Text
.
ll 1
Duke her Company (704)s75 4xp McGune Nuclear Starwn l
12700 Hugm l'erry Road Hunterwilie, NC 2M7MMa i
i DUKEPOWER l
l August 23,1993 6
U. S. Nuclear Regulatory Commission' Document Control Desk Washington, D. C. 20555 l
Subject:
McGuire Nuclear Station Docket 50-370 Unit 2 Steam Generators Pursuant to McGuire Technical Specification 4.4.5.5a) and c), the following information is submitted for I
the McGuire Unit 2 EOC-8 Refueling Outage. Information identifying P tubes, their locations, and the size of degradation is provided in the following attachments:
Steam Generator A_t.tachment A
1 i
B 2
)
C 3
D 4
The following quantities of tubes were removed from service or repaired:
I Steam Generator No. Tubes Plugged No. 'Iubes Repaired i
A 55 0
l B
48 0
)
C 35 0
I D
49 0
l Questions or problems should be directed to Kay Crane, Regulatory Compliance at (704) 875-4306.
Very truly yours, w.
T. C. McMeekin, Vice President McGuire Nuclear Station
~
c 00-9308310224 930823 7
I PDR ADOCK 05000370 K'
j G
PDR 12.a 4.
$M M %'M MkY
(
.............................+***
DPCO TUBAN !! (Version 1.0) 08/10/1993 14:02:58 McGuire Nuclear Station - Unit Two l
Sfg g j
7,,3,,o Bobbin,H/L Tubesheet Page 1 of 3 ATTACHMENT #1 - F*
F* DUERf TEST TYPE RDW COL IND %TW VOLTS CHN DEG LOCATION EXTENT 1 LEG ANLST PRD COMMENTS Bobbin 2 2 101 40 12.85 P 1 137 TE-ML
+9.94 9TH TSP TE-HL R1509 610 IDI Bobbin 2 66 101 40 13.89 P 1 158 TE-HL
+5.05 91H TSP TE-HL R1509 610 IDI Bobbin 3 13 101 40 6.92 P 1 103 TE-HL
+3.85 9TH TSP TE-HL P2201 610 IDI Bobbin 3 16 IDI 40 22.59 P 1 62 TE-HL
+15.33 91H TSP TE-HL P2201 610 IDI i
H/L Tubesheet MAI 7.60 1 42 TTS HL
-5.66 TTS HL TE-HL C9813 59n IDI i
H/L Tubesheet 3 22 SAI 4.34 1 22 TTS-HL
-4.59 TTS-HL TE-HL S1848 590101 Sobbin 4 16 IDI 40 14.70 P 1 65 TE-HL
+17.95 91H TSP TE-HL 01057 610 IDI Bobbin IDI 40 18.32 P 1 67 TE-HL
+14.14 9TH TSP TE-HL 01057 610 IDI H/L Tubesheet MAI 9.55 1 30 TTS-HL
-3.59 TTS-HL TE-ML C9813 590 IDI Bobbin 4 51 101 40 9.10 P 1 178 TE-HL
+7.16 9TH TSP TE-HL W2218 610 IDI Bobbin 4 57 IDI 40 8.08 P 1 14 TE-HL
+16.28 9TH TSP TE-HL 01057 610 IDI Bobbin 4 58 IDI 40 10.26 P 1 22 TE-HL
+7.20 97H TSP TE-HL P5436 610 IDI Bobbin 4 62 IDI 40 7.76 P 1 16 TE-HL
+17.19 9TH TSP TE-HL P5436 610 10!
H/L Tubesheet SA1 2.39 1 23 TTS-HL
-4.10 TTS-HL TE-HL H7791 590 1
Bobbin 4 83 IDI 40 34.93 P 1 38 TE-ML
+2.30 97H TSP TE-HL P5436 610 IDI Bobbin 5 19 IDI 40 5.28 P 1 107 TE-HL
+12.06 9TH TSP TE-HL C9318 610 IDI Bobbin 5 60 IDI 40 8.57 P 1 18 TE-ML
+7.26 91H TSP TE-HL R1509 610 101 Bobbin 6 12 101 40 4.84 P 1 184 TE-HL
+15.81 9TH TSP TE HL 03162 610 IDI H/L Tubesheet SAI 1.99 1 42 TTS-HL
-5.00 TTS-HL TE-ML P5436 590 IDI Bobbin 6 19 101 40 6.47 P 1 81 TE-HL
+7.80 97H TSP TE-HL C9318 610 101 Bobbin 6 10 !DI 40 3.07 P 1 123 TE-HL
+15.96 9TH TSP TE-HL C9318 610 IDI H/L Tubesheet SA!
2.12 1 46 TTS-HL
-4.97 TTS-HL TE-ML P5436 590 IDI Bobbin 6 28 101 4e 11.12 P 1 64 TE-HL
+10.94 9TH TSP TE-ML C9318 610 IDI Bobbin 7 1! i:: 40 34.59 P 1 35 TE-HL
+2.83 91H TSP TE-ML C93tB 610 101 Bobbin 8 F9 101 40 29.85 P 1 57 TE-HL
+5.72 91H TSP TE-HL C9813 610 IDI Bobbin 9 '05 IDI 40 16.32 P 1 36 TE-HL
+ 7.35 91H TSP TE-HL C9813 610 IDI Bobbin 11 59 IDI 40 3.55 P 1 134 TE-HL
+16,91 9TH TSP TE-HL C3556 610 !DI H/L Tubesheet SAI 3.04 1 47 TTS-HL
-4.52 TTS-HL TE-HL W4892 590 N/L Tubesheet 11 60 SAI 0.41 1 13 TTS-ML
-2.87 TTS-HL TE-ML W4892 590 Bobbin 11 72 IDI 40 5.49 P 1 104 TE-HL
+12.74 91H TSP TE-HL K7614 610 IDI Bobbin 12 62 IDI 40 11.01 P 1 24 TE-HL
+11.38 9TH TSP TE-ML C3556 610 1D1 Bobbin 13 13 IDI 40 7.43 P 1 49 TE-HL
+15.06 97H TSP TE-HL P9375 6101D1 Bobbin 14 59 3DI 40 9.01 P 1 16 TE-HL
+12.46 97H TSP TE-HL P5436 610 IDI Bobbin 14 73 IDI 40 40.82 P 1 42 TE-HL
+17.01 91H ISP TE HL R1509 610 101 H/L Tubesheet MAI 5.61 1 44 TTS-it
-2.90 TTS-HL TE-HL E8259 590 i
Bobbin 15 45 101 40 16.S4 P 1 16 TE-HL
+17.06 97H TSP TE-HL K7614 610 IDI H/L Tubesheet MA!
2.52 1 30 TTS-HL 3.41 TTS-HL TE-HL H8259 590 Bobbin 15 67 IDI 40 29.63 P 1 45 TE-ML
+10.56 9TH TSP TE-HL R1509 610 IDI Bobbin 16 9 101 40 13.01 P 1 15 TE-HL
+13.01 91H TSP TE HL S2720 610 IDI l
Bobbin 16 29 1D1 40 15.74 P 1 24 TE-HL
+12.81 9TH TSP TE HL 01057 610 IDI Bobbin 17 24 IDI 40 22.06 P 1 26 TE-HL
+10.37 9TH TSP TE-HL B10)O 610 101 Bobbin IDI 40 23.50 P 1 37 TE-HL
+16.59 97H TSP TE-ML B1055 610 IDI i
Bobbin 17 25 ID1 40 18.94 P 1 33 TE-HL
+14.28 9TH TSP TE-HL B1055 610 IDI Bobbin 17 31 IDI 40 13.71 P 1 13 TE-HL
+16.26 9TH TSP TE-HL SS466 610 IDI Bobbin IDI 40 18.89 P 1 12 TE-HL
+9.52 9TH TSP TE-HL S8466 6101D1 Bobbin 17 48 IDI 40 8.65 P 1 75 TE-HL
+16.90 9TN TSP TE-HL 58466 610 IDI H/L Tubesheet MA1 2.00 1 32 TTS-ML
-3.34 TTS-HL TE-HL H8259 590 Bobbin 18 15 IDI 40 14.78 P 1 18 TE-HL 5.27 97H TSP TE-HL $B466 610 101 Bobbin 18 89 IDI 40 6.31 P 1 163 TE-HL
+14.33 97H TSP TE-HL R6878 610 101 Bobbin 18 104 1DI 40 6.24 P 1 123 TE-HL
+12.76 91H TSP TE-HL R6878 610 IDI H/L Tubesheet SA!
3.51 1 13 TTS-HL
-2.48 TTS-HL TE-HL H7791 590 Bobbin 19 21 IDI 40 14.77 P 1 16 TE-HL
+8.52 9TH TSP TE-HL S8466 610 IDI Bobbin 19 22 IDI 40 15.13 P 1 14 TE-HL
+4.50 9TH TSP TE-HL SB466 610 IDI Bobbin 19 29 IDI 40 17.70 P 1 20 TE-HL
+14.13 97H TSP TE-HL S4256 610 IDI Robbin 19 59 IDI 40 6.14 P 1 154 TE-HL
+16.08 9TH TSP TE-HL R1509 610 IDI Bobbin IDI 40 12.56 P 1 1 TE-HL
+16.10 9TH TSP TE-HL L7871 610 IDI Bobbin 19 89 IDI 40 1.43 P 1 118 TE-HL
+6.34 9TH TSP ' TE-HL $6961 610 IDI Bobbin 20 28 101 40 31.64 P 1 22 TE-HL
+16.92' 97H TSP TE-HL M0155 610 101 Bobbin 20 73 IDI 40 2.08 P 1 85 TE-HL
+6.28 9TH TSP TE-HL H7791 610 IDI Bobbin 20 87 101 40 2.45 P 1 58 TE-HL
+12.81 9TH TSP TE-HL H7791 610 IDI Bobbin 21 58 IDI 40 8.44 P 1 87 TE-HL
+7.18 97H TSP TE-HL H7791610 IDI Bobbin IDI 40 11.69 P 1 81 TE-HL
+ 7.16 9TH TSP TE-HL P2201 610 IDI Bobbin IDI 40 18.10 P 1 17 TE-HL
+7.46 97H TSP TE-HL P2201 610 IDI Bobbin IDI 40 22.13 P 1 38 TE-HL
+7.27 91H TSP TE-HL M7791 610 IDI H/L Tubesheet 21 98 SAI 2.77 1 31 TTS-HL
-2.76 TTS-HL TE-HL P4202 590
... g.................*************
DPCO TUBAN !! (Version 1.0) 08/10/1993 14:02:58 McGuire Nuclear Station - Unit Two gfg g 7/93 RF0 Bobbin,H/L Tubesheet Page 2 of 3 ATTACHMENT #1 F*
f* DUERY TEST TYPE RDW COL IND %TW VOLTS CHN DEG LOCATION EXTENT 1 LEG ANLST PRB COMMENTS Bobbin 21 100 101 40 5.78 P 1 27 TE-HL
+14.17 9TH TSP TE-HL H7791610 IDI Bobbin 22 55 101 40 23.17 P 1 56 TE-HL
- 15.21 9TH TSP TE-HL HT7s1 610 IDI Bobbin 22 92 IDI 40 0.54 P 1 105 TE-HL
+8.56 9TH TSP TE ML H7791 610 101 Bobbin 23 7 IDI 40 8.39 P 1 162 TE-HL
+5.82 10TH TSP TE-HL M7791610 IDI Bobbin 23 24 IDI 40 16.20 P 1 67 TE-HL
+16.83 9TH TSP TE-HL H7791610 IDI H/L Tubesheet KA1 4.82 1 28 TTS-HL
-3.73 TTS-HL TE-HL H8259 590 Bobbin 23 29 IDI 40 9.32 P 1 83 TE-HL
+7.06 9TH TSP TE-HL H7791610 IDI Bobbin 24 14 IDI 40 10.04 P 1 124 TE-HL
+13.12 9TH TSP TE-HL HT791610 IDI Bobbin 24 22 IDI 40 6.30 P 1 130 TE-HL
+14.97 10TH TSP TE-HL H77916101DI Bobbin 24 25 101 40 8.30 P 1 149 TE-HL
+17.04 91H TSP TE-HL H7791610 IDI H/L Tubesheet SA!
6.26 1 26 TTS-HL
-4.68 TTS-HL TE-HL W4892 590 Bobbin 24 36 101 40 10.27 P 1 92 TE-HL
+16.31 9TH TSP TE-HL H7791610 IDI H/L Tubesheet 24 49 SAI 0.21 1 27 TTS HL
-3.36 TTS-HL TE-HL H8259 590 H/L Tubesheet 25 29 sal 13.72 1 11 TTS-HL
-3.74 TTS-HL TE-HL A9574 590 Bobbin 25 55 101 40 11.90 P 1 176 TE-HL
+9.20 9TH TSP TE-HL G1931 610 101 Bobbin 26 45 101 40 24.02 P 1 17 TE-HL
+15.98 91H TSP TE-HL M3442 610 IDI Bobbin 27 28 ID1 40 6.72 P 1 151 TE-HL
+9.64 91H TSP TE-HL M3442 610 IDI Bobbin 27 39 101 40 18.28 P 1 29 TE-HL
+2.45 97H TSP TE-HL V9658 610 IDI j
Bobbin 27 52 IDI 40 13.91 P 1 97 TE-HL
+5.34 9TH TSP TE HL M3442 610 IDI j
Bobbin 27 61 IDI 40 5.91 P 1 81 TE-HL
+9.31 97H TSP TE-HL B1055 610 IDI l
Bobbin IDI 40 9.26 P 1 75 TE-HL
+5.42 9TH TSP TE-HL B1055 610 IDI Bobbin IDI 40 17.51 P 1 87 TE-HL
+8.30 91H TSP TE-HL B1055 610 IDI Bobbin 28 13 1D1 40 8.17 P 1 136 TE-HL
+10.74 9TH TSP TE-HL M0155 610 IDI Bobbin 28 31 IDI 40 8.32 P 1 169 TE-HL
+3.99 91H TSP TE-HL M0155 610 IDI H/L Tubesheet 28 101 VOL 0.39 1 38 TTS*HL
-2.30 TTS-HL TE-HL A9574 590 Bobbin 31 27 IDI 40 29.91 3 19 TE-HL
+10.78 9TH TSP TE-HL H7791610 IDI Bobbin 32 20 IDI 40 8.31 P 1 159 TE-HL
+16.96 97H TSP TE-HL H77916101D1 Bobbin 32 30 IDI 40 13.69 0 1 18 TE-HL
+14.69 9TH TSP TE-HL W9658 610 IDI Bobbin 32 35 IDI 40 7.77 P 1 72 TE-HL
+ 17.37 9TH TSP TE HL R6452 610 IDI I
Bobbin IDI 40 75.46 P 1 49 TE-HL
+15.49 97H TSP TE HL R6452 610 IDI H/L Tubesheet KAI 5.09 1 43 TTS-HL
-4.53 TTS-HL TE-HL P4202 590 i
H/L Tubesheet MAI 6.08 1 22 TTS-HL
-4.63 TTS-HL TE HL' H7791590 i
H/L Tubesheet KAl 9.02 1 39 TTS-HL
-6.74 TTS-HL TE-HL H7791590 J
Bobbin 33 77 IDI 40 5.39 P 1 127 TE-HL
+12.19 9TH TSP 1E-HL M0155 610 IDI Bobbin 34 29 3DI 40 19.08 P 1 24 TE-HL
+5.01 9TH TSP TE-HL M0155 610 1DI Bobbin 35 72 101 40 10.10 P 1 86 TE-HL
+11.77 97H TSP TE-HL C9318 610 101 H/L Tubesheet 36 44 SA!
5.22 1 23 TTS-HL
-3.03 TTS-HL TE-HL K7614 590 Bobbin 36 63 !DI 40 8.34 P 1 90 TE-HL
+15.07 9TH TSP TE-HL S1848 610 IDI Bobbin 37 45 IDI 40 13.40 P 1 28 TE-HL
+12.58 9TH TSP TE-HL M0155 610 1DI Bobbin 38 35 101 40 13.92 P 1 74 TE-ML
+11.08 97H TSP TE-HL $7675 610 IDI Bobbin 38 45 IDI 40 15.19 P 1 20 TE-HL
+10.18 9TH TSP TE-HL 57675 610 IDI Bobbin IDI 40 15.94 P 1 81 TE-HL
+ 9.18 9TH TSP TE-HL $7675 610101 Bobbin 38 57 IDI 40 17.63 P 1 56 TE-HL
+14.04 9TH TSP TE HL S7675 610 IDI Bobbin 38 63 101 40 11.64 P 1 10 TE-HL
+7.95 9TH TSP TE-HL P2201 61D IDI Bobbin 38 76 IDI 40 5.35 P 1 148 TE-HL
+14.96 91H TSP TE-HL P2201 610 tal Bobbin 38 91 IDI 40 6.13 P 1 78 TE-HL
+2.06 9TH TSP TE HL S1848 610 IDI Bobbin IDI 40 7.48 P 1 103 TE-HL
+6.95 97H TSP TE-HL S1848 610 IDI Bobbin IDI 40 9.40 P 1 87 TE-HL
+11.04 91H TSP TE-HL S1848 610 101 Bobbin 39 32 101 40 29.88 P 1 55 TE-HL
+11.56 9TH TSP' TE-HL 57675 610 1D1 Bobbin 39 36 IDI 40 12.33 P 1 18 TE-HL
+6.17 STN TSP TE-ML S7675 610 IDI Bobbin 39 52 IDI 40 6.36 P 1 20 TE-HL
+13.02 9TH TSP TE-HL $7675 610 IDI Bobbin 39 57 IDI 40 4.25 P 1 135 TE HL
+9.21 9TH TSP TE-HL S7675 610 IDI Bobbin 40 27 IDI 40 14.37 P 1 14 TE-HL
+16.45 9TH TSP TE-HL P5436 610 IDI H/L Tubesheet KA1 2.03 1 27 TTS-HL
-4.85 TTS-HL TE-HL HB259 590.
Subbin 41 75 101 40 13.28 P 1 22 TE-HL
+6.06 9TH TSP TE-HL P9375 610101 Bobbin 41 88 IDI 40 12.82 P 1 16 TE-HL
+13.57 9TH TSP TE-HL P9375 610 IDI Bobbin 42 76 IDI 40 11.10 P 1 20 TE-HL
+ 7.58 9TH TSP TE-HL P9375 610 IDI i
Bobbin 43 68 IDI 40 15.94 P 1 22 TE-ML
+13.26 9TH TSP TE-HL P5436 610 IDI i
Bobbin 44 57 IDI 40 31.11 P 1 59 TE-HL
+14.20 97H TSP TE HL R6656 6101DI Bobbin 44 61 101 40 12.58 P 1 B8 TE-HL
+8.29 91H TSP TE-HL H7791 610 IDI Bobbin IDI 40 18.36 P 1 22 TE-HL
+1C.49 9TH TSP TE-HL HT791610 IDI Bobbin 44 63 IDI 40 21.14 P 1 30 TE HL
+7.81 9TH TSP TE-HL H7791610 IDI I
Bobbin 45 31 DDI 40 10.86 P 1 19 TE-HL
+17.28 97H TSP TE-HL S4373 610 Bobbin 45 51 IDI 40 54.21 P 1 45 TE-HL
+14.17 91H TSP TE-HL R6656 610 1D1 Bobbin 49 71 IDI 40 15.92 P 1 16 TE-HL
+4.32 9TH TSP TE HL P2201 610 IDI 1
I 4
t DPCO TUBAN 11 (Version 1.0) 08/10/1993 14:02:58 McGuire Nuclear Station - Unit Two l'
sfg A
. u.u.u..u..... u
...u..-
7/93 RF0 Bothin,H/L Tubesheet i
Page 3 of 3 ATTACHMENT #1 - I*
i f* QUERY TEST TYPE ROW COL IND %TW VOLTS CHN DEG LOCATION EXTENT 1 LEG ANLST PRB COMMENTS Totat Indications Found
- 130 i
Total Tubes Found = 100 Total Tubes in Input File = 100 i
i r
?
4
.I I
t i
i k
l
[
i i
b 5
4 E
i t
b
DPCO TUBAN II (Version 1.0) 08/10/1993 15:02:46 m e.**.... m......u...u..*****
McGuire Nuclear Station - Unit Two
- m m
- u m ** u *******.******.**
u u...u....u u*.... m e.********
5/G B
- .*** m e**. u *.*************.*
- .u ****.. u. m........**..* u...*
7/93 RF0
- m..u m *.**......*** **.*
Bobbin,H/L Tubesheet Page 1 of 2 ATTACHMENT #2 - P l
I f* QUERY TEST TTPE ROW COL IND %TW VOLTS CHN DEG LOCATION EXTENT 1 LEG ANLST PRB COMMENTS Bobbin 2 46 IDI 40 10.61 P 1 17 TE-HL
+13.80 8TH TSP TE-HL V9098 610 IDI Bobbin IDI 97 4.92 P 1 40 TE-HL
+13.52 9TM TSP TE-HL P4202 590 IDI Bobbin 3 77 IDI 40 17.02 P 1 15 TE-HL
+2.41 M TSP TE-HL S1848 610 101 Bobbin 4 37 IDI 68 14.48 P 1 27 TE-HL
+4.18 VTH TSP TE-HL M0155 6101DI l
Bobbin 4 73 IDI 40 10.29 P 1 23 TE-HL
+15.14 9TH TSP TE-HL S1848 610 1D1 M/L Tubesheet 4 108 SAI 1.27 1 15 TTS-HL
-4.83 TTS-HL TE-HL M1680 590 i
Bobbin 5 70 IDI 40 27.94 P 1 39 TE-HL
+4.17 9TH TSP TE-HL S1848 6101D1 Bobbin 5 113 IDI 40 8.22 P 1 15 TE-HL
+16.12 9TH TSP TE-HL $1848 6101DI Bobbin 6 69 IDI 40 8.84 P 1 19 TE-HL
+8.58 9TH TSP TE-HL S1848 610 IDI Bobbin 6 70 IDI 40 13.42 P 1 20 TE-HL
+7.62 9TH TSP TE-HL S1848 610 IDI i
Bobbin 6 77 IDI 40 8.75 P 1 20 TE-HL
+6.69 91H TSP TE-HL S1848 610 IDI j
l Bobbin 7 56 1DI 40 14.95 P 1 157 TE-HL
+11.94 9TH TSP TE-HL C3556 610 IDI l
Bobbin 7 94 IDI 40 9.75 P 1 91 TE-HL
+10.84 9TH TSP TE-HL W2218 610 IDI J
Bobbin 8 104 IDI 40 32.62 P 1 168 TE-ML
+6.89 91H TSP TE-HL V2218 610101 l
Bobbin 9 108 101 40 15.70 P 1 73 TE-HL
+14.79 9TH TSP TE-ML W2218 610 IDI Bobbin 10 59 IDI 40 51.19 P 1 40 TE-HL
+12.33 91H TSP TE-HL V2218 610 101 i
Bobbin 11 48 IDI 40 14.75 P 1 65 TE-HL
+4.27 9TH TSP TE-ML C6308 610 IDI l
H/L Tubesheet 11 70 MA1 1.68 1 14 TTS HL
-3.62 TTS-HL TE-HL K7614 590-1 Bobbin 11 77 IDI 40 16.91 P 1 72 TE-HL
+10.32 9TH TSP TE-HL W2218 610 IDI I
Bobbin 12 75 101 40 8.69 P 1 98 TE-HL
+8.92 9TH TSP TE-HL W2218 610 IDI l
Bobbin 12 112 IDI 40 23.08 P 1 151 TE-HL
+15.85 9TH TSP TE-HL W2218 610 IDI l
Bobbin 13 26 IDI 40 3.23 P 1 42 TE-ML
+6.58 91H TSP TE-HL L7871 610 101 l
Bobbin 13 38 IDI 40 2.66 P 1 147 TE-HL
+12.51 9TH TSP TE-HL L7871610 IDI j
Bobbin 13 96 101 40 8.79 P 1 136 TE-HL
+6.02 9TH TSP TE-HL V2218 610 IDI Bobbin IDI 40 14.02 P 1 117 TE-HL 48.86 91H TSP TE-HL W2218 610 101 Bobbin 14 14 IDI 40 7.54 P 1 11 TE-HL
+18.10 97H TSP TE-HL B1055 610 IDI Bobbin 14 44 IDI 40 12.51 P 1 156 TE-HL
+17.04 9TH TSP TE-HL L7871 610 IDI H/L Tubesheet MAI 2.95 1 16 TTS-HL
-4.19 TTS HL TE-HL C9427 590 j
Bobbin 15 23 101 40 5.37 P 1 173 TE-HL
+3.70 9TH TSP 1E-HL L7871 610 IDI Bobbin 15 64 IDI 40 13.25 P 1 28 TE-HL
+18.11 91H TSP TE-HL V2218 610 IDI H/L Tubesheet MAI 1.94 1 17 T15-HL
-3.00 TTS-HL TE-HL G1931 590 Bobbin 16 59 IDI 40 22.71 P 1 26 TE HL
+8.51 9TH TSP TE-HL V2218 610 101 Botbin 16 76 101 40 18.12 P 1 19 1E-HL
+6.21 9TH TSP TE-HL W2218 610 IDI Bobbin 17 45 IDI 40 2.50 P 1 55 TE-HL
+ 7. 23 91H TSP TE-HL M3442 610 1D1 Bobbin 17 61 IDI 40 5.34 P 1 163 TE-HL
+5.98 9TH TSP TE-HL W2218 610 IDI Bobbin 101 40 18.27 P 1 23 TE-HL
+10.31 97H TSP TE-ML W2218 610 IDI Bobbin 17 74 IDI 40 7.43 P 1 74 TE-HL
+16.86 9TH TSP TE-HL W2218 610 IDI N/L Tubesheet SAI 5.09 1 43 TTS-HL
-4.17 TTS-HL TE-HL 01057 590 IDI Bobbin 18 71 IDI 40 16.43 P 1 36 TE-HL
+17.25 91H TSP TE-HL W2218 610 IDI H/L Tubesheet MAI 6.57 1 33 TTS-HL
-3.79 TTS-HL TE HL 01057 590 IDI Bobbin 18 103 IDI 40 31.19 P 1 60 TE HL
+17.86 9TH TSP. TE-HL V2218 610101 H/L Tubesheet MA!
9.18 1 28 TTS HL
-3.20 TTS-HL TE-HL P5436 590 101 Bobbin 19 21 IDI 40 2.70 P 1 37 TE-HL
+12.16 9TH TSP TE-HL M3442 610 101 Bobbin 20 75 IDI 40 23.60 P 1 40 TE-HL
+2.05 91H TSP TE-HL W2218 610 101 Bobbin 20 95 101 40 20.77 P 1 20 TE-HL
+ 7.4 2 9TH TSP TE-HL W2218 610 101 Bobbin 21 74 IDI 40 76.87 P 1 28 TE-HL
+16.04 10TH TSP TE-HL W2218 610 101 Bobbin 23 92 IDI 40 25.53 P 1 26 TE-HL
+11.97 9TH TSP TE-HL W2218 610 IDI Bobbin 24 81 IDI 40 7.53 P 1 89 TE HL
+8.87 97H TSP TE-HL K7614 610 1D1 Bobbin 27 27 IDI 40 4.64 P 1 45 TE-HL
+16.21 9TH TSP TE HL $2680 610 !DI Bobbin 27 69 1D1 40 11.87 P 1 25 TE-HL
+ 7.94 91H TSP TE-HL R1509 610 IDI Bobbin 101 40 12.16 P 1 25 TE-HL
+7.01 9TH TSP TE-HL R1509 610 IDI l
Bobbin 27 96 IDI 40 2.48 P 1 27 TE-HL
+4.25 9TH TSP TE-HL N0942 610 IDI i
Bobbin 27101 IDI 40 13.87 P 1 23 TE-HL
+15.16 97H TSP TE-HL R1509 610 1DI Bobbin 30 77 IDI 40 10.32 P 1 146 TE-HL
+13.67 9TH TSP TE-HL R1509 610 IDI Bobbin 30 78 !DI 40 43.99 P 1 58 TE-HL
+16.36 97H TSP TE-HL R1509 610 1DI Bobbin 31 101 101 40 8.26 P 1 26 TE-HL
+5.84 9TH TSP TE-HL 01057 610 1D1 Bobbin 31 102 101 40 6.97 P 1 24 TE-HL
+9.15 9TH TSP TE-HL 01057 610 IDI Bobbin 34 80 !DI 40 14.97 P 1 12 TE-HL
+7.70 9TH TSP TE-HL H2949 610 TDI Bobbin IDI 40 47.45 P 1 39 TE-HL
+10.29 97H TSP TE HL H2949 610 3DI Bobbin 36 92 IDI 40 7.74 P 1 20 TE-HL
+ 9.10 9TH TSP TE-HL N0698 610 IDI Bobbin 33 94 101 40 1.00 P 1 103 TE HL
+11.40 97H TSP TE-ML W9098 610 1D!
Bobbin 38 95 101 40 19.92 P 1 11 TEC
+11.09 11TH TSP TE-HL W9098 610 IDI Bobbin 41 25 IDI 40 7.46 P 1 19 TE-HL
+14.91 97H TSP TE-HL P5436 610 IDI Bobbin 42 48 IDI 40 5.28 P 1 32 TE-HL
+ 7.33 9TH TSP TE-HL H3921 610 IDI Bobbin 42 82 IDI 40 7.75 P 1 33 TE-HL
+5.86 91H TSP TE-HL R6878 610 IDI l
l
.1
\\
l l
l DPC0 TUBAN !! (Version 1.0) 08/10/1993 15:02:46
..(s...................************
McGuire Nuclear Station - Unit Two j
gfg g 7/93 RF0 i
Bobbin,H/L Tubesheet Page 2 of 2 ATI ACHMENT #2 - F*
F* QUERY j
TEST TYPE RDW COL IND %TW VOLTS CHN DEG LOCATION EXTENT 1 LEG ANLST PRB COMMENTS Bobbin 43 71 IDI 40 14.54 P 1 21 TE-HL 49.56 97H TSP TE-HL C9427 610 IDI Total Indications Found = 66 Total Tubes Found = $6 Total Tubes in input File = 56 b
l
' i i
f l
1 i
i b
- l l
... 3******************************
DPCO TUBAN 11 (Version 1.0) 08/10/1993 15:22:03 l
McGuire Nuclear Station - Unit Two S/G C l
7f93 pro Bobbin,H/L Tubesheet l
Page 1 of 2 ATTACHMENT #3 - f*
F* DUERY l
TEST TYPE RDW COL IND %TW VOLTS CHN DEG LOCATION EXTENT 1 LEG ANLST PRB COMMENTS i
Bobbin 2 39 IDI 40 18.17 P 1 65 TE-HL
+4.03 9TH TSP TE-HL J1978 610 IDI Bobbin 2 48 IDI 40 15.62 P 1 146 TE-HL
+14.13 STH TSP TE-HL $7675 610101 Bobbin 2 51 IDI 40 3.04 P 1 119 TE-HL
+15.53 BTH TSP TE-HL c6495 610 IDI J
Bobbin IDI 40 9.42 P 1 166 TE-HL
+9.29 BTH TSP TE-HL C6495 610 IDI H/L Tube $heet 2 76 SAI 1.75 1 20 TIS-HL
-4.41 TTS-HL TE-HL P2201 590 Bobbin 2107 IDI 40 29.78 P 1 29 TE-HL
+3.16 9TH TSP TE-HL C9813 610 IDI i
Bobbin 3 14 IDI 40 2.50 P 1 90 TE*HL
+11.59 9TH TSP TE-HL P2201 610 IDI i
Bobbin 3 42 IDI 40 21.80 P 1 15 TE-HL
+14.33 9TH TSP TE HL L7871 610 IDI Bobbin 3 49 IDI 40 3.01 P 1 142 TE-HL
+4.60 97H TSP TE-HL P9375 610 IDI Bobbin 3 95 IDI 40 18.22 P 1 23 TE-HL
+6.13 97H TSP TE-HL R1509 610 IDI 1
Bobbin 4 41 IDI 40 3.16 P 1 29 TE-ML
+ 9.74 91H TSP TE-HL P2201 610 IDI Bobbin 4 42 IDI 40 8.26 P 1 163 TE-HL
+14.05 91H TSP TE-HL W6871 610 IDI i
Bobbin 4 53 IDI 40 37.56 P 1 23 TE HL
+5.27 9TH TSP TE-HL P2201 610 IDI Bobbin 4 88 IDI 40 26.86 P 1 39 TE-HL
+11.81 9TH TSP TE-HL S1848 610 IDI J
Bobbin 5 6 IDI 40 14.39 P 1 164 TE-HL
+10.72 97H TSP TE-ML W6871 610 IDI i
Bobbin 5 11 IDI 40 16.63 P 1 14 TE-HL
+11.21 9TH TSP TE-HL W4892 610 IDI l
Bobbin 5 26 IDI 40 6.63 P 1 73 TE-HL
+10.85 97H TSP TE-HL W4892 610 IDI Bobbin 5 31 IDI 40 34.15 P 1 24 TE-HL
+1.21 9TH TSP TE-HL W4892 610 IDI Bobbin 5 49 101 40 8.73 P 1 166 TE-HL
+10.18 9TH TSP TE-HL W6871 610 IDI Bobbin 5 80 101 40 25.12 P 1 22 TE-HL
+16.78 9TH TSP TE-HL B5371 610 IDI Bobbin 6 69 IDI 40 15.14 P 1 162 TE-HL
+6.63 9TH TSP TE-ML B5371 610 IDI Bobbin 7 33 IDI 40 8.03 P 1 157 TE-ML
+15.98 91H TSP TE-HL C9813 610 IDI Bobbin 7 43 IDI 40 20.62 P 1 11 TE-HL
+7.30 91H TSP TE-HL C9813 610 IDI H/L Tubesheet 11 45 SAI 4.21 1 18 TTS-HL
-4.22 TIS-HL TE-HL D3162 590 Bobbin 11 67 IDI 40 8.49 P 1 21 TE-ML
+12.16 9TH TSP TE-HL $7675 610 IDI Bobbin 12 27 IDI 40 6.01 P 1 50 TE-HL
+12.32 9TH TSP TE-HL J1978 610 IDI H/L Tubesheet 12 68 MAI 3.90 1 29 TTS-HL
-4.04 TTS-HL TE-HL S7675 590 Bobbin 13 11 IDI 40 26.16 P 1 8 TE-HL
+15.17 91H TSP TE HL P2201 610 IDI Bobbin 13 66 IDI 40 7.67 P 1 14 TE-ML
+14.32 9TH TSP TE HL $7675 610 IDI Bobbin IDI 40 13.04 P 1 18 TE-HL
+10.10 9TH TSP TE-HL $7675 610 IDI Bobbin IDI 4D 17.57 P 1 21 TE-HL
+15.98 97H TSP TE-HL 57675 610101 Bobbin 13 68 IDI 40 16.10 P 1 9 TE-HL
+11.36 9TH TSP TE-HL S7675 610 IDI H/L Tubesheet 13 75 MAI 1.18 1 15 TTS-HL
-3.80 TTS HL TE-HL S7675 590 Bobbin 13 76 IDI 40 5.88 P 1 11 TE-HL
+19.51 9TH TSP TE-HL S7675 610 IDI Bobbin IDI 40 8.43 P 1 17 TE-HL
+17.62 9TH TSP TE HL $7675 610 101 Bobbin IDI 40 16.32 P 1 29 TE-HL
+14.49 9TH TSP TE-HL $7675 610 IDI i
Bobbin 13 77 IDI 40 2.28 P 1 76 TE-HL
+6.11 97H TSP TE-HL $7675 610 IDI Bobbin 13 80 IDI 40 22.02 P 1 30 TE-HL
+0.76 97n TSP TE-HL 57675 610 IDI Bobbin 14 23 101 40 28.02 P 1 17 TE-HL
+13.37 97N TSP - TE-HL P5436 610 IDI Bobbin 14 67 101 40 12.66 P 1 18 TE-HL
+6.83 9TH TSP TE-HL 57675 610 101 Bobbin 14 71 101 40 16.89 P 1 16 TE-HL
+16.21 97H TSP TE-HL C6495 610 IDI Bobbin IDI 40 18.37 P 1 22 TE-HL
+15.16 9TH TSP TE HL C6495 610 IDI Bobbin 14 72 101 40 13.85 P 1 25 TE-HL
+18.13 97H TSP TE-HL C9813 610 IDI i
H/L Tubesheet KAI 1.00 1 29 TTS-HL
-2.81 TTS-HL TE-HL $7675 590 H/t Tubesheet 14 78 MAI 3.76 1 24 TTS-HL
-3.65 TTS-HL TE-HL DB661590 l
Bobbin 15 20 101 40 30.39 P 1 7 TE-HL
+5.16 97H TSP TE-HL P5436 610 IDI Bobbin 15 30 IDI 40 8.16 P 1 107 TE-HL
+10.80 91H TSP TE-HL P5436 610 IDI Bobbin 16 16 IDI 40 6.42 P 1 152 TE-HL
+13.98 9TH TSP TE*HL P5436 610 IDI Bobbin 16 18 IDI 40 9.64 P 1 132 TE-HL
+11.43 97H TSP TE-HL P5436 610 IDI M/L Tubesheet 17 30 SAI 1.95 1 18 TTS-HL
-4.12 TTS-HL.
TE-HL C3556 590 Bobbin 18 11 !DI 40 21.85 P 1 11 TE+HL
+8.07 9TH TSP TE-HL P5436 610 IDI Bobbin 18 29 IDI 40 8.80 P 1 126 TE-HL
+14.18 10TH TSP TE-HL P5436 610 IDI H/L Tubesheet 1h 31 SAI 1.35 1 25 TTS-HL
-4.16 TTS-HL TE-HL R1509 590 H/L Tubesheet 18 60 SAI 1.83 1 20 TTS-HL
-4.49 TIS-HL TE-HL C9813 590 IDI H/L Tubesheet 18 61 SAI 2.88 1 18 TTS-HL
-4.68 TTS-HL 1E-HL C9813 590 IDI H/L Tubesheet 18 65 SAI 1.05 1 30 TTS HL
-4.83 TTS-HL TE-HL A9574 590 H/L Tubesheet 19 63 MAI.
1.68 1 18 TTS-HL
-4.46 TTS-HL TE-HL C9813 590 IDI fobbin 20 20 IDI 40- 16.72 P 1 77 TE-HL
+13.92 91H TSP TE-HL N0698 610 IDI H/L Tubesheet 20 44 SAI 1.05 1 13 TTS-HL
-3.52 TTS-ML TE-HL HB259 590 N/L Tubesheet 20 62 SAI 2.34 1 14 TTS-HL
-4.60 TTS-HL TE ML C9813 590 IDI H/t Tubesheet 21 36 SAI 1.89 1 29 TTS-HL
-4.02 TTS-HL TE HL R1509 590 Bobbin 23 14 IDI 40 5.86 P 1 150 TE-HL
+17.93 91H TSP TE-HL P5436 610 IDI H/L Tubesheet SAI 4.40 1 33 TTS-HL
~3.15 TTS-ML TE-HL P5436 590 IDI Bobbin 23 27 IDI 40 6.08 P 1 23 TE HL
+11.96 97H TSP TE-HL P5436 610 101 Bobbin 25 79 IDI 40 2.40 P 1 142 TE-HL
+3.28 9TH TSP TE-HL D4576 610 IDI
~
i DPC, tub H,,
,,e,,,o,,.0, 0,,10,,,,, 15.,,.c3 McGuire Nuclear Station - Unit Two 5/L C 7f93 pro
.............a.........************
Bobbin,H/L Tubesheet I
a Page 2 of 2 ATTACHMEhi #3 - F*
[
F* QUERY TEST TYPE ROW COL IND %TW VOLTS CHN DEG LOCATION EXTENT 1 LEG ANLST PRB COMMENTS Bobbin 26 27 103 40 16.27 P 1 52 TE-HL
+17.64 91H TSP TE-HL A9574 610 IDI a
Bobbin 28 13 IDI 40 8.69 P 1 153 TE+HL
+15.00 91H TSP TE-HL B5534 610 IDI i
Bobbin 28 56 IDI 40 3.03 P 1 60 TE-HL
+15.15 9TH TSP TE-HL B5534 610 IDI l
Bobbin 32 78 IDI 40 6.43 P 1 33 TE-HL
+5.30 97H TSP TE-HL 82S60 610 101 I
Bobbin 37 44 IDI 40 11.10 P 1 18 TE HL
+13.16 9TH TSP TE-HL 01057 610101 Bobbin IDI 40 15.45 P 1 19 TE-HL
+14.27 91H TSP TE-HL 01057 610 IDI Bobbin 41 36 IDI 40 3.52 P 1 169 TE-HL 8.68 9TH TSP TE-HL R6452 610101 Bobbin 41 39 IDI 40 3.93 P 1 167 TE-HL
+8.67 9TH TSP TE-ML R6452 610101 Bobbin 41 43 1D1 40 2.76 P 1 160 TE-HL
+16.54 91H TSP TE HL R6452 610 IDI Total Indications found = 74 Total Tubes Found = 65 Total Tubes in input File = 65 t
I E
t i
l a
4
+
j e..
g......e een ne eeeee e*****
DPCO TUBAN II (version 1.0) 08/10/1993 15:54:44 ee.... ** eeeeeeeeeeeeee**eeeee***
McCulre Nuclear Station - Unit Two l
ee......... ***..e****eeeeee **.
gfg o
..........,****e.
j o n eenn en en....e*** *
- enee
- 7/93 RF0 l
)
Bobbin,H/L Tubesheet Pege 1 of 2 l
ATTACHMENT #4 - F*
f* GUERY TEST TYPE ROW COL IND 1TW VOLTS CHN DEG LOCATION EXTENT 1 LEG ANLST PRB COMMENTS Bobbin 2 61 !DI 40 9.15 P 1 67 TE-HL
+14.96 97H TSP TE-HL W4892 610 IDI Bobbin 4 35 IDI 40 8.93 P 1 118 TE-HL
+17.17 9TH TSP TE-HL P2201 610 IDI Bobbin IDI 40 11.07 P 1 153 TE-HL
+17.05 9TH TSP TE-HL B5534 610 1D1 H/L Tubesheet MAI 5.04 1 32 TTS-HL
-4.39 TTS-HL TE-HL M0155 590 Bobbin 4 40 1D! 40 3.49 P 1 40 TE-HL
+l.13 9TH TSP TE-HL B5534 610 IDI Bobbin IDT 40 7.86 P 1 15 TE-HL
+1.70 9TH TSP TE-HL P2201 610 IDI
]
H/L Tubesheet 6 64 SAI 3.16 1 18 TTS-HL
-5.57 TTS-HL TE-HL W2218 590 IDI Bobbin 6 99 IDI 40 3.85 P 1 130 TE-HL
+15.86 9TH TSP TE-HL S2680 610 IDI l
Bobbin 7 72 IDI 40 60.76 P 1 39 TE-HL
+16.81 9TH TSP TE-HL S2680 610 IDI j
H/L Tubesheet MAI 16.57 1 34 TTS-HL
-4.98 TTS-HL TE-HL H7791 590 i
Bobbin 7 61 1DI 40 34.47 P 1 33 TE-HL
+3.51 9TH TSP TE-HL S2680 610 IDI I
Bobbin 7 83 IDI 40 13.81 P 1 148 TE-HL
+4.55 9TH TSP TE-HL $2680 610 IDI Bobbin 7 94 IDI 40 6.18 P 1 78 TE-HL
+15.76 91H TSP TE-HL S2680 610 IDI Bobbin 8 84 IDI 40 23.52 P 1 148 TE-HL
+6.66 97H TSP TE-HL $2680 610 IDI Bobbin 8 93 IDI 40 5.61 P 1 78 TE-HL
+13.16 97H TSP TE-HL S2680 610 IDI Bobbin 9 26 101 40 3.77 P 1 146 TE-HL
+4.59 9TH TSP TE-HL H2949 610 IDI j
Bobbin 9 75 IDI 40 2.82 P 1 34 TE-HL
+9.29 9TH TSP TE-HL S2680 610 IDI Bobbin 9 79 IDI 40 8.13 P 1 64 TE-HL
+13.53 9TH TSP TE-HL S2680 610 IDI Bobbin IDI 40 22.84 P 1 170 TE-HL
+12.35 9TH TSP TE-HL S2680 6101DI Bobbin 10 82 IDI 40 16.10 P 1 26 TE-HL
+12.71 9TH TSP TE-HL J1978 610 IDI Bobbin IDI 40 16.30 P 1 91 TE-HL
+9.13 9TH TSP TE-HL J1978 610 101 H/L Tubesheet 10 87 MAI 2.75 1 204 TTS-HL
-4.30 TTS-HL TE-HL H7791 590 H/L Tubesheet 11 64 SA!
1.35 1 18 TTS-HL
-5.64 TTS-HL TE-HL HT791 590 Bobbin 11 94 !DI 40 1.63 P 1 51 TE-HL
+6.44 9TH TSP TE HL J1978 610 3DI Bobbin 12 BS IDI 40 1.84 P 1 55 TE-HL
+16.78 91H TSP TE-HL J1978 610 IDI H/L Tubesheet SAI 3.09 1 26 TTS-HL
-5.41 TTS-HL TE-HL HT791590 Bobbin 13 64 IDI 40 7.81 P 1 155 TE-HL
+15.93 97H TSP TE HL B5534 610 IDI l
Bobbin 14 75 IDI 40 2.14 P 1 32 TE-HL
+10,17 9TH TSP TE-HL P9375 610 IDI H/L Tubesheet 14 101 SAI 4.62 1 20 TTS-HL
-2.91 TTS*HL TE-HL N0698 590 Sobbin 15 91 IDI 40 2.37 P 1 34 TE-HL
+4.83 9TH TSP TE-HL P9375 610 IDI i
Bobbin 16 92 IDI 40 7.56 P 1 20 TE-HL
+15.28 9TH TSP TE HL W2218 610 IDI Bobbin IDI 40 15.81 P 1 26 TE-HL
+8.29 9TH TSP TE-HL W2218 610 IDI
]
Bobbin 18 25 101 40 0.87 P 1 141 TE-HL
+14.94 91H TSP TE-HL L7871610 !DI Bobbin 18 75 IDI 40 4.20 P 1 152 TE-HL
+6.43 91H TSP TE HL W2218 610 IDI-Bobbin 18 89 IDI 40 2.43 P 1 22 TE-HL
+4.52 9TH TSP TE-HL W2218 610 IDI Bobbin 19 82 IDI 40 8.23 P 1 50 TE-HL
+3.69 9TH TSP TE-HL W2218 610 IDI Bobbin 21 56 101 40 17.75 P 1 40 TE-HL
+ 0. 48 9TH TSP TE-HL $6961610 IDI Bobbin 23 104 IDI 40 7.20 P 1 44 TE-HL
+1.27 9TH TSP TE-HL P5436 610 IDI Bobbin 26 61 1D! 40 6.93 P 1 19 TE-HL
+13.11 9TH TSP TE-HL $6369 6101D1 Bobbin 27 71 IDI 40 11.92 P 1 19 TE-HL
+18.12 9TH TSP TE-HL 56369 610 IDI H/L Tubesheet MAI 4.43 1 26 TTS HL
-3.10 TTS-HL TE-HL R6452 590 IDI Bobbin 28 35 IDI 40 5.45 P 1 26 TE-HL
+2.92 9TH TSP TE-HL B5371610 IDI I
Bobbin 28 70 IDI 40 10.60 P 1 30 TE-HL
+17.18 9TH TSP TE-HL S6369 610 IDI I
N/L Tubesheet MAI 4.26 1 25 TTS-HL
-4.16 TTS-HL TE-HL R6452 590 IDI
.l Bobbin 29 76 IDI 40 7.73 P 1 142 TE-HL
+15.86 9TH TSP TE-ML S6369 610 1D1 Bobbin 3DI 40 11.26 P 1 9 TE-HL
+10.33 9TH TSP - TE-HL $6369 610 IDI Bobbin 29 103 101 40 17.70 P 1 28 TE-HL
+18.12 9TH TSP TE-HL $6961 610 IDI
^
H/L Tubesheet MAI 2.55 1 30 TTS-HL
-3.15 TTS-HL.
TE-HL V2218 590 IDI-i Bobbin 30 88 IDI 40 13.37 P 1 21 TE-HL
+18.05 9TH TSP TE-HL $6961 610 IDI i
H/L Tubesheet MAI 2.15 1 31 TTS-HL
-3.01 TTS HL TE HL C9813 590 IDI H/L Tubesheet 32 59 MA!
3.95 1 19 TTS-HL
-4.71 TTS-HL TE-HL R6452 590
' Bobbin 32 99 101 40 2.04 P 1 126 TE-HL
+10.76 9TH TSP TE HL $6961 610 IDI Bobbin 38 56 IDI 40 13.38 P 1 42 TE-HL
+16.24 97H TSP TE-HL J1978 610 IDI I
Bobbin 40 79 IDI 40 5.07 P 1 15 TE-HL
+13.15 9TH TSP TE-HL W4892 610 IDI Bobbin IDI 40 11.60 P 1 35 TE-HL
+17.19 9TH TSP TE HL W4892 610 IDI H/L Tubesheet MAI 1.57 1 24 TTS-HL
-3.37 TTS-HL TE-HL C3556 590 i
H/L Tubesheet 41 83 sal 0.56 1 52 TTS-HL
-3.98 TTS-HL TE-HL C3556 590 Bobbin 42 49 1D1 40 3.22 P 3 45 TE-HL
+14.49 97H TSP TE-HL 57675 610101 Bobbin 42 73 1DI 40 11.70 P 1 66 TE-HL
+17.01 97H TSP TE-ML P2201 610 101
~
H/L Tubesheet MAI 6.75 1 39 TTS-HL
-3.57 TTS-HL TE-HL C3556 590 Bobbin 45 40 !DI 40 4.09 P 1 32 TE-HL
+6.13 91H TSP TE-HL $7675 610 IDI Bobbin 46 63 IDI 40 2.69 P 1 42 TE-HL
+16.20 97H TSP TE-HL E6878 610 !DI Total Indications f ound = 62 Total Tubes found = 46 l
v 9
i DPC0 TUBAN 11 (Version 1.0) 08/10/1993 15:54:44
- e..****************************
McGuire Nuclear Station - tJnit Two
?
5/G D 7fg3 gro l
............ 6*********************
Sobbin,il/L Tubesheet f
Fege 2 of 2 ATTACHMLh1 #4 - f*
i f* QUERY TEST TYPE ROJ COL IND %Tkl VOLTS CHN DEG LOCA110W EXTENT 1 LEG ANLST PRB COMMENTS Total Tubes in input File = 46 i
)
l l
1 1
i t