'o y

O Deaver Valley Power Station SNppmgport. PA 15077-0004 (412) 393-5206 (412) 643 8069 F AX GE.ORGE S. THOMAS Iu$ "Nr'vice."#*"'

December 6, 1994 Nuclear Power Division U.

S.

Nuclear Regulatory Commission Attn:

Document Control Desk Washington, DC 20555

Subject:

Beaver Valley Power Station, Unit No. 2 Docket No. 50-412, License No. NPF-73 Emergency Response Data System (ERDS)

In accordance with the requirements published in NUREG 1394 Rev.

1, Section 3.6,

" Administrative Implementation Requirements,"

the enclosed Data Point Library (DPL) changes are being submitted.

These two (2)

DPL's have undergone a

change in their Hi alarm

)

setpoints.

These changes are currently in effect on the Beaver Valley Plant computers which provide the data to the ERDS computer.

Any questions regarding these DPL changes should be addressed to l

Glenn McKee at (412) 393-5778.

j Sincerely, T\\

c_,[5

- eo S.

Thomas Attachments cc:

Mr.

L. W.

Rossbach, Sr. Resident Inspector Mr.

T. T. Martin, NRC Region I Administrator Mr.

J.

R. Jolicoeur, USNRC' Incident Response Branch Mr.

T.

P.

LaRosa, NUS Corporation /El Division Mr.

R. R. Keimig, NRC Region I, Emergency Preparedness Mr.

P.

D.

Kaufman, NRC Region I, Emergency Preparedness Mr.

G.

E.

Edison, Sr. Project Manager

.3J;1J

'p/h I

l 9412130281 941206 s

PDR ADOCK 05000412 P

PDR

Ar e

,e DEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY BV2 ERDS INPUT Date 11/14/94 Re'ctor Unit DV2 a

Data Feeder:

ERFCS

!IRC ERDS Parameter CTMNT SMP WR Point ID:

LO750A Plant Spec Point Desc.

RX CNMT SUMP LVL RSS*LT151A Generic /Cond Desc.

CTMNT SUMP WIDE RANGE LEVEL Analog / Digital:

A Engr Units / Dig Statest IN Engr Units Conversion:

N/A Minimum Instr Range:

0 Maximum Instr hangei 225 Zero Poir t 9eferences CNTFLR Feferenca Point No*es:

SEE UNIQUE SYSTEM DESCRIPTICN FIELD PROC or SENSr S

Number Of Sensors:

1 How Processed:

N/A Sensor Locstioner SEE UNIQUE SYSTEM DESCRIPTION FIELD Alarm / Trip Set Points:

HI ALM a 35 IN NI Detector Power Supply Cut-off Power Level:

N/A N! Detector Pcwer Supply Turn-en Power level:

N/A Inst rument Failure Moder LOW Temperature Compensation For DP Transmitters:

N l

Ievel Reference Leg:

N/A Unique System Dese.

2kSS*LT151A MEASURES CONTAINMENT St#4P LEVEL FROM THE FLOCR TO A HE!

GHT OF 709' 10 3/8" 2RSS-P21A-D SUCTION LINES ARE AT THE 692' 11" LEVEL IN CONTAINMENT. AT 695' THE CCNTAINMENT AIR RECIRCULATION A AND C FANS TRIP.

2RSS*LT151A MEASURES LEVEL FROM Tile CONTAINMENT FIXOR AT ELEVATION (91' 1 1/8" TO A HEIGHT OF 709' 10 3/8", ZERO RE j

F CONTAINMEtTT FLDOR (691' 1 1/8")

REF: MSP-2-13.09, 1DC80-TLD-13A-003s RF-6M; OP. MAN. CHAP. 13 i

c 7

~.

~..

+

2

'e.,,

W 'e' BEAVER VALLEY POWER STATION ERDS DATA POINT LIBRARY BV2 ERDS INPtfr Dates 11/14/94 Reactor Unit.:

BV2 Data Feeder ERFCS NHC ERDS Parameters CTMNT SMP WR s

a Point ID s.

LO751A Plant Spec Point D. esc.t RX CNMT SUMP LVL RSS*LT151B ceneric/cond Dese.:

CTMNT SUMP WIDE RANGE LEVEL Analog / Digital:

A Engr Units / Dig States:

IN Engr Units Conversion:

N/A Minimum Instr Rangen 0

Maximum Instr Range 225 i

Zero Point

Reference:

CNTFLR Reference Point Notes:

SEE UNIQUE SYSTEM DESCRIPTION FIELD PROC or SENS:

S Number Of Sensoxsr 1

llow Processed:

N/A Sennor Locations SEE UNIQUE SYSTEM DESCRIPTION FIELD a

Alarm / Trip Set Pointar HI AIJ4 e 35 IN NI Detector Power Supply Cut off Power Level N/A NI Detector Power Supply Turn-on Power Level:

N/A Instrument Failure Mode LOW Temperature Compensation For DP Transmitters:

N Level Heference Logt N/A Unique System Desc.

2RSS*LT1519 MEASURES CONTAINMENT SUMP LEVEL FROM THE FLOOR TO A HEI GHT OF 709' 10 3/D'. 2RSS-P21A-D SUCTION LINES ARE AT THE 692' 11' 4

LEVEL IN CCNTAINMENT. AT 694' THE CONTAINMENT AIR RECIRCULATION B AND C FANS TRIP.

2RSS*LT151B MEAStJRES LEVEL FROM THE CONTAINMENT F LOOR AT ELEVATION 631' 1 3/6' TO A HEIGHT OF 709' 10 3/8'. ZERO REF j

CONTAINMENT FLOOR (691' 1.1/8"). REF: MS/-2 13.09; 10060-TLD-13A j