August 22,1996 LJM:96:066 i
U.S. Nuclear Re::alatory Commission, Region IV Attention: Mr. L. J. Callan, Regional Administrator 611 Ryan Plaza Drive, Suite 400 Arlington, TX 76011-8064
Dear Mr. Callan:
License SNM 1227 Docket 70-1257
Subject:
Required Reporting of Effluents per 10 CFR 70.59 As required by 10 CFR 70.59, Siemens Power Corporation (SPC) is reporting discharges of radioactive materials in the effluents from its nuclear fuels fabrication plant on Horn Rapids Road, in Richland, Washington. Data from January 1,1996 through June 30,1996 are reported in the attached tables, i
The gaseous effluent stacks K50 and K55 from the Solid Waste Uranium Recovery (SWUR) facility were restarted in May 1996.
All data indicate continued compliance with applicable discharge limits.
l The LLD values listed in the 1995 Liquid Effluent Reports conveyed via transmittal letters dated August 29,1995 and February 26,1996, should be corrected to read 8.9 E-8 and 8.5 E-8 Ci/ml, respectively. The calculations in the old database were not updated to incorporate the lower reportable analytical detection limit for uranium. The new database now reflects this change. We apologize for any inconvenience this may cause. if there are any questions please contact me at (509) 375-8537.
Very truly yours, v
l W
L. J. Maas, Manager Regulatory Compliance 9610080171 960630 Attachments PDR ADOCK 07001257 C
PDR gu' N~ l97 b Siemens Power Corporation I /
Nuclear Dnnsion 2101 Horn Rapids Road Tet (509) 375-8100 Engrneenng & Manuf actunng Po. Box 130 Far (509) 375 8402 Richland. WA 993524130 l e-op
i 4
0 9'
August 22,1995 cc:
Carl J. Paperiello, Director, NMSS Allen W. Conklin, State of Washington Department of Health C. A. Hooker, U.S. Nuclear Regulatory Commission, Region IV, WCFO J
1 i
i l
i
o GASEOUS EFFLUENT JANUARY 1,1996 - JUNE 30,1996 AVERAG6 ERROR AVERAGE CONCENTRATION ESTIMATE LLD QUANTITY FLOW STACK
( Ci/ml)
(%)
( Ci/ml)
( Ci u) *
(m')
3 1.27-15 13 1.4 16 0.44 3.61 + 8 6
6.17-16 18 3.0-16 0.07 1.28 + 8 9
1.23-15 15 7.8-16 0.02 2.02 + 7 10 1.36-14 7
6.2-15 0.13 1.02 + 7 21 9.20-16 21 6.0-16 0.11 1.48 + 8 25 1.86-15 12 3.3-16 0.04 2.39 + 7 31 6.47-16 25 6.7-16 0.23 3.88 + 8 32 1.44-13 5
1.1-14 3.20 2.55 + 7 37 3.88-15 6
2.8-16 0.53 1.51 + 8 42 3.69-16 18 9.8-17 0.02 5.10 + 7 46 2.22-16 27 2.1-16 0.03 1.58 + 8 47 6.52-15 10 8.8 16 0.05 9.54 + 6 49 2.06-15 10 4.2-16 0.12 6.60 + 7 50 1.14-14 6
2.6-15 0.03 2.00 + 6 55 1.54-15 10 1.9-16 0
2.67 + 6 56 3.66-16 22 2.6-16 0
7.95 + 6 58 6.97-16 12 2.8-16 0.10 1.53 + 8 60 6.38-16 18 8.3-17 0.06 1.14 + 8 TOTAL 5.20 1.82 + 9 Radionuclide: Mixed Fission and Activation Products ( Ci p) 52 3.53-15 66 3.6-14 0.18 5.09 + 7 TOTAL 0.18 5.09 + 7 Typical lower limit of detection for 7-day sampling period except stacks 10 and 32 were for daily sampling.
Based on low enriched uranium.
O O
LIQUID EFFLUENT "
JANUARY 1,1996 - JUNE 30,1996 CONCENTRATION ERROR ESTIMATE LLD""
QUANTITY FLOW
( Ci/ml)
(%)
(pCi/ml)
(Cl)
(m )
< 9.93-8 5
9.6-8
< 0.015 1.49 x 10 5
0.003 "'"
i Source is the sewer effluent to the City of Richland POTW.
Lower limit of detection for individual samples.
Based on measurements of uranium discharges from the lagoon system, as reported on NRC Form 741.
i l
{
\\
SOLID EFFLUENT JANUARY 1,1996 - JUNE 30,1996 NUMBER OF MODE OF DESTINATION VOLUME QUANTITY "**
- SHIPMENTS TRANSPORTATION Allied Technology Group 11 Truck Richland, WA 156 m 0.023 Ci l
4 i
l 4
""" Based on 3.4 wt% enriched uranium.
i
,