ND-20-1265, ITAAC Closure Notification on Completion of ITAAC 2.3.03.03a (Index Number 320)
| ML20357B062 | |
| Person / Time | |
|---|---|
| Site: | Vogtle |
| Issue date: | 12/21/2020 |
| From: | Yox M Southern Nuclear Operating Co |
| To: | Document Control Desk, Office of Nuclear Reactor Regulation |
| References | |
| ITAAC 2.3.03.03a, ND-20-1265 | |
| Download: ML20357B062 (6) | |
Text
Southern Nuclear DEC 2 1 2020 Docket No.: 52-026 U.S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555-0001 Michael J. Yox Regulatory Affairs Director Vogtle 3 & 4 7825 River Road Waynesboro, GA 30830 706-848-6459 tel ND-20-1265 10 CFR 52.99(c)(1)
Southern Nuclear Operating Company Vogtle Electric Generating Plant Unit 4 ITAAC Closure Notification on Completion of ITAAC 2.3.03.03a [Index Number 3201 Ladies and Gentlemen:
In accordance with 10 CFR 52.99(c)(1), the purpose of this letter is to notify the Nuclear Regulatory Commission (NRC) of the completion of Vogtle Electric Generating Plant (VEGP) Unit 4 Inspections, Tests, Analyses, and Acceptance Criteria (ITAAC) Item 2.3.03.03a [Index Number 320]. This ITAAC verified that the volume of each fuel oil storage tank available to the standby diesel generator is greater than or equal to 55,000 gallons. The closure process for this ITAAC is based on the guidance described in NEI 08-01, "Industry Guideline for the ITAAC Closure Process under 10 CFR Part 52," which was endorsed by the NRC in Regulatory Guide 1.215.
This letter contains no new NRC regulatory commitments. Southern Nuclear Operating Company (SNC) requests NRC staff confirmation of this determination and publication of the required notice in the Federal Register per 10 CFR 52.99.
If there are any questions, please contact Tom Petrak at 706-848-1575.
Respectfully submitted, Michael J. Yox
^
Regulatory Affairs Director Vogtle 3 & 4
Enclosure:
Vogtle Electric Generating Plant (VEGP) Unit 4 ITAAC Closure Notification on Completion of ITAAC 2.3.03.03a [Index Number 320]
MJY/JFV/sfr
U.S. Nuclear Regulatory Commission ND-20-1265 Page 2 of 3 To:
Southern Nuclear Operating Company/ Georgia Power Company Mr. Peter P. Sena III (w/o enclosures)
Mr. D. L. McKinney (w/o enclosures)
Mr. M. D. Meier (w/o enclosures)
Mr. G. Chick Mr. S. Stimac Mr. P. Martino Mr. M. J. Yox Mr. A. S. Parton Ms. K. A. Roberts Mr. T. G. Petrak Mr. C. T. Defnall Mr. C. E. Morrow Mr. R. L. Beiike Mr. S. Leighty Ms. A. C. Chamberlain Mr. J. C. Haswell Document Services RTYPE: VND.LI.L06 File AR.01.02.06 cc:
Nuclear Reoulatorv Commission Ms. M. Bailey (w/o enclosures)
M M
M M
M M
Ms. N. C. Coovert M
M M
M M
M M
M M
M M
M M
M. King H. K. Nieh C. P. Patel G. J. Khouri C. J. Even B. J. Kemker C. Welch
. J. Gaslevic
. O. Lopez-Santiago G. Armstrong M. Webb T. Fredette C. Santos B. Davis J. Vasquez J. Eargle E. Davidson T. Fanelli S. Rose Ms. K. McCurry Qqlethorpe Power Corporation Mr. R. B. Brinkman Mr. E. Rasmussen
U.S. Nuclear Regulatory Commission ND-20-1265 Page 3 of 3 Municipal Electric Authority of Georgia Mr. J. E. Fuller Mr. 8. M. Jackson Daiton Utilities Mr. T. Bundros Westinqhouse Electric Company. LLC Dr. L. Oriani (w/o enclosures)
Mr. D. 0. Durham (w/o enclosures)
Mr. M. M. Corletti Mr. Z. 8. Harper Mr. J. L. Coward Other Mr. 8. W. Kline, Bechtel Power Corporation Ms. L. Matis, Tetra Tech NUS, Inc.
Dr. W. R. Jacobs, Jr., Ph.D., GDS Associates, inc.
Mr. 8. Roetger, Georgia Public Service Commission Mr. R. L. Trokey, Georgia Public Service Commission Mr. K. C. Greene, Troutman Sanders Mr. 8. Blanton, Baich Bingham
U.S. Nuclear Regulatory Commission ND-20-1265 Enclosure Page 1 of 3 Southern Nuclear Operating Company ND-20-1265 Enclosure Vogtle Electric Generating Plant (VEGP) Unit 4 ITAAC Closure Notification on Completion of ITAAC 2.3.03.03a [Index Number 320]
U.S. Nuclear Regulatory Commission ND-20-1265 Enclosure Page 2 of 3 ITAAC Statement Design Commitment S.a) Each fuel oil storage tank provides for at least 7 days of continuous operation of the associated standby diesel generator.
Inspections. Tests. Analvsis Inspection of each fuel oil storage tank will be performed.
Acceptance Criteria The volume of each fuel oil storage tank available to the standby diesel generator is greater than or equal to 55,000 gallons.
ITAAC Determination Basis An inspection was performed to demonstrate that the volume of each fuel oil storage tank available to the standby diesel generator is greater than or equal to 55,000 gallons.
A calculation was performed to verify that the tank size will provide for at least 55,000 gallons of available volume. The available volume includes the volume above the pump trip set point and below the tank "high-tank" level. Fuel oil storage tanks DOS-MT-01A and DOS-MT-01B were inspected (Reference 1) to verify the as-built dimensions of the tanks. In order to obtain the net working volume of the tanks, the design volumes of the nozzle N5 and N7 drop pipes, pipe clips and the design maximum thickness of the tank internal coating were subtracted from the calculated volume of the tank and documented in Reference 1.
The inspection determined the fuel oil storage tank's available volume to supply fuel to each standby diesel generator is 70,686 gallons for tank D0S-MT-G1A and 70,627 gallons for tank DOS-MT-01B and meets the ITAAC acceptance criteria. This report is available for NRC inspection as part of the ITAAC 2.3.03.03a Completion Package (Reference 2).
ITAAC Finding Review In accordance with plant procedures for ITAAC completion. Southern Nuclear Operating Company (SNC) performed a review of all ITAAC findings pertaining to the subject ITAAC and associated corrective actions. This review found that there are no relevant ITAAC findings associated with this ITAAC. The ITAAC completion review is documented in the ITAAC Completion Package for ITAAC 2.3.03.03a (Reference 2) and is available for NRC review.
ITAAC Completion Statement Based on the above information, SNC hereby notifies the NRC that ITAAC 2.3.03.03a [Index Number 320] was performed for VEGP Unit 4 and that the prescribed acceptance criteria were met.
U.S. Nuclear Regulatory Commission ND-20-1265 Enclosure Page 3 of 3 Systems, structures, and components verified as part of this ITAAC are being maintained in their as-designed, ITAAC compliant condition in accordance with approved plant programs and procedures.
References (available for NRG inspection)
- 1. SV4-DOS-ITC-800000, Rev. 0; DOS Fuel Oil Storage Tank Volume Calculation
- 2. 2.3.03.03a-U4-CP-Rev0 ITAAC Completion Package
- 3. NEI 08-01 Rev. 5, Industry Guideline for the ITAAC Closure Process under 10 CFR Part 52