ard EndC'r
$enwnts Date l1c
/5 20 a {,
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
05/26/2005 Sheet:
1 of I Unit:
I Program No.05-004 WO 00578474 Repair Organization P.O. No., Job No., etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Main Steam, Class 1
- 5. (a) Applicable Construction Code: ASME Sect. 1968 Edition, Winter 1968 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case f; TAnt-fir-#inn
-f (Dnmrr-At
-Ani~
n-o
-~twet
-un
-~io t r
-mn.tc-1U.
AUIU*LilltOL1UAU U&
11JAUIIIW sx..
lL.u C
U Usp U5,t_ l AIIU z
'lh5lIlt
.tlSla*AL3._
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or N o )
Safety-Relief Target-Rock 225 N/A 1-0203-3A N/A Replacement No V a lv e I
_I_
- 7. Description of Work: Replaced valve, studs and HydraNuts lAW WO.
- 8. Tests Conducted:
Hydrostatic El Pneumatic Cl Nominal Operating Pressure 0 Other 0 Pressure _
psi Test Temp.
'F
- 9. Remarks:
None CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Code,Section XI repair or replcement Type of Code Symbol Stamp N/A - Exelon Nuclear 10CFR50 App B. 0 A Program Certificate of Author tion No.
N/A Expiration Date N/A Signed oa t
eate
)A-2 20 of
!forywner's Designee, Tile CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Ilinois.
and employed by HSB CT. of Connecticut have inspected the components described in this Owner's Report during the period CSI2VIOSY to CS-6/OS-,and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code,Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
e1,.- -
Commissions Ax 15C' Iwspectorn Ssg Nsaknal Borud.
Staie.
PImvince. and Erndorwnts Date
&AY Z&O 20 to 5
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
07/13/2005 Sheet:
I of I Unit:
I Program No.05-013, 05-014, WO 00685172 Repair Organization P.O. No., Job No., etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Residual Heat Removal, Class 2
- 5. (a) Applicable Construction Code: ASME Sect. VIII 1965 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N-416-2 Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Floating Head, Various N/A N/A I-1003-B N/A Replacement No Heat Exchanger I
I I
I _
- 8. Tests Conducted:
Hydrostatic n Pneumatic El Nominal Operating Pressure 3 Other 2 Pressure psi Test Temp.
F
- 9. Remarks:
None CERTIFICATE OF COMPLIANCE We ccrtify that the statements made in this report are correct and this replacement conforms to thc rules of ASME Code, Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear IOCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed q
v\\ t, J5:1 Fen 6vWoc Date 4
IV, 20O S V
Owder or Owner's Decsig
'itleJ II CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
,and employed by HSB CT f Connecticut have inspected the components described in this Owner's Report during the period OZAŽ71o sZ to 0 7//C" oC~, and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code.Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
__ 4 Commissions 74 C5J10 lanprmtos S natume Namian4 Baird. Stae. I'nmvinLe.
and Endor'envnts Date cJ C ( y / 60 20 Zedor5 Date jgAL//6 20
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
06/24/2005 Sheet:
I of I Unit:
I Program No.05-015 WO 00590943 Repair Organization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Control Rod Drive, Class I
- 5. (a) Applicable Construction Code: Component: ASME Section III 1965 Edition, W-1965
- Addenda, 1361 Code Case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda, N/A Code Case
- 6. Identification of Co ponents Repaired or Replaced, and R placement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Control Rod Drive GE Nuclear Energy SIN: 575 N/A 1-0300-26-27 N/A Replacement Yes
- 7. Description of Work: Replaced flange bolting in accordance with the W.O.
- 8. Tests Conducted:
Hydrostatic El Pneumatic E]
Nominal Operating Pressure El Other El Pressure _
psi Test Temp.
'F
- 9. Remarks:
None CERTIFICATE OF COMIPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Code,Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed
<s:c c on' t Date t
N-w<
20 Z-n or Owner's Designee. tit I CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of
- Illinois, and employed by HSB CT. of Connectieut have inspected the components described in this Owner's Report during the period CZ/Z7/0'- to
_6____1__
.and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code,Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
'i-Commissions Jt /IS 0o DaN.tiel Numi. Swic. Prl imv. all Emlwse i20 Date ad t"A c~
V 20 M~;
FORMI NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
7/15/2005 Sheet:
I of I Unit:
I Program No.05-023. WO 00613959 Repair Organization P.O. No.. Job No.. etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Reactor Recirculation, Class I
- 5. (a) Applicable Construction Code: USAS B31.1 1965/1968 Edition.
N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Nifrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced. or Code No.
Replacement Stamped (Yes or
_ _ _N o )
Recirculation Borg-Warner 661 S 1161/4 N/A1
-0202-B N/A Repaired No P u m p I__
- 7. Description of Work: Overbored damaged casing thread holes TAW WO.
- 8. Tests Conducted:
Hydrostatic 0 Pneumatic z Nominal Operating Pressure 2 Other E]
Pressure psi Test Temp.
OF
- 9. Remarks:
None CERTIFICATE OF COMPLIANCE
\\Ve ccrtify that the statemcnts mae(l in this report arc correct and this repair to the ules of ASMtE Code. Scction Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 ADD B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed 14 ;
gv Date t)vy I(o 200 Ownet'dorwner's Do i ace, Til IF CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
. and employed by ItSB Cl7. of Connecticut have inspected the components described in this Owner's Rcport during the period 07bs-/es£ to 471/ol/ds
. and state that to the best of my knowledge and belief, the owner has perfoirmed examinations and takcn corrective measures described in this Owner's Report in accordance the requirements of the ASME Codc.Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
HAL___
Commissions St /5TO 1D1t veigrure al thard
- 2.
Sta te. I'm0ie. jiki ISdore sn Dale Jut L y /.
20 0 S-
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI I. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
7/14/2005 Sheet:
I of I Unit:
I Program No.05-024, WO 00613959 Repair Organization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Reactor Recirculation, Class I
- 5. (a) Applicable Construction Code: ASME Section III 1965/1968 Edition, N/A Addenda. N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mifrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or
_ _N o)
Recirculation Borg-Warner 661 S 1161/4 NIA 1-0202-B N/A Replacement No
- 7. Description of Work: Replaced rotating assembly (containing pressure retaining parts) and bolting 1AW WO
- 8. Tests Conducted:
Hydrostatic a Pneumatic M Nominal Operating Pressure 0 Other El Pressure psi Test Temp.
OF
- 9. Remarks:
IR 352210 CERTIFICATE OF COMPLIANCE We certify that the statements made in this report arc correct and this replacement to the nles of ASME Code.Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed 0AA9 Ad Pul 5s-V Date J. Ik 14 200'S I;
owvner or Ow~ner's Deignee. Tlet I
CERTIFICATE OF INSERVICE INSPECTION I. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois. and employed by IISB CT. of Connecticut have inspected the components described in this Owner's Report during the period L9;A&/Cs to
_/7//&./W
. and state that to the best of my knowledge and belief. the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASNIE Code,Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty. expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
__Commissions
_r isVO Date I
(6 xt0S 03 Nalimal dBard.statc. in am rndrcnwnt Dalte ty 1G 20
°f
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section Xi
- 1. Owner:
Exelon Generation Company. LLC 4300 Winfield Road Warrenville, Il. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
07/14/2005 Sheet:
I of I Unit:
I Program No.05-025 WO 99042806 Repair Organization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Main Steam, Class I
- 5. (a) Applicable Construction Code: USAS B331.1 1967 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Snubber Load Pin Exelon N/A No 1-3001-A58 N/A Replacement No
- 8. Tests Conducted:
Hydrostatic E Pneumatic C Nominal Operating Pressure 0 Other C Pressure psi Test Temp.
`F
- 9. Remarks:
None CERTIFICATE OF COMPLIANCE WVe certify that the statements madc in this report arc correct and this replacement conlorms to the rules of ASN1E Code, Section Xl repair or replacemient Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. O A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed UA
,r4 e
has) 5tup'.
Date JV
.!j 14 2005 O}wncr ovnrDwirs csifnec'1illc CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois - and employed by HSB CT. of Coinecticut have inspected the components described in this Owner's Report during the period C,)J/tf(OS to C72s5iO7/
-. and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of thc ASME Code,Section XI.
By signing this certificatc. neither the inspector nor his employer makes any warranty. expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of aniy kind arising from or connected with this inspection.
A_ _ _
-__ Commissions egi /5Y
° fitte t tcJ sintSu-I-N20i IIWI B
-Suir, Imrince0 aM F t"nenwm Date J,,tf 1-20 C) S
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
7/9/2005 Sheet:
I of I Unit:
I Program No.05-028, 05-046 WO 00784532 Repair Organization P.O. No., Job No.. etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Reactor Vessel, Class I
- 5. (a) Applicable Construction Code: USAS B31.1 1967/ASME Section 11965 Edition, N/A/Summerl 966 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N-416-2 Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Flange UNK N/A N/A 1-0263 N/A Replacement No
- 8. Tests Conducted:
Hydrostatic E Pneumatic El Nominal Operating Pressure 0 Other E Pressure psi Test Temp.
'F
- 9. Remarks:
None CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement to the rules of ASME Code, Section Xl repaior replacement Type of Code Symbol Stamp N/A - Exelon Nuclear IOCFR50 Ann B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed Ay.. e g
S"U.-
w%^
rDate Jv 31 20O5 V
Oner or Owndr's Destgnet, Tflel CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
.and employed by HSB CT. of Connecticut have inspected the components described in this Owner's Report during the period 0T1/23 /o0z to tr7/I)/sOr and state that to the bestofmy knowledgeand belief, theownerhas performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code, Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions
_/i tiY O inDatre Signtu Naional Board. State.
Jta.iL.
aW Erd520ment Date J w L- /3 20 65-
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACENIENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, It. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
05/14/2005 Sheet:
I of I Unit:
I Program No.05-030, WO 00795331 Repair Organization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Feedwater, Class I
- 5. (a) Applicable Construction Code: USAS B31.1 1967 Edition.
N/A
- Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or
_ _ _N o )
Cheek Valve Crane Nova 159262101 N/A
[
-()220-62A N/A Replacement No I MachineProducts I
- 7. Description of Work: Replaced liner and trim TAW WO.
- 8. Tests Conducted:
Hydrostatic El Pneumatic E Nominal Operating Pressure E Other Z Pressure 43.9 psi Test Temp.
OF
- 9. Remarks:
Appendix J Local Leak Rate Test comnleted per OCTS 0600-07: JR 00353449.
CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this renlacement to the rules of ASME Code.Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 Apr B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed StA J LJ(kY K F,=
Date J Iy 1
20 a5 is Q
Cncr'or Oufter' Desi1.n#A,. TitcJ CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
, and employed by HSB CT. of Connecticut have inspected the components described in this Owner's Report during the period 3Ut 7 10 S-to
__7________,
and state that to thc best of iy knowlcdge and belie E.the owner has prtormed examilinations and taken corrective measures described in this Owner's Report in accordance the requirements or the ASME Code.Section XI.
By signing this certificate. neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owvier's Report. Furthermore. neither the Inspector nor his employer shall be liable in any mamier for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
.//4^
/'
Commissions CJL.t Y
leapt. ;igwtI~~n~are /
w.Njxi:nI fhirJ. Sife.
niZke. Jbk)
ELndwrr n-Iel, Date i kc ts 20 05-
FORNI NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, 11. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
7/16/2005 Sheet:
I of I Unit:
I Program No.05-033, WO 00379905 Repair Organization P.O. No.. Job No.. etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Residual Heat Removal, Class I
- 5. (a) Applicable Construction Code: USAS B331.1 1967 Edition, N/A Addenda. N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda, N/A Code Case
- 6. Identification of Co ponents Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Snubber Pacific Scientific TL99324 N/A 1-1012-B8 N/A Replacement No
- 8. Tests Conducted:
Hydrostatic a Pneumatic a
Nominal Operating Pressure a
Other E Pressure psi Test Temp.
'F
- 9. Remarks:
None CERTIFICATE OF COMPLIANCE Ve certify that the statements made in this report rre correct and this replacement to the ilcs of ASME Code. Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear 10CF1R5() App B. Q A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed v &ALI.o s,
Date VJt y io 20 Va Olyner or ofter s N-gig
. Titli CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned. holding a valid commission issued by the National Board or Boiler and Pressure Vessel Inspectors and the State of Illinois
. ani emplo ed by tISB ClT. of Connecticut have inspected the components described in this Owner's Report during the period 67 7/7 u /or to d
byo
.and state that to the best of my knowlcdgc and belief. the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code. Section Xl.
By signing this certificate. neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manmier for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
&'-~/
i.16-yoY ICommissions
/Ghcabrsl
,Sign>,ur, I
Nalinul &%trd. Sule. Pn.vince. and L",mment, Date
.ALV
/A 20 CS-Date rL.LV /4 20 0S
FORNI NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North. Cordova, IL 61242 Date:
07/14/2005 Sheet:
I of I Unit:
I Program No.05-037. WO 00795495 Repair Organization P.O. No.. Job No.. etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Main Steam, Class I
- 5. (a) Applicable Construction Code: USAS B3 1.1 1967 Edition.
N/A Addenda. N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition.
1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced. and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'I Other Year
- Repaired, ASME Component Ivifr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Flued Head Anchor Various N/A N/A I I-I6(X)-XO7B N/A Replacem'ent No
- 8. Tests Conducted:
Hydrostatic D Pneumatic 5 Nominal Operating Pressure 5 Other 5 Pressure psi Test Temp.
'F
- 9. Remarks:
None CERTIFICATE OF COMPLIANCE WVe certify that the statements made in this report are correct and this replarcement to the nibs of ASME Code. Scction XI repair or rcptcempLnt Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed A
Aft Vp Date Jv Ii 20 05 A/Owntro6r Cner'si esNignec.'Title I
CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois and employed by I ISB CT. of Connecticut have inspected the components described in this Owner's Report during the period
'"V/ /C$'
to 7//3y_6,
and state that to the best of my knowledge and belicf: the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code.Section XI.
By signing this certificate. neither the inspector nor his employer makes any warranty. expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
_________I__
Commissions yI- /_ Yo Dates S200Nj l M.
Mate. ivirwe. am a
[d w
200i Date amity /C 20 V 5
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, ll. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
07/13/2005 Sheet:
I of I Unit:
I Program No.05-038, WO 007955()0 Repair Organization P.O. No., Job No.. etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 3. Work Performed by:
Quad Cities Generating Station 2271() 206th Ave. North, Cordova. IL 61242
- 4. Identification of System: Feedwater, Class I
- 5. (a) Applicable Construction Code: USAS B331.1 1967 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda. N/A Code Case
- 6. Identification of Components Repaired or Replaced. and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, AShlE Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or
_N o )
Flued Head Anchor Various N/A NIA I-16()-XO9A N/A Repair/
No I__
I__
I__
I__
R eplacem ent
- 7. Description of Work: Repair or replace flued head anchor retainer clips / welds and replace load pin IAW WO,
- 8. Tests Conducted:
Hydrostatic D Pneumatic E Nominal Operating Pressure 5 Other 5 Pressure psi Test Temp.
°F
- 9. Remarks:
IR 00352627 CERTIFICATE OF COMPLIANCE Wc certily that the statcmeints made in this report are correct and this repair/replacement to ihe niles of ASE Code. Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFRS5 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed
(
I;eAL M.
P ty Date I 95 20O0 V
IL) ter orOwner's Desittce,Title CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
. and employed by I-ISB CT. of Connecticut have inspected the components described in this Owner's Rcport d(uring the period
,i/C
( les-to 7 1Y/os
.and state that to thc best of my knowledge and bclic the oweticr has performed examilltiols alid taken corrective measures described in this Owner's Report in accordance the requirements of the ASNIE Code.Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty. expressed or implied. concerning the examinations and correctivc measures described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall be liable in any manncr for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
AK_
Commissions
/1/- /SV Date ro.r, sii/mlre N.£ALi.
1W.( %late, Pnniiwe.
/rki I'r 2r0Cil Date J>CY I,
20 0 5
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section Xi
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville. II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North. Cordova, IL 61242 Date:
07/13/2005 Sheet:
I of I Unit:
I Program No.05-039, WO 00795499 Repair Organization P.O. No.. Job No.. etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Feedwater, Class I
- 5. (a) Applicable Construction Code: USAS B331.1 1967 Edition, N/A Addenda. N/A Code Case (b) Applicable Edition of Section Xi Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced. and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component M fr.
No.
l3d.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Flued Head Anchor Various N/A N/A I I-1600-X09B N/A Replacement No
- 7. Description of Work: Replaced fiued head anchor pins and retainer clips lAW WO.
- 8. Tests Conducted:
Hydrostatic 5 Pneumatic 5 Nominal Operating Pressure 5 Other a Pressure psi Test Temp.
OF
- 9. Remarks:
None CERTIFICATE OF COMPLIANCE WVe certify that the statements made in this report are correct and this replacement to the rules of ASNIE Code. Section Xi repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed j
Date JU 1 i
20OF I0 Onerdr Owher's DesiglieW.' itle CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
. and employed by I1SB C(i. of Connecticut have inspected the components described in this Owner's Report during the period vq/", /es5 to Ca7/I3/J5-.and statc that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Ox ner's Report in accordance the requirements of the ASNIE Code. Section Xi.
By signing this certificate. neither the inspector nor his employer makes any warranty. expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall he liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
z..
a<&/
Commissions 1l,' /Jf 0 Dttealure hAt il Board, state. mmrlxe-no raars 20 ens Dale J
t-
/
2() o -'7
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 Date:
4-14-2005 Sheet:
I of 2 Unit:
0 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 PO# 707 REL.# 12761 Repair Organization P.O. No., Job No., etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Control Rod Drive, Class 1
- 5. (a) Applicable Construction Code: ASNIE Sec. III 1974 Edition, Winter 1975 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or
_N o )
Control Rod Drive G.E.
A5028 N/A 0-Spare-DIS UNK.
Replaced Yes Control Rod Drive G.E.
A2465 N/A 0-Spare-D15 UNK.
Replaced Yes
-Ascription of Work: Replaced the Cap Screws as required by the PO.
- 8. Tests Conducted:
Hydrostatic E Pneumatic E Nominal Operating Pressure Ea Other E Pressure N/A psi Test Temp.N/A IF
- 9. Remarks: None CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Code, Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Authization No.
N/A Expiration Date N/A Signed Title n
CR, P Date st%
k Y
20 14
%I
'Ter
)5Owner s Dcsugrcc. Titke CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois.
and employed by IISB CT, of Connecticut have inspected the components described in this Owner's Report during the period p7/iao g to....e
- s. o and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code, Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
____________ommissions JL /7t InsMctdiigmture, Natk)tal Board. Statc. Pruvine. md Enbrienmts Date
/20 K
_2
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT (Supplement)
As Required by the Provisions of ASME Code Section XI C iwner:
Exelon Generation Company, LLC
~-
4300 Windfield Road Warrenville, IL 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
4-14-2005 Sheet:
2 of 2 Unit:
0 PO# 707 REL. # 12761 Repair Organization P.O. No., Job No., etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Control Rod Drive, Class I
- 5. (a) Applicable Construction Code: ASME SEC. III 1974 Edition, Winter 1975 Addenda, NA Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components: Continued Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Control Rod Drive G.E.
1029 N/A O-Spare-D 15 UNK.
Replaced Yes Control Rod Drive G.E.
A3630 N/A 0-Spare-DIS UNK.
Replaced Yes Control Rod Drive G.E.
64 N/A 0-Spare-DI5 UNK.
Replaced Yes atrol Rod Drive G.E.
886A N/A 0-Spare-D15 UNK.
Replaced Yes Control Rod Drive G.E.
301 N/A 0-Spare-DIS UNK.
Replaced Yes Control Rod Drive G.E.
A8759 N/A 0-Spare-D15 UNK.
Replaced Yes Control Rod Drive G.E.
888 N/A 0-Spare-D15 UNK.
Replaced Yes Control Rod Drive G.E.
120 N/A 0-Spare-D15 UNK.
Replaced Yes Control Rod Drive G.E.
738C N/A 0-Spare-D115 UNK.
Replaced Yes Control Rod Drive G.E.
A8734 N/A 0-Spare-D15 UNK.
Replaced Yes Control Rod Drive G.E.
A8544 N/A 0-Spare-D 15 UNK.
Replaced Yes Control Rod Drive G.E.
A3410 N/A 0-Spare-D 15 UNK.
Replaced Yes Control Rod Drive G.E.
8466 N/A 0-Spare-D15 UNK.
Replaced Yes Control Rod Drive G.E.
A8337 N/A 0-Spare-D15 UNK.
Replaced Yes Control Rod Drive G.E.
9144 N/A 0-Spare-D15 UNK.
Replaced Yes Control Rod Drive G.E.
A5405 N/A 0-Spare-D15 UNK.
Replaced Yes Control Rod Drive G.E.
A2568 N/A 0-Spare-D15 UNK.
Replaced Yes Control Rod Drive G.E.
7563A N/A 0-Spare-D15 UNK.
Replaced Yes
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
4-2-2005 Sheet:
I of I Unit:
0 PO# 707 REL.# 12761 Repair Organization P.O. No., Job No., etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Control Rod Drive, Class 1
- 5. (a) Applicable Construction Code: ASME Sec. III 1974 Edition, Winter 1975 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or
_ _N o)
Control Rod Drive G.E.
A2465 N/A 0-Spare-DI5 UNK.
Replaced Yes
--.escription of Work: Replaced the Piston Tube as required by the PO.
- 8. Tests Conducted:
Hydrostatic a Pneumatic 0 Nominal Operating Pressure a Other 0 Pressure N/A psi Test Temp. N/A IF
- 9. Remarks: None CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Code,Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Athorization No.
N/A Expiration Date N/A Signed Daco o
Mp a
M1 L
1'M 20Dat or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
, and employed by HSB CT. of Connecticut have inspected the components described in this Owner's Report during the period d) AZ.SO to V
, and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code, Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
-ocommissions
/*i In n%)rs jlutwe Date-
'171 l: 1 Naikmnal Bowud.
State. fiuv.ince. wad Endorsements 20 05
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI I. Owner:
(
Exelon Generation Company, LLC 4300 Winfield Road WVarrenville, 11. 60555 Date:
4-2-2005 Sheet:
I of I Unit:
0 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 PO# 707 REL.# 12761 Repair Organization P.O. No., Job No., etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Control Rod Drive, Class I
- 5. (a) Applicable Construction Code: ASME Sec. III 1974 Edition, Winter 1975 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or No)
Control Rod Drive G.E.
A2568 N/A 0-Spare-D 15 UNK.
Replaced Yes ascription of Work: Replaced the Piston Tube Nut as required by the PO.
- 8. Tests Conducted:
Hydrostatic D Pneumatic 0 Nominal Operating Pressure E Other D Pressure NIA psi Test Temp. N/A IF
- 9. Remarks: None CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Code, Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear IOCFR50 App B. 0 A Program Certificate of Au ization No.
N/A Expiration Date N/A Signed orcn_
hS:5:
e Date _t-14 4
20 Of rOwner's Designee.Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
, and employed by USB CT f Connecticut have inspected the components described in this Owner's Report during the period e)3/iZt oI to 6Y/o$, and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code, Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
- -Commissions Zn A57/
0 D
Inattrs Sigiiature Nationa &rd State. P2wime1 mg Er..ements Date ffetIqAi 20 -0S~
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road C
Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
4-12-2005 Sheet:
I of I Unit:
0 PO# 707 REL.# 12761 Repair Organization P.O. No., Job No.. etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Control Rod Drive, Class I
- 5. (a) Applicable Construction Code: ASME Sec. IiI 1974 Edition, Winter 1975 Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Control Rod Drive G.E.
A8759 N/A 0-Spare-D15 UNK.
Replaced Yes 7
escription of Work: Replaced the Piston Tube as required by the PO.
- 8. Tests Conducted:
Hydrostatic E Pneumatic l:
Nominal Operating Pressure E Other E Pressure N/A psi Test Temp. N/A F
- 9. Remarks: None CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Code, Section Xl repair or replacement Type of Code Symbol Stamp N/A-Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Au rization No.
N/A Expiration Date N/A Signed
- I NQ 3D ate Dat 1LA 20 4)5
-rcerr Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION l, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of linois
. and empled by HSB CTof Connecticut have inspected the components described in this Owner's Report durhig the period ey/1 2!toY to./arL/D5i, and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code, Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Date.
fat saget Commissions SA'O/JT Inkrtnr Signatire AP,'4, /IV NAtional D)rd. State. nuviwe, and Endorsermenti 20
-0>>
D a t
2 0
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owvner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
05/13/2005 Sheet:
I of I Unit:
I Program No.05-044, WO 00685172 Repair Organization P.O. No., Job No., etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Residual Heat Removal; Class 2
- 5. (a) Applicable Construction Code: ASME Sect. VIII 1965 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or N o )
Floating Head, N/A NN/A
/A I-1003-B N/A Repaired No Heat Exchanger I
- 8. Tests Conducted:
Hydrostatic E]
Pneumatic El Nominal Operating Pressure E Other El Pressure
_ psi Test Temp.
F
- 9. Remarks:
None CERTIFICATE OF CONIPLIANCE We certify that the statements made in this report are correct and this repair conforms to the rules of ASME Code,Section XI repair or-replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 App B. 0 A Program Certificate of Au irization No.
N/A Expiration Date N/A Signed Date M&A4
- let, 20 OZ cOwer or Owner's Designee. Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
. and employed by HSB CT. of Connecticut have inspected the components described in this Owner's Report during the period e '1/{& to to 7/Is-/o!-
,and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owncr's Report in accordance the requirements of the ASME Code.Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
C______Commissions arLt l10o n r Signatture Natnal 9,jnL, State. Pnwinme.
arnd Endirxencenti Date 34-1 5b 20
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova. IL 61242 Date:
07/15/2005 Sheet:
I of I Unit:
I Program No.05-049,05-051 WO 00799763 RepairOrganization P.O. No.. Job No.. etc.
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Residual Heat Removal, Class I
- 5. (a) Applicable Construction Code: USAS B31.1 1967 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or
_N o)
Flued Head Anchor N/A N/A N/A I-1600-X I3A N/A Replacement No Pins and Retaining C lips
- 8. Tests Conducted:
Hydrostatic El Pneumatic El Nominal Operating Pressure Other Ea Pressure
_ psi Test Temp.
OF
- 9. Remarks:
None CERTIFICATE OF CONMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Code. Section Xl repair or replacemLnt Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR5() Arm B. 0 A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed A"
Age 9-a5 M JD ate DJuly IS 20O qwndor wner's DVSig cen.
' Lie CERTIFICATE OF INSERVICE INSPECTION I. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
. and employed by FISB CT. Of Connecticut have inspected the components described in this Owner's Report during the period rIff// ZS to O7f/r,5, and state that to the best of my knowledge and belief. the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code.Section XI.
By signing this certificate, neither the inspector nor his employer makes any warranty. expressed or implied. conceming the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner For any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
,4/di r.5ij/ICommissions N4
/
B )
Dattr Sienltur NJiul Nard. Sle.
ianin-2 xid rrkir27.
Date JOEIY /5-
-20 C 5
FORM NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242 Date:
03/17/2005 Sheet:
1 of I Unit:
0 Purchase Order # 71184 Repair Organization P.O. No., Job No., etc.
Type Code Symbol Stamp:
None Authorization No.:
None Expiration Date:
N/A
- 4. Identification of System: Spare Valve, Classl
- 5. (a) Applicable Construction Code: ASME Section III Class A 1965 or 1968 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements: 1995 Edition, 1996 Addenda, N/A Code Case
- 6. Identification of Components Repaired or Replaced, and Replacement Components:
Name of Component Name of Mfrs. Ser.
Natl Other Year
- Repaired, ASME Code Mfr.
No.
Bd.
Identification Built Replaced, or Stamped No.
Replacement (Yes or No)
Safety Valve Dresser Industries BK 7158 N/A O-Spare N/A Replacement No
- 7. Description of Work: Replaced the Disc as required by the PO.
- 8. Tests Conducted:
Hydrostatic El Pneumatic El Nominal Operating Pressure E]
Other 0 Pressure 1255 psi Test Temp.265 IF
- 9. Remarks: Replacements were performed off site by NWS QA System Manual Rev 2 CERTIFICATE OF COMPLIANCE We certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Code,Section XI repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear IOCFR50 App B. 0 A Program Certificate of Author zation No.
N/A Expiration Date N/A Signed IQ4L 6 IS l W
c N'AtoQ Date M AtZ CO
/1 2017. -
ne or wner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois
, and employed by HSB CT of Connecticut have inspected the components described in this Owner's Report during the period 03/,17&/5' to 037i /1o7
, and state that to the best of my knowledge and belief, the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code, Section Xl.
By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
Commissions
/!/ /s5-f()
[Inspaiors Signau Date. >X< A v
e
/ 7 National Board, State, Province, aHI Endorsernents
FORNI NIS-2 OWNERS REPORT OF REPAIR OR REPLACEMENT As Required by the Provisions of ASME Code Section XI
- 1. Owner:
Exelon Generation Company, LLC 4300 Winfield Road Warrenville, II. 60555 2.Plant:
Quad Cities Generating Station 22710 206th Ave. North, Cordova, IL 61242
- 3. Work Performed by:
Quad Cities Generating Station 22710 206th Ave. North, Cordova. IL 61242 Date:
7/14/2005 Sheet:
I of I Unit:
0 Program No.00-109 WO 990042820 Repair Organization P.O. No., Job No.. etc.
Type Code Symbol Stamp:
Authorization No.:
Expiration Date:
None None N/A
- 4. Identification of System: Main Steam, Class I (spare)
- 5. (a) Applicable Construction Code: USAS B31.1 1967 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements:
1989 Edition, N/A Addenda, N-496-1 Code Case
- 6. Identification of Components Repaired or Replaced. and Replacement Components:
Name of Name of Mfrs. Ser.
Nat'l Other Year
- Repaired, ASME Component Mfr.
No.
Bd.
Identification Built Replaced, or Code No.
Replacement Stamped (Yes or Electromatic Relief Dresser Industries BX00293 N/A 0-Spare-V26 N/A Replacement No V a lv e I
_I_
- 7. Description of Work: Installed two helicoils in the inlet flange bolt holes as required by the W.O.
- 8. Tests Conducted:
Hydrostatic a Pneumatic E Nominal Operating Pressure 5 Other 5 Pressure _
psi Test Temp.
'F
- 9. Remarks:
N/A CERTIFICATE OF COMPLIANCE WVe certify that the statements made in this report are correct and this replacement conforms to the rules of ASME Code, Section Xl repair or replacement Type of Code Symbol Stamp N/A - Exelon Nuclear I OCFR50 AVV B. O A Program Certificate of Authorization No.
N/A Expiration Date N/A Signed
& L At, grg7 my
-Date Jowly i§ 20bS o *%)cr or Owner'sLDosiglice.Iii-ulc CERTIFICATE OF INSERVICE INSPECTION
- 1. the undersigned. holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State of Illinois.
and employed by H1SB CT. of Connecticut have inspected the components described in this Owner's Report during the period z
~flZ Y/60 to J£ and state that to the best or my knowledge and belief. the owner has performed examinations and taken corrective measures described in this Owner's Report in accordance the requirements of the ASME Code, Section Xl.
By signing this certificate. neither the inspector nor his employer makes any warranty, expressed or implied. concerning the examinations and corrective measures described in this Owner's Report. Furthermore. neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
_Commissions I 4 /5 y/0 iaijxiro Sigbtinre Njitwul B. iard. Stjte. nwincc. and rr'.rmennti Date Ant, /6 20 O 3