ML20058G797

From kanterella
Jump to navigation Jump to search
Forwards NRC Insp Procedure 38703 Entitled, Commercial Grade Dedication
ML20058G797
Person / Time
Site: Farley Southern Nuclear icon.png
Issue date: 11/30/1993
From: Wermiel J
Office of Nuclear Reactor Regulation
To: Stoltz
SOUTHERN NUCLEAR OPERATING CO.
References
NUDOCS 9312100143
Download: ML20058G797 (21)


Text

.-

l

=<

t l-November 30, 1993 Southern Nuclear Operating Company Nuclear Technical Services 40 Inverness Center Parkway PO Box 1295 Birmingham, Alabama 35201

Dear Mr. Stoltz:

Enclosed is the Commercial Grade Dedication Inspection Procedure which Mr. William Russell spoke of at the NUSMG meeting in Annapolis on the 21st of October.

I believe you requested a copy at that time.

I'm sorry it has taken this long to provide, but there was a formatting and printing delay. While this Procedure is not directly applicable to commercial software systems, you may be able to get an understanding of the type of concerns the regional personnel would be looking for in any inspection of software commercial grade dedication procedures.

Original signed by:

Jared S. Wermiel, Chief Instrumentem.on and Controls Branch Division of Reactor Controls and Human Factors Office of Nuclear Reactor Regulation

Enclosure:

Inspection Procedure 38703

Contact:

Paul Loeser, HICB 504-2825

[RP ig C P:lrJ'h di U d DISTRIBUTION Pr;n ripm -

' ' W L -A u A M

. Central File PDR HiCB R/r 002069 P. Loeser J. Mauck J. Wermiel w.a p?- /J.

y & q M & ( n/g )

/ e g g. 2 o^

(SNIICBj BC:(llCB:DRCH HICB PLoeser:lshk Nb JWeh II / 3793 M h0 93

// /[O/93

/

DOCUMENT NEME:

S10LTZ.LTR 030C04 9312100143 931130 I

PDR ORQ NRRB

/

PDR

l f n%

3 UNITED STATES f)1

[,

NUCLEAR REGULATORY COMMISSION o.s i~orou. o.c. roses ooos 4.....-

NRC INSPECTION MANUAL RviB INSPECTION PROCEDURE 38703 COMMERCIAL GRADE DEDICATION 1

PROGPAM APPLICABILITY:

2515 SALP FUNCTIONAL AREA: ENGINEERING (50ETS-0) 38703-01 INSPECTION OBJECTIVES 01.01 To determine whether the failure of a safety-related system, structure, component (SSC), or part to perform its intended safety function was the result of a deficient comercial grnde item (CGI) dedication process.

01.02 To verify that the licensee's process for dedicating CGIs, as implemented, meets the applicable portions of Appendix B to 10 CFR Part 50 and provides reasonable assurance that CGIs will perform their intended safety function.

i 38703-02 INSPECTION REQUIREMENTS 02.01 Reactive Inspection Recuirements a.

Initial Evaluation.

After reviewing the licensee's evaluation of the failed item, determine if the failed item was procured as a CGI and i

dedicated for safety-related applications.

If the failed item was dedicated, review the complete procurement and dedication records to determine if the commercial grade dedication process was sufficiently thorough.

b.

Further Assessments.

If it is determined that the dedicated item failed as the result of certain critical characteristics not being identified and/or properly accepted, the inspector should perform the following assessments:

1.

Determine if other CGIs from the same accepted lot or batch as the failed dedicated CGI have been similarly dedicated and installed in other safety-related applications.

If yes, determine if the licensee has evaluated the operability of the systems or components where these CGIs are installed.

The inspector also should review l

licensee-provided data, if available, for some CGIs (non-dedicated) that failed in applications that were not safety-related.

Explore l

l the possibility that the same CGIs also may have been used (following dedication) in a safety-related application and may have the potential to affect the safe operation of a SSC.

Issue Date:

11/08/93 38703 l

t r

2.

If possible select and evaluate, as in step 1 above, at least three other dedicated CGIs having sinilar applications and critical characteristics as the CGI(s) that resulted in the identified failures.

3.

If, after performing step 2 above, it is determined that there were weaknesses in the comercial grade dedication process, the ).ypector should periorm a more comprehensive inspection of the licensee's dedication process in accordance with the inspection requirements in Section 02.02 below.

02.02 Procramatic Insoection Recuirements a.

Review of Procram and Procedures.

Using the inspection guidance contained in Section 03.02 and Appendix A to this procedure, review the licensee's program and procedures for the procurement and dedication of CGIs in order to understand the basic operation of the licensee's

program, b.

Selection of Dedication Packaoes.

Select approximately 20 dedication i

packages for evaluation from a list of comercially dedicated items provided by the licensee.

Request that the licensee provide (or make available for review) a complete package of the pertinent procurement and dedication records for each item.

c.

Evaluation of Dedication Packaoes.

Using the inspection guidance contained in Section 03.01 of this procedure, perform a detailed i

evaluation of the dedication packages selected in item b above.

j d.

Evaluation of Trainino Effectiveness.

If the inspector's evaluation of comercial grade dedication activities indicates there are weaknesses in the way these activities are being performed, the inspector should investigate further to determine if weaknesses within the licensee's training program may have contributed to the cause. The inspector should determine if the licensee is implementing an effective training program.

38703-03 INSPECTION GUIDANCE GENERAL GUIDANCE Backaround. Licensees are required to ensure the quality of items purchased and installed in safety-related applications. In the past, licensees procured major assemblies from approved vendors who maintained quality assurance (QA) programs pur tuant to Appendix B to 10 CFR Part 50. Because of the decrease in the number of qualified nuclear-grade vendors, licensees are increasing the numbers of comercial grade replacement parts that they procure and dedicate for use in i

safety-related applications.

1 Since comercial grade dedications have increased in number, the Nuclear-Regulatory Comission (NRC) has developed this inspection procedure to provide guidance to assist the inspector in assessing the effectiveness of the implementation of the licensee's comercial grade procurement practices and provide for early identification of any adverse trends or emerging problems.

The Vendor Inspection Branch, of the NRC's Office of Nuclear Reacter Regulation, is available to assist with specific questions that arise during the performance of this procedure.

387)3 Issue Date:

11/08/93

Schedulino the Inspection. This inspection procedure should be considered for implementation when there is reason to believe that the failure of a SSC or part to perform its intended safety function was the result of weaknesses in CGI dedication. This inspection procedure may be implemented independently or it may be used as a supplement to other major team inspections.

Such inspections may include maintenance, modification, or system-specific inspections where review of failed SSCs or parts is appropriate, or an augmented inspection team investigating failures.

The NRC should contact the appropriate NRC and licensee personnel to schedule the inspection.

When practical, inform the licensee of the objectives of the inspection 4-6 weeks before the inspection is to begin and advise them of information that will be needed, such as a list of items that the licensee purchased as comercial grade after July 1990 and subsequently dedicated for use in safety-related applications. Before the beginning of the onsite inspection, the inspector should request and review the licensee's program and procedures to become familiar with the licensee's procurement and dedication process.

Also explore with the licensee the possibility of obtaining a list of recent component failures. Request this list only if the licensee states this type of information would be easily retrievable. The list of component failures can be used by the inspector during the selection of dedication packages for review described in Section 02.02 of this inspection procedure.

This inspection procedure is consistent with the Nuclear Management and Resources Council (NUMARC) initiative for improving the utilization of CGIs in nuclear safety-related applications that was implemented in July 1990. The methods used to comercially dedicate items procured by licensees before that date will not necessarily meet the guidance contained in this inspection procedure.

If the inspector encounters a significant failure of a comercially dedicated item, j

which was dedicated before July 1990, the inspector may review the dedication of that item with the understanding that the licensee was not expected to meet the i

current guidelines.

SPECIFIC GUIDANCE l

03.01 Reactive Insoection I

i a.

Initial Evaluation. A failure resulting from general weaknesses in the comercial grade dedication program ney occur when the important design, j

material, and performance characteriatics that are necessary to provide j

reasonable assurance that the dedicated CGI will perform its intended safety function are not addressed during dedication.

For example, failures of safety-related bolting have occurred when the dedication process did not verify that the material composition and/or mechanical properties met the specified requirements and nonconforming material was supplied.

Review and discuss with licensee personnel the failure / root-cause analysis when required or applicable for the failed CGI. The inspector should attempt to determine if the failure was due to a design deficiency, failure unrelated to the item's safety function, or normal wear, and eliminate these from further review.

The inspector should focus on the inspection of failures that appear to be due to weaknesses in the comercial grade dedication process.

If none of the failures are due to weaknesses in the comercial grade dedication process, then the inspector should not continue using this inspection procedure.

If the inspector decides to change the focus of the inspection to examine other issues related to the failures, such as the adequacy of corrective Issue Date:

11/08/93 38703 I

actions, other procedures should be used, such as NRC Inspection Procedure 92720, ' Corrective Action." Once the failure mode and cause of failure have been postulated or determined, review the dedication package as described in Section 03.01a(1) to determine if appi

-iate critical characteristics had been identified by the licensee. App iix A to this inspection procedure should not be interpreted as inspection requirements but only as a discussion of dedication issues including guidance on selection and verification of critical characteristics. Appendix A, if properly implemented, represents an acceptable means of complying with regulatory requirements.

Individual licensee's may develop alternate methods of achi$ving Appendix B compliance.

Appendix B provides definitions of terms used for comercial grade dedication activities, and Appendix C provides the typical contents of a dedication package.

The goal of the review of the dedication packages is to provide reasonable assurance that the CGIs dedicated for safety-related applications will perform their intended safety functions.

Inspection effort should be directed towards the identification of weaknesses in the dedication process that could potentially render SSCs or parts inoperable.

When reviewing licensee's operability determinations for dedication of CGIs, the inspector should refer to the " Technical Guidance" section of HRC Inspection Manual, Part 9900, for further guidance.

a(1)

Review of Dedication Packaaes.

After becoming familiar with the licensee's procurement and dedication program and procedures, perform a detailed review of the dedication package as described below.

Determine if the safety function of the item for its intended use has been identified by reviewing the documents associated with the technical evaluation including, as applicable:

classification of the item consideration of credible failure modes

- item equivalency /substitutien evaluaticas Determine if the important design, material, and performance a

characteristics relevant to the safety function have been identified.

Determine whether the licensee verified the characteristics necessary to provide reasonable assurance that the i

item will perform its intended safety function.

If appropriate, l

take into account post-installation testing and periodic surrillance testing and inspection.

Review the basis for engineering judgment when it is used as the basis for selection or verification of critical characteristics.

Determine whether the item is an equivalent replacement or a new item replacement of an obsolete item.

Determine if the item is or may be used in a different safety-related application than previously evaluated in which different design, material, and performance characteristics may be applicable.

This is especially applicable for generic dedications of bulk items and stock material.

Determine if the dedication ensures those design, material, and performance characteristics relevant to the safety function.

38703 Issue Date:

11/08/93

Determine t:hy the item is being replaced. Have there been repeated 3

failures?

Is the degraded performance a result of adverse t

environment? Did it fail because it was a refurbished or fraudulent item? General information on similar activities subject to Appendix B to 10 CFR Part 50 is provided in American National Standards Institute (ANSI) AIMI N45.2-1977,

" Quality Assurance Program Requirements for Nucl.rar Power Plants," Section 17, " Corrective Action."

Determine how the identity of the item is controlled from the time

=

it is receipt inspected until the time it is installed.

General information on similar activities subject to Appendix B to 10 CFR i

Part 50 is provided in ANSI N45.2-1977, Section 9, " Control of Parts and Components."

Determine if information learned during the dedication process is

=

fed back to the appropris' 9ersons to evaluate existing stock items, or installed items, c for future use in surveys and source verifications. This information could include positive and adverse findings obtained during surveys and source verifications. General information on similar activities subject to Appendix B to 10 CFR Part 50 is provided in ANSI N45.2.13-1976, " Quality Assurance Requirements for Control of Procurement of Items and Services for Nuclear Power Plants," Section 9, " Corrective Action."

Refer to the discussion of significant dedication issues in Appendix A l

for guidance during the review of dedication packages. Also refer to the specific guidance for each of the four dedication methods provided below.

Focus should be on those activities that are likely to affect the performance of the items being dedicated.

It is not necessary to review the licensee's programmatic compliance to the 18 criteria of Appendix B to 10 CFR Part 50 as they may nat apply to the activities reviewed.

Appendix B to 10 CFR 50 does not apply to commercial grade activities which occur prior to dedication for use in a safety-related system. It also should be recognized that this appendix provides f er the application of QA to safety-related systems and components consistent with their importance to safety (graded quality approach).

i Although guidance concerning the application of graded quality assurance is discussed in the first paragraph of Appendix A to this inspection procedure, it is expected that the inspector will need to exercise considerable judgment in determining the adequacy of controls applied to a specific activity.

The following are the four acceptance methods that can be used to accept CGIs.

These methods provide, either individually or in combination, a i

means to reasonably ensure that a CGI that is receivea meets the requirements of the item specified. The results of employing each method should be documented.

Method 1 - Special Tests and Inspections General infamation on similar activities subject to Appendix B to 10 CFR Part 50 is provided in ANSI N45.2.13-1976, Srction 10

" Acceptance of Item or Service."

Use the following approach to review packages that were dedicated using this method.

1 Issue Date:

11/08/93 38703 1

To the ' extent practicable, attempt to uitness receipt inspections and tests of -in-process dedication of CGIs that are similar to that of the failed item to verify the identified critical characteristics.

Review receiving records and associated tests and inspections.

Review post-installation test records.

Verify that the tests and inspections specified for acceptance adequately verify the identified critical characteristics.

Verify that sampling plans are controlled and have adequate.

technical basis, considering lot traceability and homogeneity, I

complexity of the item, and adequacy of supplier controls.

Verify t..

CGI receiving inspection activities are adequately controlled under a quality program regardless of whether they are being performed in conjunction with other plant receipt inspection activities.

Verify that receipt inspection activities establish and maintain traceability of CGIs by capturing and appropriately relating traceability documents through identification and monitoring of CGIs.

Verify that measuring and test equipment was properly calibrated, that approved vendors were used to perform tests, and that personnel were qualified to perform the tests.

Method 2 - Comercial Grade Survey Use the following guidance to review packages that were dedicated using this method:

Determine if the guidance of Generic Letter 89-02, or an appropriate alternate, is included in the appropriate procedures. Specifically, confirm that (1) the documented commercial quality program was effectively implemented end (2) the surveys were conducted at the location necessary to v rify that adequate controls were exercised e

on distributors as well as manufacturers.

Through interview, determine if the persons who perform vendor surveys are knowledgeable in the following:

i the use of performance-based surveys screening third-party surveys processing and evaluating adverse findings resulting from the review of third-party surveys to ascertain if those findings affect CGIs already installed or stored in the warehouse awaiting future installation General information on similar activities subject to Appendix B to 10 CFR Part 50 is provided in ANSI N45.2.12-1977, " Requirements for Auditing of Quality Assurance Programs for Ncclear Power Plants," and ANSI N45.2.23-1978, " Qualification of Quality Assurance Program Audit Personnel for Nuclear Power Plants."

38703 1: sue Date:

11/08/93 4

E

Verify that the supplier's comercial quality controls are imposed in the procurement documents.

Determine if the critical characteristics that are to be verified by the survey team are accurately and completely incorporated in the survey plans.

Determine if the validity of supplier documentation, relied on in the dedication of the item, is verified during the survey.

Determine if surveys of comercial grade suppliers are performance based as opposed to programatic.

Specifically, verify that the l

critical characteristics for the CGIs being surveyed are controlled by the supplier's quality activities.

Determine if survey teams include technical and quality personnel, as appropriate, that are knowledgeable in the operation of the item (s) and the associated critical characteristics to be verified, including any special processes such as welding and heat treatment that are specific to the critical characteristics.

Determine if surveys are conducted at appropriate times relative to the procurement.

Are surveys required to be updated on a regular basis to support dedication?

Determine if the control of subvendors is adequately addressed by the surveys so that the supplier has an adequate basis to accept test results and certifications from the subvendor.

Determine if pertinent information about a supplier or its products is used to plan, conduct, and report results of surveys and source verifications.

Such information could have been available from source verifications, receiving inspections, the dedication process, supplier / product performance history, or outside sources such as NRC information notices and bulletins, nuclear plant reliability data system reports, or Nuclear Utility Procurement Issues Comittee (NUPIC) comercial grade survey reports.

Method 3 - Source Verification General information on similar activities subject to Appendix B to 10 CFR Part 50 is provided in ANSI N45.2.13-1976, Section 10.3.2, " Acceptance by j

Source Verification." Use the following approach to r6 view packages that were dedicated using this method:

Deternine if source verifications involve witnessing the supplier performing quality activities on the actual items being procured and adoquately verify the item's critical characteristics.

Determine if personnel who participated in the socrce verification surveys were qualified for their specific assignment.

Determine if appropriate hold points are imposed in the purchase orders. This would include a hold point to verify design, material, and performance characteristics relevant to the safety function i

I that cannot be verified after the item has been completely-manufactured.

Issue Date:

11/08/93 38703 l

Determine if the results of the source verifications were adequately

-l o

documented.

I i

Method 4 - Acceptable Supolier/ Item Performance Record Use the following guidance to review packages that were dedicated using this method:

Determine if the guidance of Generic Letter 89-02, or an appropriate alternate, has been incorporated. Specifically, (1) the established historical record is based on industry-wide performance data that is directly applicable to the item's critical characteristics and the intended safety-related application and (2) the manufacturer's measures for the control of design, process, and material _ changes i

have been adequately implemented as verified by survey (multi-i licensee team surveys are acceptable).

Detennine if information pertinent to the CGI's quality of performance, obtained from outside sources (e.g., operational event reports, NRC, vendor equipment and technical information program, and Institute of Nuclear Power Operations) and from commercial grade

surveys, source verifications, receipt inspections, previous dedication or qualification and operational history, is factored into the dedication process.

Determine if the item or manufacturer is included in the licensee's performance trending program.

b.

Further Assessments l.

No inspection guidance.

2.

From the list of dedicated items provided by the licensee, the inspector should select for review approximately three other dedication packages having similar applications and critical characteristics as the CGI(s) that resulted in the identified failures.

After the selet.tions have been made, the inspector should request that the licensee compile a complete package of all the procurement and dedication records for each item. Typical contents of a dedication package are described in Appendix C of this inspection procedure.

The inspector should review the dedication packages as described in Section 03.01a(1) of this inspection procedure.

3.

No inspection guidance.

1 03.02 Proarammatic Insoection a.

Review of Procram and Procedures.

The review of the program and procedures should be performed to familiarize the inspector with the licensee's CGI tiedication process.

For cases in which problems are identified with the licensee's CGI dedication process, the inspector may decide to perform a more extensive review of the program ano procedures to determine if these problems are the result of inadequate procedures.

The inspector's review should include procedures that control:

procurement activities; material control; the dedication of CGIs, including receipt inspection and acceptance testing; surveys of 38703 Issue Date:

11/08/93

commercial grade suppliers; classification of compsnents; training' c' l

personnel;E trending of supplier performance; and equipment failures.

Attempt to identify any apparent weak areas to concentrate on during the evaluation of the. program implementation.

l Tfter arriving onsite, the inspector should request that the-licensee explain its comercial grade dedication process and conduct a walkthrough -

of areas associated with it. Areas in the walkthrough could include the engineering, receipt inspection, component testing, and warehouse. The inspector should become familiar with key licensee personnel involved in the commercial grade dedication process.

These key personnel should.

include the responsible engineer (s) who developed the dedication i

package (s) and systems engineers, procurement engineers, receipt.

inspectors, quality assurance engineers and inspectors, and warehouse.

personnel. The inspector should discuss the commercial grade dedication j

process with these key personnel to gain a better understanding of the process, including:

i How processing of CGI procurement documents is controlled under tN quality program and how they receive review and approval.

General information on similar activities subject to Appendix B to 10-CFe Part 50 is provided in ANSI N45.2.13-1976, Section 3, " Procurement

'i Document Preparation, Review, and Change Control."

How technical personnel participate in the preparation, review, and i

approval process of procurement documents.

How consistency and coordination is maintained between corporate l

1evel, engineering / support level, and site level programs and

~!

implementing procedures.

Selection of Dedication Packaoes. As discussed in the general guidance

}

section above, the NUMARC initiative for the utilization of CGIs in nuclear safety-related applications was not implemented until July 1990.

Therefore, the methods used to perform commercial grade dedication of items procured or dedicated by licensees before that date will. not necessarily meet the guidance contained in this inspection procedure.

The selection process should be perfonnance oriented (e.g., weighted toward the review of dedication packages for equipment, components, or

-j parts that have experienced' failures). To accomplish this, the inspector should request from '.he licensee approximately 20 packages for review using the two-step approach described below.

The licensee should be t

given sufficient lead time to prepare the 20 packages and make them available for the first day of onsite inspection.

Sten 1: Review the licensee's records available at the plant site to identify recent failures (approximately the last 2 years) of equipment, components, or parts.

Review these failures to determine if any were CGIs dedicated for use in safety-related applications. -If available, j

select approximately 75 percent of the total sample from CGI failures.

Steo 2: From the list of dedication packages supplied by the licensee.

under the " Inspection Guidance" section of this procedure, ' select the l

remainder of packages for review.

The total sample. size - including j

packages from steps 1 and 2 should be approximately 20 packages.

However, the inspector can select a larger or smaller sample depending on the complexity of the packages and the time available. ~ The inspector Issue Date:

11/08/93

.9-38703 J

)

should select these packages on the basis of the following j

considerations:

The inspector should select packages for items whose failure would have the most effect on the ability of the plant to safely operate, safely shutdown from an adverse condition, or maintain a safe 1

shutdown condition.

If time permits, review the plant-specific j

probabilistic risk assessment, individual plant examination, and risk-based inspection guides that provide information on the risk significance of safety-related plant equipment.

The inspector should take a performance oriented approach to the selection process by incl'uding in the :; ample packages those items that have been problems.in the past.

Review available sources of information to identify any known failures of CGIs that were used in safety-related applications.

These sources of information could include:

i component failure lists or lists of items requiring frequent maintenance or replacement as provided by the licensee misrepresented or fraudulent items reported in NRC information i

notices licensee trending of equipment and supplier performance previous history of component failures or malfunctions as reported in licensee event reports or plant nonconformance reports The inspector should include both simple and complex packages in the sample as well as packages that include a variety of dedication methods (e.g., Methods 1 through 4) described in Section 03.01a(1) above.

In addition to selecting packages based on the above considerations (safety significance, complexity, and failures), the inspector should attempt to select samples from each of the following areas:

electrical, instrumentation and control, mechanical equipment, and materials.

i c.

Evaluation of Dedication Packaoes.

Perform a detailed review of the dedication packages as described above in Section 03.01a(1).

d.

Evaluation of Trainino Effectiveness.

Experience gained during the i

procurement assessments and pilot inspections suggested that training of personnel involved in CGI dedication activities was a very important factor in the development of a good CGI dedication program.

The CGI dedication process generally requires more highly qualified / trained personnel than specified in Appendix 8 to 10 CFR Part 50 procurement.

J Personnel involved in this process need to be familiar with current industry and NRC guidance and have a strong interface with the licensee's design / engineering organizations.

The training expectations, however, should not exceed what is required by the existing licensee's QA program.

As applicable to their job function, select and review the training records for individuals involved in the following areas:

i Determining the safety classification of an item. Training in this area is appropriate when the job function includes reclassification 38703 Issue Date:

11/08/93

)

of items or establishing safety classification of piece parts of safety-related components.

Specifying design,

material, and performance characteristics relevant to the safety function and establishing the acceptance criteria for these characteristics.

Speci fying or perfoming commercial grade

surveys, source verifications, and tests and inspections, including enhanced post-receipt verification testing or inspection.

The preparation and review of procurement documents.

Through observation, interviews, and a review of records of work performed by the individuals:

l Determine if the individuals selected have adequate knowledge to

=

perform the specific tasks assigned to them.

Attend a trainiing course, if available, or review the lesson plans for selected training courses.

Determine if training inadequacies contributed to any of the deficiencies that may be identified during the inspection.

Determine if the personnel are familiar with the program requirements and procedures and if they have been properly trained.

in the dedication process.

It should be noted that alternatives to a formal training program may be adequate to ensure satisfactory program implementation (e.g., on the job training). Additional information in this area is provided in NRC Inspection Procedure 41500, " Training and Qualification Effectiveness."

l 38/53-04 INSPECTION RESOURCE ESTIMATE The estimated number of onsite inspection hours required to complete all inspection requirements is 144 hours0.00167 days <br />0.04 hours <br />2.380952e-4 weeks <br />5.4792e-5 months <br /> when both the reactive and programmatic options are implemented. This estimate is for broad resource planning and is not intended as a quota or standard for judging inspector or regional performance.

The on-site hours can be expected to vary significantly depending on the specific circumstance and scope of each inspection.

38703-05 REFERENCES The following documents are listed for the inspector's information only and are not considered regulatory requirements unless the licensee has formally committed to implementing any of these documents for application to safety-related activities. The inspector may wish to review these documents to become familiar with comercial grade dedication issues.

ANSI N45.2-1977, " Quality Assurance Program Requirements for Nuclear Power Plants," as endorsed by V' Regulatory Guide 1.28, Revision 2.

ANSI N45.2.13-1976, "t:

, Assurance Requirements for Control of Procurement of Items and Services for Nuclear Power Plants," as endorsed by NRC Regulatory Guide 1.123, Revision 1.

Issue Date:

11/08/93 38703

Electric Power Research Institute (EPRI) NP-5652, " Guidelines for the Utilization of Commercial-grade Items in Nuclear Safety Related Applications (NCIG-07)," as conditionally endorsed in NRC Generic Letter 89-02.

Generic Letter 89-02, " Actions to Improve the Detection of Counterfeit and Fraudulently Marketed Products" (microfiche 48960-001).

Generic Letter 91-05, " Licensee Commercial Grade Procurement and Dedication i

Programs" (microfiche 57468-264).

NRC Inspection Procedure 41500, " Training and Qualification Effectiveness."

6 SECY-90-304, "NUHARC Initiatives on Procurement" (microfiche 55277-049).

SECY-91-291,

" Status of NRC's Procurement Assessments and Resumption of Programmatic Inspection Activity" (micrnfiche 59490-079).

END Appendices:

i A.

Dedication Issues B.

Definitions 1

C.

Contents of Dedication Packages i

38703 Issue Date:

11/08/93 j

4 APPENDIX A DEDICATION ISSUES BASIS FOR THE SELECTION AND VERIFICATION OF CRITICAL CHARACTERISTICS h

1.

Consideration of Item's Safety Function Critical characteristics should be based on the item's safety function.

i The licensee is responsible for (a) identifying the important design, material, and performance char'acteristics that have a direct effect on the item's ability to accomplish its intended safety function and (b) selecting from these characteristics a set of critical (or acceptance).

characteristics that, once verified, will provide reasonable assurance that the item will perform its intended safety function. Criterion II cf Appendix B to 10 CFR Part 50 provides for the application of quality assurance over activities affecting the quality of structures, systems, and components to an extent consistent with their importance to safety.

This graded quality approach can be _used h the selection and verification of critical characteristics for Lanercial grade items (CGIs).

When an existing equipment specification is available that contains adequate technical requirements for the item being purchased, that specification can be used to select the critical characteristics for j

this item.

2.

Graded Ouality Assurance

'The application of graded quality assurance to the CGI dedication process should include consideration of the item's importance to safety and other' factors specific to'the item being procured. Certain items and services may require extensive controls throughout all stages of development while others may require only a limited quality assurance involvement in selected phases of development.

The following factors should be considered in determining the extent of quality assurance to be applied:

l (a) The importance af malfunction or failure of the item to plant safety, (b) the complexity or uniqueness of the item, (c) the need for special j

controls and surveillance over process and equipment, (d) the degree to which functional compliance can be demonstrated by inspection and test, and (e) the quality history and degree of_ standardization of the item.

Additional guidance on the use of graded quality assurance can be found j

in the nonmandatory appendix to ANSI N45.2.13-1976.

3.

Consideration of Failure Modes An evaluation of credible failure modes of an item in its operating-environment and the effects of these failure modes on the item's safety function may be used in the safety classification of an item and as a basis for the selection of critical characteristics.

]

4.

Reasonable Assurance -

The dedication process represents an acceptable method of ' achieving j

compliance with Appendix B to' 10 CFR Part 50 with the purchaser assuming -

many of the responsibilities for ensuring quality and functionality of an item that had previously been the responsibility of the vendor. In this context,-reasonable assurance consists of the purchaser controlling or Issue Date:

11/08/93 A-1 38703, Appendix A 1

verifying the activities affecting the itca's quality to an extent consistent tsith the item's importance to safety or ensuring that these activities are adequately controlled by the supplier. For more complex items, dialogue with the original equipment manufacturer may be necessary to identify the design and functional parameters of specific piece parts.

Once the dedication process is completed, the quality assurance and/or other measures applied to those aspects of the item that directly affect its safety function should result in the same level of performance as for a like item manufactured or purchased under a quality assurance program of Appendix B to 10 CFR Part 50.

5.

Enoineerina Judoment Engineering judgment can be used in selecting those important design, material, and performance characteristics that are identified as the item's critical characteristics. The bases for engineering judgment for this application should be documented.

TRACEABILITY Material / Items Purchased From Distributors Traceability can be defined as the ability to verify the history, location, or application of an item by means of recorded identification.

Where the item's acceptance is based entirely or partially on a certification by the manufacturer, the traceability must extend to the manufacturer. The purchaser should ensure by survey or by other means that the manufacturer has established adequate traceability controls and that these controls are effectively implemented. For situations in which intermediaries (distributors) are included in the supply chain, the activities of these organizations may need to be surveyed to ensure that traceability and proper storage conditior:s are maintained. A survey of the distributor may not be necessary if the distributor acts only as a broker and does not warehouse or repackage the items or in cases where traceability can be established by other means such as verification of the manufacturer's markings or shipping records.

SAMPLING 1.

Established Heat Traceability (Materialsl When heat traceability of metallic material has been established and each piece of the material is identified with the material heat number, chemical analysis and destructive testing required for the acceptance of thi: ::t:ri:1 ::y be performed on one piece of the material.

The same rationale may be used for the acceptance of containers of nonmetallic materials such as lubricants providing that traceability has been 1

established and each container is identified with a unique mix or batch number.

2.

Established Lot / Batch Control (Itens)

When lot / batch (defined as units of product of a single type, grade, class, size, and composition, manufactured under essentially the same conditions and at essentially the same time) control is established through a commercial grade survey, the party performing dedication of such items can use sampling prescribed by standard statistical methods 38703, Appendix A A-2 Issue Date:

11/08/93 1

that are based on homogeneous product lots. Such sample plans should be identified and should provide for the verification of the critical characteristics with confidence level consistent with the item's importance to safety.

Other means of demonstrating adequate lot / batch control may include satisfactory performance history and the results of receipt inspection / testing.

When such methods are used as a basis for developing product sampling strategy, they should be supported by documented objective evidence.

3.

Material and Items With No Lot / Batch Control When lot / batch control cannot be established, sampling plans need to be considered on individual, item-specific basis and ensure that they are capable of providing a high level of assurance of the item's suitability for service. There may be situations where each item needs to be tested.

COMMERCIAL GRADE SURVEYS 1.

Verification of Vendor's Control of Specific Characteristics A comercial grade survey should be specific to the scope of the CGI(s) being purchased.

The vendor's controls of specific critical characteristics to be verified during the survey should be identified in the survey plan.

The verification should be accomplished by reviewing the vendor's program / procedures controlling these characteristics and observing the actual implementation of these controls in the manufacture of items identical or similar to the items being purchased.

2.

Identification of Aeolicable Proaram/ Procedures The vendor must have a documented program and/or procedures to control the critical characteristics of the item or items being procured that are to be verified during the survey. When many items are being purchased, a survey of a representative group of similar items may be sufficient to demonstrate that adequate controls exist.

If the vendor's controls are determined to be satisfactory, purchase orders for these items should invoke these controls as contract requirements by refererking the applicable program / procedure (s) and revision. If multiple working level procedures are applicable to the vendor's activities, which affect the item's critical characteristics and these procedures, in turn, are control?ed by a higher level document, it may be appropriate to reference that. document in the purchase order. It is important to ensure that the specific controls reviewed and accepted during the survey be applied during the manufacturing process. Upon completion of the work, the vendor should certify compliance with the purchase order requirements.

3.

Documentation of Survey Results Comercial grade survey documentation should include the identification of the item or items for which the vendor is being surveyed, identification of the critical characteristics of these items that the vendor is expected to control, identification of the controls to be applied (program / procedure and revision), and a description of the verification activities performed and results obtained.

Critical characteristics that are not adequately controlled should be addressed by contractually requiring the vendor to institute additional controls or by utilizing other verification and acceptance methods.

Issue Date:

11/08/93 A-3 38703, Appendix A

l 4.

Survey Frecuency Comercial grade surveys should be conducted at sufficient frequency to ensure that the process controls applicable to the critical characteristics of - the item procured continue to be effectively implemented.

Factors to be considered in determining the frequency of comercial grade surveys include the complexity of the item, frequency of procurement, receipt inspection,1 tem performance history, and knowledge _

i of changes in the vendor's controls.

The survey frequency should not exceed the audit frequency established for 10 CFR Part 50, Appendix B, suppliers.

ACCEPTANCE OF CERTIFIED MATERIAL TEST REPORTS (CMTRs) AND CERTIFICATES OF COMPLIANCE (CoCs)

Validity Verified Throuch Vendor /Sucolier Audit or Testino When the verification of critical characteristics is based on vendor CMTRs or Cots, the validity of these documents should be ensured.

This can be accomplished through a comercial grade survey or, for simple items, periodic testing of the product on receipt.

Such verifications should be conducted at intervals comensurate with the vendor's past performance. If the item's supply l

chain includes a distributor, a survey of the distributor's activities may be necessary (see " Traceability").

USE OF INDUSTRY GUIDANCE The Electric Power Research Institute (EPRI) NP-5652, " Guideline for the Utilization of Comercial Grade Items in Nuclear Safety Related Applications (NCIG-07)," defines critical characteristics as " identifiable and measurable attributes / variables of a CGI, which once selected to be verified, provide reasonable assurance that the item received is the item specified."

NRC's conditional endorsement of EPRI NP-5652 by Generic Letter 89-02 was based on interpreting that in the EPRI definition of critical characteristics the " item specified" encompassed those attributes that are essential for the performance of the item's safety function.

This interpretation is consistent with the definition of " critical characteristics for acceptance" found in EPRI NP-6406,

" Guidelines for the Technical Evaluation of Replacement Items in Nuclear Power Plants," which notes that critical characteristics for acceptance are a subset of " critical characteristics for design."

The EPRI NP-6406 definition of

" critical characteristics for design" includes those attributes that ensure the performance of the item's design function.

Published NRC guidance does not differentiate between design and acceptance critical characteristics and the CGI dedication guidance provided in Generic Letters 89-02 and 91-05 does not suggest that all dcsign requirements of an item need to be verified during the dedication process.

Rather, the licensee is expected to identify the item's design, material, and performance characteristics that have a direct effect on the item's ability to accomplish its intended safety function and select from these characteristics a set of crit' cal (or acceptance) characteristics that, once verified, will provide reasonable assurance that the item will perform that function.

Consistency in the definition of critical characteristics can be improved by equating the NRC's definition of critical characteristics to the EPRI definition of " critical characteristics for acceptance."

END 38703, Appendix A A-4 Issue Date:

11/08/93

~

APPENDIX B DEFINITIONS The following terms are listed to provide the inspectors with working definitions of important terms used during the procurement and dedication of commercial grade items (CGIs). These terms are defined only in the context of the CGI dedication process and are solely to aid the inspector in the inspection process.

Basic Component - A plant structure, system, component, or part thereof necessary to ensure one of the following:

condition the capability to prevent or mitigate the consequences of accidents that could result in offsite radiation exposuras comparable to those referred to in 10 CFR Part 100.11 Certificate of Comoliance - A written statement attesting that the materials are in accordance with specified requirements.

Certified Material Test Report - A document attesting that the material is in accordance with specified requirements, including the actual results of all required chemical analyses, tests, and examinations.

Commercial Grade Item - An item satisfying All the following criteria:

i

  • not subject to design or specification requirements that are unique to nuclear facilities
  • used in applications other than nuclear facilities

'I

  • ordered from the manufacturer / supplier on the basis of specifications set forth in the manufacturer's published ;:roduct description (e.g., catalog)

Commercial Grade Survey - Activities conducted by the purchaser or its agent to i

verify that a supplier of CGIs controls, through quality activities', the critical chara:teristics of specifically designated CGIs, as a method to accept those items for safety-related use.

Critical Characteristics - Those important design, material, and performance characteristics that, once verified, will provide reasonable assurance that the item will perform its intended safety function.

Dedication - The process by which a CGI is designated for use as a basic component. This process includes the identification and verification of critical characteristics. (Also refer to definition in 10 CFR Part 21.3(4)(c-1))

Enaineerina Judament - A process of logical reasoning that leads from stated premises to a conclusion.

This process should be suppo'.ted by sufficient i

documentation to permit verification by a qualified individual.

Issue Date:

11/08/93 B-1 38703, Appendix B 4

~

Source Verificaliqti - Activities witnessed at the suppliers' facilities by the purchaser or its agent for specific items to verify that a supplier of CGIs controls the critical characteristics of that item as a method to accept the item

-for safety-related use.

Traceability - Is the ability to verify the history, location, or application of an item by means of recorded identification.

END l

i 38703, Appendix B B-2 Issue Date:

11/08/93 J

APPENDIX C CONTENTS OF DEDICATION PACKAGES The dedication packages compiled by the licensee may contain the following items, as applicable, depending on the item chosen and the dedication methods used.

  • Purchase requisitions and purchase orders.
  • Other pertinent vendor / licensee correspondence.
  • Design specifications - original and updated to verify certain important parameters, such as original design pressure of a system or degraded pickup voltage of a solenoid or relay.
  • Catalog specifications.
  • Procurement basis evaluation - like-for-like, equiniency, plant design change packages, drawing and specification updates.
  • Haterial receiving reports, packing lists / invoices, and other shipping documents.
  • Receipt inspection reports and any related test reports.
  • Other documents to trace the item from the time it was dedicated to the time it was installed, tested, and accepted.
  • Certificates of conformance/ compliance / quality.
  • Vendor test and inspection reports.
  • Third-party or subvendor test and inspection reports.
  • Shelf life information.
  • Design / material / process change history information.

- safety classification

- identification of safety functions / application requirements

- identification of critical characteristics identification of verification methods and acceptance criteria for the critical characteristics

- evaluation of credible failure modes (if applicable)

. Any deviation from design, material, and performance characteristics relevant Issue Date:

11/08/93 C-1 38703,' Appendix C

to.the safety function (nonconformance dispositions).

~

  • Documents showing objective evidence:

special test and inspection procedures and results commercial grade survey reports - item, design, material, and specific performance characteristic (relevant to safety function)-

- source inspection reports Completed post-installation test procedure and results.

a Completed stock or material issue forms and installation work orders or reports.

Historical performance info.wat.f,n.

END i

1

-l 38703, Appendix C C-2 Issue Date:

11/08/93 i

~