2 PERRY NUCLEAR POWER PLANT PAGE1OF 5YSTEM COMPONENT EVALUATION WORKSHEET (FOR CL A551E EQUIPMENT IN NAR5H ENVIRONMENT)
SP-594-00-13 QUALIFICATION
SUMMARY
(FILE NO.)
MANUF ACTURER'S QUALIFICATION REPORT NO.
ES-1000; 43706-2 R E Y.
B QUALIFICATION METHOD Test EQUIPMENT DESCRIPTION Eel 8V MANUFACTURER /MODEL NO.
Aqastat/E7012-PCM, ACM, PCM1, ACIJ1 TESTED DEVICE MODEL NO.
E7012 AGING
SUMMARY
VALUE DURATION NORMAL / ABNORMAL ENVELOPE ENVIRO 20 E (1)
T EMPER ATURE (oF): MAXIMUM AB-9 107 F 8,410 llours AVERAGE AB-9 930F 338,486 Ilours MINIMUM AB-9 860F 3,504 flours ABNORM AL TEMP. TRAN5IENT5 (oF): Loss of IIVAC AB-9 126/1070F 49 !!ours 2
AL-9 8.8 x 10 Rads (2) 40 Years ACCELERATED AGING TEMP./ TIMES 212 F/42 Days QUALIFIED LIFE / MAINTENANCE INTERVAL 10 Years /None LIFE-LlulTING COMPONENT Knob Seal. Washer, Diaphragm (A.E. - 0.61 eV)
TEST R ADIATION DOSE (TID) 2 x 105 Rads (2)
SUMMARY
FUNCTION R E QUIR EM E NT5 (3)
QUALIFICATION DEMONSTR ATED EQUIPMENT The relay was func;ionally tested during the C ATEGORY (EC)
A3 hontiin onviron-one ennt.
FUNCTION 30-Days Test extended to 180 Days Post-LOCA TIME (FT)
J (180 Days) by Analysis ACCURACY (ACC) (4)
+ 10% (Note 4)
N/A (Note 4)
N/A ACCIDENT
SUMMARY
(Note 5)
REQUIRED ENVELOPE QU ALIFICATION DEMONSTRATED O
PARAMETER MAXIMUM V ALUE MAXIMUM VALUE M ARGIN 0
TEMPE R ATURE (*F)
AB-9 2170F 40-212 F Note 5 PRES $URE (PSIG)
AB-9 1.6 PSIG 1.6 PSIC Note 5 R.N.(%)
AB-9 100%
10-95%
N /A SPRAY N/A N/A N/A N/A SUBMERGENCE N/A N/A N/A N/A R ADI ATION (RADS)
AB-9 1 x 103 Pads 2 x 105 Rads (2)
> 10%
(FOR SUPPLEMENTAL NOTES SEE PAGE 2)
R E Y.NO DATE
,rv,c, l r
o,,,novrc Claude GOSch (GAI)
[2/1/84 REVIEWED BY d
CHECKED BY h.
/
/
/
W/qs/NMM_'im_;
1%4Y 8403130118 840307 APPROVED BY g
PDR ADOCK 05000440 5
A PDR
i PERRY HUCLEAR POWER PLANT PAGE 2 oF 2 SYSTEM COMPONENT EVALUATION WORK 5HEET I
(FOR CLA55 IE equip!.'ENT IN A H AR5H ENVit!NMENT) l Sp-594-00-13 QUALIFICATION
SUMMARY
(FILE NO.)
J l
SUPPLEMENTAL NOTES:
- 1. See FSAR Tables 3.11-1 thru 8.
- 2. A portion of the " TEST RADIATION DOSE (RADS, TID)" is applied to qualify the device for the required Normal / Abnormal radiation dose (for the desired qualified life). The remainder of the " TEST RADIATION DOSE (RADS, TID)" is applied to qualify the device for the required Accident radiation dose (for the required function time) plus 10% margin.
TE'ST RAD. DOSE A NORMAL / ABNORMAL RAD (Qual. Life) +(ACCIDENT RAD DOSE (FT) +
10% MARGIN)
- 3. "0PERABILITY
SUMMARY
- REQUIREMENTS" are as specified in the Environmental Qualification Review List (EQRL) report titled " SAFETY RELATED EQUIPMENT IDENTIFICATION AND ENVIRON-MENTAL QUALIFICATION
SUMMARY
- 4. Source of accuracy requirements:
The only function of these relays is to prevent spurrious alarms. The relay has a maximum time delay of 15 seconds and a normal setting of 10 seconds.
If the relay takes 15 seconds to change state, its function will have been performed.
If the relay takes O seconds to change state, there will be a
- momentary alarm' which will clear when the fan comes up to speed. Therefore, the accuracy of this relay is not critical.
5.
The Agastat relays which are located in liarsh Environment (Zone AB-9) are normally de-energized and are not required to operate to mitigate the RWCU break in AB-9.
The equipment ~in which they are located will not receive an auto start signal and will not be manually activated. Further, their failure is deemed not detrimental to plant safety or accident mitigation.
It should be noted that the relays are qualified to 212oF maximum in their de-energized
- mode and that the short (15 second) temperature rise to 217oF outside the panel will not result in a temperature rise inside the panel above 2120F.
This is because the panel is a NEMA-12 enclosure (sealed from moisture) which prevents the warm air outside the enclosure from quickly entering the enclosure and raising its internal temperature. Heat will be-transferred by conduction, how-ever, this will not occur quickly enough to raise the temperature inside the enclosure from 1150F to 2170F in 15 seconds.
Further, the gaskets around all doors, conduit entries, and removable panels will prevent the 1 M accad 100%
humidity and 1.6 psig pressure condition external to the panel from affecting its internal conditions. This analysis, however, is not required to prove qualification, since the relays are not required to operate to mitigate the RWCU break and their failure is deemed not detrimental to plant safety or accident mitigation.
TABLE 1
' NISCEU.ANEOUS PARTS AND HATERIALS LIST POR SPECIFICATION SP-594-4549-00 (MATERTALS OF CDNSTRUCTION)
The items listed mder Part.A of this table are used in tb equipment assemblies listed imider Part B.
A. Items List Item Wo.
Description Manufac'turer Type No.
1._
Indicating Lamps Ceneral Electric ET-16 2.
Terminal Boards General Electric CR15152 3.
Cable General Electric.
Vulkene Supreme SP-57279 4.
Thrminal Lugs Thomas & Betts Sta-Koo R8T853 5.
Fuse Blocks Buchanan NQO361 C.
Section Blocks Buchanan NQO211 7.
BIw Wire Boston BOSTRAD XL 40 [
8m
, Auxiliary @ Bel p Ageetse
page two TABLE 1 Part A (continued)
Item No.
Description Manufacturer Type No.
9.
Amrilf ary Imgic Relays General Electric 19tAlllB 10.
L=iliary Logic Relays ITE-Could J10 11.
Control Switches General Electric CR2940Y 12.
Indicating Differential ITT Barton 580A-1 Pressure Switches i
13.
Temperature Transmitters Weed 4000 14.
Pressure Transmitters Rosemount 1153 l
l e
l l
i
,6
?
Table 1 (conttamed) l 3.
pg.itement Assemblies tJot (Panels and Racks)
Fanel/ Rack Fanel/Back Service Description Imratice:
Environeestal Manofacturer 4 Ite=S Used MPL Mo.
Description System /Functinn Building Elevation Zone Mir.Dua.No./CAI Ibg. Per Part A 1
0451 P 4036A C>etrel Pamel.
ECC Famp Area HTAC Centret 574 ft.
CB-5 Mild Coasty - C sto=1tne
- 1. 2. 3. 4, 11 vall Monsited som Lantrol Statica 44-056/3-201-142 l
DNSI F 0036s control Panel.
ECC Famp Area MTAC Centrol 574 ft.
CB-5 Mild Comsty - Custo 11 e 1, 2. 3. 4. Il
}
Mall Mounted nos control Stattan 44-155/s-201-142 Cu51 P 0039 open Rack.
Emergency Closed cooling Control 5J4 ft.
Cs,5 Mild co-sty - Custo=11ae
- 2. 3. 4 14 Free Standing System Instr. Rack 44-057/5-909-247 1
WTTTTF5W Control Panel.
MCC. Sugr. & Batt. Roome Control 679 ft.
h Consty - Custoellne 1 thru ti, i
Tree Standing.
MVAC Control Panet (Divsi.1) 44-0 5/5-809-076 8 thru 11
. Enclosed suST"F"WITfB Control Panel, MCC. Swgr. & RatIt. Rooms Control 679 ft.
OTWTR Coesty - Casteell.e 1 thru 11 i
Free Standing.
HTAC Control Panel (Dive.2) 44-188/5-809-081 Enclosed OH51 F 0178 open Rack.
Emergency Closed Coo 11ag Control
.574 ft.
CB-5 Mild Coasty - Custo 11.e
- 2. 3. 4, 14 Free Standing System Instr. Rack 44-144/s-809-243 OM51 F 0193 Open Rack.
ECCW Preps & CC Oillied Control 574 ft.
CS-5 Mild Coesty - Custo=11oe 2, 3. 4, 12, 13 '
4 Tree Standing rater Instr. Rack "A" 44-147/B-809-237 ONSI F 0194 open Rack.
Ecot Puses & CC Chilled Control 574 ft.
Cn-5 Mild "
Co-sty - Custo=1tme 2, 3. 4. 12, 13 i
Free Standing Water Instr. Rack "C" 44-146/5-809-238 1
CH51 F 0195 Cren Rack.
ECOI Pumps & CC Chilled Control 374 ft.
CB-5 Mild Co sty - Custeeltae 2, 3. 4, 12, 13 Tree Standing Nater Instr. Rack "B" 44-t45/s-801-239
=
4segyT'WWP Control Panel;,
Fump Room Cooling IIVAC Auxillary 599 ft.
-stesT"1turuk Coasty - Custo=11n4 1 thru 6,8..
Floor Heunted.
Control Panel 44-151/B-809-073 10,11 Enclosed lH51 F 0134A Open Rack.
Contalnuent Atmospheric Aux 11tary 620 ft.
AB-1 Mild Co= sty - Custeeltae
- 2. 3. 4 14 Tree Standing Hewit tortaa Instr. Back "A" 44-148/B-809-230 1
IR5I F 01348 open Rack.
Cor.tainment Atmospheric Interse4 tate 654 ft.
TS-4 Mild Consfp - Custeellne
- 2. 3. 4, 14 j
Free Standinit Monitoring Instr. Rack "B"
&&-058/s-209-248 IR51 P 014 Wall possited Box contalement System Temp.
Intermediate 620 ft.
TB-5 Mild Comste - Custo=11ne ~ 13 i
j Trans. Enclosure (Dfvii.1)*
44-149/B-201-142 4
)
IH51 P 0143 wall Mounted Reic Cantalvament Syntem Yemp.
In terme.it a t c.
620 ft.
Ta-5 Mild Co-sap - Custo=1tne. 13
}
Trans. Enclesure (Divn.2) 44-154/B-201-142 s
l
ATTACHMENT A Document ation required to prepare the NUREG-0588 check list vill be' maintained in an auditable form for the entire period during which the covered items is installed at Perry.
ALTERNATE PLAN If the documentation required to prepare the NUREG-0588 check list is not available in our auditable file, we will:
1.
Attempt to obtain the documentation from the Vendor.
2.
If the Vendor will not release the documentation, we will attempt to obtain a letter from the Vendor stating that he will maintain the required documentation for the 40 year life of the item and if he Eoes out of business, he will provide us with the required documentation.
3.
If the Vendor fails to provide the documentation or letter, we will obtain the necessary documentation to support qualification. This will be in the form of either documentation obtained from other utilities or further material analysis to support qualification of the item.
SP 506 Siemens/Allis Will go to Norwood Summary acceptable +
alternate plan SP 632 Reliance Motors Summary acceptable SP 645 Reliance Motors SP 646 Reliance Motors SP 594 G.E. ETl6 Lights Alternate Plan and Could J10 Relays
, Lt
/
/
{t
,,/'
l 2uf I b-
-.