ML20078G148
| ML20078G148 | |
| Person / Time | |
|---|---|
| Site: | Beaver Valley |
| Issue date: | 01/23/1995 |
| From: | George Thomas DUQUESNE LIGHT CO. |
| To: | NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM) |
| References | |
| RTR-NUREG-1394 NUDOCS 9502020426 | |
| Download: ML20078G148 (4) | |
Text
e Beaver Valley Power Station Shippingport. PA 15077-0004 (412) 393-5206 (412) 643-8069 F AX GEORGE S. THOMAS
$$e*." $$."*"'
January 23, 1995 Nuclear Power Division U.
S.
Nuclear Regulatory Commission Attn:
Document Control Desk Washington, DC 20555-0001 Subject.:
Beaver Valley Power Station, Unit No. 1 Docket No. 50-334, License No. DPR-66 Emergency Response Data System (ERDS)
In accordance with the requirements published in NUREG 1394, Rev.
1, Section 3.6,
" Administrative Implementation Requirements,"
the enclosed Data Point Library (DPL) changes are being submitted.
These three (3)
DPL's have undergone a
change in their Hi alarm setpoints.
These changes are currently in effect on the Beaver valley Plant computers which provide the data to the ERDS computer.
Any questions regarding these DPL changes should be addressed to Joe Senko at (412) 393-5728.
Sincerely, d'ytth
< eb
\\
George S. Thomas Attachments cc:
Mr.
L.
W.
Rossoach, Sr. Resident Inspector Mr.
T.
T. Martin, NRC Region I Administrator Mr.
G.
E.
Edison, Sr. Project Manager Mr.
J.
R.
Jolicoeur, USNRC Incident Response Branch Mr. T.
P.
LaRosa,-NUS Corporation /El Division Mr.
R.
R.
Keimig, NRC Rcgion 1, Emergency Preparedness Mr.
P.
D. Kaufman, NRC Region 1, Emergency Preparedness i
.<<s Y
,Q
\\
i 9502020426 950123 i
SEAVER VALLEY POWER STATION FRDS DATA POINT LIBRARY BV1 ERDS INPUT Date:
01/06/95 Reactor Unit GY1 Data Feeders PVC NRC ERDS Parameter RCS LTDN RAD Point ID 20037A Plant Spec Point Desc.:
RC LTDN LO RNC ACTIV R-CM101B Generic / Cord Desc.:
RAD LEVEL OF RCS LETDOWN LINE Analog /Olgttel:
A Engr Units / Dig States:
CPM Engr Units Conversion:
N/A Minimum Instr Range:
10 Maalmso Instr konge 1E6 Zero Point
Reference:
N/A Reference Point Notes:
N/A PROC or SENS:
S Nurnber of Sensors:
1 i
How Processed:
N/A Sensor Locations:
SEE UNIQUE SYSTEM DESCRIPTION FIELD Alarm / Trip Set Points:
NI ALM S 6.2E4 CPM /LO ALM G 6.4E3 CPM NI Detector Power Supply Cut off Power Level: N/A i
N1 Detector Power Supply Turn on Power Level: N/A Instrunent Failure Mode:
LOW Te@erature Conpensation for DP Transmitters: N j
Level Reference Leg:
N/A Unique System Desc.:
RM 1CH-101B MONITORS THE GROSS ACTIVITY OF THE REACTOR COOLANT (Co-60 & CS-137) BY DRAWING SAMPLES FROM THE REACT 0k COLAUT LETDFA LI NE AND DELAYING THEM TO PERMIT SUFFICIENT DECAY OF THE N 16 !$0 TOP E BEFORE THEY PASS BY THE DETECTORS. TH18 IS AN IND!3 TION OF FISSI ON PRODUCTS PRESENT IN THE REACTOR COOLANT. THIS RADIATION MONITOR PROVIDES THE LOW AC MIGH RANGE INDICATION. A gam 4A SCINTILLATION I
DETECTOR MONITORS THE GROS $ ACTIVITY OF THE REACTOR COOLANT BY DRAW ING SAMPLES FROM THE REACTOR COOLANT LETDOWN LINE DOWNSTEAM OF THE
e SEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY BV1 ERDS INPUT e
Date:
01/06/95 Reactor Unit BV1 Data Feeder PVC NRC ERDS Parameter:
EFF L10 RAD Polnt ID:
R0030A Plant Spec Point Dese.:
LIQUID DISCH RAJ MONITOR R-LW104 Generic /Cond Dese.:
RADI0 ACTIVITY OF RELEASFD LIQUID Atulog/ Digital:
A Engr Units / Dig States:
CPM Engr Units Conversion:
N/A Minimum Instr Range 10 Maxinun Instr Range 1E6 i
Zero Point References N/A Reference Point Notes:
N/A PROC or SEN$3 S
Number of Sensors:
1 How Processed:
N/A i
Sensor Locations:
SEE IM10UE SYSTEM DESCRIPTION FIELD 1 Alarm / Trip Set Points:
HI ALM a 17000 CPM /LO ALM S -1600 CPM 1
NI Detector Power Supply Cut off Power Level N/A 31 Detector Power Stpply Turn-on Power Level: N/A Instrument failure Mode:
LOW 1
Teaperature Conpensation for DP Transmitters: N i
level Ref9rence Leg:
N/A i
Unique System Dese.:
RM 1LW 104 MONITORS THE ACTIVITY (CO-60 & CS 137) 0F ANY RAD 10ACTIV I
E LIQUID WASTE DI MARGED FROM THE STATION. A HIGH MIGN ACTIVITY AUTOMATICALLY TERMINATES FLOW BY CLOSING THE DISCHARGE LINE !$0LAT 10N VALYLS. A GMetA SCINTILLATION DETECTOR MONITORS THE ACTIVITY OF RADI0 ACTIVE LIQUID WASTE DISCHARGED DOWNSTREAM OF THE LAST Po!NT 0 F RADIDACTIVE EFFLUENT ADDITION TO THE DISCHARCE HEADER. OP MANUA L CHAPTER 43, RM 417-1 1
' BEAVER VALLEY POWER STATION ERDS DATA PolWT LIBRARY IV1 ERDS INPUT e
Date:
01/06/95 Reactor Units BV1 Data Feeders PVC NRC ERDS Parameters COND A/E RAD Point 10:
RD029A
?
Plant Spec Point Desc.:
CONDENSER AIR EJEC ACTIV R-SV100 Generic /Cond Desc.:
COND AIR EJECTOR RADICACTIVITY l
Analog / Digital:
A Engr Units / Dig States:
. Engr Units conversion:
N/A Mininus Instr Range:
10 Maxinua Instr Range:
1E6 Zero Point
Reference:
N/A Reference Point Notes:
N/A
?
PROC or SENS:
S Ntaber of Sensors:
1 How Processed:
N/A I
sensor Locations:
SEE UNIQUE SYSTEM DESCRIPTION FIELD Alarm / Trip Set Points:
HI ALM G 430 CPM /LO ALM G -100 CPM NI Detector Power Supply Cut-off Power Level N/A WI Detector Power stoply Turn-on Power Level N/A Instru.ent Failure Mode:
LOW Teaperature Compensation For DP Transmitters: N Level Reference Leg N/A Unique System Dese.:
RM 1SV 100 CONTINU0USLY MONITORS THE EFFLUENT FOR GASCUS ACTIVITY (
l 131, XE 133, KR*85) FROM THE CONDENSER AIR EJECTOR VENT. AN ALAR M INDICATES A PRIMARY TO SECONDARY LEAK. A HIGH-MIGN RAD 10ACTIVIT Y ALARM DIVERTS THE GASEQUS DISCHARGE TO THE CONTAINMENT BUIDING F0 R SUBSEQUENT DISCHARGE THROUGH THE ELEVATED RELEASE PolN1. A BETA SCINTILLATION DETECTOR CONilWUOUSLY MONITORS THE CONDENSER AIR EJE CTOR VENT. OP MANUAL CHAPTER 43, RM 422-1
.